Loading...
BRES2016-0220 Title 24I BUILDING ENERGY ANALYSIS REPORT PROJECT: Timothy Ellenz Residence 54671 Avenida Diaz La Quinta, CA 92253 Project Designer: California Window & Door, Inc 75091 St. Charles Place, Suite G Palm Desert, CA 92211 760-773-1053 Report Prepared by: Jack LaFontaine Energy Management Services 41-485 Adams Street, Unit C Bermuda Dunes, CA 92203 760-360-4631 Job Number: 09172016 Date: 9/19/2016 1 CITY OF LA QUINTA BUILDING & T, &SAFETY DEP The EnergyPro computer program has been used to perform the calculations summarized in this dbmpl�nck �e l� ISE0 r n has a roval and is authorized by the California Energy Commission for use with both the Residential and Nonr6-sLenIiiE7&nMt tfllrp Efficiency tandards. This program developed by EnergySoft, LLC www.energysoft.com. ►LL�I�� TABLE OF CONTENTS Cover Page Table of Contents Form CF -1 R -PRF -01-E Certificate of Compliance Form RMS -1 Residential Measures Summary Form MF -1 R Mandatory Measures Summary HVAC System Heating and Cooling Loads Summary CITY O F LA Q l� I NTA BUILDING & SAFETY DEPT APPROVE® FOR CONSTRUCTION DATE BY EnergyPro 6.7 by Energysoft Job Number: ID: 09172016 User Number: 5021 1 2 3 11 12 16 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Ellenz Residence—La Quinta Calculation Datefrime: 12:06, Mon, Sep 19, 2016 Calculation Description: Title 24 Analysis Input File Name: Ellenz_LaQuinta.xml CF1 R -PRF -01 Page 1 of 8 GENERAL INFORMATION ENERGY USE SUMMARY 01 Project Name Ellenz Residence—La Quinta 14 5 02 Calculation Description Title 24 Analysis 08 (kTDV/ff2-yr) 03 Project Location 54671 Avenida Diaz Compliance Margin Percent Improvement 04 City La Quinta 05 Standards Version Compliance 2015 06 Zip Code 92253 07 Compliance Manager Version BEMCmpMgr 2013-4 (744) 08 Climate Zone CZ15 09 Software Version EnergyPro 6.6 10 Building Type Single Family 11 Front Orientation (deg/Cardinal) 270 12 _. Project Scope Addition and/or Alteration 13 Number of Dwelling Units 1 14 Total Cond. Floor Area (ft2) 1266 15 �Q/ Number of Zones 1 16 Slab Area (ft2) 0 17�(/v Number of Stories 1 18 Addition Cond. Floor Area 0 ,�9'� Natural Gas Available No 20 Addition Slab Area (ft2) 0 T �1 Glazing Percentage (%) 17.8% AW COMPLIANCE RESULTS 01 Building Complies with Computer Performance 02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider. Aft (Cid 1611V .y Registration Number: Registration Date/Time: HERS Provider: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-04072016-744 Report Generated at: 2016-09-19 12:07:35 ENERGY USE SUMMARY 14 5 06 07 08 (kTDV/ff2-yr) Standard Design Proposed Design Compliance Margin Percent Improvement Heating �' 2.27 1.14 1.13 49.8% Cooling 138.78 119.95 18.83 13.6% ntilation ri► 0.00 0.00 0.00 0.0% Heating wW 29.19 14.12 15.07 51.6% Laic Offset I ---- 0.00 0.00 ---- Energy Total �^�� 170.24 135.21 35.03 20.6% .y Registration Number: Registration Date/Time: HERS Provider: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-04072016-744 Report Generated at: 2016-09-19 12:07:35 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Ellenz Residence—La Quinta Calculation Description: Title 24 Analysis Calculation Datefrime: 12:06, Mon, Sep 19, 2016 Input File Name: Ellenz_LaQuinta.xml REQUIRED SPECIAL FEATURES The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis. NO SPECIAL FEATURES REQUIRED HERS FEATURE SUMMARY CF1 R -PRF -01 Page 2of8 The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is provided in the building components tables below. 02 17V Building -level Verifications: 04 • — None -- 06 Cooling System Verifications: 90 • Minimum Airflow - • Verified EER Avg. Ceiling • Verified SEER Number of Water Heating Systems • Fan Efficacy Watts/CFM Conditioned Floor Area ( 2)> HVAC Distribution System Verifications: �® • Duct Sealing Cooling Systems Domestic Hot Water System Verifications: - • — None 1 ENERGY DESIGN RATING This is the sum of the annual TDV energy consumption for energy use components included4n the performance compliance approach for the Standard Design Building (Energy Budget) and the annual TDV energy consumption for lighting and components not regulated by Title 24, Part 6 (such was domestic appliances and consumer electronics) and accounting for the annual TDV energy offset by an on-site renewable energy system. S Reference Energy Useg/ Energy Design Rating MarginPercent Improvement /f2 -yr)• 239.26 W 1204.23 135.03 114.6% v irtAudes calculate�p ' c s and Miscellaneous Energy Use (AMEU) ®� M' -n , -- —4 Aft ILDING Tl ikT1FlIF§RMATION 11,4*v n In 02 17V 03 04 05 06 07 90 4' Number of Dwelling Zone Floor Area Avg. Ceiling Number of Ventilation Number of Water Heating Systems P�) a Conditioned Floor Area ( 2)> Units Number of Bedrooms Number of Zones Cooling Systems Water Heating System 2 enz Re en a uint 1266 4*1 1 3 1 0 1 I I l_ lilt. 1 1 K_ E INFOAl; O Awl OD % 02 � 03 04 05 06 07 > Zone Floor Area Avg. Ceiling - Zone Name ZoneAType HVAC System Name (ft) Height Water Heating System 1 Water Heating System 2 Conditioned Heat Pump Split 15 seerl 1266 9 DHW Sys 1 SO Registration Number: �► CA Building Energy Efficiency Stands 2013 Residential Compliance Registration Date/Time: Report Version - CF1R-04072016-744 HERS Provider: Report Generated at: 2016-09-19 12:07:35 CERTIFICATE OF COMPLIANCE -RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Ellenz Residence -La Quinta Calculation Date/Time: 12:06, Mon, Sep 19, 2016 Calculation Description: Title 24 Analysis Input File Name: Ellenz_LaQuinta.xml CFI R -PRF -01 Page 3of8 OPAQUE SURFACES 01 02 03 04 05 06 07 08 09 10 Name Zone Construction Azimuth Orientation Gross Area (ftz) Window & Door Area (ft2) Tilt (deg) Status Verified Existing Condition Front Wall -21'x8' R15 Whole House R-15 Wall 90 Back 168 56 90 Altered N/A Left Wall -9'6 x8' R15 Whole House R-15 Wall 180 Right 76 9 90 Altered N/A Front Wall 19'x8' R15 Whole House R-15 Wall 90 Back 152 50 90 Altered N/A Left Wall_24'x8' R15 Whole House R-15 Wall 180 Right 192 20 90 Altered N/A Rear Wall_5'6 x8' R15 Whole House R-15 Wall 270 ,Front 44 12 90 Altered N/A Left Wall -9'x8'6 R15 Whole House R-15 Wall 180 , Right 68 6 90 Altered N/A Rear Wall -34'6 x8' R15 Whole House R-15 Wall 270 Front 276 46 90 Altered N/A Right Wall -42'x8' R15 Whole House R-15 Wall 0;0 Left 336 46 90 Altered N/A Roof Whole House R-30 Roof Attic 1266 Altered N/A v ATTIC t 01 02 03 �Q64 05 06 07 08 09 10 Name Construction Type #e ORoof Rise Roof Reflectance Roof Emittance Radiant Barrier Cool Roof Statu s Verified Existing Condition Attic Whole House Attic RoofWhole House Ventilate/ 2 0.1 0.85 No No Enigsti No D QJ 0 C _" rn O > 0 �® 0 %J Z 0 O 01P -10D 4� 30 AP n<mo Zilill C: OV O ITI U .� Registration Number: i� Registration Date/Time: HERS Provider: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-04072016-744 Report Generated at: 2016-09-19 12:07:35 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Ellenz Residence -La Quinta Calculation Date/Time: 12:06, Mon, Sep 19, 2016 Calculation Description: Title 24 Analysis Input File Name: Ellenz_LaQuinta.xml CF1 R -PRF -01 Page 4 of 8 WINDOWS 01 02 03 04 05 06 07 08 09 10 11 Name Surface (Orientation -Azimuth) Width(ft) Height (ft) Multiplie r Area (W) U -factor SHGC Exterior Shading Status Verified Existing Condition Window D_Sierra 28/21 Front Wall -21' x8' R15 (Back -90) - ---- ---- 1 24.0 0.28 0.21 Insect Screen (default) New N/A Window C_Sierra 29/23 Front Wall -21' x8' R15 (Back -90) ---- ---- 1 32.0 0.29 0.23 Insect Screen (default) New N/A Window B_Sierra 29/22 Left WaII_9'6 x8' R15 (Right -180) ---- ---- 1 9.0 0.28 0.21 Insect Screen (default) New N/A Window A_29/23 Front Wall_19'x8' R15 (Back -90) ---- 1 30.0 0.29 0.23 Insect Screen (default) New N/A French Door_3068 Left Wall_24'x8' R15 (Right -180) 1 j'20.0 0.37 0.29 Insect Screen (default) New N/A Window N_Sierra 31/22 Rear Wall_5'6 x8' R15 (Front -270) ---- -- 1 12.0 0.31 0.22 Insect Screen (default) New N/A Window M_Sierra 26/21. Left Wall_9'x8'6 R15 (Right -180) ---- ---- ,1 6.0 0.26 0.21 Insect Screen (default) Altered N/A Window L_2030 Sierra 28/1 Rear Wall -34'6 x8' R15 (Front 270) ---- ---- 6.0 0.28 0.18 Insect Screen (default) Altered N/A Sldg GI DR K- Sierra 29/23 Rear Falllln32'6 x8' R15 70) ---- ---- �� 1 40.0 0.29 0.23 Insect Screen (default) Altered N/A Window 1_3018 Sierra 29/2 Right Wall -42'x8' R15 (Left -0) ---- i 1 5.0 0.29 0.23 Insect Screen (default) Altered N/A Window H_3018 Sierra 29/2 Right Wall_42'x8' R15 (Left -0) 1 5.0 0.29 0.23 Insect Screen (default) Altered N/A Window G_3060 Sierra 29/2 Right Wall 42'x8' R15 (Left -0) ---- i �y 1 18.0 0.29 0.22 Insect Screen (default) Altered N/A Window F_3060 Sierra 29/2 Right Wall -42'x8' R15 (Left -0) ---- 1 18.0 1 0.29 1 0.22 1 Insect Screen (default) Altered I N/A D( ORS 01 M -11 Tl�am�- DoorTOffn3bd8 wood O P Tp :0 > �M:� ZOO �> 02 Side of Front Wall 0304 05 06 10 1 Ig Area (ft) U -factor Status Verified Existing Condition R15 20.0 0.50 New No V .y Registration Number: Registration Date/Time: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-04072016-744 HERS Provider: Report Generated at: 2016-09-19 12:07:35 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Ellenz Residence_La Quinta Calculation Datefrime: 12:06, Mon, Sep 19, 2016 Calculation Description: Title 24 Analysis Input File.Name: Ellenz_LaQuinta.xml CF1 R -PRF -01 Page 5of8 OPAQUE SURFACE CONSTRUCTIONS 01 02 03 04 05 06 07 08 r W Parallel Piping Compact Distribution Total Cavity Winter Design Solar Construction Name Surface Type Construction Type Framing R -value U -value Assembly Layers Fraction Insulation R -value Verified Existing Name System Type Distribution Type - Cavity/Frame: no insul. /2x4 Top Chrd Heaters M Status 2x4 Top Chord of Roof Truss @ 24 DHW Sys 1 DHW - Roof Deck. Wood Siding/sheathing/decking Attic RoofWhole House Attic Roofs Wood Framed Ceiling in. O.C. none 0.644 - Roofing: Light Roof (Asphalt Shingle) - Inside Finish: Gypsum Board - Cavity/Frame: R -15/2x4 • Exterior Finish: Wood R-15 Wall Exterior Walls Wood Framed Wall 2x4 @ 16 in. O.C. R 15 0.089 Siding/sheathing/decking - Inside Finish: Gypsum Board Ceilings (below b� - Cavity/Frame: R-9.1 /2x4 R-30 Roof Attic attic) Wood Framed Ceiling 2x4 @ 24 in. O.C,,.o R 30 0.032 - Over Floor Joists: R-20.9 insul. is WATER HEATING SYSTEMS 01 02 03 �' 04 05 06 07 08 r W Parallel Piping Compact Distribution Tank Volume Energy Factor or Solar Tank Exterior Standby Loss -, NamC Heater Element Type ® (gal) Number of Fraction Insulation R -value Verified Existing Name System Type Distribution Type Water Heater Heaters M Status Condition DHW Sys 1 DHW Standard v DHW Heater 1 1 Annual New No 0 WATER HEATERS Z 02 03�`W 04 05 06 07 08 r W Parallel Piping Compact Distribution Tank Volume Energy Factor or Recirculation with Sensor Control Tank Exterior Standby Loss -, NamC Heater Element Type TaainA Type (gal) Efficiency Input Rating Insulation R -value (Fraction) Qt j r L.� Electric Resistance ' tEill Storage 6 0.92 EF 1500 -watts 0 0 ATER�}I ERIFICATION t�A Z 02 Y 03 04 05 06 07 W n!Recirculation M I rT1Sys Pipe Insulation Parallel Piping Compact Distribution Point -of Use with Manual Control Recirculation with Sensor Control n/a *4� n/a n/a n/a n/a n/a z�M2 Registration Number: t� CA Building Energy Efficiency Stan fds - 2013 Residential Compliance Registration Date/Time: Report Version - CF1R-04072016-744 HERS Provider: Report Generated at: 2016-09-19 12:07:35 CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Ellenz Residence—La Quinta Calculation Date/Time: 12:06, Mon, Sep 19, 2016 Calculation Description: Title 24 Analysis Input File Name: Ellenz_LaQuinta.xml CF1 R -PRF -01 Page 6 of 8 SPACE CONDITIONING SYSTEMS 01 02 03 04 05 06 07 08 09 Type HSPF/COP Cap 47 Cap 17 Heating System Cooling System SplitHeatPump - Central split heat 9 29600 F19100 15.75 13 Duct Leakage pump Distribution Fan Floor Area Condition Verified Existing Name System Type Name Ducted Name' Ducted System System Served Status Condition Heat Pump Split 15 Heat Pump Heating Heat Pump Yes Heat Pump Yes Air Distribution HVAC Fan 1266 New No seerl and Cooling System System 1 System 1 System 1 1 HVAC - HEATING SYSTEMS: Heat Pumps 01 02 03 04 05 06 07' 06 07 Heating Cooling Name Type HSPF/COP Cap 47 Cap 17 SEER EER Heat Pump System 1 SplitHeatPump - Central split heat 9 29600 F19100 15.75 13 Duct Leakage pump Bypass Duct Status Condition v HVAC - DISTRIBUTION SYSTEMS �� 01 02 03 04 4,* 05 06 07 08 09 10 Verified Duct Design Return Supply -hers-dist Insulation �� OSupply Duct Return Duct -- --- Verified Existing HERS Name Type Duct Leakage R -value .. Location Location Bypass Duct Status Condition Verification Air Distribution Air Distribution Ducts located in attic Sealed and tested 8.0 Attic Attic None New No System Sys em 1 7 1 -hers -dist ItIV RS VERIFICATION �v 02 03 04 05 06 Duct Leakage Aww� Verificationt, Duct Leakage Target (%) Verified Duct Location Verified Duct Design Return Supply -hers-dist Required®- 6.0 --- -- --- i iERS VERIFICATION► ♦-`� 02 03 04 D �p j Type Fan Power (Watts/CFM) HERS Verification in 1 Single Speed PSC Furnace Fan 0.58 Required `I. Registration Number: CA Building Energy Efficiency Standards - 2013 Residential Compliance Registration Date/Time: Report Version - CF113-04072016-744 HERS Provider: Report Generated at: 2016-09-19 12:07:35 ao o — LL o a a� o LL a U - s Ln m 0 N m of 0 �o 0 N m dr O1 v c al L m CC n Lu 2 w s a O N n CL a) o ® � N n O c o x cd 2 c o 0 � J 10 C O O E' I N N t w Y ty N_ Q p E Q c o Z a! 0 � 75 u u to w 0 � n � U c Ln m 0 N m of 0 �o 0 N m dr O1 v c al L m CC n Lu 2 w s a n o ® � N n O v 6 o s u 1® LL Y 10 C O O ! l Q Y ty N_ Q Q 10® Y u u to ® C o 0 Jc 2 v ' N Q! m N O N c CITY OF LA QUINTA BUILDING & SAFETY DEPT APPROVE® FOR CONSTRUCTION Z ui c oa o c ATE BY Cc • __ �_ a' Q z v CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD Project Name: Ellenz Residence—La Quinta Calculation Date/Time: 12:06, Mon, Sep 19, 2016 Calculation Description: Title 24 Analysis Input File Name: Ellenz_LaQuinta.xml CF1 R -PRF -01 Page 8 of 8 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT. ` 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Documentation Author Signature: - Jack LaFontaine c J Company: Signature Date: Energy Management Services 9/19/2016 Address: CEA/HERS Certification Identification (If applicable): com 41-485 Adams Street, Unit C A City/Stateip: Bermuda Dunes, CA 92203 Phone: 7�0-i360-4631 RESPONSIBLE PERSON'S DECLARATION STATEMENT_ I certify the following under penalty of perjury, under the laws of the State of California: .��J 1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for�th�e building design identified on this Certificate of Compliance. 2. 1 certify that the energy features and performance specifications identified on this Certificate Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agencxvr approval with this building permit application. Responsible Designer Name: Responsible Designer Signature: Timithy Ellenz Company: v Date Signed: — alifornia i dow &Door, Inc A�ress: C:: �� License: �'7AM 15t. rtes Place, Suite G ty/State*t Z Phone: I�XRA 92211 ,�,� 760-773-1053 -4�� ' 4-$4 0 - �� �� C �& o®o Z �4V •may Registration Number: CA Building Energy Efficiency Stand rds - 2013 Residential Compliance Registration Date/Time: Report Version - CF1R-04072016-744 HERS Provider: Report Generated at: 2016-09-19 12:07:35 RESIDENTIAL MEASURES SUMMARY RMS-1 Project Name Timothy Ellenz Residence Building Type m Single Family O Addition Alone 0 Multi Family m Existing+ Addition/Alteration Date 9/19/2016 Project Address 54671 Avenida Diaz La Quinta California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 1,266 Addition 0 # of Units 1 INSULATION Construction Type Area Cavi (ft)Special Features Status Wall Wood Framed R 15 1,067 Altered Door Opaque Door - no insulation 20 New Roof Wood Framed Attic R 30 1,266 Altered FENESTRATION Orientation Area ft2 I Total Area: 225 Glazing Percentage: 17.8%1 U-Fac SHGC Overhang Sidefins New/Altered Average U-Factor: 0.30 Exterior Shades Status Rear (E) 24.0 0.280 0.21 none none Bug Screen New Rear (E) 62.0 0.290 0.23 none none Bug Screen New Right (S) 9.0 0.280 0.21 none none Bug Screen New Right (S) 20.0 0.370 0.29 none none Bug Screen New Front (IM 12.0 0.310 0.22 none none Bug Screen New Right (S) 6.0 0.260 0.21 none none Bug Screen Altered Front (IM 6.0 0.280 0.18 none none Bug Screen Altered Front (IM 40.0 0.290 0.23 none none Bug Screen Altered Left (N) 10.0 0.290 0.23 none none Bug Screen Altered Left (N) 36.0 0.290 0.22 none none Bug Screen Altered HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status 1 Split Heat Pump 9.00 HSPF Split Heat Pump 15.8 SEER Setback New HVAC DISTRIBUTION Location Heating Cooling Duct Location Duct R-Value Status Heat Pump Split 15 seer Ducted Ducted Attic 8.0 New WATER HEATING Qty. Type Gallons Min. Eff s. iStatus 1 Small Storage Electric 6 0.92 t d rd New BUILD FOR EnemyPro 6.7 by EnemySoft user Number. 5021 RunCode: 2016-09-19T12:07:54 /D: 09172016 Pae 11 of 16 t3Y 2013 Low -Rise Residential Mandatory Measures Summary NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the COMDliance approach used. Exceptions may annly Reviow tho ro.cnortivo endo wrtinn fnr mnro infnrmntinn Building Envelope Measures: §I 10.6(a)1: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage. § 110.6(a)5: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain Coefficient SHGC , and infiltration that meets the requirements of § 10-111 (a). § 110.7: Exterior doors and windows are weatherstripped; all joints and penetrations are caulked and sealed. §I 10.8(a): Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R. § 110.8(i): The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of § 110.8(i) when the installation of a cool roof is specified on the CF 1 R. § 110.80): A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CFI R. Minimum R-30 insulation in wood -frame ceiling; or the weighted average U -factor shall not exceed 0.031. Minimum R-19 in a § 150.0(a): rafter roof alteration. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The attic access shall be gasketed to prevent air leakage. §I50.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -value. §150.0(c): Minimum R-13 insulation in 2x4 inch wood framing wall or have a U -factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U - factor). § I50.0(d): Minimum R-19 insulation in raised wood -frame floor or 0.037 maximum U -factor. §150.0(g)l: In Climate Zones 14 and 16 a Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior walls, vented attics and unvented attics with air -permeable insulation. § I50.0(g)2: In Climate Zones 1-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class II vapor retarder. In a building having a controlled ventilation crawl space, a Class I or Class II vapor retarder shall be placed over the earth floor of § I50.0(g)3: the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section 150.0(d). § 150.0(1): Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%; have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration; and when installed as part of a heated slab floor meets the requirements of § 110.8 150.0 § (q)' Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U- factor of 0.58; or the weighted average U -factor of all fenestration shall not exceed 0.58. Fireplaces, Decorative Gas Appliances and Gas Log Measures: § 150.0(e) I A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox. §I50.0(e)IB: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is equipped with a readily accessible, operable, and tight -fitting damper or a combustion -air control device. §I50.0(e)IC: Masonry or factory -built fireplaces have a flue damper with a readily accessible control. §I50.0(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of the building, are prohibited. Space Conditioning, Water Heating and Plumbing System Measures: §110.0-§110.3: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified to the Energy Commission. § 110.3(c)5: Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of § 110.3(c)5. Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appli- § 110.5: ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool ands a heaters. §150.0(h)l: Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified in §150.0(h)2. §150.0(h)3A: Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any dryer vent. § I50.0(i): Heating systems are equipped with thermostats that meet the setback requirements of 110.2 c § 150.00)1 A: Storage gas water heaters with an energy factor equal to or less than th federal � Stan ar s4taTJ�b� t r a pped Ov with insulation havingan installed thermal resistance of R-12 or reate . P� §150.00)1B: Unfired hot water tanks, such as storage tanks and backup storage tanksfor a v ' ti& aA�, xte 1 insulation or R-16 internal insulation where the internal insulation R -value i md� o >� For domestic hot water system piping, whether buried or unburied: the Irst 5 feeMOW MNAAcYpAyes lMm the sto age tank, all piping with a nominal diameter of 3/4 inch or larger, all piping ssoc,atTlNtli C )"i TR ulation system § 150.00)2A: regardless of the pipe diameter, piping from the heating source to storagtank or between tanks, piping buried below grad , and all hot water pipes from the heating source to kitchen fixtures must be in ulated according to the requirements of TABLE 20.3- A. n AT F BY § 150.00)2B: All domestic hot water pipes that are buried below grade must be installed in a Ovate ng or s eeve that allows for installation, removal, and replacement of the enclosed pipe and insulation. 2013 Low -Rise Residential Mandatory Measures Summary § I50.00)2C: Pipe for cooling system lines shall be insulated as specified in § I50.00)2A. Piping insulation for steam and hydronic heating systems or hot waters stems with pressure > 15 psig shall meet the requirements in TABLE 120.3-A. § 150.00)3: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For §150.00)3A: example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or painted with coating that is water retardant and provides shielding from solar radiation that degrades the material. Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I §I50.00)3B: or Class II vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class II vapor retarder. Systems using gas or propane water heaters to serve individual dwelling units shall include: a 120V electrical receptacle within 3 feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the §150.0(n)l: space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000 Btuihr. §150.0(n)2: Recirculating loops serving multiple dwelling units shall meet the requirements of §110.3(c)5. § I50.0(n)3: Solar water -heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC) or by a testing agency approved by the Executive Director. Ducts and Fans Measures: All air -distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC §601.0, §602.0, §603.0, §604.0, §605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition. Supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC §605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing (RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed §150.0(m)l: with mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than 'A inch, the combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. Factory -Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; joints § 150.0(m)2: and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. § I50.0(m)3-6: Field -Fabricated Duct Systems shall comply with requirements for: pressure -sensitive tapes, mastics, sealants, and other requirements specified for duct construction; duct insulation R -value ratings; duct insulation thickness; and duct labeling. §150.0(m)7: All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic dampers. § I50.0(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers except combustion inlet and outlet air openings and elevator shaft vents. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not §150.0(m)9: limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation. § I50.0(m)10: Flexible ducts cannot have porous inner cores. When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be §I50.0(m)1 l: sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal § I50.0(m)12: conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of 150.0 m 12. Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The §I50.0(m)13: space conditioning system must also demonstrate airflow> 350 CFM per ton of nominal cooling capacity through the return grilles, and an air -handling unit fan efficacy:5 0.58 W/CFM as confirmed by field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode, § 150.0(m)15: ing an airflow from the dwelling, through the air handler fan and delivered to the dwellin of 35�001M capacity, and operating at an air -handling unit fan efficacy of:5 0.58 W/CF as co d 1 ve%�'f testing, in accordance with Reference Residential Appendix RA3. spy § 150.0(0): All dwelling units shall meet the requirements of ASHRAE Standard 62.2. est n�Q mlii ratio of forced handlers n bn� qM�� central air system air tlrf�i used in central fan integrated ventilati n s e e i t oviding t e Whole BuildingVentilation. §150.0(o)IA: Whole Building Ventilation -airflow shall be confirmed through field verific tion and-(kEltics t , . with Reference Residential Appendix RA3. r Pool and Spa Heating Systems and Equipment Measures: Any pool or spa heating system shall be certified to have: a thermal efficiency th" ih the ppkarratrEff>Z<tr nc § 1 10.4(a): Regulations; an on-off switch mounted outside of the heater that allows shutiing-of ermostat setting; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating. 2013 Low -Rise Residential Mandatory Measures Summary §110.4(b)1: Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction and return lines, or built-up connections for future solar heating. § 110.4(b)2: Outdoor pools or spas that have a heat pump or gas heater shall have a cover. §I 10.4(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro - rammed to run only during off-peak electric demand periods. §110.5: Natural gas pool and spa heaters shall not have a continuous burning pilot light. § I50.0(p): Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements. Lighting Measures: § 110.9: All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of § 110.9. §150.0(k)IA: Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with §I50.0(k) in accordance with TABLE 150.0-A or TABLE 150.0-13, as applicable. §I50.0(k)IB: When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply with the applicable provisions of § 150.0(k). The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with §150.0(k)1 C: § I30.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180 watts of low efficacy lighting er electrical box. §I50.0(k)1D: Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz. Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no §I50.0(k)IE: more than 5 watts of power per luminaire or exhaust fan as determined in accordance with §I30.0(c). Night lights do not need to be controlled by vacancy sensors. § I50.0(k)IF: Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable requirements of § 15 0.0 k . § 150.0(k)2A: High efficacy luminaires must be switched separately from low efficacy luminaires. §I50.0(k)2B: Exhaust fans shall be switched separately from lighting systems. § I50.0(k)2C: Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF. §I50.0(k)2D: Controls and equipment are installed in accordance with manufacturer's instructions. § I50.0(k)2E: No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with §I50.0(k). §I50.0(k)2F: Lighting controls comply with applicable requirements of §1 10.9. An Energy Management Control System (EMCS) may be used to comply with dimmer requirements if: it functions as a dimmer § 150.0(k)2G: according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements of § 130.5; and all other requirements in §150.0(k)2. An Energy Management Control System (EMCS) may be used to comply with vacancy sensor requirements of § I50.0(k) if. it §150.0(k)2H: functions as a vacancy sensor according to §110.9; meets Installation Certificate requirements of §130.4; the EMCS requirements of § 130.5; and all other requirements in § 150.0(k)2. § 150.0(k)21: A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the functionality of a dimmer according to §110.9, and complies with all other applicable requirements in §150.0(k)2. §150.0(k)3A: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy. Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only § 150.0(k)3B: the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are considered kitchen lighting if they are not separately switched from kitchen lighting. §I50.0(k)4: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated cabinet. §150.0(k)5: A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom shall be high efficacy or controlled by vacancy sensors. §I50.0(k)6: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and controlled by vacancy sensors. § 150.0(k)7: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high efficacy, or shall be controlled by either dimmers or vacancy sensors. Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing § 150.0(k)8: and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and allow ballast maintenance and replacement without requiring cutting holes i For recessed compact fluorescent luminaries with ballasts to qualify as high 4 fflP elwi& 0�1 I!�th gflas A shall be certified to the Ener Commission to corn I with the applicable re ui s 9. Lam\ _lad lJ i���i rpt in For single-family residential buildings, outdoor lighting permanently mount to J3(iPgNN JDil&r8AFeeiie th same lot shall be high efficacy, or may be low efficacy if it meets all of the following r�quta , i. Controlled by a manual ON and OFF switch that does not override to ON t e auto cti ns i w; and §I50.0(k)9A: ii. Controlled by a motion sensor not having an override or bypass switch tha disableF@%(@@N8_frFVEJ&T4dMby a motion sensor having a temporary override switch which temporarily bypass s the motion sensing function and automatically reactivates the motion sensor within 6 hours; and iii. Controlled by one of the following methods: DTE BY 2013 Low -Rise Residential Mandatory Measures Summary i AN it e s %.O v "-L-' FOR CONSTRUCTION DATE BY a. Photocontrol not having an override or bypass switch that disables the photocontrol; or b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is programmed to automatically turn the outdoor lighting OFF during daylight hours; or c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of an astronomical time clock in accordance with §110.9; meets the Installation Certification requirements in §130.4; meets the requirements for an EMCS in §130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and, is programmed to automatically turn the outdoor lighting OFF during daylight hours. For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the §150.0(k)9B: following requirements: i. Shall comply with §I50.0(k)9A; or ii. Shall comply with the applicable requirements in '110.9, 130.0, § 130.2, 130.4, 140.7 and 141.0. § I50.0(k)9C: For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by § I50.0(k)9B or 150.0(k)9D ' shall comply with the applicable requirements in 110.9, § 130.0, § 130.2, §130.4, § 140.7 and § 141.0. §I50.0(k)9D: Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply with the applicable requirements in § 110.9, § 130.0, § 130.2, § 130.4, § 140.7 and § 141.0. §I50.0(k)10: Internally illuminated address signs shall comply with §140.8; or shall consume no more than 5 watts of power as determined according to §130.0(c). § I50.0(k)1 l: Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for '130.4 nonresidential garages in 110.9 130.0, § 130.1, 140.6, and 141.0. In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of § I 50.0(k) I 2A: the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or controlled by an occupant sensor. In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20 percent of the floor area, permanently installed lighting in that building shall: §150.0(k)12B: i. Comply with the applicable requirements in §110.9, §130.0, §130.1, §140.6 and §141.0; and ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of ingress and egress. Solar Ready Buildings: Single family residences located in subdivisions with ten or more single family residences and where the application for a §I 10.10(a)1: tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January 1, 2014, shall comply with the requirements of § 110.10 b through § 110.10 e . §I 10.10(a)2: Low-rise multi -family buildings shall comply with the requirements of §I 10.10(b) through §I 10.10(d). The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway, smoke ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a local jurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than 80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for §110.10(b)1: buildings with roof areas greater than 10,000 square feet. For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less than 250 square feet. For low-rise multi -family buildings the solar zone shall be located on the roof or overhang of the building or on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the building project and have a total area no less than 15 percent of the total roof area of the building excluding any skylight area. § 110.10(b)2: All sections of the solar zone located on steep -sloped roofs shall be oriented between 110 degrees and 270 degrees of true north. § 110.10(b)3A: No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be located in the solar zone. Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice §I 10.10(b)3B: the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the horizontal projection of the nearest point of the solar zone, measured in the vertical plane. § 110.10(b)4: For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly indicated on the construction documents. The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit § 110.10(c): from the solar zone to the point of interconnection with the electrical service (for single family residences the point of interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water -heating system. § 110.10(d): A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through § 110.10(c) shall be provided to the occupant. § 110.10(e)1: The main electrical service panel shall have a minimum busbar rating of 20 The main electrical service panel shall have a reserved space to allow fort in a a io of'r(doubt$61ebTM bVelAft8r § 110.10(e)2: future solar electric installation. The reserved space shall be: positioned at tie o %I(�. bNGn&"FhEiTMtOEaF?TQcat' n or main circuit location, and permanently marked as "For Future Solar Electri ". i AN it e s %.O v "-L-' FOR CONSTRUCTION DATE BY HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Timothy Ellenz Residence Date 9/19/2016 System Name Heat Pump Split 15 seer Floor Area 1,266 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL CFM Total Room Loads 809 Return Vented Lighting Return Air Ducts Return Fan Ventilation 0 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD 1 COOLING PEAK COIL HTG. PEAK Heating System Sensible Latent CFM Sensible Output perSystem 29,600 15,492 1,610 368 11,914 Total Output Btuh 29,600 0 Output Btuh/s ft 23.4 894 455 Cooling System 0 0 Output perSystem 28,200 0 0 0 0 Total Output Btuh 28,200 1,535 894 18,816 1,610 -1,535 Total Output Tons 2.4 455 Total Output Btuh/s ft 22.3 Total Output s ft/Ton 538.7 11,290 Air System CFM perSystem 1,000 HVAC EQUIPMENT SELECTION ,Airflow cfm 1,000 YorkYZF030/AHV36C+TXV+2% 19,929 3,863 17,484 Airflow cfm/s ft 0.79 Airflow cfmrron 425.5 Outside Air % 0.0 % Total Adjusted System Output 19,929 3,863 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK Aug 3 PM 17,484 Jan 1 AM Outside Air cfm/s ft 0.00 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 24 OF Outside Air 0 cfm 68 OF 68 OF 97 OF 98 OF Heating Coil Supply Fan 98 OF 1,000 cfm ROOM + 68 OF L COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 112/79°F Outside Air 0 cfm 76/62°F 76/62°F 55/54°F 56/54°F Cooling Coil Supply Fan 57/55 1,000 cfm CITY OUUM BLALMNGI 0 RT /Ar-� g OF I EnergyPro 6.7 by EnergySoR User Number: 5021 Run Code: 2016-09-19712:07.54 � ID: 09f72D 6'- - 75091 Saint Charles Place, Suite G Palm Desert, CA 92211 Phone: 760-773-1053 Fax: 760-776-8139 BILL TO: Avenida Diaz La Quinta Phone Email SHIP TO: Avenida Diaz La Quinta . Phone Fax ��: SIERRA `'PACIFIC WINDOWS CA 922 1.1 `r�QUOTE #PROJECTNAME _u 1;CUSTOMERaPO# ;ORDER 'PLACED BYPLANNED 'LOAD DATE 794793 Avenida Diaz 13146 tellenz 6/8/2016 `JOB NAME,, t .QUOTE`NAME,'.�-�3`?�: ' "•�' = 4,�',ORDER DATE: asp ':'srSI3IP METHOD ;n:. Avenida Diaz Avenida Diaz 6/9/2016 SPW TRUCK LINE # LINE TYPE DESCRIPTION QUANTITY 100-1 WindowAndDoor PK 260 1 H3 Aluminum Clad Windows Casement Left / Fixed / Right 93.5 x 47.5 Unit 1, 3: Custom: Frame Width = 24, Frame Height = 47.5 Unit 2: Custom: Frame Width = 45:5, Frame Height = 47.5 Unit 1, 3: Complete Unit, Drawing Numbers = WI-794793.2-2AF, DP Rating = Standard Unit 2: Complete Unit, Drawing Numbers = , DP Rating = Standard Frame Color = Patina Green, AAMA 2604, Ultra Coat Interior, With Nail Holes Filled = Yes, Pine Interior - 2G t;.S Sash -Panel Color = Patina Green, Sash -Panel Clad Finish = AAMA 2604 935 Dual Insulated, Super Sun Blocker Low -E, Spacer Channel = Standard Intercept Spacer Hardware = Shipped with Unit, E -Guard Finish (Beige), Encore, White, Window Opening Control Device = No Screen Option = Full Screen Applied, White, Fiberglass Mesh Simulated Divided Lite, Diamond, 5/8", Exterior Grille Color = Patina Green, Ultra Coat, Pine Interior, w/out spacer, 2W3H Integral Rigid Vinyl Nailing Fin 4-9/16", Interior Mull Casing Ship ed Se arately $ `� Unit 1, 3: U=.Factor`= 0.,29;�SRGC,:.,.0_l9 CR = 54, VT = 0.43, CPD = �' SIE -N-105-0011 1=00004, Energy Star Region = NC,SC,S Unit 2 Facto_r,. 0.28+�.SHGC ="0:23 CR = 54, VT = 0.54, CPD = SIE -N -107-002W_'00001, Energy Star Region t NC,SC,S Overall Unit Width = 93.5, Overall Unit Height = 47.5 Non' -Manufacturer Related = Unit 1,3: Glass Width = 20.5, Glass Height = 43.75, Unit 2: Glass Width = 42.25, Glass Height = 43.75 Rough Opening: 94" X 48" Room Location: Morning Room Overall Unit Size: 93.5" X 47.5" * All drawings are viewed from exterior of window. Page 1 Of 4 NPR 6/9/2016 s " ',QUOTE #`c 3 ', PROJECT -NAME r? CUSTONIER PO# - �ORDER'PL'ACED_BY; PLANNED LOAD DATE ' 794793 Avenida Diaz 13146 tellenz 6/8/2016 ' OB NAME"_'_ E» a QIIOTE:NAME {`� .: k•s3 ��_ _' I _'.ORDER DATE r4 '�:• `SHIP; METHOD Avenida Diaz Avenida Diaz Yes, Pine Interior 6/9/2016 SPW TRUCK LINE # LINE TYPE DESCRIPTION QUANTITY 200-1 WindowAndDoor PK 260 1 H3 Aluminum Clad Windows Sash Set Picture 71.5 x 47.5' Custom: Frame Width = 71.5, Frame Height = 47.5 Complete Unit, Drawing Numbers = WI-794793.3-2AF, DP Rating = Standard Frame Color = Patina Green, AAMA 2604, Ultra Coat Interior, With Nail Holes Filled = Yes, Pine Interior >< Sash -Panel Color = Patina Green, Sash -Panel Clad Finish = AAMA 2604 Dual Insulated, Super Sun Blocker Low -E, Spacer Channel = Standard Intercept Spacer Simulated Divided Lite, Diamond, 5/8", Exterior Grille Color = Patina Green, Ultra Coat, "S Pine Interior, w%out spacer, 1 W 1 H Integral Rigid Vinyl Nailing Fin 4-9/16" iT=Factor-0 28_,„SIIGC ..0:21, CR = 53, VT = 0.48, CPD = SIE -N-107-00311-00004, Energy Star Region = NC,SC,S Overall Unit Width = 71.5, Overall Unit Height = 47.5 .Non -Manufacturer Related -- Unit 1: Glass Width = 67.75, Glass Height = 43.75 Unit Rough Opening: 72” X 48" Room Location: None Assigned Overall Unit Size: 71.5" X 47.5" LINE # LINE TYPE DESCRIPTION QUANTITY 300-1 WindowAndDoor PK 260 1 H3 Aluminum Clad Windows Casement Left / Fixed / Right 93.5 x 59.5 Unit 1, 3: Custom: Frame Width = 24, Frame Height = 59.5 Unit 2: Custom: Frame Width = 45.5, Frame Height = 59.5 Unit 1, 3: Complete Unit, Drawing Numbers = WI-794793.4-2AF, DP Rating = Standard Unit 2: Complete Unit, Drawing Numbers = , DP Rating = Standard Frame Color = Patina Green, AAMA 2604, Ultra Coat Interior, With Nail Holes Filled = Yes, Pine Interior Sash -Panel Color— Patina Green, Sash -Panel Clad Finish = AAMA 2604 . Dual Insulated, Super Sun Blocker Low -E, Spacer Channel = Standard Intercept Spacer Hardware = Shipped with Unit, E -Guard Finish (Beige), Encore, White, Window Opening Control Device = No Screen Option = Full Screen Applied, White, Fiberglass Mesh Simulated Divided Lite, Diamond, 5/8", Exterior Grille Color = Patina Green, Ultra Coat, Pine Interior, w/out spacer, 2W3H Integral Rigid Vinyl Nailing Fin 4-9/16",Interior Mull CasmSShhi ped Se arately Unit 1, 3: FactU 2SHGCx�.�0.19 CR = 54, VT = 0.43, CPD = SIE -N 105-00111-00004, Energy Star Region = NC,SC,S Unit=2,U-Eac028, S GC = 0_23 CR = 53, VT = 0.53, CPD = SIE -N-107-003.11-00001, Energy Star Region= NC,SC,S Overall Unit Width = 93.5, Overall Unit Height = 59.5 Non -Manufacturer Related = Unit 1,3: Glass Width = 20.5, Glass Height = 55.75, Unit 2: Glass Width = 42.25, Glass Height = 55.75 Rough Opening: 94" X 60" Overall Unit Size: 93.5" X 59.5" Room Location * All drawings are viewed from exterior of window. Page 2 Of 4 NPR Bedroom 6/9/2016 ' QUOTE # ` ; �y 'PROJECT. NAME -`k : , ;,CUSTObiER,PO#.='- ,ORDER PLACED BY - PLANNED: LOAD DATE 794,793 Avenida Diaz 13146 tellenz 6/8/2016 h _ QUOTE' -NAME_ -; ;•._ .y+.:�r d:..._ .'--, ' ,wORDERDATV SHIP METHOD�..,:;p Avenida Diaz Avenida Diaz 6/9/2016 SPW TRUCK LINE # LINE TYPE DESCRIPTION. QUANTITY 400-1 WindowAndDoor PK 260 1 Aluminum Clad Wood Windows Direct Set Octagon 36 x 36 3-0 x 3-0, Frame Width = 36, Frame Height = 36 Complete Unit, Drawing Numbers = WI -794793 ). Frame Color = Patina Green, AAMA 2604, Ultra Coat Interior, With Nail Holes Filled = Yes, Pine Interior Dual Insulated, Super Sun Blocker Low -E, Standard Bead, Spacer Channel = Standard Intercept Spacer Simulated Divided Lite, Queen Anne, 5/8", Exterior Grille Color = Patina Green, Ultra Coat, Pine Interior, w/spacer, LRTB, Horz Edge = 5.25", Vert Edge = 5.25" Vinyl Nail Fin, No Drip Cap 4-9/16" LJ- ;actor= 029:SG_C� U.2 CR = 55, VT = 0.52, CPD = HUR-N-20-00788-00002, Energy Star Region = NC,SC,S Overall Unit Width = 36, Overall Unit Height = 36 Non -Manufacturer Related Unit 1: Glass Width = 34.1875, Glass Height = 34.1875 Rough 'Opening: 36.75" X 36.5" Overall Unit Size: 36" X 36" Room Location: m - 36 --y None Assigned * All drawings are viewed from exterior of window. Page 3 Of 4 . NPR .6/9/2016 t QUOTE, #, '_• 41 PROJECT NAME` i'r <'.�CUSTOAIER PO#",; :ORDER'PLACED�BY�_ PLANNED LOAD DATE 794793 Avenida Diaz 13146 tellenz 6/8/2016 .,, JOB'NAME "' T QUOTE NAME.' ' -•`�'' ¢ " `rf � ORDER DATE'. ; � -SHIP METHOD_, ' Avenida Diaz Avenida Diaz 6/9/2016 SPW TRUCK PROJECT QUOTE Avenida Diaz Avenida Diaz Comments: CW 1313 4/15/16 PRICE IS LIST AND VALID FOR' 0 DAYS 4/21/2016 CHANGES LC 4/22/2016 changes LC COMPANY Unless otherwise noted on the line item, this product is covered under a Sierra Pacific Windows limited warranty. Please see your dealer, the Websites (www.Hurd.com, www.supersealwindows.com) or our marketing literature for a copy of the applicable limited warranty for specific language, limitations and exclusions. The pricing on this Quote is valid for 30 days and not intended to.be used as a final Invoice. The Quote does not include charges for Shop Drawings. Sierra Pacific 6ffers a variety of wood species produced in combinations of solid and veneer -wrapped wood parts that have varying grain patterns. Wood characteristics also vary due to the species of the wood. The combination of these items could result in color variations of the finished stained products. Outswing Doors will have a complementary species of wood threshold. RATINGS Oversized units and certain mulled/stacked gurations confihave not been tested and therefore have no design pressure (DP) rating. Job -specific engineering analysis may be available for these non -rated units. Please contact your DST group to determine available options for non -tested product. A complete list of tested products is available at www.hurd.com. The Transcend H3 products do not have a DP rating. If units are being installed in an area requiring specific DP ratings, the unit must be installed in the exact manner tested, as shown in our certified installation details. These details can be found on the Florida Building Code website at www.floridabuilding.org or can be obtained by contacting Sierra Pacific's Architectural Services Department at 800-433-4873 ext. 3500. Recent building code changes require the addition of limiting devices on any operating unit installed where the finished clear opening of the unit is within 24" of the floor and is more than 72" above the finished grade or other surface below the window. Please check with your local building department to determine if this code is a requirement in your jurisdiction and order units accordingly. We Appreciate Your Business! * All drawings are viewed from exterior of window. Page 4 Of 4 NPR 6/9/2016 75091 Saint Charles Place, Suite G Palm Desert, CA • 92211 Phone: 760-773-1053 Fax:- 760-776-8139 BILL TO: SHIP TO: Avenida Diaz Avenida Diaz La Quinta La Quints Phone Phone Email Fax �� %��► SIERRA taw :d PACIFIC' WINDOWS CA 92211 Q.._ CUSTOMER,PO# ZORDER'PLACED;-BY"% PLANNED:LOAD'DATE 807947 Avenida Diaz - back 13145 tellenz Quote Not Ordered ;JOB NAME r: ;'; "A``, QUOTE 'NAME` y� ':; 4 s ' � �s i r r� "ORDER.DATE: « ; iSHIP,METHOD �: " c Avenida Diaz Copy of Avenida Diaz - Quote Not Ordered SPW TRUCK I MIUK - 1 LINE # LINE TYPE DESCRIPTION QUANTITY 100-1 WindowAndDoor PK 260 1 **Standard Painted exterior color Set -Up Charge not included. Charge will not apply to orders of vinyl units greater than 4 or any quantity in combination with clad of the same color.** Vinyl Superseal 8000 Designers Single Slider Left/Fixed 71.5 x 35.5 72 x 36, Frame Width = 71.5, Frame Height =.35.5, Sash Split = 50/50 Complete Unit, DP Rating = Standard Frame Color = Patina Green, Interior Finish = White, Frame Type = J -Channel Sash -Panel Color = Patina Green Dual Insulated, Super Sun Blocker Low -E, Standard Bead,.Spacer Channel=. Standard Intercept Spacer Hardware = Applied, Standard Hardware Type, Standard Handle, White, Lock -Keepers = 2 -Locks - Screen Option = Half Screen Applied, Patina Green, Fiberglass Mesh integral Rigid Vinyl Nailing Fin, No Drip Cap 1 15/16" Dr Wall Return —None U=Factor;,�0;29 SH C x0:21, CR = 55, VT = 0.5, CPD = SPM -N-50-00064-00001, Energy Star Region = NC,SC,S , Non -Manufacturer Related = Unit 1: Left Glass Width = 33. C25, Left Glass Height = 30.5625, Right Glass Width == 33.125, Right Glass Height = 31.1875 Rough Opening: 72" X 36" Overall Unit Size: 71.5" X 35.5" Room Location: Living * 6/9/2016 All drawings are viewed from exterior of window. Page 1 • Of 5 NPR `-`QUOTE# a °_;PROJECTNAMER.""r;CUSTOMERaPO#;-` ;40RDERPI✓ACEDBY PLANNEDLOAD'DATE 807947 Avenida Diaz = back 13145 tellenz Quote Not Ordered x :JOB NAME ;,� NAME,4,,--, F t; 4 `ORDER DATE=. ; METHOD;; r. :QUOTE �"; .t ti j•. >SHIP Avenida Diaz Copy of Avenida Diaz - Quote Not Ordered SPW TRUCK back LINE # LINE TYPE DESCRIPTION QUANTITY 200-1 - . , �WindowAndDoor PK 260 **Standard Painted exterior color Set -Up Charge not included. Charge will not apply to . orders of vinyl units greater than 4 or any quantity in combination with clad of the same color.** Vinyl Superseal 8000 Sliding Patio Door Double Sliding Door Inactive/Active 71.5 x 81.5 6-0 x 6-10; Frame Width = 71.5, Frame Height = 81.5 Complete Unit, Set Up, DP Rating = Standard Frame Color = Patina Green, Interior Finish = White Sash -Panel Color = Patina Green Dual Insulated, Super Sun Blocker Low -E, Standard Bead, Tempered Glass = Yes, both lites, Spacer Channel = Standard Intercept Spacer 1 pt Lock, Standard Hardware Type, Keyed Lock = No, White, Exterior Hardware Finish = Mountain Trail Screen Option = Sliding Screen Applied, Patina Green, Fiberglass Mesh Integral Rigid Vinyl Nailing Fin, No Drip Cap 3 1/2" acto0:29, SH C _= 0.23 CR = 55, VT = 0.53, CPD = SPM -N-10-00239-00001, Energy Star Region = N,NC,SC,S Non -Manufacturer Related = Unit 1: Glass Width = 33.1875, Glass Height = 75.11875 Rough Opening: 72" X 82" Overall Unit Size: 71.5" X 81.5" LINE # LINE TYPE. DESCRIPTION QUANTITY 300-1 WindowAndDoor PK 260 1 Room Location: Living **Standard Painted exterior color Set -Up Charge not included. Charge will not apply to orders of vinyl units greater than 4 or any quantity in combination with clad of the same color.** Vinyl Superseal 8000 Builders Single Slider Left/Fixed 39.5 x 47.5._ Custom: Frame Width = 39.5, Frame Height = 47.5, Sash Split = 50/50 Complete Unit, DP Rating = Standard Frame Color = Patina Green, Interior Finish = White Sash -Panel Color = Patina Green Dual Insulated, Super Sun Blocker Low -E, Standard Bead, Spacer Channel = Standard Intercept Spacer Hardware = Applied, Standard Hardware Type, White, Lock -Keepers = 2 -Locks Screen Option = Half Screen Applied, Patina Green, Fiberglass Mesh Integral Rigid Vinyl Nailing Fin; No Drip Cap 1 1%4" ,Dry Wall Return = None �1"J=FacCor0.3�,tSHGC _=.0:22, CR = 53, VT = 0.52, CPD = SPM -N-41-00084-00001, Energy Star Region = S Non -Manufacturer Related = Unit 1: Left Glass Width = 17.4375, Left Glass Height = 43.0625, Right Glass Width = 17.4375, Right Glass Height = 43.8125 Rough Opening: 40" X 48" Overall Unit Size: 39.5" X 47.5" 71.s N.5 Room Location: Master Bed * All drawings are viewed from exterior of window. Page 2 Of 5 NPR a 6/9/2016 QUOTE #7, . `,+PROJECT:NAME;:" :; CUSTOMERWPO# ORDER'PLACEDRBY;;. PLANNED LOAD DATE 807947 Avenida Diaz - back 13145 tellenz Quote Not Ordered JOB''NAME �t ° `QUOTE`NAME" 7 ORDER'DATE . -,. 's` � SHIP; METHOD' Avenida Diaz Copy of Avenida Diaz - Quote Not Ordered SPW TRUCK back LINE # LINE TYPE DESCRIPTION QUANTITY 400-1 NonConfigPart -- PK 1. EA 052360 - 2 OZ. TOUCH UP PAINT - PATINA GREEN Rough Opening: Overall Unit Size: LINE # LINE`TYPE DESCRIPTION QUANTITY 500-1 WindowAndDoor - PK 267 1 Room Location: None Assigned **Standard Painted'exterior color Set -Up Charge not included. Charge will not apply to orders of vinyl units greater than 4 or any quantity in combination with clad of the same color.** Vinyl Superseal 8000 CasementAwning Casement Picture 23.5 x 35.5 24 x 36, Frame Width = 23.5, Frame Height = 35.5 Complete Unit, DP Rating = Standard Frame Color = Patina Green, Interior Finish = White Sash -Panel Color = Patina Green Dual Insulated, Super Sun Blocker Low -E, Standard Bead, Argon Gas = Yes, Spacer Channel = Standard Intercept Spacer Integral Rigid Vinyl Nailing Fin, No Drip Cap 1 15/16", Dry Wall Return = None ,actor.. Q. 6 �SFMC7 27 I CR ='5 8, VT = 0.49, CPD = SPM -N-44-00055-00001, Energy Star Region = N,NC,SC,S -- - - - - Non -Manufacturer Related = Unit 1: Glass Width = 17.8125, Glass Height = 29.8125 Rough Opening: 24" X 36" Overall Unit Size: 23.5" X 35.5" Room Location Crl©S- New-Assigwd * All drawings are viewed from exterior of window. Page 3 Of 5 NPR 6/9/2016 ' "QUOTE #,"' T "� PROJECT'NAME:.' :y CUSTOMER PO# ?ORDER PLACED BYs" : PLANNED 'LOAD.DATE ,.r_; S 4' f' ^ -Avenida . ;';" 807947 Diaz - back 13145 tellenz Quote Not Ordered JOWNAME`.: "X_ x. 3::1 ; QUOTE"NAME;�" `,. � „ SHIP!METHOD', _... ORDER_tDATE`i ,' Avenida Diaz Copy of Avenida Diaz - Quote Not Ordered SPW TRUCK back LINE# LINE TYPE DESCRIPTION QUANTITY 600-1 WindowAndDoor PK 267. **Standard Painted exterior color Set -Up Charge not included. Charge will not apply to orders of vinyl units greater than 4 or any quantity in combination with clad of the same color.** Vinyl Superseal 8000 CasementAwning Casement Left 23.5 x 35.5 24 x 36, Frame Width = 23.5, Frame Height = 35.5 Complete Unit, DP Rating = Standard Frame Color = Patina Green, Interior Finish = White Sash -Panel Color = Patina Green Dual Insulated, Super Sun Blocker Low -E, Standard Bead, Argon Gas = Yes, Spacer Channel = Standard Intercept Spacer. E -Guard Finish (Beige), Roto, Standard Handle, White, Window Opening Control Device = No Screen Option = Full Screen Applied, White, Fiberglass Mesh Integral Rigid Vinyl Nailing Fin, No Drip Cap 1 15/16", Dry Wall Return =None actor. =X0.2'& SI_GC=O_h� 87CR = 59, VT = 0.41, CPD = SPM -N-46-00033-00001, Energy Star Region = NC,SC,S Non -Manufacturer Related = Unit 1: Glass Width = 17.8125, Glass Height = 29.8125 Rough Opening: 24" X 36" Overall Unit Size: 23.5" X 35.5" Room Location DleRe�sigfl�d * All drawings are viewed from exterior of window. Page 4 Of 5 NPR 6/9/2016 QUOTE #_• "t'r•PROJECT NAME, CUSTOMER PO#'- , .._ORDER -PLACED BY PLANNED LOAD 'DATE 807947 Avenida Diaz - back 13145 tellenz Quote Not Ordered ;-JOB NAME ' < Y ";QUOTE'NAME' ORDER DATE, t `.E' SHIP METHOD, -, Avenida Diaz Copy of Avenida Diaz - Quote Not Ordered SPW TRUCK back LINE # LINE TYPE' DESCRIPTION QUANTITY • 400-1 NonConfigPart PK 1 1 EA 052360 - 2 OZ. TOUCH UP PAINT - PATINA GREEN Rough Opening: Overall Unit Size: LINE# 'LINE TYPE. 'DESCRIPTION- QUANTITY 500-1 WindowAndDoor PK 267 1 Room Location: None Assigned **Standard Painted exterior color Set -Up Charge not included. Charge will not apply to orders of vinyl units greater than 4 or any quantity in combination with clad of the same color.** Vinyl Superseal 8000 CasementAwning Casement Picture 23.5 x 35.5 24 x 36, Frame Width = 23.5, Frame Height = 35.5 Complete Unit, DP Rating = Standard Frame Color = Patina Green, Interior Finish = White Sash -Panel Color = Patina Green Dual Insulated, Super Sun Blocker Low -E, Standard Bead, Standard Obscure, Argon Gas = Yes, Spacer Channel = Standard Intercept Spacer Integral Rigid Vinyl Nailing Fin, No Drip Cap 1 15/16", Dry Wall Return = None CPD = Non=Manufacturer Related = " ' - Unit 1: Glass Width = 17.8125, Glass Height = 29.8125 Rough Opening: 24" X 36" Overall Unit Size: 23.5" X 35.5" Room Location: None Assigned * All drawings are viewed from exterior of window. Page 3 Of 5 NPR 6/9/2016 +K u ? "QUOTE # ` c ., :,PROJECT' NAME'= °CUSTOMER- ,O#L., !.. kORDER'PLACED BY ._ PLANNED LOAD DATE _. 80747 Avenida Diaz - back 13145 tellenz Quote Not Ordered _, JOB ,NAMEF.,_ : y ~QUOTE NAME ; a_ ;'y , u' > :�..;T; _ ORDER'DATE �, ';``' SHIP, METHOD Avenida Diaz Copy of Avenida Diaz - Quote Not Ordered SPW TRUCK back LINE# LINE TYPE DESCRIPTION . QUANTITY 600-1 WindowAndDoor PK 267 1 * *Standard -Painted exterior color Set -Up Charge not included. Charge will not apply to orders of.vinyl units greater than 4 or any quantity in combination with clad of the same color.** Vinyl Superseal 8000.CasementAwning Casement Left 23.5 x 35.5 24 x 36, Frame Width = 23.5, Frame Height = 35.5 Complete Unit, DP Rating = Standard Frame Color = Patina Green, Interior Finish = White Sash -Panel Color = Patina Green Dual Insulated, Super Sun Blocker Low -E, Standard Bead, Standard Obscure, Argon Gas = Yes, Spacer Channel = Standard Intercept Spacer E -Guard Finish (Beige), Roto, Standard Handle, White, Window Opening Control Device = No Screen Option = Full Screen Applied, White, Fiberglass Mesh Integral Rigid Vinyl Nailing Fin, No Drip Cap 1 15/16", Dry Wall Return = None CPD = Non -Manufacturer Related = Unit 1: Glass Width = 17.8125, Glass Height = 29.8125 Rough Opening: 24" X 36" Overall Unit Size: 23.5" X 35.5" Room Location None Assigned * All drawings are viewed from exterior of window. Page 4 Of 5 NPR 6/9/2016 QUOTE # -PROJECT NAME 'CUSTOMER P,.O# " ORDER PLACED BY PLANNED LOAD -DATE 807 47 Avenida Diaz - back 13145 tellenz Quote Not Ordered .„ i' 15 QUOTE NAME. .._.,' .-- O RDER DATE:: .'SHIP METHOD°JOBNAME Avenida Diaz Copy of Avenida Diaz - Quote Not Ordered SPW TRUCK nacK 1 PROJECT QUOTE Avenida Diaz - back Copy of Avenida Diaz-- back Comments: 4/27/2016 PRICE IS LIST AND VALID FOR 30 DAYS LC 4/28/2016 CHANGES LC COMPANY Unless otherwise noted on the line item, this product is covered under a Sierra Pacific Windows limited warranty. Please see your dealer, the Websites (www.Hurd.com, www.supersealwindows.com) or our marketing literature for a copy of the applicable limited warranty for specific language, limitations and exclusions. The pricing on this Quote 'is valid for 30 days and not intended to be used as a final Invoice. The Quote does not include charges for Shop Drawings. Sierra Pacific offers a variety of wood sp@cies produced in combinations of solid and veneer -wrapped wood parts that have varying grain patterns. Wood characteristics also vary due to the species of the wood. The combination of these items could result in color variations of the finished stained products. Outswing Doors will have a complementary species of wood threshold. RATINGS Oversized units and certain mulled/stacked gurations confihave not been tested and therefore have no design pressure (DP) rating. Job -specific engineering analysis may be available for these non -rated units. Please contact your DST group to determine available options for non -tested product. A complete list of tested products is available at www.hurd.com. The Transcend H3 products do not have a DP rating. If units are being installed in an area requiring specific DP ratings, the unit must be installed in the exact manner tested, as shown in our certified installation details. These details can be found on the Florida Building Code website at www.floridabuilding.org or can be obtained by contacting Sierra Pacific's Architectural Services Department at 800-433-4873 ext. 3500. Recent building code changes require the addition of limiting devices on any operating unit installed where the finished clear opening of the unit is within 24" of the floor and is more than 72" above the finished grade.or other surface below the window. Please check with your local building department to determine if this code is a requirement in your jurisdiction and order units accordingly. We Appreciate Your Business! * A11, drawings are viewed from exterior of window. • Page 5 Of 5 NPR . 6/9/2016