BRES2014-1149 Title 24BUILDING ENERGY ANALYSIS REPORT M
r z:. 'PROJECT;
' INGRAM RESIDENCE's CASITA
r� r 79370 -Canterbury . a
r. Lb Quinta, CA 92253
Project Designer:' -
EDUARDO NAVA
VALLE POSADA49132
_
COACHELLA , CA 92236
01
IS;Q. , (760) 777-3260le
'
f
,Report Prepared by:
Y Armando Chavez
~TITLE 24 OF THE DESERT _ s.
K -.44890 seeley:dr
' La Quinta, Ca 92253-
-1760
2253 •1760 278.1840,':
F DEC Y 5:.2014
IIIMTZ
__...... ............._..:__.W.._.,.
1,2/11/2014
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
` This program developed by EnergySoft, LLC - www.energysoft.com.
Energ Pro 6.3 b EnergySoft User Number. 20648 ID: 2014-NAVA-001-1R
a
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: INGRAM CASITA
Calculation Description: Title 24 Analysis
Calculation Date/Time: 06:31, Thu, Dec 11, 2014
Input File Name: 004-INGRAM CASITA.xml
CF1 R -PRF -01
Page 1 of 8
GENERAL INFORMATION
01
Project Name INGRAM CASITA
02
Calculation Description Title 24 Analysis
03 This building incorporates one or more Special Features show elow
03
Project Location 79370 Canterbury
04
A City La Quinta
05
Standards Version Compliance 2014
06
Zip code 92253
07
Compliance Manager Version BEMCmpMgr 2013-3 (651)
08
Climate Zone CZ15
09
Software Version EnergyPro 6.3
10
Building Type Single Family
11
Front Orientation (deg/Cardinal) 45
12
Project Scope Newly Constructed
13
Number of Dwelling Units 1
14
Total Cond. Floor Area (FT2) 450
15 A—
Number of Zones 1
16
Slab Area (FT2) 450
17
Number of Stories 1
18
Addition Cond. Floor Area N/A
411
Natural Gas Available Yes
20
Addition Slab Area (FT2) N/A'
11
Glazing Percentage (%) 41.1%
M—
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing and or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
A 99
03 This building incorporates one or more Special Features show elow
.PV14; ENERGY USE SUMMARY
04
0��
06
07
08
Energy Use
(kTDV/ft)
Stardrd
zcnign
Proposed
Design
Compliance
Margin
Percent
Improvement
Space Heating
09 0.08
0.12
-0.04
-50.0%
Space Cooling
Ot. 157.57
180.84
-23.27
-14.8%
IAQ Ventilation
�� 1.94
1.94
0.00
0.0%
Water Heating
41.67
17.79
23.88
57.3%
Photovoltaic Offset
----
0.00
' rI-Q-ov C
Compliance Energy Total
201.26
200.69
I BUI0.571N °
& sA�
3 °
:J
Registration Number:® Registration Date/Time:
CA Building Energy Efficiency Stanfa-,ds - 2013 Residential Compliance Report Version - CF1R-10172014-651
/"I PROVE®
FOR CONSTRUCTION
'DATE BY
-------H E RS. Rrovi d er:
Report Generated at: 2014-12-1106:32:10
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1 R -PRF -01
Project Name: INGRAM CASITA. - ' Calculation Date/Time: 06:31, Thu, Dec 11, 2014 " : ' ' Page 2 of 8
f
' Calculation Description: Title 24 Analysis Input File Name: 004-INGRAM CASITA.xml ,
REQUIRED SPECIAL FEATURES z -
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis. '
Ducts with high level of insulation
Cathedral Ceiling
Exposed slab floor in conditioned zone
HERS FEATURE SUMMARY „ -� " p ty. • r
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance for this computer analysis. Additional detail is
provided in the building components tables below.'
F
Building -level Verifications:
IAQ mechanical ventilation
Cooling System Verifications- s k _ -4 c'-4, r I 4
}
Verified SEER Y x' x r. -- _ `• r ' • • - � .c `
-Refrigerant Charge
• Fan Efficacy Watts/CFM
HVAC Distribution System Verifications:'
Duct Sealing
Domestic Hot Water System Verifications:
- None - . _ P
r t,
ENERGY DESIGN RATING
This is the sum of the annual TDV energy consumption for energy use components incluc(aI
by Title 24, Part 6 _�
in the performance compliance approach for the Standard Design Building (Energy Budget) and the annual.'
domestic and electronics) and accounting for the annual TDV energy offset by an
TDV energy consumption for lighting and components not regulated
as appliances consumer
on-site renewable enersstem:
r
- , Reference Energy U e -
Energy Design Rating + Margin Percent Improvement,
"Total Energy (kTDV/f2)' 304.71
304 14 • 0.57 'r 0.2% 771
'
gy y
includes calculated Appliances and Miscellaneous Energy Use (AMEU) n
• j
BUILDING -FEATURES INFORMATION, -
01
02
03
04
05 ,
06•
07
'Zone Name
5
Number of Dwelling
Zone Floor Area
(ff2)
Avg. Ceiling
Height
Number of Ventilation
Number of Water
Project Name
Conditioned Floor Area (6ft)
Units
Number of Bedrooms
Number of Zones
Cooling Systems ..
Heating Systems
INGRAM CASITA
450 3�
1
1
:1
0 -
1
ZONE INFORMATIONV
01
0
03
04
05
06
07 .
'Zone Name
��11
�Zo4'e4Type
- +
HVAC System Name •
Zone Floor Area
(ff2)
Avg. Ceiling
Height
Water Heating System 1,
Water Heating System 2
ENTIRE CASITA
Conditioned
HVAC1
450-.
.-9
DHW Sys 1
,
Registration Number:® Registration Date/Time: -
CA Building Energy Efficiency Stan?-- 2013 Residential Compliance Report Version - CF1R-10172014-651
HERS Provider:
+ Report Generated at: 2014-12-1106:32:10
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1 R -PRF -01,
Project Name: INGRAM CASITA Calculation Date/Time: 06:31, Thu,- Dec 11, 2014 Page 3 of 8
Calculation Description: Title 24 Analysis i. Input File Name: 004-INGRAM CASITA.xml
T
' A
OPAQUE SURFACES
`
01
02
03
04
05'
06
07
08
Name
-Zone
Construction _
Azimuth
Orientation
Gross Area (ft)
Window Area (ft2)
Tilt(deg)
NE -144
ENTIRE CASITA
R-21 Wall
45
Front
144
48
90
SE -276
ENTIRE CASITA
R-21 Wall +
135
Left
276
28
90
SW -144
K ENTIRE CASITA
R-21 Wall
225
Back
144
76
90
NW -276
ENTIRE CASITA
R-21 Wall
315
Right
-, 276
32
90
4502
ENTIRE CASITA'-
R-49 Roof Attic
18.43
0.1
449'
0.07 '
OPAQUE SURFACES —Cathedral Ceilings
ATTIC
01 `02 03a 04 05 06 07
Name Construction Roof Rjse Roof Reflectance Roof Emittance Radiant Barrier Cool Roof
Attic Attic Roof Cons 4 0.1 - . 0.85 Yes No
.5
,
ASI
Registration Number: �$� Registration Date/Time: HERS Provider:
CA Building Energy Efficiency Standards - 2013 Residential Compliance Report Version - CF1R-10172014-651 ' , Report Generated at: 2014-12-1106:32:10
01
02
03
04 Q
06
07
08
09 •
10
11
Roof
Roof
Roof
Framin
Orientatio
Skylight
Roof Rise
Roof
Tilt
Reflectan
Emmittanc
g
Name, •
Zone
Type
n rea (ftZ)
Area (tt2)
(x in 12)
Pitch
(deg)
ce
a
Factor
450.
ENTIRE CASITA
R-49 Roof Attica
-specify - � 1.1
0.5
4 •
0.33'
18.43
0.1
0.85
0.07 '
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: INGRAM CASITA Calculation Date/Time: 06:31, Thu, Dec 11, 2014
Calculation Description: Title 24 Analysis Input File Name: 004-INGRAM CASITA.xml
CF1 R -PRF -01
Page 4 of 8
WINDOWS
01
02
03
04
05
06
Construction Name
. Surface Type
Construction Type d�
01
02
03
04
05
06
07
08
09
10
Name
Type
Surface (Orientation -Azimuth)
Width(ft)
Height
(ft)
Multiplier
Area
(ft)
U -factor
SHGC
Exterior Shading
6080
Window
NE -144 (Front -45)
----
O.C.
1
48.0
0.32
0.25
Insect Screen (default)
3680
Window
SE -276 (Left -135)
1
28.0
0.32
0.25
Insect Screen (default)
36802
Window
SW -144 (Back -225)
R 49
Over Floor Joists: R-39.9 insul.
1
28.0
0.32
0.25
Insect Screen (default)
60802
Window-
SW -144 (Back -225)
----
----
1
48.0
0.32
0.25
Insect Screen (default)
2040
Window
NW -276 (Right -315)
1
8.0
0.32
0.25
Insect Screen (default)
20402
Window
NW -276 (Right -315)
R 49
Roofing: 10 PSF (RoofTile)
1
8.0
0.32
0.25
Insect Screen (default)
20403
Window
NW -276 (Right -315)
1
8.0
0.32
0.25
Insect Screen (default)
20404
Window
NW -276 (Right -315)
1
8.0
0.32
0.25
Insect Screen (default)
10 solatube
Skylight
450 ( specify --45)
1
.5
0.28
0.20
'
10 solatube 2
Skylight
450 ( specify --45)
��
1
.5
0.28
0.20
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
Construction Name
. Surface Type
Construction Type d�
Framing
Total Cavity R -value
Assembly Layers
y
Cavity/Frame: no insul. /2x4 Top Chrd
2,4 Top Chord of
Roof Deck: Wood Siding/sheathing/decking
Roof Truss @ 24 in.
Tile Gap: present
Attic Roof Cons
Attic Roofs
Wood Framed Ung
O.C.
none
Roofing: 10 PSF (RoofTile)
°��pr
Inside Finish: Gypsum Board
• Cavity / Frame: R-9.1 / 2x4
R-49 Roof Attic
Ceilings (below attic)
Wood F ed Ceiling
2x4 @ 24 in. O.C.
R 49
Over Floor Joists: R-39.9 insul.
Inside Finish: Gypsum Board
• Cavity/ Frame: R-49 12x4
• Roof Deck: Wood Siding/sheathing/decking
• Tile Gap: present
R-49 Roof Atticl
Cathedral "Ceilings
I iNood Framed Ceiling
2x4 @ 24 in. O.C.
R 49
Roofing: 10 PSF (RoofTile)
• Inside Finish: Gypsum Board
Cavity / Frame: R-21 / 2x6
R-21 Wall
/�
Exterior Walls •{%
Wood Framed Wall
2x6 @ 24 in. O.C.
R 21
Exterior Finish: Wood Siding/sheathing/decking
Registration Number:�1�►, Registration Date/Time: HERS Provider:
CA Building Energy Efficiency StanrJatds - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-12-1106:32:10
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: INGRAM CASITA Calculation Date/Time: 06:31, Thu, Dec 11, 2014
Calculation Description: Title 24 Analysis
Input File Name: 004-INGRAM CASITA.xml
.3
CF1 R -PRF -01
Page 5 of 8
SLAB FLOORS
01 02 03 04 05 06 07
Name Zone Area (ft) Perimeter (ft) Edge Insul. R -value& Depth Carpeted Fraction Heated
(slab) 450 ENTIRE CASITA 450 0.1 None 0 No
BUILDING ENVELOPE - HERS VERIFICATION
01 02 03 04
Quality Insulation Installation (QII) Quality Installation of Spray Foam Insulation Building Envelope Air Leakage ACH @ 50 Pa
Not Required Not Required Not Required
WATER HEATING SYSTEMS
A
01 02
03 04. 05 06
Name System Type
Distribution Type° Water Heater • Number of Heaters Solar Fraction (%)
DHW Sys 1 DHW
Standard �� DHW Heater 1 1 •0%
WATER HEATING - HERS VERIFICATION
WATER HEATERS
01
02
03
04
05
06
07
08
t•
Parallel Piping
Compact Distribution
Point -of Use
Recirculation
Control
Central DHW
Distribution
DHW Sys 1 - 1/1
Tank Exterior
N/A •
N/A
N/A
N/A
Tank Volume
Energy Factor or
Other eat/Cool
Rw►
Insulation
Standby Loss
Name
Heater Element Type
Tank Type
(gal)
Efficiency
Input Rating
R -value
(Fraction)
DHW Heater 1
Natural Gas
Small Instantaptous
0
0.88
30710 Btu/hr
I
0
I
0
WATER HEATING - HERS VERIFICATION
01
02
03
04
05
06
07
Name
Pipe Insulation
t•
Parallel Piping
Compact Distribution
Point -of Use
Recirculation
Control
Central DHW
Distribution
DHW Sys 1 - 1/1
N/A A.
N/A •
N/A
N/A
N/A
N/A
HVAC SYSTEMS
A
01
02
03
04
05
06
07
Heating System
Cooling System
Distribution
Floor Area
Name
♦ est
Systerpr�Type'
Name Ducted
Name Ducted
System
Fan System
Serve
HVAC1
Other eat/Cool
Rw►
Heating Component 1
Yes
Cooling Component 1
Yes
Air Distribution
System 1
450
A -
Registration Number: �� Registration Date/Time: HERS Provider:
CA Building Energy Efficiency StanAh s - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-12-1106:32:10
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: INGRAM CASITA Calculation Date/Time: 06:31, Thu, Dec 11, 2014
Calculation Description: Title 24 Analysis Input File Name: 004-INGRAM CASITA.xml
HVAC - HEATING SYSTEMS
01 02 03
Name Type Efficiency
Heating Component 1 CntrlFurnace - Fuel -fired central furnace 92 AFUE
CF1 R -PRF -01
Page 6 of 8
HVAC - COOLING SYSTEMS
01
02
03 04
05
06
07
07
08
Efficiency
Type
Multi -speed
Verified Refrigerant
Name
System Type
EER SEEIi
Zonally Controlled
Compressor
HERS Verification
Coolin Com 1
g p onent
SplitAirCond - Split air conditioning
11.87
1�
No
No
Cooling Component
1 -hers -cool
1 -hers -dist
system
HVAC COOLING - HERS VERIFICATION •
01
02
03
04
05
06
07
08
Name
Type
Duct Leakam'4
Verified Refrigerant
Name
Verified Airflow
Airfio Tar et
Verified EER
Verified SEER
Charge
Cooling Component 1 -hers -cool
Required
�
Not Required
Required
Required
HVAC - DISTRIBUTION SYSTEMS A^!17 M
01
02
03
04
05
06
07
08
Name
Type
Duct Leakam'4
Insulation R -value
Supply Duct
Location
Return Duct
Bypass Duct
HERS Verification
Air Distribution System 1
Ducts located in attic
e
Sealed ancj°,tbgted
8
Attic
Attic
None
Air Distribution
System 1 -hers -dist
K
HVAC DISTRIBUTION - HERS VERIFICATION,
01
02
03
04
05 06
07
Duct Leakage
Verified Duct Design
Low -leakage
Name
Verification
Duct Leakage Target (%)
Verified Duct Location
Return Supply
Air Handler
Air Distribution System
Required
6.0
Not Required
Not Required
Not Required
1 -hers -dist
Registration Number:
CA Building Energy Efficiency Stan liai7Js - 2013 Residential Compliance
Registration Date/Time:
Report Version - CF1R-10172014-651
HERS Provider:
Report Generated at: 2014-12-1106:32:10
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: INGRAM CASITA Calculation Date/Time: 06:31, Thu, Dec 11, 2014
Calculation Description: Title 24 Analysis Input File Name: 004-INGRAM CASITA.xml
CF1 R -PRF -01
Page 7 of 8
HVAC -FAN SYSTEMS
01 02 03 04
Name Type Fan Power (Watts/CFM) HERS Verification
HVAC Fan 1 Single Speed PSC Furnace Fan 0.54 HVAC Fan 1 -hers -fan
HVAC FAN SYSTEMS - HERS VERIFICATION '
01 02 03
f Name VerifiedFanWaft Draw Required Fan Efficiency (Watts/CFM)
HVAC Fan 1 -hers -fan Required 0.54
IAQ (Indoor Air Quality) FANS r
01
02
03
;' 04 =
05
06
Name
IAQ CFM •— "
4�
`IAQ Watts/CF,�AI - - -
_ .,IAQ Fan Type
IAQ Recovery
Effectiveness(%)
HERS Verification
DwellingUnit
19.5
0.25
Default
0
Required
Registration Number: ee0� Registration Date/Time: ' HERS Provider:
CA Building Energy Efficiency Stan afds - 2013 Residential Compliance Report Version - CF1R-10172014-651 Report Generated at: 2014-12-1106:32:10
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: INGRAM CASITA Calculation Date/Time: 06:31, Thu, Dec 11, 2014
Calculation Description: Title 24 Analysis Input File Name: 004-INGRAM CASITA.xml
CF1 R -PRF -01
Page 8of8
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Documentation Author Signature: `
Armando Chavez,
Company: -
Signature Date:
TITLE 24 OF THE DESERT
12/11/2014
Address:
CEA/HERS Certification Identification (If applicable):
44890.seeley dr
City/StatZip:
Ta Quinta, Ca 92253
Phone:
1 278.1840
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California: ,-
1. I am eligible under Division 39f the Business and Professions Code to accept responsibility for bbuilding design identified on this Certificate of Compliance.
2. 1 certify that the energy features and performance specifications identified on this Certificate mpliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations. �
documents,
3. The building design features or system design features identified on this Certificate of Comp lance are consistent with the information provided on other applicable compliance
worksheets, calculations, plans and specifications submitted to the enforcement agencyAlcir approval with this building permit application.
Responsible Designer Name: iQv.Responsible
Designer Signature:
Company:
Date Signed:`
EDLIARDO NAVA
Address:
License:
49132 VALLE POSADA
City/State/Zip:
AV
Phone:
COACHELLA , CA 92236
(760) 777-3260
Registration Number:�� Registration Date/Time:
CA Building Energy Efficiency StanCds - 2013 Residential Compliance 'Report Version - CF1R-10172014-651
HERS Provider:
Report Generated at: 2014-12-1106:32:10
RESIDENTIAL MEASURES SUMMARY
RMS -1
Project Name
INGRAM RESIDENCE'S CASITA
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
11211112014
Project Address
79370 Canterbury La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
450
Addition
n/a
# of Units
1
INSULATION
Construction Type
Area
Cavity (ft) Special Features
Status
Slab Unheated Slab -on -Grade - no insulation 450 Perim = 0'
New
Roof Wood Framed Attic R49 449
New
Wall Wood Framed R 21 656
New
FENESTRATION Total Area: 185TGla,,ng Percentage: 41.1 % New/Altered Average U -Factor:
Orientation Area ft2 U -Fac SHGC Overhang Sidefins Exterior Shades
0.32
Status
Skylight 0.5 0.280
0.20 none none None
New
Skylight 0.5 0.280
0.20 none none None
New
Front (NE) 48.0 0.320
0.25 none none Bug Screen
New
Left (SE) 28.0 0.320
0.25 none none Bug Screen
New
Rear (SW) 76.0 0.320
0.25 none none Bug Screen
New
Right (NM 32.0 0.320
0.25 none none Bug Screen
New
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling Min. Eff Thermostat
Status
1 Central Furnace 92% AFUE
Split Air Conditioner 14.0 SEER Setback
New
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location R -Value
Status
HVAC Ducted
Ducted Attic 8.0
New
WATER HEATING
Qty. Type Gallons Min. Eff Distribution
Status
1 Small Instantaneous Gas 0
0.88 Standard
New
EnergyPro 6.3 by EnergySoft User Number. 20648
RunCode: 201412-11706:35:16 ID: 2014-NAVA-001-1R
Pae 11 of 14
MANDATORY MEASURES SUMMARY: Residential (Page 1 of 3 MF -1 R
Project Name
Date
INGRAM RESIDENCE'S CASITA
11211112014
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
110.6(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§110.6(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
110.7: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
110.8(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -2R Form.
§110.8(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §110.8(i) when the
installation of a Cool Roof is specified on the CF -1 R Form.
*§1 50.0 a : Minimum R-30 R-19 for Alterations insulation in wood -frame ceiling orequivalent U -factor.
150.0(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value.
*§1 50.0 c : Minimum R-13 insulation in 2x4 wood -frame wall R-19 in 2x6 orequivalent U -factor.
*§1 50.0 d : Minimum R-19 insulation in raised wood -frame floor orequivalent U -factor.
150.0 : Air retarding wrap is tested, labeled, and installed according to ASTM El677-95 2000 when specified on the CF -1 R Form.
150.0 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150.0(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
§150.0(q) Fenestration Products. Fenestration separating conditioned space from unconditioned space or outdoors shall meet the
requirements of either Item 1 or 2 below:
1. Fenestration, including skylight products, must have a maximum U -factor of 0.58.
2. The weighted average U -factor of all fenestration, including skylight products, shall not exceed 0.58.
EXCEPTION to Section 150.0(q)1: Up to 10 square feet of fenestration area or 0.5 percent of the Conditioned Floor Area, whichever is
greater, is exempt from the maximum U -factor requirement.
150.0 r Solar Ready Buildings. Shall meet the requirements of Section 110.10 applicable to the building project.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150.0 a 1A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150.0(e)l B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device.
§150.0(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110.0-§110.3: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§110.3(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §110.3(c)5.
§110.5: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
150.0(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
150.0(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 11 0.2 c .
§150.00)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally
wrapped with insulation having an installed thermal resistance of R-12 or greater.
§150.00)113: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
EnergyPro 6.3 by EnergySoft User Number: 20648 ID: 2014-NAVA-001-1R Page 12 of 14
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R
Project Name
Date
INGRAM RESIDENCE'S CASITA
12/11/2014
§150.00)2A: All domestic hot water system piping conditions listed below, whether buried or unburied, must be insulated per TABLE
120.3-A.
i. The first 5 feet (1.5 meters) of hot and cold water pipes from the storage tank.
ii. All piping with a nominal diameter of 3/4 inch (19 millimeter) or larger.
iii. All piping associated with a domestic hot water recirculation system regardless of the pipe diameter.
iv. Piping from the heating source to storage tank or between tanks.
v. Piping buried below grade.
vi. All hot water pipes from the heating source to the kitchen fixtures.
§150.00)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards
Table 120.3-A.
150.0 ' 3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§150.00)4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
§150.0(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC
Sections 601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed
level of R-6 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that
meets the applicable requirements of UL 181, UL 181A, or UL 1816 or aerosol sealant that meets the requirements of UL 723. If mastic
or tape is used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150.0(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150.0(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150.0(m)7: Exhaust fans stems have back draft or automatic dampers.
§150.0(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150.0(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150.0(m)10: Flexible ducts cannot have porous inner cores.
§150.0(n)1: Systems using gas or, propane water heaters, whether tank or on -demand, to serve individual dwelling units shall include
all the following components :
A. A 120V electrical receptacle that is within 3 feet from the water heater and accessible to the water heater with no obstructions;
B. A Category III or IV vent, or a Type B vent with straight pipe between the outside termination and the space where the water
heater is installed;
C. A condensate drain that is no more than 2 inches higher than the base of the installed water heater, and allows natural draining
without pump assist,
D. A gas supply line with a capacity of at least 200,000 Btu/hr.
§150.0(0): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2 Ventilation and Acceptable Indoor Air Quality
in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in
Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§110.4(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§110.4(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
110.4(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§110.4(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
150.0 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150.0
Residential Lighting Measures:
§150.0(k)1A: Installed luminaires shall be classified as high -efficacy or low -efficacy for compliance with Section 150.0(k) in accordance
with TABLE 150.0-A or TABLE 150.0-B, as applicable.
150.0 k 1C: The wattage of permanently installed luminaires shall be determined asspecified by §130.0(c).
150.0 k 1 D: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency - 20 kHz.
§150.0(k)1 E: Permanently installed night lights and night lights integral to installed luminaires or exhaust fans shall be rated to consume
no more than five watts of power per luminaire or exhaust fan as determined in accordance with Section 130.0(c). Night lights shall not
be required to be controlled by vacancy sensors.
EnergyPro 6.3 by EnergySoft User Number: 20648 ID: 2014-NAVA-001-1 R Page 13 of 14
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF-1 R
Project Name
Date
INGRAM RESIDENCE'S CASITA
12111/2014
150.0 k 1 F: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150.0(k).
150.0(k)2: All switching devices and controls shall meet the requirements of §150.0(k)2.
§150.0(k)3: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts
for dwelling units larger than 2,500 ftZ may be exempt from the 50 percent high efficacy requirement when all
lighting in the kitchen is controlled in accordance with the applicable provisions in Section 150.0(k)2, and is also
controlled by vacancy sensors or dimmers.
§150.0(k)4: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
§150.0(k)5: Lighting installed in bathrooms shall meet the following requirements:
A. A minimum of one high efficacy luminaire shall be installed in each bathroom; and
B. All other liqhting installed in each bathroom shall be high efficacy or controlled by vacancy sensors.
§150.0(k)6: Lighting installed in attached and detached garages, laundry rooms, and utility rooms shall be high efficacy luminaires and
controlled by vacancy sensors.
§150.0(k)7: Lighting installed in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, and utility rooms shall be
high efficacy, or shall be controlled by either dimmers or vacancy sensors.
EXCEPTION 1: Luminaires in closets less than 70 square feet.
EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site.
§150.0(k)8: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the luminaire is airtight with air
leakage less than 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150.0(k)9A: For single -family residential buildings, outdoor lighting permanently mounted to a residential building or other buildings on
the same lot shall be high efficacy, or may be low efficacy if it meets all of the following requirements:
i. Controlled by a manual ON and OFF switch that does not override to ON the automatic actions of items
ii or iii below; and
ii. Controlled by a motion sensor not having an override or bypass switch that disables the motion sensor, or controlled by a
motion sensor having a temporary override switch which temporarily bypasses the motion sensing function and
automatically reactivates the motion sensor within 6 hours
iii. Controlled by one of the following methods:
a. Photocontrol not having an override or bypass switch that disables the photocontrol; or
b. Astronomical time clock not having an override or bypass switch that disables the astronomical time clock, and
which is programmed to automatically turn the outdoor lighting OFF during daylight hours; or
c. Energy management control system which meets all of the following requirements:
At a minimum provides the functionality of an astronomical time clock in accordance with Section 110.9;
meets the Installation Certification requirements in Section 130.4; meets the requirements for an EMCS in
Section 130.5; does not have an override or bypass switch that allows the luminaire to be always ON; and,
is programmed to automatically turn the outdoor lighting OFF during daylight hours.
§150.0(k)9A: For low-rise multi-family residential buildings, outdoor lighting for private patios, entrances, balconies, and porches; and
outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site shall comply with one of the
following requirements:
i. Shall comply with Section 150.0(k)9A; or
ii. Shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)9: For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by Section 150.0(k)9B or
Section 150.0(k)9D shall comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130 4,14Q.Z,_and_441-0��
Op
§150.0(k)9D: Outdoor lighting for residential parking lots and residential carports with a total of eight or ore vehicles per shall
comply with the applicable requirements in Sections 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§150.0(k)10: Internally illuminated address signs shall comply with Section 140.8; OR not contain asc_w_=,; se sOket, and onsume
no more than five watts of ower as determined accordingto 130.0(d). U
§150.0(k)11: Lighting for residential parking garages for eight or more
vehicles shall comply with the applicable requirements for nonresidential garages in Sections 110.9130 .0,;130.:1
130.4, 140.6, and 141.0. lL j1
§150.0(k)12A. In a low-rise multi-family residential building where the total interior common area inangle uildi'n—equals 2 percent
less floor bZhigh
or of the area, permanently installed lighting for the interior common areas in that building hate dfficacy lu�m naires or
controlled by an occupant sensor. LL 0_0
§150.0(k)126. Ina low-rise multi-family residential building where the total interior common area in s'nl Lb ling=equals re than
20 percent of the floor area, permanently installed lighting in that building shall:
< 0
i. Comply with the applicable requirements in Sections 110.9, 130.0, 130.1, 140.6, and anc
141.0; P LL w
ii. Lighting installed in corridors and stairwells shall be controlled by occupant sensors that rrduce`t�f e lighting poker i each
space by at least 50 percent. The occupant sensors shall be capable of turning the light fully On and OroW all designed Pat sof
and a ress.
r
ro 6.3 by EnergySoft User Number: 20648 ID: 2014-NAVA-001-1R Page 14 of 14
Ul RATINGS
ARI Standard 210/240 Ratings
_Capacity - Btuh Efficiency Total Watts COP
Highw HSPF
Cooling Temp. TCoot High Low High L(
Heating jHetitlpg EER EER Id V Heat Heat Heat HI
13HPD-018
HEAT PUMPS
Indoor Unit Model No_ Expansion
Device
1310 1 3.46 1 2.36 1 CB26UH-018-R
1.5 TON
Factory Installed
113H;PD}024. " -- 2 TO .
_
��..-122:000f'Fado .Installed
24,000 13:00 -1150 7.70 7.05 2085 1825[1715 ;354' 2.38 -CB26UH-024-R. (UpRow/Horizontai) -
31,000
128,600
117,900
113.00111.0017.7017.1012820124051218013.48
12.40
I CB26UH-030-R (Up-Row/Honzont3l)
Installed
0
I
RFC .072
13HPo-036
3 TON
35,200
33,800
21,000
13.00
11.00
7.70
7.10
3200
2760
2515
358
2.44
C826UH-3642 (Up -Flow / Horizonlal)
Fadory Installed
RFC (0 074)
13HPD-042 3.5 TON
41,50041,000
26,400
13.00
11.00
8.50
7.45
3775
3780
3275
3.18
2.36
CB26UH-042-R (Upflow/Horizontal)
Factory Installed
RFC (0.082)
13HPD-060 S TON
57,000
1 55,000
135,600
13.00
11.00
7.707.O
5060
4890
4295
3.30
2.42
CB26UH-O6 (Up-Flow/Horizontal)
Factory Installed
RFC (0.098)
HP13-018 1.5 TONf
18,000
16,800
10,600
13.00
11.50
7.70
6.90
1565
1425
1310
3.46
2.36
CB26UH-01842 (Up-Flow/Hodzontal)
FadoryInstalle
RFC (0 057)`
HP13-024 2.. a `?
24,000
22,000
13,900
13.00
11.50
7.70 17.05
2085
1825
1715
3.54
2.38
CB26UFI-024-R (Up-Row/Horizontal)
Factory Installed ��
RFC (0.061)
IHPl3-030 2.S TON
31,000
28,600
17,900
13.00
11.00
7.70
7.10
2820
2405
2180
3.48
2.40
CB26UH-030-RU Iow/Horizontal
(� )
Factory Installed
(0
RFC 072)
rrr�3-v36 3 TON
35,200
33,800
21,000
13.00
11.00
7.70
7.10
3200
2760
2515
3.58
2.44
CB26UH-03642 (UpRow/Horizontai)
Factory Installed
RFC (0.074)
HP13-042 3.S TON
41,500
41,000
26,400
13.00
11.00
8.50
7.45
3775
3780
3275
3.18
2.36
C826UH-042 R (Up-FlowMorizontal)
Flory Installed
RFC (0 082)
HP13-060 S TON
57,000 55,000 1 35,600 13.00 11.007.70 7.30 5060 4890 4295 3-3012-42 1 CB26UH-06M (UpFlow/Horizontal) Fadory Installed
RFC (0.098)
NOTE - ..nen used with gas furnaces, a dual -fuel control (i.e. FM21) or a control system with dual -fuel capabilifies (i.e. Harmony III, LZP-2 or LZP-4) must be used (ordered extra).
1 Certified in accordance with USE certification program which is based on ARI Standard 2101240 25 ft.
with of connecting refrigerant lines;
Cooling Ratings - 95'F outdoor air temperature and 80'F db/67'F wb entering indoor coil air.
High Temperature Heating Ratings -47'F db/43'F wb outdoor air temperature and 701F db entering indoor cog air.
Low Temperature Heating Ratings - 17'F db/15'F wb outdoor air temperature and 70'F db entering indoor coil air.
CB26UH-R -1.5 to 5 ton Air Handlers / Page 9