9812-104 (CSCS) HVAC Load DataPAGE 1 PROJECT: MAZDA SUPERSTORE CLIENT: T -SQUARED DATE: 10-13-98 ELITE SOFTWARE HVAC LOADS PROGRAM DESIGNER: BRIAN S. BUILDING MASTER DATA DESIGN PARAMETERS: DESIGN OUTDOOR OUTDOOR INDOOR INDOOR HUMID CORRECTION MONTH DRY BULB WET BULB REL.HUM DRY BULB DIFF FACTOR MAY 100 68 50% 72 -7.33 4 JULY 110 68 50% 72 -23.47 14 SEPTEMBER 116 70 50% 72 -22.50 20 NOVEMBER 100 68 ;50% 72 -7.33 4 WINTER 26 0 50% 75 0.00 GLASS SUMMER WINTER GL.SHD INT.SHD ROOM GLASS GLASS .TYPES U FACT U FACT COEFF COEFF CONST HEIGHT WIDTH 1. 1.110 1'.130 0.710 0.000 MED 10.0 1.0 2. 1.110 1.130 0.710 0.000 MED 8.5 1.0 3. 1.110 1.130 0.710 0.000 MED 4.5 1.0 4. 1.110 1:130 0.710 0.000 MED 5.0 1.0 SHADING HOR R.FIN L.FIN TYPES ,PROD PROD, PROJ 1. 17.0 0.0 0.0 2. 28.0 0.0 0.0 3. 12.0 0.0 0.0 ROOF U ASHRAE SUSP TYPE FACT ROOF NO CLG 1. 0.037 1 YES WALL U ASHRAE TYPE FACT GROUP 1. 0.560 A 2. 0.060 B PART. U CLG. HTG. TYPES FACT T.D. T.D. 1. 0.087 35 35 ***** COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ***** SAN DIEGO, CALIFORNIA MAZDA SUPERSTORE 10-13-98 PAGE 2 ******************** BUILDING MASTER DATA (CONTINUED) ********************* GENERAL PROJECT INFORMATION: PROJE.CT FILE NAME: TORRE PROJECT LOCATION: LA QUINTA DEGREES NORTH•LATITUDE: 30 DEGREES LONGITUDE: 116 BAROMETRIC PRESSURE: 29.921 TIME ZONE: 8 DAYLIGHT SAVINGS TIME: YES MEAN DAILY TEMPERATURE RANGE: 34 ZONE SENSIBLE SAFETY FACTOR = 0 ZONE LATENT SAFETY FACTOR = 0 ZONE HEATING SAFETY FACTOR = 0 BUILDING OPENS AT 8 AM. BUILDING CLOSES AT 6 PM. NUMBER OF UNIQUE ZONES IN THIS PROJECT = 8 BUILDING DEFAULT VALUES: BUILDING DEFAULT CEILING HEIGHT = 8 PEOPLE SENSIBLE LOAD MULTIPLIER = 230 PEOPLE LATENT LOAD MULTIPLIER = 180 FLOOR HEAT LOSS COEFFICIENT = 0 LIGHTING ADDED ON A SQUARE FOOTAGE BASIS OF 1.5 WATTS PER SQ.FT. EQUIPMENT ADDED DIRECTLY TO ZONES PEOPLE ADDED ON A SQUARE FOOTAGE BASIS OF 1 PERSON PER 100 SQ.FT. INTERNAL OPERATING LOAD PROFILES: PROFILE HR HR HR HR HR HR HR HR HR HR HR HR HR NUMBER 8 9 10 11 12 13 14 15 16 17 18 19 20 1. 100 100 100 100 100 100 100 100 100 100 100 100 100 2. 100 100 100 100 100 100 100 100 100 100 100 100 100 3. 100 100 100 100 100 100 100 100 100 100 100 100 100 4. 100 100 100 100 100 100 100 100 100 100 100 100 100 S. 100 100 100 100 100 100 100 100 100 100 100 100 100 6. 100 100 100 100 100 100 100 100 100 100 100 100 100 ALL DESIGN DATA TAKEN FROM THE 1985 ASHRAE HANDBOOK OF FUNDAMENTALS ***** COMMERCIAL HVAC LOADS PROGRAM,BY ELITE SOFTWARE DEVELOPMENT INC ***** SAN DIEGO, CALIFORNIA MAZDA SUPERSTORE 10-13-98 PAGE 3 ******************** BUILDING MASTER DATA (CONTINUED) ********************* DEFAULT AIR SYSTEM DESCRIPTION: THIS -AIR SYSTEM OCCURS 1 TIME(S) THROUGHOUT THE BUILDING LIGHTING: PROFILE.# 1 IS USED.100% OF LOAD IS APPLIED TO CONDITIONED SPACE EQUIPMENT: PROFILE #•1 IS USED. PEOPLE: PROFILE-# 1 IS USED. PACKAGED EQUIPMENT IS EMPLOYED USING A CONSTANT VOLUME SYSTEM A 20.0 DEGREE LEAVING COIL -ZONE TEMPERATURE DIFFERENCE HAS BEEN SPECIFIED SEASON VENTILATION -- METHOD INFILTRATION -- METHOD ' SUMMER, 15.00 CFM PER PERSON 0.00 NONE WINTER 15.00 CFM PER PERSON 0.00 NONE ** COMMERCIAL HVAC LOADS PROGRAM BY -'ELITE SOFTWARE.DEVELOPMENT INC ** SAN DIEGO, CALIFORNIA MAZDA SUPERSTORE 10-13-98 PAGE 4 ************** DETAILED PROJECT ZONE LOAD CALCULATIONS *************** LOAD 1396 UNIT LOAD TEMP.. LOAD SEN. LAT. HTG. HTG. DESCRIP. 91 QUAN FACT. DIFF. MULT-. HEAT HEAT MULT. LOAD 5. SHOWROOM PEAK TIME 1 PM SEPTEMBER 2000 SF. SYS. 5 ROOF 1 2000 0.037 91 3.367 6734 1602 1.813 3626 N.WALL 1 30 0.560 30 16.800 504 160 27.440 823 E.WALL 1 40 0.560 40 22.400 896 3.410 27.440 1098 NE.WALL 1 0 0.560 36 20.160 10 27.440 0 SE.WALL .1 0 0.560 38 21.280 0 27.440 0 S.WALL 1 30 0.560 34 19.040 571 27.440 823 N.GLASS 1 140 1.110 53.384 7474 55.370 7752 NE.GLASS 1 90 1.110 59.071 5316 55.370 4983 E.GLASS 1 390 1.110 89.445 34883 55.370 21594 SE.GLASS 1 90 1.110 104.532 9408 55.370 4983 S.GLASS 1 206 1.110 101.486 20906 55.370 11406 SH.S.GLASS 1 14 1.110 .53.384 747 55.370 775 LIGHTS 3000.00 100% 3.410 10230 PEOPLE 20.00 100% 230 180 4600 3600 TOTAL 102270 3600 57863 6. 6 1396 PEAK PEAK TIME 1 PM SEPTEMBER ROOF 1 770 0.037 91 3.367 2593 N.WALL 1 242 0.560 30 16.800 4066 E.WALL 1 168 0.560 40 22.400 3763 N.GLASS 4 30 1.110 53.384 1602 E.GLASS 4 80 1.110 89.445 7156 PART. 1 160 0.087 35 35 3.045 487 LIGHTS 1155.00 100% 3.410 3939 PEOPLE 8.00 100% 230 180 1840 TOTAL 25445 7. 7 1396 PEAK TIME 3 PM SEPTEMBER ROOF 1 2900 0.037 98 3.626 10515 N.WALL 1 356 0.560 30 16.800 5981 PART. 1 416 "0.087 35 35 3.045 1267 LIGHTS 4350.00 100% 3.410 14834 .PEOPLE 29.00 100% 230 180 6670 TOTAL 39267 770 SF. SYS. 6 1.813 1396 27.440 6640 27.440 4610 55.370 1661 55.370 4430 3.045 487 1440 1440 19224 2900 SF. SYS. 7 1.813 5258 27.440 9769 3.045 1267 5220 5220 16294 ** COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ** SAN DIEGO, CALIFORNIA MAZDA SUPERSTORE 10-13-98 PAGE 5 ************** DETAILED PROJECT ZONE LOAD CALCULATIONS *************** LOAD UNIT LOAD TEMP. LOAD SEN. LAT. HTG. HTG. DESCRIP. ---------- QUAN ------ FACT. ----- DIFF. ----- MULT. ----- HEAT ------ ------ HEAT . MULT. ----- LOAD ------ 8. 8 PEAK TIME 2 PM SEPTEMBER 1225 SF. SYS. 8 ROOF 1 1225 0.037 97 3.589 4397 1.813 2221 E.WALL 1 178 0.560 41 22.960 4087 27.440 4884 SE.WALL 1 33 0.560 39 21.840 721 27.440 906 S.WALL 1 103 0.560 34 19.040 1961 27.440 2826 N.WALL 1 256 0.560 30 16.800 4301 27.440 7025 S.GLASS 2 179 1.110 103.753 18572 55.370 9911 SH.S.GLASS 2 .8 1.110 54.735 438 55.370 443 E.GLASS, 4 30 1.110 84.392 2532 55.370 1661 SE.GLASS 4 55 •1.110 97.974 5389 55.370 3045 S.GLASS 4 28 1.110 103.753 2905 55.370 1550 SH.S.GLASS 4 2 1.110 54.735 109 55.370 111 ,LIGHTS 1837.50 100% 3.410 6266 PEOPLE 13.00 100% 230 180 2990 2340 TOTAL 54668 2340 34583 *****.COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ***** SA.N DIEGO. CALIFORNIA MAZDA SUPERSTORE 10-13-98 PAGE 6 *********************** ZONE SUMMARY OF SYSTEM 5 ************************* S9N ABBREV. PEAK TIME FLOOR SENSIBLE HEATING. VENT INFL EXH SUPPLY CFM NO. --- DESCRIP ------- AND MONTH ---------------- AREA LOAD LOAD CFM CFM CFM CFM /SF 5 SHOWR00 .1 PM SEP ------- 2000 ---------------- 102270 ----- 57863 300 ---- 0 --- 0 ------ 4649 ---- 2.3 ZONE PEAK TOTALS 2000 -------- -------- 102270 ----- 57863 300 ---- 0 --- 0 ------ 4649 ---- 2.3 ---------=----------------------------------------------------------------- * ----------7--------------------------------7------------------------------- MONTHLY AND HOURLY SYSTEM ZONE SENSIBLE LOAD PROFILE * MAY JULY SEPTEMBER NOVEMBER NOT USED NOT USED * * HOUR ZONE.SEN -------------------=------------------------------------------------------- ZONE.SEN ZONE.SEN ZONE.SEN ZONE.SEN ZONE.SEN * 8 AM 38442 50433 76288 52891 0 0 9 AM 58871 69197 81555 64027 0. 0 10 AM 62315 72686 91593 70614 0 0 11 AM 73912 84852 96690 76600 0 0 12 AM 74338 85304 99521 81765 0 0 1 PM 75620 86656 102270 85467 0 0 2 PM 74277 85380 101176 85240 0 0 •3 PM 73185 84324 99352 83206 0 0 4 PM 69899 81097 95289 78840 0 0 5 PM 65738 77302 89883 73047 0 0 6 PM 62378 74007 84983 67532 0 0 7 PM 0 0 0 0 0 0 8 --------------------------------------------------------------------------- PM 0 0 0 0 0 0 ***** COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ***** SAN DIEGO, CALIFORNIA 'MAZDA SUPERSTORE 10-13-98 PAGE 7 ******************** TOTAL LOAD SUMMARY OF AIR SYSTEM 5 ****************** SYSTEM TYPE: PACKAGED EQUIPMENT WITH CONSTANT VOLUME TERMINALS SENSIBLE HEAT RATIO: 0.97 -- THIS SYSTEM OCCURS 1 TIMES) IN THE BUILDING SYSTEM 5 PEAKS IN SEPTEMBER AT 2 PM OUTSIDE TEMP IS 115 'INSIDE TEMP IS 72 BECAUSE.OF THE DIVERSITY IN ZONE, PLENUM, AND VENT LOADS, THE ZONE SENSIBLE PEAK TIME IN SEPTEMBER AT 1 PM IS DIFFERENT FROM THE TOTAL SYS. PEAK TIME HENCE, THE AIR SYSTEM CFM WAS COMPUTED USING A ZONE SEN LOAD OF 102,270 SUMMER: VENT CONTROLS OUTSIDE AIR ---- WINTER: VENT CONTROLS OUTSIDE AIR WINTER VENT AIR LOAD - 15,876 BTU/HR ( 300 CFM) WINTER EXH AIR LOAD = 0 BTU/HR ( 0 CFM) WINTER INFIL AIR LOAD = 0 BTU/HR ( 0 CFM) TOTAL ZONE HEATING LOAD = 57,863 BTU/HR BTU/HR TOTAL SYSTEM HEATING LOAD = 73.739 BTU/HR **** ALL COOLING LOADS BELOW WERE COMPUTED AT THE AIR SYSTEM PEAK TIME **** SUMMER VENT SENSIBLE GAIN = EXHAUST AIR SENSIBLE GAIN = SUMMER INFL SENSIBLE GAIN = TOTAL ZONE SENSIBLE GAIN = TOTAL PLNM SENSIBLE.GAIN = ZONE LOAD SEN SUBTOTAL DRAW-THRU FAN SEN GAIN = BLOW-THRU FAN SEN GAIN = MCL SUP.SIDE COIL GAIN = MCL RET.SIDE COIL GAIN. _ SUPPLY DUCT HEAT GAIN = RETURN'DUCT HEAT GAIN = AIR HANDLING SUBTOTAL 14,190 BTU/HR ( 300 CFM) 0 BTU/HR ( 0 CFM) 0 BTU/HR ( 0 CFM) 101,176 BTU/HR BTU/HR 0 BTU/HR LATENT GAIN = 0 = 115,366 BTU/HR 0 BTU/HR LATENT 0 BTU/HR BTU/HR 0 BTU/HR LATENT GAIN = 0 BTU/HR 0 BTU/HR 0 BTU/HR = 0 BTU/HR TOTAL SYSTEM SENSIBLE GAI = 115,366 BTU/HR SUMMER VENT LATENT GAIN = -4,261 BTU/HR EXHAUST AIR LATENT GAIN = 0 BTU/HR SUMMER INFL LATENT GAIN = 0 BTU/HR TOTAL ZONE LATENT GAIN = 3,600 BTU/HR TOTAL SYSTEM LATENT GAIN = -661 BTU/HR TOTAL SYSTEM COOLING LOAD = 114,705 BTU/HR INTERNAL LOADS SUMMARY: 300 CFM) 0 CFM) 0 CFM) 3000 WATTS OF LIGHTING, 0 WATTS OF EQUIP, AND 20.0 PEOPLE TOTAL SYSTEM SUPPLY AIR = 4,649 CFM BASED ON 20.0 DT TOTAL CONDITIONED AIR SPACE = 2,000 SQ.FT. SUPPLY AIR CFM/SQ.FT. = 2.3243 TONNAGE PER SQ.FT = 0.0048 TOTAL TONNAGE REQUIRED FOR AIR SYSTEM 5 WITH OUTSIDE AIR = 9.56 TONS I 4 ***** COMMERCIAL HVAC LOADS PROGRAM.BY ELITE SOFTWARE DEVELOPMENT INC ***** ''. SAN DIEGO, CALIFORNIA MAZDA SUPERSTORE 10-13-98 PAGE 8 ZONE SUMMARY OF SYSTEM 6 ************************* SQN ABBREV. PEAK -TIME FLOOR SENSIBLE HEATING VENT INFL EXH SUPPLY CFM NO. --- DESCRIP ------- AND'MONTH --------- AREA ------- LOAD -------- LOAD CFM CFM CFM CFM /SF 6 - 6 1 PM SEP 770 ------- -------- 25445 -------- ----- 19224 120 ---- --- ------ 0 0 ---- 1157 1.5 ZONE PEAK TOTALS 770 -------- 25445 ----- 19224 120 ---- --- ------ 0 0 ---- 1157 1.5 ----------------------------7------7--------------------------------------- * --------------------------------------------------------------------------- MONTHLY AND HOURLY SYSTEM ZONE SENSIBLE LOAD PROFILE * MAY JULY SEPTEMBER NOVEMBER NOT USED NOT USED * _} * HOUR --------------------------------------------------------------------------- ZONE.SEN-ZONE.SEN ZONE.SEN ZONE.SEN ZONE.SEN ZONE.SEN * 8 AM 12858 16732 22446 15842 0 0 9 AM 13579 17464 23630 16900 0 0 10 AM 14311 18205 24345 17580 0 0 11 AM 19496 23195 25432 18179 0 0 12 AM 19249 22970 25192 18088 0 0 1 PM 19500 23234 25445 18424 0 0 2 PM 19395 23141 25346 18415 0 0 3 PM 19398 23150 25351 18463 0 0 4 PM 18986 22746 24947 18131 0 0 5 PM 18529 22297 24493 17743 0 0 6 PM 17876 21652 -23840 17128 0 0 7 PM 0 0 0 0 0 0 8 .--------------------------------------------------------------------------- PM 0. 0 0 0 0 0 4 **** COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ***** SAN DIEGO, CALIFORNIA MAZDA SUPERSTORE 10-13-98 PAGE 9 ******************** TOTAL LOAD SUMMARY OF AIR SYSTEM-: 6 ****************** SYSTEM TYPE: PACKAGED EQUIPMENT WITH CONSTANT VOLUME TERMINALS SENSIBLE HEAT RATIO: 0.95 --'THIS SYSTEM OCCURS 1 TIME(S) IN THE BUILDING SYSTEM 6 PEAKS IN SEPTEMBER AT 3 PM OUTSIDE TEMP IS 116 INSIDE TEMP IS 72 BECAUSE OF THE DIVERSITY IN ZONE, PLENUM, AND VENT LOADS, THE ZONE SENSIBLE PEAK TIME IN SEPTEMBER AT 1 PM IS DIFFERENT FROM THE TOTAL SYS. PEAK TIME HENCE, THE.AIR SYSTEM CFM WAS COMPUTED USING A ZONE SEN LOAD OF 25,445 SUMMER: VENT CONTROLS OUTSIDE AIR ---- WINTER: VENT CONTROLS OUTSIDE AIR WINTER VENT AIR LOAD = 6,350 BTU/HR ( 120 CFM) WINTER EXH AIR LOAD = 0 BTU/HR ( 0 CFM) WINTER INFIL AIR LOAD = 0 BTU/HR ( 0 CFM) TOTAL.ZONE HEATING LOAD = 19,224 BTU/HR BTU/HR TOTAL SYSTEM HEATING LOAD = 25,574 BTU/HR **** ALL COOLING LOADS BELOW WERE COMPUTED AT THE AIR SYSTEM PEAK TIME SUMMER VENT SENSIBLE GAIN = EXHAUST AIR SENSIBLE GAIN = SUMMER INFL SENSIBLE GAIN = TOTAL ZONE SENSIBLE GAIN = TOTAL PLNM SENSIBLE GAIN = ZONE LOAD SEN SUBTOTAL DRAW-THRU FAN SEN GAIN = BLOW-THRU FAN SEN GAIN = MCL SUP.SIDE COIL GAIN = MCL RET.SIDE.COIL GAIN = SUPPLY DUCT HEAT GAIN = RETURN DUCT HEAT GAIN = AIR HANDLING SUBTOTAL 5,808 BTU/HR ( 120 CFM) 0 BTU/HR ( 0 CFM) 0 BTU/HR ( 0 CFM) 25,351 BTU/HR BTU/HR 0 BTU/HR LATENT GAIN = 0 = 31,159 BTU/HR 0 BTU/HR LATENT 0 BTU/HR BTU/HR 0 BTU/HR LATENT GAIN = 0 BTU/HR 0 BTU/HR 0 BTU/HR = 0 BTU/HR TOTAL SYSTEM SENSIBLE GAI = 31,159 BTU/HR SUMMER VENT LATENT GAIN = -1,835 BTU/HR EXHAUST AIR LATENT GAIN = 0 BTU/HR SUMMER INFL LATENT GAIN = 0 BTU/HR TOTAL ZONE LATENT GAIN = 1,440 BTU/HR TOTAL SYSTEM LATENT GAIN = -395 BTU/HR TOTAL SYSTEM COOLING LOAD = 30,764 BTU/HR INTERNAL LOADS SUMMARY: 120 CFM) 0 CFM) 0 CFM) 1155 WATTS OF LIGHTING, 0 WATTS OF EQUIP, AND 8.0 PEOPLE TOTAL SYSTEM SUPPLY•AIR = 1,157 CFM BASED ON 20.0 DT TOTAL'CONDITIONED AIR SPACE = 770 SQ.FT. SUPPLY AIR CFM/SQ.FT. = 1.5021 TONNAGE PER SQ.FT = 0.0033 TOTAL TONNAGE REQUIRED FOR AIR SYSTEM' 6 WITH OUTSIDE AIR = 2.56 TONS ***.**-COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ***** SAN DIEGO, CALIFORNIA MAZDA*SUP.ERSTORE 10-13-98 PAGE 10 *********************** ZONE SUMMARY OF SYSTEM 7 ************************* SQN ABBREV. PEAK TIME FLOOR SENSIBLE HEATING VENT INFL EXH SUPPLY CFM NO. DESCRIP AND MONTH AREA LOAD LOAD CFM CFM CFM ' CFM /SF 7 7 3 PM SEP 2900 39267 -------- 16294 435 ----- 0 ---- 0' --- 1785 0.6 ------ ---- ZONE PEAK ------- TOTALS 2900 -------- 39267 16294 435 0 0 1785 0.6 -=------------------------------------------------------------------------- * MONTHLY AND HOURLY SYSTEM ZONE SENSIBLE LOAD PROFILE ---------------------------------------------------------------.------------ * MAY JULY SEPTEMBER NOVEMBER NOT USED NOT USED * * HOUR ZONE.SEN ZONE.SEN ZONE.SEN ZONE.SEN ZONE.SEN ZONE.SEN * =------------------------------7------------------------------------------- 8 AM 27356 30422 32263 27356 0 0 9 AM 28658 31725 33565 28658 0 0 10.AM 30160 33227 35067 30160 0 0 11 AM 31356 34423 36263 31356 0 0 .12 AM 32644 35711 37551 32644 0 0 1 PM 33610 36677 38516 33610 0 O 2 PM 34253' 37320 39160 34253 0 0 3 PM 34361 37428 39267 34361 0 0 4 PM 33931 36998 38838 33931 0 0 5 PM 33379 36446 38286 33379 0 0 .6 PM 32199 35266 37106 32199 0 0 7 PM 0 0 0 0 0 0 8 --------------------------------------------------------------------------- PM 0 0 0 0 0 0 ***** COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ***** SAN DIEGO, CALIFORNIA MAZDA SUPERSTORE 10-13-98 PAGE 11 ******************** TOTAL LOAD SUMMARY OF AIR SYSTEM'` 7 ****************** SYSTEM TYPE: PACKAGED EQUIPMENT WITH CONSTANT VOLUME TERMINALS SENSIBLE HEAT RATIO: 0:88 -- THIS SYSTEM OCCURS 1 TIMES) IN THE BUILDING SYSTEM 7 PEAKS"IN SEPTEMBER AT 3 PM OUTSIDE TEMP IS 116 INSIDE TEMP IS 72 SUMMER: VENT CONTROLS OUTSIDE AIR ---- WINTER:' VENT CONTROLS OUTSIDE AIR WINTER VENT AIR LOAD = 23,020 BTU/HR ( 435 CFM) WINTER EXH AIR LOAD = 0 BTU/HR ( 0 CFM) WINTER INFIL AIR LOAD = 0 BTU/HR ( 0 CFM) TOTAL ZONE HEATING LOAD = 16,294 BTU/HR ----------- TOTAL SYSTEM HEATING LOAD- 39,314 BTU/HR **** ALL COOLING LOADS BELOW WERE COMPUTED AT THE AIR SYSTEM PEAK TIME **** SUMMER VENT SENSIBLE GAIN = 21,054 BTU/HR ( 435 CFM) EXHAUST AIR SENSIBLE GAIN = 0 BTU/HR ( 0 CFM) SUMMER INFL SENSIBLE GAIN = 0 BTU/HR ( 0 CFM) TOTAL ZONE SENSIBLE GAIN = 39,267 BTU/HR TOTAL PLNM SENSIBLE GAIN = 0 BTU/HR ZONE LOAD SEN SUBTOTAL = 60,321 BTU/HR DRAW-THRU FAN SEN GAIN = 0 BTU/HR BLOW=THRU FAN SEN GAIN = 0 BTU/HR MCL SUP.SIDE COIL GAIN = 0 BTU/HR MCL RET.SIDE COIL GAIN = 0 BTU/HR SUPPLY DUCT HEAT GAIN = 0 BTU/HR RETURN DUCT HEAT GAIN = 0 BTU/HR AIR HANDLING SUBTOTAL = 0 BTU/HR TOTAL SYSTEM SENSIBLE GAI = 60,321 BTU/HR SUMMER VENT LATENT GAIN = -6,654 BTU/HR ( 435 CFM) EXHAUST AIR LATENT GAIN = 0 BTU/HR ( 0 CFM) SUMMER INFL LATENT GAIN = 0 BTU/HR ( 0 CFM) TOTAL ZONE LATENT GAIN = 5,220.BTU/HR TOTAL SYSTEM LATENT GAIN = -1,434 BTU/HR TOTAL SYSTEM COOLING LOAD = ,58,887 BTU/HR INTERNAL LOADS SUMMARY: 4350 WATTS OF LIGHTING, TOTAL SYSTEM SUPPLY AIR = TOTAL CONDITIONED AIR SPACE _ SUPPLY AIR CFM/SQ.FT. _ TONNAGE PER SQ.FT. _ TOTAL TONNAGE REQUIRED FOR AIR SYSTEM 0 WATTS OF EQUIP, AND 29.0 PEOPLE 1,785 CFM BASED ON 20.0 DT 2,900 SQ.FT. 0.6155 0.0017 7 WITH OUTSIDE AIR = 4.91 TONS i ***** COMME_RCIAL.`HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC ***** .SAN DIEGO, CALIFORNIA MAZDA SUPERSTORE 10-13-98 PAGE 12 *********************** ZONE SUMMARY OF SYSTEM 8 ************************* SQN ABBREV. PEAK TIME FLOOR SENSIBLE HEATING VENT INFL EXH SUPPLY CFM NO. --- DESCRIP AND MONTH -------------- AREA LOAD ---- LOAD CFM CFM CFM CFM /SF 8'8. 2 PM SEP 1225 --------------- 54668 ----- 34583 195 ---- --- ------ 0 0 --- 2485 2.0 ZONE PEAK TOTALS ------- 1225 -------- -------- 54668 ----- 34583 195 ---- --- ------ 0 0 ---- 2485 2.0 -----------7--------------------------------------------------------------- * --------------------------------------------------------------------------- MONTHLY AND HOURLY SYSTEM ZONE SENSIBLE LOAD PROFILE * MAY JULY SEPTEMBER NOVEMBER NOT USED NOT USED * * HOUR ZONE.SEN ZONE.SEN ZONE.SEN ZONE.SEN ZONE.SEN ZONE.SEN * --------------------------------------------------------------------------- 8 AM 22391 29523 35748 24318 0 0 9 AM 23911 31203 37259 30967 0 0 10 AM 24576 31827 41633 34175 0 0 11 AM 28188 35386 44740 37524 0 0 12 AM 32228 39044 50748 45589 0 0 1 PM 33785 40596 53921 49211 0 0 2 PM 34185 41006 54668 50446 0 0 3 PM 33945 40758 53713 48926 0 O 4 PM 33012 39846 51994 46538 0 0 5 PM 32031 39178 49749 43498 0 0 6 PM 31186 38356 47056 40072 0 0 7 PM 0 0 0 0 0 0 8 ------------------------------------ PM 0 0 0 ----------------------------------------- 0 0 0 i ***.**-C_OMMERCIAL'HVAC LOADS PROGRAM BY -ELITE SOFTWARE DEVELOPMENT INC ***** SAN DIEGO, CALIFORNIA MAZDA SUPERSTORE 10-13-98 PAGE -13 ******************** TOTAL LOAD SUMMARY OF AIR SYSTEM. 8 ***************** SYSTEM TYPE: PACKAGED EQUIPMENT WITH CONSTANT VOLUME TERMINALS SENSIBLE HEAT RATIO:. 0.96 THIS SYSTEM OCCURS 1 TIMES) IN THE BUILDING SYSTEM. 8 PEAKS IN SEPTEMBER AT 2 PM OUTSIDE TEMP IS 115 INSIDE TEMP IS 72 SUMMER: VENT CONTROLS OUTSIDE AIR ---- WINTER: VENT CONTROLS OUTSIDE AIR WINTER VENT AIR LOAD = 10,319 BTU/HR ( 195 CFM) WINTER EXH AIR LOAD = 0 BTU/HR ( 0 CFM) WINTER INFIL AIR LOAD = 0 BTU/HR ( 0 CFM) TOTAL ZONE HEATING LOAD = 34,583 BTU/HR BTU/HR TOTAL SYSTEM HEATING LOAD = 44,902 BTU/HR **** ALL COOLING LOADS BELOW WERE COMPUTED AT THE AIR SYSTEM PEAK TIME **** SUMMER VENT SENSIBLE GAIN = EXHAUST AIR SENSIBLE GAIN = SUMMER INFL SENSIBLE GAIN = TOTAL ZONE SENSIBLE GAIN = TOTAL PLNM SENSIBLE GAIN = ZONE LOAD SEN SUBTOTAL DRAW-THRU FAN SEN GAIN = BLOW-THRU FAN SEN GAIN = MCL SUP.SIDE COIL GAIN = MCL RET.SIDE COIL GAIN = SUPPLY DUCT HEAT GAIN = RETURN DUCT HEAT GAIN = AIR HANDLING SUBTOTAL 9,224 BTU/HR 0 BTU/HR 0 BTU/HR 54,668 BTU/HR 0 BTU/HR O BTU/HR 0 BTU/HR 0 BTU/HR 0 BTU/HR 0 BTU/HR 0 BTU/HR ( 195 CFM) ( 0 CFM) ( 0 CFM) TOTAL SYSTEM COOLING LOAD = 63,463 BTU/HR = 63,892 BTU/HR 195 CFM) 0 CFM) 0 CFM) 0 BTU/HR INTERNAL LOADS SUMMARY: 1837 WATTS OF LIGHTING, 0 WATTS OF EQUIP, AND 13.0 PEOPLE TOTAL SYSTEM SUPPLY AIR = 2,485 CFM BASED ON 20.0 DT TOTAL CONDITIONED AIR SPACE = 1,225 SQ.FT. SUPPLY AIR CFM/SQ.FT. = 2.0285 TONNAGE PER SQ.FT = 0.0043 TOTAL TONNAGE REQUIRED FOR AIR SYSTEM 8 WITH OUTSIDE AIR = 5.29 TONS TOTAL SYSTEM SENSIBLE GAI = 63,892 BTU/HR SUMMER VENT LATENT GAIN = -2,769 BTU/HR EXHAUST AIR LATENT GAIN = O BTU/HR SUMMER INFL LATENT GAIN = 0 BTU/HR TOTAL ZONE LATENT GAIN = 2,340 BTU/HR TOTAL SYSTEM LATENT GAIN = -429 BTU/HR TOTAL SYSTEM COOLING LOAD = 63,463 BTU/HR = 63,892 BTU/HR 195 CFM) 0 CFM) 0 CFM) 0 BTU/HR INTERNAL LOADS SUMMARY: 1837 WATTS OF LIGHTING, 0 WATTS OF EQUIP, AND 13.0 PEOPLE TOTAL SYSTEM SUPPLY AIR = 2,485 CFM BASED ON 20.0 DT TOTAL CONDITIONED AIR SPACE = 1,225 SQ.FT. SUPPLY AIR CFM/SQ.FT. = 2.0285 TONNAGE PER SQ.FT = 0.0043 TOTAL TONNAGE REQUIRED FOR AIR SYSTEM 8 WITH OUTSIDE AIR = 5.29 TONS