Loading...
BCOM2019-0021 Title 24BUILDING ENERGY ANALYSIS REPORT PROJECT: Okura Robata GrilleTenant Improvement 78480 Highway 111 La Quinta, CA 92253 Project Designer: RC Design 73700 Dinah Shore, #405 Palm Desert, CA 92260 (760) 892-1494 Report Prepared by: Tim Scott Scott Design and Title 24, Inc, 74-818 Velie Way, Suite #8 Palm Desert, CA 92260 (760) 200-4780 HR GREEN PACIFIC, II?�C. Reviewed and Approved for Code Compliance Job Number: These plans were reviewed for code compliance on behalf of the AHJ. Approval of these plans shall not be Consirucd to I a permit for or an approval of any violations of any C County, State or Federal laws. Oate: 7/8/2019 RECEIVED JUL 11 2019 CM OF LA QUINTA DESIGN AND DENELOPMENT DEPARTMENT ?C OA4 201 % . 002 I {ICUF LA Q d4 BUILDING DIVISION REYI-EWED FOR �JI� CODE, CO MPLIANCE DATE.P 6' 1; Pao JF C)FF1cE The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2016 Building Energy Efficiency Standards. This program developed by EnergySoft Software — www.energysoft.com. I TABLE OF CONTENTS Cover Page Table of Contents 2 STATE OF CALIFORNIA Indoor Lighting NRCC-LTI-E (Created 7/18) CERTMCATE OF COMPLIANCE This document is used to demonstrate compliance with requirements ;Project Name: Okura Robata GrilleTenant Improvement Project Address: 78480 Hiehwav 111 L. GENERAL INFORMATION 01 Project Location (city) La Quinta 02 Climate Zone 15 03 Occupancy Types Within Project (select all that apply): Office ❑ Retail ❑ Warehouse Parking Garage ❑ High -Rise Residential n Relocatable 230.1 !40.6 and Y4L0 b 2 for indoor Ugh Report Page: Date Prepared: 04 Total Conditioned Floor Area (ft2) 05 Total Unconditioned Floor Area (ft2) 06 $t of Stories (Habitable Above Grade) [] Hotel/Motel ❑ School ✓0 Other (write in): C. COMPLIANCE RESULTS Table Instructions: If any cell on this table says "DOES NOT COMPLY" or "COMPLIES with Exceptional Conditions" refer to Table D for guidance Lighting in conditioned and unconditioned spaces must not be combined for compliance per g1aQ.6r�L: Conditioned: Unconditioned: Allowed Lighting Power per 14§ 0.6(b) (Watts) 01 02 03 1 04 = 05 Complete Building 140.6 c 1 Area Category 140.E c 2 Area Category Footnotes 140.E t 2G Tailored 140.6 c 3 Total Allowed (Watts) 7,500 N N (See Table 1) (See Table 1) 7,500 (See Table K) (See Table L) CALIFORNIA ENERGY COMMISSION M NRCC-LTI• pes using the prescriptive path. Page 1 of 7/8/209 7,500 0 1 ❑ Support Areas Actual Lighting Power per 140.6 a (Watts) 06 07 08 09 Adjustments > Total Designed = Total Actual (Watts) Portable Lighting PAF Control Credits (Watts) 140.E a 140.E a 2 *Includes (-) (-) Adjustments (See Table F) (See Table J) (See Table R) > 7,484 7,484 Controls Compliance (See Table H for Details) Rated Power Reduction Compliance (See Table S for Details) Compliance Results 10 05 Must be>_ 09 140.6 COMPLIES DOES NOT COMPLY Not Applicable CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance: http://www.energy.ca.gov/title24/2016standards July 2018 STATE OF CALIFORNIA Indoor Lighting NRCC-LTI-E (Created 7/!S) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI- Project Name: Okura Robata GrilleTenant Improvement lReport Page: Page 2 of Project Address: 78480 Highway 111 Date Prepared: 7/8/201 D. EXCEPTIONAL CONDITIONS This table is auto filled with uneditable comments because of selections made or data entered in tables throughout the form. No exceptional conditions apply to this project. E. ADDITIONAL REMARKS 19 This table includes remarks made by the permit applicant to the Authority Having Jurisdiction. F. INDOOR LIGHTING FIXTURE SCHEDULE Table Instructions: Include all permanent designed lighting and all portable lighting in offices. 01 02 03 04 05 06 07 08 09 Name or Item Tag Complete Luminaire Description Specialized Luminaire Types Watts per luminaires How Wattage is determined Total number luminaires Exempt per 140.6 a 3 Design Watts g Field Inspector Track Portable Pass Fail 1X4 TPL 1X4 29w 29 NA8 Default 3 87 2X2 TPL 2X2 29 NA8 Default 17 [] 493 [] 40w pend 40 W LED 40 NA8 Default 29 1] 1,160 ❑ ❑ Elk PendIsIll100 W LED 100 NA8 Default 20 ❑ 2,000 El 1:1 Elk Pen 60 W LED 60 NA8 Default 21 1,260 El El Pend 1 Pendant! 150 NA8 Default 1 150 El 1:1 Pend 2 Pendant 2 150 NA8 Default 1 150 El El RFL4 RFL4-14w 14 NA8 Default 118 ❑ 1,652 RFL4-dir RFL4-14w-dir El El 14 NA8 Default 4 El 56 El El Syra Syra Pend. 28w []Ej 28 NA8 Default 17 ❑ 476 El 0 Total Designed Watts CONDITIONED SPACES: 7,484 'NOTES: Authority Having Jurisdiction may ask for Luminaire cut sheets to confirm wattage used for compliance per 130.0 c Wattage used must be the maximum rated for the luminaire, not the lamp. G. TRACK LIGHTING This Section Does Not Apply CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance: http://www.energy.ca.gov/title24/2016standards July 2018 STATE OF CALIFORNIA Indoor Lighting NRCC-LTI-E (Created 7/18) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-E Project Name: Okura Robata GrilleTenant Improvement lReport Page: Page 3 of 6 Project Address: 78480 Highway 111 JDate Prepared: 7/8/2019 H. INDOOR LIGHTING CONTROLS (Not Including PAFs) Table Instructions: Building Level Controls Please include lighting controls for conditioned and unconditioned 01 02 03 paces in this table. When an option having a * is selected, the notes section of this table must be completed. The lighting controls section Mandatory Demand Response Shut-off Controls Field Inspector of the Compliance Summary Table on the first page will show "DOES §JaLlLel §130.11c)Pass Fail NOT COMPLY" if the notes are left blank. Required > 10,000 SF Whole Building: Automatic Time Switch ❑ Area Level Controls 04 05 06 07 08 09 10 11 12 Area Description tion Complete Building or Area Category Primary Function Area Area Controls 13§ 1(, Multi -Level Controls 13p 1 4� Shut -Off Controls 130.1 Uc Primary/Skylit Daylighting 130.1 d Secondary Daylighting 140.6 d Interlocked Systems §140.6(a)1 Field Inspector Pass Fail ❑ ❑ ❑ Restaurant I Dining Manual ON/OFF Dimmer Auto Timeswitch ❑ ❑ ❑ Kitchen Kitchen, Food Preparation Manual ON/OFF Bi-level Switch Auto Timeswitch ❑ ❑ ❑ Restrooms Corridor, Restrm, Stair, Support Manual ON/OFF Bi-level Switch Occ Sensor ❑ ❑ ❑ Office Office (> 250 square feet) Manual ON/OFF Bi-level Switch Occ Sensor ❑ ❑ ❑ *NOTES: Controls with a * require a note in the space below explaining how compliance is achieved. EX. Conference 1: Primary/Skylight Daylighting: Exempt because less than 120 watts of general lighting; EXCEPTION 1 to §130.1(d)2 13 Plan Sheet Showing Daylit Zones: I. LIGHTING POWER ALLOWANCE: COMPLETE BUILDING OR AREA CATEGORY METHODS Table Instructions: Complete the table for each area complying using the Complete Building or Area Category Methods per 140.6 b . Indicate if additional lighting power allowances per AIAQ.E cI or adjustments per 114Q.6 a are being used. Conditioned Spaces 01 02 03 04 05 06 Area Description Complete Building or Area Category Primary Prima Function Area Allowed Density W ftz ( / ) Area z (ft) Allowed Wattage (Watts) Additional Allowances / Adjustments Footnotes PAF Portable Ltg Tenant Improvement Dining 1 7,500 7,500 ❑ ❑ TOTAL: 7,500 7,500 See Tables J, K, R for detail J. POWER ADJUSTMENT: PORTABLE LIGHTING IN OFFICES This Section Does Not Apply CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance: http://www.energy.ca.gov/title24/2016standards July 2018 STATE OF CALIFORNIA Indoor Lighting NRCC-LTI-E (Created 7/18) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-E Project Name: Okura Robata GrilleTenant Improvement Report Page: Page 4 of 6 Project Address: 78480 Highway 111 jDate Prepared: 7/8/2019 K. ADDITIONAL LIGHTING ALLOWANCE: AREA CATEGORY METHOD FOOTNOTES This Section Does Not Apply a] L. TAILORED METHOD GENERAL LIGHTING POWER ALLOWANCE This Section Does Not Apply M. ADDITIONAL LIGHTING ALLOWANCE: TAILORED SPECIAL FUNCTION AREAS ta This Section Does Not Apply N. ADDITIONAL LIGHTING ALLOWANCE: TAILORED WALL DISPLAY This Section Does Not Apply -61 0. ADDITIONAL LIGHTING ALLOWANCE: TAILORED FLOOR AND TASK LIGHTING This Section Does Not Apply P. ADDITIONAL LIGHTING ALLOWANCE: TAILORED ORNAMENTAL/SPECIAL EFFECTS This Section Does Not Apply Q. ADDITIONAL LIGHTING ALLOWANCE: TAILORED VERY VALUABLE MERCHANDISE This Section Does Not Apply R. POWER ADJUSTMENT: LIGHTING CONTROL CREDIT (PAF) 69 This Section Does Not Apply S. RATED POWER REDUCTION COMPLIANCE BY SPACE Fa This Section Does Not Apply CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance: http://www.energy.ca.gov/title24/2016standards July 2018 STATE OF CALIFORNIA Indoor Lighting NRCC-LTI-E (Created 7i1 E) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-E Project Name: Okura Robata GrilleTenant Improvement lReport Page: Page 5 of 6 Project Address: 78480 Highway 111 Date Prepared: 7/8J2019 T. DECLARATION OF REQUIRED CERTIFICATES OF INSTALLATION Table Instructions: Selections have been made based on information provided in previous tables of this document. If any selection needs to be changed, please explain why in Table E. Additional Remarks. These documents must be provided to the building inspector during construction and can be found online at htt YES NO Form/Title Field Inspector Pass Fail t• C NRCI-LTI-01-E - Must be submitted for all buildings ❑ (0 (., NRCI-LTI-02-E - Must be submitted for a lighting control system, or for an Energy Management Control System (EMCS), to be recognized for compliance. El ❑ (.. NRCI-LTI-03-E - Must be submitted for a line -voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to energize only line -voltage track lighting, to be recognized for compliance. 0 ❑ �. 0, NRCI-LTI-04-E - Must be submitted for two interlocked systems serving an auditorium, a convention center, a conference room, a multipurpose room, or a theater to be recognized for compliance. ❑ ❑ (^ (06 NRCI-LTI-05-E - Must be submitted for a Power Adjustment Factor (PAF) to be recognized for compliance. �. (0— NRCI-LTI-06-E - Must be submitted for additional wattage installed in a video conferencing studio to be recognized for compliance. CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance: http://www.energy.ca.gov/title24/2016standards July 2018 STATE OF CALIFORNIA Indoor Lighting NRCC-LTI-E (Created 7/18) CERTIFICATE OF COMPLIANCE Name: Okura Robata GrilleTenant Improvement Address: 78480 Highway 111 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT cumentation Author Name: pany: Tim Scott Scott Design and Title 24, Inc, Report Page: Date Prepared: Documentation Author Signature: Timothy Scott ure Date: CALIFORNIA ENERGY COMMISSION Address: 74-818 Velie Way, Suite #8 CEA/ HERS Certification Identification (if applicable): City/State/Zip: Palm Desert, CA 92260 Phone: (760) 200-4780 RESPONSIBLE PERSON'S DECLARATION STATEMENT I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. NRCC-LTI-E Page 6 of 6 Digitally signed by Timothy Scott Date: 2019 07 08 16:54:19-07'00' 2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer) 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: ress: ip: Ruben Coronado RC Design 73700 Dinah Shore, #405 Palm Desert, CA 92260 Responsible Designer Signature: Date Signed � ._ Z r License: Phone: (760)892-1494 CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance: http://www.energy.ca.gov/title24/2016standards July 2018