06-0331 (OFC) Title 24.. 6- � 7
TITLE 24 REPORT
Title 24 Report for:
PETCO ANIMAL SUPPLIES, INC.
111 LA QUINTA CENTER
LA QUINTA, CA 92253
Project Designer:
CARL COX, AIA
81-557 DR. CARREON BLVD.
I N D 10, CA- 92201
(760) 347-4007
Report. Prepared By:
JOHN JOLLY
C+J Technical Solutions and Services
404 Laspino Lane
Diamond Bar, CA 91765FBU
OF LA QUINTA
(909) 896-3631 NG & SAFETY DEPT..
PPROVED
FOR CONSTRUCTION
DA ✓>c Z gy ol L %
Job Number:
C05083
Date: fir.
4/3%2006
The EnergyPro computer program has been used to perform the calculations summarized In this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.1 by EnergySoft Job Number: C05083 User Number 5950
� ! y. A ..
� e } y'} '
ERFORMANCE CERTIFICATE OF
ROJECT NAME
PETCO ANIMAL SUPPLIES, INC.
ROJECT ADDRESS
CIAINs111 LA QUINTA CENTER LA QUINTA
w, n
MPLIANCE Part 1 of 3
DATE
PERF -1
4/3/2006
c14YCLVF•t
CARL COX, AIA TELEPHONE �uldmg erm` f#r
K a r
AENTATION AUTHOR
(760) 347-4007
� t
C+J Technical Solutions andTELEPHONE y1�D`atQ F t::
Services 909 896-3631 eC`ea Y
;RAL INFORMATION
IF PLANS BUILDING ONDITIONED FLOOR AREA
15 249 CLIMATE ZONE
sq.Ft. 15
VG TYPE ® NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL ❑ HOTEL/MOTEL GUEST ROOM
OF CONSTRUCTION ® NEW CONSTRUCTION ❑ ADDITION ❑ EXISTING + ADDITION/ALTERATION
Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
ornla Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
documentation preparer hereby certifies that the documentation Is accurate and complete.
I III�C hITAT1A�, w, T.ai._
The Principal Designer hereby certifys that the proposed b ' ding desig represented in this set of constructi
; on documents is
onsistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this
permit application. 'The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116,
through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
ENV. LTG. MECH.
❑ ❑ 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, or I am a licensed architect.
❑ ❑ ❑ 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section
5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
❑ ❑ ❑ ,3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in
full in the Nonresidential Manual,)
Indicate location on plans of Note Block for Mandatory Measures
Required For V-1
CIPAL ENVELOPE DESMmFR . meRAr ..
Indicate location on plans of Note Block for Mandatory Measures Lightinc
Required.Forms This S
ICIPAL LIGHTING DESIGNER • NAME S!GNATUR€
;�IANICAL COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
Required Forms IVIECH-
CIPAL MECHANICAL DESIGNER - NAME SIGNA�UR
C + J TECHNICAL SOLUTIONS & I rl n,DZ/n
CWffaKm
Compliance Not In The Scope Of
NO. I DATE
-2, MECH-3, MEC
ILIC. NO. I DAl
Vj
nun irnztauon lime* 000-3/0617,S2:08 Run Codes 1144110728
4.1 by Energysoft User Number, 5950 Job Number: C05083 Page:3 of 16
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 ---PERF.
NAME
ET
ENERGY COMPONENT
Space Heating
Space Cooling
Indoor Fans
Heat Rejection
Pumps & Misc.
Domestic Hot Water
Lighting
Receptacle
Process
Standard
Design °
TOTALS: 633.54
Percent better than Standard:
z
Proposed
Design
Compliance
Margin
0.56
50.12
17.48
0.00
0.00
0.00
0.00
0.00
0.00
565.38 68.16
10.8% ( 10.8%
DATE
Building Orientation N o deg Conditioned Floor Area 15,249 sgft.
Number of Stories 1 Unconditioned Floor Area 0 sqh.
Number of Systems 5 Conditioned Footprint Area 15,249 sgft.
Number of Zones 2 Fuel Type Natural Gas
Orlentatlon Gross Area Glazing Area
Front Elevation N 1,800 sgft. 0
Left Elevation E 2,946 sgft. 0
Rear Elevation s 1,800 sqh. 505
Right Elevation W) 837 sgft. 0
Glazlnp
sgft.
sgft.
sgft.
sqh.
Ratio
0.0%
0.0%
28.1%
0.0%
Total 7,383 sqh. 505
sgft.
6.8%
Roof 15,249 sqft. L---�
sgft
Standard Proposed
Lighting Power Density 1.647 W/sgft. 1.647 W/sgft.
Prescriptive Env. Heat Loss 3,835 Btu/h 2,396 Btu/h
Prescriptive Env. Heat Gain 252,976 Btu/h-F 184,808 13tu/h-F
Remarks:
4.1 by EnergySoft User Number: 596o Job Number: C05083 • w Page:4 of 16
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PFR;'_i
and ocumentation, and special verlflcatlon-.,_to _ _b__e. u_sed_._...wit.,,,,h thet—h'e-- . ""' apou,nou 111 11113 Cr1eCK118[. r nese items require special written justification
performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
submitted.
The HVAC System "Lennox LGA1201-1"' Includes Demand Control Ventilation per Standards Section 121.
The HVAC System "Lennox LGA060H+" includes an Economizer. This system has a cooling output < 75,000 Btuh or a sup2ly cfm < 2500.
The HVAC System "Lennox LGA0601-1"" Includes Demand Control Ventilation per Standards Section 121.
C.
The exceptional features listed In this erforrnance approach ppappli application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Authorized Signature or Stomn
r,ur rninaiton tune• 04/03/06 17.32.08 Run Code• 1144110728
4.1 by EnergySoft User Number: 5950 Job Number: C05083 . Paae:5 of 16
CERTIFICATE OF COMPLIANCE =E=NV-1
PROJECT NAME
PETCO ANIMAL SUPPLIES, INC. DATE
�PA0t1F Al iR�errc 4/3/2006
t—j— --, u—iii i cunsoucuon ana In the b Ilding manager's once after Construction
Act. Cond. Location/
# T e Area U -Fac' SHGC2 Azm. Stat. Maging Type Comments
1 Window Rear S 505 1.280 116-A 0.67 116-B 180 New Sin le Metal Tinted RETAIL
(1) U•factor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manuel Appendix, NFRC LabelQd value.
2 SHOO Type: 116.8 Default Table Irani St—Inrda rrnr; r`rmo..d ni
EXTERIOR SHADING
# Exterior Shade Type
1 None
Window Overhang Left Fin Right Fin
SHGC Hgt. Wd. Len. H t. LEMAExt. Dist. Len. H t. Dist. Len. H t.
0.76 11.3 44.7 10.0 0.1 10.0 10.0
MINIMUM SKYLIGHIAREA FOR
LA_RGEENCLMED SpACES
❑The proposed building contains an enclosed space with floor area greater than 26,000 sq,ft, a calling height greater than 16 feet and a LPD for general lighting of at least 0.6 W/ao.ft. If this
box Is checked. ENV -d -r moat h. auen ...e k.. .. ..-'__ "_ ..__ _ _ ... _ .. _
EnergyPro 4.1 by EnergySoft User Number: 5950 Job Number: C05083 Page: B of 16
ICERTIFICATE OF COMPLIANCE
MECH-I-C
PROJECT NAME
PETCO ANIMAL SUPPLIES INC. DATE
Designer: 4/3/2006
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section In the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (Le. the Installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space-condltloning system serving a
building or space Is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation
certificates, and operating and maintenance Information meet the requirements of Sectinn 10-lnafw ..A T101- nA n_—
P4ATI'^
❑ MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing
Test required on all New systerns both New Construction and Retrofit
❑ MECH-3-A: Packaged HVAC Systems Acceptance Document
Equipment requiring acceptance testing
Test required on all Now systems both New Construction and Retrofit.
❑ MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing
Test required on all Now systems both New Construction and Retrofit. Units with economizers that are Installed at the factory and cenllled with the
commisslon do not require equipment testing but do require construction Inspection.
❑ MECH-5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
7'h1s test required if the unit serves 5,000If2 of space or less and 25% or more of the ducts are In nonconditioned or semioondldoned space like an
a01c. New systems that meet the above requirements. Retrofit systems that meat the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
❑ MECH-6-A: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls Installed on new or existing packaged syctoms must be tested.
Q MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
All new VA fan volume controls Installed on now or existing systems must be tested
MECH-8-A:-Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to chilled and hot water systems.
-Automatic Isolation Controls Applies to new bollers and chillers and the primary pumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to now constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 etulhr.
-Water-loop Heat Pump Controls
Applies to all new waterloop heat pump systems where the combined loop pumps are greater than 5 hp.
-Variable Frequency Controls Applies to all now distribution pumps on now variable flow chilled, hydronlc heatpump
or condenser water systems where the pumps motors are greater than 5 hp.
4.1 by EnergySoft User Number: 5950 Job Number: C05083 Peos:7 of 16
R SYSTEM REQUIREMENTS
PROJECT NAME
PETCO ANIMAL SUPPLIES, INC.
ITEM OR SYSTEM TAG(S)
Number of Systems W
MANDATORY MEASURESSectiecti
on .
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.219
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compllance3
Part 1 of 2 MECH-2-C
DATE
4/3/2006
Reference on Plans or Specification 1
112(x)
80% AFUE
80% AFUE
112(a)
11.0 EER
13.0 SEER / 11.0 EER
112 b
n/a
n/a
112(c), 115(a)
n/a
n/a
121(b)
Yes
Yes
121 b
1054 cfm
102 cfm
121 c
No.
No
121 c
Yes
Yes
121(c), 122(e)
Programmable Switch
Programmable Switch
122(e)
Heating & Cooling Required
Heatirfg & Cooling Require
122(f)
Auto
Auto
122(g)
n/a
n/a
123
124
R-8.0
R-8.0
144 a & b
n/a
n/a
144 a & b
752,000 btuh
99,000 btuh
144 a & b
n/a
n/a
144 a & b
370,647 btuh
48,035 btuh
144 c
Constant Volume
Constant Volume
144 c
144 c
Yes
Yes
144 d
No
No
144 a
Fixed Tem (Integrated)
Fixed Tem Non -Into
144 f
Constant Temp
Constant Tem
144 (f)
Constant Temp
Constant Temp
144 k
No
No
1: For each central and single zone air systems (or group of similar units)1111 In the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement Is not applicable, put "N/A" In the column.
2: Not required for hydronic heating and cooling, Either enter a value here or put In reference of plans and speclflcatons per footnote 1.
3: Enter Yes If System is: Constant Volume, Single Zone; Serves < 5,000 sgfh Has > 25% duct In unconditioned apace.. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
VOTES TO FIFI_ 19 _ Fnr R,ifirlinra n,&nsr#m n• i i-- ^-t..
I EnergyPro 4.1 by EnergySoft User Number: 5950 Job Number: C05083 Paga:8 of 16
0
V
Ui
Z
O
Q
J
Z
W
a
L)
2
V
W
LU
Q
Z
I-
0 U
W
O
Q
a
Z
Z
O
F—
Uj
a_
Z TraqMinAi
FIE
s
0)
m
wV
LU c
of
m
a
jr 0
s N, J,
W o
> m
CFM
IICFM
a
°'Z.4
I
c
E
n= O
U i=
>
Qq. ft.
_
1.
1.
>
LU H
a
esign
x
m
_�
Supply
r
3
m
m
d
c
Design ,Ea in
-T
o
`o
m
— Vent. Air o o
m
o
CFM
'
G
3
m�
o
m
.2 2
co
READ V.Ar` n
0
000
z Max of v v
a
a
�
ro
� x
e
(D or G) c' °'
m
v E
o
N Min CFM
c3
m
z
a
a.-
m
rn by Occupant
�
o
a<
E 5
-0
Q
m (ExF)
Fv
ga
a.
E=
aE
E
z
v CFM
m0-0
_ 8
u per
S
<
z
m�
m a
QZ
oL. Person
m
¢
=
m
U
<
t c
`m'
`
(3Number of
W
.m
c-
r
0
O People
=
o=
o
m m
s
m m
s
mm
Min CFM
e
° L
m
m-
Q by Area v_
a
m
""
m (BxC) cD
�mE
s
2_
0)
Q CFM
m
g E
�o
Tcov per o
0
oma
m
N W Square Foot
m
m
o
E
"m3
_�
m <
z
a Condition
Q
o
m
` m Area �
=s4
m'
m
o
>9
(SF)
I
m m
m=m
>
cn
xmm;
�
m m
z
m=
t
m j°
`o
EE
¢'
m c
00<
c�
x m�(cj
-a
m¢
m>=
_
_o
..m
a
mt
_
m
3 m
W0
V v
Y
o
Z W
o
F
`oG$LL•=ma
i°
m
W }
Q
m
o=
w m
-
E 5
O
v m
c
LU
Z
> m
E arca
Em
U O
=9m
cE`m
m=.
v
N
a
m a
c
E E
O`
Q
m
�a
a
X
In
cr
J
U Q
N
W
U
.-
w`
C w
¢
O
Q
W
Z
MECHANICAL EQUIPMENT DETAILS Part 1 of 2 MECH-5-C
PROJECT NAME
PETCO ANIMAL SUPPLIES INC. °ATE 4/3/2006
HILLER AND TOWER SUMMARY
Efficiency.
Tons
PUMPS
Equipment Name
Equipmentlypg
Ot .
Ott
GPMFBHp
MotorEff.
°Effrive
Control
Energy
Factor
or RE
StandbyANK
Loss or
Pilot
INSUL.
System Name
System Type
Distribution Typo
Oty
Rated
Input
Vol.
Gals.)
Condition
Status
Ext.
R -Val.
MULTI -FAMILY CENTRAL W6JEB HEATING DETAILS
Hot Water P mp
Hot Water Piping Len th ft
Control
#
HP
Type
In Plenum
Outside
Buried
Insulation
ENTRAL SYSTEM RATINGS
HEATING
COOLING
System Name
System T
_Output
Aux.
kW
Eff.
outDut
Efficiency
Condition
Status
Economizer Type
Lennox LGA120H*
Split DX
4
188,000
0,0
80%AFUE
128,000
11.0 EER
New
Fixed Temp (integrate(
Lennox LGA060H*
Split DX
1
99,000
0.0
80%AFUE
63,900
13.0 SEER / 11.0 EER
New
Fixed Temp (Non -Into
CENTRAL SYSTEM FAN SUMMARY
SUPPLY
EARETURN
FAN
S stem Name
Fan Type
Motor Location
CFM_
BHP
Motor
Eff.
Drive
Eff.
CFM
BHP
Mlotor
Eff.
Drive
Eff.
Lennox LGA120H*
Constant Volume
Draw -Through
4,000
3.00
86.5%
100.0%
none
Lennox LGA060H'
Constant Volume
Draw -'Through
2,000
1.50
84.0%
100.0%
none,
Run Initiation Times 04/03/06 17&32@08 Run Codes 1144110728
EnergyPro 4,1 by EnergySoft User Number: 5950 Job Number: C05083 Page: 10 of 16
NVELOPE MANDATORY MEASURES ENV -MM
ROJECT NAME
PETCO ANIMAL SUPPLIES, INC. DAVE
4/3/2006
DESCRIPTION Designer Enforcement
X§118(a) Installed Insulating Material shall have been certified by the manufacturer to comply
with the California Quality Standards for Insulating material, Title 20, Chapter 4, Article
3.
® §118(c) All Insulating Materials shall be Installed In compliance with the flame spread rating
and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2.
® § 117(a) All Exterior Joints and openings in the building that are observable sources of air
• leakage shall be caulked, gasketed, weatherstrlpped or otherwise sealed.
F § 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit
and the building, and shall be weatherstripped (except for unframed glass doors end
fire doors).
IAJ § 116(a)1 Manufactured Doors and Windows Installed shall have air Infiltration rates not
exceeding those shown in Table Number I.E. of the Standards. Manufactured
fenestration products must be labeled for U -value according to NFRC procedures.
0 §118(e) Demising Walls In Nonresidential Buildings:
The opaque portions of framed demising walls in nonresidential buildings shall have
Insulation with an Installed R -value of no less than R-13 between framing members.
tnergymo Uy EnergySoft UserNumber• User Job Number: C05083 Page 11 of 16
LIGHTING MANDATORY MEASURES LTG -MM
PROJECT NAME
PETCO ANIMAL SUPPLIES. -INC.
DATE
DESCRIPTION
Designer
Enforcement
a§131(d)1 For every floor, all Interior lighting systems shall be equipped with a separate automatic
control to shut off the lighting. This automatic control shall meet the requirements of
Section 119 and may be an occupancy sensor, automatic time switch, or other device
capable of automatically shutting off the lighting.
X❑ 8131(d)20verride for Building Lighting Shut-off: The automatic building shut-off system is
provided with a manual, accessible override switch in sight of the lights. The area
of override Is not to exceed 5,000 square feet.
§119(h) Automatic Control Devices Certified: All automatic control devices specified are
certified, all alternate equipment shall be certified and Installed as directed by the
manufacturer.
§111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for
the project are certified and listed In the Directory. All Installed fixtures shall be
certified.
§132 ' Tandem Wiring for One and Three Lamp Fluorescent Fixtures: All one and three
lamp fluorescent fixtures are tandem wired with two lamp ballasts where required
by Standards Section 132; or all one and three lamp fluorescent fixtures are
specified with electronic high -frequency ballasts and are exempt from tandem
wiring requirements.
❑ §131(a) Individual Room/Area Controls: Each room and area In this building Is equipped
with a separate switch or occupancy sensor device for each area with floor -to -
ceiling walls.
§131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 900
square feet and more than 0.8 watts per square foot of lighting load shall be
controlled with bi-level switching for uniform reduction of lighting within the room.
§131(c) Daylight Area Control: All rooms with windows and skylights that are greater than
250 square feet and that allow for the effective use of daylight In the area shall
have 50% of the lamps in each daylit area controlled by a separate switch; or the
effective use of daylight cannot be accomplished because the windows are
continuously shaded by a building on the adjacent lot. Diagram of shading during
different times of the year Is included on plans.
El §131(e) Display Lighting. Display lighting shall be separately switched on circuits that
are 20 amps or less.
EnergyPro 4.1 by EnergySofi User Number: 5950 Job Number: C05083 Page: 12 of 16
ECHANICAL MANDATORY MEASURES
NAME
PETCO ANIMAL SUPPLIES, INC.
DESCRIPTION
Equipment and Systems Efficiencies
§111 Any appliance for which there is a California standard established In the
Appliance Efficiency Regulations will comply with the applicable standard.
§ 115(a) Fan type central furnaces shall not have a pilot light.
§ 123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees
Fahrenheit, or within HVAC equipment, shall be Insulated In accordance with
Standards Section 123.
§ 124 Air handling duct systems shall be Installed and Insulated in compliance with
Controls Sections 601, 603 and 604 of the Uniform Mechanical Code.
§ 122(e) Each space conditioning system shall be Installed with one of the following:
a§ 122(e)1 A Each space conditioning system serving building types such as offices and
manufacturing facilities (and all others not explicitly exempt from the
requirements of Section 112 (d)) shall be Installed with an automatic time switch
with an accessible manual override that allows operation of the system during
off -hours for up to 4 hours. The time switch shall be capable of programming
different schedules for weekdays and weekends and have program backup
capabilities that prevent the loss of the device's program and time setting for at
least 10 hours if power is Interrupted; or
F§ 122(e)1 B An occupancy sensor to control the operating period of the system; or
§ 122(e)1C A 4 -hour timer that can be manually operated to control the operating period of .
the system.
® § 122(e)2 Each space conditioning system shall be Installed With controls that temporarily
restart and temporarily operate the system as required to maintain a setback
heating and/or a setup cooling thermostat setpolnt.
0 § 122(g) Each space conditioning system serving multiple zones with a combined
conditioned floor area more than 25,000 square feet shall be provided with
Isolation zones. Each zone: shall not exceed 25,000 square feet; shall be
provided with Isolation devices, such as valves or dampers, that allow the supply
of heating or cooling to be setback or shut off Independently of other Isolation
areas; and shall be controlled by a time control device as described above.
I-,
VNI
§ 122(a&b) Each space conditioning system shall be controlled by an Individual thermostat
that responds to temperature within the zone. Where used to control heating, the
control shall be adjustable down to 55 degrees F or lower. For cooling, the
control shall be adjustable up to 85 degrees F or higher. Where used for both
heating and cooling, the control shall be capable of providing a deadband of at
least 5 degrees F within which the supply of heating and cooling is shut off or
reduced to a minimum.
§ •i22(c) Thermostats shall have numeric setpolnts In degrees Fahrenheit (F) and
adjustable setpolnt stops accessible only to authorized personnel.
❑ §112(b)
Heat pumps shall be Installed with controls to prevent electric resistance
supplementary heater operation when the heating load can be met by the heat
pump alone.
Part 1 of 2 MECH-MMI
DATE
Designer JEnforcement
I EnergyPro By EnergySoft User Number: User Job Number: C05083 PaQe:13 of 16
MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-AI _m_
NAME
PETCO_ANIMAL SUPPLIES, INC.
DATE
4/3/2006
—Description
Designer
Enforcement
Ventilation
X§ 121(a) Controls shall be provided toallow outside air dampers or devices to be operated at
the ventilation rates as specified on these plans.
§ 122(f) Gravity or automatic dampers Interlocked and closed on fan shutdown shall be
provided on the outside air Intakes and discharges of all space conditioning and
exhaust systems.
X❑ § 122(f) All gravity ventilating systems shall be provided with automatic or readily accessible
manually operated dampers In all openings to the outside, except for combustion air
openings.
IX -1 ' § 121(f)1 Air Balancing: The system shall be balanced In accordance with the National
Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or
Associated Air Balance Council (AABC) National Standards (1989); or
El § 121(f)2 outside Air Certification: The system shall provide the minimum outside air as
shown on the mechanical drawings, and shall be measured and certlfled by the
Installing licensed C-20 mechanical contractor and certified by (1) the design
mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) the
person with overall responsibility for the design of the ventilation system; or
§ 121(f)3 Outside Air Measurement: The system shall be equipped with a calibrated local or
remote device capable of measuring the quantity of:outside air on a continuous
basis and displaying that quantity an a readily accessible display divice; or
§ 121(f)4 Another method approved by the Commission.
Service Water Beating Systems
❑ § 113(b)2 If a circulating hot water system Is Installed, It shall have a control capable of
automatically turning off the circulating pump(s) when hot water Is not required.
F] § 113(b)3B :Lavatories in restrooms of public facilities shall be equipped with controls to limit the
outlet temperature to 110 degrees F.
§ 113(b)3C Lavatories In restrooms of public facilities shall be equipped with one of the
following:
Outlet devices that limit the flow of hot water to a maximum of 0.5 gallons per
minute.
Foot actuated control valves, and outlet devices that limit the flow of hot water to a
maximum of 0.75 gallons per minute.
Proximity sensor actuated control valves, and outlet devices that limit the flow of hot
water to a maximum of 0'S. gallons per minute.
Self-closing valves, and outlet devices that limit the flow of hot water to a maximum
of 2.5 gallons per minute, and 0.25 gallons/cycle (circulating system).
Self-closing valves, and outlet devices that limit the flow of hot water to a maximum
of 2.5 gallons per minute, and 0.50 gallons/cycle (non -circulating system).
Self-closing valves, and outlet devices that limit the flow of hot water to a maximum
of 2.5 gallons per minute, and 0.75 gallons/cycle (foot switches and proximity sensor
controls).
EnergyPro By EnergySoft User Number: User Job Number: C05083 Page: 14 of 16
AC SYSTEM HEATING AND COOLING LOADS SUMMARY
ECT NAME DATE
PETCO ANIMAL SUPPLIES INC. 4/3/2006
EM NAME FLOOR AREA
AC -1 1,340
Number of Systems
1
Heating System
Output per System
99,000
Total Output (Stuh)
99,000
Output (Btuh/sqft)
73.9
Cooling System
Output per System
63,900
Total Output (Btuh)
63,900
Total Output (Tons)
5.3
Total Output (Btuh/sqft)
47.7
Total Output (sgft/Ton)
251.6
Air S stem
CFM per System
2,000
Airflow (cfm)
2,000
Airflow (cfm/sqft)
1.49
Alrflow (cfm/Ton)
375.6
Outside Air (%)
5.1
Outside Air (cfm/sgft)
0.08
Note: values above given at ARI conditions
26.0 OF
Outside Air
102 cfm
69.6 OF
12.0 / 77.9 OF
Outside Air
102 cfm
74.7/61.7 °F
67.4 OF
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan -
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
I COIL HTG. PEAK
CFM
ISensiblel Latent
CFM
Sensible
1,46
29,549
2,680
466
17,360
0
1,477
868
0
0
102
4,030
1,973
102
4,709
0
0
1,477
868
361535 4,653 23 805 1
Lennox LGA060H" 48,035 6,682
Total Adjusted System Output48,035 6,682
(Adjusted for Peak Design Condltlons)
TIME OF SYSTEM PEAK I Jul 3 pm
105.0 OF
Heating Coll
99,000
99,000
Jan 12 am
105.0 OF
Supply Air Ducts g —�
Supply Fan 104,6 OF
2000 cfm ROOMS
70.0 OF
Return Air Ducts I
76.6 / 62.7 OF 0 55.0 / 53.9 OF,
Cooling Coll
Supply Fan
2000 cfm
55.0 / 53.9 of
—�� Supply Air Ducts
55.7 / 54.2 of
49.2% R.H. ROOMS
74.0 / 61.5 OF
K Return Air Ducts 'I
EnoroyPro 4.1 by EnergySoft User Number: 5950 Job Number: C05083 Page:16 of 16