10-0331 (RER) Title 24BUILDING ENERGY ANALYSIS REPORT I
PROJECT:
Lynch Residence
46560 Cameo Palms Drive
La Q ui nta, CA
Project Designer:
Report Prepared by:
Joan D. Hacker
Insu-form, Inc.
77-810 Las Montana Road,: Suite 210
Palm Desert, Ca 92211
760-345-1352
Job Number::.
APR 18 2010
Date:
3/24/2010
CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CONSTRUCTION
28 20l D 13Y_ ---------
DATE
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
TABLE OF CONTENTS I
Cover Page 1
Table of Contents 2
Form CF -1R Certificate of Compliance 3
Form MF -1R Mandatory Measures Summary 10
HVAC System Heating and Cooling Loads Summary 13
EnergyPro 5.0 by EnergySoft Job Number ID' User Number 2655
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Lynch Residence
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration 13/24/2010
Date
Project Address
46560 Cameo Palms Drive
La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
1,680
Addition
0
# of Stones
1
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes El No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavity (ft) Features see Part 2 of 5 Status
Slab Unheated Slab -on -Grade
None 1,680 Perim = 152' Existing
Wall Wood Framed
R-13 1,106 Existing
Roof Wood Framed Attic
R-22 1,680 Existing
FENESTRATION
Orientation Area(ft)
U- Exterior
Factor SHGC Overhang Sidefins Shades Status
Front (W) 12.0
1.190 0.83 2.0 none Bug Screen Existing
Front (Vlq 40.0
0.710 0.73 2.0 none Bug Screen New
Front (lM 4.5
0.710 0.73 2.0 none Bug Screen New
Front (tM 20.0
0.710 0.73 2.0 none Bug Screen New
Front (Kq 12.2
0.710 0.73 2.0 none Bug Screen New
Front (lM 12.2
0.710 0.73 2.0 none Bug Screen New
Left (N) 7.5
1.190 0.83 2.0 none Bug Screen Existing
Left (N) 40.01
0.710 0.73 2.0 none Bug Screen New
Left (N) 12.2
0.710 0.73 2.0 none Bug Screen New
Left (N) 2.3 (
0.710 0.73 2.0 none Bug Screen New
Left (N) 2.3 f
0.710 0.73 2.0 none Bug Screen New
HVAC SYSTEMS
Qty. Heating
Min. Eff Cooling Min. Eff Thermostat Status
1 Central Furnace
78% AFUE Split Air Conditioner 12.0 SEER Setback Existing
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
Living Zone Ducted
Ducted Atffc, Ceiling Ins, vented 4.2 Existing
WATER HEATING
QtY. Type
Gallons Min. Eff Distribution Status
EnergyPro 5.0 by EnergySoft User Number. 2655 RunCode: 2010-03-24T16:17:2 ID:
Page 3 of 13
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Lynch Residence
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Afteration 13/24/2010
Date
Project Address
46560 Cameo Palms Drive La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
1,680
Addition
0
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes EI No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION Area Special
Construction Type Cavity Features see Part 2 of 5 Status
FENESTRATION U- Exterior
Orientation Area(ft) Factor SHGC Overhang Sidefins Shades Status
Rear (E) 40.0 l 0.710 0.73 2.0 none Bug Screen New
Rear (E) 20.0 0.710 0.73 2.0 none Bug Screen New
Rear (E) 40.0 0.710 0.73 2.0 none Bug Screen New
Right (S) 12.5 1.190 0.83 2.0 none Bug Screen Existing
Right (S) 3.1 1.190 0.83 2.0 none Bug Screen Existing
Right (S) 20.0 0.710 0.73 2.0 none Bug Screen New
Right (S) 40.0 / 0.710 0.73 2.0 none Bug Screen New
Right (S) 3.1 0.710 0.73 2.0 none Bug Screen New
HVAC SYSTEMS
Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status
HVAC DISTRIBUTION Duct
Location Heating Cooling Duct Location R -Value Status
WATER HEATING
Ot . Type Gallons Min. Eff Distribution Status
EnergyPro 5.0 by Ener Soft User Number. 2655 RunCode: 2010-03-24T16:17:2 ID:
Page 4 of 13
PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R
Project Name
Lynch Residence 1
Building Type 0 Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration
Date
3/24/2010
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -4R form for each of the measures listed below for final to be given.
EnemyPro 5.0 by EnergySoft User Number. 2655 RunCode: 201003-24T16:17:2 ID: Page 5 of 13
PERFORMANCE CERTIFICATE: Residential Part 3 of 5 CF -1 R
Project Name
Building Type m Single Family ❑ Addition Alone
Date
Lynch Residence
1 ❑ Multi Family m Existing+ Addition/Alteration
3/24/2010
ANNUAL ENERGY USE SUMMARY
Standard Proposed Margin
TDV kBtu/fe- r
Space Heating 9.69 6.18 3.51
Space Cooling 184.90 178.10 6.80
Fans 40.05 38.36 1.68
Domestic Hot Water 20.03 20.03 0.00
Pumps 0.00 0.00 0.00
Totals 254.67 242.67 12.00
Percent Better Than Standard: 4.7%
BUILDING COMPLIES - NO HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: (M 270 deg Ext. Walls/Roof Wall Area Area
Number of Dwelling Units: 1.00 I'm 320 101
Fuel Available at Site: Natural Gas (N) 250 64
Raised Floor Area: 0 (E) 550 100
Slab on Grade Area: 1,680 (S) 330 79
Average Ceiling Height: 8.0 Roof 1,680 0
Fenestration Average U -Factor: 0.76 TOTAL: 344
Average SHGC: 0.74 Fenestration/CFA Ratio: 20.5%
REMARKS
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
The documentation author hereby certifies that the documentation is accurate and complete.
Documentation Author
Company lnsu-form, Inc.
3/24/2010
Address 77-810 Las Montana Road, Suite 210 Name Joan D. Hacker
ASi
C' /State/Zi Palm Desert Ca 92211 Phone 760-345-1352 ned Date
The individual with overall design responsibility hereby certifies that the proposed building design represented in this set
of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and
with any other calculations submitted with this permit application, and recognizes that compliance using duct design,
duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require
installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Company
Address Name
City/State/Zip Phone Signed License # Date
Ene ro 5.0 by EnergySoft User Number. 2655 RunCode: 2010-03-24T18:17:2 /D: Pace 6 of 13
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
Lynch Residence
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration
Date
13/24)2010
OPAQUE SURFACE DETAILS
24.0
1.190 Default
Surface U- Insulation Joint Appendix
T e Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4
Location/Comments
Slab 1.680 0.730 None
0 180 Existing 4.4.7-A1
Existing Living
we// 219 0.102 R-13
270 90 Existing 4.3.1-A3
Existing Living
Door 40 1.450 None
270 90 Removec 4.5.1-A1
Existing Living
Wall 186 0.102 R-13
0 90 Existing 4.3.1-A3
Existing Living
Door 16 1.450 None
0 90 Remove 4.5.1-A1
Existing Living
Wall 450 0.102 R-13
90 90 Existing 4.3.1-A3
Existing Living
Wall 251 0.102 R-13 1
180 90 Exiling 4.3.1-A3
Existing Living
Roof 1.680 0.0431R-2
270 0 Existing 4.2.1-A6
Existinq Livinq
FENESTRA
ID I Type
1 Window
EXTERIOR SF
ID Exterior
1 Bug Screen
2 Bug Screen
3 Bug Screen
4 Bug Screen
5 Buq Screen
Screen
Screen
Screen
14 JBug Screen
15 IBug Screen
16 IBLtq Screen
N SURFACE DETAILS
Window
Area
U -Factor
SHGC
24.0
1.190 Default
0.83 Default
12.0
1.190 Default
0.83 Default
16.7
1.190 Default
0.83 Default
16.7
1.190 Default
0.83 Default
40.0
0.710 Default
0.73 Default
4.5
0.710 Default
0.73 Default
20.0
0.710 Default
0.73 Default
12.2
0.710 Default
0.73 Default
12.2
0.710 Default
0.73 Default
7.5
1.190 Default
0.83 Default
40.0
0.710 Default
0.73 Default
12.2
0.710 Default
0.73 Default
2.3
0.710 Default
0.73 Default
2.3
0.710 Default
0.73 Default
21.0
1.190 Default
0.83 Default
66.7
1.190 Default
0.83 Default
Type:
pe:
116-A = Default Table from Stanc
116-13 = Default Table from Stanc
WING DETAILS
3.0
270 Removed Single Metal Clear
270 Existing Single Metal Clear
270 Removed Single Metal Clear
270 Removed Single Metal Clear
270 New Double Metal Clear
270 New Double Metal Clear
270 New Double Metal Clear
270 New Double Metal Clear
270 New Double Metal Clear
0 Existing Single Metal Clear
0 New Double Metal Clear
0 New Double Metal Clear
0 New Double Metal Clear
0 New Double Metal Clear
90 Removed Single Metal Clear
90 Removed Single Metal Clear
NFRC = Labeled Value
NFRC = Labeled Value
EnergyPro 5.0 by EnergySoff User Number. 2655 RunCode: 2010-03-24T16:17:2 1D: Page 7 of 13
Window
Ove hang
aC
H t
Wd
Len
H t
LExt
RExt
0.76
4.0
6.0
2.0
0.1
2.0
2.0
0.76
6.0
1.0
2.0
0.1
2.0
2.0
0.76
3.4
5.0
2.0
0.1
2.0
2.0
0.76
3.4
5.0
2.0
0.1
2.0
2.0
0.76
6.8
6.0
2.0
0.1
2.0
2.0
0.76
1.5
1.5
2.0
0.1
2.0
2.0
0.76
6.8
3.0
2.0
0.1
2.0
2.0
0.76
3.4
3.0
2.0
0.1
2.0
2.0
0.76
3.4
3.0
2.0
0.1
2.0
2.0
0.76
3.0
2.5
2.0
0.1
2.0
2.0
0.76
6.8
6.0
2.01
0.1
2.0
2.0
0.76
3.4
3.8
2.0
0.1
2.0
2.0
0.76
1.5
1.5
2.0
0.1
2.0
2.0
0.76
1.5
1.5
2.0
0.1
2.0
2.0
0.76
3.5
6.0
2.0
0.1
2.0
2.0
0.76
6.81
10.0
2.0
0.11
2.0
2.0
EnergyPro 5.0 by EnergySoff User Number. 2655 RunCode: 2010-03-24T16:17:2 1D: Page 7 of 13
CERTIFICATE OF COMPLIANCE:
Residential
Part 4 of 5 CFA R
Project Name
Lynch Residence
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration
Date
1312412010
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
FENESTRATION SURFACE DETAILS
ID
Type Area
U -Factor
SHGC
Azm Status Glazing Type
Location/Comments
17
Window 40.0
1.190 Default
0.83 Default
90 Removed Single Metal Clear
Existing Living
18
Window 40.0
0.710 Default
0.73 Default
90 New Double Metal Clear
Existing Living
19
Window 20.0
0.710 Default
0.73 Default
90 New Double Metal Clear
Existing Living
20
Window 40.0
0.710 Default
0.73 Default
90 New Double Metal Clear
Existing Living
21
Window 12.5
1.190 Default
0.83 Default
180 Existing Single Metal Clear
Existing Living
22
Window 3.1
1.190 Default
0.83 Default
180 Existing Single Metal Clear
Existing Living
23
Window 20.0
0.710 Default
0.73 Default
180 New Double Metal Clear
Existing Living
24
Window 40.0
0.710 Default
0.73 Default
180 New Double Metal Clear
Existing Living
25
Window 3.1
0.710 Default
0.73 Default
180 New Double Metal Clear
Existing Living
(1) U -Factor Type:
2 SHGC T
116-A = Default Table from Standards, NFRC = Labeled Value
116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type
SHGC
Window
Hot Wd
Ove hang Left Fin Right Fin
Len H t LExt RExt Dist Len H t Dist I Len Hgt
17
Bug Screen
0.76
6.8 6.0
2.0 0.1 2.0 2.0
18
Bug Screen
0.76
6.8 6.0
2.0 0.1 2.0 2.0
19
Bug Screen
0.76
6.8 3.0
2.0 0.1 2.0 2.0
20
Bug Screen
0.76
6.8 6.0
2.0 0.1 2.0 2.0
21
Bug Screen
0.76
2.5 5.0
2.0 0.1 2.0 2.0
22
Bug Screen
0.76
1.2 2.8
2.01 0.1 2.0 2.0
23
Bug Screen
0.76
6.8 3.0
2.0 0.1 2.0 2.0
24
Bug Screen
0.76
6.8 6.0
2.0 0.1 2.0 2.0
25
Bug Screen
0.76
1.2 2.8
2.0 0.1 2.0 2.0
EnergyPro
5.0 by EnergySoft
User Number. 2655
Runcode: 2010-03-24T16:17:2 ID:
Page 8 of 13
CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5
CF -1 R
Project Name
Lynch Residence
Building Type
® Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration
Date
3/24/2010
BUILDING ZONE INFORMATION
System Name
Zone Name New
Floor Area
Existing Altered Removed Volume Year Built
Living Zone Existing Living
1,680
13,440 1980
Totals
01 1,6801 01 01
1
HVAC SYSTEMS
System Name
Qty. Heating Type Min. Eff.
Cooling Type Min. Eff. Thermostat Type Status
Living Zone
1 Central Furnace 7846 AFUE Split Air Conditioner 12.0 SEER Setback
Existing
HVAC DISTRIBUTION
System Name
Heating Cooling
Duct
Duct Location R -Value
Ducts
Tested? Status
Living Zone Ducted Ducted Attic, Ceiling Ins, vented 4.2
❑ Existing
13
WATER HEATING SYSTEMS
S stem Name
Type
Distribution
Rated
Input
Btuh
Tank
Cap.
al
Energy Standby
Factor Loss or
or RE Pilot
Ext.
Tank
Insul. R-
Value
Status
Standard Gas 50 gal or Le
1
Small Gas
Kitchen Pipe Ins
40,000
50
0.53 n/a
n/a
Existing
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONIC
HEATING SYSTEM
PIPING
Control
E
2
E
T
w tL
Hot Water Piping Length
ff
c
o
io
a —
System Name
Pipe
Length
Pipe
Diameter
Insul.
Thick.
Ot . HP
Plenum Outside Buried
❑
❑
❑
❑
❑
❑
❑
❑
❑
❑
Enemifto 5.0 by EneigySoft
User Number. 2655 RunCode: 2010-03-24T16:17:2 ID:
Page 9 of 13
CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5
CF -1 R
Project Name
Lynch Residence
Building Type
® Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration
Date
1312412010
BUILDING ZONE INFORMATION
System Name
Zone Name New
Floor Area
Existing Altered Removed Volume Year Built
Living Zone Existing Living
1,680
13,440 1980
Totals
01 1,6801 01 0
HVAC SYSTEMS
System Name Qty.
Heating Type Min. Eff.
Cooling Type Min. Eff. Thermostat Type Status
Living Zone
1 Central Furnace 78% AFUE Split Air Conditioner 12.0 SEER Setback
Existing
HVAC DISTRIBUTION
System Name
Heating Cooling
Duct
Duct Location R -Value
Ducts
Tested? Status
Living Zone Ducted Ducted Attic, Ceiling Ins, vented 4.2
❑ Existing
13
13
WATER HEATING SYSTEMS
S stem Name
Type
Distribution
Rated
Input
Btuh
Tank
Cap.
al
Energy Standby
Factor Loss or
or RE Pilot
Ext.
Tank
Insul. R-
Value
Status
Standard Gas 50 gal or Le 1
Small Gas
Kitchen Pipe Ins
40,000
50
0.53 n/a
n/a
Existing
MULTI -FAMILY WATER HEATING
DETAILS
HYDRONIC
HEATING SYSTEM
PIPING
Control
E
m
w a-
Hot Water Piping Length
ff
c
N
v
a —
System Name
Pipe
Len th
Pipe
Diameter
Insul.
Thick.
Qty. HP
Plenum Outside Buried
❑
❑
❑
❑
❑
❑
❑
❑
Enemktro 5.0 by EnergySoft
User Number. 2655 RunCode: 2010-03-24T16:17:2 ID:
Page 9 of 13
MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R
Project Name
Lynch Residence
Date
13)24/2010
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -6R Form.
§118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the
installation of a Cool Roof is specified on the CF -1 R Form.
*§150(a): Minimum R-19 insulation in wood -frame ceiling orequivalent U -factor.
§150(b): Loose fill insulation shall conform with manufacturer's installed desi n labeled R -Value.
*§1 50 c : Minimum R-13 insulation in wood -frame wall orequivalent U -factor.
*§1 50 d : Minimum R-13 insulation in raised wood -frame floor or equivalent U -factor.
§150(f): Air retarding wrap is tested, labeled, and installed according to ASTM E1677-95(2000) when s ecified on the CF -1R Form.
§150(q): Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0 permAnch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150 e 1 A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150(e)l B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible operable, and tight -fitting damper and or a combustion -air control device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow, prevention, pump isolation valve and recirculation loop connection requirements of §113(c)5.
§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
§150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c).
§1506)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§1506)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
§1506)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of
recirculating sections of hot water pipes are insulated per Standards Table 150-13.
§1506)2: Cooling system piping (suction, chilled water, or brine Iines),and piping insulated between heating source and indirect hot
water tank shall be insulated to Table 150-B and Equation 150-A.
§1506)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table
123-A.
1500)3A: Insulation is protected from damage, including that due to sunlight, moisture equipment maintenance and wind.
§1506)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned space.
150(a)4: Solar water-heatin systems and/or collectors are certified by the Solar Rating and Certification Corporation.
EnergyPro 5.0 by EnergySoft User Number. 2655 RunCode: 2010-03-24T16:17:24 ID: Page 10 of 13
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R
Project Name
Date
Lynch Residence
13/24/2010
§150(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150(m)l : Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tae is used in combination with mastic and draw bands.
150(m)7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150(m)10: Flexible ducts cannot have porousinner cores.
§150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
required in Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines or built-up connections for future solar heating.
114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
§150(p): Residential pool systems orequipment meet the pump sizing,flow rate, piping, filters and valve requirements of §150(p).
Residential Lighting Measures:
§150(k)l : High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is not a low efficacy luminaire as specified by §150(k)2.
150(k)3: The wattage of permanently installed luminaires shall be determined as specified by §130(d).
§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz.
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
medium screw -base socket.
150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k).
150(k)7: All switching devices and controls shall meet the requirements of §150(k)7.
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and all permanently installed
luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a
manual -on occupant sensor.
§150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
EnergyPro 5.0 by EnergySoft User Number. 2655 RunCode: 2010.03-24716:17:24 ID: Page 11 of 13
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R
Project Name
Date
Lynch Residence 13/24/2010
§150(k)11: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less
than 1000 square feet located on a residential site is not required to comply with §150 k 11.
§150(k)l2. Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)l3: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exceptions to §150(k)l3 may be controlled by a temporary override switch which bypasses the motion
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be high efficacy luminaires.
§150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more than five watts of power as determined according to §130(d).
§150(k)l5: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
requirements of Sections 130,131, 134, and 146.
§150(k)l6: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided
that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
EnergyPro 5.0 by EnergySoff User Number. 2655 RunCode: 2 01 0-03-24 71 6:17:24 /D: Page 12 of 13
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Lynch Residence
Date
3/24/2010
System Name
Living Zone
Floor Area
1,680
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL COOLING PEAK
CFM Sensible
Total Room Loads 1,072 34,185
Return Vented Lighting o
Return Air Ducts 3,811
Return Fan 0
Ventilation 0 0
Supply Fan 0
Supply Air Ducts 3,811
TOTAL SYSTEM LOAD 41,807
COIL
Latent CFM
1,987 584
0 0
1,987
G. PEAK
Heating System
Sensible
Output per System 70,000
29,146
Total Output Btuh) 70,000
Output Btuh/s ft 41.7
2,537
Cooling System
0
Output per System 56.E
0
Total Output (Btuh) 58,000
0
Total Output (Tons) 4.8
2,537
Total Output Btuh/s ft 34.5
Total Out ut s ft/Ton 347.6
34,219
Air System
CFM per System
1,300
HVAC EQUIPMENT SELECTION
Alrftow ctm)
1,300
Existing HVAC 46,998
Total Adjusted System Output 46,998
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
0 70,000
0 70,000
Aug 3 PM I Jan 1 AM
Airflow (cfm/ft 0.77
Airflow cin/Ton 269.0
Outside Air %) 0.0%
Outside Air (cfm/s ft) 0.00
Note: values above given at ARI conditions I
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
26 OF 68 OF
Air
0 cfm Supply Fan
1,300 afrn
68 OF
-NBC
68 OF 119 OF
PJOutside
Heating Coil
H7
117 OF
ROOM
" M
70 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Coolie Peak
112/78°F 80/59°F 80/59°F 46/44°F
Outside Air
0 cfm Supply Fan Cooling Coil
1,300 cfm
29.7 %
80/59°F
48 / 45 OF
-
ROOM
78/58°F
EnergyPro 5.0 by EnergySoff
User Number. 2655 RunCode: 201043-24T16:17:24 ID:
Page 13 of 13