Loading...
14-0780 (SFD) Title 24BUILDING ENERGY ANALYSIS REPORT PROJECT: CITRUS - LOT 5 50625 BREVA LA QUI NTA, CA 92253 Project Designer: Temple Construction Inc. 699 Indian Trail Palm Springs, CA 92264 760-323-5310 Report Prepared by: 1st Choice HERS Rating Roy Eads 68811 Risueno Road Cathedral City, CA 92234 760-641-2447 � � I® RE o/ JUL 0 3 2014 CIT`( OF LA QUINTA COMMUNITY DEVELOPMENT Job Number: FBYJ 140506_REV2 140528& LA �`NTq SAFETY DEPT. Date: APPROVED CONSTRUCTION 5/28/2014 The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This progra as approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2008 Building Energy=y Standards. This program developed by EnergySoft, LLC — www.energysoft.com. 14052 qiy ,PERFORMANCE CERTIFICATE: Residential Part 1 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type m Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 5/28/2014 Project Address 50625 BREVA LA QUINTA California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 3,444 Addition n/a # of Stories 1 FIELD INSPECTION ENERGY CHECKLIST ® Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form. El Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details. INSULATION Construction Type Area Special CavityFeatures see Part 2 of 5 Status Wall Wood Framed R-21 3,009 Ext --R-3.9 New Door Opaque Door None 52 New Wall Wood Framed R-21 416 New Slab Unheated Slab -on -Grade None 3,444 Perim = 387' New Roof Wood Framed Attic R-38 3,444 Radiant Barrier Cool Roof Venting New FENESTRATION U- Exterior Orientation Area Factor SHGC Overhang Sidefins Shades Status Front (E) 36.0 0.310 0.20 none 20.020.0 Bug Screen New Front (E) 14.1 0.330 0.20 none 20.020.0 Bug Screen New Front (E) 2.0 0.300 0.24 none none Bug Screen New Left (S) 15.0 0.330 0.20 1.5 20.020.0 Bug Screen New Left (S) 64.0 0.330 0.23 1.5 20.020.0 Bug Screen New Left (S) 15.0 0.330 0.20 1.5 20.020.0 Bug Screen New Rear (lAq 64.0 0.330 0.20 1.5 20.020.0 Bug Screen New Front (E) 15.0 0.330 0.20 1.5 0.0/11.0 Bug Screen New Front (E) 2.0 0.300 0.24 1.5 none Bug Screen New Right (N) 3.0 0.330 0.30 1.5 none Bug Screen New Right (N) 85.0 0.330 0.20 1.5 none Bug Screen New HVAC SYSTEMS Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status 2 Central Furnace 80% AFUE Split Air Conditioner 14.0 SEER Setback New HVAC DISTRIBUTION Location Heating Duct Cooling Duct Location R -Value Status HVAC Ducted Ducted Attic, Ceiling Ins, vented 8.0 New WATER HEATING JJ Ot . Type Gallons Min. Eff Distrib1uti'on , ,Status 1 Large Gas 75 0.80 Recircln;ner I Y 7;New' Ic iv EneigyPro 5.1 by EnergySoft User Number. 8305 RunCode: 2014-05-28721:35:12 ID: 140506 REu244052. Pa e)3 of 21 �J .PERFORMANCE CERTIFICATE: Residential Part 1 of 5 CF-1 R Project Name CITRUS - LOT 5 Building Type m Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration 1512812014 Date Project Address 50625 BREVA LA QUINTA California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 3,444 Addition n/a # of Stories 1 FIELD INSPECTION ENERGY CHECKLIST ® Yes ❑ No HERS Measures -- If Yes, A CF-4R must be provided per Part 2 of 5 of this form. ❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details. INSULATION Construction Type Area Special Cavity Features see Part 2 of 5 Status FENESTRATION U- Orientation Area Factor Exterior SHGC Overhang Sidefins Shades Status Right (N) 48.0 0.320 0.22 1.5 none Bug Screen New Right (N) 36.0 0.330 0.20 none none Bug Screen New Rear (Ko 90.0 0.330 0.20 none none Bug Screen New Rear (tM 36.0 0.320 0.22 none none Bug Screen New Left (S) 64.0 0.330 0.20 20.0 2.0124.0 Bug Screen New Rear (149 200.0 0.330 0.23 12.0 14.0110.0 Bug Screen New Right (N) 24.0 0.770 0.73 24.0 24.012.0 Bug Screen New Left (S) 30.0 0.330 0.20 none none Bug Screen New Left (S) 12.0 0.320 0.22 none none Bug Screen New Left (S) 33.0 0.340 0.22 none none Bug Screen New Right (N) 16.0 0.330 0.20 1.5 20.020.0 Bug Screen New HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status HVAC DISTRIBUTION Location Heating Duct Cooling Duct Location R-Value Status WATER HEATING Y, , Qty. Type Gallons Min. Eff Distribrution'' �',�, ; p r,. �atus I r `)A FE EnergyPro 5.1 by EnergySoft User Number 8305 RunCode: 201405-28T21:35:12--ID:=1_40506 R52'14052c__ Page 4of21 '�J PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type ® Single Family ❑ Addition Alone 1 ❑ Multi Family ❑ Existing+ Addition/Alteration Date 1512812014 SPECIAL FEATURES INSPECTION CHECKLIST The enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. The DHW System Bradford -White U2XR75S6RN is a non-NAECA large storage gas water heater. Verify DHW details. A hot water recirculation systems has been modeled. Verification of type is required. The Roof R-38 Roof V/Attic CRRC 0918-0030 Reflectance = 0.21, Emittance = 0.93 shall be rated and labeled by the Cool Roof Rating Council in accordance with Section 10-113 of the standards. The Roof R-38 Roof V/Attic CRRC 0918-0030 includes credit for a Radiant Barrier that is Continuous meeting eligibility and installation criteria as specified in Residential Appendix RA4.2.2. The Roof R-38 Roof V/Attic CRRC 0918-0030 Concrete Tile (10 Wso Roofing 50% of Vents Located High requires verification. HERS REQUIRED VERIFICATION Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a completed CF -4R form for each of the measures listed below for final to be given. The Cooling System 14 SEER/11.2 EER 180% FURNACE includes credit for a 11.2 EER Condenser. A certified HERS rater must field verity the installation of the correct Condenser. The HVAC System HVAC includes credit for Vefied Fan Energy. Measured Fan Energy may not exceed 0.58 w/ctm. The HVAC System HVAC incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display. The HVAC System HVAC includes credit for verified adequate airflow. A certified HERS rater must diagnostically measure airflow of the HVAC System. The HVAC System HVAC incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct leakage meets the specified criteria. BIW r� A E3 U1 OL��IL� T r UEPT L;ONS rRucrrory EnemyPro 5. 1 by EnemySoft User Number: 8305 RunCode: 201405-28T21:35:1Z)A-rr ID: 140506 REV2 14052 Pa e15 of 21 PERFORMANCE CERTIFICATE: Residential Part 3 of 5 CF-1 R Project Name Building Type m Single Family ❑ Addition Alone Date CITRUS - LOT 5 ❑ Multi Family ❑ Existing+ Addition/Alteration 5/28/2014 ANNUAL ENERGY USE SUMMARY Standard Proposed Margin TDV kBtu/ft2- r Space Heating 4.25 6.21 -1.96 Space Cooling 61.34 46.21 15.13 Fans 12.05 10.65 1.40 Domestic Hot Water 10.59 17.58 -6.98 Pumps 0.00 1.06 -1.06 Totals 88.23 81.70 6.53 Percent Better Than Standard: 7.4% BUILDING COMPLIES - HERS VERIFICATION REQUIRED Fenestration Building Front Orientation: (E) 90 deg Ext. Walls/Roof Wall Area Area Number of Dwelling Units: 1.00 (E) 800 69 Fuel Available at Site: Natural Gas (S) 1,282 233 Raised Floor Area: 0 (K9 927 390 Slab on Grade Area: 3,444 (N) 1,373 212 Average Ceiling Height: 11.0 Roof 3,444 0 Fenestration Average U-Factor: 0.34 TOTAL: 904 Average SHGC: 0.23 Fenestration/CFA Ratio: 26.3% REMARKS CITRUS LOT 5 - AS PER PLANS AND INFORMATION PROVIDED 1. WALLS = 2X6 R-21 + 1"RIGID FOAM 2. CEILINGS = R-38 3. WINDOWS = NFRC AS LISTED 4. COOL ROOF = CRRC 918-0030 US TILE 3645 CAPISTRANO SUNRISE BLEND 5. RADIANT BARRIER CREDIT W/ 50% HIGH VENT 6. DHW = Bradford-White U2XR75S6RN + RECIRC+TIMER 7. HVAC = Trane 14 SEER111.2 EER180% Furnace W/HERS REQUIRED 8. DUCTS = R-8 STATEMENT OF COMPLIANCE This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the Efficiency Standards of the California Code of Regulations. The documentation author hereby certifies that the documentation is accurate and complete.� Documentation Author Company Roy Eads ..U.�i-- 68811 Risueno Road 1st Choice HERS Rating5/182014 Address Name City/State/ZipCity/State/Zip Cathedral City, CA 92234 Phone 760-641-2447 Signed Date The individual with overall design responsibility hereby certifies that the proposed building design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application, and recognizes that compliance using duct design, duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require installer testing and certification and field verification by an approved HERS rater. Designer or Owner (per Business & Professions Code) C O; L,- �, f Tr ' t �U'' �,�� TA Company Temple Construction Inc. "� "" f Address 699 Indian Trail Name Mark Temple City/State/Zip Palm Springs, CA 92264 Phone 760-323-5310Signed CONS-F[Licen`se.#J Date ILJu I ION DAT EnerqyPro 5.1 by EneMySoft User Number: 8305 Run Code: 201405-28721:35:12 -- ID: 140506-RE-&14052 Pae 6 of 21 .CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type m Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 5/28/2014 OPAQUE SURFACE DETAILS Surface Type Area U- Insulation Factor Cavity Exterior Frame Interior Frame Azm Joint Appendix Tilt Status 1 4 Location/Comments Wall 180 0.054 R-21 3.9 None 90 90 New 4.3.1-A6 BLOCK LOAD Door 28 0.500 None 90 90 New 4.5.1-A4 BLOCK LOAD Wall 126 0.054,R-21 3.9 None 180 90 New 4.3.1-A6 BLOCK LOAD Wall 76 0.054 R-21 3.9 None 270 90 New 4.3.1-A6 BLOCK LOAD Wall 155 0.054 R-21 3.9 None 180 90 New 4.3.1-A6 BLOCK LOAD Wall 163 0.054 R-21 3.9 None 90 90 New 4.3.1-A6 BLOCK LOAD Wall 60 0.054 R-21 3.9 None 180 90 New 4.3.1-A6 BLOCK LOAD Wall 145 0.069 R-21 90 90 New 4.3.1-A6 BLOCK LOAD Wall 402 0.054 R-21 3.9 None 0 90 New 4.3.1-A6 BLOCK LOAD Wall 430 0.054 R-21 3.9 INone 0 90 New 4.3.1-A6 BLOCK LOAD Wall 158 0.054 R-21 3.9 None 270 90 New 4.3.1-A6 BLOCK LOAD Wall 118 0.054 R-21 3.9 None 180 90 New 4.3.1-A6 BLOCK LOAD Wall 112 0.054 R-21 3.9 None 270 90 New 4.3.1-A6 BLOCK LOAD Wall 145 0.054 R-21 3.9 None 0 90 New 4.3.1-A6 BLOCK LOAD Wall 191 0.054 R-21 3.9 None 270 90 New 4.3.1-A6 BLOCK LOAD Wall 283 0.054 1 R-21 13.9 TNone 180 90 New 4.3.1-A6 BLOCK LOAD FENESTRATION SURFACE DETAILS ID Type Area U -Factor SHGC Azm Status Glazing Type Location/Comments 1 Window 36.0 0.310 NFRC 0.20 NFRC 90 New DBL/VINYL 3120 SL BLOCK LOAD 2 Window 14.1 0.330 NFRC 0.20 NFRC 90 New DBL/VINYL 3320 FX BLOCK LOAD 3 Window 2.0 0.300 NFRC 0.24 NFRC 90 New DBL/VINYL 3024 FX BLOCK LOAD 4 Window 15.0 0.330 NFRC 0.20 NFRC 180 New DBLNINYL 3320 SH BLOCK LOAD 5 Window 64.0 0.330 NFRC 0.23 NFRC 180 New DBLN/NYL 3323 SGD BLOCK LOAD 6 Window 15.0 0.330 NFRC 0.20 NFRC 180 New DBLN/NYL 3320 SH BLOCK LOAD 7 Window 64.0 0.330 NFRC 0.20 NFRC 270 New DBL/VINYL 3320 SGD BLOCK LOAD 8 Window 15.0 0.330 NFRC 0.20 NFRC 90 New DBL/VINYL 3320 SH BLOCK LOAD 9 Window 2.0 0.300 NFRC 0.24 NFRC 90 New DBL/VINYL 3024 FX BLOCK LOAD 10 Window 3.0 0.330 NFRC 0.30 NFRC 0 New DBL/VINYL 33/30 SH BLOCK LOAD 11 Window 25.0 0.330 NFRC 0.20 NFRC 0 New DBL/VINYL 3320 SH BLOCK LOAD 12 Window 20.0 0.330 NFRC 0.20 NFRC 0 New DBL/VINYL 3320 SH BLOCK LOAD 13 Window 20.0 0.330 NFRC 0.20 NFRC 0 New DBL/VINYL 3320 SH BLOCK LOAD 14 Window 20.0 0.330 NFRC 0.20 NFRC 0 New DBLNINYL 3320 SH BLOCK LOAD 15 Window 12.0 0.320 NFRC 0.22 NFRC 0 New DBL/VINYL 3222 FX BLOCK LOAD 16 Window 12.0 0.320 NFRC 0.22 NFRC 0 New DBL/VINYL 3222 FX BLOCK LOAD (1) U -Factor Type: 116-A =Default Table from Standards, NFRC =Labeled Value 2 SHGC Type: 116-13 = Default Table from Standards, NFRC = Labeled Value EXTERIOR SHADING DETAILS ID Exterior Shade Type SHGC Window H t Wd Ove hanq Left Fin Len H t LExt REA Dist Len Right Fin H t Dist Len Hot 1 Bug Screen 0.76 6.0 7.0 3.5 20.0 0 -9.0 20.0 0 2 Bug Screen 0.76 3.5 7.0 3.5 20.0 0 9.0 20.0 0 3 Bug Screen 0.76 4 Bug Screen 0.76 5.0 3.0 1.5 2.0 10.0 10.0 1.0 20.0 0 16.0 20.0 0 5 Bug Screen 0.76 8.0 8.0 1.5 2.0 10.0 10.0 6.0 20.0 0 6.0 20.0 0 6 Bug Screen 0.76 5.0 3.0 1.5 2.0 10.0 10.0 16.0 20.0 0 1.0 20.01 0 7 Bug Screen 0.76 8.0 8.0 1.5 2.0 10.0 10.0 3.0 20.0 0 8.0 20.01 0 8 Bug Screen 0.76 5.0 3.0 1.5 2.0 5.0 10.0 0.0 0.0 0 13.0 11.0 0 9 Bug Screen 0.76 2.0 1.0 1.5 2.0 10.0 10.0 10 Bug Screen 0.76 1.0 3.0 1.5 2.0 10.0 10.0 11 Bug Screen 0.76 5.0 5.0 1.5 2.0 10.0 10.0 12 Bug Screen 0.76 5.0 4.0 1.5 2.0 10.0 10.0 T "i--- 13 Bug Screen 0.76 5.0 4.0 1.5 2.0 10.0 10:0 ( ! r 14 Bug Screen 0.76 5.0 4.0 1.5 2.0 10.0 10`0 111\1-r A 15 Bug Screen 0.76 2.0 6.0 1.5 2.0 10.0 10.0 _ 1V Q, 4 16 Bug Screen 0.76 2.0 6.0 1.5 2.0 10.0 10.0 E i 0 r , ,--% FOR covsT"��� RUCTInhi EnergyPro 5.1 by EnergySoft User Number: 8305 Run Code: 201405-28721:35:12 ID: 140506 REV2 14052. Page 7 of 21 .CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF-1 R Project Name CITRUS - LOT 5 Building Type ® Single Family ❑ Addition Alone 0 Multi Family ❑ Existing+ Addition/Alteration Date 1512812014 OPAQUE SURFACE DETAILS Surface TyDe Area U Insulation Joint Appendix I Factor C-a-v-itYTExterior Frame Interior Frame Azm Tilt Status 4 Location/Comments Wall 227 0.054 R-21 3.9 None 180 90 New 4.3.1-A6 BLOCK LOAD Wall 215 0.069 R-21 90 90 New 4.3.1-A6 BLOCK LOAD Wall 56 0.069 R-21 180 90 New 4.3.1-A6 BLOCK LOAD Door 24 0.500 None 180 90 New 4.5.1-A4 BLOCK LOAD Wall 184 0.054 R-21 3.9 None 0 90 New 4.3.1-A6 BLOCK LOAD Slab 3,4441 0.730 None 0 180 New 4.4.7-A1 BLOCK LOAD Roof 3,4441 0.025 R-38 180 14 New 4.2.1-A21 BLOCK LOAD FENESTRATION SURFACE DETAILS ID TvDe Area U-Factor SHGC2 Azm Status Glazing Type Location/Comments 17 Window 12.0 0.320 NFRC 0.22 NFRC 0 New DBL/VINYL 32/22 FX BLOCK LOAD 18 Window 36.0 0.330 NFRC 0.20 NFRC 0 New DBL/VINYL 33/10 SH BLOCK LOAD 19 Window 12.0 0.320 NFRC 0.22 NFRC 0 New DBL/VINYL 32/12 FX BLOCK LOAD 20 Window 15.0 0.330 NFRC 0.20 NFRC 270 New DBL/VINYL 33/20 SH BLOCK LOAD 21 Window 6.0 0.320 NFRC 0.22 NFRC 270 New DBL/VINYL 3222 FX BLOCK LOAD 22 Window 15.0 0.330 NFRC 0.20 NFRC 270 New DBL/VINYL 3320 SH BLOCK LOAD 23 Window 6.0 0.320 NFRC 0.22 NFRC 270 New DBLN/NYL 3222 FX BLOCK LOAD 24 Window 15.0 0.330 NFRC 0.20 NFRC 270 New DBL/VINYL 3320 SH BLOCK LOAD 25 Window 6.0 0.320 NFRC 0.22 NFRC 270 New DBL/VINYL 32/22 FX BLOCK LOAD 26 Window 64.0 0.330 NFRC 0.20 NFRC 180 New DBLNINYL 3320 SGD BLOCK LOAD 27 Window 200.0 0.330 NFRC 0.23 NFRC 270 New DBL/VINYL 4323 SGD BLOCK LOAD 28 Window 24.0 0.770 NFRC 0.73 NFRC 0 New FR DOOR DBL MTL DEFAULT BLOCK LOAD 29 Window 15.0 0.330 NFRC 0.20 NFRC 270 New VINYL 3320 SH BLOCK LOAD 30 Window 6.0 0.320 NFRC 0.22 NFRC 270 New 3222 FX BLOCKLOAD 31 Window 15.0 0.330 NFRC tDBLIVINYL 0.20 NFRC 270 New VINYL 3320 SH BLOCKLOAD 32 Window 6.0 0.320 NFRC 0.22NFRC 270 New VINYL 3222 FX I BLOCK LOAD (1) U-Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value 2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value EXTERIOR SHADING DETAILS ID Exterior Shade Type SHGCH Window t Wd Ove hanq Left Fin Ri ht Fin Len Hat LExt REA Dist Len H t Dist Len H t 17 Bug Screen 0.76 2.0 6.0 1.5 2.0 10.0 10.0 18 Bug Screen 0.76 19 Bug Screen 0.76 2.0 6.0 1.5 2.0 10.0 10.0 20 Bug Screen 0.76 21 Bug Screen 0.76 22 Bug Screen 0.76 23 Bug Screen 0.76 24 Bug Screen 0.76 25 Bug Screen 0.76 26 Bug Screen 0.76 8.0 8.0 20.0 2.0 3.0 1.0 1.0 2.0 0 1.0 24.0 0 27 Bug Screen 0.76 10.0 20.0 12.0 2.0 2.0 2.0. 2.0 14.0 -0 . 2.0 10.0 0 28 Bug Screen 0.76 8.01 3.0 24.0 5.0 6.0 3.0 16.011 24.0 - t 0 , 1.0 . X2.0 0 29 Bug Screen 0.76 i-(` 30 Bug Screen 0.76 " ' c Z" ;, V rl ` 31 IBug Screen 0.76 32 JBug Screen 1 0.76 f-� Lj -7C) EnergyPT 5. 1 by EnergySoft User Number: 8305 RunCode: 201405-28T21:35:12 " `ID: -140506 REV2-1.4052, Page 8:of 21 �J .CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type m Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 1512812014 OPAQUE SURFACE DETAILS Surface U- Tvoe Area Factor Insulation Joint Appendix Cavitv Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments FENESTRATION SURFACE DETAILS ID Tvpe Area U -Factor SHGC Azm Status Glazing Type Location/Comments 33 Window 15.0 0.330 NFRC 0.20 NFRC 270 New DBL/VINYL 33/20 SH BLOCK LOAD 34 Window 6.0 0.320 NFRC 0.22 NFRC 270 New DBL/VINYL 3222 FX BLOCK LOAD 35 Window 15.0 0.330 NFRC 0.20 NFRC 180 New DBL/VINYL 3320 SH BLOCK LOAD 36 Window 6.0 0.320 NFRC 0.22 NFRC 180 New DBLNINYL 3222 FX BLOCK LOAD 37 Window 15.01 0.330 NFRC 0.20 NFRC 180 New DBL/VINYL 3320 SH BLOCK LOAD 38 Window 6.0 0.320 NFRC 0.22 NFRC 180 New DBL/VINYL 3222 FX BLOCK LOAD 39 Window 33.0 0.340 NFRC 0.22 NFRC 180 New DBL/VINYL 3422 FX BLOCK LOAD 40 Window 16.0 0.330 NFRC 0.20 NFRC 0 New DBL/VINYL 3320 SH BLOCK LOAD (1) U -Factor Type: 2 SHGC Type: 116-A = Default Table from Standards, NFRC = Labeled Value 116-B = Default Table from Standards, NFRC = Labeled Value EXTERIOR SHADING DETAILS ID Exterior Shade Type Window SHGC H t Wd Ove hanq Left Fin Ri ht Fin Len H t LExt RExt Dist Len Hat Dist Len H t 33 Bug Screen 0.76 34 Bug Screen 0.76 35 Bug Screen 0.76 36 Bug Screen 0.76 37 Bug Screen 0.76 38 Bug Screen 0.76 39 Bug Screen 0.76 40 Bug Screen 0.76 4.0 4.0 1.5 2.0 10.0 10.0 10.0 20.0 0 6.5 20.0 0 ILL;V ' L1�J�11�VI�V'�f EnergyPro 5.1 by EnetgySoft User Number: 8305 RunCode: 201405-28721:35:12 .` ID: 140506 REV2 14052. Page 9 721 .CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type ® Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 5/28/2014 BUILDING ZONE INFORMATION System Name Zone Name Floor Area New Existinq Altered Removed Volume Year Built HVAC ALL ROOMS IN ZONE 3,444 37,884 Totals 3,4441 01 01 0 HVAC SYSTEMS System Name Qty. Heatin Type Min. Eff. Cooling Type Min. Eff. Thermostat Type Status HVAC 2 Central Furnace 80% AFUE Split Air Conditioner 14.0 SEER Setback New HVAC DISTRIBUTION System Name Heating Duct Ducts Cooling Duct Location R -Value Tested? Status HVAC Ducted Ducted Attic, Ceiling Ins, vented 8.0 m New 13 WATER HEATING SYSTEMS S stem Name Qty. Type Distribution Rated Input (Btu h) Tank Cap. al Energy Factor or RE Standby Loss or Pilot Ext. Tank Insul. R- Value Status Bradford -White U2XR75Si 1 Large Gas RecircfFimer 76,000 75 0.80 2.50% n/a New MULTI -FAMILY WATER HEATING DETAILS HYDRONIC HEATING SYSTEM PIPING Control Hot Water Piping Length ft 0 0 in a c S stem Name"~ Pipe —Len th. Pipe _Diameter Insul. Thick. Qt . HP Plenum Outside Buried ❑ �� :YD__:)T I EnergyPro 5.1 by EnergySoft User Number. 8305 Run Code: 201405-28T21:35:12 t nn l0a 140506 REV2 14052, Pae 10 of21 MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF-1 R Project Name Date CITRUS - LOT 5 5/28/2014 NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF-1 R, CF-1 R-ADD, or CF- 1 R-ALT Form) shall supersede the items marked with an asterisk (') below. This Mandatory Measures Summary shall be incorporated into the permit documents, and the applicable features shall be considered by all parties as minimum component performance specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF-1 R Form with plans. Building Envelope Measures: 116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage. §116(a)4: Fenestration products (except field-fabricated windows) have a label listing the certified Ll-Factor, certified Solar Heat Gain Coefficient SHGC and infiltration that meets the requirements of 10-111 (a). 117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed. 118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF-613 Form. §118(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(i) when the installation of a Cool Roof is specified on the CF-1 R Form. *§1 50a : Minimum R-19 insulation in wood-frame ceiling orequivalent Ll-factor. 150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R-Value. *§1 50c : Minimum R-13 insulation in wood-frame wall orequivalent Ll-factor. 150(d): Minimum R-13 insulation in raised wood-frame floor orequivalent Ll-factor. 150(f): Air retarding wrap is tested labeled, and installed according to ASTM E1677-95 2000 when specified on the CF-1 R Form. 150 : Mandatory Vapor barrier installed in Climate Zones 14 or 16. §150(1): Water absorption rate for slab edge insulation material alone without facings is no greater than 0.3%; water vapor permeance rate is no greater than 2.0perm/inch and shall be protected from physical damage and LIV light deterioration. Fireplaces, Decorative Gas Appliances and Gas Log Measures: 150 e 1 A: Masonry or factory-built fireplaces have a closable metal or glass door covering the entire opening of the firebox. §150(e)1 B: Masonry or factory-built fireplaces have a combustion outside air intake, which is at least six square inches in area and is equipped with a with a readily accessible operable, and tight-fitting damper and or a combustion-air control device. §150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of the building, are prohibited. Space Conditioning, Water Heating and Plumbing System Measures: §110-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy Commission. §113(c)5: Water heating recirculation loops serving multiple dwelling units and High-Rise residential occupancies meet the air release valve, backflow prevention, pump isolation valve and recirculation loop connection requirements of §113(c)5. §115: Continuously burning pilot lights are prohibited for natural gas: fan-type central furnaces, household cooking appliances (appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and spa heaters. 150(h): Heating and/or cooling loads are calculated in accordance with ASH RAE, SMACNA or ACCA. 150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c). §1500)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped with insulation having an installed thermal resistance of R-12 or greater. §1500)113: Unfired storage tanks, such as storage tanks or backup tanks for solar water-heating system, or other indirect hot water tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank. §1500)2: First 5 feet of hot and cold water pipes closest to water heater tank, non-recirculating systems, and entire length of recirculating sections of hot water pipes are insulated per Standards Table 150-13. §1500)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot water tank shall be insulated to Table 150-B and Equation 150-A. §1500)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table 123-A. 150(i)3A: Insulation is protected from damage, includingthat due to sunlight, moisture a tui ,ment;mainten, anc ad-wind— §1500)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapor fetaar�dgnt ofis�enclosbd"enti lye NTA conditioned space. NG P, c n rr- �, , 1 504: Solar water-heating systems and/or collectors are certified b the Solar Rating and Certificatjon;Cor o•,ration. �y �� ' f. FOR CONSTR _ N CT EnergyPro5.1 by EnergySoR User Number. 8305 RunCode: 2014-05-28721:35:12 I n,4-1/P: 140506 REV2 1405, Page 11 of,;1 MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R Project Name Date CITRUS - LOT 5 5/28/2014 §150(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections 601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R- 4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings reater than 1/4 inch the combination of mastic and either mesh or tape shall be used §150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. §150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with mastic and draw bands. 150(m)7: Exhaust fans stems have back draft or automatic dampers. §150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers. §150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material. 150 m 10: Flexible ducts cannot have porous inner cores. §150(o): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in Section 4 of that Standard. Pool and Spa Heating Systems and Equipment Measures: §114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating ora pilot light. §114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction and return lines or built-up connections for future solar heating. 114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover. §114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or programmed to run only during off-peak electric demand periods. 150 : Residential pool systems orequipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150 Residential Lighting Measures: §150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies contained in Table 150-C and is not a low efficacy luminaire asspecified by §150(k)2. 150(k)3: The wattage of permanently installed luminaires shall be determined asspecified by §130(d). §150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than 20 kHz. §150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line - voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a medium screw -base socket. 150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k). 150(k)7: All switching devices and controls shall meet the requirements of §150(k)7. §150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy. EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ftz or 100 watts for dwelling units larger than 2,500 ftz may be exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and all permanently installed luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a manual -on occupant sensor. r----_ _ §150(k)9: Permanently installed lighting that is internal to cabinets shall use no more than 20 watts.of power, per linear.foot of illuminated cabinet. , T LI- r, n ., ~'; ftp,3 -1`'' .� CL�d6'-'UC h0N EnergyPro5.1 by EnergySoff User Number: 8305 RunCode: 2014-05-28721:35:12 ] ID: 140506 REV2 1405. Page 12 df 21 MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R Project Name Date CITRUS - LOT 5 1512812014 §150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms shall be high efficacy. EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on occupant sensor certified to comply with the applicable requirements of §119. EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a manual -on occupancy sensor. §150(k)11: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual - on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less than 1000 square feet located on a residential site is not required to comply with §150 k 11. §150(k)12: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between the luminaire housing and ceiling. §150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor, and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor luminaires used to comply with Exceptions to §150(k)13 may be controlled by a temporary override switch which bypasses the motion sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not be high efficacy luminaires. §150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no more than five watts of power as determined according to §130(d). §150(k)15: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable requirements of Sections 130 131 134, and 146. §150(k)16: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119. ;_LAO'1fj)qTA G & SAFEY DEPT, FC,i ONSTRUCTION EnergyPro 5.1 by EnergySoR User Number: 8305 RunCode: 201405-28721:35:12 L -___-_ID_ 140506 REv 1405 P-age_i,3 of 21 J HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name CITRUS - LOT 5 Date 5/28/2014 System Name HVAC Floor Area 3,444 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 2 COIL CFM Total Room Loads 1,877 Return Vented Lighting Return Air Ducts Return Fan Ventilation o Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COOLING PEAK COIL HTG. PEAK Heating System Sensible Latent CFM Sensible output perSystem 120,000 37,313 468 1,645 47,734 Total output Btuh 240,000 0 Output Btuh/s ft 69.7 2,154 2,346 Cooling System 0 0 output perSystem 60,000 0 0 0 0 Total output Btuh 120,000 3,454 468 -3,454 Total output ons 10.0 1 2,154 2,346 Total output Btuh/s ft 34.8 Total output s ft/Ton 344.4 1 45,075 48,972 Air System CFM perSystem 2,000 HVAC EQUIPMENT SELECTION Airflow cfm 4,000 14 SEER/11.2 EER /80% FURNACE 88,701 12,800 240,000 Airflow cfm/s ft 1.16 Airflow cfm/Ton 400.0 Outside Air % 0.0% Total Adjusted System Output (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK 88,701 12,8001 Aug 3 PM 240,000 Jan 1 AM Outside Air cfm/s ft 0.00 Note: values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26 OF Outside Air 0 cfm 69 OF 69 OF 97 OF 98 OF f C� Heating Coil Supply Fan 97 OF 4,000 cfm I ROOM In 70 OF COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 111 /73°F Outside Air 0 cfnt 76 / 62 OF 76/62°F 55/54°F 56/54°F Cooling Coil Supply Fan 4,000 cfm 56_/,54 OF C I TY C rpt /t /-� ` T� BU ., ,c RoOW�, 1 .� T. -'� v !� 75 / J OF . ' " o 1 rluu I ICON EnergyPro 5.1 by EnergySoft User Number: 8305 RunCode: 201405-28721:35:12 j. ID: 140506 REV2-14052 — P_age 14 of 21 J ROOM LOAD SUMMARY Project Name Date CITRUS — LOT 5 5/28/2014 System Name Floor Area HVAC 3,444 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult. CFM Sensible Latent CFM Sensible Latent CFM Sensible BLOCK LOAD ALL ROOMS /N ZONE 1 1 1 1,8771 37,3131 468 1,8771 37,3131 468 1,6451 47,734 PAGE TOTAL TOTAL' I ' Total includes ventilation load for zonal er r t_..,' � U U I NTA & 5j [FETY DEPT. 1877 FC -7,y3,13; � (\j46i3, y I;1;645,r'Np,147,734 11877 37,313 468 1,645 v47,734� ROOM HEATING PEAK LOADS Project Name CITRUS - LOT 5 7 Date 5/28/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name ALL ROOMS IN ZONE Floor Area 3,444.0 ft2 Indoor Dry Bulb Tem erature 70 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area 3,008.9 X 36.0 X U-Value X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X ' BUILDING AT *F 44 = 44 = Btu/hr R-21 Wall + 1"rigid foam 0.0544 7,198 DBL/VINYL 3120 SL 0.3100 491 DBWINYL 3320 FX 14.1 X 0.3300 44 = = 205 DBL/VINYL 3024 FX 4.0 X 0.3000 44 53 Wood Door 52.0 X X X X X X X X X X X X X X 0.5000 44 = 1,144 DBL/VINYL 3320 SH 302.0 0.3300 44 = = 4,385 DBL/VINYL 3323 SGD 64.0 0.3300 44 929 DBLNINYL 3320 SGD 128.0 0.3300 44 = = 1,859 R-21 Wall ASR=1 416.0 0.0690 44 1,263 DBWINYL 33/30 SH 3.0 0.3300 44 = = 44 DBWINYL 3222 FX 96.0 0.3200 44 1,352 DBLNINYL 4323 SGD 200.0 0.3300 44 c = 2904 FR DOOR DBL MTL DEFAULT 77173 24.0 0.7700 44 813 DBWINYL 3422 FX 33.0 0.3400 44 = 494 Slab-On-Grade perim = 386.5 0.7300 44 = 12,414 R-38 Roof V/Attic CRRC 0918-0030 3,444.0 0.0250 44 = = = = 3,788 X X X X = = = = = = X X X X X X X X X through an interior surface to X 3,444 X Area Ceiling = = = = = = Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X 1.064 Schedule Air Sensible Fraction another room 11.00 X Height ACH' Page Total 1/6,01 "�XX I A 04 I AT_ & SAFETY 39,335 y �, ����8,399 DEPT. TOTAL HOURLY HEAT LOSS FOR ROOM EnergyPro 5.1 by EnergySoft User Number, 8305 RunCode: 201405-28721:35:12 I /0:,140506 REV2 14052y Pae 16 of 21 I _ J RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date CITRUS - LOT 5 5/28/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name ALL ROOMS IN ZONE Outdoor Dry Bulb Temperature I 1 I OF Floor Area 3,444.0 ft' Outdoor Wet Bulb Temperature 73 OF Indoor Dry Bulb Temperature 75 OF Outdoor Daily Range: 34 OF Onanue Surfaces R-21 Wall + 1 " rigid foam Wood Door R-21 Wall + 1 " rigid foam R-21 Wall + 1"rigid foam R-21 Wall ASR=1 R-21 Wall + 1 " rigid foam R-21 Wall ASR=1 Wood Door R-38 Roof V/Attic CRRC 0918-003 Orientation (E) (E) (S) (iM (E) (N) (S) (S) (S) Area X X X X X X X X X U -Factor X X X X X X X X X CLTD' = = = = = = = = = 342.9 0.0544 33.0 28.0 0.5000 33.0 969.0 0.0544 26.0 536.5 0.0544 33.0 360.0 0.0690 33.0 1,160.5 0.0544 23.0 56.0 0.0690 26.0 24.0 0.5000 26.0 3,444.0 0.0250 1 56.0 Btu/hr 615 1 1 1,4511 Page Total L Items shown with an asterisk (") denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF W1 - ENTRY W2- 1/2 ROUND W3 CRTYD UPPER W4 BONUS LEFT W5 BONUS SGD W6 BONUS RT W7 BD3 SGD W8 BD3 FRONT W9 BA 3 Internal Gain (E) (E) (E) (S) (S) (S) (IM (E) (E) 0.0 X X X X X X X X X 13.6 + + + + + + + + + 36.0 X X X X X X X X X 25.5 = = = = = = = = = 0.0 14.0 14.1 25.8 0.0 14.9 2.0 29.2 13.3 14.0 1.7 14.0 35.4 15.1 28.6 15.2 13.3 14.0 1.7 14.0 0.0 14.0 64.0 25.8 0.0 14.0 15.0 25.8 0.01 14.9 2.0 29.2 Page Total Occupants 4.0 Occupants X 230 Btuh/occ. _ Equipment 1.0 Dwelling Unit X 1,600 Btu = Infiltration: 1.064 )( 0.88 X 188.46 X 36 = Air Sensible CFM ELA AT AL HOURLY SENSIBLE HEAT GAIN FOR ROOM Latent Gain 4.0 Occupants X 200 Infiltration: 4.771 X 0.88 X 188.46 X -0.00042 = Air Sensible CFM ELA AW 10, Btu/hr 916 364 58 210 969 210 1,654 388 Btu/hr 920 1,600 6,381 37.313 Qc N OF U► BUILDNAIG & SAFE I Y I is :�) C L� FOR CONSTRUCTI( I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 1 4681 31 L1 RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date CITRUS - LOT 5 1 5/28/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name ALL ROOMS IN ZONE Outdoor Dry Bulb Temperature 111 OF Floor Area 3,444.0 ft' Outdoor Wet Bulb Temperature 73 OF Indoor Dry Bulb Temperature 75 OF Outdoor Daily Ranae: 34 OF Surfaces Orientation Area X X X X X X X X X U -Factor X X X X X X X X X CLTD' = = = = = = = = = GLF = = = = = = = = = 0.01 17.8 3.0 17.8 0.0 14.0 25.0 14.0 0.0 14.0 20.0 14.0 0.0 14.0 20.0 14.0 0.0 14.0 20.0 14.0 0.0 14.5 12.0 14.5 0.0 14.5 12.0 Page Total Items shown with an asterisk (•) denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration W10 BA2 RT W11 BD2 RT W12 BONUS RT -1 W13 BONUS RT -2 W14 BONUS RT -3 W15 KITCH UP -1 W16 KITCH UP -2 W17 KITCH UP -3 W18 DIN RM f1rientatinn (N) (N) (N) (N) (N) (N) (N) (N) (N) Area X X X X X X X X X GLF + + + + + + + + + Area X X X X X X X X X GLF = = = = = = = = = 0.01 17.8 3.0 17.8 0.0 14.0 25.0 14.0 0.0 14.0 20.0 14.0 0.0 14.0 20.0 14.0 0.0 14.0 20.0 14.0 0.0 14.5 12.0 14.5 0.0 14.5 12.0 14.5 0.0 14.5 12.0 14.5 0.0 14.0 36.0 14.0 Page Total Btu/hr 0 Btu/hr 53 349 279 279 279 175 175 175 503 Internal Gain Btu/hr Occupants 4.0 Occupants X 230 Btuh/occ. ' Equipment 1.0 Dwelling Unit X 1,600 Btu = Infiltration: 1.064 X 0.88 X 188.46 X 36 = 6,381 Air Sensible CFM ELA AT I TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 37.3131 Latent Gain Btu/hr Occupants 4.0 Occupants X 20'0 I BIDh/ocit t 11 A t-�e U-1 VV Infiltration: 4,771 X 0.88 X 188.46 X-o.000a2 = BUILDII�G & SAFEr UQr Air Sensible CFM ELA AW AP ROV" LJ I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM I 4,SR1 RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date CITRUS - LOT 5 1 5/28/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name ALL ROOMS IN ZONE I Outdoor Dry Bulb Temperature 111 OF Floor Area 3,444.0 ft2 Outdoor Wet Bulb Temperature 73 OF Indoor Dry Bulb Temperature 75 °F Outdoor Dailv Ranae: 34 OF ue Surfaces Orientation Area X X X X X X X X X U -Factor X X X X X X X X X CLTD' = = = = = = = = = GLF = = = = = = = = = 0.0 14.5 12.0 14.5 0.0 14.0 15.0 25.8 0.0 14.5 6.0 27.6 0.0 14.0 15.0 25.8 0.0 14.5 6.0 27.6 0.0 14.0 15.0 25.8 0.0 14.5 6.0 Page Total Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Fenestration W19 UPPER W20 DIN REAR -1 W21UPPER W22 DIN REAR -2 W23 UPPER W24 DIN REAR -3 W25 UPPER W26 DIN SGD W27 GRT RM SGD Orientation (N) (169 (Kq (IM (IM (Kq (Kq (S) (Kq Shaded Unshaded Area X X X X X X X X X GLF + + + + + + + + + Area X X X X X X X X X GLF = = = = = = = = = 0.0 14.5 12.0 14.5 0.0 14.0 15.0 25.8 0.0 14.5 6.0 27.6 0.0 14.0 15.0 25.8 0.0 14.5 6.0 27.6 0.0 14.0 15.0 25.8 0.0 14.5 6.0 27.6 64.0 14.0 0.0 14.0 152.0 15.1 48.0 28.8 Page Total Btu/hr 0 Btu/hr 175 388 166 388 166 388 166 894 3,679 Internal Gain Btu/hr Occupants 4.0 Occupants X 230 Btuh/occ. = 920 Equipment 1.0 Dwelling Unit X 1,600 Btu 1,600 Infiltration: 1.064 x 0.88 x 188.46 x 36 = 6,381 Air Sensible CFM ELA AT 1 TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 37.3131 Latent Gain Btu/hr K - Occupants 4.0 Occupants X 20,0 Btuh/occr r I - -1,, 1-� uI 0tr- - L Gv Iv I Infiltration: x,771 X 0.88 x 18s.4s x -0.00042 = BUILDI14G & SAFE Air Sensible CFM ELA AW A P P R O V L L) I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM I 4&RI ,RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date CITRUS - LOT 5 1 5/28/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name ALL ROOMS IN ZONE I Outdoor Dry Bulb Temperature 111 OF Floor Area 3,444.0 ft2 Outdoor Wet Bulb Temperature 73 OF Indoor Dry Bulb Temperature 75 °F Outdoor Daily Range: 34 OF ue Surfaces n Area X X X X X X X X X U -Factor X X X X X X X X X CLTD' = = GLF = = = 0.0 42.7 24.0 42.7 0.0 14.0 15.0 25.8 0.0 14.5 6.0 27.6 0.0 14.0 15.0 25.8 0.0 14.5 6.0 27.6 0.0 14.0 15.0 25.8 0.0 14.5 6.0 Page Total Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Fenestration W28 MB FR DOOR W29 MBD REAR -1 W30 UPPER W31 MBD REAR -2 W32 UPPER W33 MBD REAR -3 W34 UPPER W35 MBD LEFT -1 W36 UPPER Orientation (N) (W1 (►M (►M (149 (149 (S) (S) Shaded Unshaded Area X X X X X X X X X GLF + + + + + + + + + Area X X X X X X X X X GLF = = = 0.0 42.7 24.0 42.7 0.0 14.0 15.0 25.8 0.0 14.5 6.0 27.6 0.0 14.0 15.0 25.8 0.0 14.5 6.0 27.6 0.0 14.0 15.0 25.8 0.0 14.5 6.0 27.6 0.0 14.0 15.0 14.0 0.0 14.5 6.0 14.6 Page Total r 0 Btu/hr 1,025 388 166 388 166 388 166 210 2, Internal Gain Btu/hr Occupants 4.0 Occupants X 230 Btuh/occ. ` Equipment 1.0 Dwelling Unit X 1,600 Btu Infiltration: 1.064 )( 0.88 x 188.46 X 36 = 6,381 Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 37,313 Latent Gain Btu/hr Occupants 4.0 Occupants X 200 Btuh//occ/c. _n -800 /� . OF I_i"� tr 1 Infiltration: 4,771 Air Sensible X 0.88 X 188.46 CFM ELA X 0.00042 = 1 i n�332 BUILDING & SAFE.. - - AW APPR')` M --D I TOTAL HOURLY LATENT HEAT GAIN FOR ROOM I rno r-nnicTRl ICTION4681 DATE _ by RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date CITRUS - LOT 5 5/28/2014 ROOM INFORMATION DESIGN CONDITIONS Room Name ALL ROOMS IN ZONE Outdoor Dry Bulb Temperature 111 OF Floor Area 3,444.0 ft2 Outdoor Wet Bulb Temperature 73 OF Indoor DrV Bulb Temperature 75 OF I Outdoor Daily Range: 34 OF Opaque Surfaces Orientation Area U-Factor CLTD' Btu/hr X X X X X X X X = X X = X X X X X X = X X Page Total 0 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF Btu/hr W37 MBD LEFT-2 (S) 0.0 X 14.0 + 15.0 X 14.0 0 210 W38 UPPER (S) 0.0 X 14.5 + 6.0 X 14.6 = 88 W39 MBA (S) 0.0 X 14.9 + 33.0 X 15.0 = 494 W40 LAUND (N) 0.0 X 14.0 + 16.0 X 14.0 c 223 X + X - X + X - X + X - X + X - X +1 XI - Page Total 1,015 Internal Gain Btu/hr Occupants 4.0 Occupants X 230 Btuh/occ. = 920 Equipment 1.0 Dwelling Unit X 1,600 Btu _ 1,600 Infiltration: 1.064 X 0.88 X 188.46 X 36 a 6,381 Air Sensible CFM ELA AT [TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 37,313 Latent Gain Btu/hr Occupants 4.0 Occupants X 2oo Btuh/occ. -_800 LA CITYI Infiltration: 4.771 X 0.88 X 188.46 X -0.00042 = SAFE DEPY332 Air Sensible CFM ELA AW gUILUNG TOTAL HOURLY LATENT HEAT GAIN FOR ROOM � "" ` � r�4 (: N����tlJi� 468 Ene Pro 5.1 b Ene Soft User Number: 8305 RunCode: 2014-05-28T21:35:12 21 N 506 REV2 1 0 2 Page of 21 ID: 140 45� a _ _ -� DATE ---�— �� �C1ec`tronically Filed by 1st Choice HERS Rating and Authenticated at CalCERTS.com - 7/2/2014 Electronically Signed at CalCERTS.com by Mark A Temple (Temple Construction) 7/2/2014 PERFORMANCE CERTIFICATE: Residential Part 1 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type ® Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 7/2/2014 Project Address 50625 BREVA LA QUINTA California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 3,444 Addition# n/a . of Stories 1 FIELD INSPECTION ENERGY CHECKLIST ® Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form. ❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details. INSULATION Area Special Construction Type Cavity (ft) Features see Part 2 of 5 Status Wall Wood Framed R-21 3,009 Ext --R-3.9 New Door Opaque Door None 52 New Wall Wood Framed R-21 416 New Slab Unheated Slab -on -Grade None 3,444 Perim = 387' New Roof Wood Framed Attic R-38 3,444 Radiant Barrier Cool Roof Venting New FENESTRATION .:. ;:: U- Exterior Orientation Area(it?) :::'Factor SHGC Overhang Sidef ins Shades Status Front (E) 36.0 :0.310 0.20 none 20.0/20.0 Bug Screen New .......... Front.(Ejl "' " 14.1 `" »0:330: _ _ ,none 20.0/20..0 Bug..Scres- New .��. ,:.:.:..,:.,.,"n=._,=•.,_:.�.:�.�:>�,. �... u�<�'�»rim.: cL Front (EJ;.;;;:;: 2.0 . , rlarte B Siren New :.. .:': A ,�: Yri'in.`..'- .v': 'iEWi? .4it�(".::'._V';n�::" Left S `''`::.' z15 00330: 0 20�s20 UP10 0"Bug Scree •<:'.'.:. ..:. New' ...... . ( J z,. Left S.:���:-�>:. ...:.6+�A.:...:-:.....ca0.330 0„23�as;�1':5:r;;;:...;r.��"�:.�:.,._.20a120.0. �x'-8. .:Screena:...::.::.r�..>.,�`_'.;::NBv✓:�..:" .:}.. ::: ;:.:�"L�� ,�; 3-��R•,':' Left ........:...:... . .... ..... ... .... .. ... ..... ... .... .. .... ...i,... :... .... _....... .:-.., ..-...... ....:-..:.....-..::::.::::::�:�:::�=�`�::::�:':�:��::: Rear (Ut/J30 _;�:::;::::,,; ,:0?70.._ 5 _:;::::.:'::::: 20:0720.0 : rr' ; ;::8ug Screen New 15.0 `0.330 0.20 1.5 0.0/11.0 Bug Screen New 2.0 ::.•::0.300 0.24 1.5 none Bug Screen New Right (N) 3.0 `. :.:: 0.330 0.30 1.5 none Bug Screen New Right (N) 85:0.:::. ` .s';:; 0.330 0.20 1.5 none Bug Screen New HVAC SYSTEMS Qty. Heating Min. Eff Cooling Min. Eff Thermostat Status 2 Central Furnace 80% AFUE Split Air Conditioner 14.0 SEER Setback New HVAC DISTRIBUTION Duct Location Heating Cooling Duct Location R -Value Status HVAC Ducted Ducted Attic, Ceiling Ins, vent 8.0 New ISI °f r,ini/�n ` WATER HEATING tl. .�,'r� ° r- T. I Ot . Type Gallons Min. Eff Distri utioflQD Status I 1 Large Gas 75 0.80 RecircAmer C v v ° V �' I New MMU EnergyPro 5.1 by EnergySoft User Number: 8305 RunCode: 2014-07-02T15:06:47 ID: 1405-- REV2 40521 Page 1 of 8 Reg: 214-N0050494A-000000000-0000 Registration Date/Time: 2014/07/02 18:10:09 HERS Provider: CalCERTS, Inc Electronically Filed by 1st Choice HERS Rating and Authenticated at CalCERTS.com - 7/2/2014 Electronically Signed at CalCERTS.com by Mark A Temple (Temple Construction) 7/2/2014 PERFORMANCE CERTIFICATE: Residential Part 1 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type ® Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 7/2/2014 Project Address 50625 BREVA LA QUINTA California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 3,444 Addition n/a # of Stories 1 FIELD INSPECTION ENERGY CHECKLIST ❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form. ❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details. INSULATION Construction Type' Area Special Cavity (ft) Features see Part 2 of 5 Status FENESTRATION .:: ' '; :': U- Orientation Area{ftz) :.::::;Factor Exterior SHGC Overhang Sidefins Shades Status Right (N) 48.0--.O.320 0.22 1.5 none Bug Screen New een>:• New 36.0 b:330::' 0. 0::.._ .one_ :.. one Bu Sc <_. Right (NJ .3 ... Vis :........ .. ... ...:.... Rear 90.0 _ _ , '- New Rear (14 11 00{320: 0 22 rnorre nonex =bug Screen.:... New'........ . Left (S)1.. ; 4.0. Sreet`r`'.oi:�.`"e Rear {Wj: 2Gt0.0 0, 330 ,rte AO 23< 12 D.,.:14,Q/fd_0 Bug Screen1'rti .:z� 8few. a1 xt Right (Nj ... ,;;:. >:=::.::: r:' :24.0 '::`<:>:'i0.770::_::`';':: ;.::::0:79: 24.0. ....:.._ : '.._. 24'0!7.0 >:' Bug Screen: _:;':: New Left (SJ .::.:::.;;:;:::+ `>=:' 30.0 0.330 0.20 none none Bug Screen New Left(sJ';:.;;:;:?.:' :" ::::::;::..12.0:.r;<..:0.320 0.22 none none Bug Screen New Left (S) 33.0:.;'::`;:`:: 0.340 0.22 none none Bug Screen New Right (N) 0.330 0.20 1.5 20.0/20.0 Bug Screen New HVAC SYSTEMS Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status HVAC DISTRIBUTION Location Heating Duct Cooling Duct Location R -Value Status WATER HEATING CITY OF LA QUINTA Ot . Type Gallons Min. Eff DistributiWILDING & SAFETY [-Stagy us _ V FOR CONSTRucTinN I DATE RY EnergyPro 5.1 by EnergySoft User Number. 8305 RunCode: 2014-07-02715:06:47 L._J ) X4900. -6 I V2 14052; Page 2 of 8 Reg: 214-N0050494A-000000000-0000 Registration Date/Time: 2014/07/02 18:10:09 HERS Provider: CalCERTS, Inc •Electronically•Filed by 1st Choice HERS Rating, and Authenticated at CalCERTS.com - 7/2/2014 Electronically Signed at CalCERTS.com by Mark A Temple (Temple Construction) 7/2/2014 PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type ® Single Family ❑ Addition Alone 1 ❑ Multi Family ❑ Existing+ Addition/Alteration Date 7/2/2014 SPECIAL FEATURES INSPECTION CHECKLIST The enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. The DHW System Bradford -White U2XR75S6RN is a non-NAECA large storage gas water heater. Verify DHW details. A hot water recirculation systems has been modeled. Verification of type is required. The Roof R-38 Roof V/Attic CRRC 0918-0030 Reflectance= 0. 21, Emittance = 0.93 shall berated and labeled by the Cool Roof Rating Council in accordance with Section 10-113 of the standards. The Roof R-38 Roof V/Attic CRRC 0918-0030 includes credit for a Radiant Barrier that is Continuous meeting eligibility and installation criteria as specified in Residential Appendix RA 4.2.2. The Roof R-38 Roof V/Attic CRRC 0918-0030 Concrete Tile (10 #/st) Roofing 50% of Vents Located High requires verification. y.'.�k.>ti1i _ fi'!q: NgjR. - ;.: :: T �'" .. ....: .. ...: .'.3i`:::.. /;:. .. .. . .. :a -h'".:...:.::::.:�:::_::::::`:7c`�. '`.:::•.:3} N:wr. `g_"t: ..�: iii,":. HERS.RE RIF ATLON:..:.�_ .. _ .. . _ ........ _ ...,.,: �.:.........._.:.. _ H'.b , .':[ f �^nTr' [T. fZ.'i5 1, v�ib `�cT. 'tF `k T '•:' : �. items in;tl)s sectlor�eGt�tre field tesilftg aneilr verlftcatlonF�y�acerttf��d HERS Rater=Tteairispecfor riiust receive a Com letF:.7 fdem foreat"..-Th Psfed behiGu'far finaffo be ivi=n: The Cooling System sl4 SEER/11.2 EER l80% FURNACE includes credit fora 11.2 EER Condenser. A certified HERS rater must field verify the installaTton of!ftfe correct;Condertser : `:`?,'�: The HVACSystem H VAC `includes•credit for Verified Fan Energy. Measured Fan Energy may not exceed 0-58 wlcfm. The HVAC System HVAC incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display. The HVAC System HVAC includes credit for verified adequate airflow. A certified HERS rater must diagnostically measure airflow of the HVAC System. The HVAC System HVAC incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct leakage meets the specified criteria. - C17Y OF LAS Cil i m.IT OUILUING & SAFETY DEPT. UVtL) FOR CONS n r '•. Ener Pro 5.1 by Ener Soft User Number. 8305 Run Code: 2014-07 02T15:0647 '7D,t4e506—Rf�'W14052i Pabe 3 of 8 Reg: 214-NOO50494A-000000000-0000 Registration Date/Time: 2014/07/02 18:10:09 HERS Provider: CalCERTS, Inc Electronically Filed by 1st Choice HERS Rating and Authenticated at CalCERTS.com - 7/2/2014 Electronically Signed at CalCERTS.com by Mark A Temple (Temple Construction) 7/2/2014 PERFORMANCE CERTIFICATE: Residential Part 3 of 5 CF -1 R Project Name Building Type ® Single Family ❑ Addition Alone Date CITRUS - LOT 5 ❑ Multi Family ❑ Existing+ Addition/Alteration 7/2/2014 ANNUAL ENERGY USE SUMMARY Standard Proposed Margin TDV kBtu/ft2- r Space Heating 4.25 6.21 -1.96 Space Cooling 61.34 46.21 15.13 Fans 12.05 10.65 1.40 Domestic Hot Water 10'59 17.58 -6.98 Pumps 0.00 1.06 -1.06 Totals 88.23 81.70 6.53 Percent Better Than Standard: 7.4% BUILDING COMPLIES - HERS VERIFICATION REQUIRED Fenestration Building Front Orientation: (E) 90 deg Ext. Walls/Roof Wall Area Area Number of Dwelling Units: 1.00 (E) 800 69 Fuel Available at Site: Natural Gas (S) 1,282 233 Raised Floor Area: 0 (W) 927 390 Slab on Grade Area: 3,444 (N) 1,373 212 Average Ceiling Height: 11.0 Roof 3,444 0 Fenestration Average.U-Fagtor: 0'34 TOTAL: 904 Avera e SHGC: 0.23 Fenestration/CFA Ratio: 26.3% REMARKS ........:.: CITRUS LOT 5 -AS PER PLANS ANDINFORMATION PROVIDED 1. WALLS = 2X6 R-21 + i" RIGID 170AIt7I>::::.:: ..-._ , ........,.. ... .. �',sw'.. .....:...*'A ., .. nk_. ?�-.fit:: :..::st. .� Si'f'y. _ 2. CEILINGS% -:.R -38..:.x.:....- '':.:.::. �,,.....:;::_......-..:;::... <�::_:< '.:°�:`:::'::�.: ?i1. . :..:....... ..�_:...... ,..:..... ,,...:.:..,.:.......: ;.,..:_ <.:,,-:..,.tet.... art,.; ....:.:.... .. ....... ......: ft.-.� .. i..:.:.,.. ,�.�• .?`:�. �. _ _ .._..:...:..... 'Yr... .....:...:...:::.. .:... ,. _�. t ..-:.... ter..:..........-�><j_1 �_ .: '.. t. .. - ::-:,,::a::v: r:.:?: ^.�:: :'.=��::, \::a :. ...: .::'. ,jFv'vs.:: . 3. WINDOWS =i NFRG A5 LISTED � n. 4. COOL ROdF = CRRC 9191400.Us TILE 3645 CAPISTRAkd� SUNRISE BLEND '` .: F ,n'.: Pi, . :?rw?..: ,l'4.A .,: .•: ,.`:"� at:. ..,x!.-;:.: .,. Z%�.��;%l..'<::ir,:;:':';: :xw•'ai•.: 5. RAD(NT BARRIER CRED13 W! 50% HIGH iJENT k h'S `a..' �;: rG 4 fi „' Py:.....;. t >y -. -::. - 3 fr �.. ..�. •:�'= :ii'.': '? 3 d`�;f .j4.1. ': 4;N�:SL 6. GIRC+TIiMER : ; ',.Ss.- . •.::.;: �� # . .. .._ a' .:.�.-.. 7. .. aw.: HVAG;=•Trane 14 SEEkU11 2 EERl80% Pomace W/HERS REQUIRED e. DUCTS STAT MEi iT OF COAIfPLtANCE This ceitf'icaie of corxiplialice lisfs the building features and specifications needed to comply with Title 24 Parts l tl'e Administrative Regulations and Part 6 the Efficiency Standards of tk-60,. ifornia Code of Regulations. The documentation author hereby certifies that the documentation is accurate and complete. Documentation Author Company Roy Eads 68811 Risueno Road 1st Choice HERS Rating7/22014 Address Name City/State/ZipCity/State/Zip Cathedral City, CA 92234 Phone 760-641-2447 Signed Date The individual with overall design responsibility hereby certifies that the proposed building design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application, and recognizes that compliance using duct design, duct sealing, verification of refrigerant charge, insulation installation quality, and building envelope sealing require installer testing and certification and field verification by an approved HERS rater. CITY OF LA QUINITA Designer or Owner (per Business & Professions Code) BUILDING & SAFETY DEPT. Company Temple Construction Inc. -� Address 699 Indian Trail Name Mark Temple "'," i rvlr I IVI City/State/Zip Palm Springs, CA 92264 Phone 760-323-53 Signed License # Date LUA I It �-_ BY--- EnerqyPro 5.1 by Ener Soft User Number. 8305 RunCode: 2014-07-02715:06:47 ID: 140506 R�M-405"-f-- Raaej of Reg: 214-N0050494A-000000000-0000 Registration Date/Time: 2014/07/02 18:10:09 HERS Provider: CalCERTS, Inc -Electronically Filed by 1st Choice HERS Rating and Authenticated at Ca10ERTS.com - 7/2/2014 Electronically Signed at CalCERTS.com by Mark A Temple (Temple Construction) 7/2/2014 CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type ® Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 7/2/2014 OPAQUE SURFACE DETAILS Surface Type Area U- Insulation Joint Appendix Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments Wall 180 0.054 R-21 3.9 None 90 90 New 4.3.1-A6 BLOCK LOAD Door 28 0.500 None 90 90 New 4.5.1-A4 BLOCK LOAD Wall 126 0.054 R-21 3.9 None 180 90 New 4.3.1-A6 BLOCK LOAD Wall 76 0.054 R-21 3.9 None 270 90 New 4.3.1-A6 BLOCK LOAD Wall 155 0.054 R-21 3.9 None 180 90 New 14.3.1-A6 BLOCK LOAD Wal 163 0.054 R-21 3.9 None 90 90 New 4.3.1-A6 BLOCK LOAD Wall 60 0.054 R-21 3.9 None 180 90 New 4.3.1-A6 BLOCK LOAD Wall 145 0.069 R-21 90 90 New 4.3.1-A6 BLOCK LOAD Wall 402 0.054 R-21 3.9 None 0 90 New 4.3.1-A6 BLOCK LOAD Wall 430 0.054 R-21 3.9 None 0 90 New 4.3.1-A6 BLOCK LOAD Wall 158 0.054 1 R-21 3.9 None 270 90 New 4.3.1-A6 BLOCK LOAD Wall 118 0.054 R-21 3.9 None 180 90 New 4.3.1-A6 BLOCK LOAD Wall 112 0.054 R-21 3.9 None 270 90 New 4.3.1-A6 BLOCK LOAD Wall 145 0.054 R-21 3.9 None 0 90 New 4.3.1-A6 BLOCK LOAD Wall 191 0.054 R-21 3.9 None 270 90 New 4.3. 1,46 IBLOCK LOAD Wall 283 0.054 R-21 3.9 None 180 90 New 4.3.1,A6 BLOCK LOAD FENESTRATION SURFACE. DETAILS ID Type Area .-..U-Factor' SHGC Azm Status Glazing Type Location/Comments 1 Window 36.0 . 0.310NFRC 0.20 NFRC 90 New DBLIVINYL 31120 SL BLOCK LOAD 2 Window 14.1 0.330 !NFRC 0.20 NFRC 90 New DBLIVINYL 33120 FX BLOCK LOAD .3 Mhdow:: 2.0 0.300 NFRC 0.24 NFRC 90 New DBL/VINYL 30124 FX BLOCK LOAD 4.. Window 15.0 0.330 NFRC 0.20 NFRC 180 New DBLIVINYL 33120 SH BLOCK LOAD 5::.. Window.,,., _� _ 64.0 0.330 NFRC... 0 23 NFRC.........._ 180 New....,.,..,., DBL/VINYL 33123 SGD .._. BLOCK LOAD 6e5A5:0 0.330 NFI?C _0 20' NFRC X80. News < Wirrdov OBL/a71R1 YL 33120 SH; BLOCK LOAD 7 Window::" ti64;0 0.330 �tF12C _ Q:2fJ lUFRC� 270: `Newer _ ..: B(/VfNYL,33%ZO SGD„ .. . = `l9ZOCK LOAD e Windavr: __ 15 0 a33fl 1tiIFRC, 0.20 NFRC -`= ... f . s::.90 Neto = pBtJiffNYL 320 SH .y,v;;:..: BLOCf< LOAD ...- 9 Winoiv 200 300 111FR;C, . 0247F--,.. :: 90 New DBL/l/lNYCy30124 FXS r� : BLOCff LOAD, 10 Wfndgw X30U,3$D, IVFR,G Q30 NFR D Nev✓ D131M1A�Y433/30 :BLOCF�LOAp... 11 Windgw- 25p a;1-0y33Q AfFRM 6� tdF1�C.M9 .0 �h , D 11tew .. .� .i)BLN1NYLt33120 5t7 12.: UVindvtiv?a:: "' `. 2 Q 330 NFRC 0 20 NFRC .. 0 NeW. DBL -M YL:33120 SH.::::.:::..: `' BLOCK LOAD 13 . Window 20.0 0.330 NFRC:: 0.20 NFRC 0 New DBLIVINYL 33120 SH BLOCK LOAD .14..;, , rrdotv`;ij77 20.0 a330 NFRC 0.20 NFRC 0 New DBLIVINYL 33120 SH BLOCK LOAD 0.320 :NFRC 0.22 NFRC 0 New DBLIVINYL 32122 FX BLOCK LOAD 16 Window 17.01:..0.3200 0.22 NFRC 01 New I DBUVINYL 32122 FX IBLOCK LOAD (1) U -Factor Type: 1,16-Ai:=;Default Table from Standards. NFRC =Labeled Value (2) SHGC Type: "fi6-1 "= Defauft Table from Standards, NFRC = Labeled Value EXTERIOR SHADING DETAILS ID Exterior Shade Type SHGC Window Ove hang Left Fin Right Fin Hot TWd Len Hot I LExt REA Dist Len I Hot Dist Len H t 1 Bug Screen 0.76 6.01 7.0 3.5 20.0 0 9.0 20.0 0 2 Bug Screen 0.76 3.5 7.0 3.5 20.0 0 9.0 20.0 0 3 Bug Screen 0.76 4 Bug Screen 0.76 5.0 3.0 1.5 2.0 10.0 10.0 1.0 20.0 0 16.0 20.0 0 5 Bug Screen 0.76 8.0 8.0 1.5 2.0 10.0 10.0 6.0 20.0 0 6.0 20.0 0 6 ug Screen 0.76 5.0 3.0 1.5 2.0 10.0 10.0 16.0 20.0 0 1.0 20.0 0 7 Bug Screen 0.76 8.0 8.0 1.5 2.0 10.0 10.0 3.0 20.0 0 8.0 20.0 0 8 Bug Screen 0.76 5.0 3.0 1.5 2.0 5.0 10.0 0.0 0.0 0 13.0 11.0 0 9 Bug Screen 0.76 2.0 1.0 1.5 2.0 10.0 10.0 10 ug Screen 0.76 1.0 3.0 1.5 2.0 10.0 10.01 w 11 Bug Screen 0.76 5.0 5.0 1.5 2.0 10.0 10.01 U I I Y WE I� 9 I � I! l ' 12 ug Screen 0.76 5.0 4.0 1.5 2.0 10.0 10A R I I R I R F 3 o c. � -.- � � � r r 13 u Screen 0.76 5.0 4.0 __ �x v �rL t I I. 1.5 2.0 10.0 10.0; 14 rug Screen 0.76 5.0 4.0 1.5 2.0 10.0 10.0 +7--�' P. 1 /1 15 ug Screen 0.76 2.0 6.0 1.5 2.0 10.0 10.0 - � 7 , 16 JBug Screen 0.76 2.0 6.0 1.5 2.0 10.0 10.0 DATE B Io Ener Pro 5.1 by Ener Soft User Number: 8305 RunCode: 2014-07-02715:06:47 52. Pa -f 8 Reg: 214-N0050494A-000000000-0000 Registration Date/Time: 2014/07/02 18:10:09 HERS Provider: CalCERTS, Inc Electronically Filed by 1st Choice HERS Rating and Authenticated at CalCERTS.com - 7/2/2014 Electronically Signed at'CalCERTS.com by Mark A Temple (Temple Construction) 7/2/2014 CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type ® Single Family O Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 7/2/2014 OPAQUE SURFACE DETAILS Surface Type Area U- Insulation Joint Appendix Factor Cavity Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments Wall 227 0.054 R-21 3.9 None 180 90 New 4.3.1-A6 BLOCK LOAD Wall 215 0.069 R-21 90 90 New 4.3.1-A6 BLOCK LOAD Wall 56 0.069 R-21 180 90 New 4.3.1-A6 BLOCK LOAD Door 24 0.500 None 180 90 New 4.5.1-A4 BLOCK LOAD Wall 184 0.054 R-21 3.9 None 0 90 New 4.3.1-A6 BLOCK LOAD Slab 3,444 0.730 None 0 180 New 4.4.7-A 1 BLOCK LOAD Roof 3,444 0.025 R-38 180 14 New 4.2.1-A21 BLOCK LORD FENESTRATION SURFACE DETAILS ID Type Area : U -Factor SHGC Azm Status Glazing Type Location/Comments 17 Window 12.0 . 0.320 NFRC 0.22 NFRC 0 New DBL/VINYL 32/22 FX BLOCK LOAD 18 Window 36.0 0.330 NFRC 0.20 NFRC 0 New DBL/VINYL 33/20 SH BLOCK LOAD 19 . Mndow--. o ...: 12.0 0.320 NFRC 0.22 NFRC 0 New DBL/VWNYL 32/22 FX BLOCK LOAD 20 Window 15.0 0.330 NFRC 0.20 NFRC 270 New DBL/VINYL 33/20 SH BLOCK LOAD 21--.: Window -,_ 6.0 0.320 NFRC.::.. 0 22 NFRC...... _..._270 New _._,.::__ DBLNWNYt. 32/22 FX, _ BLOCK LOAD 22.: btkndpw 0.330 NFRC; 0 2U ;ltfFRCs ° 27Q :News ,. ; • tDBLN1NYt�332Q SW ` BLOCK LOAD 23 lMndofr�; ". . 6 0 0 320 NF: RCF § , BLOCK LOAD ,;s:0:22 NFRC+ = 270, Newer �... . QBE.W YL 3?l12 FX. r . _ 24 .. bYmdoVr: . "5 0:0 330 NFRC 0.20 NFRC -F 270 New_, DBiJV(NY�33/20 SH: gid ::. BLOCK LOAD .: . .. . 25 Uirirrdow 6=0, ; 1{D332(1 NF13C `: 0.22 NFRC :>£`=270 Aleve T = pBL/VJl1�J2r32/22 FX 26ndaw . fi4 0 0 330 NF C 0.20 NFRC- 180 :+New M DBL/!/INYL33/20 SGD 4w .BLOCff"LOAD.. 27 1Rlndow ?,_.'20(14`© 330 NFRC 0 73„NFRC::�270 ;Nett'.,... ;iiBL/IIUYYi 43723 28.. Wtnddw :240 `077(3 NFRC 0 73 NFRG..: O New FR?DODRDBL IbiTL DEFAUET`"BLOCK LOAD 29 Window':. 15.0 0.330 IVPC :'- 0.20 NFRC 270 New DBL/VINYL 33/20 SH BLOCK LOAD 30.,:: 0.320 NERC 0.22 NFRC 270 New DBL/VINYL 32/22 FX BLOCK LOAD 31.'5; W(nddw:'- ', '1:: i"15 0 0.330 NFRC 0.20 NFRC 1 2701 New DBWINYL 33/20 SH BLOCK LOAD 32 Wridow 6.0:.... 0.320. NFRC 1 0.22 NFRC 1 2701 New DBL/VINYL 32/22 FX IBLOCK LOAD (1) U -Factor Type: 1.164-.*'�:_Defauk Table from Standards, NFRC =Labeled Value 2 SHGC Type: 116 f3'= DefauR Table from Standards, NFRC =Labeled Value EXTERIOR SHADING DETAILS ID: Exterior Shade Type SHGC Window Ove hang Left Fin Right Fin Hot Wd Len Hot I LExt RExt Dist Len Hot Dist Len H t 17 Bug Screen 0.76 2.0 6.0 1.5 2.0 10.0 10.0 18 Bug Screen 0.76 19 Bug Screen 0.76 2.0 6.0 1.5 2.0 10.0 10.0 20 Bug Screen 0.76 21 Bug Screen 0.76 22 Bug Screen 0.76 23 Bug Screen 0.76 24 Bug Screen 0.76 25 Byg Screen 0.76 26 Bug Screen 0.76 8.0 8.0 20.0 2.0 3.0 1.0 1.0 2.0 0 1.0 24.0 0 27 Bug Screen 0.76 10.0 20.0 12.01 2.0 2.0 2.0 2.0 14.0 0 2.0 10.0 0 28 Bug Screen 0.76 8.0 3.0 24.0 5.0 6.0 3.0 ,6:,01 .,..x,2¢.0 s _ 0' `0 2-0 0 29 Bug Screen 0.76 i )t- LA Q1 I I N I 30 Pug Screen 0.76 g j I 6f�1 _, C` i rr-�., 31 ug Screen 0.76 t u Cri I • I 32 ug Screen 1 0.76 Iiiy,ii�dr-� IFOR CONSTRUCTIO=Pa6 Ener Pro 5.1 b Ener Soft User Number: 8305 RunCode: 2014-07-02T15:06:47 I ID: 140506 REV2 14052 Reg: 214-NO050494A-000000000-0000 Registration Date/Time: 2014/07/02 18:10:09 HERS Proviaer: alt�trrs o-+ Electronically Filed by 1st Choice HERS Rating and Authenticated at CalCERTS.com - 7/2/2014 Electronically Signed at CalCERTS.com by Mark A Temple (Temple Construction) 7/2/2014 CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type ® Single Family ❑ Addition Alone 0I Multi Family ❑ Existing+ Addition/Alteration Date 7/2/2014 OPAQUE SURFACE DETAILS Surface U- Insulation Joint Appendix Type Area Factor Cavi Exterior Frame Interior Frame Azm Tilt Status 4 Location/Comments FENESTRATION SURFACE DETAILS ID Type Area U -Factor SHGCz Azm Status Gla2in2 Type Location/Comments 33 Window 15.0 - 0.330 .NERC 0.20 NFRC 270 New DBLIVINYL 33/20 SH BLOCK LOAD 34 Wndow 6.0 0.320 NFRC 0.22 NFRC 270 New DBUVINYL 32/22 FX BLOCK LOAD 35, WiridaW :'" ...:.' 15.0 0.330 NERC 0.20 NFRC 180 New DBLIVINYL 33/20 SH BLOCK LOAD 36 Window 6.0 0.320 NFRC 0.22 NFRC 180 New DBLIVINYL 32/22 FX BLOCK LOAD 37::: Wfndow., ­_._ 15.01 0.330 NFRC,:. 0.,10., NFRC ..... ....... 80 New__...,.,._, DBL/VINYL_ 33/20 SH , . __. BLOCK LOAD x:6;0 0.320 NFRC 0 22 ;NFRC ?80. Newer _ ' , OBL Y1NYL 3Z/22 FX , .,MBLOCK LOAD 38 Mndow' .. _F a� ; _ . 39 UVrndotti :` ' x'33'0 0.340NFRC, x=;0:22 'NFRC` e<' 18Q NeiNy ;':. DBL/VlNYL�34/2?F?C:` BLOCK LOAD 40 1Mndpin? i6.0 0 330 NFRC, 0.20 NFRCw0 NUm- ,. DBL.(V1NY,L1W0 SH :: _� _:-. BLOCK LOAD-:-:. ' ....... .. `"'�.�_''asU� .. J^�a �s. ..#1 ... x..: .. ..%RF .,-,:*,C:.. .':::t"' _ .....-1185 I':: &W P. : (1) U -Factor Type: ':::116-A.=`Default Table from Standards, NFRC =Labeled Value 2 SHGC Type: 1•`16-0_,Defauft Table from Standards, NFRC = Labeled Value EXTERIOR SHADING DETAILS Window Ove hang Left Fin Right Fin ID Exterior Shade T e SHGC H t Wd Len H t LExt REA Dist Len I H t Dist Len Hat 33 Bug Screen 0.76 34 Bug Screen 0.76 35 Bug Screen 0.76 36 Bug Screen 0.76 37 Bug Screen 0.76 38 Bug Screen 0.76 39 Bug Screen 0.76 40 Bug Screen 0.76 4.01 4.0 1.5 2.0 10.0 10.0 10.0 20.0 0 6.5 20.0 0 /Rt R I l�I IT u Q11 1I( I -Ir IIrsir n A •� - vitt L CI -'1. ;ice" P a B DATE BY Ener Pro 5.1 by Ener Soft User Number. 8305 RunCode: 2014-07-02T15:06:47 Pa 7 0 Reg: 214-N0050494A-000000000-0000 Registration Date/Time: 2014/07/02 18:10:09 HERS Provider: CalCERTS, Inc Electronically Filed by 1st Choice HERS Rating and Authenticated at CalCERTS.com - 7/2/2014 Electronically Signed at CalCERTS.com by Mark A Temple (Temple Construction) 7/2/2014 CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5 CF -1 R Project Name CITRUS - LOT 5 Building Type ® Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 7YM014 BUILDING ZONE INFORMATION Floor Area f System Name Zone Name New Existinq Altered I Removed Volume Year Built HVAC ALL ROOMS IN ZONE 3,444 37,884 Totals 3,4441 01 01 0 HVAC SYSTEMS System Name Qt :>:'::'Heatin Type Min. Eff. Cooling Type Min. Eff, Thermostat Type Status HVAC.'. ':::::::'•:':' 2 ':GentralFurnace 80%AFUE Split Air Conditioner 14.0 SEER Setback New - _ t4 _..�."" 0i:...,.:':: ,: 201" k' no.o� c3�I`ue .<�k.a.. S Status T sled? HVAC. ."Ducted? :::: Ducted Attic, Ceiling Ins, vented 8.0 m New WATER HEATING SYSTEMS S stem Name Oty. Type Distribution Rated Input Btuh Tank Cap. al Energy Factor or RE Standby Loss or Pilot Ext. Tank Insul. R- Value Status Bradford -White U2XR75S( 1 Large Gas RecirclTimer 76,000 75 0.80 2.50% n1a New MULTI -FAMILY WATER HEATING DETAILS HYDRONIC HEATING SYSTEM PIPING Control Hot Water Piping Length ft 0 _ o QU)ft-e - S stem a -e,. thl --Pip — F41S` . /Dig1r 4t4rJ �5" Qty. HP Plenum Outside Buried T r CQ ❑ ILQ,N� AF ' - ❑ r—t d t IcTION ❑ F0-, EnergyPro 5.1 by Ener Soft User Number. • 8305 RunCode: 2014-07-02T15:06:47 1 6 REV2 14052,BY---4-dgeT-5TT Reg: 214-N0050494A-000000000-0000 Registration Date/Time: 2014/07/02 18:10:09 HERS Provider: CalCERTS, Inc WINDOW WORKSHEET DATE: 5/17/2014 BY: ROY EADS TEMPLE CITRUS LOT 5 REV: 5/28/2014 9PM BY: ROY EADS 50625 BREVA, LA QUINTA WINDOW DESCRIPTION WALL TOTAL WINDOW SIZE FACE TYPE FRAME DBL CLEAR U SHGC HZ OVERHANG DIST LEFT RIGHT LEFT SIDEFIIy°^-�+� INVOICE DIST BIST. REFERENCE # # SF W' W" HH" SINGLE OBSCURE FACTOR PRO1 ABOVE EXT FROM EXT FR M # WINDOW LOCATION X, Lru% 1 Z 1 FRONT ENTRY 1 36.0 6 0 6 0 E SL VINYL DBL CLR 0.31 0.20 20.0 3.5 20.0 j9A Ol 2 1/2 ROUND UPPER 1 14.1 6 0 3 0 E FX VINYL DBL CLR 0.33 0.20 20.0 3.5 2"0.0X9'.0- 'LL6 3 CRTYRD UPPER 1 2.0 1 0 2 0 E FX VINYL DBL CLR 0.30 0.24 , r LL "09 4 BONUS CRTYD LEFT 2 15.0 3 0 5 0 S SH VINYL DBL CLR 0.33 0.20 1.5 2 10.0 10.0 20.0 1.0 20.0 j 16A 002 5 BONUS CRTYD SGD 2 64.0 8 0 8 0 5 SGD VINYL DBL CLR 0.33 0.23 1.5 2 10.0 10.0 20.0 6.020.0 6:0 (, 019 6 BONUS CRTYD RT 2 15.0 3 0 5 0 S SH VINYL DBL CLR 0.33 0.20 1.5 2 10.0 10.0 20.0 16.020:0' i �1;0 i) 0 2 7 BD 3 SGD 3 64.0 8 0 8 0 W SGD VINYL DBL CLR 0.33 0.20 1.5 2 10.0 10.0 20.0 3.0 120.0 :8:0 1 1y f019 8 BD 3 FRONT 5 15.0 3 0 5 0 E SH VINYL DBL CLR 0.33 0.20 1.5 2 5 10.0 0.0 0.0 111-0 X13,.0 -i X003 9 BA 3 FRONT 5 2.0 1 0 2 0 E FX VINYL DBL OBSC 0.30 0.24 1.5 2 10.0 10.0 X006 10 BA 2 RT SIDE 8 3.0 3 0 1 0 N SH VINYL DBL CLR 0.33 0.30 La 004 C 11 BD 2 RT SIDE 8 25.0 5 0 5 0 N SL VINYL DBL CLR 0.33 0.20 1.5 2 10.0 10.0 " -007 12 BONUS RT SIDE -1 8 20.0 4 0 5 0 N SH VINYL DBL CLR 0.33 0.20 1.5 2 10.0 10.0 005 13 BONUS RT SIDE -2 8 20.0 4 0 5 0 N SH VINYL DBL CLR 0.33 0.20 1.5 2 10.0 10.0 005 14 BONUS RT SIDE -3 8 20.0 4 0 5 0 N SH VINYL DBL CLR 0.33 0.20 1.5 2 10.0 10.0 005 15 KITCH UPPER -1 8A 12.0 6 0 2 0 N FX VINYL DBL CLR 0.32 0.22 1.5 2 10.0 10.0 010 16 KITCH UPPER -2 8A 12.0 6 0 2 0 N FX VINYL DBL CLR 0.32 0.22 1.5 2 10.0 10.0 010 17 KITCH UPPER -3 BA 12.0 6 0 2 0 N FX VINYL DBL CLR 0.32 0.22 1.5 2 10.0 10.0 010 18 DIN RT SIDE 8A 36.0 6 0 6 0 N SL VINYL DBL CLR 0.33 0.20 008 19 CLERESTORY 8A 12.0 6 0 2 0 1 N FX VINYL DBL CLR 0.32 0.22 1.5 2 5 10.0 010 20 DIN REAR -1 9 15.0 3 0 1 5 0 W SH VINYL DBL CLR 0.33 0.20 003 21 CLERESTORY 9 6.0 3 0 2 0 W FX VINYL DBL CLR 0.32 0.22 011 22 DIN REAR -2 9 15.0 3 0 5 0 W SH VINYL DBL CLR 0.33 0.20 003 23 CLERESTORY 9 6.0 3 0 2 0 W FX VINYL DBL CLR 0.32 0.22 011 24 DIN REAR -3 9 15.0 3 0 5 0 W SH VINYL DBL CLR 0.33 0.20 003 25 CLERESTORY 9 6.0 3 0 2 0 W FX VINYL DBL CLR 0.32 0.22 011 26 1 DIN SGD 10, 64.0 8 1 0 8 0 1 S SGD VINYL DBL CLR 0.33 0.20 20.0 3.0 2.0 1.0 1,1 2.0 1.0 24.0 1.0 020 27 GRT RM SGD 11 200.0 20 0 10 0 W SGD ALUM DBL CLR 0.43 0.23 12.0 2.0 2.0 2.0 14.0 2.0 10.0 2.0 1-1 28 MB FR DOOR 12 24.0 3 0 8 0 N FD 77 DBL CLR 0.77 0.73 24.0 5.0 6.0 3.0 124.0 6.0 2.0 1.0 DEFAULT 29 MB REAR -1 13 15.0 3 0 5 0 W SH VINYL DBL CLR 0.33 0.20 003 30 CLERESTORY 13 6.0 3 0 2 0 W FX VINYL DBL CLR 0.32 0.22 011 31 MB REAR -2 13 15.0 3 0 5 0 W SH VINYL DBL CLR 0.33 0.20 003 32 1 CLERESTORY 13 6.0 3 0 2 0 W FX VINYL DBL CLR 0.32 0.22 011 33 IMB REAR -3 13 15.0 3 0 5 0 W SH VINYL DBL CLR 0.33 0.20 003 CITY Cp Lj� QUINTA COMMUNITY DEVELOPMENT lip WINDOW WORKSHEET DATE: 5/17/2014 BY: ROY EADS TEMPLE CITRUS LOT 5 REV: 5/28/2014 9PM BY: ROY EADS 50625 BREVA, LA QUINTA OVERHANG INVOICE IDEFIN WINDOW DESCRIPTION WALL TOTAL WINDOW SIZE FACE TYPE FRAME DBL CLEAR U JSHGC HZ I DIST I LEFT RIGHT LEFT DI T, fRT 1. DIST REFERENC # N SF W' W" H' H" SINGLE OBSCURE FACTOR PROD ABOVE EXT FROM ,EXyf FROM # 34 CLERESTORY 13 6.0 3 0 2 0 W FX VINYL DBL CLR 0.32 0.22 N �9 ? 011 35 11,11B LEFT SIDE -1 14 15.0 3 0 5 0 S SH VINYL DBL CLR 0.33 0.20 N - 003 36 1 CLERESTORY 14 6.0 3 0 2 0 S FX VINYL DBL CLR 0.32 0.22 i( f7 u� E 011 37 MB LEFT SIDE -2 14 15.0 3 0 5 0 S SH VINYL DBL CLR 0.33 0.20 LL ; 003 38 CLERESTORY 14 6.0 3 0 2 0 S FX VINYL DBL CLR 0.32 0.22 ���J7 011 0] 39 MBA 14A 33.0 5 6 6 0 S FX VINYL DBL CLR 0.34 0.22 IT o "_ 009 40 LAUNDRY 17 16.0 4 0 4 0 N SH VINYL DBL CLR 0.33 0.20 1.5 2 10.0 10.0 20.010.0' 320;0 C6'.5 C) 001 a C ;Tc LU w #28 MB FRENCH DOOR - USE DEFAULTS OF 77/73 '' �'` L Q TOTAL WINDOWS SF >>> 904 TOTAL EXT WALL SURFACE SF >>> 4480 CFA 5F >>> 3444 WEST FACING SF >>> 190 W W R% >>> 20.2% WEST FACE/TOTAL WINDOWS >>> 21.0% WEST FACING/CFA RATIO >>> 5.5% FENESTRATION/CFA RATIO >>> 26.3% DOORS 1 FRONT ENTRY DOOR 1 28.0 1 3 6 8 0 IS THERE GLASS ON THIS DOOR ??? 2 GARAGE DOOR 16 24.0 3 0 8 0 1