BCOM2015-0019 Title 24BUILDING ENERGY ANALYSIS REPORT PROJECT: IN -N -OUT La Quinta 78611 Highway 111 La Quinta, CA 92253 Project Designer: GHA Architecture / Development 14901 Quorum Drive , Suite 300 Dallas, TX 75254 (972) 239-8884 Report Prepared by: Jeff'Pollock TECHLOGIC ENERGY CONSULTING 23890 Copper Hill Drive, Suite 320 Valencia, CA 91354 t` 661.714.0133 IRE U,�#� • 'G Job Number: Proto 15 C PIP Date: OCT 07 2015 7/20/2015 By The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC—www.energysoft.com. Ener Pro 6.5 by Ener Soft User Number. 6397 ID: Proto 15 C TABLE OF CONTENTS Cover Page 1 Table of Contents 2 Form LTI-01-E Indoor Lighting 3 Form LTI-02-E Lighting Controls g Form LTI-03-E Indoor Lighting Power Allowance 13 Form LTO -01-E Outdoor Lighting 16 Form LTO -02-E Outdoor Lighting Controls 20 Form LTO -03-E Outdoor Lighting Power Allowances 23 w EnergyPro 6.5 by EnergySoft Job Number: ID: Proto 15 C User Number: 6397 STATE OF CALIFORNIA INDOOR LIGHTING is CEC-NRCC-LTI-01-E Revised 06/14 CALIFORNIA ENERGY COMMISSION < CERTIFICATE OF COMPLIANCE — USER INSTRUCTIONS NRCC-LTI-01-E Indoor Lighting (Page 1 of 5) Project Name: IN -N -OUT La Quinta Date Prepared: 7/20/2015 Climate Zone: 15 Conditioned Floor Area : 3,750 YES NO FORM TITLE - YES NRCC-LIT-01-E Certificate of Compliance; All Pages required on plans for all submittals. Unconditioned Floor Area : 1,010 Lighting Controls, Certificate of Compliance, and PAF Calculation. All Pages required on plans for all submittals. General Information Indoor Lighting Power Allowance NO NRCC-LIT-04-E Tailored Method Worksheets NO NRCC-LIT-05-E Line Voltage Track Lighting Worksheets Building Type: ❑ Schools ' El Nonresidential ❑ Relocatable Public Schools ❑ ❑ High -Rise Residential Conditioned Spaces ❑ 0 Hotel/Motel Unconditioned Spaces Phase of Construction: 0 New Construction ❑ Addition ❑ Alteration Method of Compliance: m Complete Building ❑ Area Category ❑ Tailored LIGHTING COMPLIANCE DOCUMENTS (select yes for each document included) For detailed instructions on the use of this and all Energy Efficiency Standards compliance documents, refer to the Nonresidential Manual published by the California Energy Commission. YES NO FORM TITLE - YES NRCC-LIT-01-E Certificate of Compliance; All Pages required on plans for all submittals. YES NRCC-LIT-02-E Lighting Controls, Certificate of Compliance, and PAF Calculation. All Pages required on plans for all submittals. YES NRCC-LIT-03-E Indoor Lighting Power Allowance NO NRCC-LIT-04-E Tailored Method Worksheets NO NRCC-LIT-05-E Line Voltage Track Lighting Worksheets Summary of Allowed Lighting Power Conditioned and Unconditioned space Lighting must not be combined for compliance Indoor Lighting Power for Conditioned Spaces Indoor Lighting Power for Unconditioned Spaces 1. Installed Lighting NRCC-LTI-01-E, page 4 Watts Installed Lighting NRCC-LTI-01-E, page 4 Watts + 3,629 + 482 2 PORTABLE ONLY FOR OFFICES NRCC-LTI-01-E, page 3 + 3 Minus Lighting Control Credits NRCC-LTI-02-E, page 2 0 Minus Lighting Control Credits NRCC-LTI-02-E, page 2 0 4 Adjusted Installed Lighting Power_ (row 1 plus row 2 minus row 3) 3 629 Adjusted Installed Lighting Power (row 1 minus row 3) _ 482 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 J STATE OF CALIFORNIA INDOOR LIGHTING CERTIFICATE OF COMPLIANCE — USER INSTRUCTIONS NRCC-LTI-01-E Indoor Lighting (Page 2 of 5) Project Name: IN -N -OUT La Quints Date Prepared: 7/20/2015 5. Complies ONLY if Installed <_ Allowed Complies ONLY if Installed <_ Allowed Form/Title 6. Allowed Lighting Power Conditioned NRCC-LTI-03-E, page 1 4,499 Allowed Lighting Power Unconditioned NRCC-LTI-03-E, page 1 1,212 Declaration of Required Installation Certificates — Declare by selecting yes for all Installation Certificates that will be submitted. (Retain copies and verify forms are completed and signed.) YES NO Form/Title NRCI-LTI-01-E - Must be submitted for all buildings ❑ Field Inspector NRCI-LTI-02-E - Must be submitted for a lighting control system, or for an Energy Management Control System (EMCS), to be recognized for compliance. ❑ Field Inspector NRCI-LTI-03-E - Must be submitted for a line -voltage track lighting integral current limiter, or for a supplementary overcurrent protection panel used to energize only line -voltage track lighting, to be recognized for compliance. ❑ Field Inspector V NRCI-LTI-04-E - Must be submitted for two interlocked systems serving an auditorium, a convention center, a conference room, a multipurpose room, or a theater to be recognized for compliance. ❑ Field Inspector. _ ® NRCI-LTI-05-E - Must be submitted for a Power Adjustment Factor (PAF) to be recognized for compliance. ❑ Field Inspector NRCI-LTI-06-E - Must be submitted for additional wattage installed in a video conferencing studio to be recognized for compliance. ❑ Field Inspector Declaration of Required Certificates of Acceptance — Declare by checking all of the Certificates of Acceptance that will be submitted. (Retain copies and verify forms are completed and signed.) YES- NO Form/Title NRCA-LTI-02-A - Must be submitted for occupancy sensors and automatic time switch controls. ❑ Field Inspector NRCA-LTI-03-A - Must be submitted for automatic daylight controls. ❑ Field Inspector NRCA-LTI-04-A - Must be submitted for demand responsive lighting controls. ❑ Field Inspector CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA INDOOR LIGHTING CEC-NRCC-LTI-01-E Revised 06/14 CERTIFICATE OF COMPLIANCE — USER INSTRUCTIONS Indoor Lighting Project Name: IN -N -OUT La'Quinta k,/ALIr VRIVIH CIVCRUT VVIVIIVII.J IUN NRCC-LTI-01-E (Page 3 of 5) Date Prepared: 7/20/2015 A separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces. Installed lighting Power listed on this Lighting Schedule is only for: ® CONDITIONED SPACE ❑ UNCONDITIONED SPACE A. INDOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY CHECKLIST ❑ The actual indoor lighting power listed on this page and on the next page includes all installed permanent and planned portable lighting systems. ❑ When Complete Building Method is used for compliance, list each different type of luminaire on separate lines. ❑ When Area Category Method or Tailored Method is used for compliance, list each different type of luminaire by each different function area on separate lines ❑ Also include track lighting in schedule, and submit the track lighting compliance form (NRCC-LTI-OS-E) when line -voltage track lighting is installed. B. Installed Portable Luminaires in Offices — Exception to Section 140.6(a) ❑ 'This section shall be filled out ONLY for portable luminaires in offices (As defined in §100.1). All other planned portable luminaires shall be documented on next page of this compliance form. ❑ This section is used to determine if greater than 0.3 watts of portable lighting is planned for any office ❑ Fill out a separate line for each different office. Small offices that are typical (having the same general and portable lighting) may be grouped together. This allowance shall not be traded between offices having different lighting systems. Office Portable Luminaire Office Installed Portable Luminaire Watts Per Square Office Location Field Schedule. Foot Inspector A B C D E F G H I J Installed r Z ° 3. 3 portable 0 v+ s Watts If F s 0.3, Identify Office area in which luminaire N v per enter zero; Complete Luminaire Description ° v n, !� watts in this ° M square E x G these portable luminaires are n W. (i.e., LED, under cabinet, furniture mounted Watts per M o — office m ; :° foot if F > 0.3, installed direct/indirect) Luminaire (B x C) (D / E) (F-0.3) ❑ ❑ 1:1❑ ❑ ❑ ❑ ❑ ❑ ❑ Enter sum total of all pages into NRCC- Total installed portable luminaire watts that are greater than 0.3 watts per square foot per office: LTI-OI-E; Page 1 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA INDOOR LIGHTING CEC-NRCC-LTI-01-E Revised 06/14 CERTIFICATE OF COMPLIANCE — USER INSTRUCTIONS Indoor Lighting Project Name: IN -N -OUT La Quinta Date Prepared: 7/20/2015 ENERGY COMMISSION NRCC-LTI-01-E (Page 4 of 5) A separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces. Installed Lighting Power listed on this Lighting Schedule is only for: ❑ CONDITIONED SPACE ❑ UNCONDITIONED SPACE C. INDOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY CHECKLIST Luminaire Schedule Installed Watts ' Location Field Inspector' A B C D E F G H How wattage was determined lu Q o R Complete Luminaire Description3. o^ 4 c 3 z s 5 R (i.e, 3 lamp fluorescent troffer, a z v o 0 01. cr x m a Primary Function area in which z — F32T8, one dimmable electronic ballast) `� m ; = `� `�° - a C- these luminaires are installed Pass Fail A NA- 2 x 4 Rec Troffer Lithonia 2GTL 4 LED 71.0 ❑ 0 9 639 Kitchen, Food Preparation ❑ ❑ B, BEM H.E. WILLIAMS #12 -4 -L52/840 -S 59.0 ❑ 0 11 649 Dining ❑ ❑ C COLUMBIA LIGHTING #LCL -8 -40 -ML -ED -U 96.0 ❑ 0 8 768 Kitchen, Food Preparation ❑ ❑ D, D1 N D, 1 X 4 RECESSED, Lithonia TL4 43L LE 46.0 ❑ 0 11 506 Corridor/Restroom/Support ❑ ❑ E N E-1 x 4 Surf Mtd Lithonia LBL4LP840 LED 50.0 ❑ 0 5 250 Kitchen, Food Preparation ❑ ❑ H N H - Hi -Lite Mfg. Co.SP-H-260-1 S LED 12.0 ❑ 0 10 120 Dining ❑ ❑ K N K RECESS FLUOR, DNLT, EliteB61C-LED 14.0 ❑ 0 30 420 Dining ❑ ❑ P N P - Lithonia ZL1 N 4' Strip LED 31.0 ❑ 0 5 155 Dining ❑ ❑ W NW - Lithonia FEM8 LED 9L 1122.0 1 ❑ 0 11 122 Kitchen, Food Preparation ❑ ❑ INSTALLED WATTS PAGE TOTAL: 3,629 Enter sum total of all pages into NRCC-LTI-01-E; Page 2 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA INDOOR LIGHTING CEC-NRCC-LTI-01-E Revised 06/14 CERTIFICATE OF COMPLIANCE — USER INSTRUCTIONS Indoor Lighting Project Name: IN -N -OUT La Quinta CALIFORNIA ENERGY COMMISSION NRCC-LTI-01-E (Page 4 of 5) Date Prepared: 7/20/2015 A separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces. Installed Lighting Power listed on this Lighting Schedule is only for: ❑ CONDITIONED SPACE ❑ UNCONDITIONED SPACE C. INDOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY CHECKLIST r Luminaire Schedule Installed Watts Location Field Inspector 1 A B C D E F G H How wattage was determined : .a 0 o o A Complete Luminaire Description C o^ 3 z s M v F- R (i.e, 3 lamp fluorescent troffer, v 3 O w a Z b w s- c o. 3 n v �. x w v Primary Function area in which z— F32T8, one dimmable electronic. ballast) IR 00 � = E; `C°`� CL these luminaires are installed Pass Fail C, Cl N C Tandem Strip Lithonia TZL1N L96 LED 84.0 ❑ ❑ 4 336 Comp Bldg Restaurant ❑ ❑ D, D1 N D, 1 X 4 RECESSED, Lithonia TL4 43L LE 46.0 ❑ F41 1 46 Comp Bldg Restaurant ❑ ❑ E N E-1 x 4 Surf Mtd Lithonia LBL4LP840 LED 50.0 ❑ ® 2 100 Comp Bldg Restaurant ❑ ❑ ❑ ❑ ❑ .❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ INSTALLED WATTS PAGE TOTAL: 482 Enter sum total of all pages into NRCC-LTI-OS-E; Page 2 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA INDOOR LIGHTING CEC-NRCC-LTI-01-E Revised 06114 CALIFORNIA ENERGY COMMISSION CERTIFICATE OF.COMPLIANCE — USER INSTRUCTIONS NRCC-LTI-01-E Indoor Lighting (Page 5 of 5) Project Name: IN -N -OUT La Quinta Date Prepared: 7/20/2015 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Jeff Pollock Documentation Author Signature: Company: TECHLOGIC ENERGY CONSULTING signature Date: 7/20/2015 Address: 23890 Copper Hill Drive, Suite 320 CEA/HERS Certification Identification (if applicable): CALl L/V City/state/zip: Valencia, CA 91354. Phone. 661.714.0133 California Association of Building Energy Consultants RESPONSIBLE PERSON'S DECLARATION STATEMENT CEA# NR08-05--S39 I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: John Gholmleh LIC# E17044 Responsible Designer Signature: Company: Lippe and Associates Date signed: Za Address: 15950 Midway Road License: E17044 City/state/zip: Addison, TX 75001 Phone. 972-387-3500 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA INDOOR LIGHTING — LIGHTING CONTROLS MV_'. GEG-NRGG-LI I -02-E (Revised 06/14) CALIFORNIA ENERGY COMMISSION ""?:""' CERTIFICATE OF COMPLIANCE NRCC-LTI-02-E Indoor Lighting - Lighting Controls (Page 1 of 3) Project Name: IN-N-OUT La Quinta Date Prepared: 7/20/2015, The NRCC-LTI-02-E shall be used to document all mandatory and prescriptive lighting controls that are applicable to the project. Mandatory Lighting Control Declaration Statements (Indicate if the measure applies by checking yes or no below.) YES NO Control Requirements Lighting shall be controlled by self-contained lighting control devices which are certified to the Energy Commission according to the Title 20 Appliance Efficiency Regulations in accordance with Section 110.9. Lighting shall be controlled by a lighting control a system or energy management control system in accordance with §110.9. An Installation Certificate shall be submitted in accordance with Section 130.4(b). ® One or more Track Lighting Integral Current Limiters shall be installed which have been certified to the Energy Commission in accordance with §110.9 and v §130.0. Additionally, an Installation Certificate shall be submitted in accordance with Section 130.4(b). t: JA Track Lighting Supplementary Overcurrent Protection Panel shall be installed in accordance with Section 110.9 and Section 130.0. Additionally, an Installation Certificate shall be installed in accordance with Section 130.4(b). JAll lighting controls and equipment shall comply with the applicable requirements in §110.9 and shall be installed in accordance with the manufacturer's instructions in accordance with Section 130.1. JAll luminaires shall be functionally controlled with manually switched ON and OFF lighting controls in accordance with Section 130.1(a). General lighting shall be separately controlled from all other lighting systems in an area. Floor and wall display, window display, case display, ornamental, and special effects lighting shall each be separately controlled on circuits that are 20 amps or less. When track lighting is used, general, display, ornamental, and special effects lighting shall each be separately controlled; in accordance with Section 130.1(a)4. JThe general lighting of any enclosed area 100 square feet or larger, with a connected lighting load that exceeds 0.5 watts per square foot shall meet the multi-level lighting control requirements in accordance with Section 130.1(b). J All installed indoor lighting shall be equipped with controls that meet the applicable Shut -OFF control requirements in Section 130.1(c). Lighting in all Daylit Zones shall be controlled in accordance with the requirements in Section 130.1(d) and daylit zones are shown on the plans. ` Lighting power in buildings larger than 10,000 square feet shall be capable of being automatically reduced in response to a Demand Responsive Signal in accordance with Section 130.1(e). Before an occupancy permit is granted for a newly constructed building or area, or a new lighting system serving a building, area, or site is operated for r normal use, indoor lighting controls serving the building, area, or site shall be certified as meeting the Acceptance Requirements for Code Compliance in accordance with Section 130.4.(a). The controls required to meet the Acceptance Requirements include automatic daylight controls, automatic shut -OFF controls, and demand responsive controls. CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA INDOOR LIGHTING — LIGHTING CONTROLS A", 440 Vii. 'EC -NRCC-LTI-02-E (Revised 06/14) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-02-E Indoor Lighting - Lighting Controls (Page 2 of 3) `fo'e"Name: IN -N -OUT La Quinta Date Prepared: 7/20/2015 A separate document must be filled out for Conditioned and Unconditioned Spaces. This page is used only for the following: IZI CONDITIONED SPACES ❑ UNCONDITIONED SPACES MANDATORY AND PRESCRIPTIVE INDOOR LIGHTING CONTROL SCHEDULE, PAF CALCULATION, and FIELD INSPECTION CHECKLIST PAF Credit Calculation 2 t rl M D (D is • Standards Complying With 1 r � QO 1 G/ l7 D X f(D C R c v D Lighting Control Schedule (✓ all that apply, or enter 'E' if Exempted) A' fl- O T X (o ° o � Q M o A B C D E F G H I J K L M N O Type/ Description of Lighting Control (i.e.: occupancy sensor, # W '0; L471A Location in Building automatic time switch, of o 0 0 0 0 o dimmer, automatic daylight, Units iv : �. etc... ) Dining Dimming - Multiscene ✓ ❑ ❑ Restrooms/Storacle Dimming = Multiscene ✓ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Control Credit PAGE TOTAL (Sum of Column M): 0 IF MULTIPLE PAGES ARE USED, ENTER SUM TOTAL OF Control Credit for all pages HERE (Sum of all Column M): 0 Enter Control Credit total into NRCC-LTI-01-E; Page 1. 1. §130.1(a) = Manual area controls; §130.0(b) = Multi Level; §130.1(c) = Auto Shut -Off; §130.1(d) = Mandatory Daylight; §130.1(e) = Demand Responsive; §140.6(d) _ Additional lighting controls installed to earn a PAF, • §140.6(d) = Prescriptive Secondary Sidelit Daylight Controls. 2. Check Table 140.6-A for correct Factor. PAFs shall not be traded between conditioned and unconditioned spaces. As a condition to earn a PAF, an Installation Certificate is also required to be filled out signed, and submitted. CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA r INDOOR LIGHTING — LIGHTING CONTROLS CEC-NRCC-LTI-02-E Revised 06/14 CALIFORNIA ENERGY COMMISSION �� f CERTIFICATE OF COMPLIANCE NRCC-LTI-02-E Indoor Lighting - Lighting Controls (Page 2 of 3) Project Name: IN-N-OUT La Quinta Date Prepared: 7/20/2015 ' A separate document must be filled out for Conditioned and Unconditioned Spaces. This page is used only for the following: ' I] CONDITIONED SPACES ll UNCONDITIONED SPACES MANDATORY AND PRESCRIPTIVE INDOOR LIGHTING CONTROL SCHEDULE, PAF CALCULATION, and FIELD INSPECTION CHECKLIST PAF Credit Calculation Z t n D _T n Standards Complying With. 1 r p ? o N ("1 ;z Q o NrD Lighting Control Schedule (✓ all that apply, or enter 'E' if Exempted). aQ Q -n = �' n m- A B C D E F G H I J K L M N O Type/ Description of Lighting Control (i.e.: occupancy sensor, # 0 to,to, a; i) A °; Location in Building automatic time switch, of o 0 0 0 0 o dimmer, automatic daylight, Units 2 tt v a m -2 Q etc...) Unconditioned Enclosed Sp 3 Dimming - Multiscene ✓ ❑ ❑ Unconditioned Enclosed Sp Dimming - Multiscene ✓ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ Control Credit PAGE TOTAL (Sum of Column M): 0 IF MULTIPLE PAGES ARE USED, ENTER SUM TOTAL OF Control Credit for all pages HERE (Sum of all Column M): 0 Enter Control Credit total into NRCC-LTI-01-E; Page 1. 1. §130.1(a) = Manual area controls; §130.0(b) = Multi Level; §130.1(c) = Auto Shut -Off; §130.1(d) = Mandatory Daylight, §130.1(e) = Demand Responsive; §140.6(d) = Additional lighting controls installed to earn a PAF- §140.6(d) = Prescriptive Secondary Sidelit Daylight Controls. 2. Check Table 140.6-A for correct Factor. PAFs shall not be traded between conditioned and unconditioned spaces. As a condition to earn a PAF, an Installation Certificate is also required to be filled out, signed, and submitted. CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA INDOOR LIGHTING - LIGHTING CONTROLS CERTIFICATE OF COMPLIANCE NRCC-LTI-02-E Indoor Lighting - Lighting Controls (Page 3 of 3) Project Name: IN -N -OUT La Quinta Date Prepared: 7/20/2015 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Jeff Pollock Documentation Author Signature: Company: TECHLOGIC ENERGY CONSULTING Signature Date: g 7/20/2015 Address: 23$90 Copper HIII Drive, Suite 320 CEA/HERSCertiflcationldentification(ifapplicablel: <.J�LV City/state/zip: Valencia, CA 91354 Phone: 661.714.0133 California Assotiationof RESPONSIBLE PERSON'S DECLARATION STATEMENT Building Energy Consultants CfA# NR08.05-533 I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: John Gholrnieh LIC# E17044 Responsible Designer Signature: `O Company: Lippe and Associates Date Signed: Address: 15950 Midway Road License: q- 4 1 V City/State/Zip: Addison, TX 75001 Phone: CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA INDOOR LIGHTING POWER ALLOWANCE Iril,'T,'.: 'EC -NRCC-LTI-03-E (Revised 06/14) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-03-E Certificate of Compliance - Indoor Lighting Power Allowance (Page 1 of 4) Project Name: IN-N-OUT La Quinta - Date Prepared: 7/20/2015 ALLOWED LIGHTING POWER A separate page must be filled out for Conditioned and Unconditioned Spaces. This page is only for: 0 CONDITIONED spaces ❑ UNCONDITIONED spaces A. SUMMARY TOTALS OF LIGHTING POWER ALLOWANCES ❑ If using Complete Building Method for compliance, use only the total in column (a) as total allowed building watts. ❑ If using Area Category Method, Tailored Method, or a combination of Area Category and Tailored Method for compliance, use only the total in column (b) as the'total allowed building watts (a) 1. Complete Building Method Allowed Watts. Documented in section B of NRCC-LTI-03-E (below on this page) 4,499 2. Area Category Method Allowed Watts. Documented in section C-1 of NRCC-LTI-03-E (below on this page) 3. Tailored Method Allowed Watts. Documented in section A of NRCC-LTI-04-E TOTAL ALLOWED BUILDING WATTS. Enter number into correct cell on NRCC-LTI-01, Page 2, Row 1 4,499 Check here if building contains both conditioned and unconditioned areas. (b) B. COMPLETE BUILDING METHOD LIGHTING POWER ALLOWANCE A B C D TYPE OF BUILDING (From §140.6 Table 140.6-B) WATTS PER (ft) X COMPLETE BLDG. AREA = ALLOWED WATTS Comp Bldg Restaurant 1.20 3,750 4,499 Total Area: Total Watts. Enter Total Watts into section A, row 1 (Above on this page) C -1 AREA CATEGORY METHOD TOTAL LIGHTING POWER ALLOWANCES (C-2 plus C-3) Watts Total from section C-2 Total from section C-3 Total Watts. Enter Total Watts into section A, row 2 (Above on this page) CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA INDOOR LIGHTING POWER ALLOWANCE 'EC -NRCC-LTI-03-E (Revised 06/14) CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTI-03-E Certificate of Compliance - Indoor Lighting Power Allowance (Page 1 of 4) Project Name: IN -N -OUT LaQuinta Date Prepared: 7/20/2015 ALLOWED LIGHTING POWER A separate page must be filled out for Conditioned and Unconditioned Spaces. This page is only for: ❑ - CONDITIONED spaces ❑ UNCONDITIONED spaces A. SUMMARY TOTALS OF LIGHTING POWER ALLOWANCES - ❑ If using Complete Building Method for compliance, use only the total in column (a) as total allowed building watts. ❑ If using Area Category Method, Tailored Method, or a combination of Area Category and Tailored Method for compliance, use only the total in column (b) as the total allowed building watts (a) I I (b) 1. Complete Building Method Allowed Watts. Documented in section B of NRCC-LTI-03-E (below on this page) 1,212 2. Area Category Method Allowed Watts. Documented in section C-1 of NRCC-LTI-03-E (below on this page) 3. Tailored Method Allowed Watts. Documented in section A of NRCC-LTI-04-E TOTAL ALLOWED BUILDING WATTS. Enter number into correct cell on NRCC-LTI-01, Page 2, Row 1 1,212 C El Check here if building contains both conditioned and unconditioned areas. B. COMPLETE BUILDING METHOD LIGHTING POWER ALLOWANCE A B C D TYPE OF BUILDING (From §140.6 Table 140.6-B) WATTS PER (ft2) X COMPLETE BLDG. AREA = ALLOWED WATTS Comp Bldg Restaurant 1.20 1,010 1,212 Total Area: Total Watts. Enter Total Watts into section A, row 1 (Above on this page) C -1 AREA CATEGORY METHOD TOTAL LIGHTING POWER ALLOWANCES (C-2 plus C-3) Watts Total from section C-2 Total from section C-3 Total Watts. Enter Total Watts into section A, row 2 (Above on this page) CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA INDOOR LIGHTING POWER ALLOWANCE CEC-NRCC-LTI-03-E Revised 06/14 CALIFORNIA ENERGY COMMISSION'=" CERTIFICATE OF COMPLIANCE NRCC-LTI-03-E Certificate of Compliance - Indoor Lighting Power Allowance (Page 4 of 4) Project Name` IN -N -OUT La Quinta - Date Prepared: 7/20/2015 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Jeff PollockDocumentation Author Signature: ' Company: TECHLOGIC ENERGY CONSULTING signature Date: 7/20/2015 �- r Address: Copper Hill Drive, Suite.320 CEA/ HERS Certification Identification (if applicable):23890 CAJJEC City/State/Zip: Valencia, CA: 91354 Phone. 661.714.0133 California Association of RESPONSIBLE PERSON'S DECLARATION STATEMENT Building Energy Consultants CfA# NR08-05-539 ' .4 I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: John Gholmleh LIC# E17044 Responsible Designer Signature: ` �O Company: Lippe and Associates Date Signed: Address: 15950 Midway Road License: `^ 1 City/state/zip: Addison, TX 75001 Phone: CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA OUTDOOR LIGHTING CEC-NRCC-LTO-01-E Revised 06/14 CERTIFICATE OF COMPLIANCE Outdoor Lighting Pro;ectName: IN -N -OUT La Quinta Date Prepared: 7/20/2015 N RCC -LTO -01-E (Page 1 of 4) I Project Address: 78611 Highway 111 La Quinta, CA 92253 Total Illuminated Hardscape Area 54,412 General Information Phase of Construction: ® New Construction ❑ Addition ❑ Alteration Outdoor Lighting Zone (OLZ) ❑ OLZ-1 ❑ OLZ-2®❑ OLZ-3 ❑ OLZ-4 I have confirmed with the AH1 which OLZ applies to this site. For default lighting zone designations, see Title 24 Part 6, §10-114 LIGHTING COMPLIANCE DOCUMENTS (check box for each document included) For detailed instructions on the use of this and all Energy Efficiency Standards compliance documents, refer to the Nonresidential Manual published by the California Energy Commission. NRCC-LTO-01-E Certificate of Compliance NRCC-LTO-02-E Outdoor Lighting Controls Certificate of Compliance NRCC-LTO-03-E Outdoor Lighting Power Allowance Certificate of Compliance Summary of Allowed Outdoor Lighting Power Watts 1. Sum Total ALLOWED Outdoor Lighting Wattage from NRCC-LTO-03-E, page 1 = 7,717 Complies ONLY if Installed <_ Allowed 2. Sum Total INSTALLED Outdoor lighting Wattage from NRCC-LTO-OS-E, page 3 2,520 Declaration of Required Installation Certificates — Declare by checking all Installation Certificates that will be submitted. (Retain copies and verify forms are completed and signed.) 0 NRCI-LTO-01-E - Must be submitted for all buildings ❑ Field Inspector 0 NRCI-LTO-02-E - Must be submitted for a lighting control system, or for an ❑ Field Inspector Energy Management Control System (EMCS), to be recognized for compliance. Declaration of Required Certificates of Acceptance — Declare by checking all of the Certificates of Acceptance that will be submitted. (Retain copies and verify forms are completed and signed.) O NRCA-LTO-02-A - Must be submitted for outdoor lighting controls. 10 Field Inspector CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA OUTDOOR LIGHTING � CEC-NRCC-LTO-01-E Revised 06/14 CALIFORNIA ENERGY COMMISSIONk '10!i CERTIFICATE OF COMPLIANCE NRCC-LTO-01-E Outdoor Lighting (Page 2 of 4) Pro;ectName: IN -N -01 -IT La Quinta Date Prepared: 7/20/2015 Schedule of luminaires exempt from the outdoor lighting power requirements in §140.7 Name or Symbol Description of exempt luminaire in accordance with the exemptions Schedule of luminaires exempt from the cutoff requirements in §130.2(b) Name or Symbol Description of exempt luminaire in accordance with the exemptions Schedule of luminaires exempt from the outdoor lighting control requirements in §130.2(c) Name or Symbol Description of exempt luminaire in accordance with the exemptions CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA OUTDOOR LIGHTING CERTIFICATE OF COMPLIANCE NRCC-LTO-01-E Outdoor Lighting (Page 3 of 4) Prviect Name: IN -N -OUT La Quinta Date Prepared: 7/20/2015 A. OUTDOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY CHECKLIST Luminaire Schedule Installed Watts r Location Cutoff Field Inspector A B C D E F G H I Name or3 Ilene Tag Complete Luminaire Description ° of _. a rD m How wattage was determined �. 3 v a r� v ° Q -4 3 — x m " ^ ? c, Q d Primary Function area in which these luminaires are installed � w' o, a ^ _ a w ^ ii n .� ^ w 0 3 p o aof z 0 9 00 C = °° o M N M-Maxilume HH10-LED 6000L 80.0 ❑ ® 5 400 Dining ❑• ❑ S NS - Lithonia FEM8 LED 9L 122.0 ❑ ® 3 366 Non Sales Canopy ❑ " ❑ M N M-Maxilume HH10-LED 6000L 80.0 ❑ ❑ 5 400 Sales Canopy ❑ ❑ M N M-Maxilume HH10-LED 6000L 80.0 ❑ El 2 160 Other Entrance/Exit ❑ ❑ BC NBC - Amerilux E2.9RD-G2 20.0 ❑ El 4 80 Other Entrance/Exit ❑ , ❑ M N M-Maxilume HH10-LED 6000L 80.0 ❑ ❑ 2 160 Non Sales Canopy ❑ ❑ SA1 N-SA1 iGuzzini- U.F.O.Optismart 1.131-09 54.4 ❑ ❑ 5 272 Automotive Hardscape ❑ ❑ SA2 N-SA2 iGuzzini -U.F.O. Optismart I.B1-09 108.8 ❑ El 5 544 Automotive Hardscape ❑ ❑ D1 N D, 1 X 4 RECESSED, Lithonia TL4 43L 46.0 ❑ ❑ 3 138 Non Sales Canopy ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ 1 ❑ INSTALLED WATTS PAGE TOTAL: 2,520 Enter sum total of all pages (Sum Total INSTALLED Outdoor lighting wattage) into NRCC-LTO-01-E; Page 1 2,520 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2013 STATE OF CALIFORNIA OUTDOOR LIGHTING CEC-NRCC-LTO-01-E Revised 06/14 CALIFORNIA ENERGY COMMISSION " CERTIFICATE OF COMPLIANCE NRCC-LTO-01-E Outdoor Lighting (Page 4 of 4) .Project Name: IN -N -OUT La Quinta - - -Date Prepared: 7/20/2015 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Jeff POIIOCk Documentation Author Signature: t Company: TECHLOGIC ENERGY CONSULTIN - Signature Date: 7/20/2015 Address: - 23890 Copper HIII Drive, Suite 320 CEA/ HERS Certification Identification (if applicable): - i T 77 .[K/L1H /lJ CA City/state/zip: Valencia, CA 91354 Phone: 661.714.0133 California Association of Nuilding Energy Consultants RESPONSIBLE PERSON'S DECLARATION STATEMENT CEA# NR©3-05-539 I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. 'The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,- ocuments,worksheets, worksheets,calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: John GhOlmleh LIC# E17044 Responsible Designer Signature: Company: Lippe and Associates Date Signed: (7 r� O \-S (— C Address: 15950 Midway Road License: E17044 City/State/Zip: Addison, TX 75001 one: Ph 972-387-3500 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2013 STATE OF CALIFORNIA ' OUTDOOR LIGHTING CONTROLS CEC-NRCC-LTO-02-E (Revised 06/14) CALIFORNIA ENERGY COMMISSION `M' ' CERTIFICATE OF COMPLIANCE NRCC-LTO-02-E Outdoor Lighting Controls (Page 1 of 3) Project Name: IN -N -OUT La Quinta Date Prepared: 7/20/2015 The NRCC-LTO-02-E shall be used to document all mandatory outdoor lighting controls that are applicable to the project. Mandatory Outdoor Lighting Control Declaration Statements Check all that apply: • Lighting shall be controlled by self-contained lighting control devices which are certified to the Energy Commission according to the Title 20 Appliance Efficiency Regulations in accordance with §110.9. 0 Lighting shall be controlled by a lighting control system'or energy management control system in accordance with §110.9. An Installation Certificate shall be submitted in accordance with §130.4(b). 0 All lighting controls and equipment shall comply with the applicable requirements in §110.9 and shall be installed in accordance with the manufacturer's instructions in accordance with §130.1 ❑ Part -Night Outdoor Lighting Controls, as defined in Section 100.1, shall meet the requirements in Section 110.9(b)5 ' ❑ All outdoor incandescent luminaires rated over 100 watts, determined in accordance with Section 130.0(c), shall be controlled by a motion sensor. ❑ All outdoor luminaires rated for use with lamps greater than 150 lamp watts, determined in accordance with Section 130.0(c), shall comply with Backlight, Uplight, and Glare (collectively referred to as "BUG") in accordance with Section 130.2(b) - 0 All installed outdoor lighting shall be controlled by a photocontrol or outdoor astronomical time -switch control in accordance with Section 130.2(c)1 0 All installed outdoor lighting shall be circuited and independently controlled from other electrical loads by an automatic scheduling control in accordance with Section 130.2(c)2 IZI All installed outdoor lighting, where the bottom of the luminaire is mounted 24 feet or less above the ground, shall be controlled with automatic lighting controls in accordance with Section 130.2(c)3 ❑ For Outdoor Sales Frontage, Outdoor Sales Lots, and Outdoor Sales Canopies lighting, an automatic lighting control in accordance with Section 130.2(c)4 ® For Building Facade, Ornamental Hardscape and Outdoor Dining lighting, an automatic lighting control in accordance with Section 130.2(c)5 0 Before an occupancy permit is granted for a.newly constructed building or area, or a new lighting system serving a building, area, or site is operated for normal use, indoor lighting controls serving the building, area, or site shall be certified as meeting the Acceptance Requirements for Code Compliance in accordance with §130.4.(a). Outdoor lighting controls shall comply with the applicable requirements of Section 130.2(c) and Reference Nonresidential Appendix NA7.8 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA r _ OUTDOOR LIGHTING CONTROLS . GEC-NRCC-LTO-02-E Revised 06/14 CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTO-02-E Outdoor Lighting Controls (Page 2 of 3) Project Name: IN -N -OUT La Quints Date Prepared: 7/20/2015 MANDATORY OUTDOOR LIGHTING CONTROL SCHEDULE and FIELD INSPECTION CHECKLIST w \ _-n h F 1 Standards Complying With z D Outdoor Lighting Control Schedule (✓ all that apply, or enter 'E' if Exempted) v Q n n O (D A B C D E F G H I N O Type/ Description of Lighting Control (i.e. motion sensor, photocontrol, outdoor # to, W' to, °' i°' to, Location and Application ofastronomical time -switch control, of o 0 0 0 0 0 Luminaires being controlled N N N N N N n centralized time -based zone lighting Units control) '-' r N W A . Ln Building Entrance Photo -Control / Central Time Clock Zonal N/A y y ❑ ❑ Sales Canopy Photo -Control / Central Time Clock Zonal N/A y y y ❑ ❑ Non -Sales Canopy Photo -Control / Central Time Clock Zonal N/A y y ❑ ❑ Outdoor Dining Photo -Control / Central Time Clock Zonal N/A y y y ❑ ❑ Hardsca a Photo -Control/ Central Time Clock Zonal N/A y y y ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA OUTDOOR LIGHTING CONTROLS CEC-NRCC-LTO-02-E Revised 06/14 CALIFORNIA ENERGY COMMISSION '`Lt=fir CERTIFICATE OF COMPLIANCE _ NRCC-LTO-02-E Outdoor Lighting Controls (Page 3 of 3) Project Name: IN -N -OUT La Quinta Date Prepared: 7/20/2015 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Jeff Pollock Documentation Author Signature: Company' TECHLOGIC ENERGY CONSULTING signature Date: 7/20/2015 r- Address: 23$90 Copper HIII Drive, Suite 320 CEA/HERS Certification Identification (if applicable): R 77 CAlal City/State/Zip: Valencia, CA 91354 phone: 661.714.0133 Ca/ifornraAssociatiionof . RESPONSIBLE PERSON'S DECLARATION STATEMENT Building Energy Consultznts CFA# /VR08-05-539 I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. " 2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. Ay 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the + enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: John Gholrnieh LIC# E17044 Responsible Designer Signature: Company: Lippe and Associates Date Signed: �• rz-c�-' Zo Address: 15950 Midway Road License: `^ O ` City/State/Zip: Addison, TX 75001 Phone: CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA OUTDOOR LIGHTING POWER ALLOWANCES CERTIFICATE OF COMPLIANCE NRCC-LTO-03-E Outdoor Lighting Power Allowances (Page 1 of 4) Project Name: IN -N -OUT La Quinta - Date Prepared: 7/20/2015 A. OUTDOOR LIGHTING POWER ALLOWANCE SUMMARY Area Wattage All (AWA) 1. General Hardscape Lighting Power Allowance (Site Total from Section B of NRCC-LTO-03-E) 1. 6,437 2. Additional Specific "use it or lose it" Lighting Power Allowances listed in each of these cells shall be identical to total allowed watts A B determined in Section C-1 to C-4 of NRCC-LTO-03-E. TT D PER APPLICATION PER UNIT LENGTH PER HARDSCAPE AREA PER SPECIFIC AREA F G from Section C-1 (SALES FRONTAGE) (ORNAMENTAL LIGHTING) from Section C-4. I from Section C-2 from Section C-3 AWA Per Square Foot 90 + 0 + 0 + 11191 = 2. 1,281 3. Sum Total ALLOWED Outdoor Lighting Wattage (add rows 1 and 2) 3. 7,717 B. GENERAL HARDSCAPE LIGHTING POWER ALLOWANCE FROM TABLE 140.7-A Area Wattage All (AWA) Linear Wattage Allowance (LWA) Initial Wattage Allowance (IWA) Total General Hardscape Lighting Allowance A B C TT D E F G H I Illuminated Name of area Hardscape Area AWA Per Square Foot AWA (B x C) Perimeter Length of General Hardscape LPA per LWA Linear Foot (E x F) 0.600 770 IWA (Watts) D + G + H Driveway & Parking 54,412 0.090 4,897 1,283 770 6,437 TOTAL 6,437 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE OF CALIFORNIA ea OUTDOOR LIGHTING POWER ALLOWANCES l _ - 'EC-NRCC-LTO-03-E (Revised 06/14) CALIFORNIA ENERGY COMMISSION 11—&., fir CERTIFICATE OF COMPLIANCE NRCC-LTO-03-E Outdoor Lighting Power Allowances (Page 2 of 4) Project Name: IN -N -OUT La Quinta Date prepared: 7/20/2015 C. ADDITIONAL "USE IT OR LOSE IT" OUTDOOR LIGHTING POWER ALLOWANCES FOR SPECIFIC APPLICATIONS ❑ The additional specific outdoor lighting power allowance shall be the smaller of the allowed lighting power or the actual lighting power used. ❑ Use Outdoor Lighting Zone (OLZ) that is documented on page 1 of NRCC-LTO-01-E to calculate the specific wattage allowances. C-1. WATTAGE ALLOWANCE PER APPLICATION —Table 140.7-13 ❑ Available only for qualifying locations, which include Building Entrances or Exits; Primary Entrances to Senior Care Facilities, Police Stations, Hospitals, Fire Stations, and Emergency Vehicle Facilities; Drive Up Windows; Vehicle Service Station Uncovered Fuel Dispenser ❑ If more than one luminaire type is used per location, use multiple rows for that location A B I C D E F G H I J Name of Location for which allowance is claimed ALLOTTED WATTS DESIGN WATTS Number of qualifying locations Wattage Allowance per qualifying location Allotted Watts (B x C) Luminaire Code or Symbol Luminaire Luminaire Description Quantity Watts per luminaire Design Watts (G x H) Allowed Watts (smaller of D or 1) -Building Exits 1 90 90 M N M-Maxilume HH10-LED 6001 2 80.0 160 -90 BC NBC - Amerilux E2.9RD-G2 4 20.0 80 Sum total allowance per application on this site: g0 C-2. WATTAGE ALLOWANCE PER UNIT LENGTH (Sales Frontage) from Table 140.7-8 ❑ If more than one luminaire type is used per location, use multiple rows for that location A B I C D E F G H I J Name of Location for which allowance is claimed ALLOTTED WATTS DESIGN WATTS Wattage Allotted Linear feet of Allowance per Watts Sales Frontage linear foot (B x C) Luminaire Code or Symbol Luminaire Description Luminaire Watts per Design Watts Quantity luminaire (G x H) Allowed Watts (smaller of D or 1) Sum total allowance for sales frontage on the site:. 0 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 STATE'OF CALIFORNIA OUTDOOR LIGHTING POWER ALLOWANCES CEC-NRCC-LTO-03-'E (Revised 06/14) CALIFORNIA ENERGY COMMISSION " d°' CERTIFICATE OF COMPLIANCE NRCC-LTO-03-E Outdoor Lighting Power Allowances (Page 3 of 4) Project Name: IN -N -OUT La Quinta oacerreparea: 7/20/2015 C-3. WATTAGE ALLOWANCE PER SQUARE FOOT OF HARDSCAPE AREA (Ornamental Lighting) — Table 140.7-13 ❑ Allowance for the total site illuminated hardscape area. Luminaires qualifying for this allowance shall be rated for 100 watts or less as determined in accordance with Section 130.0(c), and shall be post -top luminaires, lanterns, pendant luminaires, or chandeliers. ❑ If more than one luminaire type is used per location, use multiple rows for that location A B C D f , F G H I J Name of area for which ornamental allowance is claimed ALLOTTED WATTS DESIGN WATTS Wattage Allotted Square feet of Allowance per Watts Hardscape square foot (B x C) Luminaire Code or Symbol Luminaire Watts per Design Watts Luminaire Description Quantity luminaire (G x H) Allowed Watts (smaller of D or 1) Sum total allowance for ornamental lighting on the site:. 0 C-4. WATTAGE ALLOWANCE PER SQUARE FOOT OF SPECIFIC AREA -Table 140.7-13 ❑ Allowances for Building Facades; Outdoor Sales Lots; Vehicle Service Station Hardscape; Vehicle Service Station Canopies; Sales Canopies; Non -sales Canopies; Guard Stations; Student Pick-up/Drop-off zone: Outdoor Dining; Special Security Lighting for Retail Parking and Pedestrian Hardscape. ❑ If more than one luminaire type is used per location, use multiple rows for that location A B I C D E F G H I J Name of Location for which allowance is claimed ALLOTTED WATTS DESIGN WATTS Wattage Allotted Luminaire Illuminated Area Allowance per Watts Code or Luminaire Watts per Design Watts Allowed Watts of Application square foot (B x C) Symbol Luminaire Description Quantity luminaire (G x H) (smaller of D or I) Outdoor Dining Can 720 0.240 173 M N M-Maxilume HH10-LED 6C 5 80.0 400 173 Non Sales Canopy 1 1,208 0.408 493 S NS - Lithonia FEM8 LED 9L 3 122.0 366 366 Sales Canopie Driv( 1,060 0.908 962 M N M-Maxilume HH10-LED 6( 5 80.0 400 400 Non -sales Cano ie 339 0.408 138 M N M-Maxilume HH10-LED 60 2 80.0 160 138 Trash Enclosure 278 0.408 113 D1 N D, 1 X 4 RECESSED, Lith 3 46.0 138 113 Sum total allowance for specific area on the site:1 1,191 CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 1* STATE OF CALIFORNIA OUTDOOR LIGHTING POWER ALLOWANCES CEC-NRCC-LTO-03-E Revised 06/14 CALIFORNIA ENERGY COMMISSION CERTIFICATE OF COMPLIANCE NRCC-LTO-03-E Outdoor Lighting Power Allowances (Page 4 of 4) Project Name: IN -N -OUT La Quinta Date Prepared: 7/20/2015 DOCUMENTATION AUTHOR'S DECLARATION STATEMENT 1. 1 certify that this Certificate of Compliance documentation is accurate and complete. Documentation Author Name: Jeff Pollock Documentation Author Signature: /- - Company: - TECHLOGIC ENERGY CONSULTING Signature Date: " g 7/20/2015rr Address: 23890 Copper Hill Drive, Suite 320 CEA/ HERS Certification Identification (if applicable): A�� �y /CJ City/State/Zip: Valencia, CA 91354 Phone: 661.714.0133 - ....'," California Association of RESPONSIBLE PERSON'S DECLARATION STATEMENT Co Energy ns Consultants Building - C64# NROS-O5-539 I certify the following under penalty of perjury, under the laws of the State of California: 1. The information provided on this Certificate of Compliance is true and correct. 2. 1 am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer). 3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations. 4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance . documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application. 5. 1 will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy. Responsible Designer Name: John Gholmleh LIC# E17044 Responsible Designer Signature: 1 Company: Lippe and Associates Date Signed: ZGt\, �) S Address: 15950 Midway Road License: t V \f City/state/zip: Addison, TX 75001 Phone: CA Building Energy Efficiency Standards - 2013 Nonresidential Compliance June 2014 H