BRES2018-0378 Title 24BUILDING ENERGY ANALYSIS REPORT
'�3R65SUIg-o3`7S
PROJECT:
Fire Damage
44185 Carmen PL
La Quinta , Ca 92253
Project Designer:
Powell & Assosicates Inc.
9980 Indiana Ave Ste 3
Riverside, Ca 92503
951-352-3588
Report Prepared by:
Robert Gonzales
DESIGN 4 BUILDING
7755 Center Ave. Suite #1100
Huntington Beach, Ca 92647
562-981-4890
CITY OF LA QUANTA
BUILDING DIVISION
REVIEWED FOR
CODE
COMPLIANCE 1
DATE + r D SY
DESIGN ;40BUILDING
Job Number:
18-520
Date:
11/11/2018
RECEIVED
DEC 2 U 2018
CITY 0E LA QUINTA
COMMUNITY DEVELOPMENT
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2016 Building Energy Efficiency Standards.
This program developed by EnergySoft Software — www.energysoft.com.
zND
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
�—Project Name: 44185 Carmen PL Calculation Date/Time: 10:27, Sun, Nov 11, 2018
Calculation Description: Title 24 Analysis Input File Name: 18-520.ribd16x
COMPLIANCE RESULTS
CF1 R-PRF-01
Page 1 of 8
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HER
provider.
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
NO SPECIAL FEATURES REQUIRED
Registration Number: 418-P010089220A-000-000-0000000-0000 Registration Date/Time: 11/11/2018 10:32 HERS Provider: CHEERS
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-11-11 10:27:56
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: 44185 Carmen PL Calculation Date/Time: 10:27, Sun, Nov 11, 2018
CF1 R-PRF-01
Page 2 of 8
Calculation Description: Title 24 Analysis
Input File Name: 18-520.ribd16x
HERS FEATURE SUMMARY
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
• --None--
Cooling System Verifications:
• Minimum Airflow
• Verified Refrigerant Charge
• Fan Efficacy Watts/CFM
HVAC Distribution System Verifications:
• Duct Sealing
Domestic Hot Water System Verifications:
• -- None --
BUILDING - FEATURES INFORMATION
01
02
03
04
05
06
07
Project Name
Conditioned Floor Area (ft2)
Number of Dwelling
Units
Number of Bedrooms
Number of Zones
Number of Ventilation
Cooling Systems
Number of Water
Heating Systems
44185 Carmen PL
1935
1
4
2
0
1
ZONE INFORMATION
01
02
03
04
05
06
07
Zone Name
Zone Type
HVAC System Name
Zone Floor Area
(ftZ)
Avg. Ceiling
Height
Water Heating System 1
Water Heating System 2
Exist. 2nd Floor
Conditioned
HVAC System1
818
8
DHW Sys 1
n/a
Exist. 1st Floor
Conditioned
HVAC System1
1117
8
DHW Sys 1
n/a
Registration Number: 418-P010089220A-000-000-0000000-0000 Registration Datefrime: 11/11/2018 10:32 HERS Provider: CHEERS
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-11-11 10:27:56
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: 44185 Carmen PL Calculation Date/Time: 10:27, Sun, Nov 11, 2018
Calculation Description: Title 24 Analysis
Input File Name: 18-520.ribd16x
CFI R-PRF-01
Page 3 of 8
OPAQUE SURFACES
01
02
03
04
05
06
07
08
09
10
11
Name
Zone
Construction
Azimuth
Orientation
Gross Area
(ftZ)
Window & Door
Area (ftZ)
Tilt
(deg)
Wall
Exception
Status
Verified
Existing
Condition
Front Wall
Exist. 2nd Floor
R-13 Wall
90
Front
208
0
90
n/a
Altered
n/a
Left Wall
Exist. 2nd Floor
R-13 Wall
180
Left
304
40
90
n/a
Altered
n/a
Rear Wall
Exist. 2nd Floor
R-13 Wall
270
Back
208
16
90
n/a
Altered
n/a
Right Wall
Exist. 2nd Floor
R-13 Wall
0
Right
304
44
90
n/a
Altered
n/a
Roof
Exist. 2nd Floor
(N) R-30 Roof Attic
818
n/a
Altered
n/a
Interior Surface
Exist. 2nd Floor»Exist. 1st
Floor
R-0 Floor No Crawlspace
818
n/a I
Existing
No
Front Wall 2
Exist. 1st Floor
R-13 Wall
90
Front
312
77
90
n/a
Altered
n/a
Left Wall 2
Exist. 1st Floor
R-13 Wall
180
Left
288
20
90
n/a
Existing
No
Rear Wall 2
Exist. 1st Floor
R-13 Wall
270
Back
312
72
90
n/a
Altered
n/a
Right Wall 2
Exist. 1st Floor
R-13 Wall
0
Right
288
32
90
n/a
Altered
n/a
Roof 2
Exist. 1st Floor
Default Roof 1978 to Pres
1117
n/a
Existing
No
ATTIC
01
02
03
04
05
06
07
08
09
10
Name
Construction
Type
Roof Rise
Roof
Reflectance
Roof
Emittance
Radiant
Barrier
Cool
Roof
Status
Verified Existing
Condition
Attic Exist. 2nd Floor
Attic RoofExist. 2nd Floor
Ventilated
4
0.1
0.85
No
No
Existing
No
Attic Exist. 1st Floor
Attic RoofExist. 1st Floor
Ventilated
4
0.1
0.85
No
No
Existing
No
Registration Number: 418-P010089220A-000-000-0000000-0000 Registration Date/Time: 11/11/2018 10:32 HERS Provider: CHEERS
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-11-11 10:27:56
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: 44185 Carmen PL Calculation Date/Time: 10:27, Sun, Nov 11, 2018
CF1 R-PRF-01
Page 4 of 8
Calculation Description: Title 24 Analysis
Input File Name: 18-520.ribd16x
FENESTRATION / GLAZING
01
02
03
04
05
06
07
08
09
10
11
Name
Surface (Orientation -Azimuth)
Width (ft)
Height (ft)
Multiplier
Area (ft)
U-factor
SHGC
Exterior Shading
Status
Verified
Existing
Condition
Glass Door
Left Wall (Left-180)
—
1
40.0
0.55
0.67
Insect Screen (default)
Existing
No
Window
Rear Wall (Back-270)
-
1
16.0
0.55
0.67
Insect Screen (default)
Existing
No
Window 2
Right Wall (Right-0)
—
--
1
44.0
0.55
0.67
Insect Screen (default)
Existing
No
Window 3
Front Wall 2 (Front-90)
—
—
1
35.0
0.55
0.67
Insect Screen (default)
Existing
No
Window 4
Left Wall 2 (Left-180)
—
1
20.0
0.55
1 0.67
Insect Screen (default)
Existing
No
Glass Door 2
Rear Wall 2 (Back-270)
1
40.0
0.55
0.67
Insect Screen (default)
Existing
No
Window 5
Rear Wall 2 (Back-270)
—
—
1
32.0
0.55
0.67
Insect Screen (default)
Existing
No
Window 6
Right Wall 2 (Right-0)
—
—
1
32.0
0.55
0.67
Insect Screen (default)
Existing
No
OPAQUE DOORS
01
02 1
03
04
05
06
Name
Side of Building
Area (ft2)
U-factor
Status
Verified Existing Condition
Front Door
Front Wall 2
42.0
0.50
New
No
Registration Number: 418-P010089220A-000-000-0000000-0000 Registration Date/Time: 11/11/2018 10:32 HERS Provider: CHEERS
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-11-11 10:27:56
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: 44185 Carmen PL Calculation Date/Time: 10:27, Sun, Nov 11, 2018
Calculation Description: Title 24 Analysis
Input File Name: 18-520.ribdl6x
CF1 R-PRF-01
Page 5 of 8
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
07
Total Cavity
Winter Design
Construction Name
Surface Type
Construction Type
Framing
R-value
U-factor
Assembly Layers
- Cavity/Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
• Roof Deck: Wood Siding/sheathing/decking
Attic RoofExist. 2nd Floor
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
• Roofing: Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
• Cavity/Frame: R-13/2x4
R-13 Wall
Exterior Walls
Wood Framed Wall
2x4 @ 16 in. O.C.
R 13
0.101
• Exterior Finish: 3 Coat Stucco
• Inside Finish: Gypsum Board
Ceilings (below
Cavity/Frame: R-14.3/2x6
(N) R-30 Roof Attic
attic)
Wood Framed Ceiling
2x6 @ 16 in. O.C.
R 30
0.032
• Over Ceiling Joists: R-15.7 insul
• Floor Surface: Carpeted
• Floor Deck: Wood Siding/sheathing/decking
• Cavity / Frame: no insul. / 2x 12
R-0 Floor No Crawlspace
Interior Floors
Wood Framed Floor
2x12 @ 16 in. O.C.
none
0.196
• Ceiling Below Finish: Gypsum Board
• Cavity/ Frame: no insul / 2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
• Roof Deck: Wood Siding/sheathing/decking
Attic RoofExist. 1st Floor
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
• Roofing: Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
Ceilings (below
• Cavity/Frame: R-9.1 /2x4
Default Roof 1978 to Pres
attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 19
0.049
Over Ceiling Joists: R-9.9 insul.
SLAB FLOORS
01
02
03
04
05
06
07
08
09
Name
Zone
Area (ft2)
Perimeter
(ft)
Edge Insul. R-value
Carpeted
Fraction
Heated
Status
Verified
Existing
Condition
Slab
Exist. 1st Floor
1117
1 150
1 None
0.8
No
Existing
No
BUILDING ENVELOPE - HERS VERIFICATION
01
02
03
04
Quality Insulation Installation (QII)
Quality Installation of Spray Foam Insulation
Building Envelope Air Leakage
CFM50
Not Required
Not Required
Not Required
n/a
Registration Number: 418-P010089220A-000-000-0000000-0000 Registration Date/Time: 11/11/2018 10:32 HERS Provider: CHEERS
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-11-11 10:27:56
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: 44185 Carmen PL Calculation Date/Time: 10:27, Sun, Nov 11, 2018
Calculation Description: Title 24 Analysis Input File Name: 18-520.ribd16x
WATER HEATING SYSTEMS
03 04 05
01 02
Name System Type
DHW Sys 1 DHW
WATER HEATERS
01
02
03
04
Heater
Element
Number
Name
Type
Tank Type
I of Units
DHW Heater 1
Gas
Small Storage
1
Number of
Distribution Type Water Heater Heaters
Standard I DHW Heater 1 1
CF1 R-PRF-01
Page 6 of 8
06 07 08
Solar
Fraction Verified Existing
(%) Status Condition
0 Altered No
05
06
07
08
09
10
11
12
Input Rating /
Tank
Standby
Tank
Uniform Energy
Pilot /
Insulation
Loss /
First Hour
Tank Location
Volume
Factor / Energy
Thermal
R-value
Recovery
Rating /
NEEA Heat Pump
or Ambient
(gal)
Factor / Efficiency
Efficiency
(Int/Ext)
Eff
Flow Rate
Brand I Model
Condition
50
0.65 EF
<= 75 kBtu/hr
0
n/a
n/a
n/a
n/a
SPACE CONDITIONING SYSTEMS
08
01 02
03
04
05 06
07
Distribution
Verified Existing
SC Sys Name System Type
Heating Unit Name
Cooling Unit Name
Fan Name Name
Status Condition
Other Heating and Cooling
HeatingComponent 1
p
Cooling Component 1
Air Distribution
HVAC Fan 1 System 1
Altered No
HVAC Systeml System
HVAC - HEATING UNIT TYPES
02
03
04
01
System Type
Number of Units
Efficiency
Name
1
80 AFUE
Heating Component 1
CntrlFurnace
HVAC - COOLING UNIT TYPES
08
01 02
03
04 05
06 07
Efficiency
System Type
Number of
Units EER SEER
Zonally Controlled Compressor Type HERS Verification
Name
Cooling Component
Cooling Component 1 SplitAirCond
1
11.7 14T
Not Zonal Single Speed
1-hers-cool
Registration Number: 418-P010089220A-000-000-0000000-0000 Registration Date/Time: 11/11/2018 10:32 HERS Provider: CHEERS
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-11-11 10:27:56
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: 44185 Carmen PL Calculation Date/Time: 10:27, Sun, Nov 11, 2018
Calculation Description: Title 24 Analysis Input File Name: 18-520.ribd16x
HVAC COOLING - HERS VERIFICATION
01
02
Name
Verified Airflow
Cooling Component 1-hers-cool
Required
HVAC - DISTRIBUTION SYSTEMS
01
02
03
Name
Type
Duct Leakage
Air Distribution
Ducts located in attic
System 1
(Ventilated and
Sealed and tested
Unventilated)
HVAC DISTRIBUTION - HERS VERIFICATION
01
1
02
Duct Leakage
Name Verification
Air Distribution System 1-hers-dist Required
HVAC - FAN SYSTEMS & HERS VERIFICATION
01
Name
HVAC Fan 1
IAQ (Indoor Air Quality) FANS
01 02
Dwelling Unit IAQ CFM
SFam IAQVentRpt 0
03
Airflow Target
350
04
Verified EER
Not Required
05
Verified SEER
Not Required
CF1 R-PRF-01
Page 7 of 8
06
Verified Refrigerant
Charge
Required
04
05
06
07
08
09
10
Insulation
Supply Duct
Return Duct
Verified Existing
HERS
R-value
Location
Location
Bypass Duct
Status
Condition
Verification
6.0
Attic
Attic
None
Altered
No
Air Distribution
System
1-hers-dist
03
04
05
06
07
08
Duct Leakage
Verified Duct
Verified Duct
Buried
Deeply Buried
Low -leakage
Target (%)
Location
Design 9
Ducts
Ducts
Air Handler
5.0
Not Required
Not Required
Not Required
Not Required
n/a
02 03 04
Type Fan Power (Watts/CFM) EHER Verification
Single Speed PSC Furnace Fan 0.58 Required
03 04 F 05 06
IAQ Recovery
IAQ Watts/CFM IAQ Fan Type Effectiveness(%) HERS Verification
0.25 Default 0 Not Required
Registration Number: 418-P010089220A-000-000-0000000-0000 Registration Date/Time: 11/11/2018 10:32
HERS Provider: CHEERS
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149
Report Generated at: 2016-11-11 10:27:56
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: 44185 Carmen PL Calculation Date/Time: 10:27, Sun, Nov 11, 2018
Calculation Description: Title 24 Analysis
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Robert Gonzales
Company:
Design 4 Building
Address:
7755 Center Ave. Suite 1100
City/State/Zip:
Huntington Beach , CA 92648
RESPONSIBLE PERSON'S DECLARATION STATEMENT
Input File Name: 18-520.ribdl6x
Documentation Author Signature:
RoveYtGonVaies-
Signature Date.
11/11/2018
CEA/HERS Certification Identification (If applicable):
Phone:
562-981-4890
CF1 R-PRF-01
Page 8 of 8
I certify the following under penalty of perjury, under the laws of the State of California.
1. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents.
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
Responsible Designer Name
Robert Gonzales
Company:
Design 4 Building
Address:
7755 Center Ave. Suite 1100
City/State/Zip:
Huntington Beach , CA 92648
Responsible Designer Signature
Robei^tGow5alew
Date Signed:
11/11/2019
License:
Phone:
562-981-4890
Registration Number: 418-P010089220A-000-000-0000000-0000 Registration Date/Time: 11/11/2018 10:32 HERS Provider: CHEERS
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-11-11 10:27:56
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
Building Type
m Single Family ❑ Addition Alone
Date
Fire Damage
❑ Multi Family
m Existing+ Addition/Alteration
111111201
Project Address
California Energy Climate Zone
Total Cond. Floor Area Addition
j # of Units
44185 Carmen PL La Quinta
CA Climate Zone 15
1, 935 0
1
INSULATION
Area
Construction Type
Cavity
ft Special
Features
Status
Wall Wood Framed
R 13
208
Altered
Wall Wood Framed
R 13
264
Altered
Wall Wood Framed
R 13
192
Altered
Wall Wood Framed
R 13
260
Altered
Roof Wood Framed Attic
R 30
818
Altered
Demising Wood Framed w/o Crawl Space
- no insulation
818
Existing
Wall Wood Framed
R 13
235
Altered
Door Opaque Door
- no insulation
42
New
FENESTRATION Total Area:
259 Glazing
Percentage: 13.4 % New/AlteredAvera a U-Factor:
0.00
Orientation Area(ff2) U-Fac
SHGC Overhang Sidefins Exterior Shades
Status
Left (S) 60.0 0.550
0.67 none
none
Bug Screen
Existing
Rear (W) 88.0 0.550
0.67 none
none
Bug Screen
Existing
Right (N) 76.0 0.550
0.67 none
none
Bug Screen
Existing
Front (E) 35.0 0.550
0.67 none
none
Bug Screen
Existing
HVAC SYSTEMS
Qty. Heating
1 Central Furnace
HVAC DISTRIBUTION
Location Heath
HVAC System Ducted
WATER HEATING
Qty. Type
1 Small Storage Gas
Min. Eff Cooling Min. Eff Thermostat Status
80% AFUE Split Air Conditioner 14.0 SEER Setback Altered
Cooling Duct Location
n„,ro.4 n*#r..
Gallons Min. Eff Distribution
50 0.65 Standard
Duct
R-Value
6.0
Status
Altered
Status
Altered
7.2 by En&rqySo# User Number. 20180 ID: 18-520 Pape 10 of 12
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
Building Type
m Single Family ❑ Addition Alone
Date
Fire Damage
❑ Multi Family m Existing+ Addition/Alteration
�1111112018
Project Address
California Energy Climate Zone Total Cond. Floor Area
Addition
# of Units
44185 Carmen PL La Quinta
CA Climate Zone 15 1,935
0
I 1
INSULATION
Area
Construction Type
Cavity
(ft) Special Features
Status
Wall Wood Framed
R 13
268
Existing
Wall Wood Framed
R 13
240
Altered
Wall Wood Framed
R 13
256
Altered
Roof Wood Framed Attic
R 19
1,117
Existing
Slab Unheated Slab -on -Grade
- no insulation
1,117 Perim = 150'
Existing
FENESTRATION I Total Area: 259 Glazing Percentage: 13.4 New/Altered Average U-Factor: 0.00
Orientation Area(ff) U-Fac SHGC Overhang Sidefins Exterior Shades Status
HVAC SYSTEMS
Qtv. Heating
HVAC DISTRIBUTION
Location Heati
WATER HEATING
Min. Eff Coolin
Cooli
Min. Eff
Duct Location
Gallons Min. Eff Distribution
Thermostat Status
Duct
R-Value Status
Status
7.2 by EnaoySoft User Number. 20180 ID: 18-520 Pape 1177
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name Date
Fire Damage 11/11/2018
System Name Floor Area
HVAC System 1,935
Cw1!!IK10C13IAIl- t UC!`LFQ QVQTGnn 1 nnn
Number of Systems
1
COIL
CFM
Total Room Loads 1,629
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output per System
80,000
33,019
638
700
27,079
Total Output (Btuh)
80,000
0
Output Btuh/s ft)
41.3
1,827
1,202
Cooling System
0
0
Output per System
60,000
0
0 0
0
Total Output Btuh
60,000
0
638
0
Total Output (Tons)
5.0
1,827
1,202
Total Output (Btuh/sqft)
31.0
Total Output s ft/Ton
387.0
1 36,674
29,482
Air System
CFM per System
1,800
HVAC EQUIPMENT SELECTION
Airflow cfm
1,800
Furnace - A/C
31,803
18,856
80,000
Airflow cfm/s ft
0.93
Airflow (cfm/Ton)
360.0
Outside Air %Ia
0•0 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
I TIME OF SYSTEM PEAK
31,803
18,856
80,000
Outside Air cfm/s ft
0.00
Note: values above givan at ARI conditions
Aug 3 PM
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
67 OF
67 OF 105 OF
Outside Air
0 cfm
Supply Fan
Heating Coil
1,800 cfm
67 OF
104 OF
ROOM 7
68 OF
COOLING SYSTEM PSYCHROMETRICS Airstream Temperatures
at Time of Cooling Peak
112/73OF
76/62OF 76/62OF 55/54OF
Outside Air
0 cfm
Supply Fan Cooling Coil
56 / 54 OF
1,800 cfm
46.4 % ROOM = I
76/62OF
75161 OF
`
I