06-1863 (RC) Revision 1 Title 24TITLE 24 REPORT
Title 24 Report for:
Land America Commonwealth'
w,a 78 -982_ -Highway 111_STE
La Quinta, CA 92253
Project Designer:
Carl Cox, AIA
81-557 Dr. Carreon Blvd.
Indio, CA 92201
(760) 547-4007
Report Prepared By:
John Jolly
C+J Technical Solutions and Services, Inc.
1320 Valley Vista Dr. Suite 206
Diamond Bar, CA 91765
(909) 896-3631
CITY OF LA QUINTA
BUILDING & SAFETY DEPT. ..,.
APPROVED Job Number:
FOR CONSTRUCTION
C06107
DA Y Q wN 0 1006
Date:
6/6/2006 ey
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.1 by EnergySoft Job Number: C06107 User Number: 5950
TABLE OF CONTENTS
Cover Page
Table of Contents
Form LTG -1-C Certificate of Compliance
Form LTG -2-C Indoor Lighting Schedule
Form LTG -3-C Portable Lighting Worksheet
Form LTG -4-C Lighting Controls Credit Worksheet
Form LTG -5-C Indoor Lighting Power Allowance
Form LTG -MM Lighting Mandatory Measures
1
2
3
7
8
10
11
12
EnergyPro 4.1 by EnergySoft Job Number: C06107 User Number: 5950
CERTIFICATE OF COMPLIANCE (Part 1 of 4) LTG -
PROJECT NAME
DATE
Land America Commonwealth
6/6/2006
PROJECT ADDRESS--=-+.---•
78-982 Highway 111 STE 1-B La Quinta
`
PRINCIPAL DESIGNER - LIGHTING
TELEPHONE
Building.Permit#
{
DOCUMENTATION AUTHOR
C+J Technical Solutions and Services, Inc.
TELEPHONEChecked
909 896-3631
by/Date
Enforcement Agency. Use
GENERAL INFORMATION
DATE OF PLANS
BUILDING CONDITIONED FLOOR AREA
CLIMATE ZONE
2,643 sq.Ft.
15
BUILDING TYPE ® NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTEL/MOTEL GUEST ROOM
❑X CONDITIONED SPACES ❑ UNCONDITIONED SPACES ❑ INDOOR & OUTDOOR SIGNS
PHASE OF CONSTRUCTION NEW CONSTRUCTION ❑ ADDITION ❑ ALTERATION
METHOD OF LIGHTING ❑ COMPLETE BUILDING ® AREA CATEGORY ❑ TAILORED ❑ PERFORMANCE
COMPLIANCE ❑ COMMON LIGHTING
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24,
Parts 1 and 6 of the California Code of Regulations. This certificate applies only to building lighting requirements.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
IG T E
I
p T
John Jolly
The Principal Lighting Designer hereby certifies that the pr sed building esign represented in this set of construction documents
is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with
this permit application. The proposed building has been designed to meet the lighting requirements contained in Sections 110, 119,
130 - 132, 146, 148 & 149 of Title 24, Part 6.
KThe plans & specifications meet the requirements of Part 6 (Sections 10-103a).
he installation certificates meet the requirements of Part 6 (10-103a 3).
❑ The operation & maintenance information meet the requirements of Part 6 (10-103c).
Please Check One: (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.)
❑ I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsib
its preparation; and that I am licensed in the State of California as a civil engineer or electrical engineer, or I am a licensed architect.
❑ I affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code by Section 5537.2 or 6737.3 to sign this document as
person responsible for its preparation; and that I am a licensed contractor performing this work.
❑ I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code to sign this document because it pertains to a structur
type of work described as exempt pursuant to Business and Prof ons Cod"e0'ej 5537, 5538 and 6737.1.
PRINCIPAL nING DESIGNS - AME
SI NA URE
DATE
LI #
LIGHTING NDATORY MEASURES
Indicate location on plans of Note Block for Mandatory Measures
LIGHTING COMPLIANCE FORMS & WORKSHEETS Check box if worksheet is included
®LTG -1-C, Parts 1 of 4 and 2 of 4: Certificate of Compliance. Part 1 of 4 and 2 of 4 are required for all submittals
®LTG -1-C, Part 3 of 4: Certificate of Compliance. Part 3 of 4 submittal is required only if Control Credits are claimed
®LTG -1-C, Part 4 of 4: Certificate of Compliance. Part 4 of 4 submittal is required when lighting controls are installed
®LTG -2-C: Indoor Lighting Schedule
®LTG -3-C: Portable Lighting Worksheet
®LTG -4-C: Lighting Controls Credit Worksheet
(9 LTG -5-C: Indoor Lighting Power Allowance
OLTG-6-C: Tailored Method Worksheet
O LTG -7-C: Room Cavity Ratio Worksheet
OLTG-8-C: Common Lighting Systems Method Worksheet
OLTG-9-C: Line Voltage Track Lighting Worksheet
EnergyPro 4.1 by EnergySoft User Number: 5950 Job Number: C06107 Page:3 of 12
a for
.he
or
CERTIFICATE OF COMPLIANCE (Part 2 of 4) LTG -1-C
PROJECT NAME DATE
Land America Commonwealth 6/6/2006
INSTALLED INDOOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) 0
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (From LTG -5-C) ALLOWED
❑X AREA CATEGORY METHOD (From LTG -5-C) WATTS
❑ TAILORED METHOD (From LTG -5-C) ALLOWED LIGHTING POWER 3,137
IALTERNATE COMPLIANCE
❑ PERFORMANCE METHOD
❑ COMMMON LIGHTING SYSTEM (From LTG -8-C)
ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C) 0
MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS
CONTROL LOCATION
(Room #)
CONTROL
IDENTIFICATION
CONTROL TYPE
(Auto Time Switch, Dimming, etc.)
Check if
SPACE CONTROLLED Daylighting
NOTE TO
FIELD,
NOTES TO FIELD - For Buildina Department Use Only
INSTALLED
WATTS
INSTALLED LIGHTING, CONDITIONED SPACES (From LTG -2-C)
3,492
PORTABLE LIGHTING (From LTG -3-C)
0
LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG -4-C)
364
CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER
3,128
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) 0
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (From LTG -5-C) ALLOWED
❑X AREA CATEGORY METHOD (From LTG -5-C) WATTS
❑ TAILORED METHOD (From LTG -5-C) ALLOWED LIGHTING POWER 3,137
IALTERNATE COMPLIANCE
❑ PERFORMANCE METHOD
❑ COMMMON LIGHTING SYSTEM (From LTG -8-C)
ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C) 0
MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS
CONTROL LOCATION
(Room #)
CONTROL
IDENTIFICATION
CONTROL TYPE
(Auto Time Switch, Dimming, etc.)
Check if
SPACE CONTROLLED Daylighting
NOTE TO
FIELD,
NOTES TO FIELD - For Buildina Department Use Only
v
EnergyPro 4.1 by Energysoft
User Number: 5950
Job Number: C06107 Page:4 of 12
CERTIFICATE OF COMPLIANCE (Part 3 of 4) LTG -
PROJECT NAME DATE
Land America Commonwealth 6/6/2006
C0NTP0I S FnP rRFnlT IN rnNnITInNGn Akin I1NrnunrTi^Kien enwre0
CONTROL LOCATION
(Room # or Dwg. #)
ADA Restroom
ADA Restroom
Server Room
Office 2
Office 3
Office 4
CONTROL
IDENTIFICATION
CONTROLTYPE
(Occupant, Daylight, Dimming, etc.)
Occ Sensor - — 250 sqft
Occ Sensor - — 250 sqft
Occ Sensor - — 250 sqft
Occ Sensor - — 250 sqft
Occ Sensor - — 250 sqft
Occ Sensor - — 250 sqft
Occ Sensor - — 250 sqft
Occ Sensor - — 250 sqft
Occ Sensor - — 250 sqft
Dimming - Manual
LUMINA S CONTROLLED
TYPE # OF LUMINAIRES
75
1
75
1
2x4
2
2x4
2
2x4
2
2x4
2
2x4
2
2x4
2
2x4
2
75
2
NOTE TO
FIELD
NOTES TO FIELD - For Buildina Department Use Only
`,fi
'-'. 4 �x 'd t 3 '4 4g
a r
9 n x t K ,.s<�wff
i, L
EnergyPro 4.1 by EnergySoft User Number: 5950
Job Number: C06107 Page:5 of 12
CERTIFICATE OF COMPLIANCE (Part 4 of 4) LTG-1-C
PROJECT NAME
Land America Commonwealth
DATE
6/6/2006
Designer:'
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance
tests for lighting systems. The designer is required to check the boxes by all acceptance tests that
apply and list all equipment that require an acceptance test. If all equipment of a certain type requires
a test, list the equipment description and the number of systems to be tested in parentheses. The NJ
number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the
test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design
professional or an agent selected by the owner). Since this form will be part of the plans, completion
of this section will allow the responsible party to budget for the scope of work appropriately.
Building Departments:
Before an occupancy permit is granted for a newly constructed building or space, or a new lighting
system system serving a building or space is operated for normal use, all control devices serving the
building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
In addition a Certificate of Acceptance, LTG-1-A, Forms shall be submitted to the building department
that:
A. Certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of§ 10-103(b) and Title 24 Part 6.
Test Descri tion
Test Performed BY:
❑ LTG-2-A: Lighting Control Acceptance Document
- Occupancy Sensor Acceptance
- Manual Daylight Controls Acceptance
- Automatic Time Switch Control Acceptance
Equipment requiring acceptance testing
0 LTG-3-A: Automatic Daylighting Controls Acceptance Document
Equipment requiring acceptance testing
EnergyPro 4.1 by EnergySoft User Number: 5950 . Job Number: C06107 Page:6 of 12 1
U
N o
N
J �
CC)
W
Q
N
O
N
a_
W
J s
.r
W
W CO
2
C
0
V
Z
2 Q
0
J �
W
O
Q
O Z
0
Z 0
n00c
JOLILI�
Q m
H IM
W G
a o
a
U
e �
J
E
U N
J
E Q
o
C14
c
is 0
U
t7
Z
m
J
O
O � Q
H
Z
U
a
7
Installed
M
Watts
M
(G x 1)
IT
Number
00
N
of
�p
Luminaires
CEC
C=
Default?
X
X
0
0
Watts
per
r
ti
Luminaire
r'
Number of
LL
Ballast per
Luminaire
C14
LO
Watts
Ch
~
W
per
U)
Lamp
Number of
m
0
Lamps per
to
Luminaire
E
w
J
U
Lamp
Type
co
N
c+�
LL
U
d
W
C
m
c
ccy
U
o
.--
N
n
N
C
.0
N
Q
CO
C
C
n
�
�
J
2
LL
U)
�
3
r`
a�
v
Zcc
N
n00c
JOLILI�
Q m
H IM
W G
a o
a
U
e �
J
E
U N
J
E Q
o
O
z
(7
JG
is 0
U
t7
Z
m
J
O
O � Q
H
Z
U
a
Q
0
U
L:
E
z
z
0
0
n
E
z
D
PORTABLE LIGHTING WORKSHEET LTG -
PROJECT NAME
Land America Commonwealth
DATE
6/6/2006
TOTAL WATTS
BUILDING TOTAL
TABLE 1 - PORTABLE LIGHTING
NOT SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE
FEET
A
B
C
D
ROOM #
OR ZONE ID
DEFAULT
/s ft
AREA
SF
TOTAL WATTS
B X C
TOTAL
WATTS
(C x E)
ADA Restroom
62 1
62
ADA Restroom
62 1
62
Server Room
137 1
137
Break Room
148 1
148
Office 1
167 1
167
Office 2
TOTAL
0
0
TABLE 2 - PORTABLE LIGHTING
SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE FEET
TOTAL WATTS
BUILDING TOTAL
A
B
C D E
F
G
ROOM #
OR ZONE ID .
PORTABLE LIGHTING
Description
# OF
FIXT.
LUMIN. TASK # OF
WATTS PER AREA TASK
FIXTURE (SF) AREAS
TOTAL
AREA (SF)
(D x E)
TOTAL
WATTS
(C x E)
ADA Restroom
62 1
62
ADA Restroom
62 1
62
Server Room
137 1
137
Break Room
148 1
148
Office 1
167 1
167
Office 2
167 1
167
Office 3
167 1
167
Office 4
167 1
167
TOTAL
1,077
=0
TABLE 3 - PLANS SHOW PORTABLE LIGHTING IS NOT REQUIRED FOR OFFICE AREAS > 250 SQUARE FEET
ROOM # TOTAL AREA
OR ZONE ID (SF)
TOTALI 0
BUILDING SUMMARY - PORTABLE LIGHTING
Designer needs to provide detailed documentation that the lighting
level provided by the overhead lighting meets the needs of the
space. The details Include luminaire types and mounting locations
relative to work areas.
BUILDING SUMMARY
TOTAL AREA (SF)
(FROM TABLES 1+2+3)
TOTAL WATTS
BUILDING TOTAL
2,643
0
EnergyPro 4.1 by EnergySoft User Number: 5950 Job Number: C06107 Page:8 of 12
PORTABLE LIGHTING WORKSHEET LTG -3 C]
PROJECT NAME
Land America Commonwealth
DATE
6/6/2006
FEET
A
TABLE 1 - PORTABLE LIGHTING
NOT SHOWN ON PLANS FOR OFFICE AREAS >250 S DARE FEET
A
B
C D
ROOM #
OR ZONE ID
DEFAULT
/s ft
AREA TOTAL WATTS
SF B X C
# OF
FIXT.
LUMIN.
WATTS PER
FIXTURE
TASK # OF
AREA TASK
(SF) AREAS
TOTAL
AREA (SF)
(D x E)
TOTAL
WATTS
(C x E)
Conference Room
200 1
200
Offices
1,366 1
1,366
TOTAL
0 0
TABLE 2 - PORTABLE LIGHTING
SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE
FEET
A
B
0
C
D E
F
G
ROOM #
OR ZONE ID
PORTABLE LIGHTING
Description
# OF
FIXT.
LUMIN.
WATTS PER
FIXTURE
TASK # OF
AREA TASK
(SF) AREAS
TOTAL
AREA (SF)
(D x E)
TOTAL
WATTS
(C x E)
Conference Room
200 1
200
Offices
1,366 1
1,366
TOTAL
1,566
0
TABLE 3 - PLANS SHOW PORTABLE LIGHTING IS NOT REQUIRED FOR OFFICE AREAS > 250 SQUARE FEET
ROOM # TOTAL AREA
OR ZONE ID (SF)
TOTALI 0
BUILDING SUMMARY - PORTABLE LIGHTING
Designer needs to provide detailed documentation that the lighting
level provided by the overhead lighting meets the needs of the
space. The details Include luminaire types and mounting locations
relative to work areas.
BUILDING SUMMARY
TOTAL AREA (SF)
(FROM TABLES 1+2+3)
TOTAL WATTS
BUILDING TOTAL
2,643
0
EnergyPro 4.1 by Energysoft User Number: 5950 Job Number: C06107 Page:9 of 12
LIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG -4-C]
CONTROL CREDITS FOR CONDITIONED SPACES
PROJECT NAME
DATE
Land America Commonwealth 1 6/6/2006 1
A
B
C
D
E I F I G
H
I
J
ROOM #
ZONE ID
CONDITIONED
AREAS
LIGHTING
CONTROL
DESCRIPTION
PLAN
REF.
ROOM
AREA
(SF)
DAYLIGHTING
WATTS OF
CONTROL
LIGHTING
LIGHTING
ADJUST.
FACTOR'
CONTROL
CREDIT
WATTS
(H X 1)
WINDOW
WALL
RATIO
GLAZING
VLT
SKYLIGHT
EFFECTIVE
APERTURE'
ADA Restroom
Occ Sensor - <= 250
sqft
75
62
75
0.20
15
ADA Restroom
Occ Sensor <= 250
75
62
751
0.20
15
Server Room
Occ Sensor - <= 250sqft
2X4
137
228
0.20
46
Break Room
Occ Sensor - <= 250sqft
2x4
148
228
0.20
46
Office 1
Occ Sensor
sqft <- 250
2X4
167
228
0.2046
Office 2
Occ Sensor ft- <= 250
2X4
167
228
0.20
46
offices
Occ Sensor <- 250
ft
2x4
167
228
0.20
46
Office 4
Occ Sensor <= 250
2x4
167
228
0.20
46
Conference Room
Occ Sensor - <= 250sqft
2X4
200
228
0,20
46
Offices
Dimming - Manual
75
1,366
150
0.10
15
1) From Equation 146-A
2) From Table 146-A
PAGE TOTAL 364
BUILDING TOTAL 364
Enter In LTG -2-C: Lighting Control Credit
EnergyPro 4.1 by EnergySoft User Number: 5950 Job Number. C06107 Pape: 10 of 12 1
INDOOR LIGHTING POWER ALLOWANCE LTG -5--7C
PROJECT NAME
Land America Commonwealth
DATE
6/6/2006
ALL9A9Q LIGHTING POWER (Choose One Method)
COMPLETE BUILDING METHOD - CONDITIONED SPACES
COMPLETE ALLOWED
BLDG. AREA WATTS
BUILDING CATEGORY (From Section 146 Table 146-B)
WATTS
PER SF
AREA CATEGORY METHOD - CONDITIONED SPACES
AREA CATEGORY (From Section 146 Table 146-0)
WATTS
PER SF
AREA
(SF)
ALLOWED
WATTS
Corridor/Restroom/Support
0.60
124
74
Office
1.20
2,319
2,783
Convention/Conference/Meeting
1.40
200
280
PAGE TOTAL
BUILDING TOTAL
2,643
3,137
2,643
3,137
AREA
WATTS
TAILORED METHOD - CONDITIONED SPACES
TOTAL ALLOWED WATTS
(From LTG -6-C or from computer run.)
��
UNCONDITIONED SPACES
Complete Building and Area Category Methods
Category (From Section 146 Table 146 -B&C)
WATTS
PER SF
AREA
(SF)
ALLOWED
WATTS
PAGE TOTAL
BUILDING TOTAL
AREA
WATTS
TAILORED METHOD - UNCONDITIONED SPACES
TOTAL UNCONDITIONED SPACES ALLOWED WATTS
(From LTG -5-C and LTG -6-C) 0
�.=gyrru �. uy ui"iyyOun user Numoer: aaau JOD Number: 606107 Page: 11 Of 12 1
LIGHTING MANDATORY MEASURES LTG -MM
ECT NAME
Land America Commonwealth
DATE
6/6/2006
DESCRIPTION
Designer
Enforcement
§131(d)1 For every floor, all interior lighting systems shall be equipped with a separate automatic
control to shut off the lighting. This automatic control shall meet the requirements of
Section 119 and may be an occupancy sensor, automatic time switch, or other device
capable of automatically shutting off the lighting.
X] §131 (d)2 Override for Building Lighting Shut-off: The automatic building shut-off system is
provided with a manual, accessible override switch in sight of the lights. The area
of override is not to exceed 5,000 square feet.
X] §119(h) Automatic Control Devices Certified: All automatic control devices specified are
certified, all alternate equipment shall be certified and Installed as directed by the
manufacturer.
a§111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for
the project are certified and listed in the Directory. All installed fixtures shall be
certified.
❑ §132 Tandem Wiring for One and Three Lamp Fluorescent Fixtures: All one and three
lamp fluorescent fixtures are tandem wired with two lamp ballasts where required
by Standards Section 132; or all one and three lamp fluorescent fixtures are
specified with electronic high -frequency ballasts and are exempt from tandem
wiring requirements.
X❑ §131(a) Individual Room/Area Controls: Each room and area in this building is equipped
with a separate switch or occupancy sensor device for each area with floor -to -
ceiling walls.
§131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100
square feet and more than 0.8 watts per square foot of lighting load shall be
controlled with bi-level switching for uniform reduction of lighting within the room.
❑ §131(c) Daylight Area Control: All rooms with windows and skylights that are greater than
250 square feet and that allow for the effective use of daylight in the area shall
have 50% of the lamps in each daylit area controlled by a separate switch; or the
effective use of daylight cannot be accomplished because the windows are
continuously shaded by a building on the adjacent lot. Diagram of shading during
different times of the year is included on plans.
§131(e) Display Lighting. Display lighting shall be separately switched on circuits that
are 20 amps or less.