BRES2015-0352 Title 241
BUILDING ENERGY ANALYSIS +REPORT
4'
PROJECT:
Bihari Residence
Lot 4 Traditions
La Quinta, CA 92253
Project Designer:
Helton Deford
17-411 Irvine Blvd.
Tustin, CA 92780
(909) 957-4550
Report Prepared by:
Tim Scott
Scott Design and Title 24 0NNA
77085 Michigan Dri e(;IV & SA�E� pEPT-
Palrn Desert, CA 92211gUILD 0VE-
_ (760) 200-4780 App �� -TION
FOR
DATE
Job Number:
Nov
,:�C��11N� MENS
Date:
�o
10/28/2015
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for,use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
w This program developed by EnergySoft, LLC —www.energysoft.com.
Ene Pro 6.7 6 Ene Soft User Number: 6712 ID:
CERTIOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE SHOD
Project Name: New Residence Calculation Daterrime: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis
Input File Name: Bihari Residence-Helton-Deford-15.xml
CIORF-01
Page 1 of 14
GENERAL INFORMATION
ENERGY USE SUMMARY
01
Project Name New Residence
04
05
02
Calculation Description Title 24 Analysis
08
Energy Use (kTDV/ft2-yr)
03
Project Location Lot 4 Traditions
Compliance Margin
Percent Improvement
04
City La Quinta
05
Standards Version Compliance 2015
06
Zip Code 92253
07
Compliance Manager Version SEMCmpMgr 20134 (744)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.6
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 180
12
Project Scope Newly Constructed
13
Number of Dwelling Units 1
14
Total Cond. Floor Area (ft) 6292
15
Number of Zones 5
16
Slab Area (ft2) 6292
17
Number of Stories 1
18
Addition Cond. Floor Area N/A
19
Natural Gas Available Yes
20
Addition Slab Area (ft2) N/A
21
Glazing Percentage (%) 26.8%
COMPLIANCE RESULTS
01 Building Complies with Computer Performa`nce"4 /r' " I F-`
02 This building incorporates features that require field-testing and/or venficatiomby a.certifiedliHERS rater under the supervision of a CEC-approved HERS provider.
+"� y LZ ,mkk _#5 i! ai_ t __._ ar wi k4 -i .«t rf 14 Y1 %1.' r+
03 This building incorporates one or,more Specpal R eaturesowbelow r=.. ;raw.
Registration Number: 215-N6296701B-000000000-0000 Registration Date/Time: 2015-10-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2015-10-28 15:25:15
ENERGY USE SUMMARY
04
05
06
07
08
Energy Use (kTDV/ft2-yr)
Standard Design
Proposed Design
Compliance Margin
Percent Improvement
Space Heating
4.75
5.23
-0.48
-10.1%
Space Cooling
125.54
119.62
5.92
4.7%
IAQ Ventilation
0.71
0.71
0.00
0.0%
Water Heating
4.08
4.55
-0.47
-11.5%
Photovoltaic Offset
—
0.00
0.00
—
Compliance Energy Total
135.08
130.11
4.97
3.7%
Registration Number: 215-N6296701B-000000000-0000 Registration Date/Time: 2015-10-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2015-10-28 15:25:15
CERTIOE OF COMPLIANCE -'RESIDENTIAL PERFORMANCE COMPLIANCE *HOD CIORF-01
Project Name: New Residence Calculation Daterrime: 15:23, Wed, Oct 28, 2015 Page 2 of 14
Calculation Description: Title 24 Analysis Input File Name: Bihari Residence-Helton-Deford-15.xmi
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Window overhangs and/or fins
HERS FEATURE SUMMARY
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
• Nigh Quality Insulation Installation (QII)
• IAQ mechanical ventilation
Cooling System Verifications:
• Minimum Airflow
• Verified EER
• Verified SEER
• Refrigerant Charge
• Fan Efficacy Watts/CFM "
HVAC Distribution System Verifications: f V
• Duct Sealing 1•!
Domestic Hot Water System Verifications:'. ,?-' -
-None—
ENERGY DESIGN RATING J
This is the sum of the annual TDV energy consumption forlenergy usee om'ponentslincluded in -the performance compliance app Mach fc�-lhe'standard Design Building (Energy Budget) and the annual
TDV energy consumption for lighting and components not>regulated by Title 24; PaftF6 (such as dorilestic=appliances`and consumer electronics) and accounting for the annual TDV energy offset by an
on-site renewable energy system. ® ' *_�o V I LW V
Reference Energy Use Energy Design Rating Margin Percent Improvement
Total Energy (kTDV/f2-yr)* 170.42 165.45, 4.97 2.9%
includes calculated Appliances and Miscellaneous Energy Use (AMEU)
BUILDING - FEATURES INFORMATION
01
02
03
04
05
06
07
Project Name
Conditioned Floor Area (ft2)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
New Residence
6292
1
4
5
0
1
Registration Number: 215-1462967018-000000000-0000 Registration Date/Time: 2015-10-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2015-10-28 15:25:15
CERTIE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCEtOD
Project ame: New Residence Ca culation Daterrime: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis Input File Name: Bihari Residence-Helton-Deford-15.xm1
C*RF-01
Page 3 of 14
ZONE INFORMATION
01
02
03
04
05
06
07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height
Water Heating System 1
Water Heating System 2
Kit Game room
Conditioned
HVAC 1 kit gamel
1471
9
DHW Sys 1
great bed 3
Conditioned
HVAC 2 great bed 32
1478
9
DHW Sys 1
master
Conditioned
HVAC 3 mster3
1352
9
DHW Sys 1
media
Conditioned
HVAC 4media4
884
9
DHW Sys 1
guest
Conditioned
HVAC 5 guest5
1107
9,
DHW Sys 1
t.
• F
AMCm*RT"p*H -'ERS-
Registration Number: 215N6296701B-000000000-0000. Registration Date/Time: 201510-2816:40:37
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CFIR-08252015-744
v
HERS Provider: CaICERTS inc.
Report Generated at: 2015-10-28 15:25:15
CERTIIPE OF COMPLIANCE -RESIDENTIAL PERFORMANCE COMPLIANCE COD
Project ame: New Residence Ca culation Date/Time: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis
Input File Name: Bihari Residence-Helton-Deford-15.xml
C*RF-01
Page 4 of 14
OPAQUE SURFACES
01
02
03
04
05
06
07
08
Name
Zone
Construction
Azimuth
Orientation Gross Area (ft2)
Window & Door Area (ft2)
Tilt (deg)
N Wall
Kit Game room
R-21 Wall (W.21.2x6.16)
0
Back
504
120
90
E Wall
Kit Game room
R-21 Wall (W.21.2x6.16)
90
Right
1100
315
90
S Wall
Kit Game room
R-21 Wall (W.21.2x6.16)
180
Front
200
90
W Wall
Kit Game room
R-21 Wall (W.21.2x6.16)
270
Left
1365
35.295
90
Roof
Kit Game room
R-38 Roof Attic
1471
N Wall 2
great bed 3
R-21 Wall (W.21.2x6.16)
0
Back
1104
260
90
E Wall 2
great bed 3
R-21 Wall (W.21.2x6.16)
90
Right
440
92
90
S Wall 2
great bed 3
R-21 Wall (W.21.2x6.16)
180
Front
1200
208
90
W Wall 2
great bed 3
R-21 Wall (W.21.2x6.16)
270
Left
600
24
90
Roof 2
great bed 3
R-38"Roof Attic
1478
N Wall 3
master
R-21 Wall (W.21.2x6.16)
0
Back
875
120.9
90
E Wall 3
master
R-21 Wall (W.21.2x6.16)
90
Right
90
78.3
90
S Wall 3
master
"^ �. R-�21aWalh(1N21{2x6tY6)'RY80
Front
280
24
90
W Wall 3
master
F: 21^Wall (1N21'2x'616)`
.f'�'� ;7 1k bt an S�
x`270
kt
ft
'Left s
400
6
90
Roof 3
master
h R=38%Roof Attie
f '"
D
�' t
1352
N Wall 4
media
k-,-21Walls(W.21 f2z6.16)
(*r 1
BaGi ;
300
48
90
E Wall 4
media
R-21 Wall (W.21.2x6.16)
90
Right
700
18
90
S Wall 4
media
R-21 Wall (W.21.2x6.16)
180
Front
700
18
90
W Wall 4
media
R-21 Wall (W.21.2x6.16)
270
Left
700
144
90
Roof 4
media
R-38 Roof Attic
884
N Wall 5
guest
R-21 Wall (W.21.2x6.16)
0
Back
800
120
90
E Wall 5
guest
R-21 Wall (W.21.2x6.16)
90
Right
1000
30
90
S Wall 5
guest
R-21 Wall (W.21.2x6.16)
180
Front
800
33.6
90
W Wall 5
guest
R-21 Wall (W.21.2x6.16)
270
1
Left
1000
37.8
90
Roof 5
guest
R-38 Roof Attic
1
1107
Registration Number: 215-N62967018-000000000-0000 Registration Date/Time: 2015-10-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2015-10-28 15:25:15
CERTIOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE &OD
Project Name: New Residence Calculation Date/Time: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis Input File Name: Bihari Residence-Helton-Deford-15.xmi
C*RF-01
Page 5 of 14 -
ATTIC
01
02
03
04
05
06
07
08
Name
Construction
Type
Roof Rise
Roof Reflectance
Roof Emittance
Radiant Barrier
Cool Roof
Attic Kit Game room
Attic RoofKit Game room
Ventilated
3
0.1
0.85
No
No
Attic great bed 3
Attic Roofgreat bed 3
Ventilated
3
0.1
0.85
No
No
Attic master
Attic Roofmaster
Ventilated
3
0.1
0.85
No
No
Attic media
Attic Roofinedia
Ventilated
3
0.1
0.85
No
No
Attic guest
Attic Roofguest
Ventilated
3
0.1
0.85
No
No
f `O'l C E RTS, -,I,. n
r
` HERS PROVIDEM
Registration Number: 215-N62967018-000000000-0000 Registration Date/Time: 201510-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2015-10-28 15:25:15
CERTI*E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE IkOD
Project Name: New Residence Ca culation Daterrime: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis
Input File Name: Bihari Residence-Helton-Deford-15.xmi
C*RF-01
Page 6 of 14
WINDOWS
01
02
03
04
05
06
07
08
09
10
Name
Type
Surface (Orientation -Azimuth)
Width (ft) Height (ft)
Multipli
er
Area
(ft2)
U -factor
SHGC
Exterior Shading
1K o
Window
N Wall (Back -0)
12.0
10.0
1
120.0
0.46
0.36
Insect Screen (default)
1 L o
Window
E Wall (Right -90)
9.0
10.0
1
90.0
0.46 1
0.36
Insect Screen (default)
1C o
Window
E Wall (Right -90)
22.5
10.0
1
225.0
0.46
0.36
Insect Screen (default)
106 f
Window
W Wall (Left -270)
3.0
2.0
1
6.0
0.39
0.24
Insect Screen (default)
107 f
Window
W Wall (Left -270)
3.0
2.0
1
6.0
0.39
0.24
Insect Screen (default)
108 f
Window
W Wall (Left -270)
2.5
4.5
1.004
11.3
0.39
0.24
Insect Screen (default)
109 f
Window
W Wall (Left -270)
3.0
2.0
1
6.0
0.39
0.24
Insect Screen (default)
110 f
Window
W Wall (Left -270)
3.0
2.0
1
j 6.0
0.39
0.24
Insect Screen (default)
1 M o
Window
N Wall 2 (Back -0)
20.0
10.0
1
200.0
0.46
0.36
Insect Screen (default)
1N o
Window
N Wall 2 (Back -0)
6.0
10.0
1
60.0
0.46
0.36
Insect Screen (default)
1 DD o
Window
E Wall 2 (Right -90)
2.5
8.0
1
20.0
0.46
0.36
Insect Screen (default)
1 D o
Window
E Wall 2 (Right -9 1 . t 9:0 f, 8.0
1
72.0
0.46
0.36
Insect Screen (default)
1A o
Window
S Wall 2 (Fr ntt-180) €« 4':0
L 9.0
1
J f1j) %'`36.0
0.46
0.36
Insect Screen (default)
1 B o
Window
�N S 1Nallr2-(Frontx,180) ` .
13.0
P k40-0
Ll
U 1 U X130 0
0.46
0.36
Insect Screen (default)
105 f
Window
S Wall 22 (Front 180)> <
4:0'1
t ` 4�,-5
n g:
X18.0
0.39
0.24
Insect Screen (default)
111 f
Window
N Wall 3 (Back -0)
-
-
1
2.3
0.39
0.24
Insect Screen (default)
112 f
Window
N Wall 3 (Back -0)
-
-
1
2.3
0.39
0.24
Insect Screen (default)
113f
Window
N Wall 3 (Back -0)
-
--
1
2.3
0.39
0.24
Insect Screen (default)
1P o
Window
N Wall 3 (Back -0)
-
-
1
72.0
0.46
0.36
Insect Screen (default)
115f
Window
N Wall 3 (Back -0)
-
-
1
12.0
0.39
0.24
Insect Screen (default)
116f
Window
N Wall 3 (Back -0)
--
-
1
18.0
0.39
0.24
Insect Screen (default)
117f
Window
N Wall 3 (Back -0)
--
-
1
12.0
0.39
0.24
Insect Screen (default)
118f
Window
E Wall 3 (Right -90)
-
-
1
2.3
0.39
0.24
Insect Screen (default)
1Q o
Window
E Wall 3 (Right -90)
-
-
1
20.0
0.46
0.36
Insect Screen (default)
119f
Window
E Wall 3 (Right -90)
--
-
1
12.0
0.39
0.24
Insect Screen (default)
120 f
Window
E Wall 3 (Right -90)
-
--
1
12.0
0.39
0.24
Insect Screen (default)
121 f
Window
E Wall 3 (Right -90)
-
-
1
12.0
0.39
0.24
Insect Screen (default)
1 R o
Window
E Wall 3 (Right -90)
-
-
1
20.0
0.46
0.36
Insect Screen (default)
129 f
Window
S Wall 3 (Front -180)
-
--
1
24.0
0.39
0.24
Insect Screen (default)
Registration Number: 215-N6296701B-000000000-0000 Registration Date/Time: 201510-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2015-10-28 15:25:15
CERTI E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE HOD
Project ame: New Residence a , ation DatelTime: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis
Input File Name: Bihari Residence-Helton-Deford-15.xm1
C*RF-01
Page 7 of 14
114 f
Window
W Wall 3 (Left -270)
-
-
1
6.0
0.39
0.24
Insect Screen (default)
1T o
Window
N Wall 4 (Back -0)
6.0
8.0
1
48.0
0.32
0.24
Insect Screen (default)
123 f
Window
E Wall 4 (Right -90)
2.0
3.0
1
6.0
0.24
0.18
Insect Screen (default)
124 f
Window
E Wall 4 (Right -90)
2.0
3.0
1
6.0
0.24
0.18
Insect Screen (default)
125 f
Window
E Wall 4 (Right -90)
2.0
3.0
1
1 6.0
0.24
0.18
Insect Screen (default)
126 f
Window
S Wall 4 (Front -180)
2.0
3.0
1
6.0
0.24
0.18
Insect Screen (default)
127 f
Window
S Wall 4 (Front -180)
2.0
3.0
1
6.0
0.24
0.18
Insect Screen (default)
128 f
Window
S Wall 4 (Front -180)
2.0
3.0
1
6.0
0.24
0.18
Insect Screen (default)
11.10
Window
W Wall 4 (Left -270)
18.0
8.0
1
144.0
0.32
0.24
Insect Screen (default)
1TT o
Window
N Wall 5 (Back -0)
-
-
1
20.0
0.46
0.36
Insect Screen (default)
1 W o
Window
N Wall 5 (Back -0)
-
-
1
64.0
0.46
0.36
Insect Screen (default)
130 f
Window
N Wall 5 (Back -0)
-
-
1
36.0
0.39
0.24
Insect Screen (default)
131 f
Window
E Wall 5 (Right -90)
-
-
1
6.0
0.39
0.24
Insect Screen (default)
1X o
Window
E Wall 5 (Right -90)
-
-
1
24.0
0.46
0.36
Insect Screen (default)
132 f
Window
S Wall 5 (Front -180)
-
-
1
6.0
0.39
0.24
Insect Screen (default)
133 f
Window
. " S V%11-5'(Front-180) /:,-M t: ar I�
-
1
13.8
0.39
0.24
Insect Screen (default)
134 f
Window
S Wall 5 (Front X80) t r
--
?-11) -f3.8
0.39
0.24
Insect Screen (default)
1 V o
Window
W 1Nell 5;(Left-'270)°jam-L,
U 1 t
t X24"0
0.46
0.36
Insect Screen (default)
133 f 2-
Window
W WAS1,51(-4K2707.4 ?
-^ 1 z
1" 1
13.8
0.39
0.24
Insect Screen (default)
DOORS
01
02
03
04
Name
Side of Building
Area (ft2)
U -factor
1AA
S Wall 2
24.0
0.50
1EE
W Wall 2
24.0
0.50
Registration Number: 215-N6296701B-000000000-0000 Registration Date/Time: 2015-10-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2015-10-28 15:25:15
CERTIOE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCEtOD
Project Name: New Residence Calculation Date/Time: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis
Input File Name: Bihari Residence-Helton-Deford-15.xml
CRF -01
Page 8 of 14
OVERHANGS AND FINS
01
02
03
04
05 06
07
08 09
10
11
12
13
14
Overhang
Left Fin
Right Fin
Window
Depth
Dist Up
Left
Extent
Right
Extent Flap Ht.
Depth
Top Up Distl-
Bot Up
Depth
Top Up
Dist R
Bot Up
1Ko
10
0.1
10
10 0
0
0 0
0
0
0
0
0
11-o
10
0.1
10
10 0
0
0 0
0
0
0
0
0
1co
10
0.1
10
10 0
0
0 0
0
0
0
0
0
106f
8
0.1
8
8 0
0
0 0
0
0
0
0
0
107f
8
0.1
8
8 0
0
0 0
0
0
0
0
0
108f
8
0.1
8
8 0
0
0 0
0
0
0
0
0
109f
8
0:1
8
8 0
0
0 0
0
0
0
0
0
110f
8,
0.1
8
8 0
0
0 0
0
0
0
0
0
1M o
18 '
0.1
18
18 0
0
0 0
0
0
0
0
0
1N o
7-18
0.1
18 _
18 0
0
0 0
0
0
0
0
0
1DDo
118
0.1
j8
n 18,E 00--1'�� r'
0p 0
0
0
0
0
0
1D o
18
0.1
18p
1�8 0d
111 0
Oil Oft
0
0
0
0
0
1A o
r18
g
\#0.1
i ,�8t►-a�
{1
i
l� `1'8�i 1�.� ��
1� 0t+�r �# Oil I I E 0" t
0
0
0
0
0
113o
rr'18
`N 0;1
&18C
r.18C r in
f'0, 6"1
0 On
0
0
0
0
0
105 f
18
O.1.
"18
� X18' � 0 � '
`6
V d'" V.— e `
0
0
0
0
0
1To
10
0.1
10
10 0
0
0 0
0
0
0
0
0
123f
6
0.1
6
6 0
0
0 0
0
0
0
0
0
124f
6
0.1
6
6 0
0
0 .0
0
0
0
0
0
125f
6
0.1
6
6 0
0
0 0
0
0
0
0
0
126f
6
0.1
6
6 0
0
0 0
0
0
0
0
0
127f
6
0.1
6
6 0
0
0 0
0
0
0
0
0
128f
6
0.1
6
6 0
0
0 0
0
0
0
0
0
1uo
10
0.1
10
10 0
0
0 0
0
0
0
0
0
Registration Number: 215-N6296701B-000000000-0000 Registration Date/Time: 2015-10-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2015-10-28 15:25:15
CERTI&E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE.HOD
Project Name: New Residence Calculation DatefTime: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis
Input File Name: Bihari Residence-Helton-Deford-15.xm1
CORF-01
Page 9 of 1.4
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
07
02
03
04
05
Total Cavity
Winter Design
Name
Construction Name
Surface Type
Construction Type
Framing
R -value
U -value
Assembly Layers
Kit Game room
1471
125
None
0.8
No
• Cavity/ Frame: no insul. /2x4 Top Chrd
great bed 3
1478
200
2x4 Top Chord of Roof Truss @ 24
0.8
No
Roof Deck: Wood Siding/sheathing/decking
Attic RoofKit Game room
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
media
884
106
None
0.8
No
• Inside Finish: Gypsum Board
guest
Ceilings (below
144
None
0.8
No
Cavity/Frame: R-9.1 /2x4
R-38 Roof Attic
attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 38
0.025
Over Floor Joists: R-28.9 insul.
• Inside Finish: Gypsum Board
• Cavity / Frame: R-21 / 2x6
• Exterior Finish: Wood
R-21 Wall (W.21.2x6.16)
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
0.066
Siding/sheathing/decking
• Cavity/ Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roofgreat bed 3
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
-
Cavity/ Frame: no insul. / 2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck. Wood Siding/sheathing/decking
Attic Roofmaster
Attic Roofs
Wood Framed;Ceiling
fm�O.C, � f
none •
0.644
Roofing: Light Roof (Asphalt Shingle)
tCavity
2x4 Top Chord of Roof Truss @ 24
)flnoJ
/ Frame: no insul. / 2x4 Top Chrd
Roof Deck. Wood Siding/sheathing/decking
Attic Roofinedia
Attic Roofs
4
Wood Fra med-CeiIi g
in O.0 U It
0:644
Roofing: Light Roof (Asphalt Shingle)
t
K► e K U
V I U 1=
ff.
Cavity/ Frame: no insul. / 2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roofguest
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
SLAB FLOORS
01
02
03
04
05
06
07
Name
Zone
Area (ft)
Perimeter (ft)
Edge Insul. R -value & Depth
Carpeted Fraction
Heated
Covered Slab
Kit Game room
1471
125
None
0.8
No
Covered Slab 2
great bed 3
1478
200
None
0.8
No
Covered Slab 3
master
1352
110
None
0.8
No
Covered Slab 4
media
884
106
None
0.8
No
Covered Slab 5
guest
1107
144
None
0.8
No
Registration Number: 215-N6296701B-000000000-0000 Registration Date/Time: 2015-10-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2015-10-28 15:25:15
CERTIIPE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE WOD
Project ame: New Residence ation Date/Time: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis Input File Name: Bihari Residence-Helton-Deford-15.xml
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04
` Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage CFM50
Required Not Required Not Required —
C*RF-01
Page 10 of 14
WATER HEATING SYSTEMS
01
02,E
01
02 03
04 05 06
Name
System Type Distribution Type
Water Heater Number of Heaters Solar Fraction (%)
DHW Sys 1 - 1/2
DHW Pipe Insulation, All Lines
DHW Heater 1 2 .0%
WATER HEATERS
..1�
01
02,E
03 04
05
06
07
08
F r Z 4-..o v 5 I-
Ix
Recirculation
Tank Exterior
Name
Pipe Insulation
`�
Tank Volume
Energy Factor or
Distribution
Insulation
Standby Loss
Name
Heater Element Type
Tank Type (gal)
Efficiency
Input Rating
R -value
(Fraction)
DHW Heater 1
Natural. Gas ' –
Small Storage 50
0.66
40000-Btu/hr
0
0
rip* if It
WATER HEATING - HERS VERIFICATION,, •
/ 1�'' �»
01
�02�
'V 6
`03" `04
YID Mi/ -w •#+ ellc fey � .fM. t A 'R f4�.
M `05
tAd /Ftir
06
07
F r Z 4-..o v 5 I-
Ix
Recirculation
Central DHW
Name
Pipe Insulation
Parallel Piping Compact Distribution
Point -of Use
Control
Distribution
DHW Sys 1-1/2
—
— —
—
—
—
r
Registration Number: 215-N6296701B-000000000-0000 Registration Date/Time: 2015-10-2816:40:37
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744
HERS Provider: CaICERTS inc.
Report Generated at: 2015-10-28 15:25:15
CERTIIPE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCEtIOD
Project ame: New Residence Caation Date/Time: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis
Input File Name: Bihari Residence-Helton-Deford-15.xmi
CI.RF-01
Page 11 of 14
SPACE CONDITIONING SYSTEMS
01
02
03
04
05
06
SC Sys Name
System Type
Heating Unit Name
Cooling Unit Name.
Fan Name
Distribution Name
:Heat Pump System 1:Air Distribution System
Heat Pump Heating and
Heat Pump System 1
Heat Pump System 1
HVAC Fan 1
Air Distribution System 1
1:HVAC Fan 1:2
Cooling System
Verification
Heat Pump System 1
_
d #I 9
:Heat Pump System 2:Air Distribution System
Heat Pump Heating and
Heat Pump System 2
Heat Pump System 2
HVAC Fan 2
Air Distribution System 2
2:HVAC Fan 2:2
Cooling System
1 r
:Heat Pump System 3:Air Distribution System
Heat Pump Heating and
Heat Pump System 3
Heat Pump System 3
HVAC Fan 3
Air Distribution System 3
3:HVAC Fan 3:2
Cooling System
1
'r►
Cpl' t
� C
12.5'
:Heat Pump System 4:Air Distribution System
Heat Pump Heating and
Heat Pump System 4
Heat Pump System 4
HVAC Fan 4
Air Distribution System 4
4:HVAC Fan 4:2
Cooling System
16
:Heat Pump System 5:Air Distribution System
Heat Pump Heating and
Heat Pump System 5
Heat Pump System 5
HVAC Fan 5
Air Distribution System 5
5:HVAC Fan 5:2
Cooling System
No
No
Heat Pump System
3 -hers -cool
Heat Pump System 4
HVAC - HEAT PUMPS
01
'` �-� '02 ,,
03 04 05
06 07
08
09
10
Heating
j
'W Cooling
Zonally
Multispeed
HERS
Name
q .Type}}{{HS}aPF/51 -,COP,,
p 4C7pplS)EER
EERY
Controlled
Compressor
Verification
Heat Pump System 1
i r
%-SplitHeatPump
d #I 9
58000
0
56000
�' 16
� �
M2.5.
' No
No
Heat Pump tem
1 r
�
1 -hers -cool
✓
;;oll
1
'r►
Cpl' t
� C
12.5'
Yes
No
Heat Pump System
Heat Pump System 2
SplitHeatPump
9
58000
56000
16
2 -hers -cool
Heat Pump System 3
SplitHeatPump
9
58000
56000
16
12.5
No
No
Heat Pump System
3 -hers -cool
Heat Pump System 4
SplitHeatPump
9.5
36400
36400
17
13.3
No
No
Heat Pump System
4 -hers -cool
Heat Pump System 5
SplitHeatPump
9
58000
56000
16
12.5
No
No
Heat Pump System
5 -hers -cool
Registration Number: 215-N62967016-000000000-0000 Registration Date/Time: 2015-10-2816:40:37
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-08252015-744
HERS Provider: CaICERTS inc.
Report Generated at: 2015-10-28 15:25:15
CERTI#E OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE OOD
Project Name: New Residence Calculation Date/Time: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis
Input File Name: Bihari Residence-Helton-Deford-15.xml
CF•RF-01
Page 12 of 14
HVAC COOLING - HERS VERIFICATION
01
02
03
04
05
01
02
03
04
05
06
Name
Verified Airflow
Airflow Target
Verified EER
Verified SEER
Verified Refrigerant
Charge
Heat Pump System 1 -hers -cool
Required
350
Required
Required
Required
Heat Pump System 2 -hers -cool
Required
350
Required
Required
Required
Heat Pump System 3 -hers -cool
Required
350
Required
Required
Required
Heat Pump System 4 -hers -cool
Required
350
Required
Required
Required
Heat Pump System 55 -hers -cool
Required
350
Required
Required
Required
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
Name
Type
Duct Leakage
Insulation R -value
Duct Location
Bypass Duct
HERS Verification
Air Distribution System 1
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
1 -hers -dist
Air Distribution System 2
DuctsAttic
Sealed. and tested
8
Attic
None
Air Distribution System
2 -hers -dist
Not Required
Not Required
I1 r—,—,�
—
it
Required
6.0
Air Distribution System 3
DuctsAttJ/Sealed
#( #;r 4L_
and tested
i,�
t
8Attic
Air Distribution System 4 -hers -dist
�'
None
Air Distribution System
Not Required
Not Required
Not Required
g�
Air Distribution System 5 -hers -dist
Required
6.0
Not Required
3 -hers -dist
Not Required
Not Required
—
Af
"'
Attic.
None
Air Distribution System
Air Distribution S stem 4
y
DuctsAttic
Sealed and tested
+�
8
�' � �
4 -hers -dist
�
Air Distribution System 5
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
5 -hers -dist
HVAC DISTRIBUTION - HERS VERIFICATION
01
02
03
04
05
06
07
08
Name
Duct Leakage
Verification
Duct Leakage
Target (%)
Verified Duct
Location
Verified Duct
Design
Buried
Ducts
Deeply Buried
Ducts
Low -leakage
Air Handler
Air Distribution System 1 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
—
Air Distribution System 2 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
—
Air Distribution System 3 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
—
Air Distribution System 4 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
—
Air Distribution System 5 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
—
Registration Number: 215-N6296701B-000000000-0000 Registration Date/Time: 201510-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2015-10-28 15:25:15
CERTI'PE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE�OD
Project
'PE
New Residence Ca culation Daterrime: 15:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis Input File Name: Bihari Residence-Helton-Deford-15.xml
C*RF-01
Page 13 of 14
HVAC -FAN SYSTEMS
01
02
01
01
02
03
04
Name
Type
Fan Power (Watts/CFM)
HERS Verification
HVAC Fan 1
Single Speed PSC Furnace Fan
0.58
HVAC Fan 1 -hers -fan
HVAC Fan 2
Single Speed PSC Furnace Fan
0.58
HVAC Fan 2 -hers -fan
HVAC Fan 3
Single Speed PSC Furnace Fan
0.58
HVAC Fan 3 -hers -fan
HVAC Fan 4
Single Speed PSC Furnace Fan
0.58
HVAC Fan 4 -hers -fan
HVAC Fan 5
Single Speed PSC Furnace Fan
0.58
HVAC Fan 5 -hers -fan
HVAC FAN SYSTEMS - HERS VERIFICATION
01
02
01
02
03
Name "
Verified Fan Watt Draw
Required Fan Efficiency (Watts/CFM)
HVAC Fan 1 -hers -fan
Required
0.58
HVAC Fan 2 -hers -fan 1
Required
0.58
HVAC Fan 3 -hers -fan - -
- _ Required
0.58
HVAC Fan 4-hers-fanRe�quirgd
11111111110 000 A
0.58
HVAC Fan 5 -hers -fan: -
Required'"'
0.58
IAQ (Indoor Air Quality) FANS
01
02
'� 03 a. �"'" 'd"*04
05
06
Dwelling Unit
IAQ CFM
IAQ Watts/CFM IAQ Fan Type
IAQ Recovery
Effectiveness(%)
HERS Verification
SFam IAQVentRpt
100.42
0.25 Default
0
Required
PROJECT NOTES
Traditions Country Club
Registration Number: 215-N6296701B-000000000-0000 Registration Date/Time: 201510-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 Report Generated at: 2015-10-28 15:25:15
CERTI#E OF COMPLIANCE -RESIDENTIAL PERFORMANCE COMPLIANCE POD
Project ame: New Residence ation Date/Time: 1.5:23, Wed, Oct 28, 2015
Calculation Description: Title 24 Analysis
Input File Name: Bihari Residence-Helton-Def6rd-15.xml
CRF -01
Pa e14of14
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Tim Scott
Company:
Signature Date:
Scott Design and Title 24, Inc..
2015-10-28 16:40:37
Address:
CEA/HERS Certification Identification (If applicable):
77085 Michigan Drive
City/State/Zip:
Phone:
Palm Desert, CA 92211
760-200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. I am eligible under Division 3 of the Businks and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.% '
building design features system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
3. The or
worksheets, calculations, plans and specifications_ submitted tto�the enforcement a-gency�for approval -with this _building perkmit application.
Responsible Designer Name: f gg'Re'sponsible
Tim Scott 1 /fi'! LL
Designer Signature:
C# T�
Company: i rIt:
%j
Date Signed:
�, .i! V
16.40:37
Scott Design and Title 24, Inc.
2015-10-28
Address:
License:
77085 Michigan Drive
na
City/State/Zip:
Phone:
Palm Desert, CA 92211
760-200-4780
Digitally signed by Ca10ERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration Provider responsibility for the accuracy of the '
information.
Registration Number: 215-N6296701B-000000000-0000 Registration Date/Time: 201510-28 16:40:37 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-08252015-744 C Report Generated at: 2015-10-28 15:25:15
1�
C
RESIDENTIAL MEASURES SUMMARY'
RMS -1
Project Name
Bihari Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration 11012812015
Date
Project Address
Lot 4 Traditions La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floorddition
Area
6,292
A
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity (ft)
Special Features Status
Roof Wood Framed Attic
R38 6,292
New
Wall Wood Framed
R 21 12,425
New
Slab Unheated Slab -on -Grade
- no insulation 6,292
Perim = 685'
New
Demising Wood Framed
R 13 2,730
New
Door Opaque Door
- no insulation 48
New
FENESTRATION
Orientation Area ft
I Total Area: 1,685 Glazing Percentage: 26.8%1New/Altered
U -Fac SHGC Overhang Sidefins
Average U -Factor: 0.43
Exterior Shades Status
Rear(N) 120.0
0.460
0.36 10.0
none
Bug Screen New
Right (E) 315.0
0.460
0.36 10.0
none
Bug Screen New
Left (1M 35.3
0.390
0.24 8.0
none
Bug Screen New
Rear (N) 260.0
0.460
0.36 18.0
none
Bug Screen New
Right (E) 92.0
0.460
0.36 18.0
none
Bug Screen New
Front (S) 166.0
0.460
0.36 18.0
none
Bug Screen New
Front (S) 18.0
0.390
0.24 18.0
none
Bug Screen New
Rear (N) 84.9
0.390
0.24 none
none
Bug Screen New
Rear (N) 156.0
0.460
0.36 none
none
Bug Screen New
Right (E) 44.3
0.390
0.24 none
none
Bug Screen New
Right (E) 64.0
0.460
0.36 none
none
Bug Screen New
Front (S) 57.6
0.390
0.24 none
none
Bug Screen New
Left (tM 19.8
0.390
0.24 none
none
Bug Screen New
Rear (N) 48.0
0.320
0.24 10.0
none
Bug Screen New
HVAC SYSTEMS
Qty. Heating
Min. Eff
Cooling
Min. Eff
Thermostat Status
1 Split Heat Pump
9.00 HSPF
Split Heat Pump
16.0 SEER
Setback
New
1 Split Heat Pump
9.00 HSPF
Split Heat Pump
16.0 SEER
Setback
New
1 Split Heat Pump
9.00 HSPF
Split Heat Pump
16.0 SEER
Setback
New
HVAC DISTRIBUTION
Location Heating
Cooling Duct Location
Duct
R -Value Status
HVAC 1 kit game Ducted
Ducted Attic
8.0
New
HVAC 2 great bed 3 Ducted
Ducted Attic
8.0
New
HVAC 3 mster Ducted
Ducted Attic
8.0
New
WATER HEATING
Qty. Type
Gallons Min. Eff
Distribution Status
2 Small Storage Gas
50
0.66
All Pipes Ins
New
EnemyPro 6.7 by Ene Soft User Number: 6712
Run Code: 2015-10-28715:25:53
ID:
Pae 17 of 44
C
•
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
Bihafi Residence
Building Type 12 Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
California Energy Climate Zone Total Cond. Floor Area Addition
CA Climate Zone 15 6,292 n/a
Date
11012812015
# of Units
1
Project Address
Lot 4 Traditions La Quinta
INSULATION
Construction Type
Area
Cavity (ft) Special Features
Status
FENESTRATION
Orientation Area(ft)
I Total Area: 1,685 Glazing Percentage: 26.8 New/Altered Average U -Factor:
U -Fac SHGC Overhang Sidefins Exterior Shades
0.43
Status
Right (E) 18.0
0.240 0.18 6.0 none Bug Screen
New
Front (S) 18.0
0.240 0.18 6.0 none Bug Screen
New
Left (IM 144.0
0.320 0.24 10.0 none Bug Screen
New
Left (Vtoq 24.0
0.460 0.36 none none Bug Screen
New
HVAC SYSTEMS
Qty. Heating
Min. Eff Cooling Min. Eff Thermostat
Status
1 Split Heat Pump
9.50 HSPF Split Heat Pump 17.0 SEER Setback
New
1 Split Heat Pump
9.00 HSPF Split Heat Pump 16.0 SEER Setback
New
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value
Status
HVAC 4 media Ducted
Ducted Attic 8.0
New
HVAC 5 guest Ducted
Ducted Attic 8.0
New
WATER HEATING
Qty. Type
Gallons Min. Eff Distribution
Status
EnemyPro6.7 by EnemySoft User Number., 6712 RunCode: 2015-10-28T15:25:53 /D:
Pae 18 of 44
4
2013 .,ow -Rise Residential Mandatory Measures Summary
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the
compliance approach used. Exceptions may aDDly. Review the respective code section for more information.
Building Envelope Measures:
§I 10.6(a)1:
Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§ 110.6(a)5:
Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC and infiltration that meets the requirements of 10-111 a .
§ 110.7:
Exterior doors and windows are weatherstripped; all joints and penetrations are caulked and sealed.
§ 110.8(a):
Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R.
§ 110.8(i):
The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of §I 10.8(1) when the
installation of a cool roof is specified on the CFI R.
§ 110.80):
A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CF1R.
Minimum R-30 insulation in wood -frame ceiling; or the weighted average U -factor shall not exceed 0.031. Minimum R-19 in a
§ I50.0(a):
rafter roof alteration. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The
attic access shall be gasketed to prevent air leakage.
§I50.0(b):
Loose fill insulation shall conform with manufacturer's installed design labeled R -value.
§ 150.0(c):
Minimum R-13 insulation in 2x4 inch wood framing wall or have a U -factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U -
factor).
§ I50.0(d):
Minimum R-19 insulation in raised wood -frame floor or 0.037 maximum U -factor.
In Climate Zones 14 and 16 a Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior
§150.0(g)l:
walls, vented attics and unvented attics with air -permeable insulation.
In Climate Zones 1-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class II
§ 150.0(g)2:
vapor retarder.
In a building having a controlled ventilation crawl space, a Class I or Class II vapor retarder shall be placed over the earth floor of
.§ I50.0(g)3:
the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section
150:0 d .
§ 150.0(1):
Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%;
have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration;
and when installed as part of a heated slab floor meets the requirements of § 110.8
§ 150.0(q):
Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U -
factor of 0.58; or the weighted average U -factor of all fenestration shall not exceed 0.58.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
§150.0(e)IA:
Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150.0(e)1B:
Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a readily accessible operable, and tight -fitting damper or a combustion -air control device.
§ 150.0(e)I C:
Masonry or factory -built fireplaces have a flue damper with a readily accessible control.
§150.0(e)2:
Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside
of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110.0-§110.3:
HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified to the Energy Commission.
§I 10.3(c)5:
Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation
valve, and recirculation loop connection requirements of § 110.3(c)5.
Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appli-
§110.5:
ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool
and spa heaters.
§ I50.0(h)1:
Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified
in §150.0(h)2.
§ 150.0(h)3A:
Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any
dryer vent.
§ I50.0(i):
Heating systems are equipped with thermostats that meet the setback requirements of § 110.2(c).
§150.00)]A:
Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§ 150.00)1 B:
Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, have R-12 external
insulation or R -I6 internal insulation where the internal insulation R -value is indicated on the exterior of the tank.
For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage
tank, all piping with a nominal diameter of 3/4 inch or larger, all piping associated with a domestic hot water recirculation system
§ 150.00)2A:
regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and
all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3-
A.
§ I50.00)2B:
All domestic hot water pipes that are buried below grade must be installed in a water proof and non -crushable casing or sleeve
that allows for installation, removal, and replacement of the enclosed pipe and insulation.
4
2013 Low -Rise Residential Mandatory Measures Summary
§I50.00)2C:
Pipe for cooling system lines shall be insulated as specified in §150.00)2A. Piping insulation for steam and hydronic heating
systems or hot waters stems with pressure > 15 psig shall meet the requirements in TABLE 120.3-A.
§ 150.00)3:
Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For
§150.00)3A:
example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or
painted with coating that is water retardant and provides shielding from solar radiation that degrades the material.
Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I
§ I50.00)3B:
or Class II vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class II vapor
retarder.
Systems using gas or propane water heaters to serve individual dwelling units shall include: a 120V electrical receptacle within 3
feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the
§ 150.0(n)1:
space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed
water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000
Btu/hr.
§ I50.0(n)2:
Recirculating loops serving multiple dwelling units shall meet the requirements of § 110.3(c)5.
§ I50.0(n)3:
Solar water -heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC)
or by a testing agency approved by the Executive Director.
Ducts and Fans Measures:
All air -distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC §601.0, §602.0,
§603.0, §604.0, §605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition.
Supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC
§605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed
§150.0(m)1:
with mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B or
aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than ''A inch, the
combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums
defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying
conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms
shall not be compressed to cause reductions in the cross-sectional area of the ducts.
Factory -Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; joints
§ I50.0(m)2:
and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is
used in combination with mastic and draw bands.
§ I50.0(m)3-6:
Field -Fabricated Duct Systems shall comply with requirements for: pressure -sensitive tapes, mastics, sealants, and other
requirements specified for duct construction; duct insulation R -value ratings; duct insulation thickness; and duct labeling.
§150.0(m)7:
All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic
dampers.
§ 150.0(m)8:
Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers
except combustion inlet and outlet air openings and elevator shaft vents.
Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not
§ I50.0(m)9:
limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum,
sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is
water retardant and provides shielding from solar radiation.
§150.0(m)10:
Flexible ducts cannot have porous inner cores.
When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be
§I50.0(m)11:
sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference
Residential Appendix RA3.
Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal
§I50.0(m)12:
conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of
150.0(m) 12.
Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the
placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The
§ 150.0(m)13:
space conditioning system must also demonstrate airflow> 350 CFM per ton of nominal cooling capacity through the return
grilles, and an air -handling unit fan efficacy:5 0.58 W/CFM as confirmed by field verification and diagnostic testing, in
accordance with Reference Residential Appendix RA3.
Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode,
§ 150.0(m)15:
an airflow from the dwelling, through the air handler fan and delivered to the dwelling, of>_ 350 CFM per ton of nominal cooling
capacity, and operating at an air -handling unit fan efficacy of:5 0.58 W/CFM as confirmed by field verification and diagnostic
testing, in accordance with Reference Residential Appendix RA3.
All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of
§ 150.0(0):
central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the
Whole Building Ventilation.
§I50.0(o)IA:
Whole Building Ventilation airflow shall be confirmed through field verification and diagnostic testing, in accordance with
Reference Residential Appendix RA3.
Pool and Spa Heating Systems and Equipment Measures:
Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
§ 110.4(a):
Regulations; an on-off switch mounted outside of the heater that allows shutting off the heater without adjusting the thermostat
setting; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating.
2013 Low -Rise Residential Mandatory Measures Summary
§I 10.4(b)1:
Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction
and return lines, or built-up connections for future solar heating.
§ 110.4(b)2:
Outdoor pools or spas that have a heat pump or gas heater shall have a cover.
§ 110.4(6)3:
Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro -
rammed to run only during off-peak electric demand periods.
§ 110.5:
Natural gas pool and spa heaters shall not have a continuous burning pilot light.
§150.0(p):
Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements.
Lighting Measures:
§ 110.9:
All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of § 110.9.
§I50.0(k)IA:
Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with §150.0(k) in accordance with TABLE
150.0-A or TABLE 150.0-13, as applicable.
§ 150.0(k)I B:
When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply
with the applicable provisions of § 150.0(k).
The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with
§1 50.0(k)]C:
§ 130.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has
been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180
watts of low efficacy lighting er electrical box.
§I50.0(k)ID:
Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz.
Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no
§I50.0(k)IE:
more than 5 watts of power per luminaire or exhaust fan as determined in accordance with §130.0(c). Night lights do not need to
be controlled by vacancy sensors.
§I50.0(k)IF:
Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable
requirements of §150.0(k).
§ 150.0(k)2A:
High efficacy luminaires must be switched separately from low efficacy luminaires.
§I50.0(k)2B:
Exhaust fans shall be switched separately from lighting systems.
§ I50.0(k)2C:
Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF.
§I50.0(k)2D:
Controls and equipment are installed in accordance with manufacturer's instructions.
§ 150.0(k)2E:
No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with § 150.0(k).
§ 150.0(k)2F:
Lighting controls comply with applicable requirements of § 110.9.
An Energy Management Control System (EMCS) may be used to comply with dimmer requirements if: it functions as a dimmer
§ I50.0(k)2G:
according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements of §130.5; and all other
requirements in §150.0(k)2.
An Energy Management Control System (EMCS) may be used to comply with vacancy sensor requirements of § 150.0(k) if: it
§ ] 50.0(k)2H:
functions as a vacancy sensor according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements
of § 130.5; and all other requirements in § 150.0(k)2.
§ 150.0(k)2I:
A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the
functionality of a dimmer according to 110.9, and complies with all other applicable requirements in §150.0(k)2.
§ I50.0(k)3A:
A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only
§ 150.0(k)3B:
the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are
considered kitchen lighting if they are not separately switched from kitchen lighting.
§ ] 50.0(k)4:
Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated
cabinet.
§150.0(k)5:
A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom
shall be high efficacy or controlled by vacancy sensors.
§150.0(k)6:
Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§I50.0(k)7:
Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high
efficacy, or shall be controlled by either dimmers or vacancy sensors.
Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other
nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0
CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing
§150.0(k)8:
and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and
allow ballast maintenance and replacement without requiring cutting holes in the ceiling.
For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with §150.0(k), the ballasts
shall be certified to the Energy Commission to comply with the applicable requirements in § 110.9.
For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the
same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and
§ I50.0(k)9A:
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically
reactivates the motion sensor within 6 hours; and
iii. Controlled by one of the following methods:
4
4
2013 Low -Rise Residential Mandatory Measures Summary
0
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is
programmed to automatically turn the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of
an astronomical time clock in accordance with §110.9; meets the Installation Certification requirements in §130.4; meets the
requirements for an EMCS in §130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically turn the outdoor lighting OFF during daylight hours.
For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor
lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
§150.0(k)9B:
following requirements:
i. Shall comply with § I50.0(k)9A; or
ii. Shall comply with the applicable requirements in §110.9, §130.0, §130.2, §130.4, 140.7 and §141.0.
§ I50.0(k)9C:
For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by § 150.0(k)9B or 150.0(k)9D
shall comply with the applicable requirements in $110.9 § 130.0, § 130.2, § 130.4, § 140.7 and § 141.0.
§ 150.0(k)9D:
Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply
with the applicable requirements in § 110.9, § 130.0, $130.2, § 130.4, § 140.7 and § 141.0.
§150.0(k)10:
Internally illuminated address signs shall comply with § 140.8; or shall consume no more than 5 watts of power as determined
according to § 13 0.0 c .
§I50.0(k)11:
Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for
nonresidential garages in § 110.9 § 130.0 § 130.1 § 130.4 § 140.6, and § 141.0.
In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of
§150.0(k)12A:
the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20
percent of the floor area, permanently installed lighting in that building shall:
§150.0(k)12B:
i. Comply with the applicable requirements in §110.9, §130.0, §130.1, §140.6 and §141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
ingress and egress.
Solar Ready Buildings:
Single family residences located in subdivisions with ten or more single family residences and where the application for a
§ 110.10(a)1:
tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January 1, 2014,
shall comply with the requirements of § 110.10 b through § 110.10 e .
§110.10(a)2:
Low-rise multi -family buildings shall comply with the requirements of §110.10 b through §110.10(d).
The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway, smoke
ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a
local jurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than
80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for
§110.10(b)1:
buildings with roof areas greater than 10,000 square feet.
For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less
than 250 square feet. For low-rise multi -family buildings the solar zone shall be located on the roof or overhang of the building or
on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the
building project and have a total area no less than 15 percent of the total roof area of the building excluding any skylight area.
§ 110.10(b)2:
All sections of the solar zone located on steep -sloped roofs shall be oriented between 110 degrees and 270 degrees of true north.
§ 110.10(b)3A:
No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be
located in the solar zone.
Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice
§ 110.10(b)3B:
the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the
horizontal projection of the nearest point of the solar zone measured in the vertical plane.
§ 110.10(b)4:
For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly
indicated on the construction documents.
The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit
§ 110.10(c):
from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water -heating
system.
§ 110.10(d):
A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through § 110.10(c)
shall be provided to the occupant.
§110.10(e)1:
The main electrical service panel shall have a minimum busbar rating of 200 amps.
The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a
§ 110.10(e)2:
future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or
main circuit location, and permanently marked as "For Future Solar Electric'.
0
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
ihari Residence
Date
10/28/2015
System Name
HVAC 1 kit game
Floor Area
1,471
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL
CFM
2,087
221
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 58,000
25,869
2,101 2,322
27,235
Total Output Btuh 58,000
0
Output Btuh/s ft 39.4
1,493
1,041
Cooling System
0
0
Output per System 56,500
9,698
3,225 221
10,687
Total Output Btuh 56,500
0
5,326
0
Total Output Tons 4.7
1,493
1,041
Total Output Btuh/s ft 38.4
Total Output s ft/Ton 312.4
1 38,554
40,005
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
25HCB660-FV4CNB006
37,478 11,883
36,225
Airflow cfmis ft 1.36
Airflow cfm/Ton 424.8
Outside Air %
11.0%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
1 TIME OF SYSTEM PEAK
37,478 11,883 36,225
Aug 3 PM Jan 1 AM
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 66 OF.
Outside Air
221 cfm Supply Fan
2,000 cfm
72 OF
d
66 OF 84 OF
Heating Coil
,
A .. A.
83 OF
ROOM )"
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F 75/64°F 75/64°F 58/57°F
Outside Air Ar
221 cfm Supply Fan Cooling Coil
2,000 cfm
71/62°F
58 / 57 OF
62.7% ROOM
70/62°F
EnergyPro 6.7 by EnergySoR User Number: 6712 Run Code: 2015-10-28T15:25:53 ID: Page 23 of 44
r
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
ihari Residence
Date
10/28/2015
System Name
HVAC 2 great bed 3
Floor Area
1,478
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 2,122
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 222
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 58,000
26,226
2,111 2,825
32,520
Total Output Btuh 58,000
0
Output Btuh/s ft 39.2
1,514
1,243
Cooling System
0
0
Output per System 56,500
9,742
3,230 222
10,715
Total Output Btuh 56,500
0
1,514
1 38,995 5,341
0
Total Output Tons 4.7
1,243
Total Output Btuh/s ft 38.2
Total Output s ft/Ton 313.9
45,722
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
25HCB660-FV4CNB006 37,485 11,896
36,225
Airflow cfm/s ft
1.35
Airflow cfm/Ton
424.8
Outside Air %
11.1 %
Total Adjusted System Output 37,485 11,896
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK Aug 3 PM
36,225
Outside Air cfm/s ft 0.15
-Note: values above given at ARI conditions
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 66 OF
Outside Air C+
222 cfm Supply Fan
2,000 cfm
71 OF
66 OF 83 OF
Heating Coil 83 OF
ROOM ffi
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F 75/64°F 75/64°F 58/57°F
Outside Air
222 cfm Supply Fan Cooling Coil 58 / 57 OF
2,000 cfm
62.7% ROOM
71/62°F 70/62°F
EnergyPro 6.7 by EnergySoff User Number: 6712 Run Code: 2015-10-28715:25:53 ID: Page 24 of 44
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
ihari Residence
Date
10/28/2015
System Name
HVAC 3 mster
Floor Area
1,352
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,221
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 203
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 58,000
16,152
1,931 1,350
16,919
Total Output Btuh 58,000
0
Output(Bt uh/s ft 42.9
932
647
Cooling System
0
0
Output per System 56,500
8,970
3,159 203
9,862
Total Output Btuh 56,500
0
932
26,987 5,090
0
Total Output Tons 4.7
647
Total Output Btuh/s ft 41.8
Total Output s ft/Ton 287.2
28,075
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
25HCB660-FV4CN8006 37,296 11,667
36,225
Airflow cfmis ft
1.48
Airflow cfm/Ton 424.8
Outside Air % 10.1 %
Total Adjusted System Output 37,296 11,667
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK Aug 3 PM
36,225
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 67 OF
10-0=
Outside Air
203 cfm Supply Fan
2,000 cfm
72 OF
67 OF 84 OF
LE
Heating Coil 84 OF
ROOM
72 OF
J =
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F 75/63°F 75/63°F 57/56°F
Outside Air Ar
203 cfm Supply Fan Cooling Coil 58 / 56 OF
2,000 cfm 61.4% ROOM
70 / 61 OF 70 / 61 OF
EnergyPro 6.7 by EnergySoff User Number: 6712 RunCode: 2015-10-28715:25:53 ID: Page 25 of 44
4
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
ihari Residence
Date
10/28/2015
System Name
HVAC 4 media
Floor Area
884
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
( Supply Air Ducts
TOTAL SYSTEM LOAD
COIL
CFM
415
133
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output perSystem 36,400
12,789
1,263 1,312
16,462
Total Output Btuh 36,400
0
Output Btuh/s ft 41.2
738
629
Cooling System
0
0
Output perSystem 56,500
5,845
5,060 133
6,422
Total Output Btuh 56,500
0
6,323
0
Total Output Tons 4.7
738
629
Total Output Btuh/s ft 63.9
Total Output s ft/Ton 187.8
20,111
24,143
Air System
CFM perSystem
1,200
HVAC EQUIPMENT SELECTION
Airflow cfm
1,200
Carrier 25HNB636-FV4CNB006
44,280 0
22,734
Airflow cfm/s ft
1.36
Airflow cfmfTon
254.9
Outside Air %
11.1 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
44,280 0 22,734
Aug 3 PM Jan 1 AM
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 66 OF
Outside Air Ar -
133 cfm Supply Fan
1,200 cfm
72 OF
66 OF 84 OF
Heating Coil
84 OF
ROOM
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F 75/57°F 75/57°F 40/39°F
Outside Air
133 cfm Supply Fan Cooling Coil
1,200 cfm
71 /54°F
41 / 39 OF
31.8% ROOM
70/53°F
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2015-10-28715:25:53 ID: Page 26 of 44
r
14
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
ihari Residence
Date
10/28/2015
System Name
HVAC 5 guest
Floor Area
1,107
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,353
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 166
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output er System 58,000
18,858
1,581 1,778
23,444
Total Output Btuh 58,000
0
'
Output Btuh/s ft 52.4
1,089
896
Cooling System
0
0
Output per System 56,500
7,332
2,827 166
8,054
Total Output Btuh 56,500
0
1 1,089
1 28,367 4,408
1 0
Total Output Tons 4.7
896
Total Output Btuh/s ft 51.0
Total Output s ft/Ton 235.1
133,291
Air System
CFM per System
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
25HCB660-FV4CNB006 37,394 10,995
36,225
Airflow cfm/s ft 1.81
Airflow cfm/Ton 424.8
Outside Air % 8.3%
Total Adjusted System Output 37,394 10,995
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK Aug 3 PM
36,225
Outside Air cfm/s ft 0.15
Note: values above given at ARI conditions
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 68 OF
Outside Air
166 cfm Supply Fan
2,000 cfm
72 OF
68 OF 85 OF
Heating Coil 84 OF
ROOM
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F 74/63°F 74/63°F 56/56°F
0'
Outside Air ..�
166 cfm Supply Fan Cooling Coil 57 / 56 OF
' 2,000 cfm
59.5% ROOM
71/61°F 70/61°F
EnergyPro 6.7 by EnergySoft User Number: 6712 Run Code: 2015-10-28715:25:53 ID: Page 27 of 44
•
ROOM HEATING PEAK LOADS
Project Name
Bihari Residence
Date
10/28/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Kitchen and Game Room
Floor Area 1,471.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value OT'F
0.0260 X 46 =
0.0690 X 46 =
0.4600 X 46 c
0.3900 X 46 =
0.7300 X 46 =
0.1020 X 0 c
X =
X
X =
X
X =
X
X c
X =
X =
X
X =
X =
X
X =
X =
X =
X
X c
X
X
X
X
X
X =
X =
another room Page Total
9.00 X 0.266 /60] X 46
Height ACH AT
Btu/hr
R-38 Roof Attic
1,471.0
1,759
R-21 Wall (W.21.2x6.16)
2,698.7
8,566
Low-E.46.36o
435.0
9,205
Low -E.39.24 f
35.3
633
Slab -On -Grade
perim = 125.0
4,198
'R-13 Wall
516.0
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,471 X
Area
24,360
_ 2,875
TOTAL HOURLY HEAT LOSS FOR ROOM 27,235
EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2015-10-28T15:25:53 ID: Page 33 of 44
ROOM HEATING PEAK LOADS.
Project Name
Bihari Residence
Date
10/28/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great room and Bedroom 3
Floor Area 1,478.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U -Value
X 0.0260
X 0.0690
X 0.4600
X 0.5000
X 0.3900
X 0.7300
X 0.1020
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
to another room
9.00 X 0.266
Ceiling Height ACH
AT *F
X 46
X 46
X 46
X 46
X 46
X 46
X 0
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Page Total
/60] X
AT
Btu/hr
= 1,768
c 8,760
= 10,961
0 1,104
_ 323
= 6,716
= 0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
_
=
=
=
=
=
=
29,632
46 = 2,889
R-38 Roof Attic
1,478.0
R-21 Wall (W.21.2x6.16)
2,760.0
Low -E.46.36 o
518.0
Wood Door
48.0
Low -E.39.24 f
18.0
Slab -On -Grade
perim = 200.0
"R-13 Wall
711.0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,478 X
Area
TOTAL HOURLY HEAT LOSS FOR ROOM 32,520
EnergyPro 6.7 by EnergySoft User Number: 6712 Run Code: 2015-10-28715:25:53 fD: Page 34 of 44
r1
ROOM HEATING PEAK LOADS
Project Name
Bihari Residence
Date
10/28/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master Bedroom
Floor Area 1,352.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area U -Value
1,352.0 X 0.0260 X
1,415.8 X 0.0690 X
117.2 X 0.3900 X
112.0 X 0.4600 X
Perim = 110.0 X 0.7300 X
612.0 X 0.1020 X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
through an interior surface to another room
X 1,352 X 9.00 X 0.266
Area Ceiling Height ACH
OT'F Btu/hr
46 = 1,617
46 = 4,494
46 _ 2,103
46 c 2,370
46 = 3,694
0 c 0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
c
=
=
=
=
=
=
Page Total 14,277
/60] X 46 = 2,642
AT
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
Low -E.39.24 f
Low-E.46.36o
Slab -On -Grade
'R-13 Wall
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 16,919
EnergyPro 6.7 by EnergySoR User Number: 6712 RunCode: 2015-10-28715:25:53 /D: Page 35 of 44
r1
U
17J
C
ROOM HEATING PEAK LOADS
Project Name
Bihad Residence
Date
10/28/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Media Room
Floor Area 884.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
884.0 X
2,172.0 X
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
AT *F
Btu/hr
= 1,057
= 6,894
= 2,826
c 397
= 3,559
c 0
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
14,734
46 c 1,728
R-38 Roof Attic
0.0260
46
R-21 Wall (W.21.2x6.16)
0.0690
46
MEDIA Low -E..32.24 o
192.0
X
0.3200
46
MEDIA Low -E..24.18 f
36.0
X
X
X
X
0.2400
46
Slab -On -Grade
perim = 106.0
0.7300
46
'R-13 Wall
416.0
0.1020
0
X
X
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Items shown with an asterisk(') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface to
X 884 X
Area Ceiling
another room
9.00 x 0.266
Height ACH
Page Total
/60] X
AT
TOTAL HOURLY HEAT LOSS FOR ROOM 16,462
EnergyPro 6.7 by EnergySoft User Number., 6712 RunCode: 2015-10-28715:25:53 ID: Page 36 of 44
•
1�
ROOM HEATING PEAK LOADS
Project Name
Bihari Residence
Date
10/28/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Rooms
Floor Area 1,107.0 ft-
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT *F
46 c
Btu/hr
R-38 Roof Attic
1,107.0
0.0260
1,324
R-21 Wall (W.21.2x6.16)
3,378.6
0.0690
46
=
=
10,724
Low -E.46.36 o
132.0
0.4600
46
2,793
Low -E.39.24 f
89.4
0.3900
46
=
c
=
=
1,604
Slab -On -Grade
perim = 144.0
0.7300
46
4,836
'R-13 Wall
475.0
0.1020
0
0
=
=
=
=
=
=
=
=
=
=
=
=
=
o
=
=
=
=
=
=
Page Total
/60] X 46
AT
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 1,107 X
Area
another room
9.00 X 0.266
Height ACH
21,280
= 2,164
TOTAL HOURLY HEAT LOSS FOR ROOM 23,444
EnergyPro 6.7 by EnergySoft User Number., 6712 Run Code: 2015-10-28715:25:53 /D: Page 37 of 44
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
' Bihari Residence
ROOM INFORMATION DESIGN CONDITIONS
Room Name Kitchen and Game Room Outdoor Dry Bulb Temperature
Floor Area 1,471.0 ft2 Outdoor Wet Bulb Temperature
Indoor Dry Bulb Temperature 70 OF Outdoor Daily Ranqe:
C
ODaaue Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
'R-13 Wall
Orientation
(IM
(N)
(E)
(S)
(Vtq
10/28/2015
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,471.0
0.0260
56.0
384.0
0.0690
23.0
785.0
0.0690
33.0
200.0
0.0690
26.0
1,329.7
0.0690
33.0
516.01
0.1020
0.0
6.0
16.7
+
0.0
31.0
11.3
16.7
+
0.0
31.0
6.0
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
lK o
1Lo
1Co
106 f
107 f
108 f
109 f
110f
Internal Gain
Orientation
Shaded
Area
X
X
X
X
X
X
X
X
X
GLF
Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
22.6
+
+
+
+
120.0
22.6
71.1
22.6
18.9
43.9
177.7
22.6
47.3
43.9
6.0
16.7
0.0
31.0
6.0
16.7
+
0.0
31.0
11.3
16.7
+
0.0
31.0
6.0
16.7
+
0.0
31.0
6.0
16.7
+
0.0
31.0
+
Page Total
112 OF
78 OF
34 OF
Btu/hr
2,142
609
1,787
359
3,028
7,
Btulhr
2,707
2,434
6,086
100
100
189
100
100
1 11,8171
4.4 Occupants X 245 Btuh/occ. 1,0
1,471 Floor Area X 0.50 w/sgft = 2,5
Infiltration: 1.064 X 0.94 X 60.67 X 42 = 2,536
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 25,869
Latent Gain Btu/hr
Occupants 4 4 Occupants X 1551 Btuh/occ. = 684
Infiltration: 4.771 X 0.94 X 60.67 X 0.00523 = 1,417
Air Sensible CFM ELA OW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 684
I EnerovPro 6.7 by EnerovSoft User Number: 6712 Run Code: 2015-10-28715:25:53 ID: Paae 38 of 44 1
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Bihari Residence
1 10/28/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Great room and Bedroom 3
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,478.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
R-38 Roof Attic
(W) 1,478.0 X 0.0260
X
56.0 =
2,152
R-21 Wall (W.21.2x6.16)
(N) 844.0 X 0.0690
X
23.0 =
1,339
R-21 Wall (W.21.2x6.16)
(E) 348.0 X 0.0690
X
33.0 =
792
R-21 Wall (W.21.2x6.16)
(S) 992.0 X 0.0690
X
26.0 =
1,780
Wood Door
(S) 24.0 X 0.5000
X
26.0 =
312
R-21 Wall (W.21.2x6.16)
(149 576.0 X 0.0690
X
33.0 =
1,312
Wood Door
(tM 24.0 X 0.5000
X
33.0 =
396
'R-13 Wall
711.0 X 0.1020
X
0.0 =
0
X J
X I=
Page Total
8,083
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
1 M o
(N) 0.0 X 22.6 +
200.0 X
22.6 =
4,512
1No
(N) 0.0 X 22.6 +
60.0 X
22.6 =
1,354
IDD o
(E) 20.0 X 22.6 +
0.0 X
43.9 =
451
i 1 D o
(E) 72.0 X 22.6 +
0.0 X
43.9 =
1,624
lA o
(S) 36.0 X 22.6 +
0.0 X
22.6 =
812
1B 0
(S) 136.0 X 22.6 +
0.0 X
22.6 =
2,933
105 f
(S) 18.0 X 16.7 +
0.0 X
16.8 =
301
X +
X
=
X + I
X
=
Page Total
11,986
Internal Gain
Btulhr
Occupants
4 4 Occupants X 245
Btuh/occ.
=
1,086
Equipment
1,478 Floor Area X 0.50
w/sgft
=
2,522
Infiltration: 1.064
X 0.94 X 60.96 X 42 =
2,548
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
26,226
Latent Gain
Btu/hr
Occupants
4 4 Occupants X 155
Btuh/occ.
=
687
Infiltration: 4.771
X 0.94 X 60.96 X 0.00523 =
1,424
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
687
EnerqyPro 6.7 by Ene Soft
User Number: 6712 RunCode: 2015-10-28715:25:53 ID:
Page 39 of 44
I
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Bihad Residence
ROOM INFORMATION DESIGN CONDITIONS
Room Name Master Bedroom Outdoor Dry Bulb Temperature
Floor Area 1,352.0 ft2 Outdoor Wet Bulb Temperature
Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranae:
Ooaaue Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W..21.2x6.16)
'R-13 Wall
Orientation
I'm
(N)
(E)
(S)
(M
10/28/2015
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,352.0
0.0260
56.0
754.1
0.0690
23.0
11.7
0.0690
33.0
256.0
0.0690
26.0
394.0
0.0690
33.0
612.0
0.1020
0.0
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
111 f
112 f
113 f
1Po
115 f
116 f
117f
118 f
1Qo
Orientation
(N)
(N)
(N)
(N)
(N)
(N)
(N)
(E)
(E)
112 OF
78 OF
34 OF
Btu/hr
1,969
1,197
27
459
897
0
1 4,5481
Shaded
Area
GLF
X 16.7
X 16.7
X 16.7
X 22.6
X 16.7
X 16.7
X 16.7
X 16.7
X 22.6
+
+
+
+
+
+
+
+
+1
Unshaded
Area
GLF
X 16.7
X 16.7
X 16.7
X 22.6
X 16.7
X 16.7
X 16.7
X 31.0
X 43.9
Page Total
=
=
=
=
=
=
=
=
=
0.0
2.3
0.0
2.3
0.0
2.3
0.0
72.0
0.0
12.0
0.0
18.0
0.0
12.0
0.0
2.3
0.0
20.0
Btu/hr
38
38
38
1,624
200
301
200
71
1 3,3911
Internal Gain Btu/hr
Occupants 41 Occupants X 245 Btuh/occ. 994
Equipment 1,352 Floor Area X 0.50 w/sgft = 2,307
Infiltration: 1.064 X 0.94 X 55.76 X 42 = 2,331
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 16,152
Latent Gain Btu/hr
Occupants 41 Occupants X 155 Btuh/occ. = 629
Infiltration: 4,771 X 0.94 X 55.76 X 0.00523 = 1,302
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
I EnerovPro 6.7 by EneravSoft User Number. 6712 RunCode: 2015-10-28T15:25:53 ID: Paae 40 of 44 1
r�
U
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Bihari Residence
1 10/28/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Master Bedroom
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,352.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X L
X
=
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
119f
(E) 0.0X 16.7+
12.0X
31.0=
371
120 f
(E) 0.0 X 16.7 +
12.0 X
31.0 =
371
121f
(E) 0.0 X 16.7 +
12.0 X
31.0 =
371
1 R o
(E) 0.0 X 22.6 +
20.0 X
43.9 =
879
129 f
(S) 0.0 X 16.7 +
24.0 X
16.8 c
402
114 f
(VV) 0.0 X 16.7 +
6.0 X
31.0 =
186
X +
X
=
X +
X
=
X +1
X
=
Page Total
2,581
Internal Gain
Btu/hr
Occupants
41 Occupants X 2451
Btuh/occ.
=
994
Equipment
1,352 Floor Area X 0.50
w/sgft
Infiltration: 1.064
X 0.94 X 55.76 X 42 =
2,331
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
16,152
Latent Gain
Btu/hr
Occupants
41 Occupants X 155
Btuh/occ.
=
629
Infiltration: 4,771
X 0.94 X 55.76 X 0.00523 =
1,302
Air Sensible
CFM ELA OW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
629
Energypro 6.7 by Ene Soft
User Number., 6712 Run Code: 2015-10-28715:25:53 ID:
Page 41 of 44
fl
An
qP
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Bihari Residence 1 10/28/2015
ROOM INFORMATION DESIGN CONDITIONS
Room Name Media Room Outdoor Dry Bulb Temperature 112 °F
Floor Area 884.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF I Outdoor Daily Range: 34 OF
Ooaaue Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W..21.2x6.16)
R-21 Wall (W..21.2x6.16)
R-21 Wall (W..21.2x6.16)
-R-13 Wall
Orientation
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
884.01
0.0260
56.0
252.0
0.0690
23.0
682.0
0.0690
33.0
682.0
0.0690
26.0
556.0
0.0690
33.0
416.0
0.1020
0.0
Page Total
Items shown with an asterisk (') denote conduction,through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
Fenestration Orientation Area GLF Area
1To
123 f
124 f
125 f
126 f
127 f
128 f
1Uo
Internal Gain
0.0
X
X
X
X
X
X
X
X
X
15.3
+
+
+
+
+
+
+
+
+
48.0
6.0
6.0
6.0
6.0
6.0
6.0
11.5
0.0
11.5
0.0
11.5
0.0
11.5
0.0
11.5
0.0
11.5
0.0
142.2
15.3
1.8
GLF
Btu/hr
1,287
400
1,553
1,224
1,2661
0
1 5,7291
X 15.3 =
X 22.2 =
X 22.2 =
X 22.2 =
X 11.5 =
X 11.5 =
X 11.5 c
X 29.6 c
X =
Page Total
Btu/hr
735
69
69
69
69
69
69
Z230
Occupants 2.7 Occupants X 245 Btuh/occ. = 650
Equipment 884 Floor Area X 0.50 W/sgft = 1,509
Infiltration: 1.064 X 0.94 X 36.46 X 42 = 1,524
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 12,786
Latent Gain
Occupants 2 7 Occupants X 155 Btuh/occ.
Infiltration: 4,771 X 0.94 X 36.46 X 0.00523 =
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
Btu/hr
= 411
852
411
C
•
171
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Bihari Residence 10/28/2015
ROOM INFORMATION DESIGN CONDITIONS
Room Name Guest Rooms Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,107.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Daily Ranqe: 34 OF
Ooaaue Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
-R-13 Wall
Orientation
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
1,107.0
0.0260
56.0
680.0
0.0690
23.0
970.0
0.0690
33.0
766.4
0.0690
26.0
962.2
0.0690
33.0
475.0
0.1020
0.0
16.8
0.0
13.8
X
16.8
0.0
13.8 X
24.0 X
I
0.0
43.9
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
I Fpnpstratinn
1 TT o
1Wo
130 f
131 f
1X o
132 f
133 f
134 f
1Vo
Oripntatinn
(N)
(N)
(N)
(E)
(E)
(S)
(S)
(S)
W
Btu/hr
1,612
1,079
2,209
1,375
2,191
1 8,4651
Shaded
Area
X
X
X
X
X
X
X
X
GLF
22.6 +
22.6 +
16.7+
16.7 +
22.6 +
16.7 +
16.7 +
16.7 +
22.6 +
Unshaded
Area
20.0 X
64.0 X
GLF
=
=
=
=
=
=
=
=
0.0
22.6
0.0
22.6
0.0x
36.0X
16.7=
0.0
6.0
X
X
31.0
0.0
24.0
43.9
0.0
6.0
X
16.8
0.0
13.8
X
16.8
0.0
13.8 X
24.0 X
16.8
0.0
43.9
Page Total
1 Gain
its
3.3
Occupants
!nt
1,107
Floor Area
X 245 Btuh/occ.
X 0.50 w/sqft
I Infiltration: 1.064 X 0.94 X 45.66 X 42 =
Air Sensible CFM ELA AT
Btu/hr
451
1,444
601
186
1,054
101
231
231
1,054
Btu/hr-
814
= 1,8891,889
I 1.909
I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 18,8581
Latent Gain
Occupants 3 3 Occupants X 155 Btuh/occ.
Infiltration: 4,771 x 0.94 x 45.66 x 0.00523 =
Air Sensible CFM ELA OW
)URLY LATENT HEAT GAIN FOR ROOM
7 by EnergySott User Number: 6712 Run
Btu/hr
= 515
1,066
515
Am
r,1
L-A
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Bihari Residence
1 10/28/2015
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Guest Rooms
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,107.0 ft--
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U -Factor
CLTD'
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
0
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
133 f
0.0 X 16.7 +
13.8 X 31.0
= 427
X +
X
=
X +
X
=
X +
X
=
Ix +
X
=
X +
X
=
X +
X
=
X +
X
=
X1 +1
X
=
Page Total
42
Internal Gain
Btu/hr
Occupants
33 Occupants X 245
Btuh/occ. =
814
Equipment
1,107 Floor Area X 0.50
w/ggft
=
1,889
Infiltration: 1.064
X 0.94 X 45.66 X 42 =
1,909
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
18,858
Latent Gain
Btu/hr
Occupants
3 3 Occupants X 155
Btuh/occ. =
515
Infiltration: 4,771
X 0.94 X 45.66 X 0.00523 —
11066
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
515
6
EneMyPro 6.7 by EnemySoft
User Number. 6712 RunCode: 2015-10-28715:25:53 ID:
Page 44 of 44