14-0515 (AR) Title 24�i
I 11 BUILDING ENERGY ANALYSIS REPORT I
0=
PROJECT:
Mr. & Mrs. Randy Eifler
81-695 Brown Deer Park
La Quinta, CA 92253
Project Designer:
Robert A. Pitchford Design and Drafting
77-622 Country Club Dr. Suite O
Palm Desert, Ca 92211
(760) 346-2856
Report Prepared by:
ARTim.-Scott
Scott Design and Title 24, Inc,
77-085 Michigan Drive
Palm Desert, Ca 92211
(760) 200-4780
LDA-rE
®`F' LA QUA�-
LDING & SAF
AP m,�
OR C h°UCT C
Job Number: ApR 22�h4
BY _ .,pcakt9T�
Date:
4/28/2014
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC—www.energysoft.com.
RunCode: 20140428709:05:16 ID:
l
•
CJ
PERFORMANCE CERTIFICATE: Residential Part 1 of 5
CF -1 R
Project Name
Mr. & Mrs. Randy Eifler
Building Type m Single Family ❑ Addition Alone
❑ Multi Family m Existing+ Addition/Alteration
Date
4/28/2014
Project Address
81-695 Brown Deer Park La Quinta
California Energy Climate Zone
CA Climate Zone 15
Total Cond. Floor Area
4,209
Addition
304
# of Stories
1
FIELD INSPECTION ENERGY CHECKLIST
❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form.
❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details.
INSULATION
Construction Type
Area Special
Cavity f Features see Part 2 of 5 Status
Roof Wood Framed Attic
R-30 3,905 Existing
Wall Wood Framed
R-19 2,777 Existing
Door Opaque Door
None 24 Existing
Slab Unheated Slab -on -Grade
None 4,209 Perim = 358' Existing
Roof Wood Framed Attic
R-38 3 Ext=R-7.0 New
Wall Wood Framed
R-19 196 New
FENESTRATION U-
Orientation Area Factor
Exterior
SHGC Overhang Sidefins Shades Status
Front (N) 26.4 1.040
0.63 none none Bug Screen Existing
Front (N) 8.6 0.550
0.55 none none Bug Screen Existing
Front (N) 43.0 0.550
0.55 none none Bug Screen Removed
Left (E) 126.0 0.550
0.55 none none Bug Screen Existing
Left (E) 82.0 0.550
0.55 none none Bug Screen Removed
Rear (S) 18.0 0.550
0.55 none none Bug Screen Removed
Rear (S) 278.4 0.550
0.55 none none Bug Screen Existing
Right (W) 137.6 0.550
0.55 none none Bug Screen Existing
Left (E) 24.0 0.550
0.55 none none Bug Screen New
HVAC SYSTEMS
Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status
3 Central Fumace 80% AFUE Split Air Conditioner 12.0 Setback
Existing
rSEER
r y LA /�'�
C7A ee• r % .Ii
HVAC DISTRIBUTION
Location HeatingCoolingR,
�� � & MvctTy DE A
Duct LoaationAPPP,'Value� Status
HVAC 1 existing Ducted
Cy
Ducted Attic, Ceiling IA s, vented" H CONS 4r2(W ir`TA, ,
Existib
UH
WATER HEATING
Qt Type Gallons Min. Eff Distribution Status
EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2014-04-28709:05:16 /D:
Page 3 of 21
17J
r-1
L-A
t J
PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R
Project Name
Mr. & Mrs. Randy Eifler
Building Type m Single Family ❑ Addition Alone
1 ❑ Multi Family m Existing+ Addition/Alteration
Date
4/28/2014
SPECIAL FEATURES INSPECTION CHECKLIST
The enforcement agency should pay special attention to the items specified in this checklist. These items require special written
justification and documentation, and special verification to be used with the performance approach. The enforcement agency
determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of
the special justification and documentation submitted.
HERS REQUIRED VERIFICATION
Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a
completed CF -4R form for each of the measures listed below for final to be given.
Cil -
--7-A
BUILDING & QU
/-AHPR0 C
%aUNSTRUCTION
` DATE By
I
Ene Pro 5.1 6 Ene Soft User Number: 6712 RunCode: 20140428709:05:16 /D: Page 4 of 21
0
PERFORMANCE CERTIFICATE: Residential Part 3 of 5 CF -1 R
Project Name
Building Type m Single Family ❑ Addition Alone
Date
Mr. & Mrs. Randy Eifler
❑ Multi Family m Existing+ Addition/Alteration
4/28/2014
ANNUAL ENERGY USE SUMMARY
Standard Proposed Margin
TDV kBtu/ft2- r
Space Heating 3.55 2.69 0.86
Space Cooling 110.55 102.87 7.68
Fans 23.69 22.00 1.70
Domestic Hot Water 0.00 0.00 0.00
Pumps 0.00 0.00 0.00
Totals 137.80 127.56 10.24
Percent Better Than Standard: 7.4%
BUILDING COMPLIES - NO HERS VERIFICATION REQUIRED
Fenestration
Building Front Orientation: (N) 0 deg Ext. Walls/Roof Wall Area Area
Number of Dwelling Units: 1.00 (N) 630 35
Fuel Available at Site: Natural Gas (E) 1,123 150
Raised Floor Area: 0 (S) 648 278
Slab on Grade Area: 4,209 (K9 1,197 138
Average Ceiling Height: 10.5 Roof 3,908 0
Fenestration Average U -Factor: 0.57 TOTAL: 601
Average SHGC: 0.55 Fenestration/CFA Ratio: 14.3%
REMARKS
STATEMENT OF COMPLIANCE
This certificate of compliance lists the building features and specifications needed
to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the
Efficiency Standards of the California Code of Regulations.
The documentation author hereby certifies that the documentation is accurate and complete.
Documentation Author C1 F U, (�(��NT/�
Company Scott Design and Title 24, Inc,
E3U1e t °„;��t , — 282014
Address 77-085 Michigan Drive Name Tim Scott Uri4`' ,
p
City/State/ZipCity/State/Zip Palm Desert, Ca 92211 Phone (760) 200-4780 1 ed VED Date
The individual with overall design responsibility hereby certifies that the propose building derprWrt:estt t' b in th's set
of construction documents is consistent with the other compliance forms and worksheets, with the specifications, Ad
with any other calculations submitted with this permit application, and recolgnizes:that compliance{using duct desig ,
duct sealing, verification of refrigerant charge, insulation installation quality; -and building envelope sealing -require -
installer testing and certification and field verification by an approved HERS rater.
Designer or Owner (per Business & Professions Code)
Company Robert A. Pitchford Design and Drafting
77-622 Country Club Dr. Suite O Robert Pitchford 1
Address Name
City/State/Zip Palm Desert Ca 92211 Phone (760) 346-2856 Signed License # Date
Ene Pro 5.1 by EnerqySoft User Number: 6712 RunCode: 20140428709:05:16 ID: Page 5 of 21
F--1q
lu
C6
CERTIFICATE OF COMPLIANCE: Residential
Part 4 of 5 CF -1 R
Project Name
Mr. & Mrs. Randy Eifler
Building Type m Single Family O Addition Alone
❑ Multi Family m Existing+ Addition/Alteration
Date
4/28/2014
OPAQUE SURFACE DETAILS
Surface
Type Area
U- Insulation Joint Appendix
Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
Roof
3,905
0.031 R-30
0
20 Existing 4.2.1-A20
Existing Residence
Wall
571
0.074 R-19
0
90 Existing 4.3.1-A5
Existing Residence
Door
24
0.500 None
0
90 Existing 4.5.1-A4
Existing Residence
Wall
136
0.074 R-19
0
90 Removec 4.3.1-A5
Existing Residence
Wall
777
0.074 R-19
90
90,Existing 4.3.1-A5
Existing Residence
Wall
167
0.074 R-19
90
90 Removec 4.3.1-A5
Existing Residence
Wall
161
0.074 R-19
180
90 Removec 4.3.1-A5
Existing Residence
Wall
370
0.074 R-19
180
90 Existing 4.3.1-A5
Existing Residence
Wall
1,059
0.074 R-19
270
90 Existing 4.3.1-A5
Existing Residence
Slab
3,905
0.730 None
0
180 Existing 4.4.7-A1
Existing Residence
Roof
3
0.022 R-38 7.0
None
0
20 New 4.2.1-A9
Once Addition
Wall
196
0.074 R-19
90
90 New 4.3.1-A5
Office Addition
Slab
304
0.730 None
0
180 Existing 4.4.7-A 1
Office Addition
FENESTRATION SURFACE DETAILS
ID
Type
Area LI -Factor'
SHGC
Azm Status
Glazing Type
Location/Comments
1
Window
26.4 1.040 Default .
0.63 Default
0 Existing
Entry Door
Existing Residence
2
Window
8.6 0.550 Default
0.55 Default
0 Existing
Double NonMetal Tint
Existing Residence
3
Window
40.0 0.550 Default
0.55 Default
0 Removed
Double NonMetal Tint
Existing Residence
4
Window
3.0 0.550 Default
0.55 Default
0 Removed
Double NonMetal Tint
Existing Residence
5
Window
18.0 0.550 Default
0.55 Default
901 Existing
Double NonMetal Tint
Existing Residence
6
Window
18.0 0.550 Default
0.55 Default
90 Existing
Double NonMetal Tint
Existing Residence
7
Window
3.0 0.550 Default
0.55 Default
• 90 Existing
Double NonMetal Tint
Existing Residence
8
Window
18.0 0.550 Default
0.55 Default
90 Existing
Double NonMetal Tint
Existing Residence
9
Window
18.0 0.550 Default
0.55 Default
90 Existing
Double NonMetal Tint
Existing Residence
10
Window
3.0 0.550 Default
0.55 Default
90 Existing
Double NonMetal Tint
Existing Residence
11
Window
12.0 0.550 Default
0.55 Default
90 Existing
Double NonMetal Tint
Existing Residence
12
Window
12.0 0.550 Default
0.55 Default
90 Existing
Double NonMetal Tint
Existing Residence
13
Window
24.0 0.550 Default
0.55 Default
90 Existing
Double NonMetal Tint
Existing Residence
14
Window
64.0 0.550 Default
0.55 Default
90 Removed Double NonMetal Tint
Existing Residence
15
Window
18.0 0.550 Default
0.55 Default
180 Removed Double NonMetal Tint
Existing Residence
16
Window
192.0 0.550 Default
0.55 Default
1801 Existing
Double NonMetal Tint
Existing Residence
(1) Ll -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-13 = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
ID
Exterior Shade Type SHGC
Window
H t Wd
Overhanq Left Fin
Len H t LExt RExt Dist Len
Ri ht Fin
H t Dist Len H t
1
Bug Screen
0.76
r
2
Bug Screen
0.76
1 K; Y V f- r r ,� ,- ' l
3
Screen
0.76
4
Bu Screen
0.76
A ��.�r-Yi11vi
& S,AO=FTr
5
Bug Screen
0.76
6
Bu Screen
0.76
��
' vt b 1 1
7
Bug Screen
0.76
L
.
S -h
8
Bug Screen
0.76
y
-11
9
Bug Screen
0.76
_
10
Bug Screen
0.76
I ✓" C - -_
Bly
11
Bug Screen
0.76
- ---- - --
-_ _- -
12
Bug Screen
0.76
13
Bug Screen
0.76
14
Bug Screen
0.76
15
Bug Screen
0.76
16
JBug Screen
1 0.761
1
EnergyPro,
5.1 by EnemySoft User Number: 6712 RunCode: 20140428709:05:16 ID:
Page 6 of 21
•
Ll
CERTIFICATE OF COMPLIANCE:
Residential
Part 4 of 5 CF -1 R
Project Name
Mr. & Mrs. Randy Eifler
Building Type m Single Family ❑ Addition Alone
❑ Multi Family la Existing+ Addition/Alteration
Date
1412812014
OPAQUE SURFACE DETAILS
Surface U-
Type Area Factor
Insulation Joint Appendix
Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
FENESTRATION SURFACE DETAILS
ID
Type Area
U -Factor
SHGC
Azm Status
Glazing Type
Location/Comments
17
Window 36.0
0.550 Default
0.55 Default
180 Existing
Double NonMetal Tint
Existing Residence
18
Window 21.6
0.550 Default
0.55 Default
180 Existing
Double NonMetal Tint
Existing Residence
19
Window 3.6
0.550 Default
0.55 Default
180 Existing
Double NonMetal Tint
Existing Residence
20
Window 21.61
0.550 Default
1 0.55 Default
1 180 Existing
Double NonMetal Tint
Existing Residence
21
Window 3.6
0.550 Default
0.55 Default
180 Existing
Double NonMetal Tint
Existing Residence
22
Window 3.0
0.550 Default
0.55 Default
270 Existing
Double NonMetal Tint
Existing Residence
23
Window 3.0
0.550 Default
0.55 Default
270 Existing
Double NonMetal Tint
Existing Residence
24
Window 3.0
0.550 Default
0.55 Default
270 Existing
Double NonMetal Tint
Existing Residence
25
Window 20.0
0.550 Default
0.55 Default
270 Existing
Double NonMetal Tint
Existing Residence
26
Window 3.0
0.550 Default
0.55 Default
270 Existing
Double NonMetal Tint
Existing Residence
27
Window 13.2
0.550 Default
0.55 Default
270 Existing
Double NonMetal Tint
Existing Residence
28
Window 13.2
0.550 Default
0.55 Default
270 Existing
Double NonMetal Tint
Existing Residence
29
Window 13.2
0.550 Default
0.55 Default
270 Existing
Double NonMetal Tint
Existing Residence
30
Window 6.0
0.550 Default
0.55 Default
270 Existing
Double NonMetal Tint
Existing Residence
31
Window 18.0
0.550 Default
0.55 Default
270 Existing
Double NonMetal Tint
Existing Residence
32
Window 1 18.01
0.550 1 Default
1 0.55 Default
2701 Existing
Double NonMetal Tint
Existing Residence
(1) U -Factor Type:
2 SHGC Type:
116-A = Default Table from Standards, NFRC = Labeled Value
116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
ID
Exterior Shade Type
SHGC
Window
H t Wd
Ove hang Left Fin
Len H t LExt RExt Dist Len
Right Fin
H t Dist Len H t
17
Bug Screen
0.76
18
Bug Screen
0.76
,-
19
Bug Screen
0.76
; ' • + I r - r
.ji ' "
20
Bug Screen
0.76
_
21
Bu Screen
0.76
( `' "��' r L SPT 1
22
Bug Screen
0.76
�= 1-
23
Bug Screen
0.76
p c - "v
24
Bug Screen
0.76
' 1V IIU
25
Bug Screen
0.76
26
Bug Screen
0.76
27
Bug Screen
0.76
28
Bug Screen
0.76
-
29
Bug Screen
0.76
30
Bug Screen
0.76
31
1Bug Screen
0.76
32
IBug Screen
0.76
EnergyPro
5.1 ;-y EnergySoft User Number: 6712 RunCode: 2014-04-28709:05:16 /D:
Page 7 of 21
1�
CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R
Project Name
Mr. & Mrs. Randy Eifler
Building Type 0 Single Family O Addition Alone
❑ Multi Family m Existing+ Addition/Alteration
Date
4/28/2014
OPAQUE SURFACE DETAILS
Surface U- Insulation Joint Appendix
Type Area Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments
FENESTRATION SURFACE DETAILS
ID Type Area U -Factor SHGC Azm Status Glazing Type Location/Comments
33 Window 24.0 0.550 1 Default 0.55 Default 270 Existing Double NonMeta/ Tint Existing Residence
34 Window 24.0 0.550 Default 0.55 Default 90 New Double NonMeta) Tint Office Addition
35 Window 18.0 0.550 Default 0.55 Default 90 Removed Double NonMeta/ Tint Office Addition
(1) U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value
2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value
EXTERIOR SHADING DETAILS
Window Ove hang Left Fin Ri ht Fin
ID Exterior Shade Type SHGC H t Wd Len H t I LExt I RExt Dist Len H t Dist Len H t
33 Bug Screen 0.76
34 Bug Screen 0.76 ; I tA7 e- r—
35 Bug Screen 0.76 R� ,� �Y� (� M�\ITA
-� IVUN
r° �;, " "'�
o
.I:z
-
3 Y ►. �- "
"'
RV 1
EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2014-04-28T09:05:16 ID: Page 8 of 21
•
L_I
0
CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5 CF -1 R
Project Name
Mr. & Mrs. Randy Eifler
Building Type m Single Family ❑ Addition Alone
❑ Multi Family m Existing+ Addition/Alteration
Date
1412812014
BUILDING ZONE INFORMATION
System Name Zone Name
Floor Area
New Existinq Altered Removed Volume Year Built
HVAC 1 existing Existing Residence
3,905 41,003 2002
Office Addition
304 3,040
Totals 1 3041 3,9051 01 0
HVAC SYSTEMS
System Name Qty. Heatin Type
Min. Eff. Cooling Type Min. Eff. Thermostat Type Status
HVAC 1 existing 3 Central Furnace
80% AFUE Split Air Conditioner 12.0 SEER Setback Existing
HVAC DISTRIBUTION
System Name Heating
Duct Ducts
Cooling Duct Location R -Value Tested? Status
HVAC 1 existing Ducted
Ducted Attic, Ceiling Ins, vented 4.2 ❑ Existing
WATER HEATING SYSTEMS
S stem Name
Qty.
Type
Distribution
Rated
Input
Btuh
Tank
Cap.
al
Energy
Factor
or RE
Standby
Loss or
Pilot
Ext.
Tank
Insul. R-
Value
Status
CEC Standard
r—
-
I toff
I
I OF 1
A QI IIN11-a—
rr
MULTI -FAMILY WATER
HEATING
DETAILS
HYDRONI,C
HEATING`$YSTEM
PIPING
Control
Hot Water Piping Length
(ft)
o
y
Q
/1t`-` 1
FOR CONS
Sem Name
t
-RUCTI
Pipe
11Ce.n Jh
N
Pipe
-aametei
Insul.
Thick.
Qty. HP
Plenum
Outside Buried
-EnemyAro 5.1 by EnemySoft User Number. 6712
RunCode: 2014-04-28T09:05:16 ID: Page 9 of 21
4
4
MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R
Project Name
Mr. & Mrs. Randy Eifler
Date
1412812014
NOT Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of
the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF -
1 R -ALT Form) shall supersede the items marked with an asterisk (') below. This Mandatory Measures Summary shall be incorporated
into the permit documents, and the applicable features shall be considered by all parties as minimum component performance
specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R
Form with plans.
Building Envelope Measures:
116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage.
§116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain
Coefficient SHGC and infiltration that meets the requirements of 10-111 (a).
117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed.
118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -6R Form.
§118(1): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the
installation of a Cool Roof is specified on the CF -1 R Form.
150(a): Minimum R-19 insulation in wood -frame ceiling orequivalent U -factor.
4150(b): Loose fill insulation shall conform with manufacturer's installed desi n labeled R -Value.
150(c): Minimum R-13 insulation in wood -frame wall orequivalent LI -factor.
150(d): Minimum R-13 insulation in raised wood -frame floor orequivalent U -factor.
150(f): Air retarding wrap is tested labeled and installed according to ASTM E1677-95 2000 when specified on the CF -1 R Form.
150 : Mandatory Vapor barrier installed in Climate Zones 14 or 16.
§150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance
rate is no greater than 2.0perm/inch and shall be protected from physical damage and UV light deterioration.
Fireplaces, Decorative Gas Appliances and Gas Log Measures:
150 e 1 A: Masonry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox.
§150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is
e uipped with a with a readily accessible operable, and tight -fitting damper and or a combustion -air control device.
§150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the
outside of the building, are prohibited.
Space Conditioning, Water Heating and Plumbing System Measures:
§110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy
Commission.
§113(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release
valve backflow prevention, pump isolation valve and recirculation loop connection requirements of §113(c)5.
§115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances
(appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and
spa heaters.
150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACOA.
150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c).
§150(j)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped
with insulation having an installed thermal resistance of R-12 or greater.
§150(j)l B: Unfired storage tanks, such as storage tanks or backup tanks for solar w�ter"� eating=syptlm4or kotherlindi rec( hot water
tanks have R-12 external insulation or R-16 internal insulation where the internal insO-Qtion R -value is inti cate1d�on the exterior of the
tank. N BUILDING & SAFFTY nI
§150(j)2: First 5 feet of hot and cold water pipes closest to water heater tank, non-recirculatin�g)systern djestir, ength of
recirculatingsections of hot water pipes are insulated per Standards Table 150-B. �r U V E 11 I
§150(j)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated%betQe a t�.iUoj(col'qd indir ct hot
water tank shall be insulated to Table 150-B and Equation 150-A. I
§150(j)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Stand rds Table
123-A. I DATE BY
150(j)3A: Insulation is protected from damage, including that due to sunlight, moisture a ui ment-maintenance=and-wimd.
§150(j)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor retardant or is enclosed entirely in
conditioned space.
150 ' 4: Solar water -heating systems and/or collectors are certified by the Solar Rating and Certification Corporation.
EnergyPro 5.1 by EnergySoft User Number., 6712 RunCode: 2014-04-28709:05:16 /D: Page 10 of 21
4
MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R
Project Name
Date
r. & Mrs. Randy Eifler
1412812014
§150(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections
601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R-
4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the
applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is
used to seal openings reater than 1/4 inch the combination of mastic and either mesh or tape shall be used
§150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed
sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may
contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area
of the ducts.
§150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes
unless such tape is used in combination with mastic and draw bands.
150(m)7: Exhaust fans stems have back draft or automatic dampers.
§150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated
dampers.
§150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar
radiation that can cause degradation of the material.
150 m 10: Flexible ducts cannot have porous inner cores.
§150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air
Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation
required in Section 4 of that Standard.
Pool and Spa Heating Systems and Equipment Measures:
§114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency
Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and
shall not use electric resistance heating ora pilot light.
§114(b)l : Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction
or built -u connections for future solar heatin .
utdoor ools ors as that have a heat um or as heater shall have a cover.
Lreturnnes
ools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or
d to run onl Burin off eak electric demand eriods.
sidential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150
Residential Lighting Measures:
§150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies
contained in Table 150-C and is not a low eff icacy luminaire asspecified by §150(k)2.
150(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d).
§150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than
20 kHz.
§150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain
only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line -
voltage lamp holder; OR shall be rated to consume no more than five watts of power as -determined by §130(d), and shall not contain a
medium screw -base socket. n►-.-
K
4150(k)6: Li htin integral to exhaust fans, in rooms other than kitchens, shall meet ithe_avy licable(re uirements of; 15Q k ._
X`0l " if' Y 1 V
150(k)7: All switchingdevices and controls shall meet the requirements of 150 k 7. �fl�(� $� �A` 4. . _ r
§150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lightinglin kitchens s shall b`e'hgli efficacy.
s
�M y
EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for -dwelling units largerltha 2,500 ftz ay be
exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kit(hen aree controlled by a•ma Aural on occupant
sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and a�I p��maneritly installed
luminaries in garages, laundry rooms, closets greater than 70 square feet, and utilityjpoi s are high efficacy and controlled by a
manual -on occupant sensor. 1
§150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than`20 watts=of power pe inear-foot_of
illuminated cabinet.
EnergyPro5.1 by EnergySoft User Number: 6712 Run Code: 20140428709:05:16 /D: Page 11 of 21
r
4
i
MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R
Project Name
Date
r. & Mrs. Randy Eifler
4/28/2014
§150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms
shall be high efficacy.
EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on
occupant sensor certified to comply with the applicable requirements of §119.
EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a
manual -on occupancy sensor.
§150(k)l 1: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms,
closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be
allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual -
on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less
than 1000 square feet located on a residential site is not required to comply with §150 k 11.
§150(k)l2: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters
Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air
leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between
the luminaire housing and ceiling.
§150(k)l3: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more
dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the
same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that
they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor,
and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an
astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management
control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor
luminaires used to comply with Exceptionl to §150(k)l3 may be controlled by a temporary override switch which bypasses the motion
sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed
luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not
be high efficacy luminaires.
§150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no
more than five watts of power as determined according to §130(d).
§150(k)l5: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable
requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable
requirements of Sections 130 131 134 and 146.
§150(k)16: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more
dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided
that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119.
CITY OF LA QUINTA
BUILDING & SAFETY
DEPT,
APPROVED P PROVED
RUCTION
DATE
_�� By
EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 20140428709:05:16 /D: Page 12 of 21
4
4
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
Mr. & Mrs. Randy Eifler
Date
4/28/2014
System Name
HVAC 1 existing
Floor Area
4,209
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
3
COIL
CFM
Total Room Loads 2.792
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation 0
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COOLING
Sensible
55,761
0
4,728
01
0
0
4,728
1 65,217
PEAK COIL HTG.
PEAK
Heating System
Latent CFM
Sensible
Output perSystem 71,000
6,887 1,321
56,416
Total Output Btuh 213,000
Output Btuh/s ft 50.6
4,008
Cooling System
0
Output perSystem 48,000
0 0
0
Total Output Btuh 144,000
6,887
0
Total Output Tons 12.0
4,008
Total Output Btuh/s ft 34.2
Total Output s ft/Ton 350.8
1 64,432
Air System
CFM perSystem
1,600
HVAC EQUIPMENT SELECTION
Airflow cfm
4,800
Existing HVAC
105,319 9,729
213,000
Airflow cfm/s ft
1.14
Airflow cfm/Ton
400.0
213,000
F Jan 1 AM
Outside Air % 0.0%
Total Adjusted System Output
(Adjusted for Peak Design conditions)
TIME OF SYSTEM PEAK
105,319 9,729
Aug 3 PM
Outside Air cfm/s ft 0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS
Airstream Temperatures at Time of Heating
Peak
26 OF 71 OF
Outside Air
0 cfm Supply Fan
4,800 cfm
71 OF
71 OF 113 OF
Heating Coil
112 OF
ROOM
72 OF
CI T 1 �� 1
COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 1 DIAIr-, " Ui -r
112 / 78 OF 71 / 58 OF 71 / 58 OF 50 / 49 °F/-��PR®VE
p c
Outside Air c
0 cfm Supply Fan Cooling Coil
4,800 cfm
71 / 58 OF
4
DEpT
CON f ►v
A7E N
—'�� gy 51 / 50 OF
48.0% R
70 / 58 OF
EnergyPro 5.1 by EnergySoft
User Number: 6712 RunCode: 201404-28T09:05:16
ID: Page 13 of 21
C
•
ROOM HEATING PEAK LOADS
Project Name
Mr. & Mrs. Randy Eifler
Date
4/28/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Existing Residence
Floor Area 3,905.0 ft2
Indoor Dry Bulb Temperature 72 OF
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
1.064
Area
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
to
Ceiling
U -Value
AT *F
Btu/hr
R-30 Roof Attic
3,905.0
0.0310
X
46 =
5,569
R-19 Wall (W. 19.2x6.16)
2,777.0
0.0740
X
46 =
9,453
Entry Door
26.4
1.0400
X
46 =
1,263
Wood Door
24.0
0.5000
X
X
X
X
X
46 =
46 =
46 =
=
=
552
Double NonMetal Tint
550.6
0.5500
13,930
Slab -On -Grade
perim = 336.0
0.7300
11,283
X
X
=
=
X
=
X
X
X
X
X
=
=
=
=
=
X
=
X
X
=
=
X
X
=
=
X
X
X
X
-X
=
=
=
=
=
r--/_
B
P,L
Wtv 1,
FXV,PIOVE
x
b��� FE
; �'`'Pi111is.
► STRU
DF
i
n►
2,049
through an interior surface
X 3,905 X
Area
another room DATE
L _��
10.50 X 0.342/
Height ACH
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X
Schedule Air Sensible
Fraction
Page Total
By
igp
AT
6 = 1,458
TOTAL HOURLY HEAT LOSS FOR ROOM 53,507
EnergyRro 5.1 by EnergySoft User Number.- 6712 RunCode: 20140428709:05:16 /D: Pae 15 of 21
•
•
ROOM HEATING PEAK LOADS
Project Name
Mr. & Mrs. Randy Eifler
Date
4/28/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Office Addition
Floor Area 304.0 ft'
Indoor Dry Bulb Temperature 72 °F
Time of Peak Jan 1 AM
Outdoor Dry Bulb Temperature 26 OF
Conduction
1.064
Area
U -Value
AT °F Btu/hr
46 = 3
46 = 667
46 = 607
46 = 739
=
=
-�
In •" 1:)T.
ED=
n
i8D�
l 2,017
g
/10_461 _46 = 892
R-38 Roof(R.38.2x14.16)
3.4
X
X
X
0.0220 X
0.0740 X
0.5500 X
R-19 Wall (W. 19.2x6.16)
196.0
Double NonMetal Tint
24.0
Slab -On -Grade
perim = 22.0
X
X
0.7300 X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
�r r
X
x FO
to anot er room
DATE
10.-00"X--0,36,0_
Ceiling Height ACH
Items shown with an asterisk (') denote conduction
Infiltration:[ 1.00 X
Schedule Air Sensible
Fraction
through an interior surface
X 304 X
Area
TOTAL HOURLY HEAT LOSS FOR ROOM 2,909
Energ Pro 5.1 by Energ Soft User Number: 6712 Run Code: 20140428709:05:16 /D: Pae 16 of 21
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Mr. & Mrs. Randy Eifler 1 4128/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Existing Residence Outdoor Dry Bulb Temperature 112 OF
Floor Area 3,905.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Daily Range: 34 OF
Orientation
R-30 Roof Attic
R-19 Wall (W. 19.2x6.16)
Wood Door
R-19 Wall (W. 19.2x6.16)
R-19 Wall (W. 19.2x6.16)
R-19 Wall (W 19.2x6.16)
(N)
(N)
(E)
(S)
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
3,905.0
0.0310
56.0
571.0
0.0740
23.0
24.0
0.5000
23.0
777.0
0.0740
33.0
369.6
0.0740
26.0
1,059.4
0.0740
33.0
0.0
31.4
3.0
64.1
0.0
31.4
18.0
64.1
0.0
31.4
18.0
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenectratien
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Internal Gain
Orientatinn
(N)
(N)
(E)
(E)
(E)
(E)
(E)
(E)
(E)
Btu/hr
6,779
972
276
1,897
711
2,587
I 13,2231
Shaded
Area
X
X
X
X
X
X
X
X1
X
GLF
+
+
+
+
+
+
+
+
+
Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
0.0
44.2
26.4
44.2
0.0
31.4
8.6
31.4
0.0
31.4
18.0
64.1
0.0
31.4
18.0
64.1
0.0
31.4
3.0
64.1
0.0
31.4
18.0
64.1
0.0
31.4
18.0
64.1
0.0
31.4
3.0
64.1
0.0
31.4
12.0
Page Total
Occupants 4.0 Occupants X 230 Btuh/occ. _
Equipment 1.0 Dwelling Unit X 1,600 Btu =
Infiltration: 1.064 X 0.94 X 241.80 X 2 - Ty OF ' ^ QUINT, Sensible CFM ELA AT BUILDING &SAF
_ ETY DPP -
TOTAL HOURLY SENSIBLE HEAT GAIN FOR R
Latent Gain
CONSTRUCTION
Occupants 4.0 Occupants X DATE 200 Btuh/occ.
Infiltration: 4,771 X 0.94 X 241.80 X 0.00523 =
Air Sensible CFM ELA AW
• TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
biumr
1,166
270
1,153
1,153
192
1,153
1,153
192
769
7.202
Btu/hr
920
1,600
10107
52,954
Btu/hr
800
5,647
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name Date
Mr. & Mrs. Randy Eifler 1 4/28/2014
ROOM INFORMATION DESIGN CONDITIONS
Room Name Existing Residence Outdoor Dry Bulb Temperature 112 OF
Floor Area 3,905.0 ft' Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Daily Ranoe: 34 OF
Surfaces Orientation
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
I=
=
=
=
=
=
GLF
=
=
=
=
=
=
=
=
=
0.0
31.4
12.0
64.1
0.0
31.4
24.0
64.1
0.0
31.4
192.0
31.5
0.0
31.4
36.0
31.5
0.0
31.4
21.6
31.5
0.0
31.4
3.6
31.5
0.0
31.4
21.6
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fpnpctratinn
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Oripntatinn
(E)
(E)
(S)
(S)
(S)
(S)
(S)
(S)
(tM
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
31.4
12.0
64.1
0.0
31.4
24.0
64.1
0.0
31.4
192.0
31.5
0.0
31.4
36.0
31.5
0.0
31.4
21.6
31.5
0.0
31.4
3.6
31.5
0.0
31.4
21.6
31.5
0.0
31.4
3.6
31.5
0.0
31.4
3.0
64.1
Page Total
Btu/hr
01
Btu/hr
769
1,538
6,055
1,135
681
114
681
Internal Gain Btu/hr
Occupants 4.0 Occupants X 230 Btuh/occ. = 920
Equipment 1.0 Dwelling Unit X ,t-1;600 ,B(u = 1,600
CITY OF LA QUIN
Infiltration: 1.064 X 0.94 X 241.80 X 42 = BUILDING &,SAFE 0,107
Air Sensible CFM ELA eT N DEPT,
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM I r'vH UONVgTR► 152,9541
Latent Gain
Occupants 4.0 Occupants X-200 _gtu, BY - 800
Infiltration: 4,771 X 0.94 X 241.80 X 0.00523 = 5,647
Air Sensible CFM ELA AW
•TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 6.447
•
•
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name7412812014
ate
Mr. & Mrs. Randy Eifler
ROOM INFORMATION DESIGN CONDITIONS
Room Name Existing Residence Outdoor Dry Bulb Temperature 112 OF
Floor Area 3,905.0 ft2 Outdoor Wet Bulb Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranoe: 34 OF
ue Surfaces
Orientation
Area
X
X
X
X
X
X
X
X
X
U -Factor
X
X
X
X
X
X
X
X
X
CLTD'
=
=
=
=
=
=
=
=
=
GLF
=
=
=
=
=
=
=
=
=
0.0
31.4
3.0
64.1
0.0
31.4
3.0
64.1
0.0
31.4
20.0
64.1
0.0
31.4
3.0
64.1
0.01
31.4
13.2
64.1
0.0
31.4
13.2
64.1
0.0
31.4
13.2
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Fenestration
Window Existing
Window Existing
Window Existing
-Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Window Existing
Internal Gain
Orientation
r►M
(►M
(KO
(tM
(tM
(tM
(►M
(►M
(►M
Shaded Unshaded
Area
X
X
X
X
X
X
X
X
X
GLF
+
+
+
+
+
+
+
+
+
Area
X
X
X
X
X
X
X
X
X
GLF
=
=
=
=
=
=
=
=
=
0.0
31.4
3.0
64.1
0.0
31.4
3.0
64.1
0.0
31.4
20.0
64.1
0.0
31.4
3.0
64.1
0.01
31.4
13.2
64.1
0.0
31.4
13.2
64.1
0.0
31.4
13.2
64.1
0.0
31.4
6.0
64.1
0.0
31.4
18.0
64.1
4.0 Occupants X
1.0 Dwelling Unit X
Infiltration: 1.064 X 0.94 X 241.80 X
Air Sensible CFM ELA
AL HOURLY SENSIBLE HEAT GAIN FOR ROOM
Page Total
Btu/hr
171
Btu/hr
192
192
1,281
192
846
846
846
384
1,153
tsiwnr
230 Btuh/occ. = 920
]l,�IY OF LA QUIIN
=BUILDING & SAFETY DE
I APPROVED
Latent Gain I DATE gY
Occupants 4.0 Occupants X z 200"Btuhfocca--
Infiltration: 4,771 X 0.94 X 241.80 X 0.00523 =
Air Sensible CFM ELA AW
1,600
10,107
52,954
I/hr
800
5,647
•
0
4. 4 .i
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name7412812014
ate
Mr. & Mrs. Randy Eifler
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Existing Residence
Outdoor Dry Bulb Temperature 112 OF
Floor Area 3,905.0 ft2
Outdoor Wet Bulb Temperature
78 OF
Indoor Dry Bulb Temperature 70 OF
I Outdoor Daily Range:
34 OF
Opaque Surfaces Orientation Area
U -Factor
CLTD' Btu/hr
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
Page Total 0
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area
GLF
Area GLF Btu/hr
Window Existing (VV)
0.0 X 31.4 +
18.0 X 64.1 = 1,153
Window Existing (IM
0.0 X 31.4 +
24.0 X 64.1 = 1,538
X +
X =
X +
X -
X +
X =
X +
X -
X +
X -
X +
X -
X +
X =
Page Total 2,691
Internal Gain
Btu/hr—
tu/hrOccu
ants 4.0 Occupants X
Occupants
230
Btuh/occ. = 920
Equipment 1.0 Dwelling Unit X
1,600
Btu = 1,600
Infiltration: 1.064 X 0.94 X 241.80 X 42 =
10,107
Air Sensible CFM ELA
AT
ff!T� ®F LA
. C -I 11h
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
ClUILUI fG &
Latent Gain
APPROVED -
NSTF3lIC
Occupants 4.0 Occupants X
100
Btuh/occ. �QN 800
Infiltration: 4,771 X 0.94 X 241.80 X 0.00523 = DATE-- BY 5,6471
Air Sensible CFM ELA
AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
6,447
EneravPro 5.1 by Ene-mySoft User Number: 6712 Run Code: 20140428709:05:16 /D:
Page 20 of 21
•
4
RESIDENTIAL ROOM COOLING LOAD SUMMARY
Project Name
Date
Mr. & Mrs. Randy Eifler
1 4/28/2014
ROOM INFORMATION
DESIGN CONDITIONS
Room Name Office Addition
Outdoor Dry Bulb Temperature 112 OF
Floor Area 304.0 ft2
Outdoor Wet Bulb
Temperature 78 OF
Indoor Dry Bulb Temperature 70 OF
Outdoor Daily Range: 34 OF
Opaque Surfaces Orientation Area
U -Factor CLTD' Btu/hr
R-38 Roof(R.38.2x 14.16) (N)
3.4 X
0.0220 X 56.0 = 4
R-19 Wall (W. 19.2x6.16) (E) 196.0 X
0.0740 X 33.0 = 479
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
X
X =
Page Total 1 483
Items shown with an asterisk (') denote conduction through an interior surface to another room.
1. Cooling Load Temperature Difference (CLTD)
Shaded
Unshaded
Fenestration Orientation Area
GLF
Area GLF Btu/hr
Window New (E)
0.0 X 31.4
+ 24.0 X 64.1 = 1,538
X
+ X -
X
+ X -
X
+ X -
X
+ X =
X
+ X -
X
+ X -
X
+ X -
X
+ X =
Page Total 1,538
Internal Gain
Btu/hr—
tu/hrOccu
ants 0.0 Occupants X
Occupants
230 Btuh/occ. = 0
Equipment 0.0 Dwelling Unit X 1
1,600 Btu = 0
Infiltration: 1.064 X 0.94 X 18.82 X 42 =
787
Air Sensible CFM ELA
AT
CITY OE AQf III\ I -t -
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM
ILU - & c, ter-, —_ -' _ ''2, 07
Latent Gain
APPROVED Btu/h
Occupants o.0 Occupants X
'dfuED
hPocRNSTRUCTa 0
Infiltration: 4,771 X 0.94 X 18.82 X 0.00523 -
D-�_ BY 440
fTE
Air Sensible CFM ELA
AW
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM
440
EnergyPro 5.1 by EnemySoft User Number: 6712 Run Code: 2014 04-28 70 9:05:16
/D: Page 21 of 21