BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Lot 15-B Residence
81-413 Columbus Way
La Quinta, CA 02253
Project Designer:
Kristi Hanson Architects, Inc.
72-185 Painters Path Suite A
Palm Desert , Ca 92260
760-776-4068
Report Prepared by:
Butch White
BREEZE AIR CONDITIONING
75-145 St. Charles Place
Palm Desert, CA 92211
RIE103 E-- T I IV E D
OCT 17 2014
CITY OF LA QUINTA
COMMUNITY DEVELOPM
Job Number:
Date:
10/3/2014
CITY OF
AQTUINT
BUILDING
APPROVED
FOR CONSTRUCTION
DATE 2l BY
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
�� .tom{�•F�:��'�
I TABLE OF CONTENTS
Cover Page
Table of Contents
Form CF -1 R Certificate of Compliance
Form RMS -1 Residential Measures Summary
Form MF -1 R Mandatory Measures Summary
HVAC System Heating and Cooling Loads Summary
Room Load Summary
Room Heating Peak Loads
Room Cooling Peak Loads
EnergyPro 6.3 by EnergySoft Job Number: ID: User Number: 3665
1
2
3
21
24
27
34
41
48
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 1 of 18
GENERAL INFORMATION
01
Project Name Private Residence
02
Calculation Description Title 24 Analysis
03 This building incorporates one or more Special Features shown'below
03
Project Location 81-413 Columbus Way
1�►
04
A City La Quinta
05
Standards Version Compliance 2014
06
Zip code 2253
07
Compliance Manager Version BEMCmpMgr 2013-3 (651)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.3
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 45
12
Project Scope Newly Constructed
13
Number of Dwelling Units 1
14
Total Cond. Floor Area (FT2) 8922
15
Number of Zones 7
16
Slab Area (FT� 6859
17 (/v
Number of Stories 3
18
Addition Cond. Floor Area NA
,1J�
Natural Gas Available Yes
20
Addition Slab Area (FT) NA
0.0%
Glazing Percentage (%) 24.0%
COMPLIANCE RESULTS { v
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03 This building incorporates one or more Special Features shown'below
1�►
IV ENERGY USE SUMMARY
04
05��"
06
07
08
Energy Use
(kTDV/ft)
Staf lord
Rgs gn
Proposed
Design
Compliance
Margin
Percent
Improvement
Space Heating
0 3.80
4.89
-1.09
-28.7%
Space Cooling
A. '-"-* 90.41
88.04
2.37
2.6%
IAO Ventilation
1.27
1.27
0.00
0.0%
Water Heating
3.04
3.65
-0.61
-20.1%
Photovoltaic Offset
----
0.00
0.00
Compliance Energy Total��
98.52
97.85
0:6 O
LA QU! N74�o
Registration Number: Registration Date/Time:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-09292014-651
BUILDING & SAFETY DEP-i .
APPROVED
FOR CONSTRUCTION
DATE HES ��reeV
Report Generated at`. 2014=10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03,.2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Ducts with high level of insulation
• Cathedral Ceiling
• Window overhangs and/or fins
I HERS FEATURE SUMMARY
CF1 R -PRF -01
Page 2 of 18
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
01
• High Quality Insulation Installation (QII)
03
• IAQ mechanical ventilation
05
Cooling System Verifications:
07
• Verified EER
Conditioned Floor Af (sft)
• Verified SEER
• Refrigerant Charge
�0
• Fan Efficacy Watts/CFM
Number of Ventilation
Cooling Systems
HVAC Distribution System Verifications:
Private Residence
• Duct Sealing
1
Domestic Hot Water System Verifications:
7
• Pipe Insulation, All Lines
2
ENERGY DESIGN RATING ♦ 10
This is the sum of the annual TDV energy consumption for energy use components included in the performance compliance approach for the Standard Design Building (Energy Budget) and the annual
TDV energy consumption for lighting and components not regulated by Title 24, Part, '(such as domestic appliances and consumer electronics) and accounting for the annual TDV energy offset by an
on-site renewable energy system.
Reference Energytise Energy Design Rating MarginPercent Improvement
Total Energy (kTDV/f2)' 132.34; 131.67 0.67 0.5%
includes calculated Appliances and Miscellaneous Energy Use (AMEUU)
,ems/
BUILDING - FEATURES INFORMATION
01
02 �"
03
04
05
06
07
Project Name
Conditioned Floor Af (sft)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
Private Residence
8922 vV
1
21
7
1
2
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Stand ra ds - 2013 Residential Compliance Report Version - CF1R-09292014-651 Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 3 of 18
ZONE INFORMATION
01
02
03
04
05
06 07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height
Water Heating System 1 Water Heating System 2
Zone 1
Conditioned
HVAC 11
1317
10
DHW Sys 1
Zone 2
Conditioned
HVAC 22
1380
10
DHW Sys 1
Zone 3
Conditioned
HVAC 33
599
10
DHW Sys 1
Zone 4
Conditioned
HVAC 44
1369
10
DHW Sys 1
Zone 5
Conditioned
HVAC 55
1005*
10
DHW Sys 1
ZONE 6
Conditioned
HVAC 66
2053" 1
8
DHW Sys 1
Zone 7
Conditioned
HVAC 77
W1.-199
8
1 DHW Sys 1
5p
Registration Number: �� �fRegistration Date/Time: HERS Provider:
CA Building Energy Efficiency Standa ds - 2013 Residential Compliance Report Version - CF113-09292014-651 Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 4 of 18
OPAQUE SURFACES
01
02
03
04
05
06
07
08
Name
Zone
Construction
Azimuth
Orientation
Gross Area (ft2)
Window Area (ft2)
Tilt(deg)
NW Exterior Wall
Zone 1
R-21 Wall
315
Right
755
25
90
SW Exterior Wall
Zone 1
R-21 Wall
225
Back
140
100
90
SE Exterior Wall
Zone 1
R-21 Wall
135
Left
140
0
90
Roof 2
Zone 1
R-38 Roof Attic
589
NW Exterior Wall 2
Zone 2
R-21 Wall
315
Right
50
27
90
SW Exterior Wall 2
Zone 2
R-21 Wall
h225
Back
380
256
90
SE Exterior Wall 2
Zone 2
R-21 Wall
W 135
Left
340
188.441
90
NE Exterior Wall
Zone 2
R-21 Wall
Y 45
Front
450
77.003
90
Roof 3
Zone 2
R-38 Roof Attic e
`
1380
NE Exterior Wall 2
Zone 3
R-21 Wall �"
45
Front
126
97.992
90
SW Exterior Wall 3
Zone 3
R-21 Wall UO J
225
Back
290
150
90
NW Exterior Wall 3
Zone 3
R-21 Wall.v
315
Right
100
31.008
90
Roof 4
Zone 3
R-38 Roof=Attic
599
NW Exterior Wall 4
Zone 4
R-21'Wall
315
Right
510
0
90
SE Exterior Wall 3
Zone 4
`14J41 Wall
135
Left
770
237.013
90
SW Exterior Wall 4
Zone 4
WR -21 Wall
225
Back
240
130
90
Roof 5
Zone 4
WFt-38 Roof Attic
1356.2
NE Exterior Wall 3
Zone 5
,h%� R-21 Wall
45
Front
370
71
90
NW Exterior Wall 5
Zone 5
r R-21 Wall
315
Right
390
117.019
90
SE Exterior Wall 4
Zone 5
R-21 Wall
135
Left
380
52
90
SW Exterior Wall 5
Zone 5
�` R-21 Wall
225
Back
160
84.02
90
Roof 6
Zone 5 R-38 Roof Attic
1005
NE Exterior Wall 4
ZONE 6 '�
R-21 Wall
45
Front
490
256.501
90
NW Exterior Wall 6
ZONE 6,.%
R-21 Wall
315
Right
500
31.001
90
SE Exterior Wall 5
ZONE f3i
R-21 Wall
135
Left
500
144.973
90
SW Exterior Wall 6
ZO�NE�6
R-21 Wall
225
Back
490
60.3901
90
Roof 7,IZ6NE
6
R-38 Roof Attic
2053
Interior Surface -Floor
ZONE 6»Zone 7
R-30 Floor No Crawlspace
2053
NE Exterior Wall 5
Zone 7
R-21 Wall
45
Front
560
0
90
NW Exterior Wall 7
`�` Zone 7
R-21 Wall
315
Right
250
0
90
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Stand' ds - 2013 Residential Compliance Report Version - CF1R-09292014-651 Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 5 of 18
SE Exterior Wall 6 Zone 7 R-21 Wall 135 Left 250 0 90
SW Exterior Wall 7 Zone 7 R-21 Wall 225 Back 260 0 90
OPAQUE SURFACES — Cathedral Ceilings
01
02
03
04
05
06
07
08
09
10
11
Name
Zone
Type
Orientatio
n
Area (ft)
Skylight
Area (ft2)
Roof Rise
(x in 12)
Roof
Pitch
Roof
Tilt
(deg)
Roof
Reflectan
ce
Roof
Emmittanc
a
Framin
9
Factor
Roof
Zone 4
R-38 Roof Attica
specify -
2.9
1.4
2
0.17
9.46
0.1
0.85
0.07
:►
ATTIC
lQl�
01 02 03 05 06 07
Name Construction Roof Rise Roof%Reflectance Roof Emittance Radiant Barrier Cool Roof
Attic Attic Roof Cons 2�� 0.1 0.85 Yes No
♦O�
Registration Number:
CA Building Energy Efficiency Stand ra ds - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09292014-651
HERS Provider:
Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 6 of 18
WINDOWS
01
02
03
04
05
06
07
08
09
10
Name
Type
Surface (Orientation -Azimuth)
Width(ft)
Height
(ft)
Multiplier
Area
(ft)
U -factor
SHGC
Exterior Shading
Window 08
Window
NW Exterior Wall (Right -315)
5.0
5.0
1
25.0
0.39
0.24
Insect Screen (default)
Window 09
Window
SW Exterior Wall (Back -225)
10.0
2.0
1
20.0
0.39
0.24
Insect Screen (default)
Window E1
Window
SW Exterior Wall (Back -225)
10.0
8.0
1
80.0
0.54
0.24
Insect Screen (default)
Window 10
Window
NW Exterior Wall 2 (Right -315)
3.0
9.0
1
27.0
0.39
0.24
Insect Screen (default)
Window 11
Window
SW Exterior Wall 2 (Back -225)
50.0 <
2.0
0.1
10.0
0.39
0.24
Insect Screen (default)
Window 12
Window
SW Exterior Wall 2 (Back -225)
4.5
2.0
1
9.0
0.39
0.24
Insect Screen (default)
Window 13
Window
SW Exterior Wall 2 (Back -225)
4.5��
2.0
1
9.0
0.39
0.24
Insect Screen (default)
Window 14
Window
SW Exterior Wall 2 (Back -225)
X5:0
2.0
1
10.0
0.39
0.24
Insect Screen (default)
Window S-1
Window
SW Exterior Wall 2 (Back -225)
;Q§21.8
10.0
1
218.0
0.54
0.24
Insect Screen (default)
Window 15
Window
SE Exterior Wall 2 (Left -135)
�� 5.5
2.0
1.091
12.0
0.39
0.24
Insect Screen (default)
Window 16
Window
SE Exterior Wall 2 (Left -135) V 4.5
2.0
1
9.0
0.39
0.24
Insect Screen (default)
Window 17
Window
SE Exterior Wall 2 (Left -135) �"
5.0
2.0
1
10.0
0.39
0.24
Insect Screen (default)
Window F2
Window
SE Exterior Wall 2 (Left -135)
16.0
10.0
0.984
157.4
0.54
0.24
Insect Screen (default)
Window 04
Window
NE Exterior Wall (Front -45). 69
3.0
7.0
1
21.0
0.39
0.24
Insect Screen (default)
Window 05
Window
NE Exterior Wall (Front -458,
3.0
7.0
1
21.0
0.39
0.24
Insect Screen (default)
Window 06
Window
NE Exterior Wall (Front
17.8
2.0
0.986
35.0
0.39
0.24
Insect Screen (default)
Window 02
Window
NE Exterior Wall 2 (F�,rpo�nt-45)
3.0
10.0
1
30.0
0.39
0.24
Insect Screen (default)
Window 03
Window
NE Exterior Wall 2�(.F.6t-45)
7.8
2.0
0.968
15.0
0.39
0.24
Insect Screen (default)
Window 61
Window
NE Exterior Wal ' AFront-45)
5.2
10.0
1.019
53.0
1.28
0.80
Insect Screen (default)
Window G1
Window
SW Exterior Wall 3 (Back -225)
12.5
10.0
1
125.0
0.54
0.24
Insect Screen (default)
Window 18
Window
SW Extehor)Wall 3 (Back -225)
12.5
2.0
1
25.0
0.39
0.24
Insect Screen (default)
Window 56
Window
NW Ezt�rior Wall 3 (Right -315)
3.8
6.0
1.009 1
23.0
0.56
0.25
Insect Screen (default)
Window 57
Window
NW Ezierior Wall 3 (Right -315)
3.8
2.0
1.053
8.0
0.39
0.24
Insect Screen (default)
Window 20
Window
qS I ttxterior Wall 3 (Left -135)
4.5
2.0
1
9.0
0.39
0.24
Insect Screen (default)
Window 21
Window
%SE Exterior Wall 3 (Left -135)
6.0
2.0
1
12.0
0.39
0.24
Insect Screen (default)
Window 22
Window
SE Exterior Wall 3 (Left -135)
4.5
2.0
1
9.0
0.39
0.24
Insect Screen (default)
Window 23
Window
SE Exterior Wall 3 (Left -135)
5.5
5.0
1
27.5
0.39
0.24
Insect Screen (default)
Window 24
Window
SE Exterior Wall 3 (Left -135)
5.5
2.0
1
11.0
0.39
0.24
Insect Screen (default)
Window 25
WindowSE
Exterior Wall 3 (Left -135)
13.0
9.0
0.889
104.0
0.39
0.24
Insect Screen (default)
Registration Number:
CA Building Energy Efficiency Stands - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF111-09292014-651
HERS Provider:
Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Datefrime: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 156.xml
CF1 R -PRF -01
Page 7 of 18
Window 26
Window
SE Exterior Wall 3 (Left -135)
13.0
2.0
1
26.0
0.39
0.24
Insect Screen (default)
Window 27
Window
SE Exterior Wall 3 (Left -135)
5.5
5.0
1
27.5
0.39
0.24
Insect Screen (default)
Window 28
Window
SE Exterior Wall 3 (Left -135)
5.5
2.0
1
11.0
0.39
0.24
Insect Screen (default)
Window H1
Window
SW Exterior Wall 4 (Back -225)
13.0
8.0
1
104.0
0.54
0.24
Insect Screen (default)
Window 19
Window
SW Exterior Wall 4 (Back -225)
13.0
2.0
1
26.0
0.39
0.24
Insect Screen (default)
Skylight S05-47
Skylight
Roof ( specify --45)
1
1.4
0.30
0.30
Skylight S06-48
Skylight
Roof (- specify --45)
1
1.4
0.30
0.30
Window 32
Window
NE Exterior Wall 3 (Front -45)
5.0
2.0
1
10.0
0.39
0.24
Insect Screen (default)
Window 36
Window
NE Exterior Wall 3 (Front -45)
1.0 5.0
1
5.0
0.39
0.24
Insect Screen (default)
Window 37
Window
NE Exterior Wall 3 (Front -45)
8.0 w�Q y
2.0
1
16.0
0.39
0.24
Insect Screen (default)
Window 38
Window
NE Exterior Wall 3 (Front -45)
5'9
6.0
1
30.0
0.56
0.25
Insect Screen (default)
Window 39
Window
NE Exterior Wall 3 (Front -45)
'5o
2.0
1
10.0
0.39
0.24
Insect Screen (default)
Window 40
Window
NW Exterior Wall 5 (Right 315)3.8
6.0
1.053
24.0
0.71
0.73
Insect Screen (default)
Window 41
Window
NW Exterior Wall 5 (Right -315)
3.8
2.0
1.053
8.0
0.39
0.24
Insect Screen (default)
Window 42
Window
NW Exterior Wall 5 (Right -315) 1%4'
3.8
6.0
1.009
23.0
0.56
0.25
Insect Screen (default)
Window 43
Window
NW Exterior Wall 5 (Right -315)
3.8
2.0
1.053
8.0
0.39
0.24
Insect Screen (default)
Window 48
Window
NW Exterior Wall 5 (Right -315) �`
4.8
8.0
1
38.0
0.39
0.24
Insect Screen (default)
Window 49
Window
NW Exterior Wall 5 (Right -315)
8.0
2.0
1
16.0
0.39
0.24
Insect Screen (default)
Window 29
Window
SE Exterior Wall 4 (Left -l*
30.0
5.0
0.1
15.0
0.56
0.25
Insect Screen (default)
Window 30
Window
SE Exterior Wall 4 (LeftpJ 5)
9.0
2.0
1
18.0
0.39
0.24
Insect Screen (default)
Window 31
Window
SE Exterior Wall 4 (LWl35)
1.0
5.0
1
5.0
0.39
0.24
Insect Screen (default)
Window 33
Window
SE Exterior Wall,�(Left 135)
1.0
5.0
1
5.0
0.39
0.24
Insect Screen (default)
Window 34
Window
SE Exterior VY40F(Left 135)
1.0
2.0
1
2.0
0.39
0.24
Insect Screen (default)
Window 35
Window
SE Exterior] W it 4 (Left -135)
3.5
2.0
1
7.0
0.39
0.24
Insect Screen (default)
Window 44
Window
SW Exterior Wall 5 (Back -225)
3.8
6.0
1.009
23.0
0.56
0.25
Insect Screen (default)
Window 45
Window
SW Exterior Wall 5 (Back -225)
3.8
2.0
1.053
8.0
0.39
0.24
Insect Screen (default)
Window 46
Window
SW Exterior Wall 5 (Back -225)
4.8
8.0
0.974
37.0
0.39
0.24
Insect Screen (default)
Window 47
Window
(SW-txterior Wall 5 (Back -225)
8.0
2.0
1
16.0
0.39
0.24
Insect Screen (default)
Window 65
Window
A&NE Exterior Wall 4 (Front -45)
9.0
6.0
1
54.0
0.39
0.24
Insect Screen (default)
Window 66
Window
O NE Exterior Wall 4 (Front -45)
9.0
6.0
1
54.0
0.56
0.25
Insect Screen (default)
Window P1
Window
NE Exterior Wall 4 (Front -45)
16.7
9.0
0.991
148.5
0.54
0.24
Insect Screen (default)
Window 67
Window
, �' NW Exterior Wall 6 (Right -315)
5.5
2.0
1.091
12.0
0.39
0.24
Insect Screen (default)
Window 68
Window
NW Exterior Wall 6 (Right -315)
3.5
2.0
1
7.0
0.39
0.24
Insect Screen (default)
Registration Number:
CA Building Energy Efficiency Stand ra ds - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09292014-651
HERS Provider:
Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 8 of 18
Window 69
Window
NW Exterior Wall 6 (Right -315)
6.0
2.0
1
12.0
0.39
0.24
Insect Screen (default)
Window 58
Window
SE Exterior Wall 5 (Left -135)
13.9
9.0
0.983
123.0
0.39
0.24
Insect Screen (default)
Window 63
Window
SE Exterior Wall 5 (Left -135)
5.5
2.0
1
11.0
0.39
0.24
Insect Screen (default)
Window 64
Window
SE Exterior Wall 5 (Left -135)
5.5
2.0
1
11.0
0.39
0.24
Insect Screen (default)
Window 59
Window
SW Exterior Wall 6 (Back -225)
3.8
7.3
1.034
28.5
0.39
0.24
Insect Screen (default)
Window 60
Window
SW Exterior Wall 6 (Back -225)
3.8
2.0
1.026
7.8
0.39
0.24
Insect Screen (default)
Window 61
Window
SW Exterior Wall 6 (Back -225)
6.5
2.0
0.985
12.8
0.39
0.24
Insect Screen (default)
Window 62
Window
SW Exterior Wall 6 (Back -225)
3.5
2.0
1
7.0
0.39
0.24
Insect Screen (default)
Window 73
Window
SW Exterior Wall 6 (Back -225)
4.2
< 1.0
1.024
4.3
0.39
0.24
Insect Screen (default)
074-
DOORS
7
DOORS
A
01
02 �
03
04
Name
Side of Building
Area (ft2)
U -factor
Door C1
NE Exte�io� Wall 5
74.0
0.50
Door C2
NE Exterior Wall 5
148.0
0.50
Door C3
NE Exterior Wall 5
74.0
0.50
♦O�
Registration Number: �f+�
CA Building Energy Efficiency Stan�da ds - 2013 Residential Compliance
Registration Date/Time:
Report Version - CFSR-09292014-651
HERS Provider:
Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 9 of 18
OVERHANGS AND FINS
01
02
03
04
05
06
07
08
09
10
11
12
13
14
Overhang
Left Fin
Right Fin
Window
Depth
Dist Up
Left
Extent
Right
Extent
Flap Ht.
Depth
Top Up
DistL
Bot Up
Depth
Top Up
Dist R
Bot Up
Window 08
2
0.1
2
2
0
0
0
0
0
0
0
0
0
Window 09
8
0.1
8
8
0
0
0
0
0
0
0
0
0
Window El
8
0.1
8
8
0
0
0
0
0
0
0
0
0
Window 10
10
0.1
10
10
0
0
0
0
0
0
0
0
0
Window 11
10
0.1
10
10
0
S0,
0
0
0
0
0
0
0
Window 12
10
0.1
10
10
0
p�0
0
0
0
0
0
0
0
Window 13
10
0.1
10
10
0" 0
0
0
0
0
0
0
0
Window 14
10
0.1
10
10
0
0
0
0
1 0
0
0
0
0
Window S-1
10
0.1
10
10
0001"y0
0
0
0
0
0
0
0
Window 15
10
0.1
10
10
`OJ
0
0
0
0
0
0
0
0
Window 16
10
0.1
10
10
evo
0
0
0
0
0
0
0
0
Window 17
10
0.1
10
10
< 0
0
0
0
0
0
0
0
0
Window F2
10
0.1
10
10,0
0
0
0
0
0
0
0
0
Window 04
10
0.1
10
OA v
0
0
0
0
0
0
0
0
0
Window 05
10
0.1
10
r—ib
0
0
0
0
0
0
0
0
0
Window 06
10
0.1
10v 10
0
0
0
0
0
0
0
0
0
Window 02
10
0.1
10
10
0
0
0
0
0
0
0
0
0
Window 03
10
0.1
110
10
0
0
0
00
0
0
0
0
Window 61
10
0.1
410
10
0
0
0
0
0
0
0
0
0
Window G1
10
0.1 (1110
10
0
0
0
0
0
0
0
0
0
Window 18
10
0.1 44"
10
10
0
0
0
0
0
0
0
0
0
Window 56
10
0.1v
10
10
0
4
0
0.1
0
0
0
0
0
Window 57
10
60
10
10
0
4
0
0.1
0
0
0
0
0
Window 20
8^i
0.1
8
8
0
0
0
0
0
0
0
0
0
Window 21
8 eG� 0.1
8
8
0
0
0
0
0
0
0
0
0
Window 22
8 ��`
0.1
8
8
0
0
0
0
0
0
0
0
0
Window 23
k8��v
0.1
8
8
0
0
0
0
0
0
0
0
0
Window 248
0.1
8
8
0
0
0
0
0
0
0
0
0
Registration Number: A�
CA Building Energy Efficiency Stan' ads - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF111-09292014-651
HERS Provider:
Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/rime: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 10 of 18
Window 25
8
0.1
8
8
0
0
0
0
0
0
0
0
0
Window 26
8
0.1
8
8
0
0
0
0
0
0
0
0
0
Window 27
8
0.1
8
8
0
0
0
0
0
0
0
0
0
Window 28
8
0.1
8
8
0
0
0
0
0
0
0
0
0
Window H1
8
0.1
1 8
8
0
0
0
0
0
0
0
0
0
Window 19
8
0.1
8
8
0
0
0
0
0
0
0
0
0
Window 32
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 36
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 37
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 38
4
0.1
4
4
0
0
0
0
0
0
0
0
Window 39
4
0.1
4
4
0
�0
0
0
0
0
0
0
0
Window 40
4
0.1
4
4
0
Ito 0
0
0
0
0
0
0
0
Window 41
4
0.1
4
4
0
`� J 0
0
0
0
0
0
0
0
Window 42
4
0.1
4
4
0� 0
0
0
0
0
0
0
0
Window 43
4
0.1
4
4
W'0"
0
0
0
0
0
0
0
0
Window 48
4
0.1
4
4
0-0
0
0
0
0
0
0
0
0
Window 49
4
0.1
4
4 `L` 0
0
0
0
0
0
0
0
0
Window 29
4
0.1
4
4#
0
0
0
0
0
0
0
0
0
Window 30
4
0.1
4
0
0
0
0
0
0
0
0
0
Window 31
4
0.1
4
'OOV.4
0
0
0
0
0
0
0
0
0
Window 33
4
0.1
4 Iry 4
0
0
0
0
0
0
0
0
0
Window 34
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 35
4
0.1
�4 %
4
0
0
0
0
0
0
0
0
0
Window 44
4
0.1
�`�'4
4
0
0
0
0
0
0
0
0
0
Window 45
4
0.1
t 4
4
0
0
0
0
0
0
0
0
0
Window 46
4
0.1 `� 4
4
0
0
0
0
0
0
0
0
0
Window 47
4
4
4
0
0
0
0
0
0
0
0
0
Window 65
401
4
4
0
0
0
0
0
0
0
0
0
Window 66
4
,'Y0.1
4
4
0
0
0
0
0
0
0
0
0
Window P1
8 i 0.1
8
8
0
0
0
0
0
0
0
0
0
Window 67
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 68
0.1
4
4
0
0
0
0
0
0
0
0
Window 69
V'4
0.1
4 14
0
0 10
--40
0
0 10
0
0
0
Registration Number: Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Stant ds - 2013 Residential Compliance Report Version - CF111-09292014-651 Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 11 of 18
Window 58
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 63
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 64
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 59
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 60
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 61
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 62
4
0.1
4
4
0
0
0
0
0
0
0
0
0
Window 73
4
0.1
4
4
0
0
0
0
0
0
0
0
0
O.
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
Construction Name
Surface Type
Construction Type
FramingtV '
Total Cavity R -value
Assembly Layers
2x4 Top CHoni of
Cavity/ Frame: no insul. /2x4 Top Chrd
Roof Truss@24 in.
r
Roof Deck: Wood Siding/sheathing/decking
Attic Roof Cons
Attic Roofs
Wood Framed Ceiling
OIC.
none
Roofing: Light Roof (Asphalt Shingle)
Inside Finish: Gypsum Board
• Cavity / Frame: R-21 / 2x6
R-21 Wall
Exterior Walls
Wood Framed Wall
@ 16 in. O.C.
R 21
Exterior Finish: Wood Siding/sheathing/decking
•
Inside Finish: Gypsum Board
Cavity / Frame: R-9.1 / 2x4
R-38 Roof Attic
Ceilings (below attic)
Wood Framed Ceilin%,
2x4 @ 24 in. O.C.
R 38
Over Floor Joists: R-28.9 insul.
Inside Finish: Gypsum Board
• Cavity/ Frame: R-38 / 2x4
• Roof Deck: Wood Siding/sheathing/decking
R-38 Roof Attici
Cathedral Ceilings
Wood Frame0ceiling
2x4 @ 24 in. O.C.
R 38
Roofing: Light Roof (Asphalt Shingle)
Floor Surface: Carpeted
• Floor Deck: Wood Siding/sheathing/decking
• Cavity / Frame: R-25 /2x10
R-30 Floor No Crawlspace
Interior Floors
Wood Framed Floor
2x10 @ 16 in. O.C.
R 25
Ceiling Below Finish: Gypsum Board
9
.A0
Registration Number: A�
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF113-09292014-651
HERS Provider:
Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 12 of 18
SLAB FLOORS
01
02
103'
04
05
06
01
02
03
04
05
06
07
Name
Zone
Area (ft)
Perimeter (ft)
Edge Insul. R -value& Depth
Carpeted Fraction
Heated
Slab -on -Grade
Zone 1
1317
89.5
None
1
No
Slab -on -Grade 2
Zone 2
1380
113
None
1
No
Slab -on -Grade 3
Zone 3
599
50
None
1
No
Slab -on -Grade 4
Zone 4
1359
91
None
1
No
Slab -on -Grade 5
Zone 5
1005
75
None
1
No
Slab -on -Grade 6
Zone 7
1199
b1107
None
1
No
BUILDING ENVELOPE - HERS VERIFICATION QA`i►
01 02 03 04
Quality Insulation Installation (OII) Quality Installation of Spray Foam Insu�lati'on Building Envelope Air Leakage ACH @ 50 Pa
Required Not Required �� Not Required ---
WATER HEATING SYSTEMS Aw
01
02
103'
04
05
06
Name
System Type
Disth6ution Type
Water Heater
Number of Heaters
Solar Fraction (%)
DHW Sys 1
DHW
(HER S'd) Pipe Insulation, All
q
DHW Heater 1
1
Annual
Large Storage
60
Lines
120000-Btu/hr
0
0.021
DHW Heater 1
Natural Gas ri
(Hq�S req'd) Pipe Insulation, All
60
0.994
120000-Btu/hr
DHW Sys 1
DHW
Lines
DHW Heater 1
2
Annual
^�
I`
WATER HEATERS `V
01
02
r 03
04
05
06
07
08
Name
Heater Element Type
Tank Type
Tank Volume
(gal)
Energy Factor or
Efficiency
Input Rating
Tank Exterior
Insulation
R -value
Standby Loss
(Fraction)
DHW Heater 1
Natural Gas 097R
Large Storage
60
0.994
120000-Btu/hr
0
0.021
DHW Heater 1
Natural Gas ri
Large Storage
60
0.994
120000-Btu/hr
0
0.021
•may
Registration Number:
CA Building Energy Efficiency Stanch ds - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09292014-651
HERS Provider:
Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 13 of 18
WATER HEATING - HERS VERIFICATION
01
02
03
04
05
06
07
Name
Pipe Insulation
Parallel Piping
Compact Distribution
Point -of Use
Recirculation
Control
Central DHW
Distribution
DHW Sys 1 - 1/1
Pipe Insulation, All Lines
N/A
N/A
Pipe Insulation, All
Lines
N/A
N/A
DHW Sys 1 -1/2
Pipe Insulation, All Lines
N/A
N/A
Pipe Insulation, All
Lines
N/A
N/A
HVAC SYSTEMS
01
02
03
04
05
06
07
Heating System
�� Cooling System
Distribution
Floor Area
Name
System Type
Name Ducted
Name Ducted
System
Fan System
Served
HVAC 11
Other Heat/Cool
Heating Component 1
♦ �"
Yes,
Cooling Component 1
Yes
Air Distribution
1317
System 1
Air DistributionSystem
HVAC 22
Other Heat/Cool
Heating Component 2
Yes
Cooling Component 2
Yes
2
1380
HVAC 33
Other Heat/Cool
Heating Component 34'�
Yes
Cooling Component 3
Yes
Air Distribution
System 3
599
HVAC 44
Other Heat/Cool
Heating Componen`i14
�
Yes
Cooling Component 4
Yes
Air Distribution
System 4
1369
HVAC 55
Other Heat/Cool
Heating Comoohent 5
Yes
Cooling Component 5
Yes
Air Distribution
System 5
1005
HVAC 66
Other Heat/Cool
Heating,Component 6
Yes
Cooling Component 6
Yes
Air Distribution
2053
System 6
HVAC 77
Heat Pump
Heat., ' mp System 7
No
Heat Pump System 7
No
None
1199
HVAC 77
Heat Pump
H`ea'd Pump System 7
No
Heat Pump System 7
No
None
1199
ICU'*
®*
♦O�
Registration Number:
CA Building Energy Efficiency Stand rds - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09292014-651
HERS Provider:
Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 14 of 18
HVAC - HEATING SYSTEMS
01
02
01
02
03
Name
Type
Efficiency
Heating Component 1
CntrlFurnace - Fuel -fired central furnace
98 AFUE
Heating Component 2
CntrlFurnace - Fuel -fired central furnace
98 AFUE
Heating Component 3
CntrlFurnace - Fuel -fired central furnace
98 AFUE
Heating Component 4
CntrlFurnace - Fuel -fired central furnace
98 AFUE
Heating Component 5
CntrlFurnace - Fuel -fired central furnace
98 AFUE
Heating Component 6
CntrlFurnace - Fuel -fired central furnace
98 AFUE
off;
HVAC - HEATING SYSTEMS: Heat Pumps &%
01
02
03 04 1 VA65
06 07
08
09
10
04
05
Heating `Q�
Cooling
Zonally
Multispeed
HERS
Name
Type
HSPF/COP Cap 4'WCap 17
SEER EER
Controlled
Compressor
Verification
Heat Pump System 7
Ductless HeatPump
10 HSPF
36200
27300
18
12.5
No
Yes
Heat Pump System
�►
7 -hers -cool
�r
Heat Pump System
Heat Pump System 7
Ductless HeatPump
10 HSPF
W-36200
27300
18
12.5
No
Yes
7 -hers -cool
♦0w
HVAC HEAT PUMP COOLING - HERS VERIFICATION
of
01
02 V
03
04
05
Name
Verified Airtlow
Verified EER
Verified SEER
Verified Refrigerant Charge
HVAC 77 SCSysRpt 1
Not Re�uWed
��
Not Required
Required
Not Required
HVAC 77 SCSysRpt 2
Not Required
Not Required
Required
Not Required
♦ 0
Registration Number: A�S Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-09292014-651 Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 15 of 18
HVAC - COOLING SYSTEMS
01
02
03 04
05
06
07
02
V03
Efficiency
05
Multi -speed
Name
Name
System Type
EER SEER
Zonally Controlled
Compressor
HERS Verification
Cooling Component 1
SplitAirCond - Split air conditioning
13
20
No
Yes
Cooling Component
350
system
Required
Required
Cooling Component 3 -hers -cool
Required
1-herscool
Cooling Component 2
SplitAirCond - Split air conditioning
13
20
No
Yes
Cooling Component
Required
system
Cooling Component 5 -hers -cool
Required
350
Required
2 -hers -cool
Cooling Component 3
SplitAirCond - Split air conditioning
14
24
No
Yes
Cooling Component
Heat Pump System 7 -hers -cool
system
Not Required
Required
Not Required
3 -hers -cool
Cooling Component 4
SplitAirCond - Split air conditioning
13
20�
No
Yes
Cooling Component
system
4 -hers -cool
Cooling Component 5
SplitAirCond - Split air conditioning�+
14
21
No
Yes
Cooling Component
system
• ��
5 -hers -cool
Cooling Component 6
SplitAirCond - Split air conditioning
130
20
No
Yes
Cooling Component
system
6 -hers -cool
V
HVAC COOLING - HERS VERIFICATION
01
02
V03
04
05
06
Name
Verified Airflow
• �
Airflow Target
Verified EER
Verified SEER
Verified Refrigerant
Charge
Cooling Component 1 -hers -cool
Required
350
Required
Required
Required
Cooling Component 2 -hers -cool
Required
350
Required
Required
Required
Cooling Component 3 -hers -cool
Required
350
Required
Required
Required
Cooling Component 4 -hers -cool
Required
350
Required
Required
Required
Cooling Component 5 -hers -cool
Required
350
Required
Required
Required
Cooling Component 6 -hers -cool
Required �„
350
Required
Required
Required
Heat Pump System 7 -hers -cool
Not Required
Not Required
Required
Not Required
KM
.0
Registration Number: A�
CA Building Energy Efficiency Standards - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF111-09292014-651
HERS Provider:
Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 16 of 18
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
08
*Ik�
Verified Duct Design
Low -leakage
Supply Duct
Verification
Duct Leakage Target (%)
Verified Duct Location
Name
Type
Duct Leakage
Insulation R -value
Location
Return Duct
Bypass Duct
HERS Verification
Air Distribution System 1
Ducts located in attic
Sealed and tested
8
Attic
Attic
None
Air Distribution
System 1 -hers -dist
Air Distribution System 2
Ducts located in attic
Sealed and tested
8
Attic
Attic
None
Air Distribution
System 2 -hers -dist
Air Distribution System 3
Ducts located in attic
Sealed and tested
8
Attic
Attic
None
Air Distribution
System 3 -hers -dist
6.0
Not Required
Not Required
Not Required
3 -hers -dist
Air Distribution
Air Distribution System 4
Ducts located in attic
Sealed and tested
8Attic
Air Distribution System
Attic
None
System 4 -hers -dist
Not Required
Not Required
---
(�
Air Distribution
Air Distribution System 5
Ducts located in attic
Sealed and tested
8 ��
Attic
Attic
None
System 5 -hers -dist
Air Distribution System 6
Ducts located in attic
Sealed and tested
8
Attic
Attic
None
Air Distribution
Air Distribution System
y
Required
6.0
Not Required
Not Required
Not Required
System 6 -hers -dist
HVAC DISTRIBUTION - HERS VERIFICATION ^�
01
02
03
04
05 06
07
Duct Leakage
*Ik�
Verified Duct Design
Low -leakage
Name
Verification
Duct Leakage Target (%)
Verified Duct Location
Return Supply
Air Handler
Air Distribution System
Required
�V6.0
Not Required
Not Required
Not Required
---
1 -hers -dist
Air Distribution System
Required
q
V0�
6.0
Not Required
Not Required
Not Required
---
2 -hers -dist
Air Distribution System
Required�v
6.0
Not Required
Not Required
Not Required
3 -hers -dist
Air Distribution System
Required
(� e
V 6.0
Not Required
Not Required
Not Required
---
4 -hers -dist
Air Distribution System
Required
6.0
Not Required
Not Required
Not Required
---
5-hers-dist
Air Distribution System
y
Required
6.0
Not Required
Not Required
Not Required
6 -hers -dist
Now
.0
Registration Number: A�® Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CFIR-09292014-651 Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CF1 R -PRF -01
Page 17 of 18
HVAC -FAN SYSTEMS
&A
02
01
01
02
03
04
Name
Type
Fan Power (Watts/CFM)
HERS Verification
HVAC Fan 1
Single Speed PSC Furnace Fan
0.58
HVAC Fan 1 -hers -fan
HVAC Fan 2
Single Speed PSC Furnace Fan
0.58
HVAC Fan 2 -hers -fan
HVAC Fan 3
Single Speed PSC Furnace Fan
0.58
HVAC Fan 3 -hers -fan
HVAC Fan 4
Single Speed PSC Furnace Fan
0.58
HVAC Fan 4 -hers -fan
HVAC Fan 5
Single Speed PSC Furnace Fan
0.58
HVAC Fan 5 -hers -fan
HVAC Fan 6
Single Speed PSC Furnace Fan
0.58
HVAC Fan 6 -hers -fan
GZI
HVAC FAN SYSTEMS - HERS VERIFICATION
&A
02
01
02
03
Name
VerifiedF�anWatt Draw
Required Fan Efficiency (Watts/CFM)
HVAC Fan 1 -hers -fan
Required
0.58
HVAC Fan 2 -hers -fan
►. `'� Required
0.58
HVAC Fan 3 -hers -fan
�� Required
0.58
HVAC Fan 4 -hers -fan
Required
0.58
HVAC Fan 5 -hers -fan
. Required
0.58
HVAC Fan 6 -hers -fan
Required
0.58
IAO (Indoor Air Quality) FANS v
01
02
W 03
04
05
06
Name
�(
IAO CFM
IAQ Watts/CFM
IAO Fan Type
IAO Recovery
Effectiveness(%)
HERS Verification
DwellingUnit
254.22 0-
0.25
Default
0
Required
U
COOLING VENTILATION
k
01
'00 02 03 04 05
Name
^tooling Vent CFM Cooling Vent Watts/CFM Number of Fans HERS Verification
WH Fan 1
4W 80 0.025 1 Required
Registration Number:r, Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-09292014-651 Report Generated at: 2014-10-03 14:01:06
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: Private Residence Calculation Date/Time: 13:56, Fri, Oct 03, 2014
Calculation Description: Title 24 Analysis
Input File Name: Lot 15B.xml
CFI R -PRF -01
Page 18 of 18
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:.
Butch White
Company:
Signature Date:
BREEZE AIR CONDITIONING
10/3/2014
Address:
CEA/HERS Certification Identification (If applicable):
75-145 St. Charles Place
City/statePalm Desert, CA 92211
Phone: 7600-346-0855
XW
RESPONSIBLE PERSON'S DECLARATION STATEMENT(/
I certify the following under penalty of perjury, under the laws of the State of California:
1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility fort a building design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate gf;.Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
Responsible Designer Name: 4C�'
Responsible Designer Signature:
Christopher Kidney . G�
Company:
Date Signed:
to
Kristi Hanson Architects, Inc.
Address: �`�
License: � �'�,' ,p f ,�
% I
72-185 Painters Path Suite A ��
�
City/State/Zip: r`N
Phone:
Palm Desert , Ca 92260 i�
760-776-4068
.may
Registration Number:
CA Building Energy Efficiency Stantlbrds - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-09292014-651
HERS Provider:
Report Generated at: 2014-10-03 14:01:06
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Lot 15-B Residence
Building Type 2 Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
10/3/2014
Project Address
81-413 Columbus Way La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
8,922
Addition
n/a
# of Units
7
INSULATION
Construction Type
Area
Cavity
Special Features Status
Wall Wood Framed
R 21 10,274
New
Roof Wood Framed Attic
R 38 6,982
Cool Roof
New
Slab Unheated Slab -on -Grade
- no insulation 6,859
Perim = 526'
New
Demising Wood Framed w/o Crawl Space R 25 2,053
New
Door Opaque Door
- no insulation 296
New
FENESTRATION
Orientation Area
I Total Area: 2,139 Glazing Percentage: 24-0%1
U -Fac SHGC Overhang Sidefins
New/Altered Average U -Factor: 0.49
Exterior Shades Status
Right (NKq 25.0
0.390
0.24 2.0
none
Bug Screen New
Rear (SVtq 46.0
0.390
0.24 8.0
none
Bug Screen New
Rear (SVtq 184.0
0.540
0.24 8.0
none
Bug Screen New
Right (NVtq 27.0
0.390
0.24 10.0
none
Bug Screen New
Rear (SW) 63.0
0.390
0.24 10.0
none
Bug Screen New
Rear (SVtq 343.0
0.540
0.24 10.0
none
Bug Screen New
Left (SE) 31.0
0.390
0.24 10.0
none
Bug Screen New
Left (SE) 157.5
0.540
0.24 10.0
none
Bug Screen New
Front (NE) 122.0
0.390
0.24 10.0
none
Bug Screen New
Front (NE) 53.0
1.280
0.80 10.0
none
Bug Screen New
Right (NIAq 23.0
0.560
0.25 10.0
4.00/0.00
Bug Screen New
Right (NVIq 8.0
0.390
0.24 10.0
4.00/0.00
Bug Screen New
Left (SE) 237.0
0.390
0.24 8.0
none
Bug Screen New
Skylight 1.4
0.300
0.30 none
none
None New
HVAC SYSTEMS
Qty. Heating
Min. Eff
Cooling
Min. Eff
Thermostat Status
1 Central Furnace
98% AFUE
Split Air Conditioner
20.0 SEER
Setback
New
1 Central Furnace
98% AFUE
Split Air Conditioner
20.0 SEER
Setback
New
1 Central Furnace
98% AFUE
Split Air Conditioner
24.0 SEER
Setback
New
HVAC DISTRIBUTION
Location Heating
Cooling Duct Location
Duct
R -Value Status
HVAC 1 Ducted
Ducted Attic
8.0
New
HVAC 2 Ducted
Ducted Attic
8.0
New
HVAC 3 Ducted
Ducted Attic
8.0
New
WATER HEATING
Ot . Type
Gallons Min. Eff
Distribution Status
2 Large Storage Gas
60
0.99
All Pipes Ins (HERS) New
Ene Pro 6.3 by Ener Soft User Number: 3665
Runcode: 2014-10-03T14:02:35
ID:
Page 21 of 59
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Lot 15-8 Residence
Building Type 10 Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
10/3/2014
Project Address
81-413 Columbus Way La Quinta
Cal ifomia Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
8,922
Addition
n/a
# of Units
7
INSULATION
Construction Type
Area
Cavity Special Features Status
FENESTRATION
Orientation Area
I Total Area: 2,139 Glazing Percentage: 24.0%1
U -Fac SHGC Overhang Sidefins
New/Altered Average U -Factor: 0.49
Exterior Shades Status
Skylight 1.4
0.300
0.30 none none
None New
Front (NE) 95.0
0.390
0.24 4.0 none
Bug Screen New
Front (NE) 84.0
0.560
0.25 4.0 none
Bug Screen New
Right (NVIO 24.0
0.710
0.73 4.0 none
Bug Screen New
Right (NVI0 101.0
0.390
0.24 4.0 none
Bug Screen New
Right (NV19 23.0
0.560
0.25 4.0 none
Bug Screen New
Left (SE) 15.0
0.560
0.25 4.0 none
Bug Screen New
Left (SE) 182.0
0.390
0.24 4.0 none
Bug Screen New
Rear (SV1) 23.0
0.560
0.25 4.0 none
Bug Screen
New
Rear (SVA) 121.4
0.390
0.24 4.0 none
Bug Screen
New
Front (NE) 148.5
0.540
0.24 8.0 none
Bug Screen New
HVAC SYSTEMS
Ot . Heating
Min. Eff
Cooling Min. Eff
Thermostat Status
1 Central Furnace
98% AFUE
Split Air Conditioner 20.0 SEER
Setback
New
1 Central Furnace
98% AFUE
Split Air Conditioner 21.0 SEER
Setback
New
1 Central Furnace
98% AFUE
Split Air Conditioner 20.0 SEER
Setback
New
HVAC DISTRIBUTION
Location Heating
Cooling Duct Location
Duct
R -Value Status
HVAC 4 Ducted
Ducted Attic
8.0
New
HVAC 5 Ducted
Ducted Attic
8.0
New
HVAC 6 Ducted
Ducted Attic
8.0
New
WATER HEATING
Ot . Type
Gallons Min. Eff Distribution Status
Ener Pro 6.3 by EnerqySoft User Number., 3665
RunCode: 2014-10-03T14:02:35
ID:
Page 22 of 59
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Lot 15-B Residence
Building Type 10 Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
10/3/2014
Project Address
81-413 Columbus Way
La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
8,922
Addition
n/a
# of Units
7
INSULATION
Construction Type
Area
Cavity Special Features Status
FENESTRATION
Orientation Area
I Total Area: 2,139 Glazing Percentage: 24.0 % I New/Altered Average U -Factor: 0.49
U -Fac SHGC Overhang Sidefins Exterior Shades Status
HVAC SYSTEMS
Ot . Heating
Min. Eff Cooling Min. Eff Thermostat Status
2 Split Heat Pump
10.00 HSPF Split Heat Pump 18.0 SEER Setback
New
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
HVAC 7 Ductless / with Fan Ductless n/a n/a
New
WATER HEATING
Qty. Type
Gallons Min. Eff Distribution Status
Ene Pro 6.3 by EnergySoft
User Number: 3665 RunCode: 2014-10-03714:02:35 /D:
Page 23 of 59
MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R
Project Name
Date
Lot 15-B Residence
1101312014
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
110.6(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§110.6(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
110.7: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
110.8(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -2R Form.
§110.8(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §110.8(i) when the
installation of a Cool Roof is specified on the CF -1 R Form.
*§1 50.0 a : Minimum R-30 R-19 for Additions/Alterations insulation in wood -frame ceiling orequivalent U -factor.
§150.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value.
*§1 50.0 c : Minimum R-13 insulation in 2x4 wood -frame wall R-19 in 2x6 orequivalent U -factor.
*§1 50.0 d : Minimum R-19 insulation in raised wood -frame floor orequivalent U -factor.
150.0 : Air retarding wrap is tested, labeled, and installed according to ASTM E1677-95 2000 when specified on the CF -1 R Form.
150.0 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150.0(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
§150.0(q) Fenestration Products. Fenestration separating conditioned space from unconditioned space or outdoors shall meet the
requirements of either Item 1 or 2 below:
1. Fenestration, including skylight products, must have a maximum U -factor of 0.58.
2. The weighted average U -factor of all fenestration, including skylight products, shall not exceed 0.58.
EXCEPTION to Section 150.0(q)1: Up to 10 square feet of fenestration area or 0.5 percent of the Conditioned Floor Area, whichever is
reater, is exempt from the maximum U -factor requirement.
150.0 r Solar Ready Buildings. Shall meet the requirements of Section 110.10 applicable to the building project.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150.0 e 1 A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150.0(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device.
§150.0(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110.0-§110.3: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§110.3(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §110.3(c)5.
§110.5: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
150.0(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or RCCA.
§150.0(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 11 0.2 c .
§150.00)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally
wrapped with insulation having an installed thermal resistance of R-12 or greater.
§150.00)113: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
EnergyPro 6.3 by EnergySoR User Number: 3665 ID: Page 24 of 59
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R
Project Name
Date
Lot 15-8 Residence
10/3/2014
§150.00)2A: All domestic hot water system piping conditions listed below, whether buried or unburied, must be insulated per TABLE
120.3-A.
i. The first 5 feet (1.5 meters) of hot and cold water pipes from the storage tank.
ii. All piping with a nominal diameter of 3/4 inch (19 millimeter) or larger.
iii. All piping associated with a domestic hot water recirculation system regardless of the pipe diameter.
iv. Piping from the heating source to storage tank or between tanks.
v. Piping buried below grade.
vi. All hot water pipes from the heating source to the kitchen fixtures.
§150.00)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards
Table 120.3-A.
150.0 3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§150.00)4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
§150.0(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC
Sections 601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed
level of R-6 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that
meets the applicable requirements of UL 181, UL 181A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic
or tape is used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150.0(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150.0(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150.0(m)7: Exhaust fans stems have back draft or automatic dampers.
§150.0(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150.0(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150.0 m 10: Flexible ducts cannot have porous inner cores.
§150.0(n)1: Systems using gas or propane water heaters, whether tank or on -demand, to serve individual dwelling units shall include
all the following components :
A. A 120V electrical receptacle that is within 3 feet from the water heater and accessible to the water heater with no obstructions;
B. A Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the space where the water
heater is installed;
C. A condensate drain that is no more than 2 inches higher than the base of the installed water heater, and allows natural draining
without pump assist,
D. A gas supply line with a capacity of at least 200,000 Btu/hr.
§150.0(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2 Ventilation and Acceptable Indoor Air Quality
in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in
Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§110.4(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§110.4(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
110.4(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§110.4(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
150.0 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150.0
Residential Lighting Measures:
§150.0(k)1A: Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with Section 150.0(k) in accordance
with TABLE 150.0-A or TABLE 150.0-B, as applicable.
150.0 k 1 C: The wattage of permanently installed luminaires shall be determined asspecified by §130.0(c).
150.0 k 1 D: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency - 20 kHz.
§150.0(k)1 E: Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume
no more than five watts of power per luminaire or exhaust fan as determined in accordance with Section 130.0(c). Night lights shall not
be required to be controlled by vacancy sensors.
EnergyPro 6.3 by EnergySoft User Number. 3665 ID: Page 25 of 59
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R
Project Name
Date
Lot 15-8 Residence
10/3/2014
150.0 k 1 F: Lighting integral to exhaust fans, in rooms other than kitchens shall meet the applicable requirements of §150.0(k).
150.0(k)2: All switching devices and controls shall meet the requirements of §150.0(k)2.
§150.0(k)3: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ftZ or 100 watts
for dwelling units larger than 2,500 ft2 may be exempt from the 50 percent high efficacy requirement when all
lighting in the kitchen is controlled in accordance with the applicable provisions in Section 150.0(k)2, and is also
controlled by vacancy sensors or dimmers.
§150.0(k)4: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
§150.0(k)5: Lighting installed in bathrooms shall meet the following requirements:
A. A minimum of one high efficacy luminaire shall be installed in each bathroom; and
B. All other lighting installed in each bathroom shall be high efficacy or controlled by vacancy sensors.
§150.0(k)6: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§150.0(k)7: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be
high efficacy, or shall be controlled by either dimmers or vacancy sensors.
EXCEPTION 1: Luminaires in closets less than 70 square feet.
EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site.
§150.0(k)8: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the luminaire is airtight with air
leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150.0(k)9A: For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on
the same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of items
ii or iii below; and
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and
automatically reactivates the motion sensor within 6 hours
iii. Controlled by one of the following methods:
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and
which is programmed to automatically turn the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements:
At a minimum provides the functionality of an astronomical time clock in accordance with Section 110.9;
meets the Installation Certification requirements in Section 130.4; meets the requirements for an EMCS in
Section 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically turn the outdoor lighting OFF during daylight hours.
§150.0(k)9A: For low-rise multi -family residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and
outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
following requirements:
i. Shall comply with Section 150.0(k)9A; or
ii. Shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)9: For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by Section 150.0(k)9B or
Section 150.0(k)9D shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)9D: Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall
comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)10: Internally illuminated address signs shall comply with Section 140.8; OR not contain a screw -base socket, and consume
no more than five watts of power as determined according to §130.0(d).
§150.0(k)11: Lighting for residential parking garages for eight or more
vehicles shall comply with the applicable requirements for nonresidential garages in Sections 110.9, 130.0, 130. 1,
130.4, 140.6, and 141.0.
§150.0(k)12A. In a low-rise multi -family residential building where the total interior common area in a single building equals 20 percent
or less of the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
§150.0(k)12B. In a low-rise multi -family residential building where the total interior common area in a single building equals more than
20 percent of the floor area, permanently installed lighting in that building shall:
i. Comply with the applicable requirements in Sections 110.9, 130.0, 130.1, 140.6, and 141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
ingress and egress.
EnergyPro 6.3 by EnergySoft User Number: 3665 ID: Page 26 of 59
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lot 15-B Residence
Date
10/3/2014
System Name
HVAC 1
Floor Area
1,317
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 537
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 88,200
11,137
1,800 381
11,740
Total Output Btuh 88,200
0
Output Btuh/s ft 67.0
525
448
Cooling System
0
0
Output per System 58,000
0
0 0
0
Total Output Btuh 58,000
190
1,800
-190
Total Output ons 4.8
525
448
Total Output Btuh/s ft 44.0
Total Output s ft/Ton 272.5
1 12,377
12,446
Air System
CFM per System
1,000
HVAC EQUIPMENT SELECTION
Airflow cfm
1,000
Lennox XC25-060-230-" 43,962
5,125
88,200
Airflow cfm/s ft
0.76
Airflow cfm/Ton
206.9
Outside Air %
0.0%
Total Adjusted System Output 43,962
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
5,125
Aug 3 PM
88,200
Jan 1 AM
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air to
0 cfm
68 OF
68 OF 97 OF 97 OF
10
Heating Coil Supply Fan 97 OF
1,000 cfm
ROOM
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
75/62°F
75/62°F 55/54°F 55/54°F
Cooling Coil Supply Fan 56 / 54 OF
1,000 cfm
47.8% ROOM
75/62°F
EnergyPro 6.3 by EnergySoft
User Number: 3665 RunCode: 201410-03T14:02:35 /D:
Page 27 of 59
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lot 15-B Residence
Date
10/3/2014
System Name
HVAC 2
Floor Area
1,380
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,014
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output perSystem 88,200
20,573
1,886 708
21,551
Total Output Btuh 88,200
0
Output Btuh/s ft 63.9
969
823
Cooling System
0
0
Output perSystem 58,000
0
0 0
0
Total Output Btuh 58,000
190
969
22.702
F 1,886
-190
Total Output ons 4.8
823
Total Output Btuh/s ft 42.0
F23,006
Total Output s ft/Ton 285.5
Air System
CFM perSystem
1,000
HVAC EQUIPMENT SELECTION
Airflow cfm
1,000
Lennox XC25-060-230-" 44,090
5,111
88,200
Airflow cfm/s ft
0.72
Airflow cfm/Ton
206.9
Outside Air %
0.0%
Total Adjusted System Output 44.090
(Adjusted for Peak Design conditions)
I TIME OF SYSTEM PEAK
5,111
Aug 3 PM
88,200
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 of
Outside Air No
0 cfm
67 of
67 of 97 OF 97 OF
10
Heating Coil Supply Fan 96 of
1,000 cfm
ROOM
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
76/62oF
76/62oF 55/54°F 55/54OF
Cooling Coil Supply Fan 56 / 54 OF
1,000 cfm
47.8% ROOM
75/62OF
EnergyPro 6.3 by EnergySoff
User Number: 3665 RunCode: 201410-03714:02:35 ID:
Page 28 of 59
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lot 15-B Residence
Date
10/3/2014
System Name
HVAC 3
Floor Area
599
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 780
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 68,600
15,526
818 385
11,802
Total Output Btuh 68,600
0
Output Btuh/s ft 114.5
732
451
Cooling System
0
0
Output per System 24,000
0
0 0
0
Total Output Btuh 24,000
190
818
-190
Total Output ons 2.0
732
451
Total Output Btuh/s ft 40.1
Total Output s ft/Ton 299.5
1 17,179
12,513
Air System
CFM per System
600
HVAC EQUIPMENT SELECTION
Airflow cfm
600
Lennox XC25-024-230-** 17,736
2,584
68,600
Airflow cfm/s ft
1.00
Airflow cfm/Ton
300.0
Total Adjusted System Output 17,736
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
2,584 68,600
Aug 3 PM Jan 1 AM
Outside Air % 0.0%
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air -4 V-
0 cfm
67 OF
67 OF 97 OF 97 OF
M
Supply Fan
Heating Coil 97 OF
600 cfm
ROOM
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air A._
0 cfm
76/62°F
76/62°F 55/54°F 55/54°F
0,
Cooling Coil Supply Fan 56 / 54 OF
600 cfm
47.1 % ROOM
75/62°F
EnergyPro 6.3 by EnergySoft
User Number: 3665 RunCode: 2014-10-03714:02:35 /D:
Page 29 of 59
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lot 15-B Residence
Date
10/3/2014
System Name
HVAC 4
Floor Area
1,369
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 834
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output perSystem 88,200
17,059
1,871 574
17,572
Total Output Btuh 88,200
0
Output Btuh/s ft 64.4
804
671
Cooling System
0
0
Output perSystem 58,000
0
0 0
0
Total Output Btuh 58,000
190
1,871
-190
Total Output ons 4.8
804
671
Total Output Btuh/s ft 42.4
Total Output s ft/Ton 283.2
1 18,857
18,723
Air System
CFM perSystem
1,000
HVAC EQUIPMENT SELECTION
Airflow cfm
1,000
LennoxXC25-060-230-" 44,031
5,132
88,200
Airflow cfm/s ft
0.73
Airflow cfm/Ton
206.9
Outside Air %
0.0%
Total Adjusted System Output 44,031
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
5,132
Aug 3 PM
88,200
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air -4 V-
0 cfm
67 OF
67 OF 97 OF 97 OF
f 0
M
Heating Coil Supply Fan 97 OF
1,000 cfm
ROOM
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
76 / 62 OF
76/62°F 55/54°F 55/54°F
ail
Cooling Coil Supply Fan 56 / 54 OF
1,000 cfm
47.8% ROOM
75 / 62 OF
EnergyPro 6.3 by EnergySoft
User Number: 3665 RunCode: 2014-10-03714:02:35 /D:
Page 30 of 59
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lot 15-B Residence
Date
10/3/2014
System Name
HVAC 5
Floor Area
1,005
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 793
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output perSystem 88,200
16,173
1,373 480
14,896
Total Output Btuh 88,200
0
Output Btuh/s ft 87.8
762
569
Cooling System
0
0
Output perSystem 48,500
0
0 0
0
Total Output Btuh 48,500
510
1,373
-510
Total Output ons 4.0
762
569
Total Output Btuh/s ft 48.3
Total Output s ft/Ton 248.7
1 18,206
115,523
Air System
CFM perSystem
1,200
HVAC EQUIPMENT SELECTION
Airflow cfm
1,200
Lennox XC25-048-230-" 35,617
5,297
88,200
Airflow cfm/s ft
1.19
Airflow cfm/Ton
296.9
Outside Air %
0.0%
Total Adjusted System Output 35,617
(Adjusted for Peak Design conditions)
1 TIME OF SYSTEM PEAK
5,297
Aug 3 PM
88,200
r Jan 1 AM
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air 4V-
0 cfm
68 OF
68 OF 97 OF 97 OF
f iC��Tr'
M
Heating Coil Supply Fan
1,200 cfm
97 OF
ROOM
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak)
112/78°F
Outside Air
0 cfm
76/62°F
76/62°F 55/54°F 55/54°F
Cooling Coil Supply Fan 56 / 54 OF
1,200 cfm
47.0% ROOM
75/62°F
EnergyPro 6.3 by EnergySoft
User Number: 3665 RunCode: 2014-10-03T14:02:35 /D:
Page 31 of 59
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lot 15-B Residence
Date
10/3/2014
System Name
HVAC 6
Floor Area
2,053
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,327
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 88,200
26,542
2,805 683
20,830
Total Output Btuh 88,200
0
Output Btuh/s ft 43.0
1,251
795
Cooling S stem
0
0
Output per System 58,000
0
0 0
0
Total Output Btuh 58,000
190
2,805
-190
Total Output ons 4.8
1,251
795
Total Output Btuh/s ft 28.3
Total Output s ft/Ton 424.8
1 29,234
22,230
Air System
CFM per System
1,000
HVAC EQUIPMENT SELECTION
Airflow cfm
1,000
Lennox XC25-060-230-" 43,602
5,910
88,200
Airflow cfm/s ft 0.49
Airflow cfm/Ton
206.9
Total Adjusted System Output 43,602
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
5,910 88,200
Aug 3 PM Jan 1 AM
Outside Air % 0.0%
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
101
Outside Air
0 cfm
67 OF
67 OF 97 OF 97 OF
f n:�
Heating Coil Supply Fan 96 OF
1,000 cfm
ROOM
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
76/63°F
76/63°F 55/54°F 55/54°F
Cooling Coil Supply Fan 56 / 54 OF
1,000 cfm
48.9% ROOM
75/62°F
EnergyPro 6.3 by EnergySoft
User Number 3665 RunCode: 2014-10.03714:02:35 ID:
Page 32 of 59
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lot 15-B Residence
Date
10/3/2014
System Name
HVAC 7
Floor Area
1,199
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
2
COIL COOLING PEAK
CFM Sensible
Total Room Loads 558 11,789
Return Vented Lighting 0
Return Air Ducts 0
Return Fan 0
Ventilation 0 0
Supply Fan 381
Supply Air Ducts 0
TOTAL SYSTEM LOAD 1 12,170
COIL HTG.
Latent CFM
1,638 489
0 0
1,638
PEAK
Heating System
Sensible
Output perSystem 36,200
15,367
Total Output Btuh 72,400
Output Btuh/s ft 60.4
0
Cooling System_
0
Output perSystem 27,300
0
Total Output Btuh 54,600
-381
Total Output ons 4.6
0
Total Output Btuh/s ft 45.5
Total Output s ft/Ton 263.5
14,986
Air System
CFM perSystem
600
HVAC EQUIPMENT SELECTION
Airflow cfm
1,200
Fujitsu Mini Split 24RLXFW/AOU24 45,997
0
45,219
Airflow cfm/s ft 1.00
2.4 kW Supplemental Electric
16,246
Airflow cfm/Ton
263.7
61,465
Jan 1 AM
Outside Air % 0.0 %
Total Adjusted System Output 45,997
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
0
Aug 3 PM
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
68 OF
68 OF 97 OF 97 OF 97 OF
C
Heating Coil Aux. Heat Coil Supply Fan
97 OF
1,200 cfm
ROOM
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
75/62°F
75/62°F 55/54°F 55/54°F
Cooling Coil Supply Fan
1,200 cfm
47.3%
55 / 54 OF
ROOM
75/62°F
EnergyPro 6.3 by EnergySoft
User Number: 3665 RunCode: 201410-03714:02:35 ID:
Page 33 of 59
ROOM LOAD SUMMARY
Project Name Date
Lot 15-8 Residence 10/3/2014
System Name Floor Area
HVAC 1 1,317
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult.PFensibleM SLatent CFM Sensible Latent CFM I Sensible
Zone 1 Dining, Media, Powder, Li 1 5371 11,1371 1,800 5371 11,1371 1,800 3811 11,740
PAGE TOTAL
TOTAL*
537
11,137
1,800
381
11,740
537
11,137
1,800
381
11,740
* Total includes ventilation load for zonal systems.
EnergyPro 6.3 by EnergySoft User Number.' 3665 RunCode: 2014-10-03714:02:35 /D: Page 34 of 59
ROOM LOAD SUMMARY
Lot 15-8 Residence
10/3/2014
HVAC 2 1,380
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible Latent CFM I Sensible I Latent I CFM I Sensible
Zone 2 Great Room, Kitchen, Pad 1 1,0141 20,5731 1,886 1,0141 20,5731 1,8861 7081 21,551
PAGE TOTAL
TOTAL '
' Total includes ventilation load for zonal
1,014
20,573
1,886
708
21,551
1,014
20,573
1,886
708
21,551
ROOM LOAD SUMMARY
Lot 15-8 Residence 10/3/2014
System Name Floor Area
HVAC 3 599
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room NameMult. CFM Sensible Latent CFM Sensible Latent CFM Sensible
Zone 3 Entry, Office 1 780 1 15,526 1 818 7801 15,5261 818 3851 11,802
' Total includes ventilation load for zonal
PAGE TOTAL
TOTAL'
780
15,526
818
385
11,802
780
15,526
818
385
11,802
2014-10-03T14:02:35 /D:
I ROOM LOAD SUMMARY I
Project Name Date
Lot 15-8 Residence 10/3/2014
System Name Floor Area
HVAC 4 1,369
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK
Zone Name I Room Name Mult. I CFM I Sensible I Latent CFM I Sensible I Latent CFM Sensible
Zone 4 1 Master Suite 1 1 8341 17,0591 1, 871 8341 17,0591 1,871 5741 17,572
PAGE TOTAL
TOTAL'
834
17,059
1,871
574 17,572
834
17,0591
1,8711
574 17,5721
Total includes ventilation load for zonal systems.
EnergyPro 6.3 by EnergySoft User Number: 3665 RunCode: 2014-10-03T14:02:35 /D: Page 37 of 59
ROOM LOAD SUMMARY
Project Name Date
Lot 15-8 Residence 10/3/2014
System Name Floor Area
HVAC 5 1,005
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name I Room Name I Mult. I CFM Sensible I Latent CFM Sensible Latent CFM I Sensible
Zone 5 1 Guest BR 1, 2, GBa 1,2 1 1 1 7931 16,1731 1,373 793 16,1731 1,373 4801 14,896
PAGE TOTAL
TOTAL*
793
16,173
1,373
480
14,896
793
16,173
1,373
480
14,896
* Total includes ventilation load for zonal systems.
EnergyPro 6.3 by EnergySoft User Number. 3665 RunCode: 2014-10-03714:02:35 ID: Page 38 of 59
ROOM LOAD SUMMARY
Project Name Date
Lot 15-8 Residence 10/3/2014
System Name Floor Area
HVAC 6 2,053
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name I Room Name I Mult.P1,3271
FM Sensible Latent CFM Sensible Latent CFM Sensible
ZONE 6 Guest Suite 126,5421 2,805 1,3271 26,5421 2,805 6831 20,830
PAGE TOTAL
TOTAL*
1,3271
26,5421
2,8051
683
20, 830
1,327
26,542
2,805
683
20,830
* Total includes ventilation load for zonal systems.
EnergyPro 6.3 by EnergySoft User Number: 3665 RunCode: 2014-10-03714:02:35 ID: Page 39 of 59
ROOM LOAD SUMMARY
Project Name Date
Lot 15-8 Residence 10/3/2014
System Name Floor Area
HVAC 7 1,199
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name I Room Name I Mult.CFM Sensible Latent CFM Sensible Latent CFM Sensible
Zone 7 Conditioned Storage 1 5581 11,7891 1,638 5581 11,7891 1,638 4891 15,367
PAGE TOTAL
TOTAL'
I ' Total includes ventilation load for zonal
558
11,7891
1,6381
489
15,367
558
11,7891
1,6381
489
15,367
ROOM HEATING PEAK LOADS
Project Name
Lot 15-8 Residence
Date
10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Dining, Media, Powder, Laundry, Hall
Floor Area 1,317.0 ft'
Indoor Dry Bulb Temperature 68 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U-Value
0.0690 X
0.3900 X
0.0690 X
0.5400 X
0.0250 X
0.7300 X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
another room
10.00 X 0.323
Height ACH
AT °F Btu/hr
42 = 2,637
42 = 737
0 c 0
42 _ 1,814
42 c 618
42 = 2, 744
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Page Total 8,551
/60] X 42 = 3,188
AT
R-21 Wall
910.0
Dual Pane Tinted, Metal, Fixed
45.0
'R-21 Wall
720.0
Dual Pane Tinted, Metal, Sliding
80.0
R-38 Roof Attic
589.0
Slab-On-Grade
perim = 89.5
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.072
Schedule Air Sensible
Fraction
through an interior surface
X 1,317 X
Area
TOTAL HOURLY HEAT LOSS FOR ROOM 11,740
EnergyPro 6.3 by EnergySoft User Number: 3665 Runcode: 2014-10.03714:02:35 ID: Page 41 of 59
ROOM HEATING PEAK LOADS
Project Name
Lot 15-8 Residence
Date
10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great Room, Kitchen, Pantry, Bar
Floor Area 1,380.0 ft2
Indoor Dry Bulb Temperature 68 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U-Value
0.0690 X
AT °F
42 _
42 =
0 =
42 =
Btu/hr
R-21 Wall
671.5
1,946
Dual Pane Tinted, Metal, Fixed
173.0
0.3900
X
X
X
2,834
'R-21 Wall
620.0
0.0690
0
Dual Pane Tinted, Metal, Sliding
375.5
0.5400
8,516
R-38 Roof Attic
1,380.0
0.0250
X
42
c
1,449
Slab-On-Grade
perim = 113.0
0.7300
X
42
=
3,465
X
=
X
X
=
=
X
X
X
=
=
=
X
=
X
=
X
X
X
=
=
=
X
=
X
X
=
=
=
X
X
=
X
X
X
=
=
=
X
=
X
X
X
=
=
=
X
I=
=
X
I d
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.072
Schedule Air Sensible
Fraction
through an interior surface
X 1,380 X
Area
another room
10.00 X 0.323
Height ACH
Page Total
/60] X 42
AT
18,210
= 3,341
TOTAL HOURLY HEAT LOSS FOR ROOM 21,551
EnergyPro 6.3 by EnergySoft User Number: 3665 Run Code: 2014-10-03714:02:35 ID: Page 42 of 59
ROOM HEATING PEAK LOADS
Project Name
Lot 15-8 Residence
Date
10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Entry, Office
Floor Area 599.0 ft2
Indoor Dry Bulb Temperature 68 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT *F
_
=
c
c
=
c
0
c
=
=
=
=
=
=
=
=
=
42
Btu/hr
"R-21 Wall
426.0
0.0690
0
0
R-21 Wall
237.0
0.0690
42
687
Dual Pane Tinted, Metal, Fixed
78.0
0.3900
42
1,278
Single 1 " Pane Glass Door
53.0
1.2800
42
2,849
Dual Pane Tinted, Metal, Sliding
125.0
0.5400
42
2,835
Dual Metal Tinted Casement
23.0
0.5600
42
541
R-38 Roof Attic
599.0
0.0250
42
629
Slab -On -Grade
perim = 50.0
0.7300
42
1,533
Items shown with an asterisk (') denote conduction
Infiltration: 1.00 X 1.072
Schedule Air Sensible
Fraction
through an interior surface
X 599 X
Area
another room
10.00 X 0.323
Height ACH
Page Total
/60] X
AT
10,352
_ 1,450
TOTAL HOURLY HEAT LOSS FOR ROOM 11,802
EnergyPro 6.3 by EnergySoft User Number.' 3665 RunCode: 2014-10-03714:02:35 ID: Page 43 of 59
ROOM HEATING PEAK LOADS
Project Name
Lot 15-8 Residence
Date
10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master Suite
Floor Area 1,369.0 ft2
Indoor Dry Bulb Temperature 68 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U -Value
AT of Btu/hr
X 42 = 3,341
X 0 = 0
X 42 c 4,308
X 42 c 2,359
X 42 = 1,424
X 42 = 35
X 42 = 2,790
X =
X
X =
X =
X
X
X =
X =
X
X
X
X
X
X =
X
X =
X =
X =
X =
X =
X =
X
X
X =
Page Total 14,257
/60] X 42 0 3,314
AT
R-21 Wall
1,153.0
X
X
0.0690
'R-21 Wall
390.0
0.0690
Dual Pane Tinted, Metal, Fixed
263.0
X
X
0.3900
Dual Pane Tinted, Metal, Sliding
104.0
0.5400
R-38 Roof Attic
1,356.2
X
X
0.0250
So/atube 290 Dse
2.8
0.3000
Slab -On -Grade
perim = 91.0
X
X
0.7300
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to another room
10.00 X 0.323
Ceiling Height ACH
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.072
Schedule Air Sensible
Fraction
through an interior surface
X 1,369 X
Area
TOTAL HOURLY HEAT LOSS FOR ROOM 17,572
EnergyPro 6.3 by EnergySoft User Number.' 3665 RunCode: 2014-10-03714:02:35 /D: Page 44 of 59
ROOM HEATING PEAK LOADS
Project Name
Lot 15-B Residence
Date
10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest BR 1, 2, GBa 1,2
Floor Area 1,005.0 ftZ
Indoor Dry Bulb Temperature 68 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U-Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT °F
Btu/hr
c 2,828
= 3,423
= 2,140
c 716
= 0
c 1,055
= 2,300
=
=
=
=
=
=
=
=
=
=
=
12,463
42 = 2,433
R-21 Wall
976.0
X
0.0690
42
Dual Pane Tinted, Metal, Fixed
209.0
X
0.3900
42
Dual Metal Tinted Casement
91.0
X
X
0.5600
42
Double Metal Clear
24.0
0.7100
42
'R-21 Wall
210.0
X
X
0.0690
0
R-38 Roof Attic
1,005.0
0.0250
42
Slab-On-Grade
perim = 75.0
X
0.7300
42
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.072
Schedule Air Sensible
Fraction
through an interior surface
X 1,005 X
Area
to another room
10.00 X 0.323
Ceiling Height ACH
Page Total
/60] X
AT
TOTAL HOURLY HEAT LOSS FOR ROOM 14,896
EnergyPro 6.3 by EnergySoft User Number.' 3665 RunCode: 2014-10-03714:02:35 ID: Page 45 of 59
ROOM HEATING PEAK LOADS
Project Name
Lot 15-8 Residence 710/3/2014
Date
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Suite
Floor Area 2,053.0 ft'
Indoor Dry Bulb Temperature 68 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U -Value
AT *F
Btu/hr
= 4,310
= 4,757
= 1,270
= 3,368
c 2,156
0 0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
15,860
42 = 4,970
R-21 Wall
1,487.1
X
X
X
X
0.0690
X
X
X
42
Dual Pane Tinted, Metal, Fixed
290.4
0.3900
42
Dual Metal Tinted Casement
54.0
0.5600
42
Dual Pane Tinted, Metal, Sliding
148.5
0.5400
X
42
R-38 Roof Attic
Z053.0
_X
X
0.0250
X
42
'R-30 Floor No Crawlspace
2,053.0
0.0390
X
0
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to another room
8.00 X 0.403
Ceiling Height ACH
X
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.072
Schedule Air Sensible
Fraction
through an interior surface
X 2,053 X
Area
Page Total
/60] X
AT
TOTAL HOURLY HEAT LOSS FOR ROOM 20,830
EnergyPro 6.3 by EnergySott User Number: 3665 RunCode: 2014-10-03T14:02:35 ID: Page 46 of 59
ROOM HEATING PEAK LOADS
Project Name
Lot 15-8 Residence
Date
10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Conditioned Storage
Floor Area 1,199.0 ftZ
Indoor Dry Bulb Temperature 68 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U-Value AT *F
0.0690 X 42
0.5000 X 42
0.0690 X 0
0.7300 X 42
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
another room Page Total
8.00 X 0.403 /60] X
Height ACH AT
Btu/hr
= 2,968
= 6,216
= 0
= 3,281
=
=
=
=
=
=
=
=
=
=
=
=
=
12.464
42 = 2,903
R-21 Wall
1,024.0
Wood Door
296.0
'R-21 Wall
1,449.0
Slab-On-Grade
perim = 107.0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.072
Schedule Air Sensible
Fraction
through an interior surface
X 1,199 X
Area
TOTAL HOURLY HEAT LOSS FOR ROOM 15,367
EnergyPro 6.3 by EnergySoft User Number. 3665 RunCode: 2014-10-03714:02:35 ID: Page 47 of 59
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lot 15-B Residence
1 10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Dining, Media, Powder, Laundry, Hall
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,317.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 75 OF
Outdoor Daily Range.
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-21 Wall
(NIM 730.0 X 0.0690
X
30.2 =
1,523
`R-21 Wall
720.0 X 0.0690
X
0.0 =
0
R-21 Wall
(SIM 40.0 X 0.0690
X
31.0 =
86
R-21 Wall
(SE) 140.0 X 0.0690
X
31.0 =
299
R-38 Roof Attic
(N) 589.0 X 0.0250
X
56.0 =
825
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
2.732
Items shown with an asterisk (")
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF
Btu/hr
Window 08
(NIM 0.0 X 16.7 +
25.0
X 24.4 =
611
Window 09
(SIM 20.0 X 16.7 +
0.0
X 22.1 =
334
Window El
(SIM 80.0 X 19.7 +
0.0
X 25.1 =
1,576
X +
X -
X +
X -
X +
X -
X +
X -
X +
X -
X +1
X -
Page Total
21521
Internal Gain
Btu/hr
Occupants
4.0 Occupants X 245
Btuh/occ.
=
E968
Equipment
1,317 Floor Area X 0.50
w/sgft
=
2,247
Infiltration: 1.072
X 1.20 X 55.96 X 37 =
2,668
Air Sensible
CFM ELA AT
[TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
11,137
Latent Gain
Btu/hr
Occupants
4 0 Occupants X 155
Btuh/occ.
=
612
Infiltration: 4,806
X 1.20 X 55.96 X 0.00367 =
1,187
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
612
EnergyPro 6.3 by EnerqySoft
User Number- 3665 RunCode: 2014-10-03714:02:35 /D:
Pa a 48 of 59
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Lot 15-B Residence 1 10/3/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Great Room, Kitchen, Pantry, Bar Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,380.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 75 OF Outdoor Dailv Ranqe: 34 OF
Surfaces
R-21 Wall
'R-21 Wall
R-21 Wall
R-21 Wall
R-21 Wall
R-38 Roof Attic
Orientation
(N►M
(SM
(SE)
(NE)
(N)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
23.0
0.0690
30.2
620.0
0.0690
0.0
124.0
0.0690
31.0
151.5
0.0690
31.0
373.0
0.0690
29.0
1,380.0
0.0250
56.0
10.0
16.7
0.0
22.1
218.0
19.7
0.0
25.1
12.0
16.7
0.0
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Window 10
Window 11
Window 12
Window 13
Window 14
Window S-1
Window 15
Window 16
Window 17
Orientation
(NW)
(SVtq
(SVtq
(SW)
(SVV)
(SW)
(SE)
(SE)
(SE)
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
-
=
=
-
=
_
_
-
-
0.0
16.7
27.0
24.4
10.0
16.7
0.0
22.1
9.0
16.7
0.0
22.1
9.0
16.7
0.0
22.1
10.0
16.7
0.0
22.1
218.0
19.7
0.0
25.1
12.0
16.7
0.0
22.1
9.0
16.7
0.0
22.1
10.0
1 16.7
0.0
1 22.1
Page Total
Btu/hr
48
0
265
324
746
1,932
3,316
Btu/hr
659
167
150
150
167
4,296
200
150
167
6,108
Internal Gain Btu/hr
Occupants 41 Occupants X 245 Btuh/occ. 1'1
Equipment 1,380 Floor Area X 0.50 w/sgft = 2,;
Infiltration: 1.072 X 1.20 X 58.63 X
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 20,5731
Latent Gain Btu/hr
Occupants 41 Occupants X 155 Btuh/occ. = 642
Infiltration: 4,806 X 1.20 X 58.63 X 0.00367 = 1,244
Air Sensible CFM ELA AW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 6421
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lot 15-8 Residence
1 10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Great Room, Kitchen, Pantry, Bar
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,380.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 75 °F
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
Window F2
(SE) 157.5 X 19.7 +
0.0 X 25.1 =
3,104
Window 04
(NE) 0.0 X 16.7 +
21.0 X 24.4 =
513
Window 05
(NE) 0.0 X 16.7 +
21.0 X 24.4 =
513
Window 06
(NE) 0.0 X 16.7 +
35.0 X 24.4 =
855
X +
X =
X +
X =
X +
X =
X +
X =
X +
X =
Page Total
4.98
Internal Gain
Btu/hr
Occupants
4.1 Occupants X 245
Btuh/occ. =
1,014
Equipment
1,380 Floor Area X 0.50
w/sgft =
2,355
Infiltration: 1.072
X 1.20 X 58.63 X 37 =
2,796
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
20,573
Latent Gain
Btu/hr
Occupants
4.1 Occupants X 155
Btuh/occ. =
642
Infiltration: 4,806
X 1.20 X 58.63 X 0.00367 =
1,244
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
642
EnergyPro 6.3 by EnerqySoft
User Number., 3665 RunCode: 2014.10-03T14:02:35 ID:
Page 50 of 59
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lot 15-B Residence
1 10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Entry, Office
Outdoor Dry Bulb Temperature
112 OF
Floor Area
599.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature
75 OF
I Outdoor Dally Range.
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
'R-21 Wall
426.0 X 0.0690
X
0.0 =
0
R-21 Wall
(NE) 28.0 X 0.0690
X
34.0 =
66
R-21 Wall
(Sim 140.0 X 0.0690
X
52.0 =
502
R-21 Wall
(NK) 69.0 X 0.0690
X
48.1 =
229
R-38 Roof Attic
(N) 599.0 X 0.0250
X
77.0 =
1,153
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
1,950
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
Window 02
(NE) 0.0 X 19.7 +
30.0
X 28.6 =
857
Window 03
(NE) 0.0 X 19.7 +
15.0
X 28.6 =
429
Window 81
(NE) 0.0 X 63.6 +
53.0
X 92.2 =
4,886
Window G 1
(s V109 125.0 X 22.7 +
0.0
X 53.5 =
2,834
Window 18
(SVV) 25.0 X 19.7 +
0.0
X 50.5 =
492
Window 56
(NVt,) 0.0 X 23.6 +
23.0
X 46.5 =
1,068
Window 57
(NVIoq 0.0 X 19.7 +
8.0
X 41.6 =
333
X +
X -
X +1
X -
Page Total
1o,soo
Internal Gain
Btu/hr
Occupants
1.8 Occupants X 245
Btuh/occ.
=
d440E
ui ment
599 Floor Area X 0.50
w/sgft
=
1,
Infiltration: 1.072
X 1.20 X 25.45 X 37 =
1,214
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
15,526
Latent Gain
Btu/hr
Occupants
1.8 Occupants X 155
Btuh/occ.
=
279
Infiltration: 4,806
X 1.20 X 25.45 X 0.00367 =
540
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
279
EnergyPro 6.3 by Ene Soft
User Number.- 3665 Run Code: 201410-03T14:02:35 ID:
Page 51 of 59
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestratinn
Window 20
Window 21
Window 22
Window 23
Window 24
Window 25
Window 26
Window 27
Window 28
Orientation
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
RESIDENTIAL ROOM COOLING LOAD SUMMARY
X
X
X
X
X
X
X
X
X
GLF
=
=
=
_
=
_
-
=
=
Project Name
16.7
0.0
22.1
Date
Lot 15-B Residence
0.0
22.1
1
10/3/2014
ROOM INFORMATION
22.1
DESIGN CONDITIONS
16.7
0.0
22.1
Room Name
Master Suite
Outdoor Dry Bulb Temperature
22.1
112 OF
Floor Area
1,369.0 ft2
Outdoor Wet Bulb Temperature
26.0
78 OF
Indoor Dry Bulb Temperature
75 OF
I Outdoor Daily Range.-
16.7
0.0
34 OF
11.0
16.7
0.01
22.1
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-21 Wall
(NVtq
510.0
X
0.0690
X
30.2
=
1,064
"R-21 Wall
390.0
X
0.0690
X
0.0
=
0
R-21 Wall
(SE)
533.0
X
0.0690
X
31.0
=
1,140
R-21 Wall
(SK9
110.0
X
0.0690
X
31.0
=
235
R-38 Roof Attic
(N)
1,356.2
X
0.0250
X
56.0
=
1,899
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
4,338
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestratinn
Window 20
Window 21
Window 22
Window 23
Window 24
Window 25
Window 26
Window 27
Window 28
Orientation
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
_
=
_
-
=
=
9.0
16.7
0.0
22.1
12.0
16.7
0.0
22.1
9.0
16.7
0.0
22.1
27.5
16.7
0.0
22.1
11.0
16.7
0.0
22.1
104.0
16.7
0.0
22.1
26.0
16.7
0.0
22.1
27.5
16.7
0.0
22.1
11.0
16.7
0.01
22.1
Page Total
Btu/hr
150
200
150
459
184
1,737
434
459
184
Internal Gain Btu/hr
Occupants 41 Occupants X 245 Btuh/occ. = 1.1
Equipment 1,369 Floor Area X 0-W w/sgft = 2,;
Infiltration: 1.072 X 1.20 X 58.17 X 37 = C
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 17,0591
Latent Gain Btu/hr
Occupants 41 Occupants X 155 Btuh/occ. = 637
Infiltration: 4,806 X 1.20 X 58.17 X 0.00367 = 1,234
Air Sensible CFM ELA AW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 6371
52
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lot 15-B Residence
1 10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Master Suite
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,369.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature
75 OF
I Outdoor Dally Range.
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
Window H1
(SW) 104.0 X 19.7 +
0.0
X 25.1
= 2,049
Window 19
(SI/10 26.0 X 16.7 +
0.0
X 22.1
= 434
Skylight SOS -47
(N) 0.0 X 17.5 +
1.4
X 58.1
= 81
Skylight S06-48
(N) 0.0 X 17.5 +
1.4
X 58.1
= 81
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +1
X
—
Page Total
2.64
Internal Gain
Btu/hr
Occupants
41 Occupants X 245
Btuh/occ.
=
L:::1,006
Equipment
1,369 Floor Area X 0.50
w/sqft
=
2,336
Infiltration: 1.072
X 1.20 X 58.17 X 37 =
2,773
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
17,059
Latent Gain
Btu/hr
Occupants
4.1 Occupants X 155
Btuh/occ.
c
637
Infiltration: 4,806
X 1.20 X 58.17 X 0.00367 =
1,234
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
637
EnergyPro 6.3 by EnerqySoft
User Number: 3665 RunCode: 2014-10-03714:02:35 ID:
Page 53 of 59
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Lot 15-B Residence 1 10/3/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Guest BR 1, 2, GBa 1,2 Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,005.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 75 OF 1 Outdoor Daily Range: 34 OF
Opaque Surfaces
R-21 Wall
R-21 Wall
R-21 Wall
R-21 Wall
"R-21 Wall
R-38 Roof Attic
Orientation
(NE)
(NtM
(SE)
(SW)
(N)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
I X
CLTD'
=
=
=
=
=
=
=
=
299.0
0.0690
29.0
273.0
0.0690
30.2
328.0
0.0690
31.0
76.0
0.0690
31.0
210.0
0.0690
0.0
1,005.0
0.0250
56.0
0.0X
16.7+
10.0X
24.4=
0.0
41.3
24.0
64.8
I=
16.7
8.0
Page Total
Items shown with an asterisk (*) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Window 32
Window 36
Window 37
Window 38
Window 39
Window 40
Window 41
Window 42
Window 43
Orientation
(NE)
(NE)
(NE)
(NE)
(NE)
(NKK
(NIM
(NW)
(NW)
Shaded Unshaded
Btu/hr
1 5691
Area
X
X
X
X
X
GLF
+
+
+
+
+
Area
X
X
X
X
X
GLF
=
-
_
_
-
0.0X
16.7+
10.0X
24.4=
0.0X
16.7+
5.0X
24.4=
0.0
16.7
16.0
24.4
0.0
20.5
30.0
28.5
0.0X
16.7+
10.0X
24.4=
0.0
41.3
24.0
64.8
0.0
16.7
8.0
24.4
0.0X
20.5+
23.0X
28.5=
0.0
16.7
8.0
24.4
Page Total
1,
Btu/hr
244
122
391
856
244
1,554
195
656
19
4,4581
Internal Gain
Btu/hr
Occupants
3 0 Occupants X
245 Btuh/occ. _
Equipment
1,005 Floor Area X
0.50 w/sqn
Infiltration: 1.072 X 1.20 X 42.70 X 37 =
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 16,1731
Latent Gain Btu/hr
Occupants 3 0 Occupants X 155 Btuh/occ. = 467
Infiltration: 4,806 X 1.20 X 42.70 X 0.00367 = 906
Air Sensible CFM ELA OW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 4671
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Lot 15-8 Residence 10/3/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Guest BR 1,2, GBa 112 Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,005.0 ft' Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 75 OF Outdoor Daily Range: 34 OF
ue Surfaces
Orientation
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
=
=
=
c
=
-
=
=
0.0
X
X
X
16.7
38.0
24.4
0.0X
16.7+
16.0X
24.4=
15.0
20.5
0.0
26.1
18.0
16.7
0.0
22.1
5.0
X
X
16.7
0.0
22.1
5.0
16.7
0.0
22.1
2.0
X
X
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Window 48
Window 49
Window 29
Window 30
Window 31
Window 33
Window 34
Window 35
Window 44
Orientation
(NM
(NM
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
(SVO
Shaded
Area
GLF
+
+
+
+
+
+
+
+1
Unshaded
Area
X
X
X
X
X
X
X
X1
GLF
=
=
=
c
=
-
=
=
0.0
X
X
X
16.7
38.0
24.4
0.0X
16.7+
16.0X
24.4=
15.0
20.5
0.0
26.1
18.0
16.7
0.0
22.1
5.0
X
X
16.7
0.0
22.1
5.0
16.7
0.0
22.1
2.0
X
X
16.7
0.0
22.1
7.0
16.7
0.0
22.1
22.8
X1
20.5
0.2
26.1
Page Total
Btu/hr
Btu/hr
928
391
307
301
84
84
33
117
472
2, 71
Internal Gain Btu/hr
Occupants 3.0 Occupants X 245 Btuh/occ. = 739
Equipment 1,005 Floor Area X 0.50 w/sgft = 1,715
Infiltration: 1.072 X 1.20 X 42.70 X 37 = C
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 16,173
Latent Gain Btu/hr
Occupants 3 0 Occupants X 155 Btuh/occ. = 467
Infiltration: 4,806 X 1.20 X 42.70 X 0.00367 = 906
Air Sensible CFM ELA AW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 4671
IEnergyPro 6.3 by EnergySoft User Number: 3665 RunCode: 2014-10-03714:02:35 ID: Page 55 of 591
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lot 15-B Residence
1 10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guest BR 1, 2, GBa 1,2
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,005.0 ftZ
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 75 OF,
Outdoor Daily Range.
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
o
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF
Btu/hr
Window 45
(SM 8.0 X 16.7 +
0.0
X 22.1
= 134
Mindow 46
(St" 27.6 X 16.7 +
9.4
X 22.1
= 669
Window 47
(S K9 16.0 X 16.7 +
0.0
X 22.1
= 267
X +
X
—
X +
X
—
X +
X
—
X +
X
=
X +
X
—
X +1
XI
—
Page Total
1,070
Internal Gain
Btu/hr
Occupants
3 0 Occupants X 245
Btuh/occ.=L
739
Equipment
1,005 Floor Area X 0.50
w/sqft
=
1,715
Infiltration: 1.072
X 1.20 X 42.70 X 37 =
2,036
Air Sensible
CFM ELA 4T
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
16,173
Latent Gain
Btu/hr
Occupants
3.0 Occupants X 155
Btuh/occ.
=
467
Infiltration: 4,806
X 1.20 X 42.70 X 0.00367 =
906
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
467
EnergyPro 6.3 by EnergySoft
User Number. 3665 RunCode: 2014-10-03714:02:35 ID:
Pae 56 of 59
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Lot 15-8 Residence 10/3/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Guest Suite Outdoor Dry Bulb Temperature 112 OF
Floor Area 2,053.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 75 OF 1 Outdoor Daily Range: 34 OF
Opaque Surfaces
R-21 Wall
R-21 Wall
R-21 Wall
R-21 Wall
R-38 Roof Attic
'R-30 Floor No Crawlspace
Orientation
(NE)
(NVt9
(SE)
(SVL9
(N)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
Btu/hr
233.5
0.0690
29.0
467
469.0
0.0690
30.2
978
355.0
0.0690
31.0
759
429.6
0.0690
31.0
919
2,053.0
0.0250
56.0
2,874
2,053.0
0.0390
0.0
0
7.0
24.4
171
0.0
16.7
12.0
24.4
293
81.5
16.7
I=
22.1
2,280
11.0
Page Total
5,998
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
Fenestration
VVindow 65
Krindow 66
Window P1
VVindow 67
Krindow 68
Window 69
Window 58
Kfindow 63
Window 64
I Internal Gain
Orientation
(NE)
(NE)
(NE)
(NVtq
(NVtg
(NAA
(SE)
(SE)
(SE)
Area
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
GLF
-
=
=
=
_
-
-
-
Btu/hr
0.0
16.7
54.0
24.4
1,319
0.0
20.5
54.0
28.5
1,540
0.0
19.7
148.5
27.4
4,072
0.0X
16.7+
12.0X
24.4-
293
0.0
16.7
7.0
24.4
171
0.0
16.7
12.0
24.4
293
81.5
16.7
41.5
22.1
2,280
11.0
16.7
0.0
22.1
184
11.0
16.7
0.0
22.1
184
Page Total
10,33
6.2 Occupants X 245 Btuh/occ. 1
2,053 Floor Area X 0•mw/sgft = 3
Infiltration: 1.072 X 1.20 X 87.23 X 37 c
Air Sensible CFM ELA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 26,5421
Latent Gain Btu/hr
Occupants 6 2 Occupants X 155 Btuh/OCC. = 955
Infiltration: 4,806 X 1.20 X 87.23 X 0.00367 = 1,851
Air Sensible CFM ELA AW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 9551
I EnergyPro 6.3 by Ener_gySoft User Number- 3665 RunCode: 2014-10-03714:02:35 ID: Page 57 of 591
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lot 15-8 Residence
1 10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guest Suite
Outdoor Dry Bulb Temperature
112 OF
Floor Area
2,053.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 75 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
X
X =
X
X =
X
X =
X
X =
X
X
X
X =
X
X =
X
X =
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
Window 59
(S K9 23.4 X 16.7 +
5.1 X 22.1
— 504
Window 60
(SM 7.8 X 16.7 +
0.0 X 22.1
= 130
Window 61
(StM 12.8 X 16.7 +
0.0 X 22.1
= 214
Window 62
(SIAL 7.0 X 16.7 +
0.0 X 22.1
_ 117
Window 73
(SIA9 4.3 X 16.7 +
0.0 X 22.1
= 72
X +
X
—
X +
X
—
X +
X
—
X +1
X
—
Page Total
1,03
Internal Gain
Btu/hr
Occupants
6 2 Occupants X 245
Btuh/occ. =
1,509
Equipment
2,053 Floor Area X 0.50
w/sq(t o
3,503
Infiltration: 1.072
X 1.20 X 87.23 X 37 =
4,159
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
26,542
Latent Gain
Btu/hr
Occupants
6 2 Occupants X 155
Btuh/occ. =
955
Infiltration: 4,806
X 1.20 X 87.23 X 0.00367 =
1,851
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
955
EnergyPro 6.3 by EnergySoft
User Number. 3665 RunCode: 2014-10-03714:02:35 /D:
Pae 58 of 59
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Lot 15-B Residence
1 10/3/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Conditioned Storage
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1, 199.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 75 OF
I Outdoor Daily Range.
34 OF
Opaque Surfaces
Orientation Area U -Factor CLTD'
Btu/hr
R-21 Wall
(NE) 264.0 X
0.0690 X 29.0 =
528
Wood Door
(NE) 296.0 X
0.5000 X 29.0 =
4,292
R-21 Wall
(NW) 250.0 X
0.0690 X 30.2 =
521
R-21 Wall
(SE) 250.0 X
0.0690 X 31.0 =
535
R-21 Wall
(SW) 260.0 X
0.0690 X 31.0 =
556
'R-21 Wall
1,449.0 X
0.0690 X 0.0 =
0
X
X =
X
X =
X
X =
Page Total
6,433
Items shown with an asterisk
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area GLF
Btu/hr
X
+ X -
X
+ X -
X
+ X -
X
+ X -
X
+ X =
X
+ X -
X
+ X -
X
+ X -
X
+ X -
Page Total
0
Internal Gain
Btu/hr
Occupants
3.6 Occupants X
245 Btuh/occ. =
881
Equipment
1, 199 Floor Area X
0.50 w/spft =
2,046
Infiltration: 1.072
X 1.20 X 50.94 X 37
=
2,429
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
11,789
Latent Gain
CITvT T CF i � L1tI�
Btu/hr
Occupants
36 Occupants X I
6UlW Btu /occSAFEI Y DL i -IT.
I 558
PPROVED
Infiltration:
X 1.20 X 50.94 X o.003s
= FOR CONSTRUCTION
1'081
Sensible
Air Sensible
CFM ELA DW
DATE
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
By
558
EneMyPro 6.3 by EnergySoft
User Number 3665 RunCode: 2014-10-03714:02:35 /D: Page 59 of 59