BRES2016-0169 Revision 1 Title 24BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Jones Residence
Lot #59, San Lucas
La Quinta, CA 92253
Project Designer:
Jones Development
78-060 Calle Estrado
La Quinta, CA 92253
(760) 285-8712
Report Prepared by:
Tim Scott
Scott Design and Title 24, Inc,
74-818 Velie Way, Suite 8
Palm Desert, CA 92260?e ws 10ti
(760) 200-4780
PFICEt1fEL
DEC 20 2018
koll- r OF UI QUINTA
COMMUNITY DEVELOPMENT
Job Number:
Date:
10/11/2018
TY OF LA QUINTA
BUILDING DIVISION
REVIEWED FOR
CODE
COMPLIANCE
loSZoi BY
OF—Fic
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC—www.energysoft.com.
User
TABLE OF CONTENTS
Cover Page 1
Table of Contents 2
Form CF-1 R-PRF-01-E Certificate of Compliance 3
Form RMS-1 Residential Measures Summary 14
Form MF-1 R Mandatory Measures Summary 16
HVAC System Heating and Cooling Loads Summary 20
Zone Load Summary nA
CERTIr
TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE
r 40D
Project Name:
Jones Residence
Calculation Description: Title 24 Analysis
Calculation Date/Time: 09:50, Thu, Oct 11, 2018
Input File Name: Jones Res -Jody Jones-18.ribdx
GENERAL INFORMATION
01
Project Name Jones Residence
02
Calculation Description Title 24 Analysis
03
Project Location Lot #59, San Lucas
04
City La Quinta
05
06
Zip Code 92253
Standards Version Compliance 2015
08
Climate Zone CZ15
07
Compliance Manager Version BEMCmpMgr 2013-4b (433)
10
Building Type Single Family
09
Software Version EnergyPro 6.8
12
11
Front Orientation (deg/Cardinal) 270
Project Scope Newly Constructed
13
14
Total Cond. Floor Area (ft) 3652
Number of Dwelling Units 1
16
15
Number of Zones 4
Slab Area (ft) 3652
17
18
Addition Cond. Floor Area N/A
Number of Stories 1
20
Addition Slab Area (ftZ) N/A
19
Natural Gas Available Yes
21
Glazing Percentage (%) 21.4%
CF 'RF-01
Page 1 of 11
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CECa P pproved HERS provider.
This compliance analysis is valid only for permit applications through December 31, 2016
ENERGY USE SUMMARY
04
05
06
Energy Use (kTDV/ft2-yr)
Standard Design
07
08
Space Heating
Proposed Design
p 9
Compliance Margin
Percent Improvement
Space Cooling
3.52
4.73
-1.21
-34.4%
IAQ Ventilation
114.39
100.8313.56
11.9%
Water Heating
0.91
0.91.91
0.00
0.0%
Photovoltaic Offset
7.00
9.36
-2.36
-33.70%
Compliance Energy Total
125.82
0.00
0.00
115.83
9.99
7.9%
Registration Number: 216-N0207144G-000000000-00o0
Registration Date/Time: 2018-10-11 09:58:54
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 HERS Provider: CaICERTS inc.
Report Generated at: 2018-10-1109:51:34
CERTI! TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE' HOD
Project Name: Jones Residence CF 'RF-01
Calculation Date/Time: 09:50, Thu, Oct 11, 2018 Calculation Description: Title 24 Analysis Input File Name: Jones Res -Jody Jones-18.ribdx Page 2 of 11
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
NO SPECIAL FEATURES REQUIRED
HERS FEATURE SUMMARY
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
• IAQ mechanical ventilation
Cooling System Verifications:
• Minimum Airflow
• Verified EER
• Verified SEER
• Refrigerant Charge
• Fan Efficacy Watts/CFM
HVAC Distribution System Verifications:
• Duct Sealing
• Ducts located entirely in conditioned space
Domestic Hot Water System Verifications:
• -- Hone —
ENERGY DESIGN RATING
This is the sum of the annual TDV energy consumption for energy use components included in the performance compliance approach for the Standard Design Building (Energy Budget) and the annual
TDV energy consumption for lighting and components not regulated by Title 24, Part 61,3L _ as domesticappliances and consumer electronics) and accounting for the annual TDV energy offset by an
on -site renewable energy system.
Total Energy (kTDV/f2-yr)*
Reference Energy Use
165.34
includes calculated Appliances and Miscellaneous Energy Use (AMEU)
BUILDING - FEATURES INFORMATION
01 02 03
Project Name Number of Dwelling
1 Conditioned Floor AErea(ft2]) Units
Jones Residence 3652 1
Energy Design Rating
155.35
04 1 05
Number of Bedrooms Number of Zones
4 4
Margin
9.99
06
Number of Ventilation
Cooling Systems
0
Percent Improvement
64
07
Number of Water
Heating Systems
1
Registration Number: 216-N0207144G-000000000-0000
Registration Date/Time: 2018-10-11 09:58:54
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 HERS Provider: CaiCERinc.
Report Generated at: 2018-10-1109:51:34 4
CERTI' TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE' HOD CF `RF-01
Project Name: Jones Residence Calculation Date/Time: 09:50, Thu, Oct 11, 2018 Page 3 of 11
Calculation Description: Title 24 Analysis Input File Name: Jones Res -Jody Jones-18.ribdx
OPAQUE SURFACES
01
Name
N Wall
E Wall
S Wall
W Wall
Roof 3
E Wall 2
S Wall 2
W Wall 2
Roof 4
N Wall 2
E Wall 3
S Wall 3
W Wall 3
Roof 5
N Wall 3
S Wall 4
W Wall 4
Roof 6
02
Zone
master
master
master
master
master
iivinq
living
living
living
bed
bed
bed
bed
bed
family
family
family
family
03
Construction
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W21.2x6.16)
R-21 Wall (W,21.2x6.16)
R-38 Roof Attic
R-21 Wall (W21.24.16)
- R-21 Wall (W.21.2x6.16)
R-21 Wall (W21.2x6.16)
R-38 Roof Attic
R-21 Wall (W21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-38 Roof Attic
04
Azimuth
0
90
180
270
90
180
270
0
90
180
270
0
180
270
05
Orientation
Left
Back
Right
Front
Back
Right
Front
Left
Back
Right
Front
Left
Right
Front
06
Gross Area (ft2)
308
308
702
308
836
756
208
756
1517
702
402
96
125
1015
308
308
308
278.8
07
Window & Door Area (ft)
40
40
80
200
80
184.5
33
40
80
08
Tilt (deg)
90
90
90
90
90
90
90
90
90
90
90
90
90
90
Registration Number: 216-N0207144G-000000000-0000 Registration Date/Time: 2018-10-11 09:58:54 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 Report Generated at: 2018-10-1109:51:34
CERTI' TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE'
HOD
Project Name: Jones Residence
CIF 'RF-01
Calculation Date/Time: 09:50, Thu, Oct 11, 2018
Calculation Description: Title 24 Analysis
Page 4 of 11
Input File Name: Jones Res -Jody Jones-18.ribdx
OPAQUE SURFACES -- Cathedral Ceilings
01
02
03
04
05 06 07 08
09
10 11
Name
Zone
Type
Orientatio
n
Skylight Area Roof Rise
Area (ft2)
Roof
Roof Tilt
Roof
Roof Framing
Roof
living
R-38 Roof Attic1
Front
(f:2) (x in 12)
Pitch
(deg)
Reflectance
Emittance Factor
Roof 2
family
R-38 Roof Attic11Front
4.1 4 3
13
�O.25�11.04
01
0.85 0.1
123
.04
0.1
0.85 0.1
ATTIC
01
Name
02
Construction
03
Type
04
OS
O6
07
08
Attic master
Attic Roofmaster
Roof Rise
Roof Reflectance
Roof Emittance
Radiant Barrier
Cool Roof
Attic living
Attic Roofliving
Unventilated
Unventilated
3
0.1
0.85
No
No
Attic bed
Attic Rooft>ed
Unventilated
3
0.1
0.85
No
No
Attic family
Attic Rooffamily
Unventilated
3
0 1
0.85
No
No
0.1
0.85
No
No
� CaICERTS, Inc.
Registration Number: 216-N0207144G-000000000-0000 Re Registration B Date/Time: 2018-10-11 09:58:54 HERS Provider: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 CaICERTS inc.
Report Generated at: 2018-10-1109:51:34
CERTI' TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE' HOD
Project Name: Jones Residence Calculation DatelTime: 09:50, Thu, Oct 11, 2018
Calculation Description: Title 24 Analysis
Input File Name: Jones Res -Jody Jones-18.ribdx
CF 'RF-01
Page 5 of 11
WINDOWS
01
02
03
04
05
06
07
08
09
10
Name
Type
Surface (Orientation -Azimuth)
Width (ft)
Height (ft)
Multipli
er
Area
(ft)
U-factor
SHGC
Exterior Shading
A
Window
N Wall (Left-0)
-
----
1
40.0
0.34
0.13
Insect Screen (default)
A 2
Window
E Wall (Back-90)
-
1
40.0
0.34
0.13
Insect Screen (default)
A 3
Window
W Wall (Front-270)
---
1
40.0
0.34
0.13
Insect Screen (default)
A 4
Window
W Wall (Front-270)
-----
1
40.0
0.34
0.13
Insect Screen (default)
A 5
Window
E Wall 2 (Back-90)
--
1
40.0
0.34
0.13
Insect Screen (default)
A 6
Window
E Wall 2 (Back-90)
--
-
1
40.0
0.34
0.13
Insect Screen (default)
A 7
Window
E Wall 2 (Back-90)
----
--
1
40.0
0.34
0.13
Insect Screen (default)
A 8
Window
E Wall 2 (Back-90)
--
-----
1
40.0
0.34
0.13
Insect Screen (default)
A 9
Window
E Wall 2 (Back-90)
-
---
1
40.0
0.34
0.13
Insect Screen (default)
A 10
Window
S Wall 2 (Right-180)
-
-
1
40.0
0.34
0.13
Insect Screen (default)
All
Window
S Wall 2 (Right-180)
-
1
40.0
0.34
0.13
Insect Screen (default)
A 12
Window
W Wall 2 (Front-270)
-
--
1
40.0
0.34
0.13
Insect Screen (default)
A 13
Window
W Wall 2 (Front-270)
-
--
1
40.0
0.34
0.13
Insect Screen (default)
B
Window
W Wall 2 (Front-270)
--
--
1
12,5
0.32
0.16
Insect Screen (default)
A 14
Window
W Wall 2 (Front-270);
-
1
-40.0
0.34
0.13
Insect Screen (default)
Entry
Window
W Wall 2 (Front-270)
-
--
1
52.0
1.19
0.59
Insect Screen (default)
Skylight
Skylight
Roof (Front-270)
1
4.0
0.48
0.27
C
Window
N Wall 2 (Left-0)
--
-
1
4.0
0.32
0.20
Insect Screen (default)
B 2
Window
N Wall 2 (Left-0)
-
1
12.5
0.32
0.16
Insect Screen (default)
C 2
Window
N Wall 2 (Left-0)
--
-
1
4.0
0.32
0.20
Insect Screen (default)
B 3
Window
N Wall 2 (Left-0)
-
--
1
12.5
0.32
0.16
Insect Screen (default)
A 15
Window
E Wall 3 (Back-90)
-
--
1
40.0
0.34
0.13
Insect Screen (default)
A 16
Window
S Wall 4 (Right-180)
---
-
1
40.0
0.34
0.13
Insect Screen (default)
A 17
Window
S Wall 4 (Right-180)
--
1
40.0
0.34
0.13
Insect Screen (default)
Sola Tube
Skylight
Roof 2 (Front-270)
1
1.2
0.30
0.30
Registration Number: 216-N0207144G-000000000-0000 Registration Date/Time: 2018-10-11 09:58:54 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 Report Generated at: 2018-10-1109:51:34
CERTI TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE' 'HOD
')RF-01
CF
Project Name: Jones Residence
Calculation Date/Time: 09:50, Thu, Oct 11, 2018
Page 6 of 11
Calculation Description: Title 24 Analysis
Input File Name:
Jones Res -Jody Jones-18.ribdx
OPAQUE SURFACE CONSTRUCTIONS
01 02
03
04
05
06-1
07
Construction Name Surface Type
Construction Type
Framing
Total Cavity
R-value
Winter Design
U-value
Assembly Layers
• Cavity/Frame: no insul. /2x4 Top Chrd
Attic Roofmaster Attic Roofs
Wood Framed Ceiling
2x4 Top Chord of Roof Truss @ 24
in. O.C.
Roof Deck: Wood Siding/sheathing/decking
none
0.644
Roofing: Light Roof (Asphalt Shingle)
Ceilings (below
• Inside Finish: Gypsum Board
R-38 Roof Attic attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 38
0.025
Cavity/Frame: R-9.1 /2x4
Over Ceiling Joists: R-28.9 insul.
Inside Finish: Gypsum Board
• Cavity / Frame: R-21 / 2x6
R-21 Wall (W.21.2x6.16) Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
0.066
Exterior Finish: Wood
Siding/sheathing/decking
• Cavity/Frame: no insul. /2x4 Top Chrd
Attic Roofliving Attic Roofs
Wood Framed Ceiling
2x4 Top Chord of Roof Truss @ 24
in. O.C.
- Roof Deck: Wood Siding/sheathing/decking
none
0.644
Roofing: Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
• Cavity / Frame: R-38 / 2x4
R-38 Roof Attica Cathedral Ceilings Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 38
0.041
• Roof Deck. Wood Siding/sheathing/decking
Roofing: Light Roof (Asphalt Shingle)
• Cavity/Frame: no insul. /2x4 Top Chrd
Attic Roofbed Attic Roofs
Wood Framed Ceiling
2x4 Top Chord of Roof Truss "@ 24
in. O.C.
Roof Deck. Wood Siding/sheathing/decking
none
0.644
Roofing: Light Roof (Asphalt Shingle)
Attic Rooffamily Attic Roofs
2x4 Top Chord of Roof Truss @ 24
• Cavity/Frame: no insul. /2x4 Top Chrd
Roof Deck.' Wood Sidinglsheathing/decking
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
SLAB FLOORS
01
02
03
04
05
06 07
Name
Covered Slab
Covered Slab 2
Covered Slab 3
Covered Slab 4
Zone
master
living
bed
family
Area (ft2)
836
1521
1015
280
Perimeter (ft)
106
106
96
46
Edge Insul. R-value & Depth
None
None
None
None 10.8
Carpeted Fraction
0.8
0.8
0.8
Heated
No
No
No
No
Registration Number: 216-N0207144G-000000000-0000 Registration Date/Time: 2018-10-11 09:58:54 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 Report Generated at: 2018-10-1109:51:34
CERTI' TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE' HOD
Project name: Jones Residence Calculation Date/Time: 09:50, Thu, Oct 11, 2018
Calculation Description: Title 24 Analysis Input File Name: Jones Res -Jody Jones-18.ribdx
BUILDING ENVELOPE - HERS VERIFICATION
02 03
01
Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage
Not Required Not Required Not Required
TING SYSTEMS
04
CFM50
WATER HEA
03
04
05
01
4
02
System Type
Distribution Type
Water Heater
Number of Heaters
Name
Standard
DHW Heater 1
2
DHW Sys 1 - 1/2
DHW
WATER HEATERS
05
06 07
01
02
03
Tank Exterior
fTankfVolum]eEnergy
Factor or
nsuation
Heater Element Type
Tank Type
Efficiency
Input Rating R-value
Name
50
0.6
34000-Btu/hr 0
DHW Heater 1
Natural Gas
Small Storage
WATER HEATING - HERS VERIFICATION
01
Name
DHW Sys 1 - 1/2
SPACE CONDITIONING SYSTEMS
01
SC Sys Name
AC #41
AC #32
AC #23
AC #14
CF ''RF-01
Page 7 of 11
06
Solar Fraction (%)
.0%
08
Standby Loss
(Fraction)
0
02
03
04 05
06
07
Recirculation
Central DHW
Pipe Insulation
Parallel Piping Compact Distribution Point -of Use
Control
Distribution
02
03
04
05
06
System Type
Heating Unit Name
Cooling Unit Name
Fan Name
Distribution Name
Other Heating and Cooling
Heating Component 1
Cooling Component 1
HVAC Fan 1
Air Distribution System 1
System
Other Heating and Cooling
Heating Component 2
Cooling Component 2
HVAC Fan 2
Air Distribution System 2
System
Other Heating and Cooling
Heating Component 3
Cooling Component 3
HVAC Fan 3
Air Distribution System 3
System
Other Heating and Cooling
Heating Component 4
Cooling Component 4
HVAC Fan 4
Air Distribution System 4
System
Registration Number: 216-N0207144G-000000000-0000 Registration Date/Time: 2018-10-11 09:58:54
HERS Provider: CaICERTS inc
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433
Report Generated at: 2018-10-1109:51:34
CERTI[ TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE O
Calculation Date/Time: 09:50, Thu, Oct 11, 2018
Project Name: Jones Residence
Input File Name: Jones Res -Jody Jones-18.ribdx
Calculation Description: Title 24 Analysis
HVAC - HEATING UNIT TYPES 02
01
Type
Name
Heating Component 1 CntrlFurnace - Fuel -fired central furnace
Heating Component 2 CntrlFurnace - Fuel -fired central furnace
Heating Component 3 CntrlFumace . Fuel -fired central furnace
Heating Component 4 CntdFurnace - Fuel -fired central furnace
HVAC - COOLING UNIT TYPES 04 05
0
02
1 03
Efficiency
Name
Cooling Component 1
Cooling Component 2
Cooling Component 3
Cooling Component 4
HVAC COOLING - HERS VERIFICATION
01
Name
Cooling Component 1-hers-cool
Cooling Component 2-hers-cool
Cooling Component 3-hers-cool
Cooling Component 4-hers-cool
EER
SEER
Zonally Controlled
System Type
12.7
16
Not Zonal
SplitAirCond
12.7
16
Not Zonal
SplitAirCond
12.7
16
Not Zonal
SplitAirCond
12.7
16
Not Zonal
5plilAifCQnd
03
Efficiency
80 AFUE
80 AFUE
80 AFUE
80 AFUE
06
Multi -speed
Compressor
Single Speed
Single Speed
Single Speed
Single Speed
CF 'RF-01
Page 8 of 11
07
HERS Verification
Cooling Component
1-hers-cool
Cooling Component
1-hers-cool
Cooling Component
1-hers-cool
Cooling Component
1-hers-cool
03
04
05
06
02
Verified Refrigerant
Airflow Target
Verified EER
Verified SEER
Charge
Verified Airflow
Required
Required
Required
Required
350
Required
Required
Required
Required
350
Required
Required
Required
Required
350
Required
Required
Required
Required
350
Registration Date/Time: 2018-10-11 09:58:54
HERS Provider: CaICERTS inc.
Registration Number: 216-N0207144G-000000000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016 433 Report Generated at: 2018-10-1109:51:34
CERTII TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE CalculOation DatelTime: 09:50, Thu, Oct 11, 2018
Project Name: Jones Residence Input File Name: Jones Res -Jody Jones-18.ribdx
Calculation Description: Title 24 Analysis
HVAC - DISTRIBUTION SYSTEMS 04 05
02 03
01 Insulation R-value Duct Location
Type Duct Leakage
Name 8 Conditioned zone
DuctslnAll Sealed and tested
Air Distribution System 1 Conditioned zone
Sealed and tested 8
DuctslnAll
Air Distribution System 2 Conditioned zone
Sealed and tested 8
ctslnAll
Air Distribution System 3 DuAttic
Sealed and tested 8
Air Distribution System 4 DuctsAttic
HVAC DISTRIBUTION - HERS VERIFICATION
01 02
Duct Leakage
Verification
Required
ed
Required
ed
Required
Required
Name
Air Distribution System 1-hersist
Air Distribution System 2-hers list
Air Distribution System 3-hers-dist
Air Distribution System 4-hers-dist
HVAC-FAN SYSTEMS
01
Name
HVAC Fan 1
HVAC Fan 2
HVAC Fan 3
HVAC Fan 4
HVAC FAN SYSTEMS - HERS VERIFICATION
01
Name
FEEEHVAC Fan 1-hers-fan
HVAC Fan 2-hers-fan
HVAC Fan 3-hers fan
03
Duct
Target (°/a)
6.0
6-0
6.0
6.0
04
Verified Duct
Location
Required
Required
Required
Not Required
02
Type
Single Speed PSC Furnace Fan
Single Speed PSC Furnace Fan
Single Speed PSC Furnace Fan
Single Speed PSC Furnace
Registration Number: 216-N0207144G-000000000-0000
CA Building Energy Efficiency Standards - 2013 Residential Compliance
05
Verified Duct
Design
Not Required
Not Required
ed
Not Required
Not Required
02
Verified Fan Watt Draw
Required
Required
Required
06
Buried
Ducts
Not Required
Not R�
Not Required
NotesRequired
03
Fan Power (WattsICFM)
0.58
0.58
0.58
0.58
Registration Date/Time: 2018-10-11 09:58:54
Report Version - CF1R-01212016-433
06
Bypass Duct
None
None
None
None
07
Deeply
Ducts
Not Required
Not Required
Not Required
Not Required
CF 'RF-01
Page 9 of 11
07
HERS Verification
Air Distribution System
1-hers-dist
Air Distribution System
2-hers-dist
Air Distribution System
3-hers-dist
Air Distribution System
4-hers-dist
08
Low -leakage
Air Handler
04
HERS Verification
HVAC Fan 1-hers-fan
HVAC Fan 2-hers-fan
HVAC Fan 3-hers-fan
HVAC Fan 4-hers-fan
03
Required Fan Efficiency (Watts/CFM)
0.58
0.58
0.58
HERS Provider: CaICERTS inc.
Report Generated at: 2018-10-1109:51:34
CF °RF-01
CERTIF. TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE ! 401) Page 10 of 11
Calculation DatelTime: 09:50, Thu, Oct 11, 2018
Project Name: Jones Residence Input File Name: Jones Res -Jody Jones-18.ribdx
Calculation Description: Title 24 Analysis
0.58
Required
HVAC Fan 4-hers-fan
IAQ (Indoor Air Quality) FANS 03 04 05 06
01 02 IAQ Recovery
o HERS Verification
IAQ WattsICFM IAQ Fan Type Effectiveness(%)
Dwelling Unit IAQ CFM Default 0 Required
SFam IAQVentRpt
74.02 0.25
ti.CaICERTS, Incs,
HERS p,_- 7o iDER
Registration Date/Time: 2018-10-11 09:58:54
HERS Provider: caICERTS inc.
Registration Number: 216-N0207144G-000000000-0000 Report Generated at: 2018-10-1109:51:34
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R 01212016-433
CERTIF' TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE / 40D
Project Name: Jones Residence Calculation Daterrime: 09:50, Thu, Oct 11, 2018
Calculation Description: Title 24 Analysis Input File Name: Jones Res -Jody Jones-18.ribdx
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Tim Scott
Company:
Scott Design and Title 24, Inc.
Address:
77085 Michigan Drive
City/State/Zip:
Palm Desert, CA 92211
RESPONSIBLE PERSON'S DECLARATION STATEMENT
Documentation Author Signature -
Signature Date:
2018-10-11 09:58:54
CEA/HERS Certification Identification (If applicable):
Phone:
760-200-4780
CF `RF-01
Page 11 of 11
l certify the following under penalty of perjury, under the laws of the State of California:
risibility for the building design identified on
1. I am eligible under Division 3 of the Business and Professions Code to accept respoifid this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
atures identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance do
3. The building design features or system design fecumen ,
worksheets, calculations, plans and specifications submitted to the enformnent agency for approval with this building permit application.
Responsible Designer Signature
Responsible Designer Name: 14 it
Tim Scott
Date Signed:
Company: 1
201$-14-11�9:58:54
Scott Design and Title 24, Inc.
License:
Address:
77085 Michigan Drive na
Phone-
City/State/Zip:
760-200-4780
Palm Desert, CA 92211
Digitally signed by CaICERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration
Provider responsibility for the accuracy of the information.
Registration Number: 216-N0207144G-000000000-0000 Registration Date/Time: 2018-10-11 09:58:54
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433
Ell TO
Easy to Verify
at CaICERTS.com
HERS Provider: CaICERTS inc.
Report Generated at: 2018-10-1109:51:34
RESIDENTIAL MEASURES SUMMARY RMS-1
Project Name Building Type m Single Family ❑ Addition Alone
Jones Residence ❑ Multi Family ❑ Existing+ Addition/Alteration Date
Project Address 1011112018
California Energy Climate Zone Total Cond. Floor Area Addition # of Units
Lot #59, San Lucas La Quints CA Climate Zone 15 3, 652 n/ti 1
INSULATION Area
Construction Type
Cavit ft) Special Features
Status
Roof Wood Framed Attic
R 38 3,647
Wall Wood Framed
R 21 4,818
New
Slab Unheated Slab -on -Grade
- no insulation 3,652 Perim = 354'
New
Demising Wood Framed
R 13 1,435
New
New
FENESTRATION
Orientation Area
ft2
Total Area:
U-Fac SHGC
783 Glazir,I Percents e: 21.4
0.40
OverhangSidefins
Exteriror Shadesa�r
Status
Left (N)
40.0
0.340
0.13 none none
Bug Screen
New
Rear (E)
280.0
0.340
0.13 none none
Bug Screen
New
Front (W)
200.0
0.340
0.13 none none
Bug Screen
New
Skylight
4.0
0.480
0.27 none none
None
New
Right (S)
160.0
0.340
0.13 none none
Bug Screen
New
Front (W)
12.5
0.320
0.16 none none
Bug Screen
New
Front (W)
52.0
1.190
0.59 none none
Bug Screen
New
Left (N)
8.0
0.320
0.20 none none
Bug Screen
New
Left (N)
25.0
0.320
0.16 none none
Bug Screen
New
Skylight
1.2
0.300
0.30 none none
None
New
HVAC SYSTEMS
Qty. He ting
Min. Eff
Cooling Min. Eff
Thermostat
Status
1 Central Furnace
80% AFUE
Split Air Conditioner 16.0 SEER
Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner 16.0 SEER
Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner 16.0 SEER
setback
HVAC DISTRIBUTION
New
Location
Heating
Cooling Duct Location
Duct
R-Value
Status
AC #4
Ducted
Ducted Conditioned
8.0
AC #3
Ducted
Ducted Conditioned
8.0
New
AC #2
Ducted
Ducted Conditioned
New
WATER HEATING
e.o
New
Qty. Type
Gallons Min. Eff Distribution
2 Small Storage Gas
50
0.60
Status
Standard
New
14 of
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
Jones Residence
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration 11011112018
Date
Project Address
Lot #59, San Lucas La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
3,652
Addition
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity ft Special Features Status
FENESTRATION Total Area: 789 Glaxin Percents e: 21A % New/Altered Average U-Factor: 0-40
Orientation Area ftz U-Fac SHGC Overhang Sidefins Exterior Shades Status
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE
Split Air Conditioner 16.0 SEER Setback New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R-Value Status
AC #1 Ducted
Ducted Attic 8.0 New
WATER HEATING
Qty. Type Gallons Min. Eff Distribution Status
Ens Pro 6. by EnergySoft User Number,• 6712
/D: Pa a 15 of 40
2013 Low -Rise Residential Mandatory Measures Summary
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the
rninnhanre annroarh used_ Fxrenrionr may anniv. Review the resueetive code section For more information.
Building Envelope Measures:
§ 110.6(a)1:
Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§ 110.6(a)5:
Fenestration products (except field -fabricated windows) have a label listing the certified U-Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of § 10-111 (a).
§ 110.7:
Exterior doors and windows are weatherstripped; all joints and penetrations are caulked and sealed.
§ 110.8(a):
Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R.
§ 110.8(1):
The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of § 110.8(i) when the
installation of a cool roof is specified on the CFIR.
§110.80):
A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CF1R.
Minimum R-30 insulation in wood -frame ceiling; or the weighted average U-factor shall not exceed 0.031. Minimum R-19 in a
§ I50.0(a):
rafter roof alteration. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The
attic access shall be gasketed to prevent air leakage.
§ 150.0(b):
Loose fill insulation shall conform with manufacturer's installed design labeled R-value.
§ 150.0(c):
Minimum R-13 insulation in 2x4 inch wood framing wall or have a U-factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U-
factor).
§ 150.0(d):
Minimum R-19 insulation in raised wood -frame floor or 0.037 maximum U-factor.
In Climate Zones 14 and 16 a Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior
§150.0(g)l:
walls, vented attics and unvented attics with air -permeable insulation.
In Climate Zones 1-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class II
§ I50.0(g)2:
vapor retarder.
In a building having a controlled ventilation crawl space, a Class I or Class II vapor retarder shall be placed over the earth floor of
§ I50.0(g)3:
the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section
150.0 d .
§ 150.0(1):
Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%;
have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration;
and when installed as part of a heated slab floor meets the requirements of § 110.8
150.0
§ (q)'
Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U-
factor of 0.58, or the weighted average U-factor of all fenestration shall not exceed 0.58.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
§150.0(e)IA:
Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§ 150.0(e)1B:
Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a readily accessible, operable, and tight -fitting damper or a combustion -air control device.
§150.0(e)1C:
Masonry or factory -built fireplaces have a flue damper with a readily accessible control.
Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside
§ I50.0(e)2:
of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110.0-§110.3:
HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified to the Energy Commission.
§ 110.3(c)5:
Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation
valve, and recirculation loop connection requirements of §I10.3(c)5.
Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appli-
§ 110.5:
ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool
ands a heaters.
§150.0(h)l:
Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified
in § 150.0(h)2.
Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any
§ 150.0(h)3A:
dryer vent.
§ I50.0(i):
Heating systems are equipped with thermostats that meet the setback requirements of § 110.2(c).
§150.00)IA:
Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§150.00)1B:
Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, have R-12 external
insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank.
For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage
tank, all piping with a nominal diameter of 3/4 inch or larger, all piping associated with a domestic hot water recirculation system
§ 150.00)2A:
regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and
all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3-
A.
§ I50.00)2B:
All domestic hot water pipes that are buried below grade must be installed in a water proof and non -crushable casing or sleeve
that allows for installation, removal, and re iacement of the enclosed pipe and insulation.
2013 Low -Rise Residential Mandatory Measures Summary
§ I50.00)2C: Pipe for cooling system lines shall be insulated as specified in § I50.00)2A. Piping insulation for steam and hydronic heating
systems or hot waters stems with pressure > 15 psi& shall meet the re uirements in TABLE 120.3-A.
150.0 03: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
_ ,- _ _I r__ _ .•s.. ..L..11 .,A . ,.' L1, .. .h. W. f,• .,,rt. — —A— Rnr
§ 150.00)3A:
1116UlalIV11 UAt/UOVU — Wl•0.L11 J1L(L.. a.a. . —.u.vu .va .•,..a.v»• ».••. ,•• ••••••»••—•• ••---• » -- • ---------- --- -- ---- -- - -
example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or
ainted with coating that is water retardant andprovide,,; shielding from solar radiation that degrades the material.
Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I
§ 150.00)3B:
or Class II vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class II vapor
retarder.
Systems using gas or propane water heaters to serve individual dwelling units shall include: a 120V electrical receptacle within 3
feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the
§ 150.0(n)l:
space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed
water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000
Btu/hr.
§ 150.0(n)2:
Recirculating loops serving multiple dwelling units shall meet the requirements of § 110.3(c)5.
Solar water -heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC)
§ I50.0(n)3:
or by a testing agency aeproved by the Executive Director.
Ducts and Fans Measures:
All air -distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC §601.0, §602.0,
§603.0, §604.0, §605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition.
Supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC
§605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed
§ 150.0(m) l:
with mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL I81 A, or UL 181 B or
aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than %a inch, the
combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums
defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying
conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms
shall not be compressed to cause reductions in the cross -sectional area of the ducts.
Factory -Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; joints
§ 150.0(m)2:
and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is
used in combination with mastic and draw bands.
150.0 m 3-6: rieta-ranrlcatea LUCI Jysiems snan comply wlue loyuucu1c111J LUl. t11GJJUlI'JVl,J1L1YV .uyw, •••w�.. "»• ••.�, ••
§ ( ) ..:i:•.•i f .• A,,..t d—f inc„lntinn R -vnhle rnlinacr duct insulation thickness: and duct labelinit.
All tan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic
§ 150.0(m)7:
dampers.
Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers
§150.0(m)8:
except combustion inlet and outlet air openings and elevator shaft vents.
Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not
limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum,
§ 150.0(m)9-.
sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is
water retardant and provides shielding from solar radiation.
§ 150.0(m)l0:
Flexible ducts cannot have porous inner cores.
When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be
§I50.0(m)11:
sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference
Residential Appendix RA3.
Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal
§ 150.0(m)12:
conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of
1 50.0rn 12.
Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the
placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The
§ 150.0(m)13:
space conditioning system must also demonstrate airflow_ 350 CFM per ton of nominal cooling capacity through the return
grilles, and an air -handling unit fan efficacy < 0.58 W/CFM as confirmed by field verification and diagnostic testing, in
accordance with Reference Residential A . endix RA3.
Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode,
an airflow from the dwelling, through the air handler fan and delivered to the dwelling, of >_ 350 CFM per ton of nominal cooling
§ 150.0(m)15:
capacity, and operating at an air -handling unit fan efficacy of < 0.58 W/CFM as confirmed by field verification and diagnostic
testing. in accordance with Reference Residential Appendix RA3.
All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of
§150.0(o):
central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the
Whole Building Ventilation.
Whole Building Ventilation airflow, shall be confirmed through field verification and diagnostic testing, in accordance with
Reference Resident.
lmlxiq
Pool and Spa Heating Systems and Equipment Measures:
Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
§ 110.4(a): Regulations; an on -off switch mounted outside of the heater that allows shutting off the heater without adjusting the thermostat
settinst: a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heatin
2013 Low -Rise Residential Mandatory Measures Summary
§ 110.4(b)1:
Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction
and return lines, or bui it -up connections for future solar heating.
§ 110.4(b)2:
Outdoor pools or spas that have a heat pump or gas heater shall have a cover.
§ 110.4(b)3:
Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro-
grammed to run only during off-peak electric demand . eriods.
§ 110.5:
Natural gas pool and spa heaters shall not have a continuous burning pilot light.
§ 150.0(p):
Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements.
Lighting Measures:
§ 110.9.
All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of § 110.9.
§ 150.0(k)IA:
Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with § 150.0(k) in accordance with TABLE
150.0-A or TABLE 150.0-B, as applicable.
§ 150.0(k)1 B:
When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply
with the applicable provisions of § 150.0(k).
The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with
§ 150.0(k)1 C:
§ 130.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has
been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180
watts of low efficacy lighting er electrical box.
§150.0(k)1D:
Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz.
Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no
§ 150.0(k)1 E:
more than 5 watts of power per luminaire or exhaust fan as determined in accordance with § 130.0(c). Night lights do not need to
be controlled by vacancy sensors.
§ 150.0(k)1 F:
Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable
requirements of § 150.0(k).
§ 150.0(k)2A:
High efficacy luminaires must be switched separately from low efficacy luminaires.
§ 150.0(k)2B:
Exhaust fans shall be switched separately from lighting systems.
§ 150.0(k)2C:
Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF.
§150.0(k)2D:
Controls and equipment are installed in accordance with manufacturer's instructions.
§ 150.0(k)2E:
No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with § 150.0(k).
§ I50.0(k)2F:
Lighting controls comply with applicable requirements of § 110.9.
An Energy Management Control System (FMCS) may be used to comply with dimmer requirements if: it functions as a dimmer
§ 150.0(k)2G:
according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements of § 130.5; and all other
requirements in § 150.0(k)2.
An Energy Management Control System (EMCS) may be used to comply with vacancy sensor requirements of § I50.0(k) if: it
§ 150.0(k)2H:
functions as a vacancy sensor according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements
of § 130.5; and all other requirements in § 150.0(k)2.
§ 150.0(k)2I:
A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the
functionality of a dimmer according to § 110.9, and complies with all other applicable requirements in § 150.0 k 2.
§ 150.0(k)3A:
A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only
§ 150.0(k)3B:
the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are
considered kitchen lighting if they are not separately switched from kitchen li htin .
§ 150.0(k)4:
Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated
cabinet.
§ 150.0(k)5:
A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom
shall be high efficacy or controlled by vacancy sensors.
§ 150.0(k)6:
Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§ 150.0(k)7:
Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high
efficac. or shall be controlled by either dimmers or vaeancy sensors.
Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other
nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0
CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing
§ 150.0(k)8:
and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and
allow ballast maintenance and replacement without requiring cutting holes in the ceiling.
For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with § I50.0(k), the ballasts
shall be certified to the Energy Commission to comply with the applicable requirements in § 110.9.
For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the
same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and
§ I50.0(k)9A:
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically
reactivates the motion sensor within 6 hours; and
iii. Controlled by one of the following methods:
2013 Low -Rise Residential Mandator Measures Summary
F-
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is
programmed to automatically turn the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of
an astronomical time clock in accordance with § 110.9; meets the Installation Certification requirements in § 130.4; meets the
requirements for an EMCS in § 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is mrogrammed to automatically turn the outdoor lighting OFF during da li ht hours.
For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor
lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
§150.0(k)9B: following requirements:
i. Shall comply with § 150.0(k)9A; or
ii. Shall comply with the appiicable requirements in § 110.9, § 130.0, § 130.2, § 130.4, § 140.7 and § 141.0.
§ I50.0(k)9C: For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by.§ 150.0(k)9B or 150.0(k)9D
shall comply with the applicable requirements in 110.9 130.0, ' 130.2 § 130.4, § 140,7 and § 141.0.
§ I50.0(k)9D: Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply
with the applicable requirements in § 110.9 130.0 130.2, § 130.4 140.7 and § I41.0.
§ 150.0(k)10: Internally illuminated address signs shall comply with § 140.8, or shall consume no more than 5 watts of power as determined
according to § 130.0(c).
§ 150.0(k)11: Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for
nonresidential garages in ' 110. 9J 13 0. 0130.1, § 130A, § 140.E and J 141.0.
In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of
§150.0(k)12A: the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor,
In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20
percent of the floor area, permanently installed lighting in that building shall:
§ 150.0(k)1213: i. Comply with the applicable requirements in § 1 10.9, § 130.0, § 130.1, §I40.6 and §141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
inRress and egress.
Solar Ready Buildings:
§110.10(a)1:
§ 110.10 a 2:
§I10.10(b)1:
§ 110.10(b)2:
§ 110.10(b)3A:
§I10.10(b)3B:
§ 110. l 0(b)4:
§ 110.10(c):
Single family residences located in subdivisions with ten or more single family residences and where the application for
tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January 1, 2014,
shall comply with the requirements of 110.10 through §110.10(e).
Low-rise multi -family buildin s shall comply with the requirements of § 110.10 through § 110.10 d
The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway, smoke
ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a
local jurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than
80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for
buildings with roof areas greater than 10,000 square feet.
For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less
than 250 square feet. For low-rise multi -family buildings the solar zone shall be located on the roof or overhang of the building or
on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the
building project and have a total area no Iess than 15 percent of the total roof area of the building excluding any skylight area.
All sections of the solar zone located on steep -sloped roofs shall be oriented between 110 degrees and 270 degrees of true north.
No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be
located in the solar zone.
Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice
the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the
horizontal projection of the nearest point of the solar zone, measured in the vertical plane.
For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly
indicated on the construction documents.
The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit
from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water -heating
§ 110.10(d): A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through § 110.10(c)
shall be rovided to the occu ant.
§ 110.10(e)1: The main electrical service panel shall have a minimum busbar rating of 200 amps.
The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a
§ 110.10(e)2: future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or
main circuit location, and perm:uientl) marked as "For Future Solar Electric".
HVAr. SYSTEM W=ATIAIr Aklfl ^/'1^1 twin t n A r
rrolect Name
Jones Residence
5ysiem Name
AC #4
ENGINEERING CHECKS
Number of Systems 1
Heating System
Oiuitipult per System
71,000
Total output stuh
71.000
Dut ut Stuhls ft
84.9
Cooling System
Output per Sys to m
36,000
Total Output Btuh
36,000
Total Output Tons
3.0
Total Output Btuhls ft
43.1
Total Output s ftfTon
278.7
Air System
CFM per System
1.200
Airflow cfm
1,200
Airflow cfmis ft
1.44
Airflow cfmfTon
400.0
Outside Air %
11.0 %
Outside Air cfmis ft
0.16
SYSTEM LOAD
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
IS SUMMARY
Date
10/11/2018
Floor Area
836
COIL COOLING PEAK COIL HTG. PEAK
CFM
J Sensible
Latent
CFM
Sensible
655
10,465
1,286
253
13,536
0
151
161
0
0
132
5,900
2,572
132
6,462
0
151
16,667 3,858
0
161
20,320
HVAC EQUIPMENT SELECTION
rane 3 Ton 25,370
total Adjusted System Output 25,370
(Adjusted for Peak Design conditions)
5
71,000
i 71,0001
Note: values above given at ARI conditions I TIME OF SYSTEM PEAK I Aug 3 PM Jan 1
HEATING SYSTEM PSYCHROMETRICS Airstream Tem ratures at Time of Neatin Peak
26 OF 67 OF 122 OF 122 OF
Outside Air
132 cfm Heating Coil Supply Fan
1,200 cfm 122 OF
ROOM
72 OF --I !
_ IA 72 °F
COOLING SYSTEM
112/78OF
Outside Air
132 cfm
70/60°F
5 Airstream Temperatures at Time of Coc
75/62°F 55/54°F 55/54°F
Cooling Coil Supply Fan
1,200 cfm
6. by EnOWSofl User Number: 6712
1
55/54°F
56.4 % ROOM
70 / 60 OF
w
Page 20 of 40
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Jones Residence
Date
System Dame
10/11/2018
AC #3
Floor Area
ENGINEERING CHECKS
SYSTEM LOAD
1,521
NumberofSystems
1
COIL COOLING PEAK COIL HTG. PEAK
stem
Sensible Latent CFM Sensible
7HeatinCFM
Total Room Loads 1,979
A55
23,460 2,340 56922A4i
Stuh
Return Vented Lighting
0
ls ft
Return Air Ducts
340
CoR[[qq1 S tem
26'c
Return Fan
0 C
Out ut er S stem
57,500 Ventilation 284
12,642 3,654 284 13.862
total Ou ut Btuh
57,500 Supply Fan
2,943
Total Output Tons
4.81 Supply Air Ducts
-2,943
340
Total Output Btuhls Ft
37.8
262
Total output s Wron
317.4 TOTAL SYSTEM LOAD
39,725 5,994
Air S stem
33,490
CFM er S tem
2,000 HVAC EQUIPMENT SELECTION
Alrtlow cfm
2,000 Trane 5 Ton
Airflowcfmis ft
1.31
39,974 11,342 89,000
Airtlow cfmi fon
417.4
Outside Air %
14.2 % Total Adjusted System Output
39,974 11,342
Outside Alr cfmfs ft
0.18 (Adjusted for Peak Design conditions]
89,000
Note: values above given at ARI conditions TIME OF SYSTEM PEAK
Aug 3 PM
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time Heating
of Peak
26 OF
67 OF 109 OF 109 OF
0 T
-1 -
Outside Air
v ---------------------
284 cfm
Heating Coil Supply Fan
,
2,000 cfm
108 OF
72 OF
ROOM
_ _ _
72 OF
COOLING SYSTEM
112 / 78 OF
Outside Air
284 cfm
70 / 62 OF
.l
.t I . fl 4
1
5 Airstream Temperatures at Time of Coolin
Peak
77 / 65 OF 59 / 58 OF
59 / 58 OF
!!!!
Cooling Coil
Supply Fan
2,000 cfm
59 / 58 OF
64.9 % ROOM i
70 / 62 °F
6. byt=nergy5oft User Number., 6712
ID: Page 21 of 40
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Jones Residence
I AC #2
ENGINEERING CHECKS
Number of Systems 1
Heating S stem
Output per System
71,000
Total Output Btuh
71,000
Output (Stuh/sciftl
70.0
Cooling System
Output per System
36,000
Total Output Btuh
36,000
Total Output Tons
3.0
Total Output Stuhls ft
35.5
Total Output s ftrron
Air System
CFM per System
Airflow cfm
Airflow cfmis ft
Airflow cfmlFon
Outside Air %
338.3
1,200
1,200
1.18
400.0
12.7 %
Outside Air cfm/s ft
0.15
SYSTEM LOAD
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
HVAC EQUIPMENT SELECTION
frane 3 Ton
Total Adjusted System Output
(Adjusted for Peak Design conditions)
10/11/2018
Floor Area
1,015
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible
Latent
CFM
Sensible
624
9,442
1,562
222
11,734
0
137
140
0
0
152
6,788
2,726 152
7,436
0
137
16,503 4,288
0
140
19,448
25,232[ 5.837
71,000
i 71,0001
Note: values above given at ARI conditions I TIME OF SYSTEM PEAK Aug 3 PM Jan 1
HEATING SYSTEM PSYCHROMETRICS tAirsteam Temperatures at Time of Heating Peak
26 OF 66 OF 122 OF 122 OF
I '
Nr --I
Outside Air -�1-AV- N _
152 cfm Heating Coil Supply Fan
1,200 cfm 122 OF
72 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Coolinst Peak
ROOM
72 OF
112/78OF
75/63°F 56/55°F
56/55°F
®
Outside Air
I
152 cfm
Cooling Coil
Supply Fan
56 / 55 OF
1,200 cfm
58.4 % ROOM
70 / 61 °F
70 / 61 OF
4 AD'
_I
UT[
EnergyPro 6. by EnergySoff User Number: 6712 ID: Page 22 of 40
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Jones Residence
5ystern Name
AC #1
ENGINEERING CHECKS
Number of Svstems
Total Ou ut (Btu
Output_(Btuhlsgft
ding S tem
Output per Systat
Total Output (Btu
Total Output Ton
Total Output (Btu.
Air Svstem
1
SYSTEM LOAD
Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
51,000,Total
51,000
182.1
24.000
24,000
2.0
85.7
140.0
Date
10/11/2018
Floor Area
280
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible
Latent
CFM
Sensible
357
5,604
431
185
6.435
0
324
316
0
0
42
1,656
825 42
2,045
0
324
8,117 1,256
0
316
9,112
CFM perSystem
Airflow cf:m
1,200
1.200
HVAC EQUIPMENT SELECTION
Trane 2 Ton 12,805 7,160 51,000
Airflow cfm/s ft
4.29
I
Airflow efmlTon
600.0
Outside Air %
3.5 %
Total Adjusted System Output 12,805 7,160 51,000
(Adjusted for Peak Design conditions)
Outside Air cfm/s ft
0.15
NOW values above given at ARI conditions TIME OF SYSTEM PEAK I Aug 3 PM1 I Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26 OF 70 OF 105 OF 105 OF
op 0 .� t _I
Outside Air
42 cfm Heating Coil Supply Fan
1,200 cfm 105 °F
ROOM
72 OF - 7� OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78OF
72/61 OF 55/54°F 55/54°F
Outside Air
O I_T
0
42 cfm
Supply Fan
Cooling Coil
55 / 54 OF
1,200 cfm
56.1 % ROOM
70 / 60 OF
70 / 60 OF
6. by EnergySofl User Number: 6712 ID: Page 23 of 40
ZONE LOAD SUMMARY
Project Name
Jones Residence
Date
1011112018
System Name
AC #4
Floor Area
836
ZONE LOAD SUMMARY
ZONAL SYSTEM
COOLING PEAK
HEATING PEAK
ZONE NAME
master
SYSTEM NAME
Mull.
1.0
CFM
Sensible
Latent
Heating
OA CFM
132
Peak Hr
Aug 3 PM
CFM
655
Sensible
16,381
Latent
4,505
CFM
253
Sensible
20,016
TOTALS
0
0
0
132
Aug 3 PM
16,381
4,505
20,016
(BLOCK LOAD)EneTyPro
6. by EnergySofi user Number: 6712 Q. Page 24 of 40
ROOM LOAD SUMMARY
Project Name
Jones Residence
Date
1011112018
System Name
AC #2
Floor Area
1,015
ROOM LOAD SUMMARY
ROOM
COOLING PEAK
COIL COOLING PEAK
COIL HTG.
PEAK
Zone Name
Room Name
Mult.
CFM
Sensible
Latent
CFM
Sensible
Latent
CFM
Sensible
bed
Bedrooms 2 - 4
1
624
9,442
1,562
624
9,442
1,562
222
11,734
PAGE TOTAL 624 9,4421 1.562 2221 11.734
TOTAL 1 624 9.442 1,562 222 11,734
' Total includes ventilation load for zonal systems.
Enervem 6. by EnenqySoff User Number: 6712 1D: Page 30 of 40
ROOM HEATING PEAK LOADS
Date
Project Name 1 Jones Residence 10/11/2018
ROOM INFORMATION DESIGN CONDITIONS
Room Name Master Bedroom Time of Peak Jan 1 AM
Floor Area
836.00 ft2 Outdoor Dry Bulb Temperature 26 OF
Indoor Dry Bulb Temperature 72 OF
Conduction
Area
U-Value
R-38 Roof Attic
836.0 X v.v,
R-21 Wall (W.21.2x6.16)
1,466.0 X O.Oi
French Door.341..13
160.0 X 0.3.
Slab -On -Grade
perim = 106.0 X 0.7,
•R-13 Wall
412.0 X 0.1
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Items shown with an asterisk (') denote conduction through an interior surface to another room
Infiltration:[ 1.00 X
Schedule
Fraction
TOTAL HOURLY HEA
AT °F
Page Total
Btu/hr
1,000
4,653
2,502
3,559
0
j 11,7151
1.064 X $36 X 9.50 X 0.281 / 60 ] X 46 s
Air Sensible Area Ceiling Height ACH �7
FOR
User Number: 6712 ID:
j 1,6211
13, 536
ROOM HEATING PEAK LOADS
Project Name
Jones Residence
ROOM INFORMATION
Room Name
Floor Area
Indoor DrV Bulb Temperature
❑F51GN rnMnITIONS
Living Area Time of Peak
1,521.00 ft2 Outdoor Dry Bulb Temperature
72 °F
Area
U-Value
Conduction
1,517.0
X
0.0260
X
R-38 Roof Attic
4,0
X
0.4800
X
Skylight
1,255.5
X
0.0690
X
R-21 Wall (W.21.2x6.16)
400.0
X
0.3400
X
French Door.34/.13
ESlab-On-Grade
0.3200
X
12.5
�(
Casement .32/.16
1.1900
X
52.0
X
Custom Entry Door
Perim = 106.0
X
0.7300
X
355.0
X
0.1020
X
"R-13 Wall
X
X
X
X
X
X
X
X
X
x
X
x
x
x
x
x
x
x
x
x
x
X
x
x
mix
x
x
x
x
X
denote conduction through an interior surface to another room
Items shown with an asterisk (')
AT °F
Date
1011112018
Jan 1 AM
26 °F
Btu/hr
1,814
88
3,985
6, 256
184
2,846
3,559
0
18,734
1.00 1A64 X 1,521 X 11.20 X 0.238 / 60 ] X 4G = 3,313
Infiltration: X AT
Schedule Air Sensible
Area Ceiling fie�ght ACH
Fraction
22,047
TOTAL HOURLY HEAT LOSS FOR ROOM
ID: Ps e 33 of 40
User Number: fi712
ROOM HEATING PEAK LOADS
Project Name
Jones Residence
ROOM INFORMATION DESIGN CONDITIONS
Room Name Bedrooms 2 - 4 Time of Peak
Floor Area 1,015.00 W1 Outdoor Dry Bulb Temperature
Indoor Dry Bulb Temperature 72 OF.
Conduction
Area
U-Value
R-38 Roof Attic
1,015.0 x u.u.
R-21 Wall (W.21.2x6.16)
1,252.0 x 0.01
Casement .321..20
8.0 x 0.3:
Casement .32/.16
25.0 x 0.3:
French Door.34/.13
40.0 x 0.3,
Slab -On -Grade
perim = 96.0 x 0.7,
'R-13 Wall
388.0 x 0.1
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Items shown with an asterisk (') denote conduction through an Interior surface to another room
OT °F
Date
1011112018
■
I
�r
1
1
I
1
I
1
I
Jan 1 AM
26 OF
Btu/hr
1,214
3,974
118
368
626
3,224
0
9,5231
1.00 1.064 x 1,015 x 9.00 x 0.297 / 60 ] x 46 = 2,211
Infiltration: X
Schedule Air Sensible Area Ceiling Height ACH AT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 11,734
User Number: 6712 ID: Pa o 34 of 40
ROOM HEATING PEAK LOADS
Project Name
Jones Residence
ROOM INFORMATION DESIGN CONDITIONS
Room Name Family Room Time of Peak
Floor Area 280.00 ft' Outdoor Dry Bulb Temperature
Indoor Dry Bulb Temperature
72 OF
Conduction
R-38 Roof Attic
Solatube Skylight
R-21 Wall (W 21.2x6.16)
French Door .341..13
Slab -On -Grade
Area
U-Value
0.0260 X
0.3000 X
0.0690 X
0.3400 X
0.7300 X
0
280.0 X 0.102
"R-13 Wall
X
X
x
X
x
X
x
X
x
X
x
X
x
X
x
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Items shown with an asterisk (') denote conduction through an interior surface to another room
AT °F
Dace
1011112018
Jan 1 AM
26 OF
Btu/hr
333
17
2,679
1,251
1,545
0
5,825
1.00 1.064 X P80 X 9.00 X 0.297 / 60 ] X 46 = 610
Infiltration: X AT
Schedule Air Sensible Area Ceiling Height ACFi
Fraction
6 435
TOTAL HOURLY HEAT LOSS FOR ROOM
6712 ID: Page 35 of 40
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Jones Residence
ROOM INFORMATION
Room Name
Floor Area
Indoor Dry Bulb Temper
opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
"R-13 Wall
DESIGN CONDITIONS
Master Bedroom Outdoor Dry Bulb Temperature
836.00 ftZ Outdoor Wet Bulb Temperature
70 OF Outdoor Daily Range:
Orientation
Hate
1011112018
Area
U-Factor
CLTD'
836.0
X
0.0260
X
56.0 =
268.0
X
0.0690
X
23.0 =
268.0
X
0.0690
X
33.0 =
702.0
X
0.0690
X
26.0 =
228.0
X
0.0690
X
33.0 =
412.0
X
0.1020
X
0.0 =
X
X
=
X
X
=
X
X
=
Page Total
Items shown with an asterisk (`) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD) Chadpd Unshaded
Fenestration Orientation
A (N)
A (E)
A (M
A (M
I i::� F1
Area GLF Area
GLF
11.6
0.0 X 11.6 + 40.0
X
=
19.3
0.0 X 11.6 + 40.0
X
=
0.0 X 11.6 + 40.0
X
19.3
=
0.0 X 11.6 + 40.0
X
19.3
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
Page Total
Internal Gain _
El
Occupants X 245 Btuh/occ.Occu ants 0.50 E ui mentFloor Area X w/scift
Infiltration: 1.064 X 0.94 X 38.43 X 42 =
Air Sensible CFM E AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
Latent Gain _
2.5 Occupants X 155 Btuh/occ.
Occupants -
Infiltration: 4,771 X 0.94 X 38.43 X 0.00523
Air Sensible CFM EL°' t,W
TOTAL HOURLY LATENT HEAT GAIN
112 OF
78 OF
34 OF
Btulhr
1,217
425
610
1.259
519
4,031
Btulhr
774
774
2.786
Btulhr
614
1,427
1, 60f
10,46!
Btu/hr
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Jones Residence
ROOM INFORMATION DESIGN CONDITIONS
Living Area Outdoor Dry Bulb Temperature
Room Name
1,521.00
ftZ Outdoor Wet Bulb Temperature
Floor Area
70 °F Outdoor Daily Range:
Indoor Dry Bulb Temperature
Opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
*R-13 Wall
Orientation
Date
1011112018
112 7F
78 OF
34 OF
Area
U-Factor
CLTD'
X
0.0260
X
56.0 =
X
0.0690
X
33.0 =
X
0.0690
X
26.0 =
XA0.06
X
33.0 =
I
X
X
0.0XXXXXXX
=
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded
Fenestration
Skylight
A
A
A
A
A
A
A
A
Orientation
Area
GLF
Area
GLF
56.5
0.0 X
19.9
+
4.0 X
=
0.0 X
11.6
+
40.0 X
19.3 =
0.0 X
11.6
+
40.0 X
19.3 =
0.0 X
11.6
+
40.0 X
19.3 =
0.0 X
11.6
+
40.0 X
19.3 =
0.0 X
11.6
+
40.0 X
19.3 =
0.0 X
11.6
+
40.0 X
11.7 =
0.0 X
11.6
+
40.0 X
11.7 =
0.0 X
11.6
+
40.0 X
19.3 -
Page Total
Internal Gain EE�
Btuh/occ.
Oauiment
nts 4 6 Occupants X -
E
1,521 Floor Area X w/sgft
Infiltration:
?.064 0.94 X X ELA 9.92 X AT 42
Air Sensible CFM
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
Latent Gain Btuh/occ.
Occupants 4•6 Occupants X 155
Infiltration: 4,771 X 0.94 X 69.92 X 0.00523 =
AW
Air Sensible CFM ELA
TOTAL HOURLY LATENT HEAT GAIN
6.
Btulhr
1,266
1,301
5,
Btulhr
226
774
774
774
774
774
466
466
Btu/hr
1'
2,+
2,
Btulhr
1
tr+J
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Jones Residence ❑ESIGN CONDITIONS
ROOM INFORMATION rature
Room Name
Floor Area
Indoor Dry Bulb Tem
ue Surfaces
Orientation
Living Area Outdoor Dry Bulb Tempe
1,521.00 ft2 Outdoor Wet Bulb Temperature
70 °F Outdoor Daily Range.
1011112018
112 °F
78 OF
34 OF
Area
U-Factor CLTD' Btulhr
X X =
X X
X X =
X X =
X X
X X
X X
X X =
X X
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded
Fenestration
A
B
A
Entry
Orientation
Area
GLF
Area
GLF
0.0 X
11.6
+
40.0 X
19.3 =
0.0 X
12.3
+
12.5 X
21.8 =
0.0 X
11.6
+
40.0 X
19.3 =
0.0 X
45.7
+
52.0 X
80.7 =
X
+
X
X
+
X
X
+
X
X
+
X
X
+
X
Page Total
internal Gain E�E�
Btuh/occ.occu ants 4.6 Occupants X w/sgft
ERuivment 1,521 Floor Area X
1.064 X 0.94 X 69.92 X e7 42
Infiltration: Et_A
Air Sensible CFM
TDTAL HOURLY SEIVSIf3L1= HEAT GAIN FOR ROOM
Latent Gain 155 Btuh/occ.
4.6 Occupants X
occu ants
4, 771 X 0.94 X 69.92 X 0.00523
Infiltration: ELA ❑W
Air Sensible CFM
TDTAL HDURLY LATENT HEAT GAIN FOR ROOM
fL]:
�_a i mar mimbPr- 6712
6tuthr
774
273
774
4,198
6, 018
itulhr
1,118
2,596
2, 923
::�-J23,460
Btulhr
707
1,633
707
iNP 38 of 40
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Jones Residence DESIGN CONDI I IVNS
ROOM INFORMATION Ib T m erature
Room Name
Floor Area
Indoor Dry Bulls Tern
O a ue Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
`R-13 Wall
nature
Bedrooms 2 - 4 Outdoor Dry Bu e p
1,015.00 ft2 Outdoor Wet Bulb Temperature
70 OF outdoor Daily Ran e:
orientation
Date
1011112018
112 OF
78 OF
34 OF
U-Factor
CLTD'
Btu/hr
Area
=
1,478
1,015.0
X
0.0260
X
669.0
X
0.0690
X
23.0
23.0 =
1,062
362.0
X
0.0690
X
33.0 =
824
96.0
X
0.0690
X
26.0 =
172
125.0
X
0.0690
X
33.0 =
285
388.0
X
0.1020
X
0.0 =
0
X
X
X
X
=
X
X
=
Page Total
3,821
denote conduction through an
interior surface to another room-
Items shown with an asterisk (")
Temperature Difference (CLTD)
Unshaded
1. Cooling Load
Shaded
Area
GLF
Area
GLF
Btulhr
estration Orientation
Frguo
13.8
+
4.0
X
13.8 =
55
X
12.3
+
12.5
X
12.3 =
154
X
13.8
+
4.0
X
13.8 =
55
X
12.3
12.5
X
12.3 =
154
X
11.6
+
+
40.0X
19.3 =
774X
X
+
X
=
X
+
X
=
X
+
X
=
X
+
X
Page Total
1,19
Internal Gain
Occupants X
245Btuh/occ.
74
17pccuats0.50
Floor Area X
RWI
w/sgft
F ui meet
1, 9:
1.064
X 0.94 X 6 666
42
X
AT
Infiltration:
Air Sensible
CFM ALA
9,4
TOTAL HDURLY
SENSIBLE BEAT GAIN FOR ROOM
Btulhr
Latent Gain
3.0 Occupants X
155 gtuh/occ.
Cccu ants
4, 771
X 0.94 X 46.66
X 0523
Infiltration:
Air Sensible
CFM EL
pW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
ID. Pa a 39
FnamvPra 6. by f ne Safi User Number: 6712
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Jones Residence
ROOM INFORMATION DESIGN CONDITIONS
Room Name Family Room Outdoor Dry Bulb Temperature
Floor Area 280.00 ftZ Outdoor Wet Bulb Temperature
Indoor Dry Bulb Temperature 70 'F1 Outdoor Dail Ran e:
opaque Surfaces
R-38 Roof Attic
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
R-21 Wall (W.21.2x6.16)
`R-13 Wall
Orientation
(W)
(N)
(W)I
Date
1011112018
112 OF
78 OF
34 OF
Area
X
X
X
X
X
X
X
X
X
U-Factor
X
X
X
X
X
X
X
X
X
CLTD1
=
=
=
=
=
=
=
=
=
278.8
0.0260
77.0
308.0
0.0690
31.0
228.6
0.0690
38.0
308.0
0.0690
55.0
280.0
0.1020
0.0
Page Total
Items shown with an asterisk (`) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD) Charlarl Unshaded
Fenestration
Sola Tube
A
A
Orientation
(W)
(S)
(S)
Btulhr
558
659
598
1,169
a
1 2,9841
Area
X
X
X
X
X
X
X
X
Xt:�::J
GLF
+
+
+
+
+
+
+
+
+
Area
X
Xq
X
X=
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
1.2
113.12
4 ..0
00.0
40.0
Page Total
Internal Gain
Into ants 0 8 Occupants X F:�:--245 Btuh/occ.Occup_
280 Floor Area X o.50 w/sgft =
Equipment
Infiltration: 1.064 X 0.94 X i2.87 X 42 =
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
Latent Gain
Cccu ants
0.8 Occupants X 155 Btuh/occ.
Infiltration: 4,771 X 0.94 X 12.87 X 0.00523 =
Air Sensible CFM FLA OW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
17.3
Btulhr
111
644
644
1,
Btu/hr
4
Btu/hr
130
301
130
Parrs 40 of 40