BCOM2016-0031 Title 24r�
BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Washington Park - Ulta Beauty
78-825 Highway 111
La Quinta, CA 92253
Project Designer:
LR/Architecture
213 W. Alameda Ave, Suite 203
Burbank, Ca 91502
(818)840-8361
Report Prepared by:
Joshua Enriquez, PE, LEED AP
665 Fairmont Ave # 11
Glendale, Ca 91203
213-820-3683
CITY 0 LA'QUINTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CONSTRUCTION
� ► U.1bCFEW
DATE,�_,BY
Job Number:
�tt�tio lb • 0031 AUG 2 3 2016 -
1016
CITY OF LA QUINTA
Date: COMMUNITY DEVELOPMENT
8/17/2016
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed. by EnergySoft, LLC—www.energysoft.com.
EnergyPro6byEnergySoft User Number: 1064 ID: 1016
t
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 1 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
A. PROJECT GENERAL INFORMATION
1.
Project Location (city)
La Quinta
8.
Standards Version
Compliance2015
2.
CA Zip Code
92253
9.
Compliance Software (version)
EnergyPro 6.8
3.
Climate Zone
15
10.
Building Orientation (deg)
(N) 0 deg
4.
Total Conditioned Floor Area in Scope
12,626 ftZ
11.
Permitted Scope of Work
ExistingAlteration
S.
Total Unconditioned Floor Area
Oft'
12.
BuildingType(s)
Nonresidential
6.
Total # of Stories (Habitable Above Grade)
1
13
Gas Type
NaturalGas
7.
Total # of dwelling units
0
B. COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS (Annual TDV Energy Use, kBtu/ft 2-yr) § 140.1
BUILDING COMPLIES
1. Energy Component
2. Standard Design (TDV)
3. Proposed Design (TDV)
4. Compliance Margin (TDV)
S. Percent Better than Standard
Space Heating
9.6
6.6
3.0
31.3%
Space Cooling
.350.4
179.5
170.9
48.8%
Indoor Fans
90.2
81.9
8.3
9.2%
Heat Rejection
-
_
--
--
Pumps & Misc. -
0.4
--
0.4
-
Domestic Hot Water
9.0
9.0
--
0.0%
Indoor Lighting
103.9
103.9
-
0.0%
COMPLIANCE TOTAL
563.5
380.9
182.6
32.4%
Receptacle
91.3
91.3
0.0
0.0%
Process
91.3
91.3
0.0
0.0%
Other Ltg
--
--
-
--
TOTAL
746.1
563.5
182.6
24.S%
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 2 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/rime:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
C. PRIORITY PLAN CHECK/ INSPECTION ITEMS (in order of highest to lowest TDV energy savings(
1st
Space Cooling: Check envelope and mechanical
Compliance Margin By Energy
Component
/from Table B column 4)
2nd
Indoor Fans: Check envelope and mechanical
Space Cooling
Indoor Fans
Space Heating
Pumps & Misc.
Heat Rejection
Domestic Hot Water
Indoor Lighting
Penally
3rd
Space Heating: Check envelope and mechanical
no C It
4th
Pumps & Misc.: Check mechanical
5th
Heat Rejection: Check envelope and mechanical
6th
Domestic Hot Water: Check mechanical
7th
Indoor Lighting: Check lighting
D. EXCEPTIONAL CONDITIONS
The building does not include service water heating. Verify that service water heating is not required and is not included in the design.
The proposed building includes HVAC components that do not meet the mandatory efficiency requirements.
E. HERS VERIFICATION
This Section Does Not Apply
F. ADDITIONAL REMARKS
None
Provided
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 3 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016 _
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
Identify which building components use the performance or prescriptive path for compliance. NAu= not in project
For components that utilize the performance path, indicate the sheet number that includes mandatory notes on plans.
Building Component
Compliance Path
Compliance Forms (required forsubmittal)
Location of Mandatory Notes on
Plans
Envelope
®
Performance
NRCC-PRF-ENV-DETAILS (section of the NRCC-PRF-01-E)
❑
Prescriptive
NRCC-ENV-01 / 02 / 03 / 04 / 05 / 06-E
❑
NA
Mechanical
®
Performance
NRCC-PRF-MCH-DETAILS (section of the NRCC-PRF-01-E)
❑
Prescriptive
NRCC-MCH-01 / 02 / 03 / 04 / 05 / 06 / 07-E
❑
NA
Domestic Hot Water
❑
Performance
NRCC-PRF-PLB-DETAILS (section of the NRCC-PRF-01-E)
'
❑
Prescriptive
NRCC-PLB-01-E
®
NA
Lighting (Indoor Conditioned)
❑
1Performance
Performance
NRCC-PRF-LTI-DETAILS (section of the NRCC-PRF-OS-E)
❑
Prescriptive
NRCC-LTI-01 / 02 / 03 / 04 / 05-E
®
NA
Covered Process:
Commercial Kitchens
❑
52 (section of the NRCC-PRF-01-E)
❑
Prescriptive
NRCC-PRC-01/ 03-E
®
NA
Covered Process: ,
Computer Rooms
❑
Performance
S3 (section of the NRCC-PRF-01-E)
❑
Prescriptive
NRCC-PRC-01/ 04-E
®
NA
Covered Process:
Laboratory Exhaust
❑
Performance
S4 (section of the NRCC-PRF-01-E)
❑
Prescriptive
NRCC-PRC-01/ 09-E
®
NA
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance
Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 4 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
G. COMPLIANCE PATH & CERTIFICATE OF COMPLIANCE SUMMARY
The following building components are only eligible for prescriptive compliance. Indicate which are
The following building components may have mandatory requirements per Part 6. Indicate
relevant tc the project.
which are relevant to the project.
Yes NA
Prescriptive Requirement
Compliance Forms
Yes NA
Mandatory Requirement
Compliance Forms
❑ ®
Lighting (Indoor
Commissioning: §120.8
Uncoriditioned) §140.6 ".
NRCC-LTI-01 / 02 / 03 / 04 / 05-E
❑ ®
Simple Systems
NRCC-CXR-01 / 02 / 03 / 05-E
❑ ®
Complex Systems
NRCC-CXR-01 / 02 / 04 / 05-E
❑ ®
Lighting (Outdoor) §140.-
NRCC-LTO-01 / 02 / 03,E
❑ ®
Electrical: §130.5
NRCC-ELC-01-E
❑ ®
Lighting (Sign) §140.8
NRCC-LTS-01-E
❑ ®
Solar Ready: §110.10
NRCC-SRA-01 / 02-E
Covered Process: §120.6
NRCC-PRC-01-E
❑ ®
Parking Garage
NRCC-PRC-02-E
❑ ®
Solar Thermal Water
NRCC-STH-Ol-E
❑ ®
Commercial Refrigeration
NRCC-PRC-05-E
Heating:.§140.5
❑ ®
Warehouse Refrigeration
NRCC-PRC-06/07/08-E
❑ ®
Compressed Air
NRCC-PRC-10-E
❑ ®
Process Boilers
NRCC-PRC-11-E
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 5 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/rime:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCl/NRCA/NRCV) —
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component
Compliance Forms frequired forsubmittaQ
Pass
Fall
Envelope
® NRCI-ENV-01-E- For all buildings
❑
❑
® NRCA-ENV-02-F- NFRC label verification for fenestration
❑
❑
•
Mechanical -
-
® NRCI-MCH-01-E - For all buildings with Mechanical Systems
❑
❑
® NRCA-MCH-02-A-Outdoor Air -
❑
❑
® NRCA-MCH-03-A—Constant Volume Single Zone HVAC -
❑
❑
❑ NRCA-MCH-04-H- Air Distribution Duct Leakage
❑
❑
® NRCA-MCH-05-A- Air Economizer Controls -
❑ -
❑
® NRCA-MCH-06-A- Demand Control Ventilation
❑
❑
® NRCA-MCH-07-A—Supply Fan Variable Flow Controls
❑
❑
❑ NRCA-MCH-08-A- Valve Leakage Test
❑
❑
❑ NRCA-MCH-09-A— Supply Water Temp Reset Controls
❑
❑
❑ NRCA-MCH-10-A- Hydronic System Variable Flow Controls
❑
❑
❑ NRCA-MCH-11-A—Auto Demand Shed Controls
❑
❑
® NRCA-MCH-12-A- Packaged Direct Expansion Units
❑
❑'
❑ NRCA-MCH-13-A-Air Handling Units and Zone Terminal Units
❑
-❑ .
❑ NRCA-MCH-14-A- Distributed Energy Storage
❑
❑
❑ NRCA-MCH-15-A—Thermal Energy Storage
❑
❑
❑ NRCA-MCH-16-A- Supply Air Temp Reset Controls
❑
❑
❑ NRCA-MCH-17-A— Condensate Water Temp Reset Controls
❑
❑
❑ NRCA-MCH-18-A- Energy Management Controls Systems
❑
❑
❑ NRCV-MCH-04-H- Duct Leakage Test
❑
❑
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-081220i6-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 6 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCl/NRCA/NRCV) —
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component
Compliance Forms (required/orsubmittal)
Pass
Fail
Plumbing
❑ NRCI-PLB-01-E - For all buildings with Plumbing Systems
❑
❑
❑ NRCI-PLB-02-E - required on central systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCI-PLB-03-E - Single dwelling unit systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCI-PLB-21-E - HERS verified central systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCI-PLB-22-E - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCV-PLB-21-H- HERS verified central systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCV-PLB-22-H - HERS verified single dwelling unit systems in high-rise residential, hotel/motel application.
❑
❑
❑ NRCI-STH-01-E - Any solar water heating
_❑
❑
Indoor Lighting
❑ NRCI-LTI-01-E - For all buildings
❑
❑
❑ NRCI-LTI-02-E - Lighting control system, or for an Energy Management Control System (EMCS)
❑
❑
❑ NRCI-LTI-03-E - Line -voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to
energize only line -voltage track lighting
❑
❑
❑ NRCI-LTI-04-E - Two interlocked systems serving an auditorium, a corwention center a conference room, or a theater
❑
❑
❑ NRCI-LTI-OS-E -Lighting Control Credit Power Adjustment Factor (PAF)
❑
❑
❑ NRCI-LTI-06-E - Additional wattage installed in a video conferencing studio
❑
❑
❑ NRCA-LTI-02-A - Occupancy sensors and automatic time switch controls.
❑
❑
❑ NRCA-LTI-03-A- Automatic daylighting controls
❑
❑
❑ NRCA-LTI.04-A - Demand responsive lighting controls
❑
❑
Outdoor Lighting
❑ NRCI-LTO-01-E—Outdoor Lighting
❑
❑
❑ NRCI-LTO-02-E- EMCS Lighting Control System
❑
❑
❑ NRCA-LTO-02-A - Outdoor Lighting Control
❑
❑
Sign Lighting
❑ NRCI-LTS-01-E—Sign Lighting
❑
❑
Electrical
❑ NRCI-ELC-01-E - Electrical Power Distribution
❑
❑
Photovoltaic
❑ NRCI-SPV-01-E Photovoltaic Systems
❑
❑
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01•E
Page 7 of 18 -
Project Address:
78-825 Highway 111 La Quinta 92253 -
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
H. CERTIFICATE OF INSTALLATION, CERTIFICATE OF ACCEPTANCE & CERTIFICATE OF VERIFICATION SUMMARY (NRCl/NRCA/NRCV) —
Documentation Author to indicate which Certificates must be submitted for the features to be recognized for compliance
(Retain copies and verify forms are completed and signed to post in field for Field Inspector to verify).
See Tables G. and H. in MCH and LTI Details Sections for Acceptance Tests and forms by equipment.
Confirmed
Building Component
Compliance Forms (required forsubmittal)
Pass
Fail
Covered Process
❑ NRCI-PRC-01-E Refrigerated Warehouse.
❑
❑
❑ NRCA-PRCDI-F- Compressed Air Systems
❑
❑
❑ NRCA-PRC-024- Kitchen Exhaust
❑
❑
❑ NRCA-PRC-03-F-Garage Exhaust
❑
❑
❑ NRCA-PRC-04-F- Refrigerated Warehouse- Evaporator Fan Motor Controls
❑
❑
❑ NRCA-PRC-05-F- Refrigerated Warehouse- Evaporative Condenser Controls
❑
❑
❑ NRCA-PRC-C6-F- Refrigerated Warehouse- Air Cooled Condenser Controls
❑
❑
❑ NRCA-PRC-07F- Refrigerated Warehouse- Variable Speed Compressor
❑
❑
❑ NRCA-PRC-08-F- Electrical Resistance Underslab Heating System
❑
❑
I. ENVELOPE GENERAL INFORMATION (See NRCC-PRF-ENV-DETAILS for more information)
1.
Total Conditioned Floor Area
12,626 ft2
S.
Number of Floors Above Grade
1
Confirmed
2.
Total Unconditioned Floor Area
0 ft2
6.
Number of Floors Below Grade
0
3.
Addition Conditioned Floor Area
0 ft2
4.
Addition Unconditioned Floor Area
0 ft2
7. Opaque Surfaces & Orientation
8. Total Gross Surface Area
9. Total Fenestration Area
10. Window to Wall Ratio
North Wall
1,132 ft2
560 ft2
49.5%
❑
❑
East Wall
Oft,
0 ft2
00.0%
❑
❑
South Wall
1,496 ft2
0 ft2
00.0%
❑
❑
West Wall
4,079 ft2
0 ft2
00.0%
❑
❑
Total
6,707 W
S60 ft2
08.3%
❑
❑
Roof -
12,626 ft2
Oft,
00.0%
❑
❑
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
N RCC-PRF-01-E
Page 8 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
C: Iculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration .
Irput File Name:
1016-ULTA.cibdx
J. FENESTRATION ASSEMBLY SUMMARY .
§ 110.6
Confirmed
1.
2.
3.
4.
5.
6.
7.
B.
9.
Fenestration Assembly Name /
Tag or I.D.
Fenestration Type
Certification Methodl
Assembly Method
Area ft1 �
Overall
U-factor
Overall
SHGC
Overall
VT
IS
N
Storefront Glazing
Vertical Fenestration
DefaultPerformance
SiteBuilt
560
0.71
0.73
0.88
N
❑
❑
every mnaneoTenesvanan snaunave a cert0leo 1- tanel -ropoale or use me ctC derault tables found In Table 110.E-A and Table 1. 0.6-a. Center of Glass (COG) values ore for the glass -only, determined by the manufacturer, and are shown for rose
of-ifimbon. Site -built fineslrodon values are mlrulated per Nonresidmdal Appendix NA6 and are used in the anoWs.
1 Slatw, N. New, A -Altered, E-Existing
Taking compliance credit for fenestration shading devices? (if "Yes", see NRCC-PRF-ENV-DETAILS for more information) No
K. OPAQUE SURFACE ASSEMBLY SUMMARY
§ 120.7/ § 140.3
Confirmed
1.
2.
3.
4.
5.
6.
7.
8.
Surface Name
Surface Type
Area (ftz -
Framing
Type
Cavity
R-Value
Continuous
R-Value
U-Factor/F-Factor
/ C-Factor
;,
N
8 CMU Wa117
ExteriorWall
5575
NA
0
NA
U-Factor: 0.366
E
❑
❑
R-20 Metal Deck Roof9
Roof
12626
NA
0
NA
U-Factor: 0.490
E
❑
❑
R-15 Wall Metal Studll
- ExteriorWall
1132
NA
0
NA
U-Factor: 0.418
A
1 01,0
R-13 Wall Metal Stud15
InteriorWall
0
NA
0
NA
U-Factor: 0.345
A
❑
❑
Slab On Grdde17
Underground Floor
12626
NA
0 -
NA
F-Factor: 0.730
E
❑
I ❑
ssatus. w w--erea, t - txls0ng
L. ROOFING PRODUCT SUMMARY I § 140.3
Confirmed
1.
2.
3.
4.
S.
6.
7.
Product Type
Product Density
Aged Solar
Thermal
SRI
Cool Roof
Roofing Product
(lb/ft)
Reflectance
Emittance
Credit
Description
R-20 Metal Deck Roof9
50.06
0.08
0.75
NA
No
NA
❑
❑
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance
Report Ver-'ion: NRCC-PRF-01-E-08122016-3995, Report Generated at: 2016-09-17 22:36:18
i
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 9 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
M. HVAC SYSTEM SUMMARY (see NRCC-PRF-MCH-DETAILS for more information) § 110.1 / § 110.2
Dry System Equipment I (Fan & Economizer info included below in Table N)
Confirmed
1.
2.
3.
4.
S.
6:_
7.
8.
9.
10.
11.
System Type
3
Total Heating
Supp Heat
Supp Heat
Total Coolingto
Efficiency
Acceptance
Testing
V
v
Equip Name
q p
E ul T e
q p yp
(Simple or
Qty
Output
Source (Y/N)
output
Output
Required? (Y/N)
Complex 4)
(kBtu/h)
(kBtuh)
(kBtu/h)
Cooling
Heating
6
RTU 1thru 4
SZVAVAC
(Packaged3Phase)
Complex
4
104
No
0
113
EER-13.8
AFUE-80.0
Yes.
N
❑
❑
Wet System Equipment
Pumps
Confirmed
12.
13.
14.
1S.'
16.
27.
18.
19.
20.
21.
22.
23.
24.
Equip Name
Equip Type
City
Vol (gal)
Rated Capacity
Efficiency
Standby Loss
Tank
Ext. R
City
GPM
HP
VSD
-
N
w
(kBtu/h)
Value
(/N)
c
Non Res BaseWaterHeater
Storage
1
19
20
EF:0.646
NA
NA
NA
NA
NA
No
N
❑
❑
,..y..»,e,n c,tu,r.,ncn. mauvesrurna nnana mguru., earpump; etc.
21, System Equipment includes boilers, chillers, cooling towers, water heaters, etc. -
3 Simple Systems must complete NRCC-CXR-03-E commissioning design review form
4 Complex systems must complete NRCC-CXR-04-E commissioning design review form
S A summary of which acceptance tests one applicable is provided in NRCC-PRr-MCH-DETAILS
6 Status: N-New, A -Altered, E-Existing
Discrepancy between modeled and designed equipment sizing? (if "Yes", see Table F. "Additional Remarks" for an explanation) No
N. ECONOMIZER & FAN SYSTEMS SUMMARY'
§ 140.4
Confirmed
1.
2.
3.
4.
5.
Outside
AU
Supply Fan
Return Fan
v
ti
Equip Name
q P
Economizer Type
d
TSP
TSP
CFM
CFM
HP
BHP
(inch-
Control
CFM
HP
BHP
(inch
Control
(if present)
WC)
WC)
rRTU 1 thru 4
J89
4000
3.000
3.000
2.86
Variable5peedDrive
NA
NA
NA
NA
NA
DifferentialEnthalp
❑
Y
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance
Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
r
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 10 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
O. EQUIPMENT CONTROLS I § 120.2
Confirmed
1.
2.
3.
v
N
-
Equip Name
Equip Type
Controls
1 Zones With CO2Sensor Vent. Control
RTU 1 thru 4 -
SZVAVAC
Differential Enthalpy Economizer
Q
❑
No Supply Air Temp. Control
No Optimum Start
NonResBaseSHWSystem
Service Hot Water, Primary Only
Fixed Temperature Control, No DDC
❑
❑
P. SYSTEM DISTRIBUTION SUMMARY § 120.4/ § 140.4(I)
Dry System Distribution
Confirmed
2.
3.
4.
5.
d
N
d
Equip Name
- Equip Type
Duct Leakage and Sealing
Required per 140.4(1)
Duct Leakage will be
verified NA2 Aland
Ducts
Insulation R-Value
Location
RTU 1 thru 4
SZVAVAC
No
No
8
Conditioned
❑
❑
Does the Project Include Zonal Systems? (if "Yes", see NRCC-PRF-MCH-DETAILS for system Information)
No
Does the Project Include a Solar Hot Water System? (if "Yes", see NRCC-PRF-MCH-DETAILS for system Information)
No
Multifamily or Hotel/ Motel Occupancy? (If "Yes", see NRCC-PRF-MCH-DETAILS for DHW system Information)
No
Q. INDOOR CONDITIONED LIGHTING GENERAL INFO (see NRCC-PRF-LTI-DETAILS for more info),
§ 140.6
Confirmed
1.
2.
3.
4.
5.
1
Occupancy Type
Conditioned Floor Area =
Installed Lighting Power
Lighting Control Credits
Additional (Custom) Allowance
9
'a
T
6
—
(ft=)
(Watts)
(Watts)
Area Category Footnotes
Tailored Method (Watts)
❑
❑
(Watts)
Retail Merchandise Sales,
12,626
0
0
0
❑
❑
Wholesale Showroom
Building Totals:
12,626
0
0
0
See Table 140.6-C
1 See NRCC-07-01-E/or —diliwed spares
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 11 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/rime:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
3Lighting infor"Indon for existing spaces modeled is not included in the table
R. INDOOR CONDITIONED LIGHTING SCHEDULE (Adapted from NRCC-LTI-01-E)'
This Section Does Not Apply -
'IJlighting power densides were used in the compliance model Building Departments will need to check prescriptive tams for Luminaire Schedule details.
S1. COVERED PROCESS SUMMARY— ENCLOSED PARKING GARAGES § 140.9
This Section Does Not Apply
S2. COVERED PROCESS SUMMARY —COMMERCIAL KITCHENS § 140.9
This Section Does Not Apply
53. COVERED PROCESS SUMMARY -COMPUTER ROOMS § 140.9.
This Section Does Not Apply
S4. COVERED PROCESS SUMMARY— LABORATORY EXHAUSTS § 140.9
This Section Does Not Apply
T. UNMET LOAD HOURS
Thermal Zone Name
Cooling Unmet Load.Hour Umit for
proposed Cooling Unmet Load Hours
Heating Unmet Load Houi Limit for
1proposed Heating Unmet Load Hours
Thermal Zone
Thermal Zone
1-First Floor-Retail/Sales -
150
1744.75
- . 150
0
U. ENERGY USE SUMMARY
Energy Component
Standard Design Site
(MWh)
Proposed Design Site
(MWh)
Margin
(MWh)
Standard Design Site
(MBtu)
Proposed Design Site
(MBtu)
Margin
(MBtu)
Space Heating
0.0
--
—
62.8
43.5
19.3
Space Cooling
141.0
78.8
62.2
--
-
--
Indoor Fans
36.9
41.7
-4.8
Heat Rejection
Pumps & Misc.
0.3
—
--
--
--
__
Domestic Hot Water
--
-
--
68.5
68.5
0.0
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 12 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
U. ENERGY USE SUMMARY
Energy Component
-
Standard Design Site
(MWh)
Proposed Design Site
w (MWh)
Margin
(MWh)
Standard Design Site
(MBtu)
Proposed Design Site
(MBtu)
Margin
(MBtu)
Indoor Lighting
52.4
52.4
0.0
-
--
--
COMPLIANCE TOTAL
230.6
172.9
57.7
131.3
112.0
19.3
- Receptacle
45.9
-45.9
0.0
--
--
--
Process
45.9
45.9
0.0
--
--
--
Other Ltg
_
TOTAL
322.4
264.7
57.7
131.3
- 112.0 -
19.3
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 'Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 13 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Datefrime:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT § 10-103
1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Joshua Enriquez, PE, LEED AP
Signature:
Company:
Address: 665 Fairmont Ave # 11
Signature Date:
City/State/Zip: Glendale Ca 91203
CEA Identification (If applicable):
Phone:213-820-3683
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1
1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am
licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
2
1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section 5537.2 or 6737.3 to sign this document as the person responsible for its
preparation; and that I am a licensed contractor performing this work.
3
I affirm that 1 am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to
Business and Professions Code Sections 5537, 5538 and 6737.1.
Responsible Envelope Designer Name: John Gilmore Deenihan, RA
Company: LR/Architecture
Signature:
Address: 213 W. Alameda Ave, Suite 203
Date Signed:
City/State/Zip: Burbank Ca 91502
Declaration Statement Type:
Phone: (818)84D-8361
Title:
License #: C9147
Responsible Lighting Designer Name: '
Company:
Signature: NOT IN SCOPE
Address:
Date Signed:
City/State/Zip:
Declaration Statement Type:
Phone:
Title:
License M
Responsible Mechanical Designer Name: Joshua Enriquez, PE, LEED AP
Company: EnergyLogics, Inc.
Signature:
Address: 665 Fairmont Ave #11
Date Signed:
City/State/Zip: Glendale CA 91203
Declaration Statement Type:
Phone: 213-820-3683
Title: License #:
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 14 of 18
Project Address:
78-825 Highway 111 La Quinta92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
'
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
NRCC-PRF-ENV-DETAILS -SECTION START -
A. OPAQUE SURFACE ASSEMBLY DETAILS
Confirmed
2.
3.
4..
v
m
v
d
—
Surface Name
Surface Type
Description of Assembly Layers
Notes
8 CMU Wa117
ExteriorWall
Concrete - Solid Grout - 1051b/ft3 - 8 in.
❑
❑
- -
Air - Cavity - Wall Roof Ceiling -4in. or more
Built-up roofing - 3/8 in.
R-20 Metal Deck Roof9
Roof
Plywood -1/2 in.
❑
❑
Concrete - 140 Ib/ft3 - 4 in. -
-
'
Stucco - 7/8 in.
R-15 Wall Metal Stud11
EMeriorWall
Vapor permeable felt -1/8 in.
❑
❑
Air -Wall - 3 1/2 in.
/
- Gypsum Board - 1/2 in.
`
Stucco - 7/8 in.
R-13 Wall Metal Stud15
InteriorWall
" permeable felt - 1/8 in.
VaporAir
-
❑'
- Wall - 3 1/2in.
Gypsum Board - 1/2 in.
Slab Type = UnheatedSlabOnCrade
Slab On Grade17
UndergroundFloor
- Insulation Orientation .= None
❑ •
❑
- - Insulation R-Value = RO
B. OVERHANG DETAILS (Adapted from NRCC-ENW02-E)
This Section Does Not Apply -
C. OPAQUE DOOR SUMMARY
This Section Does Not Apply - -
CA Building Energy Efficiency Standards- 2013 Nonresid ential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 15 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
NRCC-PRF-MCH-DETAILS -SECTION START-
r `
A. MECHANICAL VENTILATION AND REHEAT (Adapted from 2013-NRCC-MCH-03-E)
Confirmed
1. DESIGN AIR FLOWS
2. VENTILATION (§ 120.1)
=
o
c
z
Z
v
T
Z
g_
Z
D3
fc
D3
Ov
^p
Z
g
in
Z
.G
Z
a
r
„ !c
LAZ
CONDITIONED
n
O
r
O D
�L
T 9
O
g
3
O
-
t�
O
n
'+ m
g
Z
C
3
D
C
f1 m
D
v
r
ZONE NAME
c O
3 a
'-' t
i
a
D
O
m
O
a s
�-
Z
a
n
3 3
3
Z A
3 z
o z
g
D
_ D
a
r
c
D
A
z
Z
z<
G1
Z Gi
o
o
i
T
5
g
a
a
a
Z
v
O
i
n
Z
3
3
1-First
Floor-Retail/Sales
RTU 1 thru 4
4,000
2,600
0.65
NA
NA
N
RTU 1 thru 4
12,626
NA
210
15.0
3,156
3,156
E
y
❑
❑
TOTAL
12,626
NA
NA
NA
NA
❑
❑
B. ZONAL SYSTEM AND TERMINAL UNIT SUMMARY
§ 140.4
1.
2.
3.
4.
5.
6.
7.
8.
Confirmed
Rated Capacity
Airflow (cfm)
Fan
System ID
System Type
ty
City
Economizer
Zone Name
�
r
w
Heating
Cooling
Design
Min.
- BHP
Cycles
ECM
Ratio
Motor
First
Floor-Retail/Sales3-
VAVNoReheatBox
4
NA
NA
NA
1-First Floor-Retail/Sales
4000
2600
0.65
NA
NA
❑
❑
❑
TRM
\UST FAN SUMMARY
lion Does Not Apply'
I EQUIPMENT SUMMARY — (Adapted from NRCC-PLB-01)
lion Does Not Apply
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park: Ulta Beauty
NRCC-PRF-01-E
Page16 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
E. MULTI -FAMILY CENTRAL DHW SYSTEM DETAILS
This Section Does Not Apply
F. SOLAR HOT WATER HEATING SUMMARY (Adapted from NRCC-STH-01)
This Section Does Not Apply
G. MECHANICAL HVAC ACCEPTANCE TESTS & FORMS (Adaptedfrom 1013-NRCC-MCH-0I-E) J§ RA4
Declaration of Required Acceptance Certificates (NRCA) —Acceptance Certificates that may be submitted. (Retain copies and verify forms are completed and signed to post in field for Field
Inspector to verify).
3
n
3
n
3
n
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Test Description
x
b
x
b
x
n
x
b
n
x
b
n
x
b
n
x
b
n
x
b
n
x
n
x
i+
n
x
n
x
n
x
n
x
n
x
n
x
n
x
Confirmed
►
r•
i+
�.
�.
�.
�.
v
<
c
o
o
n
Equipment
w
A
D
0
°
�'
a
n
'O
o
S
m
<
c
Requiring
Nof
o
3'
o
<
'°
m
Testing or
units
1D
o
n
<
m m
e c
c
X
,', S
a
n
m
o
9
Verification
D
0
D
W
m
M
C
n
c
3
v
o f
m
�
NonResBase
1
-
SHWSystem
—
--
—
--
—
--
--
--
--
--
--
—
—
--
--
❑
❑
RTU 1 thru 4
4
X
X
—
X
X
X
—
--
--
X
—
—
—
❑
❑
H. EVAPORATIVE COOLER SUMMARY
This Section Does Not Apply
NRCC-PRF-LTI-DETAILS -SECTION START -
IA. INDOOR CONDITIONED LIGHTING CONTROL CREDITS (Adapted from NRCC-LTI-02-E) § 140.6
This Section Does Not Apply
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 17 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name:
1016-ULTA.cibdx
B. INDOOR CONDITIONED LIGHTING MANDATORY LIGHTING CONTROLS (Adapted from NRCC-LTI-02-E)
This Section Does Not Apply -
§130.1(a) = Monuol area controls, §130.0(b) - Multi ttuel,§130.1(c) = Auto Shut -Off; §130.1(d) = Mandatory Daylight, §130.1(e) = Demond Respamlve
C. TAILORED METHOD CONDITIONED LIGHTING POWER ALLOWANCE SUMMARY AND CHECKLIST (Adapted from NRCC-LTI-04-E)
§ 140.6 .
General lighting power (see Table D)
0
General lighting power from special function areas (see Table E)
NA
Additional "use it or lose it" (See Table G)
0
Total watts
0
D. GENERAL LIGHTING POWER (Adapted from NRCC-LTI-04-E) § 140X-11)
This Section Does Not Apply
E. GENERAL LIGHTING FROM SPECIAL FUNCTION AREAS (Adapted from NRCC-LTI-04-E)
§ 140.6(c) 3H
Room Number
Primary Function Area
Illuminance Value
(LUX)
Room Cavity Ratio
(Table G)
Allowed LPD
Floor Area (ft')
Allowed Watts
Confirmed
Pass
Fall
NA
NA
NA
NA
NA
NA
.NA .
❑ 1
❑
F. ROOM CAVITY RATIO (Adapted from NRCC-LTI.04-E)
Rectangular Spaces
Room Number
Task/Activity Description
Room Length (ft)
Room Width (ft)
Room Cavity Height (ft)
RCR
Confirmed
Pass
Fall
NA
NA
NA
NA
NA
NA
I ❑
❑
Non -Rectangular Spaces
This Section Does Not Apply
ry . w, vppncvan, spaces are iaiev unvei one rvan-nec�engu�er.apvices mv�e
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016.08.17 22:36:18
Project Name:
Washington Park - Ulta Beauty
NRCC-PRF-01-E
Page 18 of 18
Project Address:
78-825 Highway 111 La Quinta 92253
Calculation Date/Time:
22:35, Wed, Aug 17, 2016
Compliance Scope:
ExistingAlteration
Input File Name: '
1016-ULTA.cibdx
G. ADDITIONAL "USE IT OR LOSE IT" (Adapted from NRCC-LTI-04-E)
1.
2.
3.
4.
Allowed Watts
Confirmed
Wall Display
Combined Floor Display and Task
Lighting
Combined Ornamental and Special
Effects Lighting
Very Valuable Merchandise
v
o
0
0
0
0
0
❑
❑
S. Wall Display
This Section Does Not Apply
6. Floor Display and Task Lighting
This Section Does Not Apply
7. Combined Ornamental and Special Effects Lighting
This Section Does Not Apply
8. Very Valuable Merchandise
This Section Does Not Apply
H. INDOOR & OUTDOOR LIGHTING ACCEPTANCE TESTS & FORMS (Adapted from NRCC-LTI-01-E and NRCC-LTO-01-E) I § 130.4
Declaration of Required Acceptance Certificates (NRCA) —Acceptance Certificates that must be verified in the field. (Retain copies and verify forms are completed and signed to post in field for
Field Inspector to verify).
Test Description
Indoor
Outdoor
Confirmed
NRCA-LTI-02-A
NRCA-LTI-03-A
NRCA-LTI-04-A
,
NRCA-LTO-02-A
Equipment Requiring
Testing or Verification
p of units
Switch Occ SensorsAuto Time
Auto Daylight
Demand Responsive
Outdoor Controls
n�
w
-
Occupant Sensors
0
❑
❑
❑
❑
❑
❑
Automatic Time Switch
0
❑
❑
❑
❑
❑
❑
Automatic Daylighting
0
❑
❑
❑
❑
❑
❑
Demand Responsive
0
❑
❑
❑
❑
❑
❑
Outdoor Controls
0
❑
❑
❑
❑
❑
❑
CA Building Energy Efficiency Standards- 2013 Nonresidential Compliance Report Version: NRCC-PRF-01-E-08122016-3995 Report Generated at: 2016-08-17 22:36:18
ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV-MM
Project Name
Date
Washington Park - Ulta Beauty
811712016
DESCRIPTION
Building Envelope Measures:
§110.8(a): Installed insulating material shall have been certified by the manufacturer to comply with the California Quality
Standards for insulating material, Title 20 Chapter 4, Article 3.
§110.8(c): All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of
Sections 2602 and 707 of Title 24, Part 2.
§110.8(f): The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R-value
of no less than R-13 between framing members.
§110.7(a): All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed,
weatherstripped or otherwise sealed.
Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.2 of
§110.6(a): window area, 0.3 cfm/ft.2 of door area for residential doors, 0.3 cfm/ft.2 of door area for nonresidential single doors
(swinging and sliding),and 1.0 cfm/ft.2 for nonresidential double doors swin in .
§110.6(a): Fenestration U-factor shall be rated in accordance with NFRC 100, or the applicable default U-factor.
§110.6(a) : Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site -built fenestration, or the
applicable default SHGC.
§110.6(b): Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be
weatherstripped (except for unframed glass doors and fire doors).
EnergyPro 6. by EnergySoft User Number: 1064 ID: 1016 Page 21 of 22
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Washington Park - Ulta Beauty
Date
8/17/2016
System Name
RTU 1 thru 4
Floor Area
12,626
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
4
COIL
CFM
Total Room Loads 28,108
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 3,157
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output perSystem
104,000
414,850
84,173
1,981
120,109
Total Output Btuh
416,000
0
Output Btuh/s ft
32.9
20,742
6,005
Cooling System
0
0
Output perSystem
118,000
124,297
27,510
3,157
147,477
Total Output Btuh
472,000
35,193
111,683
-35,193
Total Output Tons
39•3
1 20,742
6,005
Total Output Btuh/s ft
37.4
Total Output s ft/Ton
321.0
1 615,825
244,404
Air System
CFM perSystem
4,000
HVAC EQUIPMENT SELECTION
Airflow cfm
16,000
Lennox LGH120H4M(10 T)
389,778
52,500
416,000
Airflow cf nls ft
1.27
Airflow cfm/Ton
406.8
Outside Air %
19 7 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
389,778
52,500
416,000
Outside Air cfm/s ft
0.25
Note: values above given at ARI conditions
r
Jul 3 PM
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperature! at Time of Heating Peak
26 OF
No
Outside Air
3,157 cfm
70 OF
63 OF 127 OF 127 OF
Heating Coil Supply Fan 16,000 cfm 127 ° F
ROOM
70 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78OF
Outside Air 3,157 cfm
75 / 65 OF
85/68°F 59/58°F 59/58OF
Cooling Coil Supply Fan 60 / 58 OF
16,000 cfm
60.5 % ROOM
II_ll_II_ 74 / 65 OF
EnergyPro 6. by EnergySoft
User Number: 1064 ID: 1016
Page 22 of 22