15720 (BLCK) Title 24TITLE 28 REPORT FOR:
CORONEL CONST. OFFICE ADDITION
LA QUINT&, CAL.
PROJECT DESIGNER:
CORONEL CONSTRUCTION
P. O. BOX 389
LA QUINTA, CA. 92253
REPORT PREPARED BY:
WENDELL W. VEITH
INSU-FORM, INC.
68487 HIGHWAY 111, SUITE 56
CATHEDRAL CITY, CA 92264
(619) 324-0216
JQb Number:
Date: .9/10/1997
G
The COMPLY 24 computer program has been used to perform the calculations
summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the
Residential and Nonresidential Building Energy Efficiency Standards.
This program developed by Gabel Dodd Associates (510) 428-0803.
I. I
Table of Contents for Title 24 Report
-----------------------------
Cover Page.......................................................... 1
Table of Contents 2
Form ENV -1 Envelope Certificate of compliance ........................ 3
Form ENV -2 Envelope Summary ........................................ 5
Form ENV -3 Construction Assemblies .................................. 8
Form LTG -1 Lighting Certificate of Compliance ........................ 11
Form.LTG-2 Lighting Compliance summary .............................. 13.
Form MECH-1 Mechanical Certificate of Compliance 14
Form MECH-3 Mechanical Equipment Summary .... 17
HVACZone & Space Loads Summary ..................................... 18
e
320 P. 04
CERTIFICATE OF COMPLIANCE (part 1 of 2) ENV -1 page 3 of 19
------------------;------------- - --
----------------------�--
Project Name: CORONEL CONST. OFFICE ADDITION - Date: 9/10/1997.
Address:
Envelope LA QUINTA, CAL. Building Permit No
Designer: CORONEL CONSTRUCTION Checked :by / Date
Documentation: INSU-FORM INC.
COMPLY 24 user 2655
---------------------------,---------------- ------------------------- ----
GENERAL INFORMATION
Date of Plans: Building conditioned Floor Area: 500 sf,
Building Type: Nonresidential Climate Zone: 15
Phase of Construction: O New Construction O Addition O Alteration
Method of Envelope Compliance: Performance - COMPLY 24 v 4.11
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance
specifications needed to comply with Title 24, Part 6, Chapter 1 and Title
20, Chapter 2, Subchapter 4, Article i of the California Code of Regula-
tions. This certificate applies only to building envelope requirements.
The Principal Envelope Designer hereby certifies that the proposed build-
ing design represented in this set of construction documents is consistent
with the other compliance forms and worksheets, with the specifications,
and with any other calculations submitted with this permit application.
The proposed building has been designed to meet the envelope requirements
contained in sections 110, 116 through 118, and 143 or 149 of Tittle 24,.
Part 6, Chapter 1.
Please check one:
O I hereby affirm that I am eligible under the provisions of Division 3
of the Business and Professions Code to sign this document as the
person responsible for its preparation; and that I am a -.civil engineer
or architect.
O I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section 5537,2 of the Business and
Professions Code to sign this document as the person responsible for
its preparation; and that I am a licensed contractor preparing docu-
ments for work that I have contracted to perform,
0 I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section of the
Code to sign this document as the person responsible for its
preparation; and for the following reason:
PRINCIPAL ENVELOPE DESIGNER
CORONEL CONSTRUCTION
lgna ure) (Lic.. ig) `., (Date)
ENVELOPE MANDATORY MEASURES
Indicate location on plans of Note Block for Mandatory Measures:
5EP-10-57 THU 14:L0 HAVE A NICE DAY!! 615 320 9887 F.t-D5
CERTIFICATE OF COMPLIANCE (part 2 of 2) ENV -1 page 4
-----------------------------------------------------------------------
Project Name: CoRONEL CONST. OFFICE ADDITION Date: 9/10/1997
Documentation: INSU-FORM, INC. COMPLY 24 User 2655
------------------------
-------------------------------------------------
.OPAQUE SURFACES Const Note to
.Assembly -Name Type Location/Comments Field
->------------------------ ------
R-13 Wall (W.13.2x4.16) Wood -
R-38 Roof (TRUSSES) Wood
Solid Wood Door None
FENESTRATION Frame
orient
Panes
Type
Exterior shade
-----------------------
OH
Glazing Type
Left. (N)
2
Metal
Standard Bug Screen
--
Y
--------------.----------
Double Clear
Default(N)
Back (E).
2
Metal
Standard Bug Screen
Y
Double Clear
Default(N)
Front (W)
2
Metal
None
Y
Double Clear
Default(N)
SEP -10-97 THU 14:20 HAVE A NICE DAY!! 619 320 9887 P.06
r
PERFORMANCE ENVELOPE SUMMARY Part 1 of 3 ENV -2 Paige 5 of 19
-----------------------------------------------------------------•----------
Project.Name: CORONEL CONST. OFFICE ADDITION Date: 9/7.0/1997
Documentation: INSU-FORM, INC. COMPLY 24: User 2655
GENERAL INFORMATION BY SPACE.
FIr Floor Display
Space Name Occupancy No Area Volume Perim.
----------------------- ---------------------- --- ----- ------- -------
OFFICE ADDITION Comp Bldg Office 1 500 '4000 0
k-----
Total 500
0
SEP -10-97 THU 14:21 HAVE A NICE DAY!! 619 320 9887 P.07
PERFORMANCE ENVELOPEFart 2 of 3 ENV -2 g 6 of 19
SUr1MARY a page
-- --------------...- •-----------------
Project Name:
--------------------------------
CORONEL CONST. OFFICE ADDITION
Date:
9/10/1997
Documentation:
INSU-FORM, INC.
COMPLY
24 User 2655
OPAQUE SURFACES Act Solar
Type Area U -Val Atm Tilt Gains Form 3 Reference Location/Comments
Wall 125 0.088 270 90 Yes R-13 Wall (W.13.2x4.15) OFFICE ADDITION Wall Wall 200 0.088 180 . 90 . Yes R-13 Wall (W.13.2x4.16) OFFICE ADDITION
Wall 120 0.088 90 90, Yes, R-13 Wall. (W.13.2x4.16) OFFICE ADDITION
Wall 175 0.088 0 90 Yes, R-13 Wall (W.13.2x4.'16) OFFICE ADDITION
Roof 500 0.029 270 22 Yes R-38 Roof (TRUSSES) OFFICE ADDITION
Slb 500 0.000 0 180. No .OFFICE Exposed Slab OFFICE ADDITION
PERFORMANCE ENVELOPE SUMMARY Part 3 of 3 ENV -2 page -7 0f 19
--------------------------------------------------
Project Name: CORONEL CONST. OFFICE ADDITION Date: 9/1.0/1997
Documentation: INSU-FORM, INC. COMPLY 241 User 2655
----------------------------------------------------------------------------
FENESTRATION SURFACES SC
Act Glass
0 Type Area Frame Div U -Val Azm Tilt Only Location/Comments
-- --- ---- -----
1 Wdw Front (W) 7.5 Metal No 0.72 270 90 0.88 OFFICE'ADDITION
2 Wdw Front (W) 7.5 Metal No 0.72 270 90 0.88 OF'F'ICE ADDITION
3 Wdw Hack (E) 40.0 Metal No 0.76 90 90 0.88 OFFICE ADDITION
4 Wdw Left (N). 25.0 Metal No 0.77 0 90 0.68 OFFICE ADD]:TION
OVERHANGS/SIDE FINS
--Window-- -----Overhang------ ---Left Fin--- ---Right: Fin --
if Type Ht Wd Len Ht LExt RExt Dist Len Ht Dist Len Ht
.. ---- ---- ---- ---- --- - ----
1 Wdw 5.0 1.5 4.0 0.1 4.0 4.0
2 Wdw 5.0 1.5 4.0 0.1 4.0 4.0
3 Wdw 6.7 6.0 10.0 0.1 10.0 10.0
4 Wdw 5.0 5.0 2.0 0.1 2.0 2.0
r•
aq;LY HAVE A NICE DAY!!
w ir.�r�� ". ■w r� nr619 320 9887 P.09
PROPOSED CONSTRUCTION ASSEMBLY ENV_3 page 8 of 19
--------- r------------------------------- ------------------------•---------
Project Name: CORONEL CONST. OFFICE ADDITION Date: 9/10,11997
Documentation: INSU-FORM, INC. COMPLY 24 User 2655
COMPONENT DESCRIPTION
-------------------------------
Sketch of Construction Assembly
ASSEMBLY U -VALUE
Assembly Name: R-13 Wall (W.13.2X4.16)
Assembly Type: Wall
Assembly Tilt: 90 deg (Vertical)
Framing Material: Wood
Framing Spacing: " 0. C.
Framing Percent: 15.0 4
Absorptivity: 0.70
Roughness: Stucco, Wood Shingles
ADJUSTMENT FOR FRAMING
(1 /14.53) X (0.85) + (1 / 5.00) X (0.15)
Weight:
Heat Capacity:
12.3 lb/sqft
2.87
0.088
TOTAL U -VALUE -
TOTAL R -VALUE
0.088
11.30
Th
R• -Value
Construction Components
Fr (in)
Cavity
Frame
Outside Air Film
0.17
- ~
0.17
1. Stucco
0.875
0.17
0.17
2. Membrane, Vapor -Permeable Felt
0.010
0.06
0.06'
3. Insulation, Mineral Fiber, R--13
* 3.500
13.00
3.46
4. Gypsum or Plaster Board
0.500
0.45
0.45
5.
6.
7.
8. -
9.
Inside Air Film
---------------------------------------------------------------------------
0.68
0.68
Unadjusted
R -Values
14.53
5.00
ADJUSTMENT FOR FRAMING
(1 /14.53) X (0.85) + (1 / 5.00) X (0.15)
Weight:
Heat Capacity:
12.3 lb/sqft
2.87
0.088
TOTAL U -VALUE -
TOTAL R -VALUE
0.088
11.30
•� •�� nr�vc H N1i E L _ 20 98$7 P. 10
PROPOSED CONSTRUCTION ASSEMBLY ENV -3 pago 9 of 19
--------------------------------------------- -------------.-.---------v -
Project Name: CORONEL CONST, OFFICE ADDITION Date: 9/10/1997
Documentation: INSU-FORM, INC. COMPLY 24 User 2655
----.... ----------------------------------- -----. ------------
COMPONENT DESCRIPTION Assembly Name: R-38 Roof (TRUSSES)
-------------------------------
-------------------------------
Sketch of Construction Assembly
ASSEMBLY U -VALUE
Assembly Type: Roof
Assembly Tilt: 22 deg (Tilted Up)
Framing Material: Wood
Framing Spacing: ^" O.C.
Framing Percent: 10.0 $
Absorptivity: 0.70
Roughness: Concrete, Asph. Shingles
TOTAL R -VALUE = 34.94
Weight: 14.3 lb/sgft
Heat Capacity: 4.47
Th
R• -Value
construction Components
----------------------------------------------------------------------------
Fr (in)
Cavity
Frame
Outside Air Film
0.17
0.17'
1. Roofing, Slate
0.500
0.05
0.05
2. Membrane, Vapor -Permeable Felt
0.01.0
0.06
0.06
3. Plywood
0.500
0.62
0.62
4. Air Space
* 2.000
0.78
1.98
5. Insulation, Mineral Fiber, R-38
* 11.500
38.00
11.39
6. Gypsum or Plaster Board
0.500
0.45
0.45
7.
8.
9.
Inside Air Film
0.61
0.61
---------------------------------------------------------------------------
Unadjusted
R -Values
40.74
15.32
ADJUSTMENT FOR FRAMING
(1 /40.74) x (0.90) + (1 /15.32) X (0.10)
0.029
TOTAL U -VALUE =
0,.029
TOTAL R -VALUE = 34.94
Weight: 14.3 lb/sgft
Heat Capacity: 4.47
SEP -10-97 THU 14:23 HAVE A NI Y!! - 619 320 9887 P.11
PROPOSED CONSTRUCTION ASSEMBLY ENV -3 page 10 of 19
--------------
~----------
Project Nazae:CORONELCONST OFFICE ADDITION - [)ate 9/10/1997 --r
Documentation: INSU-FORM, INC. COMPLY 24 User 2655
---------------------------------------
COMPONENT DESCRIPTION Assembly Name: Solid Wood Door,
-------------------------------
Sketch of Construction Assembly
Assembly Type: Door
Assembly Tilt: 90 deg (Vertical)
Framing Material: None
Framing Spacing: �" O.C.
Framing Percent: 0.0
Absorptivity: 0.70
Roughness:*Glass, Paint on Pine
ASSEMBLY U -VALUE
Th R: -Value
construction Components Fr (in) Cavity Frame
-------------------------------------------------
Outside Air Film 0.17 0.17
1. Softwood, Douglas Fir -Larch 1.750 1.73 1.73
2.
3.'
4.
5.
6.
7.
8. _
9.
Inside Air Film 0
68
------------------------------------ -----------68-------
- ---
Unadjusted R -Values 2.58 2.58
ADJUSTMENT FOR FRAMING
(1 / 2.58) x (1.00) + (1 / 2.58) x (0.00) -
Weight:
Heat Capacity:
5.1 lb/sqft
1.99
0.387
TOTAL U -VALUE
TOTAL R -VALUE =
0.387
2.58
:ti.
r.n vc H N1 t_;
CERTIFICATE OF COMPLIANCE (part 1 of 2) LTG -1 page 11 of 19
---------------------------------------------- -------------------- I ----_----
Project Name: CORONEL CONST. OFFICE ADDITION Date: 9/10/1997
Address:
LA QUINTA, CAL.
Lighting
Designer: CORONEL CONSTRUCTION
Building Fsrmi-No
Checked by / Date
Documentation: INSU-FORM, INC. COMPLY 24 User 2655
---------------------------------------------------------------------------
GENERAL INFORMATION
Date of Plans: Building Conditioned Floor Area: 500 sf
Building Type: Nonresidential Climate Zone: 15
Phase of Construction: O New Construction 0 Addition 0 Alteration
Method of Lighting Compliance: Performance - COMPLY 24 v 4.11
STATEMENT OF COMPLIANCE
This Certificate of -Compliance lists the building features and performance
specifications needed to comply with Title 24, Part 6, Chapter 1 and Title
20, Chapter 2, Subchapter 4, Article 1 of the California Code of Regula-
tions. This certificate applies only to building lighting requirements.
The Principal Lighting Designer hereby certifies that the proposed build-
ing design represented in this set of construction documents is consistent
with the other compliance Forms and worksheets, with the specifications,
and with any other calculations submitted with this permit application.
The proposed building has been designed to meet the lighting requirements
contained in sections 110, 119, 130 through 132 and 146 or 149.
Please check one:
0 I hereby affirm that I am eligible under the provisions of Division 3
of the Business and Professions Code to sign .this document as the
person responsible for its preparation; and that I am a civil engineer,
electrical engineer or architect.
0 I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section 5537.2 of the Business and
Professions Code to sign this document as the person responsible for
its preparation; and that I am a licensed contractor preparing docu-
ments for work that I have contracted to perform.
O I affirm that I am eligible under the exemption to Division 3 of the
Business and Professions Code by Section of the
Code to sign this document as the person responsible for its
preparation; and for the following reaso .
PRINCIPAL LIGHTING DESIGNER ��a
CORONEL CONSTRUCTION
(Si e} (i.�c. ) (Date)
ti.
LIGHTING MANDATORY MEASURES
indicate location on plans of Note Block for Mandatory Measurers:
-•�� � n v C M 1
CERTIFICATE OF COMPLIANCE (part 2 of 2) LTG -1 page 12 of 19
- - e ------ S --------------------------------------- ----------------------------
Project
-------------------------
Project Name: CORONEL CONST. OFFICE ADDITION Date: 9/1011997
Documentation: INSU-FORM, INC. COMPLY 24 User 2655
---------------------------------------------------------------------------
INSTALLED LIGHTING SCHEDULE
No of
Watts/
Ballast
Ballasts/
No of
Note -to -
Nave Lamp Type
----------------
Lamps
------
Lamp
------
Type
----------
Luminaire
---------
Fixt.
Field
-------
Fluorescent
1
34
Standard
1.0
1
Incandescent
1
75
n/a
n/a
3
Incandescent
1
100
n/a
n/a
4
MANDATORY AUTOMATIC
CONTROLS
Control
Note.to
Control Location
ID
Control
Type Space
Controlled
Field
CONTROLS FOR CREDIT
Control
Note to
Control Location
----------- ------- -------
ID
Control
----------------
Type Space
----------------------
Controlled
Field
`------
P-10-97 THU 14:24 HAVE.A NICE DAY!! 619 320 9887 P.14
LIGHTING COMPLIANCE SUMMARY LTG -2 page 13 of 19
-------------------------------------------------- --- ----------- ---------
Project Name: CORONEL CONST. OFFICE ADDITION Date: 9/10/1997
Documentation: INSU-FORM, INC. COMPLY 24 User 2655
--.: ------------------------------------------------------------------------
ACTUAL LIGHTING POWER
No of Watts Total
Name Description Lumin per Default Watts
48" T-12 Low Watt /I Lamp (Not Tndm) 1 43.0_ 43
75 w Surface Mount Incandescent 3 75.0 _ 225
100 w Surface Mount Incandescent 4 100.0 400
SubTotal 668
Less Control Credits (LTG -3) 0
Total Proposed Watts 668
* If not CEC Default value,please provide supporting documentation.
MODELLED LIGHTING POWER BY SPACE Modelled
Floor LPD Total Tailored
Space Name Occupancy Area (w/sf) (watts) (watts)
OFFICE AUDITION Comp Bldg Office 500 1.500 750 0
---
----- -----------------
TOTALS 500 1.500 750 0
* Note: Tailored Allotment requires supporting documentation on form LTG -4.
CERTIFICATE OF COMPLIANCE (part 1 of 3) MECH-1 page 14 of 19
Project Name: CORONEL CONST OFFICE ADDITIONDate: 9/10/1997
i
Address:
LA QUXNTA, CAL.
Mechanical
Designer: CORONEL CONSTRUCTION
Building Permit No
checked b,y / Date
Documentation: INSU-FORM, INC. ICOMPLY 24 User 2655
---------------------------------------------------------------------------
GENERAL INFORMATION.
Date of Plans: Building Conditioned Floor Area: 500 sf
Building Type: Nonresidential Climate Zone: 15
Phase of Construction: O New Construction O Addition O Alteration
Method of Mechanical Compliance: Performance - COMPLY 24 v 4.11.
Proof of Envelope Compliance: O Previous Permit, O Compliance Attached
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance
specifications needed to comply with Title 24, Part 6, Chapter 1 and Title
20, Chapter 2, Subchapter 4, Article 1 of the California Code of Regula-
tions. This certificate applies only to building mechanical requirements.
The Principal Mechanical Designer hereby certifies.that the proposed build-
ing design represented in this set of construction documents is consistent
with the other compliance forms and worksheets, with the specifications,
and with any other calculations submitted with this permit application.
The proposed building has been designed to meet the mechanical requirements
contained in sections 110 through 115, 120 through 124, 140 through 142,144
and 145.
Please check one:
0 1 hereby affirm that I am eligible under the provisions of Division 3
of the Business and Professions Code to sign this document as. the
person responsible for its preparation; and that I am a civil. engineer
mechanical engineer or architect.
O I affirm that I am eligible under the exemption to Division 3. of the
Business and Professions Code by Section 5537.2 of the Business and
Professions Code to sign this document as the person responsible for
its preparation; and that I am a licensed contractor preparing docu-
ments for work that I have contracted to perform.
0 I affirm that I am eligible under the exemption to Division 2, of the
Business and Professions Code by Section of the
Code to sign this document as the person responsible for its
preparation; and for the following rea on:
PRINCIPAL MECHANICAL DESIGNER /
CORONEL CONSTRUCTIONal �k/), ?
lgna ure) (L1c.) (Date)
MECHANICAL MANDATORY MEASURES
Indicate location on plans of Note Block for Mandatory Measures: `
CERTIFICATE OF COMPLIANCE (part 2 Of 3) MECH--1 page 15 of -19
---------------------------------------------------------------------------
Project Name: CORONEL CONST. OFFICE ADDITION Date: 9/10/1997
Documentation: INSU--FORM, INC. COMPLY 24 User 2655
-----------------------------------------------------------------
SYSTEM FEATURES
Zone Name
OFFICE ADDITION
Time 'Control
--------------------------------------------------
Time Control
Setback Control
Both
# of isolation Zonesn/a
HP Thermostat
Yes
Electric Neat
5.0 KW
Fan Control
Constant Volume
VAV Min Position
n/a
Simul. Heat/Cool
n/a
Heat Supply Reset
Constant Temp
Cool Supply Reset
Constant Temp
ventilation
OA Damper Control
Economizer Type
No Economizer
Outdoor Air CFM
75
Heat Equip Type
Heat Pump
Make & Model No.
Day&Night 693CN024-A
Cool Equip Type
DX
Make and Model
Note to
Field
Code 'fables
--------------------------------------------------
Time Control
Ventilation
OA Damper ..
S:Prog Switch
B:Air Balance
A:Auto
O:Occ Sensor
C:OA Cert.
G:Gravity
H: kllAn Timer
M: OA Measure
D:Demand Cont
N:14atural
387 P. 04
CERTIFICATE OF COMPLIANCE (part 3
of 3)
MECH-1
page 16 of 19
Project Name: CORONEL CONST. OFFICE
ADDITION
Date:
9/10/1997
Documentation: INSb -FORM,
----------------------- 7
INC.
--------------------------------------------------
---------------
---------
COMPLY
-----------------------
24 User 2655
DUCT INSULATION
DUCT
Duct Tape
Insul Note to
System Name
Type
Duct Location
Allowed
R -Val Field
Day&Night 693CN024-A
Heating
~
Ducts in Attic
~
Y / N
4:2
Cooling
Ducts in Attic
Y / N
4.2
PIPE INSULATION
Insul
Note to
System Name
Pipe Type Required
Field
Domestic Hot Water
Y / N
NOTES TO FIELD - For Building Department Use Only
---------------------------------------------------------------------------
9
•�—� iMV 14:32 HAVE is NICE DAY!
6 1 5 3 2 0 9867
MECHANXCAL EQUIPMENT SUMMARY MECH-3 page 17 of 19
------------------------------------------ -------------------- ----
Project Name: CORONEL CONST. OFFICE ADDITION Date: 9/10/1997
Documentation: INSU-FORM, INC. COMPLY 24 User 2655
PLANT EQUIPMENT SUMMARY Fuel Elec Total
No. Input Input Output
Equipment Name Equipment Type Sys .(KBtu) (KW) (KBtu).
-- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ------ ---- ------
Std
-----
Std Gas 50 gal or Less Gas Fired 1 40.0 0.0 31.2
CENTRAL SYSTEM SUMMARY
Sys No
No System Name System Type Sys Economizer Type.
1 Day&Night 693CN024-A Packaged Neat Pu 1 No Economizer
CENTRAL SYSTEM RATINGS
Sys------- Heating ------------------ ---------------- Cooling -----------
No Type . Output Aux KW EFF Type Output Sensible EER SEER
1 Heat Pump 20800 5.0 7.20 DX 22400 15660 13.90 10.00
CENTRAL FAN SUMMARY ------------- Supply Fan ----------- ---- Return Fan ---
SES Mtr Dry Mtr Dry
No Fan Type Motor Location CFM BHP Eff Eff CFM Blip Eff Eff
1 Constant Volume Draw -Through 765 0.33 64 100 None
ZONAL FAN SUMMARY --------- Zonal Fan ------------ Exhaust Fan -----
-Mtr Dry Mtr Drv-
Space Name No CFM BHP Eff Eff No CFM BHP Eff Eff
None
0-97 THU 14:36 HAVE A.NICE DAY!! 619 320 9887 P.01'
. 4.1
HVAC ZONE HEATING & COOLING LOAD SUMMARY page 18 of 19
-----------------------------------------------------------------•----------
project Name: CORONEL CONST. OFFICE ADDITION Date: 9/1.0/1997
Documentation: INSU-FORM, INC. ICOMPLY 24 User 2655
-------------------------------------------------------------------•----------
HVAC ZONE DESCRIPTION
HVAC Zone Name:
Heating System Name:
Cooling System Name:
System Multiplier:
Fan Schedule:
Peak Load Method:
Relative Humidity:
SPACES IN THIS ZONE PEAK HEATING
OFFICE ADDITION (Jan 12am) .10.977
TOTAL SPACE LOAD 10977
Duct Gains & Losses:. 1098
Ventilation: ( 75 CFM) 3320
Return Air Lighting Gain
TOTAL SYSTEM LOAD 15395
SYSTEM OUTPUT AT DESIGN CONDITIONS 31594
OFFICE ADDITION
Day&Night 693CN024-A
i
All On Load Cal.cs
COINCIDENT
50 &
COOLING
PEAK SENSIBLE: LATENT
(Aug 3pm) 11399, 400
11399 400
1140
2672 -27'
C!
15211. . 373
15089 5581
NOTE: The TOTAL SYSTEM LOAD shown represents the minimum size equipment
which will heat or cool .this zone during the design conditions indicated.
These numbers include no safety factor, and the HVAC contractor should
oversize by a reasonable margin to account for variations in weather
conditions and the pick-up capacity reguiired to bring the zone to temper-
ature as a result of a setback thermostat. Those responsible for final
equipment selection should note that Sensible and Latent Cooling Loads are
indicated to allow for accurate comparison with manufacturer's output data..
..r,c 1v1 L.0 b
SPACE HEATING & COOLING LOAD SUMMARY page 19 of 19
------------------------------------------------------------------..---------
Project Name: CORONEL CONST. OFFICE ADDITION Date; 9/10/1947
Documentation: INSU-FORM, INC. COMPLY 24 User 2655
----------------------------------------------------------------------------
SUMMARY OF PEAK HOUR LOADS FOR SPACE
Space Name:
OFFICE ADDITION
COOLING
DESIGN CONDITIONS
HEATING
SENSIBLE
LATENT
Peak Hour:
Jan 12am
Aug 4pm
Indoor Conditions:
70 F DB
78 F DB
50 % RH
Outdoor Conditions:
29 F DB
109 F DB
72 F VIB
LOAD COMPONENT
---------------------
Quantity
------------
Btu/hr
-----
Btu/hr
-------
Btu/hr
---
Wall Conduction
620.0
sqft
-
2249
2215
--
Window Conduction
60.0
sqft
2478
1401
Door Conduction
20.0
sqft
318
518
Roof Conduction
500.0
sqft
587
444
Skylight Conduction
0.0
sqft
0
0
Floor Conduction
0.0
sqft
0
0
Slab Conduction
500.0
sqft
3870
0
Interior Conduction
0.0
sqft
0
0
Infiltration
0.5
AC/hr
1475
0
Solar Gain
80.0
sqft
0
2237
Lighting
750.0
watts
0
2482
Receptacle
500.0
watts
0
1707
Process
0.0
watts
0
0
Occupants
2.0
oces
0
500
400
SPACE LOADS
10977
11503
400
Heating AirFlow:
10977 Btu/hr / (1.08
x 35
F DeltaT)]
= 291 cfm
Cooling AirFlow:
11503 Btu/hr / [1.08
x 23
F DeltaT))
= 463 cfm
,l.