08-0881 (RC) Title 24(� TITLE 24 REPORT I
Title 24 Report for:
Blend Restaurant
La Quinta, CA
CITY OF LA QUINTA
Project Designer BUILDING & SAFETY DEPT.
APPROVED
FOR CONSTRI IP-TitKI
Report Prepared By:
Insu-form, Inc.
41-921 Beacon Hill, Suite A '
Palm Desert, CA 92211
(760) 779-0657
Job Number: � 9 R 0 T �
lm� JUN 17 2008
Date:
6/12/2008
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
I EnergyPro 4.4 by EnergySoft Job Number: User Number: 2655
I � TABLE OF CONTENTS. I
Cover Page
Table of Contents
Form LTG -1-C Certificate of Compliance
Form LTG -2-C Indoor Lighting Schedule
Form LTG -3-C Portable Lighting Worksheet
Form LTG -4-C Lighting Controls Credit Worksheet
Form LTG -5-C Indoor Lighting Power Allowance
Form LTG -7-C Room Cavity Ratio Worksheet
Form LTG -MM Lighting Mandatory Measures
Form MECH-1-C Certificate of Compliance
Form MECH-2-C Air & Water System Requirements
Form MECH-3-C Mechanical Ventilation
Form MECH-4-C HVAC Misc. Prescriptive Requirements
Form MECH-MM Mechanical Mandatory Measures
HVAC System Heating and Cooling Loads Summary
Zone Load Summary
Room Load Summary
1
2
3
7
8
9
10
11
12
13
15
17
18
19
21
22
23
EnergyPro 4.4 by EnergySoft Job Number: User Number: 2655
ICER'TIFICATE OF COMPLIANCE (Part 1 of 4) LTG -1-C
PROJECT NAME
DATE
Blend Restaurant
6/12/2008
PROJECT ADDRESS
La Quinta
PRINCIPAL DESIGNER - LIGHTING
TELEPHONE
Building Permit #
DOCUMENTATION AUTHOR
Insu-form, Inc.
TELEPHONE
(760) 779-0657
Checked by/Date
Enforcement Agenc Use
GENERAL INFORMATION
DATE OF PLANS
BUILDING CONDITIONED FLOOR AREA
CLIMATE ZONE
3,767 Sq.Ft.
1 15
BUILDING TYPE FX_� NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTELIMOTEL GUEST ROOM
❑X CONDITIONED SPACES ❑ UNCONDITIONED SPACES ❑ INDOOR & OUTDOOR SIGNS
PHASE OF CONSTRUCTION ❑ NEW CONSTRUCTION ❑ ADDITION ALTERATION
METHOD OF LIGHTING COMPLETE BUILDING ❑ AREA CATEGORY ❑ TAILORED ❑ PERFORMANCE
COMPLIANCE ❑ COMMON LIGHTING
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24,
Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building lighting requirements.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
SIGNAT RE
DATE
sAL&,k_
"),
p Q
The Principal Lighting Designer hereby certifies that the propo ed uilding design represented in this set of construction documents
is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with
this permit application. The proposed building has been designed to meet the lighting requirements contained in Sections 110, 119,
130 - 132, 146, 148 & 149 of Title 24, Part 6.
❑ The plans & specifications meet the requirements of Part 6 (Sections 10-103a).
❑ The installation certificates meet the requirements of Part 6 (10-103a 3).
❑ The operation & maintenance information meet the requirements of Part 6 (10-103c).
Please Check One: (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.)
❑ I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person
responsible for its preparation; and that I am licensed in the State of California as a civil engineer or electrical engineer, or I am a licensed architect.
❑ I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document
as the person responsible for its preparation; and that I am a licensed contractor performing this work.
❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document because it pertains to a
structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538 and 6737.1.
PRINCIPAL LIG ING DESIGNER - ME SI A URE
DATE LIC. #
6
LI HTMANDATORY MEAS RES
IN
Indicate location on plans of Note Block for Mandatory Measures
LIGHTING COMPLIANCE FORMS & WORKSHEETS Check box if worksheet is included
0LTG-1-C, Parts 1 of 4 and 2 of 4: Certificate of Compliance. Part 1 of 4 and 2 of 4 are required for all submittals
OLTG-1-C, Part 3 of 4: Certificate of Compliance. Part 3 of 4 submittal is required only if Control Credits are claimed
IXXILTG-1-C, Part 4 of 4: Certificate of Compliance. Part 4 of 4 submittal is required when lighting controls are installed
WLTG-2-C: Indoor Lighting Schedule
GSI LTG -3-C: Portable Lighting Worksheet
[9 LTG -4-C: Lighting Controls Credit Worksheet
®LTG -5-C: Indoor Lighting Power Allowance
OLTG-6-C: Tailored Method Worksheet
14LTG-7-C: Room Cavity Ratio Worksheet
El LTG -8-C: Common Lighting Systems Method Worksheet
❑LTG -9-C: Line Voltage Track Lighting Worksheet
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:3 of 23
CERTIFICATE OF COMPLIANCE (Part 2 of 4) LTG -1 -Cil
PROJECT NAMEDATE
Blend Restaurant I I
6/12/2008
INSTALLED INDOOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) 0
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑X COMPLETE BUILDING METHOD (From LTG -5-C)
❑ AREA CATEGORY METHOD (From LTG -5-C)
❑ TAILORED METHOD -(From LTG -5-C) ALLOWED LIGHTING POWER
INSTALLED
ALTERNATE COMPLIANCE
WATTS
❑ PERFORMANCE METHOD
❑ COMMMON LIGHTING SYSTEM (From LTG -8-C)
INSTALLED LIGHTING, CONDITIONED SPACES (From LTG -2-C)
2,908
PORTABLE LIGHTING (From LTG -3-C)
0
LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG -4-C)
52
CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER
2,856
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) 0
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑X COMPLETE BUILDING METHOD (From LTG -5-C)
❑ AREA CATEGORY METHOD (From LTG -5-C)
❑ TAILORED METHOD -(From LTG -5-C) ALLOWED LIGHTING POWER
ALLOWED
WATTS
4,520
ALTERNATE COMPLIANCE
❑ PERFORMANCE METHOD
❑ COMMMON LIGHTING SYSTEM (From LTG -8-C)
ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C)
0
MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS
CONTROL LOCATION CONTROL CONTROL TYPE
(Room #) IDENTIFICATION (Auto Time Switch, Dimming, etc.)
Check if
SPACE CONTROLLED Daylighting
NOTE TO
FIELD
NOTES TO FIELD - For Building
Department Use Only
EnergyPro 4.4 by EnergySoft
User Number: 2655 Job Number: Page:4 of 23
CERTIFICATE OF COMPLIANCE (Part 3 of 4) LTG -1 -C
PROJECT NAME DATE
Blend Restaurant 6/12/2008
CONTROLS FOR CREDIT IN CONDITIONED AND UNCONDITIONED SPACES
CONTROL LOCATION
(Room # or Dwg. #)
Restaurant
Restaura
CONTROL CONTROLTYPE
IDENTIFICATION (Occupant, Daylight, Dimming, etc.)
Dimming - Manual
Dimming - Manual
19
q
NOTE TO
FIELD
NOTES TO FIELD - For Buildin-q
Department Use Only
EnergyPro 4.4 by EnergySoft
User Number: 2655 Job Number: Page:5 of 23
ICER'TIFICATE OF COMPLIANCE (Part 4 of 4) LTG-1 -C
PROJECT NAME
Blend Restaurant
DATE
6/12/2008
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance
tests for lighting systems. The designer is required to check the boxes by all acceptance tests that
apply and list all equipment that require an acceptance test. If all equipment of a certain type requires
a test, list the equipment description and the number of systems to be tested in parentheses. The NJ
number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the
test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design
professional or an agent selected by the owner). Since this form will be part of the plans, completion
of this section will allow the responsible party to budget for the scope of work appropriately.
Building Departments:
Before an occupancy permit is granted for a newly constructed building or space, or a new lighting
system system serving a building or space is operated for normal use, all control devices serving the
building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
In addition a Certificate of Acceptance, LTG-1-A, Forms shall be submitted to the building department
that:
A. Certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of§ 10-103(b) and Title 24 Part 6.
Test Description
Test Performed BY:
❑ LTG-2-A: Lighting Control Acceptance Document
- Occupancy Sensor Acceptance
- Manual Daylight Controls Acceptance
- Automatic Time Switch Control Acceptance
Equipment requiring acceptance testing
❑ LTG-3-A: Automatic Daylighting Controls Acceptance Document
Equipment requiring acceptance testing
EnerovPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:6 of 23 1
INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG -2-C
PROJECT NAME DATE
Blend Restaurant I
6/12/2008
INSTALLED LIGHTING POWER FOR CONDITIONED SPACES
Luminaire
Lamps/Ballasts
Installed Watts
C
D
E
F
G
H
I
J
Name
.
Type Description
��
0 3
cd�
333
30Cr
N
m `��° °
nri��
���
U to
C.
cd�
gETQ
m- o
c
3-0�
3�m
N V
m
MC)
o>m
C
�'
YeS No
r
Z
�. q
Moa
Q
w
G)��
xdo>
N fD
a
(2) 4 ft Fluorescent T8 Energy Savings
Elec
F32T8
2
30
1.0
54.0
X
2
108
13w Compact Fluorescent Scone
1
13
1.0
13.0
X
40
520
13w Compact Fluorescent Twin 2 Pin
FT7W/G23
1
13
1.0
13.0
X
6
78
45 w Track Light 45 w per Foot
1
45
45.0
X
8
360
60w Recessedlncandescent
1
60
60.0
X
10
600
Chandelier
6
231
1.0
138.0
X
1 9
1.2421
PAGE TOTAL 2 908
BUILDING TOTAL (sum of all pages) 2, 908
PORTABLE LIGHTING (From LTG -3-C) O
CONTROL CREDIT (From LTG -4-C) 52
ADJUSTED ACTUAL WATTS 2 856
EneroyPro 4.4 by EnergvSoft .User Number: 2655 Job Number: Page:7 of 23 �
PORTABLE LIGHTING WORKSHEET LTG -3-C
PROJECT NAME
Blend Restaurant
DATE
1 6/12/2008
A
B
TABLE 1 - PORTABLE LIGHTING
NOT SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE FEET
A
B
C D
ROOM #
OR ZONE ID
DEFAULT
W/s ft
AREA TOTAL WATTS
SF B X C
TOTAL
AREA (SF)
(D x E)
TOTAL
WATTS
(C x E)
TOTAL
0 0
TABLE 2 - PORTABLE LIGHTING
SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE FEET
A
B
1 0
C D E
F
G
ROOM #
OR ZONE ID
PORTABLE LIGHTING
Description
# OF
FIXT.
LUMIN. TASK # OF
WATTS PER AREA TASK
FIXTURE (SF) AREAS
TOTAL
AREA (SF)
(D x E)
TOTAL
WATTS
(C x E)
TOTAL
0
E01
TABLE -3 - PLANS SHOWPORTABLE LIGHTING IS NOT REQUIRED FOR OFFICE AREAS > 250 SQUARE FEET
ROOM # TOTAL AREA
OR ZONE ID (SF)
TOTALI 0
BUILDING SUMMARY - PORTABLE LIGHTING
Designer needs to provide detailed documentation that the lighting
level provided by the overhead lighting meets the needs of the
space. The details include luminaire types and mounting locations
relative to work areas.
BUILDING SUMMARY
TOTAL AREA (SF)
(FROM TABLES 1+2+3)
TOTAL WATTS
BUILDING TOTAL
1 0
0
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:8 of 23
LIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG -4-C
CONTROL CREDITS FOR CONDITIONED SPACES
PROJECT NAME DATE
Blend Restaurant 6/12/2008
A
B
C
D
E I F I G
H
I
J
ROOM #
ZONE ID
CONDITIONED
AREAS
LIGHTING
CONTROL
DESCRIPTION
PLAN
REF.
ROOM
AREA
(SF)
DAYLIGHTING
WATTS OF
CONTROL
LIGHTING
LIGHTING
ADJUST.
FACTOR'
CONTROL
CREDIT
WATTS
(H X 1)
WINDOW
WALL
RATIO
GLAZING
VLT
SKYLIGHT
EFFECTIVE
APERTURE'
Restaurant
Dimming - Manual
3,767
247
0.101
25
Restaurant
Dimming - Manual
3,767
273
0.10
27
1) From Equation 146-A
2) From Table 146-A
iJa0:111 r_i•
BUILDING TOTAL
Enter in LTG -2-C: Lighting Control Credit
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:9 of 23 .
INDOOR LIGHTING POWER ALLOWANCE LTG -5-C
PROJECT NAME
Blend Restaurant
DATE
6/12/2008
ALLOWED LIGHTING POWER Choose One Method
COMPLETE BUILDING METHOD - CONDITIONED SPACES
ALLOWED
WATTS
WATTS
PER SF
COMPLETE
BLDG. AREA
ALLOWED
WATTS
BUILDING CATEGORY (From Section 146 Table 146-B)
Com Bldg Restaurant
1.20
1767
4,520
AREA CATEGORY METHOD - CONDITIONED SPACES
AREA
(SF)
ALLOWED
WATTS
AREA CATEGORY (From Section 146 Table 146-C)
WATTS
PER SF
PAGE TOTAL
BUILDING TOTAL
D
D
AREA
WATTS
TAILORED METHOD - UNCONDITIONED SPACES
TOTAL UNCONDITIONED SPACES ALLOWED WATTS
(From LTG -5-C and LTG -6-C)
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page: 10 of 23
PAGE TOTAL
BUILDING TOTAL
D
D
D
D
AREA
WATTS
TAILORED METHOD - CONDITIONED SPACES
TOTAL ALLOWED WATTS
(From LTG -6-C or from computer run.)
D
UNCONDITIONED SPACES
Complete Building and Area Catagory Methods
Category (From Section 146 Table 146 -B&C)
WATTS
PER SF
AREA
(SF)
ALLOWED
WATTS
PAGE TOTAL
BUILDING TOTAL
D
D
AREA
WATTS
TAILORED METHOD - UNCONDITIONED SPACES
TOTAL UNCONDITIONED SPACES ALLOWED WATTS
(From LTG -5-C and LTG -6-C)
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page: 10 of 23
A
B
C
D
E
F
Room
Name
Task/Activity
Description
Room
Length (L)
(ft)
Room
Width (V)
(ft)
Room Cavity
Height (H)
(ft)
Room Cay. Ratio
5xHx(L+V)
/(LxW)
A
B
C
D
E
F
Room
Name
Task/Activity
Description
Room
Area (A)
M
Room
Perimeter (P)
(ft)
Room Cavity
Height (H)
(ft)
Room Cay. Ratio
2.5 x H x P
/A
EnergyPro 4.4 by Energysoft User Number: 2655 Job Number: Page: 11 of 23
LIGHTING MANDATORY MEASURES LTG -MM
PROJECT NAME
Blend Restaurant
DATE
6/12/2008
DESCRIPTION
Designer
Enforcement
§131(d)l For every floor, all interior lighting systems shall be equipped with a separate automatic
control to shut off the lighting. This automatic control shall meet the requirements of
Section 119 and may be an occupancy sensor, automatic time switch, or other device
capable of automatically shutting off the lighting.
§131(d)2Override for Building Lighting Shut-off: The automatic building shut-off system is
provided with a manual, accessible override switch in sight of the lights. The area
of override is not to exceed 5,000 square feet.
❑ §119(h) Automatic Control Devices Certified: All automatic control devices specified are
certified, all alternate equipmentshallbe certified and installed as directed by the
manufacturer.
§111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for
the project are certified and listed in the Directory. All installed fixtures shall be
certified.
❑ §132 Tandem Wiring for One and Three Lamp Fluorescent Fixtures: All one and three
lamp fluorescent fixtures are tandem wired with two lamp ballasts where required
by Standards Section 132; or all one and three lamp fluorescent fixtures are
specified with electronic high -frequency ballasts and are exempt from tandem
wiring requirements.
§131(a) Individual Room/Area Controls: Each room and area in this building is equipped
with a separate switch or occupancy sensor device for each area with floor -to -
ceiling walls.
❑ §131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100
square feet and more than 0.8 watts per square foot of lighting load shall be
controlled with bi-level switching for uniform reduction of lighting within the room.
§131(c) Daylight Area Control: All rooms with windows and skylights that are greater than
250 square feet and that allow for the effective use of daylight in the area shall
have 50% of the lamps in each daylit area controlled by a separate switch; or the
effective use of daylight cannot be accomplished because the windows are
continuously shaded by a building on the adjacent lot. Diagram of shading during
different times of the year is included on plans.
§131(e) Display Lighting. Display lighting shall be separately switched on circuits that
are 20 amps or less.
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page: 12 of 23
CERTIFICATE OF COMPLIANCE (Part 1 of 2) MECH-1-C
PROJECT NAME
DATE OF PLANS
DATE
Blend Restaurant
6/12/2008
PROJECT ADDRESS
BUILDING TYPE a NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTEL/MOTEL GUEST ROOM
PHASE OF CONSTRUCTION ❑ NEW CONSTRUCTION ❑ ADDITION X❑ ALTERATION ❑ UNCONDITIONED (File Affidavit)
La Quinta
COMPLIANCE
Building Permit #
PRINCIPAL DESIGNER - MECHANICAL
TELEPHONE
Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building mechanical requirements.
DOCUMENTATION AUTHOR
TELEPHONE
Checked by/Date
Insu-form, Inc.
(760) 779-0657
Enforcement Agency
GENERAL INFORMATION
DATE OF PLANS
BUILDING CONDITIONED FLOOR AREA
CLIMATE ZONE
3,767Sq.Ft.
15
BUILDING TYPE a NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTEL/MOTEL GUEST ROOM
PHASE OF CONSTRUCTION ❑ NEW CONSTRUCTION ❑ ADDITION X❑ ALTERATION ❑ UNCONDITIONED (File Affidavit)
METHOD OF MECHANICAL ® PRESCRIPTIVE ❑ PERFORMANCE
COMPLIANCE
PROOF OF ENVELOPE COMPLIANCE ❑✓J PREVIOUS ENVELOPE PERMIT ❑ ENVELOPE COMPLIANCE ATTACHED
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24,
Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building mechanical requirements.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
SIGNATU EDATE
B
�.OAAJO
The Principal Mechanical Designer hereby certifies that the pro ose building design represented in this set of construction
documents is consistent with the other compliance forms and works eets, with the specifications, and with any other
calculations submitted with this permit application. The proposed building has been designed to meet the mechanical
requirements contained in the applicable parts of Sections 100, 101, 102, 110 through115, 120 through 125, 142, 144, and 145.
❑ The plans & specifications meet the requirements of Part 1 (Sections 10-103a).
❑ The installation certificates meet the requirements of Part 1 (10-103a 3).
❑ The operation & maintenance information meets the requirements of Part 1 (10-103c).
Please check one: (These sectionsof the Business and Professions Code are printed in full in the Nonresidential Manual.)
❑ I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the
person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, or mechanical engineer or I
am a licensed architect.
❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign
this document as the person responsible for its preparation; and that I am a licensed contractor performing this work.
❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document because it pertains to a
structure or type of work described pursuant to Business and Professions Code sections 5537, 5538, and 6737.1.
PRINCIPAL ME HAN AL DESIGNER - NAME
SIG RE
DAT
CO
INSTRUCTIONS TO APPLICANT
Ox MECH-1-C: Certificate of Compliance. Part 1, 2, 3 of 3 are required on plans for all submittals.
OO MECH-2-C: Air/Water/Service/Water Pools Requirements. Part 1 of 3, 2 of 3, 3 of 3 are required for all submittals, but may be on
plans.
(N MECH-3-C: Mechanical Ventilation and Reheat is required for all submittals with mechanical ventilation, but may be on plans.
® MECH-4-C: HVAC Misc. Prescriptive Requirements is required for all prescriptive submittals, but may be on plans.
O MECH-5-C: Mechanical Equipment Details are required for all performance submittals.
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page: 13 of 23
CERTIFICATE OF COMPLIANCE (Part 2 of 2) MECH-1-C
PROJECT NAME DATE
Blend Restaurant I
6/12/2008
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation
certificates, and operating and maintenance information meet the requirements of Section 10-103(b) and Title 24 Part 6.
STATEMENT OF COMPLIANCE —71
❑ MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-3-A: Packaged HVAC Systems Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the
commission do not require equipment testing but do require construction inspection.
❑ MECH-5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
This test required If the unit serves 5, 000 fi2 of space or less and 25% or more of the ducts are in nonconditioned or semiconditioned space like an
attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
❑ MECH-6-A: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls installed on new or existing packaged systems must be tested.
❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
All new VA fan volume controls installed on new or existing systems must be tested
❑ MECH-8-A: -Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to chilled and hot watersystems.
-Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Btulhr.
-Water-loop Heat Pump Controls
Applies to all new watedoop heat pump systems where the combined loop pumps are greater than 5 hp.
-Variable Frequency Controls Applies to all new distribution pumps on new variable now chilled, hydronic heat pump
or condenser water systems where the pumps motors are greater than 5 hp.
Equipment requiring acceptance testing
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:14 of 23
d
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
PROJECT NAME DATE
Blend Restaurant 6/12/2008
SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated. Sensible Cooling. Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
AIR SYSTEMS, Central or Single Zone
Restaurant
3
Reference on Plans or Specification t
112(a)
3.30 COP
112(a)
10.3 EER
112(b)
Yes
112(c), 115(a)
n/a
121(b)
Yes
121(b)
1449 cfm
121(c)
No
121(c)
No
121 c 122(e)
Programmable Switch
122(e)
Heating & Cooling Required
122
Auto
122(g)
n/a
123
124
R-8.0
144 a & b
182,148 btuh
144 a & b
236,059 btuh
144 a &.b
253,124 btuh
144 a & b
168,091 btuh
144 c
Constant Volume
144 c
144 c
Yes
144 d
No
144 a
No Economizer
144
Constant Tem
144 (f)
Constant Temp
144 (k)
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
EneravPro 4.4 by EneravSoft User Number: 2655 Job Number: Page: 15 of 23 1
WATER SIDE SYSTEM REQUIREMENTS Part 2 of 2 MECH-2-C
PROJECT NAME DATE
Blend Restaurant 6/12/2008
SYSTEM FEATURES
2 WATER SIDE SYSTEMS: Chillers, Towers, Boilers, H dronic Loops
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section Reference on Plans or Specification
Equipment Efficiency 112(a)
Pipe Insulation 123
PRESCRIPTIVE MEASURES
Calculated Capacity
Proposed Capacity
Tower Fan Controls
Tower Flow Controls
Variable Flow System Design
Chiller and Boiler Isolation
CHW and HHW Reset Controls
WLHP Isolation Valves
VSD on CHW, CW & WLHP Pumps > 5
HP
DP Sensor Location
144 (a & b)
144 (a & b)
144 h
144 h
144 0)
144 '
144 G
144 '
144 0)
144 0)
1: For each chiller, cooling tower, boiler, and hydronic loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph
number where the required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Water side systems include wet side system using other liquids such as glycol or brine.
Service Hot Water, Pool Heating
ITEM OR SYSTEM TAG(S) DHW Heater
Number of Systems 1
MANDATORY MEASURES Reference on Plans or Specification
Water Heater Certification
113 (a)
Water Heater Efficiency
113 b
Service Water Heating Installation
113 (c)
Pool and Spa Efficiency and Control
114 (a
Pool and Spa Installation
114 b
Pool Heater - No Pilot Light
115 (c)
Spa Heater - No Pilot Light
115 d
Standard Gas 50 gal or Less
78%
n/a
n/a
n/a
1: For each water heater, pool heat and domestic water loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and
paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" ins the column.
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page: 16 of 23 1
MECHANICAL VENTILATION MECH-3-C
PROJECT NAME DATE
Blend Restaurant 6/12/2008
7
PRESCRIPTIVE REHEAT
LIMITATION (Section 144(d))
MECHANICAL VENTILATION Section
121(b)2) I
AREA
BASIS
OCCUPANCY
BASIS
I VAV MINIMUM
A
B
C
D
E
F
G
H
I
J
K
L
M
N
ZONE/SYSTEM
o
D�
N
--d_:
(n
c
din
N O �t
�g
T
°o
Cr3
p`��
k D -n
nmT
`" d
-0
co6
O Q
�_�
®M
v
.0n
y O
0�3
3
m��
k 0
cn
n "n
.r 7 3
_
m
vyD
O k
d
o
.. D
<p
0 CD
-rt .� N
3•
D
o o
nom
T fA
gcv
oto
n
Tv
3 k
r^o
x a_
c
°
way
O O k
oy o
g�
>
'O
23
'-'
D
-I
>
�,
m
D
Restaurant
3,7671
0.38
1,4311
1
1,431
1 1,449
Restaurant
Total
1,431
1,449
C Minimum ventilation rate per Section 121 Table 121-A
E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed seating.
H Required Ventilation Air (REO'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G).
I Must be greater than orequal to H or use Transfer Air column N to make up the difference.
J Design fan supply chn Fan CFM) x 30%; or
K Condition area (ft. sq. x 04 dmKL sq.; or
L Maximum of Columns H. J, K, or 300 cm
M This must be less than orequal to Column L and greater that orequal to the sum of Columns H + N.
N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal
to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M.
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page: 17 of 23
MECHANICAL SIZING AND FAN POWER MECH-4-C
PROJECT NAME
DATE
Blend Restaurant
6/12/2008
SYSTEM NAME
FLOOR AREA
Restaurant
3,767
FAN POWER CONSUMPTION
A
FAN DESCRIPTION
Supply Fan
B
DESIGN
BRAKE HP
1.500
C I D
EFFICIENCY
MOTOR DRIVE
84.0% 100.0%
E
NUMBER
OF FANS
3.0
PEAK WATTS
B x E x 746 / (C X D)i
1 3,9961
1. TOTAL FAN SYSTEM POWER INDEX or ADJUSTED FAN POWER INDEX must not exceed 0.8 W/cfm for Constant Volume systems or 1.25 W/cfm for VAV systems.
ITEM or SYSTEM TAG(S)
Total Adjustments
FILTER PRESSURE ADJUSTMENT EQUATION
144-A
A) If filter pressure drop is greater than 1 inch W.C. enter
1 TOTAL FAN SYSTEM POWER Watts, Sum Column F
3,996
2) SUPPLY DESIGN AIRFLOW (CFM)
9,000
filter pressure drop. SPa on line 4 and Total Fan pressure
3 TOTAL FAN SYSTEM POWER INDEX Row 1/Row, 2
SPf on Line 5.
144 (i
4 SPa
B) Calculate Fan Adjustment and enter on Line 6.
5 SPf
6) Fan Adjustment= 1-(SPa - 1)/SPf
C) Calculate Adjusted Fan Power Index and enter on Line 7.
7 ADJUSTED FAN POWER INDEX Line 3 x Line 61
0.444
1. TOTAL FAN SYSTEM POWER INDEX or ADJUSTED FAN POWER INDEX must not exceed 0.8 W/cfm for Constant Volume systems or 1.25 W/cfm for VAV systems.
ITEM or SYSTEM TAG(S)
PRESCRIPTIVE MEASURES
Electric Resistance Heating '
Heat Rejection System 2
Air Cooled Chiller Limitation 3
T-24
Section
Capacity
Exception
Notes
144 g
144 (h)
144 (i
1. Total installed capacity (MBtu/hr) of all electric heat on this project exclusive of electric auxiliary heat for heat pumps. If electric heat is used, explain which exception(s) to Section(g) apply.
2. Are centrifugal fan cooling towers used on this project? (Enter "Yes" or "No") If centrifugal fan cooling tower are used, explain which exception(s) to Section 144(h) apply.
3. Total installed capacity (tons) of all water and air cooled chillers under this permit. If there are more than 100 tons of air-cooled chiller capacity being installed, explain which exception(s) to Section
144(1) apply.
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page: 18 of 23
MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM
PROJECT NAME
Blend Restaurant
I1l_111121
6/12/2008
DESCRIPTION
Designer
Enforcement
Equipment and Systems Efficiencies
§I11 Any appliance for which there is a California standard established in the
Appliance Efficiency Regulations will comply with the applicable standard.
❑ §115(a) Fan type central furnaces shall not have a pilot light.
§123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees
Fahrenheit, or within HVAC equipment, shall be insulated in accordance with
Standards Section 123.
§124 Air handling duct systems shall be installed and insulated in compliance with
Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards.
Controls
§122(e) Each space conditioning system shall be installed with one of the following:
❑ §122(e)1A Each space conditioning system serving building types such as offices and
manufacturing facilities (and all others not explicitly exempt from the
requirements of Section 112 (d)) shall be installed with an automatic time switch
with an accessible manual override that allows operation of the system during
off -hours for up to 4 hours. The time switch shall be capable of programming
different schedules for weekdays and weekends and have program backup
capabilities that prevent the loss of the device's program and time setting for at
least 10 hours if power is interrupted; or
F] §122(e)1 B An occupancy sensor to control the operating period of the system; or
F] §122(e)1C A 4 -hour timer that can be manually operated to control the operating period of
the system.
§122(e)2 Each space conditioning system shall be installed with controls that temporarily
restart and temporarily operate the system as required to maintain a setback
heating and/or a setup cooling thermostat setpoint.
❑ §122(g) Each space conditioning system serving multiple zones with a combined
conditioned floor area more than 25,000 square feet shall be provided with
isolation zones. Each zone: shall not exceed 25,000 square feet; shall be
provided with isolation devices, such as valves or dampers, that allow the supply
of heating or cooling to be setback or shut off independently of other isolation
areas; and shall be controlled by a time control device as described above.
❑ §I22(a&b) Each space conditioning system shall be controlled by an individual thermostat
that responds to temperature within the zone. Where used to control heating, the
control shall be adjustable down to 55 degrees F or lower. For cooling, the
control shall be adjustable up to 85 degrees F or higher. Where used for both
heating and cooling, the control shall be capable of providing a deadband of at
least 5 degrees F within which the supply of heating and cooling is shut off or
reduced to a minimum.
§122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and
adjustable setpoint stops accessible only to authorized personnel.
§112(b) Heat pumps shall be installed with controls to prevent electric resistance
supplementary heater operation when the heating load can be met by the heat
pump alone.
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page: 19 of 23
MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM
NAME
Blend Restaurant
DATE
6/12/2008
Description
Designer
Enforcement
Ventilation
❑ §121(e) Controls shall be provided to allow outside air dampers or devices to be operated
at the ventilation rates as specified on these plans.
§122(f) Gravity or automatic dampers interlocked and closed on fan shutdown shall be
provided on the outside air intakes and discharges of all space conditioning and
exhaust systems.
❑ §I22(q All gravity ventilating systems shall be provided with automatic or readily
accessible manually operated dampers in all openings to the outside, except for
combustion air openings.
❑ §I21(f)1 Air Balancing: The system shall be balanced in accordance with the National
Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or
Associated Air Balance Council (AABC) National Standards (1989); or
§121(f)2 Outside Air Certification: The system shall provide the minimum outside air as
shown on the mechanical drawings, and shall be measured and certified by the -
installing licensed C-20 mechanical contractor and certified by (1) the design
mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3)
the person with overall responsibility for the design of the ventilation system; or
F] §121(03 Outside Air Measurement: The system shall be equipped with a calibrated local or
remote device capable of measuring the quantity of outside air on a continuous
basis and displaying that quantity on a readily accessible display divice; or
§121 (f)4 Another method approved by the Commission.
Service Water Heating Systems
§I13(b)2 If a circulating hot water system is installed, it shall have a control capable of
automatically turning off the circulating pump(s) when hot water is not required.
§I13(c) Lavatories in restrooms of public facilities shall be equipped with controls to limit
the.outlet temperature to 110 degrees F.
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:20 of 23
1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Blend Restaurant 6/12/2008
SYSTEM NAME FLOOR AREA
Restaurant 3,767
EATING SYSTEM PSYCH
26.0 of 62.7 of
Outside Air
1449 cfm
69.7 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible
Latent
I I CFM
I Sensible
12,059
132,498
26,562
3,007
54,520
0
168,091
82,543
6,625
2,726
0
0
1,449
55,953
4,064
1,449
67,404
0
0
6,625
2,726
209 194 30,6261 F77127 376
RICS (Airstream Tem
62.7 of 79.3 of
Supply Fan Heating Coil
9000 cfm
res at Time of Heati
Supply Air Ducts
87.0 of
ROOMS
70.0 of
Return Air Ducts ` I
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
111.0/77.6OF 80.5/68.6OF 80.5/68.7OF 63.0/62.0OF
Supply Air Ducts
Outside Air
1449 cfm Supply Fan Cooling Coil 63.7 / 62.3 of
9000 cfm 68.1% R.H. ROOMS
74.7/66.7 of 74.0/66.5OF
h Return Air Ducts '�
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:21 of 23 1
Carrier 50HJQ008
168,091
82,543
159,266
7.5 kW Supplemental Electric
76,792
Total Adjusted System Output
168,091 82,543
36
2,059
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK
Aug 4 pm
Jan 12 am
RICS (Airstream Tem
62.7 of 79.3 of
Supply Fan Heating Coil
9000 cfm
res at Time of Heati
Supply Air Ducts
87.0 of
ROOMS
70.0 of
Return Air Ducts ` I
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
111.0/77.6OF 80.5/68.6OF 80.5/68.7OF 63.0/62.0OF
Supply Air Ducts
Outside Air
1449 cfm Supply Fan Cooling Coil 63.7 / 62.3 of
9000 cfm 68.1% R.H. ROOMS
74.7/66.7 of 74.0/66.5OF
h Return Air Ducts '�
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:21 of 23 1
ZONE LOAD SUMMARY
PROJECT NAME
Blend Restaurant
DATE
6/12/2008
SYSTEM NAME
. Restaurant
FLOOR AREA
3,767
ZONE LOAD SUMMARY 771
ZONAL SYSTEM
COOLING PEAK
HEATING PEAK
ZONE NAME
SYSTEM NAME
Mult.
CFM
Cooling
Latent
Heating
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Restaurant
1.0
12,059
189,517
53,818
3,007
122,363
Values include ventilation load
COINCIDENT TOTAL 1 189,517 53,818 122,363
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page:22 of 23
ROOM LOAD SUMMARY
PROJECT NAME
Blend Restaurant
DATE
6/12/2008
SYSTEM NAME
Restaurant
FLOOR AREA
3,767
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Restaurant
Restaurant
1
12 059
132,498
26,562
12,059
132,498
26,562
3,007
54,520
PAGE TOTAL 1 12,059 132,498 26,562 3,00754,520
TOTAL 1 12,059 132,498 26,5621 3,007 1 54,520
EnergyPro 4.4 by EnergySoft User Number: 2655 Job Number: Page: 23 of 23