BRES2018-0335 Title 24BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Ratpack Residence
53-525 Humbolt Blvd.
La Quinta, CA 92253
Project Designer:
Gordon Stein
55-053 Sorrel Court
Indio, CA 92201
(760) 773-4488
Report Prepared by:
CITy oF LA Q�ION A
13UILDINGr DIVISION
REVIEWED FOR
CODE
COMPLIANCE
DATE LIE i l� r By
Tim Scott
Scott Design and Title 24, Inc,
74-818 Velie Way, Suite #8
Palm Desert, CA 92260
(760) 200-4780
Job Number:
Date:
12/19/2018
RE "DIVED
DEC 2 12018
CITY OF LA QUANTA
COMMUNITY DEVELOPMENT
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2016 Building Energy Efficiency Standards.
This program developed by EnergySoft Software —www.energysoft.com
C1T�
I TABLE OF CONTENTS
Cover Page 1
Table of Contents 2
Form CF-1 R-PRF-01-E Certificate of Compliance 3
Form RMS-1 Residential Measures Summary 16
Form MF-1 R Mandatory Measures Summary 23
HVAC System Heating and Cooling Loads Summary 27
Room Load Summary 33
Room Heating Peak Loads 39
Room Cooling Peak Loads 46
CERT' XTE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE 'HOD
Project Name: Ratpack Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Calculation Description: Title 24 Analysis
Input File Name: Ratpack Remodel-Stein-18.ribd16x
Cf ''RF-01
Page 1 of 13
GENERAL INFORMATION
01
Project Name
Ratpack
02
Calculation Description
Title 24 Analysis
03
Project Location
53-525 Humbolt Blvd.
04
City
La Quinta
05
Standards Version
Compliance 2017
06
Zip Code
92253
07
Compliance Manager Version
BEMCmpMgr 2016.3.1 (1149)
08
Climate Zone
CZ15
09
Software Version
EnergyPro 7.2
10
Building Type
Single Family
11
Front Orientation (deg/Cardinal)
80
12
Project Scope
Addition and/or Alteration
13
Number of Dwelling Units
1
14
Total Cond. Floor Area (ft2)
8550
15
Number of Zones
7
16
Slab Area (ft)
8550
17
Number of Stories
1
18
Addition Cond. Floor Area (ft)
0
19
Natural Gas Available
Yes
20
Addition Slab Area (ft2)
0
21
Glazing Percentage (%)
41.3%
COMPLIANCE RESULTS
01
Building Complies with Computer Performance
02
This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03
This building incorporates one or more Special Features shown below
ENERGY USE SUMMARY
04
05
06
07
08
Energy Use (kTDV/ft2-yr)
Standard Design
Proposed Design
Compliance Margin
Percent Improvement
Space Heating
7.10
7.11
-0.01
-0.1 %
Space Cooling
121.46
121.09
0.37
0.3%
IAQ Ventilation
0.00
0.00
0.00
0.0%
Water Heating
3.38
3.38
0.00
0.0%
Photovoltaic Offset
--
0.00
0.00
----
Compliance Energy Total
131.94
131.58
0.36
0.3%
Registration Number: 219-Po10266171C-000-000-00o0o00-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERT! \TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE "HOD CF 'RF-01
Project Name: Ratpack Calculation Date/Time: 08:15, Wed, Dec 19, 2018 Page 2 of 13
Calculation Description: Title 24 Analysis Input File Name: Ratpack Remodel-Stein-18.ribd16x
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Cool roof
• Window overhangs and/or fins
• Exposed slab floor in conditioned zone
• Non-standard duct location (any location other than attic)
HERS FEATURE SUMMARY
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
Cooling System Verifications:
• Minimum Airflow
• Verified EER
• Verified SEER
• Verified Refrigerant Charge
• Refrigerant Charge verification required if a refrigerant containing component is altered
• Fan Efficacy Watts/CFM
HVAC Distribution System Verifications:
• Duct Sealing
• Duct Sealing required if a duct system component, plenum, or air handling unit is altered
• Low -leakage Air Handling Unit
Domestic Hot Water System Verifications:
• -- None --
BUILDING - FEATURES INFORMATION
01
02
03
04
05
06
07
Project Name
Conditioned Floor Area (ft2)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
Ratpack
8550
1
6
7
0
1
Registration Number: 218-P010266171C-000-000-0000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERT' NTE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE 'HOD
Project Name: Ratpack Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Calculation Description; Title 24 Analysis
Input File Name: Ratpack Remodel-Stein-18Abd16x
Cl PRF-01
Page 3 of 13
ZONE INFORMATION
01
02
03
04
05
06
07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height
Water Heating System 1
Water Heating System 2
Suite 1
Conditioned
HVAC 1 mstrl
862
10.2
DHW Sys 1
n/a
great room
Conditioned
HVAC 2, 3 & 42
3995
12.1
DHW Sys 1
n/a
2
Conditioned
HVAC 5 & 63
662
10
DHW Sys 1
n/a
3
Conditioned
HVAC 5 & 63
662
10
DHW Sys 1
n/a
guest-4
Conditioned
HVAC 64
753
10
DHW Sys 1
n/a
Cart Garage Zone
Conditioned
HVAC 85
562
10
DHW Sys 1
n/a
2 Car Garage -Renovation
Conditioned
HVAC 7 & 86
1054
10
DHW Sys 1
n/a
Registration Number: 218-P010266171C-000-000-0000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERT' \TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE 'HOD
Project Name: Ratpack Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Calculation Description: Title 24 Analysis
Input File Name: Ratpack Remodel-Stein-18.ribdl6x
Cr 'RF-01
Page 4 of 13
OPAQUE SURFACES
01
02
03
04
05
06
07
08
09
10
11
Name
Zone
Construction
Azimuth
Orientation
Gross Area
(ft2)
Window & Door
Area (ftZ)
Tilt
(deg)
Wall
Exception
Status
Verified
Existing
Condition
80d Wall
Suite 1
R-21 Wall (W21.2x6.16)
80
Front
150
0
90
n/a
Existing
No
170d Wall
Suite 1
R-21 Wall (W.21.2x6.16)
170
Left
720
125.8
90
n/a
Existing
No
260d Wall
Suite 1
R-21 Wall (W21.2x6.16)
260
Back
440
133
90
n/a
Existing
No
350d Wall
Suite 1
R-21 Wall (W21.2x6.16)
350
Right
900
106.2
90
n/a
Existing
No
Interior Surface
Suite 1 —great room
R-0 Interior Wall
424
0
n/a
Existing
No
Roof R-38
Suite 1
R-38 + R13 Roof Attic
862
n/a
Existing
No
80d Wall 2
great room
R-21 Wall (W21.2x6.16)
80
Front
1056
575.6
90
n/a
Existing
No
170d Wall 2
great room
R-21 Wall (W21.2x6.16)
170
Left
575
511.055
90
n/a
Existing
No
260d Wall 2
great room
R-21 Wall (W21.2x6.16)
260
Back
952
715.863
90
n/a
Existing
No
350d Wall 2
great room
R-21 Wall (W21.2x6.16)
350
Right
432
272.3
90
n/a
Existing
No
Interior Surface 2
great room»Suite 1 1
R-0 Interior Wall
424
0
n/a
Existing
No
Roof R-38 2
great room
R-38 + R13 Roof Attic
3995
n/a
Existing
No
170d Wall 3
2
R-21 Wall (W21.2x6.16)
170
Left
230
108.2
90
n/a
Existing
No
260d Wall 3
2
R-21 Wall (W21.2x6.16)
260
Back
320
108
90
n/a
Existing
No
350d Wall 3
2
R-21 Wall (W21.2x6.16)
350
Right
230
88
90
n/a
Existing
No
Interior Surface 3
2»3
R-0 Interior Wall
230
0
n/a
Existing
No
Roof R-38 3
2
R-38 + R13 Roof Attic
662
n/a
Existing
No
80d Wall 3
3
R-21 Wall (W.21.2x6.16)
80
Front
320
88
90
n/a
Existing
No
170d Wall 4
3
R-21 Wall (W21.2x6.16)
170
Left
230
108.173
90
n/a
Existing
No
350d Wall 4
3
R-21 Wall (W21.2x6.16)
350
Right
230
88
90
n/a
Existing
No
Interior Surface 4
3»2
R-0 Interior Wall
230
0
n/a
Existing
No
Roof R-38 4
3
R-38 + R13 Roof Attic
662
n/a
Existing
No
80d Wall 4
guest-4
R-21 Wall (W.21.2x6.16)
80
Front
200
0
90
n/a
Existing
No
170d Wall 5
guest-4
R-21 Wall (W21.2x6.16)
170
Left
330
110.2
90
n/a
Existing
No
260d Wall 4
guest-4
R-21 Wall (W21.2x6.16)
260
Back
200
88.021
90
n/a
Existing
No
350d Wall 5
guest-4
R-21 Wall (W.21.2x6.16)
350
Right
330
77.988
90
n/a
Existing
No
Interior Surface 5
guest-4>>3
R-0 Interior Wall
124
0
n/a
Existing
No
Roof R-38 5
guest-4
R-38 + R13 Roof Attic
753
1 n/a
Existing
No
Registration Number: 218-P010266171C-000-000-0000000-0000 Registration DateMme: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERT' \TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE
Project Name: Ratpack
Calculation Description: Title 24 Analysis
HOD
Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Input File Name: Ratpack Remodel-Stein-18.ribdl6x
CF 'RF-01
Page 5 of 13
80d Wall 5
Cart Garage Zone
R-21 Wall (W21.2x6.16)
80
Front
190
0
90
n/a
Existing
No
170d Wall 6
Cart Garage Zone
R-21 Wall (W21.2x6.16)
170
Left
35
0
90
n/a
Existing
No
260d Wall 5
Cart Garage Zone
R-21 Wall (W.21.2x6.16)
260
Back
350
110.4
90
n/a
Existing
No
350d Wall 6
Cart Garage Zone
R-21 Wall (W21.2x6.16)
350
Right
278
78.4
90
n/a
Existing
No
Interior Surface 6
Cart Garage Zone»great
room
R-0 Interior Wall
292
0
n/a
Existing
No
Roof R-38 6
Cart Garage Zone
R-38 + RI Roof Attic
562
n/a
Existing
No
80d Wall 6
2 Car Garage -Renovation
R-21 Wall (W21.2x6.16)
80
Front
316
160
90
n/a
Existing
No
New 80d Wall
2 Car Garage -Renovation
New R-21 Wall
80
Front
160
0
90
n/a
Existing
No
170d Wall 7
2 Car Garage -Renovation
R-21 Wall (W21.2x6.16)
170
Left
70
0
90
n/a
Existing
No
260d Wall 6
2 Car Garage -Renovation
R-21 Wall (W.21.2x6.16)
260
Back
342
63.8
90
n/a
Existing
No
New 260d Wall
2 Car Garage -Renovation
New R-21 Wall
260
Back
64
0
90
n/a
Existing
No
350d Wall 7
2 Car Garage -Renovation
R-21 Wall (W.21.2x6.16)
350
Right
255
0
90
n/a
Existing
No
Interior Surface 7
2 Car
Garage-Renovation»g uest-4
R-0 Interior Wall
224
0
n/a
Existing
No
Roof R-38 7
2 Car Garage -Renovation I
R-38 + R13 Roof Attic
1054
n/a
Altered
n/a
ATTIC
01
02
03
04
05
06
07
08
09
10
Name
Construction
Type
Roof Rise
Roof
Reflectance
Roof
Emittance
Radiant
Barrier
Cool
Roof
Status
Verified Existing
Condition
Attic Suite 1
Attic RoofSuite 1
Ventilated
3
0.62
0.83
No
Yes
Existing
No
Attic great room
Attic Roofgreat room
Ventilated
3
0.62
0.83
No
Yes
Existing
No
Attic 2
Attic Roof2
Ventilated
3
0.62
0.83
No
Yes
Existing
No
Attic 3
Attic Roof3
Ventilated
3
0.62
0.83
No
Yes
Existing
No
Attic guest-4
Attic Roofgueat-4
Ventilated
3
0.62
0.83
No
Yes
Existing
No
Attic Cart Garage Zone
Attic RoofCartGarage Zone
Ventilated
1 3
1 0.62
1 0.83
1 No
Yes
Existing
No
Attic 2 Car Garage -Renovation
Attic Roof2 Car
Garage -Renovation
Ventilated
3
0.62
0.83
No
Yes
Existing
No
Registration Number: 218-po11)266171C-000-000-D000000-0000 Registration Dateffime: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERTI iTE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE
Project Name: Ratpack
Calculation Description: Title 24 Analysis
HOD
Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Input File Name: Ratpack Remodel-Stein-18.ribdl6x
CF 'RF-01
Page 6 of 13
FENESTRATION I GLAZING
01
02
03
04
05
06
07
08
09
10
11
Name
Surface (Orientation -Azimuth)
Width (ft)
Height (ft)
Multiplier
Area (ft)
U-factor
SHGC
Exterior Shading
Status
Verified
Existing
Condition
D2
170d Wall (Left-170)
4.1
10.0
1
41.0
0.37
0.26
Insect Screen (default)
Existing
No
22
170d Wall (Left-170)
5.3
j 10.0
1
53.0
0.46
0.31
Insect Screen (default)
Existing
No
D3
170d Wall (Left-170)
10.6
3.0
1
31.8
0.37
0.26
Insect Screen (default)
Existing
No
21
260d Wall (Back-260)
13.3
10.0
1
133.0
0.46
0.31
Insect Screen (default)
Existing
No
D1
350d Wall (Right-350)
--
-
1
30.2
0.37
0.26
Insect Screen (default)
Existing
No
20
350d Wall (Right-350)
----
1
64.0
0.46
0.31
Insect Screen (default)
Existing
No
C2
350d Wall (Right-350)
1
12.0
0.50
0.20
Insect Screen (default)
Existing
No
01
80d Wall 2 (Front-80)
5.0
11.0
1
55.0
0.94
0.49
Insect Screen (default)
Existing
No
58
80d Wall 2 (Front-80)
21.5
10.0
2.2
473.0
0.46
0.31
Insect Screen (default)
Existing
No
G4
80d Wall 2 (Front-80)
-
-
1
47.6
1 0.37
0.26
Insect Screen (default)
Existing
No
04
170d Wall 2 (Left-170)
----
----
1
178.0
0.46
0.31
Insect Screen (default)
Existing
No
A
170d Wall 2 (Left-170)
5.0
11.0
2.335
128.4
0.37
0.26
Insect Screen (default)
Existing
No
23
170d Wall 2 (Left-170)
7.0
11.0
1
77.0
0.76
0.18
Insect Screen (default)
Existing
No
E2
170d Wall 2 (Left-170)
6.3
15.1
1
95.1
0.37
0.26
Insect Screen (default)
Existing
No
G2
170d Wall 2 (Left-170)
-
----
1
16.1
0.37
0.26
Insect Screen (default)
Existing
No
G3
170d Wall 2 (Left-170)
---
----
1
16.4
0.37
0.26
Insect Screen (default)
Existing
No
24
260d Wall 2 (Back-260)
473.0
11.0
0.091
473.5
0.46
0.31
Insect Screen (default)
Existing
No
G1
260d Wall 2 (Back-260)
--
-
1
47.6
0.37
0.26
Insect Screen (default)
Existing
No
E1
260d Wall 2 (Back-260)
12.9
15.1
1
194.8
0.37
0.26
Insect Screen (default)
Existing
No
B
350d Wall 2 (Right-350)
-
-
1
177.0
0.37
0.26
Insect Screen (default)
Existing
No
G5
350d Wall 2 (Right-350)
-
1
55.0
0.37
0.26
Insect Screen (default)
Existing
No
G6
350d Wall 2 (Right-350)
----
-
1
23.8
0.37
0.26
Insect Screen (default)
Existing
No
C1
350d Wall 2 (Right-350)
----
1
16.5
0.50
0.20
Insect Screen (default)
Existing
No
32
170d Wall 3 (Left-170)
-
--
1
78.0
0.46
0.31
Insect Screen (default)
Existing
No
F1
170d Wall 3 (Left-170)
-
----
1
30.2
0.37
0.26
Insect Screen (default)
Existing
No
28
260d Wall 3 (Back-260)
10.8
10.0
1
108.0
0.46
0.31
Insect Screen (default)
Existing
No
27
350d Wall 3 (Right-350)
5.3
10.0
1
53.0
0.46
0.31
Insect Screen (default)
Existing
No
26
350d Wall 3 (Right-350)
3.5
10.0
1
35.0
0.46
1 0.31
Insect Screen (default)
Existing
No
Registration Number: 218-Po10266171C-000-000-0000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERTI iTE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE
Project Name: Ratpack
Calculation Description: Title 24 Analysis
•m0
Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Input File Name: Ratpack Remodel-Stein-18.ribd16x
CF 'RF-01
Page 7 of 13
37
80d Wall 3 (Front-80)
--
1
88.0
0.46
0.31
Insect Screen (default)
Existing
No
F2
170d Wall 4 (Left-170)
----
-
1
30.2
0.37
0.26
Insect Screen (default)
Existing
No
42
170d Wall 4 (Left-170)
7.9
10.0
0.987
78.0
0.46
0.31
Insect Screen (default)
Existing
No
35
350d Wall 4 (Right-350)
3.5
10.0
1
35.0
0.46
0.31
Insect Screen (default)
Existing
No
36
350d Wall 4 (Right-350)
5.3
1 10.0
1
53.0
10.46
0.31
Insect Screen (default)
Existing
No
50
170d Wall 5 (Left-170)
-
-
1
80.0
0.46
0.31
Insect Screen (default)
Existing
No
F3
170d Wall 5 (Left-170)
-
1
30.2
0.37
0.26
Insect Screen (default)
Existing
No
45
260d Wall 4 (Back-260)
8.9 1
10.0
0.989
88.0
0.46
0.31
Insect Screen (default)
Existing
No
44
350d Wall 5 (Right-350)
4.4
10.0
0.977
43.0
0.46
0.31
Insect Screen (default)
Existing
No
43
350d Wall 5 (Right-350)
3.5
10.0
1
35.0
0.46
0.31
Insect Screen (default)
Existing
No
55
80d Wall 6 (Front-80)
8.0
10.0
1
80.0
0.46
0.31
Insect Screen (default)
New
n/a
59
80d Wall 6 (Front-80)
8.0
10.0
1
80.0
0.46
0.31
Insect Screen (default)
New
n/a
New 19.9X2
260d Wall 6 (Back-260)
19.9
2.0
1
39.8
0.37
0.26
Insect Screen (default)
New
n/a
New 12X2
260d Wall 6 (Back-260)
12.0
2.0
1
24.0
0.37
0.26
Insect Screen (default)
New
n/a
OPAQUE DOORS
01
02
03
04
05
06
Name
Side of Building
Area (ft)
U-factor
Status
Verified Existing Condition
Door 08
260d Wall 5
110.4
0.08
Existing
No
Door 09
350d Wall 6
78.4
0.08
Existing
No :J
Registration Number: 218-Po10266171C-000-000-0000000-0000 Registration DateRme: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERTI XE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE HOD CF 'RF-01
Project Name: Ratpack
Calculation Description: Title 24 Analysis
Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Input File Name: Ratpack Remodel-Stein-18.ribd16x
Page 8 of 13
OVERHANGS AND FINS
01
02
03
04
05
06
07
08
og
10
11
12
13
14
Overhang
Left Fin
Right Fin
Window
Depth
Dist Up
Left
Extent
Right
Extent
Flap Ht.
Depth
Top Up
Dist L
Bot Up
Depth
Top Up
Dist R
Bot Up
D2
4
0.1
4
4
0
0
0
0
0 1
0
0
0
0
22
4
0.1
4
4
0
0
0
0
0
0
0
0
0
D3
4
0.1
4
4
0
0
0
0
0
0
0
0
0
21
4
0.1
4
4
0
0
0
0
0
0
0
0
0
01
4
0.1
4
4
0
0
0
0
0
0
0
0
0
58
12
0.1
12
12
0
0
0
0
0
0
0
0
0
A
4
0.1
4
4
0
0
0
0
0
0
0
0
0
23
8
0.1
8
8
0
0
0
0
0
0
0
0
0
E2
10
0.1
10
10
0
0
0
0
0
0
0
0
0
24
12
0.1
12
12
0
0
0
0
0
0
0
0
0
E1
10
0.1
10
10
0
0
0
0
0
0
0
0
0
28
4
0.1
4
4
0
0
0
0
0
0
0
0
0
27
4
0.1
4
4
0
0
0
0
0
0
0
0
0
26
8
0.1
8
8
0
0
0
0
0
0
0
0
0
42
10
0.1
10
10
0
0
0
0
0
0
0
0
0
35
8
0.1
8
8
0
0
0
0
0
0
0
0
0
36
4
0.1
4
4
0
0
0
0
0
0
0
0
0
45
4
0.1
4
4
0
0
0
0
0
0
0
0
0
44
4
0.1
4
4
0
0
0
0
0
0
0
0
0
43
4
0.1
4
4
0
0
0
0
0
0
0
0
0
55
4
0.1
4
4
0
0
0
0
0
0
0
0
0
59
4
0.1
4
4
0
0
0
0
0
0
0
0
0
New 19.9X2
4
0.1
4
4
0
0
0
0
0
0
0
0
0
New 12X2
4
0.1
4
11 4
0
0
0
1 0
0
0
1 0
0
0
Registration Number: 218-Po10266171C-000-000-0000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERTI ATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE
Project Name: Ratpack
Calculation Description: Title 24 Analysis
'HOD
Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Input File Name: Ratpack Remodel-Stein-18.ribdl6x
CF 'RF-01
Page 9 of 13
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
07
Total Cavity
Winter Design
Construction Name
Surface Type
Construction Type
Framing
R-value
U-factor
Assembly Layers
Cavity/Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic RoofSuite 1
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing. Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
Ceilings (below
Cavity/Frame: R-9.1 /2x4
R-38 + R13 Roof Attic
attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 38
0.025
Over Ceiling Joists: R-28.9 insul.
• Inside Finish: Gypsum Board
• Cavity/Frame: R-21 /2x6
R-21 Wall (W21.2x6.16)
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
0.069
• Exterior Finish: 3 Coat Stucco
• Inside Finish: Gypsum Board
• Cavity/Frame: no insul. /2x4
R-0 Interior Wall
Interior Walls
Wood Framed Wall
2x4 @ 16 in. O.C.
none
0.277
• Other Side Finish: Gypsum Board
• Cavity/Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
• Roof Deck. Wood Siding/sheathing/decking
Attic Roofgreat room
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
• Roofing: Light Roof (Asphalt Shingle)
• Cavity/Frame: no insuL /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
• Roof Deck: Wood Siding/sheathing/decking
Attic Roof2
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
• Roofing: Light Roof (Asphalt Shingle)
• Cavity/Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
• Roof Deck: Wood Siding/sheathing/decking
Attic Roof3
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
• Roofing. Light Roof (Asphalt Shingle)
• Cavity/Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic Roofguest-4
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing. Light Roof (Asphalt Shingle)
Cavity/Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic RoofCart Garage Zone
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
• Cavity/Frame: no insul. /2x4 Top Chrd
Attic Roof2 Car
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Garage -Renovation
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing., Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
Cavity/Frame: R-21 /2x6
New R-21 Wall
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
0.069
Exterior Finish: 3 Coat Stucco
Registration Number: 218_Po10266171C-000-000-0000000-0000 Registration Date/Time. HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERTI ATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE , HOD
Project Name: Ratpack Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Calculation Description: Title 24 Analysis
Input File Name: Ratpack Remodel-Stein-18.ribdl6x
CF . PRF-01
Page 10 of 13
SLAB FLOORS
01
02
03
04
05
06
07
08
09
Name
Zone
Area (ft)
Perimeter
(ft)
Edge Insul. R-value
Carpeted
Fraction
Heated
Status
Verified
Existing
Condition
Covered Slab
Suite 1
862
100
None
0.8
No
Existing
No
Covered Slab 2
great room
3995
88
None
0.8
No
Existing
No
Covered Slab 3
2
662
83
None
0.8
No
Existing
No
Covered Slab 4
3
662
83
None
0.8
No
Existing
No
Covered Slab 5
guest-4
753
121
None
0.8
No
Existing
No
Covered Slab 6
Cart Garage Zone
562
85
None
0
No
Existing
No
Covered Slab 7
2 Car Garage -Renovation
1054
120
None
0
No
Existing
No
BUILDING ENVELOPE - HERS VERIFICATION
01
02
03
04
Quality Insulation Installation (QII)
Quality Installation of Spray Foam Insulation
Building Envelope Air Leakage
CFM50
Not Required
Not Required
Not Required
n/a
WATER HEATING SYSTEMS
01
02
03
04
05
06
07
08
Name
System Type
Distribution Type
Water Heater
Number of
Heaters
Solar
Fraction
N
Status
Verified Existing
Condition
DHW Sys 1
DHW
Standard
DHW Heater 1
2
0
Existing
No
WATER HEATERS
01
02
03
04
05
06
07
08
09
10
11
12
Name
Heater
Element
Type
Tank Type
Number
of Units
Tank
Volume
(gal)
Uniform Energy
Factor / Energy
Factor / Efficiency
Input Rating /
Pilot /
Thermal
Efficiency
Tank
Insulation
R-value
(Int/Ext)
Standby
Loss /
Recovery
Eff
First Hour
Rating /
Flow Rate
NEEA Heat Pump
Brand / Model
Tank Location
or Ambient
Condition
DHW Heater 1
Gas
Small Storage
2
50
0.66 EF
<= 75 kBtu/hr
0
n/a
n/a
n/a
n/a
Registration Number: 218-Po10266171C-000-000-0000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERTI' TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE ' HOD
Project Name: Ratpack Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Calculation Description: Title 24 Analysis
Input File Name: Ratpack Remodel-Stein-18.ribd16x
CF `RF-01
Page 11 of 13
SPACE CONDITIONING SYSTEMS
01
02
03
04
05
06
07
08
Distribution
Verified Existing
SC Sys Name
System Type
Heating Unit Name
Cooling Unit Name
Fan Name
Name
Status
Condition
HVAC 1 mstrl
Other Heating and Cooling
Heating Component 1
Cooling Component 1
HVAC Fan 1
Air Distribution
Existing
No
System
System 1
HVAC 2. 3 & 42
Other Heating and Cooling
Heating Component 2
Cooling Component 2
HVAC Fan 2
Air Distribution
Existing
No
System
System 2
HVAC 5 & 63
Heat Pump Heating and
Cooling System
Heat Pump System 3
Heat Pump System 3
HVAC Fan 3
Air Distribution
System 3
Existing
No
HVAC 64
Heat Pump Heating and
Cooling System
Heat Pump System 4
Heat Pump System 4
HVAC Fan 4
Air Distribution
System 4
Existing
No
HVAC 85
Heat Pump Heating and
Heat Pump System 5
Heat Pump System 5
HVAC Fan 5
Air Distribution
Existing
No
Cooling System
System 5
HVAC 7 & 86
Heat Pump Heating and
Cooling System
Heat Pump System 6
Heat Pump System 6
HVAC Fan 6
Air Distribution
System 6
Altered
No
HVAC - HEAT PUMPS
01
02
03
04
05
1 06
07
1 08
09
10
11
Name
System
Type
Number of
Units
Heating
HSPF/COP Cap 47 Cap 17
Cooling
SEER EER
Zonally
Controlled
Compressor
Type
HERS
Verification
Heat Pump System 6
SplitHeatPump
2
10
26000
15600
1 19,7712
Zonally
Controlled
Single Speed
Heat Pump System
6-hers-cool
HVAC COOLING - HERS VERIFICATION
01
02
03
04
05
06
Name
Verified Airflow
Airflow Target
Verified EER
Verified SEER
Verified Refrigerant
Charge
Heat Pump System 6-hers-cool
Required
150
Required
Required
Required
Registration Number: 218-Po10266171C-000-000-0000000-0000 Registration Dateffime: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERT! 1TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE
Project Name: Ratpack
Calculation Description: Title 24 Analysis
HOD
Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Input File Name: Ratpack Remodel-Stein-18.ribd16x
CF aRF-01
Page 12 of 13
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
08
09
10
Insulation
Supply Duct
Return Duct
Verified Existing
HERS
Name
Type
Duct Leakage
R-value
Location
Location
Bypass Duct
Status
Condition
Verification
Air Distribution
Ducts located entirely in
Existing (not
8'0
Conditioned
Conditioned
None
Existing
No
n/a
System 1
conditioned space
specified)
Zone
Zone
Air Distribution
Ducts located entirely in
Existing (not
8'0
Conditioned
Conditioned
None
Existing
No
Na
System 2
conditioned space
specified)
Zone
Zone
Air Distribution
Ducts located entirely in
Existing (not
Conditioned
Conditioned
System 3
conditioned space
specified)
8'0
Zone
Zone
None
Existing
No
n/a
Air Distribution
Ducts located entirely in
Existing (not
8'0
Conditioned
Conditioned
None
Existing
No
n/a
System 4
conditioned space
specified)
Zone
Zone
Air Distribution
Ducts located entirely in
Existing (not
8'0
Conditioned
Conditioned
None
Existing
No
Na
System 5
conditioned space
specified)
Zone
Zone
Air Distribution
Ducts located in attic
Specified Lower
Air Distribution
System 6
(Ventilated and
Leakage Target
8.0
Attic
Attic
None
New
No
System
Unventilated)
6-hers-dist
HVAC DISTRIBUTION - HERS VERIFICATION
01
02
03
04
05
06
07
08
Name
Duct Leakage
Verification
Duct Leakage
Target (%)
Verified Duct
Location
Verified Duct
Design
Buried
Ducts
Deeply Buried
Ducts
Low -leakage
Air Handler
Air Distribution System 6-hers-dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
Required
HVAC - FAN SYSTEMS & HERS VERIFICATION
01
02
03
04
Name
Type
Fan Power (Watts/CFM)
HERS Verification
HVAC Fan 6
Single Speed PSC Furnace Fan
0.58
Required
IAQ (Indoor Air Quality) FANS
01
02
03
04
05
06
Dwelling Unit
IAQ CFM
IAQ Watts/CFM
IAQ Fan Type
IAQ Recovery
Effectiveness(%)
HERS Verification
SFam IAQVentRpt
0
0.25
Default
0
Not Required
PROJECT NOTES
The Madison Club
Registration Number: 218-P010266171C-000-000-0000000-0000 Registration Date/Time: HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
CERTI TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE
Project Name: Ratpack
Calculation Description: Title 24 Analysis
Calculation Date/Time: 08:15, Wed, Dec 19, 2018
Input File Name: Ratpack Remodel-Stein-1 8. ribd 1 6x
CF IRF-01
Page 13 of 13
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Tim Scott
Company:
Signature Date:
Scott Design and Title 24, Inc.
Address:
CEA/HERS Certification Identification (If applicable).
77085 Michigan Drive
City/State/Zip:
Phone:
Palm Desert, CA 92211
760-200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of Califomia:
1. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2. I certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
Responsible Designer Name:
Responsible Designer Signature:
�
Tim Scott
Company:
Date Signed:
Scott Design and Title 24, Inc.
Address:
License-
77085 Michigan Drive
NA
City/State/Zip:
Phone:
Palm Desert, CA 92211
760-200-4780
Digitally signed by CaICERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration
Provider responsibility for the accuracy of the information.
Easy to Verify
at CaICERTS.com
Registration Number: 218-Po10266171C-000-000-0000000-0000 Registration Dateffime: HERS Provider: CalCERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-12-19 08:17:13
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
Ratpack Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
California Energy Climate Zone Total Cond. Floor Area Addition
CA Climate Zone 15 8,550 n/a
Date
11211912018
# of Units
1
Project Address
53-525 Humbolt Blvd. La Quinta
INSULATION
Construction Type
Cavity
Area
(ft) Special Features
Status
Roof Wood Framed Attic
R 38
862 Cool Roof
Existing
Wall Wood Framed
R 21
150
Existing
Wall Wood Framed
R 21
594
Existing
Wall Wood Framed
R 21
307
Existing
Wall Wood Framed
R 21
794
Existing
Slab Unheated Slab -on -Grade
no insulation
862 Perim = 100'
Existing
Demising Wood Framed
- no insulation
424
Existing
Roof Wood Framed Attic
R 38
3,995 Cool Roof
Existing
FENESTRATION
Orientation Area ff
Total Area: 3,528 Glazing Percentage: 41.3 °%
U-Fac SHGC Overhang Sidefins
NewlAItered Avers a U-Factor.
Exterior Shades
0.4$
Status
Left (S) 201.2
0.370
0.26 4.0
none
Bug Screen
Existing
Left (S) 53.0
0.460
0.31 4.0
none
Bug Screen
Existing
Rear (W) 329.0
0.460
0.31 4.0
none
Bug Screen
Existing
Right (N) 286.0
0.370
0.26 none
none
Bug Screen
Existing
Right (N) 64.0
0.460 0.31 none
none
Bug Screen
Existing
Right (N) 28.5
0.500 0.20 none
none
Bug Screen
Existing
Front (E) 55.0
0.940 0.49 4.0
none
Bug Screen
Existing
Front (E) 473.0
0.460 0.31 12.0
none
Bug Screen
Existing
Front (E) 47.6
0.370 0.26 none
none
Bug Screen
Existing
Left (S) 336.0
0.460 0.31 none
none
Bug Screen
Existing
Left (S) 77.0
0.760 0.18 8.0
none
Bug Screen
Existing
Left (S) 95.1
0.370 0.26 10.0
none
Bug Screen
Existing
Left (S) 123.1
0.370 0.26 none
none
Bug Screen
Existing
Rear (W) 473.0
0.460 0.31 12.0
none
Bug Screen
Existing
HVAC SYSTEMS
Qty. Heating
Min. Eff
Cooling
Min. Eff
Thermostat
Status
1 Central Furnace
3 Central Furnace
80% AFUE
80% AFUE
Split Air Conditioner 16.0 SEER
Split Air Conditioner 16.0 SEER
Setback
Setback
Existing
Existing
2 Split Heat Pump 10.00 HSPF
HVAC DISTRIBUTION
Location Heating
Split Heat Pump 17.7 SEER
Cooling Duct Location
Setback
Duct
R-Value
Existing
Status
HVAC 1 mstr Ducted
Ducted
Conditioned
8.0
Existing
HVAC 2, 3 & 4 Ducted
Ducted
Conditioned
8.0
Existing
HVAC 5 & 6 Ducted
Ducted
Conditioned
8.0
Existing
WATER HEATING
Qty. Type
Gallons Min. Eff Distribution
Status
Emerc • Pro 7.2 by EneCqySoft User Number: 6712
ID:
Page 16 of 53
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
Ratpack Residence
TBuilding Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1211912018
Project Address
53-525 Humbolt Blvd. La Quinta
f California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
8,550
Addition
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity ft) Special Features Status
Wall Wood Framed
R 21 480
Existing
Wall Wood Framed
R 21 64
Existing
Wall Wood Framed
R 21 237
Existing
Wall Wood Framed
R 21 160
Existing
Slab Unheated Slab -on -Grade
no insulation 3,995 Perim = 88'
Existing
Demising Wood Framed
no insulation 424
Existing
Roof Wood Framed Attic
R 38 662 Cool Roof
Existing
Wall Wood Framed
R 21 122
Existing
FENESTRATION
Orientation Area(ft2)
Total Area: 3.528 Glazing Percentage: 41.3 %
U-Fac SHGC Overhang Sidefins
NewlAltered Average U-Factor: 0.43
Exterior Shades Status
Rear (W) 47.6
0.370
0.26 none none
Bug Screen Existing
Rear (W) 194.8
0.370
0.26 10.0 none
Bug Screen Existing
Right (N) 184.0
0.460
0.31 4.0 none
Bug Screen Existing
Right (N) 70.0
0.460
0.31 8.0 none
Bug Screen Existing
Front (E) 88.0
0.460
0.31 none none
Bug Screen Existing
Left (S) 78.0
0.460
0.31 10.0 none
Bug Screen Existing
Front (E) 160.0
0.460
0.31 4.0 none
Bug Screen New
Rear (W) 63.8
0.370
0.26 4.0 none
Bug Screen New
HVAC SYSTEMS
Qty. Heating
Min. Eff
Cooling Min. Eff
Thermostat Status
1 Split Heat Pump
10.00 HSPF
Split Heat Pump 19.7 SEER
Setback Existing
1 Split Heat Pump
11.30 HSPF
Split Heat Pump 18.0 SEER
Setback Existing
2 Split Heat Pump 10.00 HSPF
HVAC DISTRIBUTION
Location Heating
Split Heat Pump 19.7 SEER
Cooling Duct Location
Setback Altered
Duct
R-Value Status
HVAC 6 Ducted
Ducted Conditioned
8.0 Existing
HVAC 8 Ducted
Ducted Conditioned
8.0 Existing
HVAC 7 & 8 Ducted
WATER HEATING
Qty. Type
Ducted Attic 8.0 New
Gallons Min. Eff Distribution Status
Enero Pro 7.2 by EnerqySoft User Number: 6712
ID: Pace 17 of 53
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
Ratpack Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
California Energy Climate Zone Total Cond. Floor Area Addition
CA Climate Zone 15 8,550 n/a
Date
1211912018
# of Units
1
Project Address
53-525 Humbolt Blvd. La Quinta
INSULATION
Construction Type
Cavity
Area
(ft) Special Features
Status
Wall Wood Framed R 21
Wall Wood Framed R 21
212
142
Existing
Existing
Slab Unheated Slab -on -Grade no insulation
662 Perim = 83'
Existing
Demising Wood Framed no insulation
230
Existing
Roof Wood Framed Attic R 38
662 Cool Roof
Existing
Wall Wood Framed R 21
232
Existing
Wall Wood Framed R 21
122
Existing
Wall Wood Framed R 21
142
Existing
FENESTRATION Total Area: 3.528 GlazinR Percentage: 41.3 %J NewlAltered Average U-Factor:
Orientation Area ft2 U-Fac SHGC Overhang Sidefins Exterior Shades
0.113
Status
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling
Min. Eff Thermostat
Status
HVAC DISTRIBUTION
Location Heating
Cooling
Duct
Duct Location R-Value
Status
WATER HEATING
Qty. Type Gallons Min. Eff Distribution
Status
EnarqyPfo 7.2 by EneraySaft User Number., 6712
ID:
Pape 18 of 53
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
Ratpack Residence
Building Type
m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
11211912018
Project Address
53-525 Humbolt Blvd. La Quinta
California Energy Climate Zone I Total Cond. Floor Area
CA Climate Zone 15 8,550
Addition
n/a
# of Units
1
INSULATION
Construction Type
Cavity
Area
ftz S ecial Features
Status
Slab Unheated Slab -on -Grade no insulation
662 Perim = 83'
Existing
Demising Wood Framed
no insulation
230
Existing
Roof Wood Framed Attic R 38
753 Cool Roof
Existing
Wall Wood Framed R 21
200
Existing
Wall Wood Framed R 21
220
Existing
Wall Wood Framed R 21
112
Existing
Wall Wood Framed R 21
252
Existing
Slab Unheated Slab -on -Grade - no insulation
753 Perim = 121'
Existing
FENESTRATION Total Area: 3,528 Glazing Percentage: 4T•3 % New/Altered Average U-Factor:
Orientation Area(ft2) U-Fac SHGC Overhang Sidefins Exterior Shades
0.43
Status
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling
Min. Eff Thermostat
Status
HVAC DISTRIBUTION
Location Heating
Cooling
Duct
Duct Location R-Value
Status
WATER HEATING
Qty. Type Gallons Min. Eff Distribution
Status
Ener Pro 7.2 by EnerqySoft User Number: 6712
ID:
Page 19 of 53
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
Ratpack Residence
Building Type
10 Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1211912018
Project Address
53-525 Humbolt Blvd. La Quinta
California Energy Climate Zone Total Cond. Floor Area Addition
CA Climate Zone 15 8,550 n/a
Of of Units
1
INSULATION
Construction Type
Cavity
Area
ft Special Features
Status
Demising Wood Framed - no insulation
124
Existing
Roof Wood Framed Attic R 38
562 Cool Roof
Existing
Wall Wood Framed R 21
190
Existing
Wall Wood Framed R 21
35
Existing
Wall Wood Framed R 21
Door Opaque Door - no insulation
240
110 Add=R-12.0
Existing
Existing
Wall Wood Framed R 21
200
Existing
Door Opaque Door -
no insulation
78 Add=R-12.0
Existing
FENESTRATION I Totat Area: 3.528 Glazing Percentage: 41.3 % New/Altered Average U-Factor:
Orientation Area(ft2) U-Fac SHGC Overhang Sidefins Exterior Shades
0.43
Status
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling
Min. Eff Thermostat
Status
HVAC DISTRIBUTION
Location Heating
Cooling
Duct
Duct Location R-Value
Status
WATER HEATING
Qty. Type Gallons Min. Eff Distribution
Status
EnenqyPro 7.2 by Enerp Soft User Number: 6712
ID:
Page 20 of 53
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
Ratpack Residence
Project Address
53-525 Humbolt Blvd. La Quinta
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
1211912018
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
8,550
Addition
n/a
# of Units
1
INSULATION
Construction Type
Cavity
Area
ft Special Features Status
Slab Unheated Slab -on -Grade no insulation
562 Perim = 85' Existing
Demising Wood Framed no insulation
292 Existing
Roof Wood Framed Attic R 38
1,054 Cool Roof Altered
Wall Wood Framed R 21
156 Existing
Wall Wood Framed R 21
160 Existing
Wall Wood Framed R 21
70 Existing
Wall Wood Framed R 21
278 Existing
Wall Wood Framed R 21
64 Existing
FENESTRATION I Total Area: 3,528 Glazing Percentage: 41.3 VolNew/Altered Average U-Factor. 0.43
Orientation Area ft2 U-Fac SHGC Overhang Sidefins Exterior Shades Status
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling
Min. Eff Thermostat Status
HVAC DISTRIBUTION
Location Heating
Cooling
Duct
Duct Location R-Value Status
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
Ewer Pro 7.2 by EnetlqySoft User Number.- 6712
ID: Pape 21 of 53
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
Ratpack Residence
Project Address
53-525 Humbolt Blvd. La Quinta
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
California Energy Climate Zone Total Cond. Floor Area Addition
CA Climate Zone 15 8,550 n/a
Date
11211912018
# of Units
1
INSULATION
Construction Type
Area
Cavity ft Special Features
Status
Wall Wood Framed
R 21 255
Existing
Slab Unheated Slab -on -Grade
- no insulation 1, 054 Perim = 120'
Existing
Demising Wood Framed
- no insulation 224
Existing
FENESTRATION I Total Area: 3,528 t3lazin Percentage: 41.3 % New/Altered Average U-Factor.
Orientation Area U-Fac SHGC Overhang Sidefins Exterior Shades
0.43
Status
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling Min. Eff Thermostat
Status
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R-Value
Status
WATER HEATING
Qty. Type Gallons Min. Eff Distribution
Status
EnergyPro 7.2 by EnerqvSoft User Number: 6712
ID:
Page 22 of 53
2016 Low -Rise Residential Mandatory Measures Summary
NOTE: Low-rise residential buildings subject to the Energy Standards must comply with all applicable mandatory measures, regardless of the compliance approach
used. Review the respective section for more information. 'Exceptions may apply.
(Revised 04/20171
Building Envelope Measures:
§ 110.6(a)1:
Air Leakage. Manufactured fenestration, exterior doors, and exterior pet doors must limit air leakage to 0.3 cfm/ft2 or less when tested per
NFRC-400 or ASTM E283 or AAMA/WDMA/CSA 10l/I.S.2/A440-2011.'
§ 110.6(a)5:
Labeling. Fenestration products must have a label meeting the requirements of § 10-111(a).
§ 110.6(b):
Field fabricated exterior doors and fenestration products must use U-factors and solar heat gain coefficient (SHGC) values from TABLES
110.6-A and 110.6-B for compliance and must be caulked and/or weatherstri ed.'
§ 110.7:
Air Leakage. All joints, penetrations, and other openings in the building envelope that are potential sources of air leakage must be caulked,
aasketed. or weather striooed. _
§ 110.8(a):
Insulation Certification by Manufacturers. Insulation specified or installed must meet Standards for Insulating Material,
§ 110.8(g):
Insulation Requirements for Heated Slab Floors. Heated slab floors must be insulated per the requirements of § 110.8(g).
§ 110.8(i):
Roofing Products Solar Reflectance and Thermal Emittance. The thermal emittance and aged solar reflectance values of the roofing
material must meet the requirements of ,110.8 when the installation of a cool roof is specified on the CF1 R.
§ 110.80):
Radiant Barrier. A radiant barrier must have an emittance of 0.05 or less and be certified to the Department of Consumer Affairs
Ceiling and Rafter Roof Insulation. Minimum R-22 insulation in wood -frame ceiling; or the weighted average U-factor must not exceed 0.043.
Minimum R-19 or weighted average U-factor of 0.054 or less in a rafter roof alteration. Attic access doors must have permanently attached
§ 150.0(a):
insulation using adhesive or mechanical fasteners. The attic access must be gasketed to prevent air leakage. Insulation must be installed in
direct contact with a continuous roof or ceiling which is sealed to limit infiltration and exfiltration as specified in § 110.7, including but not limited
to placing insulation either above or below the roof deck or on top of a drywall ceiling.'
§ 150.0(b):
Loose -fill Insulation. Loose fill insulation must meet the manufacturer's required density for the labeled R-value.
Above Grade Wall Insulation. Minimum R-13 insulation in 2x4 inch wood framing wall or have a U-factor of 0.102 or less (R-19 in 2x6 or U-
§ 150.0(c):
factor of 0.074 or less). Opaque non -framed assemblies must have an overall assembly U-factor not exceeding 0.102, equivalent to an installed
value of R-13 in a wood framed assembly.'
§ 150.0(d):
Raised -floor Insulation. Minimum R-19 insulation in raised wood framed floor or 0.037 maximum U-factor.'
§ 150.0(f):
Slab Edge Insulation. Slab edge insulation must meet all of the following: have a water absorption rate, for the insulation material alone without
facings, no greater than 0.3%; have a water vapor permeance no greater than 2.0 perm/inch; be protected from physical damage and UV light
deterioration; and, when installed as part of a heated slab floor, meet the requirements of § 110.8(g).
Vapor Retarder. In Climate Zones 1-16, the earth floor of unvented crawl space must be covered with a Class I or Class II vapor retarder. This
§ 150.0(g)1:
requirement also applies to controlled ventilation crawls ace for buildings oomplyIng with the exception to § 150.0(d).
Vapor Retarder. In Climate Zones 14 and 16, a Class I or Class II vapor retarder must be installed on the conditioned space side of all
§ 150.0(g)2:
insulation in all exterior walls vented attics and unvented attics with air -permeable insulation.
150.0
§ (q)'
Fenestration Products. Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors must have a
maximum U-factor of 0.58; or the weighted average U-factor of all fenestration must not exceed 0.58.'
Fireplaces, Decorative Gas Appliances, and Gas Log Measures:
§ 150.0(e)1A:
Closable Doors. Masonry or factory -built fireplaces must have a closable metal or glass door covering the entire opening of the firebox.
§ 150.0(e)l B:
Combustion Intake. Masonry or factory -built fireplaces must have a combustion outside air intake, which is at least six square inches in area
and is equipped with a readily accessible, operable, and tight -fitting dam er or combustion -air control device.'
§ 150.0(e)l C:
Flue Damper. Masonry or factory -built fireplaces must have a flue damper with a readily accessible control.'
§ 150.0(e)2:
Pilot Light. Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of
the building, are prohibited.
Space Conditioning, Water Heating, and Plumbing System Measures:
§ 110.0-§ 110.3:
Certification. Heating, ventilation and air conditioning (HVAC) equipment, water heaters, showerheads, faucets, and all other regulated
appliances must be certified b.y the manufacturer to the Energy Commission.'
§ 110.2(a):
HVAC Efficiency. Equipment must meet the applicable efficiency requirements in TABLE 110.2-A through TABLE 110.2-K.'
Controls for Heat Pumps with Supplementary Electric Resistance Heaters. Heat pumps with supplementary electric resistance heaters
§ 110.2(b):
must have controls that prevent supplementary heater operation when the heating load can be met by the heat pump alone; and in which the
cut -on temperature for compression heating is higher than the cut -on temperature for supplementary heating, and the cut-off temperature for
compression heating, is higher than the cut-off temperature for supplementary heating.'
§ 110.2(c):
Thermostats. All unitary heating or cooling systems not controlled by a central energy management control system (EMCS) must have a
setback thermostat.'
Water Heating Recirculation Loops Serving Multiple Dwelling Units. Water heating recirculation loops serving multiple dwelling units must
§ 110.3(c)5:
meet the air release valve, backflow prevention, pump priming, pump isolation valve, and recirculation loop connection requirements of §
110.3(c)5.
§ 110.3(c)7:
Isolation Valves. Instantaneous water heaters with an input rating greater than 6.8 kBTU/hr (2 kW) must have isolation valves with hose bibbs
or other fittings on both cold water and hot water lines of water heating systems to allow for water tank flushing when the valves are closed.
§ 110.5:
Pilot Lights. Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces; household cooking appliances (appli-
ances without an electrical supply voltage conneclian w€th p1lot tights that consume less than 150 Btu/hr are exempt): and pool and sa heaters'
Building Cooling and Heating Loads. Heating and/or cooling loads are calculated in accordance with ASHRAE Handbook, Equipment
§ 150.0(h)1:
Volume, Applications Volume, and Fundamentals Volume; SMACNA Residential Comfort System Installation Standards Manual; or ACCA
Manual J using desi n conditions specified in § 150.0 h 2.
2016 Low -Rise Residential Mandatory Measures Summary
§ 150.0(h)3A:
Clearances. Installed air conditioner and heat pump outdoor condensing units must have a clearance of at least 5 feet from the outlet of any
dryer vent.
§ 150.0(h)3B:
Liquid Line Drier. Installed air conditioner and heat pump systems must be equipped with liquid line filter driers if required, as specified by
manufacturer's instructions.
§ 150.00)1:
Storage Tank Insulation. Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, must have
R-12 external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank.
Water piping and cooling system line insulation. For domestic hot water system piping, whether buried or unburied, all of the following must
be insulated according to the requirements of TABLE 120.3-A: the first 5 feet of hot and cold water pipes from the storage tank; all piping with a
§ 150.00)2A:
nominal diameter of 3/4 inch or larger; all piping associated with a domestic hot water recirculation system regardless of the pipe diameter;
piping from the heating source to storage tank or between tanks; piping buried below grade; and all hot water pipes from the heating source to
kitchen fixtures.'
§ 150.00)2B:
Water piping and cooling system line insulation. All domestic hot water pipes that are buried below grade must be installed in a water proof
and non -crushable casing or sleeve.'
§ 150.06)2C:
Water piping and cooling system line insulation. Pipe for cooling system lines must be insulated as specified in § 150.00)2A. Distribution
piping for steam and h dronic heating systems or hot waters stems must meet the requirements in TABLE 120.3-A.'
§ 150.00)3:
Insulation Protection. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Insulation Protection. Insulation exposed to weather must be installed with a cover suitable for outdoor service. For example, protected by
§ 150.00)3A:
aluminum, sheet metal, painted canvas, or plastic cover. The cover must be water retardant and provide shielding from solar radiation that can
cause degradation of the material.
§ 150.00)3B:
Insulation Protection. Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space must have a
Class I or Class II vapor retarder.
Gas or Propane Systems. Systems using gas or propane water heaters to serve individual dwelling units must include all of the following: a
§ 150.0(n)l:
120V electrical receptacle within 3 feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside
termination and the space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the
water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000 Btu/hr.
§ 150.0(n)2:
Recirculating Loops. Recirculating loops serving multiple dwelling units must meet the requirements of § 110.3(c)5.
§ 150.0(n)3:
Solar Water -heating Systems. Solar water -heating systems and collectors must be certified and rated by the Solar Rating and Certification
Corporation SRCC) or by a listing a enc that is approved by the Executive Director.
Ducts and Fans Measures:
§ 110.8(d)3:
Ducts. Insulation installed on an existing space -conditioning duct must comply with § 604.0 of the California Mechanical Code (CMC). If a
contractor installs the insulation, the contractor must certify to the customer, in writing,that the insulation meets this requirement,
CMC Compliance. All air -distribution system ducts and plenums must be installed, sealed, and insulated to meet the requirements of CMC
§§ 601.0, 602.0, 603.0, 604.0, 605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition. Portions
of supply -air and return -air ducts and plenums must be insulated to a minimum installed level of R-6.0 (or higher if required by CMC § 605.0) or
a minimum installed level of R-4.2 when entirely in conditioned space as confirmed through field verification and diagnostic testing
§ 150.0(m)l:
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts must be mechanically fastened. Openings must be sealed with
mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181 B or aerosol sealant that
meets the requirements of UL 723. If mastic or tape is used to seal openings greater than'/< inch, the combination of mastic and either mesh or
tape must be used. Building cavities, support platforms for air handlers, and plenums designed or constructed with materials other than sealed
sheet metal, duct board or flexible duct must not be used for conveying conditioned air. Building cavities and support platforms may contain
ducts. Ducts installed in cavities and support platforms must not be compressed to cause reductions in the cross -sectional area of the ducts.'
Factory -Fabricated Duct Systems. Factory -fabricated duct systems must comply with applicable requirements for duct construction,
§ 150.0(m)2:
connections, and closures; joints and seams of duct systems and their components must not be sealed with cloth back rubber adhesive duct
tapes unless such tape is used in combination with mastic and draw bands.
§ 150.0(m)3:
Field -Fabricated Duct Systems, Field -fabricated duct systems must comply with applicable requirements for: pressure -sensitive tapes,
mastics, sealants, and other requirements specified for duct.00nstruction.
§ 150.0(m)7:
Backdraft Dampers. All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or
automatic. dampers.
§ 150.0(m)8:
Gravity Ventilation Dampers. Gravity ventilating systems serving conditioned space must have either automatic or readily accessible,
manually operated dampers in all openings to the outside, except combustion inlet and outlet air openings and elevator shaft vents.
Protection of Insulation. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance, and
§ 150.0(m)9:
wind. Insulation exposed to weather must be suitable for outdoor service. For example, protected by aluminum, sheet metal, painted canvas, or
plastic cover. Cellular foam insulation must be protected as above or painted with a coating that is water retardant and provides shielding from
solar radiation.
§ 150.0(m)10:
Porous Inner Core Flex Duct. Porous inner core flex duct must have a non -porous layer between the inner core and outer vapor barrier.
Duct System Sealing and Leakage Test. When space conditioning systems use forced air duct systems to supply conditioned air to an
§ 150.0(m)l1:
occupiable space, the ducts must be sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in
accordance with § 150.0 m l land Reference Residential Appendix RA3.
Air Filtration. Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet In length and through a thermal
§ 150.0(m)12:
conditioning component, except evaporative coolers, must be provided with air filter devices that meet the design, installation, efficiency,
ressure drop, and labe Ing requirements of§ 150.0(m)12.
e2016 Low -Rise Residential Mandatory Measures Summary
Duct System Sizing and Air Filter Grille Sizing. Space conditioning systems that use forced air ducts to supply cooling to an occupiable
space must have a hole for the placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the
§ 150.0(m)13:
supply plenum. The space conditioning system must also demonstrate airflow z 350 CFM per ton of nominal cooling capacity through the return
grilles, and an air -handling unit fan efficacy <- 0.58 WICFM as confirmed by field verification and diagnostic testing, in accordance with
Reference Residential Appendix RA3.3. This applies to both single zone central forced air systems and every zone for zonally controlled central
forced air stems.'
Ventilation for Indoor Air Quality. All dwelling units must meet the requirements of ASHRAE Standard 62.2. Neither window operation nor
§150.0(o)
continuous operation of central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of
providing whole -building ventilation.
§ 150.0(o)1A:
Field Verification and Diagnostic Testing. Whole -building ventilation airflow must be confirmed through field verification and diagnostic
testing, in accordance with Reference Residential Appendix RA3.7.
Pool and Spa Systems and Equipment Measures:
Certification by Manufacturers. Any pool or spa heating system or equipment must be certified to have all of the following: a thermal efficiency
§ 110.4(a):
that complies with the Appliance Efficiency Regulations; an on -off switch mounted outside of the heater that allows shutting off the heater
without adjusting the thermostat setting; a permanent weatherproof plate or card with operating instructions; and must not use electric
resistance heating.'
§ 110.4(b)1:
Piping. Any pool or spa heating equipment must be installed with at least 36 inches of pipe between the filter and the heater, or dedicated
suction and return lines, or built-in or built-up connections to allow for future solar heating.
§ 110.4(b)2:
Covers. Outdoor pools or spas that have a heat pump or gas heater must have a cover.
§ 110.4(b)3:
Directional inlets and time switches for pools. Pools must have directional inlets that adequately mix the pool water, and a time switch that
will allow all pumps to be set or programmed to run only during off-peak electric demand periods,
§ 110.5:
Pilot Light. Natural gas pool and spa heaters must not have a continuously burning pilot light.
150.0
§ (p)'
Pool Systems and Equipment Installation. Residential pool systems or equipment must meet the specified requirements for pump sizing, flow
rate, piping, filters, and valves.'
Lighting Measures:
§ 110.9..
Lighting Controls and Components. All lighting control devices and systems, ballasts, and luminaires must meet the applicable requirements
of § 110.9.'
§ 110.9(e):
JA8 High Efficacy Light Sources. To qualify as a JA8 high efficacy light source for compliance with § 150.0(k), a residential light source must
be certified to the Ener y Commission according to Reference Joint Appendix JA8.
§ 150.0(k)1A:
Luminaire Efficacy. All installed luminaires must be high efficacy in accordance with TABLE 150.0-A.
Blank Electrical Boxes. The number of electrical boxes that are more than 5 feet above the finished floor and do not contain a luminaire or
§ 150.0(k)1 B:
other device must be no greater than the number of bedrooms. These electrical boxes must be served by a dimmer, vacancy sensor control, or
fan speed control.
Recessed Downlight Luminaires in Ceilings. Luminaires recessed into ceilings must meet all of the requirements for: insulation contact (IC)
§ 150.0(k)1C:
labeling; air leakage; sealing; maintenance; and socket and light source as described in § 150.0(k)1C. A JA8-2016-E light source rated for
elevated temperature must be installed by final inspection in all recessed downli ht luminaires in ceilings.
§ 150.0(k)1 D:
Electronic Ballasts. Ballasts for fluorescent lamps rated 13 watts or greater must be electronic and must have an output frequency no less than
20 kHz.
Night Lights. Permanently installed night lights and night lights integral to installed luminaires or exhaust fans must be rated to consume no
§ 150.0(k)1 E:
more than 5 watts of power per luminaire or exhaust fan as determined in accordance with § 130.0(c). Night lights do not need to be controlled
by vacancy sensors.
§ 150.0(k)1 F:
Lighting Integral to Exhaust Fans. Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods)
must meet the applicable requirements of § 150.0(k).*
Screw based luminaires. Screw based luminaires must not be recessed downlight luminaires in ceilings and must contain lamps that comply
§ 150.0(k)1 G:
with Reference Joint Appendix JA8. Installed lamps must be marked with "JA8-2016" or "JA8-2016-E" as specified in Reference Joint Appendix
JAB.'
§ 150.0(k)1 H:
Enclosed Luminaires. Light sources installed in enclosed luminaires must be JA8 compliant and must be marked with "JA8-2016-E.'
§ 150.0(k)2A:
Interior Switches and Controls. All forward phase cut dimmers used with LED light sources must comply with NEMA SSL 7A.
§ 150.0(k)2B:
Interior Switches and Controls. Exhaust fans must be switched separately from lighting systems.'
§ 150.0(k)2C:
Interior Switches and Controls. Luminaires must be switched with readily accessible controls that permit the luminaires to be manually
switched ON and OFF.
§ 150.0(k)2D:
Interior Switches and Controls. Controls and equipment must be installed in accordance with manufacturer's instructions.
§ 150.0(k)2E:
Interior Switches and Controls. No control must bypass a dimmer or vacancy sensor function if the control is installed to comply with
150.0(k).
§ 150.0(k)2F:
Interior Switches and Controls. Lighting controls must comply with the applicable requirements of § 110.9.
Interior Switches and Controls. An energy management control system (EMCS) may be used to comply with dimmer requirements if it:
§ 150.0(k)2G:
functions as a dimmer according to § 110.9; meets the Installation Certificate requirements of § 130.4; meets the EMCS requirements of §
130.5 f • and meets all other requirements in § 150.0(k)2.
Interior Switches and Controls. An EMCS may be used to comply with vacancy sensor requirements in § 150.0(k) if it meets all of the
§ 150.0(k)2H:
following: it functions as a vacancy sensor according to § 110.9; the Installation Certificate requirements of § 130.4; the EMCS requirements of §
130.5 ; and all other requirements in § 150.0(K)2.
§ 150.0(k)21:
Interior Switches and Controls. A multiscene programmable controller may be used to comply with dimmer requirements in § 150.0(k) if it
provides the functionality of a dimmer according to § 110.9 and complies with all other applicable requirements in § 150.0.Ck). __ _.
2016 Low -Rise Residential Mandatory Measures Summary
§ 150.0(k)2J:
Interior Switches and Controls. In bathrooms, garages, laundry rooms, and utility rooms, at least one luminaire in each of these spaces must
be con trolled_by a vacancy sensor.
§ 150.0(k)2K:
Interior Switches and Controls. Dimmers or vacancy sensors must control all luminaires required to have light sources compliant with
Reference Joint Appendix JAB, except luminaires in closets less than 70 square feet and luminaires in hallways.'
§ 150.0(k)2L:
Interior Switches and Controls. Undercabinet lighting must be switched separately from other lighting systems.
Residential Outdoor Lighting. For single-family residential buildings, outdoor lighting permanently mounted to a residential building, or to other
§ 150.0(k)3A:
buildings on the same lot, must meet the requirement in item § 150.0(k)3Ai (ON and OFF switch) and the requirements in either item
§ 150.0(k)3Aii (photocell and motion sensor) or item § 150.0(k)3Aiii (photo control and automatic time switch control, astronomical time clock, or
EMCS).
Residential Outdoor Lighting. For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies,
§ 150.0(k)3B:
and porches; and outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site must comply with
either § 150.0(k)3A or with the applicable requirements in §§ 110.9, 130.0 130.2, 130.4, 140.7 and 141.0.
§ 150.0(k)3C:
Residential Outdoor Lighting. For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by
150.0 k 3B or § 150.0(k)3D must comply with the applicable requirements in §§ 110.9, 130.0,130.2, 130.4, 140.7 and 141.0.
§ 150.0(k)3D:
Residential Outdoor Lighting. Outdoor lighting for residential parking lots and residential carports with a total of eight or more
vehicles per site must comply with the applicable requirements in §§ 110.9 130.0. 130.2,130.4 140.7 and 141.0.
§ 150.0(k)4:
Internally illuminated address signs. Internally illuminated address signs must comply with § 140.8; or must consume no more than 5 watts of
power as determined accordin to 5 130.0(c).
§ 150.0(k)5:
Residential Garages for Eight or More Vehicles. Lighting for residential parking garages for eight or more vehicles must comply with the
applicable requirements for nonresidential garages in §§ 110.9.130.0. 130.1, 130.4 140.E and 141.0.
Interior Common Areas of Low-rise Multi -Family Residential Buildings. In a low-rise multifamily residential building where the total interior
§ 150.0(k)6A:
common area in a single building equals 20 percent or less of the floor area, permanently installed lighting for the interior common areas in that
building must be high efficacy luminaires and controlled by an occupant sensor.
Interior Common Areas of Low-rise Multi -Family Residential Buildings. In a low-rise multifamily residential building where the total interior
common area in a single building equals more than 20 percent of the floor area, permanently installed lighting in that building must:
§ 150.0(k)6B:
i. Comply with the applicable requirements in §§ 110.9, 130.0, 130.1, 140.6 and 141.0; and
ii. Lighting installed in corridors and stairwells must be controlled by occupant sensors that reduce the lighting power in each space by at least
50 percent. The occupant sensors must be capable of turning the light fully on and off from all designed paths of ingress and egress.
Solar Ready Buildings:
Single Family Residences. Single family residences located in subdivisions with ten or more single family residences and where the
§ 110.10(a)1:
application for a tentative subdivision map for the residences has been deemed complete by the enforcement agency must comply with the
raq uirements of 5 110.10 b th ro49 h § 110.10 e .
§ 110.10(a)2:
Low-rise Multi -family Buildings. Low-rise multi -family buildings must comply with the requirements of § 110.10(b) through § 110.10(d).
Minimum Area. The solar zone must have a minimum total area as described below. The solar zone must comply with access, pathway, smoke
ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a local
jurisdiction. The solar zone total area must be comprised of areas that have no dimension less than 5 feet and are no less than 80 square feet
each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for buildings with roof areas
§ 110.10(b)1;
greater than 10,000 square feet.
For single family residences the solar zone must be located on the roof or overhang of the building and have a total area no less than 250
square feet. For low-rise multi -family buildings the solar zone must be located on the roof or overhang of the building, or on the roof or overhang
of another structure located within 250 feet of the building, or on covered parking installed with the building project, and have a total area no less
than 15 oeitem of the total roof area of the building excluding any skylight area!
§ 110.10(b)2:
Orientation. All sections of the solar zone located on steep -sloped roofs must be oriented between 110 degrees and 270 degrees of true north.
§ 110.10(b)3A:
Shading. The solar zone must not contain any obstructions, including but not limited to: vents, chimneys, architectural features, and roof
mounted equipment.'
Shading. Any obstruction located on the roof or any other part of the building that projects above a solar zone must be located at least twice the
§ 110.10(b)3B:
distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the horizontal projection of
the nearest point of the solar zone, measured in the vertical lane.'
§ 110.10(b)4:
Structural Design Loads on Construction Documents. For areas of the roof designated as solar zone, the structural design loads for roof
dead load and roof live load must be clearly indicated on the construction documents.
Interconnection Pathways. The construction documents must indicate: a location for inverters and metering equipment and a pathway for
§ 110.10(c):
routing of conduit from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); and a pathway for routing of plumbing from the solar zone to the water -heating system.
§ 110.10ld):
Documentation. A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through
§110.10(c) must be provided to the occupant.
§ 110.10(e)1:
Main Electrical Service Panel. The main electrical service panel must have a minimum busbar rating of 200 amps.
Main Electrical Service Panel. The main electrical service panel must have a reserved space to allow for the installation of a double pole circuit
§ 110.10(e)2:
breaker for a future solar electric installation. The reserved space must be: positioned at the opposite (load) end from the input feeder location or
main circuit location; and permanently marked as "For Future Solar Electric'.
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Ratpack Residence
Date
12/19/2018
System Name
HVAC 1 mstr
Floor Area
862
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 853
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 147
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output perSystem
89,000
17,822
1,031
459
19,363
Total Output Btuh
89,000
0
Output Btuh/s ft
103.2
258
230
Cooling System
0
0
Output perSystem
59,000
5,595
3,071
147
7,157
Total Output Btuh
59,000
2,943
4,102
-2,943
Total Output Tons
4.9
258
230
Total Output Btuh/s ft
68.4
Total Output s ft/Ton
175.3
1 26,877
24,037
Air System
CFM perSystem
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2.000
Day and Night 5 Ton
50,860
0
89,000
Airflow cfm/s ft
2.32
Airflow cfmJTon
406.8
Outside Air %
7.3 °/a
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
50,860 0
Aug 3 PM
89,000
Jan 1 AM
Outside Air cfm/s ft
0.17
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF
Outside Air
147 cfm
AL
72 OF
69 IF 110 IF 112 IF
Heating Coil Supply Fan
2,000 cfm
112 IF
ROOM
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Tem eratures at Time of Cooling
Peak
112 / 78 IF
Outside Air
147 cfm
76 / 62 OF
79163 OF 55 / 54 OF 56 / 54 OF
�III�
Cooling Coil Supply Fan
2,000 cfm
56 / 54 OF
—
44.4 % ROOM
_ r
76 / 62 IF
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Ratpack Residence
Date
12/19/2018
System Name
HVAC 2, 3 & 4
Floor Area
3,995
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
3
COIL
CFM
Total Room Loads 3.890
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 806
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output perSystem
89,000
72,113
4.777
1,581
61,936
Total Output Btuh
267,000
0
Output Btuh/s ft)
66.8
1.044
737
Cooling System
0
0
Out ut erS stem
59,000
30,726
13,817
806
39,341
Total Output Btuh
177,000
8.830
18,594
-8,830
Total Output Tons
14.8
1.044
737
Total Output Btuh/s ft
44.3
Total Output s ft/Ton
270.8
113,757
93,921
Air System
CFM perS stem
2,000
HVAC EQUIPMENT SELECTION
Airflow f cfm
6.000
Day and Night 5 Ton
152.880
5,009
267,000
Airflow cfm/s ft
1.50
Airflow cfmfTon
406.8
Outside Air %
13.4 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
152,8801
5,0091
267,000
Outside Air cfm/s ft
0.20
Note: values above givan at ARI conditions
Aug 3 PM
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 IF
vp
Outside Air Ar
806 cfm
72 OF
If
66 OF 108 IF 109 IF
O
Heating Coil Supply Fan
6,000 cfm
109 OF
ROOM
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling
Peak
112/78°F
Outside Air
806 cfm
76 / 63 IF
81 /65OF 57/56OF 58/56IF
a
Cooling Coil Supply Fan
6,000 cfm
59 / 56 OF
48.5 % ROOM
76 / 63 IF
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Date
Ratpack Residence
12/19/2018
System Name
Floor Area
HVAC 5 & 6
1,324
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
2
COIL
CFM
Total Room Loads 452
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 221
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output per System
50,000
25,529
11583
542
25,205
Total Output Btuh
100,000
0
Output Btuh/s ft
75.5
369
286
Cooling System
0
0
Output per System
45,000
8,380
11,204
221
10,745
Total Output Btuh
90,000
0
12,787
0
Total Output Tons
7.5
369
286
Total Output Btuh/s ft
68.0
Total Output s ft/Ton
176.5
I 34,648L
1 36,523
Air System
CFM per System
550
HVAC EQUIPMENT SELECTION
Airflow cfm
1,100
Fujitsu FAOU45
71,313
0
62,457.
Airflow cfm/s ft
0.83
Airflow cfm/Ton
146.7
Outside Air %
20.1 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
71,313
0
62,457
Jan 1 AM
Outside Air cfm/s ft
0.17
Note: values above given at ARI conditions
Aug 3 PM
HEATING SYSTEM PSYCH ROM ETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF
63 OF 116 OF 116 OF
Outside Air
U 1
I [l I
221 cfm
Heating Coil Supply Fan
116 OF
1,100 cfm
ROOM
72 OF
72 IF
f
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling
Peak
112/78OF
83/58°F 23/21 OF 23/21 OF
Outside Air
221 cfm
Cooling Coil Supply Fan
23 / 22 OF
1,100 cfm
12.3 % ROOM
rl
76 / 51 OF
_ ,
76.151 °F
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Ratpack Residence
Date
12/19/2018
System Name
HVAC 6
Floor Area
753
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 670
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 126
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output perSystem
26,000
13,090
900
1,119
14,742
Total Output Btuh
26,000
0
Output Btuh/s ft
34.5
189
167
Cooling System
0
0
Output jeerSystem
24,000
4,776
2,035
126
6,115
Total Output Btuh
24,000
0
189
1 18,245 2,935
0
Total Output Tons
2.0
167
Total Output Btuh/s ft
31.9
Total Output s ft/Ton
376.5
21,193
Air System
CFM perSystem
743
HVAC EQUIPMENT SELECTION
Airflow cfm
743
Fujitsu 24RLFCD
19,676
2,019
16,239
Airflow cfm1s ft
0.99
Airflow cfm/Ton
371.5
Outside Air %
16•9 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
19,676
2,019
16,239
Jan 1 AM
Outside Air cfm/s ft
0.17
Note: values above given at ARI conditions
Aug 3 PM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peaks
26 OF
ok
Outside Air��u-
126 cfm
72 OF
64 OF 85 OF 85 OF
Heating Coil Supply Fan
743 cfm
I I I
84 OF
ROOM N
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling
Peak
112/78OF
Outside Air
126 cfm
76 / 63 OF
82/66OF 57/56OF 57/56OF
I
Cooling Coil Supply Fan
743 cfm
l I
58 / 56 OF
49.5 % ROOM
9 ._.
T 76 / 63 OF
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Ratpack Residence
Date
12/19/2018
System Name
HVAC 8
Floor Area
562
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 197
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 94
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output perSystem
21,600
4,550
585
471
7,492
Total Output Btuh
21.600
0
Output Btuhls ft
38.4
66
85
Cooling System
0
0
Output erSystem
18,000
3,378
1,768
94
4,571
Total Output Btuh
18,000
0
2,352
0
Total Output Tons
1.5
66
85
Total Output Btuh/s ft
32.0
Total Output s ft/Ton
374.7
1 8,060
12,233
Air System
CFM perSystem
550
HVAC EQUIPMENT SELECTION
Airflow cfm
550
Fujitsu FAOU18
16,234
0
13,491
Airflow cfm/s ft
0.98
Airflow cfmfTon
366.7
Outside Air %
17.0 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
16,234
0
13,491
Jan 1 AM
Outside Air cfm/s ft
0,17
Note: values above given at ARI conditions
Aug 3 PM
HEATING SYSTEM PSYCHROMETRICS
Airstream Tem eratures at Time of Heating
Peak
26 OF
Air
94 cfm
72 OF
64 OF 87 OF 87 OF
U I
Heating Coil Supply Fan
550 cfm
I IOutside I�]
FtT "I
ROOM
72 OF
COOLING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Cooling
Peak
112/78°F
Outside Air r
94 cfm
78 / 63 OF
84/66OF 56/55OF 56/55OF
O
Cooling Coil Supply Fan
550 cfm
I
56 / 55 OF
43.7 % ROOM
n
78 / 63 OF
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Ratpack Residence
Date
12/19/2018
System Name
HVAC 7 & 8
Floor Area
1,054
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
2
COIL
CFM
Total Room Loads 621
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 176
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output per System
26,000
13,749
1.096
983
15,082
Total Output Btuh
52,000
0
Output Btuh/s ft
49•3
794
577
0
Cooling System
0
Output per System
24,000
6,262
3,186
176
8,531
Total Output Btuh
48,000
0
794
1 21,599 4,282
0
Total Output Tons
4.0
577
Total Output Btuh/s ft
45.5
Total Output s ft/Ton
263.5
24,767
Air System
CFM per System
743
HVAC EQUIPMENT SELECTION
Airflow cfm
1,486
Fujitsu 24RLFCD
40,733
2,175
32,478
Airflow cfmis ft
1.41
Airflow cfm/Ton
371.5
Outside Air %
11.8 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
I TIME OF SYSTEM PEAK
40,733 2,175
Aug 3 PM
32,478
Outside Air cfmis ft
0.17
Note: values above given at ARI conditions
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF
Out Air -41-
176 cfm
72 OF
■
66 OF 87 IF 87 OF
M •l:� i
Heating Coil Supply Fan
1,486 cfm
j I[�
I U 1
86 IF
ROOM
72 IF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling
Peak
112/78OF
Outside Air
176 cfm
•
82/65°F 57/55°F 57/55°F
8 1
Cooling Coil Supply Fan
1,486 cfm
T-1 I U -
i 1
57 / 56 IF
--
44.4 % ROOM
78/63°
- _--
ROOM LOAD SUMMARY
Project Name Date
Ratpack Residence 1211912018
System Name Floor Area
HVAC 1 mstr 862
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM Sensible Latent CFM Sensible Latent CFM Sensible
Suite 1 Ste 1 1 853 17,822 1,031 653 17,822 1,031 4591 19,363
PAGE TOTAL
TOTAL*
* Total includes ventilation load
853
1 17,822
1,031 459
19,363
853
17.822
1,031 459
19,363
ROOM LOAD SUMMARY
Project Name Date
Ratpack Residence 1211912018
System Name Floor Area
HVAC 2, 3 & 4 3,995
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult.H,8901
FM Sensible Latent CFM Sensible Latent CFM Sensible
great room Great Dining Kitchen 172,113 4,777 3,8901 72,1131 4,777 1,5811 61,936
PAGE TOTAL
TOTAL*
* Total includes ventilation load for zonal
3,894
72,113
4,777
1,581 61,936
3,890
1 72,113
4,777
1,581 61,936
ROOM LOAD SUMMARY
Project Name Date
Ratpack Residence 1211912018
System Name Floor Area
HVAC 5 & 6 1,324
ROOM LOAD SUMMARY
ROOM COOLING PEAK I COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM Sensible Latent CFM Sensible Latent CFM Sensible
2 Suite 2 1 228 12,889 792 228 12,889 792 275 12,782
3 Suite 3 1 224 12,640 792 224 12, 640 792 2671 I Z 423
PAGE TOTAL
TOTAL*
* Total includes ventilation load for zonal
452
25,529
1,583
542 25,205
452
25,529
1,583
542 25,205 1
ROOM LOAD SUMMARY
Project Name Date
Ratpack Residence 1211912018
System Name Floor Area
HVAC 6 753
ROOM LOAD SUMMARY
ROOM COOLING PEAK
Zone Name Room Name Mult. CFM Sensible I Latent
guest-4 Suite 4 1 1 1 6701 13,0901 900
PAGE TOTAL
TOTAL*
* Total includes ventilation load for zonal
COIL COOLING PEAK COIL HTG. PEAK
CFM Sensible Latent CFM Sensible
670 13,0901 900 1,1191 14,742
870
13,090
900
1.119
14.742
670
13,090
900
1,119
14,742
ROOM LOAD SUMMARY
Project Name Date
Ratpack Residence 1211912018
System Name Floor Area
HVAC 8 562
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK I COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible I Latent CFM Sensible Latent I CFM I Sensible
Cart Garage Zone Cart Garage 1 1 1971 4,5501 585 197 4,5501 5851 471 7,492
PAGE TOTAL
TOTAL*
* Total includes ventilation load for zonal systems.
197
4,550
585
471
7,492
197
4,550
585
471
7,492
ROOM LOAD SUMMARY
Project Name Date
Rafpack Residence 1211912018
System Name Floor Area
HVAC 7 & 8 1,054
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM Sensible Latent CFM Sensible Latent CFM Sensible
2CarGarage-Renovation Main Garage 1 621 13,749 1,096 621 13,7491 1,096 9831 15,082
PAGE TOTAL
TOTAL*
621
13,7491
1,096
983
15,082�
621
13.749
1,096
983
15,a82
ROOM HEATING PEAK LOADS
Project Name
Ratpack Residence
Date
1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Ste 1
Floor Area 862.00 ftz
Indoor Dry Bulb Temperature 72 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U-Value
x
x
x
x
x
x
x
X
X
X
X
X
X
X
X
X
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
AT °F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr _
771
R-38 + R13 Roof Attic
862.0
x
x
x
0.0194
46
R-21 Wall (W.21.2x6.16)
1,845.0
0.0690
46
5,856
Monumental.371.26
103.0
0.3700
46
1,753
Monumental.461..31
250.0
x
x
0.4600
46
5,290
Monumenlal.50/.20
12.0
0.5000
46
276
Slab -On -Grade
perim = 100.0
x
0.7300
46
3,358
'R-0 Interior Wall
424.0
x
0.3560
0
0
X
X
X
X
X
X
X
X
X
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
Items shown with an asterisk (°) denote conduction
Infiltration:[ 1.00 x 1.064
Schedule Air Sensible
Fraction
through an interior surface to
x 862 x
Area Ceiling
another room
10.20 x 0.287
Height ITCH
Page Total
/ 60 J X
AT
17,304
= 2,059
TOTAL HOURLY HEAT LOSS FOR ROOM 19,363
ROOM HEATING PEAK LOADS
Project Name
Ratpack Residence
Date
1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great Dining Kitchen
Floor Area 3,995.00 ft2
Indoor Dry Bulb Tem erature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
3,995.0
U-Value
X 0.0194
X 0.0690
X 0.9400
X 0.4600
X 0.3700
X 0.7600
X 0.5000
X 0.7300
X 0.3560
X
X
X
X
X
X
X
X
X
X
X
X
X
X
x
x
x
x
x
x
x
x
to another room
12.10 X 0.242
Ceiling Height ACI
AT OF
Btu/hr
R-38+P13RoofAf[ic
X
46
=
3,571
R-21 Wall (W.21.24.16)
940.7
X
46
=
2,986
Custom Entry Door
55.0
X
X
46
=
=
2,378
Monumental.461.31
1,124.0
46
23,784
Monumenlal.371.26
801.8
X
46
=
13,647
Monumental. 761. 18
7T0
X
46
=
2,692
Monumenfal.501.20
16.5
X
46
=
360
Slab -On -Grade
perim = 88.0
X
46
=
2,955
'R-0 Interior Wall
424.0
X
0
=
0
X
=
X
=
X
=
X
X
=
=
X
X
X
=
=
=
X
=
X
=
X
=
X
X
=
=
X
=
x
=
x
=
x
x
=
=
x
x
=
=
x
=
x
=
Items shown with an asterisk (") denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X 3,995 X
Area
Page Total
/ 60 ] X 46
I AT
52,392
= 9,544
TOTAL HOURLY HEAT LOSS FOR ROOM 61,936
ROOM HEATING PEAK LOADS
Project Name
Ratpack Residence
bate
1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Suite 2
Floor Area 662.00 ft2
Indoor Dry Bulb Temperature 72 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
662.0 X
475.8 X
U-Value
X
X
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
AT OF
=
=
_
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 + R13 Roof Attic
0.0194
46
592
R-21 Wall (W.21.2x6.16)
0.0690
46
1,510
Monumental .46/.31
274.0
x
X
0.4600
46
5,798
Monumental.371.26
30.2
0.3700
46
514
Slab -On -Grade
perim = 83.0
x
X
x
x
x
0.7300
46
2,787
'R-0 Interior Wall
230.0
0.3560
0
0
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Items shown with an asterisk (") denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface to
X 662 X
Area Ceiling
another room
10.00 x 0.293
Height ACrI
Page Total
/ 60 ] X
AT
11,201
1,582
12,782
TOTAL HOURLY HEAT LOSS FOR ROOM
ROOM HEATING PEAK LOADS
Project Name
Ratpack Residence
Date
1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Suite 3
Floor Area 662.00 ft2
Indoor Dry Bulb Temperature 72 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U-Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT OF
=
=
=
a
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R-38 + R13 Roof Adic
662.0
0.0194
46
592
R-21 Wall (W.21.2x6.16)
495.8
0.0690
46
1,574
Monumenfal.461.31
254.0
0.4600
46
5,375
Monumental.371.26
30.2
0.3700
46
514
Slab -Orr -Grade
perim = 83.0
0.7300
46
2,787
'R-0 Interior Wall
230.0
0.3560
0
0
Items shown with an asterisk (`) denote conduction
Infiltration:[ 1.00 X 1.064
Schedule Air Sensible
Fraction
through an interior surface
X G62 X
Area
another room
10.00 X 0.293
Height ACH
Page Total
/ 60 ] X
AT
10,841
_ 1,582
TOTAL HOURLY HEAT LOSS FOR ROOM IZ423
ROOM HEATING PEAK LOADS
Project Name Date
Ratpack Residence 1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Suite 4
Floor Area 753.00 ftZ
Indoor Dry Bulb Temperature 72 OF,
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
x
x
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
x
x
x
x
x
x
X
to
Ceiling
U-Value
x
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
x
x
x
x
x
x
x
AT OF
=
=
=
_
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
_
46
Btu/hr
R-38 + R13 Roof Attic
753.0
0.0194
46
673
R-21 Wall (W.21,2x6.16)
783.8
0.0690
46
2,488
Monumenla1.46/.31
246.0
0.4600
46
5,205
Monumental.37/.26
30.2
0.3700
46
574
Slab•On-Grade
perim = 121.0
0.7300
46
4,063
`R-0 Interior Wall
124.0
0.3560
0
0
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 x 1.064
5chodule Air Sensible
Fraction
through an interior surface
x 753 x
Area
another room
10.00 x 0.293
Height ACH
Page Total
/ 60 ] X
❑T
12,943
1,799
TOTAL HOURLY HEAT LOSS FOR ROOM 14,742
ROOM HEATING PEAK LOADS
Project Name
Ratpack Residence
Date
1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Cart Garage
Floor Area 562.00 ft2
Indoor Dry Bulb Temperature 72 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
U-Value
X
X
X
X
X
X
X
X
X
X
X
1X
x
X
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
AT 'F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
46
Btu/hr
R 38 + R13 Root Attic
562.0
X
X
X
0.0194
46
502
R-21 Wall (W.21.2x6.16)
664.2
0.0690
46
2,108
Insulated Garage Door
188.8
0.0788
46
684
Slab -On -Grade
perim = 85.0
X
0.7300
46
2,854
'R-0 IrrferlorWall
292.0
X
0.3560
0
0
X
X
X
X
X
X
X
x
X
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
Items shown with an asterisk (`) denote conduction
Infiltration:[ 1.00 X 1.064
Schedukc Air Sensible
Fraction
through an interior surface to
X 562 X
Area Cciling
another room
10.00 X 0.293
Height ACH
Page Total
/ 60 ] X
AT
6,149
= 1,343
TOTAL HOURLY HEAT LOSS FOR ROOM 7,492
ROOM HEATING PEAK LOADS
Project Name
Ratpack Residence
Date
1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Main Garage
Floor Area 1,054.00 ft2
Indoor Dry Bulb Temperature 72 OF,
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
_
X
X
X
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
to
Ceiling
U-Value
0.0194
X
X
X
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
AT OF
=
=
=
=
c
=
=
=
46
Btu/hr
R•38 + R13 Roof AHic
1,054.0
46
942
R-21 Wall (W,21.2x6.16)
759.2
0.0690
46
2,410
New Monumental .481..31
160.0
0.4600
46
3,386
Now R-21 Walt
224.0
0.0690
46
711
New Monumental .371.26.
63.8
0.3700
46
1,066
Slab -On -Grade
perim = 120.0
0.7300
46
4,030
'R-0 Interior Wall
224.0
0.3560
0
0
_
Items shown with an asterisk (`) denote conduction
Infiltration:[ 1.00 X 1.064
5chadule Air Sensible
Fraction
through an interior surface
X 1,054 X
Area
another room
10.00 X 0.293
Height ACH
Page Total
/ 60 ] X
AT
12,584
2,518
TOTAL HOURLY HEAT LOSS FOR ROOM 15,082
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Ratpack Residence
1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Ste 1
Outdoor Dry Bulb Temperature
112 OF
Floor Area
862.00 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 76 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U_-Factor
CLTD'
Btu/hr
R-38 + R13 Rcof Alfic
(W) 862,0 X 0.0194
X
56.0 = 938
R-21 Wall (W.21.2x6.16)
(E) 150.0 X 0.0690
X
32.1 = 332
R-21 Wafl (W.21.24.16)
(S) 594.2 X 0.0690
x
27.1 = 1.112
R-21 Wall (W.21.2x6.16)
(W) 307.0 X 0.0690
X
32.6 = 690
R-21 Wall (W21.2x6.16)
(N) 793.8 X 0.06901
X
29.0 = 1,588
'R•0 tnteriar Wall
424.0 X 0.3560
X
0.0 = 0
x
x
=
x
x
=
x
x
=
Page
Total 4,660
Items shown with an asterisk (')
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF Btu/hr
D2
(S) 41.0 X 17.0 +
0.0
X
18.4 = 699
22
(S) 53.0 X 20.7 +
0.0
X
22.3 = 1;097
03
(S) 31.8 X 17.0 +
0.0
X
18.4 = 642
21
(W) 49.6 X 20.7 +
83.4
X
38.4 = 4,231
01
(N) 0.0 X 17.0 +
30.2
X
25.4 = 767
20
(N) 0.0 X 20.7 +
64.0
X
30.7 = 1,963
C2
(N) 0.0 X 17.4 +
12.0
X
23.9 = 286
X +
X
=
X 1 +1
X
=
Page Total 9.58G
Internal Gain
Btu/hr
Occupants
2.6 Occupants x 245
Btuh/occ.
= 634
E ui ment
862 Floor Area X 0.50
w/sgft
Infiltration: 1.064
X 0.88 X 43.46 X 36 -
1,471
Air Sensible
CFM Elk AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
17,822
Latent Gain
Btu/hr
Occupants
2 6 Occupants X 155
Btuh/occ.
401
Infiltration: 4,771
X 0.88 X 1 43.46 X 0.00344 =
630
Air Latent
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
401
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Ratpack Residence 1211912018
ROOM INFORMATION DESIGN CONDITIONS
Room Name Great Dining Kitchen Outdoor Dry Bulb Temperature 112 OF
Floor Area 3,995.00 ftZ Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 76 °F Outdoor Daily Range: 34 OF
Ouaaue Surfaces
R-38 + R13 RoorAf6c
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W-21.2x6.15)
R-21 Wall (W.21.2x6.16)
Interior Wall
Orientation
Area
X
X
X
X
X
X
X
X
X
U-Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
c
=
=
=
3,995.0
0.0194
56.0
480.4
00690
32.1
64.0
0.0690
27.1
236.6
0.0690
0.0690
32.6
159.7
29.0
424.0
0.3560
0.0
Page Total
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
Fenestration
01
58
G4
04
A
23
E2
G2
G3
Orientation
(E)
(E)
(E)
(S)
(S)
(S)
(S)
(S)
(S)
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
11.9
37.0
43.1
63.1
348.4
20.7
124.6
37.2
0.0
17.0
47.6
30.9
0.0
20.7
178.0
22.3
128.4
17.0
0.0
18.4
77.0
21.9
0.0
22.8
95.1
17.0
17.0
0.0
18.4
0.0
16.1
18.4
0.0
17.0
16.4
18.4
Page Total
Btu/hr
1
5311
Btu/hr
3.159
11,852
1,471
2.
1 1,6211
Internal Gain Btu/hr
Occupants 12.0 Occupants X 2451 Btuh/occ.
E ui menE 3,995 Floor Area X 0.50 w/sgft 6,1
Infiltration: 1.064 X 0.88 X 201.42 X 36 = C
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 72,113
Latent Gain Btu/hr
Occupants 12.0 Occupants X 155' Btuh/occ. _ 1,858
Infiltration: 4.771 X 0.88 X 201.42 X 0.003441 = Z919
Air Latent CFM ELA AW
I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 1,8581
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Ratpack Residence
1
1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Great Dining Kitchen
Outdoor Dry Bulb Temperature
112 OF
Floor Area
3,995.00 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor My Bulb Temperature 76 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U-Factor CLTD'
X X
Btu/hr
=
X X
-
X X
=
X X
=
X X
-
X X
=
X X
=
X X
=
X X
-
Page Total
Items shown with an asterisk (*)
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded Unshaded
Fenestration
Orientation Area GLF Area GLF Btu/hr
24
(W) 473.0 X 20.7 + 0.0 X
38.4 = 9.701:i
G1
(W) 0.0 X 17.0 + 47.6 X
31.9 = 1.519
El
(W) 122.3 X 17.0 + 72.5 X
31.9 = 4,399
B
(N) 0.0 X 17.0 + 177.0 X
25.4 = 4,497
G5
(N) a 0 X 17.0 + 55.0 X
25.4 = 1.396
G6
(N) 0.0 X 17.0 + 23.8 X
25.4 = 605
C1
(N) 0.0 X 17.4 + 16.5 X
23.9 = 394
X + X
=
X +1 X
Page Total 22,604
Internal Gain
Btu/hr
Occupants
12.0 Occupants X 2451 Btuh/occ.
= 2,936
Equipment
3,995 1 Floor Area X 0.50 w/sgft
Infiltration: 1.064
X 0.88 X 201.42 X 36 =
6,619
Air Sensible
CFNI ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
72,113
Latent Gain
Btuihr
Occupants
12.0 _ Occupants X 1551 Btuh/occ.
= 1.858
Infiltration: 4,771
X 0.88 X 201.42 X 0.00344 =
2,919
Air Latent
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1,858
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Ratpack Residence
1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Suite 2
Outdoor Dry Bulb Temperature
112 OF
Floor Area
662.00 ftz
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 76 OF,
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U-Factor
CLTD�
Btu/hr
R-38+R13Root Aftic
(W) 662.0 X 0.0194
X 56.0 =
720
R-21 Wall (W.21.2x8.16)
(S) 121.8 X 0.0690
X 27.1 =
228
R-21 Walt (W21.2x6.16)
(W) 212.0 X 0.0690
X 32.6 =
476.
R-21 Wall (W.21.2x6.16)
(N) 142.0 x 0.0690
X 29.0 =
284
'R-0 Interior Wall
230.0 x 0.3560
X 0.0 =
0
x
x =
x
x =
-
x
x =
� x
x =
Page Total
1,709
Items shown with an asterisk (")
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area GLF
Btu/hr
32
(S) 0.0 X 20.7 +
78.0 X 22.3 =
1,743
F1
(S) 0.0 X 17.0 +
30.2 X 18.4 =
556
28
(W) 40.3 X 20.7 +
67.7 X 38.4 =
3,436
27
(N) 0.0 X 20.7 +
53.0 X 30.7 =
1,626
26
(N) 0.0 X 20.7 +
35.0 X 30.7 =
1,074
X +
X -
X +
X =
X +
X =
X +
X =
Page Total
8,435
Internal Gain
Btu/hr
Occupants
2 0 Occupants X 245
Btuh/occ. =
d130
Equipment
662 Floor Area X 0.50
w/sgft _
1,
Infiltration: 1.064
X 0.88 X 33.38 X 36 =
1,130
Air Sensible
CFM E1.A AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
12,889
Latent Gain
Btu/hr
Occupants
2 0 Occupants X 155
Btuh/occ. =
308
Infiltration: 4,771
X 0.88� X 33.38 X 0.00344 =
484
Air Latent
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
308
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Ratpack Residence
1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Suite 3
Outdoor Dry Bulb Temperature
112 OF
Floor Area
662.00 ftZ
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature
76 °F
Outdoor Daily Ran e:
34 OF
Opaque Surfaces
Orientation Area U-Factor
CLTD'
Btu/hr
R-38 + R13 Roof Attic
(W) 662.0 X 0.0194
X 56.0 =
720
R-21 Wall (W.21.2x6,16)
(E) 232.0 X 0.0690
X 32.1 =
514
R-21 Wall (W.21.2x6.16)
(S) 121.8 X 0.0690
X 27.1 =
228
R-21 Wall (W.21.2x6.16)
(N) 142.0 X 0.0690
X 29.0 =
284
'R-0 Interior Wall
230.0 X 0.3560
X 0.0 =
0
X
X =
X
X =
X
X =
_ X
X
Page Total
1,746
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF Area GLF
Btu/hr
37
(E) 0.0 X 20.7 +
88.0 X 37.2 =
3,277
F2
(S) 0.0 X 17.0 +
30.2 X 18.4 =
555
42
(S) 78.0 X 20.7 +
0.0 X 22.3 =
1.615
35
(N) 0.0 X 20.7 +
35.0 X 30.7 =
1,074
36
(N) 0.0 X 20.7 +
53.0 X 30.7 =
1.626
X +
X =
X +
X =
X +
X =
X +
I X =
Page Total
8,14
Internal Gain
Btu/hr
Occupants
2.0 Occupants X 245
Btuh/occ. = �-A
Equipment
662 Floor Area X 0.50
wlsgft _
Infiltration: 1.064
X 0.88 X 33.38 X 36 m
1,130
Air Sensible
CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
_ 12,640
Latent Gain
Occupants
2 0 Occupants X 155
gtuh/ocC. =
_B_tulhr
Infiltration: 4,771
X 0.88 X 33.38 X I 0.00344
Air Latent
CFM ELA ❑W
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
308
05�
WOO2! NOj NIVO 1V3H 1N31V1 AjynOH 1V1O1
MV V19 Wjo lUa1e1 xv
055
ti6E00'0 1 X 9fi X 88'0 X LLL`b :uol;ea;I!;ul
09£ =
000/4nII3 99L X sluednoop £•Z slue naap
a4/n�8
_
uleJ ;u83e"1
060'£L
WOO2! HO=l NIVO 1V3H 3181SN3S AjzJnOH IV1O,l
98Z'L
10 V13 Wjo alq!suasa!y
= 9E X 96'1E X 88'0 X b90'L :uol;ea;ll;ul
8Z'L
)4bs/m 09'0 X eaay cool j £9L luaw !n 3
£95 =
000/4n;8 9bZ X sluednoop £•Z slue noop
a4/n;8
uleJ IeUaa;ul
9E9'L le;ol a6ed
X.. + X
=
X + X
=
X + X
=
X + X
tiL0'L = L'0£
X 0'9£ + L'OZ X 0'0 (N) £b
6L£`L = L-0£
X 0'£ti + L'OZ X 0-0 (N) y�
008`Z = b'B£
X Z'99 + L'OZ X .8'Z£ (M) 96
99.9 = V8L
X Z"OE + 0'LL X 0'0 (S) £=l
88L `L = £'ZZ
X 0'09 + L'00 X 0'0 (S) 09
a4/n;8 dl�
easy AID easy uol;epolio uol;ea;sauaj
Pope4sun POPe4S
((il-lo) aouejelL!Q aan;eaadwa_Lpeol 6u!l000 • l
•wooa aayloue o; eoe}jns joualui ue y6noayl uoi;onpuoo alouep (,) Nsualse ue y;!m umoys swa;l
oEti'Z le;o1 a6ed
_
X X
=
X X
=
X X
0 = O'0
X 099£'0 X O'6ZL Hem aouelu/ 0-L4
b09 = O'6Z
X 0690'0 X 19 (N) (9L'9XZ'L3'M) IIeM LZ-8
Z9Z = 9'Z£
X .0690.0 X O'ZLL (M) (9L'9XZ'LZ'M) IIeM LZ-&
LLti = L'LZ
X •0690-0 X i9'6LZ (S) (9L'9XZ'LZ'M) IIeM LZ 21
L'Z£
X •0690'0 X 19*OOZ (3) (94'9XZ'LZ'M) IIeM LZ-LI
6W = 0'99
X 66L0'0 X O'E9L (M) 017IVJOO& £L2/ + 8E-2i
a4/n38
,aria ao;oed-n eaay uol;e;ualap sooe}ans an e p
=10 /,£
:a uetl Aliea aoop;np
_q0 9L aan;eaadwal gln8 a aoopul
=10 82
empuedwal gln8 ;eM aoop;np
z 00'i9L easy aoold
Jo Zd d
aan;eaadwal gln8 Aia coop;np
p, alms aweN wooa
SNOI11aNOO NOIS3a
NOI1VWUOdNl WOON
860E16l/Zd
eouepsaLj )joedle&
9;e4
aweN ;oaload
Auvwwns avo-i ON11003 WOOH IVI1N341S3y
69Z
WO02! 2103 NIVJ 1V3H 1N31V"1 AjynOH lV1Ol
MV V+ 3 W30 Suawl i!v
$ES
= 9LZ0 X EE'9Z 00'X L9.0 X LLL'ti :uol3eJ3113ul
- - - 1
3g�
_ •000/yn;8
99k 1 X s;uednoop L•1 slue noop
ay/n;8
ule0;ua;e-I
055'ti
WOON HO=I NIVO 1V3H 3181SN3S AjunOH IV1Ol
1V V13 W30 a€C{lsuas ny
$8$
= h£ X EE'9Z X ze-0 X yg0•y :uol;ea;ll3ul
696
=
4bs/M
09.0 X eaay .€oold 79S 3uaw In 3
El.b
- 000/4n3s
9tiZ X s;uednoop L•1 slue noap
a4/n3s
uleE) leuaa;ul
0
le;ol aBed
- X
+ X
- —
= X
+ X
= X
+ X
= X
+ X
= X
+ X
= X
+ X
= X
+ X
= X
+ X
= X
+ X
j4/n3s
dip
eaiv AID eeiv uol;e;uauo uol;ea;seu9=1
�!
papeysufl
papeyg
(alto) aouala}114 oIn}ejadwal peon 6uil000 •f
-woe iauloue of aoe}ans joua3ui ue y6nay} uoilonpuoo ajouap ,() �siaa;se ue q)!m umoys swell
060'Z
le;ol aBed
-
X
X
X
.099E'0 X TWE OM -10MOM 0-8.
6L L
= 0"6Z
X
.9BL0.0 X vq/ (N) looQ often pole/nsu/
66S
= O'6Z
X
�0690'0 X 9'66d (N) (9!'9xZ'lZiVl) I/eM Le -a
£8Z
= f9'ZE
X
'B8L0-0 X b'Ol L (M) looQ BGeieo polelnsu/
9E9
a 9"ZE
X
0690'0 X 9'6EZ (M) (9v9XZ'6Z'm) item !Z-H
59
= l'LZ
X
0690.0 X •0-9E (S) (96'9xZ'izM) Item ZZ-a
iZh
d'ZE
X
0690.0 X 0.06l (3) (9v9xz,tz I) om te-a
ZO
= 0'9S
X
66d0'0 X O'Z99 (M) 0111VIo08 eta + GE -a
j4/n3s
�al�a
ao;aed-� ea.1br uol;e;ualap se3epng en e p
-4o bE
:a ueM Alleaioopino
jo 8L ain;eaadwal gln8 tua joopul
J0 8L
ain;eiadwal glnB;aMjoop;no
z#! 00•Z99 BeivJool=1
=10 Z6l
ain;ejedwal glns A -,a joop;no
a8ete0 peo aweN wood
SNOI11aN00 NOIS3a
NOI1VWNO=IN1 WOON
8kOZ/6l/,k
eouepise& )/oedjeV
eje4
aweN loafed
,kmvWWf1S avo-i JNI'1000 WOOD '1VIIN3aIS9H
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Ratpack Residence
1211912018
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Main Garage
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,054.00 ftz
Outdoor Wet Bulb Temperature
78 OF
Indoor Drx Bulb Temperature 78 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U-Factor
CLTD'
Btu/hr
R-38 + R13 Roof Attic
(W) 1,054.6 X 0.0194X
56.0 =
1,147
R-21 Wall (W 21.2x6.16)
(E) 156.0 X 0.0690 X
32.1 =
346
New R-21 Wall
(E) 160.0 X 0.0690 X
32.1 =
355
R-21 Wall (W 21.2x6.16)
(S) 70.0 X 0.0690 X
27.1 =
131
R-21 Wall (W 21.2x6.16)
(W) 278.2 X 0.0690X
32.6 _ -
625
New R-21 Wall
(W) 64.0 X 0.0690 X
32.6 =
144
R-21 Wall (W 21.2x6.16)
(N) 255.0 X 0.0690 X
29.0 =
510
"R-0 Interior Wall
224.0 X 0.3560 X
-2.0 =
-159
X X
=
Page Total
3,098
Items shown with an asterisk (")
denote conduction through an interior surface to another room.
1. Cooling Load Temperature
Difference (CLTD)
Shaded Unshaded
Fenestration
Orientation Area GLF Area
GLF
Btu/hr
55
(E) 19.1 X 20.7 + 60.9
X 37.2 =
2,663
59
(E) 19.1 X 20.7 + 60.9
X 37.2 =
2,663
New 19.9X2
(W) 39.8 X 17.0 + 0.0
X 31.9 =
679
New 12X2
(W) 24.0 X 17.0 + 0.0
X 31.9 =
409
X +
X =
X +
X =
X +
X =
X +
X =
X +
X -
Page Total
6,413
Internal Gain
Btulhr
Occupants
3.2 1 Occupants X 245 Btuh/occ.
-
T75
Equipment
1,054 I Floor Area X 0.50 w/sgft
_
1,799
Infiltration: 1.064
X a.87 X 53.14 X 34 =
1,665
Air Sensible
C F M ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
13,749
Latent Gain
Btu/hr
Occupants
3.2 Occupants X 155� Btuh/occ.
-
490
Infiltration: 4,771
X 0.87 X 53.14 X 0,00276 =
606
Air Latent
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
490