14-0353 (SFD) Title 24I BUILDING ENERGY ANALYSIS REPORT I
PROJECT:
MR. & MRS. GEORGE VELARDE`l
53389 VIA .EL
BLAGIO
La Quinta, Ca 92253
Project Designer:
OCHOA DESIGN ASSOCIATES �� Z
73626 Highway 111
Palm Desert, Ca 92260
(760) 77316605 ae pv-ArA1 �
S
' v!��� �,C� r✓ C-fl�f
Report Prepared by: � jrA
' oM
Santiago Lopez-Ocampo �
Santiago Lopez-Ocamp 0F
P.O. Box (1018 B pING & SAFETY DEP
La Quinta, Ca 92247 BU��,�1PF(0VFt®
760.485.8927 FOR CpNSTRV
pATE�
I'
ED
Job Number: R(Cg�'I V
LQ040515-ReV063016 JUN 3 0 2016
CITY OF LA CUINTA
Date. COMMUNITY DEVELOPMENT
6/30/20j16
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by
LLC — www.energysoft.com.
EnergyPro 6.7 by EnergySoft User Number. 5732 f ID: L0040515-Rev06301
• "Y
I BUILDING ENERGY ANALYSIS REPORT I
PROJECT:
MR. & MRS. GEORGE VELARDE`l
53389 VIA .EL
BLAGIO
La Quinta, Ca 92253
Project Designer:
OCHOA DESIGN ASSOCIATES �� Z
73626 Highway 111
Palm Desert, Ca 92260
(760) 77316605 ae pv-ArA1 �
S
' v!��� �,C� r✓ C-fl�f
Report Prepared by: � jrA
' oM
Santiago Lopez-Ocampo �
Santiago Lopez-Ocamp 0F
P.O. Box (1018 B pING & SAFETY DEP
La Quinta, Ca 92247 BU��,�1PF(0VFt®
760.485.8927 FOR CpNSTRV
pATE�
I'
ED
Job Number: R(Cg�'I V
LQ040515-ReV063016 JUN 3 0 2016
CITY OF LA CUINTA
Date. COMMUNITY DEVELOPMENT
6/30/20j16
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by
LLC — www.energysoft.com.
EnergyPro 6.7 by EnergySoft User Number. 5732 f ID: L0040515-Rev06301
{
TABLE OF CONTENTS
3
Cover Page 1
Table of Contents 2
Form CF -1 R -PRF -01 -E Certificate of Compliance 3
Form RMS -1 Residential Measures Summary 17
Form MF -1 R Mandatory Measures Summary 19
HVAC System Heating and Cooling Loads Summary 23
t I
t I
EnergyPro 6.7 by EnergySoft Job Number: ID: L0040515-Rev063016 User Number: 5732
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation Date>Tme: 09:50, Thu, Jun 30, 2016
Calculation Description: Title 24 Analysis
Input File Name: VELARDE - T24 Rev062916.xml
CFI R -PRF -01
Page 1 of 14
GENERAL INFORMATION
01
01
Project Name VELARDE
02
This building incorporates futures -that require fleldiesting and/orkverification, by a certified; HERS ratersunder the supervision of a CEC-approved HERS provider.
02
Calculation Description Title 24 Analysis
08
Energy Use (kTDV/f?-yr)
03
Project Location 53389 VIA BELLAGIO
Compliance Margin
Percent Improvement
04
City La Quinta
05
Standards Version Compliance 2015
06
Zip Code 92253
07
Compliance Manager Version BEMCmpMgr 2013-4 (744)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.6
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 45
12
Project Scope Newly Constructed
13
Number of Dwelling Units 1
14
Total Cond. Floor Area (ft2) 4642
15
Number of Zones 5
16
Slab Area (j?) 4642"
17
Number of Stories 1
18
Addition Cond. Floor Ai" N/A
19
Natural Gas Available Yes
20
Addition Slab Area (fo' N/A
21
Glazing Percentage (6/6) 23.30/.
COMPLIANCE RESULTS J °'
01
Building Complies wit ComputerPerformance'
02
This building incorporates futures -that require fleldiesting and/orkverification, by a certified; HERS ratersunder the supervision of a CEC-approved HERS provider.
03
This building incorporates one or�mgre Special Feafuresshown below _.,''
08
Energy Use (kTDV/f?-yr)
Standard Design
Proposed Design
Registration Number: 215-N0088215B-000000000-0000 Registration Date/Time: 2016-06-3010:03:57 HERS Provider: CaICERTB jryt�.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CFlR-04072016-744 Report Generated at: 2016-06-30 09:56:54
ENERGY USE SUMMARY
04
05
06
07
08
Energy Use (kTDV/f?-yr)
Standard Design
Proposed Design
Compliance Margin
Percent Improvement
Space Heating
2.09
2.23
-0.14
-6.7%
Space Cooling
103.35
75.55
27.80
26.90/6
IAQ Ventilation
1.60
1.60
0.00
0.06/6
Water Heating
5.53
5.53
0.00
0.0%
Photovoltaic Offset
--
0.00
0.00
--
Compliance Energy Total
112.57
84.91
27.66
24.6"/6
Registration Number: 215-N0088215B-000000000-0000 Registration Date/Time: 2016-06-3010:03:57 HERS Provider: CaICERTB jryt�.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CFlR-04072016-744 Report Generated at: 2016-06-30 09:56:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE
Calculation Description: Title 24 Analysis
Calculation Daterrime: 09:50, Thu, Jun 30, 2016
Input File Name: VELARDE - T24 Rev062916.xml
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Window overhangs and/or fins
[HERS FEATURE SUMMARY
CF1 R -PRF -01
Page 2 of 14
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
IAQ mechanical ventilation
s. Higti�R=value Spray-Fosm-.lnsul8tion-
Cooling System Verifications: ,
• Minimum Airflow
• Verified EER
• Verified SEER
• Refrigerant Charge
Fan Efficacy Watts/CFM
HVAC Distribution System Verifications:
• Duct Sealing
Domestic Hot Water System Verifications: -`
— None — _ yrr".•1 -- _ __.
ENERGY DESIGN RATINGr/��� l�� �`
This is the sum of the annual TDV energy consuinptionjorenergy use oomponentsincluded in t11e performance compliance appioach foi the Starid'ard Design Building (Energy Budget) and the annual
TDV energy consumption for lighting and components not•reg' lated by Idle 24; Part:6 (such as doinestic_appliancessnd consumer electronics) and accounting for the annual TDV energy offset by an
on-site renewable energy system. V 4 C"' t'4 `# T" " %.0 V if C" i -It
Reference Energy Use Energy Design Rating Margin Percent Improvement
Total Energy (kTDVtf2-yr)' 1150.30 122.64 27.66 18.49°
• includes calculated Appliances and Miscellaneous Energy Use (AMEU)
BUILDING - FEATURES INFORMATION
01
02
03
04
05
06
07
Project Name
Conditioned Floor Area 012)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
VELARDE
4642
1
15
5
0
1
Registration Number: 215-N0088215B-000000000-0000
Registration Date/Time: 2016-06-30 10:03:57
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-04072016-744
HERS Provider: CaICERTS inc.
Report Generated at: 2016-06-30 09:52:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE
Calculation Description: Title 24 Analysis
Calculation Daterrime: 09:50, Thu, Jun 30, 2016
Input File Name: VELARDE - T24 Rev062916.)anl
CFI R -PRF -01
Page 3 of 14
ZONE INFORMATION
01
02
03
04
05
06 07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height
Water Heating System 1 Water Heating System 2
Bed 2 - Work Out AREA
Conditioned
HVAC System - Zone 1 (4 01
712
9
DHW Sys 1
Master Bedroom
Conditioned
HVAC System - Zone 2 (3 02
992
9
DHW Sys 1
Great Room & Gallery
Conditioned
HVAC System - Zone 3 (2 03
1102
9
DHW Sys 1
Dining -Kitchen -Pantry -Lau
Conditioned
HVAC System - Zone 4 (1 04
1030
9
DHW Sys 1
Guest Bedrooms
a Conditioned
HVAC System - Zone 5 (5 05
806
9
DHW Sys 1
VA &rage'
i
Registration Number: 215-N0088215B-000000000-0000 Registration Date/1-ime: 2016-06-30 10:03:57 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-04072016-744 Report Generated at: 2016-06-30 09:52:54
Registration Number: 215-N0088215B-000000000-0000 Registration Date/1-ime: 2016-06-30 10:03:57 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-04072016-744 Report Generated at: 2016-06-30 09:52:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE
Calculation Description: Title 24 Analysis
Calculation Daterrime: 09:50, Thu, Jun 30, 2016
Input File Name: VELARDE - T24 Rev062916.xml
CF1 R -PRF -01
Page 4 of 14
OPAQUE SURFACES
01
02
03
04
05
06
07
08
Name
Zone
Construction
Azimuth
Orientation Gross Area (W) Window & Door Area (ftp
Tilt (deg)
RYNW
Bed 2 - Work Out AREA
R-21 Wall
315
Right
214.5
42
90
Re/SW
Bed 2 - Work Out AREA
R-21 Wall
225
Back
132
40
90
Le/SE
Bed 2 - Work Out AREA
R-21 Wall
135
Left
214.5
0
90
Fr/NE
Bed 2 - Work Out AREA
R-21 Wall
45
Front
379.5
24
90
Roof
Bed 2 - Work Out AREA
Roof Attic + Spray Foam
178
Roof 2
Bed 2 - Work Out AREA
Roof Attic + Spray Foam
178
Roof 3
Bed 2 - Work Out AREA
Roof Attic + Spray Foam
178
Roof 4
Bed 2 -,Work Out AREA
Roof Attic + Spray Foam
178
Ri/NW 2
Master Bedroom
R-21 Wall
315
Right
665.5
54
90
Re/SW 2
Master Bedroom
R-21 Wall
225
Baric
247.5
90
90
Le/SE 2
Master.'Bedroom
R-21 Wall
135
Left
16.5
0
90
Fr/NE 2
�_T. Master Bedruum •�"""�° " R-21 Wall
45
Front
33
0
90
Roof 5'
-,,)Master. Bedroom
Roof Attic +Spray Foam i'�~("j
r
248
Roof 6
; Master Bii Jroom �
�� Roof`Attic + Spray Foam]
248
Roof 7
/'�,Mast'er.Eteiiioom '— t � Roof`Attic + Spray Foarri-`
i k=1-4(
14 u 44 "4 -:PV
248
Roof 8
V' Master Bedroom "
Roof Attic.+ Spray Foam(
a• ..,) V I
j.) t: 1 ;
248
Ri/NW 3
Great Roam & Gallery
R-21 Wall
315
Right
84.5
0
90
Re/SW 3
Great Room & Gallery
R-21 Wall
225
Baric
340
225
90
Le/SE 3
Great Room & Gallery
R-21 Wall
135
Left
520
114.5
90
Fr/NE 3
Great Room & Gallery
R-21 Wall
45
Front
383.5
167
90
Roof 9
Great Room & Gallery
Roof Attic + Spray Foam
275.5
Roof 10
Great Room & Gallery
Roof Attic + Spray Foam
275.5
Roof 11
Great Room & Gallery
Roof Attic + Spray Foam
275.5
Roof 12
Great Room & Gallery
Roof Attic + Spray Foam
275.5
Ri/NW 4
Dining -Kitchen -Pantry -Lau
R-21 Wall
315
Right
416
59.5
90
Re/SW 4
Dining -Kitchen -Pantry -Lau
R-21 Wall
225
Back
216
100
90
Le/SE 4
Dining -Kitchen -Pantry -Lau
R-21 Wall
135
Left
722
46.5
90
Roof 13
Dining -Kitchen -Pantry -Lau
Roof Attic + Spray Foam
257.5
Roof 14
Dining -Kitchen -Pantry -Lau
Roof Attic + Spray Foam
257.5
Roof 15
Dining-Kdchen-Pantry-Lau
Roof Attic + Spray Foam
257.5
Registration Number: 215-N0088215B-000000000-0000 Registration Date/Time: 2016.06-3010 3:57 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-04072016-744 Report Generated at: 2016-06-30 09:52:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation DateRme: 09:50, Thu, Jun 30, 2016
Calculation Description: Title 24 Analysis
Input File Name: VELARDE - T24 Rev062916.xml
CF1 R -PRF -01
Page 5of14
Roof 16
Dining -Kitchen -Pantry -Lau
Roof Attic + Spray Foam
03
04
257.5
06
07
Ri/NW 5
Guest Bedrooms
R-21 Wall
315
Right
452.8
82.5
90
Re/SW 5
Guest Bedrooms
R-21 Wall
225
Back
22
0
90
Le/SE 5
Guest Bedrooms
R-21 Wall
135
Left
423
31.5
90
Le/S
Guest Bedrooms
R-21 Wall
180
specify -
42.1
13.6
90
FrINE 4
Guest Bedrooms
R-21 Wall
45
Front
278.2
15.8
90
Roof 17
Guest Bedrooms
Roof Attic + Spray Foam
I Unventilated
3.5
201.5
0.85
No
Roof 18
Guest Bedrooms
Roof Attic + Spray Foam
201.5
Roof 19
Guest Bedrooms
Roof Attic + Spray Foam
201.5
Roof 20
Guest Bedrooms
Roof Attic + Spray Foam
201.5
ATTIC 1
01
02 1I �
03
04
05
06
07
08
Name
,-Constructions ._
Type
Roof Rise
Roof Reflectance
Roof Emittance
Radiant Barrier
Cool Roof
Attic Bed 2 -Work Out AREA
Attic Roof Bed 2 -Work Out
AREA
—� unventilated,
,r
!ice`"- — d F t� _
35
! f r' -N "�
0.1
'7:* f t _ �
0.85
-
No
No
Attic Master Bedroom
Attic RoofMaster_Bedroom
It Unventilated!
x - 3:5
0.1
0.85
No
No
Attic Great Room &Gallery
Attic RoofGreat Room A
:Gallery
,gallery`-,
Attic
' nti atefdl
11 ie
;" 3.5
'j 0.1) O
P I� `4
0.85
No
No
Dining -Kitchen -Pantry -Lau
Attic
RoofDining-Kitchen-Pantry-
Lau
Unventilated
3.5
0.1
0.85
No
No
Attic Guest Bedrooms
Attic RoofGuest Bedrooms
I Unventilated
3.5
0.1
0.85
No
No
Registration Number: 215-N0088215B-000000000-0000 Registration Date/Time: 201606-30 1003:57 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-04072016-744 Report Generated at: 2016-06-30 09:52:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation DatelTime: 09:50, Thu, Jun 30, 2016
Calculation Description: Title 24 Analysis
Input File Name: VELARDE - T24 Rev062916.xml
CF1 R -PRF -01
Page 6 of 14
WINDOWS
I
01
02
03
04 05
06
07
08
09
10
Name
Type
Surface (Orientation -Azimuth)
Multipli
Width (ft) Height (ft) er
Area
(ft)
U -factor
SHGC
Exterior Shading
2046 Fix
Window
Ri/NW (Right -315)
-- -
1
9.0
0.26
0.21
Insect Screen (default)
6056 Casement
Window
Ri/NW (Right -315)
-- -
1
33.0
0.27
0.19
Insect Screen (default)
(2) 2680 RDr
Window
Re/SW (Back -225)
-- -
1
40.0
0.27
0.17
Insect Screen (default)
4046 Casement
Window
Ri/NW 2 (Right -315)
- -
1
18.0
0.27
0.19
Insect Screen (default)
1620 Fix
Window
Ri/NW 2 (Right -315)
- -
1
3.0
0.26
0.21
Insect Screen (default)
1620 Fix 2
Window
Ri/NW 2 (Right -315)
-- -
1
3.0
0.26
0.21
Insect Screen (default)
1426 Fix
Window
RUNW 2 (Right -315)
-- -
1
3.3
0.26
0.21
Insect Screen (default)
1626 Fix
Window
A Ri/NW 2 (Right -315)
-- --
1
3.8
0.26
0.21
Insect Screen (default)
1426 Fix 2
Window
Ri/NW 2 (Right -315)
-- -
1
3.3
0.26
0.21
Insect Screen (default)
1656 Fix
Window
Ri/NW 2 (Right -315)
-- -
1
9.8
0.26
0.21
Insect Screen (default)
1656 Fix 2
Window.
,� - - �--Ri%NW,2-(Right-315)
-- --
1
9.8
0.26
0.21
Insect Screen (default)
2080 Sidelfte
Window
*,/�Re/SW 2,(Back-225) >"::�
r- M X 20 } i:�y 8.0
C 1
16.0
0.27
0.10
Insect Screen (default)
(2) 2680 FrDr 2
Window
1 Re/SW 2 (Back -225) (
+' 5,0 �` 8.0
! 1711N 9 --40.0
0.27
0.17
Insect Screen (default)
2080 Sidelfte 2
Window
P//` � '� Re/SW 2{Baric=225) �.� L�_= tj \] 2.0 8:0
J J1 1 f 160
0.27
0.10
Insect Screen (default)
9020 Transom
Window
'jam r '� Re/SW 2 (Back;225)
fl `
C J--
x18.0
0.29
0.11
Insect Screen (default)
(3) 58100
Window
Re/SW 3 (Back -225)
17.0 10.0
1
170.0
0.26
0.17
Insect Screen (default)
(2) 26110
Window
Re/SW 3 (Back -225)
- --
1
55.0
0.26
0.17
Insect Screen (default)
2650 Fix
Window
Le/SE 3 (Left -135)
- -
1
12.5
0.26
0.21
Insect Screen (default)
3066 Fix
Window
Le/SE 3 (Left -135)
- -
1
19.5
0.26
0.21
Insect Screen (default)
(2) 3080 FrDr
Window
Le/SE 3 (Left -135)
- -
1
48.0
0.27
0.17
Insect Screen (default)
6026 Transom
Window
Le/SE 3 (Left -135)
- -
1
15.0
0.29
0.11
Insect Screen (default)
3066 Fix 2
Window
Le/SE 3 (Left -135)
- -
1
19.5
0.26
0.21
Insect Screen (default)
5066 Fix
Window
Fr/NE 3 (Front -45)
- -
1
32.5
0.26
0.21 1
Insect Screen (default)
1620 Fix 3
Window
FUME 3 (Front -45)
-- --
1
3.0
0.26
0.21
Insect Screen (default)
80120
Window
Fr/NE 3 (Front -45)
-- -
1
96.0
0.71
0.73
Insect Screen (default)
5066 Fix 2
Window
FrINE 3 (Front -45)
-- -
1
32.5
026
0.21
Insect Screen (default)
1620 Fix 4
Window
RINE 3 (Front -45)
-- -
1
3.0
0.26
0.21
Insect Screen (default)
3066 Fix 3
Window
Ri/NW 4 (Right -315)
-- --
1
19.5
0.26
0.21
Insect Screen (default)
(2) 40100
Window
Ri/NW 4 (Right -315)
-- --
1
40.0
026
0.17
Insect Screen (default)
Registration Number: 215-NO0882158-000000000-OON Registration Date/Time: 2016-06-30 10.03:57 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-04072016-744 Report Generated at: 2016-06-30 09:S2:S4
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation Daterrime: 09:50, Thu, Jun 30, 2016
Calculation Description: Title 24 Analysis Input File Name: VELARDE - T24 Rev062916.xm1
CF1 R -PRF -01
Page 7of14
(4) 26100
Window
01 r�d� j �R
Re/SW 4 (Back -225)
10.0 10.0 1
100.0
0.26
0.17
Insect Screen (default)
2650 Fix 2
Window
Le/SE 4 (Left -135)
-- -- 1
12.5
0.26
0.21
Insect Screen (default)
2650 Fix 3
Window
08
Le/SE 4 (Left -135)
-- - 1
12.5
0.26
021
Insect Screen (default)
2020 Fix
Window
Overhang
Le/SE 4 (Left -135)
-- -- 1
4.0
0.26
021
Insect Screen (default)
2020 Fix 2
Window
Le/SE 4 (Left -135)
-- -- 1
4.0
0.26
0.21
Insect Screen (default)
3046 Casement
Window
DistL
Le/SE 4 (Left -135)
- -- 1
13.5
0.27
0.19
Insect Screen (default)
3066 Fix 4
Window
4
Ri/NW 5 (Right -315)
- -- 1
19.5
0.26
0.21
Insect Screen (default)
(2) 3080 FrDr 2
Window
(2) 2680 FrDr 2
Ri/NW 5 (Right -315)
- -- 1
48.0
0.27
0.17
Insect Screen (default)
6026 Transom 2
Window
0
Ri/NW 5 (Right -315)
- - 1
15.0
0.29
0.11
Insect Screen (default)
5046 Casement
Window
0
Le/SE 5 (Left -135)
-- - 1
22.5 1
0.27
0.19
Insect Screen (default)
2046 Fix 2
Window
18.45
Le/SE 5 (Left -135)
-- --- 1
9.0
0.26
0.21
Insect Screen (default)
1646 Fix
Window
A
Le/S (- specify -180)
- - 1
6.8
0.26
0.21
Insect Screen (default)
1646 Fix 2
Window
/,, \
Le/S (- specify -180)
- -- 1
6.8
0.26
0.21
Insect Screen (default)
3646 Casement
Window
�1/
Fr/NE 4 (Front -45)
- - 1
15.8
0.27
1 0.19
Insect Screen (default)
DOORS.rt'.&.a
01 r�d� j �R
1E 1� 03 04
Name Side of Building
Area (ft2) U factor
3080 Dr % '� .. R PRYNE
24.0 0.50
OVERHANGS AND FINS
01
02
03
04
05
06
07
08
09
10
11
12 13
14
Overhang
Left Fin
Right Fin
Window
Depth
Dist Up
Left
Extent
Right
Extent
Flap Ht.
Depth
Top Up
DistL
Bot Up
Depth
Top Up Dist R
Bot Up
2080 Sidelite
4
0.1
4
4
0
0
0
0
0
0
0 0
0
(2) 2680 FrDr 2
4
0.1
4
4
0
0
0
0
0
0
0 0
0
2080 Sidelite 2
4
0.1
4
4
0
0
0
0
0
0
0 0
0
(3) 58100
18.45
2
3
3
0
0
0
0
0
0
0 0
0
(4) 26100
15.45
2
4.58
4.58
0
0
0
0
0
0
0 0
0
Registration Number: 215-N0088215B-000000000-0000 Registration Date/7-ime: 2016-06-30 10:03:57 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-04072016-744 Report Generated at: 2016-06-30 09:52:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation DatelTme: 09:50, Thu, Jun 30, 2016
Calculation Description: Title 24 Analysis
Input File Name: VELARDE - T24 Rev062916.xml
CF1 R -PRF -01
Page 8 of 14
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
07
Total Cavity
Winter Design
Construction Name
Surface Type
Construction Type
Framing
R -value
U -value
Assembly Layers
• Under Roof Joists: R-27.0 insul.
• Cavity/Frame: R -13.0/2x4 Top Chrd
• Roof Deck: Wood Siding/sheathing/decking
Attic RoofBed 2 - Work Out
2x4 Top Chord of Roof Truss @ 24
Tile Gap: present
AREA
Attic Roofs
Wood Framed Ceiling
in. O.C.
R 40
0.024
Roofing: 10 PSF (RoofTile)
• Inside Finish: Gypsum Board
• Cavity/ Frame: R-21 /06
• Exterior Finish: Wood
R-21 Wall
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
0.066
Siding/sheathing/decking
Ceilings (below
Inside Finish: Gypsum Board
Roof Attic + Spray Foam
attic) A
Wood Framed Ceiling
2x4 @ 24 in. O.C.
none
0.481
Cavity/Frame: no insul. /2x4
]
Under Roof Joists: R-27.0 insul.
.•.,"JJ
Cavity/Frame: R -13.0/2x4 Top Chrd
Roof Deck: Wood Siding/sheathing/decking
i_--^-�
-2x4 Top Chord of Roof Truss @ 24
-
Tile Gap: prescnt
Attic RoofMaster Bedroom
Attic Roofs
Wood Framed -Ceiling
r! -.,.in. - in. O.C. � r-'°--•-* a
�+: R 40.4
0.024
Roofing: 10 PSF (RootTle)
L
L k K
j J
m
Under Roof Joists: R-27.0 insul.
Cavity/Frame: R-13.0 4Top Chrd
3
• Roof Deck: Wood Sidin sheathin /dedcing
g1
Attic RoofGreat Room &
2x4 TopChord ofRoof Truss @ 24�
61
,.
0.024
Tile Gap: present
Gallery
Gallery
Atfi/?
Attic'Roofs
Wood*Framed Ceiling„"
in.
in.
R 40 _
Roofing: 10 PSF(RootTife)
• Under Roof Joists: R-270 insul.
• Cavity/Frame: R -13.0/2x4 Top Chrd
• Roof Deck: Wood Siding/sheathing/decking
Attic
2x4 Top Chord of Roof Truss @ 24
Tile Gap: present
RoofDining-Kdchen-Pantry-Lau
Attic Roofs
Wood Framed Ceiling
in. O.C.
R 40
0.024
Roofing: 10 PSF (Roof -Tile)
• Under Roof Joists: R-27.0 insul.
• Cavity/Frame: R-13.0 /2x4 Top Chid
• Roof Deck: Wood Siding/sheathing/decking
2x4 Top Chord of Roof Truss @ 24
Tile Gap: present
Attic RoofGuest Bedrooms
Attic Roofs
Wood Framed Ceiling
in. O.C.
R 40
0.024
Roofing: 10 PSF (RootTile)
Registration Number: 215-N0088215B-000000000-0000 Registration Date/rime: 2016-06-30 10:03:57 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-04072016-744 Report Generated at: 2016-06-30 09:52:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation DateTme: 09:50, Thu, Jun 30, 2016
Calculation Description: Title 24 Analysis Input File Name: VELARDE - T24 Rev062916.xml
CFI R -PRF -01
Page 9of14
SLAB FLOORS
01
02
03
04
05
06
01
02
03
04
05
06
07
Name
Zone
Area (ft2)
Perimeter (ft)
Edge Insul. R -value & Depth
Carpeted Fraction
Heated
Slab -on -Grade
Bed 2 - Work Out AREA
712
0.1
None
0.8
No
Slab -on -Grade 2
Master Bedroom
992
0.1
None
0.8
No
Slab -on -Grade 3
Great Room & Gallery
1102
0.1
None
0.8
No
Slab -on -Grade 4
Dining -Kitchen -Pantry -Lau
1030
0.1
None
0.8
No
Slab -on -Grade 5
Guest Bedrooms
806
0.1
None
0.8
No
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04
Quality Insulation Installation (Qil) A Quality Installation of Spray Foam Insulation Building Envelope Air Leakage CFM50
Not Required /11\ Required Not Required —
rNAWsl.
WATER HEATING SYSTEMS
01 02 -oa o5 os
Name Systenf Type JN 1 F 1'Distributlontlype oV 11 �+.� Water Heatei� Number of Heaters Solar Fraction (%)
DHW Sys 1 - 1/1 Standard .DHW Heater 1J N�,j 1 .0%
WATER HEATERS r Y Y 4"' 1r It ..4 f t< A '+b. V : W-.& 1- *'b
01
02
03
04
05
06
07
08
Pipe Insulation
Parallel Piping
Compact Distribution
Point -of Use
Recirculation
Control
Central DHW
Distribution
Tank Exterior
—
—
—
--
Tank Volume
Energy Factor or
Insulation
Standby Loss
Name
Heater Element Type
Tank Type
(gal)
Efficiency
Input Rating
R -value
(Fraction)
DHW Heater 1
Natural Gas
Small Storage
50
0.6
40000-Btu/hr
0
0
WATER HEATING - HERS VERIFICATION
01
02
03
04
05
06
07
Name
Pipe Insulation
Parallel Piping
Compact Distribution
Point -of Use
Recirculation
Control
Central DHW
Distribution
DHW Sys 1 - 1/1
—
—
—
--
—
—
Registration Number: 215-N0088215B-000000000-0000 Registration Date/Time: 2016.06-30 10.U3:57 HERS Provider: CaiCERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-04072016-744 Report Generated at: 2016-06-30 09:52:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE
Calculation Description: Title 24 Analysis
Calculation DateTme: 09:50, Thu, Jun 30, 2016
Input File Name: VELARDE - T24 Rev062916.xmi
CF1 R -PRF -01
Page 10 of 14
SPACE CONDITIONING SYSTEMS
01
02
03
04
05
06
SC Sys Name
System Type
Heating Unit Name
Cooling Unit Name
Fan Name
Distribution Name
Cooling Component 1:Heating Component 1 Air
Other Heating and Cooling
Heating Component 1
Cooling Component 1
HVAC Fan 1
Air Distribution System 1
Distribution System 1:HVAC Fan 1:1
System
CntrlFurnace - Fuel -fired central furnace
80 AFUE
Cooling Component 2:Heating Component 2Air
Other Heating and Cooling
Heating Component 2
Looting Component 2
HVAC Fan 2
Air Distribution System 2
Distribution System 2:HVAC Fan 2:1
System
Cooling Component 3:1-leating Component 3Air
Other Heating and Cooling
Heating Component 3
Cooling Component 3
HVAC Fan 3
Air Distribution System 3
Distribution System 3 -HVAC Fan 3:1
System
Cooling Component 4:Heating Component 4Air
Other Heating and Cooling
Heating Component 4
Cooling Component 4
HVAC Fan 4
Air Distribution System 4
Distribution System 4:HVAC Fan 4:1
System
Cooling Component 5:Heating Component 5Air
Other Heating and Cooling
Heating Component 5
Cooling Component 5
HVAC Fan 5
Air Distribution System 5
Distribution System 5:HVAC Fan 5:1
System
HVAC - HEATING UNIT TYPES !
02
W
Name ti - = Type= �� 11
Efficiency
Heating Component 1�(CntrlFurn
ape `-Fuel=fired central.furnace
92 AFUE
Heating Component 2�..i
IJ NCntrlFurnaee'Fuel-fired centra! furnace;
80 AFUE
Heating Component 3"
0 CM_rlFurnaceFuelzfired central furnace
80 AFUE
Heating Component 4 y
�✓ M CntrlFurnace - Fuel -fired central furnace
80 AFUE
Heating Component 5
CntrlFurnace - Fuel -fired central furnace
80 AFUE
CaICERTS inc.
2016-06-30 09:52:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation Datefrime: 09:50, Thu, Jun 30, 2016
Calculation Description: Title 24 Analysis
Input File Name: VELARDE - T24 Rev062916.xml
CFI R -PRF -01
Page 11 of 14
HVAC - COOLING UNIT TYPES
01
02
03 04
05
06
07
03
04
Efficiency
06
Multi -speed
Verifi�AirflJ'
Name
System Type
EER SEER
Zonally Controlled
Compressor
HERS Verification
Cooling Component 1
SplitAirCond
12
14
Not Zonal
Single Speed
Cooling Component
1 -hers -cool
Cooling Component 2
SplitAirCond
14.5
14.6
Not Zonal
Single Speed
Cooling Component
2 -hers -cool
Cooling Component 3
SplitAirCond
14
15
Not Zonal
Single Speed
Cooling Component
3 -hers -cool
Cooling Component 4
SplitAirCond
- 14.5
14.6
Not Zonal
Single Speed
Cooling Component
4 -hers -cool
Cooling Component 5
SplitAirCond
14.4
16
Not Zonal
Single Speed
Cooling Component
5 -hers -cool
f A t
HVAC COOLING - HERS VERIFICATION
01
.�� '" ` 0Y
03
04
-05
06
Name
Verifi�AirflJ'
If {# AirHo-w argetCiVer'rfiedEER
y5�
Verified SEER
Verified Refrigerant
Charge
Cooling Component 1 -hers -cool
Vim`<Required 350, [ tjj Required I 1d � �1i
Not Required
Required
Cooling Component 2 -hers -cool
f� Requir`ed
350 1> e �LRequired
C: r.
Required
Required
Cooling Component 3 -hers -cool
Required
v 356 4
Fiequiied
Required
Required
Cooling Component 4 -hers -cool
Required
350
Required
Required
Required
Cooling Component 5 -hers -cool
Required
350
Required
Required
Required
Registration Number: 215-NOOSS215B-000000000-0000 Registration Date/Time: 2016-06-30 10:03:57 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-04072016-744 Report Generated at: 2016-06-30 09:52:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation DaterTime: 09:50, Thu, Jun 30, 2016
Calculation Description: Title 24 Analysis Input File Name: VELARDE - T24 RevO62916.xml
CFI R -PRF -01
Page 12 of 14
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
Name
Type
Duct Leakage
Insulation R -value
Duct Location
Bypass Duct
HERS Verification
Air Distribution System 1
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
- j IVofRequired
Not Required —
Air Distribution System 2 -hers -dist
j 4,�,IRequredL`j6.0
i �`':`
f `Not diiedLl
1 -hers -dist
Air Distribution System 2
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
N6t-Required
Not Required —
Air Distribution System 4 -hers -dist
Required
6.0
Not Required
2 -hers -dist
Air Distribution System 3
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
Not Required
Not Required —
3 -hers -dist
Air Distribution System 4
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
4 -hers -dist
Air Distribution System 5
DuGtsAttic
Sealed and tested
8
Attic
None
Air Distribution System
5 -hers -dist
Fit
HVAC DISTRIBUTION -HERS VERIFICATION 11�\
01
02
01
_ f 02<
03
04
05
06
07 08
Name
ti Duct Leekag�..— Duct leakage Verified Duct Verified Duct
Verifications " �,* Target (°k)Location fDesign
Buried
Ducts
Deeply Buried Low -leakage
Ducts Air Handler
Air Distribution System 1 -hers -dist
dRequired
X6.0I
- Required
`Not Required
- j IVofRequired
Not Required —
Air Distribution System 2 -hers -dist
j 4,�,IRequredL`j6.0
i �`':`
f `Not diiedLl
G
i)Not.Required
Not Required —
Air Distribution System 3 -hers -dist
Required,
F6.0R S
N6t Requi� C
Ngt'Requir
N6t-Required
Not Required —
Air Distribution System 4 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required —
Air Distribution System 5 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required —
HVAC -FAN SYSTEMS
01
02
03
04
Name
Type
Fan Power (Watts/CFM)
HERS Verification
HVAC Fan 1
Single Speed PSC Furnace Fan
0.58
HVAC Fan 1 -hers -fan
HVAC Fan 2
Single Speed PSC Furnace Fan
0.58
HVAC Fan 2 -hers -fan
HVAC Fan 3
Single Speed PSC Furnace Fan
0.58
HVAC Fan 3 -hers -fan
HVAC Fan 4
Single Speed PSC Furnace Fan
0.58
HVAC Fan 4 -hers -fan
HVAC Fan 5
Single Speed PSC Furnace Fan
0.58
HVAC Fan 5 -hers -fan
HVAC FAN SYSTEMS - HERS VERIFICATION
01 02 03
Registration Number: 215-N0088215B-000000000.0000 Registration Datefrime: 2016-06-3010.03:57 HERS Provider: CaiCERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-04072016-744 Report Generated at: 2016-06-30 09:52:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation Date`Time: 09:50, Thu, Jun 30, 2016
Calculation Description: Title 24 Analysis Input File Name: VELARDE - T24 Rev062916.xml
CF1 R -PRF -01
Page 13 of 14
Name
Verified Fan Watt Draw
Required Fan Efficiency (Watts/CFM)
HVAC Fan 1 -hers -fan
Required
0.58
HVAC Fan 2 -hers -fan
Required
0.58
HVAC Fan 3 -hers -fan
Required
0.58
HVAC Fan 4 -hers -fan
Required
0.58
HVAC Fan 5 -hers -fan
Required
0.58
IAQ (Indoor Air Quality) FANS
01
02
03
04
05
06
Dwelling Unit
IAQ CFM
IAQ Watts/CFM
IAQ Fan Type
IAQ Recovery
Effectiveness(9'o)
HERS Verification
SFam IAQVentRpt
,1166.42
0.25
Default
0
Required
i!(11a-\, CE -0RTS17 n C
HERS PROVIDER
Registration Number: 215-NO0882158-000000000-0000 Registration Date/Time: 2016-06-30 10:03:57 HERS Provider: CaiCERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF111-04072016-744 Report Generated at: 2016-06-30 09:52:54
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation DatefTime: 09:50, Thu, Jun 30, 2016
Calculation Description: Title 24 Analysis Input File Name: VELARDE - T24 RevO62916.xml
CFI R -PRF -01
Page 14 of 14
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Santiago Lopez-Ocampo
Company:
Signature Date:
Santiago Lopez-Ocampo
2016-06-30 09:58:53
Address:
CEA/HERS Certification Identification (If applicable):
P.O. Box 1018
NA
City/State/Zip:
Phone:
La Quinta, CA 92247
760-485-8927
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations. J V
3. _ _-The building design features or system design featuresid tified.on=this Certificate of Compliance are consistent with the information -provided on other applicable compliance documents, -
worksheets, calculations, plans and specifications submilteVo the enforcement agency,for approval -with this building permit application.
f
Responsible Designer Name:
L� I
IL
I L"
'Responsible Designer Signature:
Eduardo Escobar
,
Company:
Date Signed -HERS "
ER
Escobar Design
2016-06-30 10:03:5
Address:
License:
43-927 Pacific Ave.
NA
City/StatefLip:
Phone:
Indio, CA 92201
760-289-9221
Digitally signed by CaICERTS. This digital signature is provided in order to secure the content of this registered document and in noway implies Registration Provider responsibility for the accuracy of the
information.
Registration Number: 215-N0088215B-000000000-0000 Registration Date/Time: 2016-06-30 10:03:57 HERS Provider: CaiCERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-04072016-744 Report Generated at: 2016-06-30 09:52:54
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
MR. & MRS. GEORGE VELARDE
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
6/30/2016
Project Address
53389 VIA BELLAGIO La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
4,642
Addition
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity
Special Features Status
Slab Unheated Slab -on -Grade
- no insulation 4,642
Perim = 0'
New
Wall Wood Framed
R21 4,697
New
Demising Wood Framed
R 19 2,938
New
Door Opaque Door
- no insulation 24
New
Roof Wood Framed Attic
- no insulation 4,642
Rigid=R-40.0
New
FENESTRATION
Orientation Area
I Total Area: 1,082 Glazing Percentage: 23.3 %
U -Fac SHGC Overhang Sidefins
New/Altered Average U -Factor: 0.30
Exterior Shades Status
Right (NVV) 84.0
0.260
0.21 none
none
Bug Screen New
Right (NM 51.0
0.270
0.19 none
none
Bug Screen New
Rear (SW) 40.0
0.270
0.17 none
none
Bug Screen New
Rear (SVv) 32.0
0.270
0.10 4.0
none
Bug Screen
New
Rear (SW) 40.0
0.270
0.17 4.0
none
Bug Screen
New
Rear (SVtq 18.0
0.290
0.11 none
none
Bug Screen
New
Rear (SVV) 170.0
0.260
0.17 18.5
none
Bug Screen
New
Rear (SM 55.0
0.260
0.17 none
none
Bug Screen
New
Left (SE) 93.5
0.260
0.21 none
none
Bug Screen
New
Left (SE) 48.0
0.270
0.17 none
none
Bug Screen
New
Left (SE) 15.0
0.290
0.11 none
none
Bug Screen
New
Front (NE) 71.0
0.260
0.21 none
none
Bug Screen
New
Front (NE) 96.0
0.710
0.73 none
none
Bug Screen
New
Right (NM 40.0
0.260
0.17 none
none
Bug Screen
New
HVAC SYSTEMS
(fit . Heating
Min. Eff
Cooling
Min. Eff
Thermostat Status
1 Central Furnace
92% AFUE
Split Air Conditioner
14.0 SEER
Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner
14.6 SEER
Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner
15.0 SEER
Setback
New
HVAC DISTRIBUTION
Location Heating
Cooling Duct Location
Duct
R -Value Status
HVAC System - Zone 1 (4 1 Ducted
Ducted Attic
8.0
New
HVAC System - Zone 2 (3 1 Ducted
Ducted Attic
8.0
New
HVAC System - Zone 3 (2 1 Ducted
Ducted Attic
8.0
New
WATER HEATING
Ot . Type
Gallons Min. Eff
Distribution Status
EnerqvPro 6.7 bv EnerovSoft User Number: 5732
RunCode: 2016-06-30T09:53:31
ID: L 040515-Rev06301
Pae 17 of 27
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
MR. & MRS. GEORGE VELARDE
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
6/30/2016
Project Address
53389 VIA BELLAGIO La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
4,642
. Addition
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity Special Features Status
FENESTRATION I Total Area: 1.082 Glazing Percentage: 23.3 % New/Altered Average U -Factor: 0.30
Orientation Area U -Fac SHGC Overhang Sidefins Exterior Shades Status
Rear (SIN) 100.0 0.260
0.17 15.5 none Bug Screen New
Leff (SE) 36.0 0.270
0.19 none none Bug Screen New
Right (NM 48.0 0.270
0.17 none none Bug Screen New
Right (Nth) 15.0 0.290
0.11 none none Bug Screen New
Left (S) 13.6 0.260
0.21 none none Bug Screen New
Front (NE) 15.8 0.270
0.19 none none Bug Screen New
HVAC SYSTEMS
(fit . Heating Min. Eff
Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE
Split Air Conditioner 14.6 SEER Setback
New
1 Central Furnace 80% AFUE
Split Air Conditioner 16.0 SEER Setback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value Status
HVAC System - Zone 4 (1 1 Ducted
Ducted Attic 8.0
New
HVAC System - Zone 5 (5 ( Ducted
Ducted Attic 8.0
New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
EnemvPro 6.7 bv EnerovSoft User Number. 5732
Run Code: 2016-06.30709:53:31 ID: L 040515-Rev06301
Pae 18 of 27
2013 Low -Rise Residential Mandatory Measures Summary
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the
compliance aDaroach used. Exceptions may aDaly. Review the respective code section for more information.
Building Envelope Measures:
§110.6(a)1:
Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§ 110.6(a)5:
Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of § 10-11l(a).
§110.7:
Exterior doors and windows are weatherstripped; all joints and penetrations are caulked and sealed.
§110.8(a):
Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R.
§I 10.8(i):
The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of §I 10.8(1) when the
installation of a cool roof is specified on the CFIR.
§110.80):
A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CF1R.
Minimum R-30 insulation in wood -frame ceiling; or the weighted average U -factor shall not exceed 0.031. Minimum R-19 in a
§150.0(a):
rafter roof alteration. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The
attic access shall be gasketed to prevent air leakage.
§ 150.0(b):
Loose fill insulation shall conform with manufacturer's installed design labeled R -value.
§ 150.0(c):
Minimum R-13 insulation in 2x4 inch wood framing wall or have a U -factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U -
factor).
§150.0(d):
Minimum R-19 insulation in raised wood -frame floor or 0.037 maximum U -factor.
§150.0(g)l :
In Climate Zones 14 and 16 a Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior
walls vented attics and unvented attics with air -permeable insulation.
In Climate Zones 1-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class II
§150.0(g)2:
vapor retarder.
In a building having a controlled ventilation crawl space, a Class I or Class II vapor retarder shall be placed over the earth floor of
§150.0(g)3:
the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section
150.0(d).
§150.0(1):
Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%,
have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration;
and when installed as part of a heated slab floor meets the requirements of 110.8
§ 150.0(q):
Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U -
factor of 0.58; or the weighted average U -factor of all fenestration shall not exceed 0.58.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
§150.0(e)IA:
Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150.0(e)1 B:
Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a readily accessible operable, and tight -fitting damper or a combustion -air control device.
§150.0(e)IC:
Masonry or factory -built fireplaces have a flue damper with a readily accessible control.
§150.0(e)2:
Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside
of the building,are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110.0-§110.3:
HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified to the Energy Commission.
§ 110.3(c)5:
Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation
valve, and recirculation loop connection requirements of § 110.3(c)5.
Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appli-
§110.5:
ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool
ands a heaters.
§150.0(h)1:
Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified
in §150.0(h)2.
§ 150.0(h)3A:
Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any
dryer vent.
§150.0(i):
Heating systems are equipped with thermostats that meet the setback requirements of § 110.2(c).
§150.00)IA:
Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§150.00)1B:
Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, have R-12 external
insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the tank.
For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage
tank, all piping with a nominal diameter of 3/4 inch or larger, all p'ping associated with a domestic hot water recirculation system
§150.00)2A:
regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and
all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3-
A.
§150.00)2B:
All domestic hot water pipes that are buried below grade must be installed in a water proof and non -crushable casing or sleeve
that allows for installation removal and replacement of the enclosed pipe and insulation.
2013 Low -Rise Residential Mandatory Measures Summary
§150.00)2C:
Pipe for cooling system lines shall be insulated as specified in §150.00)2A. Piping insulation for steam and hydropic heating
systems or hot water systems with pressure > 15 psig shall meet the requirements in TABLE 120.3-A-
20.3-A-
§150.00)3:
§ 150.00)3:
Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For
§150.00)3A:
example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or
painted with coating that is water retardant and provides shie;ding from solar radiation that degrades the material.
Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I
§150.00)3B:
or Class Il vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class U vapor
retarder.
Systems using gas or propane water heaters to serve individual dwelling units shall include: a 120V electrical receptacle within 3
feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the
§150.0(n)l:
space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed
water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000
Btu/hr.
§150.0(n)2:
Recirculating loops serving multiple dwelling units shall meet the requirements of § 110.3(c)5.
§I 50.0(n)3:
Solar water -heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC)
or by a testing agency approved by the Executive Director.
Ducts and Fans Measures:
All air -distribution system ducts and plenums installed are sealed and insulated to meet the requirements of CMC §601.0, §602.0
§603.0, §604.0, §605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition.
Supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC
§605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed
§I 50.0(m)1:
with mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, or UL 18113 or
aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than `/4 inch, the
combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums
defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying
conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms
shall not be compressed to cause reductions in the cross-sectional area of the ducts.
Factory -Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; join
§I50.0(m)2:
and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape i
used in combination with mastic and draw bands.
§150.0(m)3-6:
Field -Fabricated Duct Systems shall comply with requirements for: pressure -sensitive tapes, mastics, sealants, and other
requirements specified for duct construction; duct insulation R -value ratings; duct insulation thickness; and duct labeling.
§ 150.0(m)7:
All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic
dampers.
§I 50.0(m)8:
Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers
except combustion inlet and outlet air openings and elevator shaft vents.
Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not
§I 50.0(m)9:
limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum
sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is
water retardant and provides shielding from solar radiation.
§150.0(m)10:
Flexible ducts cannot have porous inner cores.
When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be
§150.0(m)ll:
sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference
Residential Appendix RA3.
Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal
§ 150.0(m)12:
conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of
§150.0(m)12.
Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the
placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The
§ 150.0(m)13:
space conditioning system must also demonstrate airflow 2:350 CFM per ton of nominal cooling capacity through the return
grilles, and an air -handling unit fan efficacy:5 0.58 W/CFM as confirmed by field verification and diagnostic testing, in
accordance with Reference Residential Appendix RA3.
Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode, _
§ 150.0(m)15:
an airflow from the dwelling, through the air handler fan and delivered to the dwelling, of >_ 350 CFM per ton of nominal cooling.,.,,,-
oolingt;capacity,
capacity,and operating at an air -handling unit fan efficacy of <_ 0.58 W/CFM as confirmed by field verification and diagnostic
testing,in accordance with Reference Residential Appendix RA3.
All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of
§150.0(0):
central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the
Whole Building Ventilation.
§150.0(o)IA:
Whole Building Ventilation airflow shall be confirmed through field verification and diagnostic testing, in accordance with
Reference Residential Appendix RA3.
Pool and Spa Heating Systems and Equipment Measures:
Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
§ 110.4(a):
Regulations; an on-off switch mounted outside of the heater that allows shutting off the heater without adjusting the thermostat
settin • a perrnanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating.
2013 Low -Rise Residential Mandatory Measures Summary
§I 10.4(b)1:
Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction
and return lines or built-up connections for future solar heating.
§110.4(b)2:
Outdoor pools or spas that have a heat pump or gas heater shall have a cover.
§ 110.4(b)3:
Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro-
grammed to run only during off-peak electric demand periods.
§110.5:
Natural gas pool and spa heaters shall not have a continuous burning pilot light.
§150.0(p):
Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements.
Lighting Measures:
§110.9:
All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of §110.9.
§150.0(k)IA:
Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with §150.0(k) in accordance with TABLE
150.0-A or TABLE 150.0-B as applicable.
§I50.0(k)1B:
When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply
with the applicable provisions of 150.0
The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with
§150.0(k)IC:
§130.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has
been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180
watts of low efficacy lighting er electrical box.
§150.0(k)ID:
Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz.
Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume no
§I50.0(k)1E:
more than 5 watts of power per luminaire or exhaust fan as determined in accordance with §I30.0(c). Night lights do not need to
be controlled by vacancy sensors.
§150.0(k)1F:
Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable
requirements of § 150.0
§150.0(k)2A:
High efficacy luminaires must be switched separately from low efficacy luminaires.
§ 150.0(k)2B:
Exhaust fans shall be switched separately from lighting systems.
§150.0(k)2C:
Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF.
§150.0(k)2D:
Controls and equipment are installed in accordance with manufacturer's instructions.
§I50.0(k)2E:
No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with §150.0(k).
§ 150.0(k)2F:
Lighting controls comply with applicable requirements of § 110.9.
An Energy Management Control System (EMCS) may be used to comply with dimmer requirements if: it functions as a dimmer
§I 50.0(k)2G:
according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements of § 130.5; and all other
requirements in i 150.0(k)2.
An Energy Management Control System (EMCS) may be used to comply with vacancy sensor requirements of § 150.0(k) if: it
§ 150.0(k)2H:
functions as a vacancy sensor according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements
of § 130.5• and all other requirements in § 150.0(k)2.
§ 150.0(k)2I:
A multiscene programmable controller may be used to comp:y with dimmer requirements of this section if it provides the
flinctionality of a dimmer according to § 110.9, and complies with all other applicable requirements in § 150.0 2.
§I50.0(k)3A:
A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only
§ 150.0(k)3B:
the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are
considered kitchen lighting if they are not separately switched from kitchen lighting.
§ 150.0(k)4:
Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated
cabinet.
§150.0(k)5:
A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom
shall be high efficacy or controlled by vacancy sensors.
§ 150.0(k)6:
Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§ 150.0(k)7:
Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high
efficacy,or shall be controlled by either dimmers or vacancy sensors.
Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other
nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0
CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing
§150.0(k)8:
and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and
allow ballast maintenance and replacement without requiring cutting holes in the ceiling.
For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with § 150.0(k), the ballasts
shall be certified to the Energy Commission to comply with the applicable requirements in § 110.9.
For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the
same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and
§I 50.0(k)9A:
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically
reactivates the motion sensor within 6 hours; and
iii. Controlled by one of the following methods:
2013 Low -Rise Residential Mandatory Measures Summary
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is
programmed to automatically tum the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of
an astronomical time clock in accordance with §110.9; meets the Installation Certification requirements in §130.4; meets the
requirements for an EMCS in § 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically tum the outdoor lighting OFF during daylight hours.
For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor
lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
§I50.0(k)9B:
following requirements:
i. Shall comply with § I50.0(k)9A; or
ii. Shall comply with the applicable requirements in § 110.9, § 130.0 § 130.2, § 130.4 § 140.7 and § 141.0.
§ 150.0(k)9C:
For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by § 150.0(k)9B or 150.0(k)9D
shall comply with the applicable requirements in 110.9 130.0 130.2 130.4 140.7 and § 141.0.
§150.0(k)9D:
Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply
with the applicable requirements in 110.9 130.0 130.2 130.4 140.7 and 141.0.
§1 50.0(k)10:
Internally illuminated address signs shall comply with § 140.8; or shall consume no more than 5 watts of power as determined
according to § 130.0(c).
§150.0(k)11:
Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for
nonresidential garages in 110.9 130.0, 130.1 130.4, 140.6, and 141.0.
In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of
§150.0(k)12A:
the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20
percent of the floor area, permanently installed lighting in that building shall:
§150.0(k)12B:
i. Comply with the applicable requirements in §110.9, §130.0, §130.1, §140.6 and §141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be ca-pable of turning the light fully On and Off from all designed paths of
ingress and ejEess.
Solar Ready Buildings:
Single family residences located in subdivisions with ten or more single family residences and where the application for a
§110.10(a)1:
tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January 1, 2014,
shall comply with the requirements of § 110.10 b through 110.10 e .
110.10(a)2:
Low-rise multi -family buildings shall comply with the requirements of § 110.10 through 110.10(d).
The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway, smoke
ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a
local jurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than
80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for
§110.10(b)1:
buildings with roof areas greater than 10,000 square feet.
For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less
than 250 square feet. For low-rise multi -family buildings the solar zone shall be located on the roof or overhang of the building or
on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the
building project and have a total area no less than 15 ercent of the total roof area of the building excluding any skylight area.
§110.10(b)2:
All sections of the solar zone located on steep -sloped roofs shall be oriented between 110 degrees and 270 degrees of true north.
§ 110.10(b)3A:
No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be
located in the solar zone.
Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice
§110.10(b)3B:
the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the
horizontal projection of the nearest point of the solar zone measured in the vertical plane.
§ 110.10(b)4:
For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly
indicated on the construction documents.
The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit
§ 110.10(c):
from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water -heating
system.
§110.10(d):
A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through § 110.10(c)
shall be provided to the occupant
§110.10(e)l:
The main electrical service panel shall have a minimum busbar rating of 200 amps.
The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a
§ 110.10(e)2:
future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or
main circuit location, and permanently marked as "For Future Solar Electric'.
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
MR. & MRS. GEORGE VELARDE
Date
6/30/201E
System Name
HVAC System - Zone 1 (4 On Mechanical)
Floor Area
712
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
I
CFM
Total Room Loads 416
Return Vented Lighting
Return Air Ducts
{
Return Fan
i
Ventilation o
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAI
Heating System
Sensible
Latent CFM
Sensib
Output perSystem 80,000
8,297
801 172
6,1
Total Output Btuh 80,000
0
Output Btuh/s ft 112.4
479
Cooling System
0
Output perSystem 1
0
0 0
Total Output Btuh 1
0
801
Total Output Tons 0.0
479
Total Output Btuh/s ft 0.0
Total Output s ft/Ton 8,544,000.0
9,255
7,:
Air S stem
CFM perSystem
0
HVAC EQUIPMENT SELECTION
Alr low cfm
0
High Efficiency Fau/AC
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
1 0 80,(
1 0 80,(
Aug 3 PM Jan 1
Airflow cfm/s ft 0.00
Airflow(cfm/Ton) 0.0
Outside Air % 0-0%
Outside Alr cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
67 OF
67 OF 105 OF
Heating Coil
104 OF
ROOM
68 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
76 / 63 °F
ed
76/63°F 55/54°F
II
Cooling Coil
(_ _
56 ! 54 OF
48.7% ROOM
75/ 62 OF
EnergyPro 6.7 by EnergySoft
User Number. 5732 RunCode: 2016-06.30709:53:31 ID: LQ040515-Rev06301 Page 23 of
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
I� -- U..w,.L..,.,..L,..,..,•
Project Name
MR. & MRS. GEORGE VELARDE
4P-
0 cfm
Date
6/30/201E
System Name
HVAC System - Zone 2 (3 On Mechanical)
Floor Area
992
ENGINEERING CHECKS
SYSTEM LOAD
105 °F
Number of Systems 1
COIL
, CFM
Total Room Loads 501
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Alr Ducts
TOTAL SYSTEM LOAD
COOLING
Senslble
10,499
0
606
0
0
0
606
1 11,711
PEAK COIL HTG.
PEAI
Heating System
Latent CFM
Sensib
Output perSystem 80,000
1,116 200
7,;
'Total Output Btuh 80,000
Output Btuhls ft 80.6
Cooling System
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
Output per System 47,000
0 0
112/78°F
Total Output Btuh 47,000
1,116
Total Output Tons 3.9
Total Output Btuhls ft 47.4
�,..
Total Output s ft/Ton 253.3
8,(
Air System
Outside Air
CFM perSystem 1,800
HVAC EQUIPMENT SELECTION
I._..
Airflow cfrn 1,800
York H4TSO48S06
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
31,428
1 31,428
8,203 80,(
8,203 80,(
Aug 3 PM Jan 1
Alrflow cfm/s ft 1.81
Airflow drn/Ton 459.6
Outside Air % 0-0%
Outside Alr cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
(Airstream Temperatures at Time of Heatina
Peak)
46.8%
26 OF 68 OF 105 OF 105 OF
Outside Air
I� -- U..w,.L..,.,..L,..,..,•
I......
4P-
0 cfm
Heating Coil Supply Fan
1,800 cfm
105 °F
Pit OQ -
68 OF
68°F
14
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F
75/62°F 55/54°F 55/54°F
�,..
I
Outside Air
I._..
. «.1....
0 cfm
Cooling Coil Supply Fan
55 154 of
1,800 cfm
46.8%
� R.�, OIYIi � f
75 / 62 OF
6.
Number. 5732 RunCode:
:31
ID: LQ040515-7 dev=01 Page 24 of
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
MR. & MRS. GEORGE VELARDE
Date
6/30/201E
System Name
HVAC System - Zone 3 (2 On Mechanical)
Floor Area
1,102
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
f CFM
Total Room Loads 1,041
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
Sensible
21,441
0
1,238
0
0
0
1,238
1 23,916
PEAK COIL HTG.
PEAI
Heating System
Latent CFM
Sensib
Output perSystem 80,000
1,240 360
14,1
Total Output Btuh 80,000
Output Btuh/s ft 72.6
1
Cooling System
Output perSystem 59,500
0 0
Total Output Btuh 59,500
1,240
Total Output Tons 5.0
E
Total Output Btuh/s ft 54.0
Total Output s ft/Ton 222.3
15.
Air System
CFM perSystem
1,800
HVAC EQUIPMENT SELECTION
Alrflow cfm
1,800
York H4TS060S06
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
42,278 7,987 80,(
42,278 7.987 80,(
Aug 3 PM Jan 1
Airflow cfm/s ft 1.63
Alrflow cfm/Ton 363.0
Outside Air % 0-0%
Outside Air cfmis ft 0.00
Note: values above alven at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF
Outside Air
0 cfm
68 OF
68 OF 105 OF 105 OF
Heating Coil Supply Fan
1,800 cfm
_ _ _
105 o F
ROOM
68 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling
Peak
112/78°F
Outside Air
0 cfm
76 / 62 °F;7,T
76/62°F 55/54°F 55/54°F
m
Cooling Coil Supply Fan
1,800 cfm
56-r54 T;
i
46.9% ROaOM
P �n T
EnergyPro 6.7 by EnergySoR
User Number. 5732 RunCode: 2016-06-30709:53:31
ID: LQ040515-F deYN301 Page 25 of
589
0
0
C
389
408
)00
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Date
MR. & MRS. GEORGE VELARDE
6/30/2016
System Name
Floor Area
HVAC System - Zone 4 (1 On Mechanical)
1,030
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING
CFM Sensible
Total Room Loads 595 12,421
Return Vented Lighting 0
Return Air Ducts 717
Return Fan 0
Ventilation 0 0
Supply Fan 0
Supply Air Ducts 717
TOTAL SYSTEM LOAD 1 13,855
PEAK COIL HTG.
PEAK
Heating System
Latent CFM
Sensible
Output perSystem 80,000
1,159 245
9,567
Total Output Btuh 80,000
Outut Stuh/s ft 77.7
470
Cooling System
0
Output perSystem 47,000
0 0
0
Total Output Btuh 47,000
1,159
0
Total Output Tons 3.9
470
Total Output Stuh/s ft 45.6
Total Output s ft/Ton 263.0
110,508
Air System
CFM perSystem
1,800
HVAC EQUIPMENT SELECTION
Airflow cirn
1,800
York H4TSO48S06 31,490
8,156
80,000
Airflow cfm/s ft
1.75
Total Adjusted System Output 31,490
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
8,156 80,000
Aug 3P ml Jan 1 AM
Airflow cfm/Ton 459.6
Outside Alr % 0.0 %
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Tem eratures at Time of Heating Peak
26 OF
68 OF 105 OF 105 OF
Outside Air
_�
0 cfm
Heating Coil Supply Fan
1,800 cfm
105 o F
ROOM
68 OF
68 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
112/78°F
75/62°F 55/54°F 55/54°F
•R— O
--« --I►
Outside Air
glfI1
0 cfm
Cooling Coil Supply Fan
55 / 54 OF
1,800 cfm
46.8%
..�. _
ROOM
75/62°F
75/62°F
EnergyPro 6.7 by EnergySoft
User Number. 5732. Run Code: 2016-06-30T09:53:31 ID: LQ040515-Rev06301 Page 26 of 27
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
MR. & MRS. GEORGE VELARDE
Date
6/30/201E
System Name
HVAC System - Zone 5 (5 On Mechanical)
Floor Area
806
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems 1
COIL COOLING PEAK COIL HTG.
I
CFM Sensible Latent CFM
Total Room Loads 482 10,095 907 201
Return Vented Lighting 0
Return Air Ducts 583
Return Fan 0
Ventilation 0 0 0 0
Supply Fan 0
Supply Air Ducts 583
1
TOTAL SYSTEM LOAD 1 11,2611 907
PEAI
Heating System
Sensib
Output per System 80,000
7,;
Total Output Btuh 80,000
Peak
Output Btuh/s ft 99.3
68 OF 105 OF 105 OF
Cooling System
No
Outside Air
Output per System 36,000
1� ..,
Total Output Btuh 36,000
Heating Coil Supply Fan
Total Output Tons 3.0
Total Output Btuh/s ft 44.7
105 ° F
Total Output (sgft/Ton) 1 268.7
8,t
CFM per System
1,800
HVAC EQUIPMENT SELECTION
Airflow(cfm)
1,800
York H4TS036S06
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
22,215 8,119 80,(
22,215 8,119 80,(
Aug 3 PM Jan 1
Airflow cfmis ft 2.23
Airflow cfm/Ton 600.0
Outside AJr1 00%
Outside Air cfmis ft 0.00
Note: values above -given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF
68 OF 105 OF 105 OF
No
Outside Air
. L..1..,..
1� ..,
0 cfm
Heating Coil Supply Fan
1,800 cfm
105 ° F
ROOM
68 °F_
68 OF
_ _II_
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling
Peak
112/78°F
75/62°F 55/54°F 55/54°F
54 (5-� --
I
Outside Air A 111
H
0 cfm
Cooling Coil Supply Fan
55 / 54 OF
1,800 cfm
46.7 % ROOM
75/62°F
75/62°F
8 0-
EnergyPro6.7 by EnergySoft
User Number. 5732 RunCode: 2016-06-30709:53:31
/D: LQ040515-Rev06301 Page 27 of 27