BRES2018-0341 Title 24 AdditionalBUILDING ENERGY ANALYSIS REPORT
1*65 mil$ a 3slI
PROJECT:
MURRAY RESIDENCE's addition
78190 CALLE CADT
LA QUINTA, CA 92253
Project Designer:
GLS ARCHITECTURE GROUP INC.
74991 JONI DR #9
PALM DESERT, CA 92260
60 340.3528
Report Prepared by:
Armando Chavez
44890 SEELEY
LA QUINTA, CA 92253
760 278.1840
Job Number:
TY OF LA QUINT A
BUILDING REVIEWED FOR
R
CODE
COMPLIANCE
L
RECE'VED 18 - GLS / 109 - 083
�C i 6ui Date:
O1TY or LA QUINTA 10/10/2018
OOMMUNI"iY DEVELOPMENT
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2016 Building Energy Efficiency Standards.
This program developed by EnergySoft Software — www.energysoft.com.
I TABLE OF CONTENTS I
Cover Page 1 '
Table of Contents 2 `
Form CF-1 R-PRF-01-E Certificate of Compliance 3
Form RMS-1 Residential Measures Summary 12
Form MF-1 R Mandatory Measures Summary 13
HVAC System Heating and Cooling Loads Summary 17
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MURRAY RESIDENCE's addition
Calculation Description: Title 24 Analysis
Calculation Date/Time: 12:24, Wed, Oct 10, 2018
Input File Name: 083 - 78190 CALLE CADIZ.ribd16x
CF1 R-PRF-01
Page 1 of 9
GENERAL INFORMATION
01
Project Name
MURRAY RESIDENCE's addition
02
Calculation Description
Title 24 Analysis
03
Project Location
78190 CALLE CADIZ
04
City
LA QUINTA
05
Standards Version
Compliance 2017
06
Zip Code
92253
07
Compliance Manager Version
BEMCmpMgr 2016.3.1 (1149)
08
Climate Zone
CZ15
09
Software Version
CBECC-Res 2016 3.1 (1019)
10
Building Type
Single Family
11
Front Orientation (deg/Cardinal)
180
12
Project Scope
Addition and/or Alteration
13
Number of Dwelling Units
1
14
Total Cond. Floor Area (ft)
4605
15
Number of Zones
2
16
Slab Area (ft2)
4605
17
Number of Stories
1
18
Addition Cond. Floor Area (ft2)
1192
19
Natural Gas Available
Yes
20
Addition Slab Area (ft2)
1192
21
Glazing Percentage (%)
11.7%
COMPLIANCE RESULTS
01 Building Complies with Computer Performance
02 This building incorporates features that require field testing and/or verification by a certified HERS rater under the supervision of a CEC-approved HERS provider.
03 This building incorporates one or more Special Features shown below
ENERGY USE SUMMARY
04
05
06
07
08
Energy Use (kTDV/ft2-yr)
Standard Design
Proposed Design
Compliance Margin
Percent Improvement
Space Heating
1.79
3.95
-2.16
-120.7%
Space Cooling
92.33
89.73
2.60
2.8%
IAQ Ventilation
0.76
0.76
0.00
0.0%
Water Heating
5.85
5.85
0.00
0.0%
Photovoltaic Offset
----
0.00
0.00
-----
Compliance Energy Total
100.73
100.29
0.44
0.4%
Registration Number: 218-Po10276852A-000-000-0000000-0000 Registration Date/Time: 2018-10-10 12:41:11 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-10-10 12:24:59
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD CF1 R-PRF-01
Project Name: MURRAY RESIDENCE's addition Calculation Date/Time: 12:24, Wed, Oct 10, 2018 Page 2 of 9
Calculation Description: Title 24 Analysis Input File Name: 083 - 78190 CALLE CADIZ.ribd16x
REQUIRED SPECIAL FEATURES
The following are features that must be installed as condition for meeting the modeled energy performance for this computer analysis.
• Raised heel truss
• Cool roof
• Window overhangs and/or fins
• Exposed slab floor in conditioned zone
HERS FEATURE SUMMARY
The following is a summary of the features that must be field -verified by a certified HERS Rater as a condition for meeting the modeled energy performance
for this computer analysis. Additional detail is
provided in the building components tables below.
Building -level Verifications:
• IAQ mechanical ventilation
Cooling System Verifications:
• Minimum Airflow
• Fan Efficacy WattsICFM
HVAC Distribution System Verifications:
• Duct Sealing
Domestic Hot Water System Verifications:
- None --
BUILDING - FEATURES INFORMATION
01 02
03 04 05
06
07
Number of Dwelling
Number of Ventilation
Number of Water
Project Name Conditioned Floor Area (ftz) Units Number of Bedrooms Number of Zones
Cooling Systems
Heating Systems
MURRAY RESIDENCE's addition 4605
1 3 2
0
1
ZONE INFORMATION
01
02
03
04
05
06
07
Zone Floor Area
Avg. Ceiling
Zone Name
Zone Type
HVAC System Name
(ft2)
Height
Water Heating System 1
Water Heating System 2
(E) 3413
Conditioned
AC-1
3413
9
DHW Sys 1
n/a
(N) - 1192
Conditioned
AC-1
1192
9
DHW Sys 1
n/a
Registration Number: 218-P010276852A-000-000-0000000-0000 Registration Date/Time: 2018-10-10 12:41:11 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-10-10 12:24:59
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MURRAY RESIDENCE's addition Calculation Date/Time: 12:24, Wed, Oct 10, 2018
Calculation Description: Title 24 Analysis
Input File Name: 083 - 78190 CALLE CADIZ.ribdl6x
CF1 R-PRF-01
Page 3 of 9
OPAQUE SURFACES
01
02
03
04
05
06
07
08
09
10
11
Name
Zone
Construction
Azimuth
Orientation
Gross Area
(ft)
Window & Door
Area (ft)
Tilt
(deg)
Wall
Exception
Status
Verified
Existing
Condition
E - 645
(E) 3413
Def Wall '92 to Presentl
90
Right
645
58.32
90
n/a
Existing
No
S - 762
(E) 3413
Def Wall '92 to Presentl
180
Front
762
285.435
90
n/a
Existing
No
W - 270
(E) 3413
Def Wall '92 to Presentl
270
Left
325
12
90
n/a
Existing
No
TO GARAGE
(E) 3413» (N) - 1192
Def Wall '92 to Present
180
0
n/a
Existing
No
3413
(E) 3413
Def Roof'78 to Present
3413
n/a
Existing
No
N - 479
(N)-1192
R-21 Wall
0
Back
479
153
90
none
New
n/a
E - 248
(N)-1192
R-21 Wall
90
Right
248
0
90
none
New
n/a
W- 306
(N)-1192
R-21 Wall
270
Left
306
50
90
none
New
n/a
N TO GARAGE
(N)-1192
R-15 Wall --
427
16.66
n/a
New
n/a
1192
(N)-1192
R-38 + CRRC 0.86-0.88
1192
n/a
New
n/a
ATTIC
01
02
03
04
05
06
07
08
09
10
Name
Construction
Type
Roof Rise
Roof
Reflectance
Roof
Emittance
Radiant
Barrier
Cool
Roof
Status
Verified Existing
Condition
Attic (E) 3413
Attic Roof(E) 3413
Ventilated
1
0.1
0.85
No
No
Existing
No
Attic (N) - 1192
Attic Roof(N) - 1192
Ventilated
0.2
0.86
0.88
Yes
Yes
New
No
Registration Number: 218-P010276852A-000-000-0000000-0000 Registration Date/Time: 2018-10-10 12:41:11 HERS Provider: CaICERTS inc
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-10-10 12:24:59
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MURRAY RESIDENCE's addition Calculation Date/Time: 12:24, Wed, Oct 10, 2018
Calculation Description: Title 24 Analysis
Input File Name: 083 - 78190 CALLE CADIZ.ribd16x
CF1 R-PRF-01
Page 4 of 9
FENESTRATION I GLAZING
01
02
03
04
05
06
07
08
09
10
11
Name
Surface (Orientation -Azimuth)
Width (ft)
Height (ft)
Multiplier
Area (ft2)
U-factor
SHGC
Exterior Shading
Status
Verified
Existing
Condition
2450
E - 645 (Right-90)
----
---
1
11.7
0.51
0.24
Insect Screen (default)
Altered
n/a
24502
E - 645 (Right-90)
-
-
1
11.7
0.51
0.24
Insect Screen (default)
Altered
n/a
5050
E - 645 (Right-90)
--
1
25.0
0.51
0.24
Insect Screen (default)
Altered
n/a
2050
E - 645 (Right-90)
-
1
10.0
059
0.40
Insect Screen (default)
Existing
No
5080
S - 762 (Front-180)
- -
1
40.0
0.51
0.24
Insect Screen (default)
Altered
n/a
8080
S - 762 (Front-180)
8.0
8.0
1
64.0
0.59
0.40
Insect Screen (default)
Existing
No
5480
S - 762 (Front-180)
5.3
8.0
1.014
43.0
0.59
0.40
Insect Screen (default)
Existing
No
5414
S - 762 (Front-180)
5.0
1.3
1.094
7.1
0.59
0.40
Insect Screen (default)
Existing
No
6050
S - 762 (Front-180)
6.0
5.0
1
30.0
0.59
0.40
Insect Screen (default)
Existing
No
10080
S - 762 (Front-180)
10.0
8.0
1
80.0
0.59
0.40
Insect Screen (default)
Existing
No
2020
W - 270 (Left-270)
----
----
1
4.0
0.59
0.40
Insect Screen (default)
Existing
No
20202
W - 270 (Left-270)
-
-
1
4.0
0.59
0.40
Insect Screen (default)
Existing
No
20203
W - 270 (Left-270)
1
4.0
0.59
0.40
Insect Screen (default)
Existing
No
80802
N - 479 (Back-0)
--
1
64.0
0.51
0.24
Insect Screen (default)
New
n/a
80803
N - 479 (Back-0)
-
1
64.0
0.51
0.24
Insect Screen (default)
New
n/a
50502
N - 479 (Back-0)
----
1
25.0
0.51
0.24
Insect Screen (default)
New
n/a
2680
W- 306 (Left-270)
-
1
20.0
0.51
0.24
Insect Screen (default)
New
n/a
60502
W- 306 (Left-270)
-
1
30.0
0.51
1 0.24
Insect Screen (default)
New
n/a
OPAQUE DOORS
01
02
03
04
05
06
Name
Side of Building
Area (ft)
U-factor
Status
Verified Existing Condition
2880
S - 762
21.3
0.50
Existing
No
Registration Number: 218-P010276852A-000-000-0000000-0000 Registration Date/Time: 2018-10-10 12:41:11 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-10-10 12:24:59
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MURRAY RESIDENCE's addition Calculation Date/Time: 12:24, Wed, Oct 10, 2018
Calculation Description: Title 24 Analysis
Input File Name: 083 - 78190 CALLE CADIZ.ribd16x
CFI R-PRF-01
Page 5 of 9
OVERHANGS AND FINS
01
02
03
04 05
06
07
08
09
10
11
12
13 14
Overhang
Left Fin
Right Fin
Window
Depth
Dist Up
Left
Extent
Right
Extent
Flap Ht.
Depth
Top Up
Dist L
Bot Up
Depth
Top Up
Dist R
Bot Up
8080
6
0.1
6
6
0
0
0
0
0
0
0
0
0
5480
6
0.1
6
6
0
0
0
0
0
0
0
0
0
5414
6
0.1
6
6
0
0
0
1 0
0
0
0
0
0
6050
2
1.33
2
2
0
0
0
0
0
0
0
0
0
10080
8
0.1
8
8
0
0
0
0
0
0
0
0
0
OPAQUE SURFACE CONSTRUCTIONS
01
02
03
04
05
06
07
Total Cavity
Winter Design
Construction Name
Surface Type
Construction Type
Framing
R-value
U-factor
Assembly Layers
- Cavity/Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
• Roof Deck: Wood Siding/sheathing/decking
Attic Roof(E) 3413
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
• Roofing: Light Roof (Asphalt Shingle)
- Inside Finish: Gypsum Board
Ceilings (below
- Cavity/Frame: R-9.1 /2x4
Def Roof '78 to Present
attic)
Wood Framed Ceiling
2x4 @ 16 in. O.C.
R 19
0.049
- Over Ceiling Joists: R-9.9 insul.
- Inside Finish: Gypsum Board
Cavity / Frame: R-13 / 2x4
Def Wall '92 to Present
Interior Walls
Wood Framed Wall
2x4 @ 16 in. O.C.
R 13
0.092
- Other Side Finish: Gypsum Board
• Inside Finish: Gypsum Board
• Cavity/ Frame: R- 13 / 2x4
Def Wall '92 to Presentl
Exterior Walls
Wood Framed Wall
2x4 @ 16 in. O.C.
R 13
0.101
• Exterior Finish: 3 Coat Stucco
- Cavity/Frame: no insul. /2x4 Top Chrd
2x4 Top Chord of Roof Truss @ 24
• Roof Deck: Wood Siding/sheathing/decking
Attic Roof(N) - 1192
Attic Roofs
Wood Framed Ceiling
in. O.C.
none
0.644
- Roofing: Light Roof (Asphalt Shingle)
• Inside Finish: Gypsum Board
Ceilings (below
2x4 @ 24 in. O.C. with Raised Heel
- Cavity/Frame: R-9.1 /2x4
R-38 + CRRC 0.86-0.88
attic)
Wood Framed Ceiling
Truss Height 20 in
R 38
0.025
- Over Ceiling Joists: R-28.9 insul.
- Inside Finish: Gypsum Board
- Cavity / Frame: R-15 / 2x4
R-15 Wall --
Interior Walls
Wood Framed Wall
2x4 @ 16 in. O.C.
R 15
0.086
• Other Side Finish: Gypsum Board
- Inside Finish: Gypsum Board
Cavity / Frame: R-21 / 2x6
R-21 Wall
Exterior Walls
Wood Framed Wall
2x6 @ 16 in. O.C.
R 21
0.069
Exterior Finish: 3 Coat Stucco
Registration Number: 218-P010276852A-000-000-0000000-0000 Registration Date/Time: 2018-10-10 12:41:11 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-10-10 12:24:59
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MURRAY RESIDENCE's addition Calculation Date/Time: 12:24, Wed, Oct 10, 2018
Calculation Description: Title 24 Analysis
Input File Name: 083 - 78190 CALLE CADIZ.ribd16x
CF1 R-PRF-01
Page 6 of 9
SLAB FLOORS
01
02
03
04
05
06
07
08
09
Name
Zone
Area (ftz)
Perimeter
(ft)
Edge Insul. R-value
Carpeted
Fraction
Heated
Status
Verified
Existing
Condition
34132
(E) 3413
3413
0.1
None
0.8
No
Existing
No
11922
(N)-1192
1192
0.1
None
0
No
New
No
BUILDING ENVELOPE - HERS VERIFICATION
01
02
03
04
Quality Insulation Installation (QII)
I Quality Installation of Spray Foam Insulation
Building Envelope Air Leakage
CFM50
Not Required
Not Required
Not Required
n/a
WATER HEATING SYSTEMS
01
02
03
04
05
06
07
08
Name
System Type
Distribution Type
Water Heater
Number of
Heaters
Solar
Fraction
M
Status
Verified Existing
Condition
DHW Sys 1
DHW
Standard
DHW Heater 1
1
0
Existing
No
WATER HEATERS
01
02
03
04
05
06
07
08
09
10
11
12
Input Rating /
Tank
Standby
Heater
Tank
Uniform Energy
Pilot /
Insulation
Loss /
First Hour
Tank Location
Element
Number
Volume
Factor / Energy
Thermal
R-value
Recovery
Rating /
NEEA Heat Pump
or Ambient
Name
Type
Tank Type
of Units
(gal)
Factor / Efficiency
Efficiency
(Int/Ext)
Eff
Flow Rate
Brand / Model
Condition
DHW Heater 1
Gas
Small Storage
1
50
0.525 EF
<= 75 kBtu/hr
0
n/a
n/a
n/a
n/a
SPACE CONDITIONING SYSTEMS
01
02
03
04
05
06
07
08
Distribution
Verified Existing
SC Sys Name
System Type
Heating Unit Name
Cooling Unit Name
Fan Name
Name
Status
Condition
AC-1
Other Heating and Cooling
Heating Component 1
Cooling Component 1
HVAC Fan 1
Air Distribution
Altered
No
System
System 1
Registration Number: 218-P010276852A-000-000-0000000-0000 Registration Date/Time: 2018-10-10 12:41:11 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-10-10 12:24:59
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MURRAY RESIDENCE's addition Calculation Date/Time: 12:24, Wed, Oct 10, 2018
Calculation Description: Title 24 Analysis
Input File Name: 083 - 78190 CALLE CADIZ.ribd16x
CF1 R-PRF-01
Page 7 of 9
HVAC - HEATING UNIT TYPES
01
02
03
04
Name
System Type
Number of Units
Efficiency
Heating Component 1
CntrlFurnace
2
80 AFUE
HVAC - COOLING UNIT TYPES
01
02
03
04
05
06
07
08
Name
System Type
Number of Units
Efficiency
EER SEER
Zonally Controlled
Compressor Type
HERS Verification
Cooling Component 1
PkgAirCond
2
11
14
Not Zonal
Single Speed
Cooling Component
1-hers-cool
HVAC COOLING - HERS VERIFICATION
01
02
03
04
05
06
Name
Verified Airflow
Airflow Target
Verified EER
Verified SEER
Verified Refrigerant
Charge
Cooling Component 1-hers-cool
Required
350
Not Required
Not Required
Not Required
HVAC - DISTRIBUTION SYSTEMS
01
02
I 03
04
05
06
07
08
09
10
Insulation
Supply Duct
Return Duct
Verified Existing
HERS
Name
Type
Duct Leakage
R-value
Location
Location
Bypass Duct
Status
Condition
Verification
Ducts located in attic
Air Distribution
Air Distribution
(Ventilated and
Sealed and tested
8.0
Attic
Attic
None
Altered
No
System
System 1
Unventilated)
1-hers-dist
HVAC DISTRIBUTION - HERS VERIFICATION
01
02
03
04
05
06
07
08
Name
Duct Leakage
Verification
Duct Leakage
Target (%)
Verified Duct
Location
Verified Duct
Design
Buried
Ducts
Deeply Buried
Ducts
Low -leakage
Air Handler
Air Distribution System 1-hers-dist
Required
5.0
Not Required
Not Required
Not Required
Not Required
n/a
HVAC - FAN SYSTEMS 8: HERS VERIFICATION
01
02
03
04
Name
Type
Fan Power (Watts/CFM)
HERS Verification
HVAC Fan 1
Single Speed PSC Furnace Fan
0.58
Required
Registration Number: 218-P010276852A-000-000-0000000-0000 Registration Date/Time: 2018-10-10 12.41:11 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-10-10 12:24:59
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MURRAY RESIDENCE's addition Calculation Date/Time: 12:24, Wed, Oct 10, 2018
Calculation Description: Title 24 Analysis
Input File Name: 083 - 78190 CALLE CADIZ.ribd16x
CF1 R-PRF-01
Page 8 of 9
IAQ (Indoor Air Quality) FANS
01
02
03
04
05
06
Dwelling Unit
IAQ CFM
IAQ Watts/CFM
IAQ Fan Type
IAQ Recovery
Effectiveness(%)
HERS Verification
SFam IAQVentRpt
76
0.25
Default
0
Required
PROJECT NOTES
-- ALL EXISTING AND PROPOSED INPUT DATA USED IN THIS REPORT WAS PROVIDED BY THE PLANS PREPARER. -- LOAD CALCULATIONS AND AC SIZING EQUIPMENT SHALL BE
VERIFIED BY THE AC CONTRACTIOR PRIOR TO PLACEMENT OF ITS ORDER. -- AC EQUIPMENT'S EFFICENCY SHALL BE EQUAL (OR BETTER) THAN REQUIRED BY THIS REPORT. --
ANY ALTERATION OR DEVIATION FROM THIS REPORT WILL BE GENERAL CONTRACTOR'S RESPONSABILITY.
Registration Number: 218-P010276852A-000-000-0000000-0000 Registration Date(Time: 2018-10-10 12:41:11 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-10-10 12:24:59
CERTIFICATE OF COMPLIANCE - RESIDENTIAL PERFORMANCE COMPLIANCE METHOD
Project Name: MURRAY RESIDENCE's addition Calculation Date/Time: 12:24, Wed, Oct 10, 2018
Calculation Description: Title 24 Analysis
Input File Name: 083 - 78190 CALLE CADIZ.ribd16x
CFI R-PRF-01
Page 9 of 9
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. 1 certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signaturr- l-�
ARMANDO CHAVEZ
—�
Company:
Signature Date:
TITLE 24 OF THE DESERT
2018-10-10 12:40:55
Address:
CEA/HERS Certification Identification (If applicable):
74800 Shirley #62
N.A.
City/State/Zip:
Phone:
PALM DESERT, CA 92260
760-278-1840
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design identified on this Certificate of Compliance
2. 1 certify that the energy features and performance specifications identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of
Regulations.
3. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
Responsible Designer Name:
Responsible Designer Signature -
Ruben Romero`"s`
Company:
Date Signed:
GLS ARCHITECTURE GROUP INC
2018-10-10 12:41:11
Address:
License:
74491 JONI DR SUITE #9
N.A.
City/State/Zip:
Phone:
Palm Desert, CA 92260
760-340-3528
Digitally signed by Ca10ERTS. This digital signature is provided in order to secure the content of this registered document, and in noway implies Registration
Provider responsibility for the accuracy of the information.
�T M
[o-
Easy to Verify
at CaICERTS.com
Registration Number: 218-P010276852A-000-000-0000000-0000 Registration Date/Time: 2018-10-10 12:41:11 HERS Provider: CaICERTS inc.
CA Building Energy Efficiency Standards - 2016 Residential Compliance Report Version - CF1 R-06232018-1149 Report Generated at: 2018-10-10 12:24:59
RESIDENTIAL MEASURES SUMMARY
RMS-1
Project Name
MURRAY RESIDENCE'S addition
Project Address
78190 CALLE CADIZ LA QUINTA
Building Type 10 Single Family ❑ Addition Alone
❑ Multi Family [21 Existing+ Addition/Alteration
California Energy Climate Zone ' Total Cond. Floor Area Addition
CA Climate Zone 15 4,605 1,192
Date
1011012018
# of Units
1
INSULATION
Construction TyRe
Cavity
Area
ftz Special Features
Status
Roof Wood Framed Attic R 19
3,413
Existing
Slab Unheated Slab -on -Grade - no insulation
Demising Wood Framed R 13
3,413 Perim = 0'
1,556
Existing
Existing
Door Opaque Door -
no insulation
21
Existing
Roof Wood Framed Attic R 38
1,192 Cool Roof
New
Slab Unheated Slab -on -Grade - no insulation
1,192 Perim = 0'
New
Demising Wood Framed R 15
410
New
Wall Wood Framed R 21
830
New
FENESTRATION I Total Area: 537 Glazing Percentage: 11.7% Now/Altered Average U-Factor;
Orientation Area ft2 U-Fac SHGC Overhang Sidefins Exterior Shades
0.51
Status
Right (E) 48.3 0.510
0.24 none
none Bug Screen
Altered
Right (E) 10.0 0.590
0.40 none
none Bug Screen
Existing
Front (S) 40.0 0.510
0.24 none
none Bug Screen
Altered
Front (S) 114.1 0.590
0.40 6.0
none Bug Screen
Existing
Front (S) 30.0 0.590
0.40 2.0
none Bug Screen
Existing
Front (S) 80.0 0.590
0.40 8.0
none Bug Screen
Existing
Left (lM 12.0 0.590
0.40 none
none Bug Screen
Existing
Rear (N) 153.0 0.510
0.24 none
none Bug Screen
New
Left (M 50.0 0.510
0.24 none
none Bug Screen
New
HVAC SYSTEMS
Qty. Heating Min. Eff
Cooling
Min. Eff Thermostat
Status
2 Central Furnace 80% AFUE
Packaged Air Condition 14.0 SEER Setback
Altered
HVAC DISTRIBUTION
Location Heating
Cooling
Duct
Duct Location R-Value
Status
AC- Ducted
Ducted
Attic 8.0
Altered
WATER HEATING
Qty. Type Gallons Min. Eff Distribution
Status
EnenqyPro 7.1 by Ener-qySoft User Number: 20648
ID: 18 - GLS / 109 - 083
Paae 12 of 17
2016 Low -Rise Residential Mandatory Measures Summary
NOTE.' Low-rise residential buildings subject to the Energy Standards must comply with all applicable mandatory measures, regardless of the compliance approach
used. Review the respective section for more information. `Exceptions may apply.
Uf+ +nal Ut 2o1Yi
Building Envelope Measures:
§ 110.6(a)l:
Air Leakage. Manufactured fenestration, exterior doors, and exterior pet doors must limit air leakage to 0.3 cfm/ft' or less when tested per
NFRC-400 or ASTM E283 or AAMA/WDMAICSA 101/I.S.2/A440-2011.'
§ 110.6(a)5:
Labeling. Fenestration products must have a label meeting the requirements of § 10-111(a).
§ 110.6(b):
Field fabricated exterior doors and fenestration products must use U-factors and solar heat gain coefficient (SHGC) values from TABLES
110.6-A and 110.6-B for compliance and must be caulked and/or weatherstri ed.'
§ 110.7:
Air Leakage. All joints, penetrations, and other openings in the building envelope that are potential sources of air leakage must be caulked,
asketed, or weather stripped.
§ 110.8(a):
Insulation Certification by Manufacturers. Insulation specified or installed must meet Standards for Insulating Material.
§ 110.8(g):
Insulation Requirements for Heated Slab Floors. Heated slab floors must be insulated per the requirements of § 110.8(g).
Roofing Products Solar Reflectance and Thermal Emittance. The thermal emittance and aged solar reflectance values of the roofing
§ 110.8(i):
material must meet the requirements of § 110.8 i when the installation of a cool roof is specified on the CF1 R.
§ I10.80):
Radiant Barrier. A radiant barrier must have an emittance of 0.05 or less and be certified to the Department of Consumer Affairs.
Ceiling and Rafter Roof Insulation. Minimum R-22 insulation in wood -frame ceiling; or the weighted average U-factor must not exceed 0.043.
Minimum R-19 or weighted average U-factor of 0.054 or less in a rafter roof alteration. Attic access doors must have permanently attached
§ 150.0(a):
insulation using adhesive or mechanical fasteners. The attic access must be gasketed to prevent air leakage. Insulation must be installed in
direct contact with a continuous roof or ceiling which is sealed to limit infiltration and exfiltration as specified in § 110.7, including but not limited
to placing insulation either above or below the roof deck or on top of a drywall ceiling.'
§ 150.0(b):
Loose -fill Insulation. Loose fill insulation must meet the manufacturer's required density for the labeled R-value.
Wall Insulation. Minimum R-13 insulation in 2x4 inch wood framing wall or have a U-factor of 0.102 or less (R-19 in 2x6 or U-factor of 0.074 or
§ 150.0(c):
less). Opaque non -framed assemblies must have an overall assembly U-factor not exceeding 0.102, equivalent to an installed value of R-13 in a
wood framed assembly.*
§ 150.0(d):
Raised -floor Insulation. Minimum R-19 insulation in raised wood framed floor or 0.037 maximum U-factor.'
§ 150.0(f):
Slab Edge Insulation. Slab edge insulation must meet all of the following: have a water absorption rate, for the insulation material alone without
facings, no greater than 0.3%; have a water vapor permeance no greater than 2.0 perm/inch; be protected from physical damage and UV light
deterioration; and, when installed as part of a heated slab floor, meet the requirements of § 110.8(g).
Vapor Retarder. In Climate Zones 1-16, the earth floor of unvented crawl space must be covered with a Class I or Class II vapor retarder. This
§ 150.0(g)l:
requirement also applies to controlled ventilation crawls ace for buildings complying with the exce tion to § 1 50.0d .
Vapor Retarder. In Climate Zones 14 and 16, a Class I or Class II vapor retarder must be installed on the conditioned space side of all
§ 150.0(g)2:
insulation in all exterior walls, vented attics, and unvented attics with air -permeable insulation.
150.0
§ (q)'
Fenestration Products. Fenestration, including skylights, separating conditioned space from unconditioned space or outdoors must have a
maximum U-factor of 0.58; or the weighted average U-factor of all fenestration must not exceed 0.58.'
Fireplaces, Decorative Gas Appliances, and Gas Log Measures:
§ 150.0(e)lA:
Closable Doors. Masonry or factory -built fireplaces must have a closable metal or glass door covering the entire opening of the firebox.
§ 150.0(e)l B:
Combustion Intake. Masonry or factory -built fireplaces must have a combustion outside air intake, which is at least six square inches in area
and is equipped with a readily accessible, operable, and tight -fitting damper or combustion -air control device.'
§ 150.0(e)1C:
Flue Damper. Masonry or factory -built fireplaces must have a flue damper with a readily accessible control'
§ 150.0(e)2:
Pilot Light. Continuous burning pilot lights and the use of indoor air for cooling a firebox jacket, when that indoor air is vented to the outside of
the building,are lomolhibited.
Space Conditioning, Water Heating, and Plumbing System Measures:
§ 110.0-§ 110.3:
Certification. Heating, ventilation and air conditioning (HVAC) equipment, water heaters, showerheads, faucets, and all other regulated
appliances must be certified by the manufacturer to the EneTy Commission.'
§ 110.2(a):
_
HVAC Efficiency. Equipment must meet the applicable efficiency requirements in TABLE 110.2-A through TABLE 110.2-K.`
Controls for Heat Pumps with Supplementary Electric Resistance Heaters. Heat pumps with supplementary electric resistance heaters
§ 110.2(b):
must have controls that prevent supplementary heater operation when the heating load can be met by the heat pump alone; and in which the
cut -on temperature for compression heating is higher than the cut -on temperature for supplementary heating, and the cut-off temperature for
compression heating is higher than the cut-off temperature for supplementary heatin .'
§ 110.2(c):
Thermostats. All unitary heating or cooling systems not controlled by a central energy management control system (EMCS) must have a
setback thermostat.'
Water Heating Recirculation Loops Serving Multiple Dwelling Units. Water heating recirculation loops serving multiple dwelling units must
§ 110.3(c)5:
meet the air release valve, backflow prevention, pump priming, pump isolation valve, and recirculation loop connection requirements of §
11 0.3c 5.
§ 110.3(c)7:
Isolation Valves. Instantaneous water heaters with an input rating greater than 6.8 kBTU/hr (2 kW) must have isolation valves with hose bibbs
or other fittings on both cold water and hot water lines of water heating systems to allow for water tank Pushing when the valves are closed.
§ 110.5:
Pilot Lights. Continuously burning pilot lights are prohibited for natural gas: fan -type central furnaces; household cooking appliances (appli-
ances without an electrical supply voltage connection with pilot lights that consume less than 150 Btu/hr are exempt); and pool and spa heaters.'
Building Cooling and Heating Loads. Heating and/or cooling loads are calculated in accordance with ASHRAE Handbook, Equipment
§ 150.0(h)l:
Volume, Applications Volume, and Fundamentals Volume; SMACNA Residential Comfort System Installation Standards Manual; or ACCA
Manual J using design conditions s ecified in 150.0�.
2016 Low -Rise Residential Mandatory Measures Summary
§ 150.0(h)3A:
Clearances. Installed air conditioner and heat pump outdoor condensing units must have a clearance of at least 5 feet from the outlet of any
dryer vent.
§ 150.0(h)3B:
Liquid Line Drier. Installed air conditioner and heat pump systems must be equipped with liquid line filter driers if required, as specified by
manufacturer's instructions.
§ 150.00)1:
Storage Tank Insulation. Unfired hot water tanks, such as storage tanks and backup storage tanks for solar water -heating systems, must have
R-12 external insulation or R-16 internal insulation where the internal insulation R-value is indicated on the exterior of the tank.
Water piping and cooling system line insulation. For domestic hot water system piping, whether buried or unburied, all of the following must
be insulated according to the requirements of TABLE 120.3-A: the first 5 feet of hot and cold water pipes from the storage tank; all piping with a
§ 150.00)2A:
nominal diameter of 3/4 inch or larger; all piping associated with a domestic hot water recirculation system regardless of the pipe diameter;
piping from the heating source to storage tank or between tanks; piping buried below grade; and all hot water pipes from the heating source to
kitchen fixtures.`
§ 150.00)26:
Water piping and cooling system line insulation. All domestic hot water pipes that are buried below grade must be installed in a water proof
and non -crushable casin2 or sleeve.'
§ 150.00)2C:
Water piping and cooling system line insulation. Pipe for cooling system lines must be insulated as specified in § 150.00)2A. Distribution
piping for steam and h dronic heating systems or hot waters stems must meet the requirements in TABLE 120.3-A.'
§ 150.00)3:
Insulation Protection. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind.
Insulation Protection. Insulation exposed to weather must be installed with a cover suitable for outdoor service. For example, protected by
§ 150.00)3A:
aluminum, sheet metal, painted canvas, or plastic cover. The cover must be water retardant and provide shielding from solar radiation that can
cause degradation of the material.
§ 150.00)3B:
Insulation Protection. Insulation covering chilled water piping and refrigerant suction piping located outside the conditioned space must have a
Class I or Class 11 vapor retarder.
Gas or Propane Systems. Systems using gas or propane water heaters to serve individual dwelling units must include all of the following: a
§ 150.0(n)1:
120V electrical receptacle within 3 feet of the water heater; a Category III or IV vent, or a Type B vent with straight pipe between the outside
termination and the space where the water heater is installed; a condensate drain that is no more than 2 inches higher than the base of the
water heater, and allows natural draining without pump assistance; and a gas supply line with a capacity of at least 200,000 Btu/hr.
§ 150.0(n)2:
Recirculating Loops. Recirculating loops serving multiple dwelling units must meet the requirements of § 110.3(c)5.
§ 150.0(n)3:
Solar Water -heating Systems. Solar water -heating systems and collectors must be certified and rated by the Solar Rating and Certification
Corporation SRCC) or by a listing agency that is approved by the Executive Director.
Ducts and Fans Measures:
§ 110.8(d)3:
Ducts. Insulation installed on an existing space -conditioning duct must comply with § 604.0 of the California Mechanical Code (CMC). If a
contractor installs the insulation, the contractor must certify to the customer, in writing, that the insulation meets this requirement.
CMC Compliance. All air -distribution system ducts and plenums must be installed, sealed, and insulated to meet the requirements of CMC
§§ 601.0, 602.0, 603.0, 604.0, 605.0 and ANSIISMACNA-006-2006 HVAC Duct Construction Standards Metal and Flexible 3rd Edition. Portions
of supply -air and return -air ducts and plenums must be insulated to a minimum installed level of R-6.0 (or higher if required by CMC § 605.0) or
a minimum installed level of R-4.2 when entirely in conditioned space as confirmed through field verification and diagnostic testing
§ 150.0(m)1:
(RA3.1.4.3.8). Connections of metal ducts and inner core of flexible ducts must be mechanically fastened. Openings must be sealed with
mastic, tape, or other duct -closure system that meets the applicable requirements of UL 181, UL 181A, or UL 181B or aerosol sealant that
meets the requirements of UL 723. If mastic or tape is used to seal openings greater than'/< inch, the combination of mastic and either mesh or
tape must be used. Building cavities, support platforms for air handlers, and plenums designed or constructed with materials other than sealed
sheet metal, duct board or flexible duct must not be used for conveying conditioned air. Building cavities and support platforms may contain
ducts. Ducts installed in cavities and support platforms must not be compressed to cause reductions in the cross -sectional area of the ducts.'
Factory -Fabricated Duct Systems. Factory -fabricated duct systems must comply with applicable requirements for duct construction,
§ 150.0(m)2:
connections, and closures; joints and seams of duct systems and their components must not be sealed with cloth back rubber adhesive duct
tapes unless such toe is used in combination with mastic and draw bands.
§ 150.0(m)3:
Field -Fabricated Duct Systems. Field -fabricated duct systems must comply with applicable requirements for: pressure -sensitive tapes,
mastics, sealants, and other requirements specified for duct construction.
§ 150.0(m)7:
Backdraft Dampers. All fan systems that exchange air between the conditioned space and the outside of the building must have backdraft or
automatic dampers.
§ 150.0(m)8:
Gravity Ventilation Dampers. Gravity ventilating systems serving conditioned space must have either automatic or readily accessible,
manually operated dampers in all openings to the outside, except combustion inlet and outlet air openings and elevator shaft vents.
Protection of Insulation. Insulation must be protected from damage, including that due to sunlight, moisture, equipment maintenance, and
§ 150.0(m)9:
wind. Insulation exposed to weather must be suitable for outdoor service. For example, protected by aluminum, sheet metal, painted canvas, or
plastic cover. Cellular foam insulation must be protected as above or painted with a coating that is water retardant and provides shielding from
solar radiation.
§ 150.0(m)10:
Porous Inner Core Flex Duct. Porous inner core flex duct must have a non -porous layer between the inner core and outer vapor barrier.
Duct System Sealing and Leakage Test. When space conditioning systems use forced air duct systems to supply conditioned air to an
§ 150.0(m)11:
occupiable space, the ducts must be sealed and duct leakage tested, as confirmed through field verification and diagnostic testing, in
accordance with § 150.0 m 11 and Reference Residential Appendix RA3.
Air Filtration. Mechanical systems that supply air to an occupiable space through ductwork exceeding 10 feet in length and through a thermal
§ 150.0(m)12:
conditioning component, except evaporative coolers, must be provided with air filter devices that meet the design, installation, efficiency,
pressure drop, and labeling requirements of § 150.0(m)12.
Z2016 Low -Rise Residential Mandatory Measures Summary
Duct System Sizing and Air Filter Grille Sizing. Space conditioning systems that use forced air ducts to supply cooling to an occupiable
space must have a hole for the placement of a static pressure probe (HSPP), or a permanently installed static pressure probe (PSPP) in the
§ 150.0(m)13:
supply plenum. The space conditioning system must also demonstrate airflow z 350 CFM per ton of nominal cooling capacity through the return
grilles, and an air -handling unit fan efficacy:5 0.58 WICFM as confirmed by field verification and diagnostic testing, in accordance with
Reference Residential Appendix RA3.3. This applies to both single zone central forced air systems and every zone for zonally controlled central
forced air systems.'
Ventilation for Indoor Air Quality. All dwelling units must meet the requirements of ASHRAE Standard 62.2. Neither window operation nor
§150.0(o):
continuous operation of central forced air system air handlers used in central fan integrated ventilation systems are permissible methods of
providinq whole -building ventilation.
§ 150.0(o)1A:
Field Verification and Diagnostic Testing. Whole -building ventilation airflow must be confirmed through field verification and diagnostic
testin , in accordance with Reference Residential Appendix RA3.7.
Pool and Spa Systems and Equipment Measures:
Certification by Manufacturers. Any pool or spa heating system or equipment must be certified to have all of the following: a thermal efficiency
§ 110.4(a):
that complies with the Appliance Efficiency Regulations; an on -off switch mounted outside of the heater that allows shutting off the heater
without adjusting the thermostat setting; a permanent weatherproof plate or card with operating instructions; and must not use electric
resistance heating.'
§ 110.4(b)1:
Piping. Any pool or spa heating equipment must be installed with at least 36 inches of pipe between the filter and the heater, or dedicated
suction and return lines, or built-in or built-up connections to allow for future solar heating.
§ 110.4(b)2:
Covers. Outdoor pools or spas that have a heat pump or gas heater must have a cover.
§ 110.4(b)3:
Directional inlets and time switches for pools. Pools must have directional inlets that adequately mix the pool water, and a time switch that
will allow all pumps to be set or programmed to run only during off-peak electric demand periods.
§ 110.5:
Pilot Light. Natural gas pool and spa heaters must not have a continuously burning pilot light.
150.0
§ (p)'
Pool Systems and Equipment Installation. Residential pool systems or equipment must meet the specified requirements for pump sizing, flow
rate piping, filters and valves.`
Lighting Measures:
§ 110.9:
Lighting Controls and Components. All lighting control devices and systems, ballasts, and luminaires must meet the applicable requirements
of § 110.9:
§ 110.9(e):
JA8 High Efficacy Light Sources. To qualify as a JA8 high efficacy light source for compliance with § 150.0(k), a residential light source must
be certified to the Energy Commission according to Reference Joint Appendix JA8.
§ 150.0(k)1A:
Luminaire Efficacy. All installed luminaires must be high efficacy in accordance with TABLE 150.0-A.
Blank Electrical Boxes. The number of electrical boxes that are more than 5 feet above the finished floor and do not contain a luminaire or
§ 150.0(k)1 B:
other device must be no greater than the number of bedrooms. These electrical boxes must be served by a dimmer, vacancy sensor control, or
fan speed control.
Recessed Downlight Luminaires in Ceilings. Luminaires recessed into ceilings must meet all of the requirements for: insulation contact (IC)
§ 150.0(k)1 C:
labeling; air leakage; sealing; maintenance; and socket and light source as described in § 150.0(k)1 C. A JA8-2016-E light source rated for
elevated temperature must be installed by final inspection in all recessed downli ht luminaires in ceilings.
§ 150.0(k)1 D:
Electronic Ballasts. Ballasts for fluorescent lamps rated 13 watts or greater must be electronic and must have an output frequency no less than
20 kHz.
Night Lights. Permanently installed night lights and night lights integral to installed luminaires or exhaust fans must be rated to consume no
§ 150.0(k)1 E:
more than 5 watts of power per luminaire or exhaust fan as determined in accordance with § 130.0(c). Night lights do not need to be controlled
by vacancy sensors.
§ 150.0(k)1 F:
Lighting Integral to Exhaust Fans. Lighting integral to exhaust fans (except when installed by the manufacturer in kitchen exhaust hoods)
must meet the applicable requirements of § 150.0(k).*
Screw based luminaires. Screw based luminaires must not be recessed downlight luminaires in ceilings and must contain lamps that comply
§ 150.0(k)1 G:
with Reference Joint Appendix JA8. Installed lamps must be marked with "JA8-2016" or "JA8-2016-E" as specified in Reference Joint Appendix
JAB.`
§ 150.0(k)1 H:
Enclosed Luminaires. Light sources installed in enclosed luminaires must be JA8 compliant and must be marked with "JA8-2016-E."
§ 150.0(k)2A:
Interior Switches and Controls. All forward phase cut dimmers used with LED light sources must comply with NEMA SSL 7A.
§ 150.0(k)2B:
Interior Switches and Controls. Exhaust fans must be switched separately from lighting systems.'
§ 150.0(k)2C:
Interior Switches and Controls. Luminaires must be switched with readily accessible controls that permit the luminaires to be manually
switched ON and OFF.
§ 150.0(k)2D:
Interior Switches and Controls. Controls and equipment must be installed in accordance with manufacturer's instructions.
§ 150.0(k)2E:
Interior Switches and Controls. No control must bypass a dimmer or vacancy sensor function if the control is installed to comply with
150.0(k).
§ 150.0(k)2F:
Interior Switches and Controls. Lighting controls must comply with the applicable requirements of § 110.9.
Interior Switches and Controls. An energy management control system (EMCS) may be used to comply with dimmer requirements if it:
§ 150.0(k)2G;
functions as a dimmer according to § 110.9; meets the Installation Certificate requirements of § 130.4; meets the EMCS requirements of §
130.5 ; and meets all other requirements in § 150.0(k)2.
Interior Switches and Controls. An EMCS may be used to comply with vacancy sensor requirements in § 150.0(k) if it meets all of the
§ 150.0(k)2H:
following: it functions as a vacancy sensor according to § 110.9; the Installation Certificate requirements of § 130.4; the EMCS requirements of §
130.5 ; and all other requirements in § 150.0(k)2.
§ 150.0(k)21:
Interior Switches and Controls. A multiscene programmable controller may be used to comply with dimmer requirements in § 150.0(k) if it
provides the functionality of a dimmer according to § 110.9, and complies with all other applicable requirements in 5 150.0(k)2.
2016 Low -Rise Residential Mandatory Measures Summary
§ 150.0(k)2J:
Interior Switches and Controls. In bathrooms, garages, laundry rooms, and utility rooms, at least one luminaire in each of these spaces must
be controlled by a vacancy sensor.
§ 150.0(k)2K:
Interior Switches and Controls. Dimmers or vacancy sensors must control all luminaires required to have light sources compliant with
Reference Joint Appendix JA8, except luminaires in closets less than 70 square feet and luminaires in hallways.'
§ 150.0(k)2L:
Interior Switches and Controls. Undercabinet lighting must be switched separately from other lighting systems.
Residential Outdoor Lighting. For single-family residential buildings, outdoor lighting permanently mounted to a residential building, or to other
§ 150.0(k)3A:
buildings on the same lot, must meet the requirement in item § 150.0(k)3Ai (ON and OFF switch) and the requirements in either item
§ 150.0(k)3Aii (photocell and motion sensor) or item § 150.0(k)3Aiii (photo control and automatic time switch control, astronomical time clock, or
EMCS.
Residential Outdoor Lighting. For low-rise multifamily residential buildings, outdoor lighting for private patios, entrances, balconies,
§ 150.0(k)38:
and porches; and outdoor lighting for residential parking lots and residential carports with less than eight vehicles per site must comply with
either § 150.0 k 3A or with the applicable requirements in §§ 110.9, 130.0, 130.2, 130.4, 140.7 and 141.0.
§ 150.0(k)3C:
Residential Outdoor Lighting. For low-rise residential buildings with four or more dwelling units, outdoor lighting not regulated by
150.0 k 3B or § 150,0 k 3D must comply with the applicable requirements in §§ 110.9, 130.0, 130.2, 130.4, 140.7 and 141.0.
§ 150.0(k)3D:
Residential Outdoor Lighting. Outdoor lighting for residential parking lots and residential carports with a total of eight or more
vehicles per site must com I with the applicable requirements in 5§ 110.9, 130.0, 130.2, 130.4, 140.7, and 141.0.
§ 150.0(k)4:
Internally illuminated address signs. Internally illuminated address signs must comply with § 140.8; or must consume no more than 5 watts of
power as determined according to § 130.0(G).
§ 150.0(k)5:
Residential Garages for Eight or More Vehicles. Lighting for residential parking garages for eight or more vehicles must comply with the
applicable requirements for nonresidential garages in §§ 110.9 130.0, 130.1, 130.4,140.6, and 141.0.
Interior Common Areas of Low-rise Multi -Family Residential Buildings. In a low-rise multifamily residential building where the total interior
§ 150.0(k)6A:
common area in a single building equals 20 percent or less of the floor area, permanently installed lighting for the interior common areas in that
building must be high efficacy luminaires and controlled by an occupant sensor.
Interior Common Areas of Low-rise Multi -Family Residential Buildings. Ina low-rise multifamily residential building where the total interior
common area in a single building equals more than 20 percent of the floor area, permanently installed lighting in that building must:
§ 150.0(k)6B:
I. Comply with the applicable requirements in §§ 110.9, 130.0, 130.1, 140.6 and 141.0; and
ii. Lighting installed in corridors and stairwells must be controlled by occupant sensors that reduce the lighting power in each space by at least
50 percent. The occupant sensors must be capable of turning the light fully on and off from all desi ned paths of ingress and egress.
Solar Ready Buildings:
Single Family Residences. Single family residences located in subdivisions with ten or more single family residences and where the
§ 110.10(a)1:
application for a tentative subdivision map for the residences has been deemed complete by the enforcement agency must comply with the
requirements of § 110.10(b) throw h § 110.10 e .
§ 110.10(a)2:
Low-rise Multi -family Buildings. Low-rise multi -family buildings must comply with the requirements of § 110.10(b) through § 110.10(d).
Minimum Area. The solar zone must have a minimum total area as described below. The solar zone must comply with access, pathway, smoke
ventilation, and spacing requirements as specified in Title 24, Part 9 or other Parts of Title 24 or in any requirements adopted by a local
jurisdiction. The solar zone total area must be comprised of areas that have no dimension less than 5 feet and are no less than 80 square feet
each for buildings with roof areas less than or equal to 10,000 square feet or no less than 160 square feet each for buildings with roof areas
§ 110.10(b)1:
greater than 10,000 square feet.
For single family residences the solar zone must be located on the roof or overhang of the building and have a total area no less than 250
square feet. For low-rise multi -family buildings the solar zone must be located on the roof or overhang of the building, or on the roof or overhang
of another structure located within 250 feet of the building, or on covered parking installed with the building project, and have a total area no less
than 15 percent of the total roof area of the building excluding any skylight area.'
§ 110.10(b)2:
Orientation. All sections of the solar zone located on steep -sloped roofs must be oriented between 110 degrees and 270 degrees of true north.
§ 110.10(b)3A:
Shading. The solar zone must not contain any obstructions, including but not limited to: vents, chimneys, architectural features, and roof
mounted equipment'
Shading. Any obstruction located on the roof or any other part of the building that projects above a solar zone must be located at least twice the
§ 110.10(b)3B:
distance, measured in the horizontal plane, of the height difference between the highest point of the obstruction and the horizontal projection of
the nearest point of the solar zone, measured in the vertical lane'
Structural Design Loads on Construction Documents. For areas of the roof designated as solar zone, the structural design loads for roof
§ 110.10(b)4:
dead load and roof live load must be clearly indicated on the construction documents.
Interconnection Pathways. The construction documents must indicate: a location for inverters and metering equipment and a pathway for
§ 110.10(c):
routing of conduit from the solar zone to the point of interconnection with the electrical service (for single family residences the point of
interconnection will be the main service panel); and a pathway for roWng of plumbing from the solar zone to the water-heati swam.
Documentation. A copy of the construction documents or a comparable document indicating the information from § 110.10(b) through
§ 110.1 Old):
110.10 c must be provided to the occupant.
§ 110.10(e)1:
Main Electrical Service Panel. The main electrical service panel must have a minimum busbar rating of 200 amps.
Main Electrical Service Panel. The main electrical service panel must have a reserved space to allow for the installation of a double pole circuit
§ 110.10(e)2:
breaker for a future solar electric installation. The reserved space must be: positioned at the opposite (load) end from the input feeder location or
main circuit location; and permanently marked as "For Future Solar Electric".
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
Project Name
MURRAY RESIDENCE'S addition
System Name
AC-
Date
10/10/2018
Floor Area
4,605
ENGINEERING CHECKS
SYSTEM LOAD
Number of Systems
2
LCFM
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL
5,388
0
COOLING
PEAK
COIL HTG.
PEAK
Heating System
Sensible
Latent
CFM
Sensible
Output perSystem
100,000
49,239
1,621
1,292
37,303
Total Output Btuh
200,000
0
Output Btuh/s ft
43.4
2,842
1,833
Cooling System
0
0
Output perSystem
58,000
0
0
0
0
Total Output Btuh
116,000
0
1,621
0
Total Output(Tons)
9•7
2,842
1,833
Total Output Btuhls ft
25.2
Total Output s ftrron
476.4
54,924
40,969
Air System
CFM perSystem
3,400
HVAC EQUIPMENT SELECTION
Airflow cfm
6,800
RTU 5-TON 14/11/0.80 SEER/EER/AFUE
67,831
29,841
200,000
Airflow cfm/s ft
1.48
Airflow cfmrron
703.4
Total Adjusted System Output
(Adjusted for Peak Design conditions)
1 TIME OF SYSTEM PEAK
200,000
Jan 1 AM
Outside Air %
0•0%
67,831
29,841
Outside Air cfm/s ft
0.00
Note: values above given at ARI conditions
Aug 3 PM
HEATING SYSTEM PSYCHROMETRICS
Airstream Tem eratures at Time of Heating Peak
26 OF 68 OF 68 OF 95 OF
•
Outside Air -
0 cfm Supply Fan Heating Coil
6,800 cfm
68 IF f I!
ROOM An
68 IF
COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak
112 l73 OF 75 / 62 OF 75 / 62 OF 66 / 58 °F
Outside A-' ❑ _
0 cfm Supply Fan Cooling Coil
6,800 cfm
75 / 62 IF
T�-� '
46.4%
1
66 ! 58 OF
ROOM
75161 OF
EnergyPro 7.1 by EnergySoit
User Number: 20648
ID: 18 - GLS / 109 - 083 Page 17 of 17