13911 (CSCS) Title 24r� TITLE 24 REPORT FOR: DOMINO'S PIZZA RESTAURANT La Quinta, CA PROJECT DESIGNER: ORANCO DEVELOPMENT 1370 Reynolds Ave. #107 Irvine, CA 92714 (714)660-1199 REPORT PREPARED BY: Julie Ann Van Dyke G.M.S. 2280 Meyers Ave., Ste. "A" Escondido, CA 92029 (619) 741-0178 Job Number: #94-930N.H Date: 7/15/1994 The COMPLY 24 computer program has been used to perform the calculations summarized in this compliance report: This program has approval and is authorized by the California. Energy Commission for use with both the Residential and Nonresidential Building Energy Efficiency Standards. This:program developed by Gabel Dodd Associates (510) 428-0803. Table Of Contents for Title 24 Report ------------------------------------- • Cover Page Table of Contents ...:...........c................. ................ 2 Form ENV -1 Envelope Certificate of Compliance ............... Form ENV -2 Envelope Summary ............ 5 Form PERF -1 Building Energy Performance Summary Form LTG -1 Lighting Certificate of Compliance ............ Form LTG -2 Lighting g g Com pliance Summary ..... ........................ 12 Form MECH-1 Mechanical Certificate of Compliance Form MECH-2 Mechanical Summary ................... Form MECH-3 Mechanical Equipment Summary ........ Form MECH-4 Mechanical Ventilation HVAC Zone & Space Loads Summary s. f CERTIFICATE OF COMPLIANCE (part 1 of 2) ENV-1page a e 3 of 20 --------------------------------- ------------------- Project Name: DOMINO'S PIZZA RESTAURANT (Date: 7/15/1994 Address: La Quinta, CA Envelope Designer: ORANCO DEVELOPMENT Documentation: G.M.S. bUilaing Permit No C ec e y Da e COMPLY 24 User 1c;ir, GENERAL INFORMATION Date of Plans: Building Conditioned Floor Area: 1866 sf Building Type: Nonresi ial Climate Zone: 15 Phase of Construction: O New Construction O Addition. O Alteration Method of Envelope Compliance: Prescriptive - Overall Envelope STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Part 6, Chapter 1 and Title 20, Chapter 2, Subchapter 4; Article 1 of the California Code of Regula- tions. This certificate applies only to building envelope requirements. The Principal Envelope Designer hereby certifies that the proposed build- ing design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building has been designed to.meet the envelope requirements contained in sections 110, 116 through 118; and 143 or 149 of Title 24, Part 6, Chapter 1. Please check one: O I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am a civil engineer or architect. O I affirm that I am eligible under the exemption to Division 3 of the Busi-ness and Professions Code by Section 5537.2 of the Business and Professions Code to sign this document as the person responsible its preparation; and that I am a licensed for contractor preparing docu- ments for work that I have contracted to perform. O I affirm that I am eligible under the exemption to Division 3 of Business the and Professions Code by Section of the Code to sign this document as Effie person responsible prepara ion; and for the following reason: or i s PRINCIPAL ENVELOPE DESIGNER ORANCO DEVELOPMENT (714)660-1199 (Signature (Lic. Da e ENVELOPE MANDATORY MEASURES Indicate location on plans of Note Block for Mandatory Measures: � � a CERTIFICATE OF COMPLIANCE (part 2 of 2) ENV -1 page 4 of 20 -------------=----=-------------------------------------------------------- Project Name: DOMINO'S PIZZA RESTAURANT Date: 7/15/1994 Documentation: G.M.S. COMPLY 24 User 1536 --------------------------------------------------------------------------- OPAQUE SURFACES Const Note to Assembly Name Type Location/Comments Field ----------------------- ----- --------------------------------- ------- R-19 Wall (W.19.2x6.16) Wood R-30 Roof(R.30.2xl2.16) Wood FENESTRATION Frame Orient Panes Type Exterior Shade OH Glazing Type --------- ----- ---------------------------- -- ----------------------- Front (S) 2 Metal None N Double Clear (Mtl) Left (W) 2 Metal None N Double Clear (Mtl) Y. OVERALL ENVELOPE METHOD Part 1 --------------------------------------------------------------------------- of 4 ENV -2 page 5 of 20 Proj.ect Name: DOMINO'S PIZZA RESTAURANT Date: 7/15/1994 Documentation: G.M.S. --------------------------------------------------------------------------- COMPLY 24 User 1536 WINDOW AREA TEST _ A. Display Perimeter 0.0 ft X 6 ft = 0.0 sf Display Area B. Gross Exterior Wall Area 1179.0 sf X 0.40 = 471.6 sf 40% Area C'. Gross Exterior Wall Area 1179:0 sf X 0.10 = 117.9 sf Min Std Area D. Enter Larger of A or B 471.6 sf Max Std Area E. Enter Proposed Window Area 307.0 sf Proposed Area If E is greater than D or less than C, proceed to the next calculation for window area adjustment. If not, go to part 2 of 4. 1. If E is greater than D.: Window D: Maximum Standard Area E: Proposed Area Adjustment Factor ------------------------ N/A / ---------------- N/A ----------------- = N/A 2. If E is .less than C: Window C. Minimum Standard Area ------------------------ E. Proposed Area Adjustment Factor I- I / ---------------- N/A ---------------- = N/A SKYLIGHT AREA TEST Atrium Height ------------- 0.0 ft If -Height < 55 ft If Height >= 55 ft Standard = 5% ----------+---------- Standard = 10% V A. Gross Exterior Roof Area 1866:0 sf X 0.05 = 93.3 sf Standard Area B. Enter Proposed Skylight Area 0.0 sf Proposed Area If the Proposed Skylight Area is greater than the Standard Skylight Area; proceed to the next calculation for the skylight area adjustment. If not got to part 2 of 4: 1. If Proposed Skylight Area > Standard Skylight Area: Skylight Standard Skylight Area Proposed Skylight Area Adjustment Factor -------------- ----------- ------------------ ----------------- N/A / �N/A = N/A OVERALL ENVELOPE METHOD Part 2 of 4 ENV -2 page 6 of 20 --------------------------------------------------------------------------- Project Name: DOMINO'S PIZZA RESTAURANT Date: 7/15/1994 Documentation: G.M.S. COMPLY 24 User 1536 OVERALL HEAT LOSS i PROPOSED Adj. STANDARD Assembly Name Area HC U -Val UxA Area U -Val UxA R-19 Wall (W.19.2x6.16) 270.0 3.2 0.065 17.7 270.0 0.084 22.7 R-19 Wall (W.19.2x6.16) 96.0 3.2 0.065 6.3 96.0 0.084 8.1 .R-19 Wall (W.19.2x6.16) 506.0 31.2 0.065 33.1 506.0 0.084 42.5 R-30 Roof(R.30.2xl2.16) 1866.0 2.7 0.035 64.8 1866.0 0.057 106.4 Double Clear (Mtl) 154:0 N/A 0.870 134.0 154.0 0.720 110.9 Double Clear (Mtl) 20.0 N/A 0.870 17.4 20.0 0.720 14.4 Double Clear (Mtl) 133.0 N/A 0.870 115.7 133.0 0.720' 95.8 Total 389.0 Total 400.6 ** OVERALL HEAT LOSS COMPLIES PROPOSED UA <= STANDARD UA ** l OVERALL --------------------------------------------------------------------------- ENVELOPE METHOD Part 3 of 4 ENV -2 page 7 of 20 Project Name: DOMINO'S PIZZA RESTAURANT Date: 7/15/1994 Documentation: G.M.S. --------------------------------------------------------------------------- COMPLY 24 User 1536 ' OVERALL HEAT GAIN PROPOSED STANDARD Glazing -------------- WF Area SC H V OHF Total Area RSHG Total South ---- ------ 1.12 ---- ---- ---- 154.0 0.88 ---- ------ 151.8 ------ 154.0 ---- ------- 0.57 98.3 South 1.12 20.0 0.88 19.7 20.0 0.57 12.8 West 1.13 133.0 0.88 132.3 133.0 0.57 85.7 Total 303.7 Total 196.7 ** OVERALL HEAT GAIN DOES NOT COMPLY PROPOSED HG > STANDARD HG ** l Skylight Area Adjustment Calculations Gross Roof Name Dir Area ----------------------- --- ----- Roof H 1866.0 TOTALS 1866.0 Adjusted Skylt Adjust. Skylt Roof OVERALL ENVELOPE METHOD --------------------------------------------------------------------------- Part 4 of 4 Area Area ENV -2 page 8 of 20 Project Name: DOMINO'S PIZZA RESTAURANT 0.0 1866.0 Date: 7/15/1994 Documentation: G.M.S. --------------------------------------------------------------------------- COMPLY 24 User 1536 Window Area Adjustment Calculations Adjusted Gross Door Window Adjust Window Wall .Wall Name Dir Area Area Area Factor Area Area ----------------------- North --- N ----- ------ 270.0 ------ 0.0 ------ 1.0000 ------ ------ 0.0 270.0 South S 270.0 174.0 1.0000 174.0 96.0 West W 639.0 133'.0 1.0000 133.0 506.0 TOTALS ----- ------ 1179.0 0.0 ------ 307.0 ------ ------ 307.0 872.0 Skylight Area Adjustment Calculations Gross Roof Name Dir Area ----------------------- --- ----- Roof H 1866.0 TOTALS 1866.0 Adjusted Skylt Adjust. Skylt Roof Area ------ Factor ------ Area Area 0.0 0.0000 ------ ------ 0.0 1866.0 0.0 0.0 1866.0 *** BUILDING COMPLIES *** OPTIONAL CAPABILITES AND SPECIAL COMPLIANCE INFORMATION PERFORMANCE COMPLIANCE SUMMARY -------------------------------------------7------------------------------- PERF -1 page 9 of 20 Project Name: DOMINO'S.PIZZA RESTAURANT Date: 7/15/1994 Documentation: G.M.S. --------------------------------------------------------------------------- COMPLY 24 User 1536 ANNUAL SOURCE ENERGY USE (KBtu/sqft-yr) Calc: DOE -24 (COMPLIANCE) Standard Proposed Compliance Energy Component Design Design I Margin Space Heating 3.10 3.10 0.00 Space.Cooling 53.07 54.90 -1.83 HVAC Fans & Pumps 13.60 20.85 -7.25 Domestic Hot Water 5.62 5.62 0.01 Lighting 64:98 44.31 20.68 Receptacle 25.48 25.48 0.00 Process 0.00 .0.00 0.00 TOTALS 165.86 154.27 11.60 *** BUILDING COMPLIES *** OPTIONAL CAPABILITES AND SPECIAL COMPLIANCE INFORMATION CERTIFICATE OF COMPLIANCE (part 1 of 2) LTG -1 page 10 of 20 --------------------------------------------------------------------------- Project Name: DOMINO'S PIZZA RESTAURANT (Date: 7/15/1994 Address::La Quinta, CA Lighting Designer: Documentation: G.M.S. Building Perm1 o C ec e y Date COMPLY 24 User 1536 GENERAL INFORMATION Date of Plans: Building Conditioned Floor Area: 1866 sf Building Type: Nonresi en ial Climate Zone: 15 Phase of Construction: O New Construction O Addition O Alteration Method of Lighting Compliance: Prescriptive STATEMENT OF COMPLIANCE This Certificate of Compliance lists.the building features and performance specifications needed to comply with Title 24, Part 6, Chapter 1 and Title 20, Chapter 2, Subchapter 4, Article 1 of the California Code of Regula- tions. This certificate applies only to building lighting requirements. The Principal Lighting Designer hereby certifies that the proposed build- ing design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building has been designed to meet the lighting requirements contained in sections 110, 119, 130 through 132 and 146 or 149. Please check one: O I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am a civil engineer electrical engineer or architect. O I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section 5537:2 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am a licensed contractor preparing docu- ments for work that I have contracted to perform. o I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section of the Code to sign this document asfie person responsible or i s prepara ion; and for the following. reason: PRINCIPAL LIGHTING DESIGNER (Signature) Li•c. Da e LIGHTING MANDATORY MEASURES Indicate location on plans of Note Block for Mandatory Measures: CERTIFICATE OF COMPLIANCE (part 2 of 2) LTG -1 page 11 of 20 -------------------------------------------------------------------7------- Project Name: DOMINO'S PIZZA RESTAURANT Date: 7/15/1994 Documentation: G.M.S. --------------------------------------------------------------------------- COMPLY 24 User 1536 INSTALLED LIGHTING SCHEDULE No of Watts/ Ballast Ballasts/ No of Note to Name Lamp Type Lamps Lamp ----------------- ------ Type Luminaire Fixt. Field MANDATORY AUTOMATIC CONTROLS Control Note to Control Location ID Control -------------------------------------- Type Space Controlled ---------------------- Field ------- CONTROLS FOR CREDIT Control Note to Control Location ID Control -------------------------------------- Type Space Controlled --------------------- Field LIGHTING COMPLIANCE SUMMARY LTG -2 page 12 of 20 --------------------------------------------------------------------------- 4 Project Name: DOMINO'S PIZZA RESTAURANT Date: 7/15/1994 } Documentation:-G.M.S.------------------------------COMPLY 24 User 1536 -------------------------------------------- ACTUAL LIGHTING POWER No of Watts Total Name Description Lumin per Default Watts ---------------------------------------------- ----- ------------ ----- If not CEC Default value; please provide supporting documentation. ALLOWED LIGHTING POWER BY SPACE Allowed I Floor LPD ' Total Tailored Space Name Occupancy Area (w/sf) (watts) (watts) ------------------------ ---------------------- ----- -------------------- #1-WHOLE BUILDING Kitchen 1866 2.200 4105 0 TOTALS 1866 2.200 4105 0 * Note: Tailored Allotment requires supporting documentation on form LTG -4. 4 _r CERTIFICATE OF COMPLIANCE (part 1 of 3) MECH-1 page 13 of 20 --------------------------------------------------------------------------- Project Name: DOMINO'S PIZZA RESTAURANT (Date: 7/15/1994 Address: La Quinta, CA EMechanical Designer: Documentation: G.M.S. Building Permit o Checked by Date COMPLY 24 User 1536 GENERAL INFORMATION Date of Plans: Building Conditioned Floor Area: 1866 sf Building Type! Nonresidential Climate Zone: 15 Phase of Construction: O New Construction O Addition O Alteration Method of Mechanical Compliance: Prescriptive Proof of Envelope Compliance: O Previous Permit O Compliance Attached STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Part 6, Chapter 1 and Title 20, Chapter 2, Subchapter 4, Article 1 of the California Code of Regula- tions., This certificate applies only to building mechanical requirements. The Principal Mechanical Designer hereby certifies that the proposed build- ing design represented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building has been designed to meet the mechanical requirements contained in sections 110 through 115, 120 through 124, 140 through 142,144 and 145. Please check one: O 'I hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its reparation; and that I am a civil engineer mechanical engineer or architect: O I affirm that I am eligible under the exemption to Division 3 of the Business and Professions Code by Section 5537.2 of the Business and Professions Code to sign this document as the person responsible for itspreparation; and that I am a licensed contractor preparing docu- ments for work that I have contracted to perform: O I affirm that i am eligible under the exemption to Division 3 of the Business and Professions Code by Section of the Code to sign this document as ESS person responsible or i s prepara ion; and for the following reason: PRINCIPAL MECHANICAL•DESIGNER (Signature) Lic. a e MECHANICAL MANDATORY MEASURES Indicate location on.plans of Note Block for Mandatory Measures: CERTIFICATE OF COMPLIANCE (part 2 of 3) MECH-1 page 14 of 20 ---------------------------------7----------------------------------------- Project Name: DOMINO'S PIZZA RESTAURANT Date: 7/15/1994 Documentation: G.M.S. ICOMPLY 24 User 1536 --------------------------------------------------------------------------- SYSTEM FEATURES' Zone Name 12 1/2 Ton Gas/Elec.RTU Time Control Setback Control Both # of Isolation Zonesn/a HP Thermostat n/a Electric Heat n/a Fan Control Constant Volume VAV Min Position n/a Simul. Heat/Cool n/a Heat Supply Reset Constant Temp Cool Supply Reset Constant Temp Ventilation OA Damper Control Economizer Type Fixed Enth (Integrated) Outdoor Air CFM 280 Heat Equip Type Gas Furnace Make & Model No. Lennox#GSC16-1603(Exst) Cool Equip Type DX Make and Model Code Tables Time Control Ventilation ' - OA Damper S:Prog Switch W Air Balance AiAuto O:Occ Sensor Q OA Cert: G:Grivity M:Man Timer M!OA Measure ,DiDemand Cont NiNatural Note to Field CERTIFICATE OF COMPLIANCE ---------------------7----------------------------------------------------- (part 3 of 3) MECH-1 page 15 of 20 Project Name: DOMINO'S PIZZA RESTAURANT Date: 7/15/1994 Documentation: G.M.S. --------------------------------------------------------------------------- COMPLY 24 User 1536 DUCT INSULATION Duct Tape Insul Note to System Name =---------------------- Type Duct Location Allowed. R -Val Field Lennox#GSC16=1603(Exst) -------------------------- Heating Ducts in Attic ------- Y / N ----- 2.1 ------- Cooling Ducts in Attic Y / N 2.1 PIPE INSULATION Insul Note to .System Name ----------------------- Pipe Type Required ----------- ----=--- Field Domestic Hot Water Y / N ------- Lennox#GSC16-1603(Exst) 'Y / N NOTES TO FIELD -.For Building Department Use Only --------------------------------------------------------------------------- MECHANICAL SIZING AND FAN POWER MECH-2 page 16 of 20 --------------------------------------------------------------------------- Project Name: DOMINO'S PIZZA RESTAURANT Date: 7/15/1994 Documentation: G.M.S. COMPLY 24 User 1536 --------------------------------------------------------------------------- SIZING AND EQUIPMENT SELECTION HVAC Zone Name: Heating System Name: Cooling System Name: System Multiplier: Peak Load Method: Relative Humidity: 1. DESIGN CONDITIONS FOR La Quinta 2. SIZING 12 1/2 Ton Gas/Elec.RTU Lennox#GSC16-1603(Exst) 1 COINCIDENT 50 % COOLING HEATING SENSIBLE LATENT ------- -------- ------ 29 F 111 F 75 F SPACES SERVED BY SYSTEM PEAK ----------------------- ---- Btu/hr ------- PEAK Btu/hr Btu/hr #1-WHOLE BUILDING (Jan 12am) 21581 ------------ (Aug 4pm) 46820 ------ 2216 TOTAL SPACE LOAD 21581 46820 2216 Duct Gains & Losses: 2158 4682 Supply Fan 1 x Ventilation: ( 280 CFM) 12476 9129 127 Return Air Lighting Gain Totals 0 944 TOTAL SYSTEM LOAD 36215 60631 2343 3. SELECTION A. Safety/Warmup Factor 1.43 1.21 B. Maximum Adjusted Load 51787 73364 C.•Installed Equipment Capacity 132500 86263 If Line 3-C > Line 3-B, Explain:, 9575 FAN POWER CONSUMPTION No. Efficiency Peak Conv Peak Supply Fan Description Sys --------------------- --- BHP Motor Drive ---7- HP Fact Watts CFM Supply Fan 1 x ----- ----- 1.00 / [0:79 x 1.00] ----- ---- = 1.27 x 746 ----- = 944 ------ 5000 Totals 1.27 944 5000 FAN POWER DEMAND 944 watts / 5000 cfm = 0.189 watts/cfm MECHANICAL EQUIPMENT SUMMARY MECH-3 page 17 of 20 --------------------------------------------------------------------------- Project Name: DOMINO'S PIZZA RESTAURANT (Date: 7/15/1994 Documentation: G.M.S. ICOMPLY 24 User 1536 ------------------------------------------------------'--------------------- PLANT EQUIPMENT SUMMARY Fuel Elec Total No. Input Input Output Equipment Name Equipment Type Sys (KBtu) (KW) (KBtu) ------------------------------------------ --- ----=- ------ ------ Std Gas 50 gal or Less Gas Fired 1 40.0 0.0 31.2 CENTRAL SYSTEM SUMMARY Sys No No System Name System Type Sys Economizer Type ---------------------------------------- --- --------------------------- 1 Lennox#GSC16-1603(Exst) Split FAU-A/C 1 Fixed Enth (Integrated) CENTRAL SYSTEM RATINGS Sys ------- Heating ------------------ ---------------- Cooling ---------- No Type Output Aux KW EFF Type Output Sensible EER SEER --------------------- ------ ---- ------- ------- -------- ----------- 1 Gas Furnace 132500 n/a 0.80 DX 102300 89000 9.00 n/a CENTRAL FAN SUMMARY ------------ Supply Fan ----------- ---- Return Fan --- Sys Mtr Dry Mtr Dry No Fan Type Motor Location CFM BHP Eff Eff CFM BHP Eft Eff -------------------------------- ----- ------ --- --- ----- ----- --- --- 1 Constant Volume Draw -Through 5000 1.00 79 100 None 'ZONAL FAN SUMMARY --------- Zonal Fan ------------ Exhaust Fan ----- Mtr Dry Mtr Dry Space Name No CFM BHP Eff Eff No CFM BHP Eff Eff ----------------------- -- ----- ------ ---- ---- -- ----- ------ ---- ---- None y ^= 14 MECHANICAL VENTILATION MECH-4 page 18 of 20 --------------------7------------------------------------------------------ Project Name:. DOMINO'S PIZZA RESTAURANT Date: 7/15/1994 Documentation: G.M,;S. COMPLY 24 User 1536 '- ----------------- I --------------------------- -------------------------- VENTILATION SUMMARY BY SPACE Tran Floor sqft CFM Min Design sfer Space Name T Occupancy Area /Occ /Occ CFM CFM CFM ----------------------- -------------- ----- ---- ---- ---- ------ ---- #1-WHOLE BUILDING Kitchen 1866 200 30.0 280 280 TOTALS 280 280 Note: If Tailored (T=*), user must document sqft/Occ and/or CFM/Occ values. c !p HVAC ZONE HEATING & COOLING LOAD SUMMARY -------------7------------------------------------------------------------- page 19 of 20 Project Name: DOMINO'S PIZZA RESTAURANT Date: 7/15/1994 Documentation: G.M.S. ,. --------------------------------------------------------------------------- COMPLY 24 User 1536 HVAC ZONE DESCRIPTION f HVAC Zone Name: 12 1/2 Ton Gas/Elec.RTU Heating System Name: Lennox#GSC16-1603(Exst) Cooling System Name: - System Multiplier: 1 Fan Schedule: Day Fans STD Peak Load Method: COINCIDENT Relative Humidity: 50 $ COOLING 4 SPACES IN THIS ZONE PEAK ----------------------- ---- HEATING PEAK SENSIBLE LATENT #1-WHOLE BUILDING (Jan 12am) -------- 21581 ------------ (Aug 4pm) 46820 ------ 2216 TOTAL SPACE LOAD 21581 -------- 46820 ------ 2216 ~ Duct Gains & Losses: 2158 4682 f Ventilation: ( 280 CFM) 12476 9129 127 Return Air Lighting Gain 0 TOTAL SYSTEM LOAD 36215 60631 2343 SYSTEM OUTPUT AT DESIGN CONDITIONS 132500 86263 9575 NOTE: The TOTAL SYSTEM LOAD shown represents the minimum size equipment which will heat or cool this zone during the design conditions indicated. These numbers include no safety factor; and the HVAC contractor should oversize by a reasonable margin to account for variations in weather conditions and the pick-up capacity required to bring the zone to temper- ature as a result of a setback thermostat: Those responsible for final equipment selection should note that Sensible and Latent Cooling Loads are indicated to allow for accurate comparison with.manufacturer's output data.