09-0708 (RC) Title 24h I TITLE 24 REPORT I
Title 24 Report for:
Dr. Nash -Tenant Improvement
47-647 Caleo Bay, Suite 240
La Quinta, Ca 92253
Project Designer:
Candice Noto Designs
74-830 Velie Way, Suite A
Palm Desert, Ca 92260
(760) 880-3016
Report Prepared By:
Tim Scott
Scott Design & Title 24
77085 Michigan Dr.
Palm Desert, CA 92211
(760) 200-4780
CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
APPROVED
Job Number: FOR CONSTRUCTION
DATE
Date: o MA TI ZD
10/15/2009
EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
orized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
I EnergyPro 4.4 by EnergySoft Job Number: User Number: 6712
11
1PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1
PROJECT NAME DATE
Dr. Nash -Tenant Improvement 10/15/2009
OJECT ADDRESS
47-647 Caleo Bay, Suite 240 La Quinta
PRINCIPAL DESIGNER - ENVELOPE TELEPHONE Building Permit #
Candice Noto Designs (760) 880-3016
DOCUMENTATION AUTHOR TELEPHONE Checked by/Date
Scott Design & Title 24 (760) 200-4780 Enforcement Agency Use
GENERAL INFORMATION
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is ac urate an,# complete.
DOCUMENTATION AUTHOR
DATE OF PLANS
DAT
Tim Scott
BUILDING CONDITIONED FLOOR AREA
2,063Sq.Ft.
The Principal Designer hereby certifys that the proposed building design represented in this set of construction docume is is
CLIMATE ZONE
15
BUILDING TYPE
(�C
NONRESIDENTIAL HIGH RISE RESIDENTIAL
HOTEL/MOTEL GUEST ROOM
PHASE OF CONSTRUCTION
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
NEW CONSTRUCTION F—] ADDITION
5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
EXISTING + ADDITION/ALTERATION
I'
L
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is ac urate an,# complete.
DOCUMENTATION AUTHOR
SIGNA,
DAT
Tim Scott
_Vo
The Principal Designer hereby certifys that the proposed building design represented in this set of construction docume is is
consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this
permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116,
through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
ENV. LTG. MECH.
F] ❑ ❑ 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
0 ❑ 2.1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section
5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
❑ F] ❑ 3.1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in
full in the Nonresidential Manual.)
ENVELOPE COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
Envelope Compliance Not In The Scope Of
IS Submittal
Required Forms
PRINCIPAL ENVELOPE DESIGNER - NAME
SIGNATURE LIC. NO.
DATE
LIGHTING COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
LTG -1, LTG -2, LTG -4
Required Forms
PRINCIPAL LIGHTING DESIGNER - NAME
SIGNATU
LIC. NO. DATE
Candice Noto Designs
Z
MECHANICAL COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
ECH-1, MECH-2 MECH-3 MECH-5
Requi ed Forms
PRINCIPAL MECHANICAL DESIGNER - NAME
SI RE
LIC. NO.
DAT
Scott Design and Title 24 Inc
/(� iJ 0
L
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:3 of 26
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 PERF -1
PROJECT NAME DATE
Dr. Nash -Tenant Improvement 10/15/2009
ANNUAL TDV ENERGY USE SUMMARY kl3tu/s ft- r
ENERGY COMPONENT
Standard
Design
Proposed Compliance
Design Margin
0.64 0.21
238.24 52.25
80.04 -4.64
0.00 0:00
0.00 0.00
18.54 -0.25
90.82 -11.21
91.54 0.00
0.00 0.00
519.82 36.36
6.5% . (. 6.5%° excl
Space Heating
Space Cooling'
Indoor Fans
Heat Rejection
Pumps & Misc.
Domestic Hot Water
Lighting
Receptacle
Process
TOTALS:
Percent better than Standard:
0.85
290.49
75.40
0.00
0.00
18.29
79.61
91.64
o.o0
556.17
BUILDING COMPL
GENERAL INFORMATION.
process)
Building Orientation
Number of Stories
Number of Systems
Number of Zones
w 270 de'
Conditioned Floor Area 2,063 sqft.
Unconditioned Floor Area 0 sqft.
Conditioned Footprint Area ` 2,063 sqft.
Fuel Type Natural Gas .
1
2
1
Front Elevation
Standard Proposed
Lighting Power Density 1.200 wisgft. 1.369 wisgft.
Prescriptive Env. Heat Loss 487 Btu/h, 602 Btu/h
Prescriptive Env. Heat Gain 39,054 etum-F 52,839 Btu/h-F
Remarks:
Run Initiation Time: 10/15/09 09:22:53 Run Code: 1255623773
EnergyPro 4.4 by EnergySoft User Number. 6712 Job Number: Page:4 of 26
Orientation
Gross Area
Glazing Area
Glazing Ratio
Front Elevation
(w)
o
sqft.
0
sqft.
0.0%
Left'Elevation
(N)
20
sqft.
0
sqft.
0.0%
Rear Elevation
(E)
480
sqft.
204
sqft.
42.5%
Right Elevation
Total
Roof
(S)
20
520
2,os3
sqft.
sqft.204
sqft.
o
�
SO'
sqft.
sqft.
0.0%
0.0%
Standard Proposed
Lighting Power Density 1.200 wisgft. 1.369 wisgft.
Prescriptive Env. Heat Loss 487 Btu/h, 602 Btu/h
Prescriptive Env. Heat Gain 39,054 etum-F 52,839 Btu/h-F
Remarks:
Run Initiation Time: 10/15/09 09:22:53 Run Code: 1255623773
EnergyPro 4.4 by EnergySoft User Number. 6712 Job Number: Page:4 of 26
4
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1
PROJECT NAME
Dr. Nash -Tenant Improvement
DATE
10/15/2009
ONE INFORMATION
System Name Zone Name Occupancy Type
Floor Inst.
Area LPD
(sgft.) (W/sf)1
Ctrl. Allowed LPD
Credits Area Tailored
(W/sf)2 (W/S3 W/s 4
Proc.
Loads
(W/Sq
5 Ton units Tenant improvement Office
2,063 1.57
0.203
Notes: ls:otes:1. See LTG -2-C 2. See LTG -4-C 3. See LTG -5-C 4. See LTG -6-C
(items marked with asterisk, see LTG -2 -C by others) (by others)
Items above require special documentation
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification
and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
submitted.
IThe HVAC System "Carrier 50HJD006" is desiqnated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement. I
The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and
Documentation for their use have been provided by the applicant.
uthorized Siqnature or Stamp
I Enerovloro 4.4 by EnerovSoft User Number: 6712 Job Number: Page:5 of 26 1
CERTIFICATE OF COMPLIANCE (Part 1 of 3) LTG -1 -C
ECT NAME DATE
Dr. Nash -Tenant Improvement 10/15/2009
ALLED INDOOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES
INSTALLED
WATTS
INSTALLED LIGHTING, CONDITIONED SPACES (From LTG -2-C) 3,242
PORTABLE LIGHTING (From LTG -3-C) 0
LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG -4-C) 418
CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 2 824
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) 0
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (From LTG -5-C)
ALLOWED
AREA CATEGORY METHOD (From LTG -5-C)
WATTS
TAILORED METHOD (From LTG -5-C) ALLOWED LIGHTING POWER
2,824
ALTERNATE COMPLIANCE
77771
•] PERFORMANCE METHOD
n COMMMON LIGHTING SYSTEM (From LTG -8-C)
ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C)
0
MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS
CONTROL LOCATION CONTROL CONTROL TYPE Check if NOTE TO
(Room #) IDENTIFICATION (Auto Time Switch, Dimming, etc.) SPACE CONTROLLED Daylighting FIELD
J44L,kC L OCA,-,- w► w &.3
® UE &VA'KOILSLS 17�4
NOTFR TC) FIFI Il _ Fnr Rnilrlinn hanartmant I Ica Only
Run Initiation Time: 10/15/09 09:22:53 Run Code: 1255623773
EnergvPro 4.4 by Energvsoft User Number: 6712 Job Number: Page:6 of 26
CERTIFICATE OF COMPLIANCE (Part 2 of 3) LTG -1 -C
�ROJECT NAME DATE
Dr. Nash -Tenant Improvement 10/15/2009
CONTROL
IDENTIFICATION
CONTROL TYPE
(Occupant, Daylight, Dimming, etc.)
Occ Sensor - — 250 sqft
Occ Sensor - — 250 sqft
LUMINAIRES CONTROLLED
TYPE # OF LUMINAIRES
2X2 36
C 4
NOTE TO
FIELD
NOTES TO FIELD - For Building Department Use Only
Run Initiation Time: 10/15/0909:22:53 Run Code: 1255623773
EnergyPro 4.4 by Energysoft User Number: 6712 Job Number: Page:7 of 26
,CERTIFICATE OF COMPLIANCE (Part 3 of 3) LTG-1-C
PROJECT NAME
Dr. Nash-Tenant improvement
DATE
10/15/2009
esigner:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance
tests for lighting systems. The designer is required to check the boxes by all acceptance tests that
apply and list all equipment that require an acceptance test. If all equipment of a certain type requires
a test, list the equipment description and the number of systems to be tested in parentheses. The NJ
number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the
test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design
professional or an agent selected by the owner). Since this form will be part of the plans, completion
of this section will allow the responsible party to budget for the scope of work appropriately.
Building Departments:
Before an occupancy permit is granted for a newly constructed building or space, or a new lighting
system system serving a building or space is operated for normal use, all control devices serving the
building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
In addition a Certificate of Acceptance, LTG-1-A, Forms shall be submitted to the building department
that:
A. Certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of§ 10-103(b) and Title 24 Part 6.
Test Description
Test Performed By:
❑ LTG-2-A: Lighting Control Acceptance Document
- Occupancy Sensor Acceptance
- Manual Daylight Controls Acceptance
. - Automatic Time Switch Control AcceptanceL
Equipment requiring acceptance testing 'fimr- W Ae-
Cz��
[LLMC
❑ LTG-3-A: Automatic Daylighting Controls Acceptance Document
Equipment requiring acceptance testing
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:8 of 26 1
CERTIFICATE OF COMPLIANCE MECH-1-C
PROJECT NAME
Dr. Nash -Tenant Improvement
DATE
10/15/2009
Ueslgner:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-1-A Form shall be submitted to the building department that certifies plans, specifications, installation
certificates, and operatinq and maintenance information meet the requirements of Section 10-103(b) and Title 24 Part 6.
STATEMENT OF COMPLIANCE
•Applies
❑ MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
��
Equipment requiring acceptance testing P W'y4 ,& rL Z
Test required on all New systems both New Construction and Retrofit.
❑ MECH-3-A: Packaged HVAC Systems Acceptance Docume{tI
YY
Equipment requiring acceptance testing
,r Y1 V Ae q�
Test required on all New systems both New Construction and Retrofit.
] MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the
commission do not require equipment testing but do require construction inspection.
❑ MECH-5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
This test required If the unit serves 5,000 1`12 or space or less and 25% or more of the ducts are in nonconditioned or semiconditioned space like an
attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
❑ MECH-6-A: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls installed on new or existing packaged systems must be tested.
❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
All new VA fan volume controls installed on new or existing systems must be tested
❑ MECH-8-A:-Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to chilled and hot water systems.
-Automatic Isolation Controls Applies to new boilers and chillers and the primarypumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Btu/hr.
-Water-loop Heat Pump Controls
to all new watedoop heat pump systems where the combined loop pumps are greater than 5 hp.
-VariableFreq uencyControls Applies to all new distribution pumps on new variable now chilled, hydronic heat pump
or condenser water systems where the pumps ,motors are greater than 5 hp.
Equipment requiring acceptance testing
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:9 of 26
INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG -2-C
ECT NAME
Dr. Nash -Tenant Improvement
INSTALLED LIGHTING POWER FOR CONDITIONED SPACES
DATE
10/15/2009
Luminaire
Lamps/Ballasts
Installed Watts
C
D
E
F
G
H
I
J
Name
Type Description
�v
CD 'O
c d c
3..03
D Q
N
`D rn
moi
an d
'O I N
c d
3.v3
9 Q_
CD CD
m `�
c
���
N
co
vm
J
r
Z
x'03
Cr
m m
N
G���
_
.- N !D
o.
Yes
No
2X2
(3) 2 ft Fluorescent T8 Elec
F17T8
3
17
2.0
55.0
X
481
2,640
B
(1) 13w Compact Fluorescent Triple 4 Pin
Elec
1
13
1.0
14.0
X
5
70
C
(1) 26w Compact Fluorescent Triple 4 Pin
Elec
FTR26W/GX24 -3
1
26
1.0
28.0
X
19
532
PAGE TOTAL 3 242
BUILDING TOTAL (sum of all pages) 3,242
PORTABLE LIGHTING (From LTG -3-C) O
CONTROL CREDIT (From LTG -4-C) 418
• ADJUSTED ACTUAL WATTS 2 824
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 10 of 26 1
LIGHTING CONTROLS CREDIT WORKSHEET (Part 1 of 2) LTG-4-C
CONTROL CREDITS FOR CONDITIONED SPACES
OJECT NAME DATE
Dr. Nash-Tenant improvement 10/15/2009
r—
L_
A
B
C
D
E I F 1 G
H
I
J
ROOM #
ZONE ID
CONDITIONED
AREAS
LIGHTING
CONTROL
DESCRIPTION
PLAN
REF.
ROOM
AREA
(SF)
DAYLIGHTING
WATTS OF
CONTROL
LIGHTING
LIGHTING
ADJUST.
FACTOR'
CONTROL
CREDIT
WATTS
(H X I)
WINDOW
WALL
RATIO
GLAZING
VLT
SKYLIGHT
EFFECTIVE
APERTURE'
Offices, Exam,
RR
Occ Sensor�– 250
2X2
2,0631
1,9801
0.20
396
Offices, Exam, Waiting,
RR
Occ Sensor - — 250
sqft
C
2,063
112
0.20
22
PAGE TOTAL 418
1) From Equation 146-A
2) From Table 146-A BUILDING TOTAL 418
iEnter in LTG -2-C: Lighting Control Credit
Run Initiation Time: 10115/0909:22:53 Run Code: 1255623773
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 11 of 26
FAIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-CI
IECT NAME
Dr. Nash -Tenant Improvement
TEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
DATE
10/15/2009
AIR SYSTEMS, Central or Single Zone
5 Ton units
. 2
Reference on Plans or Specification 1
112(a)
7.70 HSPF
112(a)
13.0 SEER / 10.3 EER
112(b)
Yes
112(c), 115(a)
n/a
121(b)
0
121(b)
619 cfm
121 c
No
121(c)
No
121 c 122(e)
Programmable Switch
122(e)
Heating & Cooling Required
122
Auto
122()
n/a
123
124
1 R-4.2
144 a & b
n/a
144 a & b
72,450 btuh
144 a & b
n/a
144 a & b
94,437 btuh
144 c
Constant Volume
144 (c
144 c
Yes
144 d
No
144 a
No Economizer
144
Constant Tem
144 (f)
Constant Temp
144 (k)
No
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft: Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
Run Initiation Time: 10/15/0909:22:53 Run Code: 1255623773
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 12 of 26
WATER SIDE SYSTEM REQUIREMENTS Part 2 Of 2 MECH-2-C
i ROJECT NAME DATE
Dr. Nash -Tenant Improvement 10/15/2009
SYSTEM FEATURES
2 WATER SIDE SYSTEMS: Chillers, Towers, Boilers, Hydronic Loops
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section Reference on Plans or Specification'
Equipment Efficiency 112(a)
Pipe Insulation 123
PRESCRIPTIVE MEASURES
Calculated Capacity
144 (a & b)
Proposed Capacity
144 (a & b)
Tower Fan Controls
144 h
Tower Flow Controls
144 h
Variable Flow System Design
144 0)
Chiller and Boiler Isolation
144
CHW and HHW Reset Controls
144 0)
WLHP Isolation Valves
144
VSD on CHW, CW & WLHP Pumps > 5
144
HP
DP Sensor Location
144
1: For each chiller, cooling tower, boiler, and hydronic loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph
•number where the required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Water side systems include wet side system using other liquids such as glycol or brine.
Service Hot Water, Pool Heating
ITEM OR SYSTEM TAG(S) DHW Heater
Number of Systems 2
MANDATORY MEASURES Reference on Plans or Specification'
Water Heater Certification
Water Heater Efficiency
Service Water Heating Installation
Pool and Spa Efficiency and Control
Pool and Spa Installation
Pool Heater - No Pilot Light
Spa Heater - No Pilot Light
113 (a)
113 (b)
113 (c)
114 (a)
114 (b)
115 (c)
115 d
AO SMITH ELJF-06*
99%
n/a
n/a
n/a
n/a
1: For each water heater, pool heat and domestic water loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and
paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" ins the column.
I EnerovPro 4.4 by EnergvSoft User Number: 6712 Job Number: Page:13 of 26 1
MECHANICAL VENTILATION MECH-3-C
ROJECT NAME
Dr. Nash -Tenant Improvement
DATE
10/15/2009
PRESCRIPTIVE REHEAT
LIMITATION (Section 144(d))
MECHANICAL VENTILATION Section 121 b 2
AREA
BASIS
OCCUPANCY
BASIS
VAV MINIMUM
A
B
C
D
E
F
G
H
I
J
K
L
M
N
ZONE/SYSTEM
o
D3
y
v�n
O
to
c
Iv 0
'a
��3
o
c3
W'<�
x Dn
n T
yr
m3
v�
N
o
v
m n
.0
o ��
7
Q
m0—'
xc 0
T� T
v»
m
0�lJ
d
�x 0
O
"-" D
�0
nfDA
3' to
D 7
-
N o
�'
OM
�.
3c0
N
T.
c (O
3
T
3W
x
�o
A
�
n
c
w3m
oinx
n �.
m =
L
A
yN'
^�
o 3
» 7
D
to
D
enant improvement
2,063
0.15
309
1
309
619
5 Ton units
Total
309
619
C Minimum ventilation rate perSection 121, Table 121-A
E Based on fixed seal or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed seating.
11 Required Ventilation Air (REO'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS (column D or G).
I Must be greater than orequal to H or use Transfer Air column N to make up the difference.
J Design fan supply cfm (Fan CFM) x 30%; or
K Condition area (ft. sq.) x 04 cfm/ft. sq.; or
L Maximum of Columns H. J. K. or 300 cfm
M This must be less than orequal to Column L and greater that orequal to the sum of Columns H + N.
N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal
to the difference between the Required Venti ation Air (column 1) and the Design Minimum Air (column M), column H - M.
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 14 of 26
.MECHANICAL EQUIPMENT DETAILS Part 1 of 2 MECH-5-C
PROJECT NAME
Dr. Nash -Tenant Improvement
Energy
Factor
or RE
DATE, 0/15/2009
ILLER AND TOWER SUMMARY
System Name
System Type
Efficiency
Tons
PUMPS
Vol.
(Gals.)
Condition
Status
Ext.
R -Val.
Equipment Name
Equipment Type
Qty.
Tot.
Qty
GPM
BHP
Motor
Eff.
Drive
Eff.
Pump
Control
n/a
CENTRAL SYSTEM RATINGS
HEATING
COOLING
S stem Name
System Type
Oty
Output
Aux.
kW
Eff.
Output
Efficient
Condition
Status
Economizer Type
Carrier 50HJD006
Packaged DX
2
DHW / BOILER SUMMARY
0.0
MI II TI-FAM11 Y CFNTRAI WATFR HFATING nFTAII S
Energy
Factor
or RE
Standby
Loss or
Pilot
TANK INSUL.
System Name
System Type
Distribution Type
Qty
Rated
Input
Vol.
(Gals.)
Condition
Status
Ext.
R -Val.
O SMITH ELJF-06'
Small Elec.
Point of Use
2
5,120
6
New
0.95
n/a
n/a
CENTRAL SYSTEM RATINGS
MI II TI-FAM11 Y CFNTRAI WATFR HFATING nFTAII S
Run Initiation Time: 10115/0909:22:53 Run Code: 1255623773
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 15 of 26
Hot Water P mp
Hot Water Pipin Length ft
Control
#
HP
Type
In Plenum
Outside
Buried
Add 1/2"
Insulation
CENTRAL SYSTEM RATINGS
HEATING
COOLING
S stem Name
System Type
Oty
Output
Aux.
kW
Eff.
Output
Efficient
Condition
Status
Economizer Type
Carrier 50HJD006
Packaged DX
2
58,000
0.0
7.70 HSPF
59,000
13.0 SEER / 10.3 EER
New
No Economizer
CENTRAL SYSTEM FAN SUMMARY
SUPPLY N
RETURN FAN
System Name
Fan Tv pe
Motor Location
CFM
BHP
Motor
Eff.
Drive
I Eff.
CFM
BHP
Motor
Eff.
Drive
Eff.
Carrier 50HJD006
Constant Volume
Blow -Through
2,000
1.00
82.5%
100.0%
none
•
Run Initiation Time: 10115/0909:22:53 Run Code: 1255623773
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 15 of 26
ZOOM CAVITY RATIO WORKSHEET (RCR>=3.5) LTG -7-C
ROJECT NAME Dr. Nash -Tenant Improvement FOR ENFORCEMENTrAGENCY USE ONLY
ENTATION AUTHOR DATE PLAN CHECK BY' DATE
1 x/15/2009
SPACES
A
B
C
D
E
F
Room
Name
Task./Activity
Description
Room
Length (L)
(ft)
Room
Width (W)
(ft)
Room Cavity
Height (H)
(ft)
Room Cay. Ratio
5xHx(L+W)
/(LxW)
A
B
C
D
E
F
Room
Name
Task/Activity
Description
Room
Area (A)
(so
Room
Perimeter (P)
(ft)
Room Cavity
Height (H)
(ft)
Room Cay. Ratio
2.5 x H x P
/A
4.4 by EnergySoft User Number: 6712 Job Number: Page: 16 of 26
4
.LIGHTING MANDATORY MEASURES LTG -MM
ECT NAME DATE
Dr. Nash -Tenant Improvement I
10/15/2009
DESCRIPTION
Designer
Enforcement
§ 131(d)1 For every floor, all interior lighting systems shall be equipped with a separate automatic
control to shut off the lighting. This automatic control shall meet the requirements of
Section 119 and may be an occupancy sensor, automatic time switch, or other device
capable of automatically shutting off the lighting.
a § 131(d)20verride for Building Lighting Shut-off: The automatic building shut-off system is
provided with a manual, accessible override switch in sight of the lights. The area of
override is not to exceed 5,000 square feet.
FX] § 119(h) Automatic Control Devices Certified: All automatic control devices specified are
certified, all alternate equipment shall be certified and installed as directed by the
manufacturer.
RX § 111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for the
project are certified and listed in the Directory. All installed fixtures shall be certified.
FX] § 131(a) Individual Room/Area Controls: Each room and area in this building is equipped with
a separate switch or occupancy sensor device for each area with floor-to=ceiling
walls.
FIX I § 131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100
square feet and more than 0.8 watts per square foot of lighting load shall be -
controlled with bi-level switching for uniform reduction of lighting within the room.
131(c) Daylight Area Control: All rooms with windows and skylights that are greater than
250 square feet and that allow for the effective use of daylight in the area shall have
50% of the lamps in each daylit area controlled by a separate switch; or the effective
use of daylight cannot be accomplished because the windows are continuously
shaded by a building on the adjacent lot. Diagram of shading during different times
of the year is included on plans.
§ 131(e) Display Lighting. Display lighting shall be separately switched on circuits that are
20 amps or less.
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 17 of 26
4
L
MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM
r
ROJECT NAME
Dr. Nash -Tenant Improvement
DATE
10/15/2009
DESCRIPTION
Designer
Enforcement
Equipment and Systems Efficiencies
❑X 911 Any appliance for which there is a California standard established in the
Appliance Efficiency Regulations will comply with the applicable standard.
❑ §115(a) Fan type central furnaces shall not have a pilot light.
❑ §123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees
Fahrenheit, or within HVAC equipment, shall be insulated in accordance with
Standards Section 123.
X❑ §124 Air handling duct systems shall be installed and insulated in compliance with
Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards.
Controls
§122(e) Each space conditioning system shall be installed with one of the following:
X] §I22(e)1A Each space conditioning system serving building types such as offices and
manufacturing facilities (and all others not explicitly exempt from the
requirements of Section 112 (d)) shall be installed with an automatic time switch
with an accessible manual override that allows operation of the system during
off -hours for up to 4 hours. The time switch shall be capable of programming
different schedules for weekdays and weekends and have program backup
capabilities that prevent the loss of the device's program and time setting for at
least 10 hours if power is interrupted; or
In§122(e)l B An occupancy sensor to control the operating period of the system; or
❑ §122(e)1C A 4 -hour timer that can be manually operated to control the operating period of
the system.
X] §122(e)2 Each space conditioning system shall be installed with controls that temporarily
restart and temporarily operate the system as required to maintain a setback
heating and/or a setup cooling thermostat setpoint.
§122(g) Each space conditioning system serving multiple zones with a combined
conditioned floor area more than 25,000 square feet shall be provided with
isolation zones. Each zone: shall not exceed 25,000 square feet; shall be
provided with isolation devices, such as valves or dampers, that allow the supply
of heating or cooling to be setback or shut off independently of other isolation
areas; and shall be controlled by a time control device as described above.
§122(a&b) Each space conditioning system shall be controlled by an individual thermostat
that responds to temperature within the zone. Where used to control heating, the
control shall be adjustable down to 55 degrees F or lower. For cooling, the
control shall be adjustable up to 85 degrees F or higher. Where used for both
heating and cooling, the control shall be capable of providing a deadband of at
least 5 degrees F within which the supply of heating and cooling is shut off or
reduced to a minimum.
r§122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and
adjustable setpoint stops accessible only to authorized personnel.
§112(b) Heat pumps shall be installed with controls to prevent electric resistance
supplementary heater operation when the heating load can be met by the heat
pump alone.
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 18 of 26
L
4
.MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM
ECT NAME
Dr. Nash -Tenant Improvement
DATE
10/15/2009
Description
Designer
Enforcement
Ventilation
❑X §121(e) Controls shall be provided to allow outside air dampers or devices to be operated
at the ventilation rates as specified on these plans.
F] §122(f) Gravity or automatic dampers interlocked and closed on fan shutdown shall be
provided on the outside air intakes and discharges of all space conditioning and
exhaust systems.
[X §122(f) §12Y(f) All gravity ventilating systems shall be provided with automatic or readily
accessible manually operated dampers in all openings to the outside, except for
combustion air openings.
X❑ §121(f)1 Air Balancing: The system shall be balanced in accordance with the National
Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or
Associated Air Balance Council (AABC) National Standards (1989); or
-
R§121(f)2 Outside Air Certification: The system shall provide the minimum outside air as
shown on the mechanical drawings, and shall be measured and certified by the
installing licensed C-20 mechanical contractor and certified by (1) the design
mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3)
the person with overall responsibility for the design of the ventilation system; or
X❑ §121(f)3 Outside Air Measurement: The system shall be equipped with a calibrated local or
remote device capable of measuring the quantity of outside air on a continuous
basis and displaying that quantity on a readily accessible display divice; or
§121(f)4 Another method approved by the Commission.
Service Water Heating Systems
R§113(b)2 If a circulating hot water system is installed, it shall have a control capable of
automatically turning off the circulating pump(s) when hot water is not required.
X❑ §113(c) Lavatories in restrooms of public facilities shall be equipped with controls to limit
the outlet temperature to 110 degrees F.
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 19 of 26
iVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Dr. Nash -Tenant Improvement 10/15/2009
STEM NAME FLOOR AREA
5 Ton units 2,063
Number of Systems
21
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
Heating System
Output per System
58,000
Total Output (Btuh)
116,000
Output (Btuh/sgft)
56.2
Cooling System
Output per System
59,000
Total Output (Btuh)
118,000
Total Output (Tons)
9.8
Total Output (Btuh/sgft)
57.2
Total Output (sgft/Ton)
209.8
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible
Latent
CFM
I Sensible
3,569
72,162
7,840
1 927
34,522
Carrier 50HJD006
0
8,044
Airflow (cfm)
3,608
1,726
0
0
619
24,470
1,020
619
28,713
Airflow (cfm/Ton)
0
Total Adjusted System Output 94,437 8,044
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 2 pm
0
3,608
1,726
103,8478[776 820
Air System
I HVAC EQUIPMENT SELECTION
CFM per System
2,000
Carrier 50HJD006
94,437
8,044
Airflow (cfm)
4,000
Airflow (cfm/sgft)
1.94
Airflow (cfm/Ton)
406.8
Total Adjusted System Output 94,437 8,044
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 2 pm
Outside Air (%)
15.5
Outside Air (cfmisgft)
0.30
Note: values above given at ARI conditions
66 688
72,450
72,450
Jan 12 am
EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26.0 of 62.8 of 62.8 of - 105.0 of
" lowO Supply Air Ducts
Outside Air
619 cfm 104.6 of
Supply Fan Heating Coil
4000 cfm ROOMS
70.0 of
69.6 of I
Return Air Ducts `
ICOOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
112.0 / 72.8 of
Outside Air
619 cfm
74.8 / 61.7 of
80.6 / 63.6 of 80.6 / 63.6 of 55.0 / 53.6 of
O Supply Air Ducts
Supply Fan Cooling Coil 55.8 / 54.0 of
4000 cfm 49.1% R.H. ROOMS
74.0 / 61.4 of
Return Air Ducts I
I EneravPro 4.4 by EnerovSoft User Number: 6712 Job Number: Paae:20 of 26
4
.ZONE LOAD SUMMARY
OJECT NAME
Dr. Nash -Tenant improvement
;-STEM
DATE
10/15/2009
NAME
5 Tori units
FLOOR AREA
2,063
ZONE LOAD SUMMARY
ZONAL SYSTEM
COOLING PEAK
HEATING PEAK
ZONE NAME
SYSTEM NAME
Mult.
CFM
Cooling
Latent
Heating
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Tenant improvement
1.0
3,537
96,554
6,330
927
63,503
Values include ventilation load
COINCIDENT TOTAL 1 96,554 6,330 63,503
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:21 of 26
4
4
ROOM LOAD SUMMARY
PROJECT NAME
Dr. Nash -Tenant Improvement
DATE
10/15/2009
(STEM NAME
5 Ton units
FLOOR AREA
2,063
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Tenant improvement
Offices, Exam, Waiting. RR
1
3,569
72,162
7,840
3,569
72,162
7,840
927
34,522
IL
PAGE TOTAL 3,569 72,162 7,840 927 34,522
TOTAL 1 3,569 72,162 7,840 927 34,522
EnergyPro 4.4 by Energy5oft User Number: 6712 Job Number: Page: 22 of 26
ROOM HEATING PEAK LOADS
roject Title Date
r. Nash -Tenant Improvement 10/15/2009
Room Information Desi n Conditions
Room Name Offices, Exam, Time of Peak' Jan 12 am
R
Floor Area Waitin 3 Outdoor Dry Bulb Temperature 26°F
Indoor Dry Bulb Temperature 70°F
Conduction Area U -Value QT of Btu/hr
2,063.0
X
X
X
x
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
0.0320
X
X
X
X
X
X
X
X
X
X
X
X
X
X
x
X
X
X
X
X
X
X
x
X
x
X
X
X
x
X
X
X
X
X
X
X
X
X
X
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
2,905
20.0
0.8200
44
722
276.0
0.8200
44
9,958
48.0
0.8700
44
1,837
108.0
0.8700
44
4,134
48.0
0.8700
44
1,837
20.0
0.8200
44
722
2,063.0
0.0480
44
4,357
Mems shown with an astensk (f) denote conduction through an interior sunace to another room. Page Total: 26,472
Infiltration: 1.00 x 1.064 x 2 063 x 10.00 x 0.500 / 60] x 44 = 8 050
chedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 34,522
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 23 of 26
4
ROOM COOLING PEAK LOADS
kject Title
Dr. Nash -Tenant Improvement
X
X
X
X
X
X
X
X
X
Date
10/15/2009
OM INFORMATION
DESIGN CONDITIONS
0.0320
Room Name Offices, Exam, Waiting. RR
Time Of Peak
Jul 2 pm
Floor Area 2,063
Outdoor Dry Bulb Temperature
111 OF
Indoor Dry Bulb Temperature 74OFOutdoor
Wet Bulb Temperature
73 OF
Conduction
Area
X
X
X
X
X
X
X
X
X
U -Value
X
X
X
X
X
X
X
X
X
2,063.0
0.0320
20.0
0.8200
276.0
0.8200
48.0
0.8700
108.0
0.8700
48.0
0.8700
20.0
0.8200
2,063.0
0.0480
48.0
46
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
DETD 1
71.1 =
33.6 =
36.6 =
25.3 =
25.3 =
25.3 =
39.7 =
31.2 =
Page Total
Orientation
Area
X
X
X
X
X
X
X
X
X
X
SGF
X
X
X
x
X
X
X
X
X
X
SC
Weighting
X
X
X
x
X
X
X
X
X
X
Factor
=
=
=
=
=
=
=
=
=
=
(E)
48.0
46
0.657
1.870
U
108.0
46
0.657
1.870
(E)
48.0
46
0.657
1.870
Page Total
Btu/hr
4,696
550
8,280
1,055
2.375
1,055
650
3,085
z 17as
Btu/hr
2,711
6,101
2,711
11 524
Sched. Weighting
Internal Gain Frac. Area Heat Gain Factor Btu/hr
fights -1.00 X 2,063 X 1.571 Watts/sqft X '3.41 Btuh/Watt X 1.000 = 11,063
Occupants 1.0d X 2,063 X 250 Btuh/OCc. / 50 sgft/OCc. X 1.00 = 10,315
Receptacle 1.0c X 2,063 X 1.500 Watts/sgft x 3.41 Btuh/Watt X 1.00 = 10,562
Process 1.0c X 2,063 X 0.000 Watts/sgft X 3.41 Btuh/Watt X 1.00 = 0
Infiltration: [ 1.00 x 1.064 X 2 063 X 10.00 x 0.50 /601 X 38 = 6 952
Schedule Air Sensible Area Ceiling Height ACH Z�,T
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 72,162
Sched. Btu/hr
Latent Gain Frac. Area Heat Gain
Occupants 1.00 X 2 063 x 200 Btuh/OCC. / 50 sgft/occ. = 8 252
Receptacle 1.00 X x 0.0.00 Watts/sgft x Btuh/Watt = 0
Process 1.00 X 2,063 X 0.000 Watts/sgft X 3.413 Btuh/Watt = 00
Infiltration: [ 00 x 4,771 x n63 X 10 00 x 0 50 / 60] x oano = �g-i
Schedule Air Latent Area Ceiling Height ACH pw
EnergyPro 4.4 by EnergySoft I User Number: 6712 Job Number: Page: 24 of 26
ROOM COOLING COIL LOADS
roject Title Date
Dr. Nash -Tenant Improvement 10/15/2009
ROOM INFORMATION DESIGN CONDITIONS
Room Name Offices, Exam, Waiting. RR Time of Peak Jul 2 pm
Floor Area 2,063 Outdoor Dry Bulb Temperature 111 OF
Indoor Dry Bulb Temperature 74cl� Outdoor Wet Bulb Temperature 73 `k
Conduction
Area
63.0
20.0
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
X
X
X
X
X
X
X
X
X
U -Value
0.0320
0.8200
DETD 1
X
X
X
X
X
X
X
X
X
71.1
=
=
=
=
=
=
=
=
=
33.6
36.6
25.3
25.3
25.3
39.7
31.2
48.0
Page Total
Orientation
Area
X
X
x
X
X
X
X
X
X
X
SGF
X
X
X
x
X
X
X
x
X
X
SC
Weighting
X
X
x
x
x
x
X
X
x
X
Factor
=
=
=
=
=
=
=
=
=
=
U
48.0
46
0.657
1.870
(E)
108.0
46
0.657
1.870
(E)
48.0
46
0.657
1.870
Page Total
Btu/hr
4,696
550
8,280
1,055
2,375
1 055
650
3 085
21 746
Btu/hr
Sched. Weighting gtu/hr
Internal Gain Frac. Area Heat Gain Factor
Lights 1.0-0 X 2,063 X 1.571 Watts/sqft x 3.413 Btuh/Watt x 1.000 = 11,063
10ants 1.0( X 2,063 X 250 Btuh/occ. / 5 sgft/occ. X 1.00 = 10,315
r-ccup1.Oq X 2,063 X 1.500
eceptacle Watts/sgft x 3.41 Btuh/VVatt X 1.00 = 10,562
rocess 1.00 X 2,063 X 0.000 Watts/sqft X 3.41 BtuhfWatt x 1.00 = 0
Infiltration: 1.00 x 1.064 x 2 063 x 10.00 x 0.50 /601 x 38 = 6 952
-Schedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 72,162
Sched. Btulhr
Latent Gain Frac. Area Heat Gain
Occupants 1.00 X 2,0631 X 200 Btuh/OCC. / 50 sgft/occ. = 8 252
Receptacle 1 QQ x x O-OOQ Watts/sgft x Btuh/Watt = 0
Process 1.00 X 2,063 X 0.000 Watts/sgft x 1 3.413 Btuh/Watt = 0
Infiltration:[� x� x 0.83 .x 1�Qp x �� / 6] x - 0.0 =
16 Schedule Air Latent Area Ceiling Height ACH pw
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page: 25 of 26
LII �GPiTING INSPECTION CHECKLIST LTG -I
ROJECT NAME
Dr. Nash -Tenant Improvement
INSPECTION DATE
10/15/2009
FIXTURE
CODE
TYPE
DESCRIPTION
LAMP
TYPE
LAMP
QUANT.
NUMBER OF
FIXTURES
WATTS PER
FIXTURE
FIELD NOTES
2X2
3 2 ft Fluorescent T8 Elec
F17T8
3
48
55.0
B
1 13w Compact Fluorescent Triple 4 Pin Elec
CFM
1
5
14.0
C
1 26w Com act Fluorescent Tri le 4 Pin Elec
1
19
28.0
•
Type DESCRIPTION
MH METAL HALIDE
INC INCANDESCENT
INC/LV INCANDESCENT LOW VOLTAGE
CFL COMPACT FLUORESCENT
FL FLUORESCENT
OTHER
EnergyPro 4.4 by EnergySoft User Number: 6712 Job Number: Page:26 of 26