14-0353 (SFD) Revision 1 Title 24BUILDING -ENERGY ANALYSIS REPORT `
PROJECT: S
MR. & MRS. GEORGE V,ELARDE
53389 VIA BE'_LAGIO
La Quinta, Ca 92253
a
Project Designer:
OCHOA DESIGN ASSOCIATES
73626 Highway 111
Palm Desert! Ca 92260: b . too
(760)77 3 6605
Report Prepared by:
Santiago Lopes-Ocam ;CITY OF LA QUINT
Santiago Lopez-Ocam o BUILDING & SAFETY DEPT.
P.o. Box f 018 APPROVED
La'Quinta,'Ca 92247 FOR CONSTR CTION
760.485.8927
.WE
r
RECEIVED
Job Number:
LQ040515 MAY 14 2015 ;
�{Cffy OF VEDate: COMMUNITYDEOPMENT
4/5/2015
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report: This program has approval and is
authorized by the California Energy Commission for use with both the Re
sidential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by EnergySot. LLC — www.energysoft.com.
_ t,
Ener_g7t 6.5 by Ener_gySoft User Number: 5732 ID: LQ040515
1
TABLE OF CONTENTS
Cover Page 1
Table of Contents 2.
Form CF -1 R -PRF -01-E Certificate of Compliance 3
Form RMS -1 Residential Measures Summary 17
Form MF -1 R Mandatory Measures Summary 19
HVAC System Heating and Cooling Loads Summary 23
i
j
i
EnergyPro 6.5 by EnergySoft Job Number: ID: LQ040515 User Number: 5732
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE
Calculation Description: Title 24 Analysis
Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Input File Name: VELARDE - T24 040515.xm1
CF1 R -PRF -01
Page 1 of 14
GENERAL INFORMATION
01
Project Name VELARDE
Building Complies with Computer Performance .-•. r� 3 t
�"a `t�"T� ° f ``
02
Calculation Description Title 24 Analysis
02
This building incorporates features that require field testing and/or�verificatior-by certifiedHERS rater'unidei the supervision of a CECapproved HERS provider.
03
Project Location 53389 VIA BELLAGIO
' „Y *lu
04
City La Quinta
05
Standards Version Compliance 2015
06
Zip Code 92253
07
Compliance Manager Version BEMCmpMgr 2013-3c (710)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.5
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 45
12
Project Scope Newly Constructed
13
Number of Dwelling Units 1
14
Total Cond. Floor Area (FT2)4642
15
Number of Zones 5
16
Slab Area (FT 2) 4642
17
Number of Stories 1
18
Addition Cond. Floor Area N/A
19
Natural Gas Available Yes
20
Addition Slab Area (FT?) N/A
21
Glazing Percentage (%) 23.3%
COMPLIANCE RESULTS
01
Building Complies with Computer Performance .-•. r� 3 t
�"a `t�"T� ° f ``
02
This building incorporates features that require field testing and/or�verificatior-by certifiedHERS rater'unidei the supervision of a CECapproved HERS provider.
03
This building incorporates one or more Special`Feiturtes shown below w`P
' „Y *lu
ENERGY USE SUMMARY
04
05
06
07
08
Energy Use
(kTDV/ft2-yr)
Standard
Design
Proposed
Design
Compliance
Margin
Percent
Improvement
Space Heating
2.24
2.90
-0.66
-29.5%
Space Cooling
108.33
93.60
14.73
13.6%
IAQ Ventilation
1.60
1.60
0.00
0.0%
Water Heating
5.53
5.53
0.00
0.0%
Photovoltaic Offset
--
0.00
0.00
--
Compliance Energy Total
117.70
103.63
14.07
12.0%
J
Registration Number: 215-N0088215A-000000000-0000 Registration Date/Time: 2015-05-1116:42:27 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-02272015-710 Report Generated at: 2015-04-05 15:58:18
J
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE CFI R-PRF-01Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Page 2of14
Calculation Description: Title 24 Analysis Input File Name: VELARDE - T24 040515.xml
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Window overhangs and/or fins
HERS FEATURE SUMMARY
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
• IAQ mechanical ventilation
Cooling System Verifications:
• Minimum Airflow
• Verified EER
• Verified SEER
• Refrigerant Charge
• Fan Efficacy Watts/CFM
HVAC Distribution System Verifications:
• Duct Sealing
Domestic Hot Water System Verifications:
• -- None --
ENERGY DESIGN RATING
This is the sum of the annual TDV energy
TDV energy consumption for lighting and c
on-site renewable energy system.
Total Energy (kTDV/f2-yr)*
n fdr energy use components: included in the performE
not'regulated by Title 24, -Part 6�(such as dorn"tic'
�`- r -1 r- K: * mow.'
Reference Energy Use
155.43
• includes calculated Appliances and Miscellaneous Energy Use (AMEU)
BUILDING - FEATURES INFORMATION
01 02 03
Number of Dwelling
Project Name Conditioned Floor Area (ft2) Units
VELARDE 4642 1
04
compliance approach for -I
:es and consumerelectri
� R�M R pwr
argy Design Rating
.141.36
05
Number of Bedrooms I Number of Zones
15 5
Registration Number: 215-N0088215A-000000000-0000 Registration Date/Time: 2015-05-11 16:42:27
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CFIR-02272015-710
rd Design Building (Energy Budget) and the annual
accounting for the annual TDV energy offset by an
Margin
14.07
06
Number of Ventilation
Cooling Systems
0
Percent Improvement
9.1%
07
Number of Water
Heating Systems
1
HERS Provider: CaICERTS inc.
Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Calculation Description: Title 24 Analysis Input File Name: VELARDE - T24 040515.xml
CF1 R -PRF -01
Page 3of14
ZONE INFORMATION
01
02
03
04
05
06
07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ft2)
Avg. Ceiling
Height
Water Heating System 1
Water Heating System 2
Bed 2 - Work Out AREA
Conditioned
HVAC System - Zone 1 (4 01
712
11
DHW Sys 1
Master Bedroom
Conditioned
HVAC System - Zone 2 (3 02
992
11
DHW Sys 1
Great Room & Gallery
Conditioned
HVAC System - Zone 3 (2 03
1102
13
DHW Sys 1
Dining -Kitchen -Pantry -Lau
Conditioned
HVAC System - Zone 4 (1 04
1030
12
DHW Sys 1
Guest Bedrooms
Conditioned
HVAC System - Zone 5 (5 05
806
11
DHW Sys 1
1
r
�.`
HERS PROS
E
Registration Number: 215-NO088215A-000000000-0000 Registration Date/Time: 2015-05-1116:42:27 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-02272015-710 Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Calculation Description: Title 24 Analysis
Input File Name: VELARDE - T24 040515.xml
CF1 R -PRF -01
Page 4 of 14
OPAQUE SURFACES
01
02
03
04
05
06
07
08
Name
Zone
Construction
Azimuth
Orientation
Gross Area (ft2)
Window Area (W)
Tilt (deg)
Ri/NW
Bed 2 - Work Out AREA
R-21 Wall
315
Right
214.5
42
90
Re/SW
Bed 2 - Work Out AREA
R-21 Wall
225
Back
132
40
90
Le/SE
Bed 2 - Work Out AREA
R-21 Wall
135
Left
214.5
0
90
Fr/NE
Bed 2 - Work Out AREA
R-21 Wall
45
Front
379.5
0
90
Roof
Bed 2 - Work Out AREA
R-38 Roof Attic - w/Radia
178
Roof 2
Bed 2 - Work Out AREA
R-38 Roof Attic - w/Radia
178
Roof 3
Bed 2 - Work Out AREA
R-38 Roof Attic - w/Radia
178
Roof 4
Bed 2 - Work Out AREA
R-38 Roof Attic - w/Radia
178
Ri/NW 2
Master Bedroom
R-21 Wall
315
Right
665.5
54
90
Re/SW 2
Master Bedroom
R-21 Wall
225
Back
247.5
90
90
Le/SE 2
Master Bedroom
R-21 Wall
135
Left
16.5
0
90
Fr/NE 2
Master Bedroom —
R-21 Wall
45
Front
33
0
90
Roof 5
Master Bedroom f r
R-38 Roof Attic- w/Radia,'—^ /f
_
248
Roof 6
Master Bedroom y i
R-38 Roof Attic - w/Radia'
_
? '~ ' 1 `
248
Roof?
Master.Bedroom
�R-38RoofAttic -w/Radia'
z - / '
�� 248
Roof 8
Master Bedroom
R-38 Roof Attic - w/Radia�
? !`
' ,; "`,,
248
Ri/NW 3
Great Room & Gallery
R-21 Wall
315
Right
84.5
0
90
Re/SW 3
Great Room & Gallery
R-21 Wall
225
Back
340
225
90
Le/SE 3
Great Room & Gallery
R-21 Wall
135
Left
520
114.5
90
Fr/NE 3
Great Room & Gallery
R-21 Wall
45
Front
383.5
167
90
Roof 9
Great Room & Gallery
R-38 Roof Attic - w/Radia
275.5
Roof 10
Great Room & Gallery
R-38 Roof Attic - w/Radia
275.5
Roof 11
Great Room & Gallery
R-38 Roof Attic - w/Radia
275.5
Roof 12
Great Room & Gallery
R-38 Roof Attic - w/Radia
275.5
Ri/NW 4
Dining -Kitchen -Pantry -Lau
R-21 Wall
315
Right
416
59.5
90
Re/SW 4
Dining -Kitchen -Pantry -Lau
R-21 Wall
225
Back
216
100
90
Le/SE 4
Dining -Kitchen -Pantry -Lau
R-21 Wall
135
Left
722
46.5
90
Roof 13
Dining -Kitchen -Pantry -Lau
R-38 Roof Attic - w/Radia
257.5
Roof 14
Dining -Kitchen -Pantry -Lau
R-38 Roof Attic - w/Radia
257.5
Roof 15
Dining -Kitchen -Pantry -Lau
R-38 Roof Attic - w/Radia
257.5
Registration Number: 215-N0088215A-000000000-0000 Registration Date/Time: 2015-05-11 16:42:27 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-02272015-710 Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE
Calculation Description: Title 24 Analysis
Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Input File Name: VELARDE - T24 040515.xml
CF1 R -PRF -01
Page 5of14
Roof 16
Dining -Kitchen -Pantry -Lau
R-38 Roof Attic - w/Radia
03
04
257.5
06
07
Ri/NW 5
Guest Bedrooms
R-21 Wall
315
Right
452.8
82.5
90
Re/SW 5
Guest Bedrooms
R-21 Wall
225
Baric
22
0
90
Le/SE 5
Guest Bedrooms
R-21 Wall
135
Left
423
31.5
90
Le/S
Guest Bedrooms
R-21 Wall
180
- specify -
42.1
13.6
90
Fr/NE 4
Guest Bedrooms
R-21 Wall
45
Front
278.2
15.8
90
Roof 17
Guest Bedrooms
R-38 Roof Attic - w/Radia
3.5
201.5
0.85
Roof 18
Guest Bedrooms
R-38 Roof Attic - w/Radia
Ventilated
3.5
201.5
0.85
Yes
Roof 19
Guest Bedrooms
R-38 Roof Attic - w/Radia
201.5
Roof 20
Guest Bedrooms
R-38 Roof Attic - w/Radia
Ventilated
3.5
201.5
0.85
Yes
ATTIC
01
02
03
04
05
06
07
08
Name
Construction
Type
Roof Rise
Roof Reflectance
Roof Emittance
Radiant Barrier
Cool Roof
Attic Bed 2 - Work Out AREA
Attic RoofBed 2 - Work Out
AREA
„� Ventilated: -1
3.5 ;moi.€
0. I _ -
0.85
Yes
-
No
�o^ !' �»...�
."Y"�
- -
Attic Master Bedroom
Attic RoofMaster Bedroom
Venteed,E
# , —=i 3'Sj j '
`� 0.1, i !
- 0.85
Yes
No
AtticRoofGreatRoom&1,1�fAttic
"Ven
Yes
No
Great Room &Gallery
Galle ' �,
3.5
[r 0.1
0.85
AtticAttic
RoofDining-Kitchen-Pantry-
Ventilated
3.5
0.1
0.85
Yes
No
Dining -Kitchen -Pantry -Lau
Lau
Attic Guest Bedrooms
I Attic RoofGuest Bedrooms
Ventilated
3.5
0.1
0.85
Yes
No
Registration Number: 215-N0088215A-000000000-0000 Registration Date/Time: 2015-05-11 16:42:27 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-02272015-710 Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Calculation Description: Title 24 Analysis
Input File Name: VELARDE - T24 040515.xml
CF1 R -PRF -01
Page 6 of 14
WINDOWS
01
02
03
04 05
06
07
08
09
10
Name
Type
Surface (Orientation -Azimuth)
Width (ft) Height (ft)
Multipli
er
Area
(ft)
U -factor
SHGC
Exterior Shading
2046 Fix
Window
Ri/NW (Right -315)
--- -
1
9.0
0.26
0.21
Insect Screen (default)
6056 Casement
Window
Ri/NW (Right -315)
--- -
1
33.0
0.27
0.19
Insect Screen (default)
(2) 2680 FrDr
Window
Re/SW (Back -225)
-- -
1
40.0
0.27
0.17
Insect Screen (default)
4046 Casement
Window
Ri/NW 2 (Right -315)
--- -
1
18.0
0.27
0.19
Insect Screen (default)
1620 Fix
Window
Ri/NW 2 (Right -315)
- --
1
3.0
0.26
0.21
Insect Screen (default)
1620 Fix 2
Window
Ri/NW 2 (Right -315)
- --
1
3.0
0.26
0.21
Insect Screen (default)
1426 Fix
Window
Ri/NW 2 (Right -315)
--- ---
1
3.3
0.26
0.21
Insect Screen (default)
1626 Fix
Window
Ri/NW 2 (Right -315)
--- ---
1
3.8
0.26
0.21
Insect Screen (default)
1426 Fix 2
Window
Ri/NW 2 (Right -315)
-- --
1
3.3
0.26
0.21
Insect Screen (default)
1656 Fix
Window
Ri/NW 2 (Right -315)
- --
1
9.8
0.26
0.21
Insect Screen (default)
1656 Fix 2
Window
- Ri/NW 2 (Right -315)
-- ---
1
9.8
0.26
0.21
Insect Screen (default)
2080 Sidelite
Window
Re/SW 2 -(Back -225) - r^- - r-�t 2 Q- - 8.0 r
1
16.0 -
0.27 -
0.10
Insect Screen (default)
(2) 2680 FrDr 2
Window
r- Re/SW 2 (B6ck-225) r ° t ; "
�. 5.0 �., 8.0
; 1 a`t / r 40.0
0.27
0.17
Insect Screen (default)
Sidelite 2
Wndow
r
Re/SW 2 (Back -225)
8.0 t
`
12080
.
�16.Q
0.27
0.10
Insect Screen (default)2.0
9020 Transom
Window
Re/SW 2� Back -225) , y �^
-y 'R- f m "
+ 1
:?18.0
0.29
0.11
Insect Screen (default)
(3) 58100
Window
Re/SW 3 (Ba6k-225)
17.0 10.0
1
170.0
0.26
0.17
Insect Screen (default)
(2) 26110
Window
Re/SW 3 (Back -225)
---- ---
1
55.0
0.26
0.17
Insect Screen (default)
2650 Fix
Window
Le/SE 3 (Left -135)
-- ---
1
12.5
0.26
0.21
Insect Screen (default)
3066 Fix
Window
Le/SE 3 (Left -135)
--- --
1
19.5
0.26
0.21
Insect Screen (default)
(2) 3080 FrDr
Window
Le/SE 3 (Left -135)
-- --
1
48.0
0.27
0.17
Insect Screen (default)
6026 Transom
Window
Le/SE 3 (Left -135)
-- --
1
15.0
0.29
0.11
Insect Screen (default)
3066 Fix 2
Window
Le/SE 3 (Left -135)
-- --
1
19.5
0.26
0.21
Insect Screen (default)
5066 Fix
Window
Fr/NE 3 (Front -45)
-- - --
1
32.5
0.26
0.21
Insect Screen (default)
1620 Fix 3
Window
Fr/NE 3 (Front -45)
--- --
1
3.0
0.26
0.21
Insect Screen (default)
80120
Window
Fr/NE 3 (Front -45)
-- --
1
96.0
0.71
0.73
Insect Screen (default)
5066 Fix 2
Window
Fr/NE 3 (Front -45)
-- --
1
32.5
0.26
0.21
Insect Screen (default)
1620 Fix 4
Window
Fr/NE 3 (Front -45)
--- --
1
3.0
0.26
0.21
Insect Screen (default)
3066 Fix 3
Window
Ri/NW 4 (Right -315)
--- ---
1
19.5
0.26
0.21
Insect Screen (default)
(2) 40100
Window
Ri/NW 4 (Right -315)
--- --
1
40.0
0.26
0.17
Insect Screen (default)
Registration Number: 215-N0088215A-000000000-0000 Registration Date/Time: 2015-05-11 16:42:27 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-02272015-710 Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Calculation Description: Title 24 Analysis
Input File Name: VELARDE - T24 040515.xml
CF1 R -PRF -01
Page 7 of 14
(4) 26100
Window
Re/SW 4 (Back -225)
10.0 10.0 1
100.0
0.26
0.17
Insect Screen (default)
2650 Fix 2
Window
Le/SE 4 (Left -135)
-- --- 1
12.5
0.26
0.21
Insect Screen (default)
2650 Fix 3
Window
Le/SE 4 (Left -135)
--- -- 1
12.5
0.26
0.21
Insect Screen (default)
2020 Fix
Window
Le/SE 4 (Left -135)
--- --- 1
4.0
0.26
0.21
Insect Screen (default)
2020 Fix 2
Window
Le/SE 4 (Left -135)
-- --- 1
4.0
0.26
0.21
Insect Screen (default)
3046 Casement
Window
Le/SE 4 (Left -135)
--- --- 1
13.5
0.27
0.19
Insect Screen (default)
3066 Fix 4
Window
Ri/NW 5 (Right -315)
--- --- 1
19.5
0.26
0.21
Insect Screen (default)
(2) 3080 FrDr 2
Window
Ri/NW 5 (Right -315)
--- -- 1
48.0
0.27
0.17
Insect Screen (default)
6026 Transom 2
Window
Ri/NW 5 (Right -315)
-- - 1
15.0
0.29
0.11
Insect Screen (default)
5046 Casement
Window
Le/SE 5 (Left -135)
--- - 1
22.5
0.27
0.19
Insect Screen (default)
2046 Fix 2
Window
Le/SE 5 (Left -135)
- - 1
9.0
0.26
0.21
Insect Screen (default)
1646 Fix
Window
Le/S ( specify --180)
-- - 1
6.8
0.26
0.21
Insect Screen (default)
1646 Fix 2
Window
Le/S (- specify --180)
-- - 1
6.8
0.26
0.21
Insect Screen (default)
3646 Casement
Window
Fr/NE 4 (Front -45)
-- - 1
15.8
0.27
0.19
Insect Screen (default)
DOORS
-gyp-
Overhang Left Fin Right Fin
Window Depth
01-'02
Left
Extent
Right
Extent
03 04
�4�
Name +�� t
�: �' ✓ , �+,`
Side;of Building tom- r ;"j
Area (ft2) U -factor
3080 Dr '� `t,
f..,� 1:7,
"SFr/NE ` * ,
24.0 0.50
OVERHANGS AND FINS
01 02 03 04 05 06 07 08 09 10 11 12 13 14
Overhang Left Fin Right Fin
Window Depth
Dist Up
Left
Extent
Right
Extent
Flap Ht. Depth
Top Up
DistL
Bot Up Depth
Top Up
Dist R
Bot Up
2080 Sidelite 4
0.1
4
4
0 0
0
0
0 0
0
0
0
(2) 2680 FrDr 2 4
0.1
4
4
0 0
0
0
0 0
0
0
0
2080 Sidelite 2 4
0.1
4
4
0 0
0
0
0 0
0
0
0
(3) 58100 18.45
2
3
3
0 0
0
0
0 0
0
0
0
(4) 26100 15.45
2
4.58
4.58
0 0
0
0
0 0
0
0
0
Registration Number: 215-NO088215A-000000000-0000 Registration Date/Time: 2015-05-11 16:42:27 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-02272015-710 Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Calculation Description: Title 24 Analysis
Input File Name: VELARDE - T24 040515.xml
CF1 R -PRF -01
Page 8 of 14
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
07
02
03
04
05
Total Cavity
Winter Design
Name
Construction Name
Surface Type
Construction Type
Framing
R -value
U -value
Assembly Layers
Bed 2 - Work Out AREA
712
0.1
None
0.8
No
• Cavity/Frame: no insul. /2x4 Top Chrd
Attic RoofBed 2 - Work Out
992
0.1
2x4 Top Chord of Roof Truss @ 24
0.8.
No
Roof Deck: Wood Siding/sheathing/decking
AREA
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
Dining -Kitchen -Pantry -Lau
1030
0.1
None
0.8
No
• Inside Finish: Gypsum Board
Guest Bedrooms
806
0.1
None
0.8
No
• Cavity / Frame: R-21 / 2x6
• Exterior Finish: Wood
R-21 Wall
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
0.066
Siding/sheathing/decking
• Inside Finish: Gypsum Board
Ceilings (below
Cavity/ Frame: R-9.1 /2x4
R-38 Roof Attic - w/Radia
attic)
Wood Framed Ceiling
2x4 @ 24 in. O.C.
R 38
0.025
Over Floor Joists: R-28.9 insul.
• Cavity/Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic RoofMaster Bedroom
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
• Cavity/ Frame: no insul. / 2x4 Top Chrd
Attic RoofGreat Room &
_
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Gallery
Attic Roofs
Wood Framed Ceilingr
;l> :_ in' O.C.- -"
r none
0.644
Roofing: Light Roof (Asphalt Shingle)
Cavity/ Frame: no insul. / 2x4 Top Chrd
Attic
t�. _
2x4 Top Chord of Roof Truss@ 24
; ! I t # c
` _ , t
�
Roof Deck: Wood Siding/sheathing/decking
RoofDinin Kitchen -Pant Lau
Attic Roofs
-,Wood Framed Ceiling-'
^' `'--` s in. O.C. " � - �
' none
` 0.644'
Roofing: Light Roof (Asphalt Shingle)
1—i te—
i `
Z% '
>E ,
Cavity / Frame: no insul. / 2x4 Top Choi
2x4 Top Chord of Roof Truss @ 24
Roof Deck: Wood Siding/sheathing/decking
Attic RoofGuest Bedrooms
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
Roofing: Light Roof (Asphalt Shingle)
SLAB FLOORS
01
02
03
04
05
06
07
Name
Zone
Area (ft)
Perimeter (ft)
Edge Insul. R -value & Depth
Carpeted Fraction
Heated
Slab -on -Grade
Bed 2 - Work Out AREA
712
0.1
None
0.8
No
Slab -on -Grade 2
Master Bedroom
992
0.1
None
0.8.
No
Slab -on -Grade 3
Great Room & Gallery
1102
0.1
None
0.8
No
Slab -on -Grade 4
Dining -Kitchen -Pantry -Lau
1030
0.1
None
0.8
No
Slab -on -Grade 5
Guest Bedrooms
806
0.1
None
0.8
No
Registration Number: 215-NO088215A-000000000-0000 Registration Date/Time: 2015-05-11 16:42:27 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-02272015-710 Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1R-PRF-01
Project Name: VELARDE Calculation Date/Time: 15:54, Sun, Apr 05, 2015 Page 9 of 14
Calculation Description: Title 24 Analysis Input File Name: VELARDE - T24 040515.xml
III -DING ENVELOPE - HERS VERIFICATION
01 02 03 04
Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage ACH @ 50 Pa
Not Required Not Required Not Required —
WATER HEATING SYSTEMS
01
Name
DHW Sys 1 - 1/1
WATER HEATERS
01
Name
DHW Heater 1
02
03
04
05
06
System Type
Distribution Type
Water Heater
Number of Heaters
Solar Fraction (%)
DHW
Standard
DHW Heater 1
1
•0%
02
03
04
05
06
07
08
Tank Exterior
Tank Volume
Energy Factor or
Insulation
Standby Loss
Heater Element Type
Tank Type
(gal)
Efficiency
Input Rating
R -value
(Fraction)
Natural Gas
- —;Small Storage
50
0.6
40000-Btu/hr
0
0
WATER HEATING - HERS VERIFICATION Vk,
01 _ _ 03 _ _
Name Pipe Insulation Parallel Piping Compact Distribution Point -of Use
DHW Sys 1 - 1/1 — --' -- - -
Registration Number: 215-N0088215A-000000000-0000 Registration Date/Time: 2015-05-11 16:42:27
_ CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-02272015-710
06 07
Recirculation Central DHW
Control Distribution
HERS Provider: CaICERTS inc.
Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
06
Fan Name
Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Project Name: VELARDE
Air Distribution System 1
Input File Name: VELARDE - T24 040515.xml
Calculation Description: Title 24 Analysis
HVAC Fan 3
Air Distribution System 3
HVAC Fan 4
SPACE CONDITIONING SYSTEMS
HVAC Fan 5
Air Distribution System 5
01
02
03
04
SC Sys Name
System Type
Heating Unit Name
Cooling Unit Name
Cooling Component 1:Heating Component 1:Air
Other Heating and Cooling
Heating Component 1
Cooling Component 1
Distribution System 1:HVAC Fan 1:1
System
Cooling Component 2:Heating Component 2:Air
Other Heating and Cooling
Heating Component 2
Cooling Component 2
Distribution System 2:HVAC Fan 2:1
System
Cooling Component 3:Heating Component 3:Air
Other Heating and Cooling
Heating Component 3
Cooling Component 3
Distribution System 3:HVAC Fan 3:1
System
Cooling Component 4:Heating Component 4:Air
Other Heating and Cooling
Heating Component 4
Cooling Component 4
Distribution System 4:HVAC Fan 4:1
System
5:Heating Component 5:Air
Other Heating and Cooling
Heating Component 5
Cooling Component 5
rC-ooliingentCompon
Distribution System 5:HVAC Fan 5:1
System
HVAC - HEATING UNIT TYPES
•
02
- - - •Name -. - -
�. v
.
Heating Component 1
,� i' f rCntrlFurnace 'Fuef fired centPal furnace
Heating Component 2
'�C_ntrlFurnace ;Fuel-firedcentral `furnace
6
Heating Component 3
�,,��{
�t CntrlFurnaceY, Fuetfired central fumace^t
Heating Component 4
..�
CntrlFurnace - Fuel-fired' central furnace
Heating Component 5
CntrlFurnace - Fuel-fired central furnace
Registration Number: 215-NO088215A-000000000-0000 Registration Date/Time: 2015-05-11 16:42:27
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-02272015-710
CFI R -PRF -01
Page 10 of 14
05
06
Fan Name
Distribution Name
HVAC Fan 1
Air Distribution System 1
HVAC Fan 2
Air Distribution System 2
HVAC Fan 3
Air Distribution System 3
HVAC Fan 4
Air Distribution System 4
HVAC Fan 5
Air Distribution System 5
03
Efficiency
92 AFUE
80 AFUE
80 AFUE
80 AFUE
80 AFUE
HERS Provider: CaICERTS inc.
Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE
Calculation Description: Title 24 Analysis
Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Input File Name: VELARDE - T24 040515.xml
CF1 R -PRF -01
Page 11 of 14
HVAC - COOLING UNIT TYPES
01
02
03 04
05
06
07
01. _ .. _
py .. .. ;
Efficiency
Multi -speed
05
Name
System Type
EER SEER
Zonally Controlled
Compressor
HERS Verification
Cooling Component 1
SplitAirCond
12
14
Not Zonal
Single Speed
Cooling Component
1 -hers -cool
Cooling Component 2
SplitAirCond
14.5
14.6
Not Zonal
Single Speed
Cooling Component
1 -hers -cool
Cooling Component 3
SplitAirCond
14
15
Not Zonal
Single Speed
Cooling Component
1 -hers -cool
Cooling Component 4
SplitAirCond
14.5
14.6.
Not Zonal
Single Speed
Cooling Component
1 -hers -cool
Cooling Component 5
SplitAirCond
14.4
16
Not Zonal
Single Speed
Cooling Component
1 -hers -cool
HVAC COOLING - HERS VERIFICATION
01. _ .. _
py .. .. ;
- - - 03
_- 04 -
05
- 06
- - -- - - - -- - --
Name
- - -
Verified Airflow
- t ,
AirftowTar s
Target
t Z �• -_ -- - -
� Verified EER ,- f "?
✓�
-- - - - -
Verified SEER
--
- - Verified Refrigerant
Charge
Cooling Component 1 -hers -cool
%, Required. ,r ref j �, '`max 350.aRequired'
Not Required
Required
Cooling Component 2 -hers -cool
Required
350-�,"
Required
Required
Required
Cooling Component 3 -hers -cool
Required
350
- Required
Required
Required
Cooling Component 4 -hers -cool
Required
350
Required
Required
Required
Cooling Component 5 -hers -cool
Required
350
Required
Required
Required
Registration Number: 215-N0088215A-000000000-0000 Registration Date/Time: 2015-05-11 16:42:27 HERS Provider: CalCERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CFiR-02272015-710 Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE
Calculation Description: Title 24 Analysis
Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Input File Name: VELARDE - T24 040515.xml
CF1R-PRF-01
Page 12 of 14
HVAC - DISTRIBUTION SYSTEMS
01
02
03
04
05
06
07
Name
Type
Duct Leakage
Insulation R -value
Duct Location
Bypass Duct
HERS Verification
Air Distribution System 1
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
1 -hers -dist
Air Distribution System 2
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
2 -hers -dist
Air Distribution System 3
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
3 -hers -list
Air Distribution System 4
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
4 -hers -dist
Air Distribution System 5
DuctsAttic
Sealed and tested
8
Attic
None
Air Distribution System
5 -hers -dist
HVAC DISTRIBUTION - HERS VERIFICATION
01
02,
03
04
05
06
07
08
'Name
Duct Leakage
Verification.
w Duct Leakage
^"* Target (%)
Verified Duct
r7_Lccation�-, ,'
Verified Duct
);, `=Design r
Buried
Ducts
Deeply Buried
Ducts
Low -leakage
Air Handler
Air Distribution System 1 -hers -dist
Required. ri
.1i.0 ; i
l `Not Required
-Not Required S
^% r Not Required
Not Required
--
Air Distribution System 2 -hers -dist
Required k
HVAC Fan 4 -hers -fan
.''Not Required -
f; -Wt Required l
?. Not Required
Not Required
—
Air Distribution System 3 -hers -dist
Required ;E-6.0�
Not Required
Not Required)
- Not Required
Not Required
—
Air Distribution System 4 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
--
Air Distribution System 5 -hers -dist
Required
6.0
Not Required
Not Required
Not Required
Not Required
--
HVAC -FAN SYSTEMS
01
02
03
04
Name
Type
Fan Power (Watts/CFM)
HERS Verification
HVAC Fan 1
Single Speed PSC Furnace Fan
0.58
HVAC Fan 1 -hers -fan
HVAC Fan 2
Single Speed PSC Furnace Fan
0.58
HVAC Fan 2 -hers -fan
HVAC Fan 3
Single Speed PSC Furnace Fan
0.58
HVAC Fan 3 -hers -fan
HVAC Fan 4
Single Speed PSC Furnace Fan
0.58
HVAC Fan 4 -hers -fan
HVAC Fan 5
Single Speed PSC Furnace Fan
0.58
HVAC Fan 5 -hers -fan
HVAC FAN SYSTEMS - HERS VERIFICATION
01 02 03
Registration Number: 215-N0088215A-000000000-0000 Registration Date/Time: 2015-05,11 16:42:27 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-02272015-710 Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name:.VELARDE Calculation Date/Time: 15:54, Sun, Apr 05, 2015`
Calculation Description: Title 24 Analysis _ Input File Name: VELARDE - T24 040515.xml
CF1 R -PRF -01
Page 13 of 14
Name
Verified Fan Watt Draw
Required Fan Efficiency (Watts/CFM)
HVAC Fan 1 -hers -fan
Required
0.58
HVAC Fan 2 -hers -fan
Required
0.58
HVAC Fan 3 -hers -fan
Required
0.58
HVAC Fan 4 -hers -fan
Required
0.58
HVAC Fan 5 -hers -fan
-Required
0.58 .
IAQ (indoor Air Quality) FANS
01
02
03
04
05
06
- • Dwelling Unit
IAQ CFM
IAQ Watts/CFM
IAQ Fan Type
IAQ Recovery
Effectiveness(%)
HERS Verification
SFam IAQVentRpt
x166.42
0.25
Default •
0
Required
n,,
,. c
ERT.
E.
Registration Number: 215-N0088215A-000000000-0000 Registration Date/Time: 2015-05-11 16:42:27 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - MR -02272015-710 Report Generated at: 2015-04-05 15:58:18
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: VELARDE
Calculation Description: Title 24 Analysis
Calculation Date/Time: 15:54, Sun, Apr 05, 2015
Input File Name: VELARDE - T24 040515.xml
CF1 R -PRF -01
Page 14 of 14
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Santiago Lopez-Ocampo
Company:
Signature Date:
Santiago Lopez-Ocampo
2015-04-07 08:43:48
Address:
CEA/HERS Certification Identification (If applicable):
P.O. Box 1018
NA
City/State/Zip:
Phone:
La Quinta, CA 92247
760 485 8927
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations. '
3. •The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on,other applicable compliance documents,
worksheets, calculations, plans and specifications submitted tothe enforcement ;agency fo[ approval with this.building permit application.
Responsible Designer Name: _F 1
``•._
Responsible Designer Signature:;
Eduardo Escobar .
Company: t rr-^
Date,Signed:
2:2
Escobar Design
2015-G5-11 1 :
Address:
License:
43-927 Pacific Ave.
NA
City/State/Zip:
Phone:
Indio, CA 92201
760-289-9221
Digitally signed by Ca10ERTS. This digital signature is provided in order to secure the content of this registered document, and in no way implies Registration Provider responsibility for the accuracy of the
information.
Registration Number: 215-N0066215A-000000000-0000 Registration Date/Time: 2015-05-11 16:42:27 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF113-02272015-710 Report Generated at: 2015-04-05 15:58:18
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
MR. & MRS. GEORGE VELARDE
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
4/5/2015
Project Address
53389 VIA BELLAGIO La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
4,642
Addition
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity (ft)
Special Features
Status
Slab Unheated Slab -on -Grade
- no insulation 4,642
Perim = 0'
New
Wall Wood Framed
R 21 4,697
New
Demising Wood Framed
R19 2,938
New
Door Opaque Door
-
no insulation 24
New
Roof Wood Framed Attic
R38 4,642
New
FENESTRATION Total Area: 1.082 Glazing Percentage: 23.3 % New/Altered Average U -Factor:
Orientation Area(ft) U -Fac SHGC Overhang Sidefins Exterior Shades
0.30
Status
Right (NW) 84.0
0.260
0.21 none
none Bug Screen
New
Right (NW) 51.0
0.270
0.19 none
none Bug Screen
New
Rear (SW) 40.0
0.270
0.17 none
none Bug Screen
New
Rear (SW) 32.0
0.270
0.10 4.0
none Bug Screen
New
Rear (SW) 40.0
0.270
0.17 4.0
none Bug Screen
New
Rear (SW) 18.0
0.290
0.11 none
none Bug Screen
New
Rear (SW) 170.0
0.260
0.17 18.5
none Bug Screen
New
Rear (SW) 55.0
0.260
0.17 none
none Bug Screen
New
Left (SE) 93.5
0.260
0.21 none
none Bug Screen
New
Left (SE) 48.0
0.270
0.17 none
none Bug Screen
New
Left (SE) 15.0
0.290
0.11 none
none Bug Screen
New
Front (NE) 71.0
0.260
0.21 none
none Bug Screen
New
Front (NE) 96.0
0.710
0.73 none
none Bug Screen
New
Right (NW) 40.0
0.260
0.17 none
none Bug Screen
New
HVAC SYSTEMS
Qty. Heating
Min. Eff
Cooling
Min. Eff Thermostat
Status
1 Central Furnace
92% AFUE
Split Air Conditioner
14.0 SEER Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner
14.6 SEER Setback
New
1 Central Furnace
80% AFUE
Split Air Conditioner
15.0 SEER Setback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value
Status
HVAC System - Zone 1 (4 Ducted
Ducted Attic
8.0
New
HVAC System - Zone 2 (3 Ducted
Ducted Attic
8.0
New
HVAC System - Zone 3 (2 Ducted
Ducted Attic
8.0
New
WATER HEATING
Qty. Type
Gallons Min. Eff
Distribution
Status
Ener Pro 6.5 b Ener Soft User Number: 5732
RunCode: 2015-04-05716:19:23 /D: LQ040515
Pae 17 of 27
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
MR. & MRS. GEORGE VELARDE
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
4/5/2015
Project Address
53389 VIA BELLAGIO La Quinta
California Energy Climate Zone
CA Climate Zone V
Total Cond. Floor Area
4,642
Addition
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity (ft) Special Features
Status
FENESTRATION I Total Area: 1,082 Glazing Percentage: 23.3%1New/Altered Average U -Factor:
Orientation Area ft2 U -Fac SHGC Overhang Sidefins Exterior Shades
0.30
Status
Rear (SW 100.0 0.260
0.17 15.5 none Bug Screen
New
Left (SE) 36.0 0.270
0.19 none none Bug Screen
New
Right (NIA 48.0 0.270
0.17 none none Bug Screen
New
Right (NK9 15.0 0.290
0.11 none none Bug Screen
New
Left (S) 13.6 0.260
0.21 none none Bug Screen
New
Front (NE) 15.8 0.270
0.19 none none Bug Screen
New
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling Min. Eff Thermostat
Status
1 Central Furnace 80% AFUE
Split Air Conditioner 14.6 SEER Setback
New
1 Central Furnace 80% AFUE
Split Air Conditioner 16.0 SEER Setback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value
Status
HVAC System - Zone 4 (1 1 Ducted
Ducted Attic 8.0
New
HVAC System - Zone 5 (5 i Ducted
Ducted Attic 8.0
New
WATER HEATING
Qty. Type Gallons Min. Eff Distribution
Status
Ene Pro 6.5 by Ene Soft User Number: 5732
RunCode: 2015-0405716:19:23 /D: LQ040515
Pae 18 of 27
2013 Low -Rise Residential Mandatory Measures Summary
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the
compliance aporoach used. Exceptions may apply. Review the respective code section for more information.
Building Envelope Measures:
§I10.6(a)1:
Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§ 110.6(a)5:
Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of $10-111 a .
§110.7:
Exterior doors and windows are weatherstripped; all joints and penetrations are caulked and sealed.
§110.8(a):
Insulation specified or installed meets Standards for Insulating Material. Indicate type and include on the CF2R.
§ 110.8(i):
The thermal emittance and aged solar reflectance values of the cool roofing material meets the requirements of § 110.8(i) when the
installation of a cool roof is specified on the CFIR.
§ 110.80):
A radiant barrier shall have an emittance of 0.05 or less when the installation of a radiant barrier is specified on the CF1R.
Minimum R-30 insulation in wood -frame ceiling; or the weighted average U -factor shall not exceed 0.031. Minimum R-19 in a
§ 150.0(a):
rafter roof alteration. Attic access doors shall have permanently attached insulation using adhesive or mechanical fasteners. The
attic access shall be gasketed to prevent air leakage.
§150.0(b):
Loose till insulation shall conform with manufacturer's installed design labeled R -value.
§ 150.0(c):
Minimum R-13 insulation in 2x4 inch wood framing wall or have a U -factor of 0.102 or less (R-19 in 2x6 or 0.074 maximum U -
factor).
§150.0(d):
Minimum R- 19 insulation in raised wood -frame floor or 0.037 maximum U -factor.
In Climate Zones 14 and 16 a Class II vapor retarder shall be installed on the conditioned space side of all insulation in all exterior
§150.0(g)l:
walls, vented attics and unvented attics with air -permeable insulation.
In Climate Zones 1-16 with unvented crawl spaces the earth floor of the crawl space shall be covered with a Class I or Class 11
§150.0(g)2:
vapor retarder.
In a building having a controlled ventilation crawl space, a Class I or Class II vapor retarder shall be placed over the earth floor of
§150.0(g)3:
the crawl space to reduce moisture entry and protect insulation from condensation, as specified in the exception to Section
150.0(d).
§ 150.0(1):
Slab edge insulation shall: have a water absorption rate, for the insulation material alone without facings, no greater than 0.3%;
have water vapor permeance rate is no greater than 2.0 perm/inch, be protected from physical damage and UV light deterioration;
and when installed as part of a heated slab floor meets the requirements of § 110.8( .
150.0
§ (q)'
Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors shall have a maximum U-
factor of 0.58; or the weighted averse U -factor of all fenestration shall not exceed 0.58.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
§ 150.0(e)IA:
Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150.0(e)1B:
Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a readily accessible, operable, and tight -fitting damper or a combustion -air control device.
§150.0(e)1C:
Masonry or factory -built fireplaces have a flue damper with a readily accessible control.
§ 150.0(e)2:
Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside
of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110.0-§110.3:
HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified to the Energy Commission.
§ 110.3(c)5:
Water heating recirculation loops serving multiple dwelling units meet the air release valve, backflow prevention, pump isolation
valve, and recirculation loop connection requirements of §I10.3(c)5.
Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appli-
§110.5:
ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool
and spa heaters.
§ 150.0(h)1:
Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA using design conditions specified
in §150.0(h)2.
§ 150.0(h)3A:
Installed air conditioner and heat pump outdoor condensing units shall have a clearance of at least five feet from the outlet of any
dryer vent.
§I50.0(i):
Heating systems are equipped with thermostats that meet the setback requirements of §110.2(c).
§150.00)IA:
Storage gas water heaters with an energy factor equal to or less than the federal minimum standards shall be externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§150.00)1B:
Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, have R-12 external
insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the tank.
For domestic hot water system piping, whether buried or unburied: the first 5 feet of hot and cold water pipes from the storage
tank, all piping with a nominal diameter of 3/4 inch or larger, all piping associated with a domestic hot water recirculation system
§150.00)2A:
regardless of the pipe diameter, piping from the heating source to storage tank or between tanks, piping buried below grade, and
all hot water pipes from the heating source to kitchen fixtures must be insulated according to the requirements of TABLE 120.3-
A.
§ 150.00)2B:
All domestic hot water pipes that are buried below grade must be installed in a water proof and non -crushable casing or sleeve
that allows for installation, removal, and replacement of the enclosed pipe and insulation.
2013 Low -Rise Residential Mandato
§150.00)2C:
§ 150.00)3:
§ 150.00)3A:
§150.00)3B:
§ 150.0(n)1:
§I50.0(n)2:
§150.0(n)3:
Measures Summa
Pipe for cooling system lines shall be insulated as specified in
systems or hot waters stems with pressure > 15 psiQ shall me
150.00)2A. Piping insulation for steam and hydronic heating
the requirements in TABLE 120.3-A.
Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Insulation exposed to weather shall either be rated for outdoor use or installed with a cover suitable for outdoor service. For
example, protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation protected as specified or
_painted with coating that is water retardant and provides shielding from solar radiation that degrades the material
Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space shall have a Class I
or Class tI vapor retarding facing, or the insulation shall be installed at the thickness that qualifies as a Class I or Class 11 vapor
retarder.
Systems using gas or propane water heaters to serve individual dwelling units shall include: a 120V electrical receptacle within 3
feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the
space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the installed
water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000
Btu/hr.
Recirculating loops serving multiple dwelling units shall meetthe requirements of §110.3(c)5.
Solar water -heating systems and collectors shall be certified and rated by the Solar Rating and Certification Corporation (SRCC)
or by a testing agency approved by the Executive Director.
Ducts and Fans Measures:
All air -distribution system ducts and plenums installed are sealed and insulated to meet the requirements ofCMC §601.0, §602.0,on Standards Metal and Flexible 3rd Edition.
§603.0, §604.0, §605.0 and ANSI/SMACNA-006-2006 HVAC Duct Construction
Supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-6.0 (or higher if required by CMC
§605.0) or enclosed entirely in directly conditioned space as confirmed through field verification and diagnostic testing
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts are mechanically fastened. Openings shall be sealed
§150.0(m)]: with mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B or
aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings greater than %< inch, the
combination of mastic and either mesh or tape shall be used. Building cavities, support platforms for air handlers, and plenums
defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying
conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms
shall not be compressed to cause reductions in the cross-sectional area of the ducts.
Factory -Fabricated Duct Systems shall comply with specified requirements for duct construction, connections, and closures; joints
§ 150.0(m)2: and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is
used in combination with mastic and draw bands.
§150.0(m)3-6: Field -Fabricated Duct Systems shall comply with requirements for: pressure -sensitive tapes, 'mastics, sealants, and other
re uirements s ecified for duct construction; duct insulation R -value ratings; duct insulation thickness; and duct labeling.
§ 150.0(m)7: dampers. All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or automatic
§I50.0(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers
except combustion inlet and outlet air openings and elevator shaft vents.
Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not
§150.0(m)9: limited to the following: insulation exposed to weather shall be suitable for outdoor service. For example, protected by aluminum,
sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is
water retardant and rovides shielding from solar radiation.
§150.0(m)10: Flexible ducts cannot have porous inner cores.
When space conditioning systems use forced air duct systems to supply conditioned air to an occupiable space, the ducts shall be
§ 150.0(m)11: sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in accordance with Reference
Residential Appendix RA3.
Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal
§150.0(m)12: conditioning component, except evaporative coolers, shall be provided with air filter devices that meet the requirements of
§150.0(m)12.
Space conditioning systems that utilize forced air ducts to supply cooling to an occupiable space shall have a hole for the
placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the supply plenum. The
§ 150.0(m)13: space conditioning system must also demonstrate airflow> 350 CFM per ton of nominal cooling capacity through the return
grilles, and an air -handling unit fan efficacy:5 0.58 W/CFM as confirmed by field verification and diagnostic testing, in
accordance with Reference Residential Appendix RA3.
Zonally controlled central forced air cooling systems shall be capable of simultaneously delivering, in every zonal control mode,
§ 150.0(m)15: an airflow from the dwelling, through the air handler fan and delivered to the dwelling, of> 350 CFM per ton of nominal cooling
capacity, and operating at an air -handling unit fan efficacy of S 0.58 W/CFM as confirmed by field verification and diagnostic
testin , in accordance with Reference Residential Appendix RA3.
All dwelling units shall meet the requirements of ASHRAE Standard 62.2. Neither window operation nor continuous operation of
§150.0(o): central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of providing the
Whole Building Ventilation.
§ 150.0(o)IA: Whole Building Ventilation airflow shall be confirmed through field verification and diagnostic testing, in accordance with
Reference Residential Appendix RA3.
Pool and Spa Heating Systems and Equipment Measures:
Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
§ 110.4(a): Regulations; an on-off switch mounted outside of the heater that allows shutting off the heater without adjusting the thermostat
setting; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating.
2013 Low -Rise Residential Mandatory Measures Summary
§ 110.4(b) l:
Any pool or spa heating equipment shall be installed with at least 36 inches of pipe between filter and heater or dedicated suction
and return lines, or built-up connections for future solar heating.
§ 110.4(b)2:
Outdoor pools or spas that have a heat pump or gas heater shall have a cover.
§ 110.4(b)3:
Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or pro -
rammed to run only during off-peak electric demand periods.
§ 110.5:
Natural gas pool and spa heaters shall not have a continuous burning pilot light.
§150.0(p):
Residential pool systems or equipment shall meet specified pump sizing, flow rate, piping, filters, and valve requirements.
Lighting Measures:
§ 110.9:
All lighting control devices and systems, ballasts, and luminaires shall meet the applicable requirements of § 110.9.
§I50.0(k)IA:
Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with §150.0(k) in accordance with TABLE
150.0-A or TABLE 150.0-B, as applicable.
§I50.0(k)IB:
When a high efficacy and low efficacy lighting system are combined in a single luminaire, each system shall separately comply
with the applicable provisions of § 150.0(k).
The wattage and classification of permanently installed luminaires in residential kitchens shall be determined in accordance with
§ 150.0(k)1C:
§ 130.0(c). In residential kitchens, the wattage of electrical boxes finished with a blank cover or where no electrical equipment has
been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, shall be calculated as 180
watts of low efficacy lighting er electrical box.
§I50.0(k)ID:
Ballasts for fluorescent lamps rated 13 watts or greater shall be electronic and shall have an output frequency no less than 20 kHz.
Permanently installed night lights and night lights integral. to installed luminaires or exhaust fans shall be rated to consume no
§150.0(k)lE:
more than 5 watts of power per luminaire or exhaust fan as determined in accordance with §130.0(c). Night lights do not need to
be controlled by vacancy sensors.
§150.0(k)1F:
Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods) shall meet the applicable
requirements of § 150.0(k).
§ 150.0(k)2A:
High efficacy luminaires must be switched separately from low efficacy luminaires.
§I50.0(k)2B:
Exhaust fans shall be switched separately from lighting systems.
§ 150.0(k)2C:
Luminaires shall be switched with readily accessible controls that permit the luminaires to be manually switched ON and OFF.
§ I50.0(k)2D:
Controls and equipment are installed in accordance with manufacturer's instructions.
§ 150.0(k)2E:
No control shall bypass a dimmer or vacancy sensor function if the control is installed to comply with § I50.0(k).
§I50.0(k)2F:
Lighting controls comply with applicable requirements of §110.9.
An Energy Management Control System (FMCS) may be used to comply with dimmer requirements if: it functions as a dimmer
§ 150.0(k)2G:
according to § 110.9; meets Installation Certificate requirements of §130.4; the EMCS requirements of § 130.5; and all other
requirements in § 150.0(k)2.
An Energy Management Control System (EMCS) may be used to comply with vacancy sensor requirements of § I50.0(k) if: it
§ 150.0(k)2H:
functions as a vacancy sensor according to § 110.9; meets Installation Certificate requirements of § 130.4; the EMCS requirements
of §130.5; and all other requirements in §150.0(k)2.
§150.0(k)21:
A multiscene programmable controller may be used to comply with dimmer requirements of this section if it provides the
functionality of a dimmer according to §110.9, and complies with all other applicable requirements in §150.0(k)2.
§ 150.0(k)3A:
A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
Kitchen lighting includes all permanently installed lighting in the kitchen except internal lighting in cabinets that illuminate only
§ 150.0(k)3B:
the inside of the cabinets. Lighting in areas adjacent to the kitchen, including but not limited to dining and nook areas, are
considered kitchen I ighting if they are not separately switched from kitchen Ii htin .
§I50.0(k)4:
Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of illuminated
cabinet.
§ 150.0(k)5:
A minimum of one high efficacy luminaire shall be installed in each bathroom; and all other lighting installed in each bathroom
shall be high efficacy or controlled by vacancy sensors.
§ I50.0(k)6:
Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§ 150.0(k)7:
Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be high
efficacy, or shall be controlled by either dimmers or vacancy sensors.
Luminaires recessed into ceilings shall: be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other
nationally recognized testing/rating laboratory; have a label that certifies that the luminaire is airtight with air leakage less than 2.0
CFM at 75 Pascals when tested in accordance with ASTM E283; be sealed with a gasket or caulk between the luminaire housing
§150.0(k)8:
and ceiling, and shall have all air leak paths between conditioned and unconditioned spaces sealed with a gasket or caulk; and
allow ballast maintenance and replacement without requiring cutting holes in the ceiling.
For recessed compact fluorescent luminaries with ballasts to qualify as high efficacy for compliance with §150.0(k), the ballasts
shall be certified to the Energy Commission to comply with the applicable requirements in § 110.9.
For single-family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on the
same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of Items ii or iii below; and
§ I50.0(k)9A:
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and automatically
reactivates the motion sensor within 6 hours; and
iii. Controlled by one of the following methods:
2013 Low -Rise Residential Mandatory Measures Summary
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and which is
programmed to automatically turn the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements: At a minimum provides the functionality of
an astronomical time clock in accordance with §110.9; meets the Installation Certification requirements in §130.4; meets the
requirements for an EMCS in § 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically turn the outdoor lighting OFF during daylight hours.
For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and outdoor
lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
§150.0(k)9B:
following requirements:
i. Shall comply with § I50.0(k)9A; or
ii. Shall comply with the applicable requirements in §110.9, §130.0, §130.2, §130.4, §140.7 and §141.0.
§150.0(k)9C:
For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by §I50.0(k)9B or 150.0(k)9D
shall comply with the applicable requirements in § 110.9, §130.0, §130.2, § 130.4, §140.7 and § 141.0.
§ 150.0(k)9D:
Outdoor lighting for residential parking lots and residential carports with a total of eight or more vehicles per site shall comply
'
with the applicable requirements in § 110.9, 130.0, § 130.2, § 130.4, § 140.7 and § 141.0.
§150.0(k)10:
Internally illuminated address signs shall comply with §140.8; or shall consume no more than 5 watts of power as determined
according to §130.0(c).
§150.0(k)11:
Lighting for residential parking garages for eight or more vehicles shall comply with the applicable requirements for
nonresidential garages in § 110.9, § 130.0, § 130. 1, § 130.4, § 140.6, and § 141.0.
In a low-rise multifamily residential building where the total interior common area in a single building equals 20 percent or less of
§I50.0(k)12A:
the floor area, permanently installed lighting for the interior common areas in that building shall be high efficacy luminaires or
controlled by an occupant sensor.
In a low-rise multifamily residential building where the total interior common area in a single building equals more than 20
percent of the floor area, permanently installed lighting in that building shall:
§ 150.0(k)12B:
i. Comply with the applicable requirements in § 110.9, § 130.0, § 130. 1, § 140.6 and § 141.0; and
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that reduce the lighting power in each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and Off from all designed paths of
ingress and egress.
Solar Ready Buildings:
Single family residences located in subdivisions with ten or more single family residences and where the application for a
§1 10.10(a) 1:
tentative subdivision map for the residences has been deemed complete, by the enforcement agency, on or after January 1, 2014,
shall comply with the requirements of §1 10.10 b through 110.10 e .
§ 110.10(a)2:
Low-rise multi -family buildings shall comply with the requirements of § 110.10(b) through § 110.10(d).
The solar zone shall have a minimum total area as described below. The solar zone shall comply with access, pathway, smoke
ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a
local jurisdiction. The solar zone total area shall be comprised of areas that have no dimension less than 5 feet and are no less than
80 square feet each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for
§ 110.10(b)1:
buildings with roof areas greater than 10,000 square feet.
For single family residences the solar zone shall be located on the roof or overhang of the building and have a total area no less
than 250 square feet. For low-rise multi -family buildings the solar zone shall be located on the roof or overhang of the building or
on the roof or overhang of another structure located within 250 feet of the building or on covered parking installed with the
building project and have a total area no less than 15 percent of the total roof area of the building excluding any skylight area.
§ 110.10(b)2:
All sections of the solar zone located on steep -sloped roofs shall be oriented between 110 degrees and 270 degrees of true north.
§I 10.10(b)3A:
No obstructions, including but not limited to, vents, chimneys, architectural features, and roof mounted equipment, shall be
located in the solar zone.
Any obstruction, located on the roof or any other part of the building that projects above a solar zone shall be located at least twice
§ 110.10(b)3B:
the distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the
horizontal projection of the nearest point of the solar zone, measured in the vertical plane.
§110.10(b)4:
For areas of the roof designated as solar zone, the structural design loads for roof dead load and roof live load shall be clearly
indicated on the construction documents.
The construction documents shall indicate: a location for inverters and metering equipment and a pathway for routing of conduit
§ 110.10(c):
from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); a pathway for routing of plumbing from the solar zone to the water -heating
system.
§ 110.1 Old):
A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through § 110.10(c)
shall be provided to the occupant.
§1 10.10(e)l:
The main electrical service panel shall have a minimum busbar rating of 200 amps.
The main electrical service panel shall have a reserved space to allow for the installation of a double pole circuit breaker for a
§ 110.10(e)2:
future solar electric installation. The reserved space shall be: positioned at the opposite (load) end from the input feeder location or
main circuit location, and permanently marked as "For Future Solar Electric".
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
MR. & MRS. GEORGE VELARDE
System Name
HVAC System - Zone 1 (4 On Mechanical)
ENGINEERING CHECKS SYSTEM LOAD
Number of Systems
Heating System
output per System
Total Output (Btuh
Output Btuh/s ft
Cooling System
Output per System
Total Output Btuh
Total Output (Tons)
Total Output Btuh/s
Tntal nutnut fsnft/Tn
Air System
CFM per S ste
Airflow cfm
Airflow cfm/sc
Airflow cfm/Tc
Outside Air %a
Outside Air cfi
Note: values above
1
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
80,000
80,000
112.4
1
1
0.0
ft 0.0
n 8,544,000.0
0 cfm
0
HVAC EQUIPMENT SELECTION
0
High Efficiency Fau/AC
0.00
0.0
67 OF
0-0%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
I 0.00
at ARI conditions I
rCHROMETRICS
(Airstream Temperatures at Time
112/78°F
Date
4/5/2015
Floor Area
712
COIL COOLING PEAK COIL HTG. PEAK
CFM Sensible Latent CFM Sensible
377 7,566 942 161 6,191
0
437 304
0 0
0 0 0 0 0
0 0
437 304
8,440. 942 6,800
1
80,0001
11 01 1 80,000
Aug 3 PM Jan 1 AM
26 OF
67 OF 105 OF
Outside Air
0 cfm
Heating Coil
104 OF
ROOM
67 OF
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
76/63°F 55/54°F
HE
Outside Air
ffll
0 cfm
Cooling Coil
56 / 54 OF
49.2%
ROOM In
76/ 63 °F
No- -
_
4 - I I
75 / 62 OF
EnergyPro 6.5 by EnergySoft
User Number- 5732 RunCode: 2015-04-05716:19:23 ID: LQ040515
Page 23 of 27
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
MR. & MRS. GEORGE VELARDE
Date
4/5/2015
System Name
HVAC System - Zone 2 (3 On Mechanical)
Floor Area
992
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 452
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 80,000
9,481
1,313 186
7,269
Total Output Btuh 80,000
0
Output Btuh/s ft 80.6
547
357
Cooling System
01
0
Output per System 47,000
0
0 0
0
Total Output Btuh 47,000
0
547
10,575 1,313
11
0
Total Output (Tons) 3.9
357
Total Output Btuh/s ft 47.4
Total Output s ft/Ton 253.3
7,984
Air System
CFM per System
1,800
HVAC EQUIPMENT SELECTION
Airflow cfm
1,800
York H4TSO48S06
31,329 8,322
80,000
Airflow (cfm/s ft) 1.81
Airflow cfm/Ton
459.6
Outside Air %
0.0 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
31,329 8,322
F7 Aug 3 PM
80,000
Jan 1 AM
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF
Outside Air
0 cfm
68 OF
68 OF 105 OF 105 OF
u �
Heating Coil Supply Fan
1,800 cfm
105 OF
ROOM
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
75 / 62 OF
75/62°F 55/54°F 55/54°F
Cooling Coil Supply Fan
1,800 cfm
55 / 54 OF
47.0% ROOM
75 / 62 OF
I
EnergyPro 6.5 by EnergySoft
User Number.- 5732 RunCode: 2015-04-05T16:19:23
/D: LQ040515 Page 24 of 27
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
MR. & MRS. GEORGE VELARDE
Date
4/5/2015
System Name
HVAC System - Zone 3 (2 On Mechanical)
Floor Area
1,102
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 984
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 80,000
20,310
1,458 343
13,391
Total Output Btuh 80,000
0
Output Btuh/s ft 72.6
1,172
658
Cooling System
0
0
Output per System 59,500
0
0 0
0
Total Output Btuh 59,500
0
1,458
0
Total Output Tons 5.0
1,172
658
Total Output Btuh/s ft 54.0
Total Output s ft/Ton 222.3
1 22,655
14,708
Air System
CFM per System
1,800
HVAC EQUIPMENT SELECTION
Airflow cfm
1,800
York H4TS060S06
42,154 8,138
80,000
Airflow (cfm/s ft)
1.63
Airflow cfm/Ton
363.0
Outside Air %
0.0%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
42,154 8,138
Aug 3 PM
80,000
Jan 1 AM
Outside Air ctm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF
Outside Air
0 cfm
680F
680F 105 OF ' 10'5 OF
i^
(nom
Heating Coil Supply Fan
1,80+0 cfm
°
105 F
ROOM
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78°F
Outside Air
0 cfm
76 / 62 OF
76/62°F 55/54°F 55/54°F
c e
Cooling Coil Supply Fan
1,800 cfm
'
56 / 54 OF
47.0 % ROOM
75 / 62 °F
EnergyPro 6.5 by EnergySoft
User Number: 5732 RunCode: 2015-0405716:19:23
ID: LQ040515 Page 25 of 27
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
MR. & MRS. GEORGE VELARDE
Date
4/5/2015
System Name
HVAC System - Zone 4 (1 On Mechanical)
Floor Area
1,030
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 543
Return Vented Lighting
Return Air Ducts
Return Fan
VentilF-tion 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 80,000
11,364
1,363 229
8,971
Total Output Btuh) 80,000
0
Output Btuh/s ft 77.7
656
441
Cooling System
01
0
Output per System 47,000
0
0 0
0
Total Output Btuh 47,000
0
1,363
0
Total Output Tons 3.9
656
441
Total Output Btuh/s ft 45.6
Total Output s ft/Ton 263.0
1 12,676
9,853
Air System
CFM per System
1,800
HVAC EQUIPMENT SELECTION
Airflow cfm
1,800
York H4TSO48S06
31,387 8,280
80,000
Airflow (cfm/s ft) 1.75
Airflow cfm/Ton
459.6
80,000
F Jan 1 AM
Outside Air % 0.0%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
1 TIME OF SYSTEM PEAK
31,387 8,280
Aug 3P ml
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF
Outside Air
0 cfm
68 OF
68 OF 105 °F 105 OF
I�
Heating Coil Suppily Fan
1,800 cfm
I
105 OF
ROOM
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Ti,-ne of Cooling Peak
112/78°F
Outside Air
0 cfm
75/62°F
75/62°F 55/54°F 55/54°F
Cooling Coil Supply Fan
1,800 cfm
i
55 154 OF
47.0% j ROOM
j 75/62°F
EnergyPro 6.5 by EnergySoft
User Number. 5732 RunCode: 2015-04-C5T16:19:23
ID: LQ040515 Page 26 of 27
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
MR. & MRS. GEORGE VELARDE
Date
4/5/2015
System Name
HVAC System - Zone 5 (5 On Mechanical)
Floor Area
806
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Lads 442
Return Vented Lighting
Return Air Cucts
Returr Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output per System 80,000
9,268
1,067 189
7,388
Total Output (Btuh) 80,000
0
Output Btuh/s ft 99.3
535
363
Cooling S stem
0
0
Output per System 36,000
0
0 0
0
Total Output Btuh 36,000
0
535
1 10,3387 1,067
0
Total Output (Tons) 3.0
363
Total Output Btuh/s ft 44.7
Total Output s ft/Ton 268.7
8,114
Air System
CFM per System
1,800
HVAC EQUIPMENT SELECTION
Airflow cfm
1,800
York H4TS036S06 '
22,143 8,203
80,000
Airflow (cfm/s ft)
2.23
Airflow cfm/Ton 600.0
i
Outside Air %
0.0%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
22,143 8,203
Aug 3P m
80,000
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
260F
Outside Air
0 cfm
680F
680F 105 OF 105 OF
Heating Coil SupFly Fan
1,800 cfm
105 o F
ROOM
68 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Ti'rne of Cooling Peak
112/78°F
Outside Air
0 cfm
75/62°F75/62°F
75/62°F 55/54°F 55/54°F
Cooling Coil Supply Fan
1,800 cfm
_
55 154 OF
46.8% j ROOM
I
EnergyPro 6.5 by EnergySoft
User Number. 5732 RunCode: 2015-04-r5T16:19:23
ID: LQ040515 Page 27 of 27