BCOM2016-0021 Title 24II BUILDING ENERGY ANALYSIS REPORT '.Mh� I PROJECT: . Lazer Oasis Tenant Improvement 46-805 Dune Palms Rd La Quinta, CA 92253 Project Designer: Niche Builders, Inc. 840 East West Drive Murphys , CA 95247 (209) 609-3752 CITY OF LA OUINTA BUILDING & SAFETY Report Prepared by: r1% FOR CONSTRUCTION Tim Scott Scott Design and Title 24, In 9 , DATE (0 t to BY� . 78818 Velie Way; Suite 8 (e ZA' Palm Desert, CA 92260 (760) 777-0102 Job Number: Date: 6/23/2016 The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards. This program, developed by EnergySoft, LLC—www.energysoft.com. EnergyPro6.7 by EnemvSoft User Number: 6712 ID: r E • r� Project Name: Lazer Oasis NRCC-PRF-01-E Page 1 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xmi A. PROJECT GENERAL INFORMATION 1. Project Location (city) La Quinta 7. # of dwelling units 0 2. CA Zip Code 92253 8. Standards Version Cornpliance2015 3. Climate Zone 15 9. Compliance Software (version) EnergyPro 6.7 4. Total Conditioned Floor Area 11,700 ft2 1U. Buming urientation (deg) (E) 98 deg 5. Total Unconditioned Floor Area 4,364 ft2 11. Permitted Scope of Work ExistingAlteration 6. # of Stories (Habitable Above Grade) 2 12 Building Type(s) Nonresidential B. COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS § 140.1 BUILDING COMPLIES 1. Energy Component 2. Standard Design (TDV) 3. Proposed Design (TDV) 4. Compliance Margin (TDV) S. Percent Better than Standard Space Heating 4.0 1.9 2.1 52.5% Space Cooling 351.7 314.9 36.8 10.5% Indoor Fans 107.0 139.5 -32.5 -30.4% Heat Rejection -- -- - Pumps & Misc. 0.2 -- 0.2 Domestic Hot Water 17.0 32.3 -15.3 -90.0% Indoor Lighting 148.1 104.1 44.0 29.7% COMPLIANCE TOTAL - 628.0 592.7 35.3 5.6% Receptacle 130.1 130.1 0.0 0.0% Process -- -- -- -- Process Ltg - - -- TOTAL 758.1 722.8 35.3 4.7% CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 0 0 9 Project Name: Lazer Oasis NRCC-PRF-01-E Page 2 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xml C. PRIORITY PLAN CHECK/ INSPECTION ITEMS (in order of highest to lowest TDV energy savings) 1st Indoor Lighting: Check lighting Compliance Margin By Energy Component (from Table B column 4) Indoor Lighting Space Cooling Space Heating Pumps & Misc. Heat Rejection Domestic Hot Water Indoor Fans y ' Penalty Eriergy Credit 2nd Space Cooling: Check envelope and mechanical 3rd Space Heating: Check envelope and mechanical 4th Pumps & Misc.: Check mechanical 5th Heat Rejection: Check envelope and mechanical 6th Domestic Hot Water: Check mechanical 7th Indoor Fans: Check envelope and mechanical D. EXCEPTIONAL CONDITIONS E. HERS VERIFICATION This Section Does Not Apply F. ADDITIONAL REMARKS None Provided CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 �i Project Name: Lazer Oasis NRCC-PRF-01-E Page 3 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xml G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY Identify which building components use the performance or prescriptive path for compliance. "NA"= not in project For components that utilize the performance path, indicate the sheet number that includes mandatory notes on plans. Building Component Compliance Path Compliance Forms (required for submittal) Location of Mandatory Notes on Plans Envelope ® Performance NRCC-PRF-ENV-DETAILS (section of the NRCC-PRF-01-E) ❑ Prescriptive NRCC-ENV-01 / 02 / 03 / 04 / 05 / 06-E ❑ NA Mechanical ® Performance NRCC-PRF-MCH-DETAILS (section of the NRCC-PRF-01-E) ❑ Prescriptive NRCC-MCH-01 / 02 / 03 / 04 / 05 / 06 / 07-E ❑ NA Domestic Hot Water ® Performance NRCC-PRF-PLB-DETAILS (section of the NRCC-PRF-01-E) ❑ Prescriptive NRCC-PLB-01-E ❑ , NA Lighting (Indoor Conditioned) ® Performance NRCC-PRF-LTI-DETAILS (section of the NRCC-PRF-01-E) ❑ Prescriptive NRCC-LTI-01 / 02 / 03 / 04 / 05-E ❑ NA Covered Process: Commercial Kitchens. ❑ Performance S2 (section of the NRCC-PRF-01-E) ® Prescriptive NRCC PRC Ol/ 03 E ❑ NA Covered Process: Computer Rooms ❑ Performance S3 (section of the NRCC-PRF-01-E) ❑ Prescriptive NRCC PRC-01/ 04-E ® NA Covered Process: Laboratory Exhaust ❑ Performance 54 (section of the NRCC-PRF-01-E) ❑ Prescriptive NRCC PRC O1/ 09 E ® NA CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 Project Name: Lazer Oasis NRCC-PRF-01-E Page 4 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xm1 G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY The following building components ore only eligible for prescriptive compliance. Indicate which ore The following building components may have mandatory requirements per Part 6. Indicate relevant to the project. which are relevant to the project. Yes NA Prescriptive Requirement Compliance Forms Yes NA Mandatory Requirement Compliance Forms Lighting (Indoor Commissioning: §120.8 E] ® NRCC-LTI-01 / 02 / 03 / 04 / 05-E ❑ ® Simple Systems NRCC-CXR-01 / 02 / 03 / 05-E Unconditioned) §140.6 ❑ ® Complex Systems NRCC-CXR-01 / 02 / 04 / 05-E ❑ ® Lighting (Outdoor) §140.7 NRCC-LTO-01 / 02 / 03-E ® ❑ Electrical: §130.5 NRCC-ELC-01-E ❑ ® Lighting (Sign) §140.8 NRCC-LTS-01-E ❑ ® Solar Ready: §110.10 NRCC-SRA-01 / 02-E Covered Process: §120.6 NRCC-PRC-01-E ❑ ® Parking Garage NRCC-PRC-02-E ❑ ® Solar Thermal Water NRCC-STH-Ol-E ❑ ® Commercial Refrigeration NRCC-PRC-05-E Heating: §140.5 ❑ ® Warehouse Refrigeration NRCC-PRC-06/07/08-E ❑ ® Compressed Air NRCC-PRC-10-E ❑ ® Process Boilers NRCC-PRC-11-E CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance' Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 • Project Name: Lazer Oasis NRCC-PRF-01-E Page 5 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xml H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCl/NRCA/NRCV) — — Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment. Confirmed Building Component Compliance Forms (required for submittal) Pass Fail Envelope ® NRCI-ENV-01-E - For all buildings ❑ `❑ , ❑ NRCA-ENV-02-F- NFRC label verification for fenestration ❑ ❑ Mechanical ® NRCI-MCH-01-E - For all buildings with Mechanical Systems ❑ ❑ ® NRCA-MCH-02-A- Outdoor Air ❑ ❑ ® NRCA-MCH-03-A—Constant Volume Single Zone HVAC ❑ ❑ ❑ NRCA-MCH-04-H- Air Distribution Duct Leakage ❑ ❑ ❑ NRCA-MCH-05-A- Air Economizer Controls ❑ ❑ ❑ NRCA-MCH-06-A- Demand Control Ventilation ❑ ❑ ❑ NRCA-MCH-07-A—Supply Fan Variable Flow Controls ❑ ❑ ® NRCA-MCH-08-A- Valve Leakage Test ❑ ❑ ® NRCA-MCH-09-A—Supply Water Temp Reset Controls ❑ ❑ ❑ NRCA-MCH-10-A- Hydronic System Variable Flow Controls ❑ ❑ ❑ N RCA-MCH-11-A —Auto Demand Shed Controls ❑ ❑ ❑ NRCA-MCH-12-A- Packaged Direct Expansion Units ❑ ❑ ❑ NRCA-MCH-13-A- Air Handling Units and Zone Terminal Units ❑ ❑ ❑ NRCA-MCH-14-A- Distributed Energy Storage ❑ ❑ ❑ NRCA-MCH-15-A— Thermal Energy Storage ❑ ❑ ❑ NRCA-MCH-16-A- Supply Air Temp Reset Controls ❑ ❑ ❑ NRCA-MCH-17-A — Condensate Water Temp Reset Controls ❑ ❑ ❑ NRCA-MCH-18-A- Energy Management Controls Systems ❑ ❑ ❑ NRCV-MCH-04-H- Duct Leakage Test ❑ ❑ CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 0 0 0 Project Name: Lazer Oasis NRCC-PRF-01-E Page 6 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xml H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCl/NRCA/NRCV) — Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment. Confirmed Building Component Compliance Forms (required forsubmittal) Pass Fail Plumbing ® NRCI-PLB-01-E - For all buildings with Plumbing Systems ❑ ❑ ❑ NRCI-PLB-02-E - required on central systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCI-PLB-03-E - Single dwelling unit systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCI-PLB-21-E - HERS verified central systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCI-PLB-22-E - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCV-PLB-21-H- HERS verified central systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCV-PLB-22-H - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application. ❑ ❑ ❑ NRCI-STH-01-E - Any solar water heating ❑ ❑ Indoor Lighting ® NRCI-LTI-01-E - For all buildings ❑ ❑ ❑ NRCI-LTI-02-E -Lighting control system, or for an Energy Management Control System (EMCS) ❑ ❑ ❑ NRCI-LTI-03-E - Line -voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to energize only line -voltage track lighting ❑ ❑ ❑ NRCI-LTI-04-E - Two interlocked systems serving an auditorium, a convention center, a conference room, or a theater ❑ ❑ ❑ NRCI-LTI-05-E -Lighting Control Credit Power Adjustment Factor (PAF) ❑ ❑ ❑ NRCI-LTI-06-E - Additional wattage installed in a video conferencing studio ❑ ❑ ❑ NRCA-LTI-02-A - Occupancy sensors and automatic time switch controls. ❑ ❑ ❑ NRCA-LTI-03-A - Automatic daylighting controls ❑ ❑ ❑ NRCA-LTI-04-A - Demand responsive lighting controls ❑ ❑ Outdoor Lighting ❑ NRCI-LTO-01-E — Outdoor Lighting ❑ ❑ ❑ NRCI-LTO-02-E- EMCS Lighting Control System ❑ ❑ ❑ NRCA-LTO-02-A - Outdoor Lighting Control ❑ ❑ Sign Lighting ❑ NRCI-LTS-01-E —Sign Lighting ❑ ❑ Electrical ® NRCI-ELC-01-E - Electrical Power Distribution ❑ ❑ Photovoltaic ❑ NRCI-SPV-01-E Photovoltaic Systems ❑ ❑ CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 0 0 9 Project Name: Lazer Oasis NRCC-PRF-01-E Page 7 of 21' Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xml H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCl/NRCA/NRCV) — Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment. Confirmed Building Component Compliance Forms (required for submittal) Pass Fail Covered Process ❑ NRCI-PRC-01-E Refrigerated Warehouse ❑ ❑ ❑ NRCA-PRC-01-F- Compressed Air Systems ❑ ❑ ❑ NRCA-PRC-02-F- Kitchen Exhaust ❑ ❑ ❑ NRCA-PRC-03-F- Garage Exhaust ❑ ❑ ❑ NRCA-PRC-04-F- Refrigerated Warehouse- Evaporator Fan Motor Controls ❑ ❑ ❑ NRCA-PRC-05-F- Refrigerated Warehouse- Evaporative Condenser Controls ❑ ❑ ❑ NRCA-PRC-06-F- Refrigerated Warehouse- Air Cooled Condenser Controls ❑ ❑ ❑ NRCA-PRC-07F- Refrigerated Warehouse- Variable Speed Compressor ❑ ❑ ❑ NRCA-PRC-08-F- Electrical Resistance Underslab Heating System ❑ ❑ I. ENVELOPE GENERAL INFORMATION (See NRCC-PRF-ENV-DETAILS for more information) 1. Total Conditioned Floor Area 11,700 ft2 5. Number of Floors Above Grade 2 Confirmed 2. Total Unconditioned Floor Area 4,364 ft2 6. Number of Floors Below Grade 0 V N T OJ _ 3. Addition Conditioned Floor Area 0 ft2 4. Addition Unconditioned Floor Area 0 ft2 7. Opaque Surfaces & Orientation 8. Total Gross Surface Area 9. Total Fenestration Area 10. Window to Wall Ratio North Wall 508 ft2 0 ft2 00.0% ❑ ❑ East Wall 5,420 ft2 771 ft2 14.2% ❑ ❑ South Wall 956 ft2 90 ft2 09.4% ❑ ❑ West Wall 2,330 ft2 90 ft2 03.9% ❑ ❑ Total 9,214 ft2 951 ft2 10.3% ❑ ❑ Roof 11,700 ft2 0 ft2 00.0% ❑ I ❑ CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 Project Name: Lazer Oasis NRCC-PRF-01-E Page 8 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xm1 J. FENESTRATION ASSEMBLY SUMMARY § 110.6 Confirmed 1. 2. 3. 4. S. 6. 7. 8. 9. Fenestration Assembly Name / Overall Overall Overall � T 01 Fenestration Type Certification Method' Assembly Method Area ft1 v Tag or I.O. U-factor SHGC VT N Double Metal Tinted Vertica I Fenestration DefaultPerformance Manufactured 951 0.76 0.60 1 0.55 E ❑ ❑ 1 Newly installed fenestration shall have a certified NFRC Label Certificate or use the CEC default tables found in Table 110.6-A and Table 110.E-B. Site -built fenestration less than 1,000 ft� or more than or equal to 1,000 ftZ see Reference Nonresidential Appendix NA6. I Status: N - New, A - Altered, E - Existing Taking compliance credit for fenestration shading devices? (if "Yes", see NRCC-PRF-ENV-DETAILS for more information) K. OPAQUE SURFACE ASSEMBLY SUMMARY § 120.7/ § 140.3 Confirmed 1. 2. 3. 4. S. 6. 7. 8. Surface Name Surface Type 1 Area (ft) Framing Type Cavity R-Value Continuous R-Value U-Factor / F-Factor / C-Factor E N °' R-30 Roof Attic18 Roof 13029 Wood 30 NA U-Factor: 0.038 E ❑ ❑ Existing Wa1120 ExteriorWall 13146 NA 0 NA U-Factor: 0.366 E ❑ ❑ Existing Partition32 ExteriorWall 1040 Wood 11 NA U-Factor: 0.110 E ❑ ❑ Slab On Grade39 UndergroundFloor 22887 NA 0 NA F-Factor: 0.730 E ❑ ❑ R-30 Roof(R.30.2x12.16)92 Roof 3035 Wood 30 NA U-Factor: 0.042 E ❑ ❑ R-19 Floor Crawlspace100 ExteriorFloor 1077 Wood 19 NA U-Factor: 0.047 j A ❑ R-19 Floor Crawlspace1001 InteriorFloor 1077 Wood 19 NA U-Factor: 0.046 1 E ❑ ❑ I Status: N - New, A - Altered, E - Existing L. ROOFING PRODUCT SUMMARY I § 140.3 Confirmed 1. 2. 3. 4. S. 6. 7. Product Type Product >_25 lb ft1 Aged Solar Reflectance Thermal Emittance SRI Cool Roof Credit CRRC Product ID Number a d R-30 Roof Attic18 No 0.08 0.75 NA No NA ❑ ❑ R-30 Roof (R.30.2x12.16)92 No 0.08 0.75 NA No NA ❑ I ❑ CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 Project Name: Lazer Oasis NRCC-PRF-01-E Page 9 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xm1 M. HVAC SYSTEM SUMMARY (see NRCC-PRF-MCH-DETAILS for more information) § 110.1 / § 110.2 Dry System Equipment' (Fan & Economizer info included below in Table N) Confirmed 1. 2. 3. 4. S. 6. 7. 8. 9. 10. 11. System Type Total Heating Supp Heat Supp Heat Total Cooling Efficiency Acceptance Testing „ a Equip Name Equip Type 3 (Simple or Qty Output Source (Y/N) Output Output Required? (Y/N) N Complex') (kBtu/h) (k8tuh) (kBtu/h) s Cooling Heating HVAC 1-53 SZHP (Packaged3Phase) Simple 5 120 No 0 120 EER-11.0 COP-3.3 No E ❑ ❑ HVAC-1066 SZHP (Split3Phase) Simple 1 36 No 0 36 SEER-13.0 HSPF-7.7 Yes N ❑ ❑ HVAC81 SZHP (Packaged3Phase) Simple 4 69 Yes 17 69 EER-11.0 COP-3.3 Yes N ❑ ❑ Wet System Equipment 1 Pumps Confirmed 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. Rated Capacity Tank VSD w oVi oTi E. Equip Name q P Equip Type 4 P YP Qty Vol al (gal) (kBtu/h) Efficiency � StandbyLoss Ext. R Qty GPM HP (y/N) Value P Rheem HE119-1602 Storage 4 119 160 Thrml. Eff: 0.869 0.0085 NA NA NA NA No N ❑ ❑ " AO SMITH EUF-06*80 Storage 2 6 5 EF: 0.950 NA NA NA NA NA No N ❑ ❑ 1 Dry System Equipment includes furnaces, air handling units, heat pumps, etc. 2 Wet System Equipment includes boilers, chillers, cooling towers, water heaters, etc. 3 Simple. Systems must complete NRCC-CXR-03-E commissioning design review form Complex Systems must complete NRCC-CKR-04-E commissioning design review farm 5 A summary of which acceptance tests are applicable is provided in NRCC-PRF-MCH-DETAILS 6 Status: N - New, A - Altered, E - Existing Discrepancy between modeled and designed equipment sizing? (if "Yes", see Table F. "Additional Remarks" for an explanation) No CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 • Project Name: Lazer Oasis NRCC-PRF-01-E Page 10 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xml N. ECONOMIZER & FAN SYSTEMS SUMMARY' § 140.4 Confirmed' 1. 2. 3. 4. 5. Outside Supply Fan Return Fan Air v -n Economizer Type N T. TSP TSP Equip Name (if present) CFM CFM HP BHP (inch Control CFM HP BHP (inch Control WC) WC) HVAC 1-53 406 4000 2.000 2.000 1.90 ConstantVolume NA NA NA NA NA NoEconomizer ❑ ❑ HVAC-1066 416 1200 0.330 0.330 0.87 ConstantVolume NA NA NA NA NA NoEconomizer ❑ ❑ HVAC81 190 2300 j 1.000 j 1.000 j 1.66 j ConstantVolume j NA j NA j NA j NA j NA NoEconomizer ❑ ❑ ' Mechanical ventilation calculations and exhaust fans are included in the NRCC-PRF-MCH-DETAILS section O. EQUIPMENT CONTROLS 1.§ 120.2 Confirmed 1. 2. 3. V d T y Equip Name Equip Type Controls No DCV Controls HVAC 1-53 SZHP No Economizer ❑ ❑ No Supply Air Temp. Control No DCV Controls HVAC-1066 SZHP No Economizer ❑ ❑ No Supply Air Temp. Control No DCV Controls HVAC81 SZHP No Economizer ❑ ❑ No Supply Air Temp. Control DHW1- SHW Service Hot Water, Primary Only Fixed Temperature Control, No DDC ❑ ❑ DHW79 - SHW Service Hot Water, Primary Only Fixed Temperature Control, No DDC ❑ ❑ P. SYSTEM DISTRIBUTION SUMMARY § 120.4/ § 140.4(i) This Section Does Not Apply Does the Project Include Zonal Systems? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information) No Does the Project Include a Solar Hot Water System? (if "Yes", see NRCC-PRF-MCH-DETAILS for system information) No Multifamily or Hotel/ Motel Occupancy? (if "Yes", see NRCC-PRF-MCH-DETAILS for DHW system information) No CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 Project Name: Lazer Oasis NRCC-PRF-01-E Page 11 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xmi Q. INDOOR CONDITIONED LIGHTING GENERAL INFO (see NRCC-PRF-LTI-DETAILS for more info); § 140.6 Confirmed 1. 2. 3. 4. S. 1 Occupancy Type Conditioned Floor Area 2 Installed Lighting Power Lighting Control Credits Additional (Custom) Allowance M N -n °' (ft2) (Watts) (Watts) Area Category Footnotes Tailored Method (Watts) ❑ ❑ (Watts) Retail Merchandise Sales, 11,700 10,530 0 0 0 ❑ ❑ Wholesale Showroom Building Totals: 11,700 10,530 0 1 See Table 140.E-C 2 See NRCC-LTI-01-E for unconditioned spaces 3Lighting information for existing spaces modeled is not included in the table R. INDOOR CONDITIONED LIGHTING SCHEDULE (Adapted from NRCC-LTI-01-E)l § 130.0 Luminaire Schedule (includes all permanent installed lighting in conditioned space, and portable lighting over 0.3 w/ftz in offices) Installed Watts (Conditioned) Confirmed Name or Item Tag3-lam Complete Luminaire Description (i.e., P fluorescent troffer, F32T8, one dimmable electronic ballast) Watts per luminaire P How Wattage is Determined Total Number Luminaires Installed Watts Pass Fail CEC Default from NA8 According to §330.0(c) 1X4 1X4LED 90 Yes No 11 990 ❑ ❑ 2X2 L 2X2 LED 26 Yes No 4 104 ❑ ❑ 2X2 FI 2X2 Flor. 39 Yes No 5 195 ❑ ❑ 2X4 2X4 LED 54 Yes No 29 1,566 ❑ ❑ CLF CLF (2) 26W 52 Yes No 3 156 ❑ ❑ 4 Can 4" Can 14 Yes No 60 840 ❑ ❑ 6 Can 6" Can 20 Yes No 88 1,760 ❑ ❑ HG Lt Hang. Lt (8) 15W 120 Yes No 5 600 ❑ ❑ Ex 2X4 Ex 2X4 FI 104 Yes No 37 3,848 ❑ ❑ D (2) 4 ft Fluorescent T8 54 Yes No 8 432 ❑ ❑ Ex 2X2 Ex 2X2 FI 39 Yes No 1 39 ❑ ❑ 'if lighting power densities were used in the compliance model Building Departments will need to check prescriptive forms for Luminaire Schedule details. CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 Project Name: Lazer Oasis NRCC-PRF-01-E Page 12 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration r Input File Name: Laser Oasis -Niche -Polar Barr-16.xml S1. COVERED PROCESS SUMMARY — ENCLOSED PARKING GARAGES § 140.9 This Section Does Not Apply S2. COVERED PROCESS SUMMARY —COMMERCIAL KITCHENS § 140.9 This Section Does Not Apply S3. COVERED PROCESS SUMMARY —COMPUTER ROOMS § 140.9 This Section Does Not Apply S4. COVERED PROCESS SUMMARY— LABORATORY EXHAUSTS § 140.9 This Section Does Noi Apply T. UNMET LOAD HOURS Cooling Unmet Load Hour Limit for Heating Unmet Load Hour Limit for Thermal Zone Name Thermal Zone proposed Cooling Unmet Load Hours Thermal Zone proposed Heating Unmet Load Hours 5-Party Room Zone 150 1953.5 150 0.25 U. ENERGY USE SUMMARY Electric (kWh/yr) Natural Gas (therms/yr) Total Annual Baseline 313881 1382.32 Total Annual Proposed 310650 970.231 CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 • • • Project Name: Lazer Oasis NRCC-PRF-01-E Page 13 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xml DOCUMENTATION AUTHOR'S DECLARATION STATEMENT § 10-103 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Tim Scott Signature: Company: Scott Design and Title 24, Inc, Address: 78818 Velie Way, Suite 8 Signature Date: City/State/Zip: Palm Desert CA 92260 CEA Identification (If applicable): Phone: (760) 777-0102 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1 I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect. 2 I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. 3 I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538 and 6737.1. Responsible Envelope Designer Name: Joe Donati Signature: Company: Niche Builders, Inc. Address: 840 East West Drive Date Signed: City/State/Zip: Murphys CA 95247 Declaration Statement Type: Phone: (209) 609-3752 Title: License #: Responsible Lighting Designer Name: Joe Donati Signature: Company: Niche Builders, Inc. Address: 840 East West Drive Date Signed: City/State/Zip: Murphys CA 95247 Declaration Statement Type: Phone: (209) 609-3752 Title: License #: Responsible Mechanical Designer Name: Dexter Barr Signature: 4 ei= Company: Polar Barr Air Conditioning, Inc. Address: 41-921 Beacon Hill, Suite C Date Signed: City/State/Zip: Palm Desert Ca 92211 Declaration Statement Type: Phone: (760) 346-5529 Title: License #: CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 s 0 • Project Name:, Lazer Oasis NRCC-PRF-01-E Page 14 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration . Input File Name: Laser Oasis -Niche -Polar Barr-16.xml NRCC-PRF-ENV-DETAILS -SECTION START A. OPAQUE SURFACE ASSEMBLY DETAILS Confirmed 1. 2. 3. 4. v N '^ T � _ Surface Name Surface Type Description of Assembly Layers Notes Asphalt shingles - 1/4 in. Vapor permeable felt - 1/8 in. R-30 Roof Attic18 Roof • Plywood - 1/2 in. ❑ ❑ Air - Cavity - Wall Roof Ceiling - 4 in. or more Wood framed roof, 24in. OC, 3.5in., R-30 Gypsum Board - 1/2 in. Existing Wa1120 ExteriorWall Concrete - Solid Grout - 105 Ib/ft3 - 8 in. ❑ ❑ Air - Cavity - Wall Roof Ceiling - 4 in. or more Stucco - 7/8 in. Existing Partition32 ExteriorWall Vapor permeable felt - 1/8 in. ❑ El Wood framed wall, 16in. OC, 3.5in., R-11 Gypsum Board - 1/2 in. Slab Type = UnheatedSlabOnGrade Slab On Grade39 Underground Floor Insulation Orientation = None ❑ ❑ Insulation R-Value = RO Asphalt shingles - 1/4 in. Vapor permeable felt - 1/8 in. R-30 Roof (R.30.2x12.16)92 Roof Plywood - 1/2 in. El ❑ Air - Cavity - Wall Roof Ceiling - 4 in. or more Wood framed roof, 16in. OC, 3.5in., R-30 Gypsum Board - 1/2 in. Air - Floor - 3 1/2 in. R-19 Floor Crawlspace100 ExteriorFloor Wood framed floor, 16in. OC, 5.5in., R-19 ❑ ❑ Plywood - 1/2 in. Carpet - 3/4 in. Air - Floor - 3 1/2 in. R-19 Floor Crawlspace1001 InteriorFloor Wood framed floor, 16in. OC, 5.5in., R-19 ❑ ❑ Plywood - 1/2 in. Carpet - 3/4 in. CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 Project Name: Lazer Oasis NRCC-PRF-01-E Page 15 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: - Laser Oasis -Niche -Polar Barr-16.xml B. OVERHANG DETAILS (Adapted from NRCC-ENV-02-E) This Section Does Not Apply C. OPAQUE DOOR SUMMARY Confirmed 1. 2. 3. 4. S. Opaque Door Assembly Name / Tag or I.D. Door Type Certification Method Operation Overall U-factor Pass Fail Insulated Metal Door22 Meta lUninsulatedSingleLayerpoor DefaultPerformance Swinging 0.079 ❑ ❑ 1 Stotus: N- New, A -Altered, E- Existing NRCC-PRF-MCH-DETAILS -SECTION START - A. MECHANICAL VENTILATION AND REHEAT (Adapted from 2013-NRCC-MCH-03-E) Confirmed 1. DESIGN AIR FLOWS 2. VENTILATION (§ 120.1) tsn v o 9 A D Z Gl Z D Z Z X v < O Z O 3 Z rn C) z C < m v+ vZ+ v a� OC �� O� n Z 1 Z r1< to Z m p T O C Z Z T Z C m v d w CONDITIONED 00 3 N 3 n D < ZONE NAME 0 3 z D n m D m A v 3 v m m 70 z Z N Z r. j n< _n � 3 -n �> Or m 3 D N A O A G -n -- D z 0 D T 3 Z< _ Z D < v Z GZ1 C) Z O m O t^ r O n LAr 3 D D D :. D m O Z n T T 3 1-lower Lever HVAC 1-53 4,000 NA NA NA NA N HVAC 1-53 8,111 0.25 270 7.5 2,028 2,028 NA N ❑ ❑ 5-Party Room HVAC-1066 1,200 NA NA NA NA N HVAC-1066 554 0.75 55 7.5 416 416 NA N ❑ ❑ Zone 6-Upper Level HVAC81 2,300 NA NA NA NA N HVAC81 3,035 0.25 101 7.5 759 759 NA N ❑ ❑ TOTAL 16,064 1 426 1 3,203 3,203 NA ❑ ❑ CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 • 0 Project Name: Lazer Oasis NRCC-PRF-01-E Page 16 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xml B. ZONAL SYSTEM AND TERMINAL UNIT SUMMARY § 140.4 1. 2. 3. 4. S. 6. 7. 8. Confirmed Rated Capacity Airflow (cfm) Fan (kBtuh) System ID System Type Qty Economizer Zone Name a Heating Cooling Design Min. Min. BHP Cycles ECM N — Ratio Motor lower Lever5-TRM Uncontrolled S NA NA NA 1-lower Lever 4000 NA NA NA NA ❑ ❑ ❑ Party Room Uncontrolled 1 NA NA NA 5-Party Room Zone 1200 NA NA NA NA ❑ ❑ ❑ Zone68-TRM Upper Leve183-TRM Uncontrolled 4 NA I NA NA 6-Upper Level 2300 NA NA NA NA r ❑ ❑ ❑ C. EXHAUST FAN SUMMARY This Section Does Not Apply D. DHW EQUIPMENT SUMMARY — (Adapted from NRCC-PLB-01) § 110.3 Confirmed 1. 2. 3. 4. S. 6. 7. 8. 9. 10. 11. 12. � DHW Name Fuel Type Qty Distribution Rated Input Efficiency Pilot Energy External Tank Vol Standby Loss Vol. of Suppl. N T °' Type ketuh (Btu/h) Insulation Storage Tank Rheem NaturalGas Storage 4 Nonrecirculating 160 Thrml. Ef .: 0 NA 119 0.0085 NA ❑ ❑ HE119-1602 0.869 AO SMITH Electricity Storage 2 Non recirculating 5 EF:0.950 0 NA 6 0.027 NA El ELJF-06*80 E. MULTI -FAMILY CENTRAL DHW SYSTEM DETAILS This Section Does Not Apply F. SOLAR HOT WATER HEATING SUMMARY (Adapted from NRCC-STH-01) This Section Does Not Apply CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 r� Project Name: Lazer Oasis NRCC-PRF-01-E Page 17 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xml G. MECHANICAL HVAC ACCEPTANCE TESTS & FORMS (Adapted from 2013-NRCC-MCH-01-E) § RA4 Declaration of Required Acceptance Certificates (NRCA) — Acceptance Certificates that may be submitted. (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). Test Description n x n x n x n x n x n x n x n x n x n x n x n x n x n x n x n x n x Confirmed 6 N 6 6 6 6 6 o O 4 r i+ F+ W r A r+ Ln f+ al ►. V L. 00 D D D D D D D D D D D D D D D D D C D m o c LA v a o p� N m n Equipment - O M _ p N D Requiring #of a ON .. O -< rD z p d p 3 3 O N O o v ro x .*rD � o m r) v �, Testing or units ° fD c v n < v z o Cr a o. Q x ' rD o D < ri N fD 3 rM Verification D ? < o „ D o v o f p, K O N < 2 'O :E CD 2 ry M N DHW1- 1 -- X X El ElSHW DHW79 - 1 X ❑ ❑ SHW HVAC 1-53 5 ❑ ❑ HVAC-1066 1 X X -- - ❑ ❑ HVAC81 4 X _ X ❑ ❑ H. EVAPORATIVE COOLER SUMMARY This Section Does Not Apply CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 • 9 Project Name: Lazer Oasis NRCC-PRF-01-E Page 18 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xml NRCC-PRF-LTI-DETAILS -SECTION START - A. INDOOR CONDITIONED LIGHTING CONTROL CREDITS (Adapted from NRCC-LTI-02-E) § 140.6 Lighting Control Credits Schedule (includes all lighting controls installed in conditioned space for Control Credit Calculation Confirmed compliance credit per §140.6(a)2 and Table 140.6-A) V If Acceptance Test Required q Location in Occupancy Type (must meet Type/Description of Lighting Watts of Power Control Credit Building requirements of Table 140.6-A) Control (i.e., partial on occupancy # of Units Controlled Adjustment Watts sensor, manual dimming, etc.) Lighting Factor Pass Fail S-1-lower Lever Retail Merchandise Sales, - none specified - 1 990 0.00 0 ❑ ❑ Wholesale Showroom S 1 lower Lever Retail Merchandise Sales, -none specified - 1 104 0.00 0 ❑ ❑ Wholesale Showroom S-1-lower Lever Retail Merchandise Sales, none specified - 1 195 0.00 0 ❑ ❑ Wholesale Showroom S-1-lower Lever Retail Merchandise Sales, none specified - 1 648 •0.00 0 ❑ ❑ Wholesale Showroom S-1-lower Lever Retail Merchandise Sales, - none specified - 1 156 0.00 0 ❑ n Wholesale Showroom S-1-lower Lever Retail Merchandise Sales, none specified - 1 644 0.00 0 ❑ ❑ Wholesale Showroom S 1 lower Lever Retail Merchandise Sales, none specified - 1 1240 0.00 0 ❑ El Wholesale Showroom S 1 lower Lever Retail Merchandise Sales, none specified 1 360 0.00 0 El ❑ Wholesale Showroom S 1 lower Lever Retail Merchandise Sales, none specified 1 1144 0.00 0 El ❑ Wholesale Showroom S-5-Party Room Retail Merchandise Sales, none specified 1 432 0.00 0 ❑ ❑ Zone Wholesale Showroom S-6-Upper Level Retail Merchandise Sales, none specified - 1 432 0.00 0 ❑ ❑ Wholesale Showroom S-6-Upper Level Retail Merchandise Sales, none specified - 1 486 0.00 0 ElWholesale ❑ Showroom S 6 Upper Level Retail Merchandise Sales, none specified - 1 196 0.00 0 El El Wholesale Showroom CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 • Project Name: Lazer Oasis NRCC-PRF-01-E Page 19 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xm1 A. INDOOR CONDITIONED LIGHTING CONTROL CREDITS (Adapted from NRCC-LTI-02-E) § 140.6 Lighting Control Credits Schedule (includes all lighting controls installed in conditioned space for Control Credit Calculation Confirmed compliance credit per §140.6(a)2 and Table 140.6-A) ' V If Acceptance Test wired q Location in Occupancy Type (must meet Type/Description of Lighting Watts of Power Control Credit Building requirements of Table 140.6-A) Control (i.e., partial on occupancy # of Units Controlled Adjustment Watts sensor, manual dimming, etc.) Lighting Factor Pass Fail S-6-Upper pper Level Retail Merchandise Sales, none specified 1 520 0.00 0 ❑ El Wholesale Showroom S 6 Upper Level Retail Merchandise Sales, none specified - 1 240 0.00 0 E-] E] Wholesale Showroom S-6-Upper Level Retail Merchandise Sales, none specified - 1 2704 0.00 0 ❑ ❑ Wholesale Showroom S 6 Upper Level Retail Merchandise Sales, none specified 1 39 0.00 0 El ❑ Wholesale Showroom B. INDOOR CONDITIONED LIGHTING MANDATORY LIGHTING CONTROLS (Adapted from NRCC-LTI-02-E) § 130.1 This Section Does Not Apply $130.1(a) = Manual area controls; §130.0(b)-= Multi Level; §130.1(c) = Auto Shut -Off; §130.1(d) = Mandatory Daylight; §130.1(e) = Demand Responsive C. TAILORED METHOD LIGHTING POWER ALLOWANCE SUMMARY AND CHECKLIST (Adapted from NRCC-LTI-04-E) § 140.6 General lighting power (see Table D) 0 General lighting power from special function areas (see Table E) NA Additional "use it or lose it" (See Table G) 0 Total watts 0 D. GENERAL LIGHTING POWER (Adapted from NRCC-LTI-04-E) § 140.6-D This Section Does Not Apply E. GENERAL LIGHTING FROM SPECIAL FUNCTION AREAS (Adapted from NRCC-LTI-04-E) § 140.6(c) 3H Room Number Primary Function Area Illuminance Value (LUX) Room Cavity Ratio (Table G) Allowed LPD Floor Area (ft1) Allowed Watts Confirmed pass Fail NA NA NA NA NA NA NA ❑ 1 ❑ Note: Tailored Method for Special Function Areas is not currently implemented CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 0 0 0 Project Name: Lazer Oasis NRCC-PRF-01-E Page 20 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time: 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xm1 F. ROOM CAVITY RATIO (Adapted from NRCC-LTI-04-E) Rectangular Spaces Room Number Task/Activity Description Room Length (ft) Room Width (ft) Room Cavity Height (ft) RCR Confirmed Pass Fail NA NA NA NA NA NA ❑ ❑ Non -Rectangular Spaces This Section Does Not Apply Note: All applicable spaces are listed under the Non -Rectangular Spaces table G. ADDITIONAL "USE IT OR LOSE IT" (Adapted from NRCC-LTI-04-E) 1. 2. 3. 4. Allowed Watts Confirmed Wall Display Combined Floor Display and Task Lighting Combined Ornamental and Special Effects Lighting Very Valuable Merchandise a N d = 0 0 0 0 0 ❑ ❑ S. Wall Display This Section Does Not Apply 6. Floor Display and Task Lighting This Section Does Not Apply 7. Combined Ornamental and Special Effects Lighting This Section Does Not Apply 8. Very Valuable Merchandise This Section Does Not Apply CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 Project Name: Lazer Oasis NRCC-PRF-01-E Page 21 of 21 Project Address: 46-805 Dune Palms Rd La Quinta 92253 Calculation Date/Time:- 20:07, Thu, Jun 23, 2016 Compliance Scope: ExistingAlteration Input File Name: Laser Oasis -Niche -Polar Barr-16.xml H. INDOOR & OUTDOOR LIGHTING ACCEPTANCE TESTS & FORMS (Adapted from NRCC-LTI-01-E and NRCC-LTO-01-E) I § 130.4 Declaration of Required Acceptance Certificates (NRCA) —Acceptance Certificates that must be verified in the field. (Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify). Test Description Indoor Outdoor Confirmed NRCA-LTI-02-A NRCA-LTI-03-A NRCA-LTI-04-A NRCA-LTO-02-A Equipment Requiring Testing or Verification # of units Occ Sensors / Auto Time Switch Auto Daylight Demand Responsive Outdoor Controls Mfu T Occupant Sensors 0 ❑ ❑ ❑ ❑ ❑ ❑ Automatic Time Switch 0 ❑ ❑ ❑ ❑ ❑ j ❑ Automatic Daylighting 0 ❑ ❑ ❑ ❑ ❑ ❑ Demand Responsive 0 ❑ ❑ ❑ ❑ ❑ ❑ Outdoor Controls 0 ❑ ❑ ❑ ❑ ❑ ❑ CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-06212016-760 Report Generated at: 2016-06-23 20:08:13 • • ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV-MM' Project Name Date Lazer Oasis Tenant Improvement 612312016 DESCRIPTION Building Envelope Measures: §110.8(a): Installed insulating material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20 Chapter 4, Article 3. §110.8(c): All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. §110 8(f): The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R-value of no less than R-13 between framing members. §110.7(a): All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.Z of §110.6(a): window area, 0.3 cfm/ft.z of door area for residential doors, 0.3 cfm/ft.Z of door area for nonresidential single doors (swingingand sliding), and 1.0 cfm/ft.Z for nonresidential double doors (swinging). §110.6(a): Fenestration U-factor shall be rated in accordance with NFRC 100, or the applicable default U-factor. §110.6(a) : Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site -built fenestration, or the applicable default SHGC. §110.6(b): Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors). , l v EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-06-23T20:09:04 ID: Page 24 of 37 STATE OF CALIFORNIA Electrical Power Distribution CEC-NRCC-ELC-01-E (Revised 05/15) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-ELC-01-E Electrical Power Distribution (Page 1 of 7) Project Name: Lazer Oasis Tenant Improvement Date Prepared: 6/23/2016 A. General Information Project Address: 46-805 Dune Palms Rd Climate Zone: 15 Conditioned Floor Area 11,700 Unconditioned Floor Area 4,364 Building Type: 0 Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel ❑ Schools ❑ Relocatable Public Schools m Conditioned Spaces 0 Unconditioned Spaces Phase of Construction: ❑ New Construction ❑ Addition m Alteration C CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance May 2015 r STATE OF CALIFORNIA Electrical Power Distributiori h ;� CEC-NRCC-ELC-01-E Revised 05/15 ( ) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-ELC-01-E . Electrical Power Distribution r (Page 2 of 7) Project Name: Lazer Oasis Tenant -Improvement oa�e P.ePa,ed. 6/23/2016 - B. Electrical Service Metering , ❑ Each newly installed electrical service (in both existing and newly constructed buildings) is required to be metered, as set out in Table 130.5-A, which is reproduced below. , ❑ Fill out a separate line for each electrical service that is connected to the building. Electrical Field ` Electrical Service Schedule Service Rating Metering Capabilities (check all that are present) Inspector A B C D E F G N ~ a x _ fD N p ' • CL S 7 N (D N 3 a) N 7CCc D < v S �. N N 2 C r• Designation/location in building/description kVA a � c - ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ` ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑. ❑ ❑ -❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ r, ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑' ❑ ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Table 130.5-A- MINIMUM REQUIREMENTS FOR METERING OF ELECTRICAL LOAD More than 50kVA More than 250 kVA Services rated and less than or and less than or . more than Meter Rating (kVA) 50 kVA or less equal to 250 kVA equal to 1000kVA 1000kVA s Instantaneous (at the r -- '• Required xr ;' - ;°r� Required' } •Required •. iRequired time) kW demand y. Historical peak demand (kW) Not required Not required Required Required Resettable kWh Required '. Required Required7, Required kWh per rate period Not required Not required Not required Required CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance May 2015 4 4 STATE OF CALIFORNIA Electrical Power Distribution CEC-NRCC-ELC-01-E (Revised 05/15) CERTIFICATE OF COMPLIANCE `Electrical Power Distribution " Project Name: Lazer Oasis Tenant Improvement CALIFORNIA ENERGY COMMISSION , Date Prepared:6/23/2016 NRCC-ELC-01-E (Page 3 of 7) C. Disaggregation of Electrical Circuits ❑ Each newly installed switchboard, panel, and motor control center (in both existing and newly constructed buildings) is required to be disaggregated according to the requirements of Table 130.5-B, shown on the next page. ❑ Individual branch circuits, taps or disconnects that require overcurrent protection devices rated 60A or greater. ❑ As an alternative, current transformers can be added for individual branch circuits and loads throughout the building, and a permanent measurement system can be installed. In this case, disaggregated wiring would not be required as long as the metering system allows the equivalent disaggregated measurements. ❑ Fill out a separate line for each switchboard, motor control center, panelboard and subpanel. Switchboard, motor control center, panelboard or subpanel Electrical Service that supplies that switchboard or panel Electrical Service Rating Field Inspector m W. A B C D Designation/location in building/description Designation/location in building/description kVA ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ OR Current transformers have been attached to individual branch circuits and loads throughout the building, and a permanent measurement system is installed that allows an equivalent degree of disaggregated measurement as required by the Standards.. ❑ ❑ CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance May 2015 rl L STATE OF CALIFORNIA Electrical Power Distribution CEC-NRCC-ELC-01-E (Revised 05/15) CERTIFICATE OF COMPLIANCE Electrical Power Distribution Project Name: Lazer Oasis Tenant Improvement CALIFORNIA ENERGY COMMISSION Date Prepared: 6/23/2016 NRCC-ELC-01-E (Page 4 of 7) D. Disaggregation of Electrical Circuits (continued) Table 130.5-B - MINIMUM REQUIREMENTS FOR SEPARATION OF ELECTRICAL LOAD Table 130.5 — B sets the upper limit on how many load(s) of each type can be supplied by each feeder. A feeder may not supply loads of more'than one type unless the service is rated at 50 kVA or less. For instance, on the fifth row of the table, one feeder on a service >50 kVA could be used to supply all the plug loads on a floor of a building, provided that there are no areas in which more than 25kVA of plug load is supplied to a space less than 5000sf Services rated more than Services rated more than Services rated 50kVA and less than or 250 WA and less than or Services rated more Load Type 50 WA or less equal to 250 WA equal to 1000kVA than 1000kVA Lighting including exit and All lighting egress lighting and exterior Not required All lighting in aggregate All lighting disaggregated disaggregated by floor, lighting bfloor y , type or area type or area HVAC systems and components including chillers, fans, heaters, All HVAC in aggregate All HVAC in aggregate furnaces, package units, cooling Not required All HVAC in aggregate and each HVAC load and each HVAC load towers, and circulation pumps rated at least 50 kVA rated at least 50kVA associated with HVAC Domestic and service water system pumps and related Not required All loads in aggregate All loads in aggregate All loads in aggregate systems and components ' All plug load separated by All plug loads separated All plug load in aggregate floor, type or area by floor, type or area. Plug load including appliances Groups of plug loads Groups of plug loads All groups of plug loads rated less than 25 kVA Not required exceeding 25 kVA exceeding 25 WA exceeding 25 WA connected load in an area less than 5000 sf connected load in an area connected load in an less than 5000 sf area less than 5000 sf Elevators, escalators, moving walks, and transit systems Not required All loads in aggregate All loads in aggregate All loads in aggregate Other individual non-HVAC loads or appliances rated 25kVA Not required All Each Each or greater Industrial and commercial load centers 25 kVA or greater including theatrical lighting Not required All Each Each installations and commercial kitchens Renewable power source (net or total) Each group Each group Each group Each group Loads associated with renewable power source Not required All loads in aggregate All loads in aggregate All loads in aggregate Charging stations for electric All loads in vehicles aggregate All loads in aggregate All loads in aggregate All loads in aggregate L, CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance May 2015 STATE OF CALIFORNIA Is 'Electrical Power Distribution E. Voltage Drop ❑ Attach voltage drop worksheet to this form, ❑ Field inspector has discretion to approve the worksheets; the tables shown b=_low in this secti6n are advisory only ❑ Feeder conductors and branch circuits that are dedicated to emergency services are exempt from these requirements. ❑ An advisory table of typical power factors is shown below Field ' Inspector � N N N T Ol Feeders. Feeder conductors shall be sized for a maximum voltage drop of 2 percent at design load. ❑ 11 Branch Circuits. Branch circuit conductors shall be sized for a maximum voltage drop of 3 percent at design load. ❑ ❑ Compliance Manual, Chapter 8, Table 8 2: Typical Power Factors for Voltage Drop Calculations Default Power Factor Default Power Factor Load Type at 120 volts at 277 volts Clarifying Notes Fluorescent lighting 0.95 0.95 Compact. 0.9 (hardwired) 0.9 (hardwired) fluorescent lighting � NPF magnetic ballasts use GU-24 values 0.5 (GU-24) 0.3 (GU-24) LED lighting 0.7 0.5 May be higher if specifications call for high power factor drivers Incandescent lighting 1.0 1.0 HID lighting 0.9 0.9 May be lower if NPF ballasts are specified HVAC packages 0.85 0.9 Other motors <5 HP 0.8 0.8 Other motors >5 HP 0.85 0.85 Kitchen equipment 0.9 N/A Receptacles 0.6 N/A For dedicated receptacles, may be rated according to the load Electric heating 1.0 1.0 - including hot water Other 0.85 0.85 is CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance May 2015 STATE OF CALIFORNIA Elebtrical Power Distribution 4 ., CEC-NRCC-ELC-01-E (Revised 05/15) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-ELC-01-E Electrical Power Distribution (Page 6 of 7) Project Name: Lazer Oasis Tenant Improvement Date Prepared: 6123/2016 F. Circuit Controls for 120-Volt Receptacles ❑ Controlled 120 volt receptacles shall be provided, as required by Section 130.5(d) of the Standards. ❑ In open office areas, controlled circuit receptacles are not required if, at time of final permit, workstations are installed, and each workstation is equipped with an occupant sensing control that is permanently mounted in each workstation, and which controls a hardwired, nonresidential - rated power strip. Plug-in strips and other plug-in devices that incorporate an occupant sensor shall not be used for this exception. ❑ Receptacles that are only for the following purposes are exempt: -Receptacles specifically for refrigerators and water dispensers in kitchenettes. -Receptacles located a minimum of six feet above the floor that are specifically for clocks. -Receptacles for network copiers, fax machines, A/V and data equipment other, than personal computers in copy rooms. Field Inspector � 11 N IA T N — 1. At least one controlled receptacle is installed within 6 feet of each uncontrolled receptacle, or split -wired duplex receptacles are installed, that have one controlled and one uncontrolled receptacle. This applies in all of the following spaces: - • Private offices, open office areas • Receptions and lobbies ❑ ❑ • Conference rooms • Kitchenettes in office spaces • Copy room 2. Electric circuits serving controlled receptacles are equipped with automatic shut -OFF controls following the requirements prescribed in Section 130.1(c)1 through 5 (in many cases this will mean that the receptacles are connected ❑ ❑ to the same automatic shut -OFF system as the general lighting of the space). 3. Controlled receptacles shall have a permanent marking to differentiate them from uncontrolled receptacles. ❑ ❑ 4. For open office areas, controlled circuits shall be provided and marked to support installation and configuration of office furniture with receptacles that comply with Section 130.5(d) 1, 2, and 3. ❑ ❑ 5. For hotel and motel guest rooms at least one-half of the 120-volt receptacles in each guest room are controlled receptacles that comply with Section 130.5(d)1, 2, and 3 (see numbers 1,2 and 3 above). Electric circuits serving controlled receptacles have captive card key controls, occupancy sensing controls, or automatic controls such that, no ❑ ❑ longer than 30 minutes after the guest room has been vacated, power is switched off. 6. Plug-in strips and other plug-in devices that incorporate an occupant sensor are not used to comply with any of these requirements. ❑Fi • CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance I May 2015 STATE OF CALIFORNIA 'Electrical Power Distribution • Q_ DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Tim Scott Documentation Author Signature: Company: Scott Design and Title 24, Inc, Signature Date:6/23/2016 Address: 78818 Velie Way, Suite 8 CEA/ HERS Certification Identification (if applicable): City/State/Zip: Palm Desert, CA 92260 Phone. (760) 777-0102 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: Joe Donati Responsible Designer Signatu Company: Niche Builders, Inc. Date Signed: NJ IVA, Address` 840 East West Drive License: City/state/zip: MUr h s , CA 95247 p y Phone: (209) 609-3752 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance May 2015 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name azer Oasis Tenant Improvement Date 6/23/2016 System Name HVAC 1-5 Floor Area 8,111 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 5 COIL CFM Total Room Loads 14,868 Return Vented Lighting Return Air Ducts Return Fan Ventilation 2,028 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COOLING PEAK COIL HTG. PEAK Heating System Sensible Latent CFM Sensible Output per System 120,000 232.621 81,110 6,876 93,155 Total Output Btuh 600.000 0 -Output Btuh/s ft 74.0 11,631 4,658 Cooling System 0 0 Output per System 120,000 80,824 20,041 2,028 94,478 Total Output Btuh 600,000 0 101,151 0 Total Output Tons 50.0 11,631 4,658 Total Output Btuhls ft 74.0 Total Output s ft/Ton 162.2 336,707 196,949 Air System CFM per System 4,000 HVAC EQUIPMENT SELECTION Airflow cfm 20,000 Existing HVAC 416,995 126,525 374,744 Airflow cfm/s ft 2.47 Airflow cfm/Ton 400.0 Outside Air % 10.1 % Total Adjusted System Output (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 416,995 126,525 374,744 Jan 1 AM Outside Air cfm/s ft 0.25 Note: values above given at ARI conditions Jul 3 PM HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak) 26 OF Outside Air 2,028 cfm 70 OF 65 °F 83 OF 83 OF IC��rJ Heating Coil Supply Fan 20,000 cfm -0- 83 °F k ROOM F fl 70 OF COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak 112/78OF Outside Air 2,028 cfm 75 / 65 OF 78/66°F 59/58°F 59/58°F IN Cooling Coil Supply Fan 20,000 cfm 59 158 OF 60.1 % ROOM fl 74 / 64 OF EnergyPro 6.7 by EnergySoR User Number: 6712 RunCode: 2016-06-23T20:09:04 ID: Page 32 of 37 n� HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name LazerOasis Tenant Improvement Date 6/23/2016 System Name HVAC-10 Floor Area 554 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 COIL CFM Total Room Loads 5,464 Return Vented Lighting Return Air Ducts Return Fan Ventilation 416 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COOLING PEAK COIL HTG. PEAK Heating System Sensible Latent CFM Sensible Output per System 36,000 98,860 16,620 2,061 83,352 Total Output Btuh 36,000 0 Output Btuh/s ft 65.0 4,943 4,168 Cooling System 0 0 Output per System 36,000 15,919 -3,741 416 18,572 Total Output Btuh 36,000 0 12,879 0 Total Output Tons 3•0 4,943 4,168 Total Output Btuh/s ft 65.0 Total Output s ft/Ton 184.7 124,664 110,258 Air System CFM per System 1,200 HVAC EQUIPMENT SELECTION Airflow, cfm 1,200 New 3 Ton Split 28,248 8,346 22,485 Airflow, cfm/s ft 2.17 Airflow, cfm/Ton 400.0 Outside Air % 34.6 % Total Adjusted System Output (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 28,248 8,346 22,485 Outside Air cfm/s ft 0.75 Note: values above given at ARI conditions Jul 3 PM Jan 1 AM HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26 OF 53 OF 53 OF 110 OF O _ Outside Air 416 cfm Supply Fan Heating Coil 1,200 cfm 68 OF II (( �. Iti,._,.-) _. �I,..._.._U f 108 OF ROOM 70 OF COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 112/78OF 88/73OF 88/73OF 55/59OF �w Outside Air 416 cfm Supply Fan Cooling Coil 1,200 cfm 76/70OF 57 / 60 OF 81.4 % FROOM 74/70OF EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-06-23T20:09:04 ID: Page 33 of 37 , 4 C: HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Lazer Oasis Tenant Improvement Date 6/23/2016 System Name HVAC Floor Area 3,035 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 4 COIL CFM Total Room Loads 8,655 Return Vented Lighting Return Air Ducts Return Fan Ventilation 759 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COOLING PEAK COIL HTG. PEAK Heating System Sensible Latent CFM Sensible Output per System 69,000 142,344 30,350 2,691 58,362 Total Output Btuh 276,000 0 Output Btuh/s ft 90•9 7,117 2,918 Cooling System 0 0 Output per System 69,000 30,097 9,417 759 35,288 Total Output Btuh 276,000 0 7,117 186,676 39.767 0 Total Output Tons 23.0 2,918 Total Output Btuh/s ft 90•9 Total Output s ft/Ton 132.0 99,486 Air System CFM per System 2,300 HVAC EQUIPMENT SELECTION Airflow cfm 9,200 HVAC 6-9 195,639 50,680 172,382 Airflow cfm/s ft 3.03 5.0 kW Supplemental Electric 68,260 Airflow cfm/Ton 400.0 Outside Air % 8•2 % Total Adjusted System Output (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 195,639 50,680 240,642 Outside Air cfm/s ft 0.25 Note: values above given at ARI conditions Jul 3 PM Jan 1 AM HEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak 26 OF Outside Air 759 cfm 70 OF 66 OF 84 OF 91 OF 91 OF Heating Coil Aux. Heat Coil Supply Fan 9,200 cfm 90 OF ROOM [7Q] 70 OF COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak 112 / 78 OF Outside Air Ar 759 cfm 75 / 64 OF 78 / 65 OF 58 / 57 OF 58 / 57 OF UJ Cooling Coil Supply Fan 9,200 cfm 59 / 57 OF ---- 57.2% ; ROOM 74164 OF EnergyPro 6.7 by EnergySoff User Number., 6712 Run Code: 2016-06-23T20:09:04 /D: Page 34 of 37 ZONE LOAD SUMMARY Project Name Lazer Oasis Tenant Improvement Date 6/23/2016 System Name HVAC 1-5 Floor Area 8,111 ZONE LOAD SUMMARY ZONAL SYSTEM COOLING PEAK HEATING PEAK ZONE NAME SYSTEM NAME Mult. CFM Sensible Latent Heating OA CFM Peak Hr CFM Sensible Latent CFM Sensible lower Lever 1.0 2,028 Jul PM 14,868 314,624 119,188 6,876 188,106 TOTALS 0 0 01 3,119 Jul 3 PM 314, 624I 119,188 188,106 (BLOCK LOAD) EnergyPro 6.7 by EnergySoR -User Number: 6712 Run Code: 2016-06-23T20:09:04 ID: Page 35 of 37 • ZONE LOAD SUMMARY Project Name Lazer Oasis Tenant Improvement Date 6/23/2016 System Name HVAC-10 Floor Area 554 ZONE LOAD SUMMARY ZONAL SYSTEM COOLING PEAK HEATING PEAK ZONE NAME SYSTEM NAME Mult. CFM Sensible Latent Heating OA CFM Peak Hr CFM Sensible Latent CFM Sensible Party Room Zone 1.0 416 Jul PM 5,464 115,663 24,422 2,061 102,808 TOTALS 0 0 01 416 Jul 3PM 115,663 24,422 102,808 (BLOCK LOAD) EnergyPro 6.7 by EnergySoft User Number: 6712 RunCode: 2016-06-23T20:09:04 ID: Page 36 of 37 ZONE LOAD SUMMARY Project Name Lazer Oasis Tenant Improvement Date 6/23/2016 System Name HVAC Floor Area 3,035 ZONE LOAD SUMMARY ZONAL SYSTEM COOLING PEAK HEATING PEAK ZONE NAME SYSTEM NAME Mult. CFM Sensible Latent Heating OA CFM Peak Hr CFM Sensible Latent CFM Sensible Upper Level 1.0 759 Jul 3PM 8,655 173,028 44,598 2,691 93,891 TOTALS 0 0 0 759 Jul PM 173,028I 44,598 93,891 (BLOCK LOAD) EnergyPro 6.7 by EnergySoft User Number: 6712 Run Code: 2016-06-23T20:09:04 ID: Page 37 of 37