04-8046 (SFD) Title 24V
TITLE 24- REPORT
Title 24 Report for:
CASA ESTELLA
78225 Calle Cadiz
La Quinta, Ca 92253
Project Designer:
LENCH DESIGN STUDIO, INC.
P.O. BOX 450
LA QUINTA, CA 92247-0450
760/564-1866
Report Prepared By:
VERNA LENCH
Lench Design Studio, Inc.
P.O. Box 450
La Quinta, CA 92247-0450
(760) 564-1866
Job Number:
3.1-1316
CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
APPROVED.
FOR CONSTRUCTION
DATE -d ---Z 7O-5�r5,7
iOrrlcC
Date:
12/17/2004
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2001 Building Energy Efficiency Standards.
This program developed by Gabel Dodd/EnergySoft, LLC (415) 883-5900.
EnergyPro 3.1 By EnergySoft Job Number: 3.1-1316 User Number: 5454
I i TABLE OF CONTENTS
Cover Page
Table of Contents
Form CF -1 R Certificate of Compliance
Form MF -1 R Mandatory Measures Checklist
Form C -2R Computer Method Summary
HVAC System Heating and Cooling Loads Summary
Room Load Summary
Room Heating Peak Loads
Room Cooling Peak Loads
1
2
3
7
8
15
18
21
24
EnergyPro 3.1 By EnergySoft Job Number: 3.1-1316 User Number: 5454
Certificate of Compliance: Residential (Part 1 of 2) CF -1 R
CASA ESTELLA 12/17/2004
Project Title Date
78225 Calle Cadiz La Quinta
Project Address Building Permit #
Lench Design Studio, Inc. (760) 564-1866 Plan Check /Date
Documentation Author Telephone
Computer Performance 15 Field Check / Date
Compliance Method (Package or Computer) Climate Zone Enforcement Agency Use Only
GENERAL INFORMATION
Total Conditioned Floor Area: 4,075 f? Average Ceiling Height: 10.0 ft
Total Conditioned Slab Area: 4,075 ft2
Building Type:
(check one or more)
X❑ Single Family Detached ❑ Addition
❑ Single Family Attached ❑ Existing Building
❑ Multi -Family ❑ Existing Plus Addition
Front Orientation: (North) 0 deg Floor Construction Type: ® Slab Floor
Number of Dwelling Units: 1.00
Number of Stories: 1 ❑ Raised Floor
Location/Comments
attic, garage, typical, etc.
Exterior Roof
Exposed Slab w/R-0.0 Perimeter Insulation
Exterior Wall
Exterior Door
Exterior Wall
Covered Slab w/R-0.0 Perimeter Insulation
FENESTRATION Shading Devices
Type
Orientation
Const.
Component
Frame
Assembly
Type
Type
U -Value
R-38 Roof (R.38.2x14.16)
Wood
0.028
Slab On Grade
n/a
0.756
R-19 Wall (W.19.2x6.16)
Wood
0.065
Solid Wood Door
None
0.387
R-19 Wall w/1" EPS
Wood
0.045
Slab On Grade
n/a
0.756
Location/Comments
attic, garage, typical, etc.
Exterior Roof
Exposed Slab w/R-0.0 Perimeter Insulation
Exterior Wall
Exterior Door
Exterior Wall
Covered Slab w/R-0.0 Perimeter Insulation
FENESTRATION Shading Devices
Type
Orientation
Area
Fenestration
Exterior
Overhang Side Fins
• SF
U -Factor
SHGC
Shading
Yes / No
Yes
/ No
Skylight
4.8
0.71
0.50
None
❑
X❑
❑
X❑
Left
(East)
22.5
0.60
0.37
Bug Screen
❑
Q
❑
0
Left
(East)
96.0
0.74
0.37
Bug Screen
❑
Q
❑
Q
Rear
(South)
18.0
0.60
0.37
Bug Screen
❑
0
❑
X❑
Rear
(South)
101.3
0.46
0.37
Bug Screen
❑
0
❑
0
Right
(Wgst)
40.0
0.74
0.37
Bug Screen
❑X
❑
❑x❑
Front
(North)
45.0
0.60
0.37
Bug Screen
❑
X❑
❑
x❑
Front
(North)
68.4
0.46
0.37
Bug Screen
❑
x❑
❑
❑x
Front
(Northeast)
23.6
0.46
0.37
Bug Screen
❑
X❑
❑
X❑
Right
(Northwest)
5.6
0.46
0.37
Bug Screen
❑
X❑
❑
X❑
Front
(North)
18.0
0.61
0.39
Bug Screen
❑
X❑
❑
x❑
Rear
(Souter .
192.0
0.74
0.37
Bug Screen
x❑
❑
❑
X❑
Run Initiation Time: 12/17/04 09:12:27 Run Code: 1103303547
EnergyPro
3.1 By Ener
oft
User Number: 5454
Job Number: 3.1-1316
Pa e:3 of 29
Certificate of Compliance: Residential (Part 1 of 2) CF -1 R
CASA ESTELLA 12/17/2004
Project Title Date
78225 Calle Cadiz La Quinta
Project Address Building Permit #
Lench Design Studio, Inc. (760) 564-1866 Plan Check / Date
Documentation Author Telephone
Computer Performance 15 Field Check / Date
Compliance Method (Package or Computer) Climate Zone Enforcement Agency Use Only
GENERAL INFORMATION
Total Conditioned Floor Area: 4,075 ft2 Average Ceiling Height: 10.0 ft
Total Conditioned Slab Area: 4,075 ft2
Building Type:
(check one or more)
X❑ Single Family Detached ❑ Addition
❑ Single Family Attached ❑ Existing Building
❑ Multi -Family ❑ Existing Plus Addition
Front Orientation: (North) 0 deg Floor Construction Type: ® Slab Floor
Number of Dwelling Units: 1.00
Number of Stories: 1 ❑ Raised Floor
Const.
Component Frame Assembly Location/Comments
Type Type U -Value (attic, garage, typical, etc.)
FENESTRATION
Shadinq Devices
Type
Orientation
Area
Fenestration
Exterior
Overhang Side Fins
SF
U -Factor
SHGC
Shading
Yes / No
Yes / No
Rear
(South)
85.5
0.46
0.37
Bug ScreenX❑
❑
❑ x❑
Rear
(South)
6.0
1.28
0.80
Bug Screen
❑
❑ o
Left
(East)
9.6
0.46
0.37
Bug Screen❑
X❑
❑ ❑x
Right
(West)
12.0
0.46
0.37
Bug Screen(
y]
❑ ❑x
Right
(West)
42.0
0.61
0.39
Bug Screen❑
X❑
❑ X❑
Front
(North)
9.0
0.62
0.38
Bug Screen❑
X❑
❑ x❑
Right
(West)
9.0
0.62
0.38
Bug Screen
❑
o
❑ o
Rear
(South)
36.0
0.61
0.39
Bug Screen
❑X❑
❑ ❑x
❑
❑
❑ ❑
El
1:1
El F-1
❑
❑
❑ ❑
EJ
EJ
El El
Run Initiation Time: 12/17/04 09:12:27 Run Code: 1103303547
EnergyPro
3.1 By Energ
ySoft
User Number: 5454
Job Number: 3.1-1316
Pa e:4 of 29
' Certificate of Compliance: Residential (Part 2 of 2) CF -1 R
CASA ESTELLA 12/17/2004
Project Title Date
HVAC SYSTEMS Note: Input Hydronic or Combined Hydronic data under Water Heating Systems, except Design Heating Load.
Distribution
Heating Equipment Minimum Type and Duct or
Type (furnace, heat Efficiency Location Piping Thermostat Location /
pump, etc.) (AFUE/HSPF)(ducts, attic, etc.) R -Value Type Comments
Central Fumare 80% AFUE Ducts in Attic 42 Setback HVAC System - Zone 1
Central gurnace 80% AFUE Ducts in Attir. 42 Sethark HVAC S..ystPm - Zone 2
Central Furnace 80% AFUE Ducts in Attic 4.2 Setback HVAC System - Zone 3
Cooling Equipment Minimum Duct
Type (air conditioner, Efficiency Location Duct Thermostat Location /
heat pump, evap. cooling) (SEER) (attic, etc.) R -Value Type Comments
Split Air Conditioner
Split Air Conditioner
Split Air Conditioner
WATER HEATING SYSTEMS
Rated 1
Tank
Energy Facts 1
External
Water Heater Water Heater Distribution
# in Input
Cap.
or Recovery Standby
Tank Insul.
System Name Type Type
Syst. Btu/hr
(gal)
Efficiency Loss (%)
R -Value
A.O. SMITH FPS -75-230 Small Gas Recirc/Demand
1_ 75,000
75
0.52 n/a
12
1 For small gas storage (rated inputs of less than or equal to 75,000 Btu/hr), electric resistance and heat pump water heaters, list energy factor.
For large gas storage water heaters (rated input of greater than 75,000 Btu/hr), list Rated Input, Recovery Efficiency and Standby Loss.
For instantaneous gas water heaters, list Rated Input and Recovery Efficiency.
REMARKS
AUTHORIZATION FOR USE OF THIS TITLE 24 REPORT ONLY WITH ORIGINAL SIGNATURES.
NO DUPLICATION PERMITTED!
COMPLIANCE STATEMENT
This certificate of compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations, and the administrative regulations to implement them. This certificate has been signed by the individual with
overall design responsibility. When this certificate of compliance is submitted for a single building plan to be built in multiple orientations, any
shading feature that is varied is indicated in the Special Features/Remarks section.
Designer or Owner (per Business & Professions Code) Documentation Author
Name:
Title/Firm: LENCH DESIGN STUDIO, INC.
Address: P.Q BOX 450
Telephon9 60/564-1866
Lic. #: A
Age
Name: _
Title/Firm: _
Address:
Telephone_
/Z . /7.v
Name: VERNA LENCH
Title/Firm: Lench Design Studio, Inc.
Address: P.O. Box 450
La Quinta, CA 92247-0450
Telephone: (760) 564-1866
a
signature) (d e)
(signature/stamp) (date)
Run Initiation Time: 12/17/04 09:12:27 Run Code: 1103303547
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page:5 of 29
Certificate of Compliance: Residential (Addendum) CF -1 R
CASA ESTELLA 12/17/2004
Project Title Date
Special Features and Modeling Assumptions
The local enforcement agency should pay special attention to the items specified in this checklist. These items require special
written justification and documentation, and special verification to be used with the performance approach. The local
enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies
based on the adequacy of the special justification and documentation submitted. Plan Field
The DHW System "A.O. SMITH FPS -75-230" Energy Factor = 0.520. An EF below 0.58 requires an R-12 External Blanket.
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 0 sqft Covered Slab Floor, 3.50" thick at Zone 1
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 789 sqft Exposed Slab Floor, 3.50" thick at Zone 1
The HVAC System "HVAC System - Zone 2" includes credit for a Radiant Barrier installed per Section 8.13 of the Residential Manual.
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 216 sqft Covered Slab Floor, 3.50" thick at Zone 2
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 1055 sqft Exposed Slab Floor, 3.50" thick at Zone 2
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 1543 sqft Covered Slab Floor, 3.50" thick at Zone 3
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 472 sqft Exposed Slab Floor, 3.50" thick at Zone 3
HERS Required Verification
These features must be confirmed and/or tested by a certified HERS rater under the supervision of a CEC approved HERS
provider. The HERS rater must document the field verification and diagnostic testing of these measures on a form CF -6R.
Plan
Field
The HVAC System "HVAC System - Zone 1" is using reduced duct leakage to comply and must have diagnostic site testing of duct
leakage performed by a certified HERS Rater. The results of the diagnostic testing must be reported on a CF -6R Form.
The HVAC System "HVAC System - Zone 2" is using reduced duct leakage to comply and must have diagnostic site testing of duct
leakage performed by a certified HERS Rater. The results of the diagnostic testing must be reported on a CF -6R Form.
The HVAC System "HVAC System - Zone 3" is using reduced duct leakage to comply and must have diagnostic site testing of duct
leakage performed by a certified HERS Rater. The results of the diagnostic testing must be reported on a CF -6R Form.
I EneravPro 3.1 By EnemySoft User Number: 5454 Job Number: 3.1-1316 Paae:6 of 29 I
Mandatory Measures Checklist: Residential MF -1 R
NOTE: Lowrise residential buildings subject to the Standards must contain these measures regardless of the compliance approach used. Items marked with an
asterisk (') may be superseded by more stringent compliance requirements listed on the Certificate of Compliance. When this checklist is incorporated into
the permit documents, the features noted shall be considered by all parties as minimum component specifications for the mandatory measures whether they
are shown elsewhere in the documents or on this checklist only.
DESCRIPTION Instructions: Check or initial applicable boxes or enter N/A if not applicable.
DESIGNER JENFORCEMEN1
Building Envelope Measures
F'§150(a): Minimum R-19 ceiling insulation in wood frame assembly, or equivalent U -value.
❑ §150(b): Loose fill insulation manufacturer's labeled R -Value.
.§150(c): Minimum R-13 wall insulation in wood framed walls or equivalent U -value in metal frame walls (does not apply to
exterior mass walls).
❑ '§ 150(d): Minimum R-13 raised floor insulation in framed floors.
❑ § 150(1): Slab edge insulation - water absorption rate <= 0.3%, water vapor transmission rate <= 2.0 perm/inch.
❑X §118: Insulation specified or installed meets insulation quality standards. Indicate type and form.
❑X §116-17: Fenestration Products, Exterior Doors and Infiltration/Exfiltration Controls
1. Doors and windows between conditioned and unconditioned spaces designed to limit air leakage.
2. Fenestration products (except field fabricated) have label with certified U -Factor, certified SHGC, and infiltration certification.
3. Exterior doors and windows weatherstripped; all joints and penetrations caulked and sealed.
§150(g): Vapor barriers mandatory in Climate Zones 14 and 16 only.
§150(f): Special infiltration barrier installed to comply with Section 151 meets Commission quality standards.
® §150(e): Installation of Fireplaces, Decorative Gas Appliances and Gas Logs.
1. Masonry and factory -built fireplaces have closable doors, outside air intake with damper and control, and flue
damper and control;
2. No continuous buming gas pilots allowed.
Space Conditioning, Water Heating and Plumbing System Measures
§110-13: HVAC equipment, water heaters, showerheads and faucets certified by the Commission.
X] §150(h): Heating and/or cooling loads calculated in accordance with ASHRAE, SMACNA or ACCA.
§150(i): Setback thermostat on all applicable heating and/or cooling systems.
X❑ §1500): Pipe and Tank Insulation
1. Storage gas water heaters with less than 0.58 energy factor shall be externally wrapped with R-12.
2. First 5 feet of pipes closest to water heater tank, non -recirculating systems, insulated (R-4 or greater)
3. Back-up tanks for solar system, unfired storage tanks, or other indirect hot water tanks have R-12 external insulation or R-16
combined internal/external insulation.
4. All buried or exposed piping insulated in recirculating sections of hot water systems.
5. Cooling system piping below 55 degrees F. insulated.
6. Piping insulating between heating source and indirect hot water tank.
X❑ '§150(m): Ducts and Fans
1. All ducts and plenums installed, sealed and insulated to meet the requirements of the 1998 CMC Sections 601, 603, 604 and
Standard 6-3; ducts insulated to a minimum installed level of R-4.2 or enclosed in conditioned space. Openings shall be sealed
with mastic, tape aerosol sealant or other duct- closure system that meets the applicable requirements of UL181, UL181A, or
UL181 B. If mastic or tape is used to seal openings greater than 1/4 inch, the combination of mastic and either mesh tape or
tape shall be used. Building cavities shall not be used for conveying conditioned air. Joints and seams of duct systems and
their components shall not be sealed with cloth back rubber adhesive duct tapes unless such tape is used in combination with
mastic and drawbands.
2. Exhaust fans systems have back draft or automatic dampers.
3. Gravity ventilating systems serving conditioned space have either automatic or readily accessible, manually operated dampers.
X1 §114: Pool and Spa Heating Systems and Equipment
1. Certified with 78% thermal efficiency, on-off switch, weatherproof instructions, no electric resistance heating, no pilot.
2. System is installed with at least 36" of pipe between filter and heater for future solar, cover for outdoor pools or spas.
3. Pool system has directional inlets and a circulation pump time switch.
FX§115: Gas fired central furnaces, pool heaters, spa heaters or household cooking appliances have no continuously burning pilot
light. (Exception: Non -electrical cooking appliances with pilot < 150 Btu/hr)
Lighting Measures
§150(k)l: Luminaires for general lighting in kitchens shall have lamps with an efficacy 40 lumens/watt or greater for general
lighting in kitchens. This general lighting shall be controlled by a switch on a readily accessible lighting control panel at an
entrance to the kitchen.
RI150(k)2: Rooms with a shower or bathtub must have either at least one luminaire with lamps with an efficacy of 40 lumens/watt
or greater switched at the entrance to the room or one of the alternative to this requirement allowed in Section 150(k)2.; and .
recessed ceiling fixtures are IC (insulation cover) approved.
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page:7 of 29
Computer Method Summary
(Part 1 of 3) C -2R
CARR FSTFI I A
Project Title
12/17/2004
Date
78225 C,',qtl*7 I a nl tints
.aIle
Project Address
Building Permit #
I Design Studio, Inr._
(760) 564-1866
.nch
Documentation Author
Telephone
Plan Check/Date
Comp tt _r Performance
Compliance Method Package or Computer)
15
Climate Zone
Field Check/Date
Source Energy Use Standard
Proposed
Compliance
(kBtu/sf-yr) Design
Design
Margin
Space Heating 3.49
3.78
-0.29
Space Cooling 35.49
33.74
1.75
Domestic Hot Water 6.99
6.96
0.03
Totals 45.98
44.48
1.50
GENERAL INFORMATION
Conditioned Floor Area: 4,075 Floor Construction Type: X� Slab Floor
Building Type: Single Fam Detached Raised Floor
Building Front Orientation: (North) 0 deg
Number of Dwelling Units: 1.00 Total Conditioned Volume: 40,750
Number of Stories: 1 Slab Floor Area: 4,075
BUILDING ZONE INFORMATION # of Thermostat Vent
Zone Name Floor Area Volume Units Zone Type Type Hgt. Area
HVAC Systpm - Zone 1 789 7 890 019 ConrlitinnPri SPthark _2 n/a
HVAC . �stpm - Zone 2 1 271 12 710 031 Conditinned S . hank n/a
HVAC Syctpm - Zone 3 2,(L 20,150 0-49 Cnnrlifinned S _tthark n/
OPAQUE SURFACES Solar
Act. Gains
Type Area U -Val. Azm. Tilt Y / N
Rnnf 7.88 0.028 0 0
Wall X45 n.o65 n An
nnnr 20 0.387 f) An
Wall 230 0.045 go 90
Wall 105 0.045 180 90
Wall J31 n.045 180 AD
Wall X31 0.045 270 90
Rnnf 1 271 0.028 0 ! 0
Wall 103 0.045 -0 `go
Wall 84 0.045 45 An
Wall 12 0.045 315 go
Wall 20 0.045 0_90
poor 28_ 0.387 0 _9Q
Wall 12 0.045 45 An
Wall 84 n.045 315 An
Wall 58 0.045 0 _90
Wall 166 0.045 1R0 90
Wall 29 0.045 270 go
Wall 28 0.045 180 90
Roof 9 011 0.028 0 a
Wall �60 0.045 90 go
Wall 41 0045 45 An
Wall 128 0 045 _go _9d
Wall X51 0.045 0 _91i
Wall 239 0-045 270 -9,Q
Wall �20 0.045 0 _1Q
Wall 93 0.045 270 _9Q
Wall 0.045 0 _ 90
Wall_ 260 0.045 270 gQ
Form 3 Reference
Location / Comments
I EnerovPro 3.1 By EnergvSoft User Number. 5454 Job Number: 3.1-1316 Page:8 of 29 1
Computer Method Summary
(Part 1 of 3) C -2R
CASA FSTE1 I A
Project Title
12/17/2004
Date
78225 Calle Cadiz La Quinta
Project Address
Building Permit #
Lenc:h nesian Studio, Inc.
(760) 564-1866
Documentation Author
Telephone
Plan Check/Date
Computer Performance
Compliance Method (Package or Computer)
15
Climate Zone
Field Check!Date
Source Energy Use Standard
Proposed
Compliance
(kBtu/sf-yr) Design
Design
Margin
Space Heating 3.49
3.78
-0.29
Space Cooling 35.49
33.74
1.75
Domestic Hot Water 6.99
6.96
0.03
Totals 45.98
44.48
1.50
GENERAL INFORMATION
Conditioned Floor Area: 4,075
Building Type: Single Fam Detached
Building Front Orientation: (North) 0 deg
Number of Dwelling Units: 1.00
Number of Stories: 1
BUILDING ZONE INFORMATION
Zone Name Floor Area Volume
OPAQUE SURFACES Act.
Type Area U -Val. Azm. Tilt
Wall 46 0.065 180 90
Wall 105 0.065 270 X30_
Wall 23 0.045 180 gd
Wall 143 0.045 180 90
Wall 89 0.045 180 CiQ
Wall 225 0 Q4 gn W0_
Solar
Gains
Floor Construction Type: XX Slab Floor
❑ Raised Floor
Total Conditioned Volume: 40,750
Slab Floor Area: 4,075
# of Thermostat Vent
Units Zone Type Type Hgt. Area
Y / N Form 3 Reference
Location / Comments
Zone 3
Run Initiation Time: 12/17/04 09:12:27 Run Code: 1103303547
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page:9 of 29
Computer Method Summary (Part 2 of 3) C -2R
CASA ESTELLA 12/17/2004
Project Title Date
FENESTRATION SURFACES
# Type
Area
U-
Factor
SHGC
Act.
Azm.
Glazing Type
Tilt
Location/
Comments
1
Skylight_Front
( nrth)
0.6
0.710
0.50
f_
0 Snlatuhe
Znne 1
2
Window Left
(East)
9.0
0.600
0.37
90
90 Summit 5500 Al DP Low E
Zone 1
3
Window Left
(East)
24.0
0.740
0.37
90
90 Summit 5500 Al DP Low E
Zone 1
4
Window Rear
(South)
9.0
0.600
0.37
180
90 Summit 5500 Al DP Low E
Zone 1
5
Window Rear
(South)
29.3
0.460
0.37
180
90 Summit 5500 Al DP Low E
Zone 1
6
Window Rear
(South)
9.0
0.600
0.37
180
90 Summit 5500 Al DP Low E
Zone 1
L
Window Rear
(South)
42.0
0.460
0.37
180
90 Summit 5500 Al DP Low E
Zone 1
8
Window Right
(West)
40.0
0.740
0.37
270
90 Summit 5500 Al DP Low E
Zone 1
6
Window Front
(North)
18.0
0.600
0.37
0
90 Summit 5500 Al DP Low E
Zone 2
1Q
Window Front
(North)
_ 36.0
0.460
0.37
0
_
90 Summit 5500 Al DP Low E
Zone 2
1
Window Front
(North)
18.0
0.460
0.37
0
90 Summit 5500 Al DP Low E
Zone 2
12
Window Front
(Northeast)
5.6
0.460
0.37
45
90 Summit 5500 Al DP Low E
Zone 2
13.
Window Front
(North)
4"8
0.460
0.37
0_
90 Summit 5500 Al DP Low E
Zone 2
14
Window Right
(Northwest)
5.6
0.460
0.37
315
90 Summit 5500 Al DP Low E
Zone 2
15
Window Front
(North)
18.0
0.610
0.39
0
90 Summit 5500 Al DP Low E
Zone 2
16
Window Front
(North)
6.0
0.460
0.37
0
90 Summit 5500 Al DP Low E
Zone 2
17
Window Rear
(South)
48.0
0.740
0.37
180
90 Summit 5500 Al DP Low E
Zone 2
18
Window Rear
(South)
48.0
0.740
0.37
180
90 Summit 5500 Al DP Low E
Zone 2
1.Q
Window Rear
(South)
18.0
0.460
0.37
180
90 Summit 5500 At DP Low E
Zone 2
20
Window Rear
(South)
18.0
0.460
0.37
180
90 Summit 5500 Al DP Low E
Zone 2
21
Window Rear
(South)
48.0
0.740
0.37
180
90 Summit 5500 Al DP Low E
Zone 2
2-2
Window Rear
(South)
48.0
0.740
0.37
180
90 Summit 5500 Al DP Low E
Zone 2
23
Window Rear
(South)
18.0
0.460
0.37
180
90 Summit 5500 Al DP Low E
Zone 2
24
Window Rear
(South)
18.0
0.460
0.37
180
90 Summit 5500 Al DP Low E
Zone 2
25
Window Rear
(South)
13.5
0.460
0.37
180
90 Summit 5500 Al DP Low E
Zone 2
26
Window Rear
(South)
6.0
1.280
0.80
180
90 Summit 5500 Al DP Low E
Zone 2
27
Skylight Front
(North)
0.6
0.710
0.50
0
0 Solatube
Zone 3
28
Skylight Front
(North)
0.6
0.710
0.50
0
0 Solatube
Zone 3
29
Skylight Front
(North)
0.6
0.710
0.50
0
0 Solatube
Zone 3
INTERIOR AND EXTERIOR SHADING
Window
Overhang
Left Fin
Right Fin
#
Exterior Shade
Type
SHGC
Hgt.
Wd.
Len. Hgt.
LEA RExt. Dist. Len.
Hgt. Dist. Len. Hgt.
1
None
1.00
2
Bug Screen
0.76
3
Bug Screen
0.76
4
Bug Screen
0.76
5
Bug Screen
0.76
6
Bug Scre n
0.76
7
Bug Scre n
0.76
8
Bug Screen
0.76
8.0
5.0
10.0
0.1
10.0 10.0
9
Bug Screen
0.76
10
Bug Screen
0.76
11
Bug Screen
0.76
12
Bug Screen
0.76
13
Bug Screen
0.76
14
Bug Screen
0.76
15
Bug Screen
0.76
16
Bug Screen
0.76
17
Bug Screen
0.76
8.0
6.0
10.0
0.1
10.0 10.0
18
Bug Screen
0.76
8.0
6.0
10.0
0.1
10.0 10.0
19
Bug Screen
0.76
3.0
6.0
10.0
0.1
10.0 10.0
20
Bug Screen
0.76
3.0
6.0
10.0
0.1
10.0 10.0
21
Bug Screen
0.76
8.0
6.0
10.0
0.1
10.0 10.0
22
Bug Scre n
0.76
8.0
6.0
10.0
0.1
10.0 10.0
23
Bug Screen
0.76
3.0
6.0
10.0
0.1
10.0 10.0
24
Bug Screen
0.76
3.0
6.0
10.0
0.1
10.0 10.0
25
Bug Screen
0.76
4.5
3.0
6.0
0.1
6.0 6.0
26
Bug Screen
0.76
2.0
3.0
6.0
0.1
6.0 6.0
27
None
1.00
28
None
1.00
29
None
1.00
I EnergvPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page: 10 of 29 1
Computer Method Summary (Part 2 of 3) C -2R
CASA ESTELLA 12/17/2004
Project Title Date
FENESTRATION SURFACES
# Type
Area
U-
Factor
SHGC
Act.
Azm.
Glazing Type
Tilt
Location/
Comments
-M
Sky1ght Front
rth)
0.6
0.710
0 50
0
f) Solatube
Zone 3
31
Skylight Front
(North)
0.6
0.710
0.50
0
0 Solatube
Zone 3
32
Skylight Front
(North)
0.6
0.710
0.50
0
0 Solatube
Zone 3
33
Skylight Front
(North)
0.6
0.710
0.50
0
0 Solatube
Zone 3
34
Window Front
(Northeast)
18.0
0.460
0.37
45
90 Summit 5500 Al DP Low E
Zone 3
35
Window Left
(East)
13.5
0.600
0.37
90
90 Summit 5500 Al DP Low E
Zone 3
3fi
Window Left
(East)
3.6
0.460
0.37
90
90 Summit 5500 Al DP Low E
Zone 3
37
Window Front
(North)
27.0
0.600
0.37
0
90 Summit 5500 Al DP Low E
Zone 3
,$
Window Front
(North)
3.6
0.460
0.37
0
90 Summit 5500 Al DP Low E
Zone 3
3R
Window Right
(West)
6.0
0.460
0.37
270
90 Summit 5500 Al DP Low E
Zone 3
40
Window Right
(West)
6.0
0.610
0.39
270
90 Summit 5500 Al DP Low E
Zone 3
41
Window Right
(West)
6.0
0.610
0.39
270
90 Summit 5500 Al DP Low E
Zone 3
A2
Window Right
(Wes)
30.0
0.610
0.39
270
90 Summit 5500 Al DP Low E
Zone 3
43
Window Front
(North)
9.0
0.620
0.38
0
90 Glass Block
Zone 3
44
Window Right
(West)
9.0
0.620
0.38
270
90 Glass Block
Zone 3
45
Window Right
(West)
6.0
0.460
0.37
270
90 Summit 5500 Al DP Low E
Zone 3
46
Window Rear
(South)
30.0
0.460
0.37
180
90 Summit 5500 Al DP Low E
Zone 3
47
Window Rear
(South)
36.0
0.610
0.39
180
90 Summit 5500 Al DP Low E
Zone 3
4$
Window Left
(East)
48.0
0.740
0.37
90
90 Summit 5500 Al DP Low E
Zone 3
49
Window Left
(East)
6.0
0.460
0.37
90
90 Summit 5500 Al DP Low E
Zone 3
50
Window Left
(East)
24.0
0.740
0.37
90
90 Summit 5500 Al DP Low E
Zone 3
INTERIOR AND EXTERIOR SHADING
Window
Overhang Left Fin
Right Fin
#
Exterior Shade Type
SHGC
Hgt.
Wd.
Len. Hgt.
LEA REA Dist. Len.
Hgt. Dist. Len. Hgt.
30
None
1.00
31
None
1.00
32
None
1.00
33
None
1.00
34
Bug Screen
0.76
35
Bug Screen
0.76
36
Bug Screen
0.76
37
Bug Screen
0.76
38
Bug Screen
0.76
39
Bug Screen
0.76
40
Bug Screen
0.76
41
Bug Screen
0.76
42
Bug Screen
0.76
43
Bug Screen
0.76
44
Bug Screen
0.76
45
Bug Screen
0.76
46
Bug Screen
0.76
47
Bug Screen
0.76
48
Bug Screen
0.76
49
Bug Screen
0.76
50
Bug Screen
0.76
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page: 11 of 29 1
Computer Method Summary (Part 3 of 3) C -2R
CASA ESTELLA 12/17/2004
Project Title Date
THERMAL MASS FOR HIGH MASS DESIGN
Minimum
Distribution Type
Area
Thick.
Heat
and Location
Inside
Location
Type (sf)
(in.)
Cap.
Cond. Form 3 Reference
R -Val.
Comments
Concrete. Heavyweight —0
150
_28
0.98 n/a
—9
Zone 1 / Slah nn Grade
Concrete, Heavyweight 789
3_50
28
0_98 n/a
0
Zone 1 / Slab on Grade
Concrete Heavyweight 216
3.50
_2fl.
0.98 n/a
2
Zone 2 / Slab on Grade
Concrete. Heavyweight 1.055
3_50
28
0_98 n/a
0
Zone 2 / Slab on Grade
ConcreteHeaiWyeight 1.543
3.50
—$
0.98 n/a
—2
Zone 3 / Slab on Grade
PERIMETER LOSSES
F2 Insulation
Type Length Factor R -Val. Depth Location / Comments
Slab Perimeter 96 0.76 0.0 0 Zone 1
Slah Perimeter 6.6. 0.76 0.0 _Q Zone 1
Slab Perimeter 102 0.78 0.0 0 Zone 2
Slab Perimeter 15 0.76 2Q _Q Zone 3
Slah Perimeter 180 0.76 0.0 0 Zone 3
HVAC SYSTEMS
Heating Equipment
Minimum
Distribution Type
Type (furnace, heat
Efficiency
and Location
Duct Thermostat
Location /
pump, etc.)
(AFUE/HSPFKducts/attic,
etc.)
R -Value Type
Comments
Central Furnace
80% AFUE
Ducts in Attic
4.2 Setback
HVAC System - Zone 1
Central Furnace
80% AFUE
Ducts in Attic
4.2 Setback
HVAC System - Zone 2
Central Furnace
80° AFUE
Ducts in Attic
4.2 Setback
HVAC System - Zone 3
Hydronic Piping Pipe Pipe Insul.
System Name Length Diameter Thick.
Cooling Equipment
Minimum
Duct
Type (air conditioner,
Efficiency
Location
Duct Thermostat
Location /
heat pump,. evap. cooling)
(SEER)
(attic, etc,)
R -Value Type
Comments
Split Air Conditioner
12.0 SEEK
Ducts in Attic
4.2 Setback
HVAC System - Zone 1
Split Air Conditioner
12.0 SEER
Ducts in Attic
4.2 Setback
HVAC System - Zone 2
Split Air Conditioner
12.0 SEER
Ducts in Attic
4.2 Setback
HVAC System - Zone 3
WATER HEATING SYSTEMS
Rated/ Tank
Energy Fact! 1 Tank Insul.
Water Heater
Water Heater Distribution
# in Input Cap.
or Recovery Standby R -Value
System Name
Type
Type
Syst. (Btu/hr) (gal)
Efficiency Loss (%) Ext.
A.O. SMITH FPS -75-230
Small Gas
Recirc/Demand
_ 1 75 400 75
0.52 n/a 12
1 For small gas storage (rated input — 75000 Btu/hr), electric resistance and heat pump water heaters, list energy factor.
For large gas storage water heaters (rated input > 75000 Btu/hr), list Rated Input, Recovery Efficiency and Standby Loss.
For instantaneous gas water heaters, list Rated Input, and Recovery Efficiency.
Run Initiation Time: 12/17/04 09:12:27 Run Code: 1103303547
EnerayPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page: 12 of 29
Computer Method Summary (Part 3 of 3) C -2R
CASA ESTELLA 12/17/2004
Project Title . Date
THERMAL MASS FOR HIGH MASS DESIGN
Area Thick. Heat Inside Location
Type (sf) (in.) Cap. Cond. Form 3 Reference R -Val. Comments
Concrete HeamMight 472 3.50 98 0 A n/a —n Zone 3 / Slah on Grade
PERIMETER LOSSES
F2 Insulation
Type Length Factor R -Val. Depth Location / Comments
HVAC SYSTEMS
Heating Equipment Minimum Distribution Type
Type (furnace, heat Efficiency and Location Duct Thermostat Location /
pump, etc.) (AFUE/HSPFKducts/attic, etc.) R -Value Type Comments
Hydronic Piping Pipe Pipe Insul.
System Name Length Diameter Thick.
Cooling Equipment Minimum Duct
Type (air conditioner, Efficiency Location Duct Thermostat Location I
heat pump, evap. cooling) (SEER) (attic, etc,) R -Value Type Comments
WATER HEATING SYSTEMS Rated' Tank Energy Fact! 1 Tank Insul.
Water Heater Water Heater Distribution # in Input Cap. or Recovery Standby R -Value
System Name Type Type Syst. (Btu/hr) (gal) Efficiency Loss (%) Ext.
1 For small gas storage (rated input — 75000 Btu/hr), electric resistance and heat pump water heaters, list energy factor.
For large gas storage water heaters (rated input > 75000 Btu/hr), list Rated Input, Recovery Efficiency and Standby Loss.
For instantaneous gas water heaters, list Rated Input, and Recovery Efficiency.
Run Initiation Time: 12/17/04 09:12:27 Run Code: 1103303547
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page: 13 of 29
Computer Method Summary (Addendum) C -2R
CASA ESTELLA 12/17/2004
Project Title Date
Special Features and Modeling Assumptions
The local enforcement agency should pay special attention to the items specified in this checklist. These items require special
written justification and documentation, and special verification to be used with the performance approach. The local
enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies
based on the adequacy of the special justification and documentation submitted. ---PIan7 Field
The DHW System "A.O. SMITH FPS -75-230" Energy Factor = 0.520. An EF below 0.58 requires an R-12 External Blanket.
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 0 sqft Covered Slab Floor, 3.50" thick at Zone 1
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 789 sqft Exposed Slab Floor, 3.50" thick at Zone 1
The HVAC System "HVAC System - Zone 2" includes credit for a Radiant Barrier installed per Section 8.13 of the Residential Manual.
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 216 sqft Covered Slab Floor, 3.50" thick at Zone 2
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 1055 sqft Exposed Slab Floor, 3.50" thick at Zone 2
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 1543 sqft Covered Slab Floor, 3.50" thick at Zone 3
HIGH MASS Design(see C -2R) - Verify Thermal Mass: 472 sqft Exposed Slab Floor, 3.50" thick at Zone 3
HERS Required Verification
These features must be confirmed and/or tested by a certified HERS rater under the supervision of a CEC approved HERS
provider. The HERS rater must document the field verification and diagnostic testing of these measures on a form CF -6R.
Plan
Field
The HVAC System "HVAC System - Zone 1" is using reduced duct leakage to comply and must have diagnostic site testing of duct
leakage performed by a certified HERS Rater. The results of the diagnostic testing must be reported on a CF -6R Form.
The HVAC System "HVAC System - Zone 2" is using reduced duct leakage to comply and must have diagnostic site testing of duct
leakage performed by a certified HERS Rater. The results of the diagnostic testing must be reported on a CF -6R Form.
The HVAC System "HVAC System - Zone 3" is using reduced duct leakage to comply and must have diagnostic site testing of duct
leakage performed by a certified HERS Rater. The results of the diagnostic testing must be reported on a CF -6R Form.
Run Initiation Time: 12/17/04 09:12:27 Run Code: 1103303547
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page: 14 of 29
1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY 77]
PROJECT NAME DATE
CASA ESTELLA 12/17/2004
SYSTEM NAME FLOOR AREA
HVAC System - Zone 1 789
ENGINEERING CHECKS 11SYSTEM LOAD
Number of Systems
1
Heating System
Output per System
35,000
Total Output (Btuh)
35,000
Output (Btuh/sgft) 1
44.4
Cooling System
Output per System
35,200
Total Output (Btuh)
35,200
Total Output (Tons)
2.9
Total Output (Btuh/sgft)
44.6
Total Output (sqf fron)
269.0
Air System
CFM per System
855
Airflow (cfm)
855
Airflow (cfm/sgft)
1.08
Airflow (cfm/Ton)
291.5
Outside Air N
0.0
Outside Air (cfm/sgft)
0.00
Vote: values above given at ARI conditions
EATING SYSTEM PSYCHROMETRICS
26.0 of 69.4 of 69.4 of
Outside Air O
0 cfm
Supply Fan
855 cfm
69.4 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible Latent
H CFM
I Sensible
290
8,974
0
287
11,378
0
449
569
0
0
0
0
0
0
0
0
0
4491
1 569
9,8 0 12 516
YORK H4DH036S06 27,366 0 35,000
Total Adjusted System Output 27,366 0 35,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug 2 pm Jan 12 am
earn Temaeratures at Time of Heatina Peak)
107.8 of
Heating Coil
>% Return Air Ducts "I
Supply Air Ducts
107.2 of
ROOMS
70.0 of
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak
111.0 177.6 of 74.5 / 56.1 of 74.5 / 56.1 of 44.4 / 42.9 of
Outside Air
0 Supply Air Ducts
0 cfm Supply Fan Cooling Coil 44.9 / 43.2 of
855 cfm 30.7% R.H. ROOMS
74,5/56.1 of 74.0 ! 55.9 of
o a.._. A:_
�. U .. ..
EneravPro 3.1 By EneravSoft User Number: 5454 Job Number: 3.1-1316 Paae:15 of 29
IVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME
DATE
CASA ESTELLA
12/17/2004
SYSTEM NAME
FLOOR AREA
HVAC System - Zone 2
1,271
Number of Systems
1
Heating System
Output per System
75,000
Total Output (Btuh)
75,000
Output (Btuh/sgft)
59.0
Cooling System
Output per System
58,500
Total Output (Btuh)
58,500
Total Output (Tons)
4.9
Total Output (Btuh/sgft)
46.0
Total Output (sgftrron)
260.7
Air System
CFM per System
855
Airflow (cfm)
855
Airflow (cfm/sgft)
0.67
Airflow (cfmrron)
175.4
Outside Air (%)
0.0
Outside Air (cfm/sgft)
0.00
Note: values above given at ARI conditions
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
ISensible Latent
CFM
I Sensible
754
15,253
0
499
18,594
0
0 cfm
Supply Fan Heating Coil
855 cfm
763
930
0
0
0
0
0
0
0
0
0
763
930
16,7 0
YORK H4DHO60SO6 45,853 3,401
Total Adjusted System Output 45,853 3,401
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK I Aug 2 pm
75,000
75,000
Jan 12 am
EATING SYSTEM PSYCHROMETRICS Airstream Temperatures
at Time of Heating
Peak
26.0°F
Outside Air
69.0 OF 69.0 OF 105.0°F
0
Supply Air Ducts
0 cfm
Supply Fan Heating Coil
855 cfm
104.0 of
ROOMS
70.0 of
69.0 of
Return Air Ducts
I
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures
at Time of Cooling
Peak
111.0/77.6OF
Outside Air
74.8/61.3OF 74.8/61.3OF
O
55.0/53.9OF
Supply Air Ducts
0 cfm
Supply Fan Cooling
855 cfm
Coil
55.8 / 54.2 OF
47.7% R.H. ROOMS
74.8/61.30F
74.0/61.0 OF
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page: 16 of 29
iVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
CASA ESTELLA 12/17/2004
SYSTEM NAME FLOOR AREA
HVAC System - Zone 3 2,015
Number of Systems
1
Heating System
Output per System
75,000
Total Output (Btuh)
75,000
Output (Btuh/sqft)
37.2
Cooling System
Output per System
58,500
Total Output (Btuh)
58,500
Total Output (Tons)
4.9
Total Output (Btuh/sgft)
29.0
Total Output (sgft/Ton)
413.3
Air System
CFM per System
855
Airflow (cfm)
855
Airflow (cfm/sqft)
0.42
Airflow (cfm/Ton)
175.4
Outside Air (%)
0.0
Outside Air (cfm/sqft)
0.00
Note: values above given at ARI conditions
HEATING SYSTEM PSYCHROMETRICS (Airs,
26.0°F 68.8 OF 68.8 OF
Outside Air
0 cfm
68.8 of
C
11.0 / 77.6 of
Outside
0 cfm
75.0 / 51.0 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
I COIL HTG. PEAK
CFM
I Sensiblel
Latent
1, CFM
I Sensible
404
19,083
0
261
22,219
0
954
1,111
0
0
0
0
0
0
0
0
0
954
1,111
_20,99 OI 2474411
YORK H4DHO60SO6 42,286 0 75,000
Total Adjusted System Output 42,286 0 75,000
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug 2 pm Jan 12 am
am Tei
151.2 of
Supply Fan Heating Coil
855 cfm
K Return Air Ducts 4
75.0/51.0OF 75.0/51.OoF = 28.6/26.70F
Supply Fan Cooling Coil
855 cfm
h Return Air Ducts `S
Supply Air Ducts
150.0 of
ROOMS
70.0 of
Supply Air Ducts
29.6 / 27.4 OF
14.4% R.H. ROOMS
74.0 / 50.5 of
I EneravPro 3.1 By EneravSoft User Number: 5454 Job Number: 3.1-1316 Paoe:17 of 29 1
ROOM LOAD SUMMARY
PROJECT NAME
CASA ESTELLA
DATE
12/17/2004
SYSTEM NAME
HVAC System - Zone 1
FLOOR AREA
789
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone 1
Zone 1
1
290
8,974
0
290
8,974
0
287
11,378
PAGE TOTAL 1 2901 8,974 oil 2871 11,378
TOTAL 1 290 8,974 0 287 11,378
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Pagel8 of 29
ROOM LOAD SUMMARY
PROJECT NAME
CASA ESTELLA
DATE
12/17/2004
SYSTEM NAME
HVAC System - Zone 2
FLOOR AREA
1,271
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone 2
Zone 2
1
754
15,253
0
754
15,253
0
499
18,594
PAGE TOTAL 754 15,253 0 499 18,594
TOTAL 1 754 15,253 0 499 18,594
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Pagel9 of 29
IROOM LOAD SUMMARY
PROJECT NAME
CASA ESTELLA
DATE
12/17/2004
SYSTEM NAME
HVAC System - Zone 3
FLOOR AREA
2.015
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Zone 3
Zone 3
1
404
19,083
0
404
19,083
0
261
22,219
PAGE TOTAL 1 4041 19,083 0 261 22,219
TOTAL 1 404 19,083 0 261 22,219
EnergyPro 3.1 By Energysoft User Number: 5454 Job Number. 3.1-1316 Page:20 of 29
ROOM HEATING PEAK LOADS -71
Project Title Date
CASA ESTELLA 112/17/2004
Room Information Desi n Conditions
Room Name zone 1 Time of Peak Jan 12 am
Floor Area 789 Outdoor Dry Bulb Temperature 26°F
Indoor Dry Bulb Temperature 70°F
Conduction Area U -Value AT of Btu/hr
788.4
X
X
x
X
X
x
X
X
X
X
x
X
X
X
X
X
X
X
X
X
X
X
X
x
X
x
x
X
x
x
X
X
X
X
X
x
x
X
X
0.0280
X
X
x
X
X
x
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
x
X
x
x
X
X
X
X
X
X
X
X
X
X
44.0
=
=
=
=
=
=
=
=
=
=
=
=
971
0.6
0.7100
44.0
19
perimeter = 92.4
44.5
4,112
245.0
0.0655
44.0
706
20.0
0.3872
44.0
341
496.7
0.0453
44.0
990
27.0
0.6000
44.0
713
64.0
0.7400
44.0
2,084
0,4600
44.0
1,443
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 11 378
Infiltration: r 1.001 X 1.064 X 789 X 10.00 x 60] X LT _ �0
schedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 11,378
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page: 21 of 29
ROOM HEATING PEAK LOADS
Project Title Date 7
CASA ESTELLA 12/17/2004
Room Information Desi n Conditions
Room Name Zone 2 Time of Peak' Jan 12 am
Floor Area 1,271 Outdoor Dry Bulb Temperature 260E
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value Z�T0F Btu/hr
Summit 5500 Al DP Low E
1271.0
X
x
x
x
x
x
X
X
x
X
x
X
X
x
x
x
x
x
x
x
x
x
x
x
x
x
x
X
x
x
x
x
x
X
X
X
X
X
X
0.0280
X
x
X
X
X
X
X
X
X
X
x
X
X
x
X
x
x
x
x
x
x
x
x
x
x
x
X
X
X
x
X
x
x
x
x
x
x
X
x
44.0
=
=
=
=
=
=
=
=
=
=
=
=
1,566
perimeter = 102.1
44.5
4,543
597.5
0.0453
44.0
1,191
18.0
0.6000
44.0
475
161.5
0.4600
44.0
3,269
28.0
0.3872
44.0
477
18.0
0.6100
44.0
483
192.0
0.7400
44.0
6,252
1,2800
44.0
338
Items shown with an asterisk (') denote conduction through an interior surface to another room. Page Total: 18 594
Infiltration: r 1 .001 x Sensible
x 1 271 X 10.00 x 60]x &T = Q
schedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 18,594
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page: 22 of 29
ROOM HEATING PEAK LOADS 7771
Project Title Date
CASA ESTELLA 12/17/2004
Room Information Desicin Conditions
Room Name zone 3 Time of Peak Jan 12 am
Floor Area 2,015 Outdoor Dry Bulb Temperature 26OF
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value AT of Btu/hr
IR -19 Wall w/1" EPS I
2,010.8
X
X
X
X
X
x
X
X
X
X
x
X
x
x
x
x
X
x
x
X
X
x
X
x
x
X
X
x
x
X
x
x
X
x
x
X
x
x
X
0.0280
X
X
X
x
X
X
X
X
X
X
x
x
x
x
x
x
X
X
x
x
x
x
x
x
x
x
x
X
X
X
x
X
x
x
X
x
X
x
X
44.0
=
=
=
=
=
=
=
=
=
=
=
=
2,478
4.2
0.7100
44.0
131
perimeter = 194.9
44.5
8,673
1,516.3
0.0453
44.0
3,023
73.2
0.4600
44.0
1.482
40.5
0.6000
44.0
1,069
78.0
0.6100
44.0
2,094
18.0
0.6200
44.0
491
151.0
0,0655
44.0
435
72.0
0.7400
2,344
Items shown with an asterisk ('r) denote conduction through an Interior surface to another room. Page Total: I 22,2191
Infiltration: 1.00 x 1.064 x 2 015 X 10.00 X 6] x 0 = 0
chedule Alr Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 22,219
EnergyPro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page: 23 of 29
RESIDENTIAL ROOM COOLING LOAD SUMMARY
CASA ESTELLA 12/17/2004
Project Title Date
Room Name
Design Indoor Dry Bulb Temperature:
Design Outdoor Dry Bulb Temperature:
Design Temperature Difference:
Conduction
Area U -Value
X
DETD1
55.0
38.0
34.6
34.6
34.6
38.0
8.
38.0
Zone 1
740F
112°F
380E
Btu/hr
1,214
16
555
268
779
616
1,800
1,246
1. Design Equivalent Temperature Difference (DETD)
Page Total
Items shown with an asterisk (')denote conduction through an interior surface to another room.
6 a9a
Shaded Unshaded
Solar Gain Orientation Area SGF Area SGF Sc Btulhr
Sk i ht 0" Dia
(Skylight)
1
(East)
Window 3080 FR DR
(East)
Window 2046 SH
(South)
Window 6646 FO
(South)
Window 2046 SH
Window 1060 7 FO
(South)
(South)
Window 2680_(2) FR DR
(West)
73
0.41
( 0.0
x
x
x
x
X
x
x
X
x
x
1
+
+
+
+
+
+
+
+
+
+
0.6
X
X
X
X
X
X
X
x
x
x
152
) X
)x
)x
x
X
)X
)x
0.57
=
=
=
=
=
=
=
=
=
=
52
( 0.0
1
9.0
73
0.41
271
( 0.0
1
24.0
73
0.412
722
( 0.0
1
9.0
32)X
0.412
119
( 0.0
1
29.3
32)
0.412
386
( 0.0
1
9.0
32)x
0.412
119
( 0.0
1
42.0
32)
0.412
554
( 39.5
1"
0.5
73)x
0.412
259
(
(
Sched.
Page Total 2 a81
Internal Gain Frac. Area Heat Gain Btu/hr
Li hts 1.00 X 789 X 0.000 Wafts/sgft x 3.41 Btuh/Watt = 0
Occupants 1.00 X 789 x 9 Btuh/occ. / 20.00 sgft/occ. = 0
Receptacle 1.00 x 789 x 0.000 Wafts/sqft x 3.413 Btuh/Waft - 0
Process 1.00 x 789 x 0.000 Wafts/sgft x 3.413 Btuh/Watt = 0
Infiltration: x � x � x x � / 60] Z _
chedule Air Sensible Area Ceiling Height ACH OT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 8,974
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
OCCu ants 1.00 x 789 x 0 Btuh/occ. / 20 000 sgft/occ. = 0
Receptacle 1.00 x 789 x 0.000 Watts/sgft x 3.41 Btuh/Watt = 0
Process 1.00 x 789 x 0.000 Watts/sqft x 3.41 Btuh[Watt = 0
Infiltration: 1 1.001 x 4 77 x 78 x Heigh x 60] 0.00000 =
chedule Air Latent Area Ceiling Height ' ACH 1n1yy
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 0
Energ Pro 3.1 By Energ Soft User Number: 5454 Job Number: 3.1-1316 Pa e:24 of 29
RESIDENTIAL ROOM COOLING LOAD SUMMARY
CASA ESTELLA 12/17/2004
Project Title Date
Room Name
Design Indoor Dry Bulb Temperature:
Design Outdoor Dry Bulb Temperature:
Design Temperature Difference:
Zone 2
740F
112°F
380F
Conduction Area U -Value DETD 1 Btu/hr
X
X
X
X
X
X
X
55.0
=
=
=
=
=
=
=
1,958
34.6
937
38.0
410
38.0
2,823
34.6
375
38.0
417
1 38.01
5.399
X
X
1. Design Equivalent Temperature Difference (DETD)
Page Total 12 611
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Shaded Unshaded
Solar Gain Orientation Area SGF Area SGF SC Btu/hr
Window 3060 SH
Window 1rRQ (9) FO
(North)
(North)
Window 3020 i3i FO
(North)
Window 1/2 Rd 2626
(Northeast)
Window 1/2 Rd 3636 FO
(North)
Window 2 Rd 2626
_(Northwest)
Window 3060 XO
(North)
Window 3020 FO
(North)
Window 3080 2 FR DR
(South)
Window 3080 2 FR DR
South
( 0.0x1
X
x
x
x
x
X
+
1 +
1 +
1 +
1 +
1 +
1 +
1 +
1 +
1 +
18.0x
X
x
x
x
x
x
15)X
x
X
) x
0.41
=
=
=
=
=
=
=
=
_
=
'l
( 0.0
36.0
15)
0.41
222
( 0.0x
18.0x
15)X
0.41
111
( 0.0x
5.6X
48)x
0.41
111
( 0.0
4.8
15)x
0.41
30
( 0.0x
5.6X
48)X
0.41
111
( 0.0
18.0
15)
0.434
117
( 0.0
6.0
15)X
0.41
37
( 48.0
0.0
32)x
0.41
297
( 48.0
0.0
32
0.41
297
Sched. Page Total 1 443
Internal Gain Frac. Area Heat Gain Btu/hr
Lights 1.00 X 1,271 x 0.000 Wafts/sgft x 3.41 Btuh[Watt = 0
Occupants 1.00 x 1.27 x 0 Btuh/occ. / 20.00 sgft/occ. = 0
Receptacle 1.00 x 1,27 x 0.000 Wafts/sgft x 3.413 Btuh/Waft = 0
Process 1.00 X 1,271 xl 0.000 Wafts/sqft X 3.413 Btuh/Waft = o
Infiltration: �� x Airs x Area 27 1 x Ceiling� x ACH / 60] 1 nT 38 _01
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 15,253
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 x 1271 x 0 Btuhlocc. l 20 00o sqftlocc. = 0
Receptacle 1.00 x 1 271 x 0.000 Wafts/sqft X 3.41 BtuhlWaft = o
Process 1.00 x 1 2 1 x 0.000 Wafts/sqft x 3.41 Btuh/Waft = 0
Infiltration: chadulle x Air Latent x Area 27 x Ceiling Height x ACH 00 / 60] 1n1
OA0000 =
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM o
Energ Pro 3.1 By Ener Soft User Number: 5454 Job Number: 3.1-1316 Page:25 of 29
RESIDENTIAL ROOM COOLING LOAD SUMMARY
CASA ESTELLA 12/17/2004
Project Title Date
Room Name Zone 2
Design Indoor Dry Bulb Temperature: 740F
Design Outdoor Dry Bulb Temperature: 1 120F
Design Temperature Difference: 380F
Conduction
Area U -Value
X
1. Design Equivalent Temperature Difference (DETD)
Page Total
Items shown with an asterisk (`) denote conduction through an interior surface to another room.
o
Shaded Unshaded
Solar Gain Orientation Area SGF Area SGF SC Btu/hr
Window 6030 FO
(South)
W*nrInvv 6030 170
(South)
Window 3080 2 FR DR
(South)
Window 3080 2 FR DR
(South)
Window 6030 FO
(South)
Window 6030 FO
(South)
Window 3046 FO
(South)
Window 3020 FO
(South)
0.0
32
0.412
297
( 18.0x
x
X
x
x
X
x
x
x
X
1 +
1 +
1 +
1 +
1 +
1 +
1 +
1 +
+
+
0.0x
X
X
X
X
X
x
x
x
x
32)X
) x
x
x
)x
)x
0.41
=
=
=
=
=
=
=
=
=
=_
111
( 18.0
0.0
32)x
0.412
111
( 48.0
0.0
32
0.412
297
( 48.0
0.0
32)
0.412
297
( 18.0
0.0
32)x
0.412
111
( 18.0
0.0
32)x
0.412
111
( 13.5
0.0
32)x
0.412
83
( 6.0
0.0
32)
0.856
77
(
(
Sched.
Page Total 1 198
Internal Gain Frac. Area Heat Gain Btu/hr
Li hts 1.00 x 1,271 x O-OOC Watts/sqft x 3.41 Btuh/Watt - 0
Occupants 1.00 x 1,27 x Btuh/occ. / 20 000 sgft/occ. = 0
Receptacle 1.00 x 1,27 x 0.00 Watts/sgft x 3.413 Btuh/Waft = 0
Process 1.00 x 1,271 x 0.00 Wafts/sqft x 3.41 Btuh/Waft = 0
Infiltration: �� x Sensible x 1,271 x x � / 60� _
Schedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 15,253
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
OCCU ants 1.00 X 1 271 x 0 Btuh/occ. I 20 000 sgft/occ. = 0
Receptacle 1.00 x 1 271 x 0.000 Wafts/sqft x 3.41 Btuh/Waft = 0
Process 1.00 x 271 X 0.000 Wafts/sqft X 3.41 Btuh/Waft = 0
Infiltration: �ohetool ie x L 4,77q
Air Latent x Area 27 X Ceiling Height x ACH 00 / 60] QOtON0000 =
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 0
Energ Pro 3.1 By Ener Soft User Number: 5454 Job Number: 3.1-1316 Page:26 of 29
RESIDENTIAL ROOM COOLING LOAD SUMMARY
CASA ESTELLA 12/17/2004
Project Title Date
Room Name Zone 3
Design Indoor Dry Bulb Temperature: 740F.
Design Outdoor Dry Bulb Temperature: 1 120F
Design Temperature Difference: 380F
Conduction
Is
Area U -Value
X
DETD 1
X 55.0
X 38.0
X 34.6
X 38.0
X 38.0
X 38.0
X
X
X
Btu/hr
3,097
113
2,377
1,280
923
1,808
424
1. Design Equivalent Temperature Difference (DETD) Page Total 12 389
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Shaded Unshaded
Solar Gain Orientation Area SGF Area SGF SC Btu/hr
Skylight 10" Dia
(Skvlight)
_
(Skylight)
Sk i ht 10" Dia
(Skylight)
Skylight 10" Dia
(Skylight)
Skylight 10" Dia
(Skylight)
Sk i ht 10" Dia
(Skylight)
Skylight 10" Dia
(Skylight)
Window 1060 3 FO
Northeast
Window 3046 SH
(East)
Window 1/2 Rd 3016 FO
East
( 0.0
x
x
x
x
X
x
x
x
X
X
1
+
+
+
+
+
+
+
+
+
+
0.6
x
X
x
x
x
x
X
X
X
x
152)
X
x
) X
x
X
X
X
x
0.57
=
=
=
=
=
=
=
=
__
=
52
( 0.0
1
0.6
152)
0.57
52
( 0.0
1
0.6
152
0.575
52
( 0.0
1
0.6
152)x
0.57
52
( 0.0
1
0.6
152)
0.575
52
( 0.0
1
0.6
152)
0.57
52
( 0.0
1
0.6
152)
0.575
52
( 0.0
1
18.0
48)
0.41
356
( 0.0
1
13.5
73)x
0.412
406
( 0.0
1
3.6
73)
0.41
108
Sched. Page Total 1 237
Internal Gain Frac. Area Heat Gain Btu/hr
Licihts 1.00 X 2,015 x 0.000 Watts/sqft x 3.41 Btuh/Watt = 0
Occupants 1.00 X 2,015 x 0 Btuh/occ. / 20.00 sqft/occ. = 0
Receptacle 1.00 x 2,015 x 0.000 Watts/sqft x 3.413 Btuh/Watt = 0
Process 1.00 x 2,015 x 0.000 Watts/sgft x 3.41 Btuh[Watt = 0
Infiltration: L d_0o1 x�rs� x x ensible Area Coiling x 60]
/ 38 =
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 19,083J
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 x 2 015 x 0 Btuh/occ. / 20 000 sgft/occ. = 0
Receptacle 1.00 x 2 015 x 0.000 Watts/sqft x 3.41 Btuh/Watt = o
Process 1.00 x 2 015 x 0.000 Watts/sqft x 3.41 Btuh/Watt = o
Infiltration: Fi= oo x ule Air ni x Areao1 X Ceiling Height x ACH 00 / 60] Qo100000
ScheN=
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 0
Energ Pro 3.1 By Energ Soft User Number: 5454 Job Number: 3.1-1316 Page:27 of 29
RESIDENTIAL ROOM COOLING LOAD SUMMARY
CASA ESTELLA 12/17/2004
Project Title Date
Room Name
Design Indoor Dry Bulb Temperature:
Design Outdoor Dry Bulb Temperature:
Design Temperature Difference:
Conduction
Area U -Value
X
X
X
X
X
X
X
X
DETD1
1. Design Equivalent Temperature Difference (DETD) Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Shaded Unshaded
Zone 3
740F
112°F
380E
Solar Gain Orientation Area SGF Area SGF SC Btu/hr
Window 3046 2 SH
(North)
1 +
1 +
1 +
1 +
1 +
+
(North)
Window 1016 4 FO
(West)
Window 3020 XO
(West)
Window 3020 XO
(West)
Window 6050 XO
(West)
Window 3030 GL BLK
(North)
Window 3030 GL BLK
(West)
Window 1016 4 FO
(West)
Window 1060 5 FO
South
( 0.0x
x
x
X
x+
x+
Xdi
X+
1 +
1 +
1 +
1 +
1 +
+
27.0x
X
X
X
X
x
x
x
15)X
) X
x
x
) x
0.41
=
=
=
=
=
=
=
=
__
=
167
( 0.0x
3.6X
15)x
0.412
22
( 0.0
6.0
73
0.412
180
( 0.0
6.0
73)x
0.434
190
( 0.0
6.0
73)
0.434
190
( 0.0
30.0
73)X
0.434
951
( 0.0
9.0
15)
0.423
57
( 0.0
9.0
73)x
0.423
278
( 0.0X+
6.0X
7)x
0.41
180
( 0.0
30.0
32
0.412
395
Sched.
Page Total 2 611
Internal Gain Frac. Area Heat Gain Btu/hr
Li hts 1.00 x 2,015 x 0.00C Watts/sqft xA3.413
Btuh/Watt = 0
Occupants 1.00 x 2,015 x Btuh/occ. / sgft/occ. = 0
Receptacle 1.00 x 2,015 x 0.00 Watts/sqft x Btuh/Waft = 0
Process 1.00 x 2015 x 0.00 Wafts/sgft XBtuh/Watt = 0
Infiltration: S� x Air Sensible
� x Area 2,015 x Coiling
� x ACH / 60] nJ _
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 19,083
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
Occupants 1.00 x 2 015 x 0 Btuh/occ. / 20.00 sgft/occ. = 0
Receptacle 1.00 x 2 015 x 0.000 Watts/sqft x 3.41 Btuh/Watt = 0
Process 1.00 x 2 015 x 0.000 Wafts/sgft x 3.4d Btuh/Waft = 0
Infiltration: F 1.00 x 4 77 x 2 01 x 10.00 x 0.00 / 60] 0.00000
Schedule Air Latent Area Ceiling Height ACH DW
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 0
Energ Pro 3.1 By Ener Soft User Number: 5454 Job Number: 3.1-1316 Pa e:28 of 29
It RESIDENTIAL ROOM COOLING LOAD SUMMARY
CASA ESTELLA 12/17/2004
Project Title Date
Room Name
Design Indoor Dry Bulb Temperature:
Design Outdoor Dry Bulb Temperature:
Design Temperature Difference:
Zone 3
740E
112°F
380F
Conduction Area U -Value DETD' Btu/hr
1. Design Equivalent Temperature Difference (DETD)
Page Total
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Shaded
Unshaded
Solar Gain Orientation
Area SGF
Area
SGF
SC
Btu/hr
Window 6060 XO
(South) (
0.0
x
11
+
36.0
x
32
)x
0.434 =
500
Winclaw'408f) (9) FIR nR
(East) (
0.0
x
1
+
48.0
x
73
) x
0.41 =
1,443
Window 1016 4 FO
(East) (
0.0
x
1
+
6.0
x
73
) x
0.412 =
180
Window 3080 FR DR
(East) (
0.0
x
1
+
24.0
x
73)x
0.412 =
722
(
x
+
x
)x
=
(
x
+
x
)x
=
(
x
+
x
)x
=
(
x
+
x
)x
=
(
X
+
X
)x
=
Sched. Page Total 2845
Internal Gain Frac. Area Heat Gain Btu/hr
Li hts 1.00 X 2,015 X 0.000 Watts/sgft xA3.41
Btuh/Waft = 0
Occupants 1.00 X 2,015 X Btuh/occ. / sqft/occ. = 0
Receptacle 1.00 x 2 015 x 0.00 Watts/sqft x Btuh/Watt = 0
Process r 1.00 x 2,015 x 0.00 Watts/sgft XBtuh/Wlatt = o
Infiltration: I en� x Airs x LArea -2.015) x Coiling� x ACH / 60] en3BJ =
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 19,0831
Sched.
Latent Gain Frac. Area Heat Gain Btulhr
Occupants 1.00 X 2 015 x 0 Btuh/occ. / 20 000 sgft/occ. _
Receptacle 1.00 X 2 015 x 0.000 Wafts/sgft x 3.4 BtuhlWaft = o
Process 1.00 x 2 015 x 0.000 Watts/sgft x 3.41 Btuh/Watt = o
Infiltration: tool
oo x Air Latent X Areao1 X Calling Height x ACH 00 / 60] ootON0000 = 0
Fraction
TOTAL HOURLY LATENT HEAT GAIN FOR ROOM 0
Ener Pro 3.1 By EnergySoft User Number: 5454 Job Number: 3.1-1316 Page: 29 of 29