BRES2016-0169 Revision 1 Title 24BUILDING ENERGY ANALYSIS REPORT PROJECT: Jones Residence Lot #59, San Lucas La Quinta, CA 92253 Project Designer: Jones Development 78-060 Calle Estrado La Quinta, CA 92253 (760) 285-8712 Report Prepared by: Tim Scott Scott Design and Title 24, Inc, 74-818 Velie Way, Suite 8 Palm Desert, CA 92260?e ws 10ti (760) 200-4780 PFICEt1fEL DEC 20 2018 koll- r OF UI QUINTA COMMUNITY DEVELOPMENT Job Number: Date: 10/11/2018 TY OF LA QUINTA BUILDING DIVISION REVIEWED FOR CODE COMPLIANCE loSZoi BY OF—Fic The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC—www.energysoft.com. User TABLE OF CONTENTS Cover Page 1 Table of Contents 2 Form CF-1 R-PRF-01-E Certificate of Compliance 3 Form RMS-1 Residential Measures Summary 14 Form MF-1 R Mandatory Measures Summary 16 HVAC System Heating and Cooling Loads Summary 20 Zone Load Summary nA CERTIr TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE r 40D Project Name: Jones Residence Calculation Description: Title 24 Analysis Calculation Date/Time: 09:50, Thu, Oct 11, 2018 Input File Name: Jones Res -Jody Jones-18.ribdx GENERAL INFORMATION 01 Project Name Jones Residence 02 Calculation Description Title 24 Analysis 03 Project Location Lot #59, San Lucas 04 City La Quinta 05 06 Zip Code 92253 Standards Version Compliance 2015 08 Climate Zone CZ15 07 Compliance Manager Version BEMCmpMgr 2013-4b (433) 10 Building Type Single Family 09 Software Version EnergyPro 6.8 12 11 Front Orientation (deg/Cardinal) 270 Project Scope Newly Constructed 13 14 Total Cond. Floor Area (ft) 3652 Number of Dwelling Units 1 16 15 Number of Zones 4 Slab Area (ft) 3652 17 18 Addition Cond. Floor Area N/A Number of Stories 1 20 Addition Slab Area (ftZ) N/A 19 Natural Gas Available Yes 21 Glazing Percentage (%) 21.4% CF 'RF-01 Page 1 of 11 COMPLIANCE RESULTS 01 Building Complies with Computer Performance 02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CECa P pproved HERS provider. This compliance analysis is valid only for permit applications through December 31, 2016 ENERGY USE SUMMARY 04 05 06 Energy Use (kTDV/ft2-yr) Standard Design 07 08 Space Heating Proposed Design p 9 Compliance Margin Percent Improvement Space Cooling 3.52 4.73 -1.21 -34.4% IAQ Ventilation 114.39 100.8313.56 11.9% Water Heating 0.91 0.91.91 0.00 0.0% Photovoltaic Offset 7.00 9.36 -2.36 -33.70% Compliance Energy Total 125.82 0.00 0.00 115.83 9.99 7.9% Registration Number: 216-N0207144G-000000000-00o0 Registration Date/Time: 2018-10-11 09:58:54 CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 HERS Provider: CaICERTS inc. Report Generated at: 2018-10-1109:51:34 CERTI! TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE' HOD Project Name: Jones Residence CF 'RF-01 Calculation Date/Time: 09:50, Thu, Oct 11, 2018 Calculation Description: Title 24 Analysis Input File Name: Jones Res -Jody Jones-18.ribdx Page 2 of 11 REQUIRED SPECIAL FEATURES The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis. NO SPECIAL FEATURES REQUIRED HERS FEATURE SUMMARY The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is provided in the building components tables below. Building -level Verifications: • IAQ mechanical ventilation Cooling System Verifications: • Minimum Airflow • Verified EER • Verified SEER • Refrigerant Charge • Fan Efficacy Watts/CFM HVAC Distribution System Verifications: • Duct Sealing • Ducts located entirely in conditioned space Domestic Hot Water System Verifications: • -- Hone — ENERGY DESIGN RATING This is the sum of the annual TDV energy consumption for energy use components included in the performance compliance approach for the Standard Design Building (Energy Budget) and the annual TDV energy consumption for lighting and components not regulated by Title 24, Part 61,3L _ as domesticappliances and consumer electronics) and accounting for the annual TDV energy offset by an on -site renewable energy system. Total Energy (kTDV/f2-yr)* Reference Energy Use 165.34 includes calculated Appliances and Miscellaneous Energy Use (AMEU) BUILDING - FEATURES INFORMATION 01 02 03 Project Name Number of Dwelling 1 Conditioned Floor AErea(ft2]) Units Jones Residence 3652 1 Energy Design Rating 155.35 04 1 05 Number of Bedrooms Number of Zones 4 4 Margin 9.99 06 Number of Ventilation Cooling Systems 0 Percent Improvement 64 07 Number of Water Heating Systems 1 Registration Number: 216-N0207144G-000000000-0000 Registration Date/Time: 2018-10-11 09:58:54 CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 HERS Provider: CaiCERinc. Report Generated at: 2018-10-1109:51:34 4 CERTI' TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE' HOD CF `RF-01 Project Name: Jones Residence Calculation Date/Time: 09:50, Thu, Oct 11, 2018 Page 3 of 11 Calculation Description: Title 24 Analysis Input File Name: Jones Res -Jody Jones-18.ribdx OPAQUE SURFACES 01 Name N Wall E Wall S Wall W Wall Roof 3 E Wall 2 S Wall 2 W Wall 2 Roof 4 N Wall 2 E Wall 3 S Wall 3 W Wall 3 Roof 5 N Wall 3 S Wall 4 W Wall 4 Roof 6 02 Zone master master master master master iivinq living living living bed bed bed bed bed family family family family 03 Construction R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W21.2x6.16) R-21 Wall (W,21.2x6.16) R-38 Roof Attic R-21 Wall (W21.24.16) - R-21 Wall (W.21.2x6.16) R-21 Wall (W21.2x6.16) R-38 Roof Attic R-21 Wall (W21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-38 Roof Attic R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-38 Roof Attic 04 Azimuth 0 90 180 270 90 180 270 0 90 180 270 0 180 270 05 Orientation Left Back Right Front Back Right Front Left Back Right Front Left Right Front 06 Gross Area (ft2) 308 308 702 308 836 756 208 756 1517 702 402 96 125 1015 308 308 308 278.8 07 Window & Door Area (ft) 40 40 80 200 80 184.5 33 40 80 08 Tilt (deg) 90 90 90 90 90 90 90 90 90 90 90 90 90 90 Registration Number: 216-N0207144G-000000000-0000 Registration Date/Time: 2018-10-11 09:58:54 HERS Provider: CaICERTS inc. CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 Report Generated at: 2018-10-1109:51:34 CERTI' TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE' HOD Project Name: Jones Residence CIF 'RF-01 Calculation Date/Time: 09:50, Thu, Oct 11, 2018 Calculation Description: Title 24 Analysis Page 4 of 11 Input File Name: Jones Res -Jody Jones-18.ribdx OPAQUE SURFACES -- Cathedral Ceilings 01 02 03 04 05 06 07 08 09 10 11 Name Zone Type Orientatio n Skylight Area Roof Rise Area (ft2) Roof Roof Tilt Roof Roof Framing Roof living R-38 Roof Attic1 Front (f:2) (x in 12) Pitch (deg) Reflectance Emittance Factor Roof 2 family R-38 Roof Attic11Front 4.1 4 3 13 �O.25�11.04 01 0.85 0.1 123 .04 0.1 0.85 0.1 ATTIC 01 Name 02 Construction 03 Type 04 OS O6 07 08 Attic master Attic Roofmaster Roof Rise Roof Reflectance Roof Emittance Radiant Barrier Cool Roof Attic living Attic Roofliving Unventilated Unventilated 3 0.1 0.85 No No Attic bed Attic Rooft>ed Unventilated 3 0.1 0.85 No No Attic family Attic Rooffamily Unventilated 3 0 1 0.85 No No 0.1 0.85 No No � CaICERTS, Inc. Registration Number: 216-N0207144G-000000000-0000 Re Registration B Date/Time: 2018-10-11 09:58:54 HERS Provider: CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 CaICERTS inc. Report Generated at: 2018-10-1109:51:34 CERTI' TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE' HOD Project Name: Jones Residence Calculation DatelTime: 09:50, Thu, Oct 11, 2018 Calculation Description: Title 24 Analysis Input File Name: Jones Res -Jody Jones-18.ribdx CF 'RF-01 Page 5 of 11 WINDOWS 01 02 03 04 05 06 07 08 09 10 Name Type Surface (Orientation -Azimuth) Width (ft) Height (ft) Multipli er Area (ft) U-factor SHGC Exterior Shading A Window N Wall (Left-0) - ---- 1 40.0 0.34 0.13 Insect Screen (default) A 2 Window E Wall (Back-90) - 1 40.0 0.34 0.13 Insect Screen (default) A 3 Window W Wall (Front-270) --- 1 40.0 0.34 0.13 Insect Screen (default) A 4 Window W Wall (Front-270) ----- 1 40.0 0.34 0.13 Insect Screen (default) A 5 Window E Wall 2 (Back-90) -- 1 40.0 0.34 0.13 Insect Screen (default) A 6 Window E Wall 2 (Back-90) -- - 1 40.0 0.34 0.13 Insect Screen (default) A 7 Window E Wall 2 (Back-90) ---- -- 1 40.0 0.34 0.13 Insect Screen (default) A 8 Window E Wall 2 (Back-90) -- ----- 1 40.0 0.34 0.13 Insect Screen (default) A 9 Window E Wall 2 (Back-90) - --- 1 40.0 0.34 0.13 Insect Screen (default) A 10 Window S Wall 2 (Right-180) - - 1 40.0 0.34 0.13 Insect Screen (default) All Window S Wall 2 (Right-180) - 1 40.0 0.34 0.13 Insect Screen (default) A 12 Window W Wall 2 (Front-270) - -- 1 40.0 0.34 0.13 Insect Screen (default) A 13 Window W Wall 2 (Front-270) - -- 1 40.0 0.34 0.13 Insect Screen (default) B Window W Wall 2 (Front-270) -- -- 1 12,5 0.32 0.16 Insect Screen (default) A 14 Window W Wall 2 (Front-270); - 1 -40.0 0.34 0.13 Insect Screen (default) Entry Window W Wall 2 (Front-270) - -- 1 52.0 1.19 0.59 Insect Screen (default) Skylight Skylight Roof (Front-270) 1 4.0 0.48 0.27 C Window N Wall 2 (Left-0) -- - 1 4.0 0.32 0.20 Insect Screen (default) B 2 Window N Wall 2 (Left-0) - 1 12.5 0.32 0.16 Insect Screen (default) C 2 Window N Wall 2 (Left-0) -- - 1 4.0 0.32 0.20 Insect Screen (default) B 3 Window N Wall 2 (Left-0) - -- 1 12.5 0.32 0.16 Insect Screen (default) A 15 Window E Wall 3 (Back-90) - -- 1 40.0 0.34 0.13 Insect Screen (default) A 16 Window S Wall 4 (Right-180) --- - 1 40.0 0.34 0.13 Insect Screen (default) A 17 Window S Wall 4 (Right-180) -- 1 40.0 0.34 0.13 Insect Screen (default) Sola Tube Skylight Roof 2 (Front-270) 1 1.2 0.30 0.30 Registration Number: 216-N0207144G-000000000-0000 Registration Date/Time: 2018-10-11 09:58:54 HERS Provider: CaICERTS inc. CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 Report Generated at: 2018-10-1109:51:34 CERTI TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE' 'HOD ')RF-01 CF Project Name: Jones Residence Calculation Date/Time: 09:50, Thu, Oct 11, 2018 Page 6 of 11 Calculation Description: Title 24 Analysis Input File Name: Jones Res -Jody Jones-18.ribdx OPAQUE SURFACE CONSTRUCTIONS 01 02 03 04 05 06-1 07 Construction Name Surface Type Construction Type Framing Total Cavity R-value Winter Design U-value Assembly Layers • Cavity/Frame: no insul. /2x4 Top Chrd Attic Roofmaster Attic Roofs Wood Framed Ceiling 2x4 Top Chord of Roof Truss @ 24 in. O.C. Roof Deck: Wood Siding/sheathing/decking none 0.644 Roofing: Light Roof (Asphalt Shingle) Ceilings (below • Inside Finish: Gypsum Board R-38 Roof Attic attic) Wood Framed Ceiling 2x4 @ 16 in. O.C. R 38 0.025 Cavity/Frame: R-9.1 /2x4 Over Ceiling Joists: R-28.9 insul. Inside Finish: Gypsum Board • Cavity / Frame: R-21 / 2x6 R-21 Wall (W.21.2x6.16) Exterior Walls Wood Framed Wall 2x6 @ 16 in. O.C. R 21 0.066 Exterior Finish: Wood Siding/sheathing/decking • Cavity/Frame: no insul. /2x4 Top Chrd Attic Roofliving Attic Roofs Wood Framed Ceiling 2x4 Top Chord of Roof Truss @ 24 in. O.C. - Roof Deck: Wood Siding/sheathing/decking none 0.644 Roofing: Light Roof (Asphalt Shingle) • Inside Finish: Gypsum Board • Cavity / Frame: R-38 / 2x4 R-38 Roof Attica Cathedral Ceilings Wood Framed Ceiling 2x4 @ 16 in. O.C. R 38 0.041 • Roof Deck. Wood Siding/sheathing/decking Roofing: Light Roof (Asphalt Shingle) • Cavity/Frame: no insul. /2x4 Top Chrd Attic Roofbed Attic Roofs Wood Framed Ceiling 2x4 Top Chord of Roof Truss "@ 24 in. O.C. Roof Deck. Wood Siding/sheathing/decking none 0.644 Roofing: Light Roof (Asphalt Shingle) Attic Rooffamily Attic Roofs 2x4 Top Chord of Roof Truss @ 24 • Cavity/Frame: no insul. /2x4 Top Chrd Roof Deck.' Wood Sidinglsheathing/decking Wood Framed Ceiling in. O.C. none 0.644 Roofing: Light Roof (Asphalt Shingle) SLAB FLOORS 01 02 03 04 05 06 07 Name Covered Slab Covered Slab 2 Covered Slab 3 Covered Slab 4 Zone master living bed family Area (ft2) 836 1521 1015 280 Perimeter (ft) 106 106 96 46 Edge Insul. R-value & Depth None None None None 10.8 Carpeted Fraction 0.8 0.8 0.8 Heated No No No No Registration Number: 216-N0207144G-000000000-0000 Registration Date/Time: 2018-10-11 09:58:54 HERS Provider: CaICERTS inc. CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 Report Generated at: 2018-10-1109:51:34 CERTI' TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE' HOD Project name: Jones Residence Calculation Date/Time: 09:50, Thu, Oct 11, 2018 Calculation Description: Title 24 Analysis Input File Name: Jones Res -Jody Jones-18.ribdx BUILDING ENVELOPE - HERS VERIFICATION 02 03 01 Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage Not Required Not Required Not Required TING SYSTEMS 04 CFM50 WATER HEA 03 04 05 01 4 02 System Type Distribution Type Water Heater Number of Heaters Name Standard DHW Heater 1 2 DHW Sys 1 - 1/2 DHW WATER HEATERS 05 06 07 01 02 03 Tank Exterior fTankfVolum]eEnergy Factor or nsuation Heater Element Type Tank Type Efficiency Input Rating R-value Name 50 0.6 34000-Btu/hr 0 DHW Heater 1 Natural Gas Small Storage WATER HEATING - HERS VERIFICATION 01 Name DHW Sys 1 - 1/2 SPACE CONDITIONING SYSTEMS 01 SC Sys Name AC #41 AC #32 AC #23 AC #14 CF ''RF-01 Page 7 of 11 06 Solar Fraction (%) .0% 08 Standby Loss (Fraction) 0 02 03 04 05 06 07 Recirculation Central DHW Pipe Insulation Parallel Piping Compact Distribution Point -of Use Control Distribution 02 03 04 05 06 System Type Heating Unit Name Cooling Unit Name Fan Name Distribution Name Other Heating and Cooling Heating Component 1 Cooling Component 1 HVAC Fan 1 Air Distribution System 1 System Other Heating and Cooling Heating Component 2 Cooling Component 2 HVAC Fan 2 Air Distribution System 2 System Other Heating and Cooling Heating Component 3 Cooling Component 3 HVAC Fan 3 Air Distribution System 3 System Other Heating and Cooling Heating Component 4 Cooling Component 4 HVAC Fan 4 Air Distribution System 4 System Registration Number: 216-N0207144G-000000000-0000 Registration Date/Time: 2018-10-11 09:58:54 HERS Provider: CaICERTS inc CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 Report Generated at: 2018-10-1109:51:34 CERTI[ TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE O Calculation Date/Time: 09:50, Thu, Oct 11, 2018 Project Name: Jones Residence Input File Name: Jones Res -Jody Jones-18.ribdx Calculation Description: Title 24 Analysis HVAC - HEATING UNIT TYPES 02 01 Type Name Heating Component 1 CntrlFurnace - Fuel -fired central furnace Heating Component 2 CntrlFurnace - Fuel -fired central furnace Heating Component 3 CntrlFumace . Fuel -fired central furnace Heating Component 4 CntdFurnace - Fuel -fired central furnace HVAC - COOLING UNIT TYPES 04 05 0 02 1 03 Efficiency Name Cooling Component 1 Cooling Component 2 Cooling Component 3 Cooling Component 4 HVAC COOLING - HERS VERIFICATION 01 Name Cooling Component 1-hers-cool Cooling Component 2-hers-cool Cooling Component 3-hers-cool Cooling Component 4-hers-cool EER SEER Zonally Controlled System Type 12.7 16 Not Zonal SplitAirCond 12.7 16 Not Zonal SplitAirCond 12.7 16 Not Zonal SplitAirCond 12.7 16 Not Zonal 5plilAifCQnd 03 Efficiency 80 AFUE 80 AFUE 80 AFUE 80 AFUE 06 Multi -speed Compressor Single Speed Single Speed Single Speed Single Speed CF 'RF-01 Page 8 of 11 07 HERS Verification Cooling Component 1-hers-cool Cooling Component 1-hers-cool Cooling Component 1-hers-cool Cooling Component 1-hers-cool 03 04 05 06 02 Verified Refrigerant Airflow Target Verified EER Verified SEER Charge Verified Airflow Required Required Required Required 350 Required Required Required Required 350 Required Required Required Required 350 Required Required Required Required 350 Registration Date/Time: 2018-10-11 09:58:54 HERS Provider: CaICERTS inc. Registration Number: 216-N0207144G-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016 433 Report Generated at: 2018-10-1109:51:34 CERTII TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE CalculOation DatelTime: 09:50, Thu, Oct 11, 2018 Project Name: Jones Residence Input File Name: Jones Res -Jody Jones-18.ribdx Calculation Description: Title 24 Analysis HVAC - DISTRIBUTION SYSTEMS 04 05 02 03 01 Insulation R-value Duct Location Type Duct Leakage Name 8 Conditioned zone DuctslnAll Sealed and tested Air Distribution System 1 Conditioned zone Sealed and tested 8 DuctslnAll Air Distribution System 2 Conditioned zone Sealed and tested 8 ctslnAll Air Distribution System 3 DuAttic Sealed and tested 8 Air Distribution System 4 DuctsAttic HVAC DISTRIBUTION - HERS VERIFICATION 01 02 Duct Leakage Verification Required ed Required ed Required Required Name Air Distribution System 1-hersist Air Distribution System 2-hers list Air Distribution System 3-hers-dist Air Distribution System 4-hers-dist HVAC-FAN SYSTEMS 01 Name HVAC Fan 1 HVAC Fan 2 HVAC Fan 3 HVAC Fan 4 HVAC FAN SYSTEMS - HERS VERIFICATION 01 Name FEEEHVAC Fan 1-hers-fan HVAC Fan 2-hers-fan HVAC Fan 3-hers fan 03 Duct Target (°/a) 6.0 6-0 6.0 6.0 04 Verified Duct Location Required Required Required Not Required 02 Type Single Speed PSC Furnace Fan Single Speed PSC Furnace Fan Single Speed PSC Furnace Fan Single Speed PSC Furnace Registration Number: 216-N0207144G-000000000-0000 CA Building Energy Efficiency Standards - 2013 Residential Compliance 05 Verified Duct Design Not Required Not Required ed Not Required Not Required 02 Verified Fan Watt Draw Required Required Required 06 Buried Ducts Not Required Not R� Not Required NotesRequired 03 Fan Power (WattsICFM) 0.58 0.58 0.58 0.58 Registration Date/Time: 2018-10-11 09:58:54 Report Version - CF1R-01212016-433 06 Bypass Duct None None None None 07 Deeply Ducts Not Required Not Required Not Required Not Required CF 'RF-01 Page 9 of 11 07 HERS Verification Air Distribution System 1-hers-dist Air Distribution System 2-hers-dist Air Distribution System 3-hers-dist Air Distribution System 4-hers-dist 08 Low -leakage Air Handler 04 HERS Verification HVAC Fan 1-hers-fan HVAC Fan 2-hers-fan HVAC Fan 3-hers-fan HVAC Fan 4-hers-fan 03 Required Fan Efficiency (Watts/CFM) 0.58 0.58 0.58 HERS Provider: CaICERTS inc. Report Generated at: 2018-10-1109:51:34 CF °RF-01 CERTIF. TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE ! 401) Page 10 of 11 Calculation DatelTime: 09:50, Thu, Oct 11, 2018 Project Name: Jones Residence Input File Name: Jones Res -Jody Jones-18.ribdx Calculation Description: Title 24 Analysis 0.58 Required HVAC Fan 4-hers-fan IAQ (Indoor Air Quality) FANS 03 04 05 06 01 02 IAQ Recovery o HERS Verification IAQ WattsICFM IAQ Fan Type Effectiveness(%) Dwelling Unit IAQ CFM Default 0 Required SFam IAQVentRpt 74.02 0.25 ti.CaICERTS, Incs, HERS p,_- 7o iDER Registration Date/Time: 2018-10-11 09:58:54 HERS Provider: caICERTS inc. Registration Number: 216-N0207144G-000000000-0000 Report Generated at: 2018-10-1109:51:34 CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R 01212016-433 CERTIF' TE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE / 40D Project Name: Jones Residence Calculation Daterrime: 09:50, Thu, Oct 11, 2018 Calculation Description: Title 24 Analysis Input File Name: Jones Res -Jody Jones-18.ribdx DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. I certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Tim Scott Company: Scott Design and Title 24, Inc. Address: 77085 Michigan Drive City/State/Zip: Palm Desert, CA 92211 RESPONSIBLE PERSON'S DECLARATION STATEMENT Documentation Author Signature - Signature Date: 2018-10-11 09:58:54 CEA/HERS Certification Identification (If applicable): Phone: 760-200-4780 CF `RF-01 Page 11 of 11 l certify the following under penalty of perjury, under the laws of the State of California: risibility for the building design identified on 1. I am eligible under Division 3 of the Business and Professions Code to accept respoifid this Certificate of Compliance. 2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. atures identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance do 3. The building design features or system design fecumen , worksheets, calculations, plans and specifications submitted to the enformnent agency for approval with this building permit application. Responsible Designer Signature Responsible Designer Name: 14 it Tim Scott Date Signed: Company: 1 201$-14-11�9:58:54 Scott Design and Title 24, Inc. License: Address: 77085 Michigan Drive na Phone- City/State/Zip: 760-200-4780 Palm Desert, CA 92211 Digitally signed by CaICERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration Provider responsibility for the accuracy of the information. Registration Number: 216-N0207144G-000000000-0000 Registration Date/Time: 2018-10-11 09:58:54 CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-01212016-433 Ell TO Easy to Verify at CaICERTS.com HERS Provider: CaICERTS inc. Report Generated at: 2018-10-1109:51:34 RESIDENTIAL MEASURES SUMMARY RMS-1 Project Name Building Type m Single Family ❑ Addition Alone Jones Residence ❑ Multi Family ❑ Existing+ Addition/Alteration Date Project Address 1011112018 California Energy Climate Zone Total Cond. Floor Area Addition # of Units Lot #59, San Lucas La Quints CA Climate Zone 15 3, 652 n/ti 1 INSULATION Area Construction Type Cavit ft) Special Features Status Roof Wood Framed Attic R 38 3,647 Wall Wood Framed R 21 4,818 New Slab Unheated Slab -on -Grade - no insulation 3,652 Perim = 354' New Demising Wood Framed R 13 1,435 New New FENESTRATION Orientation Area ft2 Total Area: U-Fac SHGC 783 Glazir,I Percents e: 21.4 0.40 OverhangSidefins Exteriror Shadesa�r Status Left (N) 40.0 0.340 0.13 none none Bug Screen New Rear (E) 280.0 0.340 0.13 none none Bug Screen New Front (W) 200.0 0.340 0.13 none none Bug Screen New Skylight 4.0 0.480 0.27 none none None New Right (S) 160.0 0.340 0.13 none none Bug Screen New Front (W) 12.5 0.320 0.16 none none Bug Screen New Front (W) 52.0 1.190 0.59 none none Bug Screen New Left (N) 8.0 0.320 0.20 none none Bug Screen New Left (N) 25.0 0.320 0.16 none none Bug Screen New Skylight 1.2 0.300 0.30 none none None New HVAC SYSTEMS Qty. He ting Min. Eff Cooling Min. Eff Thermostat Status 1 Central Furnace 80% AFUE Split Air Conditioner 16.0 SEER Setback New 1 Central Furnace 80% AFUE Split Air Conditioner 16.0 SEER Setback New 1 Central Furnace 80% AFUE Split Air Conditioner 16.0 SEER setback HVAC DISTRIBUTION New Location Heating Cooling Duct Location Duct R-Value Status AC #4 Ducted Ducted Conditioned 8.0 AC #3 Ducted Ducted Conditioned 8.0 New AC #2 Ducted Ducted Conditioned New WATER HEATING e.o New Qty. Type Gallons Min. Eff Distribution 2 Small Storage Gas 50 0.60 Status Standard New 14 of RESIDENTIAL MEASURES SUMMARY RMS-1 Project Name Jones Residence Building Type m Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration 11011112018 Date Project Address Lot #59, San Lucas La Quinta California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 3,652 Addition n/a # of Units 1 INSULATION Construction Type Area Cavity ft Special Features Status FENESTRATION Total Area: 789 Glaxin Percents e: 21A % New/Altered Average U-Factor: 0-40 Orientation Area ftz U-Fac SHGC Overhang Sidefins Exterior Shades Status HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status 1 Central Furnace 80% AFUE Split Air Conditioner 16.0 SEER Setback New HVAC DISTRIBUTION Location Heating Duct Cooling Duct Location R-Value Status AC #1 Ducted Ducted Attic 8.0 New WATER HEATING Qty. Type Gallons Min. Eff Distribution Status Ens Pro 6. by EnergySoft User Number,• 6712 /D: Pa a 15 of 40 2013 Low -Rise Residential Mandatory Measures Summary NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the rninnhanre annroarh used_ Fxrenrionr may anniv. Review the resueetive code section For more information. Building Envelope Measures: § 110.6(a)1: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage. § 110.6(a)5: Fenestration products (except field -fabricated windows) have a label listing the certified U-Factor, certified Solar Heat Gain Coefficient SHGC , and infiltration that meets the requirements of § 10-111 (a). § 110.7: Exterior doors and windows are weatherstripped; all joints and penetrations are caulked and sealed. § 110.8(a): Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R. § 110.8(1): The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of § 110.8(i) when the installation of a cool roof is specified on the CFIR. §110.80): A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CF1R. Minimum R-30 insulation in wood -frame ceiling; or the weighted average U-factor shall not exceed 0.031. Minimum R-19 in a § I50.0(a): rafter roof alteration. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The attic access shall be gasketed to prevent air leakage. § 150.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R-value. § 150.0(c): Minimum R-13 insulation in 2x4 inch wood framing wall or have a U-factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U- factor). § 150.0(d): Minimum R-19 insulation in raised wood -frame floor or 0.037 maximum U-factor. In Climate Zones 14 and 16 a Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior §150.0(g)l: walls, vented attics and unvented attics with air -permeable insulation. In Climate Zones 1-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class II § I50.0(g)2: vapor retarder. In a building having a controlled ventilation crawl space, a Class I or Class II vapor retarder shall be placed over the earth floor of § I50.0(g)3: the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section 150.0 d . § 150.0(1): Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%; have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration; and when installed as part of a heated slab floor meets the requirements of § 110.8 150.0 § (q)' Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U- factor of 0.58, or the weighted average U-factor of all fenestration shall not exceed 0.58. Fireplaces, Decorative Gas Appliances and Gas Log Measures: §150.0(e)IA: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox. § 150.0(e)1B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is equipped with a readily accessible, operable, and tight -fitting damper or a combustion -air control device. §150.0(e)1C: Masonry or factory -built fireplaces have a flue damper with a readily accessible control. Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside § I50.0(e)2: of the building, are prohibited. Space Conditioning, Water Heating and Plumbing System Measures: §110.0-§110.3: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified to the Energy Commission. § 110.3(c)5: Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §I10.3(c)5. Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appli- § 110.5: ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool ands a heaters. §150.0(h)l: Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified in § 150.0(h)2. Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any § 150.0(h)3A: dryer vent. § I50.0(i): Heating systems are equipped with thermostats that meet the setback requirements of § 110.2(c). §150.00)IA: Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped with insulation having an installed thermal resistance of R-12 or greater. §150.00)1B: Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, have R-12 external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank. For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage tank, all piping with a nominal diameter of 3/4 inch or larger, all piping associated with a domestic hot water recirculation system § 150.00)2A: regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3- A. § I50.00)2B: All domestic hot water pipes that are buried below grade must be installed in a water proof and non -crushable casing or sleeve that allows for installation, removal, and re iacement of the enclosed pipe and insulation. 2013 Low -Rise Residential Mandatory Measures Summary § I50.00)2C: Pipe for cooling system lines shall be insulated as specified in § I50.00)2A. Piping insulation for steam and hydronic heating systems or hot waters stems with pressure > 15 psi& shall meet the re uirements in TABLE 120.3-A. 150.0 03: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. _ ,- _ _I r__ _ .•s.. ..L..11 .,A . ,.' L1, .. .h. W. f,• .,,rt. — —A— Rnr § 150.00)3A: 1116UlalIV11 UAt/UOVU — Wl•0.L11 J1L(L.. a.a. . —.u.vu .va .•,..a.v»• ».••. ,•• ••••••»••—•• ••---• » -- • ---------- --- -- ---- -- - - example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or ainted with coating that is water retardant andprovide,,; shielding from solar radiation that degrades the material. Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I § 150.00)3B: or Class II vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class II vapor retarder. Systems using gas or propane water heaters to serve individual dwelling units shall include: a 120V electrical receptacle within 3 feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the § 150.0(n)l: space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000 Btu/hr. § 150.0(n)2: Recirculating loops serving multiple dwelling units shall meet the requirements of § 110.3(c)5. Solar water -heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC) § I50.0(n)3: or by a testing agency aeproved by the Executive Director. Ducts and Fans Measures: All air -distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC §601.0, §602.0, §603.0, §604.0, §605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition. Supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC §605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing (RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed § 150.0(m) l: with mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL I81 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than %a inch, the combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross -sectional area of the ducts. Factory -Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; joints § 150.0(m)2: and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. 150.0 m 3-6: rieta-ranrlcatea LUCI Jysiems snan comply wlue loyuucu1c111J LUl. t11GJJUlI'JVl,J1L1YV .uyw, •••w�.. "»• ••.�, •• § ( ) ..:i:•.•i f .• A,,..t d—f inc„lntinn R -vnhle rnlinacr duct insulation thickness: and duct labelinit. All tan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic § 150.0(m)7: dampers. Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers §150.0(m)8: except combustion inlet and outlet air openings and elevator shaft vents. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum, § 150.0(m)9-. sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation. § 150.0(m)l0: Flexible ducts cannot have porous inner cores. When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be §I50.0(m)11: sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference Residential Appendix RA3. Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal § 150.0(m)12: conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of 1 50.0rn 12. Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The § 150.0(m)13: space conditioning system must also demonstrate airflow_ 350 CFM per ton of nominal cooling capacity through the return grilles, and an air -handling unit fan efficacy < 0.58 W/CFM as confirmed by field verification and diagnostic testing, in accordance with Reference Residential A . endix RA3. Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode, an airflow from the dwelling, through the air handler fan and delivered to the dwelling, of >_ 350 CFM per ton of nominal cooling § 150.0(m)15: capacity, and operating at an air -handling unit fan efficacy of < 0.58 W/CFM as confirmed by field verification and diagnostic testing. in accordance with Reference Residential Appendix RA3. All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of §150.0(o): central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the Whole Building Ventilation. Whole Building Ventilation airflow, shall be confirmed through field verification and diagnostic testing, in accordance with Reference Resident. lmlxiq Pool and Spa Heating Systems and Equipment Measures: Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency § 110.4(a): Regulations; an on -off switch mounted outside of the heater that allows shutting off the heater without adjusting the thermostat settinst: a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heatin 2013 Low -Rise Residential Mandatory Measures Summary § 110.4(b)1: Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction and return lines, or bui it -up connections for future solar heating. § 110.4(b)2: Outdoor pools or spas that have a heat pump or gas heater shall have a cover. § 110.4(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro- grammed to run only during off-peak electric demand . eriods. § 110.5: Natural gas pool and spa heaters shall not have a continuous burning pilot light. § 150.0(p): Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements. Lighting Measures: § 110.9. All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of § 110.9. § 150.0(k)IA: Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with § 150.0(k) in accordance with TABLE 150.0-A or TABLE 150.0-B, as applicable. § 150.0(k)1 B: When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply with the applicable provisions of § 150.0(k). The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with § 150.0(k)1 C: § 130.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180 watts of low efficacy lighting er electrical box. §150.0(k)1D: Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz. Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no § 150.0(k)1 E: more than 5 watts of power per luminaire or exhaust fan as determined in accordance with § 130.0(c). Night lights do not need to be controlled by vacancy sensors. § 150.0(k)1 F: Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable requirements of § 150.0(k). § 150.0(k)2A: High efficacy luminaires must be switched separately from low efficacy luminaires. § 150.0(k)2B: Exhaust fans shall be switched separately from lighting systems. § 150.0(k)2C: Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF. §150.0(k)2D: Controls and equipment are installed in accordance with manufacturer's instructions. § 150.0(k)2E: No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with § 150.0(k). § I50.0(k)2F: Lighting controls comply with applicable requirements of § 110.9. An Energy Management Control System (FMCS) may be used to comply with dimmer requirements if: it functions as a dimmer § 150.0(k)2G: according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements of § 130.5; and all other requirements in § 150.0(k)2. An Energy Management Control System (EMCS) may be used to comply with vacancy sensor requirements of § I50.0(k) if: it § 150.0(k)2H: functions as a vacancy sensor according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements of § 130.5; and all other requirements in § 150.0(k)2. § 150.0(k)2I: A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the functionality of a dimmer according to § 110.9, and complies with all other applicable requirements in § 150.0 k 2. § 150.0(k)3A: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy. Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only § 150.0(k)3B: the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are considered kitchen lighting if they are not separately switched from kitchen li htin . § 150.0(k)4: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated cabinet. § 150.0(k)5: A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom shall be high efficacy or controlled by vacancy sensors. § 150.0(k)6: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and controlled by vacancy sensors. § 150.0(k)7: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high efficac. or shall be controlled by either dimmers or vaeancy sensors. Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing § 150.0(k)8: and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and allow ballast maintenance and replacement without requiring cutting holes in the ceiling. For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with § I50.0(k), the ballasts shall be certified to the Energy Commission to comply with the applicable requirements in § 110.9. For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements: i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and § I50.0(k)9A: ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically reactivates the motion sensor within 6 hours; and iii. Controlled by one of the following methods: 2013 Low -Rise Residential Mandator Measures Summary F- a. Photocontrol not having an override or bypass switch that disables the photocontrol; or b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is programmed to automatically turn the outdoor lighting OFF during daylight hours; or c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of an astronomical time clock in accordance with § 110.9; meets the Installation Certification requirements in § 130.4; meets the requirements for an EMCS in § 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and, is mrogrammed to automatically turn the outdoor lighting OFF during da li ht hours. For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the §150.0(k)9B: following requirements: i. Shall comply with § 150.0(k)9A; or ii. Shall comply with the appiicable requirements in § 110.9, § 130.0, § 130.2, § 130.4, § 140.7 and § 141.0. § I50.0(k)9C: For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by.§ 150.0(k)9B or 150.0(k)9D shall comply with the applicable requirements in 110.9 130.0, ' 130.2 § 130.4, § 140,7 and § 141.0. § I50.0(k)9D: Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply with the applicable requirements in § 110.9 130.0 130.2, § 130.4 140.7 and § I41.0. § 150.0(k)10: Internally illuminated address signs shall comply with § 140.8, or shall consume no more than 5 watts of power as determined according to § 130.0(c). § 150.0(k)11: Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for nonresidential garages in ' 110. 9J 13 0. 0130.1, § 130A, § 140.E and J 141.0. In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of §150.0(k)12A: the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or controlled by an occupant sensor, In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20 percent of the floor area, permanently installed lighting in that building shall: § 150.0(k)1213: i. Comply with the applicable requirements in § 1 10.9, § 130.0, § 130.1, §I40.6 and §141.0; and ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of inRress and egress. Solar Ready Buildings: §110.10(a)1: § 110.10 a 2: §I10.10(b)1: § 110.10(b)2: § 110.10(b)3A: §I10.10(b)3B: § 110. l 0(b)4: § 110.10(c): Single family residences located in subdivisions with ten or more single family residences and where the application for tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January 1, 2014, shall comply with the requirements of 110.10 through §110.10(e). Low-rise multi -family buildin s shall comply with the requirements of § 110.10 through § 110.10 d The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway, smoke ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a local jurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than 80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for buildings with roof areas greater than 10,000 square feet. For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less than 250 square feet. For low-rise multi -family buildings the solar zone shall be located on the roof or overhang of the building or on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the building project and have a total area no Iess than 15 percent of the total roof area of the building excluding any skylight area. All sections of the solar zone located on steep -sloped roofs shall be oriented between 110 degrees and 270 degrees of true north. No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be located in the solar zone. Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the horizontal projection of the nearest point of the solar zone, measured in the vertical plane. For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly indicated on the construction documents. The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit from the solar zone to the point of interconnection with the electrical service (for single family residences the point of interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water -heating § 110.10(d): A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through § 110.10(c) shall be rovided to the occu ant. § 110.10(e)1: The main electrical service panel shall have a minimum busbar rating of 200 amps. The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a § 110.10(e)2: future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or main circuit location, and perm:uientl) marked as "For Future Solar Electric". HVAr. SYSTEM W=ATIAIr Aklfl ^/'1^1 twin t n A r rrolect Name Jones Residence 5ysiem Name AC #4 ENGINEERING CHECKS Number of Systems 1 Heating System Oiuitipult per System 71,000 Total output stuh 71.000 Dut ut Stuhls ft 84.9 Cooling System Output per Sys to m 36,000 Total Output Btuh 36,000 Total Output Tons 3.0 Total Output Btuhls ft 43.1 Total Output s ftfTon 278.7 Air System CFM per System 1.200 Airflow cfm 1,200 Airflow cfmis ft 1.44 Airflow cfmfTon 400.0 Outside Air % 11.0 % Outside Air cfmis ft 0.16 SYSTEM LOAD Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD IS SUMMARY Date 10/11/2018 Floor Area 836 COIL COOLING PEAK COIL HTG. PEAK CFM J Sensible Latent CFM Sensible 655 10,465 1,286 253 13,536 0 151 161 0 0 132 5,900 2,572 132 6,462 0 151 16,667 3,858 0 161 20,320 HVAC EQUIPMENT SELECTION rane 3 Ton 25,370 total Adjusted System Output 25,370 (Adjusted for Peak Design conditions) 5 71,000 i 71,0001 Note: values above given at ARI conditions I TIME OF SYSTEM PEAK I Aug 3 PM Jan 1 HEATING SYSTEM PSYCHROMETRICS Airstream Tem ratures at Time of Neatin Peak 26 OF 67 OF 122 OF 122 OF Outside Air 132 cfm Heating Coil Supply Fan 1,200 cfm 122 OF ROOM 72 OF --I ! _ IA 72 °F COOLING SYSTEM 112/78OF Outside Air 132 cfm 70/60°F 5 Airstream Temperatures at Time of Coc 75/62°F 55/54°F 55/54°F Cooling Coil Supply Fan 1,200 cfm 6. by EnOWSofl User Number: 6712 1 55/54°F 56.4 % ROOM 70 / 60 OF w Page 20 of 40 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Jones Residence Date System Dame 10/11/2018 AC #3 Floor Area ENGINEERING CHECKS SYSTEM LOAD 1,521 NumberofSystems 1 COIL COOLING PEAK COIL HTG. PEAK stem Sensible Latent CFM Sensible 7HeatinCFM Total Room Loads 1,979 A55 23,460 2,340 56922A4i Stuh Return Vented Lighting 0 ls ft Return Air Ducts 340 CoR[[qq1 S tem 26'c Return Fan 0 C Out ut er S stem 57,500 Ventilation 284 12,642 3,654 284 13.862 total Ou ut Btuh 57,500 Supply Fan 2,943 Total Output Tons 4.81 Supply Air Ducts -2,943 340 Total Output Btuhls Ft 37.8 262 Total output s Wron 317.4 TOTAL SYSTEM LOAD 39,725 5,994 Air S stem 33,490 CFM er S tem 2,000 HVAC EQUIPMENT SELECTION Alrtlow cfm 2,000 Trane 5 Ton Airflowcfmis ft 1.31 39,974 11,342 89,000 Airtlow cfmi fon 417.4 Outside Air % 14.2 % Total Adjusted System Output 39,974 11,342 Outside Alr cfmfs ft 0.18 (Adjusted for Peak Design conditions] 89,000 Note: values above given at ARI conditions TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time Heating of Peak 26 OF 67 OF 109 OF 109 OF 0 T -1 - Outside Air v --------------------- 284 cfm Heating Coil Supply Fan , 2,000 cfm 108 OF 72 OF ROOM _ _ _ 72 OF COOLING SYSTEM 112 / 78 OF Outside Air 284 cfm 70 / 62 OF .l .t I . fl 4 1 5 Airstream Temperatures at Time of Coolin Peak 77 / 65 OF 59 / 58 OF 59 / 58 OF !!!! Cooling Coil Supply Fan 2,000 cfm 59 / 58 OF 64.9 % ROOM i 70 / 62 °F 6. byt=nergy5oft User Number., 6712 ID: Page 21 of 40 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Jones Residence I AC #2 ENGINEERING CHECKS Number of Systems 1 Heating S stem Output per System 71,000 Total Output Btuh 71,000 Output (Stuh/sciftl 70.0 Cooling System Output per System 36,000 Total Output Btuh 36,000 Total Output Tons 3.0 Total Output Stuhls ft 35.5 Total Output s ftrron Air System CFM per System Airflow cfm Airflow cfmis ft Airflow cfmlFon Outside Air % 338.3 1,200 1,200 1.18 400.0 12.7 % Outside Air cfm/s ft 0.15 SYSTEM LOAD Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD HVAC EQUIPMENT SELECTION frane 3 Ton Total Adjusted System Output (Adjusted for Peak Design conditions) 10/11/2018 Floor Area 1,015 COIL COOLING PEAK COIL HTG. PEAK CFM Sensible Latent CFM Sensible 624 9,442 1,562 222 11,734 0 137 140 0 0 152 6,788 2,726 152 7,436 0 137 16,503 4,288 0 140 19,448 25,232[ 5.837 71,000 i 71,0001 Note: values above given at ARI conditions I TIME OF SYSTEM PEAK Aug 3 PM Jan 1 HEATING SYSTEM PSYCHROMETRICS tAirsteam Temperatures at Time of Heating Peak 26 OF 66 OF 122 OF 122 OF I ' N­r --I Outside Air -�1-AV- N _ 152 cfm Heating Coil Supply Fan 1,200 cfm 122 OF 72 OF COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Coolinst Peak ROOM 72 OF 112/78OF 75/63°F 56/55°F 56/55°F ® Outside Air I 152 cfm Cooling Coil Supply Fan 56 / 55 OF 1,200 cfm 58.4 % ROOM 70 / 61 °F 70 / 61 OF 4 AD' _I UT[ EnergyPro 6. by EnergySoff User Number: 6712 ID: Page 22 of 40 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Jones Residence 5ystern Name AC #1 ENGINEERING CHECKS Number of Svstems Total Ou ut (Btu Output_(Btuhlsgft ding S tem Output per Systat Total Output (Btu Total Output Ton Total Output (Btu. Air Svstem 1 SYSTEM LOAD Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD 51,000,Total 51,000 182.1 24.000 24,000 2.0 85.7 140.0 Date 10/11/2018 Floor Area 280 COIL COOLING PEAK COIL HTG. PEAK CFM Sensible Latent CFM Sensible 357 5,604 431 185 6.435 0 324 316 0 0 42 1,656 825 42 2,045 0 324 8,117 1,256 0 316 9,112 CFM perSystem Airflow cf:m 1,200 1.200 HVAC EQUIPMENT SELECTION Trane 2 Ton 12,805 7,160 51,000 Airflow cfm/s ft 4.29 I Airflow efmlTon 600.0 Outside Air % 3.5 % Total Adjusted System Output 12,805 7,160 51,000 (Adjusted for Peak Design conditions) Outside Air cfm/s ft 0.15 NOW values above given at ARI conditions TIME OF SYSTEM PEAK I Aug 3 PM1 I Jan 1 AM HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26 OF 70 OF 105 OF 105 OF op 0 .� t _I Outside Air 42 cfm Heating Coil Supply Fan 1,200 cfm 105 °F ROOM 72 OF - 7� OF COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 112/78OF 72/61 OF 55/54°F 55/54°F Outside Air O I_T 0 42 cfm Supply Fan Cooling Coil 55 / 54 OF 1,200 cfm 56.1 % ROOM 70 / 60 OF 70 / 60 OF 6. by EnergySofl User Number: 6712 ID: Page 23 of 40 ZONE LOAD SUMMARY Project Name Jones Residence Date 1011112018 System Name AC #4 Floor Area 836 ZONE LOAD SUMMARY ZONAL SYSTEM COOLING PEAK HEATING PEAK ZONE NAME master SYSTEM NAME Mull. 1.0 CFM Sensible Latent Heating OA CFM 132 Peak Hr Aug 3 PM CFM 655 Sensible 16,381 Latent 4,505 CFM 253 Sensible 20,016 TOTALS 0 0 0 132 Aug 3 PM 16,381 4,505 20,016 (BLOCK LOAD)EneTyPro 6. by EnergySofi user Number: 6712 Q. Page 24 of 40 ROOM LOAD SUMMARY Project Name Jones Residence Date 1011112018 System Name AC #2 Floor Area 1,015 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult. CFM Sensible Latent CFM Sensible Latent CFM Sensible bed Bedrooms 2 - 4 1 624 9,442 1,562 624 9,442 1,562 222 11,734 PAGE TOTAL 624 9,4421 1.562 2221 11.734 TOTAL 1 624 9.442 1,562 222 11,734 ' Total includes ventilation load for zonal systems. Enervem 6. by EnenqySoff User Number: 6712 1D: Page 30 of 40 ROOM HEATING PEAK LOADS Date Project Name 1 Jones Residence 10/11/2018 ROOM INFORMATION DESIGN CONDITIONS Room Name Master Bedroom Time of Peak Jan 1 AM Floor Area 836.00 ft2 Outdoor Dry Bulb Temperature 26 OF Indoor Dry Bulb Temperature 72 OF Conduction Area U-Value R-38 Roof Attic 836.0 X v.v, R-21 Wall (W.21.2x6.16) 1,466.0 X O.Oi French Door.341..13 160.0 X 0.3. Slab -On -Grade perim = 106.0 X 0.7, •R-13 Wall 412.0 X 0.1 X x x x x x x x x x x x x x x x x x x x x x x x x x Items shown with an asterisk (') denote conduction through an interior surface to another room Infiltration:[ 1.00 X Schedule Fraction TOTAL HOURLY HEA AT °F Page Total Btu/hr 1,000 4,653 2,502 3,559 0 j 11,7151 1.064 X $36 X 9.50 X 0.281 / 60 ] X 46 s Air Sensible Area Ceiling Height ACH �7 FOR User Number: 6712 ID: j 1,6211 13, 536 ROOM HEATING PEAK LOADS Project Name Jones Residence ROOM INFORMATION Room Name Floor Area Indoor DrV Bulb Temperature ❑F51GN rnMnITIONS Living Area Time of Peak 1,521.00 ft2 Outdoor Dry Bulb Temperature 72 °F Area U-Value Conduction 1,517.0 X 0.0260 X R-38 Roof Attic 4,0 X 0.4800 X Skylight 1,255.5 X 0.0690 X R-21 Wall (W.21.2x6.16) 400.0 X 0.3400 X French Door.34/.13 ESlab-On-Grade 0.3200 X 12.5 �( Casement .32/.16 1.1900 X 52.0 X Custom Entry Door Perim = 106.0 X 0.7300 X 355.0 X 0.1020 X "R-13 Wall X X X X X X X X X x X x x x x x x x x x x X x x mix x x x x X denote conduction through an interior surface to another room Items shown with an asterisk (') AT °F Date 1011112018 Jan 1 AM 26 °F Btu/hr 1,814 88 3,985 6, 256 184 2,846 3,559 0 18,734 1.00 1A64 X 1,521 X 11.20 X 0.238 / 60 ] X 4G = 3,313 Infiltration: X AT Schedule Air Sensible Area Ceiling fie�ght ACH Fraction 22,047 TOTAL HOURLY HEAT LOSS FOR ROOM ID: Ps e 33 of 40 User Number: fi712 ROOM HEATING PEAK LOADS Project Name Jones Residence ROOM INFORMATION DESIGN CONDITIONS Room Name Bedrooms 2 - 4 Time of Peak Floor Area 1,015.00 W1 Outdoor Dry Bulb Temperature Indoor Dry Bulb Temperature 72 OF. Conduction Area U-Value R-38 Roof Attic 1,015.0 x u.u. R-21 Wall (W.21.2x6.16) 1,252.0 x 0.01 Casement .321..20 8.0 x 0.3: Casement .32/.16 25.0 x 0.3: French Door.34/.13 40.0 x 0.3, Slab -On -Grade perim = 96.0 x 0.7, 'R-13 Wall 388.0 x 0.1 x x x x x x x x x x x x x x x x x x x x x x x x Items shown with an asterisk (') denote conduction through an Interior surface to another room OT °F Date 1011112018 ■ I �r 1 1 I 1 I 1 I Jan 1 AM 26 OF Btu/hr 1,214 3,974 118 368 626 3,224 0 9,5231 1.00 1.064 x 1,015 x 9.00 x 0.297 / 60 ] x 46 = 2,211 Infiltration: X Schedule Air Sensible Area Ceiling Height ACH AT Fraction TOTAL HOURLY HEAT LOSS FOR ROOM 11,734 User Number: 6712 ID: Pa o 34 of 40 ROOM HEATING PEAK LOADS Project Name Jones Residence ROOM INFORMATION DESIGN CONDITIONS Room Name Family Room Time of Peak Floor Area 280.00 ft' Outdoor Dry Bulb Temperature Indoor Dry Bulb Temperature 72 OF Conduction R-38 Roof Attic Solatube Skylight R-21 Wall (W 21.2x6.16) French Door .341..13 Slab -On -Grade Area U-Value 0.0260 X 0.3000 X 0.0690 X 0.3400 X 0.7300 X 0 280.0 X 0.102 "R-13 Wall X X x X x X x X x X x X x X x X x x x x x x x x x x x x x x x x x x x x Items shown with an asterisk (') denote conduction through an interior surface to another room AT °F Dace 1011112018 Jan 1 AM 26 OF Btu/hr 333 17 2,679 1,251 1,545 0 5,825 1.00 1.064 X P80 X 9.00 X 0.297 / 60 ] X 46 = 610 Infiltration: X AT Schedule Air Sensible Area Ceiling Height ACFi Fraction 6 435 TOTAL HOURLY HEAT LOSS FOR ROOM 6712 ID: Page 35 of 40 RESIDENTIAL ROOM COOLING LOAD SUMMARY Jones Residence ROOM INFORMATION Room Name Floor Area Indoor Dry Bulb Temper opaque Surfaces R-38 Roof Attic R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) "R-13 Wall DESIGN CONDITIONS Master Bedroom Outdoor Dry Bulb Temperature 836.00 ftZ Outdoor Wet Bulb Temperature 70 OF Outdoor Daily Range: Orientation Hate 1011112018 Area U-Factor CLTD' 836.0 X 0.0260 X 56.0 = 268.0 X 0.0690 X 23.0 = 268.0 X 0.0690 X 33.0 = 702.0 X 0.0690 X 26.0 = 228.0 X 0.0690 X 33.0 = 412.0 X 0.1020 X 0.0 = X X = X X = X X = Page Total Items shown with an asterisk (`) denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Chadpd Unshaded Fenestration Orientation A (N) A (E) A (M A (M I i::� F1 Area GLF Area GLF 11.6 0.0 X 11.6 + 40.0 X = 19.3 0.0 X 11.6 + 40.0 X = 0.0 X 11.6 + 40.0 X 19.3 = 0.0 X 11.6 + 40.0 X 19.3 = X + X = X + X = X + X = X + X = X + X = Page Total Internal Gain _ El Occupants X 245 Btuh/occ.Occu ants 0.50 E ui mentFloor Area X w/scift Infiltration: 1.064 X 0.94 X 38.43 X 42 = Air Sensible CFM E AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM Latent Gain _ 2.5 Occupants X 155 Btuh/occ. Occupants - Infiltration: 4,771 X 0.94 X 38.43 X 0.00523 Air Sensible CFM EL°' t,W TOTAL HOURLY LATENT HEAT GAIN 112 OF 78 OF 34 OF Btulhr 1,217 425 610 1.259 519 4,031 Btulhr 774 774 2.786 Btulhr 614 1,427 1, 60f 10,46! Btu/hr RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Jones Residence ROOM INFORMATION DESIGN CONDITIONS Living Area Outdoor Dry Bulb Temperature Room Name 1,521.00 ftZ Outdoor Wet Bulb Temperature Floor Area 70 °F Outdoor Daily Range: Indoor Dry Bulb Temperature Opaque Surfaces R-38 Roof Attic R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) *R-13 Wall Orientation Date 1011112018 112 7F 78 OF 34 OF Area U-Factor CLTD' X 0.0260 X 56.0 = X 0.0690 X 33.0 = X 0.0690 X 26.0 = XA0.06 X 33.0 = I X X 0.0XXXXXXX = Page Total Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Skylight A A A A A A A A Orientation Area GLF Area GLF 56.5 0.0 X 19.9 + 4.0 X = 0.0 X 11.6 + 40.0 X 19.3 = 0.0 X 11.6 + 40.0 X 19.3 = 0.0 X 11.6 + 40.0 X 19.3 = 0.0 X 11.6 + 40.0 X 19.3 = 0.0 X 11.6 + 40.0 X 19.3 = 0.0 X 11.6 + 40.0 X 11.7 = 0.0 X 11.6 + 40.0 X 11.7 = 0.0 X 11.6 + 40.0 X 19.3 - Page Total Internal Gain EE� Btuh/occ. Oauiment nts 4 6 Occupants X - E 1,521 Floor Area X w/sgft Infiltration: ?.064 0.94 X X ELA 9.92 X AT 42 Air Sensible CFM TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM Latent Gain Btuh/occ. Occupants 4•6 Occupants X 155 Infiltration: 4,771 X 0.94 X 69.92 X 0.00523 = AW Air Sensible CFM ELA TOTAL HOURLY LATENT HEAT GAIN 6. Btulhr 1,266 1,301 5, Btulhr 226 774 774 774 774 774 466 466 Btu/hr 1' 2,+ 2, Btulhr 1 tr+J RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Jones Residence ❑ESIGN CONDITIONS ROOM INFORMATION rature Room Name Floor Area Indoor Dry Bulb Tem ue Surfaces Orientation Living Area Outdoor Dry Bulb Tempe 1,521.00 ft2 Outdoor Wet Bulb Temperature 70 °F Outdoor Daily Range. 1011112018 112 °F 78 OF 34 OF Area U-Factor CLTD' Btulhr X X = X X X X = X X = X X X X X X X X = X X Page Total Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration A B A Entry Orientation Area GLF Area GLF 0.0 X 11.6 + 40.0 X 19.3 = 0.0 X 12.3 + 12.5 X 21.8 = 0.0 X 11.6 + 40.0 X 19.3 = 0.0 X 45.7 + 52.0 X 80.7 = X + X X + X X + X X + X X + X Page Total internal Gain E�E� Btuh/occ.occu ants 4.6 Occupants X w/sgft ERuivment 1,521 Floor Area X 1.064 X 0.94 X 69.92 X e7 42 Infiltration: Et_A Air Sensible CFM TDTAL HOURLY SEIVSIf3L1= HEAT GAIN FOR ROOM Latent Gain 155 Btuh/occ. 4.6 Occupants X occu ants 4, 771 X 0.94 X 69.92 X 0.00523 Infiltration: ELA ❑W Air Sensible CFM TDTAL HDURLY LATENT HEAT GAIN FOR ROOM fL]: �_a i mar mimbPr- 6712 6tuthr 774 273 774 4,198 6, 018 itulhr 1,118 2,596 2, 923 ::�-J23,460 Btulhr 707 1,633 707 iNP 38 of 40 RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Jones Residence DESIGN CONDI I IVNS ROOM INFORMATION Ib T m erature Room Name Floor Area Indoor Dry Bulls Tern O a ue Surfaces R-38 Roof Attic R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) `R-13 Wall nature Bedrooms 2 - 4 Outdoor Dry Bu e p 1,015.00 ft2 Outdoor Wet Bulb Temperature 70 OF outdoor Daily Ran e: orientation Date 1011112018 112 OF 78 OF 34 OF U-Factor CLTD' Btu/hr Area = 1,478 1,015.0 X 0.0260 X 669.0 X 0.0690 X 23.0 23.0 = 1,062 362.0 X 0.0690 X 33.0 = 824 96.0 X 0.0690 X 26.0 = 172 125.0 X 0.0690 X 33.0 = 285 388.0 X 0.1020 X 0.0 = 0 X X X X = X X = Page Total 3,821 denote conduction through an interior surface to another room- Items shown with an asterisk (") Temperature Difference (CLTD) Unshaded 1. Cooling Load Shaded Area GLF Area GLF Btulhr estration Orientation Frguo 13.8 + 4.0 X 13.8 = 55 X 12.3 + 12.5 X 12.3 = 154 X 13.8 + 4.0 X 13.8 = 55 X 12.3 12.5 X 12.3 = 154 X 11.6 + + 40.0X 19.3 = 774X X + X = X + X = X + X = X + X Page Total 1,19 Internal Gain Occupants X 245Btuh/occ. 74 17pccuats0.50 Floor Area X RWI w/sgft F ui meet 1, 9: 1.064 X 0.94 X 6 666 42 X AT Infiltration: Air Sensible CFM ALA 9,4 TOTAL HDURLY SENSIBLE BEAT GAIN FOR ROOM Btulhr Latent Gain 3.0 Occupants X 155 gtuh/occ. Cccu ants 4, 771 X 0.94 X 46.66 X 0523 Infiltration: Air Sensible CFM EL pW TOTAL HOURLY LATENT HEAT GAIN FOR ROOM ID. Pa a 39 FnamvPra 6. by f ne Safi User Number: 6712 RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Jones Residence ROOM INFORMATION DESIGN CONDITIONS Room Name Family Room Outdoor Dry Bulb Temperature Floor Area 280.00 ftZ Outdoor Wet Bulb Temperature Indoor Dry Bulb Temperature 70 'F1 Outdoor Dail Ran e: opaque Surfaces R-38 Roof Attic R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) R-21 Wall (W.21.2x6.16) `R-13 Wall Orientation (W) (N) (W)I Date 1011112018 112 OF 78 OF 34 OF Area X X X X X X X X X U-Factor X X X X X X X X X CLTD1 = = = = = = = = = 278.8 0.0260 77.0 308.0 0.0690 31.0 228.6 0.0690 38.0 308.0 0.0690 55.0 280.0 0.1020 0.0 Page Total Items shown with an asterisk (`) denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Charlarl Unshaded Fenestration Sola Tube A A Orientation (W) (S) (S) Btulhr 558 659 598 1,169 a 1 2,9841 Area X X X X X X X X Xt:�::J GLF + + + + + + + + + Area X Xq X X= X X X X X GLF = = = = = = = = 1.2 113.12 4 ..0 00.0 40.0 Page Total Internal Gain Into ants 0 8 Occupants X F:�:--245 Btuh/occ.Occup_ 280 Floor Area X o.50 w/sgft = Equipment Infiltration: 1.064 X 0.94 X i2.87 X 42 = Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM Latent Gain Cccu ants 0.8 Occupants X 155 Btuh/occ. Infiltration: 4,771 X 0.94 X 12.87 X 0.00523 = Air Sensible CFM FLA OW TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 17.3 Btulhr 111 644 644 1, Btu/hr 4 Btu/hr 130 301 130 Parrs 40 of 40