Loading...
06-0671 (BLCK) Title 24TITLE 24 REPORT Title 24 Report for: S-obnstr .ct. o . 78-233 B.i.r-kda1.e Court La Quinta, CA Project Designer: Report Prepared By: Joan D. Hacker Insu-Form Inc. 68255 Corta Road Cathedral City, CA 92234 (760) 324-0216 Job Number: CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTION i eop6-ls OA /VL3 0-By5 E • Date: 9/8/2005 The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2001 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC (415) 897-6400. EnergyPro 3.1 By EnergySoft Job Number: User Number: 2655 (11 I - TABLE OF CONTENTS I Cover Page 1 Table of Contents 2 Form CF -1 R Certificate of Compliance 3 Form MF -1 R Mandatory Measures Checklist 7 Form C -2R Computer Method Summary 9 HVAC System Heating and Cooling Loads Summary 14 Room Load Summary 18 EnergyPro 3.1 By EnergySoft Job Number: User Number: 2655 Certificate of Compliance: Residential (Part 1 of 2) CF -1 R Soba Construction Const. Assembly U -Value 9/8/2005 Project Title X❑ Single Family Detached Date 78-233 Birkdale Court La Quinta ❑ Existing Building ❑ Multi -Family ❑ Existing Plus Addition Project Address 90 deg Floor Construction Type: ® Slab Floor Number of Dwelling Units: Building Permit # Insu-Form Inc. (760) 324-0216 (East) 88.3 -0Fx 0.35 Plan Check / Date Documentation Author Telephone Computer Performance 15 (South) Field Check / Date Compliance Method (Package or Computer) Climate Zone Enforcement Agency Use Only GENERAL INFORMATION Total Conditioned Floor Area: 5,358 ft' Average Ceiling Height: 10.2 ft Total Conditioned Slab Area: 5,358 ft2 Building Type: Const. Assembly U -Value (check one or more) n/a X❑ Single Family Detached ❑ Addition ❑ Single Family Attached ❑ Existing Building ❑ Multi -Family ❑ Existing Plus Addition Front Orientation: (East) 90 deg Floor Construction Type: ® Slab Floor Number of Dwelling Units: 1.00 Number of Stories: 1 ❑ Raised Floor Component Slab On Grade R-19 Wall (W.19.2x6.16) R-38 Roof (R.38.2x14.16) Slab On Grade FENESTRATION Frame Type Const. Assembly U -Value Location/Comments (attic, garage, typical, etc.) n/a 0.756 Exposed Slab w/R-0.0 Perimeter Insulation Wood 0.065 Exterior Wall Wood 0.028 Exterior Roof n/a 0.756 Covered Slab w/R-0.0 Perimeter Insulation Shading Devices Type Orientation Area Fenestration Exterior Overhang Side Fins SF U -Factor SHGC Shading Yes / No Yes / No Front (East) 88.3 -0Fx 0.35 0.29 Bug Screen Left (South) 132.0 0.35 0.29 Bug Screen X❑ ❑ ❑ x❑ Rear (West) 154.5 0.35 0.29 Bug Screen X❑ ❑ ❑ X❑ Right (North) 45.4 0.34 0.26 Bug Screen X❑ ❑ ❑ X❑ Front (East) 168.0 0.34 0.26 Bug Screen X❑ ❑ ❑ X❑ Front (East) 70.5 0.29 0.36 Bug Screen[g] ❑ ❑ X❑ Rear (West) 184.0 0.33 0.33 Bug Screen X❑ ❑ ❑ a Rear (West) 40.0 0.29 0.36 Bug Screen X❑ ❑ ❑ a Left (South) 96.0 0.34 0.26 Bug Screen X❑ ❑ ❑ x❑ Left (South) 24.0 0.29 0.36 Bug Screen X❑ ❑ ❑ x❑ Rear (West) 68.0 0.34 0.26 Bug Screen X❑ ❑ ❑ X❑ Right (North) 111.5 0.35 0.29 Bug Screen X❑ ❑ ❑ x❑ Run Initiation Time: 09/08/05 10:43:00 Run Code: 1126201380 Ener Pro 3.1 By Ener Soft User Number: 2655 Job Number: Pa e:3 of 21 'Certificate of Comaliance: Residential . (Part 1 of 2) CF -1 R Soba Construction Overhang Side Fins 9/8/2005 Project Title Yes / No Date 78-233 Birkdale Court La Quinta ❑ a ❑ ❑ Project Address 1:1 1:1 Building Permit # Insu-Form Inc. (760) 324-0216 El F1 - El El Plan Check / Date Documentation Author Telephone El Computer Performance 15 Field Check / Date Compliance Method (Package or Computer) Climate Zone Enforcement Agency Use Only GENERAL INFORMATION Total Conditioned Floor Area: 5,358 ft2 Average Ceiling Height: 10.2 ft Total Conditioned Slab Area: 5,358 ft2 Building Type: (check one or more) K Single Family Detached ❑ Addition ❑ Single Family Attached ❑ Existing Building ❑ Multi -Family ❑ Existing Plus Addition Front Orientation: (East) 90 deq Floor Construction Type: ® Slab Floor Number of Dwelling Units: 1.00 Number of Stories: 1 ❑ Raised Floor BUILDING SHELL INSULATION Const. Component Frame Assembly Location/Comments Type Type U -Value (attic, garage, typical, etc.) FENESTRATION Shadinq Devices Type Orientation Area Fenestration Exterior Overhang Side Fins SF U -Factor SHGC Shading Yes / No Yes / No Skylight 34.6 0.40 0.29 None ❑ Q ❑ a ❑ ❑ ❑ ❑ 1:1 1:1 El El El El F1 - El El ❑❑ 1:1 1:1 El 1:1 El ❑❑ 1:1 El ❑❑ El FJ El El Run Initiation Time: 09/08/05 10:43:00 Run Code: 1126201380 Ener Pro 3.1 By Ener Soft User Number: 2655 Job Number. Pa e:4 of 21 Certificate of Compliance: Residential (Part 2 of 2) CF -1 R Soba Construction 9/8/2005 Project Title Date HVAC SYSTEMS Note: Input Hydronic or Combined Hydronic data under Water Heating Systems, except Design Heating Load. Distribution Heating Equipment Minimum Type and Duct or Type (furnace, heat Efficiency Location Piping Thermostat Location / pump, etc.) (AFUE/HSPF) (ducts, attic, etc.) R -Value Type Comments Cantral Furnarp 80% AFUE Ducts in Attic 42 Setback Zone 1 Centml Eurnnre _80% AFUE Ducts in Attic 42 Setback Znne 2 Central F irnara 80% AFUE Ducts in Attic 4.2 Setback Zone 3 ('antral Fiirnaca 80% AFUE Ducts in Attic 4.2 Setback Casita Cooling Equipment Minimum Duct Type (air conditioner, Efficiency Location Duct Thermostat Location / heat pump, evap. cooling) (SEER) (attic, etc.) R -Value Type Comments Split Air Conditioner 12.0 SEER Ducts in Attic 49 Sathark 7nne 1 Split Air Conditioner 12 0 SEER Ducts in Attic 42 Sethack 7onp 2 Split Air Conditioner 12.0 SEER Ducts in Attic 4.2 Setback Zone 3 Split Air Conditioner 12.0 SEER Ducts in Attic 4.2 Setback Casita WATER HEATING SYSTEMS Rated 1 Tank Energy Facts 1 External Water Heater Water Heater Distribution # in Input Cap. or Recovery Standby Tank Insul. System Name Type Type Syst. Btu/hr (gal) Efficiency Loss (%) R -Value American G82-5OT38-3 Small Gas Pine Insulation 2- 46000 50 0.65 n/a n/a For small gas storage (rated inputs of less than or equal to 75,000 Btu/hr), electric resistance and heat pump water heaters, list energy factor. For large gas storage water heaters (rated input of greater than 75,000 Btu/hr), list Rated Input, Recovery Efficiency and Standby Loss. For instantaneous gas water heaters, list Rated Input and Recovery Efficiency. REMARKS COMPLIANCE STATEMENT This certificate of compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations, and the administrative regulations to implement them. This certificate has been signed by the individual with overall design responsibility. The undersigned recognize that compliance using duct sealing and TXV's requires installer testing and certification and field verification by an approved HERS rater. Designer or Owner (per Business & Professions Code) Name: Title/Firm: Addr T epho e: Lic. #: grraRr re) (date) nforcement Agency Name: Title/Firm: Address: Telephone: Documentation Author Name: Joan D. Hacker Title/Firm: Insu-Form Inc. Address: 68255 Corta Road Cathedral City, CA 92234 Telephone: (760) 324-0216 0 (si tj ) (date) (signature/stamp) (date) Run Initiation Time: 09/08/05 10:43:00 Run Code: 1126201380 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:5 of 21 Certificate of Compliance: Residential (Addendum) CFA R Soba Construction 9/8/2005 Project Title Date Special Features and Modeling Assumptions The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adeouacv of the justification, and may refect a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. PlanT Field HIGH MASS Design(see C -2R) - Verify Thermal Mass: 1364 sqft Exposed Slab Floor, 3.50" thick at Zone 1 HIGH MASS Design(see C -2R) -Verify Thermal Mass: 1156 sqft Exposed Slab Floor, 3.50" thick at Zone 2 HIGH MASS Design(see C -2R) - Verify Thermal Mass: 1006 sqft Exposed Slab Floor, 3.50" thick at Zone 3 HIGH MASS Design(see C -2R) - Verify Thermal Mass: 1200 sqft Exposed Slab Floor, 3.50" thick at Zone 4 HIGH MASS Design(see C -2R) - Verify Thermal Mass: 632 sqft Covered Slab Floor, 3.50" thick at Casita HERS Required Verification These features must be confirmed and/or tested by a certified HERS rater under the supervision of a CEC approved HERS provider. The HERS rater must document the field verification and diagnostic testing of these measures on a form CF -6R. --FWn7 Field Run Initiation Time: 09/08/05 10:43:00 Run Code: 1126201380 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:6 of 21 .Mandatory Measures Checklist: Residential (Page 1 of 2) MF71 R NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. Items marked with an asterisk (') may be superseded by more stringent compliance requirements listed on the Certificate of Compliance. When this checklist is incorporated into the permit documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures whether they are shown elsewhere in the documents or on this checklist only. DESCRIPTION Instructions: Check or initial applicable boxes or enter N/A if not applicable. DESIGNER ENFORCEMENT Building Envelope Measures ❑X 1150(,): Minimum R-19 ceiling insulation. §150(b): Loose fill insulation manufacturer's labeled R -Value. 150(c): Minimum R-13 wall insulation in wood framed walls or equivalent U -value in metal frame walls (does ❑§ i( not apply to exterior mass walls). § 150(d): Minimum R-13 raised floor insulation in framed floors or equivalent. ❑§ 150(1): Slab edge insulation - water absorption rate no greater than 0.3%, water vapor transmission rate no greater than 2.0 perm/inch. a§118: Insulation specified or installed meets insulation quality standards. Indicate type and form. ® §116-17: Fenestration Products, Exterior Doors and Infiltration/Exfiltration Controls 1. Doors and windows between conditioned and unconditioned spaces designed to limit air leakage. 2. Fenestration products (except field fabricated) have label with certified U -Factor, certified Solar Heat Gain Coefficient (SHGC), and infiltration certification. 3. Exterior doors and windows weatherstripped; all joints and penetrations caulked and sealed. ❑ §150(g): Vapor barriers mandatory in Climate Zones 14 and 16 only. E] §150(0: Special infiltration barrier installed to comply with Section 151 meets Commission quality standards. El§150(e): Installation of Fireplaces, Decorative Gas Appliances and Gas Logs. 1. Masonry and factory -built fireplaces have: a. Closeable metal or glass door b. Outside air intake with damper and control c. Flue damper and control 2. No continuous burning gas pilots allowed. Space Conditioning, Water Heating and Plumbing System Measures ❑X §110-13: HVAC equipment, water heaters, showerheads and faucets certified by the Commission. §150(h): Heating and/or cooling loads calculated in accordance with ASH RAE, SMACNA orACCA. §150(i): Setback thermostat on all applicable heating and/or cooling systems. F] §1500): Pipe and Tank Insulation 1. Storage gas water heaters rated with an Energy Factor less than 0.58 must be externally wrapped with insulation having an installed thermal resistance of R-12 or greater. 2. First 5 feet of pipes closest to water heater tank, non -recirculating systems, insulated (R-4 or greater) 3. Back-up tanks for solar system, unfired storage tanks, or other indirect hot water tanks have R-12 external insulation or R-16 combined intemal/extemal insulation. 4. All buried or exposed piping insulated in recirculating sections of hot water systems. 5. Cooling system piping below 55 degrees F. insulated. 6. Piping insulating between heating source and indirect hot water tank. EnergyPro 3.1 By EnergySoft User Number: 2655 'Job Number. Page:7 of 21 Mandatory Measures Checklist: Residential (Page 2 of 2) MF -1 R NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. Items marked with an asterisk (') may be superseded by more stringent compliance requirements listed on the Certificate of Compliance. When this checklist is incorporated into the permit documents, the features noted shall be considered by all parties as minimum component performance specifications for the mandatory measures whether they are shown elsewhere in the documents or on this checklist only. DESCRIPTION Instructions: Check or initial applicable boxes or enter N/A if not applicable. DESIGNER JENFORCEMENT Space Conditioning, Water Heating and Plumbing System Measures: (continued) I X § 150(m): Ducts and Fans ❑ . 1. All ducts and plenums installed, sealed and insulated to meet the requirements of the 1998 CMC Sections 601, 603, 604 and Standard 6-3; ducts insulated to a minimum installed level of R-4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape, aerosol sealant, or other duct -closure system that meets the applicable requirements of UL181, UL181A, or UL181B. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh or tape shall be used. Building cavities shall not be used for conveying conditioned air. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and drawbands. 2. Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. 3. Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive I duct tapes unless such a tape is used in combination with mastic and drawbands. 4. Exhaust fan systems have back draft or automatic dampers. 5. Gravity ventilation systems serving conditioned space have eitherautomatic or readily accessible, manually operated dampers. I { 6. Protection of Insulation. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind but not limited to the following: Insulation exposed to weather shall be suitable for outdoor service e.g., protected by aluminum, sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding I from solar radiation that can cause degradation of the material. I § 114: Pool and Spa Heating Systems and Equipment 1. Certified with 78% thermal efficiency, on-off switch, weatherproof operating instructions, no electric resistance heating, and no pilot. 2. System is installed with at least 36" of pipe between filter and heater for future solar, cover for outdoor pools or spas. i a. At least 36" of pipe between filter and heater for future solar heating. b. Cover for outdoor pools or outdoor spas. 3. Pool system has directional inlets and a circulation pump time switch. LXJ §115: Gas fired central fumaces, pool heaters, spa heaters or household cooking appliances have no continuously burning pilot light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr) §118 (f): Cool Roof material meet specified criteria Lighting Measures F§150(k)1: Luminaires for general lighting in kitchens shall have lamps with an efficacy 40 lumens/watt or greater for general lighting in kitchens. This general lighting shall be controlled by a switch on a readily accessible lighting control panel at an entrance to the kitchen. FX_1 §150(k)2: Rooms with a shower or bathtub must have either at least one luminaire with lamps with an efficacy of 40 lumens/watt or greater switched at the entrance to the room or one of the alternative to this requirement allowed in Section 150(k)2.; and recessed ceiling fixtures are IC (insulation cover) approved. 3.1 By EnergySoft User Number: 2655 Job Number: Page:8 of 21 Computer Method Summary (Part 1 of 3) C -2R Sofia Cnnstructton 9/8/2005 Project Title Date 78-233 RirkdalP-,purt I q_Qijinta Project Address Building Permit # lnsu-Form Inc_ (760) 324-0216 Documentation Author Telephone Plan Check/Date Com utlreerformancQ 15 Field Check/Date Compliance Method (Package or Computer) Climate Zone Source Energy Use Standard Proposed Compliance (kBtu/sf-yr) Design Design Margin Space Heating 2.82 3.23 -0.42 Space Cooling 38.15 38.03 0.12 Domestic Hot Water 5.32 5.01 0.30 Totals 46.29 46.28 0.01 Percent better than Standard: 0.0% Total Conditioned Floor Area: Building Type: Building Front Orientation: Number of Dwelling Units: Number of Stories: BUILDING ZONE INFORMATION Zone Name 5,358 ft Single Fam Detached (East) 90 deg 1.00 1 Floor Area Volume 1 364 1 156 2„206 6.32 OPAQUE SURFACES Solar Act. Gains Type Area U -Fac. Azm. Tilt Y / N Wall 190 ---0-00- '90 9Q Wall 264 006.5 180 90 Wall 352 0 065 270 g0 Wall 839 0.065 0 90 Rnnf 1.364 0.028 270 _Q Wall ---330 OA65 180 90 Wall 30A x.065 270 2Q Wall 700 0 oss a gp W:;Il— 374 0.065 _---90_ ----a0_ Wall 278 0.06 180 90 Wall X28_ 0.065 270 90 Wall -999 0.065 o 9_Q Boot— --J-QM —0-02B_ 225 _ 0 Wall 254 0_0.6`..2 180 9.Q Wau X67 o.oss 9-0 ---aQ Wall —2.82 0.065 180 90 Wall _9.54 0 065 -0 90 /all— 26 ---Q- 06.5 _270_ 9D Rnnf 6.32 0.028 925_ 0 Floor Construction Type: ❑ Raised Floor ❑X Slab Floor Total Fenestration Area: 22.7% Total Conditioned Volume: 54,736 ft 3 Total Conditioned Slab Area: 5,358 ft 2 # of Thermostat Vent Units Zone Type Type Hgt. Area n �. f nnditinnPd SPthack 2 n/a 0 22 Conditioned SPthack 2 n/a 041 Cnnditioned _Sethack 2 n/a 0"12 Conditioned Setback n/a Form 3 Reference lone 2 Zone 2 Zone 3 7nne 3 7nne 3 Location / Comments Run Initiation Time: 09/08/05 10:43:00 Run Code: 1126201380 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Paae:9 of 21 Co'mDuter Method Summary (Part 2 of 3) C -2R Soba Construction 9/8/2005 Project Title Date FENESTRATION SURFACES U- Act. Glazing Type Location/ # Type Area Factor SHGC Azm. Tilt Comments -I- Windnw Front (Fast inn -0-350- 0.29 90 2 Window Left (South) 20.0 0.350 0.29 180 3 WindowLeft Wd. South 21.0 0.350 0.29 180 4 Window Left South 25.0 0.350 0.29 180 5 Window Rear West 12.5 0.350 0.29 270 6 Window Rear (West) 36.0 0.350 0.29 270 7 Window Right North) 21.4 0.340 0.26 0 8 Window Front (East) 56.0 0.340 0.26 90 9 Window Front (East) 56.0 0.340 0.26 90 ]R Window Front (East) 56.0 0.340 0.26 90 11 Window Front (East) 52.5 0.290 0.36 90 12 Window Front (East) 8.0 0.350 0.29 90 13 Window Bear (Nas1). 184.0 0.330 033 270 14 Window Rear West 12.0 0.290 0.36 270 15 Window Front (East) 13.5 0.350 0.29 90 16 Window Front East 12.0 0.350 0.29 90 17 Window Left (South) 48.0 0.340 0.26 180 18 Window Left (South) 24.0 0.290 0.36 180 19 Window Rear (West) 36.0 0.350 0.29 270 20 Window Rear (West) 8.0 0.350 0.29 270 21 Window Rear (West) 8.0 0.350 0.29 270 2Z Window Rear (West) 20.0 0.340 0.26 270 23 Window Right (North) 10.0 0.350 0.29 0 24 Window Right (North) 27.5 0.350 0.29 0 25 Window Right (North) 20.0 0.350 0.29 0 26 Window Left (South) 24.0 0.350 0.29 180 27 Window Left (South) 24.0 0.350 0.29 180 28 Window Left (South) 48.0 0.340 0.26 180 29 Window Rear (West) 54.0 0.350 0.29 270 .qQ Fagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows _900 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle �s 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eagle Windows 90 Eaqle Windows 90 Eaale Windows 90 Eaale Windows 90 Eaqle Windows Zone 1 Zone 1 Zone 1 Zone 1 Zone 1 Zone 1 Zone 2 Zone 2 Zone 2 Zone 2 Zone 2 Zone 2 Zone 3 Zone 3 Zone 3 Zone 3 Zone 3 Zone 3 Zone 3 Zone 3 Zone 3 Zone 3 Zone 3 Zone 3 Zone 3 90 Eagle Windows Zone 3 90 Eagle Windows Zone 3 INTERIOR AND EXTERIOR SHADING Window Overhang Left Fin Right Fin # Exterior Shade Type SHGC Hgt. Wd. Len. Hgt. LEA REA Dist. Len. Hgt. Dist. Len. Hgt. 1 Bug Screen 0.76 4.0 2.5 2.0 0.1 2.0 2.0 2 Bug Screen 0.76 4.0 2.5 2.0 0.1 2.0 2.0 3 Bug Screen 0.76 3.0 2.4 2.0 0.1 2.0 2.0 _ 4 Bug Screen 0.76 5.0 2.5 2.0 0.1 2.0 2.0 5 Bug Screen 0.76 5.0 2.5 2.0 0.1 2.0 2.0 6 Buq Screen 0.76 6.0 3-0 2.0 0.1 2.0 2.0 7 Bug Screen 0.76 8.0 2.8 2.0 0.1 2.0 2.0 8 Bug Screen 0.76 8.0 3.5 8.0 0.1 8.0 8.0 9 Buq Screen 0.76 8.0 3.5 8.0 0.1 8.0 8.0 _ 10 Bug Screen 0.76 8.0 3.5 8.0 0.1 8.0 8.0 11B cu Screen 0.76 2.5 7.0 8.0 0.1 8.0 8.0 12 Bug Screen 0.76 4.0 2.0 2.0 0.1 2.0 2.0 13 Bug Screen _ _ 0.76 8.0 23.0 17.0 0.1 17.0 17.0 14 Bug Screen 0.76 2.0 2.0 17.0 0.1 17.0 17.0 15 Bug Screen 0.76 4.5 3.0 2.0 0.1 2.0 2.0 T6 6 Bug Screen 0.76 3.0 2.0 2.0 0.1 2.0 2.0 17 Bug Screen 0.76 8.0 3.0 2.0 0.1 2.0 2.0 18 Bug Screen 0.76 8.0 3.0 2.0 0.1 2.0 _ 2.0 19 � Screen 0.76 6.0 3.0 2.0 0.1 2.0 _ 2.0 20B�cu Screen 0.76 4.0 2.0 2.0 0.1 2.0 2.0 21 Bug Screen 0.76 4.0 2.0 2.0 0.1 2.0 2.0 22 Bug Screen 0.76 8.0 2.5 2.0 0.1 2.0 2.0 _ 23 Bu S� creen 0.76 5.0 2.0 2.0 0.1 2.0 2.0 24 Buo Screen _ 0.76 5.5 2.5 2.0 0.1 2.0 2.0 25 Buq Screen 0.76 4.0 2.5 2.0 0.1 2.0 2.0 _ 26 Bug Screen 0.76 6.0 2.0 2.0 0.1 2.0 2.0 27 Bug Screen 0.76 6.0 3.0 40.0 0.1 40.0 40.0 28 Bug Screen 0.76 8.0 3.0 35.0 0.1 35.0 _ 35.0 29 Bug Screen 0.76 6.0 3.0 2.0 0.1 2.0 2.0 Run Initiation Time 09/08/05 10.43.00 Run Code: 1126201380 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page: 10 of 21 Comauter Method Summary (Part 2 of 3) C -2R Soba Construction 9/8/2005 Project Title Date FENESTRATION SURFACES U- Act. Glazing Type Location/ # Type Area Factor SHGC Azm. Tilt Comments 240 18.0 Window Right (North) _3D 31 Window Right (North) 32 Skylight Left (Southwest) 33 Window Front (East) 34 Window Front (East) 35 Window Front (East)_ 36 Window Left (South) 37 38 Window Window Rear Rear (West) (West) 3,q Window Right (North) 40 Window Rear (West) 240 18.0 0^340 0.350 0.26 0.29 34.6 0.400 0.29 36.0 0.350 0.29 18.0 0.290 0.36 8.8 0.350 0.29 18.0 -0 350 0.29 48.0 0.340 0.26 24.0 0.290 0.36 36.0 0.350 0.29 4.0 0.290 0.36 INTERIOR AND EXTERIOR SHADING # Exterior Shade Type SHGC 30 Bug Screen 0.76 31 Bug Screen 0.76 32 None 1.00 33 Bug Screen 0.76 34 Bug Screen 0.76 35 Bug Screen 0.76 36 Bug Screen 0.76 37 Bug Screen 0.76 38 Bug Screen 0.76 39 Bug Screen 0.76 40 Buq Screen 0.76 8.0 3.0 6.0 3.0 6.0 3.0 3.0 3.0 3.5 2.5 3.0 2.0 8.0 3.0 8.0 3.0 6.0 3.0 2.0 2.0 0_ _9.0. Eagle Windows 7one 3 0 90 Eagle Windows Zone 3 225 0 Eagle Windows Zone 3 90 90 Eagle Windows Casita 90 90 Eagle Windows Casita 90 90 Eagle Windows Casita 180 90 Eagle Windows Casita 270 90 Eagle Windows Casita 270 90 Eagle Windows Casita 0 90 Eagle Windows Casita 270 90 Eagle Windows Casita Overhang Left Fin Right Fin Len. Hgt. LExt. RExt. Dist. Len. Hgt. Dist. Len. Hgt. 2.0 0.1 2.0 2.0 2.0 0.1 2.0 2.0 2.0 0.1 2.0 2.0 2.0 0.1 2.0 2.0 2.0 0.1 2.0 2.0 2.0 0.1 2.0 2.0 3.0 0.1 3.0 3.0 3.0 0.1 3.0 3.0 2.0 0.1 2.0 2.0 2.0 0.1 2.0 2.0 EnergyPro 3.1 By EnergySoft User Number. 2655 Job Number: Page: 11 of 21 1 Computer Method Summary (Part 3 of 3) C -2R Soba Construction 9/8/2005 Project Title Date THERMAL MASS FOR HIGH MASS DESIGN F2 Length Factor Insulation R -Val. Depth Location / Comments Slab Perimeter Area Thick. Heat Slab Perimeter Inside Location Type (sf) (in.) Cap. Cond. Form 3 Reference R -Val. Comments Concrete, Heavyweight 1364 —3M 9$_ -OM n/a 0 Zone 1 / Slab on Grade Concrete, Heavyweight 1.156 3_50 28 0_98 n/a 0 Zone 2 / Slab on Grade Concrete. Heavyweight 1.006 3.50 28 0.98 n/a 0 Zone 3 / Slab on Grade Concrete, Heavyweight 1.200 3_50 28 0_98 n/a 0 Zone 3 / Slab on Grade Concrete Heavyweight 632 3.50 28 0.98 n/a 2 Casita / Slab on Grade PERIMETER LOSSES Type F2 Length Factor Insulation R -Val. Depth Location / Comments Slab Perimeter 22 0.76 0 0 0 Zone 1 Slab Perimeter i$ —0-7-6. —�U 0 Slab Perimeter 18 0.76 0 0 0 Zone 3 Slab Per=1e _38 -0-Z6 0.0 0 Zone 3 Slab Perimeter 18 0.76 0.0 0 Casita HVAC SYSTEMS Heating Equipment Minimum Distribution Type Type (furnace, heat Efficiency and Location Duct Thermostat Location / pump, etc.) (AFUE/HSPF)(ducts/attic, etc.) R -Value Type Comments Central Furnace 80%AFUE Ducts in Attic 4.2 Setback Zone 1 Central Furnace 80%AFUE Ducts in Attic 4.2 Setback Zone 2 _ Central Furnace 80%AFUE Ducts in Attic 4.2 Setback Zone 3 Central Furnace 80%AFUE Ducts in Attic 4.2 Setback Casita Hydronic Piping Pipe Pipe Insul. System Name Length Diameter Thick. Cooling Equipment Minimum Duct Type (air conditioner, Efficiency Location Duct Thermostat Location / heat pump, evap. cooling) (SEER) (attic, etc) R -Value Type Comments Split Air Conditioner 12.0 SEE Ducts in Attic 4.2 Setback Zone 1 Split Air Conditioner 12.0 SEER Ducts in Attic 4.2 Setback Zone 2 Split Air Conditioner 12.0 SEER Ducts in Attic 4.2 Setback Zone 3 Split Air Conditioner 12.0 SEER Ducts in Attic 4.2 Setback Casita WATER HEATING SYSTEMS Ratedl Tank Energy Fact! 1 Tank Insul. Water Heater Water Heater Distribution # in Input Cap. or Recovery Standby R -Value System Name Type Type Syst. (Btu/hr) (gal) Efficiency Loss (%) Ext. American G82 -50T38-3 Small Gas Pipe Insulation 2 46.000 50 0.65 n/a n/a 1 For small gas storage (rated input — 75000 Btu/hr), electric resistance and heat pump water heaters, list energy factor. For large gas storage water heaters (rated input > 75000 Btu/hr), list Rated Input, Recovery Efficiency and Standby Loss. For instantaneous gas water heaters, list Rated Input, and Recovery Efficiency. Run Initiation Time: 09/08/05 10:43:00 , Run Code: 1126201380 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page: 12 of 21 Computer Method Summary (Addendum) C -2R Soba Construction 9/8/2005 Project Title Date Special Features and Modeling Assumptions The local enforcement agency should pay special attention to the items specified, in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted.I Plan Field HIGH MASS Design(see C -2R) - Verify Thermal Mass: 1364 sgft Exposed Slab Floor, 3.50" thick at Zone 1 HIGH MASS Design(see C -2R) -Verify Thermal Mass: 1156 sgft Exposed Slab Floor, 3.50" thick at Zone 2 HIGH MASS Design(see C -2R) - Verify Thermal Mass: 1006 sgft Exposed Slab Floor, 3.50" thick at Zone 3 HIGH MASS Design(see C -2R) - Verify Thermal Mass: 1200 sgft Exposed Slab Floor, 3.50" thick at Zone 4 HIGH MASS Design(see C -2R) - Verify Thermal Mass: 632 sqft Covered Slab Floor, 3.50" thick at Casita HERS Required Verification These features must be confirmed and/or tested by a certified HERS rater under the supervision of a,CEC approved HERS provider. The HERS rater must document the field verification and diagnostic testing of these measures on a form CF -6R. plan Field EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number. Paoe:13 of 21 1 IHV -AC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE Soba Construction 9/8/2005 SYSTEM NAME FLOOR AREA Zone 1 1,364 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 Heating System Output per System 74,000 Total Output (Btuh) 74,000 Output (Btuhlsgft) 54.3 Cooling System Output per System 40,000 Total Output (Btuh) 40,000 Total Output (Tons) 3.3 Total Output (Btuh/sgft) 29.3 Total Output (sgft/Ton) 409.2 Air System CFM per System 1,395 Airflow (cfm) 1,395 Airflow (cfm/sgft) 1.02 Airflow (cfm/Ton) 418.5 Outside Air (%) 0.0 Outside Air (cfm/sgft) 0.00 Note: values above given at ARI conditions - 26.0 of 69.3 of Outside Air 0 cfm Supply Fan 1395 cfm 69.3 of 69.3 of Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK CFM Sensiblel Latent CFM I Sensible 1,263 21,025 3,252 395 20,377 0 1,051 1,019 0 0 0 01 0 0 0 0 0 1,051 1,019 23,1287[777732521 22 414 BDP CO. 563AN042-A 25,323 11,533 74,000 Total Adjusted System Output 25,323 11,5331 74,000 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Aug 2 pm Jan 12 am earn Temperatures at Time of Heating Peak) 118.8 of Heating Coil K Return Air Ducts '4 upp y lr ucts 118.10F ROOMS 70.0 of 1000LING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 111.0 / 77.4 of 78.7 / 67.0 of - 78.7 66.9 of 61.8 / 60.7 of Supply Air Ducts Outside Air 0 cfm Supply Fan Cooling Coil 62.5 / 61.0 of 1395 cfm 56.1% R.H. ROOMS 78.7/67.0 of 78.0166.8 of Return Air Ducts ' EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page: 14 of 21 IHV -AC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE Soba Construction 9/8/2005 SYSTEM NAME FLOOR AREA Zone 2 1,156 ENGINEERING CHECKS 11SYSTEM LOAD Number of Systems 1 Heating System Output per System 70,000 Total Output (Btuh) 70,000 Output (Btuh/sgft) 60.6 Cooling System Output per System 47,000 Total Output (Btuh) 47,000 Total Output (Tons) 3.91 Total Output (Btuh/sqft) 40.7 Total Output (sgft/Ton) 295.1 I Air System CFM per System 1,595 Airflow (cfm) 1,595 Airflow (cfm/sgft) 1.38 Airflow (cfm/Ton) 407.2 Outside Air (%) 0.0 Outside Air (cfm/sqft) 0.00 Note: values above given at ARI conditions Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK ICOILHTG.PEAK CFM I Sensible Latent I CFM 1 Sensible 1,316 23,825 2,9781 542' 22,995 0 ' 1,150 0 1,191 0 0 0 0 of 0 0 I 0 1,150 1,191 26 207 2,9781 1 25,295 BDP CO. 563AN048-A 31,268 11,347 70,000 I � I I Total Adjusted System Output 31,268 11,347 ? 70,000 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Aug 2 pm j r Jan 12 arr EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26.0 OF 69.3 OF 69.3 OF 110.30F �* Supply Air Ducts Outside Air � 0 cfm Supply Fan Heating Coil 109.6 °F 1595 cfm ' ROOMS 69.3 of 70.0 of 04 Return Air Ducts (COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Coolina Peak) I 111.0 / 77.4 of 78.7 / 66.0 of 78.7 / 65.9 of . 60.4 / 59.3 of Outside Air 0 cfm 78.7 / 66.0 of Supply Fan Cooling Coil 1595 cfm Return Air Ducts Supply Alr Ducts 61.1 / 59.5 of 52.7% R.H. i ROOMS 78.0 / 65.8 of EnergvPro 3.1 By EnergySoft User Number. 2655 Job Number: Paae:15 of 21 IHV -AC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE Soba Construction 9/8/2005 SYSTEM NAME FLOOR AREA Zone 3 2,206 ENGINEERING CHECKS 11SYSTEM LOAD Number of Systems 1 Heating System Output per System 70,000 Total Output (Btuh) 70,000 Output (Btuh/sqft) 31.7 Cooling System Output per System 47,000 Total Output (Btuh) 47,000 Total Output (Tons) 3.9 Total Output (Btuh/sqft) 21.3 Total Output (sgft/Ton) 563.2 Air System CFM per System 1,595 Airflow (cfm) 1,595 Airflow (cfm/sgft) 0.72 Airflow (cfm/Ton) I 407.2 Outside Air (%) 0.0 Outside Air (cfm/sgft) 0.00 Note: values above given at ARI conditions JEATING SYSTEM PSYCHROMETRICS 26.0 of 69.4 of 69.4 of Outside Air 0 cfm 69.4 of Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK 11COILHTG.PEAK CFMISensiblel Latent 11CFM1 Sensible 1,387 26,062 1,026 503 21,385 0 1,303 1,069 0 0 0 0 01 0 0 0 0 1,303 1,069 i 28,668 1,026 23 523 BDP CO. 563AN048-A 32,580 9,478 70,000 I Total Adjusted System Output 32,580 9,478 70,000 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Aug 2 pm Jan 12 am -earn Temperatures at Time of Heatina Peak) 110.30F Supply Fan Heating Coil 1595 cfm �% Return Air Ducts 14 Supply Air Ducts 109.7 of ROOMS 70.0 of DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 111.0 / 77.4 of 78.8 65.2 of 78.8 / 65.1 of 59.7 ! 58.5 of Supply Air Ducts Outside AirO. 0 cfm Supply Fan Cooling Coil 60.5 / 58.8 of 1595 cfm 49.9% R.H. ROOMS 78.8/65.2 of 78.0 / 65.0 of h Return Air Ducts 4 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page: 16 of 2� WAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE Soba Construction 9/8/2005 SYSTEM NAME FLOOR AREA Casita 632 Total Room Loads I I Return Vented Lighting Return Air Ducts I Return Fan I Ventilation Supply Fan i Supply Air Ducts TOTAL SYSTEM LOAD i COIL COOLING PEAK COIL HTG. PEAK CFM ISensiblel Latent ICFM Sensible 739 10,547 294 221 8,929 0 527 446 0 0 0 0 0 0 0 0 0 527 II I 446 11,602 2941 9 822 BDP CO. 563AN024-A 13,823 7,854 37,000 I it Total Adjusted System Output 13,823 7,854 37,000 (Adjusted for Peak Design Conditions) I TIME OF SYSTEM PEAK Aug 2 pm ! Jan 12 ami P-IEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heating Peak) I 26.0 OF 69.5 OF 69.5 OF 108.10F 0 :; Supply Air Ducts --( Outside Air 0 cfm 107.6 of Supply Fan Heating Coil 895 cfm ROOMS 69.5 of 70.0 of Return Air Ducts DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 111.0 / 77.4 of 78.5 / 67.8 OF 78.5 / 67.7 of 64.1 / 63.1 of 311 0 Supply Air Ducts Outside Air 0 cfm Supply Fan Cooling Coil 64.7 / 63.3 of 895 cfm 59.2% R.H. ROOMS 78.5/67.8 of 78.0 / 67.7 of Return Air Ducts I EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Paae:17 of 21 ROOM LOAD SUMMARY PROJECT NAME Soba Construction DATE 9/8/2005 SYSTEM NAME Zone 1 FLOOR AREA 1,364 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK ZONE NAME ROOM NAME Mult. CFM SENSIBLE LATENT CFM SENSIBLE LATENT CFM SENSIBLE Zone 1 Zone 1 1 1,263 21,025 3,252 1,263 21,025 3,252 395 20,377 PAGE TOTAL 1 11263 21,025 3,252 395 20,377 TOTAL 1 1,263 21,025 3,252 395 20,377 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page: 18 of 21 ROOM LOAD SUMMARY PROJECT NAME DATE Soba Construction 9/8/2005 SYSTEM NAME FLOOR AREA Zone 2 1,156 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK ZONE NAME ROOM NAME Mult. CFM SENSIBLE LATENT CFM SENSIBLE LATENT CFM SENSIBLE Zone 2 Zone 2 1 1,316 23,825 2,978 1,316 23,825 2,978 542 22,995 PAGE TOTAL 1 1,316 23,825F 2,978 1 542 22,995 TOTAL 1 1,316 23,825 2,978 542 22,995 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:19 of 21 ROOM LOAD SUMMARY PROJECT NAME DATE Soba Construction 9/8/2005 SYSTEM NAME FLOOR AREA Zone 3 2,206 ROOM LOAD SUMMARY PAGE TOTAL TOTAL ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK ZONE NAME ROOM NAME Mult. CFM SENSIBLE LATENT CFM SENSIBLE LATENT CFM SENSIBLE Zone 3 Zone 3 1 675 12,691 468 675 12,691 468 257 10,939 Zone 3 Zone 4 1 711 13,371 558 711 13,371 558 246 10,446 PAGE TOTAL TOTAL 1 11387 26,062 1,026 503 21,385 1 11387 26,062 F 1,026 503 21,385 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:20 of 21 IRGOM LOAD SUMMARY PROJECT NAME DATE Soba Construction 9/8/2005 SYSTEM NAME FLOOR AREA Casita 632 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK ZONE NAME ROOM NAME Mult. CFM SENSIBLE LATENT CFM SENSIBLE LATENT CFM SENSIBLE Casita Casita 1 739 10,547 294 739 10,547 294 221 8,929 PAGE TOTAL 1 739 10,547 294 221 8,929 TOTAL 1 739 10,547 294 221 8,929 EnergyPro 3.1 By EnergySoft User Number: 2655 Job Number: Page:21 of 21