11-1363 (RC) Title 24y
'BUILDING ENERGY ANALYSIS REPORT
PROJECT:
McDonald's
78962 Highway 111
La Quinta, CA 92253
Project Designer:
Underwood and Associates
12832 Valley View St., #207
Garden Grove, CA 98245
714-892-3900
Report Prepared by:
PP
PJP Engineering, Inc
13231 Acoro Place
Cerritois, CA 90703
562-404-2695
Job Number:
CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CO NSTR-UCCT�ION
DATE
DECEIVED PP4400-434
DEC 2 7 2011 Date:
12/26/2011
BY:
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the Califomia Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
EneigyPro 5.1 by Energ Soft User Number 4806 RunCode: 2011-12-26T13:47:02 I0: PP4400-434
TABLE OF CONTENTS
Cover Page 1
Table of Contents 2
Nonresidential Performance Title 24 Forms 3
Form ENV -MM Envelope Mandatory Measures 15
Form MECH-MM Mechanical Mandatory Measures 16
EnergyPro 5.1 by EnergySoft Job Number. ID: PP4400-434 User Number. 4806
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1 C
Project Name
Date
McDonald's
11212612011
Project Address
Climate Zone
Total Cond. Floor Area
Addition Floor Area
78962 Highway 111 La Quinta
CA Climate Zone 15
4,754
81
GENERAL INFORMATION
Building Type: ® Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
❑ Relocatable - indicate ❑ specific climate zone ❑ all climates
Phase of Construction: ❑ New Construction ❑ Addition ® Alteration
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed to
comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This
certificate applies only to a Building using the performance compliance approach.
The documentation author hereby certifies that the documentation is accurate and complete.
Documentation Author
Name PP
Signature
Company PJP Engineering, Inc Date 1226/2011
Address 13231 Acoro Place Phone 562-404-2695
City/State/Zip Cerritois, CA 90703
The Principal Designer hereby certifies that the proposed building design represented in this set of
construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with
any other calculations submitted with this permit application. The proposed building has been designed to meet the energy
efficiency requirements contained in sections 110, 116 through 118, and 140 through 149 of Title 24, Part 6. Please
check one:
ENV. LTG. MECH.
I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
❑ ❑ ❑ sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by section
❑ ❑. ❑ 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
I affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
❑ ❑ ❑ because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538 and 6737.1.
Principal Envelope Designer
Name . TL
[Signature
Company Underwood and Associates Date
Address 12832 Valley View St. #207 License #
City/State/Zip Garden Grove, CA 98245 Phone 714-892-3900
Principal Mechanical Designer
Name TL
Signature
Company Underwood & Associates Date
Address License #
City/State/Zip Garden Grove, CA Phone
Principal Lighting Designer
Name
Signature
Company Lighting Compliance Not In The Scope Of This Submittal Date
Address License #
City/State2ip Phone
INSTRUCTIONS TO APPLICANT COMPLIANCE & WORKSHEETS (check box If worksheets are Included)
m ENV -1C Certificate of Compliance. Required on plans. m MECH-1 C Certificate of Compliance. Required on plans.
❑ LTG -1C Certificate of Compliance. Required on plans. m MECH-2C Air/Water Side/Service Hot Water & Pool Requirements.
❑ LTG -2C Lighting Controls Credit Worksheet. m MECH-3C Mechanical Ventilation and Reheat.
❑ LTG -3C Indoor Lighting Power Allowance. m MECH-5C Mechanical Equipment Details.
Energ Pro 5.1 by EnergySoft User Number., 4806 Run Code: 2011-12-26T13:47:02 ID: PP4400-434 Page 3 of 16
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 PERF -1 C
Project NameDate
McDonald's 12/26/2011
ANNUAL TDV ENERGY USE SUMMARY (kBtu/sgft-vr)
Energy Component
Space Heating
Space Cooling
Indoor Fans
Heat Rejection
Pumps & Misc.
Domestic Hot Water
Lighting
Receptacle
Process
Process Lighting
TOTALS
itandard Proposed Compliance
DESInn DPcinn Marnin
1.34
1.24
0.10
511.67
502.86
8.80
136.87
142.57
-5.71
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
100.02
100.02
0.00
76.77
76.77
0.00
136.61
136.61
0.00
0.00
0.00
0.00
963.27
960.07
3.20
Heating
Cooling
Fans
Heat Rej
Pumps
DHW
Lighting
Receptacle
Process
Process Ltg
Percent better than Standard 0.3% 0.4 % excluding process)
BUILDING COMPLIES
I GENERAL INFORMATION
Building Orientation (►M 270 deg Conditioned Floor Area 4,754 sqft.
_ q
Number of Stories 1 Unconditioned Floor Area 0 sqft.
Number of Systems 5 Conditioned Footprint Area 4,754 sqft.
Number of Zones 3 Natural Gas Available On Site Yes
Front Elevation
Left Elevation
Rear Elevation
Right Elevation
Total
I Roof
Oriantntinn rirnQC Aran
(tM
854
(N)
1,246
(E)
854
(S)
1,246
4,200
4,754
Prescriptive Lighting Power Density
Prescriptive Envelope TDV Energy
Remarks:
Standard
1.430 W/sgft.
292,283
sqft.
sqft.
sqft.
sqft.
sqft.
sqft.
Glazina Area
305
59
147
483
994
0
Proposed
1.430 W/sqft.
694, 628
I 'I KIMI
sqft.
sqft.
sqft.
sqft.
sqft.
sqft.
35.7%
4.7%
17.2%
38.8%
23.7
0.0%
Prescriptive Values for
Comparison only. See
LTG -1 C for allowed LPD.
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1 C
Project Name
McDonald's
Date
11212612011
ZONE INFORMATION
System Name Zone Name
Occupancy Type
Floor
Area
s ft.
Inst.
LPD
W/sf'
Ctrl.
CreditsArea
W/sf 2
Allowed LPD Proc.
Tailored Loads
W/sf 3 W/sf ° W/sf
McDonald's Kitchen McDonald's
Kitchen, Food Preparation
2,729
"1.600
3.000
McDonald's Dining McDonald's
Comp Bldg Restaurant
1,944
`1.200
1.000
McDonald's
Comp Bldg Restaurant
81
•1.200
Notes: 1. See LTG -1 C 2. See LTG -2C 3. See LTG -3C 4. See LTG -4C
items marked with asterisk, see LTG -1-C b others b others
Items above require special documentation
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
The local enforcement agency should pay special attention to the items specified In this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The local enforcement agency
determines the adequacy of the justifications, and may reject a building or design that otherwise complies based on the adequacy of the
special justification and documentation submitted.
The exceptional features listed In this performance approach application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Authorized Signature or Stamp
EnergyPro 5.1 by EnergySoft User Number. • 4806 RunCode: 2011-12-26T13:47:02 ID: PP4400-434 Page 5 of 16
CERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1C
AND FIELD INSPECTION ENERGY CHECKLIST
Project Name
McDonald's
Date
11212612011
Project Address
78962 Highway 111 La Quinta
Climate Zone
15
Total Cond. Floor Ai;j
4,754
Addition Floor Area
81
GENERAL INFORMATION
Building Type: ® Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
❑ Schools (Public School) ❑ RRledlocatable g. Public School m Conditioned Spaces 13Unconditioned Spaces
❑ Skylight Area for Large Enclosed Space z 8000 ftz (If checked include the ENV -4C with submittal)
Phase of Construction: ❑ New Construction ❑ Addition m Alteration
Approach of Compliance: ❑ Component m Overall Envelope ❑ Unconditioned (file affidavit)
Front Orientation: N, E, S, W or in Degrees:
1270 deg
FIELD INSPECTION ENERGY CHECKLIST
OPAQUE SURFACE DETAILS
INSULATION
Ta /ID
AssemblyType
d.2
Q
3
Cy
UJLL
O2
u
i
tib
C
W>
G 5
W{L
o
d—
>
o c
d r
CU,
C
d
C 16
v
d
LL
1
Slab
2,729
(N)
0.730
Nonel
4.4.7-A1
Existing
❑
❑
2
Wall
1,168
(N)
0.110
R-11
4.3.1-A2
Existing
❑
❑
3
Roof
2,729
(N)
0.049
R-19
4.2.1-A4
Existing
❑
❑
4
Wall
300
(E)
0.110
R-11
4.3.1-A2
Existing
❑
❑
5
Roof
1,944
(N)
1 0.049
R-19
4.2.1-A4
Existing
❑
❑
6
Slab
1,944
(N)
0.730
None
4.4.7-A 1
Existing
❑
❑
7
Wall
348
(Vt9
0.110
R-11
4.3.1-A2
Existing
❑
❑
8
Wall
743
(S)
0.110
R-11
4.3.1-A2
Existing
❑
❑
9
Wall
407
(E)
0.110
R-11
4.3.1-A2
Existing
❑
❑
10
Wall
160
(149
1 0.110
R-11
4.3.1-A2
Removed
❑
❑
1. See Instructions in the Nonresidential Compliance Manual, page 3-96.
2. If Fail, then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. A fail does not meet compliance.
FENESTRATION SURFACE DETAILS
Tag/ID
Fenestration
Type
L'
a
`3
C w
:'
O Z
0
RLL
>
0
LL c
> Cn
U
'�
2¢
_ 'o
N u)
c
>
O
o
o
C) N
A
a
LL
1
Window
36
(N)
1.190
NFRC
0.830
NFRC
❑
Existing
❑
❑
2
Window
170
(tM
1.190
NFRC
0.830
NFRC
❑
Existing
❑
❑
3
Window
461
(S)
1.190
NFRC
0.830
NFRC
❑
Existing
❑
❑
4
Window
147
(E)
1.190
NFRC
0.830
NFRC
❑
Existing
❑
❑
5
Window
176
(IM
1.190
NFRC
0.830
NFRC
❑
Removed
❑
❑
6
Window
23
(N)
1.000
NFRC
0.700
NFRC
❑
New
❑
❑
7
Window
22
(S)
1.000
NFRC
0.700
NFRC
❑
New
❑
❑
8
Window
135
(W)
1.000
NFRC
0.700
NFRC
❑
New
❑
❑
❑
❑
❑
❑
❑
❑
1. See Instructions in the Nonresidential Compliance Manual, page 3-96.
2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
EnergyPro 5.1 by EnergySoft User Number., 4806 RunCode: 2011-12-26713:47:02 ID: PP4400-434 Pa e 6 of 16
CERTIFICATE OF COMPLIANCE (Part 1 of 3) ENV -1 C
AND FIELD INSPECTION ENERGY CHECKLIST
Project Name
McDonald's
Date
12/26/2011
Project Address
78962 Highway 111 La Quinta
Climate Zone
15
Total Cond. Floor Area
4,754
Addition Floor Area
81
GENERAL INFORMATION
Building Type: ® Nonresidential ❑ High -Rise Residential ❑ Hotel/Motel Guest Room
❑ Schools (Public School) ❑ Relocatable Public School m Conditioned Spaces ❑ Unconditioned Spaces
Bldg.
❑ Skylight Area for Large Enclosed Space z 8000 ftz (If checked include the ENV -4C with submittal)
Phase of Construction: 1 New Construction ❑ Addition m Alteration
Approach of Compliance: ❑ Component ® Overall Envelope ❑ Unconditioned (file affidavit)
Front Orientation: N, E, S, W or in Degrees:
270 deg
FIELD INSPECTION ENERGY CHECKLIST
OPAQUE SURFACE DETAILS
INSULATION
AssemblyT
a
30
C N
O z
V
n
2+ 7
v W
C
ww
>
2 C
U.
8
5.2
1Tag/ID >
O C
i
C
-3 a
r y
O N
N
a
U.
11
Roof
81
(N)
0.049
R-19
1
4.2.1-A4
Existing
❑
❑
12
Slab
81
(N)
0.730
None
4.4.7-A1
Existing
❑
❑
13
Wall
19
(N)
0.110
R-11
4.3.1-A2
New
❑
❑
14
Wall
20
(S)
0.110
R-11
4.3.1-A2
New
❑
❑
15
Wall
'201
0.110
R-111
4.3.1-A2
New
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
1. See Instructions in the Nonresidential Compliance Manual, page 3-96.
2. If Fail, then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. A fail does not meet compliance.
FENESTRATION SURFACE DETAILS
Tag/ID
Fenestration
Type
2w
a
3
OZ
V
RLLUT
�>
c=
> .N
V
�¢
o
NN
o� C
>
O
c
o
VN
A
a
LL
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
13
❑
131.
See Instructions in the Nonresidential Compliance Manual, page 3-96.
2. If Fail then describe on Page 2 of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
EnergyPro 5. 1 by EnergySoft User Number 4806 RunCode: 2011-12-26T13:47:02 ID: PP4400-434 Page 7 of 16
CERTIFICATE OF COMPLIANCE (Part 2 of 3)
AND FIELD INSPECTION ENERGY CHECKLIST
ENV -1 C
Project Name
McDonald's
Date
12/26/2011
ROOFING PRODUCT COOL ROOFS
(Note if the roofing product is not CRRC certified, this compliance approach cannot be used). Go to overall Envelope Approach or
Performance Approach.
CHECK APPLICABLE BOX BELOW IF EXEMPT FROM THE ROOFING PRODUCT "COOL ROOF" REQUIREMENTS:
Pass
Fall'
N/A
❑ Roofing compliance not required in Climate Zones 1 andl6 with a Low -Sloped. 2:12 pitch or less.
❑
❑
❑
❑ Roofing compliance not required in Climate Zone 1 with a Steep -Sloped with less than 5 Ib/ft2. Greater than 2:12 pitch.
❑
❑
❑
Wood framed roofs in Climate Zones 3 and 5 are exempted, solar reflectance and thermal emittance or
13SRIthat have a U -factor of 0.039 or lower. See Opaque Surface Details roof assembly, Column H of ENV -2C.
13
13
13SRI
❑ Low -sloped Metal building roofs in Climate Zone 3 and 5 are exempted, solar relectance and thermal emittance or SRI
that have a U -factor of 0.048 or lower. See Opaque Surface Details roof assembly below, Column H of ENV -2C.
❑
❑
[3
roof area covered by building integrated photovoltaic panels and building integrated solar thermal panels are
13 exempted.
ted. Solar reflectance and thermal emittance or SRI, seespreadsheet calculator at www.ener .ca. ov/title24/
13
13
13exem
❑ Roof constructions that have thermal mass over the roof membrane with a weight of at least 25 Ib/ft are exempt from
Cool Roof criteria below.
C]
13
13the
❑ High-rise residential buildings and hotels and motels with low -sloped roofs in Climate Zones 1 through 9, 12 and 16 are
ted from the low -sloped roofingcriteria.
1313
13exem
1. If Fail then describe on this page of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessary.
CRRC Product ID Roof Slope Product Weight
Number' s 2:12 > 2:12 < 51b/fe 2 51b/ft 2
Product
Type2
Aged Solar
Reflectance
Thermal
Emmitance
SPI 15
Pass
Fail6
❑ ❑ ❑ ❑
❑ 4
❑
❑
❑ ❑ ❑ ❑
❑ 4
❑
❑
❑ ❑ ❑ ❑
❑ 4
❑
❑
❑ ❑ ❑ ❑
❑ 4
❑
❑
❑ ❑ ❑ ❑
❑ 4
❑
❑
_ ❑ ❑ ❑ ❑
c3
❑
❑
1. The CRRC Product ID Number can be obtained from the Cool Roof Rating Council's Rated Product Directory at
www.coolroofs.or-q/products/search.php
2. Indicate the type of product is being used for the roof top, i.e. single -ply roof, asphalt roof, metal roof, etc.
3. If the Aged Reflectance is not available in the Cool Roof Rating Council's Rated Product Directory then use the Initial Reflectance value from the
same directory and use the equation (0.2+0.7(p,,d"al — 0.2) to obtain a calculated aged value. Where p is the Initial Solar Reflectance from the Cool
Roof Rating Council's Rated Product Directory.
4. Check box if the Aged Reflectance is a calculated value using the equation above.
5. The SRI value needs to be calculated from a spreadsheet calculator at htto://www.energy.ca.gov/title24/
6. If Fail then describe on this page of the Inspection Checklist Form and take appropriate action to correct. Verify building plans if necessarv.
To apply Liquid Field Applied Coatings, the coating must be applied across the entire roof surface and meet the dry mil thickness or coverage
recommended by the coatings manufacturer and meet minimum performance requirements listed in §118(i)4. Select the applicable coating:
❑ Aluminum -Pigmented Asphalt Roof Coating
❑ Cement -Based Roof Coating
❑ Other
Discrepancies:
EnergyPro 5.1 by EnergySoft User Number. 4806 Run Code: 2011-12-26713:47:02 ID: PP4400-434
Page 8 of 16
CERTIFICATE OF COMPLIANCE (Part 3 of 3) ENV -1 C
AND FIELD INSPECTION ENERGY CHECKLIST
Project Name
McDonald's
Date
11212612011
Required Acceptance Tests
Designer:
This form is to be used by the designer and attached to the plans. Listed below is the acceptance test for Envelope
Fenestrations system. The designer is required to check the acceptance tests and list all the fenestration products that
require an acceptance test. If all the site -built fenestration of a certain type requires a test, list the different fenestration
products and the number of systems. The NA7 Section in the Appendix of the Nonresidential Reference Appendices
Manual describes the test. Since this form will be part of the plans, completion of this section will allow the responsible
party to budget for the scope of work appropriately.
Enforcement Agency:
Systems Acceptance. Before Occupancy Permit is granted for a newly constructed building or space or whenever new
fenestration is installed in the building or space shall be certified as meeting the Acceptance Requirements.
The ENV -2A form is not considered a complete form and is not to be accepted by the enforcement agency unless the
boxes are checked and/or filled and signed. In addition, a Certificate of Acceptance forms shall be submitted to the
enforcement agency that certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of §10-103(b) of Title 24 Part 6. The field inspector must receive the properly filled
out and signed forms before the building can receive final occupancy. A copy of the ENV -2A for each different
fenestration product line must be provided to the owner of the building for their records.
Test Description ENV -2A Test Performed By:
Fenestration Products Name or ID Area of like Building Envelope
Requiring Testing or Verification Products Acceptance Test
low a window 180 m
13
13
13
13
13
13
13
13
13
13
13
13
❑
❑
13
13
13
13
13
13
13
EnergyPro 5. 1 by EnergySoft User Number: 4806 RunCode: 2011-12-26713:47:02 ID: PP4400-434 Page 9 of 16
CERTIFICATE OF COMPLIANCE and (Part 1 of 4) MECH-1C
FIELD INSPECTION ENERGY CHECKLIST
Project Name
McDonald's
Date
12/26/2011
Project Address
78962 Highway 111 La Quinta
Climate Zone
15
Total Cond. Floor Area
4,754
Addition Floor Area
81
GENERAL INFORMATION
Building Type: ® Nonresidential ❑ High-Rise Residential ❑ Hotel/Motel Guest Room
❑ Schools (Public School) ❑ Relocatable Public School Bldg. m Conditioned Spaces ❑ Unconditioned Spaces
affidavit
Phase of Construction: M New Construction ❑ Addition ® Alteration
Approach of Compliance: ❑ Component ❑ Overall Envelope TDV ❑ Unconditioned (file affidavit)
Enerqy
Front Orientation: N, E, S, W or in Degrees:
270 deg
HVAC SYSTEM DETAILS
FIELD INSPECTION ENERGY CHECKLIST
Equipment'
Ins ection Criteria
Meets Criteria
or Requirements
Pass
Fail — Describe Reason
Item or System Tags
i.e. AC-1 RTU-1 HP-1
McDonald's Kitchen
13
❑
Equipment T e3:
Packaged DX
❑
❑
Number of Systems
2
❑
❑
Max Allowed Heating Capacity'
90,000 Btulhr
❑
❑
Minimum Heating Efficiency'
78% AFUE
❑
❑
Max Allowed Cooling Capacity'
60,000 Btu/hr
❑
❑
Cooling Efficiency'
10.0 SEER / 10.0 EER
❑
❑
Duct Location/ R-Value
Attic, Ceiling Ins, vented 4.2
❑
❑
When duct testing is required, submit
& MECH-4-HERS
No
13
13MECH-4A
Economizer
No Economizer
❑
❑
Thermostat
Setback Required
❑
❑
Fan Control
Constant Volume
❑
❑
E ui ment2
Inspection Criteria
FIELD INSPECTION ENERGY CHECKLIST
Pass
Fail — Describe Reason
Item or System Tags
AC-1, RTU-1, HP-1
McDonald's Dining
[3
13i.e.
Eq ui ment Type 3:
Packaged DX
❑
❑
Number of Systems
3
❑
❑
Max Allowed Heating Capacity'
90,000 Btu/hr
❑
❑
Minimum Heating Efficiency'
78% AFUE
❑
❑
Max Allowed Cooling Capacity'
60,000 Btu/hr
❑
❑
Cooling Efficiency'
10.0 SEER / 10.0 EER
❑
❑
Duct Location/ R-value
Attic, Ceiling Ins, vented/ 4.2
❑
❑
When duct testing is required, submit
& MECH-4-HERS
NO
❑
13MECH-4A
Economizer
No Economizer
❑
❑
Thermostat
Setback Required
❑
❑
Fan Control
Constant Volume
❑
❑
1. If the Actual installed equipment performance efficiency and capacity is less than the Proposed (from the energy compliance submittal or from
the building plans) the responsible party shall resubmit energy compliance to include the new changes.
2. For additional detailed discrepancy use Page 2 of the Inspection Checklist Form. Compliance fails if a Fail box is checked.
3. Indicate Equipment Type: Gas (Pkg or, Split), VAV, HP (Pkg or split), Hydronic, PTAC, or other.
JEnergyPro6lbyEnergySoft User Number. 4806 RunCode: 2011-12-26T13:47:02 ID: PP4400-434 Pae 10 of 16
CERTIFICATE OF COMPLIANCE and (Part 2 of 4) MECH-1 C
FIELD INSPECTION ENERGY CHECKLIST
Project Name Date
McDonald's 12/26/2011
I EnergyPrO 5.1 by EnergySoft User Number., 4806 Run Code: 2011-12-26713:47:02 ID: PP4400-434 Page 11 of 16
AIR SYSTEM REQUIREMENTS
Part 1 of 2 MECH-2C
Project Name
Date
McDonald's
12/26/2011
Indicate
Air Systems Type Central,
Single Zone, Package, VAV, or etc...
Item or System Tags
i.e. AC -1, RTU -1, HP -1
McDonald's Kitchen
McDonald's Dining
Number of Systems
2
3
Indicate Page Reference on Plans or Schedule and Indicate the applicable exception(s)
MANDATORY MEASURES
T-24 Sections
Heating Equipment Efficiency
112 a
78% AFUE
78% AFUE
Cooling Equipment Efficiency
112(a)
10.0 SEER / 10.0 EER
10.0 SEER/ 10.0 EER
HVAC Heat Pump Thermostat
112(b), 112(c)
n/a
n/a
Furnace Controls/Thermostat
112(c), 115 a
n/a
n/a
Natural Ventilation
121 b
No
No
Mechanical Ventilation
121 b
409 cfm
1,013 cfm
VAV Minimum Position Control
121 c
No
No
Demand Control Ventilation
121 c
No
No
Time Control
1 22 a
Programmable Switch
Programmable Switch
Setback and Setup Control
122(e)
Setback Required
Setback Required
Outdoor Damper Control
122(f)
Auto
Auto
Isolation Zones
122
n/a
n/a
Pipe Insulation
123
N/A
N/A
Duct Location/ R -value
124
Attic, Ceiling Ins, vented 4.2 Attic, Ceiling Ins, vented 4.2
PRESCRIPTIVE MEASURES
Calculated Design Heating Load
144(a & b
n/a
n/a
Proposed Heating Capacity
144(a & b
180,000 Btu/hr
270,000 Btulhr
Calculated Design Cooling Load
144(a & b
n/a
n/a
Proposed Cooling Capacity
144(a & b
77,961 Btu/hr
128,879 Btu/hr
Fan Control
144(c)
Constant Volume
Constant Volume
DP Sensor Location
144(c)
N/A
N/A
Supply Pressure Reset (DDC only)
144(c)
No
No
Simultaneous Heat/Cool
144(d)
No
No
Economizer
144(e)
No Economizer
No Economizer
Heat Air Supply Reset
144(f)
Constant Temp
Constant Temp
Cool Air Supply Reset
144
Constant Temp
Constant Temp
Electric Resistance Heating'
144
Air Cooled Chiller Limitation
144(i)
Duct Leakage Sealing. If Yes, a
MECH-4-A must be submitted
I 144(k)
No
No
1. Total installed capacity (MBtu/hr) of all electric heat
on this project exclusive of electric auxiliary heat for heat pumps. If electric heat is used
explain which exception(s) to §144(g) apply.
EnergyPro 5.1 by EnergySoft User Number: 4806
Runcode: 2011-12-26T13:47:02 ID: PP4400-434 Pae 12 of 16
MECHANICAL VENTILATION AND REHEAT
MECH-3C.
Project Name
McDonald's
Date
12/26/2011
MECHANICAL VENTILATION §121 b 2
REHEAT LIMITATION (§144(d))
AREA BASIS
OCCUPANCY
BASIS
VAV MINIMUM
A
B
C
D
E
F
G
H
I
J
K
L
M
N
Zone/System(ft2
Condition
Area
CFM
per
ft2
Min CFM
By Area
B X C
Number
Of
People
CFM
per
Person
Min CFM
by
Occupant
E X F
REQ'D
V.A.
Max of
D or G
Design
Ventilation
Air
CFM
50% of
Design Zone
Supply
CFM
B X 0.4
CFM / ft2
Max. of
Columns
H, J, K,
300 CFM
Design
Minimum
Air
Setpoint
Transfer
Air
McDonald's
2, 729
0.15
409
27.3
15.0
409
409
409
McDonald's Kitchen
Total
409
409
McDonald's
1,944
0.38
739
64.8
15.0
972
972
972
McDonald's
81
0.38
31
2.7
15.0
41
41
41
McDonald's Dining
Total
1,013
1,013
Totals
Column I Total Design Ventilation Air
C Minimum ventilation rate per Section 121, Table 121-A.
E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes
fors aces without fixed seating.
H Required Ventilation Air REQ'D V.A. is the larger of the ventilation rates calculated on an AREA BASIS or OCCUPANCY BASIS Column D or G).
I Must be greater than orequal to H, or use Transfer Air column N to make up the difference.
J Design fan supply CFM Fan CFM x 50%; or the design zone outdoor airflow rate per 121.
K Condition area ft2 x 0.4 CFM / ft2; or
L Maximum of Columns H, J, K, or 300 CFM
M I This must be less than orequal to Column L and greater than orequal to the sum of Columns H plus N.
N Transfer Air must be provided where the Required Ventilation Air (Column H) is greater than the Design Minimum Air (Column M). Where required, transfer air must be greater than or
equal to the difference between the Required Ventilation Air Column H and the Design Minimum Air Column M), Column H minus M.
EnergyPro 5.1 by EnergySoft User Number. 4806 RunCode: 2011-12-26713:47:02
ID: PP4400-434
Pae 13 of 16
MECHANICAL EQUIPMENT DETAILS
Part 1 of 2 MECH-5C
Project Name
McDonald's
Date
12/26/2011
CHILLER AND TOWER SUMMARY
PUMPS
Equipment Name Type
Ot . Efficiency
Tons
Pump
Ot . GPM BHP Control
DHW / BOILER SUMMARY
System Name Type
Distribution Ot . Rated Input
Vol.
(Gals).
Energy Factor Standby Loss Tank Ext.
or RE or Pilot R -Value Status
MULTI -FAMILY CENTRAL WATER HEATING DETAILS
Hot Water Pump
Hot Water PIping Length ft
Control Ot . HP
Type
In Plenum Outside Buried Add 1/2" Insulation
❑
CENTRAL SYSTEM RATINGS
HEATING
COOLING
System Name Type
Ot . Output Aux. kW
Efficiency
Output Efficiency Status
Exist. AC unit Packaged DX
5 90,000 0.0
78% AFUE 60,000 10.0 SEER/ 10.0 EER Existing
CENTRAL SYSTEM FAN SUMMARY
SUPPLY FAN RETURN FAN
System Name Fan Type
[Exist.
Economizer Type
CFM BHP CFM BHP
AC unit Constant Volume
No Economizer
2,000 1.00 none
EnergyPro 5.1 by EnerqySoft User Number. 4806
RunCode: 2011-12-26T13:47:02
ID: PP4400-434 Pae 14 of 16
ENVELOPE MANDATORY MEASURES: NONRESIDENTIAL ENV -MM
Project Name
McDonald's
Date
12/26/2011
DESCRIPTION
Building Envelope Measures:
§118(a): Installed insulating material shall have been certified by the manufacturer to comply with the California Quality
Standards for insulating material, Title 20 Chapter 4, Article 3.
§118(c): All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of
Sections 2602 and 707 of Title 24, Part 2.
§118(f): The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value
of no less than R-13 between framing members.
17 a All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed,
§1 ()' weatherstripped or otherwise sealed.
Manufactured fenestration products and exterior doors shall have air infiltration rates not exceeding 0.3 cfm/ft.2 of
§116(a) 1: window area, 0.3 cfm/ft.2 of door area for residential doors, 0.3 cfm/ft.2 of door area for nonresidential single doors
(swinging and sliding),and 1.0 cfm/ft.2 for nonresidential double doors (swinging).
§116(a) 2: Fenestration U -factor shall be rated in accordance with NFRC 100, or the applicable default U -factor.
§116(a) 3: Fenestration SHGC shall be rated in accordance with NFRC 200, or NFRC 100 for site -built fenestration, or the
applicable default SHGC.
§116(b): Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be
weatherstripped (except for unframed glass doors and fire doors).
EnergyPro 5.1 by EnemySoft User Number: 4806 RunCode: 2011-12-26713:47:02 ID: PP4400-434 Pae 15 of 16
MECHANICAL MANDATORY MEASURES: NONRESIDENTIAL MECH-MM
Project Name
Date
McDonald's
12/26/2011
Equipment and System Efficiencies
§111:
Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply
with the applicable standard.
§115(a):
Fan type central furnaces shall not have a pilot light.
§123:
Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC
equipment, shall be insulated in accordance with Standards Section 123.
§124:
Air handling duct systems shall be installed and insulated in compliance with Sections 601, 602, 603, 604, and 605 of
the CMC Standards.
Controls
§122(e):
Each space conditioning system shall be installed with one of the following:
1A.
Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not
explicitly exempt from the requirements of Section 112 (d)) shall be installed with an automatic time switch with an
accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch
shall be capable of programming different schedules for weekdays and weekends and have program backup
capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power is interrupted; or
1 B.
An occupancy sensor to control the operating period of the system; or
1 C.
A 4 -hour timer that can be manually operated to control the operating period of the system.
2
Each space conditioning system shall be installed with controls that temporarily restart and temporarily operate the
system as required to maintain a setback heating and/or a setup cooling thermostat setpoint.
Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000
§122(g):
square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided
with isolation devices, such as valves or dampers that allow the supply of heating or cooling to be setback or shut off
independently of other isolation areas; and shall be controlled bv a time control device as described above.
122 c
§ ()'
Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to
authorized personnel.
§122(b):
Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the
heating load can be met by the heat pump alone
Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the
zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the
§122(a&b):
control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be
capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or
reduced to a minimum.
Ventilation
§121(e):
Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified
on these plans.
§122(f):
All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers in all
openings to the outside, except for combustion air openings.
Ventilation System Acceptance. Before an occupancy permit is granted for a newly constructed building or space, or a
§121(f):
new ventilating system serving a building or space is operated for normal use, all ventilation systems serving the
building ors ace shall be certified as meeting the Acceptance Requirements for Code Compliance
Service Water Heating Systems
§113(c)
Installation
3.
Temperature controls for public lavatories. The controls shall limit the outlet Temperature to 110° F.
2
Circulating service water -heating systems shall have a control capable of automatically turning off the circulating pump
when hot water is not required.
EnergyPro 5.1 by
EnergySoft User Number: 4806 RunCode: 2011-12-26T13:47:02 ID: PP4400-434 Pae 16 of 16