09-1142 (RC) Title 24I TITLE 24 REPORT " - I Title 24 Report for: DRMC OUTPATIENT IMAGIN 47-CALEO BAY, SUITE 100 LA QUINTA, CA 92253 � r�c�r2ae� D DEC -4 209 Project Designer: CHRISTOPHER S. MILLS 490 SOUTH FARRELL DRIVE SUITE C-203 PALM SPRINGS, CA 92262 760-320-1790 Report Prepared By: VICTOR LEON MRC Engineering, Inc. 72-880 Fred Waring Drive Suite C-11 Palm Desert, CA 92260 (760) 340-9005 CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTI®N, DATE 4:46:7- Job Number: Date: 10/16/2009 '/� Ir The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC - www.energysoft.com. EnergyPro 4.4 by EnergySoft Job Number: 09P004.00 User Number: 7746 74,47 tk /60 �� % �TABLE OF CONTENTS f Cover Page Table of Contents Nonresidential Performance Title 24 Forms Form ENV -MM Envelope Mandatory Measures Form LTG -MM Lighting Mandatory Measures Form MECH-MM Mechanical Mandatory Measures 1 2 3 18 19 20 EnergyPro 4.4 by EnergySoft Job Number: 09P004.00 User Number: 7746 PERFORMANCE CERTIFICATE OF COMPLIANCE Pala 1 of 3 PERF -1 PROJECT NAME This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the DATE DRMC OUTPATIENT IMAGING DATE OF PLANS 4/20/2009 10/16/2009 PROJECT ADDRESS VICTOR LEON ­ 47-CALEO BAY, SUITE 100 LA QUINTA Ej HIGH RISE RESIDENTIAL E] HOTEL/MOTEL GUEST ROOM PRINCIPAL DESIGNER - ENVELOPE TELEPHONE Building Permit # CHRISTOPHER S. MILLS 760-320-1790 ; DOCUMENTATION AUTHOR TELEPHONE Ched by/Date eck MRC Engineering, Inc. (760) 340-9005 Eniorcement Agency Use GENERAL INFORMATION This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation preparer hereby certifies that the documentation is accurate and c9qnplete. DATE OF PLANS 4/20/2009 BUILDING CONDITIONED FLOOR AREA 5,407 Sq.Ft. VICTOR LEON CLIMATE ZONE 15 BUILDING TYPE ® NONRESIDENTIAL Ej HIGH RISE RESIDENTIAL E] HOTEL/MOTEL GUEST ROOM PHASE OF CONSTRUCTION NEW CONSTRUCTION ❑ ADDITION ® EXISTING + ADDITION/ALTERATION STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation preparer hereby certifies that the documentation is accurate and c9qnplete. DOCUMENTATION AUTHOR SIGNATURE DATE VICTOR LEON of 11 The Principal Designer hereby certifys that the proposed building de ' n represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116, through 118, and 140, 142, 143 or 149 of Title 24, Part 6. ENV. LTG. MECH. NX jeKk 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect. ❑ 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. F1 R F-1 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.) ENVELOPE COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures ENV -1 R orms PRINCIPAL ENVELOPE DESIGNER - NAME SIGN E LIC. NO. JDATE CHRISTOPHER S. MILLS C, 0 - • OJ LIGHTING COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures LTG -1, LTG -2 Required Forms PRINCIPAL LIGHTING DESIGNER - NAME RANDALL V. MOSS SIGNATURELIC. NO. v_ io jA DATE 12- MECHANICAL COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures ECH-1 MECH-2 MECH-3 MECH-5 Required Forms PRINCIPAL MECHANICAL DESIGNER - NAMENATURE LIC. NO. DATE JIM O' CONNOR 11,z?m&a �- 4555 11,2111,Oq Run Initiation 11:51:06 Run Code: 1255719066 EnergyPro 4.4 by Energysoft User Number: 7746 Job Number: 09P004.00 Page:3 of 21 { PERFORMANCE -CERTIFICATE OF COMPLIANCE Part2 of 3 PE PROJECT NAME DATE DRMC OUTPATIENT IMAGING 10/16/2009 ANNUAL TDV ENERGY USE SUMMARY kBtu/s ft- r Standard Proposed Conditioned Floor Area Unconditioned Floor Area Conditioned Footprint Area Fuel Type Compliance ` ENERGY COMPONENT Design Design 1 (® Standard �Pmpoaed" MarginM. Space Heating 4.64 0.16 . 5,407 4.48 Space Cooling 237.08 105.86 174 131.22 Indoor Fans, 58.87 71.21 116 -12.34 1n°""F Heat Rejection 0.00 0.00 r k. 0.00 Pumps & Misc. 0.00 0.00 [::::::]4 0.00 Domestic Hot Water 4.72 4.72 > 0 0.00 9, °H Lighting 72.02 77.43 g -5.41sw Receptacle 71.70 71.70 0.00owl Process o.00 o.00 ' o.00 °°°°A � � 60.2 140 t80�`180 200 220 '8kew�r�yv TOTALS: 449.02 331.08 117.95 0 20 40 0�e80� 100%120 ` Percent better than Standard: 26.3% ( 26.3% excluding process) BUILDING COMPLIES GENERAL INFORMATION Building Orientation Number of Stories Number of Systems Number of Zones w 270 deg Conditioned Floor Area Unconditioned Floor Area Conditioned Footprint Area Fuel Type 5,407 sgft. sgft. sgft. 1 0 7 5,407 71 Natural Gas 174 16.9% Orientation Front Elevation w Left Elevation (N Rear Elevation E Right Elevation . (S Total Roofsgft. Gross Area sgft. sgft. sgft. sgft. sqn. Glazing Area Glazing sgft. sqn. sgft. sgft. sgft. sgft. Ratio 460 174 37.8% 920 174 16.9% 886 116 13.1% 1 70 0.0% 2,336 [::::::]4 > 0 O.o% 1 Standard Proposed Lighting Power Density 1.086 w/sgft. 1.167 w/sgft.' Prescriptive Env. Heat Loss 407 Btu/h 351 Btu/h Prescriptive Env. Heat Gain 42,623 Btu/h-F 39,522 Btu/h-F Remarks: Run Initiation Time: 10/1610911:51:06 Run Code: 1255719066 EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page:4 of 21 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1 PROJECT NAME DRMC OUTPATIENT IMAGING DATE 10/16/2009 ZONE INFORMATION System Name Zone Name Occupancy Type Floor Area (sgft.) Inst. LPD (Wlsf)1 Ctrl. Credits (W/sf)2 Allowed LPD Area Tailored Wls 3 Is 4 Proc. Loads (Wlsf) DSI IT ROOM All Others 156 0.59 FC -6 FC -6 Comp Bldg Medical and Clinic 400 0.00 FC -5 FC -5 Comp Bldg Medical and Clinic 180 1.55 FC -4 FC -4 Comp Bldg Medical and Clinic 629 1.79 FC -3 FC -3 Comp Bldg Medical and Clinic 2,362 1.09 FC -2 FC -2 Comp Bldg Medical and Clinic 9541 0.90 FC -1 FC -1 Comp Bldg Medical and Clinic 726 1.86 Notes: 1. See LTG -2-C (items marked with asterisk, see LTG -2 -C by others) 2. See LTG -4-C 3. See LTG -5-C (by others) 4. See LTG -6-C Items above require special documentation EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. The HVAC System "Carrier 38AUZ07: Premium Eff' 1.50 BHP Supply Fan Motor has been specified. The HVAC System "Sanyo 12 XS71: Premium Eff' 0.25 BHP Supply Fan Motor has been specified. The HVAC System "DSI" includes credit for verified adequate airflow. A certified HERS rater must diagnostically measure the airflow. The HVAC System "DSI" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve. The HVAC System "FC -6" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A. The HVAC System "FC -6" includes credit for verified adequate airflow. A certified HERS rater must diagnostically measure the airflow. The HVAC System "FC -6" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve. The HVAC System "FC -5" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A. The HVAC System "FC -5" includes credit for verified adequate airflow. A certified HERS rater must diagnostically measure the airflow. The HVAC System "FC -4" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A. The HVAC System "FC -4" includes credit for verified adequate airflow. A certified HERS rater must diagnostically measure the airflow. The HVAC System "FC -4" incorporates a HERS verified Refrigerant Char - e test or a HERS verified Thermostatic Expansion Valve. The HVAC System "FC -3" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A. The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant. Authorized Signature or EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page:5 of 21 1 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1 PROJECT NAME DRMC OUTPATIENT IMAGING DATE 10/16/2009 ZONE INFORMATION System Name Zone Name Occupancy Type Floor Inst. Area LPD (sgft.) (Wisf)1 Ctrl. Allowed LPD Credits Area Tailored (Wlsf� Wl 3 Wls 4 Proc. Loads (Wlsf) Notes: 1. See LTG -2-C 2. See LTG -4-C 3. See LTG -5-C (items marked with asterisk, see LTG -2 -C by others) (by others) 4. See LTG -6-C Items above require special documentation EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. The HVAC System "FC -3" includes credit for verified adequate airflow. A certified HERS rater must diagnostically measure the airflow. The HVAC System "FC -3" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve. The HVAC System "FC -2" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A. The HVAC System "FC -2" includes credit for verified adequate airflow. A certified HERS rater must diagnostically measure the airflow. The HVAC System "FC -2" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve. The HVAC System "FC -1" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A. The HVAC System "FC -1" includes credit for verified adequate airflow. A certified HERS rater must diagnostically measure the airflow. The HVAC System "FC -1" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve. The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant. EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 0913004.00 Page:6 of 21 1 CERTIFICATE OF COMPLIANCE ENV -1-C PROJECT NAME DATE DRMC OUTPATIENT IMAGING 10/16/2009 OPAQUE SURFACES # Surface Type Area U -Fac. Insulation Cay. Cont. Act. Am. Tilt Cond: Status Joint Appendix IV Reference Location / Comments 1 Wall 33C 0.074 R-13 R-4.5 0 90 Altered 09-A3 E=13 -D5 FC -6 2 Wall 11 0.074 R-13 R-4.5 0 90 Altered 09-A3 E=13 -D5 FC -5 3 Door 2 0.500 Insul R-0.0 0 90 Existing 28-A3 FC -5 4 Wall 7Q 0.074 1 R-13 R-4.5 180 90 Altered 09-A3 E=13 -D5 FC -4 5 lWall 1 284 0.074 R-13 R-4.5 90 90 Altered 09-A3 E=13 -D5 FC -4 6 Wall 50 0.074 R-13 R-4.5 90 90 Altered 09-A3 E=13 -D5 FC -3 7 Wall 43 0.074 R-13 R-4.5 90 90 Altered 09-A3 E=13 -D5 FC -3 8 Wall 12 0.074 R-13 R-4.5 270 90 Altered 09-A3 E=13 -D5 FC -2 9 Wall 27 0.074 R-13 R-4.5 0 90 Altered 09-A3 E=13 -D5 FC -1 10 Wall 16 0.074 R-13 R-4.51 270 90 Altered 09-A3 E=13 -D5 FC -1 A. R (New, Existing, Altered, More than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default Ll -factors from Standards Table 116-A and B. Certificate shall be filed in the contractor's project office during construction and in the building manager's office after construction # T e ## Exterior Shade Type Window Overhang Left Fin Right Fin SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t. Area U -Fac' SHGC2 Act. Am. Cond. Stat. Glazinq Type Location/ Comments 1 Window Rear E 116 0.460 NFRC 0.40 INFRIC 90 Existing Interpane INE -177 FC -4 2 Window Front W 58 0.460 NFRC 0.40 NFRC 270 New Interpane INE -177 FC -2 3 Window Left N 174 0.460 NFRC 0.40 NFRC 0 New Interpane INE -177 FC -1 4 Window Front W 116 0.460 NFRC 0.40 NFRC 270 New Interpane INE -177 FC -1 (1) LI -factor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value. 2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING ## Exterior Shade Type Window Overhang Left Fin Right Fin SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t. 1 Roll -down Blind or Slats 0.13 2 Roll -down Blind or Slats 0.13 3 Roll -down Blind or Slats 0.13 4 Roll -down Blind or Slats 0.13 MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES ❑The proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a calling height greater than 15 feet, and an LPD for general lighting of at least 0.5 Wtft2. See Section 143(c). If this box is checked, ENV4-C must be filled out. when submitting under the Prescriptive Compliance Approach. EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page:7 of 21 1 CERTIFICATE OF COMPLIANCE (Part 1 of 3) LTG -1-C (PROJECT NAME DATE f DRMC OUTPATIENT IMAGING 10/16/2009 INSTALLED INDOOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES INSTALLED WATTS INSTALLED LIGHTING, CONDITIONED SPACES (From LTG -2-C) 6,309 PORTABLE LIGHTING (From LTG -3-C) 0 LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG -4-C) 0 CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 6,309 INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0 LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) 0 UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0 ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES ❑ COMPLETE BUILDING METHOD (From LTG -5-C) ALLOWED ❑ AREA CATEGORY METHOD (From LTG -5-C) WATTS ❑ TAILORED METHOD (From LTG -5-C) ALLOWED LIGHTING POWER 6,309 IIALTERNATE COMPLIANCE ❑X PERFORMANCE METHOD ❑ COMMMON LIGHTING SYSTEM (From LTG -8-C) ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C) o MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS CONTROL LOCATI (Room #) CONTROL IDENTIFICATION CONTROL TYPE (Auto Time Switch, Dimming, etc.) Check if SPACE CONTROLLED Daylighting Run Initiation Time: 10/16/09 11:51:06 Run Code: 1255719066 EnergyPro 4.4 by Energysoft User Number: 7746 Job Number: 09P004.00 Page:8 of 21 CERTIFICATE OF COMPLIANCE (Part 3 of 3) LTG - PROJECT NAME DRMC OUTPATIENT IMAGING DATE 10/16/2009 Designer: This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for lighting systems. The designer is required to check the boxes by all acceptance tests that apply and list all equipment that require an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Building Departments: Before an occupancy permit is granted for a newly constructed building or space, or a new lighting system system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate of Acceptance, LTG -1-A, Forms shall be submitted to the building department that: A. Certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of§10-103(b) and Title 24 Part 6. Test Description Test Performed BY: ❑ LTG -2-A: Lighting Control Acceptance Document - Occupancy Sensor Acceptance - Manual Daylight Controls Acceptance - Automatic Time Switch Control Acceptance Equipment requiring acceptance testing ❑ LTG -3-A: Automatic Daylighting Controls Acceptance Document Equipment requiring acceptance testing EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page:9 of 21 1 CERTIFICATE OF COMPLIANCE MECH-1-C PROJECT NAME DATE DRMC OUTPATIENT IMAGING 1 10/16/2009 ueslgner: This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Building Departments: SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate of Acceptance, MECH-1-A Form shall be submitted to the building department that certifies plans, specifications, installation certificates, and operatinq and maintenance information meet the reauirements of Section 10-103(b) and Title 24 Part 6. STATEMENT OF COMPLIANCE ❑ MECH-2-A: Ventilation System Acceptance Document -Variable Air Volume Systems Outdoor Air Acceptance -Constant Air Volume Systems Outdoor Air Acceptance Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. ❑ MECH-3-A: Packaged HVAC Systems Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. ❑ MECH-4-A: Air -Side Economizer Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the commission do not require equipment testing but do require construction inspection. ❑ MECH-5-A: Air Distribution Acceptance Document Equipment requiring acceptance testing This test required If the unit serves 5,000 V of space or less and 25% or more of the ducts are in noncondilioned or semiconditioned space like an attic New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or replace the packaged unit. ❑ MECH-6-A: Demand Control Ventilation Acceptance Document Equipment requiring acceptance testing All new DCV controls installed on new or existing packaged systems must be tested. ❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document Equipment requiring acceptance testing All new VAV fan volume controls installed on new or existirg systems must be tested ❑ MECH-8-A: -Hydronic System Control Acceptance Document -Variable Flow Controls Applies to chilled and hot water systems. -Automatic Isolation Controls Applies to new boilers and chillers and the primarypumps are connected to a common header. -Supply Water Temperature Reset Controls. Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500, 000 atu/hr. -Water-loop Heat Pump Controls Applies to all new waledoop heat pump systems where the combined loop pumps are greater than 5 hp. -Variable Frequency Controls Applies to all new distribution pumps on new variable /low chilled, hydronic heat pump or condenser water systems where the pumps motors are greater than 5 hp. Equipment requiring acceptance testing EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page:10 of 21 INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG -2-C PROJECT NAME DATE DRMC OUTPATIENT IMAGING 1 10/16/2009 INSTALLED LIGHTING POWER FOR CONDITIONED SPACES Luminaire Lamps/Ballasts Installed Watts C D E F G H I J Name Type Description r vM CD -0 33c �vQ ANN a m `� ° r� °'gid N cdc �•»v N��N .� m `� ° c �•m°' fD Cn dm J r 3 c 503 N ��0 wd vNfD d A (1) 42w Compact Fluorescent Trip/Quad 4 in Elec CFTR42WGX24 -4 11 42 1.0 46.0 X 1 46 B (1) 42w Compact Fluorescent Trip/Quad a in Elec 1 42 1.0 46.0 X 17 782 C 50w Low Voltage Halogen Mag 0 Waft Lamp 1 50 1.0 55.0 X 2 110 1 �1lec Compact Fluorescent Triple 4 Pin FTR32WGX24 -3 1 32 1.0 35.0 X 9 315 FD2 (2) 26w Compact Fluorescent Triple 4 Pin Elec 2 26 1.0 55.0 X 4 220 (3) 2 ft Fluorescent T8 Elec 3 36 1,908 F (3) 2 ft Fluorescent T8 Elec 7T8 3 17 1.0 53.0 X 15 795 G (3) 4 ft Fluorescent T8 Rapid Start Elec 3 19 1 767 K (( P ) 40w Lng Cmpt T5 Fluorescent Twin T40W/2G11 1 40 1.0 41.0 X 3 123 L (1) 21w Linear Fluorescent T5 Elec 1 21 1:0 27.0 X 9 243 PAGE TOTAL 6,309 BUILDING TOTAL (sum of all pages) 6,309 PORTABLE LIGHTING (From LTG -3-C) CONTROL CREDIT (From LTG -4-C) O . ADJUSTED ACTUAL WATTS 6 309 Run Initiation Time: 10/16/0911:51:06 Run Code: 1255719066 EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 0913004.00 Page: 11 of 21 AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C PROJECT NAME DATE DRMC OUTPATIENT IMAGING 10/16/2009 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance AIR SYSTEMS, Central or Single Zone DSI FC -6 FC -5 1 1 1 Reference on Plans or Specification t 112(a) n/a 7.70 HSPF 7.80 HSPF 112(a) 16.0 SEER / 11.8 EER 13.0 SEER / 11.0 EER 10.0 EER 112 b n/a Yes Yes 112(c), 115(a) n/a n/a n/a 121(b) Yes Yes Yes 121 b 13 cfm 33 cfm 15 cfm 121(c) No No No 121 c No No No 121(c), 122(e) Pro rammable Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Auto Auto Auto 122(g) n/a n/a n/a 123 124 n/a R-8.0 R-8.0 144 (a& b n/a n/a n/a 144 a & b 0 btuh 15,427 btuh 0 btuh 144 a & b n/a n/a n/a 144 a & b 9,621 btuh 18,537 btuh 57,860 btuh 144 c Constant Volume Constant Volume Constant Volume 144 c 144 c Yes Yes Yes 144 d No No No 144 a No Economizer No Economizer No Economizer 144 Constant TernD Constant Temp Constant Tem 144 (f) Constant Temp Constant Temp Constant Temp 144 k No No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF -1 for performance method duct sealing requirements. Run Initiation Time: 10/16/09 11:51:06 Run Code: 1255719066 EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page:12 of 21 AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C (PROJECT NAME DATE DRMC OUTPATIENT IMAGING 10/16/2009 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance AIR SYSTEMS, Central or Single Zone FC -4 FC -3 FC -2 1 1 1 Reference on Plans or Specification 1 112(a) 7.70 HSPF 7.70 HSPF 7.70 HSPF 112(a) 13.0 SEER / 11.0 EER 13.0 SEER / 11.0 EER 13.0 SEER / 11.0 EER 112(b) Yes Yes Yes 112(c), 115(a) n/a n/a n/a 121(b) Yes Yes Yes 121 b 52 cfm 200 cfm 100 cfm 121(c) No No No 121 c No No No 121(c), 122(e) Programmable Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Auto Auto Auto 122 n/a n/a n/a 123 124 R-8.0 R-8.0 R-8.0 144 a & b n/a n/a n/a 144 a & b 19,986 btuh 34,352 btuh 17,988 btuh 144 a & b n/a n/a n/a 144 a & b 23,597 btuh 40,065 btuh 20,359 btuh 144 c Constant Volume Constant Volume Constant Volume 144 c 144 c Yes Yes Yes 144 d No No No 144 a No Economizer No Economizer No Economizer 144 Constant Temp Constant Temp Constant Tem 144 (f) Constant Temp Constant Temp Constant Temp 144 k No No No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF -1 for performance method duct sealing requirements. EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page: 13 of 21 1 AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C PROJECT NAME DATE DRMC OUTPATIENT IMAGING 710/16/2009 71 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous HeatlCool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance AIR SYSTEMS, Central or Single Zone FC -1 1 Reference on Plans or Specification t 112(a) 7.70 HSPF 112(a) 13.0 SEER / 11.0 EER 112 b Yes 112 c,115a n/a 121(b) Yes 121(b) 60 cfm 121 c No 121 c No 121(c). 122(e). Programmable Switch 122(e) Heating & Cooling Required 122 Auto 122 n/a 123 124 R-8.0 144 a & b n/a 144 a & b 28,481 btuh 144 a & b n/a 144 a & b 38,719 btuh 144 c Constant Volume 144 c 144 c Yes 144 d No 144 a No Economizer 144 Constant Tem 144 (f) Constant Temp 144 k No 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF -1 for performance method duct sealing requirements. EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page:14 of 21 MECHANICAL VENTILATION MECH-3-C PROJECT NAME DATE DRMC OUTPATIENT IMAGING I 10/16/2009 PRESCRIPTIVE REHEAT LIMITATION Section 144(d)) MECHANICAL VENTILATION Section 121 b 2 AREA BASIS OCCUPANCY BASIS VAV MINIMUM A B C D E F G H I J K L M N ZONE/SYSTEM o D° a — m= o c dvn m°m . 3 c c3 ao�e� x Dn 3 -0 ®� cQ v W 0 v °ten u�m'+ 0. 3 �`3 m0� xe, c n lu 3— m p3D 0�' C D �p T..y 3• 3� n®o mN 3 C p v y. Top 3 x a s x °c3 w3m o°x 0 N o T? m0=2 $ 0 3 d a, V D IT ROOM 156 0.15 23 23 13 10 DSI I I Total 1 23 131 1 FC -6 40C 0.15 60 60 33 1 1 27 FC -6 Total 60 33 FC -5 18C 0.15 27 27 15 12 FC -5 Total 27 15 FC -4 629 0.15 94 94 52 42 FC -4 Total 94 52 FC -3 2,362 0.15 354 354 200 154 FC -3 Total 354 200 FC -2 954 0.15 143 143 100 43 FC -2 Total 143 100 FC -1 726 0.15 109 109 60 48 FC -1 Total 109 60 C Minimum ventilation rate per Section 121 Table 121-A E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load fore Tess purposes fors aces without fixed seating. H Required Ventilation Air REQ'D V.A, is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G). I Must be greater than orequal to H or use Transfer Air column N to make up the difference. J Design fan supply cfrn (Fan CFM) x 30%; or K Condition area (ft. sq.) x 04 cfm/R. sq.; or L Maximum of Columns H, J, K, or 300 cfm M IThis must be less than or equal to Column L and greater that orequal to the sum of Columns H + N. N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M. EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page: 15 of 21 MECHANICAL EQUIPMENT DETAILS Part 1 of 2 MECH-5-C PROJECT NAME DRMC OUTPATIENT IMAGING DATE 10/16/2009 C ILL R AND TOWER SUMMARY System Type Distribution Type Efficiency [Tons PUMPS Condition Status Ext. R -Val. Equipment Name Equipment Type Qty. Tot. Qty GPM BHP Motor Eff. Drive Eff. Pump Control MULTI -FAMILY CENTRAL WATER HEATING DETAILS Hot Water P mp Hot Water Piping Len th ft Control # HP Type In Plenum Outside Buried Add 1/2" Insulation 1DHW/ BOILER SUMMARY Energy Factor or RE Standby Loss or Pilot TANK INSUL. System Name System Type Distribution Type Qty Rated Input Vol. (Gals.) Condition Status Ext. R -Val. MULTI -FAMILY CENTRAL WATER HEATING DETAILS Hot Water P mp Hot Water Piping Len th ft Control # HP Type In Plenum Outside Buried Add 1/2" Insulation CENTRAL SYSTEM RATINGS HEATING COOLING System Name System Tvve Qtv1 Output Aux. kW Eff. Out ut Efficiency Condition Status Economizer Type Sanyo 12 XS71 Split DX 1 0 0.0 n/a 12,00016.0 SEER / 11.8 EER New No Economizer Carrier 38QRRRO24 --- 3 w/ FX4CO24 Split DX 1 24,700 0.0 7.70 HSPF 24,000 13.0 SEER / 11.0 EER New No Economizer Carrier 38AUZ07 Packaged DX 1 0 0.0 7.80 HSPF 71,000 10.0 EER New No Economizer Carrier 38QRR036-3/5/6 40QAE036 Split DX 1 1 32,000 0.0 7.70 HSPF 33,000 13.0 SEER / 11.0 EER New No Economizer Carrier 38QRR060-3/5/6 40QAE060 Split DX 1 55,000 0.0 7.70 HSPF 56,000 13.0 SEER / 11.0 EER New No Economizer Carrier 38QRRO30 --- 3 w/ 40QAE036 Split DX 1 28,800 0.0 7.70 HSPF 28,00013.0 SEER / 11.0 EER New No Economizer Carrier 38QRRR048 --- 3 w/ FX4C048 S lit DX p 1 45,6001 0.0 7.70 HSPF 49,000 13.0 SEER / 11.0 EER New No Economizer CENTRAL SYSTEM FAN SUMMARY SUPPLY FAN RETURN FAN System Name Fan Type Motor Location CFM BHP Motor Eff. Drive Eff. CFM I BHP Motor Eff. Drive Eff. Sanyo 12 XS71 Constant Volume Blow -Through 235 0.25 64.0% 97.0% none Carrier 38QRRRO24 --- 3 w/ FX4CO24 Constant Volume Blow -Through 792 0.33 64.0% 97.0% none Carrier 38AUZ07 Constant Volume Draw -Through 2,400 1.50 86.5% 97.0% none Carrier 38QRR036-3/5/6 40QAE036 Constant Volume Draw -Through 1,200 0.16 55.0% 97.0% none Carrier 38QRR060-3/5/6 40QAE060 Constant Volume Draw -Through 2,000 0.33 66.0% 97.0% none Carrier 38QRRO30 --- 3 w/ 40QAE036 Constant Volume Draw -Through 1,000 0.161 55.0%1 97.0%1 none Carrier 38QRRRO48 --- 3 w/ FX4C048 Constant Volume Blow -Through 1,669 0.75 77.0% 97.0% none Run Initiation Time, 10116109 11,51:06 Run Code; 1255719066 EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page: 16 of 21 MECHANICAL EQUIPMENT DETAILS Part 2 of 2 MECH-5-CI ENVELOPE MANDATORY MEASURES ENV -MM PROJECT NAME DATE DRMC OUTPATIENT IMAGING 1 10/16/2009 DESCRIPTION Desi ner Enforcement NXI §i18(a) Installed Insulating Material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20, Chapter 4, Article 3. §118(c) All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. X] § 117(a) All Exterior Joints and openings in the building that are observable sources of. air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. X] § 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors). § 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not exceeding those shown in Table Number 1-E. of the Standards. Manufactured fenestration products must be labeled for U -value according to NFRC procedures. X❑ § 118(e) Demising Walls in Nonresidential Buildings: The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value of no less than R-13 between framing members. EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page: 18 of 21 [LIGHTING MANDATORY MEASURES LTG -MM PROJECT NAME DATE DRMC OUTPATIENT IMAGING 10/16/2009 DESCRIPTION Designer Enforcement ❑X § 131(d)1 For every floor, all interior lighting systems shall be equipped with a separate automatic control to shut off the lighting. This automatic control shall meet the requirements of Section 119 and may be an occupancy sensor, automatic time switch, or other device capable of automatically shutting off the lighting. R § 131(d)2 Override for Building Lighting Shut-off: The automatic building shut-off system is provided with a manual, accessible override switch in sight of the lights. The area of override is not to exceed 5,000 square feet. X❑ § 119(h) Automatic Control Devices Certified: All automatic control devices specified are certified, all alternate equipment shall be certified and installed as directed by the manufacturer. § 111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for the project are certified and listed in the Directory. All installed fixtures shall be certified. RI § 131(a) Individual Room/Area Controls: Each room and area in this building is equipped with a separate switch or occupancy sensor device for each area with floor -to -ceiling walls. § 131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100 square feet and more than 0.8 wafts per square foot of lighting load shall be controlled with bi-level switching for uniform reduction of lighting within the room. ❑ § 131(c) Daylight Area Control: All rooms with windows and skylights that are greater than 250 square feet and that allow for the effective use of daylight in the area shall have 50% of the lamps in each daylit area controlled by a separate switch; or the effective use of daylight cannot be accomplished because the windows are continuously shaded by a building on the adjacent lot. Diagram of shading during different times of the year is included on plans. § 131(e) Display Lighting. Display lighting shall be separately switched on circuits that are 20 amps or less. EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page: 19 of 21 MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM (PROJECT NAME DATE DRMC OUTPATIENT IMAGING 1 10/16/2009 DESCRIPTION Designer Enforcement Equipment and Systems Efficiencies X❑ §11 Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply with the applicable standard. §115(a) Fan type central furnaces shall not have a pilot light. 0 §123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC equipment, shall be insulated in accordance with Standards Section 123. §124 Air handling duct systems shall be installed and insulated in compliance with Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards. Controls §g22(e) Each space conditioning system shall be installed with one of the following: n§122(e)1A Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not explicitly exempt from the requirements of Section 112 (d)) shall be installed with an automatic time switch with an accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch shall be capable of programming different schedules for weekdays and weekends and have program backup capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power is interrupted; or rXJ §122(e)1g An occupancy sensor to control the operating period of the system; or F] §122(e)1C A 4 -hour timer that can be manually operated to control the operating period of the system. X❑ §122(e)2 Each space conditioning system shall be installed with controls that temporarily restart and temporarily operate the system as required to maintain a setback heating and/or a setup cooling thermostat setpoint. §122(g) Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000 square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided with isolation devices, such as valves or dampers, that allow the supply of heating or cooling to be setback or shut off independently of other isolation areas; and shall be controlled by a time control device as described above. ® §122(a&b) Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or reduced to a minimum. X] §122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to authorized personnel. Fiv §112(b) Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the heating load can be met by the heat pump alone. EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page:20 of 21 IMEi,'HANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM PROJECT NAME DATE DRMC OUTPATIENT IMAGING 1 10/16/2009 Description Designer Enforcement Ventilation §121(e) Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified on these plans. §122(f) Gravity or automatic dampers interlocked and closed on fan shutdown shall be provided on the outside air intakes and discharges of all space conditioning and exhaust systems. §4 22(f) All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers in all openings to the outside, except for combustion air openings. 0 §121(f)1 Air Balancing: The system shall be balanced in accordance with the National Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or Associated Air Balance Council (AABC) National Standards (1989); or a9121 (f)2 Outside Air Certification: The system shall provide the minimum outside air as shown on the mechanical drawings, and shall be measured and certified by the installing licensed C-20 mechanical contractor and certified by (1) the design mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) the person with overall responsibility for the design of the ventilation system; or F] §121(f)3 Outside Air Measurement: The system shall be equipped with a calibrated local or remote device capable of measuring the quantity of outside air on a continuous basis and displaying that quantity on a readily accessible display divice; or §121(04 Another method approved by the Commission. Service Water Heating Systems §113(b)2 If a circulating hot water system is installed, it shall have a control capable of automatically turning off the circulating pump(s) when hot water is not required. §113(c) Lavatories in restrooms of public facilities shall be equipped with controls to limit the outlet temperature to 110 degrees F. EnergyPro 4.4 by EnergySoft User Number: 7746 Job Number: 09P004.00 Page:21 of 21