BRES2015-0391 Title 24I BUILDING ENERGY ANALYSIS REPORT I
PROJECT:
Madison Club 23B
81-382 Amundson Ave.
La Quinta, CA 92253
Project Designer:
Kristi Hanson Architects, Inc.
72-185 Painters Path STE A
Palm Desert, CA 92260
(760) 776-4068
Report Prepared by:
Jon Scott
Scott Design and Title 24,
77-085 Michigan Driv
Palm Desert, CA 922 1
(760) 200-4780
8� ®r�
LDIfVG`�SAFQU/ Nr,4
4ORppR ®�T Y DEPT
DNSTpa►, —
Job Number: 1 RECEIVED"
{
Date:
FEB 0 3 2010
2/2/2016 CITY OF LA QUIRTA
COMMUNITY DEVELOPMENT
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC—www.energysoft.com.
EnemvPro 6.7 by EnemvSoft User Number: 6712 ID: 1
CERTI#E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project ame: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 2313-Kristi Hanson-15.xml
CF•RF-01
Page 1 of 16
GENERAL INFORMATION
01
Building Complies with Computer Performa`nce" I I yl "� I j""" I1 --l") ir-4
01
Project Name Madison Club 23B
04
05
02
Calculation Description Title 24 Analysis
08
Energy Use (kTDV/ft2-yr)
03
Project Location 81-382 Amundson Ave.
Compliance Margin
Percent Improvement
04
City La Quinta
05
Standards Version Compliance 2015
06
Zip Code 92253
07
Compliance Manager Version BEMCmpMgr 2013-4 (744)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.6
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 135
12
Project Scope Newly Constructed
13
Number of Dwelling Units 1
14
Total Cond. Floor Area (ft) 7797
15
Number of Zones 5
16
Slab Area (ft2) 6106
17
Number of Stories 2
18
Addition Cond. Floor Area N/A
19
Natural Gas Available Yes
20
Addition Slab Area (ft2) N/A
21
Glazing Percentage (%) 42.4%
COMPLIANCE RESULTS
01
Building Complies with Computer Performa`nce" I I yl "� I j""" I1 --l") ir-4
02
This building incorporates fear` a ,that require field-testing and/orjverification.by arcertified HERS rater under* Jhe supervision of a CEC-approved HERS provider.
04
05
03
This building incorporates one or'more Speaal Feafurespshown below
08
Energy Use (kTDV/ft2-yr)
Standard Design
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
ENERGY USE SUMMARY
04
05
06
07
08
Energy Use (kTDV/ft2-yr)
Standard Design
Proposed Design
Compliance Margin
Percent Improvement
Space Heating
4.15
5.67
-1.52
-36.6%
Space Cooling
110.06
106.67
3.39
3.1%
IAQ Ventilation
1.13
1.13
0.00
0.0%
Water Heating
3.29
4.39
-1.10
-33.4%
Photovoltaic Offset
----
0.00
0.00
---
Compliance Energy Total
118.63
117.86
0.77
0.6%
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIFOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis Input File Name: Madison Club 23B-Kristi Hanson-15.xml
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Window overhangs and/or fins
CFS)RF-01 '
Page 2of16
HERS FEATURE SUMMARY
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
• High Quality Insulation Installation (QII)
• IAQ mechanical ventilation
Cooling System Verifications:
• Minimum Airflow
• Verified EER
• Verified SEER
• Refrigerant Charge
• Fan Efficacy Watts/CFM
HVAC Distribution System Verifications:
• Duct Sealing
Domestic Hot Water System Verifications:
--None -- _
ENERGY DESIGN RATINGR In 0 11 K �I (r ~
This is the sum of the annual TDV energy consumptionor energy use components included ih the performance compliance approach fog theStandard Design Building (Energy Budget) and the annual
lk
TDV energy consumption for lighting and components not�regulated by Title 24, Part,6 (such as domestic`appliancesland consumer electronics) and accounting for the annual TDV energy offset by an
on-site renewable energy system. _<4r 1 Lt " -3 if " %_0 V i L.01 L_ "
Reference Energy Use Energy Design Rating Margin Percent Improvement
Total Energy (kTDV/f2-yr)* 153.05 152.28 0.77 0.5%
includes calculated Appliances and Miscellaneous Energy Use (AMEU)
BUILDING - FEATURES INFORMATION
01
02
03
04
05
06
07
Project Name
Conditioned Floor Area (ft2)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
Madison Club 23B
7797
1
15
5
5
1
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CFiR-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIVE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OD
Project ame: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 2313-Kristi Hanson-15.xml
CF•RF-01
Page 3 of 16
ZONE INFORMATION
01
02
03
04
05-
06
07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft)
Avg. Ceiling
Height
Water Heating System 1
Water Heating System 2
off nook dining
Conditioned
HVAC 1 off kit nookl
1922
9
DHW Sys 1
great entry
Conditioned
HVAC 2 grt enry2
1325
9
DHW Sys 1
masterguest
Conditioned
HVAC 3 mstr gest3
1452
9
DHW Sys 1
guest living
Conditioned
HVAC 4 gest liv4
1407
9
DHW Sys 1
2nd master
Conditioned
HVAC 5 2nd5
1691
9
DHW Sys 1
C(rn--�- CERTS, nc.
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIFOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE t�OD
Project Name: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 2313-Kristi Hanson-15.xml
CF&F-01
Page 4 of 16
OPAQUE SURFACES
01
02
03
04
05
06
07
08
Name
Zone
Construction
Azimuth
Orientation
Gross Area (ft2)
Window & Door Area (ft)
Tilt (deg)
NE Wall
off nook dining
R-21 Wall (W.21.2x6.16)
45
Right
832
339
90
SE Wall
off nook dining
R-21 Wall (W.21.2x6.16)
135
Front
464
129.1
90
SW Wall
off nook dining
R-21 Wall (W.21.2x6.16)
225
Left
1616
467.313
90
NW Wall
off nook dining
R-21 Wall (W.21.2x6.16)
315
Back
400
238.8
90
Roof
off nook dining
R-38 Roof Attic
431
NE Wall 2
great entry
R-21 Wall (W.21.2x6.16)
45
Right
684
120
90
SE Wall 2
great entry
R-21 Wall (W.21.2x6.16)
135
Front
416
260.536
90
SW Wall 2
great entry
R-21 Wall (W.21.2x6.16)
225
Left
684
90
NW Wall 2
great entry
R-21 Wall (W.21.2x6.16)
315
Back
455
378.5
90
Roof 2
great entry
R-38 Roof Attic
1325
NE Wall 3
masterguest
R-21 Wall (W.21.2x6.16)
45
Right
657
142.4
90
SE Wall 3
masterguest
R-21 Wall (W.21.2x6.16)
135
Front
576
104.2
90
SW Wall 3
masterguest
3225
Left
y
200
21.5
90
NW Wall 3
masterguest
r R-21 �Wall (W.21 -2x6.`11 )t
'3'15
Back.
480
146.4
90
Roof 3
masterguest
�`� !�--J U R-38`R6of Attie
I
ZJ U U
'-Z I'U 1452
NE Wall 4
guest living
R=211 V�/all.(W.21 2z6.16)
{ X45
tj� Right
g
907
203
90
SE Wall 4
guest living
R-21 Wall (W.21.2x6.16)
135
Front
619
70.6
90
SW Wall 4
guest living
R-21 Wall (W.21.2x6.16)
225
Left
907
199.6
90
NW Wall 4
guest living
R-21 Wall (W.21.2x6.16)
315
Back
619
129.6
90
Roof 4
guest living
R-38 Roof Attic
1407
NE Wall 5
2nd master
R-21 Wall (W.21.2x6.16)
45
Right
780
156
90
SE Wall 5
2nd master
R-21 Wall (W.21.2x6.16)
135
Front
350
27
90
SW Wall 5
2nd master
R-21 Wall (W.21.2x6.16)
225
Left
780
174.9
90
NW Wall 5
2nd master
R-21 Wall (W.21.2x6.16)
315
Back
350
17.8
90
Roof 5
2nd master
R-38 Roof Attic
1691
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CFIR-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIFOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE C. OD
Project ame: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 2313-Kristi Hanson-15.xml
CFF -01 -
Page 5 of 16
ATTIC
01
02
03
04
05
06
07
08
Name
Construction
Type
Roof Rise
Roof Reflectance
Roof Emittance
Radiant Barrier
Cool Roof
Attic off nook dining
Attic Roofoff nook dining
Ventilated
3
0.1
0.85
No
No
Attic great entry
Attic Roofgreat entry
Ventilated
3
0.1
0.85
No
No
Attic masterguest
Attic Roofmasterguest
Ventilated
3
0.1
0.85
No
No
Attic guest living
Attic Roofguest living
Ventilated
3
0.1
0.85
No
No
Attic 2nd master
Attic Roof2nd master
Ventilated
3
0.1
0.85
No
No
01= ._,s
LE=,NiiCER' r nco
HERS PROVIDER
Registration Number: 215-N63439678-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIFJJE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OD
Projectme: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 236-Kristi Hanson-15.xmi
CFIIORF-01
Page 6 of 16
WINDOWS
01
02
03
04
05
06
07
08
09
10
Name
Type
Surface (Orientation -Azimuth)
Width (ft)
Height (ft)
Multipli
er
Area
(ftZ)
U -factor
SHGC
Exterior Shading
K3
Window
NE Wall (Right45)
11.0
10.0
1
110.0
0.28
0.18
Insect Screen (default)
17
Window
NE Wall (Right -45)
11.6
10.0
1
116.0
0.32 1
0.24
Insect Screen (default)
K2
Window
NE Wall (Right45)
11.3
10.0
1
113.0
0.28
0.18
Insect Screen (default)
12
Window
SE Wall (Front -135)
10.9
10.0
1
109.0
0.28
0.18
Insect Screen (default)
K3 2
Window
SW Wall (Left -225)
11.0
10.0
1
110.0
0.28
0.18
Insect Screen (default)
11
Window
SW Wall (Left -225)
12.1
10.0
1
121.0
0.32
0.24
Insect Screen (default)
J2
Window
SW Wall (Left -225)
2.0
8.0
1
16.0
0.28
0.18
Insect Screen (default)
J1
Window
SW Wall (Left -225)
2.0
8.0
1
16.0
0.28
0.18
Insect Screen (default)
H1
Window
SW Wall (Left -225)
5.3
4.0
1
21.2
0.28
0.18
Insect Screen (default)
10
Window
SW Wall (Left -225)
11.0
10.0
1
110.0
0.32
0.24
Insect Screen (default)
G2
Window
SW Wall (Left -225)
6.3
6.9
1.001
43.5
0.28
0.18
Insect Screen (default)
G3
Window
SWrWall (Left -225) r- r X2.8 a r
.^� 2.0
f
1
5.6
0.28
0.18
Insect Screen (default)
08
Window
SW Wall (Left -225) If
3.0 .� 8.0
/ %24.0
0.32
0.24
Insect Screen (default)
07
Window
11 NW Wall (Back' -315) u U 19-9 10.0
L
U 1U k x..199.0
0.32
0.24
Insect Screen (default)
G1
Window
NW Wall.(Back=315)? C
t> 1:!) 19.9%
�r-2.0
r '1,�,
X39.8
0.28
0.18
Insect Screen (default)
F3
Window
NE Wall 2 (Right -45)
---
-
1
60.0
0.28
0.18
Insect Screen (default)
F2
Window
NE Wall 2 (Right45)
-
-
1
60.0
0.28
0.18
Insect Screen (default)
B1
Window
SE Wall 2 (Front -135)
1.5
5.5
1.006
8.3
0.28
0.18
Insect Screen (default)
A4
Window
SE Wall 2 (Front -135)
2.9
12.2
1.001
35.4
0.28
0.18
Insect Screen (default)
A5
Window
SE Wall 2 (Front -135)
2.8
3.3
0.996
9.2
0.28
0.18
Insect Screen (default)
01
Window
SE Wall 2 (Front -135)
8.5
10.0
1
85.0
0.32
0.24
Insect Screen (default)
A3
Window
SE Wall 2 (Front -135)
5.3
3.3
1.001
17.5
0.28
0.18
Insect Screen (default)
Al
Window
SE Wall 2 (Front -135)
2.9
12.2
1.001
35.4
0.28
0.18
Insect Screen (default)
A2
Window
SE Wall 2 (Front -135)
2.8
3.3
1.006
9.3
0.28
0.18
Insect Screen (default)
M1
Window
SE Wall 2 (Front -135)
---
---
1
60.4
0.28
0.18
Insect Screen (default)
F5
Window
NW Wall 2 (Back -315)
5.8
9.5
1
55.1
0.28
0.18
Insect Screen (default)
F6
Window
NW Wall 2 (Back -315)
5.8
3.0
1
17.4
0.28
0.18
Insect Screen (default)
06
Window
NW Wall 2 (Back -315)
17.0
12.0
1
204.0
0.32
0.24
Insect Screen (default)
F4
Window
NW Wall 2 (Back -315)
17.0
3.0
1
51.0
0.28
0.18
Insect Screen (default)
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIF
'JOE
JOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE I OD
Projecte: Madison Club 2313 Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 2313-Kristi Hanson-15.xml
CF•RF-01
Page 7 of 16
F1
Window
NW Wall 2 (Back -315)
5.1
10.0
1
51.0
0.28
0.18
Insect Screen (default)
E1
Window
NE Wall 3 (Right -45)
--
---
1
96.0
0.28
0.18
Insect Screen (default)
E2
Window
NE Wall 3 (Right -45)
--
---
1
19.2
0.28
0.18
Insect Screen (default)
D3
Window
NE Wall 3 (Right -45)
-
-
1
5.6
0.28
0.18
Insect Screen (default)
D2
Window
NE Wall 3 (Right -45)
---
---
1
21.6
0.28
0.18
Insect Screen (default)
D1
Window
SE Wall 3 (Front -135)
---
--
1
19.2
0.28
0.18
Insect Screen (default)
02
Window
SE Wall 3 (Front -135)
--
---
1
85.0
0.32
0.24
Insect Screen (default)
C1
Window
SW Wall 3 (Left -225)
--
---
1
21.5
0.28
0.18
Insect Screen (default)
05
Window
NW Wall 3 (Back -315)
---
-
1
78.0
0.32
0.24
Insect Screen (default)
E5
Window
NW Wall 3 (Back -315)
----
---
1
15.6
0.28
0.18
Insect Screen (default)
E3
Window
NW Wall 3 (Back -315)
--
--
1
44.0
0.28
0.18
Insect Screen (default)
E4
Window
NW Wall 3 (Back -315)
--
--
1
8.8
0.28
0.18
Insect Screen (default)
21
Window
NE Wall 4 (Right -45)
10.0
9.0
1
90.0
0.32
0.24
Insect Screen (default)
R2
Window
NE Wall 4 (Right -45)
2.0
8.0
1
16.0
0.28
0.18
Insect Screen (default)
R1
Window
NE Wall 4 (Right -45)
2.0
8.0
1
16.0
0.28
0.18
Insect Screen (default)
19
Window
NE Wall 4 (Right -45) r�= (-, 9.0 9.0
1
81.0
0.32
0.24
Insect Screen (default)
Q1
Window
SE Wall 4 (Front=135)i } '
6.3
2.0
i c�1
12.6
0.28
0.18
Insect Screen (default)
P3
Window
SE Wall 4 (Front -135) ll
2.0
C !J X9.0 r'
is 1(j `-18.0
0.28
0.18
Insect Screen (default)
N4
Window
"N�
SE Wall _4,(Fr6-nt-135)1 C,
4.0
f 1l):0 r )
1
40.0
0.28
0.18
Insect Screen (default)
P2
Window
SW Wall 4 (Left -225)
2.0
9.0
1
18.0
0.28
0.18
Insect Screen (default)
P1
Window
SW Wall 4 (Left -225)
2.0
9.0
1
18.0
0.28
0.18
Insect Screen (default)
N3
Window
SW Wall 4 (Left -225)
6.2
10.0
1
62.0
0.28
0.18
Insect Screen (default)
N2
Window
SW Wall 4 (Left -225)
6.2
10.0
1
62.0
0.28
0.18
Insect Screen (default)
S2
Window
SW Wall 4 (Left -225)
4.4
9.0
1
39.6
0.28
0.18
Insect Screen (default)
N1
Window
NW Wall 4 (Back -315)
4.0
10.0
1
40.0
0.28
0.18
Insect Screen (default)
18
Window
NW Wall 4 (Back -315)
7.7
10.0
1
77.0
0.32
0.24
Insect Screen (default)
S1
Window
NW Wall 4 (Back -315)
6.3
2.0
1
12.6
0.28
0.18
Insect Screen (default)
2:1
Window
NE Wall 5 (Right -45)
4.0
9.0
1
36.0
0.28
0.18
Insect Screen (default)
21 2
Window
NE Wall 5 (Right -45)
10.0
9.0
1
90.0
0.32
0.24
Insect Screen (default)
Y1
Window
NE Wall 5 (Right -45)
5.0
6.0
1
30.0
0.28
0.18
Insect Screen (default)
X1
Window
SE Wall 5 (Front -135)
7.2
2.0
1
14.4
0.28
0.18
Insect Screen (default)
V1
Window
SE Wall 5 (Front -135)
6.3
2.0
1
12.6
0.28
0.18
Insect Screen (default)
W2
Window
SW Wall 5 (Left -225)
4.9
3.0
1
14.7
0.28
0.18
Insect Screen (default)
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF113-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE C. OD
Project ame: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis Input File Name: Madison Club 23B-Kristi Hanson-15.xml
CFgRF-01
Page 8 of 16
W1
Window
SW Wall 5 (Left -225)
6.0
3.0
1
18.0
0.28
0.18
Insect Screen (default)
23
Window
SW Wall 5 (Left -225)
10.8
9.0
1
97.2
0.32
0.24
Insect Screen (default)
U2
Window
SW Wall 5 (Left -225)
8.7
3.0
1
26.1
0.28
0.18
Insect Screen (default)
U1
Window
SW Wall 5 (Left -225)
6.3
3.0
1
18.9
0.28
0.18
Insect Screen (default)
T1
Window
NW Wall 5 (Back -315)
8.9
2.0
1
17.8 1
0.28
1 0.18 1
Insect Screen (default)
DOORS
01 02 03 04
Name Side of Building Area (ft) U -factor
26 SE Wall 20.1 0.50
C(09:hl C E RTS, n c,
HERS PROVIDER
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTI*E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OD
Project Name: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 2313-Kristi Hanson-15.xml
CF•RF-01
Page 9 of 16
OVERHANGS AND FINS
01
02
03
04
05
06
07
08 09
10
11
12
13
14
Overhang
Left Fin
Right Fin
Window
Depth
Dist Up
Left
Extent
Right
Extent
Flap Ht.
Depth
Top Up DistL
Bot Up
Depth
Top Up Dist R
Bot Up
K3
10
0.1
10
10
0
0
0 0
0
0
0
0
0
17
10
0.1
10
10
0
0
0 0
0
0
0
0
0
K2
10
0.1
10
10
0
0
0 0
0
0
0
0
0
12
10
0.1
10
10
0
0
0 0
0
0
0
0
0
K32
10
0.1
10
10
0
0
0 0
0
0
0
0
0
11
10
0.1
10
10
0
0
0 0
0
0
0
0
0
J2
10
0.1
10
10
0
0
0 0
0
0
0
0
0
J1
10
0.1
10
10
0
0
0 0
0
0
0
0
0
H1
10
0.1
10
10
0
0
0 0
0
0
0
0
0
10
10
0.1
10
10
0
0
0 0
0
0
0
0
0
G2
10
0.1
x..1.0
t•1 10,w..,t .,._n0,....,,, r-0 y n
0� 0
0
0
0
0
0
G3
10A
0.1
10^
i10
L �0 1
11 0k�,,,.
0i i t 9;:=5
o
0
0
0
0
08
10
<\\`0.1
11 110„_,,6
"o
I J 01-J,
n OilH 11 '0�
0
0
0
0
0
07
18
-,%�0.1
LJ8 1=
Q18,C
ir0 in
�e•.o ti i
"t 0.—% c or)p
0
0
0
0
0
G1
18
0
418
`18—
0
i0 ~
0`"01 " Cr
0
0
0
0
0
B1
10
0.1
10
10
0
0
0 0
0
0
0
0
0
A4
10
0.1
10
10
0
0
0 0
0
0
0
0
0
A5
10
0.1
10
10
0
0
0 0
0
0
0
0
0
01
10
0.1
10
10
0
0
0 0
0
0
0
0
0
A3
10
0.1
10
10
0
0
0 0
0
0
0
0
0
Al
10
0.1
10
10
0
0
0 0
0
0
0
0
0
A2
10
0.1
10
10
0
0
0 0
0
0
0
0
0
F5
18
0.1
18
18
0
0
0 0
0
0
0
0
0
F6
18
0.1
18
18
0
0
0 0
0
0
0
0
0
06
18
0.1
18
18
0
0
0 0
0
0
0
0
0
F4
18
0.1
18
18
0
0
0 0
0
0
0
0
0
F1
18
0.1
18
18
0
0
0 0
0
0
0
0
0
21
10
0.1
10
10
0
0
0 0
0
0
0
0
0
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIF.E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 236-Kristi Hanson-15.xml
CFF -01
Page 0 of 16
R2
10
0.1
10
10 0
0
0 0
0
0
0
0
0
R1
10
0.1
10
10 0
0
0 0
0
0
0
0
0
19
10
0.1
10
10 0
0
0 0
0
0
0
0
0
Q1
10
0.1
10
10 0
0
0 0
0
0
0
0
0
P3
10
0.1
10
10 0
0
0 0
0
0
0
0
1 0
N4
10
0.1
10
10 0
0
0 0
0
0
0
0
0
P2
10
0.1
10
10 0
0
0 0
0
0
0
0
0
P1
10
0.1
10
10 0
0
0 0
0
0
0
0
0
N3
10
0.1
10
10 0
0
0 0
0
0
0
0
0
N2
10
0.1
10
10 0
0
0 0 1
0
0
0
0
0
S2
10
0.1
10
10 0
0
0 0
0
0
0
0
0
N1
10
0.1
10
10 0
0
0 0
0
0
0
0
0
18
10
0.1
10
10 0
0
0 0
0
0
0
0
0
S1
10
0.1
10
10 0
0
0 0
0
0
0
0
0
Z1
6
0.1
6
6 0
0
0 0 1
0
0
0
0
0
21 2
0
0:
,*�"-, 0
0 *� 0 f- ��
, r0 �
0 0
0
0
0
0
0
Y1
0
0
0
0;t�-0R40�+
Oil I 0'—
0
0
0
0
0
X1
10
V0.1
X10 .
1j '16
U 0
0'U j,} U 0;
0
1 0
0
0
0
V1
0
`!0
Ho F
ROS r-0' A
lrb V 1
01-1) F 0R
0
0
0
0
0
W2
6
0.1
6
6 0
0
0 0
0
0
0
0
0
W1
6
0.1
6
6 0
0
0 0
0
0
0
0
0
23
6
0.1
6
6 0
0
0 0 1
0
0
0
0
0
U2
6
0.1
6
6 0
0
0 0
0
0
0
0
0
U1
6
0.1
6
6 0
0
0 0
0
0
0
0
0
T1
10
0.1
10
10 0
0
0 0
0
0
0
0
1 0
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTI*E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 23B-Kristi Hanson-15.xml
CFF -01
Page 1 of 16
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
07
02
03
04
05
Total Cavity
Winter Design
Name
Construction Name
Surface Type
Construction Type
Framing
R -value
U -value
Assembly Layers
off nook dining
1922
206
None
0.8
No
• Cavity/ Frame: no insul. / 2x4 Top Chrd
great entry
1325
106
2x4 Top Chord of Roof Truss @ 24
0.8
No
Roof Deck: Wood Siding/sheathing/decking
Attic Roofoff nook dining
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
guest living
1407
190
None
0.8
No
• Inside Finish: Gypsum Board
Ceilings (below
Cavity/Frame: R-9.1 /2x4
R-38 Roof Attic
attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 38
0.025
Over Floor Joists: R-28.9 insul.
• Inside Finish: Gypsum Board
• Cavity/ Frame: R-21 / 2x6
• Exterior Finish: Wood
R-21 Wall (W.21.2x6.16)
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
0.066
Siding/sheathing/decking
• Cavity/ Frame: no insul. / 2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roofgreat entry
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
• Cavity / Frame: no insul. 12x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roofmasterguest
Attic Roofs
Wood Framed Ceiling
.0m ljn+_0.11-94%, wogM /
a* none
0.644
Roofing: Light Roof (Asphalt Shingle)
Attic Roofguest living
Attic Roofs
W� 9ood Framed Ceiliinn�g���1111
1
2)V�Top CA2x4 Top Chord of Roof Truss @ 24
■ iiAWO.Ci �'
,rnone
0.644
Cavity / Frame: no insul. / 2x4 Top Chrd
Roof Deck: Wood Siding/sheathing/decking
Roofing: Light Roof (Asphalt Shingle)
Cavity/ Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roof2nd master
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
SLAB FLOORS
01
02
03
04
05
06
07
Name
Zone
Area (ft2)
Perimeter (ft)
Edge Insul. R -value & Depth
Carpeted Fraction
Heated
Covered Slab
off nook dining
1922
206
None
0.8
No
Covered Slab 2
great entry
1325
106
None
0.8
No
Covered Slab 3
masterguest
1452
115
None
0.8
No
Covered Slab 4
guest living
1407
190
None
0.8
No
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04
Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage CFM50
Required Not Required Not Required -
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIFOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OD
Project Name: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis Input File Name: Madison Club 236-Kristi Hanson-15.xm1
CFO -RF -01
Page 12 of 16
WATER HEATING SYSTEMS
01
01
02 03 04 05 06
Name
System Type Distribution Type Water Heater Number of Heaters Solar Fraction (%)
DHW Sys 1 - 1/3
DHW Pipe Insulation, All Lines DHW Heater 1 3 .0%
WATER HEATERS
01
02
03
04
05
06
07
08
Name
Heater Element Type
Tank Type
Tank Volume
(gal)
Energy Factor or
Efficiency
Input Rating
Tank Exterior
Insulation
R -value
Standby Loss
(Fraction)
DHW Heater 1
Natural Gas
Small Storage
50
0.66
40000-Btu/hr
0
0
WATER HEATING - HERS VERIFICATION
01
02
03
04
05
06
07
Name
Pipe Insulation
Parallel Piping.
CRTpact Distribution
Point -of Use
Recirculation
Control
Central DHW
Distribution
DHWSys 1-1/3
--+ f
HVAC Fan 1
Air Distribution System 1
HVAC 2 grt enry2
Other Heating and Cooling
System
Heating Component 2
+C\ 7% 1'+....... i" t i I I ti.,.— i t 9 t 1 f A V I? #7 11 t€ 1 1V..-- ^
SPACE CONDITIONING SYSTEMS L-1 la M Ic M tib r^1 i Art fl*N l= C>
01
ti 02
Q.3 w v
.04y — w v
05
06
SC Sys Name
System Type
Heating Unit Name
Cooling Unit Name
Fan Name
Distribution Name
HVAC 1 off kit nookl
Other Heating and Cooling
System
Heating Component 1
Cooling Component 1
HVAC Fan 1
Air Distribution System 1
HVAC 2 grt enry2
Other Heating and Cooling
System
Heating Component 2
Cooling Component 2
HVAC Fan 2
Air Distribution System 2
HVAC 3 mstr gest3
Other Heating and Cooling
System
Heating Component 3
Cooling Component 3
HVAC Fan 3
Air Distribution System 3
HVAC 4 gest liv4
Other Heating and Cooling
System
Heating Component 4
Cooling Component 4
HVAC Fan 4
Air Distribution System 4
HVAC 5 2nd5
Other Heating and Cooling
System
Heating Component 5
Cooling Component 5
HVAC Fan 5
Air Distribution System 5
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIF.E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: Madison Club 23B Ca culation DatelTime: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 2313-Kristi Hanson-15.xml
CFlRF-01
Page 13 of 16
HVAC - HEATING UNIT TYPES
01
02
01
02
03
Name
Type
Efficiency
Heating Component 1
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 2
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 3
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 4
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 5
CntrlFurnace - Fuel -fired central furnace
80 AFUE
HVAC - COOLING UNIT TYPES
01
02
03 04
05
06
07
Verified Airflow Airflow Target
Verified EER
Efficiency
Verified Refrigerant
Charge
Multi -speed
Required 350
Name
System Type
EER SEER
Zonally Controlled
Compressor
HERS Verification
Cooling Component 1
SplitAirCond
13
16.5
Not Zonal
Single Speed
Cooling Component
1 -hers -cool
Cooling Component 2
SplitAirCond
13
_ VW"
16.5
r%0% fft
Not Zonal
a
Single Speed
Cooling Component
1 -hers -cool
Cooling Component 3
.r1
SplitAirCond,ft'Lad
Required
1#" E:r%
16.5
/
No Zon
Single Speed
CoolingComponent
.
�
1 -hers -cool
Cooling Component4
SplitAirCond
13'
"`-
16.5
r�
NohZonal;
Single Speed
Cooling Component
1
�— y +
-hers -cool
Cooling Component 5
SplitAirCond
13
16.5
Not Zonal
Single Speed
Cooling Component
1 -hers -cool
HVAC COOLING - HERS VERIFICATION
01
02 03
04
05
06
Name
Verified Airflow Airflow Target
Verified EER
Verified SEER
Verified Refrigerant
Charge
Cooling Component 1 -hers -cool
Required 350
Required
Required
Required
Cooling Component 2 -hers -cool
Required 350
Required
Required
Required
Cooling Component 3 -hers -cool
Required 350
Required
Required
Required
Cooling Component 4 -hers -cool
Required 350
Required
Required
Required
Cooling Component 5 -hers -cool
Required 350
Required
Required
Required
Registration Number: 215-N63439676-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIFOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: Madison Club 23B Ca culation Date/Time: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 2313-Kristi Hanson-15.xml
CFtF-01
Page 4 of 16
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
Name
Type
Duct Leakage
Insulation R -value
Duct Location
Bypass Duct
HERS Verification
Air Distribution System 1
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
1 -hers -dist
Air Distribution System 2
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
2 -hers -dist
Air Distribution System 3
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
3 -hers -dist
Air Distribution System 4
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
4 -hers -dist
Air Distribution System 5
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
5 -hers -dist
HVAC DISTRIBUTION - HERS VERIFICATION
01
02
03
04
05
06
07
08
Name
Duct Leakage
Verification
Duct Leakage
Target (%)
Verified Duct
Location --i f�Design
Verified Duct
(I
Buried
Ducts
Deeply Buried
Ducts
Low -leakage
Air Handler
Air Distribution System 1 -hers -dist
Require62
X6.0
Not Required
NNot,Required (
Not F:equired
Not Required
---
Air Distribution System 2 -hers -dist
Requited '*
�6.Of .�
..:Not Required U
kNot'Required U
1.i Not. Required
Not Required
--
Air Distribution System 3 -hers -dist
Required
1=11 AS
Nod=RequiredC
N"oi Required
N f Required
Not Required
-
Air Distribution System 4 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
—
Air Distribution System 5 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
—
HVAC -FAN SYSTEMS
01
02
03
04
Name
Type
Fan Power (Watts/CFM)
HERS Verification
HVAC Fan 1
Single Speed PSC Furnace Fan
0.58
HVAC Fan 1 -hers -fan
HVAC Fan 2
Single Speed PSC Furnace Fan
0.58
HVAC Fan 2 -hers -fan
HVAC Fan 3
Single Speed PSC Furnace Fan
0.58
HVAC Fan 3 -hers -fan
HVAC Fan 4
Single Speed PSC Furnace Fan
0.58
HVAC Fan 4 -hers -fan
HVAC Fan 5
Single Speed PSC Furnace Fan
0.58
HVAC Fan 5 -hers -fan
HVAC FAN SYSTEMS - HERS VERIFICATION
01 02 03
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIFOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE *OD
Project Name: Madison Club 23B Ca culation DatelTime: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 236-Kristi Hanson-15.xmi
CFF -01
Page 5 of 16
Name
Verified Fan Watt Draw
Required Fan Efficiency (Watts/CFM)
HVAC Fan 1 -hers -fan
Required
0.58
HVAC Fan 2 -hers -fan
Required
0.58
HVAC Fan 3 -hers -fan
Required
0.58
HVAC Fan 4 -hers -fan
Required
0.58
HVAC Fan 5 -hers -fan
Required
0.58
IAQ (Indoor Air Quality) FANS
01
02
03
04
05
06
Dwelling Unit
IAQ CFM
IAQ Watts/CFM
IAQ Fan Type
IAQ Recovery
Effectiveness(%)
HERS Verification
SFam IAQVentRpt
197.97
0.25
Default
0
Required
COOLING VENTILATION
01
02
03
04
05
Name
Cooling Vent CFM
Cooling Vent Watts/CFM
Total Watts
Number of Fans
WH Fan 1
j6r1"J '
t -` r0'0:52459-''
32
1
WH Fan 2
61
('r ° 0.52454-'1
32
1
WH Fan 3
'�!1 61-x` kJ
u '.s 0.52459 ::'* Y
to s t t-32
1
WH Fan 4
61M t_— K
e 0:52459 V t
L K 32
1
WH Fan 5
61
0.52459
32
1
PROJECT NOTES
The Madison Club 23B
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
CERTIF0 E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE rfOD
Project Name: Madison Club 23B Ca culation DatefTime: 07:49, Tue, Feb 02, 2016
Calculation Description: Title 24 Analysis
Input File Name: Madison Club 23B-Kristi Hanson-15.xml
CFtF-01
Page 6 of 16
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Tim Scott
Company:
Signature Date:
Scott Design and Title 24, Inc.
2016-02-02 08:02:09
Address:
CEA/HERS Certification Identification (If applicable):
77085 Michigan Drive
City/State/Zip:
Phone:
Palm Desert, CA 92211
760-200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency,for approval,with this building permit application.
Responsible Designer Name:Responsible
I I�ti';
`Designer Signature:..
Tim Scott.L tUt
Company:
Date. Signed: �
2016 02-0208:0
Scott Design and Title 24, Inc.
:09
Address:
License:
77085 Michigan Drive
NA
City/State/Zip:
Phone:
Palm Desert, CA 92211
760-200-4780
Digitally signed by CaICERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration Provider responsibility for the accuracy of the
information.
Registration Number: 215-N6343967B-000000000-0000 Registration Date/Time: 2016-02-02 08:02:09 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2016-02-02 07:51:29
0
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Madison Club 238
Building Type 10 Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
2/2/2016
Project Address
81-382 Amundson Ave. La Quints
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
7, 797
Addition
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity ftz
Special Features Status
Roof Wood Framed Attic
R38 6,306
New
Wall Wood Framed
R 21 9,450
New
Door Opaque Door
- no insulation 20
New
Slab Unheated Slab -on -Grade
- no insulation 6,106
Perim = 617'
New
Demising Wood Framed
R 13 3,680
New
FENESTRATION
Orientation Area(ft)
Total Area: 3,306 Glazin Percentage: 42.4 %
U -Fac SHGC Overhang Sidefins
New/Altered Average U -Factor: 0.30
Exterior Shades Status
Right (NE) 255.0
0.280
0.18 10.0
none
Bug Screen New
Right (NE) 287.0
0.320
0.24 10.0
none
Bug Screen New
Front (SE) 309.1
0.280
0.18 10.0
none
Bug Screen New
Left (SW) 411.9
0.280
0.18 10.0
none
Bug Screen New
Left (SW) 255.0
0.320
0.24 10.0
none
Bug Screen New
Rear (NW) 403.0
0.320
0.24 18.0
none
Bug Screen
New
Rear (NM 214.3
0.280
0.18 18.0
none
Bug Screen
New
Right (NE) 292.4
0.280
0.18 none
none
Bug Screen
New
Front (SE) 85.0
0.320
0.24 10.0
none
Bug Screen
New
Front (SE) 92.2
0.280
0.18 none
none
Bug Screen
New
Front (SE) 85.0
0.320
0.24 none
none
Bug Screen
New
Left (SW) 21.5
0.280
0.18 none
none
Bug Screen
New
Rear (NM 78.0
0.320
0.24 none
none
Bug Screen New
Rear (NM 68.4
0.280
0.18 none
none
Bug Screen
New
HVAC SYSTEMS
Qty. Heating
Min. Eff
Cooling
Min. Eff
Thermostat Status
1 Central Furnace
80% AFUE
Split Air Conditioner
16.5 SEER
Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner
16.5 SEER
Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner
16.5 SEER
Setback
New
HVAC DISTRIBUTION
Location Heating
Cooling Duct Location
Duct
R -Value Status
HVAC 1 off kit nook Ducted
Ducted Attic
8.0
New
HVAC 2 grt enry Ducted
Ducted Attic
8.0
New
HVAC 3 mstr gest Ducted
Ducted Attic
8.0
New
WATER HEATING
Qty. Type
Gallons Min. Eff
Distribution Status
3 Small Storage Gas
50
0.66
All Pipes Ins
New
EnemyPro6.7 by Ene Soft User Number: 6712
RunCode: 2016-02-02T07:52:38
/D:
Pae 19 of 49
17,
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Madison Club 23B
Building Type m Single Family ❑ Addition Alone
O Multi Family O Existing+ Addition/Alteration
Date
2/2/2016
Project Address
81-382 Amundson Ave. La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
7,797
Addition
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity (ft) Special Features Status
FENESTRATION
Orientation Area(ft)
Total Area: 3,306 Glazing Percentage: 42.4%1New/Altered Avera a U -Factor: 0.30
U -Fac SHGC Overhang Sidefins Exterior Shades Status
Rear (NlM 70.4
0.280
0.18 10.0 none Bug Screen New
Rear (NM 77.0
0.320
0.24 10.0 none Bug Screen New
Right (NE) 36.0
0.280
0.18 6.0 none Bug Screen New
Right (NE) 90.0
0.320
0.24 none none Bug Screen New
Left (SlM 77.7
0.280
0.18 6.0 none Bug Screen
New
Left (SlM 97.2
0.320
0.24 6.0 none Bug Screen
New
HVAC SYSTEMS
Qty. Heating
Min. Eff
Cooling Min. Eff Thermostat Status
1 Central Furnace
80% AFUE
Split Air Conditioner 16.5 SEER Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner 16.5 SEER Setback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value Status
HVAC 4 gest liv Ducted
Ducted Attic 8.0
New
HVAC 5 2nd Ducted
Ducted Attic 8.0
New
WATER HEATING
Qty. Type
Gallons Min. Eff Distribution Status
R
EnerqyPro 6.7 by EnerqySoft User Number: 6712
RunCode: 2016-02-02707:52:38 /D:
Page 20 of 49
4
2013 Low -Rise Residential Mandatory Measures Summary
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the
com liance a roach used. Exceptions may apply, Review the respective code section or more information.
Bung Envelope Measures:
§I 10.6(a)1:
Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§ 110.6(a)5:
Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of § 10-111 (a).
§ 110.7:
Exterior doors and windows are weatherstripped; all joints and penetrations are caulked and sealed.
§ 1 10.8(a):
Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R.
§ 110. 8(i):
The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of § 110.8(i) when the
installation of a cool roof is specified on the CF I R.
§1 10.80):
A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CFI R.
Minimum R-30 insulation in wood -frame ceiling; or the weighted average U -factor shall not exceed 0.031. Minimum R-19 in a
§ 150.0(a):
rafter roof alteration. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The
attic access shall be gasketed to prevent air leakage.
§I50.0(b):
Loose fill insulation shall conform with manufacturer's installed design labeled R -value.
§I50.0(c):
Minimum R-13 insulation in 2x4 inch wood framing wall or have a U -factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U -
factor).
§ 150.0(d):
Minimum R-19 insulation in raised wood -frame floor or 0.037 maximum U -factor.
In Climate Zones 14 and 16 a Class 11 vapor retarder shall be installed on the conditioned space side of all insulation in all exterior
§I50.0(g)1:
walls, vented attics and unvented attics with air -permeable insulation.
In Climate Zones 1-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class 11
§ 150.0(g)2:
vapor retarder.
In a building having a controlled ventilation crawl space, a Class I or Class II vapor retarder shall be placed over the earth floor of
§I50.0(g)3:
the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section
150.0(d).
§ 150.0(1):
Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%;
have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration;
and when installed as part of a heated slab Floor meets the requirements of 1$110.8
150.0 (q)'
Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U -
factor of 0.58; or the weighted average U -factor of all fenestration shall not exceed 0.58.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
§ I50.0(e)I A:
Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§ 150.0(e) I B:
Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a readily accessible, operable, and tight -fitting damper or a combustion -air control device.
§I50.0(e)IC:
Masonry or factory -built fireplaces have a flue damper with a readily accessible control.
§I50.0(e)2:
Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside
of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§I 10.0-§110.3:
HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified to the Energy Commission.
§1 10.3(c)5:
Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation
valve, and recirculation loop connection requirements of § 1 10.3(c)5.
Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appli-
§ 110.5:
ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool
ands a heaters.
§I50.0(h)1:
Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified
in §150.0(h)2.
§ 150.0(h)3A:
Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any
dryer vent.
§ 150.0(i):
Heating systems are equipped with thermostats that meet the setback requirements of § 110.2(c).
§ 150.00)1 A:
Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
150.00)1 B:
Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, have R-12 external
insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the tank.
For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage
tank, all piping with a nominal diameter of 3/4 inch or larger, all piping associated with a domestic hot water recirculation system
§150.00)2A:
regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and
all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3-
A.
§ I50.00)2B:
All domestic hot water pipes that are buried below grade must be installed in a water proof and non -crushable casing or sleeve
that allows for installation, removal, and replacement of the enclosed pipe and insulation.
4
4
2013 Low -Rise Residential Mandatory Measures Summary
§ I50.00)2C:
Pipe for cooling system lines shall be insulated as specified in § I50.00)2A. Piping insulation for steam and hydronic heating
systems or hot waters stems with pressure > 15 psig shall meet the requirements in TABLE 120.3-A.
150.00)3:
Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For
§I50.00)3A:
example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or
painted with coating that is water retardant and provides shielding from solar radiation that degrades the material.
Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class 1
§150.00)36:
or Class 11 vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class II vapor
retarder.
Systems using gas or propane water heaters to serve individual dwelling units shall include: a 120V electrical receptacle within 3
feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the
§ 150.0(n)1:
space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed
water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000
Btu/hr.
§I50.0(n)2:
Recirculating loops serving multiple dwelling units shall meet the requirements of §1 10.3(c)5.
§I50.0(n)3:
Solar water -heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC)
or by a testing agency approved by the Executive Director.
Ducts and Fans Measures:
All air -distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC §601.0, §602.0,
§603.0, §604.0, §605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition.
Supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC
§605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed
§I50.0(m)1:
with mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181 A, or UL 181 B or
aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than 'A inch, the
combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums
defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying
conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms
shall not be compressed to cause reductions in the cross-sectional area of the ducts.
Factory -Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; joints
§ I50.0(m)2:
and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is
used in combination with mastic and draw bands.
§I50.0(m)3-6:
Field -Fabricated Duct Systems shall comply with requirements for: pressure -sensitive tapes, mastics, sealants, and other
requirements specified for duct construction; duct insulation R -value ratings; duct insulation thickness; and duct labeling.
§ 150.0(m)7:
All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic
dampers.
§ I50.0(m)8:
Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers
except combustion inlet and outlet air openings and elevator shaft vents.
Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not
§ 150.0(m)9:
limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum,
sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is
water retardant and provides shielding from solar radiation.
§I50.0(m)10:
Flexible ducts cannot have porous inner cores.
When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be
§150.0(m)11:
sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference
Residential Appendix RA3.
Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal
§I50.0(m)12:
conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of
§150.0(m) 12.
Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the
placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The
§ 150.0(m)13:
space conditioning system must also demonstrate airflow > 350 CFM per ton of nominal cooling capacity through the return
grilles, and an air -handling unit fan efficacy:5 0.58 W/CFM as confirmed by field verification and diagnostic testing, in
accordance with Reference Residential Appendix RA3.
Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode,
§ 150.0(m)15:
an airflow from the dwelling, through the air handler fan and delivered to the dwelling, of>_ 350 CFM per ton of nominal cooling
capacity, and operating at an air -handling unit fan efficacy of:5 0.58 W/CFM as confirmed by field verification and diagnostic
testing, in accordance with Reference Residential Appendix RA3.
All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of
§ 150.0(0):
central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the
Whole Building Ventilation.
§I50.0(o)IA:
Whole Building Ventilation airflow shall be confirmed through field verification and diagnostic testing, in accordance with
Reference Residential Appendix RA3.
Pool and Spa Heating Systems and Equipment Measures:
Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
§ 110.4(a):
Regulations; an on-off switch mounted outside of the heater that allows shutting off the heater without adjusting the thermostat
setting; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating.
2013 Low -Rise Residential Mandatory Measures Summary
§ 110.4(b)1: Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction
and return lines, or built-up connections for future solar heating.
§ 110.4(b)2: Outdoor pools or spas that have a heat pump or gas heater shall have a cover.
§ 110.4(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro -
rammed to run only during off-peak electric demand periods.
§110.5: Natural gas pool and spa heaters shall not have a continuous burning pilot light.
§ I50.0(p): Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements.
Lighting Measures:
§110.9: All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of §110.9.
§I50.0(k)IA: Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with §I50.0(k) in accordance with TABLE
150.0-A or TABLE 150.0-B, as applicable.
§150.0(k)1B: When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply
with the applicable provisions of § 150.0(k).
The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with
§ I50.0(k)I C: § I30.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has
been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180
watts of low efficacy lighting er electrical box.
§ I50.0(k)1 D: Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz.
Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no
§I50.0(k)IE: more than 5 watts of power per luminaire or exhaust fan as determined in accordance with §130.0(c). Night lights do not need to
be controlled by vacancy sensors.
§ 150.0(k) I F: Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable
requirements of § 150.0(k).
§ 150.0(k)2A: High efficacy luminaires must be switched separately from low efficacy luminaires.
§I50.0(k)2B: Exhaust fans shall be switched separately from lighting systems.
§I50.0(k)2C: Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF.
§I50.0(k)2D: Controls and equipment are installed in accordance with manufacturer's instructions.
I50.0(k)2E: No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with § 150.0(k).
Am[§
§I50.0(k)2F: Lighting controls comply with applicable requirements of §110.9.
An Energy Management Control System (FMCS) may be used to comply with dimmer requirements if. it functions as a dimmer
§ 150.0(k)2G: according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements of § 130.5; and all other
requirements in §150.0(k)2.
An Energy Management Control System (EMCS) may be used to comply with vacancy sensor requirements of § I50.0(k) if: it
§ I50.0(k)2H: functions as a vacancy sensor according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements
of ' 130.5; and all other requirements in § 150.0(k)2.
§I50.0(k)2I: A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the
functionality of a dimmer according to §110.9, and complies with all other applicable requirements in §150.0(k)2.
§ I50.0(k)3A: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only
§ 150.0(k)3B: the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are
considered kitchen li htin if they are not separately switched from kitchen lighting.
§ 150.0(k)4: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated
cabinet.
§ I50.0(k)5: A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom
shall be high efficacy or controlled by vacancy sensors.
§ I50.0(k)6: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§ 150.0(k)7: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high
efficacy, or shall be controlled by either dimmers or vacancy sensors.
Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other
nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0
CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing
§ I50.0(k)8: and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and
allow ballast maintenance and replacement without requiring cutting holes in the ceiling.
For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with § 150.0(k), the ballasts
shall be certified to the Energy Commission to comply with the applicable requirements in §110.9.
For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the
same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and
§ 150.0(k)9A: ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically
reactivates the motion sensor within 6 hours; and
iii. Controlled by one of the following methods:
4
2013 Low -Rise Residential Mandatory Measures Summary
�7_
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is
programmed to automatically turn the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of
an astronomical time clock in accordance with §110.9; meets the Installation Certification requirements in §130.4; meets the
requirements for an EMCS in § 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically turn the outdoor lighting OFF during daylight hours.
For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor
lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
§ I50.0(k)9B:
following requirements:
i. Shall comply with §I50.0(k)9A; or
ii. Shall comply with the applicable requirements in §110.9, §130.0, §130.2, §130.4, §140.7 and §141.0.
§ I50.0(k)9C:
For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by § 150.0(k)9B or 150.0(k)9D
shall comply with the applicable requirements in § 110.9, § 130.0, § 130.2, § 130.4, § 140.7 and § 141.0.
§ 150.0(k)9D:
Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply
with the applicable requirements in § 110.9, § 130.0, § 130.2, § 130.4, § 140.7 and § 141.0.
§I50.0(k)10:
Internally illuminated address signs shall comply with §140.8; or shall consume no more than 5 watts of power as determined
according to § 130.0(c).
§ I50.0(k)11:
Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for
nonresidential garages in § 110.9, §130.0, §130.1, §130.4, §140.6, and §141.0.
In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of
§ I 50.0(k) I 2A:
the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20
percent of the floor area, permanently installed lighting in that building shall:
§I50.0(k)1213:
i. Comply with the applicable requirements in §110.9, §130.0, §130.1, §140.6 and §141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
ingress and egress.
Solar Ready Buildings:
Single family residences located in subdivisions with ten or more single family residences and where the application for a
§110.10(a)l:
tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January 1, 2014,
shall comply with the requirements of § 110.10 b through § 110.10(e).
§110.I0(a)2:
Low-rise multi -family buildin s shall comply with the requirements of §110.10(b) through §I 10.10(d).
The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway, smoke
ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a
local jurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than
80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for
§ 110.10(b)l :
buildings with roof areas greater than 10,000 square feet.
For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less
than 250 square feet. For low-rise multi -family buildings the solar zone shall be located on the roof or overhang of the building or
on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the
building project and have a total area no less than 15 percent of the total roof area of the building excluding any skylight area.
§ 110.10(b)2:
All sections of the solar zone located on steep -sloped roofs shall be oriented between 110 degrees and 270 degrees of true north.
§ 1 10.10(b)3A:
No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be
located in the solar zone.
Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice
§ 1 10.10(b)3B:
the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the
horizontal projection of the nearest point of the solar zone measured in the vertical plane.
§ 110.10(b)4:
For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly
indicated on the construction documents.
The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit
§ 110.10(c):
from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water -heating
system.
§ 110.10(d):
A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through § 110.10(c)
shall be provided to the occupant.
§1 10.10(e)l:
The main electrical service panel shall have a minimum busbar rating of 200 amps.
The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a
§ 1 10.10(e)2:
future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or
main circuit location, and permanently marked as "For Future Solar Electric'.
�7_
L_
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
adison Club 23B
Date
2/2/2016
System Name
HVAC 1 off kit nook
Floor Area
1,922
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 3,546
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 288
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 110,000
34,461
3,399 753
35,694
Total Output Btuh 110,000
0
Output Btuh/s ft 57.2
1,624
1,363
Cooling System
0
0
Output per System 58,000
12,652
2,740 288
13,917
Total Output Btuh 58,000
1,489
6,139
-1,489
Total Output Tons 4.8
1,624
1,363
Total Output Btuh/s ft 30.2
Total Output s ft/Ton 397.7
51,850
1 50,847
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
carrier 24ANB760/58MVB110-
36,824 15,648
110,000
Airflow cfm/s ft
1.04
Airflow cfm/Ton
413.8
Outside Air %
14.4%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
I TIME OF SYSTEM PEAK
36,824 15,648
Aug 3 PM
110,000
Jan 1 AM
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 65 OF
O
Outside Air
288 cfm Supply Fan
2,000 cfm
71 OF
66 OF 117 OF
Heating Coil
�I�
117 OF
ROOM
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F 77/66°F 77/66°F 60/59°F
•
C!
Outside Air
288 cfm Supply Fan Cooling Coil
AL 2,000 cfm
71/63°F
:0.1 4
61 / 59 OF
69.3% ROOM
70/63°F
1
EnergyPro 6.7 by EnergySoff User Number: 6712 Run Code: 2016-02-02707:52:38 /D: Page 25 of 49
r
i�
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
adison Club 23B
Date
2/2/2016
System Name
HVAC 2 grt enry
Floor Area
1,325
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,832
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 199
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 110,000
25,063
2,343 473
23,665
Total Output Btuh 110,000
0
Output Btuh/s ft 83.0
1,181
903
Cooling System
0
0
Output per System 58,000
8,766
3,271 199
9,640
Total Output Btuh 58,000
1489
1,181
37,681 5,615
-1,489
Total Output Tons 4.8
903
Total Output Btuh/s ft 43.8
Total Output s ft/Ton 274.1
33,623
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24ANB760/58MVB110
39,975 10,272
110,000
Airflow cfm/s ft 1.51
Airflow cfm/Ton
413.8
Outside Air %
9.9%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
1 39,975 10,272
Aug 3 PM
110,000
Jan 1 AM
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 67 OF
-
Air
199 cfm Supply Fan
2,000 cfm
72 OF
68 OF 119 OF
PJOutside
Heating Coil
119 °F
ROOM Lfl
72 OF
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak
112/78°F 75/63°F 75/63°F 57/56°F
•
Outside Air
199 cfm Supply I Fan
Cooling Coil
2,000 cfm
71 / 61 OF
57 / 56 OF
60.3% ROOM
70 / 61 OF
EnergyPro 6.7 by EnergySoff
User Number: 6712 Run Code: 2016-02-02707:52:38 /D: Page 26 of 49
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
adison Club 23B
Date
2/2/2016
System Name
HVAC 3 mstr gest
Floor Area
1,452
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,506
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 218
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 110,000
20,207
2,568 399
19,846
Total Output Btuh 110,000
0
Output Btuhls ft 75.8
952
758
Cooling System
0
0
Output per System 58,000
9,631
3,426 218
10,580
Total Output Btuh 58,000
1489
5,994
-1,489
Total Output Tons 4.8
1 952
758
Total Output Btuh/s ft 39.9
Total Output s ft/Ton 300.4
1 33,231
F 30,452
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24AN6760/58MVB110
39,853 10,676
110,000
Airflow cfm/s ft
1.38
Airflow cfm/Ton
413.8
Outside Air %
10.9%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
1 TIME OF SYSTEM PEAK
39,853 10,676 110,000
Aug 3 PM Jan 1 AM
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF 67 OF
0
Outside Air
218 cfm Supply Fan
2,000 cfm
72 OF
67 OF 119 OF
-
10
Heating Coil 119 OF
ROOM
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling
Peak
112/78°F 75/63°F
Outside Air
218 cfm
70/61 OF
76/64°F 57/56°F
Supply Fan Cooling Coil
2,000 cfm
57 / 56 OF
61.2% ROOM
70/61 OF
En. gyPro 6.7 by EnergySoff User Number: 6712 RunCode: 2016-02-02T07:52:38
/D: Page 27 of 49
�ACYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Madison Club 23B
Date
2/2/2016
System Name
HVAC 4 gest liv
Floor Area
1,407
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,822
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 211
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 110,000
24,438
2,488 561
27,790
Total Output Btuh 110,000
0
Output Btuh/s ft 78.2
1,151
1,061
Cooling System
0
0
Output per System 58,000
9,312
3,363 211
10,220
Total Output Btuh 58,000
1,489
5,852
-1,489
Total Output Tons 4.8
1,151
1,061
Total Output Btuh/s ft 41.2
Total Output s ft/Ton 291.1
1 37,542
38,643
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24ANB760/58MVB110
39,929 10,525
110,000
Airflow cfm/s ft
1.42
Airflow cfm/Ton
413.8
Outside Air %
10.6%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
39,929 1 0, 525J
Aug 3 MI
110,000
F Jan 1 AM
Outside Air cfm/s ft 0.15
ote: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF 67 OF
Outside Air
211 cfm Supply Fan
2,000 cfm
72 OF
14 10C
67 OF 119 OF
Heating Coil 119 OF
ROOM
72 OF
14 U-1— LU
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling
Peak
112/78°F 75/63°F 76/64°F 57/56°F
Outside Air Ar
211 cfm Supply Fan Cooling Coil
2,000 cfm
71 / 61 OF
°
57 / 56 F
61.0% ROOM
70/ 61 OF
EnergyP, 6.7 by EnergySoft
User Number: 6712 Run Code: 20 1 6-02-0 2 70 7:52:38
/D: Page 28 of 49
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
adison Club 23B
Date
2/2/2016
System Name
HVAC 5 2nd
Floor Area
1,691
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,660
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 254
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 110,000
20,877
2,991 361
17,673
Total Output Btuh 110,000
0
Output Btuh/s ft 65.1
984
675
Cooling System
0
0
Output per System 58,000
11,213
3,599 254
12,332
Total Output Btuh 58,000
1,489
9841
1 35,546
6,590
-1,489
Total Output Tons 4.8
675
Total Output Btuh/s ft 34.3
Total Output s ft/Ton 349.9
29,865
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24ANB760/58MVB110 39,826
11,314
110,000
Airflow cfm/s ft
1.18
Airflow cfm/Ton 413.8
Outside Air %
12.7%
Total Adjusted System Output 39,826
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
11,314
Aug 3 PM
110,000
Jan 1 AM
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of HeatingPeak
26 °F 66 OF
Outside Air
254 cfm Supply Fan
2,000 cfm
72 OF
-
67 OF 118 OF
—► �
J—I -- E
Heating Coil 118 °F
ROOM
72 °F
4 -I=u 4
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112 / 78 OF 76 / 64
Outside Air
254 cfm
70/62°F
OF 76 / 65 OF 58 / 57 OF
Supply I Fan
Cooling Coil 58 / 57 OF
2,000 cfm
63.2% ROOM
70/62°F
EnergyPro 6.7 by EnergySoft
User Number: 6712 RunCode: 2016-02-02707:52:38 ID:
Page 29 of 49
•
•
ROOM HEATING PEAK LOADS
Project Name
Madison Club 238
Date
2/2/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Office Kitchen Nook & Dining
Floor Area 1,922.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT °F
_
_
=
_
=
=
=
=
=
c
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof Attic
431.0
0.0260
46
515
R-21 Wall (W 21.2x6.16)
2,137.8
0.0690
46
6,785
FIX door window slider. 28.18
584.1
0.2800
46
7,523
OPP window door slider. 32.24
570.0
0.3200
46
8,390
Wood Door
20.1
0.5000
46
462
Slab -On -Grade
perim = 206.0
0.7300
46
6,917
'R-13 Wall
856.0
0.1020
0
0
Items shown with an asterisk (') denote conduction
Infiltration: 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,922 X
Area
another room
9.00 X 0.361
Height ACH
Page Total
/60] X
AT
30,594
_ 5,099
TOTAL HOURLY HEAT LOSS FOR ROOM 35,694
EnergyPro 6.7 by EnergySoft User Number: 6712 Run Code: 2016-02-02T07:52:38 ID: Page 35 of 49
C.
ROOM HEATING PEAK LOADS
Project Name
Madison Club 238
Date
2/2/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great Room and Entry
Floor Area 1,325.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT *F
c
_
_
=
c
c
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof Attic
1,325.0
X
0.0260
46
1,585
R-21 Wall (W.21.2x6.16)
1,480.0
X
0.0690
46
4,698
FIX door window slider. 28.18
470.0
X
0.2800
46
6,054
OPP window door slider. 32.24
289.0
X
0.3200
46
4,254
Slab -On -Grade
perim = 106.0
X
X
X
0.7300
46
3,559
'R-13 Wall
511.0
0.1020
0
0
X
X
X
X
X
X
X
X
X
X
I
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to another room
9.00 X 0.361
Ceiling Height ACH
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X
Schedule Air Sensible
Fraction
through an interior surface
1.064 X 1,325 X
Area
Page Total
/60] X
AT
20,149
= 3,515
` TOTAL HOURLY HEAT LOSS FOR ROOM 23,665
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-02-02707:52:38 /D: Page 36 of 49
I
ROOM HEATING PEAK LOADS
Project Name
Madison Club 23B
Date
2/2/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Master Bedroom
Floor Area 1,452.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
1.064
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT *F
=
c
_
_
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof Attic
1,452.0
0.0260
46
1,737
R-21 Wall (W 21.2x6.16)
1,498.5
0.0690
46
4,756
FIX door window slider. 28.18
251.5
0.2800
46
3,239
OPP window door slider. 32.24
163.0
0.3200
46
2,399
Slab -On -Grade
pen .m = 115.0
0.7300
46
3,862
"R-13 Wall
712.0
0.1020
0
0
I
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X
Schedule Air Sensible
Fraction
through an interior surface
X 1,452 X
Area
another room
9.00 X 0.361
Height ACH
Page Total
/60] X
AT
15,993
= 3,852
TOTAL HOURLY HEAT LOSS FOR ROOM 19,846
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 201 6-02-02 70 7:52:38 ID: Page 37 of 49
•
c
ROOM HEATING PEAK LOADS
Project Name
Madison Club 238
Date
2/2/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Living Area
Floor Area 1,407.0 ft'
Indoor Dry Bulb Temperature 72 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT OF
0
_
=
_
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof Attic
1,407.0
X
X
0.0260
46
1,683
R-21 Wall (W.21.2x6.16)
2,449.2
0.0690
46
7,774
OPP window door slider .32.24
248.0
X
0.3200
46
3,651
FIX door window slider. 28.18
354.8
X
X
X
X
0.2800
46
4,570
Slab -On -Grade
pen .m = 190.0
0.7300
46
6,380
"R-13 Wall
745.0
0.1020
0
0
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,407 X
Area
to another room
9.00 X 0.361
Ceiling Height ACH
Page Total
/60] X
AT
24,057
_ 3,733
TOTAL HOURLY HEAT LOSS FOR ROOM 27,790
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-02-02707:52:38 ID: Page 38 of 49
C
1�
ROOM HEATING PEAK LOADS
Project Name
Madison Club 23B
Date
2/2/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name 2nd Floor Master Bedroom
Floor Area 1, 691.0 ft'
Indoor Dry Bulb Temperature 72 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
AT *F
X 46
X 46
X 46
X 46
X 0
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Page Total
/60] X
AT
=
=
c
_
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 Roof Attic
1,691.0
0.0260
2,022
R-21 Wall (W.21.2x6.16)
1,884.3
0.0690
5,981
FIX door window slider. 28.18
188.5
0.2800
2,428
OPP window door slider .32.24
187.2
0.3200
2,756
'R-13 Wall
856.0
0.1020
0
Items shown with an asterisk (') denote conduction
Infiltration: 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,691 X
Area
another room
9.00 X 0.361
Height ACH
13,187
= 4,487
TOTAL HOURLY HEAT LOSS FOR ROOM 17,673
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-02.02T07:52:38 ID: Page 39 of 49
1�
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Madison Club 238 1 2/2/2016
ROOM INFORMATION DESIGN CONDITIONS
Room Name
Office Kitchen Nook & Dining IOutdoor
Dry Bulb Temperature
112 OF
Floor Area
1, 922.0 ftZ
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature
70 OF I
Outdoor Daily Range:
34 OF
Opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
Wood Door
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
*R-13 Wall
Orientation
(M
(NE)
(SE)
(SE)
(SIM
(NW)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
431.0
0.0260
56.0
493.0
0.0690
29.0
334.9
0.0690
31.0
20.1
0.5000
31.0
1,148.7
0.0690
31.0
161.2
0.0690
30.2
856.0
0.1020
0.0
16.4
121.0
15.3
0.0
20.8
16.0
12.3
0.0
Page Total
Items shown with an asterisk (*) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fanpctratinn
K3
17
K2
12
K3
11
J2
J1
H1
nriantatinn
(NE)
(NE)
(NE)
(SE)
(SIM
(SIM
(SIM
(SM
(SIM
Shaded Unshaded
Btu/hr
1 2,4571
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
12.3
110.0
18.1
0.0
15.3
116.0
23.0
0.0
12.3
113.0
18.1
109.0
12.3
0.0
16.4
110.0
12.3
0.0
16.4
121.0
15.3
0.0
20.8
16.0
12.3
0.0
16.4
16.0
12.3
0.0
16.4
21.2
12.3
0.0
16.4
Page Total
Btu/hr
1,987
2,671
2,042
1,338
1,351
1,852
196
196
11,
Internal Gain
Btu/hr .
Occupants
5.8 Occupants X
245 Btuh/occ.
= 1,41
Equipment
1,922 Floor Area X
0.50 W/sgft
3,28
Infiltration: 1.064 X 1.27 X 79.27 X 42 =
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 34,461
Latent Gain Btu/hr
Occupants 5 8 Occupants X 155 Btuh/OCC. = 894
Infiltration: 4,771 X 1.27 X 79.27 X 0.00523 = 2,505
Air Sensible CFM EIA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 894
EnerovPro 6.7 by EnerovSoft User Number: 6712 RunCode: 2016-02-02707:52:38 ID: Paqe 40 of 49 1
C�
1�
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Madison Club 23B
2/2/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Office Kitchen Nook & Dining
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,922.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
10
(SIAM 110.0 X 15.3 +
0.0 X
20.8 =
1,684
G2
(SIAM 43.5 X 12.3 +
0.0 X
16.4 =
534
G3
(SIAM 5.6 X 12.3 +
0.0 X
16.4 =
69
08
(SIM 24.0 X 15.3 +
0.0 X
20.8 =
367
07
(NM 0.0 X 15.3 +
199.0 X
23.0 =
4,582
G1
(NIM 0.0 X 12.3 +
39.8 X
18.1 =
719
X +
X
=
X +
X
=
X +
I X
=
Page Total
7,955
Internal Gain
Btu/hr
Occupants
5 8 Occupants X 245
Btuh/occ.
=
1,413
Equipment
1,922 Floor Area X 0.50
w/sgft
=
3,280
Infiltration: 1.064
X 1.27 X 79.27 X 42 =
4,484
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
34,461
Latent Gain
Btu/hr
Occupants
5 8 Occupants X 155
Btuh/occ.
=
894
Infiltration: 4,771
X 1.27 X 79.27 X 0.00523 =
2,505
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
894
Ene Pro 6.7 by Ener Soft
User Number: 6712 RunCode: 2016-02-02T07:52:38 /D:
Page 41 of 49
r
I RESIDENTIAL ROOM COOLING LOAD SUMMARY I
Project Name
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
Date
Madison Club 23B
1,325.0
0.0260
56.0
2/2/2016
ROOM INFORMATION
29.0
DESIGN CONDITIONS
0.0690
Room Name
Great Room and Entry
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,325.0 ft-'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature
70 OF
Outdoor Dailv Rancie:
34 OF
Ooaaue Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W 21.2x6.16)
R-21 Wall (W 21.2x6.16)
R-21 Wall (W.21.2x6.16)
"R-13 Wall
Orientation
(IM
(NE)
(SE)
(SIM
(NM
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,325.0
0.0260
56.0
564.0
0.0690
29.0
155.5
0.0690
31.0
684.0
0.0690
31.0
76.5
0.0690
30.2
511.0
0.1020
0.0
9.2
12.3
0.0
16.4
85.01
15.3
0.0
20.8
17.5
12.3
0.0
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
F3
F2
B1
A4
A5
01
A3
Al
A2
Orientation
(NE)
(NE)
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
(SE)
Shaded Unshaded
Btu/hr
1,929
1.129
1,463
160
0
1 5,0131
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
12.3
60.0
18.1
0.0
12.3
60.0
18.1
8.3
12.3
0.0
16.4
35.4
12.3
0.0
16.4
9.2
12.3
0.0
16.4
85.01
15.3
0.0
20.8
17.5
12.3
0.0
16.4
35.4
12.3
0.0
16.4
9.3
12.3
0.01
1 16.4
Page Total
Btu/hr
1,084
1,084
102
435
113
1,301
215
435
114
Internal Gain Btu/hr
Occupants 4.0 Occupants X 245 Btuh/occ. 974
E ui ment 11325 Floor Area X 0.50 w/sgft = 2,261
Infiltration: 1.064 X 1.27 X 54.65 X 42 = 3,091
Air Sensible CFM EIA AT
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 25,0631
Latent Gain Btu/hr
Occupants 4 0 Occupants X 155 Btuh/occ. = 616
Infiltration: 4,771 X 1.27 X 54.65 X 0.00523 = 1,727
Air Sensible CFM ELA AW
• TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 616
EnerovPro 6.7 by EneravSoft User Number: 6712 RunCode: 2016-02-02T07:52:38 ID: Page 42 of 49 1
•
C
C
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Madison Club 23B
2/2/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Great Room and Entry
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,325.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
1 Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
Ml
(SE) 0.0 X 12.3 +
60.4
X 16.4 =
992
F5
(Ntq 0.0 X 12.3 +
55.1
X 18.1 =
996
F6
(NIM 0.0 X 12.3 +
17.4
X 18.1 =
314
06
(NIA 0.0 X 15.3 +
204.0
X 23.0 =
4,697
F4
(NIA 0.0 X 12.3 +
51.0
X 18.1 =
921
Fl
(NIM 0.0 X 12.3 +
51.0
X 18.1 =
921
X +
X =
X +
X =
X +
X =
Page Total
1 8,842
Internal Gain
Btu/hr
Occupants
4 0 Occupants X 245
Btuh/occ.
=
974
Equipment
1,325 Floor Area X 0.50
w/sgft
Infiltration: 1.064
X 1.27 X 54.65 X 42 =
3,091
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
25,063
Latent Gain
Btu/hr
Occupants
4.0 Occupants X 155
Btuh/occ.
=
616
Infiltration: 4,771
X 1.27 X 54.65 X 0.00523 =
1,727
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
616
EnerqyPro 6.7 by EnerqySoft
User Number: 6712 Run Code: 2016-02-02T07:52:38 ID:
Page 43 of 49
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Madison Club 238 1 2/2/2016
ROOM INFORMATION DESIGN CONDITIONS
Room Name Guest Master Bedroom Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,452.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranae: 34 OF
Opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W 21.2x6.16)
'R-13 Wall
Orientation
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
1,452.0
0.0260
56.0
514.6
0.0690
29.0
471.8
0.0690
31.0
178.5
0.0690
31.0
333.6
0.0690
30.2
712.0
0.1020
0.0
0.0
12.3
19.2
16.4
0.0
15.3
85.0
20.8
0.0
12.3
21.5
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
FPnPCtratinn
E1
E2
D3
D2
D1
02
C1
05
E5
Internal Gain
Orientation
(NE)
(NE)
(NE)
(NE)
(SE)
(SE)
(S W)
(NM
(NW)
Shaded Unshaded
Btu/hr
2,114
1,030
1.009
1 5,2311
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
0.0
12.3
96.0
18.1
0.0
12.3
19.2
18.1
0.0
12.3
5.6
18.1
0.0
12.3
21.6
18.1
0.0
12.3
19.2
16.4
0.0
15.3
85.0
20.8
0.0
12.3
21.5
16.4
0.0
15.3
78.0
23.0
0.01
12.3
15.6
18.1
Page Total
4.4 Occupants X 245 Btuh/occ.
1,452 Floor Area X 0.50 w/sqft
Infiltration: 1.064 X 1.27 X 59.89 X 42
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
Latent Gain
4.4 Occupants X 1 155 Btuh/occ.
Infiltration: 4.771 X 1.27 X 59.89 X 0.00523 =
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
Btulhr
1,735
347
101
390
315
1,771
353
1.796
7,090
Btu/hr
1,067
2,478
3,388
20,207
Btu/hr
675
1,893
C �
Li
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Madison Club 238
1 2/2/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guest Master Bedroom
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,452.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
E3
(NIA9 0.0 X 12.3 +
44.0 X 18.1
= 795
E4
(NIM 0.0 X 12.3 +
8.8 X 18.1
= 159
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
-
X +
X
=
Page Total
954
Internal Gain
Btu/hr
Occupants
4 4 Occupants X 245
Btuh/occ. =
1,067
Equipment
1,452 Floor Area X 0.50
w/sgft
Infiltration: 1.064
X 1.27 X 59.89 X 42 =
3,388
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
20,207
Latent Gain
Btu/hr
Occupants
4 4 Occupants X 155
Btuh/occ. =
675
Infiltration: 4,771
X 1.27 X 59.89 X 0.00523 =
1,893
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
675
EnergyPro 6.7 by EnerqySoft
User Number: 6712 RunCode: 2016-02-02T07:52:38 /D:
Page 45 of 49
F-
L --A
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Madison Club 23B 2/2/2016
ROOM INFORMATION DESIGN CONDITIONS
Room Name Guest Living Area Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,407.0 ft-- Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranae: 34 OF
Opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21:2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W 21.2x6.16)
R-21 Wall (W.21.2x6.16)
`R-13 Wall
Orientation
(IM
(NE)
(SE)
(SIM
(NW)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,407.0
0.0260
56.0
704.0
0.0690
29.0
548.4
0.0690
31.0
707.4
0.0690
31.0
489.4
0.0690
30.2
745.0
0.1020
0.0
16.4
40.0
0.0
16.4
18.0
0.0
16.4
18.0
0.0
16.4
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
21
R2
R1
19
Q1
P3
N4
P2
Pi
Orientation
(NE)
(NE)
(NE)
(NE)
(SE)
(SE)
(SE)
(SIM
(SIM
Btu/hr
1,409
1,173
1,513
1,021
0
1 7.1641
Shaded
Area
X
X
X
X
X
X
X
X
X1
GLF
15.3 +
12.3 +
12.3 +
15.3 +
12.3 +
12.3 +
12.3 +
12.3 +
12.3 +1
Unshaded
Area
X
X
X
X
X
X
X
X
X1
GLF
=
=
=
=
=
=
=
=
=
0.0
90.0
23.0
0.0
16.0
18.1
0.0
16.0
18.1
0.0
81.0
23.0
12.6
0.0
16.4
18.0
0.0
16.4
40.0
0.0
16.4
18.0
0.0
16.4
18.0
0.0
16.4
Page Total
Btu/hr
2,072
289
289
1,865
155
221
491
221
221
5,824
Internal Gain Btu/hr
Occupants 4.2 Occupants X 245 Btuh/occ. 1,034
Equipment 1,407 Floor Area X 0.50 w/sgft = 2,401
Infiltration: 1.064 X 1.27 X 58.03 X 42 = 3,283
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 24,438
Latent Gain Btu/hr
Occupants 4 2 Occupants X 155 Btuh/occ. = 654
Infiltration: 4,771 X 1.27 X 58.03 X 0.00523 = 1,834
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 654
46 of 49
1�
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Madison Club 238
1 2/2/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guest Living Area
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,407.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U-Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
o
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
N3
(Sim 62.0 X 12.3 +
0.0
X 16.4 =
761
N2
(SM 62.0 X 12.3 +
0.0
X 16.4 =
761
S2
(SVt9 39.6 X 12.3 +
0.0
X 16.4 =
486
NI
(NVIO 0.0 X 12.3 +
40.0
X 18.1 =
723
18
(N K0 0.0 X 15.3 +
77.0
X 23.0 =
1,773
Si
(NM 0.0 X 12.3 +
12.6
X 18.1 =
228
X +
X =
X +
X =
X +
X
Page Total
4,732
Internal Gain
Btu/hr
Occupants
4.2 Occupants X 245
Btuh/occ.=[:AZ401
Equipment
1,407 Floor Area X 0.50
w/sgft
=
Infiltration: 1.064
X 1.27 X 58.03 X 42 =
3,283
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
24,438
Latent Gain
Btu/hr
Occupants
4 2 Occupants X 155
Btuh/occ.
=
654
Infiltration: 4,771
X 1.27 X 58.03 X 0.00523 =
1,834
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
654
EnergyPro 6.7 by EnerqySoft
User Number: 6712 Run Code: 2016-02-02707:52:38 /D:
Page 47 of 49
1�
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Madison Club 23B 2/2/2016
ROOM INFORMATION DESIGN CONDITIONS
Room Name 2nd Floor Master Bedroom Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,691.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranae: 34 OF
ODaaue Surfaces
R-38 Roof Attic
R-21 Wall (W21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W 21.2x6.16)
'R-13 Wall
Orientation
(1/10
(NE)
(SE)
(StM
(NM
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,691.0
0.0260
56.0
624.0
0.0690
29.0
323.0
0.0690
31.0
605.1
0.0690
31.0
332.2
0.0690
30.2
856.0
0.1020
0.0
0.0
12.3
12.6
16.4
14.7
12.3
0.0
16.4
18.0
12.3
0.0
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Z1
21
Y1
X1
v1
W2
W1
23
U2
Orientation
(NE)
(NE)
(NE)
(SE)
(SE)
(SW)
(SM
(SlM
(SW)
Shaded Unshaded
Btu/hr
2,462
1,249
691
1,294
1693
0
1 6,389
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
12.3
36.0
18.1
0.0
15.3
90.0
23.0
0.0
12.3
30.0
18.1
14.4
12.3
0.0
16.4
0.0
12.3
12.6
16.4
14.7
12.3
0.0
16.4
18.0
12.3
0.0
16.4
96.8
15.3
0.4
20.8
26.1
12.3
1 0.0
16.4
Page Total
Btulhr
650
2,072
542
177
207
181
221
1,490
1 5,8611
Internal Gain Btu/hr
Occupants 51 Occupants X 245 Btuh/occ. 1,;
Equipment 1,691 Floor Area X 0.50 w/sgft = 2,i
Infiltration: 1.064 X 1.27 X 69.75 X 42 =
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 20,877
Latent Gain Btu/hr
Occupants 51 Occupants X 155 Btuh/occ. = 786
Infiltration: 4,771 X 1.27 X 69.75 X 0.00523 = 2,204
Air Sensible CFM ELA OW
,*I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
EnerovPro6.7 by EneravSoft User Number: 6712 RunCode: 2016.02-02T07:52:38 ID: Page 48 of 49 1
If , . t y
7-,
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Madison Club 238
1 2/2/2016
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
2nd Floor Master Bedroom
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,691.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
Ul
(Std 18.9 X 12.3 +
0.0
X 16.4
= 232
T1
(NtM 0.0 X 12.3 +
17.8
X 18.1
= 322
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
Page Total
554
Internal Gain
Btu/hr
Occupants
51 Occupants X 245
Btuh/occ.
=
1,243
Equipment
1,691 Floor Area X 0.50
w/sgft
=
2,886
Infiltration: 1.064
X 1.27 X 69.75 X 42 =
3,945
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
20,877
Latent Gain
Btu/hr
Occupants
51 Occupants X 155
Btuh/occ.
=
786
Infiltration: 4,771
X 1.27 X 69.75 X 0.00523 =
2,204
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
786
EnergyPro 6.7 by Ene Soft
User Number: 6712 RunCode: 2016-02-02T07:52:38 ID:
Page 49 of 49