NO PERMIT Title 24BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Custom Residence for Desert Ring, LLC
Lot 19A, 52-740 Ross Ave., Madison Club
La Quinta, CA 92253
Project Designer:
South West Concepts
78-115 Calle Estado
La Quinta, CA 92253
(760) 564-4707
Report Prepared by:
Tim Scott
Scott Design and Title 24, 1
77-085 Michigan Drive
Palm Desert, Ca 92211
(760) 200-4780
Job Number:
Date:
2/20/2013
CITY OF LA QUINTz�
BUILDING & SAFETY DEFT.
APPROVED
FOR CONSTRUCTION;
DA W01-1> 13y*tyl�5S
[ Z-1 d"-I
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
FE-nergyPro 5, 1 by EnergySoR User Number. 6712 Run Code: 2013-02-20T17:10.35 ID:
I TABLE OF CONTENTS I
Cover Page 1
Table of Contents 2
Form CF-1 R Certificate of Compliance 3
Form MF-1 R Mandatory Measures Summary 14
HVAC System Heating and Cooling Loads Summary 17
Room Load Summary 23
Room Heating Peak Loads 29
Room Cooling Peak Loads 37
EnergvPro 5.1 by EnergySoft Job Number: ID: User Number: 6712
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF-1 R
Project Name
Custom Residence for Desert Ring, LLC
Building Type m Single Family ❑ Addition Alone Date
❑ Multi Family ❑ Existing+ Addition/Alteration 1212012013
Project Address
Lot 19A, 52-740 Ross Ave., Madison Club
California Energy Climate Zone
CA Climate Zone 15
Total Cord. Floo
7,394 r Area
Addition
n/a
7#of Stories
2
FIELD INSPECTION ENERGY CHECKLIST
IZI Yes ❑ No HERS Measures -- If Yes, A CF-4R must be provided per Part 2 of 5 of this form.
El Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavity (ft) Features (see Part 2 of 5) Status
Roof Wood Framed Attic R-38 4,853 Radiant Barrier New
Wall Wood Framed R-21 8,277 New
Slab Unheated Slab -on -Grade None 4,990 Perim = 622' New
Door Opaque Door None 21 New
Floor Wood Framed w/Crawl Space R-13 81 New
FENESTRATION U- Exterior
Orientation Area(ft) Factor SHGC Overhang Sidefins Shades Status
Front (NE) 289.5 0.350
0.33 none none Bug Screen New
Left (SE) 295.1 0.350
0.33 none none Bug Screen New
Rear (SW 848.2 0.350
0.33 none none Bug Screen New
Right (NVIO 203.0 0.350
0.33 none none Bug Screen New
Front (NE) 8.0 0.350
0.33 22.0 none Bug Screen New
Front (NE) 45.0 0.350
0.33 11.0 none Bug Screen New
Front (NE) 54.0 0.350
0.33 12.0 none Bug Screen New
HVAC SYSTEMS
Ot . Heating Min. Eff
Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE
Split Air Conditioner 15.0 SEER Setback New
2 Central Furnace 80% AFUE
Split Air Conditioner 15.2 SEER Setback New
1 Central Furnace 80% AFUE
Split Air Conditioner 15 0 SEER Setback New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R-Value Status
HVAC 1 Ducted
HVAC 2a & 2b Ducted
Ducted Attic, Ceiling Ins, vented 8.0 New
Ducted Attic, Ceiling Ins, vented 8.0 New
HVAC 3 Ducted
Ducted Attic, Ceiling Ins, vented 8.0 New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
1 Large Gas 75
0.82 All Pipes Ins New
1 Large Gas 75
0.82 All Pipes Ins New
EnergyPro 5.1 by EnBrgySoft User Number. 6712
Run Code: 2013-02-20T17.,10:35 ID:
Pane 3 of 46
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF-1 R
Project Name
Custom Residence for Desert Ring, LLC
Building Type m Single Family ❑ Addition Alone Date
❑ Multi Family ❑ Existing+ Addition/Alteration 212012013
Project Address
Lot 19A, 52-740 Ross Ave., Madison Club
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
7,394
Addition
n/a
# of Stories
2
FIELD INSPECTION ENERGY CHECKLIST
El Yes ❑ No HERS Measures -- If Yes, A CF-4R must be provided per Part 2 of 5 of this form.
El Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction Type Cavity (fi) Features (see Part 2 of 5) Status
FENESTRATION U- Exterior
Orientation Area(ft) Factor SHGC Overhang Sidefins Shades Status
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status
1 Central Furnace 80% AFUE Split Air Conditioner 15 0 SEER Setback New
1 Central Furnace 80% AFUE Split Air Conditioner 15.5 SEER Setback New
1 Central Furnace 80% AFUE Split Air Conditioner 15.0 SEER Setback New
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R-Value Status
HVAC 4 Ducted Ducted Attic, Ceiling Ins, vented 8.0 New
HVAC 5 Ducted Ducted Attic, Ceiling Ins, vented 8.0 New
HVAC 6 Ducted Ducted Attic, Ceiling Ins, vented 8.0 New
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
EnergyPro 5.1 by EnergySaft User Number: 6712 RunCode: 2013.02-20T}7:10:35 ID:
Pa e 4 of 46
PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF-1 R
Project Name
Building Type ® single Family ❑ Addition Alone
Date
Custom Residence for Desert Ring, LLC
1 ❑ Multi Family ❑ Existing+ Addition/Alteration
212012013
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
The DHW System Bradford White M-1-75S6BN is a non-NAECA large storage gas water heater. Verify DHW details.
The HVAC System HVAC 1 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have
a separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met.
HIGH MASS Design - Verify Thermal Mass: 776.0 fP Covered Slab Floor, 3.500" thick at Master Bedroom
HIGH MASS Design - Verify Thermal Mass: 220.0 fl' Exposed Slab Floor. 3.500" thick at Master Bedroom
The HVAC System HVAC 2a & 2b must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must
have a separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential A endix RA3.3 must be met.
HIGH MASS Design - ft Verify Thermal Mass: 190.0 ' Covered Slab Floor, 3.500"thick at Great RoomlKitcahon
N1GH MASS Design - Verify Thermal Mass: 1, 752, 0 ft Exposed Slab Floor, 3.500' thick at Great RoomlKitchen
HIGH MASS Design - Verify Thermal Mass: 815.0 IF Covered Slab Floor, 3.500" thick at Bedroom #2 & 3
HIGH MASS Design - Verify Thermal Mass: 124.0 ft2 Exposed Slab Floor, 3.500"thick at Bedroom #2 & 3
The DHW System Bradford White M-1-75SOBN is a non-NAECA large storage gas water heater. Verify DHW details.
The HVAC System HVAC 4 must serve only Living Areas. The non-Iosabis area between zones cannot exceed 40 sf and each zone must have a
se orate thermostat. In addition the air flow ulrements and fan watt draw r uiremenfs in Residential A endix RA3.3 must be met.
HIGH MA55 Design -Verify Them7al Mass: 375.0 ft' Exposed Slab Ffoar, 3.500" thick at Gym
HIGH MASS Design - Verify Thermal Mass.' 299.0 ft' Exposed Slab Floor, 3.500" thick at Garage
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF-4R form for each of the measures listed below for final to be given.
The Cooling System Carrier 24HCB636 / 56C VX070 includes credit for a 11.9 EER Condenser. A certified HERS rater must field verify the installation
of the correct Condenser
The HVAC System HVAC 1 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC i incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System 24ABC636 / 58CVX060 includes credit for a 12.5 EER Condenser. A certified HERS rater must field verity the installation of the
correct Condenser.
The HVAC System HVAC 2a & 2b incorporates HERS Verified Refrigerant Charge or Charge Indicator Display
The HVAC System HVAC 2a & 2b incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that
duct leakage meets the specified criteria.
The Cooling System Carrier 24HCB636 / 58CVX070 Includes credit fora 11.9 EER Condenser. A certified HERS rater must field verify the installation
of the correct Condenser.
The HVAC System HVAC 3 incorporates HERS Verified Refrigerant Charge ore Charge indicator Display.
The HVAC System HVAC 3 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Carrier 24HCB660 / 58CVX110 includes credit for a 11.9 EER Condenser. A certified HERS rater must field verify the installation
of the correct Condenser.
The HVAC System HVAC 4 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 4 Incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
Enem vPro 5.1 by Energ ySoft t/serNumbar: 6712 RunCade: 2013-02-20T17:10:35 ID: Page 5 of46
PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF-1 R
Project Name
Custom Residence for Desert Ring, LLC
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
212012013
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
HIGH MASS Design - Verify Thermal Mass: 375.0 ft2 Exposed Slab Floor, 3.500" thick at Guest Beddroom 1
HIGH MASS Design - Venfy Thermal Mass: 64.0 ft2 Exposed Slab Floor, 3.500" thick at Guest Bedroom 2
The Roof R-38 Roof Attic includes credit for a Radiant Barrier that is Continuous meeting eligibility and installation criteria as specified in Residential
A,opendix RA4.2.2.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF-4R form for each of the measures listed below for final to be given,
The Cooling System 24HCB624 / 58CVX070 includes credit for a 12.2 EER Condenser. A certified HERS rater must field verify the installation of the
correct Condenser.
The HVAC System HVAC 5 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 5 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
The Cooling System Carrier 24HCB660 / 58CVX110 includes credit for a 11.9 EER Condenser. A certified HERS rater must field verify the installation
of the correct Condenser.
The HVAC System HVAC 6 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display.
The HVAC System HVAC 6 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct
leakage meets the specified criteria.
FnemvPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-02-20T17:10:35 ID: Page 6 of 46
PERFORMANCE CERTIFICATE: Residential (Part 3 of 5)
CF-1 R
Project Name
Building Type m Single Family ❑ Addition Alone
Date
Custom Residence for Desert Ring, LLC
❑ Multi Family ❑ Existing+ Addition/Alteration
212012013
ANNUAL ENERGY USE SUMMARY
Standard Proposed Margin
TDV (kBtu/ft2-_yr)
Space Heating 5.85 4.78 1.07
Space Cooling 56.93 5496 1.96
Fans 11.45 1577 -4.31
Domestic Hot Water 4.64 2.98 1.67
Pumps 0.00 0.00 0.00
Totals 78.87 78.49 0.38
Percent Better Than Standard: 0.5 %
BUILDING COMPLIES - HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: (NE) 65 deg Ext. Walls/Roof Wall Area
Area
Number of Dwelling Units: 1.00 (NE) 2,395
397
Fuel Available at Site: Natural Gas (SE) Z407
295
Raised Floor Area: 81 (SKO 2,672
848
Slab on Grade Area: 4,990 (NM 2,567
203
Average Ceiling Height: 11.7 Roof 4,853
0
Fenestration Average U-Factor: 0.35 TOTAL:
1,743
Averse SHGC: 0.33 Fenestration/CFA Ratio:
23.6
REMARKS
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
The documentation author hereby certifies that the documentation is accurate and complete.
Documentation Author
4�
Company Scott Design and Title 24, Inc,
220/2013
Address 77-085 Michigan Drive Name Tim Scott
City/State/Zip Palm Desert Ca 92211 Phone (760) 200-4780 Signed
Date _
The individual with overall design responsibility hereby certifies that the proposed building design repre
nted in this set
of construction documents is consistent with the other compliance forms and worksheets, with the sp
i cations, and
with any other calculations submitted with this permit application, and recognizes that compliance u; g
uct design,
�g
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sfiali
require
installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
417-815
Company South West Concepts
Address 78-115 Calle Estado Name Stephen Nieto
City/State/Zip La Quinta, CA 92253 Phone (760) 564-4707 Signed License # Date
Ere Pro 5.1 by Enera Soft user Number: 6712 RunCode: 2013-02-20T17:10.35 ID.
Page 7 of 46
CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1 R
Project Name
Custom Residence for Desert Ring, LLC
Building Type O Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
212012013
OPAQUE SURFACE
DETAILS
Surface
Type
Area
U-
Factor
Insulatior
Azm
Tilt
Status
Joint Appendix
4
Location/Comments
Cavity
Exterior
Frame
Interior
Frame
Roof
996
0.025
R-38
45
0 New
4.2.1-A21
Master Bedroom #1
Wall
212
0.069
R-21
65
90
New
4.3.1-A6
Master Bedroom #1
Wall
192
0.069
R-21
155
90
New
4.3.1-A6
Master Bedroom #1
Wall
237
0.069
R-21
245
90
New
4.3.1-A6
Master Bedroom #1
Wall
535
0.069
1 R-21
335
90
New
4.3.1-A6
Master Bedroom #1
Slab
776
0.730
None
0 180
New
4.4.7-A1
Master Bedroom #1
Slab
220
0.730
1 None
0 180
New
4.4.7-A1
Master Bedroom #1
Roof
820
0.025
R-38
45
0 New
4.2.1-A21
Great Room/Kitchen
Wall
382
0.069
R-21
65
90
New
4.3.1-A6
Great Room/Kitchen
Wall
304
0.069
R-21
155
90
New
4.3.1-A6
Great Room/Kitchen
Wall
722
0.069
R-21
245
90
New
4.3.1-A6
Great Room/Kitchen
Door
21
1.450
None
245
90
New
4.5.1-A1
Great Room/Kitchen
Wall
289
0.069
R-21
335
90
New
4.3.1-A6
Great Room/Kitchen
Slab
190
0.730
None
0 180
New
4.4.7-A1
Great Room/Kitchen
Slab
1,752
0.730
None
0 180
New
4.4.7-A1
Great Room/Kitchen
Roof
80
0.025
R-38
45
0 New
4.2.1-A21
Bedroom #2 & 3
FENESTRATION
SURFACE
DETAILS
ID
Type
Area
U-Factor
SHGC
Azm
Status
Glazing Type
Location/Comments
1
Window
8.0
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Master Bedroom #1
2
Window
4.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Master Bedroom #1
3
Window
120.0
0.350
NFRC
0.33
NFRC
245
New Dual
Non Metal Tinted
Master Bedroom #1
4
Window
3.0
0.350
NFRC
0.33
NFRC
245
New Dual
Nan Metal Tinted
Master Bedroom #1
5 1
Window
9.0
0.350
NFRC
0.33
NFRC
335
New Dual
Non Metal Tinted
Master Bedroom #1
6
Window
9.0
0.350
NFRC
0.33
NFRC
335
New Dual
Non Metal Tinted
Master Bedroom #1
7
Wndow
9.0
0.350
NFRC
0.33
NFRC
335
New Dual
Non Metal Tinted
Master Bedroom #1
8
Window
4.0
0.350
NFRC
0.33
NFRC
335
New Dual
Non Metal Tinted
Master Bedroom #1
9
Wndow
8.0
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Great Room/Kitchen
10
Window
45.0
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Great Room/Kitchen
11
Window
54.0
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Great Room/Kitchen
12
Window
45.0
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Great Room/Kitchen
13
Window
22.5
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Great Room/Kitchen
14
Window
4.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Great Room/Kitchen
15
Window
120.0
0.350
NFRC
0.33
NFRC
245
New Dual
Non Metal Tinted
Great Room/Kitchen
16
Window
290.0
0.350
NFRC
0.33
NFRC
245
New Dual
Non Metal Tinted
Great Room/Kitchen
(1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-13 = Default Table from Standards, NFRC = Labeled Value
EXTERIOR
SHADING DETAILS
ID
Exterior Shade Tyne
SHGC
Window
Ove hang
Left Fin
Ri Iht Fin
-H-g-t7
Wd
Len
H t
LExt
RExt
Dist
Len
Hg t
(Dist
Len
H t
1
Bug Screen
0.76
2
Bug Screen
0.76
3
Bug Screen
0.76
4
Bug Screen
0.76
5
Bug Screen
0.76
6
Bug Screen
0.76
7
Bug Screen
0.76
8
Bug Screen
0.76
9
Bug Screen
0.76
10.01
17.0
22.0
0.11
22.0
22.0
10
Bug Screen
0.76
4.01
10.0
11.0
0.1
11.0
11.0
11
Bug Screen
0.76
4.01
6.7
12.0
0.1
12.0
12.0
12
Bug Screen
0.76
13
Bug Screen
0.76
14
Bug Screen
0.76
15
Bug Screen
0.76
16
Bug Screen
0.76�
EnerqyPio 5 1 by EnergySoff User Number: 6712 RunCode: 2013-02-20T17:10:35 ID: Page 8 of 46
CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1 R
Project Name
Custom Residence for Desert Ring, LLC
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
212012013
OPAQUE SURFACE
DETAILS
Surface
Type
Area
U-
Factor
Insulation
Azm
Tilt
Status
Joint Appendix
4
Location/Comments
Cavity
Exterior
Frame
I Interiorl
Frame
Wall
250
0.069
R-21
65
90
New
4.3.1-A6
Bedroom #2 & 3
Wall
313
0.069
,R-21
155
90
New
4.3.1-A6
Bedroom #2 & 3
Wall
123
0.069
.R-21
245
90
New
4.3.1-A6
.Bedroom #2 & 3
Wall
172
0.069
.R-21
335
90
New
4.3.1 A6
.Bedroom #2 & 3
Slab
815
0.730
.None
0 180
New
4.4.7-A1
.Bedroom #2 & 3
Slab
124
0.730
None
0 180
New
4.4.7-A1
.Bedroom #2 & 3
Roof
75
0.025
R-38
45
0 New
4.2.1-A21
G Garage/Guest 1
Wall
130
0.069
R-21
65
90
New
.4.3.1-A6
Gym/Garage/Guest 1
Wall
73
0.069
R-21
155
90
New
4.3.1-A6
G m/Gars e/Guest 1
Wall
131
0.069
R-21
245
90
New
4.3.1-A6
G m/Gars a/Guest 1
Wall
327
0.069
R-21
335
90
New
4.3.1-A6
Gym/Garage/Guest 1
Slab
375
0.730
None
0 180
New
4.4.7 Al
G m/Gars a/Guest 1
Roof
39
0.025
R-36
45
0 New
4.2.1-A21
G m/Gana e/Guest 1
Wall
130
0.069
R-21
65
90
New
4.3.1-A6
Gym/Garage./Guest 1
Wall
214
0.069
R-21
155
90
New
4.3.1-A6
G m/Gars a/Guest 1
Wall
66
0.069
R-21
245
90
New
4.3.1-A6
G m/Gars a/Guest 1
FENESTRATION
SURFACE
DETAILS
ID
Type
Area
U-Factor
SHGC
Azm
Status
Glazing Type
Location/Comments
17
'Wndow
10.0
0.350
NFRC
0.33
NFRC
245
New Dual
Non Metal Tinted
Great Room/Kitchen
18
'Wndow
48.0
0.350
NFRC
0.33
NFRC
245
New Dual
Non Metal Tinted
Great Room/Kitchen
19
'Window
10.0
0.350
NFRC
0.33
NFRC
2451
New Dual
Non Metal Tinted
Great Room/Kitchen
20
'Wndow
48.0
0.350
NFRC
0.33
NFRC
1551
New Dual
Non Metal Tinted
Bedroom #2 & 3
21
IWindow
8.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Bedroom #2 & 3
22
'Wndow
8.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Bedroom #2 & 3
23
'Window
48.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Bedroom #2 & 3
24
'Window
20.0
0.350
NFRC
0.33
NFRC
335
New Dual
Non Metal Tinted
Bedroom #2 & 3
25
'Wndow
40.0
0.350
NFRC
0.33
NFRC
335
New Dual
Non Metal Tinted
Bedroom #2 & 3
26
'Wndow
20.0
0.350
NFRC
0.33
NFRC
335
New Dual
Non Metal Tinted
Bedroom #2 & 3
27
Window
48.0
0.350
NFRC
0.33
NFRC
335
New Dual
Non Metal Tinted
Bedroom #2 & 3
28
Window
16.5
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Gym/Garage/Guest 1
29
IWindow
8.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Gym/Garaga/Guest 1
30
Window
12.6
0.350
NFRC
0.33
NFRC
2451
New dual
Non Metal Tinted
GymlGaragelGuest 1
31
Window
40.0
0.350
NFRC
0.33
NFRC
2451
New Dual
Non Metal Tinted
GymlGarage/Guest 1
32
Window
12.8
0.350
NFRC
0.33
NFRC
245
New Dual
Non Metal Tinted
Gym/Garage/Guest 1
(1) LI-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR
SHADING DETAILS
ID
Exterior Shade Type
SHGC
Window
Ove hang
Left Fin
Right Fin
H t
Wd
Len
HqA
LExt
RExt
Dist
Len
H t
Dist
Len
H t
17
Bug Screen
0.76
18
.Bug Screen
0.76
19
Bug Screen
0.76
20
Bug Screen
0.76
21
Bug Screen
0.76
22
Bug Screen
0.76
23
Bug Screen
0.76
24
Bug Screen
0.76
25
Bug Screen
0.76
26
Bua Screen
0.76
27
Bug Screen
0.76
28
Bug Screen
0.76
29
Bug Screen
0.76
30
Bug Screen
0.76
31
[Bug Screen
0.76
32
1Buq Screen
0.76
EnergyPro 5.1 by EnergySoft User Number. 6712 RunCode: 2013.02-20717.10:35 ID: Page 9 of46
CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1 R
Project Name Building
Custom Residence for Desert Ring, LLC
Type m Single Family ❑ Addition Alone Date
❑ Multi Family ❑ Existing+ Addition/Alteration 1212012013
OPAQUE SURFACE DETAILS
Surface
Type
Area
U-
Factor
Insulation
Azm
Tilt
Status
Joint Appendix
4
Location/Comments
Cavit
Exterior
Frame
Interior]
Frame.
Slab
299
0.730
None
0
180
New
4.4.7-A1
GVm/Gars e/Guest 1
Roof
547
0.025
R-38
45
0 New
4.2.1-A21
Gym/Gana a/Guest 1
Wall
210
0.069
R-21
65
90
New
4.3.1-A6
G m/Gara e/Guest 1
Wall
227
0.069
R-21
155
90
New
4.3.1-A6
Gym/Garage/Guest 1
Wall
204
0.069
R-21
245
90
New
4.3.1-A6
G m/Gara a/Guest 1
Wall
246
0.069
R-21
335
90
New
4.3.1-A6
G mlGara elGuesl 1
Slab
375
0.730
None
0
180
New
4.4.7-A1
G m/Gara e/Guest 1
Roof
465
0.025
R-38
45
0 New
4.2.1-A21
Guest Bedroom 2
Wall
199
0.069
R-21
65
90
New
4.3.1-A6
Guest Bedroom 2
Wall
351
0.069
R-21
155
90
New
4.3.1-A6
Guest Bedroom 2
Wall
195
0.069
R-21
245
90
New
4.3.1-A6
Guest Bedroom 2
Wall
355
0.069
R-21
335
90
New
4.3.1-A6
Guest Bedroom 2
Floor
81
0.046
R-13
0
180
New
4.4.1-A3
Guest Bedroom 2
Slab
64
0.730
None
0
160
New
4.4.7-A1
Guest Bedroom 2
Roof
1,8311
0.025
.R-38
451
0 New
4.2.1-A21
Master Bedroom 2
Wall
486
0.069
R-21
65
90
New
4.3.1-A6
Master Bedroom 2
FENESTRATION
SURFACE
DETAILS
ID
Type
Area
U-Factor
SHGC
Azm
Status
Glazing Type
Location/Comments
33
endow
8.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Gym/Garage/Guest 1
34
IWindow
6.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
GymlGaragelGuest 1
35
'Window
40.0
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
G m/Garage/Guest 1
36
'LMndow
11.3
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
GymlGarage/Guest 1
37
'Window
11.3
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Gym/Garage/Guest 1
38
Yl<ndow
12.8
0.350
NFRC
0.33
NFRC
245
New Dual
Non Metal Tinted
GymlGarage/Guest 1
39
V><ndow
20.0
0.350
NFRC
0.33
NFRC
245
New Dual
Non Metal Tinted
Gym/Garage/Guest 1
40
Window
12.8
0.350
NFRC
0.33
NFRC
245
New Dual
Non Metal Tinted
Gym/Garage/Guest 1
41
Window
4.0
0.350
NFRC
0.33
NFRC
335
New Dual
Non Metal Tinted
GymlGarage/Guest 1
42
Window
18.0
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Guest Bedroom 2
43
Window
18.0
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Guest Bedroom 2
44
Window
24.0
0.350
NFRC
0.33
NFRC
155
New
Dual Non Metal Tinted
Guest Bedroom 2
45
Window
40.0
0.350
NFRC
0.33
NFRC
245
New
Dual Non Metal Tinted
Guest Bedroom 2
46
Window
10.0
0.350
NFRC
0.33
NFRC
335
New
Dual Non Metal Tinted
Guest Bedroom 2
47
Window
10.0
0.350'
NFRC
0.33
NFRC
335
New
Dual Non Metal Tinted
Guest Bedroom 2
48
Window
24.0
0.350
NFRC
0.33
NFRC
65
New
Dual Non Metal 'tinted
Master Bedroom 2
(1 ) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2j SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR
SHADING DETAILS
ID
Exterior Shade T e
SHGC
Window
Overhan
Left Fin
Right Fin
H t
Wd
Len
H t
LExt
RExt
Dist
Len
Hot
Dist
Len
H t
33
,Bug Screen
0.76
34
,Bug Screen
0.76
35
Bug Screen
0.76
36
BugScreen
0.76
37
Bug Screen
0.76
38
BugScreen
0.76
39
Bug Screen
0.76
40
Bug Screen
0.76
41
Bug Screen
0.76
42
Bug Screen
0.76
43
Bug Screen
0.76
44
Bug Screen
0.76
45
Bu Screen
0.76
46
Buo Screen
0.76
47
Bug Screen
0.76
48
IBug Screen
0.76
Ene Pro5.1 6 Ens Soft User Number: 6712 RanCode: 2013.02-20T17':10:35 ID: Page 10of46
CERTIFICATE OF COMPLIANCE: Residential (Part 4 of 5) CF-1 R
Project Name
Custom Residence for Desert Ring, LLC
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
212012013
OPAQUE SURFACE DETAILS
Surface
Type
I Area
U-
Factor
Insulation
Azm
Tilt
Status
Joint Appendix
4
Location/Comments
Cavity
Exterior
Frame
Interiorl
Frame
Wall
438
0.069
R-21
155
90
New
4.3.1-A6
Master Bedroom 2
Wall
124
0.069
R-21
245
90
New
4.3.1-A6
Master Bedroom 2
Wall
440
0.069
R-21
335
90
New
4.3.1-A6
Master Bedroom 2
1
FENESTRATION
SURFACE
DETAILS
ID
Type
Area
U-Factor'I
SHGC
Azm
Status
Glazing Type
Location/Comments
49
Window
48.0
0. 3501
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Master Bedroom 2
50
Window
24.0
0.3501
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Master Bedroom 2
51
Window
32.0
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Master Bedroom 2
52
Window
8.0
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Master Bedroom 2
53
Window
8.0
0.350
NFRC
0.33
NFRC
65
New Dual
Non Metal Tinted
Master Bedroom 2
54
Window
4.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Master Bedroom 2
55
Window
4.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Master Bedroom 2
56
Window
42.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Master Bedroom 2
57
Window
16.0
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Master Bedroom 2
58
Window
mo
0.350
NFRC
0.33
NFRC
155
New Dual
Non Metal Tinted
Master Bedroom 2
59
Window
96.0
0.350
NFRC
0.33
NFRC
245
New Dual
Non Metal Tinted
Master Bedroom 2
60
Window
10.0
0.350
NFRC
0.33
NFRC
335
New Dual
Non Metal Tinted
Master Bedroom 2
61
Window
10.0
0.350
NFRC
0.33
NFRC
335
New Dual
Non Metal Tinted
Master Bedroom 2
(1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type
SHGC
Window
Ove hang
Left Fin
Right Fin
Hcjt
Wd
Len
Hat
LExt
RExt
Dist
Len
H t
Dist
Len
H t
49
Bug Screen
0.76
50
Bug Screen
0.76
51
Bug Screen
0.76
52
Bug Screen
0.76
53
Bug Screen
0.76
54
Bug Screen
0.76
55
Bug Screen
0.76
56
Bug Screen
0.76
57
Bug Screen
0.76
58
Bug Screen
0.76
59
Bug Screen
0.76
60
Bug Screen
0.76
61
Bug Screen
0.76
F-�
EnergyPro6lbyEnergySoft User Number: 6712 RunCode: 2013.02.20T17:10:35 ID: Page 11 of 46
CERTIFICATE OF COMPLIANCE: Residential (Part 5 of 5) CF-1 R
Project Name
Custom Residence for Desert Ring, LLC
Building Type ❑ Single Family ❑ Addition Alone Date
❑ Multi Family ❑ Existing+ Addition/Alteration 212012013
BUILDING ZONE INFORMATION
System Name
Zone Name
Floor Area 'ft')
Volume
Year Built
New
Existing
Altered
Removed
HVAC 1 Master
Bedroom
996
10,956
HVAC 2a & 2b Great
RoomR<itchen
1,942
31.072
HVAC 3 Bedroom
#2 & 3
939
9,390
HVAC 4 Gym
375
3,750
Garage
299
2.990
Guest
Berdroom 1
547
5,470
HVAC 5 Guest
Bedroom 2
465
4,650
HVAC 6 Master
Bedroom 2
1,831
18,310
Totals
7,3941
0
0
0
HVAC SYSTEMS
System Name
Qty.
Heating Type
Min. Eff.
Cooling Type
Min. Eff.
Thermostat T De
Status
HVAC 1
1
Central Furnace
80% AFUE
Split Air Conditioner
15.0 SEER
Setback
New
HVAC 2a & 2b
2
Central Furnace
80% AFUE
Split Air Conditioner
15.2 SEER
Setback
New
HVAC 3
1
Central Furnace
80% AFUE
Split Air Conditioner
15.0 SEER
Setback
New
HVAC 4
1
Central Furnace
80% AFUE I
Split Air Conditioner
15.0 SEER
Setback
New
HVAC 5
1
Central Furnace
80% AFUE
Split Air Conditioner
15.5 SEER
Setback
New
HVAC DISTRIBUTION
System Name
Heating
Cooling
Duct Location
Duct
R-Value
Ducts
Tested?
Status
HVAC 1 Ducted
Ducted
Attic, Ceiling Ins, vented
8.0
m
New
HVAC 2a & 2b Ducted
Ducted
Attic, Ceiling Ins, vented
8.0
m
New
HVAC 3 Ducted
Ducted
Attic, Ceiling Ins, vented
8.0
El
New
HVAC 4 Ducted
Ducted
Attic, Ceiling Ins. vented
1 8.01
IZI
New
HVAC 5 1 Ducted
Ducted
Attic, Ceiling Ins, vented
8.0
m
New
WATER HEATING SYSTEMS
S stem Name
Qty.
Type
Distribution
Rated
Input
(Btuh)
Tank
Cap.
(gal
Energy
Factor
or RE
Standby
Loss or
Pilot
Ext.
Tank
Insul. R-
Value
Status
Bradford White M-1-75S6B
1
Large Gas
All Pipes Ins
76,000
75
0.82
0.00 %
0.0
New
Bradford White M-1-706B
1
1 Large Gas
I All Pipes Ins
76,000
75
0.82
0.00 %
0.0
New
1
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONIC
HEATING SYSTEM
PIPING
Control
Hot Water Piping Length
ft
o
¢
System Name
Pipe
Length
Pipe
Diameter
Insul.
Thick.
Q
[HP
Plenum
Outside
Buried
FnetgyPro 5.1 by EnergySoft User Number: 6712 RunCade: 2013-02-20717:10:35 ID: Page 12 of 46
CERTIFICATE OF COMPLIANCE: Residential (Part 5 of 5) CF-1 R
Project Name
Custom Residence for Desert Ring, LLC
Building Type ❑ Single Family ❑ Addition Alone Date
❑ Multi Family ❑ Existing+ Addition/Alteration 1212012013
BUILDING ZONE INFORMATION
Svstem Name
Zone Name
Floor Area
Volume
Year Built
New
Existing
Altered
Removed
Totals
1 7,3941
0
0
0
HVAC SYSTEMS
System Name
0 .
Heating Type
Min. Eff.
Cooling Type
Min. Eff.
Thermostat Type
Status
HVAC 6
1
Central Furnace
80% AFUE
Split Air Conditioner
15.0 SEER
Setback
New
HVAC DISTRIBUTION
S stem Name
Heating
Cooling
Duct Location
Duct
R-Value
Ducts
Tested?
Status
HVAC 6 Ducted
Ducted
Attic, Ceiling Ins, vented
8.0
m
New
WATER HEATING SYSTEMS
Svstem Name
City.
Ty2e
Distribution
Rated
Input
(Btuh)
Tank
Cap.
(al)
Energy
Factor
or RE
Standby
Loss or
Pilot
Ext.
Tank
Insul. R-
Value
Status
f
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONIC
HEATING SYSTEM
PIPING
Control
Hot Water Piping Length
ft
0
i6
v�i
Q
System Name
Pipe
Len th
Pipe
Diameter
Insul.
Thick.
City.
HP
Plenum
Outside
Buried
EnergyPro 5.1 by EnerqySoft User Number. 6712 RunCode: 2013.02-20T17:10:35 ID Page 13 of 46
MANDATORY MEASURES SUMMARY: Residential (Page 1 of 3 MF-1 R
Project Name Date
Custom Residence for Desert Ring, LLC 212012013
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF-1 R, CF-1 R-ADD, or CF-
I R-ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF-1 R
Form with plans.
Building Envelope Measures:
116 a 1: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U-Factor, certified Solar Heat Gain
Coefficient (SHGC), and infiltration that meets the requirements of 10-111 (a).
117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
118 a : Insulationspecified or installed meets Standards for Insulating Materlal. Indicate type and include on CF-6R Form.
§118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the
installation of a Cool Roof is specified on the CF-1 R Form.
* 150 a : Minimum R-19 insulation in wood -frame ceiling orequivalent U-factor.
150 b : Loose fill insulation shall conform with manufacturer's installed design labeled R-Value.
* 150 c : Minimum R-13 insulation in wood -frame wall orequivalent U-factor.
* 150 d : Minimum R-13 insulation in raised wood -frame floor orequivalent U-factor.
150 f : Air retarding wrap is tested, labeled, and installed according to ASTM E1677-95 2000 when specified on the CF-1 R Form.
1 50: Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150(I): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150 a 1A: Mason or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of § 1 13c 5.
§115. Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
150 h : Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
150 i : Heating systems are equipped with thermostats that meet the setback requirements of Section 1 12c .
§150(j)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
with insulation having an installed thermal resistance of R-12 or greater,
§1500)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the
tank.
§150(j)2: First 5 feet of hot and cold water pipes closest to water heater tank, non-recfrculating systems, and entire length of
recirculating sections of hot water pipes are insulated per Standards Table 150-B.
§1500)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot
water tank shall be insulated.to Table 150-B and Equation 150-A.
§150(j)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table
123-A.
150(')3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§1500)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned s ace.
150 ' 4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification corporation.
EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2013-02-20T17:10:35 ID: Page 14 of 46
MANbATORY MEASURES SUMMARY: Residential (Page 2 of 3) MF-1 R
Project Name
Date
Custom Residence for Desert Ring, LLC
1212012013
§150(m)1: All air-distrlbution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross -sectional area
of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150 m 7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150(m)10: Flexible ducts cannot have porous inner cores.
§150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
required in Section 4 of that Standard.
Pool and Spa Heating Systems and E ui ment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on -off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating or a pilot light.
§114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
114 b 2: Outdoor pools ors as that have a heat um or gas heater shall have a raver.
§114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
150 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150
Residential LiShting Measures:
§150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is not a low efficacy luminaire asspecified by §150(k)2.
154(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d).
§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz.
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
medium screw -base socket.
150 k 6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k).
150 k 7: All switching devices and controls shall meet the requirements of §150(k)7.
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting In kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system and all permanently installed
luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a
manual -on occupant sensor.
§150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
EnergyPro 5.1 by EnergySoff User Number: 6712 RunCode: 2013-02-20T17:10:35 ID: Page 15 of 46
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3) MF-1 R
Project Name
Date
Custom Residence for Desert Ring, LLC
212012013
§150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a
manual -on occupancy sensor.
§i50(k)11: Permanently installed luminaires tocated in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently Installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting In detached storage building less
than 1000 square feet located on a residential site is not req uired to cam I y with 5150 k 11.
§150(k)12: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)f 3: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exceptions to §150(k)13 may be controlled by a temporary override switch which bypasses the motion
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be high efficacy luminaires.
§150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more than five watts of power as determined according to §130d).
§150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
requirements of Sections 130, 131, 134, and 146.
§150(k)16: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided
that they are controlled by an occu ant sensors certified to comeIy with the applicable requirements of 119.
EnergyPro 5.1 by EnergySoft User Number.' 6712 RunCode: 2013-02-20T17:10.35 ID: Page 16 of 46
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Custom Residence for Desert Ring, LLC
Date
2/20/2013
System Name
HVAC 1
Floor Area
996
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 537
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output perSystem
71,000
11,069
1,035
240
14,305
Total Output (Btuh)
71,000
0
Output Btuh/s ft
71.3
522
546
Cooling System
0
01
Output perSystem
35,200
0
0
0
0
Total Output (Btuh)
35,200
1,675
1,035
-1.675
Total Output(Tons)
2.9
i 522tj
546
Total Output (Btuh/s ft)
35.3
Total Output s ft/Ton
339.5
1 13,787
13,722
Air System
CFM perSystem
1,200
HVAC EQUIPMENT SELECTION
Airflow cfm
1,200
Carrier 24HCB636 / 58CVX070
27,450
3,191
71,000
Airflow cfm/s ft
1.20
Airflow (cfm/Ton)
409.1
Outside Air %
0.0 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
1 27,450
3,191
1 71.000
Jan 1 AM
Outside Air cfm/s ft
0.00
Note: values above given at ARI conditions
Aug 3 PM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
70 of
70 OF 125 IF 126 OF
0
Heating Coil Supply Fan
1,200 cfm
126 IF
FR6*'A
70 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak)
112/78OF
Outside Air
0 cfm
78164 IF
78/64°F 57/56°F 58156°F
771 n
Cooling Coil Supply Fan 59 / 56 OF
1,200 cfm
45.4 % ROOM
—z
78 / i 64 OF
EnergyPro 5.1 by EnergySoft
User Number: 6712 RunCode: 2013-02-20T17:10:35 ID:
Page 17 of 46
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Custom Residence for Desert Ring, LLC
Date
2/20/2013
System Name
HVAC 2a & 2b
Floor Area
1,942
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
2
COIL
CFM
Total Room Loads 1,482
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output perSystem
51,000
29,837
2,028
650
28,394
Total Output Btuh
102,000
0
Output (Btuh/s ft)
52.5
1,406
1,084
Cooling System
0
0
Output perSystem
35,500
0
0 0
0
Total Output Btuh
71,000
4,960
2,028
-4.960
Total Output (Tons)
5.9
j 1,4061
1,084
Total Output Btuh/s ft
36.6
Total Output s ft/Ton
328.2
37,609
25,602
Air System
CFM perSystem
1,200
HVAC EQUIPMENT SELECTION
Airflow cfm
2,400
24ABC636 / 58CVX060
56,090
5,567
102,000
Airflow cfm/s ft
1.24
Airflow (cfm/Ton
405.6
a
Outside Air (/o)
0.0 %
Adjusted System Output
Total Ad
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
56,090
5,567 102,000
Aug 3 PM I Jan 1 AM
Outside Air cfm/s ft
0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCH ROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm Ar
70 OF
70OF 110 °F 111 OF
Heating Coil Supply Fan 111 OF
2,400 cfm
ROOM
70 OF
l
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
1121
Outside Air
0 cfm
79 / 64 OF
79164 OF 57 / 55 OF 59 / 56 OF
-
Cooling Coil Supply Fan 59 / 56 °F
2,400 cfm �y
44.8 % ROOM
78 / 63 OF
EnergyPro 5.1 by EnergySoR
User Number., 6712 RunCode: 2013-02-20T17:10:35 ID:
Page 18 of 46
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Custom Residence for Desert Ring, LLC
Date
2/20/2013
System Name
HVAC 3
Floor Area
939
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 534
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output per System
71,000
10,954
1,187
213
12,737
Total Output (Btuh)
71,000
0
Output Btuh/s ft
75.6
516
486
Cooling System
0
0
output per System
35,200
0
0
0
0
Total Output Btuh
35,200
1,675
516
13,661
1,187
-1,675
Total Output(Tons)
2.9
486
Total Output (Btuh/s ft)
37.5
Total Output s ft/Ton
320.1
12,034
Air System
CFM per System
1,200
HVAC EQUIPMENT SELECTION
Airflow cfm
1,200
Carrier 24HCB636 / 58CVX070
27,336
3,350
71,000
Airflow cfm/s ft
1.28
Airflow (cfm/Ton
409.1
Outside Air %
0.0 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
I TIME OF SYSTEM PEAK
27,336
31350
71,000
Jan 1 AM
Outside Air cfm/s ft
0.00
Note: values above given at ARI conditions
Aug 3 PM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air Ok
0 cfm
70 of
70 OF 125 °F 127 OF
Heating Coil Supply Fan
126 OF
1,200 cfm
ROt7M
70 °F
COOLING SYSTEM PSYCH ROM ETICS Airstream Temperatures at Time of Cooling Peak)
112/78OF
Outside Air
0 cfm
78 / 64 OF
78/64OF 57/56OF 58/56OF
Q
Cooling Coil Supply Fan 59 / 56 OF
1,200 cfm
45.7 % ROOM
78 / 64 OF
f
Energ Pro5.1 by EnergySoft
User Number.- 6712 RunCode: 2013-02-20T17:10:35 ID:
Page 19 of 46
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Date
Custom Residence for Desert Ring, LLC
2/20/2013
System Name
Floor Area
HVAC 4
1,221
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 786
Return Vented Lighting
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output perSystem
110,000
14,249
1.223
386
21,490
Total Output (Btuh)
110,000
0
Output Btuh/s ft
90.1
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
671
820
Cooling System
0
0
Output erSystem
55,500
0
0
0
0
Total Output (Btuh
55,500
2,978
-2.978
Total Output (Tons)4.6
Supply Air Ducts
671
820
Total Output (Btuh/s ft)
45.5
Total Output s ft/Ton
264.0
TOTAL SYSTEM LOAD
18,570
1,223
20.153
Air System
CFM perSystem
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24HCB660 / 58CVX110
40,570
8,725
110,000
Airflow cfmis ft
1.64
Airflow (cfm/Ton)
432.4
Outside Air %
0.0 %
Total Adjusted System Output 40,570
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK r
8,725
Aug 3 PM
1 110,000
Jan 1 AM
Outside Air cfm/s ft
0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
70 OF 121 OF 123 OF
Q'
Outside Air
0 cfm
Heating Coil Supply Fan
122 OF
2,000 cfm
['"R'.........'
OOM
70 OF
44
70 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Conlin Peaky
112/78IF
78/65OF 59/58OF 61/59OF
Outside Air
0 cfm
Cooling Coil Supply Fan
61 159 °F
2,000 cfm
49.6
% ROOM
78 165 IF
78165 °F
4 :01,
FTA
EnergyPro 5.1 by EnergySoft
User Number: 6712 RunCode: 2013-02-20T17:10:35 ID:
Page 20 of 46
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Custom Residence for Desert Ring, LLC
Date
2/20/2013
System Name
HVAC 5
Floor Area
465
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 402
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
I CFM
Sensible
Output perSystem
71,000
7,779
590
94
8,428
Total Output (Btuh)
71,000
0
Output Btuh/s ft
152.7
367
322
Cooling System
0
0
Output perSystem
22,800
0
0
0
0
Total Output (Btuh)
22,800
995
590
-995
Total Output(Tons)
1.9
367
322
Total Output Btuh/s ft)
49.0
Total Output s ft/Ton
244.7
1 9,507
8,077
Air System
CFM perSystem
800
HVAC EQUIPMENT SELECTION
Airflow cfm
800
24HCB624 / 58CVX070
17,210
2,864
71,000
Airflow cfm/s ft
1.72
Airflow Wrn/Ton)
421.1
Outside Air %
0.0 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
17,210
2,864
71,000
Jan 1 AM
Outside Air cfm/s ft
0.00
Note: values above given at ARI conditions
Aug 3 PM
HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
70 OF
70 OF 153 IF 154 IF
Heating Coil Supply Fan
154 OF
800 cfm ......................
ROt7M
70 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
112/78OF
Outside Air
0 cfm
78164 IF
78/64°F 58/57°F 59158°F
Cooling Coil Supply Fan 60 f 5.3 - F
800 cfm
47.7 % ROOM W
_
EnergyPro 5.1 by EnergySoff
User Number: 6712 RunCode: 2013-02-20T17:10:35 ID: Page 21 of 46
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Custom Residence for Desert Ring, LLC
Date
2/20/2013
System Name
HVAC 6
Floor Area
1,831
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,137
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output perSystem
110,000
20,145
1,735
320
17,851
Total Output Btuh
110,000
0
Output Btuh/s ft
60.1
949
681
Cooling System
0
0
Output perSystem
55,500
0
0
0
0
Total Output Btuh
55,500
2,978
1.735
-2,978
Total Output (Tons)
4.6
949
681
Total Output Btuh/s ft
30.3
Total Output s ft/Ton
395.9
25,021
16,236
Air System
CFM perSystem
2,000
HVAC EQUIPMENT SELECTION
Airflow cfm
2,000
Carrier 24HCB660 / 58CVX110
40,304
9,208
110,000
Airflow cfm/s ft
1.09
Airflow cfm/Ton)
432.4
Outside Air (%)
0.0 %
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
40,304
9,208 110,000
Aug 3 PM Jan 1 AM
Outside Air cfm/s ft
0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCH ROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF
Outside Air
0 cfm
70 of
70 OF 121 OF 123 OF
Heating Coil Supply Fan
122 IF
2,000 cfm
ROOM
70 OF
COOLING SYSTEM PSYCHROMETICS (Airstream Temperatures at Time of Cooling Peak
112/78OF
Outside Air
0 cfm
78 / 65 OF
78/65OF 60/58OF 61/59OF
IJ
Cooling Coil Supply Fan 61 159 OF
2,000 cfm
50.3 % ROOM
78165 °F
EnergyPro 5.1 by EnergySoft
User Number: 6712 RunCode: 2013-02-20T17.10:35 ID:
Page 22 of 46
ROOM LOAD SUMMARY
Project Name
Custom Residence for Desert Ring, LLC
Date
212012013
System Name
HVAC 1
Floor Area
996
ROOM LOAD SUMMARY
ROOM
COOLING PEAK
COIL COOLING
PEAK
COIL HTG.
PEAK
Zone Name
Room Name
Mult.
CFM
Sensible
Latent
CFM
Sensible
Latent
CFM
Sensible
Master Bedroom #1
Master Bedroom
1
537
11,069
1,035
537
11,069
1,035
240
14,305
PAGE TOTAL 1 5371 11,0691.035 240 14,305
TOTAL 1 537 11,069 1,035 240 14,305
' Total includes ventilation load for zonal systems.
Enera Pro 5.1 by EneruvSoft User Number: 6712 RunCode: 2013-02-20T17:10:35 ID: Page 23 of 46
M LOAD SUMMARY
Project Name Date
Custom Residence for Desert Ring, LLC 212012013
System Name Floor Area
HVAC 2a & 2b 1,942
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible I Latent CFM Sensible Latent CFM Sensible
GreatRoom/Kitchen GreatRoom/Kitchen 1 1,482 29,837 2,028 1,482 2.9,8371 2,028 650 28,394
PAGE TOTAL
TOTAL*
1,462
29.637
2,028
650
28,394
1,482
29,837
2,028
650
28,394
EnergyPro 5 1 by EnergySoft User Number. 6712 Run Co de: 2013-02-24T17:10:35 ID: Page 24 of 46 1
ROOM LOAD SUMMARY
Project Name Date
Custom Residence for Desert Ring, LLC 212012013
System Name Floor Area
HVAC 3 939
ROOM LOAD SUMMARY
Zone Name Room Name
Bedroom #2 & 3 Bedroom #2 & 3
Total includes ventilation load for zonal
FnemyFro 5.1 by EneryySaR User N
ROOM COOLING PEAK
Mult. CFM Sensible Latent
1 534 10,954 1,187
PAGE TOTAL
TOTAL*
2 RunCode:2013.02-20T17:10:35
COIL COOLING PEAK
CFM Sensible I Latent
5341 10,9541 1,18
COIL HTG. PEAK
CFM I Sensible
2131 12,737
534
10,954
1,187
213
12,737
534
10,954
1,187
213
12,737
ROOM LOAD SUMMARY
Project Name Date
Custom Residence for Desert Ring, LLC 212012013
System Name Floor Area
HVAC 4 1,221
ROOM LOAD SUMMARY
ROOM COOLING PEAK I
COIL COOLING PEAK
COIL HTG.
PEAK
Zone Name
Room Name
Mult.
CFM
Sensible
Latent
CFM
Sensible I
Latent
CFM
Sensible
Gym/Garage/Guest 1
Gym
1
271
4,912
314
271
4,912
314
129
7,189
Garage
1
108
1,964
251
108
1,964
251
90
4,994
Guest Berdroom 1
1
407
7,373
658
407
7,373
658
167
9,306
PAGE TOTAL
TOTAL"
786
14,249 1,223
386
21.490
786
14,249 1,223
386
21.490
Total includes ventilation load for zonal systems.
Ene Pm 5.1 by EnerqVScift User Number: 5712 Run Code: 2013-02-20 T1 7:10:35 ID: F'a a 26 of 46
ROOM LOAD SUMMARY
Project Name
Custom Residence for Desert Ring, LLC
Date
212012013
System Name
HVAC 5
Floor Area
465
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK COIL HTG. PEAK
Zone Name
Room Name
Mult.
CFM I
Sensible
Latent
CFM
Sensible Latent CFM Sensible
Guest Bedroom 2
Guest Bedroom 2
1
402
7, 779
590
402
7,779 590 94 8,428
PAGE TOTAL 1 4021 94 8,428
TOTAL 1 402 7,779 590 94 8,428
* Total includes ventilation load for zonal systems.
EnerqyPm 5.1 b y En erg Soft User Number., 6712 Run Co de: 2013-02.20T17:10:35 ID: Page 27 of 46
ROOM LOAD SUMMARY
Project Name Date
Custom Residence for Desert Ring, LLC 212012013
HVAC 6 1 1, 831
ROOM LOAD SUMMARY
ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK
Zone Name Room Name Mult. CFM I Sensible I Latent CFM I Sensible I Latent CFM I Sensible
Master Bedroom 2 Master Bedroom 2 1 1,1371 20,1451 1, 735 1,1371 20,1451 1, 735 320 17, 851
PAGE TOTAL
TOTAL*
1,137
20,145
1.7351
320
17,851
1,137
20,145
1,735
320
17,851
* Total Includes ventilation load for zonal systems.
EnarqyPtip 5.1 by EnergySoft User Number, 6712 RunCode: 2013-02.20T77:10.35 ID: Page 28 of 46
ROOM HEATING PEAK LOADS
Project Name Date
Custom Residence for Desert Ring, LLC 212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master Bedroom
Floor Area 996.0 ftz
Indoor Dry Bulb Temperature 70 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U-Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT OF
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
44
Btu/hr
R-38 Roof Attic
996.0
0.0250
44
1,096
R-21 Wall
1,176.0
0.0690
44
3,570
Dual Non Metal Tinted
166.0
0.3500
44
2,556
Slab -On -Grade
perm = 118.0
0.7300
44
3,790
Items shown with an asterisk (`) denote conduction
Infiltration:[ 1.00 X
Schedule Alr Sensible
Fraction
through an interior surface
1.064 X 996 X
Area
another room
11.00 X 0.385
Height ACH
Page Total
/ 60 ] X
AT
11,012
= 3,292
14.305
TOTAL HOURLY HEAT LOSS FOR
ROOM
EnergyPro 5.1 by EnergySott User Number: 6712 RunCode. 2013.02-20T17:10:35 ID: Pace 29 of 46
ROOM HEATING PEAK LOADS
Project Name Date
Custom Residence for Desert Ring, LLC 212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great Room/Kitchen
Floor Area 1,942.0 ft2
Indoor D Bulb Temperature 70 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
1.064
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U-Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT *F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
44
Btulhr
R-38 Roof Attic
820.0
0.0250
44
902
R-21 Wall
1,696.9
0.0690
44
5,152
Dual Non Metal Tinted
656.5
0.3500
44
10,110
Wood Door
20.6
1.4500
44
1,314
Slab -On -Grade
perim = 140.0
0.7300
44
4,497
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X
Schedule Air Sensible
Fraction
through an Interlor surface
X 1,942 X
Area
another room
16.00 X 0.265
Height ACH
Page Total
/ 60 X
AT
21,975
= 6,419
TOTAL HOURLY HEAT LOSS FOR ROOM 28,394
EnargyPro 5.1 by EnergySoft User Number. 6712 RunCode: 2013-02-20T17:10.35 ID., Page 30 of 46
ROOM HEATING PEAK LOADS
Project Name
Custom Residence for Desert Ring, LLC
Date
212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Bedroom #2 & 3
Floor Area 939.0 ftz
Indoor Dry Bulb Temperature 70 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
x
x
x
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
to
Ceiling
U-Value
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
AT OF
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
44
Btu/hr
R 36 Roof Attic
80.0
0.0250
44
88
R-21 Wall
658.0
0.0690
44
2,605
Dual Non Metal Tinted
240.0
0.3500
44
3,696
Slab -on -Grade
perim = 101.0
0.7300
44
3,244
Items shown with an asterisk (") denote conduction
Infiltration:[ 1.00 x 1.064
Schedule Air Sensible
Fraction
through an interior surface
x 939 x
Area
another room
10.00 x 0.424
Heigh[ ACH
Page Total
/ 60 ] X
AT
9,633
= 3,104
TOTAL HOURLY HEAT LOSS FOR ROOM 12,737
EnergyPro 5.1 by EnergySaft User Number: 6712 RunCode: 2013-02-20T17:10:35 ID: Page 31 of 46
ROOM HEATING PEAK LOADS
Project Name
Custom Residence for Desert Ring, LLC
Date
212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name GYM
Floor Area 375.0 ftZ
Indoor Dry Bulb Temperature 70 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
1.064
Area
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
to
Ceiling
U-Value
X
X
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
AT OF
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
44
Btu/hr
P-35 Roof Attic
75.0
0.0250
44
83
R-21 Wall
660.9
0.0690
44
2,006
Dual Non Metal Tinted
90.1
0.3500
44
1,388
Slab -On -Grade
perim = 77.0
0.7300
44
2,473
Items shown with an asterisk (") denote conduction
Infiltration:[ 1.00 x
Schedule Air Sensible
Fraction
through an interior surface
x 375 x
Area
another room
10.00 x 0.424
Height ACH
Page Total
/ 60 ] X
AT
5,950
= 1,240
TOTAL HOURLY HEAT LOSS FOR ROOM 7,189
Energ Pro 5.1 by EnergySoft User Number: 6712 RunCode: 3013.02-20T17:10:35 ID: Page 32 of 46
ROOM HEATING PEAK LOADS
Project Name Date
Custom Residence for Desert Ring, LLC 212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Garage
Floor Area 299.0 ft2
Indoor Dry Bulb Temperature 70 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Celling
U-Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT OF
Btu/hr
R-38 Roof Attic
39.0
0.0250
44
= 43
R-21 Wall
409.6
0.0690
44
= 1,244
Dual Non Metal Tinted
16.0
0.3500
44
= 246
Slab -On -Grade
perim = 77.0
0.7300
44
= 2,473
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
4,006
44 4 988
Items shown with an asterisk (") denote conduction
Infiltration:[ 1.00 X [711064
Schedule Air Sensible
Fraction
through an interior surface
X 299 X
Area
another room
10.00 X 0.424
Height ACH
Page Total
/ 60 ] X
AT
TOTAL HOURLY HEAT LOSS FOR ROOM 4.994
FnRmvPrn 5.1 by EneravSoft User Number. 6712 RunCode: 2013-02.20T17:10:35 ICJ: Page 33 of 46
ROOM HEATING PEAK LOADS
Project Name
Custom Residence for Desert Ring, LLC
Date
212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Berdroom 1
Floor Area 547.0 f'
Indoor Dry Bulb Temperature 70 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
1.064
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
1
Ceiling
U-Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT *F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
44
Btu/hr
R-38 Roof Attic
547.0
0.0250
44
602
R-21 Wall
887.8
0.0690
44
2,695
Dual Non Metal Tinted
112.2
0.3500
44
1.728
Slab -On -Grade
perim = 77.0
0.7300
44
2,473
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X
Schedule Air Sensible
Fraction
through an interior surface
X 54i X
Area
another room
10.00 X 0.424
Height ACH
Page Total
/ 60 ] X
AT
7,498
= 1,808
TOTAL HOURLY HEAT LOSS FOR ROOM 9.306
Energ Pro 5.1 by Energ Soft User Number: 6712 RunCode: 2013-02-20Tf7:10,35 10. Page 34 of46
ROOM HEATING PEAK LOADS
Project fame
Custom Residence for Desert Ring, LLC
Date
212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Bedroom 2
Floor Area 465.0 ft2
Indoor- Dry Bulb Temperature 70 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
1.064
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U-Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT *F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Btu/hr
R-38 Roof Attic
465.0
0.0250
44
512
R-21 Wall
1,100.0
0.0690
44
3,340
Dual Non Metal Tinted
120.0
0.3500
44
1,848
R-19 Floor Crawlspace
81.0
0.0460
44
164
Slab -On -Grade
perim = 32.0
0.7300
44
1,028
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X
Schedule Air Sensible
Fraction
through an interior surface
X 465 X
Area
another room
10.00 X 0.424
Height ACH
Page Total
/ 60 J X
AT
6,891
TOTAL HOURLY HEAT LOSS FOR ROOM 8,4281
En ergyPro 5.1 by En erVySoft User Number.- 6712 RunCode: 2013.02-20T1710:35 ID. Page 35 of 40
ROOM HEATING PEAK LOADS
Project Name
Custom Residence for Desert Ring, LLC
Date
212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master Bedroom 2
Floor Area 1,831.0 ftz
Indoor Dry Bulb Temperature 70 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
1.064
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U-Value
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
AT °F
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
44
Btu/hr
R-38 Roof Attic
1.831.0
0.0250
44
2,014
R 21 Wall
1,488.0
0.0690
44
4,518
Dual Non Metal Tinted
342.0
0.3500
44
5,267
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X
Schedule Air Sensible
Fraction
through an interior surface
X 1,831 X
Area
another room
10.00 X 0.424
Height ACH
Page Total
/ 60 ] X
AT
11,798
= 6,052
TOTAL HOURLY HEAT LOSS FOR ROOM 17.851
EnergyPro 5.1 by Ens Soft User Number: 6712 RunCode: 2013-02-20T17;10:35 1D. Page 36 of 46
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Custom Residence for Desert Ring. LLC
212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master Bedroom
Outdoor Dry Bulb Temperature
112 OF
Floor Area 996.0 ftz
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
Outdoor Daily Range;
34 OF
opaque Surfaces Orientation Area U-Factor
CLTD'
Btu/hr
R-38 Roof Attic (NE) 996.0 X 0.0250
X
56.0 =
1,394
R-21 Wall (NE) 212.0 X 0.0690
X
30.8 =
450
R-21 Wall (SE) 192.0 X 0.0690
X
28.8 =
381
R-21 Wall (SIM 237.0 X 0.0690
x
31.9 =
521
R-21 Wall (NW) 535.0 X 0.0690
x
29.0 =
1,071
X
X
=
x
x
x
x
=
x
x
Page Total
3,618
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
Window 1 (NE) 0.0 X 19.2 +
8.0 X
33.8
= 271
Window 2 (SE) 0.0 X 19.2 +
4.0 X
23.5
= 94
Window 3 (SW) 0.0 X 19.2 +
120.0 X
28.0
= 3,355
Window 4 (SW) 0.0 X 19.2 +
3.0 X
28.0
= 84
Window 5 (NM 0.0 X 19.2 +
9.0 X
29.9
= 269
Window 6 (NW) 0.0 X 19.2 +
9.0 X
29.9
= 269
Window 7 (NW) 0.0 X 19.2 +
9.0 X
29.9
= 269
Window 8 (NW) 0.0 X 19.2 +
4.0 X
29.9
= 119
X +
X
=
Page Total
4,729
Internal Gain
Btu/hr
Occupants 1.0 Occupants X 230
Btuh/occ.
=
230
Equipment 0.0 Dwelling Unit X 1,60o
Btu
=
0
Infiltration: 1.064 X 1.16 X 54.50 x 34 =
2,292
Alr Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
11,069
Latent Gain
Btu/hr
Occupants 1.0 Occupants X 200
Btuh/occ.
=
200
Infiltration: 4,771 X 1.16 X 54.50 X 0.00276 =
835
Air Sensible CFM ELA ❑W
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1,035
�FneivvPro 5.1 by EneMvsoft User Number: 6712 Run Code: 20-02-20T1T:10:35 la:
Pa a 37 of 46.1
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Custom Residence for Desert Ring, LLC 212012013
ROOM INFORMATION DESIGN CONDITIONS
Room Name Great Room/Kitchen Outdoor Dry Bulb Temperature 112 OF
Floor Area 1,942.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 78 OF Outdoor Daily Range: 34 OF
Opaque Surfaces
R 38 Roof Attic
R-21 Wall
R 21 Wall
R-21 Wall
Wood door
R 21 Wall
Orientation
(NE)
(NE)
(SE)
(SK9
(SW)
(NIA9
Area
X
X
X
X
X
X
X
x
x
U-Factor
X
X
X
X
X
X
x
x
x
CLTD'
=
=
=
=
=
=
=
=
=
820.0
0.0250
56.0
382.0
0.0690
30.8
303.5
0.0690
28.8
722.4
0.0690
31.9
20.6
1.4500
31.9
289.0
0.0690
29.0
Page Total
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded Unshaded
Fanpstratinn
Window 9
Wndow 10
Window 11
Window 12
Ohndow 13
Window 14
Window 15
Window 16
Window 17
Orientation
(NE)
(NE)
(NE)
(NE)
(SE)
(SE)
(SW)
(SW)
(SW)
Area
X
X
X
x
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
6.2
19.2
1.8
33.8
42.9
19.2
2.1
33.8
54.0
19.2
0.0
33.8
0.0
19.2
45.0
33.8
0.0
19.2
22.5
23.5
0.0
19.2
4.0
2a5
0.0
19.2
120.0
28.0
0.0
19.2
290.0
28.0
0.01
19.2
10.01
28.0
Page Total
Btu/hr
1,148
811
603
1,590
953
578
Btu/hr
181
897
1.039
1,523
529
94
3,355
8,107
280
Internal Gain Btu/hr
Occupants 2•0 Occupants X 230 Btuh/occ.
Equipment 11.0 Dwelling Unit X 1,600Btu = 1
Infiltration: 1.064 X 1.16 X 106.27 X 34 = C
Air Sensible CFM EL+ AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 29,837
Latent Gain Btu/hr
flcCu ants 2•0 Occupants X 200 Btuh/occ. - 400
Infiltration: 4,771 X 1.16 X 106.27 X 0.00276 = 1,628
Air Sensible CFM ELA .7W
DOTAL HOURLY LATENT HEAT GAIN FOR ROOM 2 028
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Custom Residence for Desert Ring, LLC
1 212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Great Room/Kitchen
Outdoor Dry Bulb Temperature
112 OF
Floor Area 1,942.0 ft'
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
Outdoor Daily Range:
34 OF
O a ue Surfaces Orientation Area
U-Factor
CLTD'
Btu/hr
x
x =
x
x =
x
x =
x
x =
x
x =
x
x =
x
x =
x
x =
x
x =
Page Total
0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
t. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area
GLF Area GLF
Btu/hr
Window 18 (SM
0.0 X 19.2 +
48.0 X 28.0
= 1,342
Window 19 (Sly
0.0 X 19.2 +
10.0 X 28.0
= 280
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
I X
=
Page Total
1,621
Internal Gain
Btu/hr
Occupants 2.0 Occupants X
230
Btuh/occ. _
460
Eclulpment 1.0 Dwelling Unit X
1,600
Btu _
1,600
Infiltration: 1.064 X 1.16 X 106.27 x
4,469
Air Sensible CFM ELA
AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
29,637
Latent Gain
Btu/hr
Occupants 2.0 Occupants X
200
Btuh/occ. =
400
Infiltration: 4,771 X 1.16 X 106.27
X 0.00276 =
1,628
Air Sensible CFM ELA
AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
2,028
Ens Pro 5.1 by EnemvSoff User Number: 6712 Ru Cod : 2013.42.20T17:1 .35 ID
Page 39 of 46
ESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Custom Residence for Desert Ring, LLC
212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Bedroom #2 & 3
Outdoor Dry Bulb Temperature
112 OF
Floor Area 939.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U-Factor
CLTD'
Btu/hr
R-38 Roof Attic (NE) 80.0 x 0.0250
X
56.0 =
112
R-21 Wall (NE) 250.0 X 0.0690
X
30.8 =
531
R-21 Wall (SE) 313.0 X 0.0690
X
28.8 =
622
R-21 Wall (SIM 123.0 X 0.0690
x
31.9 =
271
R 21 Wall (NW) 172.0 X 0,0690
X
29.0 =
344
x
X
=
X
x
=
x
x
=
x
x
=
E1,879
Page Total
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
MAdow 20 (SE) 0.0 X 19.2 +
48.0
X 23.5 =
1.128
Window 21 (SE) 0.0 X 19.2 +
8.0
X 23.5 =
188
Window 22 (SE) 0.0 X 19.2 +
8.0
X 23.5 =
186
Window 23 (SE) 0.0 X 19.2 +
48.0
X 23.5 =
1,128
Window 24 (NW) 0.0 X 19.2 +
20.0
X 29.9 =
597
Window 25 (NW) 0.0 X 19.2 +
40.0
X 29.9 =
1,194
Window 26 (NW) 0.0 X 19.2 +
20.0
X 29.9 =
597
Wrndow 27 (NW) 0.0 X 19.2 +
48.0
X 29.9 =
1,433
x +
x =
Page Total
s,454
Internal Gain
Btu/hr-
Occupants 2•0 Occupants X 230
Btuh/occ.
=
460
Equipment 0.0 Dwelling Unit X 1,600
Btu
=
0
Infiltration: 1.064 x 1.16 x 51.38 x 31
2,181
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
10,954
Latent Gain
Btu/hr
Occu 2•0 Occupants x 200
Btuh/acc.
=
400
ants
Infiltration: 4,771 x 1.16 x 51.38 x 0.00276 =
787
AirSenslble CFM ESA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1 187
Erie Pro 5.1 by EnerqvSoft User Number., 6712 RunCode: 201-02-20717:10.35 ID:
Pa a 40 of 413
'ESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Custom Residence for Desert Ring, LLC
1 212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Gym
Outdoor Dry Bulb Temperature
112 OF
Floor Area 375.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces Orlentation Area U-Factor
CLTD'
Btu/hr
R-38 Roof Attic (NE) 75.0 X 0.0250
X 56.0 =
105
R-21 Wall (NE) 129.5 X 0.0690
X 30.8 =
275
R-21 Wall (SE) 73.01 X 0.0690
X 28.8 =
145
R-21 Wall (SlM 131.4, X 0.0690
X 31.9 =
289
R-21 Wall (NtM 327.0 X 0.0690
X 29.0 =
654
X
X =
X
X =
X
X =
X
X =
Page Total
1,466
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF
Area GLF
Btu/hr
Window 28 (NE) 0.0 X 19.2 +
16.5 X 33.8
= 559
Window 29 (SE) 0.0 X 19.2 +
8.0 X 23.5
= 188
Window 30 (SW) 0.0 X 19.2 +
12.6 X 28.0
= 358
Window 31 (SlM 0.0 X 19.2 +
40.0 X 28.0
= 1,118
Window 32 (SlM 0.0 X 19.2 +
12.8 X 28.0
= 358
X +
X
=
X +
X
=
X +
X
=
X +
X
=
Page Total
2,580
Internal Gain
Btu/hr
Occu ants 0.0 Occupants X 230
Btuh/occ. =
0
Equipment 0.0 Dwelling Unit X 1.600
Btu =
0
Infiltration: 1.064 X 1.16 X 20.52 X 34 =
863
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
4.912
Latent Gain
Btu/hr
Occupants 0.o Occupants X 200.
Btuh/occ. =
0
Infiltration: 4,771 X 1.16 X 20.52 X 0.00276 =
314
Air Sensible CFM ELA ❑W
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
314
EnercvPra 5.1 by EnemySoft User Number: 6712 RunCode: 2 1-02-20T17:?4:35 10--
Page 41 of 48
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Custom Residence for Desert Ring, LLC
1 212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Garage
Outdoor Dry Bulb Temperature
112 OF
Floor Area 299.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U-Factor
CLTD'
Btu/hr
R-36 Roof Attic (NE) 39.0 X 0.0250
X 56.0 =
55
R-21 Wall (NE) 130.0 x 0.0690
X 30.8 =
276
R-21 Wall (SE) 214.0 X 0.0690
X 28.8 =
425
R-21 Wall (Sl9 65.6 x 0.0690
X 31.9 =
144
x
x =
x
x =
X
x =
x
x =
x
x =
Page Total
900
Items shown with an asterisk (•) denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF
Area GLF
Btu/hr
Window 33 (SE) 0.0 X 19.2 +
8.0 X 23.5
= 188
Wrndow 34 (SE) 0.0 X 19.2 +
8.0 X 23.5
= 188
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
X +
X
=
Page Total
376
Internal Gain
Btu/hr
Occupants 0.0 Occupants X 230
Btuh/occ. =
0
Equipment 0.0 Dwelling Unit X 1,600
Btu =
0
Infiltration: 1.064 X 1.16 X 16.36 X 34 =
688
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
1,964
Latent Gain
Btu/hr
Occupants 0 Occupants X 200
Btuh/occ. =
o
Infiltration: 4,771 X 1.16 X 16.36 X 0.00276
251
AirSenslble CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
251
EnemvPro 5.1 by EneravSoft user Number- 6712 RunCode: 2013-02-20T17:10:35 0:
Pa a 42 of 46
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Custom Residence for Desert Ring, LLC
212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Berdroom 1
Outdoor Dry Bulb Temperature
112 OF
Floor Area 547.0 ftZ
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U-Factor
CLTD'
Btu/hr
R-38 Roof Attic (NE) 547.0 X 0.0250
X
56.0 =
766
R-21 Wall (NE) 210.0 X 0.0690
X
30.8 =
446
R-21 Wall (SE) 227.4 X 0.0690
X
28.8 =
452
R-21 Wall (SW) 204.41 X 0.0690
X
31.9 =
450
R-21 Wall (NW) 246.0 X 0.0690
X
29.0 =
492
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
2,605
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
Window35 (NE) 0.0 X 19.2 +
40.0 X
33.8 =
1,354
Window 36 (SE) 0.0 X 19.2 +
11.3 X
23.5 = 266
Window 37 (SE) 0.0 X 19.2 +
11.3 X
23.5 =
266
Window 38 (SlM 0.0 X 19.2 +
12.8 X
28.0 =
358
Window 39 (SW) 0.01 X 19.2 +
20.0 X
28.0 =
559
Window 40 (SW) 0.0 X 19.2 +
12.8 X
28.0 =
358
Window 41 (NM 0.0 X 19.2 +
4.0 X
29.9 =
119
X +
X
=
X +
X
=
Page Total
3,279
Internal Gain
Btu/hr
Cccu ants 1.0 Occupants X 230
Btuh/occ.
=
230
Equipment 0.0 Dwelling Unit X 1,600
Btu
=
0
Infiltration: 1.064 X 1.16 X 29.93 X 34 =
1,259
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
7.373
Latent Gain
Btu/hr
1.0 Occupants X 200
Btuh/occ.
200
Occupants
Infiltration: 4,771 X F 1.16 X 29.93 X 0.00276 =
458
Alr Sensible CFM ESA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
658
Ene Pro .1 by Ene Sot? User Numher. 6712 RunCode: 2013-02-20717:10:35 11):
Page 43 ot46
'FEE IDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Custom Residence for Desert Ring, LLC
212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Guest Bedroom 2
Outdoor Dry Bulb Temperature
112 OF
Floor Area 465.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U-Factor
CLTD'
Btu/hr
R-38 Roof Attic (NE) 465.0 X 0.0250
X
56.0 =
651
R-21 Wall (NE) 199.0 x 0.0690
X
30.8 =
423
R-21 Wall (SE) 351.0 X 0.0690
x
28.8 =
697
R-21 Wall (SW) 195.0 X 0.0690
X
31.9 =
429
R-21 Wall (NW) 355.0 X 0.0690
X
29.0 =
710
R-19 Floor Crawlspace 81.0 x 0.0460
X
19.0 =
71
x
x
=
x
x
=
x
x
=
Page Total
Z981
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
Window 42 (NE) 0.0 X 19.2 +
18.0 X
33.8
= 609
Window 43 (NE) 0.0 X 19.2 +
18.0 X
33.8
= 609
Window 44 (SE) 0.0 X 19.2 +
24.0 X1
23.5
= 564
Window 45 (SW) 0.0 X 19.2 +
40.0. X
28.0
= 1,118
Window 46 (NK9 0.0 X 19.2 +
10.0 X
29.9
= 299
Window 47 (NM 0.0 x 19.2 +
10.0 X
29.9
= 299
X +
X
=
X +
X
=
X +1
X
=
Page Total
3,498
Internal Gain
Btu/hr
X
Occupants 1.0 Occupants 230
Btuh/occ.
=
230
Equipment 0.0 Dwelling Unit X 1,600
Btu
=
0
Infiltration: 1.064 x 1.16 x 25.44 x 34 =
1,070
Air Sensible CFM ELA AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
7.779
Latent Gain
Btu/hr
Occupants 1•0 Occupants X 200 J
Btuh/occ.
=
200
Infiltration: 4,771 X 1.16 X 25.44 X 0.00276 =
390
Air Sensible CFM EL4 AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
590
Ene Pro 5.1 by EnamvSoft User Number: 6712 R nCode: 2013.02.20T17:10. fD:
Page 44 of46
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Custom Residence for Desert
Ring, LLC
I 212012013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
Master Bedroom 2
Outdoor Dry Bulb Temperature
112 OF
Floor Area
1,831.0 ftZ
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces
Orientation Area U-Factor
CLTD'
Btu/hr
R-38 Roof Attic
(NE) 1,831.01 X 0.0250
X
56.0 =
2, 563
R-21 Wall
(NE) 486.0 X 0.0690
X
30.8 =
1,032
R-21 Wall
(SE) 438.0 X 0.0690
X
28.8 =
870
R-21 Wall
(SW) 124.0 X 0.0690
X
31.9 =
273
R-21 Wall
(NV4 440.0 X 0.0690
X
29.0 =
860
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
5,619
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration
Orientation Area GLF
Area
GLF
Btu/hr
Window 48
(NE) 0.0 X 192 +
24.0 X
33.8
= 812
Window 49
(NE) 0.0 X 19.2 +
48.0 X
33.6
= 1.625
Window 50
(NE) 0.0 X 19.2 +
24.0 X
33.8
= 812
Window 51
(NE) 0.0 X 19.2 +
32.0 X
33.8
= 1,083
Window 52
(NE) 0.0 X 19.2 +
8.0 X
33.8
= 271
Window 53
(NE) 0.0 X 19.2 +
8.0 X
33.8
= 271
Window 54
(SE) 0.0 X 19.2 +
4.0 X
23.5
= 94
Window 55
(SE) 0.0 X 19.2 +
4.0 X
23.5
= 94
Window 56
(SE) 0.01 X 1 19.2 +
42.0 X 1
23.5
= 967
Page Total
s,o49
Internal Gain
Btu/hr
Occupants
1.0 Occupants X 230
Btuh/occ.
=
230
Equipment
0.0 Dwelling Unit X 1,600
Btu
=
0
Infiltration: 1.064
X 1.16 X X 34 =
4,214
Air Sensible
Et1e00.19
CFM �T
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
20,145
Latent Gain
Btu/hr
1.o Occupants X 2001,
Btuh/occ.
=
200
Occupants
Infiltration: 4,771
X 1.16 X 100.19 X 0.00276 =
1,535
Air Sensible
CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1,735
EherovPro 5.112y EneravSoft
Vwr Number: 6712 RunCode: 2013.02-20T17:10:35 ID--
Pacie 45 of 46
� r=!91DENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Custom Residence for Desert Ring, LLC
2/20/2013
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Master Bedroom 2
Outdoor Dry Bulb Temperature
112 OF
Floor Area 1,831.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 78 OF
Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area U-Factor
X
X
CLTD'
=
Btu/hr
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
X
X
=
Page Total
o
Items shown with an asterisk (") denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area GLF Area
GLF
Btu/hr
Window 57 (SE) 0.0 X 19.2 +
16.0
X 23.5 =
376
Window 58 (SE) 0.0 X 19.2 +
16.0
X 23.5 =
376
Window 59 (SW) 0.0 X 19.2 +
96.0
X 28.0 =
2,684
Window 60 (NVIO 0.0 X 19.2 +
10.0
X 29.9 =
299
Window 61 (NIAO 0.0 X 19.2 +
10.0
X 29.9 =
299
X +
X -
X +
X -
X +
X -
X +
X -
Page Total
4,033
Internal Gain
Btulhr
Occupants 1.0 Occupants X 230
Btuh/occ.
_
230
Equipment 0.0 Dwelling Unit X 1,600
Btu
=
0
Infiltration: 1.064 X 1.16 X 100.19 X 34 =
4.214
Alr 5enslble CFM EI.A AT
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
20,145
Latent Gain
Btu/hr
Occupants 1.0 Occupants X 200
Btuh/occ.
=
200
Infiltration: 4,771 X 1.16 X 100.19 X 0 00276 =
f
1.5.35
Air Sensible CFM ELA AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
1.735
EneruvPro 5.1 by EnemvSoff User Number 6712 RunCode: 2013-02-20T17:10:35 ID:
Pace 46 of 46