Loading...
04-5331 (AMUS) Title 246; Title 24 Energy Compliance Documentation Prepared for: Peterson Associates Project Title: THE HIDEAWAY GOLF CLUBHOUSE La Quinta, CA CITY OF LA QUINTA BU LDHNG & SAFETY DEPT. FOR CONSTRUCTION _ DATE BY ; 5: 80•'140 10308 Placer Lane, Suite 200, Sacramento, CA 95827 • 916-'364-1786 • FAX 916-364-1789 5� Envelope Mandatory Measures §118(a) Installed insulating material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20, Chapter 4, Article 3. §118(c) All insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of the Title 24, Part 2. §I 17(a) All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. §116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors). §I 16(a)I Manufactured Doors and Windows installed shall have air infiltration rates not exceeding those shown in Table Number 1-E. of the Standards. Manufactured fenestration products must be labeled for U -value according to NFRC procedures. §1,1.8(e) Demising Walls in Nonresidential Buildings: The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value of no less than R-1 I between framing members. Lighting Mandatory Mcasures 5131(d)l For every floor, all interior lighting systems shall be equipped with a separate automatic control to shut off the lighting. This automatic control shall meet the requirements of section 119 and may. be an occupancy sensor, automatic time switch, or other device capable of automatically shutting off the lighting. 5131(d)2 Override for Building Lighting Shut-off. The automatic building shut-off system is provided with a manual, accessible override switch in sight of the lights. The area of override is not to exceed 5,000 square feet. 5119(h) Automatic Control Devices Certified: All automatic devices specified are certified, all alternate equipment shall be certified and installed as directed by the manufacturer. Fluorescent Ballast and Luminaries Certified: All fluorescent fixtures specified for the project are certified and listed in the directory. All installed fixtures shall be certified. §132 Tandem Wiring for One and Three Lamp Fluorescent Fixtures: All one and three lamp fluorescents fixtures are tandem wired with two lamp ballasts were required by Standards Section 132; or all three lamp fluorescents fixtures are specified with electronic high - frequency ballasts and are exempt from tandem wiring requirements. §131(a) individual Room/Area Controls: Each room and area in this building is equipped with a separate switch or occupancy sensor device for each area with floor -to -ceiling walls. § 131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100 square feet and more than 0.8 watts per square foot of lighting load shall be controlled with bi-level switching for uniform reduction of lighting within the room. § 131(c) Daylight Area Control: All rooms with windows and skylights that arc greater than 250 Square feet and that allow for the effective use of daylight in the area shall have 50% of the lamps in each daylit area controlled by separate switch; or the effective use of daylight cannot be accomplished because the windows are continuously shaded by a building on the adjacent lot. Diagram of shading during' different times of the year is. included on the plans. 13 I Control of Exterior Lights: Exterior mounted fixtures served from the electrical panel inside the building are controlled with a directional photo cell control on the roof and corresponding relay in the electrical panel. �131(e) Display Lighting: Display lighting shall be separately switched on circuits that are 20 amps of less. Ij 1. Mechanical Mandatory Measures EQUIPMENT AND SYSTEM EFFICIENCES §111 Any appliance for which there is a California standard established in the Appliance Efficiency Regulations with comply with the applicable standard. §115(a) Fan type central furnaces shall not have pilot lights. § 123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC equipment, shall be insulated in accordance with Standards Section 123. §124 Air handling duct systems shall be installed and insulated in compliance with Sections 601, 603 and 604 of the Uniform Mechanical Code. CONTROLS §122(e) Each space conditioning system shall be installed with one of the following: §122(E)IA Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not explicitly exempt from the requirements of section 1.22(d)) shall be installed with an automatic time switch with an accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch shall be capable of programming different schedules for weekdays and weekends; incorporate an automatic holiday "shut off" feature that turns off all loads for at least 24 hours, then resumes the normally scheduled operation; and has program backup capabilities that prevent the loss of the device's program and time settings for at least 10 hours if power is interrupted; or §122(e)1B An occupancy sensor to control the operating period of the systems; or §122(e)1C A 4 -hour timer that can be manually operated to control the operating period of the system. § 122(e)2 Each space conditioning system shall be installed with controls that temporarily restart and temporaril-"pe-rate-t4"ysteiu-as-requirzd-to-na.iutain_.a-setbacklieating and/or_a setup cooling thermostat setpoint. §122(8) Each space conditioning system serving multiple zones with combined conditioned floor area more than 25,000 square feet shall be. provided with isolation zones. Each. zone: shall not exceed 25,000 square feet; shall be provided with isolation devices, such as valves or dampers, that allow supply of heating or cooling to be setback or shut off independently of other isolation areas; and shall be controlled by a time control device as described above. §122(a&b) Each space. conditioning zone shall be controlled by an individual thermostatic control that responds to temperature within the zone. Where used to control heating, the control shall be adjustable down to 55°F or lower.. For cooling, the control shall be adjustable up to 85°F or higher. Where used to control both heating and cooling, the control shall be capable of providing a deadband of at least 5°F within which the supply of heating and cooling is shut off or reduced to a minimum. §122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to authorized personnel. 122(b) Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the heating load can be met by the heat pump alone. VENTILATION §121(e). Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified on these plans. §122(f) Gravity or automatic dampers interlocked and closed on the fan shutdown shall be provided on the outside air intakes and discharges of all space conditioning and exhaust systems. §122(f) All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers in all openings to the outside, except for combustion air openings. §121(f)l Air Balancing: The system shall be balanced in accordance with the National Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or Associated Air Balance Council (AABC) National Standards (1989); or §121(f)2 Outside Air Certification: The system shall provide the minimum outside air as shown on the mechanical drawings, and shall be measured and certified by the installing licenced C- . 20 Mechanical contractor and certified by (1) the design mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) the person with overall responsibility. for the design of the ventilation system; or §121(f)3 Outside Air Measurement: -The System shall be equipped with a calibrated local or remote device capable of measuring the quantity of outside air on a continuous basis and displaying that quantity on a ready accessible displays; or §121(f)4 Another method approved by the Commission. WATER HEATING SYSTEMS §113(b)2 If a circulating hot water system is installed, it shall have a control capable of automatically turning off the circulating pump(s) when hot water is not required. §113(b)3B Lavatories in restrooms of public facilities shall be equipped with controls to limit the outlet temperature to 110° F. §113(b)3C Lavatories in restrooms of public facilities shall be equipped within of the following: -Outlet devices that limit the flow of hot water to a maximum of 0.5 gallons per minute. Foot actuated control valves, and outlet devices that limit the flow of hot water to a maximum of 0.75 gallons per minute. -Proximity sensors actuated control valves, and outlet devices that limit the flow of hot water to a maximum of 0.75 gallons per minute. -Self-closing valves, and outlets devices that limit the flow of hot water to a maximum of 2.5 gallons per minute, and 0.25 gallons/cycle (circulating system). -Self-closing valves, and outlet devices that limit the flow of hot water to a maximum of 2.5 gallons per minute, and 0.50 gallons/cycle (non -circulating system) -Self-closing valves, and outlet devices that limit the flow of hot water to a maximum of 2.5 gallons per minute, and 0.75 gallons/cycle (foot switches and Proximity sensor controls). 1 TITLE 24 REPORT Title 24 Report for: The Hideaway Golf Clubhouse 52-500 Village Club Drive La Quinta, CA 92253 Project Designer: H & S International 17785 N. Pacesetter Way, Suite 800 Scottsdale, AZ 85255 (480) 585-6898 Report Prepared By: Gregory Mize Valley Energy Consultants. 10308 Placer Lane, Suite #200 Sacramento, CA 95827-2511 (916) 364-1786 Job Number: 40528 Date: i 6/25/2004 i 'he EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2001 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC (415) 883-5900. I . j EnergyPro 3.1 By EnergySoft Job Number. 40528 User Number. 2531 'ERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF- tOJECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 !PROJECT ADDRESS 52-500 Village Club Drive La Quinta 'PRINCIPAL DESIGNER - ENVELOPE H & S International •.DOCUMENTATION AUTHOR Valley Energy Consultants GENERAL INFORMATION 'DATE OF PLANS ;BUILDING CONDITIONED FLO j o6-02-04 TELEPHONE (480) 585-6898 TELEPHONE (916) 364-1786 AREA 30,954 Sq.Ft Building Permit # Checked by/Date Enforcement Aqency Use BUILDING TYPE x NONRESIDENTIAL HIGH RISE RESIDENTIAL F-7 HOTEL/MOTEL GUEST ROOM PHASE OF CONSTRUCTION NEW CONSTRUCTION U ADDITION [—I ALTERATION J EXISTING + ADDITION STATEMENT OF COMPLIANCE rhis Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 3, of the State Building Code. This certificate applies only t a uilding usin rfor ce compliance approach. )OCUMENTATION AUTHOR SI E AT Gregory Mize i _ _ _ __ _ ;�j ZS/Alt rhe Principal Designers hereby certify that the proposed ilding ig a sented in the onstruction documents and mod Iled . i or this permit application are consistent with all other forms d w rks s, pecifications, and other calculations submitted with this )ermit application. The proposed building as designed meets the ener a ciency requirements of the State Building Code, Title ?4, Part 6. ENV. LTG. MECH. U J 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed as a civil engineer, mechanical engineer, electrical engineer or architect. r1 ± 17 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section O/J/.J lU SI(y11 UnS uUl:u111Cl11 CIS IIIc I/CIJVII Icopul IJIu IC IV[ IW PICpalauV11, MIU ulal 10111 a u�UIIOUu contractor preparing documents for work that I have contracted to perform. —!71 [71 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pusuant to Business and Professions j Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code ae printed in full in the Nonresidential Manual.) i ENVELOPE COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures Required Forms NV -1 PRINCIPAL ENVELOPE DESIGNER - NAME i SIGNATOR O. DATE I H& S International j G ? j IOI� •28 G�• LIGHTING COMPLIANCE ! Indicate location on plans of Note Block for M ndatory Measures ! Required Forms I ftG-1, LTG -3 LIC. NO. DATE .PRINCIIGHTING DESIGNER -NAME � SI N TU ; PAL L Peterson Associates I 4 MECHANICAL COMPLIANCE In Indicate location on plans of Note Block for Mandatory Measures , j AAAay- T kYmsatj Required Fprms (MECH-1. MECH-2. MECH-3 RINCIPAL MECHANICAL DESIGNER - NAME Peterson Associates Sze DATLff-a¢ ; IEneravPro 3.1 By EnergySoft User Number. 2531 Job Number. 40528 Page:2 of 53 FPLRF61 RMANCE`CERTIFICATS OF COMPLIANCE. Part 2. of 3 P P, �-i DATE The Hideaway Golf. Clubhouse." 6/25/2004 ANNUAL SOURCE ENERGY USE SUMMARY'. kBtU/s ft- .r Standard Proposed Cornpliance+t ,' { ENERGY COMPONENT - Design' Design ' . Margin IjrSl�ndam�_,poposegk '£ S Space Heating I 8.071 I 3 50, 4 571 t �'""a'm ti,c a s u{ t , i r��€ -Space Cooling I 72.591 1 72.804; 0 20 ' 1 -0.48 S III Indoor Fans _35.681 f 36.161 0 48 it t�,�a��wg MT V Heat Re ection. 0.001 ''o.00.0.00 J i . j r ttroffk'�w �#t _ � -Pumps & Misc. 0.00i 0.00 0.00 EEO � h Domestic Hot Water 1 17.41� 14 106; fir° £'� �1 p MA Lighting I 30.771 37591-6.821 I1 Receptacle 11.47' 11.471 I o 00 , :xmog Process 10.00 10.00 , I 0 00ell j: TOTALS: 185.99. 185.87 0.12 . r 3 { rkBtWsgflyry "�� i Percent better than -Standard: 01% ( 0.1% excluding process) BUILDING COMPLIES GENERAL INFORMATION ' 1 Building Orientation (South) 180 deg; Conditioned "Floor Area t 30,954i scift Number of; Stories 1 it Unconditioned, Floor Area ojsgft Number of Systems 191' Conditioned Footprint Area j 26 a15gft v Number of Zones ' I 221 u Orientation Gross s Area Glazing Area 'Glazing Ratio r r a 1 1 Front Elevation (South) 38871sgft 15901sgtt 40.9% Left Elevation (w } ;�1 2,49 Oft 334lsgft 13.4%1 ; Rear Elevation (North) . ro 5,837 sgft 661 sqn 11.3%i Right Elevation (East),.. 3,592 sgft. 1 857 sgft. Total 15,808sgrt. 3,aa2 sgL ft:`� 1' 21.8%I , is a ; Roof -1 14,5401 agft., ; 0 sgft: i Standard Proposed' I ' LEE Ener _q 8 Atmosphere Credit LightingPower Density '.' i 1.045'wisgft" 1.277 w�sgft. :Savings vs: Title.24' 0.07% i 1 Prescriptive Env. 'Heat Loss ' 5,390 h!' ` Bt�m Energy Performance CreditZ o Points i I 11. Prescriptive Env Heat Gain l 502,831 Btu/h-F 473,243 Btu/h-F I: 111• excludes process and receptacle 2. see LEED table 8-c or 8-d i. 1 Remarks: Did not show any of th Decorative Lighting '2" fixtures Run Initiation .Time: 06/25/04 09:57:56 Run Code:' 1088182676 EnergyPro 3.1 By EnergySoft User Number.. 2531 Job Number. 40528 Page:3 of 53 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1 tOJECT NAME The Hideaway Golf Clubhouse DATE 6/25/2004 ZONE INFORMATION' System Name Zone Name Occupancy Type Floor Area (sgft.) Inst. LPD (Wlsf)1 Port. LPD (Wlsf)1 Ctrl. Credits' (Wlsf)2 Tailored Proc. Loads (Wlsf) LPD (W/sf) 3 HP -2 Wine Room RetailMholesale Sales 720 1.907 0.000 0.381 The HVAC System "Lennox HP29-120/CBH17-135V: Premium Eff' 2.00 BHP Supply Fan Motor has been specified. HP -6 Pro Shop Retail/Wholesale Sales 1,035 2.201 0.000 0.174 The HVAC System "Dectron CCA-006/MAM-030: Premium Eff' 0.25 BHP Supply Fan Motor has been specified. HP -1,3,4,5,7,11-14 Fitness Areas Exercise Center 3,111 1.845 0.000 Salon Beauty Shop 225 2.151 0.000 0.230 Offices Office 1,506 1.145 0.000 0.010 Men's Locker/Massage Locker & Dressing Room 2,159 1.418 0.000 0.176 Lounge Areas Bar/Lounge/Casino 4,748 1.493 0.000 0.186 Dining Areas Dining Area 1,133 1.711 0.000 0.098 Entry Lobby Main Entry & Assembly 1,043 1.928 0.000 0.021 Mech/Equip/Fire/Panel Electrical & Mechanical 742 0.919 0.000 0.184 Support Areas Corridor/Restroom/Support 3,880 1.535 0.000 0.401 HP -8,10,15 Lockers Locker & Dressing Room 4,781 0.932 0.000 0.147 Attendent Office 192 1.229 0.000 0.246 Dining Areas Dining Area 2,263 1.784 0.000 0.037 Men's Restroom Corridor/Restroom/Support 280 0.746 0.000 0.098 HP -9 Caddie Room Lobby (Office & Waiting) 189 0.984 0.0001 0.197 HP -16 Kitchen Kitchen & Food Prep 1,850 1.196 0.000 0.239 9.000 Kitchen Entry Lobby (Main Entry & Assembly 108 1.722 0.000 0.344 Notes: 1. See LTG -1 (items marked with asterisk, see LTG -2 by others) 2. See LTG -3 3. See LTG -4I Items above require special documentation EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adeauacv of the iustification. and may refect a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. Kitchen Support Corridor/Restroom/Support 465 0.957 0.000 0.326 AC -1 I Elev. Equi Room I Electrical & Mechanical 81 0.765 0.000 0.153 20.000 Notes: 1. See LTG -1 (items marked with asterisk, see LTG -2 by others) 2. See LTG -3 3. See LTG -4I Items above require special documentation EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adeauacv of the iustification. and may refect a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. Plan Field The Construction Assembly 6" Concrete Underground Slab Floor has an Outside Absorptivity of 0.00. The Construction Assembly 8" CMU Underground Wall has an Outside Absorptivity of 0.00. The Construction Assembly 12" CMU Underground Wall has an Outside Absor tivity of 0.00. The HVAC System "Lennox HP29-036/CB29M-41: Premium Eff' 0.33 BHP Supply Fan Motor has been specified. The HVAC System "Lennox HP29-048/CB29M-51 : Premium Eff" 0.75 BHP Supply Fan Motor has been specified. The HVAC System "Lennox HP29-090/CBH17-95V: Premium Eff' 1.50 BHP Supply Fan Motor has been specified. The HVAC System "Lennox HP29-120/CBH17-135V: Premium Eff' 2.00 BHP Supply Fan Motor has been specified. The HVAC System "Lennox PUHI8EK/PKH18FK: Premium Eff' 0.20 BHP Supply Fan Motor has been specified. The HVAC System "Lennox THA150S: Premium Eff' 5.00 BHP Supply Fan Motor has been specified. The HVAC System "Dectron CCA-006/MAM-030: Premium Eff' 0.25 BHP Supply Fan Motor has been specified. PERFORMANCE CERTIFICATE.O-F:-.COMP,LIANCE Part 3 of 3 PERF -1' :OJECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 ZONE INFORMATION System Name Zone Name Occupancy Type Floor Area (sqft.) Inst. LPD (W/sf)1 Port. LPD (W/sf)1 Ctrl. Credits (W/sf)2 Tailored Proc. Loads (W/sf) LPD (W/sf) 3 AC -2,3 Hot Tub Locker & Dressing Room 352 0.841 0.000 0.127 Mechanical Room Electrical & Mechanical 91 0.681 0.000 0.136 Notes: 1. See LTG -1 (items marked with asterisk, see LTG -2 by others) 2. See LTG -3 3. See LTG -4 Items above require special documentation EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special 'ustification and documentation submitted. I Plan I Field The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant. Authorized Signature or Stamp I EnerovPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 _ _ _ Page:5 of 53 �E'NVELOPE COMPLIANCE SUMMARY Performance ENV -1 20JECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 OPAQUE SURFACES # Surface Framing Type Type Area U -Fac. Solar Act. Gains Azm. Tilt Y/N Form 3 Reference Location / Comments 1 Wall None 200 0.148 0 90 X 8" CMU w/ Stucco & Insul. Pro Shop 2 Wall None 376 0.148 90 90 1 X Window 8" CMU w/ Stucco & Insul. Pro Shop 3 Wall None 174 1 0.148 180 90 X Pro Shop 8" CMU w/ Stucco & Insul. Pro Shop 4 Wall Wood 482 0.056 0 90 X Double Mtl Tinted Default 8" CMU w/ R19 Fitness Areas 5 Wall Wood 432 0.056 90 90 X 180 8" CMU w/ R19 Fitness Areas 6 Wall Metal 576 0.209 0 90 X 12" CMU Underground Wall Fitness Areas 7 Wall Metal 325 0.209 _ 0 90 X 12" CMU Underground Wall Fitness Areas 8 Wall Wood 168 0.065 180 1 90 X R-19 Wall (W.19.2x6.16) Salon 9 Wall Metal 670 0.209 0 90 X 12" CMU Underground Wall Offices 10 Wall None 132 0.148 0 90 X 8" CMU w/ Stucco & Insul. Offices 11 Roof Wood 204 0.035 0 0 X Window R-30 Roof(R.30.202.16) Offices 12 Wall Wood 154 0.065 0 90 X itness Areas R-19 Wall (W.19.2x6.16) Offices 13 Door Metal 20 0.581 0 90 X Double Mtl Tinted Default Hollow Metal Door Offices 14 Wall Wood 150 0.065 270 90 XII 90 R-19 Wall (W.19.2x6.16) Offices 15 Wall None 348 0.148 90 90 X 16 0.720 8" CMU w/ Stucco & Insul. Men's Locker/Massage 16 Door Metal 60 0.581 90 90 XI 13 Hollow Metal Door Men's Locker/Massage 17 Wall None 80 0.148 90 90 X 8" CMU w/ Stucco & Insul. Men's Locker/Massage 18 Wall 112 0.148 180 90 X 0.59 8" CMU w/ Stucco & Insul. Men's Locker/Massage 19 LNone Door etal 20 0.581 180 90 Hollow Metal Door Men's Locker/Massage 20 Roof ood 1,625 0.035 0 0 X R-30 Roof(R.30.2x12.16) Men's Locker/Massage FENESTRATION SURFACES Site Assembled Glazing Check box if Building is - 100,000 sgft of CFA and - 10,000 sqft vertical glazing then NFRC Certification is required. Follow NFRC 100 -SB Procedures and submit NFRC Label Certificate Form. # Type Area U -Fac. Act. Azm. SHGC Glazing Type Location / Comments Window 52 0.720 0 0.60 Double Mtl Tinted Default Pro Shop Window 54 0.850 0 0.59 Double Mtl Tinted Default Pro Shop 3 Window 92 0.720 90 0.60 Double Mtl Tinted Default Pro Shop 4 Window 96 0.720 180 0.60 Double Mtl Tinted Default Pro Shop 5 Window 48 0.850 180 0.59 Double Mtl Tinted Default Pro Shop 6 Window 96 0.850 0 0.59 Double Mtl Tinted Default itness Areas 7 Window 96 0.720 90 0.60 Double Mtl Tinted Default Fitness Areas 8 Window 48 0.850 90 0.59 Double Mtl Tinted Default Fitness Areas 9 Window 96 0.850 90 0.59 Double Mtl Tinted Default itness Areas 10 Window 30 0.720 0 0.60 Double Mtl Tinted Default Difices 11 Window 64 0.850 90 0.59 Double Mtl Tinted Default Men's Locker/Massage 12 Window 16 0.720 0 0.60 Double Mtl Tinted Default Men's Locker/Massage 13 Window 168 0.720 180 0.60 Double Mtl Tinted Default ounge Areas 14 Window 48 0.850 180 0.59 Double Mtl Tinted Default ounge Areas 15 Window 160 0.720 90 0.60 Double Mtl Tinted Default Loun a Areas EXTERIOR SHADING ## Exterior Shade Type SHGC Window Hgt. Wd. Overhang Left Fin Right Fin Len. Hgt. LExt.RExt. Dist. Len. Hat. Dist. Len. Hat. 1 None 0.76 2 None 0.76 8.0 9.0 8.0 1.0 8.0 8.0 3 None 0.76 4 None 0.76 8.0 12.0 13.0 2.0 13.0 13.0 5 None 0.76 8.0 6.0 13.0 2.0 13.0 13.0 None 0.76 None 0.76 None 0.76 8.0 6.0 11.0 2.0 11.0 11.0 P61 None 0.76 8.0 .12.0 11.0 2.0 11.0 11.0 None 0.76 5.0 6.0 14.0 1.0 14.0 14.0 None 0.76 8.0 8.0 11.0 2.0 11.0 11.0 None 0.76 3 None 0.76 8.0 121.0 13.0 2.0 13.0 13.0 4 None 0.76 8.0 6.0 13.0 2.0 13.0 13.0 5 None 0.76 8.0 20.0 1.0 0.1 1.0 1.0 Run Initiation Time: 06/25/04 09:57:56 Run Code: 1088182 76 EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page:6 of 53 ENVELOPE COMPLIANCE SUMMARY Performance ENV -1 tOJECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 OPAQUE SURFACES # Surface Type Framing Type Act. Area U -Fac. Azm. Solar Gains Tilt Y/N Form 3 Reference Location / Comments 21 Wall Wood 264 0.065 0 90 X _ R-19 Wail (W:19.2x6.16) Men's Locker/Massa e 22 Door Metal 20 0.581 0 90 X 90 Hollow Metal Door Men's Locker/Massage 23 Wall Wood 42 0.065 90 90 X _ R-19 Wall W.19.2x6.16) Men's Locker/Massage 24 Wall Wood 300 0.065 270 90 X 36 0.720 R-19 Wall W.19.2x6.16 Men's Locker/Massage 25 Wall None 240 0.148 180 90 X 72 0.850 8" CMU w/ Stucco & Insul. Lounge Areas 26 Wall Metal 210 0.209 0 90 Window X 12" CMU Underground Wall Lounge Areas 27 Roof Wood 1,710 0.035 0 0 X 216 0.850 R-30 Roof R.30.2x12.16 Lounge Areas 28 Wall Wood 130 0.065 0 90 X 42 0.850 R-19 Wall (W.19.2x6.16) Lounge Areas 29 Wall Wood 280 0.065 90 90 X Window R-19 Wall W.19.2x6.16 Lounge Areas 30 Wall Wood 369 0.065 180 90 X 25 R-19 Wall (W.19.2x6.16) Lounge Areas 31 Roof Wood 1,152 0.035 0 0 X R-30 Roof R.30.2x12.16 Lounge Areas 32 Wall Wood 288 0.065 180 90 X Dining Areas R-19 Wall (W.19.2x6.16) Lounge Areas 33 Wall Wood 360 0.065 270 90 X R-19 Wall W.19.2x6.16 Lounge Areas 34 Wall Wood 216 0.065 180 90 X Double Mtl Tinted Default R-19 Wall (W.19.2x6.16) Dining Areas 35 Roof lWood 512 0.035 0 0 X 0.77 R-30 Roof R.30.2x12.16 Dining Areas 36 Wall _Wood 80 0.065 0 90 , X 0 R-19 Wall .1 9.2x6.16) Dining Areas 37 Wall Wood 80 0.065 180 90 X R-19 Wall (W.19.2x6.16) Dining Areas 38 Wall Wood 80 0.065 270 90 R-19 Wall (W.19.2x6.16) Dining Areas 39 Roof Wood 225 0.035 0 0 X Window Hgt. Wd. R-30 Roof(R.30.2x12.16) Dining Areas 40 Wall Wood 135 0.065 0 90 X 0.76 R-19 Wall (W.19.2x6.16) Dining Areas FENESTRATION SURFACES Site Assembled Glazing11 Check box if Building is - 100,000 sqft of CFA and - 10,000 sqft vertical glazing then NFRC Certification is required. Follow NFRC 100 -SB Procedures and submit NFRC Label Certificate Form. # Type Area U -Fac. Act. Azm. SHGC Glazing Type Location / Comments Window 32 0.720 90 0.60 Double Mtl Tinted Default Lounge Areas _ Window 48 0.850 90 0.59 Double Mtl Tinted Default Lounge Areas 18 Window 216 0.720 180 0.60 Double Mtl Tinted Default Lounge Areas 19 Window 36 0.720 180 0.60 Double Mtl Tinted Default Lounge Areas 20 Window 72 0.850 180 0.59 Double MtI Tinted Default Lounge Areas 21 Window 108 0.720 180 0.60 Double Mtl Tinted Default Lounge Areas 22 Window 216 0.850 180 0.59 Double Mtl Tinted Default Lounge Areas 23 Windcw 42 0.850 180 0.59 Double Mtl Tinted Default Dining Areas 24 Window 64 0.720 0 0.60 Double Mtl Tinted Default Dining Areas 25 Window 48 0.850 0 0.59 Double Mtl Tinted Default Dining Areas 112 0.720 180 0.60 Double Mtl Tinted Default Dining Areas Window 112 0.720 270 0.60 Double Mtl Tinted Default Dining Areas r926Window Window 45 0.720 0 0.60 Double Mtl Tinted Default Dining Areas Window 42 0.550 270 0.77 Double Clear Default (NW) Dinin Areas Window 1 48 0.720 0 0.60 Double Mtl Tinted Default Entry EXTERIOR SHADING ## Exterior Shade Type SHGC Window Hgt. Wd. Overhang Left Fin Right Fin Len. Hat. LExt.RExt. Dist. Len. Hat. Dist. Len. Hot_ 16 None 0.76 8.0 4.0 8.0 0.1 8.0 8.0 17 None 0.76 8.0 6.0 8.0 0.1 `8.0 8.0 18 None 0.76 8.0 27.0 1.0 0.1 1.0 1.0 19 None 0.76 9.0 4.0 18.0 0.1 18.0 18.0 20 None 0.76 12.0 6.0 18.0 0.1 18.0 18.0 21 None 0.76 9.0 12.0 7.0 0.1 7.0 7.0 22 None 0.76 12.0 18.0 7.0 0.1 7.0 7.0 23 None 0.76 7.0 6.0 12.0 1.0 12.0 12.0 24 None 0.76 25 None 0.76 _ 26 None 0.76 8.0 14.0 9.0 1.0 9.0 9.0 27 None 0.76 8.0 14.0 1.0 0.1 1.0 1.0 �q None 0.76 5.0 9.0 1.0 0.1 1.0 1.0 i None 0.76 7.0 6.0 1.0 0.1 1.0 1.0 None 0.76 8.0 6.0 20.0 0.0 20.0 20.0 Run Initiation Time: 06/25/04 09:57:56 Run Code: 1088182676 EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page:7 of 53 ENVELOPE COMPLIANCE SUMMARY Performance ENV -1 tOJECT NAME The Hideaway Golf Clubhouse DATE 6/25/2004 OPAQUE SURFACES # Surface Framing Type Type Area U -Fac. Solar Act. Gains Azm. Tilt y/N Form 3 Reference Location / Comments 41 Wall Wood 150 0.065 270 90 X R-19 Wall (W.19.2k6.16) Dining Areas 42 Roof Wood 768 0.035 0 0 X R-30 Root R.30.2x12.16 Entry 43 Wall Wood 144 1 0.065 0 90 X R-19 Wall (W.19.2x6.16) Entry 44 Door Metal 42 0.581 0 90 X Hollow Metal Door Entry 45 IRoof Wood 275 0.035 0 0 X R-30 Roof(R.30.2xl2.16) Entry 46 Wall Wood 48 0.065 0 90 X R-19 Wall (W.19.2x6.16) Entry 47 Wall Metal 108 0.209 0 90 X 12" CMU Underground Wall Mech/Equip/Fire/Panel 48 Wall Metal 396 0.209 0 90 X 12" CMU Underground Wall Support Areas 49 Roof Wood 490 1 0.035 0 0 X R-30 Roof(R.30.2xl2.16) Support Areas 50 Wall Wood 150 0.065 0 90 X R-19 Wall (W.19.2x6.16) Support Areas 51 Wall Wood 36 0.065 270 90 X R-19 Wall (W.19.26.16) Support Areas 52 Wall Wood 521 0.065 90 90 X R-19 Wall (W.19.2x6.16) Lockers 53 Roof Wood 1,625 0.035 0 0 XI IR-30Roof(R.30.2x12.16)Lockers Double Mtl Tinted Default 54 Wall Wood 264 0.065 0 90 xj IR-19Wall (W.19.2x6.16) Lockers 55 Door Metal 20 0.581 0 90 X I Hollow Metal Door Lockers 56 Wall Wood 42 0.065 90 90 X R-19 Wall (W.19.2x6.16) Lockers 57 Wall Wood 300 0.065 270 90 X R-19 Wall (W.19.2x6.16) Lockers 58 Roof Wood 464 0.035 0 0 X R-30 Roof(R.30.2x12.16) Lockers 59 W all None 258 0.615 90 90 X 8" CMU w/ Stucco Lockers 60 Wall None 168 0.615 1 270 90 X 8" CMU w/ Stucco Lockers FENESTRATION SURFACES 0.720 I -I Check box if Building is - 100,000 sgft of GFA and >= 1U,Uoo sqtt vertical glazing then Nt-Kc certmcauon is required. Site Assembled Glazing I Fnllnw NFP(-. inn -RR Prnrprtures and suhmit NFRC I ahel Certificate Form_ tt Type Area U -Fac. Act. Azm. SHGC Glazing Type Location / Comments I Window 24 0.850 0 0.59 Double Mtl Tinted Default Ent ? Window 25 0.720 90 0.60 Double Mtl Tinted Default Lockers 33 Window 16 0.720 0 0.60 Double Mtl Tinted Default Lockers 34 Window 240 0.720 180 0.60 Double Mtl Tinted Default Dining Areas 35 Window 68 0.720 270 0.60 Double Mtl Tinted Default IDining Areas 36 Window 48 0.720 90 0.60 Double Mtl Tinted Default Dining Areas 37 Window 48 0.720 90 0.60 Double Mtl Tinted Default IDining Areas 38 Window 52 0.850 90 0.59 Double Mtl Tinted Default Dining Areas 39 Window 48 0.720 90 0.60 Double Mtl Tinted Default Dining Areas 40 Window 24 0.720 180 0.60 Double Mtl Tinted Default Dining Areas 41 Window 54 0.850 180 0.59 Double Mtl Tinted Default :)ining Areas 42 Window 110 0.720 180 0.60 Double Mtl Tinted Default Dining Areas 43 Window 4 0.720 0 0.60 Double Mtl Tinted Default Hot Tub 44 Window :24 0.850 0 0.59 Double Mtl Tinted Default Hot Tub 45 Window 2 0.720 270 0.60 Double Mtl Tinted Default of Tub EXTERIOR SHADING ## Exterior Shade Type Window SHGC Hgt. Wd. Overhang Left Fin Len. Hot. LExt.RExt. Dist. Len. H t. Right Fin Dist. Len. Hqt. 31 None 0.76 8.0 3.0 20.0 0.0 20.0 20.0 32 None 0.76 33 None 0.76 34 None 0.76 12.0 20.0 6.0 1.0 6.0 6.0 35 None 0.76 8.0 8.5 14.0 1.0 14.0 14.0 36 None 0.76 8.0 6.0 12.0 1.0 12.0 12.0 37 None 0.76 8.0 6.0 4.0 1.0 4.0 4.0 38 None 0.76 39 None 0.76 40 None 0.76 8.0 3.0 7.0 1.0 7.0 7.0 41 None 0.76 9.0 6.0 7.0 1.0 7.0 7.0 42 None 0.76 11.0 10.0 2.0 1.0 2.0 2.0 _ '3 None 0.76 _ 4 None 0.76 .5 one 0.76 Run Initiation Time: 06/25/04 09:57:6 Run Code: 1088182 76 EnergyPro 3.1 By Energysoft User Number: 2531 Job Number: 40528 Page:8 of 53 [ENVELOPE COMPLIANCE SUMMARY Performance ENV -1 tOJECT NAME The Hideaway Golf Clubhouse DATE 6/25/2004 OPAQUE SURFACES # Surface Type Framing Type Area Act. U -Fac. Azm. Solar Gains Tilt Y/N Form 3 Reference Location I Comments 61 Roof Wood 1,512 0.035 0 0 X R-30 Roof(R.30.2x12.16) Dining Areas 62 Wall Wood 338 0.065 180 90 X R-19 Wall (W.19.2x6.16) Dining Areas 63 Wall Wood 204 0.065 270 90 X R-19 Wall (W.19.2x6.16) Dining Areas 64 Roof Wood 751 0.035 0 0 X R-30 Roof(R.30.2x12.16) Dining Areas 65 Wall Wood 120 0.065 90 90 X R-19 Wall (W.19.2x6.16) Dining Areas 66 Wall _ Wood 140 0.065 90 90 X R-19 Wall (W.19.2x6.16) Dining Areas 67 Wall Wood 148 0.065 180 90 X1 R-19 Wall W.19.2x6.16 Dining Areas 68 Roof Wood 280 0.035 0 0 X R-30 Roof(R.30.2x12.16) Men's Restroom 69 Wall Wood 168 0.065 270 90 X R-19 Wall (W.19.2x6.16 Men's Restroom 70 Wall None 204 0.290 0 90 X 8" CMU Underground Wall Caddie Room 71 Roof Wood 1,850 0.035 0 0 X R-30 Roof R.30.2x12.16 Kitchen 72 Wall Wood 270 0.065 0 90 X R-19 Wall (W.19.2x6.16) Kitchen 73 Roof Wood 108 0.035 0 1 0 X I I R-30 Roof(R.30.2x12.16) Kitchen Entry 74 Wall Wood 36 0.065 90 90 X R-19 Wall (W.19.2x6.16) Kitchen Entry 75 Wall Wood 124 0.065 180 90 X1 R-19 Wall (W.19.2x6.16) Kitchen Entry 76 Door Metal 20 0.581 180 90 X Hollow Metal Door Kitchen Entry 77 Roof Wood 272 0.035 0 0 X R-30 Roof(R.30.2x12.16) Kitchen Support 78 Roof Wood 193 0.035 0 0 R-30 Roof R.30.2x12.16 Kitchen Support 79 Roof Wood 81 0.035 0 0 X R-30 Roof R.30.2x12.16 Elev. Equip. Room 80 Roof Wood 352 0.035 0 0 X L R-30 Roof(R.30.2x12.16) Hot Tub FENESTRATION SURFACES Site Assembled Glazing Check box if Building is — 100,000 sgft of CFA and — 10,000 sqft vertical glazing then NFRC Certification is required. 11 Follow NFRC 100 -SB Procedures and submit NFRC Label Certificate Form. It Type Area U -Fac. Act. Azm. SHGC Glazing Type Location / Comments EXTERIOR SHADING Window Overhang Left Fin Right Fin ## Exterior Shade Type SHGC Hgt. Wd. Len. Hat. LExt.RExt. Dist. Len. H t. Dist. Len. H t. Run Initiation Time: 06/25/04 09:57:6 Run Code: 1088182676 EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page:9 of 53 ENVELOPE COMPLIANCE SUMMARY Performance ENV -1 tOJECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 OPAQUE SURFACES it Surface Framing Type Type Area U -Fac. Act. Azm. Solar Gains Tilt Y/N Form 3 Reference Location / Comments 81 Wall None 132 0.615 0 90 X 8" CMU w/ Stucco Hot Tub 82 Wall None 86 0.615 270 90 X I 8" CMU w/ Stucco Hot Tub 83 Roof Wood 91 0.035 0 0 X R-30 Roof R.30.2xl2.16 Mechanical Room 84 Wall None 156 0.615 270 90 X 8" CMU w/ Stucco Mechanical Room 1 I FENESTRATION SURFACES Site Assembled Glazing Check box if Building is — 100,000 sgft of CFA and — 10,000 sqft vertical glazing then NFRC Certification is required. Follow NFRC 100 -SB Procedures and submit NFRC Label Certificate Form. # Type Area U -Fac. Act. Atm. SHGC Glazing Type Location / Comments EXTERIOR SHADING Window Overhang Left Fin Right Fin ## Exterior Shade Type SHGC Hgt. Wd. Len. Hat. LExt.RExt. Dist. Len. Hgt. Dist. Len. Hat. Run Initiation Time: 06/25/04 09:57:56 Run Code: 1088182676 EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page: 10 of 53 JUGHTING COMPLIANCE SUMMARY, Part 1 of 2 LTG -1 20JECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 INSTALLED LIGHTING SCHEDULE I AMPS I RAI I ASTS II Luminaire Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # watts Lamp DESCRIPTION # (Lamp + # Ballast Watts Total Waw A 3 4 ft Fluorescent T8andem) Elec F32T8 3 32 Electronic 1.5 1 93.0 93 Al (3) 4 It Fluorescent T8 (Tandem) Elec F32T8 MANDATORY AUTOMATIC CONTROLS 32 Electronic 1.51 78 93.0 7,254 AC 37w Low Voltage Halogen HA3MR/3470S/1­113 6 1 37 Electronic I.q 921 37-01 3,4041 AP 37w Low Voltage Halogen HA3MR/347OS/HB2 6 1 37 Electronic 1.0 16 37.0 592 B 2) 4 ft Fluorescent T8 Elec F.2T8 2 32 Electronic 1.0 11 62-011 682 C (3 4 ft Fluorescent T8 (Tandem) Elec F32T8 3 32 Electronic 1.5 13 93.0 1,209 CSL (3) 35w Low Voltage Halogen (.3)_Q35MR16(12V) _3 35 Electronic 1.0 4 105.0 420 D (2) 4 It Fluorescent T8 Elec F32T8 2 32 Electronic 1.0 7 62.0 434 D1 75w Recessed Incandescent 75W 1 75 No Ballast 6 75.0 450 DS 35w Low Voltage Halogen Q35MR16 12V 1 35 Magnetic Energy Efficient 1. 33 39.0 1,287 FD (1) 32w Compact Fluorescent Triple 5/32T/LUNA 1 32 Electronic 1.0 113 32.0 3,616 FD1 1 18w Compact Fluorescent Quad 2 Pin ' CFQ18W/G24d-2 1 18 Magnetic Standard 1.0 11 25.0 275 HT20 45w Track Light 45 w per Foot Track Lights 1 45 No Ballast 40 45.0 l 800 CONTROL LOCATION (Room # or Dwg. #) CONTROL IDENTIFICATION Subtotal from this Page 21,516 Lighting Schedule on Plans Shows Exterior Lighting NOTE TO FIELD Total 44,725 Meets Multi -scene Dimming DS ❑Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) ❑ Control Requirements of §131(0 Less Control Credit Watts (From LTG -3) 5,207 Wine Room Adjusted Actual Wafts 39,518 MANDATORY AUTOMATIC CONTROLS 3 Pro Shop Manual Dimming CONTROL TYPE (Auto Time Switch, Exterior, etc.) _:IMS S SPACE CONTROLLED NOTE TO FIELD CONTROL LOCATION (Room #) CONTROL IDENTIFICATION Run Initiation Time: 06/25/04 09:57:56 Run Code: 1088182676 �►,L�ip VIA IIDI-G rr)KITROI R FOR CRFnIT CONTROL LOCATION (Room # or Dwg. #) CONTROL IDENTIFICATION CONTROL TYPE (Occupant, Daylight, Dimming, etc.) LUMINAIRES CONTROLLED NOTE TO FIELD TYPE # OF LUMINAIRES Wine Room Multi -scene Dimming DS 7 Wine Room Multi -scene Dimming Z49 4 Wine Room Multi -scene Dimming Z50 3 Pro Shop Manual Dimming HT20 40 NOTES TO FIELD - For Building Department Use Onl Run Initiation Time: 06/25/04 09:57:56 Run Code: 1088182676 EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page: 11 of 53 1 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 20JECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 INSTALLED LIGHTING SCHEDULE LAMPS I BALLASTS 11 Luminaire Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Larn DESCRIPTION # (Lamp+tsanast # Watts Total Watts HW 40w Recessed Incandescent 40W 1 40 No Ballast 5 40.0 200 S (1) 32w Compact Fluorescent Triple 5/32T/LUNA 1 32 Electronic 1. 25 32.0 800 SM4 (1)4 ft Fluorescent T8 Elec F32T8 1 32 Electronic 1. 2 32.0 64 U4 1 4 ft Fluorescent T8 Elec F32T8 1 32 Electronic 1.0 6 32.0 192 W14 U 4 ft Fluorescent T8 Elec F3218 2 32 Electronic 1.0 6 62.0 372 W14 4) 4 ft Fluorescent T8 Elec F32T8 4 32 Electronic 2.0 1 124.0 124 XB 37w Low Voltage Halogen HA M} R/347 SO /HB 6 1 37 Electronic 1.0 3 37.0 111 XW 37w Low Voltage Halogen HA3MR/ 3470S/HB_ 6 1 37 Electronic 1.0 6 37.0 222 Y1 1 32w Fluorescent 1 32 Electronic 1.0 4 32.01 128 Y2 400w Hanging Incandescent 400w 1 400 No Ballast 13400.0 5.20 Y3 (1) 39w Fluorescent F39BX/SPX35/RS 1 39 Electronic 1.0 2 39.0 78 Z10 300w Candelabra 25W 12 300 No Ballast 6 300.0 1,800 Z12 300w Candelabra 125W 12 300 No Ballast 3 300.0 900 Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page 10,191 Meets Total 44,725 Portable Lighting (From LTG -1) ❑ Efficac; and Control Requirement of §130(c) Less Control Credit Watts (From LTG -3) 5,207 ❑ Control Requirements of §131(f) Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room #) CONTROL IDENTIFICATION CONTROL TYPE (Auto Time Switch, Exterior, etc.) SPACE CONTROLLED NOTE TO FIELD AC 2 AC 4 CSL 4 CONTROL LOCATION CONTROL (Room # or Dwg. #) IDENTIFICATION Salon Office Massaae Rooms CONTROL TYPE (Occupant, Daylight, Dimming, etc.) Multi -scene Multi -scene Dimmi Occ Sensor — 250 LUMINAIRES CONTROLLED TYPE # OF LUMINAIRES AC 7 AC 2 AC 4 CSL 4 NOTE TO FIELD EneravPro 3.1 By EnergvSoft User Number. 2531 Job Number: 40528 Page: 12 of 53 1 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 ° LTG -1 ROJECT NAME The Hideawav Golf Clubhouse INSTALLED LIGHTING SCHEDULE DATE 6/25/2004 LAMPS I BALLASTS 11 Luminaire Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Per Lamp DESCRIPTION # (Lamp + # tsanast Watts Total Watts Z13 75w Candelabra 25W 3 75 No Ballast 2 75.0 150 Z14 150w Candelabra 25W 6. 150 No Ballast 1 150.0 150 Z15 75w Candelabra 25W 3 75 No Ballast 1 2 75.011150 Z16 75w Candelabra 25W 3 75 No Ballast 4 75.0 300 Z17 350w Candelabra 25W 14 350 No Ballast 3 350.0 1,050 Z19 75w Candelabra 125W 3 75 No Ballast 3 75.0 225 Z20 75w Oandelabra 25W 75 No Ballast 6 75.0 450 Z21 (2) 18w Comp. Fluor. 4 -Pin (2 1 w Comp. Fluo r. 2 18 Electronic 2.0 ill 36.0 396 Z22 175w Candelabra n 3 75 No Ballast 4 75.0 300 Z23 75w Candelabra 25W 3 75 No Ballast 2 75.0 150 Z24 50w Candelabra 25W 2 50 No Ballast 2 50.0 100 Z25 75w Candelabra 25W 3 75 No Ballast 1 51 75.011 375 Z26 50w Candelabra 25W 2 50 No Ballast 1 2 50.0 100 3,896 Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page Meets Total 44,725 ❑ Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) r_1 Control Requirements of §131(f) Less Control Credit Watts (From LTG -3) 5,207 39,518 Adjusted Actual Watts MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room #) CONTROL LOCATIOI (Room # or Dwg. #) Men's Locker Men's Locker Men's Locker Women's Lounoe CONTROL IDENTIFICATION CONTROL TYPE )ant, Daylight, Dimm Multi -scene Dimmin Occ Sensor — 250 s Occ Sensor — 250 s, Multi -scene Dimmin etc. LUMINAIRES CONTR-OILLED TYPE # OF LUMINAIRES AC 3 SM4 2 FD 36 AC 20 NOTE TO FIELD NOTE TO EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page: 13 of 53 1 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 ROJECT NAME The Hideaway Golf Clubhouse INSTALLED LIGHTING SCHEDULE DATE 6/25/2004 I AMDc I MAI 1 ACTQ II 1 uminaira Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Per Lamp V DESCRIPTION # (Lamp + Ballasd Total Watts # Watts Z27 75w Candelabra 25W 3 75 No Ballast 5 75.0 375 Z3 400w Candelabra 25W 16 400 No Ballast 4 400.0 1,600 Z32 (2) 18w Comp. Fluor. 4 -Pin 0_18w Comp. Fluor. 2 18 Electronic 2.0 2 36.0 72 Z33 (2) 18w Comp. Fluor. 4 -Pin Comp. Fluo . 2 18 Electronic 2. 2 36.0 72 Z38 1 36w Comp. Fluor. 4 -Pin �{L�w fp',tnbMEC9ma—Euo 1 36 Electronic 1.0 2 36.0 72 Z4 50w Candelabra �5W 2 50 No Ballast 4 50.0 200 Z40 (2) 18w Comp. Fluor. 4 -Pin (2-Y183K FIu01.2 18 Electronic 2.0 4 36.0 144 Z42 175w Candelabra �5V�n 3 75 No Ballast 21 75.01 150 Z43 2 18w Comp. Fluor. 4 -Pin (2)18w Comp _F_luo 2 18 Electronic 2.01 81 36.0 288 Z44 (2) 36w Comp. Fluor. 4 -Pin ff�%w Comp. Fluo . 2 36 Electronic 2.0 1 72.0 72 Z45 50w Candelabra 44 pp 25Vi/n 2 501 No Ballast 3 50.0 150 Z46 2 18w Comp. Fluor. 4 -Pin 18w Comp. Flu o . 2 18 Electronic 2. 5 36.0 180 Z48 75w Candelabra 42)) 2511 3 75 No Ballast 1 75.0 75 Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page 3,450 Meets Total 44,725 �0❑Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) ❑ Control Requirements of§131(f) Less Control Credit Watts (From LTG -3) 5,207 Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION CONTROL (Room # or Dwg. #) IDENTIFICATION Women's Lounge Women's Lounge Men's Lounge Men's Lounae CONTROL TYPE ant, Daylight, Dimming, Multi -scene Dimming Multi -scene Dimming Multi -scene Dimming Multi -scene Dimmina LUMINAIRES CONTROLLED TYPE # OF LUMINAIRES Z56 2 Z57 4 AC 21 AP 3 NOTE TO FIELD NOTE TO EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Paae:14 of 53 ILIGH-rING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 ROJECT NAME The Hideaway Golf Clubhouse INSTALLED LIGHTING SCHEDULE DATE 6/25/2004 I AMPR I RAI I AQTC II Luminaire Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Per Lamp DESCRIPTION # (Lamp + Ballast Total Watts # Watts Z49 50w Candelabra 25W 2 50 No Ballast 4 50.0 200 Z5 150w Candelabra 25W 6 150 No Ballast 1 150.0 150 Z50 300w Candelabra 25W 12 300 No Ballast 3 300.0 900 Z51 50w Candelabra 25W 2 50 No Ballast 1 50.0 50 Z52 150w Candelabra 253a 6 150 No Ballast 1 150.0 150 Z56 400w Candelabra 25W 16 400 No Ballast 2 400.0 800 Z57 100w Candelabra 258 4 100 No Ballast 4 100.0 400 Z58 (4) 32w Comp. Fluor. 4 -Pin 4 32w Co21p. Fluo 4 32 Electronic 2.10 1 128.0 128 Z60 50w Candelabra5V�n 2 50 No Ballast1 50.0 50 Z62 75w Candelabra 25W 3 75 No Ballast 2 75.0 150 Z63 75w Candelabra 25W 3 75 No Ballast 1 75.0 75 Z68 (2) 18w Comp. Fluor. 4 -Pin (2).18w Com . Fluo . 2 181 Electronic 2.0 2 36.0 72 Z69 2 18w Comp. Fluor. 4 -Pin P(w Comp. Fluo . 2 18 Electronic 2.0 2 36.0 72 Alin Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page 3,197 Meets Tota I 44,725 ❑Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) ❑ Control Requirements of §131 Less Control Credit Watts (From LTG -3) 5,207 (f) Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION CONTROL (Room # or Dwg. #) IDENTIFICATION Men's Lounge Men's Lounge Bar/Lounge Tea Room TES TO FIELD - For Buildina Deoar CONTROLTYPE (Occupant, Daylight, Dimming, etc.) Multi -scene Dimming Multi -scene Dimming Multi -scene Dimming ne Dimmi LUMINAIRES CONTROLLED TYPE # OF LUMINAIRES Z17 3 Z19 3 DS 8 AC 5 NOTE TO FIELD NOTE TO EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page: 15 of 53-1 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LT'G-1 20JECT NAME The Hideaway Golf Clubhouse INSTALLED LIGHTING SCHEDULE DATE 6/25/2004 I AMPC I Rei I Acrc II Luminaire Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Per Lamp DESCRIPTION # (Lamp + Ballast Total Watts # watts Z7 300w Candelabra 25W 12 300 No Ballast 3 300.0 900 Z8 75w Candelabra 25W _3. 75 No Ballast 5 75.0 375 Z9 400w Candelabra 25W 16 400 No Ballast 31 400.0 1,200 Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page 2,475 Meets Total 44,725 ❑Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) ❑ Control Requirements of §131(f) Less Control Credit Watts (From LTG -3) 5,207 Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room # or Dwg. #) Tea Room Private Dining Inglenook Receotion/Fover CONTROL IDENTIFICATION nt CONTROL TYPE Int, Daylight, Dimm Multi -scene Dimmin Multi -scene Dimmin Multi -scene Dimmini Multi -scene Dimmin LUMINAIRES CONTRQLLED TYPE # OF LUMINAIRES AP 2 XW 6 AC 2 AC 3 NOTE TO FIELD NOTE TO FIELD EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Paae:16 of 53 1 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 ROJECT NAME The Hideawav Golf Clubhouse INSTALLED LIGHTING SCHEDULE DATE 6/25/2004 ❑ Efficacy and Control Requirement of §'130(c) Portable Lighting (From LTG -1) 0 Less Control Credit Watts (From LTG -3) 5,207 ❑ Contro! Requirements of §131(f) 39,518 Adjusted Actual Watts MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room # or Dwg. #) LAMPS BALLASTS Luminaire 2 Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # watts Per Lamp DESCRIPTION # (Lamp + # Ballast) Watts Total Watts Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page Meets Total 0 44,725 ❑ Efficacy and Control Requirement of §'130(c) Portable Lighting (From LTG -1) 0 Less Control Credit Watts (From LTG -3) 5,207 ❑ Contro! Requirements of §131(f) 39,518 Adjusted Actual Watts MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room # or Dwg. #) CONTROL IDENTIFICATION CONTROLTYPE (Occupant, Daylight, Dimm Serving Room 2 Occ Sensor — 250 s Mech/Equip/Fire D Occ Sensor <= 250 s, Mech/Equip/Fire 3 Occ Sensor — 250 s Panel Room Occ Sensor <= 250 s etc. LUMINAIRES CONTROLLED TYPE # OF LUMINAIRES Al 2 B 2 D 3 D 3 NOTE TO FIELD NOTE TO EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page: 17 of 53 1 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 <UJtt, I NAM: The Hideaway Golf Clubhouse INSTALLED LIGHTING SCHEDULE DATE 6/25/2004 1 A)10DQ I ow. I A- II 1 umin it Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Per Lamp DESCRIPTION # (Lamp + Ballastl Total Waw # Watts F1 r_. Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page C� Meets Total 44,725 ❑Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) 11 Control Requirements of §131(f) Less Control Credit Watts (From LTG -3) 5,207 Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room #) CONTROL IDENTIFICATION CONTROL TYPE (Auto Time Switch, Exterior, etc.) SPACE CONTROLLED NOTE TO FIELD AC 2 A 1 Al 23 CONTROL LOCATION CONTROL (Room # or Dwg. #) IDENTIFICATION Restrooms Restrooms Storage Rooms Storaae Rooms CONTROLTYPE )ant, Daylight, Dimming, etc Occ Sensor — 250 sgft Multi -scene Dimming Occ Sensor Storage Occ Sensor Storaae LUMINAIRES CONTROLLED TYPE # OF LUMINAIRES B 7 AC 2 A 1 Al 23 NOTE TO EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page:18 of 53 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 ROJECT NAME The Hideaway Golf Clubhouse INSTALLED LIGHTING SCHEDULE DATE 6/25/2004 LAMPS RALLASTS IF Luminaire Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Lamp DESCRIPTION # (Lamp + Ballasty, Total Wafts # • Watts D1 6 Men/Women's Restrooms Occ Sensor — 250 sgft FD 2 Men/Women's Restrooms Occ Sensor — 250 sgfl W14 1 Women's Locker Area Multi -scene Dimming AC 9 Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page Meets Total 44,725 17Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) Less Control Credit Watts (From LTG -3) 5,207 ❑ Control Requirements of §131(f) Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room #) CONTROL IDENTIFICATION CONTROL TYPE (Auto Time Switch, Exterior, etc.) SPACE CONTROLLED NOTE TO FIELD CONTROLLED NOTE TO FIELD TYPE # OF LUMINAIRES Men/Women's RestroomE Occ Sensor — 250 s ft D1 6 Men/Women's Restrooms Occ Sensor — 250 sgft FD 2 Men/Women's Restrooms Occ Sensor — 250 sgfl W14 CONTROLS FOR CREDIT CONTROL LOCATION (Room # or Dwg. #) CONTROL IDENTIFICATION CONTROL TYPE (Occupant, Daylight, Dimming, etc.) LUMINAIRES CONTROLLED NOTE TO FIELD TYPE # OF LUMINAIRES Men/Women's RestroomE Occ Sensor — 250 s ft D1 6 Men/Women's Restrooms Occ Sensor — 250 sgft FD 2 Men/Women's Restrooms Occ Sensor — 250 sgfl W14 1 Women's Locker Area Multi -scene Dimming AC 9 I EnerovPro 3.1 By EnemvSoft User Number: 2531 Job Number: 40528 Paoe:19 of 53 I LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 ZOJECT NAME The Hideaway Golf Clubhouse INSTALLED LIGHTING SCHEDULE DATE 6/25/2004 I AMD¢ I CAI 1 Aero II Luminairp Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Per Lamp _ DESCRIPTION # (Lamp + Ballast Total Watts # Watts Occ Sensor <- 250 si Women's Locker Area Occ Sensor — 250 s, VI _fighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page .Vleets Total 44,725 Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) Less Control Credit Watts (From LTG -3) 5,207 ❑ Control Requirements of§131(f) Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room # or Dwg. #) CONTROL IDENTIFICATION CONTROL TYPE (Occupant, Daylight, Dimm Women's Locker Area 4 Multi -scene Dimmin Women's Locker Area FD1 Occ Sensor — 250 si Women's Locker Area 10 Occ Sensor <- 250 si Women's Locker Area Occ Sensor — 250 s, etc. LUMINAIRES CONTROLLED TYPE # OF LUMINAIRES AP 4 FD 28 FD1 6 S 10 NOTE TO FIELD NOTE TO EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page:20 or 53 1 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 20JECT NAME The Hideaway Golf Clubhouse INSTALLED LIGHTING SCHEDULE DATE 6/25/2004 � ❑Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) 0 ❑ Control Requirements of §131(f) Less Control Credit Watts (From LTG -3) 5,207 Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room #) LAMPS BALLASTS Luminaire NOTE TO FIELD Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Per Lamp DESCRIPTION # (Lamp + Ballast), Total Watts # Watts Subtotal from this Page Total Lighting Schedule on Plans Shows Exterior Lighting Meets 44,725 � ❑Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) 0 ❑ Control Requirements of §131(f) Less Control Credit Watts (From LTG -3) 5,207 Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room #) CONTROL IDENTIFICATION CONTROL TYPE (Auto Time Switch, Exterior, etc.) SPACE CONTROLLED NOTE TO FIELD Occ Sensor — 250 Men's Locker Area FD Multi -scene Dimmii Men's Locker Area 7 Occ Sensor — 250 . Wet Area Multi -scene Dimmii CONTROL LOCATION (Room # or Dwg. #) CONTROL IDENTIFICATION CONTROL TYPE (Occupant, Daylight, Dimn Women's Locker Area 1 Occ Sensor — 250 Men's Locker Area FD Multi -scene Dimmii Men's Locker Area 7 Occ Sensor — 250 . Wet Area Multi -scene Dimmii etc LUMINAIRES CONTROLLED TYPE 1# OF LUMINAIRES W14 1 AC 5 FD 24 AP 7 NOTE TO EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page:21 of 53 1 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 ROJECT NAME DATE The Hideawav Golf Clubhouse 1 6/25/2004 1 INSTALLED LIGHTING SCHEDULE Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) 0 Less Control Credit Watts (From LTG -3) 5,207 ❑ Control Requirements of §131(f) Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room # or Dwg. #) LAMPS BALLASTS Luminaire 4 Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Lamp DESCRIPTION # (Lamp + # Ballast)Total Watts Waw Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page Meets Total 0 44,725 r� Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) 0 Less Control Credit Watts (From LTG -3) 5,207 ❑ Control Requirements of §131(f) Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room # or Dwg. #) CONTROL IDENTIFICATION CONTROLTYPE (Occupant, Daylight, Dimming, etc Wet Area 4 Occ Sensor — 250 sgft Wet Area AC Occ Sensor <= 250 sgft Attendent 1 Multi -scene Dimming Attendent Occ Sensor <= 250 sgft LUMINAIRES CONTR LLED TYPE # OF LUMINAIRES FD 4 S 8 AC 1 FD1 1 NOTE TO FIELD NOTE TO NOTES TO FIELD - For Building Department Use Only Run Initiation Time: 06/25/04 09:57:56 Run Code: 1088182676 EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page:22 of 53 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 ROJECT NAME DATE The Hideaway Golf Clubhouse 1 '6/25/2004 1 INSTALLED LIGHTING SCHEDULE LAMPS I BALLASTS 11 Luminaire Code LUMINAIRE DESCRIPTION _ TYPE DESCRIPTION _ # Watts Per Lamp DESCRIPTION # (Lamp + Ballast)Total Watts # Watts Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page Meets Total 44,725 ❑ Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) Control Requirements of §131(f) Less Control Credit Watts (From LTG -3) 5,207 ❑ 39,518 Adjusted Actual Watts MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room #) CONTROL LOCATION CONTROL (Room # or Dwg. #) IDENTIFICATION Attendent Attendent Mixed Grill Dinin Areas )TES TO FIELD - For Buildina Deoar CONTROL TYPE )ant, Daylight, Dimmin Occ Sensor — 250 sqf Occ Sensor — 250 sqf Automatic Time Switch Multi -scene Dimmina etc LUMINAIRES CONTROLLED TYPE # OF LUMINAIRES U4 3 Y3 2 DS 16 AC 5 NOTE TO FIELD NOTE TO FIELD EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page:23 of 53 1 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 ROJECT NAME DATE The Hideaway Golf Clubhouse -]-6/25/2004 INSTALLED LIGHTING SCHEDULE LAMPS I BALLASTS 11 Luminaire Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Lamp DESCRIPTION # kLamp Ballast Total Watts # Watts Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page Meets Total 44,725 Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) Less Control Credit Watts (From LTG -3) 5,207 Control Requirements of §131(f) 39,518 Adjusted Actual Watts MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room # or Dwg. #) Dining Areas Men's Restroom Men's Restroom CONTROL IDENTIFICATION rtm CONTROL TYPE (Occupant, Daylight, Dimming, etc.) Multi -scene Dimming Multi -scene Dimming Occ Sensor <= 250 sqft Occ Sensor <= 250 sgft__ LUMINAIRES CONTROLLED TYPE # OF LUMINAIRES DS 2 AC 1 FD1 4 Al 2 NOTE TO FIELD NOTE TO I EnergvPro 3.1 By EnergvSoft User Number: 2531 Job Number: 40528 Paae:24 of 53 1 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 20JECT NAME DATE The Hideaway Golf Clubhouse 1 6/25/2004 INSTALLED LIGHTING SCHEDULE I AMPS BALLASTS Luminaire Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Lamp DESCRIPTION # (Lamp + # ballast)Total Watts Watts Occ Sensor — 250 sqft Portable Lighting (From LTG -1) 23 El Efficacy and Control Requirement of §130(c) ❑ Control Requirements Less Control Credit Watts (From LTG -3) 5,207 of §131(f) 2 Kitchen Entry Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS 2 Kitchen Storage Rooms Occ Sensor Storage J Al 1 NOTES TO FIELD - For Building Department Use Only CONTROL LOCATION (Room #) Subtotal from this Page CONTROL TYPE (Auto Time Switch, Exterior, etc.) SPACE CONTROLLED NOTE TO FIELD Lighting Schedule on Plans Shows Exterior Lighting Meets TYPE Total 44,725 Occ Sensor — 250 sqft Portable Lighting (From LTG -1) 23 El Efficacy and Control Requirement of §130(c) ❑ Control Requirements Less Control Credit Watts (From LTG -3) 5,207 of §131(f) 2 Kitchen Entry Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS 2 CONTROL LOCATION (Room #) CONTROL IDENTIFICATION CONTROL TYPE (Auto Time Switch, Exterior, etc.) SPACE CONTROLLED NOTE TO FIELD NOTE TO FIELD TYPE # OF LUMINAIRES ,Kitchen Occ Sensor — 250 sqft Al 23 Kitchen Multi -scene Dimming AC 2 Kitchen Entry Occ Sensor — 250 sgft Al 2 CONTROLS FOR CREDIT CONTROL LOCATION (Room # or Dwg. #) CONTROL IDENTIFICATION CONTROL TYPE (Occupant, Daylight, Dimming, etc.) LUMINAIRES CONTROLLED NOTE TO FIELD TYPE # OF LUMINAIRES ,Kitchen Occ Sensor — 250 sqft Al 23 Kitchen Multi -scene Dimming AC 2 Kitchen Entry Occ Sensor — 250 sgft Al 2 Kitchen Storage Rooms Occ Sensor Storage J Al 1 NOTES TO FIELD - For Building Department Use Only LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 ROJECT NAME The Hideaway Golf Clubhouse INSTALLED LIGHTING SCHEDULE DATE 6/25/2004 i AMaq I PAI i AQTQ II Luminaire Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION # Watts Per Lamp _ DESCRIPTION # (Lamp + Ballast'Total Watts # Watts Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page Meets Total 44,725 ❑� ❑Efficacy and Control Requirement of §130(c) Portable Lighting (From LTG -1) ❑ Control Requirements of §131(f) ' Less Control Credit Watts (From LTG -3) 5,207 Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION CONTROL (Room # or Dwg. #) IDENTIFICATION (Occ Kitchen Storage Rooms Kitchen Storage Rooms Elev. Equip. Room Hot Tub :)TES TO FIELD - For Building Department Us Run Initiation Time: OFT EnergyPro 3.1 By EnergySoft User Number: 2531 CONTROL TYPE it, Daylight, Dimm Occ Sensor Occ Sensor — 250 sgft Occ Sensor — LUMINAIRES.QONTROLLED TYPE 1# OF LUMINAIRES FD 2 U4 3 D 1 S 7 Job Number: 40528 NOTE TO FIELD NOTE TO of 53 LIGHTING COMPLIANCE SUMMARY Part 1 of 2 LTG -1 1 AMPS I RAI I ARTS 11 Luminaire Code LUMINAIRE DESCRIPTION TYPE DESCRIPTION# Watts er Lamp DESCRIPTION # (Lamp + Ballast Total Watts # Watts Lighting Schedule on Plans Shows Exterior Lighting Subtotal from this Page Meets Total 44,725 ❑ rtable Lighting (From LTG -1) Efficacy and Control Requirement of §130(c) Po Less Control Credit Wafts (From LTG -3) 5,207 ❑ Control Requirements of §131(f) Adjusted Actual Watts 39,518 MANDATORY AUTOMATIC CONTROLS CONTROL LOCATION (Room # or Dwg. #) Mechanical Room CONTROL IDENTIFICATION NOTE TO FIELD CONTROL TYPE I LUMINAIRES CONTROLLED NOTE TO It, Daylight, Dimming, etc.) I TYPE 1# OF LUMINAIRES I I FIELD — 250 soft I I W14 NOTES TO FIELD - For Building Department Use Only Run Initiation Time: 06/25/04 09:57:56 Run Code: 1088182676 EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page:27 of 53 LIGHTING COMPLIANCE SUMMARY Part 2 of 2 LTG -1I ROJECT NAME The Hideaway Golf Clubhouse TOTAL WATTS (FROM TABLES 1A+1B) 1 DATE 6/25/2004 0 TABLE 1A - PORTABLELIGHTING NOT SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE FEET N a a a ROOM # OR ZONE ID DEFAULT W/s ft AREA (SF) TOTAL WATTS (B X C) TOTAL 0 0 TABLE 1 B - PORTABLE LIGHTING SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE FEET 0 ROOM # 0 PORTABLE LIGHTING o O a a 0 LUMIN. TASK # OF TOTAL TOTAL # OF WATTS PER AREA TASK AREA (SF) WATTS TABLE 1C - PLANS SHOW PORTABLE LIGHTING IS NOT REQUIRED FOR OFFICE AREAS > 250 SQUARE FEET ROOM # TOTAL AREA OR ZONE ID (SF) TOTAL 0 BUILDING SUMMARY - PORTABLE LIGHTING Designer needs to provide detailed documentation that the lighti level provided by the overhead lighting meets the needs of the space. The details include luminaire types, CU, and mounting locations relative to work areas. BUILDING SUMMARY TOTAL AREA (SF) (FROM TABLES 1A+1B+1 C) TOTAL WATTS (FROM TABLES 1A+1B) BUILDING TOTAL 0 0 I EneravPro 3.1 By EneravSoft User Number. 2531 Job Number: 40528 Page:28 of 53 1 CERTIFICATE OF COMPLIANCE Performance MECH-1 20JECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 SYSTEM FEATURES SYSTEM NAME TIME CONTROL SETBACK CONTROL ISOLATION ZONES HEAT PUMP THERMOSTAT? ELECTRIC HEAT? FAN CONTROL VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/COOL? HEATING SUPPLY RESET COOLING SUPPLY RESET HEAT REJECTION CONTROL VENTILATION OUTDOOR DAMPER CONTROL ECONOMIZER TYPE DESIGN O.A. CFM MECH-3, COLUMN 1) HEATING EQUIPMENT TYPE HEATING EQUIPMENT EFFICIENCY COOLING EQUIPMENT TYPE COOLING EQUIPMENT EFFICIENCY MAKE AND MODEL NUMBER PIPE INSULATION REQUIRED? PIPE/DUCT INSULATION PROTECTED? HEATING DUCT LOCATION I R -VALUE COOLING DUCT LOCATION R -VALUE VERIFIED SEALED DUCTS IN CEILING/ROOF SPACE ----------- MECHANICAL SYSTEMS DHW Heater HP -2 I I HP -6 NOTE TO FIELD PIPE INSULATION REQUIRED? M: Out. Air Measure D: Demand Control N: Natural n/a Programmable Switch Programmable Switch n/a Heating & Cooling Required Heating & Cooling Require n/a n/a n/a n/a Yes Yes n/a 0.0 kW 0.0 kW n/a Constant Volume Constant Volume n/a No No n/a No No n/a Constant Temp Constant Temp n/a Constant Temp Constant Temp n/a n/a n/a n/a Air Balance Air Balance n/a Auto Auto n/a No Economizer No Economizer n/a 360 cfm 518 cfm Gas Fired Heat Pump Heat Pum 91% 6.90 HSPF 7.50 HSPF n/a Split DX Split DX n/a 10.1 SEER/ 9.1 EER 10.2 SEER / 8.6 EER AO Smith BTH-250 Lennox HP29-036/CB29M- 41 Lennox HP29-048/CB29M- 51 Yes Yes Yes Yes No No n/a n/a Ducts in Attic 4.2 Ducts in Attic 4.2 n/a n/a Ducts in Attic 4.2 Ducts in Attic 4.2 n/a No No CODE TABLES: Enter code from table below into columns above. HEAT PUMP THERMOSTAT? TIME CONTROL SETBACKCTRL. ISOLATION ZONES FAN CONTROL ELECTRIC HEAT? S: Prog. Switch H: Heating Enter Number of I: Inlet Vanes O: Occupancy C: Cooling Isolation Zones. P: Variable Pitch VAV MINIMUM POSITION CONTROL? Sensor B: Both V: VFD SIMULTANEOUS HEAT / COOL? Y: Yes M: Manual Timer O: Other C: Curve N: No HEAT AND COOL SUPPLY RESET? VENTILATION OUTDOOR DAMPER ECONOMIZER O.A. CFM HIGH EFFICIENCY? B: Air Balance C: Outside Air Cert. A: Auto G: Gravity A: Air Enter Outdoor Air W: Water CFM. PIPE INSULATION REQUIRED? M: Out. Air Measure D: Demand Control N: Natural N: Not Required Note: This shall be no EC: Economizer less than Col. H on Control See Section MECH-3. PIPE/DUCT INSULATION PROTECTED? SEALED DUCTS IN CEILING/ROOF SPACE 4 AAI—» EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page:29 of 53 1 CERTI'FICAT'E OF COMPLIANCE Performance MECH-1 iOJECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 SYSTEM FEATURES SYSTEM NAME (TIME CONTROL I ISOLATION ZONES HEAT PUMP THERMOSTAT? ELECTRIC HEAT? VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEATICOOL? HEATING SUPPLY RESET COOLING SUPPLY RESET HEAT REJECTION CONTROL VENTILATION OUTDOOR DAMPER CONTROL ECONOMIZER TYPE DESIGN O.A. CFM (MECH-3, COLUMN iEATING EQUIPMENT TYPE HEATING EQUIPMENT EFFICIENCY COOLING COOLING EQUIPMENT EFFIC MAKE AND MODEL NUMBER PIPE INSULATION REQUIRE[ HEATING DUCT LOCATION I R -VALUE COOLING DUCT LOCATION I VALUE Programmable Switch Heating & Cooling Re uired n/a Yes 0.0 kW Constant Volume No No Constant Tem Constant Temp n/a Air Balance Auto No Economizer 10463 cfm Heat Pum 7.84 HSPF Split DX 10.1 EER Lennox HP29-090/CBH17- 95V Yes No Ducts in Attic 4.2 Ducts in Attic 4.2 No Programmable Switch Heating & Cooling Required n/a Yes 0.0 kW Constant Volume No No. Constant Temp Constant Temp n/a Air Balance Auto No Economizer 5292cfm Heat Pum 3.20 COP Split DX 10.1 EER Lennox HP29-120/CBH17- 135V Yes No Ducts in Attic 4.2 Ducts in Attic 4.2 No Programmable Switch Heating_&L Cooling Re uire n/a Yes 0.0 kW Constant Volume No No Constant Temp Constant Temp n/a Air Balance Auto No Economizer 100 cfm Heat Pum 7.00 HSPF Split DX 12.0 SEER / 11.0 EER Lennox PUHI8EK/PKH18F Yes No Ducts in Attic --A.2 Ducts in Attic 4.2 No CODE TABLES: Enter code from table below into columns above. HEAT PUMP THERMOSTAT? ELECTRIC HEAT? VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/ COOL? HEAT AND COOL SUPPLY RESET? HIGH EFFICIENCY? PIPE INSULATION REQUIRED? PIPE/DUCT INSULATION PROTECTED? SEALED DUCTS IN CEILING/ROOF SPACEi Y: Yes N: No NOTE TO FIELD TIME CONTROL SETBACK CTRL. ISOLATION ZONES FAN CONTROL S: Prog. Switch H: Heating Enter Number of I: Inlet Vanes O: Occupancy C: Cooling Isolation Zones. P: Variable Pitch Sensor B: Both V: VFD M: Manual Timer O: Other C: Curve VENTILATION OUTDOOR DAMPER ECONOMIZER O.A. CFM B: Air Balance A: Auto A: Air Enter Outdoor Air C: Outside Air Cert. G: Gravity W: Water CFM. M: Out. Air Measure N: Not Required Note: This shall be no D: Demand Control EC: Economizer less than Col. H on N: Natural Control See Section MECH-3. 144(ee)3 Run Initiation Time: 06/25/04 09:57:56 Run Code: 1088182676 EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page:30 of 53 rERTIFICATE OF COMPLIANCE Performance MECH-1 ROJECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 SYSTEM FEATURES MECHANICAL SYSTEMS SYSTEM NAME HP -16 AC -1 AC 2.3 ITIME CONTROL I ISOLATION ZONES HEAT PUMP THERMOSTAT? ELECTRIC HEAT? VAV MINIMUM POSITION CONTROL? SIMULTANEOUS HEAT/COOL? HEATING SUPPLY RESET COOLING SUPPLY RESET HEAT REJECTION CONTROL VENTILATION OUTDOOR DAMPER CONTROL ECONOMIZER TYPE DESIGN O.A. CFM (MECH-3, COLUMN HEATING EQUIPMENT TYPE HEATING EQUIPMENT EFFICIENCY COOLING EQUIPMENT TYPE COOLING EQUIPMENT EFFICIENCY MAKE AND MODEL NUMBER PIPE INSULATION REQUIRED? HEATING DUCT LOCATION R -VALUE COOLING DUCT LOCATION R -VALUE VERIFIED SEALED DUCTS IN CEILING/ROOF SPACE Programmable Switch Heating & Cooling Re uired n/a Yes 0.0 kW Constant Volume No No Constant Tem Constant Temp n/a Air Balance Auto No Economizer 217 cfm Heat Pum 3.10 COP Packaged DX 9.5 EER Lennox THA150S Yes No Ducts in Attic 4.2 Ducts in Attic 4.2 No Programmable Switch Heating & Cooling Required n/a Yes 0.0 kW Constant Volume No No Constant Tem Constant Temp n/a Air Balance Auto No Economizer 12 cfm Heat Pump 6.90 HSPF Split DX 10.1 SEER/9.1 EER Lennox HP29-036/CB29M- 41 Yes No Ducts in Attic 4.2 Ducts in Attic 4.2 No Programmable Switch Heating & Cooling Require n/a n/a n/a Constant Volume No No Constant Temp Constant Temp n/a Air Balance Auto No Economizer 165 cfm Gas Furnace 80% AFUE Split DX 10.0 SEER / 9.0 EER Dectron CCA-006/MAM-030 Yes No Ducts in Attic 4.2 Ducts in Attic 4.2 No CODE TABLES: Enter code from table below into columns above. HEAT PUMP THERMOSTAT? SETBACK CTRL. ELECTRIC HEAT? FAN CONTROL VAV MINIMUM POSITION CONTROL? H: Heating SIMULTANEOUS HEAT/ COOL? Y: Yes HEAT AND COOL SUPPLY RESET? N: No HIGH EFFICIENCY? P: Variable Pitch PIPE INSULATION REQUIRED?- B: Both PIPE/DUCT INSULATION PROTECTED? V: VFD SEALED DUCTS IN CEILING/ROOF SPACE TIME CONTROL SETBACK CTRL. ISOLATION ZONES FAN CONTROL S: Prog. Switch H: Heating Enter Number of 1: Inlet Vanes O: Occupancy C: Cooling Isolation Zones. P: Variable Pitch Sensor B: Both N: Not Required V: VFD M: Manual Timer EC: Economizer O: Other C: Curve VENTILATION OUTDOOR DAMPER ECONOMIZER O.A. CFM B: Air Balance A: Auto A: Air Enter Outdoor Air C: Outside Air Cert. G: Gravity W: Water CFM. M: Out. Air Measure N: Not Required Note: This shall be no D: Demand Control EC: Economizer less than Col. H on N: Natural Control See Section MECH-3. ..144 03 EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page:31 of 53 1 LIGHTING CONTROL CREDIT WORKSHEET LTG -3 ROJECT NAME DATE The Hideawav Golf Clubhouse 6/25/2004 ne ne ro I massage Rooms I Men's Locker Men's Locker Multi -scene Dimming Z49 1; 7201 2001, 0.2W 401, Multi -scene Dimming Z5011 180 720: 9001 0. 1 -9. �2O [--Man,al Dimming i. Hr1TI 2_01 L 1,035i 1,800 0AU i 1801 Multi -scene Dimming AC ice --225. 1 2591' _0_.20 : i 52! Multi -scene Dimming! ACI 74�! 0.2U i 15111, 204' Multi -scene Dimming AC 1 53414811 0.201 301 1 Occ Sensor 250 CSL H 553414201 0.201 84! sqft Multi -scene Dimming AC 1,625. ill 0.20i 1 221, Occ Sensor — 250 II I i sqft 1 1041 0.201 1 1.31 Men's Locker Occ Sensor — 250 FD; 1,625 1,152 soft 0.2& 1 2 Women's Lounge -scene Dimming Multi I I L 1 159, 740� 0.201 148! Women's Lounge 1 1 Multi -scene Dimming 11159 8001! 0.201! 1601 Multi -scene Dimming Women's Lounge Z� 57 1,159;! 4001 801 Multi Men's Lounge -scene Dimming AC; 1 1,71011 1 777' 0.201 155 men 'SC0 u n —9e I Multi -scene Dimming Men's Lounge Tea Room AP 1 Multi -scene Dimming I 217:1 I,fIU 1 i 1,71011 i ; 111: U.ZUI Z Z 1 1,050 210 i 11 2251 45i 3121 i 0.201 i 621 11 1 185111 0 371 .201 i 740.20.1 . 151 0.2 1 1 44' 4 7411 020!1 151 A i Multi -scene Dimming Z1911 1,710h Multi -scene Dimm'ingi DS 1; 1,15211 Multi -scene Dimming AC 396 1 Multi -scene Dimming 1AP i 3961 ROOM DAYLIGHTING !'WATTS OF! LIGHTING CONTROL. RCIOM# 'LIGHTING CO? 4TROL, j PLANS AREA ROOM GLAZING CONTROL' i ADJUST. CREDIT ZONE ID DESCRIPTION REF. (SF) RA TIO* VILT LIGHTING FACTOR WATTS Wine Room Multi -scene Dim ming: nq;: 790 273! n 96 55 ne ne ro I massage Rooms I Men's Locker Men's Locker Multi -scene Dimming Z49 1; 7201 2001, 0.2W 401, Multi -scene Dimming Z5011 180 720: 9001 0. 1 -9. �2O [--Man,al Dimming i. Hr1TI 2_01 L 1,035i 1,800 0AU i 1801 Multi -scene Dimming AC ice --225. 1 2591' _0_.20 : i 52! Multi -scene Dimming! ACI 74�! 0.2U i 15111, 204' Multi -scene Dimming AC 1 53414811 0.201 301 1 Occ Sensor 250 CSL H 553414201 0.201 84! sqft Multi -scene Dimming AC 1,625. ill 0.20i 1 221, Occ Sensor — 250 II I i sqft 1 1041 0.201 1 1.31 Men's Locker Occ Sensor — 250 FD; 1,625 1,152 soft 0.2& 1 2 Women's Lounge -scene Dimming Multi I I L 1 159, 740� 0.201 148! Women's Lounge 1 1 Multi -scene Dimming 11159 8001! 0.201! 1601 Multi -scene Dimming Women's Lounge Z� 57 1,159;! 4001 801 Multi Men's Lounge -scene Dimming AC; 1 1,71011 1 777' 0.201 155 men 'SC0 u n —9e I Multi -scene Dimming Men's Lounge Tea Room Serving Room Mech/Equip/Fire Mech./Eauio/Fire Restrooms ARU! 768 1111 1 U.ZU ZZ! I io Al 1381 186 1 0.20' 37t ;0 BI 4091 124 i 0.20i 25 io Q 186 1 0.201 37 50 L 186i D! ;F 0.201 37: 0.201 �_�7 501 L -Ag PAGE TOTAL 2 140 For windows, use the Window Wall Ratio for the room. For skylights, use the Skylight -to -Roof ratio for the room. BUILDING TOTAL 5,2071 I Enter on LTG -1 and 2: Actual Lighting Power calculation. I EnerciyPro 3.1 By EnergySoft User Number 2531 Job Number. 40528 Page:32 of 53 AP 1 Multi -scene Dimming I 217:1 I,fIU 1 i 1,71011 i ; 111: U.ZUI Z Z 1 1,050 210 i 11 2251 45i 3121 i 0.201 i 621 11 1 185111 0 371 .201 i 740.20.1 . 151 0.2 1 1 44' 4 7411 020!1 151 i Multi -scene Dimming Z1911 1,710h Multi -scene Dimm'ingi DS 1; 1,15211 Multi -scene Dimming AC 396 1 Multi -scene Dimming 1AP i 3961 Multi -scene Dimming i i 1 Multi -scene Dimming 1 1 Multi -scene Dimming 1 xW 5121 89C 22511 r Serving Room Mech/Equip/Fire Mech./Eauio/Fire Restrooms ARU! 768 1111 1 U.ZU ZZ! I io Al 1381 186 1 0.20' 37t ;0 BI 4091 124 i 0.20i 25 io Q 186 1 0.201 37 50 L 186i D! ;F 0.201 37: 0.201 �_�7 501 L -Ag PAGE TOTAL 2 140 For windows, use the Window Wall Ratio for the room. For skylights, use the Skylight -to -Roof ratio for the room. BUILDING TOTAL 5,2071 I Enter on LTG -1 and 2: Actual Lighting Power calculation. I EnerciyPro 3.1 By EnergySoft User Number 2531 Job Number. 40528 Page:32 of 53 LIGHTING CONTROL CREDIT WORKSHEET LTG -3 ROJECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 IWORKSHEET E, -A DAYLIGHTING i WATTS OF: LIGHTING CONTROL ROOM # 1 LIGHTING CONTROL! I PLANS AREA ROOM GLAZING !CONTROL ADJUST. CREDIT ZONE ID I DESCRIPTIONI WATTS !I REF. RATIO* VILT LIGHTING ACTOR i–F (G X H) Restrooms Multi -scene Dimming 1; AC i 5961;! 0.20 15: Storage Rooms I Occ Sensor Storage N 931 0.6011 561: 150111 Storage Rooms Occ Sensor Storage I 11 AT 1,501112,139; 1 0.60' 112831 Men/Women's i cc Sensor i Restrooms i s ft D l'i 490' 450 1 1 0.20: 90; Men/Women's IL Occ Sensor <= 250 Restrooms F D 490! 64 1 131 menNvomen's 250 il Occ Sensor i 1 UAI Restrooms I sqft W141 4901 621 121: I 1 Women's Locker Area 1 Multi -scene Dimming AC j2,69 333; 1 0.20! Women's Locker Area Multi -scene Dimming AP 2,69211 14811 0.20 301 Locker Area 1 250 9: Women's Loc Occ Sensor <= D 2,692i sqft 89611. 0.201 17 1 Women's Locker Area Occ Sensor 250 1 11 F N1 2,69211 i 0.20 30: s ft 150 Women's Locker Area Occ Sensor <= 250 H 26921 S, 320, 020 .; 64' 1 sqft I Women's Locker Area Occ Sensor 250 sqft W14 2,692'1 0.201 12 Men's Locker Area IMulti-scene Dimming ACI 1,6251 18511 0.201 i 37; Men's Locker Area Occ Sensor <= 250 s_gft Mji 1,6251 16 8 i 0.20 154: Wet Area Multi -scene Dimming : API 464 259 521 1 Wet Area Occ Sensor <=250 1 sqft I FD1 46411 1 i1 2�8 0.20 i 261 1 1— Wet Area Occ Sensor <= 250 sqft S1 464 25611 0.2011 51! Attencle ming nt Multi -scene Dim AC 192 371 0.20i i T Attendent Occ Sensor <= 250 FD11. 192; sqft 1 t 251 0.20, 5 Attenderirt_ Occ Sensor <= 250 19: 192 i sqft I U4 9611 0,20i, Attenclent Occ Sensor 250 sqf.t Y3 192'. 781 0.20i 1 16; Mixed Grill 1 jAutomatic Time Switch' 0 DS! 1 512 .05 31; i . 1 4; Dining Areas Multi -scene Dimming 7511- 185' 0.201 ACI _37 Dining Areas Multi -scene Dimming DSI' 7511 i 78 0.20: ce161 Men's Restroom Multi -scene Dimming 01 i 371 ACI 28 7 Restroom I I Occ Sensor <= 250 L--sqft 28011 100 F 0.20P 201 Caddie Room 1 iOcc Sensor< 250 I Oi 1891 sqft Al1 . 186: 0.2 371 KitchenOcc Sensor — 250 Al 1 8501 2 1 0.201 sqft ; 428 1 Kitchen Multi -scene Dimming 1 I AC 1185011 74 0.201 15! PAGE TOTAL 2,808 For windows, use the Window Wall Ratio for the room. For skylights, use the Skylight -to -Roof ratio for the room. BUILDING TOTAL 5,207: Enter on LTG -1 and 2: Actual Lighting Power calculation. EnerqyPro 3.1 By EnergySoft User Number 2531 Job Number. 40528 Page:33 of 53 _IGHTING CONTROL CREDIT WORKSHEET LTG -3 ROJECT NAME Hideawav Golf Clubhouse DATE ! AI 1 B1 C D1 1E! E 'G ' H' I . 1 1 93; I ! 0.60 56' ; 60! ' j ROOM DAYLIGHTING :WATTS OF!,'! LIGHTING CONTROL ROOM # LIGHTING CONTROL; PLANS i i AREA ( ROOM i GLA23NG i CONTROL 1 1 ADJUST. ' ' CREDIT ZONE ID ; DESCRIPTION REF. ; i (SF) ; , RATIO VLT 1 WATTS LIGHTING I ; FACTOR rn Y W% Ent ry I Kitchen Storage Rooms, Kitchen Storage Rooms Occ Sensor = 250 1 S ft Occ Sensor Storage . Occ Sensor Storage {� I j 10i8 272 i 2 0.Kitchen 20; ; 37 1 1 93; I ! 0.60 56' ; 60! ' Kitchen Storage Rooms. i' Occ Sensor Storage I ; Occ Sensor <= 250 sgft I D U41 D1 I I 272 �� 8111 I 64 � I • 96: 6L_0_20 3$ 1 1 Ou I 0.6011 58 Elev. Equip. Room 1 ! 121 Hot Tub Occ Sensor <= 250 i� sgft I Occ Sensor <= 250 S11 I � W 14 3521 91' i I I j�224 0.20; ; 45 --i 0.20 12 Mechanical Room S ft q � j I H i II I I I r�I II II 'I ij I * For windows, use the Window Wall Ratio for the room. i For skylights, use the Skylight -to -Roof ratio for the room. PAGE TOTAL 259i BUILDING TOTAL 5,207 I Enter on LTG -1 and 2: Actual Lighting Power calculation. I EnergyPro 3.1 By EnergySoft User Number 2531 Job Number. 40528 Page:34 of 53 i IMECHANICAL EQUIPMENT SUMMARY Part 1 of 2 MECH-2 NAME The Hideawav Golf Cl DATE 6/25/2004 ,.;HILLER AND TOWER SUMMARY ! PUMPS _ ! Tot. 1 Motori Drive - -Pum I Equipment Name Equipment Type Qty. Efficiency Tons Qty 'GPMBHP ! Eff. 1 Eff. Control - - U CA Tu.n System Name I SvstemType Qty. j out Aux. kW I Eff. Output Sensiblei Efficiency Economizer Type !Lennox HP29-036/CB29My 41 ISplit DX I 21 23,600 0.0! 6.90 HSPFi 30,2001 28,20010.1 SEER / 9.1 EER �No Economizer DHW / BOILER SUMMARY 11 31,200 0.01 1I System Name System Type 1 Distribution Type Energy Factor Rated Vol. ! or Recovery .Qty' Input ' (Gals.) ' Efficiency Standby ! !TANK INSUL. i Loss or ! Ext Pilot R -Val. O Smith BTH-250 'Large Gas Standard 11 240,000 100: 0.91 0.0126! 0.01' Lennox HP29-120/CBH17-1 135V !Split DX 3 94,000! 0.0 3.20 COPi 106,000! - 96,000110.1 EER No EconomizerLennox IPUHI8EK/PKH18FK 'Split DX 11 17,0001 0.0 7.00 HSPF;18,000! Lennox IPUH18EK/PKH18FK _ 15,200;12.0 SEER / 11.0 EER'No Economizer j Lennox THA150S ! ;Packaged DX 1 11 145,0001 CENTRAL SYSTEM RATINGS -- 135,000;9.5 EER - No Economizer Dectron CCA-006/MAM- ;030 Split DX U CA Tu.n System Name I SvstemType Qty. j out Aux. kW I Eff. Output Sensiblei Efficiency Economizer Type !Lennox HP29-036/CB29My 41 ISplit DX I 21 23,600 0.0! 6.90 HSPFi 30,2001 28,20010.1 SEER / 9.1 EER �No Economizer Lennox HP29-048/CB29Mj G1 ISplit DX 11 31,200 0.01 7.50 HSPF1 40,700 38,100;10.2 SEER 18.6 EER ':No Economizer 1 annox HP29-090/CBH17-1- iV ISplit DX 91 61,7001 0.0! 7.84 HSPFI 75,3001 74,100:10.1 EER 1No Economizer Lennox HP29-120/CBH17-1 135V !Split DX 3 94,000! 0.0 3.20 COPi 106,000! - 96,000110.1 EER No EconomizerLennox IPUHI8EK/PKH18FK 'Split DX 11 17,0001 0.0 7.00 HSPF;18,000! Lennox IPUH18EK/PKH18FK _ 15,200;12.0 SEER / 11.0 EER'No Economizer j Lennox THA150S ! ;Packaged DX 1 11 145,0001 0.01 3.10 COPT 145,000 -- 135,000;9.5 EER - No Economizer Dectron CCA-006/MAM- ;030 Split DX 2 30,0001 0.0;800 30,700 18,010!10.0 SEER 19.0 EER iNo Economizer j ! 89.5%1 97.0%1' none! I" !Dectron CCA-006/MAM- 1 030 Constant Volume i 113Iow-Through I 8001 0.251 84.0%', 97.0%,, none' I CENTRAL SYSTEM FAN SUMMARY ! SUPPLY FAN �RETURN FAN I Motorl Drive,,' I Motor! 1 i Drive System Name } Fan Type Motor Location CFM i BHP Eff. I Eff. ! 1 CFM BHP _i_ Eff. 1 Eff. I Lennox HP29-036/CB29M� I �- ! 41 Constant Volume ;Blow -Through 1 1,2001 0.33 84.0%1 97.0%1; none;' ! j Lennox HP29-048/CB29M � 1 51 Constant Volume Ielow-Through 1 1,600 0.75; 84.0%1 97.0%11;' none: 1 Lennox HP29-090/CBH17- 195V 'Constant Volume I Blow -Through 3,000 1.50186.5% I I 97.0%I 1 none' 1 !Lennox HP29-120/CBH17- !135V Constant Volume I Blow -Through 3,00012.00 86.5%I 97.0% j none) 1 I 1 Lennox IPUH18EK/PKH18FK Constant Volume I !Blow -Through j 6001 0.20; i- - 84.0%i 97.0%i j none! ' 1 ,Lennox THA150S 1 Constant Volume Draw -Through i 5,000 5.001 ! 89.5%1 97.0%1' none! I" !Dectron CCA-006/MAM- 1 030 Constant Volume i 113Iow-Through I 8001 0.251 84.0%', 97.0%,, none' Run Initiation Time: 06/25/04 09:57:56 Run Code: 1088182676 EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number. 40528 Page:35 of 53 IMECHANICAL EQUIPMENT SUMMARY Part 2 of 2 MECH-2 PROJECT NAME DATE The Hideawav Golf Clubhouse 6/25/2004 E TERMINAL SUMMARY VAV TERMINAL BOX TERMINAL FAN Min. CFM Reheat Coil Motor Drive System Type Qtv. Ratio ape DeltaT CFM BHP Eff. Eff. EXHAU TFAN EXHAUSTFAN Room Name _qty. CFM BHP Motor Eff. Drive Eff. Room Name Qty. CFM BHP Motor Eff. Drive Eff. Men's Locker 1.0 1,000 0.25 77.0°/ 97.0% Women's Locker Area 1.0 1,000 0.25 77.00/ 97.0% Restrooms 1.0 330 0.10 77.0°/ 97.0% Men's Locker Area 1.0 1,000 0.25 77.0°/ 97.0% Men/Women'sRestrooms 1.0 1,200 0.25 77.0°/ 97.0% Wet Area 1.0 500 0 .12 77.0°/ 97.0% EneravPro 3.1 By EnergvSoft User Number: 2531 Job Number: 40528 Page -.36 of 53 1 IMECHANICAL EQUIPMENT SUMMARY Part 2 of 2 MECH-2 I PROJECT NAME The Hideaway Golf Clubhouse I DATE 6/25/2004 E TERMINAL SUMMARY VAV TERMINAL BOX . TERMINAL FAN BASEBOARD Min. CFM Reheat Coil Motor Drive System T pe O Ratio ape DeltaT CFM BHP Eff. Eff. Type Output EXHAUST AN Room Name Q . CFM BHP Motor Eff. Drive Eff. Men's Restroom 1.0 500 0.12 77.0°/ 97.0% Caddie Room 1.0 100 0.07 77.00/ 97.0% EXHAUSfFAN Room Name Qt. CFM BHP Motor Eff. Drive Eff. EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page:37 of 53 1 �MECHANICAL VENTILATION MECH-3 'ROJECT NAME DATE The Hideawav Golf Clubhouse 1 6/25/2004 MECHANICAL VENTILATION [-A I ©© o 0 0© a a o 0 EnergyPro 3.1 By EnergySofl User Number: 2531 Job Number: 40528 Page:38 of 53 AREA BASIS OCCUPANCY BASIS REQ'D O.A. (MAX OF D OR G) DESIGN OUTDOO AIR CFM VAVTRANS. MIN. RATIO FER AIR ZONE/SYSTEM COND. AREA (SF) CFM PER SF MIN. CFM (B x C) NO. OF PEOPLE CFM PER PERSON MIN. CFM (ExF) Wine Room 720 0.25 180 24. 15.0 360 360 360 HP -2 Total 360 360 Pro Shop 1,035 0.25 259 34. 15.0 518 518 518 HP -6 Total 518 518 Fitness Areas 3,11 0.15 467 88.9 15.0 1,333 1,333 1,333 Salon 225 0.40 90 15.0 15.0 225 225 225 Offices 1,506 0.15 226 15.1 15.0 226 226 226 Men's Locker/Massage 2,159 0.15 324 51.8 15.0 777 7771 1,000 Lounge Areas 4,748 1.50 7,122 316.5 15.0 4,748 7,122 4,748 2,374 Dining Areas 1,133 0.50 566 75.5 15.0 1,133 1,133 1,133 Entry 1,043 1.07 1,116 10.4 15.0 156 1,116 156 960 Mech/Equip/Fire/Panel 742 0.15 111 7.4 15.0 111 111 111 upport Areas 3,880 0.15 5821 38.8 15.0 582 582 1,530 HP -1,3,4,5,7,11-14 Total 12,625 10,463 Lockers 4,78 0.15 717 136.6 15.0 2,049 2,049 2,500 Attendent 192 0.15 29 1.9 15.01 29 29 29 Dining Areas 2,263 0.50 1,1321 150.9 15.0 2,263 2,263 2,263 Men's Restroom 2801 0.15 42 2.8 15.0 42 42 500 HP -8,10,15 Total 4,383 5,292 ' Caddie Room 189 0.15 28 1.9 15.0 28 28 100 HP -9 Total 28 100 Kitchen 1,850 0.15 278 9.2 15.0 139 278 139 139 Kitchen Entry 108 1.07 116 0.5 15.0 8 116 8 107 Kitchen Support 465 0.15 70 4.7 15.0 70 70 70 HP -16 Total 463 217 Elev. Equip. Room 81 0.15 12E100 15.0 12 12 12 AC -1 Total 12 12 Hot Tub 352 0.15 53 15.0 151 151 151 C E I K Minimum Ventilation Rate per Section 121, Table 1-F. Based on Expected Number of Occupants or at least 50% of Chapter 10 1997 UBC Occupant Density. Must be greater than or equal to H, or use Transfer Air. Design Outdoor Air includes ventilation from Supply Air System & Room Exhaust Fans. Must be greater than or equal to (H minus 1), and, for VAV, greater than or equal to (H -J). EnergyPro 3.1 By EnergySofl User Number: 2531 Job Number: 40528 Page:38 of 53 �MECHANICAL VENTILATION MECH-3 ROJECT NAME DATE The Hideawav Golf Clubhouse 1 6/25/2004 MECHANICAL VENTILATION FA O a a 0 0 0 0 0 o F EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page:39 of 53 AREA BASIS OCCUPANCY BASIS REQ'D O.A. (MAX OF D OR G) DESIGN OUTDOOF AIR CFM VAV MIN. RATIO TRANS. FER AIR ZONEISYSTEM COND. AREA (SF) CFM PER SF MIN. CFM (B x C) NO. OF PEOPLE CFM PER PERSON MIN. CFM (ExF) Mechanical Room 91 0.15 14 O.E 15.0 14 14 . 14 AC -2,3 Total 165 165 C E I K Minimum Ventilation Rate per Section 121, Table 1-F. Based on Expected Number of Occupants or at least 50% of Chapter 10 1997 UBC Occupant Density. Must be greater than or equal to H, or use Transfer Air. Design Outdoor Air includes ventilation from Supply Air System & Room Exhaust Fans. Must be greater than or equal to (H minus 1), and, for VAV, greater than or equal to (H -J). EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page:39 of 53 PROPOSED CONSTRUCTION ASSEMBLY ENV -3 ROJECT NAME DATE The Hideaway Golf Clubhouse 1 6/25/2004. COMPONENT DESCRIPTION 1 2 R -VALUE *HEAT ASSEMBLY NAME 8" CMU w/ Stucco & Insul. THICK- NESS (in.) CAVITY R -VALUE (Rc) WOOD FRAME R -VALUE WALL WEIGHT (lbs/sf) SPECIFIC HEAT (Btu/F-Ib) ASSEMBLY Floor FRAMING OUTSIDE SURFACE AIR FILM ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ — TYPE (check one) XWall — — W W 0.875 Ceiling I Roof 8.46 0.20 a FRAMING MATERIAL None 0.600 p 0.20 FRAMING % % Framing % 1,000 4.550 0.38 0.40 15% (16" o.c. Wall) 4 Gypsum or Plaster Board 0.625 0.562 12% (24" o.c. Wall) 0.26 0.68 5 10% (16" o.c. Floor/Cell.) SKETCH OF ASSEMBLY 6 7% (24" o.c. Floor/Cell.) CONSTRUCTION COMPONENTS 1 2 R -VALUE *HEAT CAPACITY (Optional) THICK- NESS (in.) CAVITY R -VALUE (Rc) WOOD FRAME R -VALUE WALL WEIGHT (lbs/sf) SPECIFIC HEAT (Btu/F-Ib) HC (A X B) (Btu/F-sf) DESCRIPTION FRAMING OUTSIDE SURFACE AIR FILM ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ — 0.170 — — — Stucco 0.875 0.175 8.46 0.20 1.69 Conc Block, Normal Weight, Conc Filled 8.000 0.600 83.33 0.20 16.67 3 Insulation, Expanded Rubber (rigid) 1,000 4.550 0.38 0.40 0.15 4 Gypsum or Plaster Board 0.625 0.562 2.60 0.26 0.68 5 6 7 8 9 *NOTE: INSIDE SURFACE AIR FILM — 0.680— Weight and Specific Heat values for materials penetrated SUBTOTA by wood 6.741 Rc framing include Rf the effects TOTAL HC members. 19.2 of the framing [� x �] + X F 1/Rc 1 - (Fr-/. / 100) 11 Rf Fr% / 100 ASSEMBLY U -VALUE COMMENTS EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page:40 of 53 PROPOSED CONSTRUCTION ASSEMBLY ENV -3 ROJECT NAME The Hideaway Golf Clubhouse DATE 6/25/2004 COMPONENT DESCRIPTION DESCRIPTION WOOD FRAME R -VALUE OUTSIDE SURFACE AIR FILM ASSEMBLY NAME 8" CMU w/ R19 Stucco 2 Conc Block, Normal Weight, Conc Filled ASSEMBLY Floor Insulation, Mineral Fiber, R-19 4 TYPE XWall (check one) 5 W � W Ceiling /Roof 0.86 NFRAMING MATERIAL Wood 8 Z p FRAMING % 12 % Framing 15% (16" o.c. Wall) 0.680 21.19 12% (24" o.c. Wall) 10% (16" o.c. Floor/Ceil.) SKETCH OF ASSEMBLY 7% (24" o.c. Floor/Ceil.) THICK- NESS (in.) 0.875 8.000 6.000 0.625 SUBTOTAI R -VALUE DESCRIPTION WOOD FRAME R -VALUE OUTSIDE SURFACE AIR FILM 1 Stucco 2 Conc Block, Normal Weight, Conc Filled 3 Insulation, Mineral Fiber, R-19 4 Gypsum or Plaster Board 5 2.36 6 0.86 7 0.26 8 9 INSIDE SURFACE AIR FILM THICK- NESS (in.) 0.875 8.000 6.000 0.625 SUBTOTAI R -VALUE CAVITY R -VALUE (Rc) WOOD FRAME R -VALUE 0.170 0.170 0.1751 0.175 0.600 0.600 19.002 5.940 0.562 0.562 2.36 0.37 0.86 2.60 0.26 0.68 0.680 0.680 21.19 8.13 RL Rr J LB *HEAT CAPACITY (Optional) WALL WEIGHT (lbs/sf) SPECIFIC HEAT (Btu/F-Ib) HC (A X B) (Btu/F-sf) [ 0.0472 x 0.88 ] 8.46 0.20 1.69 83.33 0.20 16.67 2.36 0.37 0.86 2.60 0.26 0.68 96 g TOTAL HC 1 g g *NOTE: Weight and Specific Heat values for materials penetrated by wood framing include the effects of the framing members. [ 0.0472 x 0.88 ] + [ 0.1230 X 0.12 1 / Rc 1 - (Fr% / 100) 1 / Rf Fr% / 100 ASSEMBLY U -VALUE PROPOSED CONSTRUCTION ASSEMBLY ENV -3 IJECT NAME The Hideaway Golf Clubhouse DATE 6/25/2004 COMPONENT DESCRIPTION o a ASSEMBLY NAME 12" CMU Under round Wall -HEAT ASSEMBLY Floor THICK- NESS (in.) CAVITY R -VALUE (Rc) TYPE (check one) X Wall SPECIFIC HEAT (Btu/F-Ib) 0 W Ceiling / Roof OUTSIDE SURFACE AIR FILM H 2 FRAMING MATERIAL Metal O Z FRAMING %° 12 �° Earth 2.000 2.000 Framing 0.20 17.00 2 15% (16" o.c. Wall) 2.000 0.900 12% (24" o.c. Wall) 0.20 25.00 s 10% (16" o.c. Floor/Ceil.) SKETCH OF ASSEMBLY 0.8701 7% (24" o.c. Floor/Cell.) CONSTRUCTION COMPONENTS o a R -VALUE -HEAT CAPACITY (Optional) THICK- NESS (in.) CAVITY R -VALUE (Rc) WOOD FRAME R -VALUE WALL WEIGHT (lbs/sf) SPECIFIC HEAT (Btu/F-Ib) HC (A X B) (Btu/F-so DESCRIPTION FRAMING OUTSIDE SURFACE AIR FILM ❑ ❑ © ❑ ❑ ❑ ❑ 0 ❑ — 0.170 — — — Earth 2.000 2.000 85.00 0.20 17.00 2 Conc Block, Normal Weight, Conc Filled 2.000 0.900 125.00 0.20 25.00 s Air Space 1.500 0.8701 0.01 0.10 0.00 4 Gypsum or Plaster Board 0.625 0.562 2.60 0.26 0.68 5 6 7 8 9 'NOTE: INSIDE SURFACE AIR FILM — 0,680 5.18 Rc framing include Rf the effects — — — Weight and Specific Heat values for materials penetrated SUBTOTA by wood 212.6 TOTAL HC members. 42 7 of the framing I� x =1 ¢ X E - 0.209 11 Rc 1 - (Fr% / 100) 1 / Rf Fr% / 100 ASSEMBLY U -VALUE COMMENTS Thi,, assembly contains metal framing. The Assembly U -Value has been calculated using the ASHRAE/CEC Zonal Cavity Method. EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page:42 of 53 tbPOSED CONSTRUCTION ASSEMBLY ENV jr-t- i nrimt The Hideaway Golf Clubhouse APONENT DESCRIPTION til 2 W to 0 I— Fn Z O — SKETCH OF ASSEMBLY DATE 6/25/2004 ASSEMBLY NAME 6" Concrete Underground Slab Floor ASSEMBLYx Floor TYPE (check one) Wall Ceiling / Roof FRAMING MATERIAL None FRAMING % % Framing 15% (16" o.c. Wall) 12% (24" o.c. Wall) 10% (16" o.c. Floor/Cell.) 7%, (24" o.c. Floor/Ceil.) CONSTRUCTION COMPONENTS 2 RA R -VALUE *HEAT CAPACITY (Optional) THICK- NESS (in.) CAVITY R -VALUE (Rc) WOOD FRAME R -VALUE WALL WEIGHT (lbs/sf) SPECIFIC HEAT (Btu/F-Ib) HC (A X B) (Btu/F-sf) DESCRIPTION FRAMING OUTSIDE SURFACE AIR FILM ❑ ❑ ❑ ❑ ❑ a ❑ ❑ ❑ — 0.170 — — — Earth 2.000 2.000 85.00 0.20 17.00 Concrete, 140 Ib, Not Dried 6.000 0.480 70.00 0.20 14.00 3 4 5 6 7 8 9 'NOTE: INSIDE SURFACE AIR FILM —1 0.920 — — — Weight and Specific Heat values for materials penetrated SUBTOTA by wood 3 57 Rc framing include Rf the effects 155.0 TOTAL HC members. 31.0 of the framing Co X � ] [L� X �❑ ' 0.280 1 / Rc 1 /o Rf Fr/o 1100 ASSEMBLY U -VALUE COMMENTS EnergyPro 3 1 By EnergySoft User Number,. 2531 Job Number: 40528 Page:43 of 53 'ROPOSED CONSTRUCTION ASSEMBLY ENV -2 JJCV 1 tYF1IYIC The Hideaway Golf Clubhouse 2 W a W 2 H co Z O — SKETCH OF ASSEMBLY DATE 6/25/2004 ASSEMBLY NAME g"CMU w! Stucco ASSEMBLY Floor TYPE (check one)X Wall Ceiling / Roof FRAMING MATERIAL None FRAMING % % Framing 15% (16" o.c. Wall) 12% (24" o.c. Wall) 10% (16" o.c. Floor/Ceil.) 7% (24" o.c. Floor/Ceil.) CONSTRUCTION COMPONENTS 2 a1131 R -VALUE `HEAT WALL WEIGHT (lbs/sf) CAPACITY (Optional) THICK- NESS (in.) CAVITY R -VALUE (Rc) WOOD FRAME R -VALUE SPECIFIC HEAT (Btu/F-lb) HC (A X B) (Btu/F-sf) DESCRIPTION FRAMING OUTSIDE SURFACE AIR FILM ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ — 0.170 — — — Stucco 0.875 0.175 8.46 0.20 1.69 Conc Block, Normal Weight, Conc Filled 8.000 0.600 83.33 0.20 16.67 3 4 5 6 7 8 9 INSIDE SURFACE AIR FILM — 0.680 — — — SUBTOTA 1.62 . 91 8 Rc Rf 'NOTE: Weight and Specific Heat values for materialspenetrated by wood framing include the effects of the framing ° ] [ ❑ 1 / Rc 1 (Fr/° / 100) 11 Rf E Fr% / 100 TOTAL HC members. 18.4 0.615 ASSEMBLY U -VALUE COMMENTS EnergyPro 3.1 By EnergySoft User Number: 2531 Job Number: 40528 Page:44 of 53 PROPOSED CONSTRUCTION ASSEMBLY ENV -3 OJECT NAME The Hideaway Golf Clubhouse DATE 6/25/2004 COMPONENT DESCRIPTION DESCRIPTION R -VALUE OUTSIDE SURFACE AIR FILM THICK- NESS (in.) Earth 2 Conc Block, Normal Weight, Conc Filled 3 — 4 0.20 5 ASSEMBLY NAME g" CMU Underground Wall 8.000 7 8 ASSEMBLY Floor INSIDE SURFACE AIR FILM TYPE (check one) XWall LILI p W Ceiling / Roof F- FRAMING MATERIAL None 0.680 U) Z p FRAMING % % Framing 15% (16" o.c. Wall) 12% (24" o.c. Wall) 10% (16" o.c. Floor/Ceil.) SKETCH OF ASSEMBLY 7% (24" o.c. Floor/Cell.) rj�fflC *HEAT CAPACITY (Optional) DESCRIPTION R -VALUE OUTSIDE SURFACE AIR FILM THICK- NESS (in.) Earth 2 Conc Block, Normal Weight, Conc Filled 3 — 4 0.20 5 2.000 6 8.000 7 8 9 INSIDE SURFACE AIR FILM rj�fflC *HEAT CAPACITY (Optional) WALL WEIGHT (lbs/sf) R -VALUE HC (A X B) (Btu/F-sf) THICK- NESS (in.) CAVITY R -VALUE (Rc) WOOD FRAME R -VALUE kMING ❑ ❑ El El — 0.170 0.20 2.000 2.000 8.000 0.600 — 0.680 rj�fflC *HEAT CAPACITY (Optional) WALL WEIGHT (lbs/sf) SPECIFIC HEAT (Btu/F-Ib) HC (A X B) (Btu/F-sf) 85.00 0.20 17.00 83.33 0.20 16.67 SUBTOTA3.45 168.3 TOTAL HC R 33.7 'NOTE: Weight and Specific Heat values for materials penetrated by wood framing. include the effects of the framing members. �0 X 0� x ❑�� = o.2so 1 / Rc 1 - (Fr /° / 100) 1 / Rf Fr% / 100 ASSEMBLY U -VALUE EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number: 40528 Page:45 of 53 1 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY OJECT NAME The Hideawav Golf Clubhouse YSTEM NAME HP -2 ENGINEERING CHECKS ! ;Number of Systems 1 iHeating System !!j i; iOutput per Gystem ! 23,60011; i Total Output (Btuh) 23,600' Output (Btuh/sgft) 32.81 Cooling System Output per System 30,200 Total Output (Btuh) 30,2001 j Total Output (Tons) i 2.51 Total Output (Btuh/sgft) 41.9 ! Total Output (sgft/Ton) I 286.1] ;Air System CFM per System 1 1,200 Airflow (cfm) i 1,200 j Airflow (cfm/sgft) 1.671 Airflow (cfmrron) 476.8 Outside Air (%) j 30.0 i Outside Air (cfm/sgft) j 0.50 Note: values above given at ARI conditions DATE 6/25/2004 FLOOR AREA 720 COIL COOLING PEAK j I COIL HTG. PEAK; ' CFM i Sensible: Latent ! ' CFM ; Sensible'! ! Total Room Loads i 1,204 13,258 6,120 ' 0 0 Return Vented Lighting 01 ' Return Air Ducts 663; j 0i i Return Fan1 0 01 Ventilation 360 14,737 671 360`; 16,850] Supply Fan 0 i 01 I Supply I Air Ducts 663 TOTAL SYSTEM LOAD j 29,3211 6,187 16,850! 1 HVAC EQUIPMENT SELECTION I!Lennox HP29-036/CB29M-41 1 29,275 0, I1 I i j ! Total Adjusted System Output 29 2751 01(Adjusted for Peak Design Conditions) ! TIME OF SYSTEM PEAK Jul 3 pm i EATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heatina Peak) 26.0 of 56.8 of 56.8 of m 69.0 of Outside Air 360 cfm Supply Fan Heating Coil 1200 cfm 70.0 of Supply Air Ducts DOLING SYSTEM PSYCHROMETRICS (Airstream Temoeratures at Time of Coolina Peak) ! 15,521 1 i I 15,5211 '. Jan 12 aml 69.0 of I ROOMS ; 70.0 OF, j HVAC'SYSTEM HEATING AND COOLING LOADS SUMMARY EJECT NAME The Hideawav Golf Clubhouse :SYSTEM NAME HP -6 ENGINEERING CHECKS —T 40,7001 ' Number of Systems ! 1' ;Heating System j Output per System i 3 0 I Total Output (Btuh) 31,2001 i ' I Output (Btuh/sgft) I 30.1; IAir System CFM Sensible ; ..canny Output per System —T 40,7001 Total Output (Btuh) 40,7001 j Total Output (Tons) 3.4!1 Total Output (Btuh/sgft) 39.3 j • Total Output (sgft/Ton) 305.2 'I IAir System CFM Sensible ; CFM per System 1,60011 Airflow (cfm) 1,600; Airflow (cfm/sgft) ! 1.55' Airflow (cf nrron) —� 471.71 Outside Air (%) i 32.31 Outside Air (cfm/sgft) I 0.50 Note: values above given at ARI conditions EATING SYSTEM PSYC 26.0 of 55.4 of 55.4 of Outside Air i 518 cfm 69.4 of DATE 6/25/2004 !Lennox HP29-048/CB29M-51 40,054; 85� Ij i 11 I I I it 1 I Total Adjusted System Output j (Adjusted for Peak Design Conditions) I 40,0541 _ 851 TIME OF SYSTEM PEAK 1 Jul 3 pm Temperatures at Tim 67.4 of Supply Fan Heating Coil 1600 cfm i 11 1_ 20,5191 20,5191 Jan 12 am. i Supply Air Ducts I 66.8 of j ROOMS 70.00 F Return Air Ducts E I COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Coolina Peak) 13.0 / 77.9 of Outside Air 518 cfm .3/68.3 of EnergyPro 3.1 87.5/71.6OF 87.5/71.6OF 63.9 / 62.6 of Supply Fan Cooling Coil 1600 cfm User Number. 2531 >% Return Air Ducts `S Job Number. 40528 Supply Air Ducts I 65.2/63.1OF 73.8% R.H. ' ROOMS 74.0 / 67.9 of of 53 FLOOR AREA 1,035 SYSTEM LOAD I COIL COOLING PEAK COIL HTG. PEAK: CFM Sensible; Latent CFM Sensible ; Total Room Loads i 4,629 43,2741 11,212: -6,023- 20,365! ! Return Vented Lighting 01 I Return Air Ducts I 2,164 1,0181 =— li Return Fan 0 i o� Ventilation ; 518; 20,7701 -1,730; i 518; 23,893; Supply Fang ! 0 Supply Air Ducts 2,16aj 1,018; TOTAL SYSTEM LOAD I sa,372� 9,482! 46,295 !Lennox HP29-048/CB29M-51 40,054; 85� Ij i 11 I I I it 1 I Total Adjusted System Output j (Adjusted for Peak Design Conditions) I 40,0541 _ 851 TIME OF SYSTEM PEAK 1 Jul 3 pm Temperatures at Tim 67.4 of Supply Fan Heating Coil 1600 cfm i 11 1_ 20,5191 20,5191 Jan 12 am. i Supply Air Ducts I 66.8 of j ROOMS 70.00 F Return Air Ducts E I COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Coolina Peak) 13.0 / 77.9 of Outside Air 518 cfm .3/68.3 of EnergyPro 3.1 87.5/71.6OF 87.5/71.6OF 63.9 / 62.6 of Supply Fan Cooling Coil 1600 cfm User Number. 2531 >% Return Air Ducts `S Job Number. 40528 Supply Air Ducts I 65.2/63.1OF 73.8% R.H. ' ROOMS 74.0 / 67.9 of of 53 JHVAC SYSTEM HEATING AND COOLING LOADS SUMMARY '--')JECT NAME The Hideaway Golf Clubhouse :srSTEM NAME i HP -1,3,4,5,7,11-14 ENGINEERING CHECKS SYS DATE 6/25/2004 FLOOR AREA 18.547 ;Number of Systems 1Heating System gli COIL COOLING PEAK j ' COIL HTG. PEAK CFM Sensible; Latent CFM Sensible I i Total Room Loads i 66,8531 521,884 272,5951 1-27,048: 135,715 Return Vented Lighting I o I� Return Air Ducts 26,09441 _ _ – 6,7861 ` 1 Return Fan -01 ; o Ventilation I 10,463; 423,9721 107,13811 10,4631 487,106, j I i Supply Fan 01 0 Supply Air Ducts 6,094 6,7861 ; r--� ;, TOTAL SYSTEM LOAD 998,044; 165,457+ 636,392, J Output erS stem 61,700;, i � P P v TotalOutput (Btuh) 555,300,1 Output (Btuh/sgft) 29.91 1 Cooling System Output per System ; 75,300;; Total Output (Btuh) 677,700 Total Output (Tons) 56.51 Total Output (Btuh/sgft) 36.51 I ' I Total Output (sgft/Ton) 1 328.4111 Air System HVAC EQUIPMENT SELECTION CFM per System i 3,0001 :Lennox HP29-090/CBH17-95V II Iil Total Adjusted System Output 1 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK 686,933. 01 i I � I 686,933 0 j Jul 3 pm 365,203 _J ; • ! I 365,203; j Jan 12 am' ; Airflow (cfm) 27,000] Airflow (cfm/sgft) 1.4611 Airflow (cfm/Ton) 478.1, Outside Air (%) I 38.8 Outside Air (cfm/sgft) !— 0.56 Note: values above given at ARI conditions EATING SYSTEM PSYCHROMETRICS (Airstream Tei 26.0 OF 52.8 OF 52.8 OF 65.5 OF i Outside Air. 1 10463 cfm Supply Fan Heating Coil 27000 cfm 69.8 of �N Return Air Ducts 4 Pea I Supply Air Ducts 65.3 of ROOMS 70.00 F COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) 113.0 / 77.9 OF 0 Outside 10463 cfm 9/70.1 of 89.7 / 73.2 of 89.7 / 73.2 of ® 65.8 / 64.4 of Supply Fan Cooling Coil 27000 cfm �% Return Air Ducts 4 Supply Air Ducts I I 66.7/64.7OF 81.5% R.H. ROOMS ; 74.0/69.8OF 1 EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number. 40528 Page:48 of 53-i (VAC SYSTEM HEATING AND COOLING LOADS SUMMARY --')JECT NAME . The Hideaway Golf Clubhodse arBTEM NAME HP -8,10,15 ENGINEERING CHECKS SYSTEM LOAD ;Number of Systems COI' 11-leating System Il CFM Output per system I 94.000''! Total Room Loads 19 94 I Total Output (Btuh) 282,0001 1 Output (Bfuh/sgft) 37.5 (Cooling System i 206,149; Output per System I 106,0001 Total Output (Btuh) I 318,0001 i Total Output (Tons) 26.5 i Total Output (Btuh/sgft) 42.3 Total Output (sgft/Ton) I ' 283,61 , }Air System CFM per System i 3,000 Airflow (cfm) j 9,000 Airflow (cfm/sgft) I 1.20 Airflow (cfm/Ton) 339.6 ! Outside Air (%) I 58.8' i i Outside Air (cfm/sqft) i 0.70 Return Vented Lighting Return Air Ducts Return Fan Ventilation ! 5,29 Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD DATE _ 6/25/2004 FLOOR AREA 7,516 COOLING PEAK . I COIL HTG. PEAK; Sensible) Latent ; CFM ! Sensible i 206,149; 94,630! -7,009; 51,286:1 0! 1-- - 01 2,5646 : , o; 213,4841 -17,9551 5,2921 246,184; of ! o. 1 10,3071 2,5641 i 440,2481 76,6751 302,598': ILHVAC EQUIPMENT SELECTION it ':)Lennox HP29-120/CBH17-135V 327,115 J0 i !, 1 I I 185,461 1!! Total Adjusted System Output ! ! ! (Adjusted for Peak Design Conditions) I 327,115} 0i 185,461} I i TIME OF SYSTEM PEAK I Jul 3 pm; Jan 12 am Note: values above given at ARI conditions EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heatina Peak) 26.0 of 44.0 of 44.0 of 63.4 of I Outside Air F. 5292 cfm F - Supply Fan Heating Coil 9000 cfm 69.7 of E5-41-- A M—t, I Supply Air Ducts 63.1 of , ROOMS 70.00 F I DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak 113.0 / 77.9 OF 97.4 / 74.1 OF 97.4/74.10F I= 63.2/61.30 Outside Air - + Supply Air Ducts 5292 cfm Supply Fan Cooling Coil 64.3 / 61.7 of 9000 cfm 73.9% R.H. I ROOMS 1/68.3 of 74.0 / 67.9 of Return Air Ducts I EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number. 40528 Page:49 of 53 HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY ')J ECT NAME The Hid SYSTEM NAME HP -9 Golf Clubhouse lNumber of Systems V! 'lHeating System Total Output (Btuh) i 1 Output per System 171000 Total Output (Btuh) 17,000 Output (Bt.tgsqft) 89.911! Hi 11.00nng system I Output per System 18,0001 Total Output (Btuh) i 18,0001 Total Output (Tons) Return Air Ducts Total Output (Btuh/sqft) I 95.2 Total Output (sqft/Ton) 126.011 !Air System CFM per System 600 o Airflow (,fm) I 600� Airflow (cfm/sqft) I 3.17 Airflow (cfm/Ton) 400.0j Outside Air 16.71 Outside Air (cfm/sqft) 0.53( Note: values above given at ARI conditions DATE 6/25/2004 FLOOR AREA 189 COIL COOLING PEAK COIL HTG. PEAK,' CFM Sensible! Latent CFM Sensible Total Room Loads 184 3,577. 482; 2491 2,601; Return Vented Lighting 0 Return Air Ducts i 179; 130! Return Fan U. 0! Ventilation 100, 4,6591 Supply Fan I 01 Oi Supply Air Ducts 1791 1301 TOTAL SYSTEM LOAD i S,o5a 2,2701 7,521j !Lennox PUH18EK/PKH18FK 15,8561 0,; Total Adjusted System Output i 15,8561 0, (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK j Jul 3 pm' 11,180. 11,180 Jan 12 am! k-lEATING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Heatina Peak) I 26.0 OF 62.5 OF 62.5 OF Outside Air 100 cfm Supply Fan Heating Coil 600 cfm 69.8 OF 80.0 OF 4S Supply Air Ducts � 79.8 OF ROOMS 70.0 OF Return Air Ducts (COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) I 13.0 / 77.9 OF 80.7 / 64.8 OF 80.7 / 64.8 OF M 55.9 / 54.6 OF Outside Air 100 cfm -.3/61.7 °F Supply Fan Cooling Coil 600 cfm Supply Air Ducts 56.2 / 54.7 OF S1 49.8% R.H. -i ROOM 74.0/61.6°F Return Air Ducts I EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number. 40528 Page:50 of 53 1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY EJECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 ;SYSTEM NAME FLOOR AREA HP -16 2,423 ENGINEERING CHECKS SYSTEM LOAD !Number of Systems 1i ;Heating System CFM ,Sensible; Output per System i 145,000 Total Output (Btuh) 1 145.0001 Output (Btuhfsgft) I 59.8 Cooling System 0; Output per System 145,000 Total Output (Btuh) 145,000 1: Total Output (Tons) 12.11 i Total Output (Btuhfsgft) i 59.8' 1 Total Output (sgft/Ton) i 200.5 jAir System 1 2171 8,5561 i CFM per System 5,0001 Airflow (cfm) 5,000 I Airflow (cfmfsgft) 1 2.06 Airflow (cfmfTon) 1 413.8 Outside Air {%) i 4.3 Outside Air (cfmfsgft) 0.09 Note: values above (EATING SYSTE 26.0 of Outside _�� 217 cfm 69.9 of at ARI conditions YCHROMETRICS (Ai 68.0 of Lennox THA150S j 122,2001 01 1 95,363; 1 I � I i i I 1 Total Adjusted System Output (Adjusted for Peak Design Conditions) ! 122,200 0 95,363; 1 TIME OF SYSTEM PEAK Jul 2 pm j Jan 12 ami Heating Coil im Temperatures at Time of 86.0 of Supply Fan 5000 cfm 86.0 of -� Supply Air Ducts i 85.9 of ROOMS__i; 1 70.0 of I K Return Air Ducts 4 120OLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) !111.9 / 77.6 of 76.4 / 61.7 of 53.5 / 52.3 of 53.5/52.30 1 Supply Air Ducts Outside Air. i 217 cfm Cooling Coil Supply Fan 54.3 / 52.6 of 5000 cfm 46.1% R.H. ROOMS 8/60.8 F 74.0/60.6OF; !� Return Air Ducts L- EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number. 40528 Page:51 of 53 COIL COOLING PEAK ; ;COIL HTG. PEAK; CFM ,Sensible; Latent CFM Sensible ii Total Room Loads 4,143; 86,961; 5,5801!'! 3221 5,4521 Return Vented Lighting 0; Return Air Ducts 4,3481 273: Return Fan ; 0, I 0i Ventilation 1 2171 8,5561 4,5821 2171 10,1271 ii Supply Fan ; 01 1 :i 0; Supply Air Ducts 4,3481 273; i TOTAL SYSTEM LOAD II i 104,213, 10,1621 1 16,1241 - . Lennox THA150S j 122,2001 01 1 95,363; 1 I � I i i I 1 Total Adjusted System Output (Adjusted for Peak Design Conditions) ! 122,200 0 95,363; 1 TIME OF SYSTEM PEAK Jul 2 pm j Jan 12 ami Heating Coil im Temperatures at Time of 86.0 of Supply Fan 5000 cfm 86.0 of -� Supply Air Ducts i 85.9 of ROOMS__i; 1 70.0 of I K Return Air Ducts 4 120OLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak) !111.9 / 77.6 of 76.4 / 61.7 of 53.5 / 52.3 of 53.5/52.30 1 Supply Air Ducts Outside Air. i 217 cfm Cooling Coil Supply Fan 54.3 / 52.6 of 5000 cfm 46.1% R.H. ROOMS 8/60.8 F 74.0/60.6OF; !� Return Air Ducts L- EnergyPro 3.1 By EnergySoft User Number. 2531 Job Number. 40528 Page:51 of 53 HVACSYSTEM HEATING AND COOLING LOADS SUMMARY --OJECT NAME The Hideawav Golf Clubhouse ;SYSTEM NAME AC -1 ENGINEERING CHECKS ! I j 1 ;Number of Systems !Heating System ! N v uiNua Nw .ay aicu, . Total Output (Btuh) 23,600! Output (Btuh/sgft) I 291.4 Cooling System — 74.6/61.4 OF 74.6/61.4 OF j Output per System ! 30,2001 Total Output (Btuh) ! 30,200j j Total Output (Tons) 2.5 Total Output (Btuh/sgft) 372.81 Total Output (sgft/Ton) I 32.21 ;Air System CFM per System i 1,200 Airflow (cfm) 1,2001 Airflow (cfm/sqft) 14.81 Airflcw (cfm/Ton) 476.8] Outside Air (%) 1.0 Outside Air (cfm/sqft) i 0.151 Note: values above (EATING SYSTE 26.0 of Outside Air 12 cfm 70.0 of n at ARI conditions SYCHROMETRICS 69.5 of 69.5 of Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD DATE _ 6/25/2004 _ FLOOR AREA 81 COIL COOLING PEAK ' COIL HTG. PEAK:: CFM 'Sensible! Latent ` CFM Sensible , 10i 124' 61 0! 1 12 _ — 569' 321! L 61 7,554 444; j 705; ! !Lennox HP29-036/CB29M-41 i 25,1801 01 Ij I i I 1 Total Adjusted System Output (Adjusted for Peak Design Conditions) 25,1801 Oj TIME OF SYSTEM PEAK Jul 3 pm j Supply Fan Heating Coil 1200 cfm Im Tem 81.7 of Tim 15,521; ! J 15,521! _ Jan 12 aml Supply Air Ducts 81.7 of ROOMS 70.0 of Return Air Ducts I DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Cooling Peak � 1113.0/77.9 OF 74.6/61.4 OF 74.6/61.4 OF 54.9/53.9 OF I Supply Air Ducts ! ! o i Outside Air 12 cm Supply Fan Cooling Coil 55.2 / 54.0 OF 1200 cfm I ROOMS__: ' 47.9% R.H. ! ° !.3/61.2F 74.0/61.1OF ! Return Air Ducts I j Energy Pro 3.1 By EnergySoft User Number. 2531 Job Number. 40528 Page:52 of 53 i IH`i/AC'SYSTEM HEATING AND COOLING LOADS SUMMARY OJECT NAME DATE The Hideaway Golf Clubhouse 6/25/2004 :SYSTEM NAME FLOOR AREA AC -2, 3 _ 443 NGINEERING CHECKS SYSTEM LOAD Number of Output Total O i Output (Btuh/sgft) ICooling System 135.4' I� Output per System i 30,70011 Total Output (Btuh) 61,400!1 Total Output (Tons) i 1,9241 31,3001 Total Output (Btuh/sgft) 1 138.6 Total Output (sgft/Ton) 86.61 Air System 6,4801 CFM per System 800, Airflow (cfm) 1,6001 Airflow (cfm/sgft) 3.61 Airflow (cf nrron) 312.71 Outside Air 10.3 Outside Air (cfm/sgft) 0.37 Note: values above qiven at ARI conditions 26.0 of Outside _�� 165 cfm 69.4 of OOLING S 11.9 / 77.6 of Outside �� 165 cfm 4.9/63.5 of EnerovPro 3.1 PSYCHROMETRICS 65.0 of 65.0 of Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK 1 I CFM iSensiblel Latent ii CFM Sensible i 1,9241 31,3001 3,50' 629; 19,8111 , 01 1565 991:: of . 6,4801 2,101 6 7,598; j 01 1,5651 40,9101 ' 5,602] 0 :. _9911 29,391 1Dectron CCA-006/MAM-030 35,6361 19,084; 1 60,000! I Total Adjusted System Output i (AdjustedforPeak Design Conditions) i 35,636 19,084 f 60,0001 TIME OF SYSTEM PEAK j Jul 4 pm Jan 12 am ream Temperatures at Time of Heatina Peak) 100.2 OF Supply Fan Heating Coil 1600 cfm ROMETRICS (Airstream T 78.7 / 65.2 OF 78.7 / 65.2 of '0 —� Return Air Ducts ?ratures at Time of Coo Ii 57.8/56.7°F Supply Fan Cooling Coil 1600 cfm Return Air Ducts `i User Number. 2531 Job Number. 40528 Supply Air Ducts 99.6 of I i ROOMS 70.0 91F i I i Supply Air Ducts 1 58.7/57.1OF 55.6% R.H. ; ROOMS ; ; 74.0 / 63.2 of 1 of 53