9801-055 (SFD) Title 24t
COMPLIANCE
- TITLE 24 REPORT FOR:
Gardner Residence
Lot to, Tract 28470, Traditions
La Quinta, Ca
PROJECT DESIGNER:
Robert S. Ritchey, Architect
42-575 Melanie Place
Palm Desert, Ca 92211
( 760 ) 341-6997
REPORT PREPARED BY:
Tim Scott
BREEZE AIR CONDITIONING
75-145 ST CHARLES PLACE
PALM DESERT, CA 92260
( 619 ) 346-0855
Job Number:
Date: 12/12/.1997
The COMPLY 24 computer program has been used to perform the calculations
summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the
rResidential and Nonresidential Building Energy Efficiency Standards.
. 'This program developed by Gabel Dodd/EnergySoft, llc (415) 883-5900.
Table Of Contents for Title 24 Report
CoverPage
..........................................................
1
Table
of Contents ...................................................
2
Form
CF -1R Certificate of Compliance ................................
3
Form
MF -IR Mandatory Measures Checklist .............................
5
Form
C -2R Computer Method Summary ...................................
7
Form
E11V-3 Construction Assemblies ..................................
10
HVAC
System Loads Summary .......................... ................
15
zone
Heating Loads Summary ..........................................
19
"Lone
Cooling Loads Summary ..........................................
23
HVAC
Equipment Specifications .......................................
27
Glazing
Specifications .........................................._.
39
Form
CF -6R Installation Certificate ...............................
42
CERTIFICATE OF COMPLIANCE - Residential (part 1 of 2) CF -1R page 3 of 42
-------------------------------------------------------------------------
,Project Name: Gardner Residence :Date: 12/12/1997
Address: Lot 40, Tract 28470, Traditions ;
La ouinta, Ca ;Building Permit No
Designer: Robert S. Ritchey, Architect
Checked by / Date
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
GENERAL INFORMATION
Compliance Method:
Climate zone:
Conditioned Floor Area:
Building Type:
Occupancy Type:
Building Front Orientation:
Number of Dwelling Units:
Floor Construction Type:
BUILDING SHELL INSULATION
Component
-----------------------
COMPLY 24 version 5.10
15
3475 sqf t
New
Single Fam Det
270 deg ( W )
1
Slab on Grade
U -Value Location/Comments
-------------------------------------------
R-21 Wall (W.21.2x6.16)
0.059 Master Suite
R-21 Wall (W.21.2x6.16)
0.059 Kit/Morn/Din/Entry
R-21 Wall (W.21.2x6.16)
0.059 Great/Media/Workout
solid Wood Door
R-21 Wall (W.21.2x6.16)
0.387 Great/Media/workout
0.059 Guest Suite
R-38 Roof(R.38.2x14.16)
0.029 Master Suite
R-38 Roof(R.38.2x14.16)
0.029 Kit/Morn/Din/Entry
R-38 Roof(R.38.2xl4.16)
0.029 Great/Media/Workout
R-38 Roof(R.38.2xl4.16)
0.029 Guest Suite
Slab Perimeter w/R-O.O
0.900 Master Suite
Slab Perimeter w/R-0.0
0.720 Master Suite
Slab Perimeter w/R-0.0
0.900 Kit/Morn/Din/Entry
Slab Perimeter w/R-0.0
0.720 Kit/Morn/Din/Entry
Slab Perimeter w/R-0.0
Slab Perimeter w/R-0.0
0.900 Great/Media/Workout
0.720 Great/Media/Workout
Slab Perimeter w/R O.0
0.900 Guest Suite
Slab Perimeter w/R-O.O
0.720 Guest Suite
'
FENESTRATION
Shading Devices
Frame
Orient. Area U -Val
Type
Interior Exterior
OH SF
Type
--------- ----_- -----
Left (N) 11.0 0.55
------
Double
------------------------------
Std Drape none
-- --
Y N
-----
Metal
Left (N)• 8.0 0.69
Double
Std Drape Standard Bug
Scr N N
Metal
Left (N) 25.0 0.69
Double
Std Drape Standard Bug-Scr
Y N
Metal
Back (E) 30.0 0.55
Double
Std Drape none
N N
Metal
'Back (E) 145.3 0.55
Double
Std Drape none
Y N
Metal
Back (E) 304.0 0.65
Double
Std Drape Standard Bug
Scr'Y N
Metal
Back (SE) 64.0 0.65
Double
Std Drape Standard Bug
Scr Y N
Metal
Right (S) 15.0 0.55
Double
Std Drape none
N N
Metal
Right (S) 8.0 0.55
Double
Std Drape none
Y N
Metal
Right (5) 128.0 0.65
Right (5) 8.0 0.69
Double
Double
Std Drape Standard Bug
Std Drape none
Scr Y N
Y N
Metal
Metal
Right (S) 40.0 0.69
Double
Std Drape Standard Bug
Scr Y N
Metal
Right (S) 30.0 0.72
Double
none none
Y N
None
Right (SW) 16.0 0.55
Double
Std Drape none
Y N
Metal
Flight (SW) 28.0 0.65
Double
none none
Y N
Metal
Front (W) 8.0 0.55
Double
Std Drape none
N N
Metal
Front (W) 90.0 0.55
Double
Std Drape none
Y N
Metal
Front (NW) 48.0 0.55
Double
Std Drape none
Y N
Metal
Skylight 4:0 0:80
Double
none none
N N
Metal
r
l�
THERMAL MASS
Type ---------
------------
Covering
--------
Area
(sf)
-----
Thick
(in)
-----
Location/Description
Concrete,
Heavyweight
Exposed
57
3.50
------------------------------
Slab
on
Grade
Concrete,
Heavyweight
Covered
638
3.50
Slab
on
Grade
Concrete,
Heavyweight
Exposed
688
3.50
Slab
on
Grade
Concrete,
Heavyweight
Covered
128
3.50
Slab
on
Grade
Concrete,
Heavyweight
Exposed
700
3.50
Slab
on
.Grade
Concrete,
Heavyweight
Covered
691
3.50
Slab
on
Grade
Concrete,
Heavyweight
Exposed
17
3.50
Slab
on
Grade
Concrete,
Heavyweight
Covered
556
3.50
Slab
on
Grade
r
l�
ARTIFICATE OF COMPLIANCE. — Residential (part 2 of 2) CF -1R page 4 of 42
---------------------------------------------------------------------------
Project Name: Gardner Residence ;Date= 12/12/1997
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
HVAC SYSTEMS Minimum Distrib Type
System Type Efficiency and Location
----------- ---------- ----------------
Furnace 0.800 AFUE Ducts in Attic
SpltA & Cond15.750 SEER Ducts in Attic
Furnace 0.800 AFUE Ducts in Attic
SpltAirCond14.000 SEER Ducts in Attic
Furnace 0.800 AFUE Ducts in Attic
SpltAirCond14.000 SEER Ducts in Attic
Furnace 0.800 AFUE Ducts in Attic
SpltAirCondl3.000 SEER Ducts in Attic
Duct TStat
RVal Type Location/Comments
---- ------ -----------------------
_4.2 SetBck Master Suite "Zone
4.2 SetBck
4.2 SetBck Kit/Morn/Din Zone
4.2 SetBck
4.2 SetBck Great/Media "Zone
4.2 SetBck
4.2 SetBck Guest Suite Zone
4.2 SetBck
Water No. Tank Ext.
WATER HEATING SYSTEMS Heater in Energy Size Insul
System Name Distribution Type Type Sys Factor (gal) R -Val
----------------------- ------------------ ------- --- ------ ----- -----
American G52-50T383N Recirc-Time&Temp StorGas 2 0.60 50.0 12.0
American G52 -30T33 -3N Recirc-Time&Temp StorGas 1 0.61 30.0 12.0
AFUE
WATER HEATER EQUIPMENT DETAIL /Rec Rated Stdby Tank Pilot
System Name System Type Eff Input Loss R -Val Light
----------------------- ----------- ---- ----- ----- ----- -----
American G52-5OT383N DomesticHW 0.780 38000 0.003 16.0 0
American G52 -30T33 -3N DomesticHW 0.780 33000 0.003 16.0 O
SPECIAL FEATURES/REMARKS
COMPLIANCE STATEMENT
This Certificate of Compliance lists the Building features and performance
specifications needed to comply with Title -24, Parts 1 & 6 of the Califor-
nia Code of Regulations, and the administrative regulations to implement
them. This certificate has been signed by the individual with overall
design responsibility. When this certificate of compliance is submitted for
a single Building plan to be built in multiple orientations, any shading
feature that is varied is indicated in the Special Features/Remarks section
DESIGNER or OWNER
( Per Business & Professions Code)
Robert S. Ritchey, Architect
42-575 Melanie Place
Palm Desert, Ca 92211
(760) 341-6997 Lic #:
( signature ) .
ENFORCEMENT AGENCY
Name:
Title:
Agency:
Telephone:
(date)
DOCUMENTATION AUTHOR
Tim Scott
BREEZE AIR CONDITIONING
75-145 ST CHARLES PLACE
PALM DESERT, CA 92260
( 619) 346-0855
( Z/►Z/47
(signature) (date)
(signature/stamp)
(date)
'MA,NDATORY MEASURES CHECKLIST ( part 1 of 2 ) MF -1R page 5 of 42
-------------------------=-------------------------------------------------
Project Name: Gardner Residence ;Date: 12/12/1997
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
NOTE: Lowrise residential buildings subject to the Standards must contain
these measures regardless of the compliance approach used. items marked
with an asterisk (*) may be superseded by more stringent compliance
requirements listed on the Certificate of Compliance. when this checklist
is incorporated into the permit documents, the features noted shall be
considered by all parties as binding minimum component performance
specifications for the mandatory measures whether they are shown elsewhere
in the documents or on this checklist only.
' BUILDING ENVELOPE MEASURES Enforcement
o Sec. 150(a): Minimum R-19 ceiling insulation.
' o Sec. 150(b): Loose fill insulation manufacturers
labeled R -value.
o Sec. 150(c): Minimum R-13 wall insulation in framed walls
(does not apply to exterior mass walls).
o Sec. 150(d): Minimum R-13 raised floor insulation in framed
floors; Minimum R-8 in concrete raised floors.
o Sec. 150(1): Slab edge insulation - water absorption rate
no greater than 0.3%, water vapor transmission rate no
greater than 2.0 perm/inch.
o Sec. 118: Insulation specified or installed meets California
Energy Commission quality standards. Indicate Type & form.
o Sec. 116-117: Fenestration Products, Ext Doors & Infil/Exfil Controls
a. Doors and windows between conditioned and unconditioned
spaces designed to limit air leakage.
' b. Manufactured fenestration products have label w/certified U -value
c. Exterior doors and windows weatherstripped; all joints
and penetrations caulked and sealed.
' o Sec. 150(8): Vapor barriers mandatory in Climate "Zones 14
and 16 only.
o Sec. 150(f): Special infiltration barrier installed to
comply with Sec. 151 meets Commission quality standards.
o Sec. 150(e): Installation of Fireplaces, Decorative Gas
Appliances and Gas Logs
1. Masonry and factory -built fireplaces have:
a. Closeable metal or glass door
b. outside air intake with damper and control
c. Flue damper and control
2. No continuous burning gas pilots allowed..
.1
MANDATORY MEASURES CHECKLIST (part 2 of 2) MF -1R page 6 of 42
----------------------------------------------------------------------------
Project Name: Gardner Residence ;Date: 12/12/1997
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
SPACE CONDITIONING, WATER HEATING AND PLUMBING SYSTEM MEASURES Enforcement
o Sec. 110-13: HVAC equipment, water heaters, showerheads
and faucets certified by the Commission.
o Sec. 150(i): Setback thermostat on all applicable
heating systems.
o Sec. 150(j): Pipe and Tank Insulation
1. Indirect hot water tanks (eg unfired storage tanks or
backup solar hot water tanks) have insulation blanket
(R-12 or greater) or combined interior/exterior insulation
(R-16 or greater).
2. First 5 feet of pipes closest to water heater tank,
non -recirculation systems, insulated (R-4 or greater.
3. All buried or exposed piping insulated in recirculation
sections of hot water system.
4. Cooling system piping below 55 F insulated.
5. Piping insulated between heating source and indirect hot
water tank.
o Sec.
I.
2.
3.
150(m) Ducts and Fans *
Ducts constructed, installed and sealed to comply with
UMC Sections 1002 and 1004; ducts insulated to a minimum
R-4.2 or ducts enclosed entirely within conditioned space.
Exhaust systems have backdraft or automatic dampers.
Gravity ventilating systems serving conditioned space have
either automatic or readily accessible manually operated
dampers.
o Sec. 114:Pool and Spa Heating Systems and Equipment
1. System is certified with 78% thermal efficiency, on-off
switch, weatherproof operating instructions, no electric
resistance heating and no pilot light.
2. System is installed with:
a. At least 36" pipe between filter and heater for future
solar heating.
b. Cover for outdoor pools or outdoor spas.
3. Pool system has directional inlets and a circulation
pump time switch.
o Sec. 115: Gas-fired central furnace, pool heater, spa heater
or household cooking appliance have no continuously
burning pilot light. (Exception: Non -electrical cooking
appliance with pilot < 150 Stuh)
LIGHTING MEASURES
o Sec. 150(k): Lighting - 40 lumens/watt or greater for
general lighting in kitchens and rooms with water closets;
and recessed ceiling fixtures IC (insulation cover) approved.
COMPUTER METHOD SUMMARY (part 1 -of -3)- C -2R page 7 of 42
Project Name: Gardner Residence ;Date: 12/12/1997
'Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------=-----
Source Energy Use (KBtu/sf-yr)
------------------------------
Space . Heating
Space Cooling
Domestic Hot Water
TOTALS
Standard
Proposed
Compliance
Design
--------
Design
--------
Margin
----------
4.44
4.34
0.10
30.73
29.26
1.46
7.52
--------
8.61
--------
-1.10
----------
42.69
42.22
0.47
- *** BUILDING COMPLIES ***
GENERAL INFORMATION
Compliance Method:
Climate Zone:
Conditioned Floor Area:
Building Type:
Occupancy Type:
Building Front Orientation:
Number of Dwelling Units:
Number of Stories:
Floor Construction Type:,
Total Conditioned volume:
Conditioned Footprint Area:
Ground Floor Area:.
COMPLY 24 version 5.10
15
3475 sqft
New
Single Fam Det
270 deg ( W )
1
1
Slab on Grade
38016 cuft
3475 sqft
3475 sqft
BUILDING ZONE INFORMATION
Floor # of Vent
-Zone Name Area Volume Units Zone Type TStat Type Hgt Area
----------------------- ----- ------ -------------------------- --- ----
Master Suite Zone 695 6950 0.20 Conditioned Setback 2 n/a
Kit/Morn/Din Zone 816 10608 0.23 Conditioned Setback 2 n/a
Great/Media -Zone 1391 15301 0.40 Conditioned Setback 2 n/a
Guest Suite Zone 573 5157 0.16 Conditioned Setback 2 n/a
OPAQUE SURFACES Act Solar
Type Area U -Val Azm Tilt Gains Form 3 Reference Location/Comments
---- ---- ----- --- ---- ------------=--------------- --------------------
ZONE NAME = Master Suite Zone
'
Wall 329 0.059 0 90 Yes R-21 Wall (W.21.2x6.16) Master Suite
Wall 242 0.059 180 90 Yes R-21 Wall (W.21.2x6.16),Master Suite
Wall 192 0.059 270 90 Yes R-21 Wall (W.21.2x6.16) Master Suite
'Roof 695 0.029 O 22 Yes R-38 Roof(R..38.2x14.16) Master Suite
ZONE NAME = Kit/Morn/Din Zone
Wall 247 0.059 90 90 Yes R-21 Wall (W.21.2x6.16) Kit/Morn/Din/Entry
Wall 57 0.059 135 90 Yes R=21 Wall (W.'21.2x6.16) Kit/Morn/Din/Entry
Wall 147 0.059 180 90 Yes R-21 Wall (W.21.2x6.16) Kit/Morn/Din/Entry
Wall 68 0.059 225 90 Yes R-21 Wall (W.21.2x6.16) Kit/Morn/Din/Entry
Wall 40 0.059 270 90 Yes R-21 Wall (W.21.2x6.16) Kit/Morn/Din/Entry
Wall 64 0.059 315 90 Yes R-21 Wall (W.21.2x6.16) Kit/Morn/Din/Entry
Roof 816 0.029 U 22 Yes R-38 Roof(R.38.2x14.16) Kit/Morn/Din/Entry
"ZONE NAME = Great/Media Zone
Wall 443 0.059 U 90 Yes R-21 Wall (W.21.2x6.16) Great/Media/Workout
Wall 247 0.059 90 90 Yes R-21 Wall (W.21.2x6.16) Great/Media/Workout
Wall 159 0.059 180 90 Yes R-21 Wall (W.21.2x6.16) Great/Media/Workout
Wall 359 0.059 270 90 Yes
Door 21 0.387 270 90 Yes
Roof 1387 0.029 O 22 Yes
'ZONE NAME = Guest Suite Zone
Wall 207 0.059 0 90 Yes
Wall 133 0.059 90 90 Yes
Wall 159 0.059 180 90 Yes
Wall 225 0.059 270 90 Yes
Roof 573 0.029 0 22 Yes
.1
� I
� I
� I
I I
I I
I I
R-21 Wall (W.21.2x6.16) Great/Media/Workout
Solid Wood Door Great/Media/Workout
R-38 Roof(R.38.2xl4.16) Great/Media/Workout
R-21 Wall (W.21.2x6.16) Guest Suite
R-21 Wall (W.21.2x6.16) Guest Suite
R-21 Wall (W.21.2x6.16) Guest Suite
R-21 Wall (W.21.2x6.16) Guest Suite
R-38 Roof.( R .38 .2x14:16) Guest Suite
COMPUTER METHOD SUMMARY (part 2 of 3) C-2Rag e 8 of 42
--------------------------------------------------------------
---
Project Name: Gardner Residence ,Date: 12/12/1997
i
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
insulation
PERIMETER
LOSSES
F2
Depth
-----
Type
Length Factor
------ ------
0.0
O
---------
ZONE NAME
= Master Suite
Zone
O
Exposed
6.0
0.90
0
Covered
82.0
0.72
O
ZONE NAME
= Kit/Morn/Din
Zone
'Exposed
in
67.0
0.90
O
Covered
14.0
0.72
0
"ZONE NAME
= Great/Media
Zone
0
Exposed
57.0
0.90
0.65
Covered
68.0
0.72
(E)
ZONE NAME
= Guest Suite
Zone
7
Wdw
8.0
0.90
'Exposed
Covered
92.0
0.72
insulation
Suite Zone
90
R -Val
-----
Depth
-----
Left
Location/Comments
-----------------------
0.0
O
in
Master Suite
0.0
O
in
Master Suite
0.0
0
in
Kit/Morn/Din/Entry
0.0
O
in
Kit/Morn/Din/Entry
0.0
0
in
Great/Media/Workout
0.0
O
in
Great/Media/Workout
0.0
0
in
Guest Suite
0.0
0
in
Guest Suite
FENESTRATION SURFACES
Act
# Type Area Frame Div U -Val Azm Tilt
- --------------- ----- ----- --- ----- --- ----
ZONE NAME = Master
Suite Zone
90
1-Wdw
Master Suite
Left
( N )
11.0
Metal
No
2
Wdw
Right
( S )
80.0
Metal
No
3
Wdw
Right
( S )
8.0
Metal
No
4
Wdw
Right
( 5 )
30.0
None
No
5
Wdw
Front
( W )
8.0
Metal
No
ZONE NAME = Kit/Morn/Din
Zone
0.65
6
Wdw
Back
(E)
96.0
Metal
No
7
Wdw
Back
(E)
16.0
Metal
No
8
Wdw
Back
(E)
48.0
Metal
No
9
Wdw
Back
(SE)
64 .0
Metal
No
10
Wdw
Right
(S)
40.0
Metal
No
11
Wdw
Right
(SW)
8.0
Metal
No
12
Wdw
Right
(SW)
28 .0
Metal
No
13
Wdw
Right
(SW)
8.0
Metal
No
14
Wdw
Front
(W)
12.0
Metal
No
15
Wdw
Front
(W)
36.0
Metal
No
16
Wdw
Front
(W)
24.0
Metal
No
17
Wdw
Front
(NW)
12 .0
Metal
No
18
Wdw
Front
(NW)
36 .0
Metal
No
ZONE NAME =
Great/Media Zone
Great/Media/workout
19
Wdw
Left
(N)
25.0
Metal
No
20
Wdw
Left
( N )
8.0
Metal
No
21
Wdw
Back
(E)
61.3
Metal
No
22
Wdw
Back
(E)
64.0
Metal
No
23
Wdw
Back
(E)
64.0
Metal
No
24
Wdw
Back
( E )
20.0
Metal
No
25
Wdw
Right
(S)
15.0
Metal
No
26
Wdw
Right
( S )
8.0
Metal
No
27
Sky
Left
( N )
4.0
Metal
No
ZONE NAME =
Guest
Suite Zone
28
Wdw
Back
(E)
30.0
Metal
No
29
Wdw
Back
(E)
80.0
Metal
No
30
Wdw
Right
(S)
48.0
Metal
No
31
Wdw
Front
( W )
10.0
Metal
No
32
Wdw
Front
( W )
8.0
Metal
No
SC
Glass
Only Location/Comments
----- ---------------------
0.55
0
90
0.65
Master Suite
0.65
180
90
0.65
Master Suite
0.55
180
90
0.65
Master Suite
0.72
180
90
0.88
Master Suite
0.55
270
90
0.65
Master Suite
0.65
90
90
0.65
Kit/Morn/Din/Entry
0.55
90
90
0.65
Kit/Morn/Din/Entry
0.55
90
90
0.65
Kit/Morn/Din/Entry
0.65
135
90
0.65
Kit/Morn/Din/Entry
0.69
180
90
0.65
Kit/Morn/Din/Entry
0.55
225
90
0.65
Kit/Morn/Din/Entry
0.65
225
90
0.65
Kit/Morn/Din/Entry
0.55
225
90
0.65
Kit/Morn/Din/Entry
0.55
270
90
0.65
Kit/Morn/Din/Entry
0.55
270
90
0.65
Kit/Morn/pin/Entry
0.55
270
90
0.65
Kit/Morn/Din/Entry
0.55
315
90
0.65
Kit/Morn/Din/Entry
0.55
315
90
0.65
Kit/Morn/Din/Entry
0.69
0
90
0.65
Great/Media/Workout
0.69
0
90
0.65
Great/Media/Workout
0.55
90
90
0.65
Great/Media/Workout
0.65
90
90
0.65
Great/Media/Workout
0.65
90
90
0.65
Great/Media/Workout
0.55
90
90
0.65
Great/Media/Workout
0.55
180
90
0.65
Great/Media/Workout
0.69
180
90
0.65
Great/Media/Workout
0.80
O
0
0.65
Great/Media/workout
0.55
90
90
0.65
Guest Suite
0.65
90
90
0.65
Guest Suite
0.65
180
90
0.65
Guest Suite -
0.55
270
90
0.65
Guest Suite
0.55
270
90
0.65
Guest Suite
INTERIOR
& EXTERIOR SHADING
#
--
Type
----
Interior Shade Type
SC
1
Wdw
--------------------=--
Std
Drape
----
0.78
2
wdw
Std
Drape
0.78
3
Wdw
Std
Drape
0.78
4
wdw
None
1.00
5
Wdw
Std
Drape
-0.78
6
wdw
Std
Drape
0.78
7
wdw
Std
Drape
0.78
8
Wdw
Std
Drape
0.78
9
wdw
Std
Drape
0.78
10
wdw
Std
Drape.
0.78
11
Wdw
Std
Drape
0.78
12
Wdw
None
1.00
13
Wdw
Std
Drape
0.78
14
Wdw
Std
Drape
0.78
15
Wdw
Std
Drape
0.78
16
Wdw
Std
Drape
0.78
17
wdw
Std
Drape
0.78
18
wdw
Std
Drape
0.78
19
Wdw
Std
Drape
0.78
20
wdw
Std
Drape
0.78
21
Wdw
Std
Drape
0.78
22
Wdw
Std
Drape
0.78
23
Wdw
Std
Drape
0.78
24
Wdw
Std
Drape
0.78
25
Wdw
Std
Drape
0:78
26
Wdw
Std
Drape
0.78
27
Sky
None
1.00
28
Wdw
Std
Drape
0.78
29
Wdw
Std
Drape
0.78
30
Wdw
Std
Drape
0.78
31
Wdw
Std
Drape
0.78
32
Wdw
Std
Drape
0.78
Exterior Shade Type SC
No ne
l. -OO
Standard
Bug
Screen
0.87
None
1.00
None
1.00
None
1.00
Standard
Bug
Screen
0.87
None
1.00
None
1.00
Standard
Bug
Screen
0.87
Standard
Bug
Screen
0.87
None
1.00
None
1.00
None
1.00
None
1.00
None
1.00
None
1.00
None
1.00
None
1.00
Standard
Bug
Screen
0.87
Standard
Bug
Screen
0.87
None
1.00
Standard
Bug
Screen
0.87
Standard
Bug
Screen
0.87
None
1.00
None
1.00
None
1.00
None
1.00
None
1.00
Standard
Bug
Screen
0.87
Standard
Bug
Screen
0.87
None
1.00
None
1.00
COMPUTER METHOD SUMMARY (part 3 of 3) C -2R page 9 of 42
-------------------------------------------------
Project Name: Gardner Residence ;Date: 12/12/1997
i
'Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------- ----------------------------------------
OVERHANGS/SIDE FINS
Window-- Overhang------ ---Left Fin--- ---Right Fin--
# 'Type Ht Wd Len Ht LExt RExt Dist Len Ht Dist Len Ht
' -- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
1 Wdw 2.0 5.5 2.0 0.1 2.0 2.0
2 Wdw 8.0 10.0 6.0 0.1 6.0 6.0
3 Wdw 4.0 2.0 2.0 0.1 2.0 2.0
'4 Wdw 6.0 5.0 2.0 0.1 2.0 2.0
6 Wdw 8.0 12.0 2.0 0.1 2.0 2.0
7.Wdw 2.0 8.0 10.0 0.1 10.0 10.0
'8 Wdw 6.0 8.0 10.0 0.1 10.0 10.0
9 Wdw 8.0 8.0 10.0 0.1 10.0 10.0
10 Wdw 5.0 8.0 10.0 0.1 10.0 10.0
11 Wdw 8.0 1.0 6.0 0.1 6.0 6.0
'12 Wdw 8.0 3.5 8.0 0.1 8.0 8.0
13 Wdw 8.0 1.0 10.0 0.1 10.0 10.0
14 Wdw 2.0 6.0 10.0 0.1 10.0 10.0
15 Wdw 6.0 6.0 .10.0 0.1 10.0 10.0
16 Wdw 4.0 6.0 10.0 0.1 10.0 10.0
17 Wdw 2.0 6.0 10.0 0.1 10.0 10.0
'18 Wdw 6.0 6.0 10.0 0.1 10.0 10.0
19 Wdw 5.0 5.0 2.0 0.1 2.0 2.0
21 Wdw 8.0 7.7 2.0 0.1 2.0 2.0
22 Wdw 8.0 8.0 2.0 0.1 2.0 2.0
'23 Wdw 8.0 8.0 10.0 0.1 10.0 10.0
24 Wdw 5.0 4.0 10.0 0.1 10.0 10.0
26 Wdw 4.0 2.0 2.0 0.1 2.0 2.0
28 Wdw 8.0 10.0 2.0 0.1 2.0 2.0
29 Wdw 8.0 6.0 2.0 0.1 2.0 2.0
30 Wdw 2.0 5.0 2.0 0.1 2.0 2.0
31 Wdw 4.0 2.0 2.0 0.1 2.0 2.0
THERMAL MASS Area Thick Heat Inside Location
'Type (sf) (in) Ca Cond Form 3 Reference------- R -Val . Comments
------------- ---- ----- ---P- -------------------- ------ --------
ZONE NAME = Master Suite Zone
Exposed Slab 57 3.50 28 0.98 n/a 0
Covered Slab 638 3.50 28 0.98 n/a 2
ZONE NAME = Kit/Morn/Din Zone
Exposed Slab 688 3.50 28 0.98 n/a 0
'Covered Slab 128 3.50 28 0.98 n/a 2
ZONE NAME = Great/Media Zone
Exposed Slab 700 3.50 28 0.98 n/a 0
'Covered Slab 691 3.50 28 0.98 n/a 2
ZONE NAME = Guest Suite Zone
Exposed Slab 17 3.50 28 0.98 n/a 0
Covered Slab 556 3.50 28 0.98 n/a 2
HVAC SYSTEMS Minimum Distrib Type Duct TStat
System Type Efficiency and Location RVal Type Location/Comments
Furnace 0.800 AFUE Ducts in Attic 4.2 SetBck _Master Suite Zone
'SpltAirCond15.750 SEER Ducts in.Attic 4.2 SetBck
Furnace 0.800 AFUE Ducts in Attic 4.2 SetBck Kit/Morn/Din Zone
SpltAirCond14.000 SEER Ducts in Attic 4.2 SetBck
Furnace 0.800
AFUE
Ducts
in Attic
4.2
SetBck Great/Media Zone
Ext.
SpltAirCond14.000
SEER
Ducts
in Attic
4.2
SetBck
Size
Furnace 0.800-AFUE
'WATER
Ducts
in Attic
4.2
SetBck Guest Suite "Lone
Sys
SpltAirCond13.000
SEER
Ducts
in Attic
4.2
SetBck
-------
StorGas
---
2
------
0.60
-----
50.0
-----
12.0
'American
American G52-3OT33-3N
Recirc-Time&Temp
Water
No.
Tank
Ext.
HEATING SYSTEMS
Heater
in
Energy
Size
Insul
'WATER
System Name
Distribution
Type
Type
Sys
Factor
(gal)
R -Val
------------------------
G52-5OT383N
------------------
Recirc-Time&Temp
-------
StorGas
---
2
------
0.60
-----
50.0
-----
12.0
'American
American G52-3OT33-3N
Recirc-Time&Temp
StorGas
1
0.61
30.0
12.0
AFUE
'WATER
HEATER EQUIPMENT
DETAIL
/Rec
Rated
Stdby
dank
Pilot
System Name
------------------------
System'Type
-----------
Eff
----
input
Loss
-----
R -Val
Light
American G52-5OT383N
DomesticHW
0.780
-----
38000
0.003
-----
16.0
-----
0
American G52 -30T33 -3N
DomesticHW
0.780
33000
0.003
16.0
O
'
SPECIAL FEATURES/REMARKS
PROPOSED CONSTRUCTION ASSEMBLY ENV -3 page 10 of 42
--------------------------------------_--------------------------------------
Project Name: Gardner Residence ;Date: 12/12/1997
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24. User 3665
---------------------------------------------------------------------------
COMPONENT DESCRIPTION
-------------------------------
1 I �
1 '
------------------------------
Sketch of Construction Assembly
Assembly Name: R-21 Wall ( W .21 .2x6 .16 )
Assembly Type: Wall
Assembly Tilt: 90 deg (vertical)
Framing Material: Wood
Framing Spacing: U.C.
Framing Percent: 15.0
Absorptivity: 0.70
Roughness: Stucco, Wood Shingles
Weight:
Heat Capacity:
u
13.2 lb/sgft
3.23
ASSEMBLY U -VALUE
Th
R -value
Construction Components
Fr (in)
Cavity
Frame
- ----------------------------------------
-
Outtsidsid e Air Film
0.17
0.17-
1. Stucco
0.875
0.17
0.17
2. Membrane, Vapor -Permeable Felt
0.010
0.06
0.06
3. Insulation, Mineral Fiber, R-21
* 5.500
21.00
5.45
4. Gypsum or Plaster Board
0.500
0.45
0.45
5.
6.
7.
8.
9.
Inside Air Film
0.68
0.68
'
---------------------------------------------------------------------------
Unadjusted
R -Values
22.53
6.98
ADJUSTMENT FOR FRAMING
'
( 1 /22.53) x (0.85) + '(1 / 6.98) x (0.15) =
0.059
TOTAL U -VALUE
=
0.059
TOTAL R -VALUE
=
16.89
Weight:
Heat Capacity:
u
13.2 lb/sgft
3.23
'PROPOSED CONSTRUCTION ASSEMBLY ENV -3 page 11 of 42
----------------------------------------------------------------------------
Project Name: Gardner Residence ;Date: 12/12/1997
1 '
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
1�
COMPONENT DESCRIPTION
-------------------------------
-------------------------------
Sketch of Construction Assembly
Assembly Name: R-38 Roof(R.38.2xl4.16)
Assembly 'Type: Roof
Assembly Tilt: 22 deg (Tilted Up)
Framing Material: Wood
Framing Spacing: U.C.
Framing Percent: 10.0
Absorptivity: 0.70
Roughness: Concrete, Asph. Shingles
'
ASSEMBLY U -VALUE
Th
R -Value
Construction Components
Fr (in)
Cavity
Frame
'Uuts
-----ide-----AirF-----ilm ----------------------------------------------
0__._1_7
0.17
1. Tile Roofing
0.500
0.13
0.13
2. Membrane, Vapor -Permeable Felt
0.010
0.06
0.06
'
3. Plywood
0.500
0.62
0.62
4. Air Space
* 1.750
0.77
1.73
5. Insulation, Mineral Fiber, R-38
6. Gypsum or Plaster Board
* 11.500
0.500
38.00
0.45
11.39
0.45
7.
S.
9
inside Air Film
0.61
0.61
----------------------------------------=----------------------------------
Unadjusted
R -Values
40.81
15.16
' ADJUSTMENT FOR FRAMING
' (1 /40.81) x (0.90) + (1 /15.16) x (0.10)
Weight:
' Heat Capacity:
10 .8 lb/sgft
3.18
0.029
TOTAL U -VALUE = 0.029
f0'fAL R -VALUE = 34.91
PROPOSED CONSTRUCTION ASSEMBLY ENV -3 page 12 of 42
---------------------------------------------------------------------------
Project Name: Gardner Residence. ;Date: 12/12/1997
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
COMPONENT DESCRIPTION
-------------------------------
-------------------------------
Sketch of Construction Assembly
ASSEMBLY U -VALUE
Assembly Name: Carpeted Slab On Grade
Assembly Type: floor
Assembly Tilt: 180 deg (Horizontal Floor)
Framing Material: None
Framing Spacing: O.C.
Framing Percent: 0.0 %
Absorptivity: 0.00
Roughness: Concrete, Asph. Shingles
weight:.
Heat Capacity:
210.9 lb/sgft
42.19
Th
R -Value
Construction Components
---------------------------------------------------------------------------
Fr (in)
Cavity
Frame
Outside Air Film
0.17
0.17
1. Earth
24.000
4.00
4.00
2. Concrete, 140 lb, Not Dried
3.500
0.28
0.28
3. Flooring, Carpet and Fibrous
Pad
0.250
2.08
2.08
4.
5.
6.
7.
8.
9.
Inside Air Film
0.92
0.92
---------------------------------------------------------------------------
Unadjusted
R -Values
7.45
7.45
ADJUSTMENT FOR FRAMING
(1'/ 7.45) x (1..00) t (1 / 7.45)
x (0.00) =
0.134
TOTAL U -VALUE
=
0.134
'TOTAL R -VALUE
=
7.45
weight:.
Heat Capacity:
210.9 lb/sgft
42.19
PROPOSED CONSTRUCTION ASSEMBLY ENV -3 page 13 of 42
-----------------------------------=---------------------------------------
Project Name: Gardner Residence ;Date: 12/12/1997
i
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
COMPONENT DESCRIPTION
-------------------------------
-------------------------------
Sketch of Construction Assembly
ASSEMBLY U -VALUE
Assembly Name: Exposed Slab on Grade
Assembly Type: Floor
Assembly Tilt: 180 deg (Horizontal Floor)
Framing Material: None
Framing Spacing: U.C.
Framing Percent: 0.0
Absorptivity: 0.00
Roughness: Concrete, Asph. Shingles
ADJUSTMENT FOR FRAMING
(1 / 5.37) x (1.00) + (1 / 5.37) x (0.00) = 0.186
TOTAL U -VALUE _
Weight:
' Heat Capacity:
I
i
I � .
210.8 lb/sqft
42.17
TOTAL R -VALUE _
0.186
5.37
Th
R -Value
Construction Components-
Fr (in)
Cavity
Frame
-------------------------------------------------=-------------------------
Outside Air Film
0.17
0.17
1. Earth
24.000
4.00
4.00
2. Concrete, 140 lb, Not Dried
3.500
0.28
0.28
3.
4.
5.
6.
7.
8.
9.
inside Air Film
0.92
0.92
---------------------------------------------------------------------------
Unadjusted R -Values
5.37
5.37
ADJUSTMENT FOR FRAMING
(1 / 5.37) x (1.00) + (1 / 5.37) x (0.00) = 0.186
TOTAL U -VALUE _
Weight:
' Heat Capacity:
I
i
I � .
210.8 lb/sqft
42.17
TOTAL R -VALUE _
0.186
5.37
PROPOSED CONSTRUCTION ASSEMBLY ENV-3age 14 of 42
----------------------------------- -------------------------P-----------
Project Name: Gardner Residence ;Date: 12/12/1997
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
COMPONENT DESCRIPTION Assembly Name: Solid wood Door
-------------------------------
weight:
Heat Capacity:
5.1 lb/sgft
1.99
Assembly Type: Door
i
Assembly Tilt: 90 deg (vertical)
Framing Material: None
Framing Spacing: _" U.C.
' f
Framing Percent: 0.0
Absorptivity: 0.70
------------------- ------------
Sketch of Construction Assembly
Roughness: Glass, Paint on Pine
1
ASSEMBLY U -VALUE
Th R -value
Construction Components
---------------------
-------------Fr (in)--Cavity----Frame
----
Outside Air Film
0.17 0.17
1. Softwood, Douglas Fir -Larch
1.750 1.73 1.73
'
2.
3.
i
4.
5.
6.
7.
13
9.
Inside Air Film
0.68 0.68
'
---------------------------------------------------------------------------
Unadjusted R -Values 2.58 2.58
ADJUSTMENT FOR FRAMING
(1 / 2.58) x (1.00) + (1 / 2.58)
-
x (0.00) 0.387 '
TOTAL U -VALUE = 0.387
TOTAL R -VALUE = 2.58
weight:
Heat Capacity:
5.1 lb/sgft
1.99
'
HVAC SYSTEM HEATING & COOLING LOAD
SUMMARYag
e 15
of 42
--------------------------------------------------------------P-----------
Project Name: Gardner Residence
;Date= 12/12/1997
Documentation: BREEZE AIR CONDITIONING
------------------------------------------ --------------------------------
;COMPLY 24 User
3665
HVAC SYSTEM DESCRIPTION
HVAC System Name=
Master Suite Zone
Heating System Name:
Lennox 80MGF4-75
Cooling System Name:
Lennox H521-411
System Multiplier=.
1
Fan Schedule:
CA Daytime Fans
Peak Load Method:
COINCIDENT
Relative Humidity=
50
COOLING
ZONES ON THIS SYSTEM PEAK
HEATING
PEAK SENSIBLE LATENT
----------------------- ----
Master Suite (Jan 12am)
-------
14205
-------
------------ ------
(Aug 2pm) 12566
2030
TOTAL ZONE LOAD
14205
-------- ------
12566
2030
Duct Gains & Losses=
1421
1257
ventilation: ( 0 'CFM )
O (
0 CFM) 0
O
Return Air Lighting Gain
0
Supply/Return Fan Gain:
0
0
TOTAL SYSTEM LOAD
15626
13823
2030'
SYSTEM OUTPUT AT DESIGN CONDITIONS
MAIN HEATING & COOLING SYSTEM
61200
29043
3142
TOTAL SYSTEM OUTPUT
61200
29043
3142
' NOTE: The TOTAL SYSTEM LOAD shown represents the minimum size equipment
which will heat or cool this zone during the design conditions indicated.
These numbers include no safety factor, and the HVAC contractor should
oversize by a reasonable margin to account for variations in weather
conditions and the pick-up capacity required to bring the zone to temper-
ature as a_result of a setback thermostat. Those responsible for final
equipment selection should note that Sensible and Latent Cooling Loads are
indicated to allow for accurate comparison with manufacturer's output data.
L
'HVAC SYSTEM HEATING & COOLING LOAD SUMMARY page 16 of 42
------------------------------------------------------------ --------------
Project Name: Gardner Residence ;Date: 12/12/1997
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
HVAC SYSTEM DESCRIPTION
NOTE: The TOTAL SYSTEM LOAD shown represents the minimum size equipment
which will heat or.cool this zone during the design conditions indicated.
These numbers include no safety factor, and the HVAC contractor should
oversize by a reasonable margin to account for variations in weather
conditions and the pick-up capacity required to bring the zone to temper-
ature as a result of a setback thermostat. Those responsible for final
equipment selection should note that Sensible and Latent Cooling Loads are
indicated to allow for accurate comparison with manufacturer's output data.
HVAC System Name:
Kit/Morn/Din "Zone
'Heating
System Name:
Lennox 80MGF4/5-100
Cooling System Name:
Lennox H521-511
System Multiplier:.
1
Fan Schedule:
CA Daytime Fans
Peak Load Method:
COINCIDENT
Relative Humidity:
50
COOLING
ZONES ON'THIS SYSTEM PEAK
=.----------------------
HEATINGPEAK
SENSIBLE LATENT
----
Kit/Morn/Din/Entry (Jan 12am)
-------
22727
--
------------ ------
(Aug 2pm) 26071
---
2849
TOTAL ZONE LOAD
22727
--
26071
2849
Duct Gains & Losses:
2273
2607
Ventilation: ( 0 CFM)
0 (
0 CFM) 0
0
Return Air Lighting Gain
0
Supply/Return Fan Gain:
------0
TOTAL SYSTEM LOAD
25000
-------0
28678
2849
SYSTEM OUTPUT AT DESIGN CONDITIONS
MAIN HEATING & COOLING SYSTEM
--82000
38956
-----
2056
'TOTAL SYSTEM OUTPUT
82000
38956
2056
NOTE: The TOTAL SYSTEM LOAD shown represents the minimum size equipment
which will heat or.cool this zone during the design conditions indicated.
These numbers include no safety factor, and the HVAC contractor should
oversize by a reasonable margin to account for variations in weather
conditions and the pick-up capacity required to bring the zone to temper-
ature as a result of a setback thermostat. Those responsible for final
equipment selection should note that Sensible and Latent Cooling Loads are
indicated to allow for accurate comparison with manufacturer's output data.
NOTE: The TOTAL SYSTEM LOAD shown represents the minimum size equipment
which will heat or cool this zone during the design conditions indicated.
These numbers include no safety factor, and the HVAC contractor should
oversize by a reasonable margin to account for variations in weather
conditions and the pick-up capacity required to bring the zone to temper-
ature as a result of a setback thermostat. Those responsible for final
equipment selection should note that Sensible and Latent Cooling Loads are
indicated to allow for accurate comparison with manufacturer's output data.
HVAC SYSTEM HEATING & COOLING LOAD
SUMMARY-------------------page-17
of 42
Project Name.: Gardner Residence
;Date: 12/12/1997
Documentation: BREEZE AIR CONDITIONING
;COMPLY 24 User
3665
---------------------------------------------------------------------------
HVAC SYSTEM DESCRIPTION
HVAC System Name:
Great/Media 'Zone
Heating System Name:
Lennox 80MGF4/5-100
Cooling System Name:
Lennox H521-651
System Multiplier:
1
Fan Schedule:
CA Daytime Fans
Peak Load Method:
COINCIDENT
Relative Humidity:
50 %
'
COOLING
ZONES ON THIS SYSTEM PEAK
HEATING
PEAK SENSIBLE LATENT
Great/Media/Workout (Jan 12am)
26487
--
------
(Aug 2pm) 28193
4328
TOTAL ZONE LOAD
26487
-----
28193
4328
Duct Gains & Losses:
2649
2819
Ventilation: ( 0 CFM)
O (
0 CFM) 0
0
Return Air Lighting Gain
0
Supply/Return Fan Gain:
O
0
TOTAL SYSTEM LOAD
29136
31012
4328
l
SYSTEM OUTPUT AT DESIGN CONDITIONS
MAIN HEATING & COOLING SYSTEM
82000
44670
3563
TOTAL SYSTEM OUTPUT
82000
44670
3563
NOTE: The TOTAL SYSTEM LOAD shown represents the minimum size equipment
which will heat or cool this zone during the design conditions indicated.
These numbers include no safety factor, and the HVAC contractor should
oversize by a reasonable margin to account for variations in weather
conditions and the pick-up capacity required to bring the zone to temper-
ature as a result of a setback thermostat. Those responsible for final
equipment selection should note that Sensible and Latent Cooling Loads are
indicated to allow for accurate comparison with manufacturer's output data.
NOTE: The TOTAL SYSTEM LOAD shown represents the minimum size equipment
which will heat or cool this zone during the design conditions indicated.
These numbers include no safety factor, and the HVAC contractor should
oversize by a reasonable margin to account for variations in weather
conditions and the pick-up capacity required to bring the zone to temper-'
ature as a result of a setback thermostat. Those responsible for final
equipment selection should note that Sensible and Latent Cooling Loads are
indicated to allow for accurate comparison with manufacturer's output data.
HVAC SYSTEM HEATING & COOLING LOAD
---------------------------------------------
SUMMARYag
e 18
-------- ----P-----------
of 42
Project Name: Gardner Residence
;Date: 12/12/1997
BREEZE AIR CONDITIONING
Documentation:
---------------------------------------------------------------------------
;COMPLY 24 User
3665
HVAC SYSTEM DESCRIPTION
HVAC System Name:
Guest Suite "Lone
Heating System Name
LENNOX 80MGF3-60A-*
Cooling System Name:
LENNOX H526 -311-1P
System Multiplier:.
1
Fan Schedule:
CA Daytime Fans
•�
Peak Load Method:
COINCIDENT
Relative Humidity:
50 %
COOLING
ZONES ON THIS SYSTEM PEAK
HEATING
PEAK SENSIBLE LATENT
----------------------- ----
Guest Suite (Jan 12am)
-------
-14069
-
------------ ------
(Aug 2pm) ---1487"2 --1565
TOTAL ZONE LOAD
14069
14872
1565
Duct Gains & Losses:
1407
1487
Ventilation: ( O CFM)
0(
O CFM) 0
0
Return Air Lighting Gain
0•
Supply/Return Fan Gain:
0
0
TOTAL SYSTEM LOAD
15476
16359
1565
SYSTEM OUTPUT AT DESIGN CONDITIONS
MAIN HEATING & COOLING SYSTEM
49000
--
22675
-----
4607
TOTAL SYSTEM OUTPUT
49000
22675
4607
NOTE: The TOTAL SYSTEM LOAD shown represents the minimum size equipment
which will heat or cool this zone during the design conditions indicated.
These numbers include no safety factor, and the HVAC contractor should
oversize by a reasonable margin to account for variations in weather
conditions and the pick-up capacity required to bring the zone to temper-'
ature as a result of a setback thermostat. Those responsible for final
equipment selection should note that Sensible and Latent Cooling Loads are
indicated to allow for accurate comparison with manufacturer's output data.
RESIDENTIAL ZONE HEATING LOAD SUMMARY page 19 of 42
---------------------------------------------------------------------------
Project Name: Gardner Residence ;Date: 12/12/1997
i
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
Zone Name: Master Suite
Design Indoor Dry Bulb Temperature: 70 F
Design Outdoor Winter Dry Bulb 'Temperature= 32 F
Design Temperature Difference: 38 F
Conduction
R-21 Wall ( W .21 .2x6.16 )
Dual Bronze
Dual Bronze
Dual Bronze
Glass Block Default (R)
Dual Bronze
R-38 Roof(R.38.2x14.16)
slab on Grade
Slab on Grade
Infiltration: 1.00 x 0.018 x
Btu/hr
1717
230
167
1976
821
167
757
249
3403
4719
14205
Heating AirFlow= 14205 Btu/hr / [1.07 x 35 F DeltaT )], = 379 cfm
Area
------
U -Value
-----------
TD
763.0
x
0.0592
x
38.0 =
11.0
x
0.5500
X.38.0
=
8.0
x
0.5500
x
38.0 =
80.0
x
0.6500
x
38.0 =
30.0
x
0.7200
x
38.0 =
8.0
x
0.5500
x
38.0 =
695.0
x
0.0286
x
38.0 =
Perim =
6.0
x
42 =
Perim =
82.0
x
42 =
695 sf
x 10.0
ft
x 1.00 AC
x
38.0 =
TOTAL
HOURLY
HEAT
LOSS FOR
ZONE
Btu/hr
1717
230
167
1976
821
167
757
249
3403
4719
14205
Heating AirFlow= 14205 Btu/hr / [1.07 x 35 F DeltaT )], = 379 cfm
RESIDENTIAL ZONE HEATING LOAD SUMMARY page 20 of 42
---------------------------------------------------------------------------
Project Name: Gardner Residence ;Date: 12/12/1997
rDocumentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
---------------------------------------------------------------------------
Heating AirFlow: 22727 Btu/hr / [1.07 x 35 F DeltaT)] = 606 cfm-
Zone Name_:
Kit/Morn/Din/Entry
Design Indoor Dry Bulb Temperature:
70 F
Design Outdoor Winter Dry Bulb
Temperature:
32 F
Design Temperature Difference:
38 F
Conduction
Area
U -value
TD
Btu/hr
-----------------------
R-21 Wall. (W .21 .2x6 .16 )
------
623.0
x
-------
0.0592
x
----
38.0
------
1402
Dual Bronze
64.0
x
0.5500
x
38.0
1338
Dual Bronze
96.0
x
0.6500
x
38.0 =
2371
Dual Bronze
64.0
x
0.6500
x
38.0 =
1581
Dual Bronze
40.0
x
0.6900
x
38.0 =
1049
Dual Bronze
16.0
x
0.5500
x
38.0
334
Dual Bronze
28.0
x
0.6500
x
38.0 =
692
Dual Bronze
72.0
x
0.5500
x
38.0
1505
Dual Bronze
48.0
x
0.5500
x
38.0
1003
R-38 Roof(R.38.2x14.16)
816.0
x
0.0286
x
38.0 =
888
Slab on Grade
Perim =
67.0
x
42 =
2781
Slab on Grade
Perim =
14.0
x
42. =
581
Infiltration: 1.00 x 0.018 x
816 sf
x 13.0 ft
x 1.00 AC
.x
38.0 =
7203
.�,
TOTAL
HOURLY HEAT
L055 FOR
ZONE
22727
Heating AirFlow: 22727 Btu/hr / [1.07 x 35 F DeltaT)] = 606 cfm-
Heating AirFlow:
26487 Btu/hr / [1.07 x 35 F DeltaT )] = 706 cfm
RESIDENTIAL ZONE HEATING LOAD SUMMARY
page 21
of 42
Project Name: Gardner Residence
;Date:
12/12/1997
Documentation: BREEZE AIR CONDITIONING
---------------------------------------------------------------------------
;COMPLY
24 User
3665
Zone Name:
Great/Media/Workout
Design Indoor Dry Bulb Temperature:
70 F
Design Outdoor Winter Dry Bulb Temperature:
32 F
Design Temperature Difference:
38 F
Conduction
Area
U -Value
TD
Btu/hr
R-21 Wall (W.21.2x6.16)
1207.4
x
0.0592
x
38.0 =
2717
Solid Wood Door
21.3
x
0.3872
x
38.0
313
Dual Bronze
8.0
x
0.6900
x
38.0
210
Dual Bronze
25.0
x
0.6900
x
38.0 =
656
Dual Bronze
81.3
x
0.5500
x
38.0
1699
Dual Bronze
128.0
x
0.6500
x
38.0
3162
Dual Bronze
15.0
x
0.5500
x
38.0 =
314
Dual Bronze
Dual Bronze
8.0
4.0
x
x
0.6900
0.8000
x
x
38.0 _
38.0
210
122
R-38 Roof(R.38.2x14.16)
1387.0
x
0.0286
x
38.0 =
1510
Slab on Grade Perim =
57.0
x
42 =
2366
Slab on Grade Perim =
68.0
x
42 =
2822
Infiltration: 1.00 x 0.018 x 1391 sf
x 11.0 ft
x 1.00 AC
x
38.0 =
10389
TOTAL
HOURLY HEAT
LOSS FOR
ZONE
26487
Heating AirFlow:
26487 Btu/hr / [1.07 x 35 F DeltaT )] = 706 cfm
RESIDENTIAL ZONE HEATING LOAD SUMMARYpage 22 of 42
-------------------------------------------------------------------------
Project Name: Gardner.Residence ;Date: 12/12/1997
1
Documentation: BREEZE AIR CONDITIONING ;COMPLY 24 User 3665
----------------------=----------------------------------------------------
"Zone Name:
_ Design Indoor Dry Bulb Temperature:
Design Outdoor Winter Dry Bulb Temperature:
Design Temperature Difference:
Guest Suite
70 F
32 F
38 F
U -Value TD
0.0592 x 38.0. _
0.5500 x 38.0 =
0.6500 x 38.0. _
0.6500 x 38.0 =
0.5500 x 38:0 =
0.0286 x 38.0 =
42 =
1 42 =
Infiltration: 1.00 x 0.018 x 573 sf x 9.0 ft x 1.00 AC x 38.0 =
TOTAL HOURLY HEAT LOSS FOR ZONE
Btu/hr
1629
627
1976
1186
376
624
332
3818
350'2
14069
Heating AirFlow: 14069 Btu/hr / [1.07 x 35 F DeitaT)] = 375 cfm
Conduction
Area
-----------------------
R-21
Dual
Wall ( W .21 .2x6 .16 )
Bronze
_ ------
724.0 x
30.0 x
Dual
Bronze
80.0 x
Dual
Bronze
48.0 x
Dual
Bronze
18.0 x
R-38
Roof(R.38.2x14.16)
573.0 x
Slab
on Grade
Perim = 8.0 x
Slab
on Grade
Perim = 92.0 x
Guest Suite
70 F
32 F
38 F
U -Value TD
0.0592 x 38.0. _
0.5500 x 38.0 =
0.6500 x 38.0. _
0.6500 x 38.0 =
0.5500 x 38:0 =
0.0286 x 38.0 =
42 =
1 42 =
Infiltration: 1.00 x 0.018 x 573 sf x 9.0 ft x 1.00 AC x 38.0 =
TOTAL HOURLY HEAT LOSS FOR ZONE
Btu/hr
1629
627
1976
1186
376
624
332
3818
350'2
14069
Heating AirFlow: 14069 Btu/hr / [1.07 x 35 F DeitaT)] = 375 cfm
.
RESIDENTIAL ZONE COOLING LOAD SUMMARY -------page "23 of 42
------------------------------------------------------------------
Project Name: Gardner Residence ;Date: 12/12/1997
Documentation: BREEZE AIR CONDITIONING :COMPLY 24 User 3665
---------------------------------------------------------------------------
Zone Name: Master Suite
Design indoor Dry Bulb
Temperature=
78 F
Design Outdoor Summer Dry Bulb 'Temperature=
112 F
Design Temperature Difference:
34 F
conduction
Area
U -value
DETD
Btu/hr
-----------------------
R-21 Wall (W.21.2x6.16)
------
763.0
x
-------
0.0592 x
----
30.6 =
------
1382
Dual Bronze
11.0
x
0.5500 x
34.0 =
206
Dual Bronze
8.0
x
0.5500 x
34.0 =
150
Dual Bronze
80.0
x
0.6500 x
34.0 =
1768
Glass Block Default ( R )
30.0
x
0.7200 x
34.0 =
734
Dual Bronze
8.0
x
0.5500 x
34.0 =
150
R-38 ROOf(R.";3.2x14.16)
695.0
x
0.0286 x
51.0 =
1015
Infiltration: 1.00 x 0.018 x 695 sf x 10.0 ft
x 1.00 AC x
34.0 =
4222
Shaded
unshaded
Solar Gain
Orient.
Area SGF
Area SGF
Sc
-----------------------
Dual Bronze
-----=---
North [
---- ---
0.0 x 15
+
---- ---
11.0 x 15]
----
x 0.55
= 91
Dual Bronze
South [
80.0 x 15
+
0.0 x 321
x 0.53
= 642
Dual Bronze
South [
8.0 x 15
+
0.0 x 32]
x 0.55
= 66
Glass Block Default ( R )
South [
30_.0 x 15
+
0.0 x 32]
x 0.88
= 396
Dual Bronze
West [
0.0 x 15
+
8.0 x 731
x 0.55
= 323
Internal Gain
Op Frac.
Area
Heat
---------
Gain
Conv.
-----
-----------------------
Lighting
--------
1.00
------
x 695.0
x
0.200 x
3.4.13 =
474
Equipment
1.00
x 695:0
x
0.100 x
3.413 =
237
Occupants
1.00
x 695.0
x
255 /
250 =
709
'TOTAL HOURLY
SENSIBLE HEAT
GAIN FOR ZONE
12566
Latent Gain
Op Frac.
Area
Heat
---------
Gain
Conv.
-----
Btu/hr
------
-----------------------
Equipment
--------
1.00
------
x 695.0
x
0.000 x
3.413 =
0
Occupants
1.00
x 695.0
x
255 /
250 =
709
Infiltration: 1_.00
x 695 sf
x 10.0 ft
x
1.00 AC x
0.190 =
1322
Cooling AirFlow:
is,
TOTAL HOURLY LATENT HEAT GAIN FOR "ZONE 2030
12566 Btu/hr / .[1 .07 x 23 F DeltaT )] = 510 cfm
RESIDENTIAL ZONE COOLING LOAD SUMMARY
---------------------------------------------------------------------------
page 24 of 42
Project Name:
Gardner Residence
;Date:
12/12/1997
Documentation:
BREEZE AIR CONDITIONING
;COMPLY 24
---------------------------------------------------------------------------
User
3665
Zone Name:
Kit/Morn/Din/Entry
Design Indoor
Dry Bulb Temperature:
78 F
Design Outdoor
Summer Dry Bulb Temperature:
112 F
Design Temperature
Difference:
34 F
Conduction
Area
U -value
DETD
Btu/hr
----------- ------------
R-21 Wall (W.21.2x6.16)
------
623.0
x
-------
0.0592 x
----
30.6 =
------
1129
Dual Bronze
64.0
x
0.5500 x
34.0 =
1197
Dual Bronze
96.0
x
0.6500 x
34.0 =
2122
Dual Bronze
64.0
x
0.6500 x
34.0 =
1414
Dual Bronze
40.0
x
0.6900 x
34.0 =
938
Dual Bronze
16.0
x
0.5500 x
34.0
299
Dual Bronze
28.0
x
0.6500 x
34..0
619
Dual Bronze
72.0
x
0.5500 x
34.0 =
1346
Dual Bronze
48.0
x
0.5500 x
34.0
898
R-38 Roof(R.38.2x14.16)
816.0
x
0.0286 x
51.0 _
1192
Infiltration:
1.00 x 0.018 x 816 sf x 13.0 ft
x 1.00 AC x
34.0 =
6444
Shaded
Unshaded
Solar Gain
Orient.
Area SGF
Area SGF
5C
----------
Dual - ------------
Bronze
--------- [
East
---- ---
18 0 x 15
+
--- ---
78.0 x 73]
--
-�
x 0.53
- 3190
Dual Bronze
East [
16.0 x 15
+
0.0 x 73]
x 0-.55
= 133
Dual Bronze
East [
48.0 x 15
+
0.0 x 73]
x 0.55
= 398
Dual Bronze
Southeast [
64.0 x 15
+
0.0 x 62]
x 0.53
= 513
Dual Bronze
South [
40.0 x 15
+
0.0 x 32]
x 0.53
= 321
-Dual Bronze
Southwest [
8.0 x 15
+
0.0 x 62]
x 0.55
= 66
Dual Bronze
Southwest [
28.0 x 15
+
0.0 x 62]
x 0.58
= 246
Dual Bronze
Southwest [
8.0 x 15
+
0.0 x 62]
x 0.55
= 66
Dual Bronze
West [
12.0 x 15
+
0.0 x 73]
x 0.55
= 100
Dual Bronze
West [
36.0 x 15
+
0.0 x 73]
x 0.55
= 299
Dual Bronze
West [
24.0 x 15
+
0.0 x 73]
x 0.55
= 199
Dual Bronze
Northwest [
0.0 x 15
+
12.0 x 48]
x 0.55
= 318
Dual Bronze
Northwest [
0.0 x 15
+
36.0 x 481
x 0.55
= 955
Internal Gain
Op Frac.
Area
Heat Gain
Conv.
-----------------------
Lighting
--------
1.00
------
x 816.0
---------
x
0.200 x
-----
3.413
557
Equipment
A.00
x 816.0
x
0.100 x
3.413
= 279
Occupants
1.00
x 816.0
x
255 /
250
= 832
TOTAL HOURLY
SENSIBLE HEAT
GAIN FOR ZONE
26071
Latent Gain
Op Frac.
Area
Heat Gain
Conv.
Btu/hr
-----------------------
---_----
------
--------
-----
------
Equipment
1.00
x 816.0
x
0.000 x
3.413
- 0
Occupants
1.00
x 816.0
x
255 /
-250
= 832.
Infiltration:
1.00 x 816 sf
x 13.0 ft
x
1.00 AC'x
0.190
= 2017.
TOTAL HOURLY LATENT.HEAT
GAIN FOR ZONE
2849
Cooling AirFlow: 26071 Btu/hr
/ [1.07 x 23
F DeltaT)]
= 1057
cfm
RESIDENTIAL ZONE COOLING LOAD SUMMARY page 25 of 42
---------------------------------------------------------------------------
.Nroject Name: Gardner Residence ;Date: 12/12/1997
Documentation: BREEZE AIR CONDITIONING :COMPLY 24 User 3665
---------------------------------------------------------------------------
"Zone Name:
Design Indoor Dry Bulb Temperature:
Design outdoor Summer Dry Bulb 'Temperature:
Design Temperature Difference:
Great/Media/workout
78 F
112 F
34 F
Conduction-------------
-Area-
U -value
DETD
Btu/hr
R-21 Wall (W .21 .2x6 .•16 )
1207.4
x
. 0 .0592 x
30.6 =
2188
Solid Wood Door
21.3
x
0.3872 x
30.6 =
252
Dual Bronze
8.0
x
0.6900 x
34.0
188
Dual Bronze
25.0
x
0.6900 x
34.0
587
Dual Bronze
81.3
x
0.5500 x
34.0 =
1520
Dual Bronze
128.0
x
0.6500 x
34.0
2829
Dual Bronze
15.0
x
0.5500 x
34.0
281
Dual Bronze
8.0
x
0.6900 x
34.0 =
188
Dual Bronze
4.0
x
0.8000 x
34.0
109
R-38 Roof(R.38.2x14.16)
1387.0
x
0.0286 x
51.0 _
2026
Infiltration: 1.00 x 0.018 x 1391
sf x 11.0 ft
x 1.00 AC x
34.0 =
9296
1
Shaded
Unshaded
Solar Gain
Orient.
Area SGF
Area SGF
SC
-----------------------
Dual Bronze
---------
North
---- ---
[ 0.0 x 15
+
25.0 x 15]
x 0.53
= 201
Dual Bronze
North
[ 0.0 x 15
+
8.0 x 15]
x 0.53
= 64
Dual Bronze
East
[ 11.5 x 15
+
49..8 x 73]
x 0.55
= 2105
Dual Bronze
East
[ 12.0 x 15
+
52.0 x 731
x 0.53
= 2127
Dual Bronze
East
[ 63.2 x 15
+
0.8 x 731
x 0.53
= 538
Dual Bronze
East
[ 20.0 x 15
+
0.0 x 73]
x 0.55
= 166
Dual Bronze
South
[ 0.0 x 15
+
15.0 x 32]
x 0.55
= 265
Dual'Bronze
South
[ 8.0 x 15
+
0.0 x 321
x 0.55
= 66
Dual Bronze
Skylight
[ 0.0 x 15
+
4.0 x152]
x 0.58
= 356
Internal Gain
-----------------------
Op Frac
Area
Heat
Gain
Conv.
Lighting
--------
1.00
------
x 1391.0
---------
x
0.200 x
-----
3.413 =
949
Equipment
1.00
x 1391.0
x
0.100 x
3.413
475
Occupants
1.00
x 1391.0
x
255 /
250
1419
'TOTAL HOURLY
SENSIBLE HEAT
GAIN FOR ZONE
28193
Latent Gain
Op Frac.
Area
Heat Gain
Conv.
Btu/hr
i-----------------------
Equipment
---_----
1.00
-----
x 1391. 0
x
0.000 x
.
3 413
"
_ 0
Occupants
1.00
x 1391.0
x
255 /
"250
-
- 1419
Infiltration: 1.00
x 1391 sf
x 11.0 ft
x
1.00 AC x
0.190
= 2910
TOTAL HOURLY
LATENT HEAT
GAIN FOR ZONE
4328
Cooling AirFlow: 28193
Btu/hr
/ (1.07. x 23
F DeltaT )]
= 1143
cfm
Cooling AirFlow:
t
14872 Btu/hr / [1.07 x 23 F DeltaT )] = 603 cfm
.
RESIDENTIAL ZONE COOLING LOAD SUMMARYa
e 26
of 42
--------------------------------------------------------------P-9----------
Project Name:
Gardner Residence
;Date:
12/12/1997
Documentation:
---------------------------------------------------------------------------
BREEZE AIR CONDITIONING
;COMPLY 24 User
3665
Zone Name:
Guest
Suite
Design Indoor
Dry Bulb Temperature:
78 F
Design Outdoor
Summer Dry Bulb Temperature:
112 F
Design 1'emperature Difference:
34 F
Conduction
-------------
Area
------
U_Value
DETD
Btu/hr
R-21 Wall (W.21.2x6.16)
724.0
x
0.0592 x
30.6 =
1312
Dual Bronze
30.0
x
0.5500 x
34.0 =
561
Dual Bronze
80.0
x
0.6500 x
34.0 =
1768
Dual Bronze
48.0
x
0.6500 x
34.0
1061
Dual Bronze
18.0
x
0.5500 x
34.0 =
337
R-38 Roof(R.38.2x14.16)
573.0
x
0.0286 x
51.0 =
837
Infiltration:
1.00 x 0.018 x 573 sf
x 9.0 ft
x 1.00 AC x
34.0 =
3133
Shaded
Unshaded
Solar Gain
Orient.
Area SGF
Area SGF
SC
-----------------------
Dual Bronze
---------
East [
---- ---
0.0 x 15
+
---- ---
30.0 x 73]
----
x 0.55 =
1211
Dual Bronze
East [
15.0 x 15
+
65.0 x 73].
x 0.53 =
2658
Dual Bronze
South [
42.6 x 15
+
5.4 x 321
x 0.53 =
434
Bronze
West [
7.5 x 15
+
2.5 x 73]
x 0.55 =
163
'Dual
Dual Bronze
West [
3.0 x 15
+
5.0 x 73]
x 0.55 =
227
'
internal Gain
-----------------------
Op Frac.
-
Area
--
Heat
Gain
-
Conv_
Lighting
1.00 -x
573.0
x
0.200 x
3.413 =
391
Equipment
1.00 x
573.0
x
0.100 x
3.413 =
196
Occupants
1.00 x
573.0
x
255 /
250 =
---584
TOTAL HOURLY SENSIBLE
HEAT
GAIN FOR ZONE
14872
'
Latent Gain
-----------------------
Op Frac.
--------
Area
------
Heat
---------
Gain
Conv.
-----
Btu/hr
------
Equipment
1.00 x
573.0
x
0.000 x
3.413 =
0
Occupants
1.00 x
573.0
x
255 /
250 =
584
Infiltration:
1.00 x 573 sf x
9.0 ft
x
1.00 AC x
0.190
981
■
TOTAL -HOURLY
LATENT HEAT
GAIN FOR ZONE
1565
Cooling AirFlow:
t
14872 Btu/hr / [1.07 x 23 F DeltaT )] = 603 cfm
II
L�
L
F1
s
fl
1
LfGi?C6�';
FURNACES
UP-FLO - DOWN-FLO - HORIZONTAL Bulletin #210024
*80.0% to 80.5% A-F.U.E. April 1995
45,000 to 140,000 Btuh (13.2 to 41.0 M Input Supersedes
1-1/2 thru 6 Tons (3.5 thru 21.1 M Nominal Add-on Cooling September 1994
•Isolated Combustion System Rating For Non -Weatherized Furnaces
80MGF(X)
p[Sliy
Cile rcn�c. I r 4
,zmrw I cry
ama; ,f
o r ,
CfRTIF1C0
Typical Applications
Up -Flo Utility Room Installation
With Cooling Coil
and Automatic Humidifier
0
0
Down -Flo Closet Installation
With Cooling Coil
Horizontal Attic Installation
With Cooling Coil, Electronic Air Cleaner
and Automatic Humidifier
UP-FLO POSITION
Applications — 80MGF(X) series gas fired furnaces include
eleven models (natural gas or LPG/propane) with input capaci-
ties of 45,000, 60,000, 75,000, 100,000, 120,000 and 140,000
Btuh (13.2, 17.6, 22.0, 29.3, 35.2 and 41.0 kW) and energy effi-
ciencies (AFUE) of up to 80.5%. Units are applicable to up -flow,
down -flow or horizontal applications. Lennox add-on evapora-
tor coils, electronic air cleaners and power humidifiers can be
easily added to the furnace. Units are shipped factory as-
sembled with all controls installed and wired. Each unit is fac-
tory test operated to insure proper operation.
Approvals — Units are certified by A.G.A./C.G.A. Laboratories.
and ratings are certified by GAMA. Units have been rated and
tested according to U.S. DOE test procedures and FTC labeling
regulations. 80MGF "X" models meet California Nitrogen Ox-
ides (NO,) Standards and California Seasonal Efficiency require-
ments. Blower data is from unit tests conducted in the Lennox
Laboratory air test chamber. Units are approved for conventional
or horizontal (sidewall) venting. NOTE — Horizontal venting re-
quires sidewall power venting kit, see Optional Accessories.
Equipment Warranty— Aluminized steel heat exchanger has
a limited warranty fora full ten years. Solid-state ignition mod-
ule has a limited warranty for three years. All other compo-
nents have a limited warranty for one year. Refer to the Lennox
Equipment Limited Warranty certificate included with the
equipment for details.
O The maple leaf symbol in this bulletin denotes Canadian only usage where applicable r.1995 Lennox Industries Inc.
NOTE — Due to Lennox' ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
JESPECIFICATIONS
r
L
L�
t
Model No.
80MGF2(X)-45
80MGF2-60 80MGF3(X)-60 80MGF2-75
80MGF3(X)-75
Input Btuh (kW)
45,000 (13.2)
60,000 (17.6) 60,000 (17.6) 75,000 (22.0)
75,000 (22.0)
Output Btuh NW)
36,900 (10.8)
49,200 (14.4) 49,200 (14.4) 61,700 (18.1)
61,700 (18.1)
/A.F.U.E.
80.1%
80.540 80.5% 1 80.1%
1 80.0%
California Seasonal Efficiency
75.4%
76.4% 75.9% 76.8%
76.8%
tFlue size connection diameter - in. (rhm) round
3 (76)
3 (76) 3 (76) 4 0021
4 002)
Temperature rise range -'F ('C)
25 - 55 (14 -30)
45- 75(14-30) 35 - 65 (19 -36) 45 - 75 (14 -30)
45 - 75 (14 -30)
High static certified by A.G.A./C.G.A. - in wg. (Pal
.50(125)
.50(125) .50025) .50025)
.50025)
Gas Piping Size I.P.S. Natural or "LPG/propane
1/203)
1/203) 1/203) 1/203)
1/2(13)
Blower wheel nominal
diameter x width
in.
9 x 7
9 x 7 10 x 7 9 x 7
10 x 7
mm 229 x 178 229 x 178 254 x 178 229 x 178
254x 178
Blower motor output - hp (W1
1/4(187)
1/4(187) 1/3(224) 1/4087)
1/3(224)
Nominal cooling
that can be added
Tons
1, 1-1/2 or 2
1, 1-1/2 or 2 2, 2-1/2 or 3 1, 1-1/2 or 2
2, 2-1/2 or 3
kW 3.5, 5.3 or7.0 3.5, 5.3 or7.0 1 7.0, 8.8 or 10.6 3.5, 5.3 or7.0
7.0, 8.8 or 10.6
Shipping weight - lbs. (kg) 1 package
130 (59)
130 (59) 135 (611 135 (611
135 (61!
Electrical characteristics
120 volts - 60 hertz - 1 phase (less than 12 amps) All models
• Optional Accessories (Must Be Ordered Extra) •
'•LPG/propane kit
LB -69845) (81J13)
LB -69845J (81.113)
Twinning Kit
Twinning Kit
96J69 - 5 lbs. (2 kg)
96,169 - 5 lbs. (2 kg)
*Up-flow/Horizontal
Filter Kit
,: Up-flow/HorizontaI
Filter Kit
Catalog No.
No. & Size of Filter - in. (mm)- (1) 16 x 20 x 1 (406 x 508 x 25) (1) 20 x 20 x 1 (508 x 508 x 25)
LB -69958A 132.1021 - 10 lbs. (4 kg)
Catalog No.
No. & Size of Filter - in. (mm) (1) 16 x 20 x 1 (406 x 508 x 25)
LB -69843A (32.101) - 3 lbs. (1 kg)
*Down -flow
Filter Kit
Catalog No.
LB -69843A (32.101) - 3 lbs. (1 kg)
LB -79239A (67J91) - 10 lbs. (4 kg) I LB -792398 (67,1921 - 10 lbs. (4 kg)
No. & Size of Filters - in. (mm) (2) 16 x 20 x 1 (406 x 508 x 25)
Down -flow Combustible Floor Base
LB -79239A (67.191) - 10 lbs. (4 kg)
Sidewall Power Venting Kit
7SJ15 - 25 lbs. 01 kg)
Hanging Bracket Kit
LB -69957 (46.166) - 15 lbs. IS kg)
eAnnual Fuel Utilization Efficiency based on U.S. DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non -weatherized
furnaces.
"LPG/propane kit must be ordered extra for field changeover.
*Filters are not furnished with kit and must be ordered extra. xPolyurethane frame type filter is furnished with kit.
t 2 in. x 3 in. (51 mm x 76 mm) flue adaptor furnished with -45 & -60 input furnaces for connection to furnace induced draft blower.
2 in. x 4 in. (51 mm x102 mm) flue adaptor furnished with -75 input furnaces for connection to furnace induced draft blower.
SPECIFICATIONS A
Model No.
80MGF4(X)-75
80MGF3/4(X)-100
80MGF4/5(X)-100
Input Btuh (kW)
75,000 (22.0)
100,000 129.31
100,000 (29.3)
Output Btuh (kW)
61,700 (18.1)
82.000 (24.01
82.000 (24.01
eA.F.U.E.
80.0%
80.1%
80.00/0
California Seasonal Efficiency
76.3%
76.5%
77.0%
tFlue size connection diameter - in. (mm) round
4 002)
4 002)
4 002)
Temperature rise range -'F ('C)
40 - 70 (22 -39)
45 - 75 (14 -30)
35 - 65 (19 -36)
High static certified by A.G.AJC.G.A. - in wg. (Pa)
.50025)
.50025)
.5011125)
Gas Piping Size I.P.S. Natural or ••LPG/propane
1/203)
1/203)
1/211113)
Blower wheel nominal
diameter x width
in.
12 x 8
12 x 8
12 x 9
mm 305 x 203 305 x 203
305 x 229
Blower motor output - hp (W)
1/2(373)
1/2(373)
3/4 (560)
Nominal cooling
that can be added
Tons
2, 2-1/2, 3, 3-1/2 or 4
2, 2-1/2, 3, 3-1/2 or 4
3-1/2, 4, 5 or 6
kW 7.0, 8.8,-10.6, 12.3 or 14.1 7.0, 8.8, 10.6, 12.3 or 14.1
12.3. 14.1, 17.6 or 21.1
Shipping weight - lbs. (kg) 1 package
140 (64)
175 (79) 7
175 (79)
Electrical characteristics
120 volts - 60 hertz - 1 phase (less than 12 amps) All models
• Optional Accessories (Must Be Ordered Extra) •
"'LPG/propane kit
LB -69845) (81J13)
LB -69845K 181.114)
Twinning Kit
96J69 - 5 lbs. (2 kg)
*Up-flow/Horizontal
Filter Kit
Catalog No.
LB -69958A (32.102) - 10 lbs. (A kg) LB -699588 (46J141 - 10 lbs. (4 kg)
No. & Size of Filter - in. (mm)- (1) 16 x 20 x 1 (406 x 508 x 25) (1) 20 x 20 x 1 (508 x 508 x 25)
*Down -flow
Filter Kit
Catalog No.
LB -69843A (32.101) - 3 lbs. (1 kg)
No. & Size of Filters - in. (mm) (2) 16 x 20 x 1 (406 x 508 x 25)
Down -flow Combustible floor Base
LB -79239A (67J91) - 10 lbs. (4 kg) I LB -792398 (67,1921 - 10 lbs. (4 kg)
Sidewall Power Venting Kit
7SJ15 - 25 lbs. 01 kg)
Hanging Bracket Kit
LB -69957 (46J66) - 15 tbs. (8 kg)
eAnnual Fuel Utilization Efficiency based on U.S. DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non -weatherized
furnaces.
' LPG/propane kit must be ordered extra for field changeover, tAdaptor is furnished with unit for flue connection.
*Filters are not furnished with kit and must be ordered extra. :-Polyurethane frame type filter is furnished with kit.
t 2 in. x 4 in. (51 mm x102 mm) flue adaptor furnished with -75 & -100 input furnaces for connection to furnace induced draft blower.
-3-
-DIMENSIONS — inches (mml
(UP -FLOW POSITION SHOWN)
1
1
1
1
1
1
1
25
1
11
GAS PIPING 2 (51)
INLET —�
I E
LECTRICAL INLETS
(Top & Bottom)
1
(25) -
D Yo UUU1 I ! .19-1/2 �—i•'
(495)
FLUE + i •19
OUTLET 41/4 nr. ( )
(105) �C SUPPLY
_Uyu tJUL
J AIR
`nflo �nnn OPENING
*NOTE—Supply air opening at rear and sides of cabinet is 1
equipped with a 3/4 inch (19 mm) scored flange that may (251
be bent out 901 for plenum connection. Dimensions
shown are afta flange is bent out,
Double scored flange at front of supply air opening may TOP VIEW
be bent out for a total opening dimension (front to rear)
of either 19-1/2 inches (495 mm) or 19 inches (483 mm).
A
AIR *FLOW
A
B
B
c
0
o �
E
M*CReturn Air
Ooenina 111110
**NO
1
1901
FRONT VIEW
29.5/8
(752)
2 (51)
------------
F Left Side
G Right Side GAS PIPING
INLET
(Both Sides)
1
(25)
1
(25)
00
ELECTRICAL
INLETS
(Either Side) I 19-1/2� 1
(495) I (25)
15 RETURN AIR
(381) KNOCKOUT
i — —(Either Side)
r �• r -i
LJ —
rE—Return air opening is equipped 3/4 (19)
with a 3/4 inch (19 mm) flange Return Air
that may be bent out 90` for 19-1/ 1
plenum connection. Dimensions (495) Opening (25)
shown are aftr flange is bent out,
SIDE VIEW
Model No.
A
B
C
D
E
F
G
80MGF2-45
80MGF2-60
in.
17
36-1/4
15
6-3/4
2-7/16
6-1/2
12
80MGF2-75
80MGF3-60
80MGF3-75
80MGF4-75
mm
432
921
381
171
62
114
254
80MGF3/4-100
80MGF3/4-120
in.
20-1/2
39
18-1/2
8-3/8
4-1/4
8
13-1/2
80MGF4/5-100
80MGF4/5-120
mm
521
991
470
213
108
203
343
80MGF415-140
in.
23-1/4
39
21-1/4
9-3/4
4-1/4
8
13-1/2
mm 11
591
991
540
1 248
108
203
343
—7—
u
1
1
0
POWERSAVER21 TM SER
TWO SPEED CONDENSING
EXPANSION VALVE SYSTEMS
11.00 to 15.75 SEER
*34,200 to 59,000 Btuh (10.0 to 17.3 M Cooling Capacity
3 thru 5 Tons (10.6 thru 17.6 kW)
*DOE and ARI Certified Ratings
wNEN rNE cDuvLE*E WHEN USED Y/ITN PnpEEp
SYSTEM is uSTEO COMPONEMS AS uSTED
'MTN M WITH M 1p:
/15
Typical Application
Bulletin #210051
May 1994
•
Applications
Unit Cabinet
• SEER'S of up to 15.75
• Heavy gauge steel cabinet with five station metal wash process.
• 3, 4 or 5 Ton (10.5, 14.1 or 17.6 kW) sizes.
• Baked -on outdoor enamel paint finish provides rust and corrosion
• Single or three phase power supply.
protection.
• Two speed compressor staged to deliver precise cooling capacity
• Compressor and control box located in separate fiberglass
with minimum operating costs. Compressor operates on low
insulated compartment. -
speed under light and medium loads. Switches to high speed for
• Control box is conveniently located with all controls factory wired.
heavy cooling loads.
• Large removable panel provides service access.
• Vertical air discharge allows concealment behind shrubs at grade
• Drainage holes are provided in base section for moisture removal.
level or out of sight on a roof.
• High density polyethylene base channels raise unit off mounting
• Matching blower powered or add-on furnace evaporator units
surface away from damaging moisture.
provide a wide range of cooling capacities and applications. See
• Non -corrosive PVC (polyvinyl chloride) coated steel wire
ARI Ratings table.
condenser coil guard furnished.
• For evaporator unit data, see Coils– Blower Coil Units, this section.
Two Speed Compressor
• Units shipped completely factory assembled, piped and wired.
• Designed for superior efficiency at minimum operating cost
Each unit is test operated at the factory insuring proper operation.
• Two speed operation gives staging control to fit varying cooling
• Installer must set condensing unit, connect refrigerant lines and
load requirements, extends operating life of compressor and
make electrical connections to complete job.
provides operating economy during periods of reduced loads.
Approvals
During part load conditions the compressor operates in the low
• Rated in accordance with ARI 210/240-89.
• Sound rated in Lennox reverberant sound test room in accordance
speed mode.
• Operates at 1750 rpm at low speed and 3500 rpm at high speed.
with ARI Standard 270-84.
• Compressor is suction cooled, and hermetically sealed with
• Tested in the Lennox Research Laboratory environmental test
built-in solid-state motor protection from excessive current and
room.
• Rated according to U.S. Department of Energy (DOE) test
temperatures.
• Features vertical crankshaft, ringed valves and pistons, tuned
procedures.
discharge muffler, two stage oil pump and positive venting of
• Condensing units and components within bonded for
lubrication system.
• Crankcase heater assures proper compressor lubrication.
grounding to meet safety standards for servicing required by
U.L., N.E.C. and C.E.C.
• Running gear assembly resiliently suspended internally inside
• Units are U.L. listed and C.S.A. certified.
case. Compressor is installed in unit on resilient rubber mounts
assuring low sound and vibration free operation.
Equipment Warranty
Lennox TSC -5 limed Start Control Module
• Compressor — Ten years (residential applications), five years
• Provides short cycle protection with a 5 minute timed -off delay.
(non-residential applications).
Has a 1 minute delay between compressor speed changes.
• All other covered components — five years (residential), one year
• Control has jumpers for a choice of normal operation (factory
(non-residential applications).
setting) or 3 alternate compressor speed operating modes to
• Refer to Lennox. Equipment Limited Warranty certificate
optimize comfort conditions for various climates.
included with unit for details:.
• Diagnostic LED's are furnished as an aid in troubleshooting.
O The maple leaf symbol in this bulletin denotes Canadian only usage where applicable 01994 Lennox Industries Inc. '
NOTE — Due to Lennox' ongoing committent to quality, Specifications. Ratings and Dimensions subject to change without notice.
. I
,AR/ RATINGS
Condensing
Unit
Model No.
*ARI Standard
270 SRN (bels)
•ARI Standard 210/240 Ratings
Evaporator Unit
'Expansion
Valve
Kit
Required
Cooling
tSEER EER g Total
(Btuh/ (8tuh/ Capacity Unit Up -Flo Down -Flo Horizontal
Watts) Watts) Watts
Btuh kW
HS21-411
HS21-413
(7.6)
12.25
9.40
34,200
10.0
3638
- - - -
CR 18-51
LB -85663H (49.126)
12.70 9.80 34,400 10.1 3510 - - - - CH24-41
11.80 9.40 34,400 10.1 3660 O **CVP10-31/EC10Q3 - - - - - • - -
*Factory Installed
12.50 9.85 34,600 10.1 3513 ---- CR18-41 ----
LB -85663H (49J26)
12.65 9.85 34,600 10.1 3513 23-41 ((F
12.65 9.85 34,600 10.1 3513 C24-41 FC/B24 - - - •
C24-41 W FC/824
12.85 10.05 35,600 10.4 3542 C23-46(FC)
12.85 10.05 35,600 10.4 3542 C24-46FC/B24 - - - - - - - .
12.05 9.70 35,600 10.4 3670 O **CVP10-41/EC10Q3
*Factory Installed
13.25 10.15 36,000 10.5 3547 - - - - - - - - CH22-41
14.30 10.65 36,400 10.7 3418 - - - - - - - - CH22-41+GSR21V3
13.50 10.60 36,600 10.7 3453 **CB19-41 **CB19-41 **CBH19-41
LB-53081CB (11G82)
13.50 10.60 36,600 10.7 3453 **CB19-31 **CB19-31 "C81-119-31
13.10 10.40 36,800 10.8 3538 **CB19-51 **CB19-51 **C131-119-51
13.40 10.30 37,000 10.8 3592 C22-46(FC) - - - - ----
---
*Factory Installed
13.50
13.50 10.35 37,000 10.8 3575 C22-41(FC) CR22-41/B24 - - - -
14.55 10.85 37,400 11.0 3447 - - - - - - - - CH22.51+GSR21V3
14.65 10.85 37,400 11.0 3447 C22-51IF0+G21V3 CR22-51+GSR21V3 - - - -
14.60 10.85 37,400 11.0 3447 C22-41(FC)+G21V3 CR22-41+GSR21V3
13.50 10.35 37,600 11.0 3633 C22-51(FC) CR22-51/824 - - - -
13.40 10.35 37,600 11.0 3633 - - - - CH22-51
15.40 11.10 38,000 11.1 3423 **CB21V-41 **CB21V-41 **CBH21V-41
LB-53081CB (11G82)
15.75 11.65 39,500 11.6 3391 **CB21V-51 **CB21V-51 **CBH21V-51
HS21-511
HS21-513
(7.8)
11.30
9.10
44,500
13.0
4890
- • - -
CR 18-51
LB -85663D (43.176)
12.00 9.65 45,500 13.3 4715 C23-46(FC) - - - - - - -
12.00 9.65 45,500 113.3 1 4715 C24-46FC/B24 - - - - ----
---11.75
11.75 9.40 46,500 13.6 4947 - - - - CR18-65 - - - -
11.90 9.45 47,000 13.8 4974 - - - - - - - - CH24-51
12.15 9.50 47,500 13.9 5000 1 C24-51FC/B24 - - - - - - - -
12.15 9.50 47,500 13.9 5000 C23-51(FC) ----
---11.40
11.40 9.35 47,500 13.9 5080 O **CVP10-51/EC10Q4 - - - - - - - -
*Factory Installed
12.40 9.65 48,500 14.2 5026 C23-51/65(FC) - - - - - - -'
LB 856630 (43.176)
12.40 9.65 48,500 14.2 5026 C24-65FC/B24 --
12.80 9.55 48,500 114.2 5079 **CB19-51 **CB19-51 **CBH19-51
LB-53081CC (11683)
12.55 9.65 48,500 14.2 5026 C22-46(FC) - - - - - - - -
*Factory Installed
12.30 9.70 49,000 14.4 5052 - - - - CH24-65
LB -85663D 143.176)
12.65 9.70 49,000 14.4 5052 C22-51(FC) CR22-51/1324 CH22-51
*Factory Installed
13.65 10.05 49,500 14.5 4925 C22-51(FC)+G21V5 CR22-51+GSR21V5 CH22-51+GSR21V5
11.80 9.60 49,500 14.5 5156 O **CVP10-65/EC10Q5 - - - - ----
---
12.65
12.65 9.95 50,000 14.7 5025 - - - - - - - - CH22-65
*Factory Installed
12.70 9.95 50,000 14.7 5025 **CB19-65 **CB19-65 **CBH19-65
LB -53081 CC (11G83)
12.75 10.00 50,500 14.8 5050 C22.651FC) CR22-65/B24 - - • •
*Factory Installed
13.60 10.30 50,500 14.8 4903 - - - - CH22-65+GSR21V5
14.00 10.50 50,500 14.8 4810 **C821V-51 **CB21V-51 **CBH21V•51
1.B 53081CC (11G83)
13.80 10.45 51,000 14.9 4880 **CB21V-65 **CB21V-65 **CBH21V-65
13.75 10.40 51,000 14.9 4904 C22-65(F0+G21V5 CR22-65+GSR21 V5 - - - •
I *Factory Installed .
•natea m accoraance with AHIstanaard Z1U/Z4U; 95°F (35`6) outdoor air temperature, 80'F (27'Qdb/671F (19'6) wb entering evaporator air with 25 ft.
(7.6 ml of connecting refrigerant lines.
Sound Rating Number in accordance with ARI Standard 270.
**Slower powered evaporator.
***Kit is optional and must be ordered extra, unless shown as factory installed.
t Seasonal Energy Efficiency Ratio (8tuh/Watt).
*Furnished as standard with coil.
NOTE - B24 Blowers are not included with ratings for C24 and CR22 coils. B24 is shown for matching reference only.
NOTE - Shaded area denotes most popular evaporator coil.
-3-
rWA�R,RABNGS
Condensing
Unit
Model No.
'ARI Standard
270 SRN (bels)
*ARI Standard 210/240 Ratings
Evaporator Unit
-Expansion
Valve
Required
tSEER
(Btuh/
Watts)
EER
IBtuh/
Watts)
Cooling
Capacity
Total
Unit
Watts
Up -Flo
Down -Flo
Horizontal
Btuh
kW
HS21-651
HS21-653
(7.8)
11.00
8.85
49,500
14.5
5593
- - - -
CR 18-51
- - - -
LB -85663E (43J77)
11.30
9.05
50,500
14.8
5580
- - - -
- - - -
CH24-51
11.40
9.15
52,000
15.2
5683
- - - -
CR 18-65
----
---11.75
11.75
9.40
52,500
15.4
5585
CR22-51/B24
CH22-51
*Factory Installed
12.85
9.50
53,000
15.5
5579
- - - -
CR22-51+GSR21V5
CH22-51+GSR21 V5
11.50
9.25
53,000
15.5
2:730
C23-51(FC)
- - - -
LB -85663E (43J77)
11.50
9.25
53,000
15.5
5730
C24-51FCB24
----
---11.70
11.70
9.40
54,000
15.8
5745
C22-46(FC)
- - -
- - - -
*Factory Installed
11.60
9.60
54,000
15.8
5625
C ••CVP10-65/EC10Q5
----
---11.70
11.70
9.40
54,500
16.0
5798
C23-51/65(FC)
LB -85663E (43J77)
11.70
9.40
54,500
16.0
5798
C24-65FCB24
- - - -
CH24-65
12.00
9.50
55,500
16.3
5842
C22-51(FC)
- - - -
*Factory Installed
13.00
9.85
56,000
16.4
5685
C22-51(FC)+G21V5
- - - -
----
---12.25
12.25
9.80
56,000
16.4
5714
- - - -
CR22-65/B24
CH22-65
12.15
9.50
56,500
16.6
5947
C22-65(FC)
13.00
9.75
56,500
96.6
5795
- - - -
CR22-65+GSR21V5
CH22-65+GSR21V5
13.00
10.05
57,000
16.7
5672
C22-65(FC)+G21 V5
- - - -
- • - -
12.85
9.70
58,000
17.0
5979
••CB19-51
•'CB19-51
••CBH19-51
LB -530810E (32G54)
12.80
9.50
58,500
17.1
6158
'•CB19-65
•'CB19-65
••CBH19-65
13.80
10.00
58,500
17.1
5850
*•CB21V-51
"•CB21V-51
••CBH21V-51
14.00
9.80
59,000
17.3
6020
•"CB21V-65
'•CB21V-65
••CBH21V-65
•Rated in accordance with ARI Standard 210240; 95'F (35`C) outdoor air temperature, 80"F (27`C) db/67"F (19'C) wb entering evaporator air with Z5 tt.
(7.6 m) of connecting refrigerant lines.
Sound Rating Number in accordance with ARI Standard 270. -
•• Blower powered evaporator.
••• Kit is optional and must be ordered extra, unless shown as factory installed.
t Seasonal Energy Efficiency Ratio (Btuh/Wart).
*Furnished as standard with coil.
NOTE - 824 Blowers are not included with ratings for C24 and CR22 coils. B24 is shown for matching reference only.
NOTE - Shaded area denotes most popular evaporator coil.
-4-
PA
Model No.
HS21-411
HS21-413
HS21-511
HS21-513
HS21-651
HS21-653
Line -voltage data - 60 hz
208/230v
208/230v
208/230v
208/230v
208/230v
208/230v
Unit
1ph
3ph
1ph
3ph
1ph
3ph
Rated load amps
17.6
12.7
21.6
15.8
30.8
19.9
Power factor
98
.90
.98
.90
.92
.90
Compressor
Locked rotor amps
90.0
60.0
120.0
85.0
141.0
91.0
Condenser
Full load amps
1.0
1.0
1.0
1.0
1.7
1.7
Coil
L10-65-50
Locked rotor amps
1.9
1.9
1.9
1.9
2.9
2.9
Fan Motor
Recommended maximum fuse
1-1/8
28.5
HS21-653
or circuit breaker size (amps)
40
25
45
35
60
45
'Minimum circuit ampacity
23.0
16.9
28.0
20.8
40.2
26.6
•Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage.
FIELD WIRING
rDISCONNECTI
SWITCH
L IBy Others) J
LENNOX
CONDENSING
UNIT
r------ r --- E --i
I THERMOSTAT , I SWITCH
I
CT
(Optional) IBy Others)
L --..--J L-_.�_J
LENNOX
HEATING UNIT
OR
*SLOWER COIL
EVAPORATOR
UNIT
A - Two Wire Power (not furnished)
B - Two or Three Wire Power (not furnished) - See Electrical Data
C - Three Wire Low Voltage (not furnished) - 18 ga. minimum
D - Six Wire Low Voltage (not furnished) - 18 ga. minimum
All wiring must conform to NEC or CEC and local electrical codes.
REFRIGERANT
Length of
Liquid Line
Suction Line
Condensing
Line
Lines
Outside
Outside
Unit
Set
Diameter
Diameter .
Model No.
Model No.
ft. m
in,
mmF7/8
mm
L10-65-30
30 9
HS21-411
HS21-413
HS21-511
3/8
9.5
22.2
L10-65-40
40 12
HS21-513
L10-65-50
50 15
HS21-651
-Not available
3/8
9.5
1-1/8
28.5
HS21-653
*Field fabricate.
-5=
DIMENSIONS
INLET AIR
I
INLET
a
AIR
COMPRESSOR
' _ I
INLET AIR
' TOP VIEW
16
38 fib � � 3 865)
' DISCHARGE AIR
ELECTRICAL
[,FNN¢r INLETS
LIQUID
LINE o0
INLET �
A s
o-
SUCTION (64)
LININLET ?
,/I I -07. f / L
10.85 to 13.75 SEER
*22,000 to 60,000 Btuh (6.4 to 17.6 M Cooling Capacity
2 thru 5 Tons (7.0 thru 17.6 M
*DOE and ARI Certified Ratings
Application —The HS26 series condensing units feature extra high
efficiency with minimum operating sound levels. Units are applicable
to expansion valve systems only. Units may be installed at ground
level or on a roof. Units are adaptable to several blower powered and
add-on evaporators providing a wide range of cooling capacities for
selective sizing and application versatility. For evaporator unit data
see tab Coils — Blower Coil Units in this section. Units are shipped
completely factory assembled, piped and wired. In addition, each
unit is test operated at the factory insuring proper operation. Installer
has only to place condensing unit in desired location, connect refrig-
erant lines and make electrical connections to complete the job.
Approvals—Condensing units have been tested in the Lennox Research
Laboratory environmental test room and rated in accordance with ARI
Standard 210/240-94. In addition, units have been sound rated in
the Lennox reverberant sound test room in accordance with test
conditions included in ARI Standard 270-95. Condensing units and
components within are bonded for grounding to meet safety stan-
dards for servicing required by U.L. and C.E.C. Units are also U.L.
listed and C.S.A. certified.
Equipment Warranty—The compressor has a limited warranty for
'
f
en years in residential installations and 5 years in non-residential
nstallations. All other covered components have a limited warranty
or five years in residential installations and one year in non-residential
installations. Refer to Lennox Equipment Limited Warranty included
with the unit for details.
1
Copeland'- Compliant Scroll- Compressor—High efficiency compres-
sor features durability, steady uniform suction flow, constant discharge
flow, high volumetric efficiency, quiet operation and the ability to start
under any system load. Use of the scroll compressor eliminates the need
for crankcase heater, start capacitor and start relay. The compliant scroll
type compressor is a simple compression concept design consisting of
two involute spiral scrolls matched together to generate a series of
crescent-shaped gas pockets between them. During compression,
one scroll is stationary while the other
is allowed to orbit, not rotate, around
the fixed one. As this motion occurs,
gas is drawn into the outer pocket
J sealing off the open passage. As the
spiral movement continues, the
pockets between the scrolls are slowly
pushed to the center of the scrolls
while simultaneously being reduced
in volume. When the pocket reaches
the center, the gas is now at high
-' pressure and is forced out of a port
' located in the center of the fixed
scroll. During compression, several
pockets are being compressed simul-
taneously resulting in a smooth,
nearly continuous compression
., cycle. Continuous flank contact,
maintained by centrifugal force, mini-
mizes gas leakage and maximizes
efficiency. The scroll compressor is
tolerant to the effects of liquid slug-
ging and contaminants. Should this
occur, the scrolls separate and allow
the liquid or contaminants to be
worked to the center and discharged. Low gas pulses during com-
pression minimize operational sound level. Motor is internally pro-
tected from excessive current and temperature. Compressor is installed
in the unit on resilient rubber mounts, assuring vibration free operation.
(Continued)
U@ L
CE"WCATION•PPUES ONLY LISTED
wNEN TINE COMPLETE
SYSTEM IS LISTED
MTN MI
QMP
Typical Application
Bulletin #210020
April 1996
Supersedes
April 1995
O The maple leaf symbol in this bulletin denotes Canadian only usage where applicable s 1996 Lennox Industries Inc.
NOTE — Due to Lennox' ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without Incurring liability.
Unit Size &
Model No.
"Sound Rating
Number (db)
*ARI Standard 210/240 Ratings
Cooling Cap. Total
SEER EER Unit
Stuh kW Watts
Up Flow
Down -Flow
Evaporator Coils
Horizontal
""Ex ansion
Valpve Kit
Required
2 Ton
HS26-261
(76)
23,000
6.7
12.10
10.60
2180
C26-21(FC) - - - -
- - - -
*Factory Installed
23,400 6.9 11.85 10.60 2220 C23-260l(FC) - - - - . - - -
LB -85663J (26K34)
24,000 7.0 12.10 10.95 2190 C23-31(W)(FC) - - - - . - - •
24,400 7.1 12.30 11.05 2210 C23-41(W)(FC) - - - - • • - -
24,600 7.2 12.70 11.30 2185 C26-26(W)(FC) .... - .. -
*Factory Installed
26,000 7.6 13.00 11.75 2210 C26-31(W)(FC) - - - - . - . .
26,000 7.6 13.10 11.80 2205 C26-41(FC) - - - - . - - -
25,800 7.6 14.05 12.40 2080 C26-31(W)(FCl+G25MV3 - - • -•
26,000 7.6 14.00 13.30 1955 C26-31(W)(FC)+G21V3 ---- ----
24,000 7.0 12.50 11.30 2124 - - - - CR26-31 - - - -
LB -85663) (26K34)
24,400 7.1 13.00 11.40 2140 - - - - CR26-41(N)(W) - - - -
25,800 7.6 14.05 12.40 2080 - - • • CR26-31+G25MV3
22,000 6.4 11.30 10.30 2160 - - - - . • - - CH23-21
122,8001 6.7 1 11.50 10.55 2165 - - - - CH23-31
123,5001 6.9 1 12.00 10.85 2165 - - - - CH23-41
Stuh I kW SEER EER Watts Blower Coil Units
Valve
23,800 7.0 12.05 11.10 2145 CB29M-21/26 (Multi -Position)
*Factory Installed
24,000 7.0 12.05 11.20 2140 CB29M-31 (Multi -Position)
24,400 7.1 13.05 11.75 2075 CB30M-21/26 (Multi -Position)
26,000 7.6 13.25 12.45' 2090 CB30M-31 (Multi -Position)
24,000 7.0 12.00 10.85 2210 O CVP10-26/EC10Q3 I - - - -
2.5 Ton
HS26-311
(76)
Stuh
kW
SEER
EER
Watts
Evaporator Coils
Valve
29,600 8.7 12.05 11.40 2595 C23-26(W)(FC) ---- ----
LB -85663J (26K34)
30,200 8.8 12.65 11.20 2700 C26-26(W)(FC) - - - - - - - -
*Factory Installed
30,600 9.0 12.55 11.30 2705 C23-31(W)(FC) - - -
LB -85663) (26K34)
30,800 9.0 12.65 11.40 12705 C23-41(W)(FC) - - - - ----
---32,000
32,0001 9.4 1 13.00 11.75 2720 C26.31(W)(FC) - - • - - • - -
•Factory Installed
32,400 9.5 13.25 11.90 2720 C26-41(FC) • - - -
32,400 9.5 14.10 12.50 2590 C26-41(FC)+G25MV3 - - - - - - • -
32,600 9.6 14.00 12.80 2545 C26-41(FC)+G21 V3 - - - - ----
---29,000
---
29,000 8.5 12.10 11.00 12635 - - - - CR26-31 ----
LB -85663) (26K34)
30,600 9.0 12.50 11.20 2730 - - - - CR26.41(N)(W) - - - -
30,6001
31,600 9.3 13.00 11.40 2770 - - - - CR26-51(N)(W)
32,400 9.5 14.10 12.50 2590 - - - - CR26-41(N)(W)+G25MV3 - - - -
29,500 8.6 11.80 10.80 2735 - - - - . - - - CH23-31
30,000 8.8 12.00 11.00 2730 - • - - CH23-41
Btuh kW SEER EER Watts Blower Coil Units
Valve
28,600 8.4 .12.10 10.85 2634 C829M-21/26(Multi-Position)
*Factory Installed
30,600 9.0 12.55 11.50 2660 C829M-31 (Multi -Position)
30,600 9.0 12.65 11.60 2635 CB30M-21/26 (Multi -Position)
30,800 9.0 12.65 11.50 12675 CB29M-41 (Multi -Position)
32,200 9.4 13.25 12.50 2575 CB30M-31 (Multi -Position)
32,400 9.5 13.25 12.40 2615 CB30M-41 (Multi -Position)
32,400 9.5 14.00 13.05 2485 C831MV-41 (Mufti -Position)
30,200 8.8 1 12.15 10.75 2810 O CVP10-31/EC10Q3
30,8001 9.0 1 12.20 10.90 1 2820 O CVP10-41/EC10Q3
*Rated in accordance with ARI Standard 210/240;95 F (35-C) outdoor air temperature. 80 F (27`C) db / 67°F (19°C) wb entering evaporator air with 25 h. (7.6 m) of
connecting refrigerant lines.
*Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.
•• Kit is required and must be ordered extra, unless shown as factory installed.
•Furnished as standard with coil.
NOTE - Shaded area denotes most popular evaporator coil.
HS26 / Page 3 ►
ELECTRICAL DATA
Model No.
HS26-261
HS26-311
HS26-411
HS26-461
Line voltage data - 60hz
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
Compressor
Rated load amps
11.6
13.5
18.0
20.0
Power factor .96 .96 .96
.97
Locked rotor amps 62.5 76.0 90.5
107.0
Condenser Coil
Fan Motor
I Full load amps
1.1
1.1
1.1
1.1
Locked rotor amps 2.0 2.0 2.0
2.0
Rec. max. fuse or circuit breaker size lamps)
25
30
40
45
*Minimum circuit ampacity
15.6
18.0
23.6
26.1
Rater to National Or Canadian Electrical Code manual to determine Wife, fuse and disconnect size requirements.
NOTE - Extremes of operating range are plus 10%, and minus 5% of line voltage.
ELECTRICAL DATA
Model No.
HS26-511
HS26-513
Length of
Suct. &
Liq. Lines
HS26.651
HS26-653
ft, m
Line voltage data - 60hz
208/230v
1ph
208/230v
3ph
460v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
Compressor
Rated load amps
23.7
13.5
7.4
28.8
17.4
9.0
Power factor .97 .87 .87 .97 .85
.85
Locked rotor amps 129 99 49.5 169 123
62
Condenser Coil
Fan Motor
Full load amps
1.7
1.7
1.1
1.7
1.7
1.1
Locked rotor amps 3.1 3.1 2.2 3.1 3.1
2.2
Rec. max. fuse or circuit breaker size (amps)
50
30
15
60
40
20
*Minimum circuit ampacity
31:4
18.6
10.4
37.7
23.5
12.4
'Refer to National or Canadian Electrical Code manual to determine wire, fuse and disci nnect size requirements.
NOTE - Extremes of operating range are plus 10% and minus 5% of line voltage.
r15IS6014KNECT-1 r '1 rDISCONNECTI -
SWITCH THERMOSTAT SWITCH I
L IBy Others' J L -----J L IBy Others) J
LOB
A - Two Wire Power (not furnished)
B - Two or Three Wire Power 'not furnished) - See Electrical Data
C - Two Wire Low Voltage (not furnished) - 18 ga. minimum
D - Four Wire Low Voltage (not furnished) - 18 ga. minimum
LENNOX LENNOX All wiring must conform to NEC or CEC and local electrical codes.
CONDENSING HEATING UNIT
UNIT OR
*SLOWER COIL
EVAPORATOR
UNIT
REFRIGERANT
Condensing
Unit
Model No.
Line
Set
Model No.
Length of
Suct. &
Liq. Lines
Liquid
Line
(o.d.)
Suction
Line
(o.d.)
ft, m
in.
mm
in.
mm
HS26-261
HS26-311
HS26-411
L15-41-20
20 6.1
3/8
9.5
3/4
19
L15-41-30
30 9.1
L15-41-40
40 12.2
L15-41-50
50 15.2
HS26-461
Not available
3/8
9.5
1-1/8
28.6
HS26-510
L15-65-30 30 9.1
3/8
9.5
7/8
22.2
L15-65-40 40 1 12.2
L15-65-50 50 15.2
HS26-650
"Not available
3/8
9.5
1 1-1/8
22.2
-r eia faoncate.
' NOTE -48 inches (1219 mm) clearance required on top of unit.
'NOTE -Two sides of coil may be 12 inches (305 mm).
HS26! Page 6 �•
DIMENSIONS - inches (mm)
INLETQ�
I
v
A
B
HS26-211, HS26-261
a
30-7/9'-12-3/4
H 1 H -411
mm
784
324
COMPRESSOR
in.
40-7/8
20-3/4
mm
1038
527
i
Iu
Ali
34-7/8
14-3/4
95°F (35°C)
mm
INLET 4 AIR
ELECTRICAL TOP VIEW
INLETS
32-1/8(816) SUCTION LINE 34-1/16 (865)
INLET DISCHARGE * AIR
(HS26-211 thru 461
LIQUID
INLET LINE
(HS26-510-650)
4014) A 81/2. LIQUIDLINE INLET
HS26.211 thru 461SUCTIONLINE INLET
(HS26.510-650)
88_ 2-3/4(70) 4_18-5/8
4 (473) 4
1102) 1102)
12 11358 26.5/81676) 61546
ACCESS VIEW - SIDE VIEW
Model No.
A
B
HS26-211, HS26-261
in.
30-7/9'-12-3/4
H 1 H -411
mm
784
324
HS26-461
in.
40-7/8
20-3/4
mm
1038
527
HS26 511-513
in.
34-7/8
14-3/4
95°F (35°C)
mm
886
375
HS26-651-653
11 in.
11 mm
40-7/8
It 1038
20-3/4
527
INLET
a
AIR
NOTE- For Temperatures and Capacities not shown in tables, see bulletin -Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
welst-9Rl _ rec_I.1rcrt
NU 11: - An values are gross capacities ana ao not incluae evaporator con olower motor heat seduction.
Outdoor
Air
Temperature
Entering Condenser
Coil
Enter-
Total
85`F (29°C)
95°F (35°C)
105 -F(41 -C)
115°F (46°C)
Peet
Air
Volume
Total
Com-
Sensible
To Total
Total
Com-
Sensible
To Total
Total
Sensible
To
To Total
Total
Com-
Sensible
To Total
Bulb
Temper-
Cooling
Capacity
pressor
Ratio IS/T)
Cooling
Capacity
pressor
Ratio IS/TI
Cooling
Capacity
pressor
Ratio ISM
Cooling
Capacity
pressor
Ratio ISM
Motor
Dry Bulb
Motor
Dry Bulb
Motor
Dry Bulb
Motor
Dry Bulb
azure
Watts
Watts
Watts
Watts
Us
efrrt
kW
Btuh
Input
5°F 80'F 85°F
kW
Btuh
Input
75°F 80= 85`F
kW Btuh
Input
5`F 80' 85`F
kW
Btuh
Input
5`F 80-085-F
4°C 7 C
24 29.1:
4'C 27' 'C
4--C 27 'C
°F
330
700
6.7
22,700
1470
.69 .85 .96
6.4
21,900
1660
.70 .87 1.00
6.2 21,000
1860
.71 .89 1.00
5.9
20,200
2070
.72 .91 1.00
(172°C)
400
850
6.9
23,700
1470
.73 .90 1.00
6.7
22,900
7660
.74 .9T 1.00
6.4 22,000
1860
.76 .95 1.00
6.2
21,100
2070
.77 .97 1.00
470
1000
7.2
24,500
1470
.78 .95 1.00
6.9
23,600
1660
.79 .97 1.00
6.7 22,800
1860
.81 .99 1.00
6.4
21.700
2070
.83 1.00 1.00
330
700
7.0
23.800
1470
.55 .68 .82
6.7
23,000
1660
.55 .69 .83
6.5 22,200
1860
.56 .71 .85
6.2
21,300
2070
.56 .72 .87
67°F
(19.4°C)
400
850
7.3
24.900
1470
.57 .72 .88
7.0
24,000
1660
.58 .73 .90
6.8 23.100
-1870
.58 .75 .91
6.5
22,200
2070
.59 .77 .93
470
1000
7.5
25.700
1470
.59 .76 .94
7.3
24,800
1660
.60 .77 .96
7.0 23,800
1870
.61 .79 .98
6.7
22,900
2080
.62 .81 1.00
71°F
330
700
7.3
24,900
1470
.41 .55 .68
7.0
24,000
1660
.41 .55 .69
6.8 23.200
1860
.61 .56 .70
6.5
22,300
2070
.42 .57 .71
(21,7°C)
400
850
7.6
26.000
1470
.42 .57 .72
7.4
25,200
1660
.42 .58 .73
7.1 24,300
1870
.42 .59 .74
6.8
23,300
2080
.a3 .60 .75
870
1000
7.9
26,800
1480
.43 .59 .76
7.6
26,0001
1670
.43 .60 .77
7.4 7510n
1870
.a3 .61 .79
7.0
24 000
2080
.aa .62 .80
NU 11: - An values are gross capacities ana ao not incluae evaporator con olower motor heat seduction.
t
THERMOSTATS
Bulletin #480059
September 1993
Supersedes April 1992
PROGRAMMABLE THERMOSTATS A
L21 SERIES THERMOSTATS
For Conventional Heating/Cooling Systems Only
(Non -Heat Pump Systems)
L21 Series 24 Hour Thermostats features automatic or manual
changeover, built-in time delays, large easy -to -read LCD readout
with actual time and temperature in IF or IC for alternating inside
and outside temperature readout (with optional outdoor temper-
ature sensor). Two stage cooling model features low or high
speed cooling operation indicators. Check filter indicator flashes
at preset interval. Thermostat features system selector switch
(Off -Heat -Cool -Auto) and fan switch (On -Auto) for continuous or
intermittent blower operation. Indicator lights ("Amber" light in-
dicates system operating. "Green" light indicates night period
' energy savings). Solid-state electronic technology eliminates bat-
tery back-up and maintains thermostat settings during power fail-
ure for up to 24 hours. Thermostat has two separate (Day & Night)
time and temperature settings per day. Individual slide switches
are used to set day and night heat and cool temperatures and
nighttime beginning and ending time periods. "Cancel Night"
button overrides night temperature settings. "+" and "-" buttons
set time of day. Pressing front cover reviews thermostat settings.
Optional Outdoor Temperature Sensor is also available and must
be ordered extra. With optional sensor, thermostat will give a read-
out of present outdoor temperature and the lowest and highest
outdoor temperatures of the day and times at which they occurred.
INOTE — Specifications, Ratings and Dimensions subject to change without notice.
L21 Series 7 -Day Thermostats feature full independent seven ;day
programming, automatic or manual changeover, built-in time de-
lays, large easy -to -read LCD readout with actual time and temper-
ature in IF or °C for alternating, inside and outside temperature
readout (with optional outdoor temperature sensor). Two stage
cooling model features low or high speed cooling operation indi-
cators. Check filter indicator flashes at preset interval. Thermostat
features system selector switch (Off -Heat -Cool -Auto) and fan
switch (On -Auto) forcontinuous or intermittent blower operation.
Indicator lights show "Amber" indicating system is operating in
manual mode or (flashing) 3 hour override. "Green" light indi-
cates system demand. Solid-state electronic technology elimi-
nates battery back-up and maintains thermostat settings during
power failure for up to 24 hours. Thermostat has four separate
time and temperature settings per day. Individual slide switches
are used to set time begin and heat and cool temperatures. "+"
and "-" buttons set time of day. "Day" button sets day of week
and reviews daily programs. "Review" button displays pro-
grammed time period setpoints. "Manual" button allows manual
control of temperature. "Clear" button erases programmed set -
points when re -programming. "Enter:" button enters time of day
and temperature setpoints into memory. Monitoring of compres-
sor run times and heating times in hours and cycles is also avail-
able. Pressing front cover reviews thermostat settings.
Optional Outdoor Temperature Sensor is also available and must
be ordered extra. With optional sensor, thermostat will give a read-'
out of present outdoor temperature and the lowest and highest
outdoor temperatures of the day and times at which they occurred.
1993 Lennox Industries Inc.
.41
Model No.
Description Catalog No.
Model No. Description Catalog No.
-
L211201CS
......... 1 HeaVlCool 24 Hour ........ 69H25
L211407CS .......... 1 Heat/1Cool 7 -Day ......... 75H19
'
i L212201CS
.... :.... 1 Heat/2 Cool 24 Hour ........ 691-126
L212407CS .......... 1 Heat/2 Cool 7 -Day ......... 75H2O
-
A2000 -ROS
..... Outdoor Temperature Sensor .... 69H27
A2000 -ROS ..... Outdoor Temperature Sensor .... 69H27
L21 Series 24 Hour Thermostats features automatic or manual
changeover, built-in time delays, large easy -to -read LCD readout
with actual time and temperature in IF or IC for alternating inside
and outside temperature readout (with optional outdoor temper-
ature sensor). Two stage cooling model features low or high
speed cooling operation indicators. Check filter indicator flashes
at preset interval. Thermostat features system selector switch
(Off -Heat -Cool -Auto) and fan switch (On -Auto) for continuous or
intermittent blower operation. Indicator lights ("Amber" light in-
dicates system operating. "Green" light indicates night period
' energy savings). Solid-state electronic technology eliminates bat-
tery back-up and maintains thermostat settings during power fail-
ure for up to 24 hours. Thermostat has two separate (Day & Night)
time and temperature settings per day. Individual slide switches
are used to set day and night heat and cool temperatures and
nighttime beginning and ending time periods. "Cancel Night"
button overrides night temperature settings. "+" and "-" buttons
set time of day. Pressing front cover reviews thermostat settings.
Optional Outdoor Temperature Sensor is also available and must
be ordered extra. With optional sensor, thermostat will give a read-
out of present outdoor temperature and the lowest and highest
outdoor temperatures of the day and times at which they occurred.
INOTE — Specifications, Ratings and Dimensions subject to change without notice.
L21 Series 7 -Day Thermostats feature full independent seven ;day
programming, automatic or manual changeover, built-in time de-
lays, large easy -to -read LCD readout with actual time and temper-
ature in IF or °C for alternating, inside and outside temperature
readout (with optional outdoor temperature sensor). Two stage
cooling model features low or high speed cooling operation indi-
cators. Check filter indicator flashes at preset interval. Thermostat
features system selector switch (Off -Heat -Cool -Auto) and fan
switch (On -Auto) forcontinuous or intermittent blower operation.
Indicator lights show "Amber" indicating system is operating in
manual mode or (flashing) 3 hour override. "Green" light indi-
cates system demand. Solid-state electronic technology elimi-
nates battery back-up and maintains thermostat settings during
power failure for up to 24 hours. Thermostat has four separate
time and temperature settings per day. Individual slide switches
are used to set time begin and heat and cool temperatures. "+"
and "-" buttons set time of day. "Day" button sets day of week
and reviews daily programs. "Review" button displays pro-
grammed time period setpoints. "Manual" button allows manual
control of temperature. "Clear" button erases programmed set -
points when re -programming. "Enter:" button enters time of day
and temperature setpoints into memory. Monitoring of compres-
sor run times and heating times in hours and cycles is also avail-
able. Pressing front cover reviews thermostat settings.
Optional Outdoor Temperature Sensor is also available and must
be ordered extra. With optional sensor, thermostat will give a read-'
out of present outdoor temperature and the lowest and highest
outdoor temperatures of the day and times at which they occurred.
1993 Lennox Industries Inc.
ITHE OPTIONS LISTED ARE ONLY A SAMPLE. THE ENTIRE MATRIX IS AVAILABLE BY REQUEST.
PRODUCT DESCRIPTION
ALUMINUM FIXED DOOR SYSTEM
PRODUCT NAME
NOR WOOD SERIES 3000.
NFRC RESIDENTIAL VALUES
69 CLR/AIR
- . 59 LO W E/AIR - . Sl HM#66/AIR
(SEE BELOW FOR COMMON GLAZING OPTIONS)
SPECIAL PRODUCT FEATURES
I" GLAZING
CUSTOM COLORS
LARGE SIZES'.
COMPLIMENTS SLIDER
GLAZING OPTIONSI
LL
1=10R SPACER SPACE
EXTERIOR . AA RESULT SPECIAL NOTES
I
DS 764 AIR
DS .55
2
DS LOW E .764 AIR
DS .20 LOW E
1
3
DS .382 AIR
DS ,34 HEAT MIRROR #66
q.
1/4" .SO AIR
1/4" LOW E ,28 .20 LOW E/HM#66
g.
1/4" .SO ARGON
1/4" LOW E .25 .10 LOW E/HM#66
CONSULTANT NOTES
ITHE OPTIONS LISTED ARE ONLY A SAMPLE. THE ENTIRE MATRIX IS AVAILABLE BY REQUEST.
PRODUCT DESCRIPTION
ALUMINUM SINGLE HUNG WINDOW
PRODUCT NAME
WESTWOOD SERIES 250SH
NFRC RESIDENTIAL VALUES
. 69 LOW E/AIR e .66 LOW EI ARGON-
(SEE BELOW FOR COMMON GLAZING OPTIONS)
SPECIAL PRODUCT FEATURES
5/8" INSULATED GLASS CUSTOM COLORS
2 114" FRAME MANUAL OR SELF LATCHING
EXCELLENT WATER TEST EASY PANEL REMOVAL
GLAZING OPTIONS'
L4P- INTERIOR SPACER SPACE EXTERIOR AA RESULT SPECIAL NOTES
I DS .389 AIR DS 79
2. DS LOW E .389 AIR DS .69 .20 LOW E
3. DS LOW E .389 ARGON DS .66 .20 LOW E
4.. DS LOW E '.389 AIR DS .70 DIVIDERS
5. DS LOW E .389 ARGON DS .67 DIVIDERS
CONSULTANT NOTES
'THE OPTIONS LISTED ARE ONLY A SAMPLE. THE ENTIRE MATRIX IS AVAILABLE BY
REQUEST.-
PRODUCT DESCRIPTION
ALUMINUM SLIDING GLASS DOOR
PRODUCT NAME
NOR WOOD SERIES 3000
NFRC RESIDENTIAL VALUES
.75 CLR/AIR - .65 LOW E/AIR - .52 HM#66/ARGON
(SEE BELOW FOR COMMON GLAZING OPTIONS)
SPECIAL PRODUCT FEATURES
I" INSULATED GLASS CUSTOM COLOR
STAINLESS TRACK INSERT HIGH SECURITY HOOK LATCH
AVAILABLE 12' TALL DELUXE SCREEN
GLAZING OPTIONS'
INTERIOR
SPACER
SPACE
EXTERIOR
AA RESULT
SPECIAL NOTES
1/4"
.500
AIR
1/4"
.75
.20 LOW E
1/4" LOW E
.500
AIR
1/4"
.65
.20 LOW E
3/16" LOW E
.312
ARGON
3/16"
,52
HEAT MIRROR #66
1%4" LOW E
.281
ARGON
3/16"
,53
.10 LOW E/HM#66
1i4"
.250
AIR
1/4"
.61
HEAT MIRROR #66
CONSULTANT NOTES
'THE OPTIONS LISTED ARE ONLY A SAMPLE. THE ENTIRE MATRIX IS AVAILABLE BY
REQUEST.
INS^TALLATION CERTIFICATE -----------
CF_6R--page-42 -of -42
Project Name: Gardner Residence ;Date: 12/12/1997
Documentation: BREEZE AIR CONDITIONING -_-;COMPLY 24 User 3665
-----------------------------------------------------------------
I, the undersigned, verify that the equipment listed in the category above
my signature is the actual equipment installed and that the equipment
meets or exceeds the requirements of the Appliance Efficiency Standards.
in addition, I have verified that the equipment is equivalent to or more
efficient than the equipment specified on the Certificate of Compliance
submitted to demonstrate compliance with the Energy Efficiency Standards
for Residential Buildings.
HVAC SYSTEMS
Cooi. Equip CEC Certified Manuf.
system Type Make & Model Number
----------- -----------------------
SpltAirCond Lennox H521-411
SpltAirCond Lennox H521-511
SpltAirCond Lennox HS21-651
SpltAirCond LENNOX HS26-311-1P
Actual Distrib hype
Eff. and Location
----- --------------
0.800 Ducts in Attic
0.800 Ducts in Attic
0.800 Ducts in Attic
0.800 Ducts in Attic
Duct Heat Heat
RVal Load Output
---- ------ ------
4.2 .15626 61200
4.2 25000 82000
4.2 29136 82000
4.2 15476 49000
Actual Distrib Type
Efficiency and Location
-----------------------------
15.750 SEER Ducts in Attic
14.000 SEER Ducts in Attic
14.000 SEER Ducts in Attic
13.000 SEER Ducts in Attic
Duct
RVal
4.2
4.2
4.2
4.2
Signature Date Name
Water No. bank Ext.
WATER HEATING SYSTEMS Heater in Energy Size Insul
CEC Cert. Make & Model Distribution hype hype Sys Factor (gal) R -Val
American G52 -501'383N Recirc-lime&Temp StorGas 2 0.60 50.0 12.0
American G52 -30733-3N Recirc-'Time&'Temp StorGas 1 0.61 30.0 12.0
AFUE
WATER HEATER EQUIPMENT DETAIL /Rec Rated Stdby Tank Pilot
System Name System Type Eff Input Loss R -Val Light
----------------------- ----------- ---- ----- ----- ----- -----
American G52 -50'1'383N DomesticHW 0.780 38000 0.003 16.0 U
American G52 -30T33 -3N DomesticHW 0.780 33000 0.003 16.0 U
' F AUCE 1' S & SHOWER HEADS:
All faucets and showerheads are listed in the Commissions Directory Of
Certified Faucets And showerheads, pursuant to Title 24, Part 6,
Subchapter 2, Section 111.
Signature
Date Name
Heat. Equip
CEC Certified Manuf.
System Type
Make &
Model Number
-----------
Furnace
-----------------------
Lennox
SOMGF4-75
Furnace
Lennox
80MGF4/5-100
Furnace
Lennox
80MGF4/5-100
Furnace
LENNOX
BUMGF3-60A-*
Cooi. Equip CEC Certified Manuf.
system Type Make & Model Number
----------- -----------------------
SpltAirCond Lennox H521-411
SpltAirCond Lennox H521-511
SpltAirCond Lennox HS21-651
SpltAirCond LENNOX HS26-311-1P
Actual Distrib hype
Eff. and Location
----- --------------
0.800 Ducts in Attic
0.800 Ducts in Attic
0.800 Ducts in Attic
0.800 Ducts in Attic
Duct Heat Heat
RVal Load Output
---- ------ ------
4.2 .15626 61200
4.2 25000 82000
4.2 29136 82000
4.2 15476 49000
Actual Distrib Type
Efficiency and Location
-----------------------------
15.750 SEER Ducts in Attic
14.000 SEER Ducts in Attic
14.000 SEER Ducts in Attic
13.000 SEER Ducts in Attic
Duct
RVal
4.2
4.2
4.2
4.2
Signature Date Name
Water No. bank Ext.
WATER HEATING SYSTEMS Heater in Energy Size Insul
CEC Cert. Make & Model Distribution hype hype Sys Factor (gal) R -Val
American G52 -501'383N Recirc-lime&Temp StorGas 2 0.60 50.0 12.0
American G52 -30733-3N Recirc-'Time&'Temp StorGas 1 0.61 30.0 12.0
AFUE
WATER HEATER EQUIPMENT DETAIL /Rec Rated Stdby Tank Pilot
System Name System Type Eff Input Loss R -Val Light
----------------------- ----------- ---- ----- ----- ----- -----
American G52 -50'1'383N DomesticHW 0.780 38000 0.003 16.0 U
American G52 -30T33 -3N DomesticHW 0.780 33000 0.003 16.0 U
' F AUCE 1' S & SHOWER HEADS:
All faucets and showerheads are listed in the Commissions Directory Of
Certified Faucets And showerheads, pursuant to Title 24, Part 6,
Subchapter 2, Section 111.
Signature
Date Name