BRES2015-0085 Geotechnical UpdateSladden-Engineering
f
45090 Golf Center;Parkway, Suite F, Indio, CA 92201 (760) 863-M3 Fax (760) 863-0847
082 Stanton Avenue, Suite A, Buena Park, CA;90621 (714) 523-0952 Fax (714) 523-1369
450 Egan Avenue, Beaumont, CA 92223(951) 845-7743 Fax (951) 845-8863
800 E; Florida Avenu', Hemet, CA 92543[(951)766-8777 Fax (951) 766,-8778
February 27, 2015
Project No. 54-150574
15-02-095
Goodno Construction, Inc.=
35721 Linda Rosea goad
Temecula, California 92592.
Project: Proposed TomeiRe.sidence
Via Mallorca - Lot 48C
The Hideaway
La Quinta, California.
Subject: Geotechnical Update
Ref: Geotechnical Engineering Report prepared by Earth Systems Southwest' (ESSW) dated
September 22, 2000;'File, No. 07117-10, Report No. 00-09-772
Report of Testing and Observation During Rough Grading prepared by ESSW dated
August 28,2002; File No. 07117-11, Report No. 01-07-718
Report of Testing and Observation During Rough Grading preparedby Sladden
Engineering dated October 12, 2003; Project No. 544-2199 Report No. 03-10-647
As requested, we have reviewed the above referenced - geotechnical reports as they relate to the
design ' and construction of the proposed custom residence. The project site identified as Lot 48C
is located along Via Mallorca within the Hideaway Golf Club development in the City of La
Quinta, California. It is but understanding that the proposedresidencewill be a relatively
lightweight wood -frame structure supported by conventional shallow spread footings and
concrete slabs on grade...
The 'subject lot was previously graded during the rough grading of the Hideaway project site and
was subsequently regraded. The rough grading included over -excavation of the native surface
soil along with the placementof engineered fill soil to construct the building pads. The regrading
included processing the surface soil along with minor cuts and fills to construct the individual
building pads to the current configurations. Some additional over -excavation was performed in
areas where the building envelopes, were reconfigured. The most recent site grading is
summarized in the referenced Report of Testing and Observations During Rough Grading
prepared by Sladden Engineering along,with the compaction test
t result&
The referenced reports include recommendations pertaining to the construction of residential
structure foundations. Based upon our review of the referenced reports, it is our opinion that the
structural values included in'j;
the referenced grading ,report prepared by Sladden Engineering
remain applicable for ,the design and construction, of the proposed residential structure
foundations.
I Sladden. Engineering
Z
February 27, 2015- -2- Project No. 544-15057
15-02-095
-,Because the lot has been previously rough graded, the remedial grading required at this time
should be minimal provided that the building falls within the previously established building
envelope. The building area should be cleared of surface vegetation, scarified and moisture
conditioned prior to precise grading: The exposed surface should be compacted to a minimum of
90 percent relative compaction is attained prior to fill placement. Any fill material should be
placed in thin lifts at near optimum moisture content and compacted to at least 90 percent
relative compaction.
The allowable bearing pressures recommended in the referenced grading report prepared by
Sladden Engineering remain applicable. Conventional shallow spread footings should be
bottomed into properly compacted fill material a minimum of 12 inches below lowest adjacent
grade. Continuous footings should be at least 12 inches wide and isolated pad footings should be
at least 2 feet wide. Continuous footings and isolated pad footings should be designed utilizing
allowable bearing pressures of 1500 psf and 2000 psf, respectively.. Allowable increases of 300 psf
for each additional 1 foot of width and 300 psf for each additional 6 inches of depth may be
utilized if desired. The maximum allowable bearing pressure should be 3000 psf. The
recommended allowable bearing pressures may- be increased by one-third for wind and seismic
loading.
Lateral forces may be resisted by friction along the base of the foundations/slabs and passive
resistance along the sides of the footings. A friction coefficient of 0.50 times the normal dead load
forces is recommended for use in ' design. Passiveresistance may be estimated using an
equivalent fluid weight of 300 pcf. If used in combination with the .passive resistance, the
frictional resistance should be, reduced by one third to 033 times the normal dead load forces.
The bearing soil is non -expansive and falls within ' the "very low'.' expansion category in
accordance with 2013 California Building Code (CBC) classification 'criteria. Slab thickness and
reinforcement should be determined by the structural engineer. We recommend a minimum
floor slab thickness of 4.0 inches and minimum reinforcement of #3 bars at 24 inches on center in
both directions. All slab reinforcement should be supported on concrete chairs to ensure that
reinforcement is placed at slab mid -.height.
Slabs with moisture sensitive surfaces should be underlain with a moisture vapor retarder
consisting of a polyvinyl chloride membrane such as .10 -mil Visqueen, or.equivalent. All laps
within the membrane should be sealed' and at least 2 inches of clean sand should be placed over
the membrane to promote uniform curing of the concrete. To reduce the potential for punctures,
the membrane should be placed. on a pad surface that has been graded smooth without any sharp
protrusions. If a smooth surface can not be achieved by grading, consideration should be given to
placing a 1 -inch thick leveling course of sand across the pad surface prior to placement of the
membrane.
Based on our field observations and understanding of local geologic conditions, the soil profile
type judged applicable to this site is SD, generally described as stiff soil. The following presents
additional coefficients and factors: relevant to seismic mitigation for new construction based upon
the 2013 California Building Code (CBC).
k.;
Sladden Engineering
February 27, 2015' =3- Project No. 544-15057 .
15-02-095
The seismic design category for a structure may be determined in accordance with Section 1613
of the 2013 CBC or ASCE7. According to the 2013 CBC, Site Class D may be used to estimate :
design seismic loading for the proposed structures. The 2013 CBC Seismic Design Parameters are
summarized below. -
Risk Category (Table 1.5-1): I/II/III
Site Class (Table 1613.3.2): D r
Ss (Figure 1613.3.1):1.500g `
S1 (Figure 1613.3.1): 0:6848
Fa (Table 1613.3.3(1)):1:0
Fv (Table 1613.5.3(2)): 1.5 f
Sms (Equation 16-37 (Fa X Ss)): 1.5008
Sm1 (Equation 16-38 (Fv X S1)):1.026g
SDs (Equation 16-39(2/3 X Sms)):.1.000g
SDI (Equation 16-40 (2/3 X'Sm1)): 0.6848
Seismic Design Category: D
If you have questions regarding this letter or the referenced reports, please contact the
undersigned.
Respectfully submitted,
SLADDEN ENGINEERING
A '
Brett L. And on
ANGEIESOGZ� w .
Principal Engineer
No. C4,,53 , ;,b3 ,
ur Exp. 9/30116
' UVII_
SE gvm * ENGINl:EkING
. CFCA�i�,%�
Copies: 4; / Addressee
i Sladden Engineering
5Nyr i5o57
LA QUINTA
Please verify that soils reports contain all of the above information. In addition, to assure
continuity between*the investigation/reporting stage and the execution stage, please use
the following checklist to verify that the conclusions and recommendations in the report
cover all the required -elements. Only then. can we be assured that the construction
documents address all of the site soil conditions.
-La Quinta Geotechnical Report Checklist
Does the "Conclusions and Recommendations" section of the report address each of the
following criteria?
"Address" means:
(a) the Criterion is considered significant and mitigation measure(s) noted, or;
(b) the criterion is considered insignificant and explicitly.so stated.
fifes No Criterion
M
®
----- -._............ ..... . .._... _....._ ..._........._ .................. - ....... .
Foundation criteria to mitigate the effects of expansive soils.
®
Foundation criteria based upon bearing capacity. -of natural or --compacted soil.
®
Foundation criteria to mitigate the effects of liquefaction.
®
Foundation criteria to mitigate the effects of seismically induced differential
settlement.
®
Foundation criteria to mitigate the effects of long -terra differential settlement.
®
Foundation criteria to mitigate the.effects.of.varyng soli strength. .
®
Foundation criteria to mitigate expected total and differential settlement.
Any "Ito"
answers to the above checklist should be noted as specific tre ulred
corrections.
�oPuoFESS�Q�<
# # # BRCTT I
`'• ANQFS�ly
(Ds N 5q�s 2
CIV!L
a\ GuNEER1Al;, it
M
,a G
r Sladden Engineering 10�
EIVED'
_W. 15090 Golf Center Parkway, Suite F, Indio, CA 92201 (760) 863-0713 Fax (76tT1853
6792 Stanton Avenue, Suite A, Buena Park; CA 90621 (714) 523-0952 Fax (714) 523=1369
450 Egan Avenue, Beaumont, CA 92223 (951) 845-7743 Fax (951) 845.8863 JUN 2 2015
800 E. Florida Avenue, Hemel, CA 92543 (951) 766-8777 Fax (951) 766-8778
- r CITY OF LA QUINTA
February 27, 2015 ( "ft"08 %ELOPMENT
15-02-095
Goodno Construction, Inc:
35721. Linda Rosea .Road -
Temecula, California 92592
RECEIVED
Project: Proposed Tomei Residence
Via Mallorca - i..ot 48C MAY 0 6 2015
The Hideaway
La Quinta, California `.17Y OF
LA QUINTA
COMMUNITY DEVELOPMENT
Subject: Geotechnical Update NT
Ref: Geotechnical Engineering Report prepared by Earth Systems Southwest (ESSW) dated
+' September. 22, 2000; File No. 07117-1.0, Report No. 00-09-772 `
Report of 'Testing and Observation During Rough Grading prepared by ESSW dated
August 28, 2002; File No. 07117-1.1, Report No. 01-07-718
Report of Testing and Observation During Rough Grading prepared by Sladden
Engineering dated October 12, 2003; Project No. 544-2199 Repor No. 03-10-647'
As requested, we have reviewed the above referenced geotechnical reports as they relate to the
design and construction of the proposed custom residence. The project site identified as Lot 48C
is located along Via Mallorca within the Hideaway Golf Club development in the City of La
Quinta, California. It is our understanding that the proposed residence will be a relatively
lightweight wood-frame structure supported-by conventional shallow spread footings and
concrete slabs on grade. r
The subject lot was previously graded during the rough grading of the Hideaway project site and
f was subsequently regraded. The rough grading. included over-excavation of. the native surface
soil along with the placement of engineered fill soil to construct the building pads. The regrading
included processing the surface soil blong with minor cuts and fills to construct the individual
building }gads to the current configurations. Some additional over-excavation was performed in
areas where the building envelopes were reconfigured. The most recent site grading is
summarized . in the referenced Report of Testing and Observations During Rough Grading
prepared by Sladden Engineering along with the compaction test results.
The referenced reports include recommendations pertaining. to the construction of residential
structure foundations. Based upon our review of the referenced reports,i�isAu �a e
structural values included in the referenced grading report prepared b b� U1NTA
remain applicable for the 'design",dnd",cons truction .of the .propose $d s' ® DEPT.
foundations. iUIL�j�®®/ ED '
AP
R
FOR CONSTR CTION
February 27, 201.5 -2 Project No. 544-15057
15-02-095'
Because the lot has been previously rough graded, the remedial grading required at this time
should be minimal provided that the building falls within the previously established building
envelope. The building area should. be cleared of surface vegetation; scarified and moisture
conditioned prior to precise grading. The exposed Surface should be compacted to a minimum of
90 percent relative compaction is'attained .prior to fill placement. Any fill material should be
placed in thin lifts at near_ optimum.moisture content and compacted to at least -90 percent
relative compaction.
The allowable bearing pressures recommended in the referenced grading report prepared by
Sladden Engineering remain applicable. Conventional- shallow spread footings should be
bottomed into properly compacted. fill material a minimum of 12 inches below lowest adjacent
grade. Continuous footings should beat least 12 inches wide and isolated pad footings should be
-at least 2 feet wide: Continuous footings and isolated pad footings should be designed utilizing
allowable bearing pressures of 1.500 psf and 2000 psf, respectively. Allowable increases of 300 psf
for each additional 1 foot of width and 300 psf for each, additional 6 inches of depth 'may be
utilized if desired. The maximum allowable bearing pressure should be 3000 psf. The
recommended allowable bearing pressures -may be increased by one-third for wind and seismic
loading.
Lateral forces may be resisted by, friction along the base of the.foundations/slabs and passive
resistance along the sides of the footings. A friction coefficient of 0.50 times the normal dead load
forces is recommended for use in design. Passive: resistance. may be estimated using, an
equivalent fluid weight of 300 pcf.. Jf used in. combination with the passive resistance, the
frictional resistance should be reduced'by one third to 0.33 times the normal dead load forces. -
The bearing soil- is non -expansive and .falls within the "very. low" expansion category in
accordance with 2013 California Building Code (CBC) -classification criteria. Slab thickness and
reinforcement should. be determined by 'the structural engineer. We recommend a minimum
floor slab thickness of 4.0 inches and minimum reinforcement of #3 bars at 24 inches on center in
both directions. All slab reinforcement should be supported on concrete chairs to ensure that
reinforcement is placed at slab mid -height.
Slabs with moisture sensitive surfaces should be underlain with a moisture vapor retarder
consisting of a polyvinyl chloride. membrane such as 10 -mil Visqueen, or equivalent. All laps
within the membrane should be sealed and at least 2 inches of clean sand should be placed over
the membrane to promote uniform curing of the concrete. To reduce the potential for punctures,
the membrane should be placed on a pad surface that has been graded smooth without any sharp
protrusions. If a smooth surface can not be achieved by grading, consideration should be given to
placing a 1 -inch thick leveling course of sand across the pad surface prior to placement of the
membrane..
Based on our field observations and understanding of local geologic conditions, the soil profile
type judged applicable to this site is So; generally described as stiff soil. Th �bel�
r�sNZ A
additional coefficients and factors relevant to seismic mitigation fo n vy �- �tr�n/'�
the 2013 California Building Code (CBC). �4 1 1 FEV DEPT'
BUILDING & SA VE®
A�CO�®UCTION
FOR
BY _
February 27, 2015 3-
Project No. 544-15057
15-02-095
The seismic design category for, a structure may be determined in accordance with Section.1613
of. the 2013 CBC or ASCE7. -According to the 2013 CBC, Site Class D may be used to estimate
design seismic loading for the proposed structures. The 2013 CBC Seismic Design Parameters are
summarized below.. :
Risk Category (''fable 1.5-1.):1/1'1/Ill .
Site Class (Table 1613.3.2): D
Ss (Figure 1613.3.1): 1.5005
Sr (Figure 1613.3.1): 0.6845 .
Fa (Table 16'13.3.3(1)):1..0
Fv (Table 1613.5.3(2)):1.5 .
"
Sms (Equation 16-37 (Fa XSsl): 1.5008.
Sm1(Equation 1.6-38 (Fv X SI 1): 1.0268 -
SDS (Equation 16-39 12/3 X Smsl): 1.0008
SDI. (Equation 16-40 12/3 X Smi)): 0.6848
Seismic Design Category: D
If you have questions regarding this letter ,or the referenced
reports, please contact the
undersigned. ;
Respectfully submitted,
SLADDEN ENGINEERIN -
'Brett L. And
Principal Engineer ffay N
SER/gv,n
Ex r.ru '
ClViL .
A
C Auk. i'f _
Copies: 4 [Addressee
�, (D
C� ®G DEPT.
gU1LD�N & SAFETY
pa��� R ON
FOR CQNST
BY
DATE=��
Shidilert Engineering
S Lj L-1- 7
Oct
LA QUiNTA
Please verify that soils reports contain all of the above information. In addition, to assure
continuity between•the investigationlreporting stage and the execution stage, please use
the following checklist to verify that the conclusions and recommendations in the report
cover all the required •elements.Only then can we be assured.that the construction
documents address all of the site soil conditions,
-La Quanta Geotechnical Report Checkiisi
Does the "Conclusions and Recommendations" section of the report address each of the
following criteria?
"Address" means:
(a) the criterion is considered significant and mitigation measures) noted, .or;
(b) the criterion is considered insignificant and explicitly.so stated.
Yes No Criterion _
-- - ®—Foti-nd-abon-citeria-base-d-uporrbearing-cap-ecity-of-rrafural-orc-ompacted--s, -11---
E3 Foundation criteria to mitigate the effects of expansive soils.
® Foundation criteria based upon bearing capacity. -of natural or -compacted soil.
0 Foundation criteria to mitigate the effects of liquefaction.
® Foundation criteria.- to mitigate the effects of seismically induced differential
settlement.
® Foundation criteria to mitigate the effects of long-term. differential settlement.
® Foundation criteria*
to mitigate the effects.of.varying soil strength..
® Foundation criteria to mitigate expected total and differential settlement,
Any "No" answers to the•above checklist should be noted as specific r
corrections. TA
CITY ;, T
.###
BUILE �P
TI
CML
BY
DA ::...;