13-1148 (RER) Title 24BUILDING ENERGY ANALYSIS REPORT PROJECT: Meyer's Guest House Addition 46370 Cameo Palms Dr. La Quinta, CA 92253 Project Designer: AA Design 81-692 Rancho Santana Dr. La Quinta, CA 92253 760-272-4285 Report Prepared by: Gina Rose -Starkey EQS, Inc. P.O. Box 170 Gold Hill, OR 97525 760-218-3350 Job Number: Date: 10/29/201 The EnergyPro computer program has been used to perform the calculations summ authorized by the California Energy Commission for use with both the Residential This program developed by EnergySoft, LLC 5.1 by EnergySoft User Number. I—P, ()UaNTA & sAFEV DEPT. ��O ��N FdR C�Ngi zed in this c li repop his p cet id Nonresi i I BuiPi DPSE and is I TABLE OF CONTENTS Cover Page Table of Contents Form CF -1 R Certificate of Compliance Form MF -1 R Mandatory Measures Summary Eiv ® gUkt°jr4G & VIOVED oR CpNSTR gY QATE �� EnergyPro 5.1 by EnergySoft Job Number: ID: User Number: 5862 1 2 3 9 PERFORMANCE CERTIFICATE: Residential Part 1 of 5 CF -1 R Project Name Meyer's Guest House Addition Building Type ® Single Family ❑ Addition Alone ❑ Multi Family ® Existin + Additio Alteration 11012912013 Date Project Address 46370 Cameo Palms Dr. La Quinta California Energy Climate Zone CA Climate Zone 15 Tota ond.FloorAreaY 1,444 Addition 0 # of Stories 1 FIELD INSPECTION ENERGY CHECKLIST ❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be pr ed per Part 2 of 5 of this form. ❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details. INSULATION Construction Type Area Special Cavity (ft) Features see Part 2 of 5 Status Wall Wood Framed R-19 1,701 Existing Door Opaque Door None 40 New Slab Unheated Slab -on -Grade None 1,444 Perim = 246' Existing Roof Wood Framed Attic R-30 1,453 Existing Wall Wood Framed R-21 308 New Door Opaque Door lnsul 20 Existing Roof Wood Framed Attic R-38 135 New FENESTRATION U- Exterior Orientation Area(ft) Factor SHGC Overhang Sidefins Shades Status Left (N) 308.3 0.400 0.26 none none Bug Screen New Right (S) 96.0 0.400 0.26 none none Bug Screen New HVAC SYSTEMS Qtv. Heating Min. Eff Cooling Min. Eff Thermostat Status 1 Central Furnace 78% AFUE Split Air Conditioner 14.0 SEER Setback New HVAC DISTRIBUTION Location HeatingCoolingDuct Du Location �- -Vall T t tus HVAC System Ducted Ducted Attic, Ceiling"I uen(01 Ot- "r~8-9,; Ne •• i rrM WATER HEATING Qty. Type Gallons Min. Eff Distribution St�tG 1 Instant Gas 1 0.95 Point ofxUse ew �j 0, EnergyPro 5.1 by EnergySoft User Number: 5862 RunCode: 2013-10-29T16:57:0 ID: Page 3 of 11 PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF -1 R Project Name Meyer's Guest House Addition Building Type ® Single Family ❑ Addition Alone 1 ❑ Multi Family ® Existing+ Addition/Alteration Date 11012912013 SPECIAL FEATURES INSPECTION CHECKLIST The enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. HIGH MASS Design - Verify Thermal Mass: 956.0 ft -Exposed Slab Floor, 3.500" thick at Zone 1 HIGH MASS Design - Verify Thermal Mass: 488.0 ft2 Covered Slab Floor, 3.500" thick at Zone 1 HERS REQUIRED VERIFICATION Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a completed CF -4R form for each of the measures listed below for final to be given. The HVAC System HVAC System incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct leakage meets the specified criteria. asnnkril Cj+;D �4(*FE� f O DONS r� gY ppCE EnemyPro 5.1 by EnerqySoft User Number., 5862 RunCode: 2013-10-29T16:57:0 ID: Page 4 of 11 PERFORMANCE CERTIFICATE: Residential (Part 3 of 5) CF -1 R Project Name Building Type m Single Family ❑ Addition Alone Date Meyer's Guest House Addition ❑ Multi Family 10 Existing+ Addition/Alteration 10/29/201 ANNUAL ENERGY USE SUMMARY Standard Proposed Margin TDV kgtu/ft2- r Space Heating 10.08 8.00 2.08 Space Cooling 88.21 96.32 -8.11 Fans 17.68 21.87 -4.19 Domestic Hot Water 19.85 9.22 10.64 Pumps 0.00 0.00 0.00 Totals 135.82 135.40 0.42 Percent Better Than Standard: 0.3% BUILDING COMPLIES - HERS VERIFICATION REQUIRED Fenestration Building Front Orientation: (►M 270 deg Ext. Walls/Roof Wall Area Area Number of Dwelling Units: 1.00 (tM 100 0 Fuel Available at Site: Natural Gas (N) 1,123 308 Raised* Floor Area: 0 (E) 910 0 Slab on Grade Area: 1,444 (S) 340 96 Average Ceiling Height: 9.0 Roof 1,588 0 Fenestration Average U -Factor: 0.40 TOTAL: 404 Average SHGC: 0.26 Fenestration/CFA Ratio: 28.0% REMARKS STATEMENT OF COMPLIANCE This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the Efficiency Standards of the California Code of Regulations. The documentation author hereby certifies that the documentation. is accurate and complete. Documentation Author .. Company EQS, Inc.G`(— 10/29/2013 Address P.O. Box 170 Name Gina Rose -Starkey City/State/ZipCity/State/Zip Gold Hill, OR 97525 Phone 760-218-3350 Signed N D e The individual with overall design responsibility hereby certifies that the propose_d.buildln�d s'ig 1re°p er'd this set wits iiica lbn and of construction documents is consistent with the other compliance for s-atidw ork9ROets, Ye-�p , with any other calculations submitted with this permit application, and recognizes t�iatcorttplra c� us'Nact de ign, duct sealing, verification of refrigerant charge, insulation installation qualit�rand buil8ing n q"P,e s�irequir installer testing and certification and field verification by an approved HERS rate ro, V?'00- ` N Designer or Owner (per Business & Professions Code) �4R Company AA Design �( Rancho Santana Dr. Address 81-692 Name City/State/Zip La Quinta, CA 92253 Phone 760-272-4285 Signed License # Date EnerqvPro 5.1 by EnemySoft User Number- 5862 RunCode: 2013-10-29T16:57.0 /D: Pa e 5 of 11 CERTIFICATE OF COMPLIANCE: Residential FENESTRATION SURFACE DETAILS (Part 4 of 5) CF -1 R Project Name Meyer's Guest House Addition Building Type m Single Family ❑ Multi Family ❑ Addition Alone M Existing+ Addition/Alteration Date 11012912013 OPAQUE SURFACE DETAILS Window 48.3 0.710 Default ' 0.73 Default 0 Removed Double Metal Clear Surface Type Area U- Insulation Factor Cavit Exterior Frame Interior Frame Azm I Tilt Status Joint Appendix 4 Location/Comments Wall 224 0.074 R-19 01 90 Existing 4.3.1-A5 Zone 1 0.400 NFRC Door 38 0.700 None 0 90 Removec 4.5.1-A2 Zone 1 Window 34.0 Wall 810 a074 R-19 90 90.Existing 4.3.1-A5 Zone 1 Window 34.0 Wall 70 0.074.R-19 180 90 Existin 4.3.1-A5 Zone 1 Window 40.0 Door 40 0.700 1 None 180 90 Removec 4.5.1-A2 Zone 1 8 Door 20 0.500 None 180 90 New 4.5.1-A4 Zone 1 9 Wall 437 0.074 R-19 0 90 Existing 4.3.1-A5 Zone 1 10 Door 40 0.700 None 0 90 Removec 4.5.1-A2 Zone 1 Slab 956 0.730 None 0 180 Existing 4.4.7-A1 Zone 1 Slab 488 0.730 None 0 180 Existing 4.4.7-A 1 Zone 1 Roof 1,453 0.031.R-30 0 0 Existing 4.2.1-A20 Zone 1 Wall 154 0.069 R-21 0 90 New 4.3.1-A6 Zone 1 Wall 80 0.074 R-19 90 90 Existing 4.3.1-A5 Zone 1 Door 20 0.500 None 90 90 New 4.5.1-A4 Zone 1 Wall 154 0.069 R-21 180 90 1 New 14.3.1-A6 Zone 1 Wall RO 1 0.074 R-19 270 90 1 Existino 14.3.1-A5 Zone 1 Ove hang Len Ftclt LExt PER I FENESTRATION SURFACE DETAILS A3.01 ID I Type Area I U -Factor SHGC Azm I Status Glazing Type Location/Comments 1 lWindow 37.51 0.400 NFRC 1 0.26 NFRC 1 0 New I Per Contractor Zone 1 2 Window 48.3 0.710 Default ' 0.73 Default 0 Removed Double Metal Clear Zone 1 3 Window 3.8 0.400 NFRC 0.26 NFRC 0 New Per Contractor Zone 1 4 Window 29.0 0.400 NFRC 0.26 NFRC 0 New Per Contractor Zone 1 5 Window 34.0 0.400 NFRC 0.26 NFRC 0 New Per Contractor Zone 1 6 Window 34.0 0.400 NFRC 0.26 NFRC 0 New Per Contractor Zone 1 7 Window 40.0 0.400 NFRC 0.26 NFRC 0 New Per Contractor Zone 1 8 Window 34.0 0.400 NFRC 0.26 NFRC 0 New Per Contractor Zone 1 9 Window 96.0 0.400 NFRC 0.26 NFRC 0 New Per Contractor Zone 1 10 Window 96.0 0.400 NFRC 0.26 NFRC 180 New Per Contractor Zone 1 (1) U -Factor Type: 2 SHGC Type: 116-A = Default Table from Standards, NFRC = Labeled Value 116-B = Default Table from Standards, NFRC = Labeled Value EXTERIOR SHADING DETAILS ID Exterior Shade Type SHGC Window H t Wd Ove hang Len Ftclt LExt Left Fin RExt Dist Len H t Dist Right Fin Len H t 1 Bug Screen 0.76 2 Bug Screen 0.76 3 Bug Screen 0.76 4 Bug Screen 0.76 5 Bug Screen 0.76 6 Bug Screen 0.76 7 Bug Screen 0.76 8 Bug Screen 0.76 v r VO 9 Bu Screen 0.76 10 Bug Screen 0.76 - r_ M nAT Ener Pro 5.1 by Ener Soft User Number: 5862 RunCode: 2013-10-29T16:57:0 ID: Page 6 of 11 CE-R-TIFICATE OF • •- of Project Name Meyer's House Addition Building Type 0 Single Family 1:1 Multi Family 0 Addition Alone r. .Addition/Alteration OPAQUE Joint Appendix 4 Location/Comments FENEST ATION SURFACE DETAILS 0fi9`S� �� ... . .Standards=Labeled Value ._Standards: .- SHADING DETAILS Exterior Shade Type IV M w-F—Ewd 121ml MIN NJ an mm �r�:�EW�Mmk� Ener-qyPro Page 7 . CERTIFICATE OF COMPLIANCE: Residential (Part 5 of 5) CF -1 R Project Name Meyer's Guest House Addition Building Type ® Single Family ❑ Addition Alone ❑ Multi Family 91 Existing+ Addition/Alteration Date 10/29/201 BUILDING ZONE INFORMATION System Name Zone Name New Floor Area Existinq Altered Removed Volume Year Built HVAC System Zone 1 1,444 12,996 1995 Totals 01 01 1,4441 0 HVAC SYSTEMS System Name Qty. Heating Type Min. Eff. Cooling Type Min. Eff. Thermostat Type Status HVAC System 1 Central Furnace 78% AFUE Split Air Conditioner 14.0 SEER Setback New HVAC DISTRIBUTION System Name Heatin' Cooling Duct Ducts Duct Location R -Value Tested? Status HVAC System Ducted Ducted Attic, Ceiling Ins, vented 8.0 m New WATER HEATING SYSTEMS S stem Name Qty. Type Distribution Rated Input Btuh Tank Cap. al Energy Factor or RE Ext. Standby Tank Loss or Insul. R- Pilot Value Status State GAX190 1 Instant Gas Point of Use 180,000 1 0.95 n/a n/a New MULTI -FAMILY WATER HEATING DETAILS HYDRONIC HEATINGsSYSTElJlI JN 5 w Hot Water Piping Length ¢ LIPDff �j 5& ipedN InsuControl S stem Name`°.: Len`tfiFr Thic Qt . HP Plenum Outside Buried ❑ ❑ ❑ ❑ pri�i ❑ ❑ Ene Pro 5.1 by EnerqySoft User Number: 5862 RunCode: 2013-10-29T16:57:0 ID: Pa e 8 of 11 MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R Project Name Meyer's Guest House Addition Date 11012912013 NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF - 1 R -ALT Form) shall supersede the items marked with an asterisk (') below. This Mandatory Measures Summary shall be incorporated into the permit documents, and the applicable features shall be considered by all parties as minimum component performance specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R Form with plans. .Building Envelope Measures: 116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage. §116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a). 117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed. 118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -613 Form. §118(1): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(1) when the installation of a Cool Roof is specified on the CF -1 R Form. *§1 50 a : Minimum R-19 insulation in wood -frame ceiling orequivalent U -factor. 150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value. *§1 50 c : Minimum R-13 insulation in wood -frame wall orequivalent U -factor. *§1 50 d : Minimum R-13 insulation in raised wood -frame floor orequivalent U -factor. 150(f): Air retarding wrap is tested, labeled, and installed according to ASTM E1677-95 2000 when specified on the CF -1 R Form. 150 : Mandatory Vapor barrier installed in Climate Zones 14 or 16. §150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration. Fireplaces, Decorative Gas Appliances and Gas Log Measures: 150 a 1A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox. §150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is e ui ed with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device. §150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of the building, are prohibited. Space Conditioning, Water Heating and Plumbing System Measures: §110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy Commission. §113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5. §115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and spa heaters. 150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA. 150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c). §1500)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped with insulation having an installed thermal resistance of R-12 or greater. §1500)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect ho er tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on AV the tank. §1500)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating s ste and'�n ' e* nathv� recirculatingsections of hot water pipes are insulated per Standards Table 150-B. �� §1500)2: Cooling system piping (suction, chilled water, or brine lines),and piping ins lateT,etw6en a rce d ne irect hot water tank shall be insulated to Table 150-B and Equation 150-A. \ §1500)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 p415,e'e the, reui�es` nt t ards Tab e 123-A. 6 150 • 3A: Insulation is protected from damage, including that due to sunlight, moisture, a ui n-er aintenance and wind. §1500)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclose y i conditioned space. §1500K Solar water -heating systems and/or collectors are certified by the Solar Rating a'dC rt Pica ' or oration. EnergyPro5.1 by EnergySof7 User Number- 5862 RunCode: 2013-10-29T16:57:08 1D: Page 9 of 11 MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF-1 R Project Name Date Meyer's Guest House Addition 11012912013 §150(m)1: All air-distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections 601, 602, 603, 604, 605 and Standard 6-5; supply-air and return-air ducts and plenums are insulated to a minimum installed level of R- 4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct-closure system that meets the applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal o enin s greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used §150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. §150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. 150(m)7: Exhaust fans stems have back draft or automatic dampers. §150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers. §150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material. 150 m 10: Flexible ducts cannot have porous inner cores. §150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in Section 4 of that Standard. Pool and $ a Heating Systems and Equipment Measures: §114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating ora pilot light. §114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction and return lines, or built-up connections for future solar heating. 114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover. §114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or programmed to run only during off-peak electric demand periods. 150 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150 Residential Lighting Measures: §150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies contained in Table 150-C and is not a low efficacy luminaire asspecified by §150(k)2. 150(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d). §150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than 20 kHz. §150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line-voltage socket or line- voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a medium screw-base socket. 150(k)6: Liqhting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k). 150(k)7: All switching devices and controls shall meet the requirements of §150(k)7. be-V* etc §150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitc i n pige' EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 fizor 100 watts f r d 'e ling itr'ia� gy%m be exempt from the 50%high efficacy requirement when: all low efficacy luminaires int isle aecontrofa�aanu l on occu nt dimmer, tl installe sensor, energy management system (EMCS), or a multi-scene programmable cbnt7o sys�emapra'd'�fl er�r� �ara luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility r�bom'sLa?b-ft�g e ick Dori �.' a V� °1` manual-on occupant sensor. §150(k)9: Permanently installed lighting that is internal to cabinets shall use no more th' n 20 W�'S?O� O Oer linear foot of illuminated cabinet. gY EnergyPro 5.1 by EnergySoft User Number: 5862 RunCode: 2013-10-29T16:57:08 ID: Page 10 of 11 MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R Project Name Date Meyer's Guest House Addition 11012912013 §150(k)l0: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms shall be high efficacy. EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on occupant sensor certified to comply with the applicable requirements of §119. EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a manual -on occupancy sensor. §150(k)l 1: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual - on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site is not required to comply with §150 k 11. §150(k)l2: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the Iumiunaire is airtight with air leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between the luminaire housing and ceiling. §150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor, and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor luminaires used to comply with Exceptionl to §150(k)13 may be controlled by a temporary override switch which bypasses the motion sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not be hi h efficacy luminaires. §150(k)l4: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no more than five watts of power as determined according to §130(d). §150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable requirements of Sections 130, 131, 134, and 146. §150(k)16: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119. -y ®V7- LA QU1NTA C11 SAF�'�EPT- BUILDIN PFIO\]F-D FOR ONSTRUCTION DATE EnergyPro 5.1 by EnergySoft User Number. 5862 RunCode: 2013-10-29716:57:08 ID: Page 11 of 11