11-0458 (RER) Title 24BUILDING ENERGY ANALYSIS REPORT
PROJECT:
' Cameo Palms
46590 Cameo Palms
La Quinta, CA 92253
I
t Project Designer:
National Ally Trust No 1643182009
=N
16033 Bolsa Chica, Unit 104154
Huntington Beach, CA 92649
(714) 602-3588
Report Prepared by:
Steve K. Means
EasyTitle24
852 Galvin Dr.
EI Cerrito, CA 945301%.&-Mmez
(925)6 7 -1 -4 7 89 CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
INSTALLERS: CLICK LEFT HAND APPROVED
LINK AT W W W.ETITLE24.COM
FOR FIELD COMPLIANCE FORMS FOR CONSTRUCTION
OAT
S �ti<< 8Y_
Job Number:
EZ1786
Date:
4/30/2011
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC — www.energysoft.com.
EnergyPro 5.1 by EnergySoft User Number.' 2729 RunCode: 2011-0430718:30:53 ID: EZ1786
USES AND LIMITATIONS
What This Report Is
Upon'validation (as instructed below), this Report certifies compliance of the subject building(s) with the California's
"Energy Efficiency Standards for Residential and Nonresidential Buildings" as regulated by the California Energy
Commission. Compliance is contingent upon building according to the designer -coordinated plans and other permit-'
documents. Note that all project data has been supplied by client. EasyTitle24.com is responsible for computer entry of
the supplied data, and for computer simulation only. Please keep a copy of this important Report for your records.
Form CF -111 in this Report contains minimum requirements for envelope and duct insulation, space conditioning equipment and
water heater efficiencies (WH tank size is a maximum,and WH input rating is not directly regulated). Refer to the CEC Residential
Manual, Sec. 5.1.4, for a description of any hot water Distribution Type including "Standard." The form also summaries the types
and maximum amounts of glazing for each elevation, and gives fenestration ratings maximums. Read the "Special Features inspec-
tion Checklist," "HERS Required Verification" and "Remarks" sections for other important requirements/notifications.
Form'MF-IR in this Report is a checklist of mandatory energy conservation features. Not all of these measures will pertain to
your project, and some may be superseded by more stringent measures required by Form CF -1R. Of particular significance are the
sections on "Space Conditioning, Water Heating and Plumbing System Measures," and "Residential Lighting Measures." Whole
house continuous or timer -controlled ventilation is required in new dwellings, and in projects with additions larger than 1,000
square feet. It is the designer's responsibility to ensure that the construction documents comply with applicable mandatory features.
This may entail lighting and/or mechanical design work beyond the scope of recent practice.
HVAC -Sizing Summary (if included) gives ASHRAE heating and cooling loads for the building. The inside design temperatures
used are the ones stipulated in Section 150(h)2 of the Energy Efficiency Standards, and may be somewhat extreme (thus resulting
in decreased loads). These loads are only one of many factors to consider in the selection of HVAC equipment. Air flow
requirements are more important in most cases. Any system outputs and/or airflow rates�shown are merely entered to allow the
energy. simulation program (EnergyPro) to function properly (these are not regulated, except that you must install a system that meets
or exceeds the calculated heating load).
What This Report Is Not
This Report is not a design document. It merely describes minimum and maximum specifications for certain components
and systems which may effect material and product selection. It is the building designer's responsibility to coordinate
the information contained in this Report with the project's construction documents. Any products named in this
Report are only exemplary in nature (equivalent or better products by different manufacturers almost certainly exist).
Knowledge of local energy or "green" ordinances, product specifications, construction details, design integration, option-
al upgrades, and proper instal lation/inspection procedures are not responsibilities assumed by the producer of this Report.
This Report does not describe criteria for an "energy efficient" design. It merely documents that the design --as analyzed-
-will meet California's code minimum energy efficiency requirements. If you are interested in achieving higher levels of
energy efficiency we recommend you start by contacting your utility's residential construction programs office.
Report Validation
In order for this Report to become valid, it must be processed and coordinated with the construction documents as
directed in the "Energy Efficiency Standards." The following actions are required:
—The designer(s) must review and coordinate this report with all of the project's construction documents. This includes
integrating all requirements on Form CF -1R, and applicable requirements from Form MF -I R.
-The chief designer or the owner (or owner's representative --as may be allowed by the local building department) must
sign the "Statement of Compliance" on Part 3 of Form CF -1R.
Forms MF -IR and signed CF -IR must be reproduced on the plan sheets (the intention is that they be communicated to
all bidders, contractors, and subcontractors).
Conditions Invalidating the Implied Warranty %
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Cameo Palms
Building Type m Single Family ❑ Addition Alone
❑ Multi Family ® Existing+ Addition/Alteration
Date
4/30/2011
Project Address
46590 Cameo Palms La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
1,588
Addition
0
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavity (ft) Features see Part 2 of 5 Status,
Wall Wood Framed
None 917 Existing
Door Opaque Door
None 50 Existing
Wall Wood Framed
None 104 Existing
Slab Unheated Slab -on -Grade
None 1,588 Perim = 168' Existing
Roof Wood Framed Attic
R-38 1,584 Altered
FENESTRATION U-
Orientation Area Factor
Exterior
SHGC Overhang Sidefins Shades Status
Front (tM 38.0 0.510
0.33 none none Bug Screen Altered
Front'(tM 54.0 1.190
0.83 none none Bug Screen Existing.
Left (N) 22.6 0.510
0.33 none none Bug Screen Altered
Rear (E) 30.6 0.510
0.33 none none Bug Screen Altered -
Rear (E) " 105.7 0.570
0.31 none none Bug Screen Altered
Right (S): 22.6 0.510
ti
0.33 none none Bug Screen Altered -
Skylight. 4.0 1.980
0.83 none none None Existing .
HVAC SYSTEMS
Qty.,, Heating Min. Eff Cooling Min. Eff Thermostat Status`
1 Packaged Heat Pump 5.60 HSPF Packaged Heat Pump 8.0 SEER Setback
Existing
HVAC DISTRIBUTION
Location Heating
Duct
Cooling Duct Location :{ R -Value Status
Existing HVAC Ducted
Ducted Attic, Ceiling Ins, vented 2.1
Existing•
r
w
1
WATER HEATING
Qt ..'Type Gallons Min. Eff Distribution Status
EnergyPro 5.1 by Ener Soft User Number: 2729 RunCode: 2011-04-30718:30:53 ID: EZ1786
Pa e 3 of 11
PERFORMANCE CERTIFICATE: Residential (Part 2 of 5) CF -,l R
Project Name
Cameo Palms
Building Type ® Single Family ❑ Addition Alone
1 ❑ Multi Family ® Existing+ Addition/Alteration
Date
4/30/2011
SPECIAL FEATURES INSPECTION CHECKLIST
The eriforcement agency should pay special attention to the items specified in this checklist. These items require special written,
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
e..
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -4R form for each of the measures listed below for final to be given.
i
4 �
a
i
f
1
EnergyPro 5.1 by Ener Soft User Number: 2729 RunCode: 2011-04-30718:30:53 ID: EZ1786 Page 4 of 11
PERFORMANCE CERTIFICATE: Residential (Part 3 of 5) CF -1 R
Project.Name
Building Type m Single Family ❑ Addition Alone
Date
Cameo Palms
❑ Multi Family m Existing+ Addition/Alteration
1413012011
ANNUAL ENERGY USE SUMMARY
Standard Proposed Margin
TDV kBtu/ftz r
Space Heating 20.40 21.45 -1.05
Space Cooling 248.84 225.71 23.13
Fans ' 38.66 35.09 3.56
Domestic Hot Water 0.00 0.00 0.00
Pumps 0.00 0.00 0.00
Totals 307.89 282.25 25.64
Percent Better Than Standard: 8.3%
BUILDING COMPLIES - NO HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: (W 270 deg Ext. Walls/Roof Wall Area Area
Number of Dwelling Units: 1.00 (M 416 92
Fuel Available at Site: Natural Gas (N) 256 23
Raised. Floor Area: 0 (E) 416 136
Slab ori Grade Area: 1,588 (S) 256 -23
Average Ceiling Height: 8.0 Roof 1,588 4
Fenestration Average U -Factor: 0.67 TOTAL: 278
'i Average SHGC: 0.42 Fenestration/CFA Ratio: 17.5%
REMARKS
See 'Uses and Limitations' page in this report for important practical and background information.
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed
CA BEC
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Ceiilomia Ass i
q.,000;N4ingnegy Con,ultants
Efficiency Standards of the California Code of Regulations.
Steve K Meana
R08.90.247 & NRMSO-M
t
The documentation author hereby certifies that the documentation is accurate and complete.
Documentation Author
EasyVtle24
Company p
4/30/2011
AddresSo-" ..
852 Galvin Dc Name Steve K. Means
City/State/ZipCity/State/Zip E/ Cerrito, CA 94530 Phone (925) 671-4789 Signed Date
The individual with overall design responsibility hereby certifies that the proposed building design represented in this set
of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and
with any other calculations submitted with this permit application, and recognizes that compliance using duct design,
duct sealing, verification of refrigerant charge, insulation installation quality, and building env to a sealing require
installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Company National Ally Trust No 1643182009
Address 16033 Bolsa Chica, Unit 104154 Name L. French s0�
City/State/Zip Huntington Beach, CA 92649 Phone (714) 602-3588 Signed License # Date
J. y
Ener Pro 5.1 by Ener Soft User Number: 2729 RunCode: 2011-0430718:30:53 ID: EZ1786 Page 5 of 11
,.y
CERTIFICATE OF COMPLIANCE:
Residential (Part 4 of 5) CF -1 R
Project Name
Cameo Palms
Building Type m Single Family ❑ Addition Alone
❑ Multi Family la Existing+ Addition/Alteration
Date
4/30/2011
OPAQUE SURFACE DETAILS
Surface
Tvpe• Area
U- Insulation Joint Appendix
Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Wall
304
0.356 None
270 90 Existing 4.3.1-A1
(E) House
Door
20
0.500 None
270 90 Existin 4.5.1-A4
(E) House
Wall
;- 220
0.356 None
0 90 Existing 4.3.1-A1
E House
Door
13
0.500 None
0 90 Existing 4.5.1-A4
E House
Wall
280
0.356 None
90 90 Existing 4.3.1-A1
E House
Wall
' 113
0.356 None
180 90 Existing 4.3.1-A1
E House
Door
17
0.500 None
180 90 Existing 4.5.1-A4
(E) House
Wall
104
0.356 None
180 90 Existing 4.3.1-A1
(E) House
Slab
1,588
0.730 None
0 180 Existing 4.4.7-A1
E House
Roof
1,5841
0.025 R-38
270 23 Altered 14.2.1-A21 (E=4.2.1 -A2) (E) House
a
7
FENESTRATION SURFACE DETAILS
ID
Type
Area U -Factor SHGC
Azm Status Glazing,Type
Location/Comments
1
Window
38.0 0.510 NFRC 0.33 1 NFRC
270 Altered Operable
(E) House
2
Existing
1.280 Default 0.80 Default
S. Metal Operable ^
pre -altered for above
3
Window
54.0 1.190 Default 0.83 Default
270 Existing S. Metal Fixed
(E) House
4
Window
40.0 0.990 Default 0.74 Default
270 Removed Single Glazed Wood Door
(E) House
5
Window
22.6 0.510 NFRC 0.33 NFRC
0 Altered Operable
(E) House
6
Existing
1.280 Default 0.80 Default
S. Metal Operable
pre -altered for above
7
Window
30.6 0.510 NFRC 0.33 NFRC
90 Altered Operable
(E) House
8
Existing
1.280 Default 0.80 Default
S. Metal Operable
pre -altered for above
9
Window
105.7 0.570 NFRC 0.31 NFRC
90 Altered Custom SGD
(E) House
10
Existing
1.250 Default 0.80 Default
S. Metal SGD
pre -altered for above
11
Window
22.6 0.510 NFRC 0.33 NFRC
180 Altered Operable
(E) House
12
Existing
1.280 Default 0.80 Default
S. Metal Operable
pre -altered for above
13
Skylight
4.0 1.980 Default 0.83 Default
270 Existing S. Metal Skylight
(E) House
(1). U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
(2), SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Window
'Exterior Shade Type SHGC H t Wd
Ove hang Left Fin Right Fin
Len H t LExt RExt Dist. Len Hat Dist Len ..H t
1
Bug Screen
0.76
2
Bug Screen
0.76
3
Bug Screen
0.76
4
Bug Screen
0.76
5
Bug Screen
0.76
6
Bug Screen
0.76
7
Bug Screen
0.76
8
Bug Screen
0.76
9
Bug Screen
0.76
10
Bug Screen
0.76
11
Bug Screen
0.76
12
Bug Screen
0.76
13
None
1.00
[E�neL
Pro 5.1 b EnergySoft User Number: 2729 RunCode: 2011-0430718:30:53 ID: EZ1786
Page 6 of 11
CERTIFICATE OF COMPLIANCE: Residential (Part 5 of 5) CF -1 R
Project Name
Cameo Palms
Building Type ® Single Family ❑ Addition Alone
❑ Multi Family ❑ Existing+ Addition/Alteration
Date
4/30/2011
BUILDING ZONE INFORMATION
System Name Zone Name New
Floor Area ft
Existinq Altered Removed Volume Year Built
Existing HVAG (E) House
1,588
12,704 1965
Totals 01 01 1,5881 01
1
HVAC SYSTEMS
System Name Qty. Heating Type Min. Eff. Cooling Type Min. Eff. Thermostat Type Status
Existing HVAC 1 Packaged Heat Pumj 5.60 HSPF Packaged Heat Pump 8.0 SEER Setback
Existing
HVAC, DISTRIBUTION
System Name Heating Cooling
Duct
Duct Location R -Value
Ducts r
Tested? Status
Existing HVAC Ducted Ducted Attic, Ceiling Ins, vented 2.1
❑ Existing
WATER HEATING SYSTEMS
S stem Name
Qty.
Type
Distribution
Rated
Input
(Btu h)
Tank
Cap.
al
Energy
Factor
or RE
Standby
Loss or
Pilot
Ext.
Tank
Insul. R-
Value
Status
CEC Standard
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONIC
HEATING SYSTEM
PIPING
:Control
Hot Water Piping Length
ft
c
0
iC
773
Q —
System Name
Pipe
Length
Pipe
Diameter
Insul.
Thick.
Q
HP
Plenum Outside
Buried
❑
Ener Pro 5.1 by Ener Soft User Number- 2729 RunCode: 2011-04-30T18:30:53 ID: EZ1786
Pag2 7 of 11
MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R
Project Name
Cameo Palms
Date
4/30/2011
NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (') below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a).
117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -6R Form.
§118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(1) when the
installation of a Cool Roof is specified on the CF -1 R Form.
150(a): Minimum R-19 insulation in wood -frame ceiling orequivalent U -factor.
150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value.
150(c): Minimum R-13 insulation in wood -frame wall orequivalent U -factor.
150 d : Minimum R-13 insulation in raised wood -frame floor orequivalent U -factor.
150(f): Air retarding wrap is tested, labeled, and installed according to ASTM E1677-95 2000 when specified on the CF -1 R Form.
150 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150 a 1A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5.
§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
150 h : Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA.
§150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c).
§150(j)1 A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§1500)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the
tank.
§150(j)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of
recirculating sections of hot water pipes are insulated per Standards Table 150-B.
§150(j)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot
water tank shall be insulated to Table 150-B and Equation 150-A.
§1500)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table
123-A.
150 ' 3A: Insulation is protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
§1 500)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned space.
§150(j)4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
EnergyPro 5.1 by EnergySoR User Number. 2729 RunCode: 2011-0430718:30:53 ID: EZ1786 Page 8 of 11
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R
Project Name
Date
Cameo Palms
4/30/2011
§150(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used
§150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tae is used in combination with mastic and draw bands.
1 50 m 7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150(m;1 0: Flexible ducts cannot have porous inner cores.
§150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
re uired in Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not -use electric resistance heating ora pilot light.
§114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
and return lines, or built-up connections for future solar heating.
114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover.
§114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
programmed to run only during off-peak electric demand periods.
150 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150 .
Residential Lighting Measures:
§150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is not a low eff icacy luminaire asspecified by §150(k)2.
150(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d).
§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz.'
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a
medium,:screw-base socket. 4
150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k).
150(k)7: All switching devices and controls shall meet the requirements of 4150(k)7.
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy.
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and all permanently installed
luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a
manual -on occupant sensor.
§150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts of power per linear foot of
illuminated cabinet.
EnergyPro5.1 by EnergySoft User Number: 2729 RunCode: 2011-0430718:30:53 ID: EZ 1786 Page 9 of 11
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R
Project Name
Date
Cameo' Palms
4/30/2011
§150(k)l0: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a
manual -on occupancy sensor.
§150(k)l 1: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less
than 1000 square feet located on a residential site is not required to comply with §150 k 11.
§150(k)12: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)l3: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exceptionl to §150(k)13 may be controlled by a temporary override switch which bypasses the motion
sensing"function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be hi h efficacy luminaires.
§150(k)l4: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more. than five watts of power as determined according to §130(d).
§150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
requirements of Sections 130, 131, 134, and 146.
§150(k)16: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided
that the� are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
i
t
EnergyPro 5.1 by EnergySoR User Number: 2729 RunCode: 2011-0430718:30:53 ID: EZ1786 Page 10 of 11
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Cameo Palms
Date
4/30/2011
System Name
Existingl HVAC
Floor Area
1,588
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
1
COIL
CFM
Total Room Loads 1,493
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
PEAK COIL HTG.
PEAK
Heating System
Sensible
Latent CFM
Sensible
Output perSystem 0
33,357
2,003 439
31,742
Total Output Btuh 0
0
Out�ut Btuh/s ft 0.0
4,317
2,564
Cooling System
0
0
Output perSystem 42,000
0
0 0
0
Total Output Btuh 42,000
0
4,317
41,9911
2,003
0
Total Output ons 3.5
2,564
Total Output Btuh/s ft 26.4
Total Output s ft/Ton 453.7
36,869
Air System
CFM perSystem
0
HVAC EQUIPMENT SELECTION
Airflow cfm
0
Prior to 1978 Heatpump 32,722
4,007
0
Airflow cfm/s ft
0.00
Airflow cfm/Ton
0.0
Outside Air %
0.0%
Total Adjusted System Output 32,722
(Adjusted for Peak Design conditions)
1 TIME OF SYSTEM PEAK
4,007
Aug 3 PM
0
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
Jan 1 AM
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating Peak
32 OF
Outside Air
0 cfm
{
68 OF
68 OF 140 OF
—
Heating Coil
138 OF
ROOM
70 OF
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak
111 /78°F
Outside Air
0 cfm
80/64°F
r
z,
80/64°F 55/54°F
Cooling Coil 57 / 54 OF
43.7% ROOM
78/63°F
EnergyPro 5.1 by EnergySoft
User Number: 2729 RunCode: 2011-0430718:30:53 ID: EZ1786
Page 11 of 11