14-0686 (ELEC) Title 24I BUILDING ENERGY ANALYSIS REPORT I
PROJECT:
+ _ Reserve at the Citrus Lot 9
La Quinta, CA
Project Designer:
Bassenian Lagoni Architects
2031 Orchard Drive
Newport Beach, CA 92660
949.553.9100
Report Prepared by:
Gangyi Zhou
GMEP Engineers
u
4400 Campus Drive
Newport Beach, CA 92660
949-752-1612
Job Number:
63090 CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
Date: APPR < VED
11/21/2013 FOR CONS UCTION
DATE Y
The EnergyPro computer program has been used to perform the calculations summarized in this compliance rep This p g a 'has-ap-roval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 B Idi gEnergy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
Energ Pro 5.1 by Energ Soft User Number. 8165 RunCode: 2013-11-21715:55:24 /D: 63090
I TABLE OF CONTENTS
Cover Page
Table of Contents
Form CF -1 R Certificate of Compliance
Form MF -1 R Mandatory Measures Summary
LA OU PT
-
�' ��a e° C3 SAFES DE
lam
�,;�ti•1ST�UCT40
EnergyPro 5.1 by EnergySoft Job Number: ID: 63090 User Number: 8165
1
2
3
11
t
d
1
t
i
1
1
Electronically Filed by Gangyi Zhou and Authenticated at CalCERTS.com - 11/25/2013
Electronically Signed at CalCERTS.com by Michael Rafferty (Hearthside Communities LLC) 11/25/2013
PERFORMANCE CERTIFICATE: Residential Part 1 of 5 CF -1 R
Project Name
Reserve at the Citrus Lot 9
Building Type 0 Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration 11/25/2013
Date
Project Address
La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
3,61
Addition
n/a
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
El Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
El Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction Type Cavity(ft) Features see Part 2 of 5 Status .
Wall Wood Framed R-13 2,234 New
Roof Wood Framed Attic R-30 3,618 Radiant Barrier New
FENESTRATION U- Exterior
Orientation Area(fe) . Factor SHGC OverhangSidefins Shades Status
Front (N) 259.5 0.310 0.28 none none Bug Screen New
Front (N) 96.0 0.310.:r x._,0.28.—.none..., —none —Bug Screen—_--,, New
Left (E) 111.0 0.310 f 0.28 none. none Bug Screen New
Left (E){ , 24.0 Ir 0.310 0.28 none �--n'one � Bug Screen f, New
Rear (S) ,�� 77.5 ,' ; 0.310 0.28 none ; none jr Bug Screen r New 1
Rear (S) _e�lfll 7 rJ48.0' ` t'0.310--- ' •-0.28 none none , - , Bug Screen • l '; New
Right (W) 186.5 0.310 0.28 none none Bug Screen New
Right (W) 24.0 0.310 0.28 none none Bug Screen New
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE Split Air Conditioner 13.0 SEER Setback New
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
5 T Ducted Ducted Attic, Ceiling Ins, vented _ ,__—�-8.0'77- �w
W1*4 "' "
F t � x f Fn -r
nI�t�a & SAV'E I
WATER HEATING L:— ✓ ov t =�'
Ot . Type Gallons Min. Eff Distribution ONSTRUCTION Status
1 Instant Gas 0 0.84 Kitchen Pipe Ins New,
BY
rr_
EnergyPro 5.1 b En erg Soft User Number. 8165 Run Code: 2013-11-21715:55:24 ID: 63090 Page 1 of 8
Reg: 213-N0088594A-000000000-0000 Registration Date/Time: 2013/11/25 13:21:18
HERS Provider: CalCERTS, Inc
1
1
0
i
Electronically Filed by Gangyi Zhou and Authenticated at CalCERTS.com - 11/25/2013
Electronically Signed at CalCERTS.com by Michael Rafferty (Hearthside Communities LLC) 11/25/2013
AN
PERFORM CE CERTIFICATE: Residential (Part 2 of 5) CF -1 R
Project Name Building Type ® Single Family ❑ Addition Alone Date
Reserve at the Citrus Lot 9 1 ❑ Multi Family ❑ Existing+ Addition/Alteration 11112512013
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
Compliance for all orientations is specified, see section 151 (c) 2 of the Standards and section 7.6.2 of the Residential Compliance Manual.
The Roof R-30 Roof Attic includes credit for a Radiant Barrier that is Continuous meeting eligibility and installation criteria as specified in Residential
Appendix RA4.2.2.
77—r r.
HERS REQUIRED VERIFICATION '
Items in this section require field testing and/or verification by a certified HERS Rater The'inspe torfmust receive a
completed CF -4R form for each of the measures listed below for final to be given.
The Cooling System 5 T includes credit for a 11.0 EER Condenser. A certified HERS rater must field verify the installation of the correct Condenser.
The HVAC System 5 T includes credit for Verified Fan Energy. Measured Fan Energy may not exceed 0.58 w/cfm.
The HVAC System 5 T incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System 5 T includes credit for verified adequate airflow. A certified HERS rater must diagnostically measure airflow of the HVAC System.
The HVAC System 5 T incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct leakage
meets the specified criteria.
CITY Or .,���r- EPT'
SAFETY D
FOR CON -6I
Ener Pro 5.1 by Ener Soft User Number: 8165 RunCode: 2013-11-21T15:55:24 ID: 63090 Page 2 of 8
IReg: 213-N0088594A-000000000-0000 Registration Date/Time: 2013/11/25 13:21:18 HERS Provider: CalCERTS, Inc
IReg: 213-N0088594A-000000000-0000 Registration Date/Time: 2013/11/25 13:21:18 HERS Provider: CalCERTS, Inc
Electronically Filed by Gangyi Zhou and Authenticated at CalCERTS.com - 11/25/2013
'Electronically Signed at CalCERTS.com by Michael Rafferty (Hearthside Communities LLC) 11/25/2013
t
f
r
11
1
k-1
s
' Reg: 213-N0088594A-000000000-0000 Registration Date/Time: 2013/11/25 13:21:18 HERS Provider: CalCERTS, Inc
PERFORMANCE CERTIFICATE: Residential (Part 3 of 5) CF -1 R
Project Name
Building Type m Single Family ❑ Addition Alone
I Date
Reserve at the Citrus Lot 9
❑ Multi Family ❑ Existing+ Addition/Alteration
111/25/201
ANNUAL ENERGY USE SUMMARY
Standard Facing Margin Facing Margin Facing Margin Facing Margin
TDV kBtu/ft2- r North East South West
Space Heating 4.14 5.15 -1.01 4.49 -0.35 4.05 0.09 4.55 -0.41
Space Cooling 52.16 48.41 3.74 49.29 2.87 50.94 1.21 51.11 1.04
Fans 10.40 10.78 -0.38 10.94 -0.54 11.26 -0.86 11.30 -0.90
Domestic Hot Water 10.08 7.18 2.90 7.18 2.90 7.18 2.90 7.18 2.90
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Totals 76.78 71.53 5.25 71.89 4.88 73.43 3.35 74.14 2.64
Percent Better Than Standard: 6.8% 6.4% 4.4% 3.4
BUILDING COMPLIES - HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: All Four orientations Ext. Walls/Roof Wall Area Area
Number of Dwelling Units: 1.00 (N) 802 356
Fuel Available at Site: Natural Gas (E) 828 135
Raised Floor Area: 0 (S) 398 126
Slab on Grade Area: 0 (vv) 1,033 211
Average Ceiling Height: 10.0 Roof 3,618 0
Fenestration Average U -Factor: 0.31 TOTAL: 827
Average SHGC: 0.28 Fenestration/CFA Ratio: 22.8%
REMARKS
6
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
The documentation author hereby certifies that the documentation is accurate and complete.
Documentation Author
Xxl�'
Company GMEP Engineers L�-;�V
11/25/2013
Address 4400 Campus Drive NameGan9iZhou
City/State/ZipCity/State/Zip Newport Beach, CA 92660 Phone 949-752-1612 Signed Date
The individual with overall design responsibility hereby certifies that the proposed building design represented in this set
of construction documents is consistent with the other compliance forms and worksheets, with the -specifications, and
with any other calculations submitted with this permit application, and recognizes.that-compl`gnceusing,duct design,
duct sealing, verification of refrigerant charge, insulation instal lation=quality`„and building`env '10,
installer testing and certification and field verification by an approved HERS rater'.; �,C aljng require
Sp,FE
Designer or Owner (per Business & Professions Code) gU1LD1N� =�0
�U�tj�ON
�►��
Company BassenianLagoniArchitects FOFJCONSTR
Address 2031 Orchard Drive Name
City/State/Zip Newport Beach, CA 92660 Phone 949.553.9100 BY License* #� Date
DATE -Signed-
Ener Pro 5.1 b Ener Soft User Number: 8165 RunCode: 2013-11-21T15:55:24 ID: 63090 Pa e 3 of 8
Electrqnically Filed by Gangyi Zhou and Authenticated at CalCERTS.com - 11/25/2013
'Electronically Signed at CalCERTS.com by Michael Rafferty (Hearthside Communities LLC) 11/25/2013
t
1
w
1
1
C!
CERTIFICATE OF COMPLIANCE: Residential
(Part 4 of 5) CF -1 R
Project Name
Reserve at the Citrus Lot 9
Building Type m Single Family
❑ Multi Family
❑ Addition Alone
❑ Existing+ Addition/Alteration
Date
11112512013
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Wall
447 0.102 R-13
0
90 New
4.3.1-A3 First Floor
Wall
693 0.102 R-13
90
90 New
4.3.1-A3 First Floor
Wall
272 0.102 R-13
180
90 New
4.3.1-A3 First Floor
Wall
822 0.102 R-13
2701
90 New
4.3.1-A3 First Floor
Roof
3,6181 0.031 R-30 1
0
0 New
4.2.1-A20 First Floor
FENESTRATION SURFACE DETAILS
ID
Type Area U -Factor
SHGC
Azm Status
Glazing Type Location/Comments
1
Window 44.0 0.310 NFRC
0.28 NFRC 0 New
Low E
First Floor
2
Window 18.0 0.310 NFRC
0.28 NFRC 0 New
Low E
First Floor
3
Window 18.0 0.310 NFRC
0.28 NFRC 0 New
Low E
First Floor
4
Window 18.0 0.310 NFRC
0.28 NFRC 0 New
Low E
First Floor
5
Window _ 18.0 0.310 NFRC
0.28 NFRC 0 New
Low E_
l __ First Floor
6
Window' 18.0 0.310 NFRC.,,
". ' 0.28 NFRC + 0 New
Low,E
" First Floor
7
Window 18.01 0.310 NFRC
0.28 NFRC 0 New
. Low E ,
` First Floor
8
Window 16.5 '.'0.310 NFRC
0.28 NFRC -7 0 New 'r
Low E I
First Floor
9
Window 7.0 0.310 NFRC
0.28 NFRC 0 New
Low E /
First Floor ,
10
Window ,7 /36.0 , 0.310 NFRC
0.28 NFRC 4 0 New
Low E '
First Floor,
11
Window < 6.0 0.310 NFRC
-0.28 NFRC 0 New
1LowE
First Floor
12
Window 6.0 0.310 1 NFRC
0.28 NFRC 0 New
Low E
First Floor
13
Window 6.0 0.310 NFRC
0.28 NFRC 0 New
Low E
First Floor
14
Window 6.0 0.310 NFRC
0.28 NFRC 0 New
Low E
First Floor
15
Window 6.0 0.310 NFRC
0.28 NFRC 0 New
Low E
First Floor
16
Window 6.0 0.310 NFRC
0.28 NFRC 0 New
Low E
First Floor
(1) LI -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type SHGC
Window
H t Wd
Ove hang
Len H t LExt RExt
Left Fin Ri ht in
Dist Len H t Dist Len H t
1
Bug Screen 0.76
2
Bug Screen 0.76
3
Bug Screen 0.76
4
Bug Screen 0.76
5
Bug Screen 0.76
6
Bug Screen 0.76
7
Bug Screen 0.76
8
Bug Screen 0.76
9
Bug Screen 0.76
10
Bug Screen 0.76��
-r,-r
11
Bug Screen 0.76
r✓ `
, ... S M E 1 y L' f-' ` " I
12
Bug Screen 0.76
1 ;;Ulut Ir71 1
13
Bug Screen 0.76
t-�'�l V r -'.t .
14
Bug Screen 0.76
15
JBug Screen 0.76
16
JBug Screen 0.76
1
DATE
Ener Pro 5.1 by Ener Soft User Number: 8165
RunCode: 2013-11-21715:55:24
ID: 63090 Page 4 of 8
IReg: 213-N0088594A-000000000-0000 Registration Date/Time: 2013/11/25 13:21:18 HERS Provider: CalCERTS, Inc
1
i'
1
n
i
Electrqnically Filed by Gangyi Zhou and Authenticated at CalCERTS.com - 11/25/2013
Electronically Signed at CalCERTS.com by Michael Rafferty (Hearthside Communities LLC) 11/25/2013
CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF -1 R
Project Name
Reserve at the Citrus Lot 9
Building Type 0 Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
11112512013
OPAQUE SURFACE DETAILS
Surface U-
Type Area Factor
Insulation Joint Appendix
Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
FENESTRATION SURFACE DETAILS
ID
Type Area
LI -Factor' SHGC2
Azm Status Glazing Type Location/Comments
17
Window 6.0
0.310 NFRC 0.28 NFRC 0 New Low E First Floor
18
Window 6.0
0.310 NFRC 0.28 NFRC 0 New Low E First Floor
19
Window 24.0
0.310 NFRC 0.28 NFRC 0 New Low E FR DR First Floor
20
Window 24.0
0.310 NFRC 0.28 NFRC 0 New Low E FR DR First Floor
21
Window y 24.0
0.310 NFRC 0.28 NFRC 0 New ------ Low E FR DR First Floor
22
Window 24.0
0.310 NFRC 0.28 NFRC 0 New Low.E FR DR' r First Floor
23
Window ` 15. 01
0.310 NFRC 1 0.28 NFRC 1 90 New Low E c First Floor
24
Window 16.5
:,'O. 310 NFRC 0.28 NFRC �7 90 New Low E j First Floor
25
Window 16.5
0.310 NFRC 0.28 NFRC 90 New Low E f First Floor .
26
Window ,1 116.5
0.310 NFRC 0.28 NFRC 90 New Low E First Floor
27
Window •' ' 13.5
0.310 NFRC 0.28 NFRC 90 New Low E ? First Floor
28
Window 16.5
0.310 NFRC 0.28 NFRC 90 New Low E First Floor
29
Window 16.5
0.310 1 NFRC 0.28 NFRC 90 New Low E First Floor
30
Window 24.0
0.310 NFRC 0.28 NFRC 90 New Low E FR DR First Floor
31
Window 7.0
0.310 NFRC 0.28 NFRC 180 New Low E First Floor
32
Window 16.5
0.310 NFRC 0.28 NFRC 1801 New Low E First Floor
(1) Ll -Factor Type:
2 SHGC Type:
116-A = Default Table from Standards, NFRC = Labeled Value
116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type
Window
SHGC Hot Wd
Ove hang Left Fin Right Fin
Len H t LExt RExt Dist Len H t Dist Len H t
17
Bug Screen
0.76
18
Bug Screen
0.76
19
Bug Screen
0.76
20
Bug Screen
0.76
21
Bug Screen
0.76
22
Bug Screen
0.76
23
Bug Screen
0.76
24
Bug Screen
0.76
25
_Bug Screen
0.76
26
Bug Screen
0.76
l_ J r- L -t-1` " r , pT I
27
Bug Screen
0.76
28
Bug Screen
0.76
K ISU►�-�"' _ e III.
29
Bug Screen
0.76
1 IN, �J k- n � �, ��� ��t M
30
Bug Screen
0.76
NS IF -- '
31
Bug Screen
0.76
32
JBug Screen
0.76
DATE-�
Ener Pro 5.1 by Ener Soft User Number: 8165
RunCode: 2013-11-21T15:55:24 /D: 63090 Pa e 5 of 8
Reg: 213-N0088594A-000000000-0000 Registration Date/Time: 2013/11/25 13:21:18 HERS Provider: CalCERTS, Inc
Electronically Filed by Gangyi Zhou and Authenticated at CalCERTS.com - 11/25/2013
'Electronically Signed at CalCERTS.com by Michael Rafferty (Hearthside Communities LLC) 11/25/2013
1
1
CERTIFICATE OF COMPLIANCE: Residential
(Part 4 of 5) CF -1 R
Project Name
Reserve at the Citrus Lot 9
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
11/25/2013
OPAQUE SURFACE DETAILS
Surface U-
Type Area Factor
Insulation
Cavity Exterior Frame Interior Frame Azm Tilt Status
Joint Appendix
4 Location/Comments
FENESTRATION SURFACE DETAILS
ID
Type Area
U -Factor
SHGC
Azm Status Glazing
Type Location/Comments
33
Window 18.0
0.310 NFRC
0.28 NFRC 180 New Low E
First Floor
34
Window 18.0
0.310 NFRC
0.28 NFRC 180 New Low E
First Floor
35
Window 6.0
0.310 NFRC
0.28 NFRC 180 New Low E
First Floor
36
Window 6.0
0.310 NFRC
0.28 NFRC 180 New Low E
First Floor
37
Window _ 24.0
0.310 NFRC
0.28 NFRC 1 180 New Low E FR DR
_ _ First Floor
38
Window' 24.0
0.310 NFRC
0.28 NFRC 180 New Low_E FR DR.
' ' First Floor
39
Window 6.0
0.310 NFRC
0.28 NFRC 180 New Low EFirst
Floor
40
Window 8.0 .
0.310 NFRC
0.28 NFRC !`270 New Low E Ij
1 First Floor
41
Window .8.0
0.310 NFRC
0.28 NFRC 270 New Low E ;+
First Floor -
42
Window ,r 116.5.
0.310 NFRC
0.28 NFRC 270 New Low E
First Floor,
43
Window -!:! 16.5
0.310 NFRC
.0.28 NFRC 270 New 1LowE
First Floor
44
Window 16.5
0.310 NFRC
0.28 NFRC 270 New Low E
First Floor
45
Window 18.0
0.310 NFRC
0.28 NFRC 270 New Low E
First Floor
46
Window 18.0
0.310 NFRC
0.28 NFRC 270 New Low E
First Floor
47
Window 16.5
0.310 NFRC
0.28 NFRC 270 New Low E
First Floor
48
Window 16.5
0.310 NFRC
0.28 1 NFRC 270 New Low E
First Floor
(1) Ll -Factor Type:
2 SHGC Type:
116-A = Default Table from Standards, NFRC = Labeled Value
116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS.
_
ID
Exterior Shade Type
SHGC
Window
H t 7 Wd
Ove hang Left Fin Right Fin
Len H t LEA REA Dist Len H t Dist Len H t
33
Bug Screen
0.76
34
Bug Screen
0.76
35
Bug Screen
0.76
36
Bug Screen
0.76
37
Bug Screen
0.76
38
Bug Screen
0.76
39
Bug Screen
0.76
40
Bug Screen
0.76
41
Bug Screen
0.76
42
Screen
0.76
43
-Bug
Bug Screen
0.76
44
Bug Screen
0.76
45
Bug Screen
0.76
46
Bug Screen
0.76
47
Bug Screen
0.76
48
Bug Screen
0.76
Ener Pro 5.1 by Ener Soft
User Number: 8165
RunCode: 2013-11-21T15:55:24
ID: 63090 Page 6 of 8
Reg: 213-N0088594A-000000000-0000 Registration Date/Time: 2013/11/25 13:21:18 HERS Provider: CalCERTS, Inc
Electrgnically Filed by Gangyi Zhou and Authenticated at CalCERTS.com - 11/25/2013
'Electronically Signed at CalCERTS.com by Michael Rafferty (Hearthside Communities LLC) 11/25/2013
1
fL
t
U
L
77
IJ
1
J
1
CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF -1 R
Project Name
Reserve at the Citrus Lot 9
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
11112512013
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
FENESTRATION SURFACE DETAILS
ID Type Area U -Factor SHGC2
Azm Status Glazing Type Location/Comments
49 Window 16.5 0.310 NFRC 0.28 NFRC 270 New Low E First Floor
50 Window 8.0 0.310 NFRC 0.28 NFRC 270 New Low E First Floor
51 Window 27.5 0.310 NFRC 0.28 NFRC 270 New Low E First Floor
52 Window 24.0 0.310 NFRC 0.28 NFRC 270 New Low E FR DR First Floor
s
(1) U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
Window
ID Exterior Shade Type SHGC Hat Wd
Ove hang Left Fin Right Fin
Len H t LExt RExt Dist Len H t Dist Len H t
49 Bug Screen 0.76
50 Bug Screen 0.76
51 Bug Screen 0.76
52 Bug Screen 0.76
77,-, — (1t {IV IJ I
I C A �� I v, � ncPrT I
a•n
1� :OR
BY
Ener Pro 5.1 by Ener Soft User Number: 8165
RunCode: 2013-11 '21 -15.55.-24 _ ID:=63090---- - -l- Pae 7 of 8
Reg: 213-N0088594A-000000000-0000 Registration Date/Time: 2013/11/25 13:21:18 HERS Provider: CalCERTS, Inc
1
L
L
1
J
1
F.
t
Electronically Filed by Gangyi Zhou and Authenticated at CalCERTS.com - 11/25/2013
Electronically Signed at CalCERTS.com by Michael Rafferty (Hearthside Communities LLC) 11/25/2013
CERTIFICATE OF COMPLIANCE: Residential (Part 5 of 5) CF -1 R
Project Name
Reserve at the Citrus Lot 9
Building Type ❑ Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
11/25/201
BUILDING ZONE INFORMATION
System Name Zone Name
Floor Area ft
New Existing Altered Removed Volume Year Built
5 T 1st FLR
3,618 36,180
Totals 3,6181 0 0 0
HVAC SYSTEMS
System Name Qty. Heating Type
Min. Eff. Type Min. Eff. Thermostat Type Status
5 T 1 Central Furnace
--Cooling
—
80% AFUE Split Air Conditioner 13.0 SEER Setback New
y
j �
HVAC DISTRIBUTION
System Name Heating
'Duct Ducts
Cooling Duct Location R -Value Tested? Status
5 T Ducted
Ducted Attic, Ceiling Ins, vented 8.0 m New
WATER HEATING SYSTEMS
S stem Name
Qty.
Type
Distribution
Rated
Input
Btuh
Tank
Cap.
al
Energy
Factor
or RE
Standby
Loss or
Pilot
Ext.
Tank
Insul. R-
Value
Status
Takagi T -K2
1
Instant Gas
Kitchen Pipe Ins
199,000
0
0.84
n/a
n/a
New
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONIC
HEATING SYSTEM
PIPING
Control
Hot Water Piping Length
ft
o
Q c
G�' 0F�
,, „S stem_Name_Length
Pipe,P
j - Pipe
Diameter
Insul.
Thick.
Qty. HP
Plenum Outside Buried
❑t
❑ 1
,r-,' :- TRIS
— Iviv
M
Ener Pro 5.1 by Ener Soft User Number: 8165
RunCode: 2013-11-21715:55:24 ID: 63090 Pa e 8 of 8
IReg: 213-N0088594A-000000000-0000 Registration Date/Time: 2013/11/25 13:21:18 HERS Provider: CalCERTS, Inc
1
1
1
1
u
t
1
C
1
1
MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R
Project Name
Reserve at the Citrus Lot 9
Date
11112112013
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -6R Form.
§118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(1) when the
installation of a Cool Roof is specified on the CF -1 R Form.
*§150(a): Minimum R-19 insulation in wood -frame ceiling orequivalent U -factor.
§150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value.
*§1 50 c : Minimum R-13 insulation in wood -frame wall orequivalent U -factor.
*§150(d): Minimum R-13 insulation in raised wood -frame floor orequivalent U -factor.
150(f): Air retarding wrap is tested, labeled, and installed according to ASTM E1677-95 2000 when specified on the CF -1 R Form.
150 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150 e 1 A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5.
§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c).
§1500)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§1500)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
§1500)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of
recirculating sections of hot water pipes are insulated per Standards Table 150-13.
§1500)2: Cooling system piping (suction, chilled water, or brine Iines),and piping insulated between heating=source and indirect hot
water tank shall be insulated to Table 150-B and Equation 150-A. , , �, r-�R m\I ,p
§1500)2: Pipe insulation for steam hydronic heating systems or hot water sy'stems:515tipsi, meet" -tiie rbe direments-of Standards Table
123-A. �� .��,. �r, R, SAFE. t ULr
1500)3A: Insulation is protected from damage, including that due to sunlight, moisture, a ul - merit maintena cn e; and win, d.
§1 500)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retarda�o�s`enclgsedlentirely in
conditioned space. 1 FnR COQ 1
150(j)4: Solar water -heating systems and/or collectors are certified by the Soflar Rating and Certification Corporation.
DATE
EnergyPro 5.1 by EnergySoft User Number: 8165 RunCode: 2013-11-21715:55:24 /D: 63090 Page 11 of 13
L
1
r
t
1
u
1
1
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R
Project Name
Date
Reserve at the Citrus Lot 9
11112112013
§ r50(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150(m)1: Building cavities, support plafforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
1 50 m 7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150 m 10: Flexible ducts cannot have porous inner cores.
§150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
required in Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
150 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150
Residential Lighting Measures:
§150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is not a low efficacy luminaire asspecified by §150(k)2.
150(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d).
§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz.
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
medium screw -base socket.
150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k).
150(k)7: All switching devices and controls shall meet the requirements of §150(k)7.
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system;. and.all,permanently installed
luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility -rooms are;tiigh efficacy and'confrolled by a
manual -on occupant sensor. UA
§lu 0(kated erman installed lighting that is internal to cabinets shall use nomoor than 20�watts'-of.power per,iineat foot of
.ntly
icn
FOR CONST RUCTION
BY
nATF_ .�--� -
EnergyPro 5.1 by EnergySoft User Number: 8165 RunCode: 2013-11-21 T15. -55:24 ------ID 63090 Page 12 of 13
1
1
i
11
1
L
i
L
1
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R
Project Name
Date
Reserve at the Citrus Lot 9
11112112013
§150(k)l0: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a
manual -on occupancy sensor.
§150(k)l 1: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less
than 1000 square feet located on a residential site is not required to comply with §150 k 11.
§150(k)l2: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)l3: Luminaires providing outdoor lighting, including lighting for, private patios in low-rise residential buildings with four or more
dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
juminaires used to comply with Exceptionl to §150(k)l3 may be controlled by a temporary override switch which bypasses the motion
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be high efficacy luminaires.
§150(k)l4: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more than five watts of power as determined according to §130(d).
§150(k)l5: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
re uirements of Sections 130, 131, 134, and 146.
§150(k)l6: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided
that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
C► r 1( G LA Q J 9 MITA
BUILDING & SAFETY DEPT
APPROVED
FOR CONSTRUCTION
LS
DATE BY
EnergyPro 5.1 by EnergySoft User Number: 8165 RunCode: 2013-11-21715:55:24 ID: 63090 Page 13 of 13