13-0973 (SFD) Title 24
BUILDING ENERGY ANALYSIS REPORT PROJECT: Ahlering Residence Lot 22, Cahuilla Ct., Traditions La Quinta, CA 92253 Project Designer: Gordon Stein Designs 74-794 42nd Ave, Suite 9 Palm Desert, Ca 92211 (760) 773-4488 Report Prepared by: Tim Scott . Scott Design and Title 24, Inc, #_ 77-085 Michigan Drive Palm Desert, Ca 92211 y (760) 200-4780 Job Number: Date: 10/14/2013 IThe EnergyPro computer program has been used to perform the calculations summ. authorized by the California Energy Commission for use with both the Residential • This program developed by EnergySoft, LU Ene "Pro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-10-1 REGENt-'' po Q\3 l�4 r CTVNO� pEv`�LCr COM / BUtt_t /OF LA NG 'q �R � S,q ETY DEPT. Lf din this•ebo�myplianoe report. T,�his!program has app oval and is Non residentia1.20.08;BUildi'nq 6eT'a -Efficiencv andards. TABLE OF CONTENTS Cover Page 1 Table of Contents 2 Form CF -1 R Certificate of Compliance 3 Form MF -1 R Mandatory Measures Summary 12 HVAC System Heating and Cooling Loads Summary 15 Room Load Summary 18 Room Heating Peak Loads 21 Room Cooling Peak Loads 26 CIT' OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTION DATE `_ BY 5.1 by Ene • CJ • PERFORMANCE CERTIFICATE: Residential Part 1 of 5 CF -1 R Project Name Ahlering Residence Building Type m Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration 11011412013 Date Project Address Lot 22, Cahuilla Ct., Traditions La Quinta California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 4,908 Addition n/a # of Stories 1 FIELD INSPECTION ENERGY CHECKLIST ❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form. ❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details. INSULATION Construction Type Area Special Cavity (ft) Features see Part 2 of 5 Status Roof Wood Framed Attic R-38 4,908 Radiant Barrier New Wall Wood Framed R-21 5,871 New Slab Unheated Slab -on -Grade None 4,908 Perim = 580' New Door Opaque Door None 48 New FENESTRATION U- Exterior Orientation Area Factor SHGC Overhang Sidefins Shades Status Left (SE) 84.0 0.380 0.34 none none Bug Screen New Left (SE) 192.0 0.440 0.30 none none Bug Screen New Rear (SW 96.0 0.440 0.30 none none Bug Screen New Right (NM 96.0 0.440 0.30 none none Bug Screen New Front (NE) 256.2 0.440 0.30 2.0 none Bug Screen New Front (NE) 49.9 0.380 0.34 none none Bug Screen New Rear (SW 400.0 0.440 0.30 20.0 none Bug Screen New Rear (SlM 74.9 0.380 0.34 none none Bug Screen New Rear (StM 24.0 0.440 0.30 16.0 none Bug Screen New Right (NIM 10.0 0.380 0.34 16.0 none Bug Screen New Right (NtM 52.2 0.380 0.34 none none Bug Screen New HVAC SYSTEMS City. Heating Min. Eff Cooling Min. Eff Thermostat Status 1 Split Heat Pump 9.50 HSPF Split Heat Pump 16.5 SEER Setback New 2 Split Heat Pump 9.50 HSPF Split Heat Pump 16.0 SEER Setback New 1 Split Heat Pump 10.00 HSPF Split Heat Pump 19.0 SEER Setback New HVAC DISTRIBUTION Location Heating Duct Cooling Duct Location R -Value Status HVAC 1 Ducted Ducted Attic, Ceiling Ins, vented 8.0 New HVAC 2 & 3 Ducted Ducted Attic, Ceiliag lns, vented 8.0 New HVAC 4 Ducted Ducted Attic, Ceiling Ins Vgnted� WATER HEATING I BUILDING & SaFE II A Ot . Type Gallons Min. Eff Distribution, ,___ __ �' DEPT, Atatus 1 Large Gas 100 �- 0.80 1 All Pipes.lnse f� (VED New "" j ►-SUCTION By-�- EnergyPro 5.1 by Ener Soft User Number.- 6712 RunCode: 20 13-1 0-14 71 6:35:46 I Page 3 of 31 • C PERFORMANCE CERTIFICATE: Residential Part 1 of 5 CF -1 R Project Name Ahlering Residence Building Type 14 Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration 11011412013 Date Project Address Lot 22, Cahuilla Ct., Traditions La Quinta California Energy Climate Zone CA Climate Zone 15 Total Cond. Floor Area 4,908 Addition n/a # of Stories 1 FIELD INSPECTION ENERGY CHECKLIST ❑ Yes ❑ No HERS Measures -- If Yes, A CF -4R must be provided per Part 2 of 5 of this form. ❑ Yes ❑ No Special Features -- If Yes, see Part 2 of 5 of this form for details. INSULATION Area Special Construction Type Cavity (ft) Features see Part 2 of 5 Status FENESTRATION U- Exterior Orientation Area Factor SHGC Overhang Sidefins Shades Status Right (NW) 54.0 0.380 0.34 4.0 none Bug Screen New Left (SE) 10.0 0.380 0.34 6.0 none Bug Screen New HVAC SYSTEMS Ot . Heating Min. Eff Cooling Min. Eff Thermostat Status HVAC DISTRIBUTION Duct Location Heating Cooling Duct Location R -Value Status --------------- CITY OFI A 01II WATER HEATING BUILDING & SAFETY DEPT. Ot . Type Gallons Min. Eff Listr4ptioln-1 �` �l� �tatus r F tT nATP EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-10-14T16:35:46 ID: Page 4 of 31 • • 0 PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF -1 R Project Name Building Type ® Single Family ❑ Addition Alone Date Ahlering Residence 1 ❑ Multi Family ❑ Existing+ Addition/Alteration 11011412013 SPECIAL FEATURES INSPECTION CHECKLIST The enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. The DHW System Bradford -White #M-1-100T6BN is a non-NAECA large storage gas water heater. Verify DHW details. The HVAC System HVAC 1 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential A endix RA3.3 must be met. HIGH MASS Design -Verily Thermal Mass: 552.0 ft2 Covered Slab Floor, 3.500" thick at Master Bedroom HIGH MASS Design - Verify Thermal Mass: 290.0 112 Exposed Slab Floor, 3.500" thick W Master Bedroom The HVAC System HVAC 2 & 3 must serve only Living Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a separate thermostat. In addition the air flow requirements and fan watt draw requirements in Residential Appendix RA3.3 must be met. HIGH MASS Design - Verify Thermal Mass: 232.0 ft2 Covered Slab Floor, 3.500" thick at Living/Kitchen HIGH MASS Design - Verify Thermal Mass: 2,315.0 ft2 Exposed Slab Floor, 3.500" thick at Living/Kitchen HIGH MASS Design - Verify Thermal Mass: 252.0 ft2 Covered Slab Floor, 3.500" thick at Bedroom 2 HIGH MASS Design - Verify Thermal Mass: '58. 0 ft2 Exposed Slab Floor, 3.500" thick at Bedroom 2 HIGH MASS Design - Verify Thermal Mass: 59.0 It' Covered Slab Floor, 3.500" thick at Bedroom 3 HIGH MASS Design - Verify Thermal Mass: 290.0 ft2 Exposed Slab Floor, 3.500" thick at Bedroom 3 The HVAC System HVAC 4 must serve only Sleeping Areas. The non -closable area between zones cannot exceed 40 sf and each zone must have a separate thermostat. In addition the air flow re uirements and fan watt draw requirements in Residential Appendix RA3.3 must be met. HIGH MASS Design - Verify Thermal Mass: 750.0 R2 Covered Slab Floor, 3.500" thick at Guest HERS REQUIRED VERIFICATION Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a completed CF -4R form for each of the measures listed below for final to be given. The Cooling System Carrier 25HNB94ffE4ANB006 includes credit for a 13.1 EER Condenser. A certified HERS rater must field verify the installation of the correct Condenser. The HVAC System HVAC 1 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display. The HVAC System HVAC 1 includes credit for verified adequate airflow A certified HERS rater must diagnostically measure airflow of the HVAC System. The HVAC System HVAC 1 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct leakage meets the specified criteria. The Cooling System Carrier 25HNB960/FE4ANS006 includes credit for a 12.5 EER Condenser. A certified HERS rater must field verify the installation of the correct Condenser. The HVAC System HVAC 2 & 3 incorporates HERS Verified Refrigerant Charge or a Charge Indicator Display. The HVAC System HVAC 2 & 3 includes credit for verified adequate airflow. A certified HERS rater must diagnostically measure airflow of the HVAC System. The HVAC System HVAC 2 & 3 incorporates HERS verified Duct Leakage. HERS field verification and diagnostic testing is required to verify that duct leakage meets the specified criteria. The Cooling System Carrier 25HNB936/FE4ANS006 includes credit for a 13.7 EER Condenser. A certified HERS rater must field verify the installation of the correct Condenser. I — , ^ The HVAC System HVAC 4 incorporates HERS Verified Refrigerant Charge or a Chargd In icato? Displa rlI- LAQ U l A TA V aU1Ln�f,t� .Q ,- 1 The HVAC System HVAC 4 includes credit for verified adequate airflow. A certified HERS rater must. diagnostically rne'asure a rfi v+61The VAC System. !� S -j b a' The HVAC System HVAC 4 incorporates HERS verified Duct Leakage. HERS field verification anq:gibgn o�� Jteesst ` is e_'' Wit verify th t duct A leakage meets the specified criteria. 11 � QN NDATE'—_ rE—nerqyPro 5.1 by Ener Soft User Number: 6712 RunCode: 2013-10-14TT6:35:46-----ID,�–a e 5 of 31 • • • PERFORMANCE CERTIFICATE: Residential Part 2 of 5 CF=1 R Project Name Ahlering Residence Building Type ® Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 10/14/2013 SPECIAL FEATURES INSPECTION CHECKLIST The enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. HIGH MASS Design - Verify Thermal Mass: 110.0 ft' Exposed Slab Floor, 3.500" thick at Guest The Roof R-38 Roof(R.38.2x 14.16) includes credit for a Radiant Barrier that is Continuous meeting eligibility and installation criteria as specified in Residential Appendix RA4.2.2. HERS REQUIRED VERIFICATION Items in this section require field testing and/or verification by a certified HERS Rater. The inspector must receive a completed CF -4R form for each of the measures listed below for final to be given. ii Y OF LA QUINTq -- ���r �•.� Z)/.f-I± I Y DEPT. AID r Ri. Air- r-% F OR UCNST,RUCTIO I nATP: Ene Pro 5.1 b Ene Soft User Number.' 6712 RunCode: 2013-10-14T1613.5.461 ��_ Pbae 6 of 31 • • • PERFORMANCE CERTIFICATE: Residential Part 3 of 5 CF -1 R Project Name Building Type O Single Family ❑ Addition Alone Date Ahlering Residence 1 ❑ Multi Family ❑ Existing+ Addition/Alteration 10/14/201 ANNUAL ENERGY USE SUMMARY Standard Proposed Margin TDV kBtu/ft2 r Space Heating 4.84 5.25 -0.41 Space Cooling 63.25 48.98 14.27 Fans 12.15 16.93 -4.79 Domestic Hot Water 7.43 5.00 2.43 Pumps 0.00 0.00 0.00 Totals 87.67 76.16 11.51 Percent Better Than Standard: 13.1 BUILDING COMPLIES - HERS VERIFICATION REQUIRED Fenestration Building Front Orientation: (NE) 45 deg Ext. Walls/Roof Wall Area Area Number of Dwelling Units: 1.00 (NE) 1,787 306 Fuel Available at Site: Natural Gas (SE) 2,212 286 Raised Floor Area: 0 (StM 1,809 595 Slab on Grade Area: 4,908 (NM 1,510 212 Average Ceiling Height: 14.3 Roof 4,908 0 Fenestration Average U -Factor: 0.43 TOTAL: 1,399 Average SHGC: 0.31 Fenestration/CFA Ratio: 28.5 REMARKS Traditions Country Club Lot 14 STATEMENT OF COMPLIANCE This certificate of compliance lists the building features and specifications needed to comply with Title 24, Parts 1 the Administrative Regulations and Part 6 the Efficiency Standards of the California Code of Regulations. The documentation author hereby certifies that the documentation is accurate and comp) te. Documentation Author Company Scott Design and Titie 24, Inc, 10/14/2013 Address 77-085 Michigan Drive Name Tim Scott City/State/ZipCity/State/Zip Palm Desert, Ca 92211 Phone (760) 200-4780 Signed Date The individual with overall design responsibility hereby certifies that the proposed building design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application, and recognizes that compliance using duct design, duct sealing, verification of refrigerant charge, insulation installation quaffVy,,arncd building-ervvelope s. a'n re uire installer testing field by �iERS rater. O and certification and verification an approved QL NTA Designer or Owner (per Business & Professions Code) BUILDING & SAFETY DEPT. Company Gordon Stein Designs �, s ~I P Y � ROVE® Address 74-794 42nd Ave, Suite 9 Name Gordon Stein FOij CONS TintKi City/State/Zip Palm Desert, Ca 92211 Phone (760) 773-4488 Signed License # Date r)ATP By I-EnergyPro 5.1 by Ener Soft User Number: 6712 Run Code: 2013-10-14T16:35:46 ID: Page 7 of 31 0 • CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5 CF -1 R Project Name Ahlering Residence Building Type m Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition// Iteration Date 10/14/2013 OPAQUE SURFACE DETAILS Surface Type Area U- Insulation Factor Cavity Exterior Frame Interior Frame Azm Joint Appendix Tilt Status 4 Location/Comments Roof 842 0.026 R-38 0 20 New 4.2.1-A9 Master Bedroom Wall 22 0.069 R-21 0 90 New 4.3.1-A6 Master Bedroom Wall 453 0.069 R-21 135 90 New 4.3.1-A6 Master Bedroom Wall 216 0.069 R-21 225 90 New 4.3.1-A6 Master Bedroom Wall 190 0.069 1 R-21 315 90 New 4.3.1-A6 Mester Bedroom Slab 552 0.730 None 6 180 New 4.4.7-A1 Master Bedroom Slab 290 0.730 None 0 180 New 4.4.7-A1 Master Bedroom Roof 2,547 0.026 R-38 6 20 New 4.2.1-A9 Living/Kitchen Wall 1,095 0.069 R-21 45 90 New 4.3.1-A6 Living/Kitchen Door 24 0.500 None 45 90 New 4.5.1-A4 Living/Kitchen Door 24 0.500 None 45 90 New 4.5.1-A4 Living/Kitchen Wall 720 0.069 R-21 135 90 New 4.3.1-A6 Livin /Kitchen Wall 591 0.069 R-21 225 90 New 4.3.1-A6 Living/Kitchen Wall 333 0.069 R-21 315 90 New 4.3.1-A6 Living/Kitchen Slab 232 0.730 None 0 180 New 4.4.7-A1 ILivinglKitchen Slab 2,315 0.730 None 0 180 New 4.4.7-A1 Livin /Kitchen FENESTRATION SURFACE DETAILS ID Type Area LI -Factor' SHGC Azm Status Glazing Type Location/Comments 1 Window 12.0 0.380 NFRC 0.34 NFRC 135 New Fleetwood Window (Kona) Master Bedroom 2 Window 48.0 0.440 NFRC 0.30 NFRC 135 New Fleetwood Doors (Norwood) Master Bedroom 3 Window 96.0 0.440 NFRC 0.30 NFRC 225 New Fleetwood Doors (Norwood) Master Bedroom 4 Window 96.0 0.440 NFRC 0.30 NFRC 315 New Fleetwood Doors (Norwood) Master Bedroom 5 Window 108.0 0.440 NFRC 0.30 NFRC 45 New Fleetwood Doors (Norwood) LivingfiGtchen 6 Window 8.3 0.380 NFRC 0.34 NFRC 45 New Fleetwood Window (Kona) Living/Kitchen 7 Window 40.2 0.440 1 NFRC 0.30 NFRC 45 New Fleetwood Doors (Norwood) Living/Kitchen 8 Window 8.3 0.380 NFRC 0.34 NFRC 45 New Fleetwood Window (Kona) living/Kitchen 9 Window 108.0 0.440 NFRC 0.30 NFRC 45 New Fleetwood Doors (Norwood) Living/Kitchen 10 Window 8.3 0.380 NFRC 0.34 NFRC 45 New Fleetwood Window (Kona) Living/Kitchen 11 Window 400.0 0.440 NFRC 0.30 NFRC 225 New Fleetwood Doors (Norwood) Living/Kitchen 12 Window 8.3 0.380 NFRC 0.34 NFRC 225 New Fleetwood Window (Kona) Living/Kitchen 13 Window 8.3 0.380 NFRC 0.34 NFRC 225 New Fleetwood Window (Kona) Living/Kitchen 14 Window 8.3 0.380 NFRC 0.34 NFRC 225 New Fleetwood Window (Kona) Living/Kitchen 15 Window 24.0 0.440 NFRC 0.30 NFRC 225 New Fleetwood Doors (Norwood) Living/Kitchen 16 Window 10.0 0.380 NFRC 0.34 NFRC 315 New Fleetwood Window (Kona) Living/Kitchen (1) U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value 2 SHGC Type: 116-B = Default Table from Standards, NFRC = Labeled Value EXTERIOR SHADING DETAILS ID Exterior Shade Type SHGC Window H t WdLen Ove hanq Left Fin Ri ht Fin H t LExt REM Dist Len H t Dist Len H t 1 Bug Screen 0.76 2 Bug Screen 0.76 3 Bug Screen 0.76 4 Bu . Screen 0.76 5 Bug Screen 0.76 9.0 12.0 2.0 0.1 2.0 2.0 6 Bug Screen 0.76 7 Bug Screen 0.76 9.0 8.0 2.0 0.1 2.0 2.0 8 Bug Screen 0.76 9 Bu Screen 0.76 9.0 12.0 2.0 0.1 2.0 2.0 10 Bu Screen 0.76 ---_ 11 Bu Screen 0.76 10.0 40.0 20.0 0.1 2d,,0, 2010 12 Bug Screen 0.76 13 Bu Screen 0.76 _ �" "�a W �Al= 14 Bug Screen 0.76 15 JBug Screen 0.76 10.0 3.8 16.0 0.1 16.0 '=x,16.0 ' r % V ifs N 16 JBug Screen 0.76 6.0 2.0 16.01 0.1 16.0 ` 6-(-TN-,,� DAT Ener Pro 5.1 6 Ener Soft User Number: 6712 RunCode: 2013- -35:46 paq.- 8 of 31 C7 • • CERTIFICATE OF COMPLIANCE: Residential Part 4 of 5L CF -1 R Project Name Ahlering Residence Building Type m Single Family 13Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 10/14/2013 OPAQUE SURFACE DETAILS Surface Type Area 41- Insulation Factor Cavity Exterior Frame Interior Frame Azm Joint Appendix Tilt Status 4 Location/Comments Roof 310 0.026 R-38 0 20 New 4.2.1-A9 Living/Kitchen Wall 99 0.064 R-21 45 90 New 4.3.1-A6 Living/Kitchen Wall 171 0.069 R-21 135 90 New 4.3.1-A6 Living/Kitchen Wall 22 0.069 'R-21 225 90 New 4.3.1-A6 Livin Mitchen Slab 252 6.730 None 0 180 New 4.4.7-A1 Livin %Kitchen Slab 58 0.736 None 0 180 New 4.4.7-A1 Livin /Kitchen Roof 349 0.026 R-38 0 20 New 4.2.1-A9 Living/Kitchen Wall 211 0.069 R-21 135 90 New 4.3.1-A6 Living/Kitchen Wall 146 0.069 R-21 225 90 New 4.3.1-A6 Living/Kitchen Wall 247 0.069 R-21 315 90 New 4.3.1-A6 Living/Kitchen Slab 59 0.730 None 0 180 1 New 4.4.7-A1 Living/Kitchen Slab 290 0.730 None 0 180 New 4.4.7-A1 Living/Kitchen Roof 860 0.026 R-38 6 20 New 4.2.1-A9 Guest House Wall 239 0.069 R-21 45 90 New 14.3.1-A6 Guest House Wall 371 0.069 R-21 135 90 New 14.3.1-A6 I Guest House Wall 239 0.069 R-21 225 90 New 14.3.1-A6 Guest House FENESTRATION SURFACE DETAILS ID Type Area Ll -Factor SHGC Azm Status Glazing Type Location/Comments 17 Window 24.0 0.380 NFRC 0.34 NFRC 315 New Fleetwood Window (Kona) Living/Kitchen 18 Window 54.0 0.380 NFRC 0.34 NFRC 315 New Fleetwood Window (Kona) Living/Kitchen 19 Window 11.3 0.380 NFRC 0.34 NFRC 315 New Fleetwood Window (Kona) Living/Kitchen 20 Window 12.0 0.380 NERC 0.34 NFRC 135 New Fleetwood Window (Kona) Living/Kitchen 21 Window 48.6 0.440 NFRC 0.30 NFRC 135 New Fleetwood Doors (Norwood) Living/Kitchen 22 Window 10.0 0.380 NFRC 0.34 NFRC 135 New Fleetwood Window (Kona) Living/Kitchen 23 Window 10.0 0.380 NFRC 0.34 NFRC 135 New Fleetwood Window (Kona) Living/Kitchen 24 Window 25.0 6.380 NFRC 6.34 NFRC 225 New Fleetwood Window (Kona) Living/Kitchen 25 Window 6.3 0.380 NFRC 0.34 NFRC 315 New Fleetwood Window (Kona) Living/Kitchen 26 Window 25.0 0.380 NFRC 0.34 NFRC 45 New Fleetwood Window (Kona) Guest House 27 Window 26.0 0.380 NFRC 0.34 NFRC 135 New Fleetwood Window (Kona) Guest House 28 Window 96.0 0.440 NFRC 0.30 NFRC 135 New Fleetwood Doors (Norwood) Guest House 29 Window 25.0 0.380 NFRC 0.34 NFRC 135 New Fleetwood Window (Kona) Guest House 30 Window 25.0 0.380 NFRC 0.34 NFRC 225 New Fleetwood Window (Kona) Guest House 31 Window 5.3 0.380 NFRC 0.34 NFRC 315 New Fleetwood Window (Kona) Guest House 32 Window 5.3 0.380 NFRC 0.34 NFRC 315 New I Fleetwood Window (Kona) Guest House (1) U -Factor Type: 116-A = Default Table from Standards, NFRC = Labeled Value 2 SHGC Type: 116-8 = Default Table from Standards, NFRC = Labeled Value EXTERIOR SHADING DETAILS ID Exterior Shade Type SHGC Window H t Wd Ove hanq Left Fin Len H t LExt RExt Dist Len I Ri ht Fin H t Dist Len H t 17 Bug Screen 0.76 18 Bug Screen 0.76 6.0 2.0 4.0 0.1 4.0 4.0 19 Bug Screen 0.76 20 Bug Screen 0.76 21 Bug Screen 0.76 22 Bug Screen 0.76 6.0 2.0 6.0 0.1 6.0 6.0 23 Bug Screen 0.76 24 Bug Screen 0.76 25 Bug Screen 0.76 26 Buo Screen 0.76 27 Bug Screen 0.76 28 Bug Screen 0.76 „ 29 Bu Screen 0.76 30 Bug Screen 0.76 1 A 73 n .0- 31 Bug Screen 0.76 r i 32 [Bug Screen 1 0.76 r+ DATF Ener Pro 5.1 by Ener Soft User Number: 6712 RunCode: 2013-104 :46 Pa e 9 of 31 • 0 Project Ahlering Residence■ 0 Single Family Multi Family ■ Addition Alone.. ■ .. i OPAQUE SURFACE DETAILS rim M, Joint Appendix 4 —Location/Comments EiQ7 I►�T������iQ� , . FENESTRATION ... . Default Table from Standards, Default Table from Standards, EXTERIOR Exterior Shade Type • • CERTIFICATE OF COMPLIANCE: Residential Part 5 of 5 CF -1 R Project Name Ahlering Residence Building Type D Single Family ❑ Addition Alone ❑ Multi Family ❑ Existing+ Addition/Alteration Date 110114120IJ BUILDING ZONE INFORMATION System Name Zone Name Floor Area ft New Existing Altered Removed Volume Year Built HVAC 1 Master Bedroom 842 10,357 HVAC 2 & 3 Living/Kitchen 2,547 43,299 Bedroom 2 310 3,410 Bedroom 3 349 3,839 HVAC 4 Guest 860 9,460 Totals 4,9081 01 01 0 HVAC SYSTEMS System Name Qty*Heating Type Min. Eff. Cooling Type Min. Eff. Thermostat Type Status HVAC 1 1 Split Heat Pump 9.50 HSPF Split Heat Pump 16.5 SEER Setback New HVAC 2 & 3 2 Split Heat Pump 9.50 HSPF Split Heat Pump 16.0 SEER Setback New HVAC 4 1 Split Heat Pump 10.00 HSPF Split Heat Pump 19.0 SEER Setback New HVAC DISTRIBUTION System Name Heating Duct Coolinq Duct Location R -Value Ducts Tested? Status HVAC 1 Ducted Ducted Attic, Ceiling In vented 8.0 m New HVAC 2 & 3 Ducted Ducted Attic, Ceiling Ins, vented 8.0 m New HVAC 4 Duc!ed Ducted Attic, Ceiling Ins, vented 8.0 New WATER HEATING SYSTEMS S stem Name Qty. Ty e Distribution Rated Input (Btu h) Tank Cap. al Energy Factor or RE Standby Loss or Pilot Ext. Tank Insul. R- Value Status Bradford -White #M -1-100T 1 Large Gas All Pipes Ins 85,000 100 0.80 0.00% n/a New MULTI -FAMILY WATER HEATING DETAILS HYDRONIC HEATING SYSTEM PIPING Control Hot Water Piping Length ft o .6 QIke 75 — tS stem Narne� t Pie Lent Pipe fialrteter, Insul. Thick. Qty. HP Plenum Outside Buried ❑N BIIII ,��;," �-' Ut V LA I ❑ I`ETY r A ❑ FOR ❑ V I r EnergyPro 5.1 by Ener Soft User Number: 6712 RunCode: 2013-10-1 16:3 :4 a e 11 of 31 17� 0 • MANDATORY MEASURES SUMMARY: Residential Pae 1 of 3 MF -1 R J Project Name %Ahlering Residence Date 11011412013 NOTE: Low-rise residential buildings subject to the Standards must comply with all applicable mandatory measures listed, regardless of g the compliance approach used. More stringent energy measures listed on the Certificate of Compliance (CF -1 R, CF -1 R -ADD, or CF - 1 R -ALT Form) shall supersede the items marked with an asterisk (*) below. This Mandatory Measures Summary shall be incorporated into the permit documents, and the applicable features shall be considered by all parties as minimum component performance specifications whether they are shown elsewhere in the documents or in this summary. Submit all applicable sections of the MF -1 R Form with plans. Building Envelope Measures: 116(a)l: Doors and windows between conditioned and unconditioned spaces are manufactured to limit air leakage. 7 §116(a)4: Fenestration products (except field -fabricated windows) have a label listing the certified U -Factor, certified Solar Heat Gain Coefficient SHGC , and infiltration that meets the requirements of 10-111 (a). 117: Exterior doors and windows are weather-stripped; all joints and penetrations are caulked and sealed. 118(a): Insulationspecified or installed meets Standards for Insulating Material. Indicate type and include on CF -619 Form. `C -§l 18(i): The thermal emittance and solar reflectance values of the cool roofing material meets the requirements of §118(1) when the installation of a Cool Roof is specified on the CF -1 R Form. f• '§1 50 a : Minimum R-19 insulation in wood -frame ceiling orequivalent U -factor. §150(b): Loose fill insulation shall conform with manufacturer's installed design labeled R -Value. P *§1 50 c : Minimum R-13 insulation in wood -frame wall orequivalent U -factor. *§1 50 d : Minimum R-13 insulation in raised wood -frame floor orequivalent U -factor. 150(f): Air retarding wrap is tested, labeled, and installed according to ASTM Ell 677-95(2000) when specified on the CF -1 R Form. 150 : Mandatory Vapor barrier installed in Climate Zones 14 or 16. §150(1): Water absorption rate for slab edge insulation material alone'without facings is no greater than 0.3%; water vapor permeance rate is no greater than 2.0 erm/inch and shall be protected from physical damage and UV light deterioration. Fire laces, Decorative Gas Appliances and Gas Log Measures: 150 a 1A: a onry or factory -built fireplaces have a closable metal or glass door covering the entire opening of the firebox. i §150(e)1 B: Masonry or factory -built fireplaces have a combustion outside air intake, which is at least six square inches in area and is F equipped with a with a readily accessible, operable, and tight -fitting damper and or a combustion -air control device. §150(e)2: Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of the building, are prohibited. ,-Space Conditionin , Water Heating and Plumbing System Measures: :.§l 10-§113: HVAC equipment, water heaters, showerheads, faucets and all other regulated appliances are certified by the Energy Commission. 1'§1 13(c)5: Water heating recirculation loops serving multiple dwelling units and High -Rise residential occupancies meet the air release valve, backflow prevention, pump isolation valve, and recirculation loop connection requirements of §113(c)5. §115: Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces, household cooking appliances (appliances with an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt), and pool and spa heaters. 150(h): Heating and/or cooling loads are calculated in accordance with ASHRAE, SMACNA or ACCA. 150(i): Heating systems are equipped with thermostats that meet the setback requirements of Section 112(c). 4 §150(j)1A: Storage gas water heaters rated with an Energy Factor no greater than the federal minimal standard are externally wrapped with insulation having an installed thermal resistance of R-12 or greater. §150(j)1 B: Unfired storage tanks, such as storage tanks or backup tanks for solar water -heating system, or other indirect hot water tanks have R-12 external insulation or R-16 internal insulation where the internal insulation R -value is indicated on the exterior of the tank. •§150(j)2: First 5 feet of hot and cold water pipes closest to water heater tank, non -recirculating systems, and entire length of -recirculating sections of hot water pipes are insulated per Standards Table 150-B. ` §1500)2: Cooling system piping (suction, chilled water, or brine lines),and piping insulated between heating source and indirect hot water tank shall be insulated to Table 150-B and Equation 150-A. §1500)2: Pipe insulation for steam hydronic heating systems or hot water systems >15 psi, meets the requirements of Standards Table 123-A. a n,150(j)3A: Insulation is protected from damage, includingthat due to sunlight, moisture(e u.ment,ma.nte bnd! wind- §1 500)3A: Insulation for chilled water piping and refrigerant suction lines includes a vapoyiretardana%s,enclosed a ti"rely irf� conditioned space. M JAl-L I DEPT, 1 50 ' 4: Solar water-heatingsystems and/or collectors are certified b the Solar Ratin and'CertificationCCo.r oration FUH CONSTRUCTION EnergyPro 5.1 by EnergySoft User Number, 6712 RunCode: 2013-10-14T18:35r_ ATE ND: Page 12 of 31 M MANDATORY MEASURES SUMMARY: Residential (Page 2 of 3 MF -1 R Project Name Date Ahlering Residence 11011412013 §150(m)1: All air -distribution system ducts and plenums installed, are sealed and insulated to meet the requirements of CMC Sections 601, 602, 603, 604, 605 and Standard 6-5; supply -air and return -air ducts and plenums are insulated to a minimum installed level of R- 4.2 or enclosed entirely in conditioned space. Openings shall be sealed with mastic, tape or other duct -closure system that meets the applicable requirements of UL 181, UL 181 A, or UL 181 B or aerosol sealant that meets the requirements of UL 723. If mastic or tape is used to seal openings reater than 1/4 inch, the combination of mastic and either mesh or tape shall be used §150(m)1: Building cavities, support platforms for air handlers, and plenums defined or constructed with materials other than sealed sheet metal, duct board or flexible duct shall not be used for conveying conditioned air. Building cavities and support platforms may contain ducts. Ducts installed in cavities and support platforms shall not be compressed to cause reductions in the cross-sectional area of the ducts. - § 150(m)2D: Joints and seams of duct systems and their components shall not be sealed with cloth back rubber adhesive duct tapes ,.unless such tape is used in combination with mastic and draw bands. 150(m)7: Exhaust fans stems have back draft or automatic dampers. §150(m)8: Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers. §150(m)9: Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind. Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that can cause degradation of the material. 150 m 10: Flexible ducts cannot have porous inner cores. §150(0): All dwelling units shall meet the requirements of ANSI/ASHRAE Standard 62.2-2007 Ventilation and Acceptable Indoor Air Quality in Low -Rise Residential Buildings. Window operation is not a permissible method of providing the Whole Building Ventilation required in Section 4 of that Standard. Pool and Spa Heating Systems and Equipment Measures: §114(a): Any pool or spa heating system shall be certified to have: a thermal efficiency that complies with the Appliance Efficiency Regulations; an on-off switch mounted outside of the heater; a permanent weatherproof plate or card with operating instructions; and shall not use electric resistance heating ora pilot light. §114(b)1: Any pool or spa heating equipment shall be installed with at least 36" of pipe between filter and heater, or dedicated suction and return lines, or b,uilt-up connections for future solar heating. 114(b)2: Outdoor pools ors as that have a heat pump or gas heater shall have a cover. §114(b)3: Pools shall have directional inlets that adequately mix the pool water, and a time switch that will allow all pumps to be set or programmed to run only during off-peak electric demand periods. 150 : Residential pool systems or equipment meet the pump sizing, flow rate, piping, filters, and valve requirements of §150 Residential Lighting Measures: §150(k)1: High efficacy luminaires or LED Light Engine with Integral Heat Sink has an efficacy that is no lower than the efficacies contained in Table 150-C and is not a low efficacy luminaire asspecified by §150(k)2. §150(k)3: The wattage of permanentl installed luminaires shall be determined asspecified by §130(d). §150(k)4: Ballasts for fluorescent lamps rated 13 Watts or greater shall be electronic and shall have an output frequency no less than 20 kHz. §150(k)5: Permanently installed night lights and night lights integral to a permanently installed luminaire or exhaust fan shall contain only high efficacy lamps meeting the minimum efficacies contained in Table 150-C and shall not contain a line -voltage socket or line - voltage lamp holder; OR shall be rated to consume no more than five watts of power as determined by §130(d), and shall not contain a medium screw -base socket. 150(k)6: Lighting integral to exhaust fans, in rooms other than kitchens, shall meet the applicable requirements of §150(k). §150(k)7: All switching devices and controls shall meet the requirements of §150(k)7 §150(k)8: A minimum of 50 percent of the total rated wattage of permanently installed lighting in kitchens shall be high efficacy. EXCEPTION: Up to 50 watts for dwelling units less than or equal to 2,500 ft2 or 100 watts for dwelling units larger than 2,500 ft2 may be exempt from the 50% high efficacy requirement when: all low efficacy luminaires in the kitchen are controlled by a manual on occupant sensor, dimmer, energy management system (EMCS), or a multi -scene programmable control system; and all permanently installed luminaries in garages, laundry rooms, closets greater than 70 square feet, and utility rooms are high efficacy and controlled by a manual -on occupant sensor. §150(k)9: Permanently installed lighting that is internal to cabinets shall use nom etha nf as`ipr�nearoot.of �JJL� illuminated cabinet. BUILDING & SAFETY DEPT. q f- K V'ED FOR CONSTRUCTION EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-10-14716:35:46 ID: qage 13 of 31 C • MANDATORY MEASURES SUMMARY: Residential (Page 3 of 3 MF -1 R Project Name Date Ahlering Residence 11011412013 §150(k)10: Permanently installed luminaires in bathrooms, attached and detached garages, laundry rooms, closets and utility rooms shall be high efficacy. EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by a manual -on occupant sensor certified to comply with the applicable requirements of §119. EXCEPTION 2: Permanently installed low efficacy luminaires in closets less than 70 square feet are not required to be controlled by a manual -on occupancy sensor. §150(k)11: Permanently iristalled luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, closets, and utility rooms shall be high efficacy luimnaires. EXCEPTION 1: Permanently installed low efficacy luminaires shall be allowed provided they are controlled by either a dimmer switch that complies with the applicable requirements of §119, or by a manual - on occupant sensor that complies with the applicable requirements of §119. EXCEPTION 2: Lighting in detached storage building less :'than 1000 square feet located on a residential site is not required to comply with §150 k 11. §150(k)12: Luminaires recessed into insulated ceilings shall be listed for zero clearance insulation contact (IC) by Underwriters Laboratories or other nationally recognized testing/rating laboratory; and have a label that certifies the lumiunaire is airtight with air leakage less then 2.0 CFM at 75 Pascals when tested in accordance with ASTM E283; and be sealed with a gasket or caulk between .the luminaire housing and ceiling. §150(k)13: Luminaires providing outdoor lighting, including lighting for private patios in low-rise residential buildings with four or more dwelling units, entrances, balconies, and porches, which are permanently mounted to a residential building or to other buildings on the same lot shall be high efficacy. EXCEPTION 1: Permanently installed outdoor low efficacy luminaires shall be allowed provided that they are controlled by a manual on/off switch, a motion sensor not having an override or bypass switch that disables the motion sensor, and one of the following controls: a photocontrol not having an override or bypass switch that disables the photocontrol; OR an astronomical time clock not having an override or bypass switch that disables the astronomical time clock; OR an energy management control system (EMCS) not having an override or bypass switch that allows the luminaire to be always on EXCEPTION 2: Outdoor luminaires used to comply with Exceptionl to §150(k)13 may be controlled by a temporary override switch which bypasses the motion sensing function provided that the motion sensor is automatically reactivated within six hours. EXCEPTION 3: Permanently installed luminaires in or around swimming pool, water features, or other location subject to Article 680 of the California Electric Code need not be high efficacy luminaires. ,§150(k)14: Internally illuminated address signs shall comply with Section 148; OR not contain a screw -base socket, and consume no more than five watts of power as determined according to §130(d). .§150(k)l5: Lighting for parking lots and carports with a total of for 8 or more vehicles per site shall comply with the applicable requirements in Sections 130, 132, 134, and 147. Lighting for parking garages for 8 or more vehicles shall comply with the applicable requirements of Sections 130, 131, 134, and 146. §150(k)16: Permanently installed lighting in the enclosed, non -dwelling spaces of low-rise residential buildings with four or more dwelling units shall be high efficacy luminaires. EXCEPTION: Permanently installed low efficacy luminaires shall be allowed provided that they are controlled by an occupant sensors certified to comply with the applicable requirements of 119. CIT' OF LA QUINTA BUILDING & SAFETY DEPT. APS -)ROVED FOR CONSTRUCTION DATE EnergyPro 5.1 by EnergySoR User Number: 6712 RunCode: 2013-10-14T16 35:46-=—___J ; age 14 of 31 112/78°F — 0 Outside Air 0 cfm 70 / 58 OF 1. • EnergyPro 5.1 ETICS (Airstream Temperatures at Time of Coolinq Peak 70/58°F 51 /50°F 51 /50°F Cooling Coil Supply Fan CITY ^ F LA */50 F1,600 cfm �}a�j3UILDING R.�4as��FE FiO,,�"` P-DRODY/ _� F User Number: 6712 RunCode: 2013-10-14 Pace 15 of 31 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY •Project Name Ahlering Residence Date 10/14/2013 System Name HVAC 1 Floor Area 842 ENGINEERING CHECKS SYSTEM LOAD i Number of Systems 1 COIL COOLING CFM Sensible Total Room Loads 624 12,515 Return Vented Lighting 0 Return Air Ducts 722 Return Fan 0 Ventilation o 0 Supply Fan 0 Supply Air Ducts 722 TOTAL SYSTEM LOAD 1 13,960 PEAK COIL HTG. PEAK Heating System Latent CFM Sensible Output perSystem 48,000 1,476 743 13,438 Total Output Btuh 48,000 Output Btuh/s ft 57.0 514 Cooling System 0 Output perSystem 47,000 0 0 0 Total Output Btuh 47,000 1,476 0 Total Output ons 3.9 514 Total Output Btuh/s ft 55.8 Total Output s ft/Ton 215.0 14,466 Air System CFM perSystem 1,600 HVAC EQUIPMENT SELECTION Airflow cfm 1,600 Carrier 25HNB948/FE4ANB006 33,558 3,908 29,979 Airflow cfm/s ft 1.90 Alrflow cfm/Ton 408.5 Outside Air % 0.0% Total Adjusted System Output 1 33,558 3,908 1 29,979 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK Aug 3 PM Jan 1 AM Outside Air cfm/s ft 0.00 values above given at ARI conditions •Note: HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26 OF 72 OF 89 OF ^� 89 OF Outside Air 10 Nil 0 cfm Heating Coil Supply Fan 89 OF 1,600 cfm ROOM I 72 OF 72 OF 112/78°F — 0 Outside Air 0 cfm 70 / 58 OF 1. • EnergyPro 5.1 ETICS (Airstream Temperatures at Time of Coolinq Peak 70/58°F 51 /50°F 51 /50°F Cooling Coil Supply Fan CITY ^ F LA */50 F1,600 cfm �}a�j3UILDING R.�4as��FE FiO,,�"` P-DRODY/ _� F User Number: 6712 RunCode: 2013-10-14 Pace 15 of 31 0 C� J • HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Ahlering Residence Date 10/14/2013 System Name HVAC 2 & 3 Floor Area 3,206 ENGINEERING CHECKS SYSTEM LOAD Number of Systems 2 COIL CFM Total Room Loads 2,905 Return Vented Lighting Return Air Ducts Return Fan Ventilation 0 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COOLING PEAK COIL HTG. PEAK Heating $ stem Sensible Latent CFM Sensible Output per System 58,500 43,877 4,097 3,002 55,630 Total out ut Btuh 117,000 0 Output Btuh/s ft 36.5 2,533 2,127 Cooling System 0 0 Output per System 55,500 0 0 0 0 Total Output Btuh 111,000 5,291 21533 54,234 4,097 -5,291 Total Output ons 9.3 2,127 Total Output Btuh/s ft 34.6 Total Output s ft/Ton 346.6 54,593 "Air System CFM per System 2,000 HVAC EQUIPMENT SELECTION Airflow cfm 4,000 Carrier 25HNB960/FE4ANB006 70,765 20,258 73;075 Airflow cfm/s ft 1.25 Total Adjusted System Output 1 70,765 20,258 1 73,075 (Adjusted for Peak Design conditions) TIME OF SYSTEM PEAK Aug 3 PM I F Jan 1 AM Airflow cfm/Ton 432.4 Outside Air % 0.0 % Outside Air cfm/s ft 0.00 Note: values above given at ARI conditions 7 HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26 OF Outside Air 0 cfm 72 OF 72 OF 89 OF 90 OF Nil Heating Coil Supply Fan 89 OF 4,000 cfm ROOM 72 OF COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 112/78°F Outside Air 0 cfm 71/60°F 71 /60°F 54/53°F 55/54°F � © _ Supply Fan OF LA QUINTA/ 4°F Cooling Coil 4,000 cfm GUILD NIS & SAF' T. OOYO P=AP If'"" 1A FOR CONSTRUCTION 70/ 0 °F DATE BY EnergyPro 5.1 by EnergySoft User Number. 6712 RunCode: 2013-10-14716:35:46 ID: ge 16 of 31 • • HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY Project Name Ahlering Residence Date 10/14/2013 System Name HVAC 4 Floor Area 860 .ENGINEERING CHECKS SYSTEM LOAD Number of Systems 1 Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING CFM Sensible 534 11,847 0 684 0 0 0 0 684 1 13,215 PEAK COIL HTG. PEAK Heating System Latent CFM Sensible Output perSystem 37,400 1,099 875 16,138 Total Output Btuh 37,400 Output Btuh/s ft 43.5 617 Cooling System 0 Out ut perSystem 36,600 0 0 0 Total Output Btuh 36,600 1,099 0 Total Output ons 3.1 617 Total Output Btuh/s ft 42.6 Total Output s ft/Ton 282.0 1 17,372 "Air S stem CFM perSystem 1,200 HVAC EQUIPMENT SELECTION Airflow cfm 1,200 Carrier 25HNB936/FE4ANB006 27,979 755 23,359 Airflow cfm/s ft 1.40 Airflow cfm/Ton 393.4 Total Adjusted System Output (Adjusted for Peak Design conditions) I TIME OF SYSTEM PEAK 27,979 755 1 23,359 Aug 3 PM Jan 1 AM Outside Air % 0.0% Outside Air cfm/s ft 0.00 Note:'values above given at ARI conditions HEATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26 OF Outside Air 0 cfm 72 OF 72 OF 90 OF 90 OF Heating Coil Supply Fan 1,200 cfm 89 °F VROOM 'I 72 OF COOLING SYSTEM PSYCHROMETICS Airstream Temperatures at Time of Cooling Peak 112 / 78 °F Outside Air Ar 0 cfm 71 / 57 OF 4 71 / 57 OF 49148 OF 49148 OF Cooling Coil Supply Fan 01 1,200 cfm CITY OF LA (...�.�- BUILDING 8x 8rk E I T ut= M-� ROVED 7015 OF J EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-10-14T16:35:461-' C —1q: - P-4 17 of 31 • • • ROOM LOAD SUMMARY Project Name Ahlering Residence Date 10/14/2013 System Name HVAC 1 Floor Area ' 842 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK Zone Name Room Name Mult. CFM Sensible Latent CFM Sensible Latent CFM Sensible Master Sedroom Master Bedroom 1 624 12,515 1,476 624 12,515 1,476 743 13,438 Ir r �uri�V oc TFtMY ' Total includes ventilation load for zonal systems. PAGE TOTAL F sr�ai Cp;?L►��� Fil1 �'r * TOTAL1 624 12, 515 1,4761 DATE 7431 7431 1 13,438 1 13,438 Ener Pro 5.1 by EnerqySoft User Number: 6712 —— D RunCode: 2013-10-14T16:3t.48 —— a 18 of 31 • • • ROOM LOAD SUMMARY Project Name Ahlering Residence Date 10/14/2013 System Name HVAC 2 & 3 Floor Area 3,206 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLINGPEAK COIL HTG. PEAK Zone Name Room Name Mult. CFM Sensible Latent CFM Sensible Latent CFM Sensible Living/Kitchen Living/Kitchen 1 2,418 36,516 3,255 2,418 36,516 3,255 2,434 45,089 Bedroom 2 1 225 3,396 396 225 3,396 396 235 4,357 Bedroom 3 1 263 3,965 446 263 3,965 446 334 6,184 BlJILDI t ,�� A _., R, Total includes ventilation load for zonal systems. PAGE TOTA TOTAL* DAT�— I ,M(5 2,905 �40iT 43,877 BY U4,0� 4,097 3,002 1 55,630 3,002 55,630 Ener Pro 5.1 by Ener Soft User Number: 6712 RunCode: 2013-10-14T16:35:46 Pae 19 of 31 • Cl J ROOM LOAD SUMMARY Project Name Date Ahlering Residence 10/14/2013 System Name Floor Area HVAC 4 860 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL FITG. PEAK Zone Name Room Name Mult. CFM I Sensible I Latent CFM I Sensible I Latent CFM I Sensible Guest House Guest 1 1 5341 11,8471 1,099 5341 11,8471 1,0991 8751 16,138 PAGE TOTAL TOTAL' 534 � 1.1x84•• X1,099 • 75 16,138 534 11,847 1,099 875 16,138 9 • ROOM HEATING PEAK LOADS Project Name71011412013 Ahlering Residence ate ROOM INFORMATION DESIGN CONDITIONS Room Name Master Bedroom Floor Area 842.0 ft' Indoor Dry Bulb Temperature 72 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area U -Value 842.0 X 0.0260 881.0 X 0.0690 12.0 X 0.3800 240.0 X 0.4400 perim = 71.0 X 0.7300 X X X X X X X X X X X X X X X X X X X X X X X X X X through an interior surface to another room X 842 X 12.30 X �,0.258r,,1/1600,1 Area Ceiling Height AC AT °F Btu/hr X 46 = 1,007 X 46 = 2, 796 X 46 = 210 X 46 = 4,858 X 46 = 2,384 X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = X = Page Total 11,255 ®� _1 183 c, l e y & vH1'T pEpT !�� F' O V ]qrP-' D ' C'1M"1 "^ALJ R-38 Roof(R.38.2x14.16) R-21 Wall (W. 19.2x6.16) Fleetwood Window (Kona) Fleetwood Doors (Norwood) Slab -On -Grade Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X 1.064 Schedule Air Sensible Fraction TOTAL HOURLY HEAT LOSS FOR ROOM I HUCTION 13 438 QATF 107-11 EnergyPro 5.1 by EnergySoft User Number. 6712 RunCode: 2013-10-14T16.35:4.6 !D.' —51— aae 2 • • • ROOM HEATING PEAK LOADS Project Name71011412013 Ahlering Residence ate ROOM INFORMATION DESIGN CONDITIONS Room Name Living/Kitchen Floor Area 2,547.0 ft' Indoor Dry Bulb Temperature 72 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area U -Value X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 8's ,..P AT OF Btu/hr R-38 Roof(R.38.2x14.16) 2,547.0 X 0.0260 46 = = = = 3,046 R-21 Wall (W. 19.2x6.16) 2,738.7 X 0.0690 46 8,693 Wood Door 48.0 X 0.5000 46 1,104 Fleetwood Doors (Norwood) 680.2 X X 0.4400 46 13,767 Fleetwood Window (Kona) 149.1 0.3800 46 = = = 2,606 Slab -On -Grade perim = 276.0 X X 0.7300 46 9,268 X X X X = = = = X X X X X = = = = = = = = X X X X = X = = X X X = = X = X = = X X = X = = X X to another room 17.00 X_'��0 Ceiling Height OLACH-ANG = Page Total /-6Ui LX U4. & SAFETY DEPT. rr� 0 V F dUONST Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X 1.064 Schedule Air Sensible Fraction through an interior surface X 2,547 X Area 38,484 �= 6,604 TOTAL HOURLY HEAT LOSS FOR ROOM I ruhi 1 5,089 _ 1,2 EnergyPro 5.1 by EnergySoft User Number: 6712 Run Code: 2013-10-14T16:35;46-'— ~ID ---__ BY Page of 31 • • ROOM HEATING PEAK LOADS Project Name71011412013 Ahlering Residence ate ROOM INFORMATION DESIGN CONDITIONS Room Name Bedroom 2 Floor Area 3 10. 0 ft' Indoor Dry Bulb Temperature 72 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X to U -Value X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 2 9 AT °F Btu/hr R-38 Roof(R. 38.2x 14.16) 310.0 0.0260 46 = 371 R-21 Wall (W. 19.2x6.16) 292.0 0.0690 46 = 927 Fleetwood Window (Kona) 12.0 0.3800 46 = 210 Fleetwood Doors (Norwood) 48.0 0.4400 46 = 972 Slab -On -Grade perim = 32.0 0.7300 46 = 1,075 = = = = = = = = = = = = = = = = = = = = = = = = = = Page Total r/Q6U Di •�� T IN SAFETY DEPT Items shown with an asterisk (') denote conduction Infiltration: 1.00 )( 1.064 Schedule Air Sensible Fraction through an interior surface X 310 X Area another room 11.0 / 3,553 — 804 TA Ceiling Heig BufALC�f NCS TOTAL HOURLY HEAT LOSS FOR ROOM f=ns, ® ffaQ)-v 1z 4,357, STRuCT1ON EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-10-14T16:P6-4f ID: Pa 23 of 31 • • • ROOM HEATING PEAK LOADS Project Name Ahlering Residence Date 10/14/2013 ROOM INFORMATION DESIGN CONDITIONS Room Name Bedroom 3 Floor Area 349.0 ft' Indoor Dry Bulb Temperature 72 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X to U -Value AT °F 0.0260 X 46 0.0690 X 46 0.3800 X 46 0.7300 X 46 X X X X X X X X X X X X X X X X X X X X X X X X X X X another room Page Total 11.00 rX 0. 891—/ 60�], � �id ' eigf$DI/wF�� & SAFE 1La7 SE DEPT. = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = Btu/hr R-38 Roof(R.38.2x 14.16) 349.0 417 R-21 Wall (W. 19.2x6.16) 603.7 1,916 Fleetwood Window (Kona) 51.3 897 Slab -On -Grade perm = 61.0 2,048 Items shown with an asterisk (') denote conduction Infiltration:[ 1.00 X 1.064 Schedule Air Sensible Fraction through an interior surface X 349 X Area 5,279 — 905 /► Ceiling TOTAL HOURLY HEAT LOSS FOR ROOM -OR°, ° � It 6,184 t'UC-FION EnergyPro 5.1 by EnergySoR User Number., 6712 RunCode: 2013-10-1 1 :'35:46 /D: Page 24 of 31 • • ROOM HEATING PEAK LOADS Project Name Ahlering Residence Date 10/14/2013 ROOM INFORMATION DESIGN CONDITIONS Room Name Guest Floor Area 860.0 ft' Indoor Dry Bulb Temperature 72 OF Time of Peak Jan 1 AM Outdoor Dry Bulb Temperature 26 OF Conduction Area R-38 Roof(R. 38.2x 14.16) 860.0 R-21 Wall (W.19.2x6.16) 1,355.4 Fleetwood Window (Kona) 110.6 Fleetwood Doors (Norwood) 96.0 Slab -On -Grade perim = 140.0 Items shown with an asterisk (') denote conduction through an interior surface Infiltration:[ 1.00 X 1.064 X 860 X Schedule Air Sensible Area Fraction X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X to U -Value X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X )R H NG AT OF = = = = = = = - = = = = = = = = = = = = Btu/hr 0.0260 46 1,029 0.0690 46 4,302 0.3800 46 1,933 0.4400 46 1,943 0.7300 46 4,701 another room 1 .Ob��VR r°Q�2�9 HeighlBUfLL I Page Total ]�, X 1 p�I & SAFETY DEPT, 13,908 2,230 Ceiling TOTAL HOURLY HEAT LOSS FOR ROOM", `-' �- 16,138 „r lUlq EnergyPro 5.1 by EnergySoft User Number: 6712 RunCode: 2013-10-14T1 _ :33:48 ID: P ge 25 of 31 9 C C7 RESIDENTIAL ROOM COOLING LOAD SUMMARY Project NameDate Ahlering Residence 10/14/2013 ROOM INFORMATION DESIGN CONDITIONS Room Name Master Bedroom Outdoor Dry Bulb Temperature 112 OF Floor Area 842.0 ft2 Outdoor Wet Bulb Temperature 78 OF Indoor Dry Bulb Temperature 70 OF I Outdoor Daily Range: 34 OF Opaque Surfaces Orientation Area U -Factor CLTD' Btu/hr R-38 Roof(R.38.2x 14.16) (N) 842.0 X 0.0260 X 56.0 = 1,226 R-21 Wall (W. 19.2x6.16) (N) 22.0 X 0.0690 X 23.0 = 35 R-21 Wall (W. 19.2x6.16) (SE) 453.0 X 0.0690 X 31.0 = 969 R-21 Wall (W.19.2x6.16) (SK9 I 216.0 X 0.0690 X 31.0 = 462 R-21 Wall (W.19.2x6.16) (NM 190.0 X 0.0690 X 30.2 = 396 X X = X X = X X = X X = Page Total 3,066 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF Btu/hr D (SE) 0.0 X 20.2 + 12.0 X 28.0 = 337 9 (SE) 0.0 X 19.9 + 48.0 X 26.8 = 1,288 10 (SW) 0.0 X 19.9 + 96.0 X 26.8 = 2,576 11 (NIA9 0.0 X 19.9 + 96.0 X 29.6 = 2,840 X + X = X + X = X + X - X + X = X +1 X - Page Total 7,041 Internal Gain Btu/hr Occupants 2.0 Occupants X 230 Btuh/occ. = 460 E ui ment 0.0 Dwelling Unit X 1,600 Btu = 0 Infiltration: 1.064 X 0.94 X 46.07 X 42 = 1,926 Air Sensible CFM ELA 4T TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 12,515 Latent Gain Btu/hr Occupants 2.0 Occupants X _200 Btu�h/,occc. = 400 Infiltration: 4,771 -r X 0.94 X 46.07 X 0.005 3 TY OF `-' ` Q= 1 f� 1,076 Air Sensible CFM ELA AW -JILDIiVG &SAFETY DEPT. TOTAL HOURLY LATENT HEAT GAIN FOR ROOM !' ,� p "I Z 1,476 Ener Pro 5.1 by Ener Soft User Number- 6712 Run Code: 2013-10-14.T16:35:46 ID: a e 26 of 31 RESIDENTIAL ROOM COOLING LOAD SUMMARY •Project Name Ahlering Residence ROOM INFORMATION DESIGN CONDITIONS Room Name Living/Kitchen Outdoor Dry Bulb Temperature Floor Area 2,547.0 ft2 Outdoor Wet Bulb Temperature Indoor Dry Bulb Temperature 70 OF Outdoor Dailv Ranae: • R-38 Roof(R. 38.2x 14.16) R-21 Wall (W. 19.2x6.16) Wood Door R-21 Wall (W. 19.2x6.16) R-21 Wall (W. 19.2x6.16) R-21 Wall (W. 19.2x6.16) Orientation (N) (NE) (NE) (SE) (SW) (Nle Date 10/14/2013 Area X X X X X X X X X U -Factor X X X X X X X X X CLTD' = = = = = = = = = 2,547.0 0.0260 56.0 1,094.9 0.0690 29.0 48.0 0.5000 29.0 720.0 0.0690 31.0 591.1 0.0690 31.0 332.7 0.0690 30.2 0.0 19.9 108.0 29.6 0.0 20.2 8.3 31.2 400.0 19.9 0.0 Page Total Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration 2 W 1 v 18 U 13 X Y Internal Gain Orientation 112 OF 78 OF 34 OF Btu/hr 3,708 2,191 696 1,540 1,264 694 1 10,0941 Area X X X X X X X X X GLF + + + + + + + + + Area X X X X X X X X X GLF = = = = m = = = = 0.0 19.9 108.0 29.6 0.0 20.2 8.3 31.2 0.0 19.9 40.2 29.6 0.0 20.2 8.3 31.2 0.0 19.9 108.0 29.6 0.0 20.2 8.3 31.2 400.0 19.9 0.0 26.8 0.0 20.2 8.3 28.0 0.01 20.2 8.3 28.0 Occupants X 230 Btuh/occ. 0.0 Dwelling Unit X 1,600 Btu Infiltration: 1.064 X 0.94 X 139.37 X 42 = Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM Latent Gain Occupants 0.0 Occupants X Infiltration: 4,771 X 0.94 X 139.37 X C Air Sensible CFM ELA M • TOTAL HOURLY FOR Page Total 4u�,1 is1 focc. _ ITY OF Ua QUINTA fILDING & SAFETY DEPT. Btu/hr 3,195 259 1,189 259 3,195 259 7,973 233 16,792 Btu/hr 0 0 5,826 36,516 Btu/hr 0 I 3,255 • 0 RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date Ahlering Residence 1 10/14/2013 ROOM INFORMATION DESIGN CONDITIONS Room Name Living/Kitchen Outdoor Dry Bulb Temperature 112 OF Floor Area 2,547.0 ft' Outdoor Wet Bulb Temperature 78 OF Indoor Dry Bulb Temperature 70 OF Outdoor Daily Range: 34 OF Opaque Surfaces Orientation Area U -Factor CLTD' Btu/hr X X = X X = X X = X X = X X = X X = X X = X X = X X = Page Total o Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF Btu/hr Z (SM 0.0 X 20.2 + 8.3 X 28.0 = 233 14 (SIM 24.0 X 19.9 + 0.0 X 26.8 = 478 F (NK9 0.0 X 20.2 + 10.0 X 31.2 = 312 12 (NIM 0.0 X 20.2 + 24.0 X 31.2 = 748 E (NlM 0.0 X 20.2 + 54.0 X 31.2 = 1,682 K (NIM 0.0 X 20.2 + 11.3 X 31.2 = 352 X + X = X + X = X + I X = Page Total 3,804 Internal Gain Btu/hr Occupants 0.0 Occupants X 230 Btuh/occ. = 0 Equipment 0.0 Dwelling Unit X 1,600 Btu = 0 Infiltration: 1.064 X 0.94 X 139.37 X 42 = 5,826 Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 36,516 Latent Gain Btu/hr Occupants 0.0 Occupants X �` 200+ g�h/�ccu . A QUIN 0 Infiltration: 4,771 X 0.94 X 139.37 X 0.00523 BUILDING & SAFETY DE T. 3,255 Air Sensible CFM ELA AW /'KaP>f PROVED �a."!� FOR TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 3,2 .5 Ener Pro 5.1 by Ener Soft User Number 6712 RunCode: 2013-10-14T16:3e. 6 C --49.-- Paq428 28 of 31 4 1 • f C] • • RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name Date Ahlering Residence 1 10/14/2013 ROOM INFORMATION DESIGN CONDITIONS Room Name Bedroom 2 Outdoor Dry Bulb Temperature 112 OF Floor Area 310.0 ft' Outdoor Wet Bulb Temperature 78 OF Indoor Dry Bulb Temperature 70 OF I Outdoor Daily Range: 34 OF Opaque Surfaces Orientation Area U -Factor CLTD' Btu/hr R-38 Roof(R.38.2x14.16) (N) 310.0 X 0.0260 X 56.0 = 451 R-21 Wall (W. 19.2x6.16) (NE) 99.0 X 0.0690 X 29.0 = 198 R-21 Wall (W. 19.2x6.16) (SE) 171.0 X 0.0690 X 31.0 = 366 R-21 Wall (W. 19.2x6.16) (Sly 22.0 X 0.0690 X 31.0 = 47 X X = X X = X X = X X = X X = Page Total 1,062 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF Btu/hr C (SE) 0.0 X 20.2 + 12.0 X 28.0 = 337 8 (SE) 0.0 X 19.9 + 48.0 X 26.8 = 1,288 X + X X + X - X + X - X + X X + X - X + X - X + X - Page Total 1,625 Internal Gain Btu/hr Occupants 0.0 Occupants X 230 Btuh/occ. = 0 E ui ment 0.0 Dwelling Unit X 1,600 Btu = 0 Infiltration: 1.094 X 0.94 X 16.96 X 42 = 709 Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 3,396 Latent Gain Btu/hr Occu ants 0.0 Occupants X r-�°---- 20.0_ Btub CITY ®F LInfiltration: 4,771 X o.s4 X 19.99 X 0.005 GILDING & SAAir Sensible CFM ELA AW�yTOTAL nT HOURLY LATENT HEAT GAIN FOR ROOM FOR Ene Pro 5.1 b Ener Soft User Number: 6712 RunCode: 2013-10-14 16:35:46 ID: BL- 0 L] RESIDENTIAL ROOM COOLING LOAD SUMMARY Project Name71011412013 ate Ahlering Residence ROOM INFORMATION DESIGN CONDITIONS Room Name Bedroom 3 Outdoor Dry Bulb Temperature 112 OF Floor Area 349.0 ft' Outdoor Wet Bulb Temperature 78 OF Indoor Dry Bulb Temperature 70 OF I Outdoor Daily Range: 34 OF Opaque Surfaces Orientation Area U -Factor CLTD' Btu/hr R-38 Roof(R. 38.2x 14.16) (N) 349.0 X 0.0260 X 56.0 = 508 R-21 Wall (W. 19.2x6.16) (SE) 211.0 X 0.0690 X 31.0 = 451 R-21 Wall (W. 19.2x6.16) (SW) 146.0 X 0.0690 X 31.0 = 312 R-21 Wall (W. 19.2x6.16) (NIA9 246.7 X 0.0690 X 30.2 = 515 X X = X X = X X = X X = X J X = Page Total 1,786 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF Btu/hr G (SE) 10.0 X 20.2 + 0.0 X 28.0 = 202 H (SE) 0.0 X 20.2 + 10.0 X 28.0 = 280 1 (SM 0.0 X 20.2 + 25.0 X 28.0 = 701 J (NlM 0.0 X 20.2 + 6.3 X 31.2 = 196 X + X - X + X - X + X - X +X - X + X - Page Total 1,380 Internal Gain Btu/hr Occupants 0.0 Occupants X 230 Btuh/occ. = 0 Equipment 0.0 Dwelling Unit X 1,600 Btu = 0 Infiltration: 1.064 X 0.94 X 19.10 X 42 = 798 Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 3,965 Latent Gain Btu/hr Occupants 0.0 Occupants X 200 At"h/,p - 0 rITY OF LA QUINT Infiltration: 4,771 52 X o.s4 X 1s.10 X o.00,P,VILDING 446 &SAFETY DEPT. Air Sensible CFM ELA OW APPROVED TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 446 EnemvPro 5.1 by Ener Soft User Number: 6712 RunCode: 2013-10-14T 6:35:46 ID: Pabe 30 of 31 I DAT t BY I 0 1 W f .0 • • RESIDENTIAL ROOM COOLING LOAD SUMMARY Project NameDate Ahlering Residence 10/14/2013 ROOM INFORMATION DESIGN CONDITIONS Room Name Guest Outdoor Dry Bulb Temperature 112 OF Floor Area 860.0 f 2 Outdoor Wet Bulb Temperature 78 OF Indoor Dry Bulb Temperature 70 OFI Outdoor Daily Range: 34 OF Opaque Surfaces Orientation Area U -Factor CLTD' Btu/hr R-38 Roof(R. 38.2x 14.16) (N) 860.0 X 0.0260 X 56.0 = 1,252 R-21 Wall (W.19.2x6.16) (NE) 239.0 X 0.0690 X 29.0 = 478 R-21 Wall (W. 19.2x6.16) (SE) 371.0 X 0.0690 X 31.0 = 794 R-21 Wall (W.19.2x6.16) (StM 239.0 X 0.0690 X 31.0 = 511 R-21 Wall (W.19.2x6.16) (NW) 506.4 X 0.0690 X 30.2 = 1,056 X X = X X = X X = X J X I= Page Total 4,092 Items shown with an asterisk (') denote conduction through an interior surface to another room. 1. Cooling Load Temperature Difference (CLTD) Shaded Unshaded Fenestration Orientation Area GLF Area GLF Btu/hr O (NE) 0.0 X 20.2 + 25.0 X 31.2 = 779 P (SE) 0.0 X 20.2 + 25.0 X 28.0 = 701 19 (SE) 0.0 X 19.9 + 96.0 X 26.8 = 2,576 Q (SE) 0.0 X 20.2 + 25.0 X 28.0 = 701 R (SlM 0.0 X 20.2 + 25.0 X 28.0 = 701 S (NW) 0.0 X 20.2 + 5.3 X 31.2 = 165 T (NM 0.0 X 20.2 + 5.3 X 31.2 = 165 X + X = X + X = Page Total 5, 789 Internal Gain Btu/hr Occupants 0.0 Occupants X 230 Btuh/occ. = L-A Equipment 0.0 Dwelling Unit X 1,600 Btu = Infiltration: 1.064 X 0.94 X 47.06 X 42 = 1,967 Air Sensible CFM ELA AT TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 11,847 Latent Gain Btu/hr Occupants 0-0 Occupants x200'-Biuh Y �'` LA QLJI 0 NIA Infiltration: 4,771 X o.sa X 47.os X 0.00523 _ BUILDING & SAFETYEPT- 1, 99 Air Sensible CFM ELA AWAP O® pE D �J P ROVED TOTAL HOURLY LATENT HEAT GAIN FOR ROOM �' I 1M11 Ener Pro 5.1 b Ene Soft User Number: 6712 RunCode: 2013-10-14716:35:46 B: Page 31 0