Loading...
9804-031 (CSST) HVAC Equipment Specs1 1 1 1 1 PROJECT SUBMITTAL PACKAGE - 3rd CITY OF LA QUINTA BUILDING DEPARTMENT PLAN CHECK NO. 9804-031 Project Title: SOUTHLAND LAPIS FUEL SYSTEMS LLC. MOBIL OF LA QUINTA - LOT I 79-513 Highway 111 and Dune Palms Road La Quinta, California LO -1m, L BUILDING STRUCTURAL CALCULATIONS IL CANOPY STRUCTURAL CALCULATIONS M. TITLE 24 CALCULATIONS 1V. HVAC V. PROJECT SOILS GARY ENGI 4901 Morena B San Diego, ( (619) (619) 4 PORT 14' �' - T 0 Y E.7 BUILDING & SP, -FE Y DEPARIHIMIENT COODI TIOINIALLY AC(-`,rE-rPTED FORR * bpUBJ.-tC,T'TOINS-IP�,LL.C',-I!Oi-�'Az"�IPE,,'4 fitted EPSL'- LAPPLICAB! - CoDt�:s W Suite 304 92117to �18 BY. September 1, 1998 48HJD005-007 ® 48 HJ E/HJ F004-007 Single -Package Rooftop Heating/Cooling Units "A - installation, Start -Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS .................. I INSTALLATION ............................ 1-20 Step 1 — Provide Unit Support .............. I • ROOF CURB • SLAB MOUNT Step 2 — Field Fabricate Ductwork ........... 3 Step 3 — Install External Trap for Condensate Drain ......................... 3 Step 4 — Rig and Place Unit ................. 3 • POSITIONING Step 5 — Install Flue Hood .................. 4 Step 6 — Install Gas Piping .................. 4 Step 7 — Make Electrical Connections ....... 4 • FIELD POWER SUPPLY • FIELD CONTROL WIRING • HEAT ANTICIPATOR SETTINGS Step 8 — Adjust Factory -Installed Options .... 7 • MOISTUREMISER DEHUMIDIFICATION PACKAGE • APOLLO CONTROL • DISCONNECT SWITCH • OPTIONAL DURABLADE ECONOMIZER • OPTIONAL PARABLADE ECONOMIZER Step 9 — Adjust Evaporator -Fan Speed ...... 14 • BELT DRIVE MOTORS PRE -START-UP ............................. 20 START-UP................................20-23 SERVICE .................................. 24-29 TROUBLESHOOTING ...................... 30-33 START-UP CHECKLIST ..................... CL -I SAFETY CONSIDERATIONS Installation and servicine of air-conditioning equipment can be hazardous due to system pressure and electrical com- ponents. Only trained and qualified service personnel should install, repair. or service air-conditioning equipment. Untrained personnel can perform basic maintenance func- tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per- sonnel. When working on air-conditioning equipment, ob- serve precautions in the literature. tags and labels attached to the unit. and other safety precautions that apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire ex- tinguishers available for all brazing operations. A WARNING Before performing service or maintenance operations on unit. turn off main power switch to unit. Electrical shock could cause personal injury. Disconnect gas piping from unit when leak testing at pressure greater than ' : psig. Pres- sures greater than 1 , psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than l 2 psig, it must be replaced before use. When pressure testing field -supplied gas piping at • • pressures Of' 2 psig or less, a unit connected to such piping must be isolated by manually closing the gas valve(s). INSTALLATION Unit is shipped in the vertical discharge configuration. To convert to horizontal discharge application, remove duct open- ing covers. Using the same screws, install covers on duct openings in basepan of unit with insulation -side down. Seals around openings must be tight. NOTE: Any combination of supply and return ducting is per- missible, i.e., vertical supply combined with horizontal return. Step 1 — Provide Unit Support ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 1. Install insulation, cant strips, roofing felt, and counter flash- ing as shown. Ductwork must be attached to curb, not to the unit. If electric or control power is to be routed through the basepan, attach the accessory thru-the-bottom service con- nections to the basepan in accordance with the accessory in- stallation instructions. Connections must be installed before unit can be set on roof curb. IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket sup- plied with the roof curb as shown in Fig. 1. Improp- erly applied gasket can result in air leaks and poor unit performance. Curb should be level. Unit leveling tolerances are shown in Fig. 2. This is necessary for unit drain to function prop- erly. Refer to Accessory Roof Curb Installation Instructions for additional information as required. SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser -coil air inlet to prevent grass and foliage from obstructing airflow. NOTE: Horizontal units may be installed on a roof curb if required. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Bookit 14 PC 111 Catalog No. 534-824 Printed in U.S.A. Form 48HJ-12S1 Pg 1 9-95 Replaces: 48HJ-COSI Tab Iia 6a UNIT i I "D" ALT I:n '� 1--7 U116:^ SIZE "8" "C" DRAIN POWER I CONTROL "E" CONNECTOR 46HJ i HOLE t1 ` GAS PKG ACCY � , r 0'-0 7116' II 15" NPT 'h' NPT 15• NPT CRBTMPWROO1AOO 004-007 1.5511' 1-4' 115- It/l 'BOLT NE ADS) A (FIELD SVPLIEW , (ihru-the-Bottom Connections) 'C (551) (406) (45) 1'S' NPT 'h' NPT 15' NPTCRBTMPWROO2Aoo C SCALE 1,4 r-ADWING MATERIAL (FIELD W-100 • (Thru-the-Bottom Connections) C f • ----0-------------I 1 I I 1 MIL UNIT SIZE "AM ROOF CURB 48HJ ACCESSORY 2' 004-007 61 CRRFCURBOOtA00 2--0-(6101 6RRFCURBO02A00 NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels. 3. Dimensions In [ I are in millimeters. 4. Roof curb: galvanized steel. 5. Attach ductwork to curb. (Flanges of duct rest on curb.) 6. Service clearance 4 It on each side. 7. obi. Direction of airflow. S. Either aooessory connector package can be used with either aooessory roof Curb. 0'.0 7116' :I i I TYPICAL (4) S10ES I:n '� 1--7 U116:^ 1 1 lie' I 0'-0 7116' C \ IBOU �EAOSI (SOAI p)Al Eltl 7 i `Z t1 ` tear rtA05) --- � , r 0'-0 7116' II 7'-0' p OCT 0.-0 7116' (FIELD 51PPLIEo) IND MY fIIIJ A :eolr "FADS) 191A1 It/l 'BOLT NE ADS) A (FIELD SVPLIEW , B 'C RETURN -AI IT DPEM IMG SVPPL -AIR i OPENING C SCALE 1,4 MIL UNIT SIZE "AM ROOF CURB 48HJ ACCESSORY 2' 004-007 61 CRRFCURBOOtA00 2--0-(6101 6RRFCURBO02A00 NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels. 3. Dimensions In [ I are in millimeters. 4. Roof curb: galvanized steel. 5. Attach ductwork to curb. (Flanges of duct rest on curb.) 6. Service clearance 4 It on each side. 7. obi. Direction of airflow. S. Either aooessory connector package can be used with either aooessory roof Curb. 0'.0 7116' :I i I TYPICAL (4) S10ES I:n '� 1--7 U116:^ 1 1 lie' I 0'-0 7116' 0-7116' IBOU �EAOSI (SOAI p)Al Eltl Ill] COLPITER FLASNINC - °E761� tear rtA05) (FIELD SUPPLIED) 0'-0 7116' II 7'-0' p OCT 0.-0 7116' (FIELD 51PPLIEo) IND MY fIIIJ A :eolr "FADS) 191A1 It/l 'BOLT NE ADS) A (FIELD SVPLIEW 3Mtn6 FOR ellS►M eMigr SERVICE 'C GMT STRIP (FIELD SUPPLIED) I °I{�11/7' SECTION -C' SCALE 1,4 r-ADWING MATERIAL (FIELD W-100 • J'-� I�A•171 L. 0'•A 9115 Ii 167 r— MEAD OF BOLI 109E ON INSIDE ,OFF FLANGE 0,-1 7,e/ I.B. I/ O' -I• 1251 i I 0 AREF VIEW 'B' (IYP All CORNERS) A / / / / / / 1 OEM 4I010 1/4tILA71oM 1 \ (FIELD SUPPLIED) I I 1 'E' 1 3�ER7ICE I RATE 1'd 13/16' f 11LS IDE) 1 1 / 1 1 )'-0 LS/16- 19781 / SEE vlEv Fig. 1 — Roof Curb Details 2 1 11 1 11 IC MAXIMUM ALLOWABLE DIFFERENCE (in.) Fig. 2 — Unit Leveling Tolerances Step 2 — Field Fabricate Ductwork — Secure all ducts to roof curb and building structure on vertical dis- charge units. Do not connect ductwork to unit. For horizon- tal applications, field -supplied flanges should be attached to horizontal discharge openings and all ductwork should be secured to the flanges. Insulate and weatherproof all exter- nal ductwork, joints, and roof openings with counter flash- ing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with ap- plicable fire codes. A minimum clearance is not required around ductwork. Cabinet return -air static shall not exceed —.35 in. wg with Durablade economizer, .20 in. wg with Parablade econo- mizer. or .45 in. wg without economizer. These units are designed for a minimum continuous return - air temperature in heating of 50 F (dry bulb) or an intermit- tent operation down to 45 F (dry bulb), such as when used with a night setback thermostat. Step 3 — Install External Trap for Condensate Drain — The unit's Ih in. condensate drain connections are located at the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or hori- zontal applications. When usin; the standard side drain connection, make sure the plug in the alternate bottom connection is tight before installing the unit. To use the bottom drain connection for a roof curb in- stallation, relocate the factory -installed plug from the bot- tom connection to the side connection. See Fig. 3. The pip- in- for the condensate drain and external trap can be completed after the unit is in place. All units must have an external trap for condensate drain- age. Install a trap at least 4 -in. deep and protect against freeze- up. See Fig. 4. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection. Step 4 — Rig and Place Unit — Inspect unit for transportation damage, and file any claim with transpor- tation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit, and rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table I and Fig. 5 for additional information. Operating weight is shown in Table I and Fig. 5. Lifting holes are provided in base rails as shown in Fig. 6. Refer to rigging instructions on unit. CONDENSATE PAN FACTORY4NSTALIED DRAIN PLUG LOCATION NOTE: Drain plug is shown in factory -installed position. Fig. 3 — Condensate Drain Pan MINIMUM PrrCH ONE IN. PER BASE 10 FT OF UNE RAIL OPEN VENT ROOF Frail cuae DRAIN PLUG NOTE: Trap should be deep enough to offset maximum unit static difference. A 44n. trap is recommended. Fig. 4 — External Trap Condensate Drain rCAUTION All panels must be in place when rigging. POSITIONING — Maintain clearance around and above unit to provide minimum distance from combustible materials. proper airflow, and service access. See Fig. 6. A properly positioned unit will have the following clearances between unit and roof curb: ' .-in. clearance between roof curb and base rails on each side and front of unit; 15 32 -in. clearance between roof curb and rear of unit. (See Fig. 1, section C -C.) Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of con- taminated air. Be sure that unit is installed such that snow will not block the combustion intake or flue outlet. Unit may be installed directly on wood flooring or on Class A, B, or C roof -covering material when roof curb is used. Although unit is weatherproof, guard against water from higher level runoff and overhangs. Locate mechanical draft system flue assembly at least 48 in. from any opening through which combustion prod- ucts could enter the building, and at least 48 in. from an ad- jacent building. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade. NOTE: When unit is equipped with an accessory flue dis- charge deflector, allowable clearance is 18 inches. PLACE ALL S�L �STRIPSA IN PLACE BEFORE 13, 36% S4' UNIT ON ROOF CUFa (914-1371)• DETAILSEE .o �* NOTES: 1. Dimensions in ( ) are in millimeters. 2. Hook rigging shackles through holes in base rail as shown in de- tail "A." Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit. 3. Weights include base unit without economizer. See Table 1 for unit operating weights with an economizer. I All panels must be in place when rigging. I UNIT MAX WEIGHT DIMENSIONS I ,,g.. I "C.. l.b Kg in. mm I in. mm I in. I mm 48HJEfHJF004 530 240 73.69 1872 35.50 902 33.31 847 48HJD/HJEIHJF005 540 245 73.69 1872 35.50 902 33.31 847 48HJDIHJEIHJF006 560 254 73.69 1872 35.50 902 3.31 847 48HJDIHJEIHJF007 615 279 73.69 1872 35.50 902 �333.311 847 Fig. 5 — Rigging Details Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials. Adequate combustion -air space must be provided for proper operation of this equipment. Be sure that installation com- plies with all local codes and Section 5.3, Air for Combus- tion and Ventilation. NFGC (National Fuel Gas Code), ANSI (American National Standards Institute) Z223.1-1984 and ad- dendum Z223. I a-1987. In Canada, installation must be in accordance with the CAN 1.B 149.1 and CAN l .B 149.2 in- stallation codes for gas burning appliances. Flue vent discharge must have a minimum horizontal clear- ance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment. After unit is in position, remove shipping materials and risnaing skids. Step 5 — Install Flue Hood — Flue hood is shipped screwed to the burner compartment access panel. Remove from shipping location and. using screws provided, install flue hood in location shown in Fig. 6 and 7. Step 6 — Install Gas Piping — Unit is equipped for use with type of gas shown on nameplate. Refer to local build - in; codes, or in the absence of local codes, to ANSI Z223.1- 1984 and addendum Z223- I A-1987 entitled National Fuel Gas Code. In Canada. installation must be in accordance with the CAN LB 149.1 and CAN LB 149.2 installation codes for :as burning appliances. For natural gas applications. the gas pressure at unit gas connection must not be less than 4 in. wg or greater than 13 in. wg, while the unit is operating. On 48HJ005-007 high - heat units, the eas pressure at unit gas connection must not be less than 5 in. w; or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection. Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection. Support gas piping as shown in the table in Fig. 8. For example, a'/. -in. gas pipe must have one field -fabricated sup- port beam every 8 ft. Therefore, an 18 -ft long gas pipe would have a minimum of 2 support beams, and a 48 -ft long pipe would have a minimum of 6 support beams. See Fig. 8 for typical pipe guide and locations of external manual gas shutoff valve. Step 7 — Make Electrical Connections Unit cabinet must have an uninterrupted, unbroken elec- trical ground to minimize the possibility of personal in- jury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for elec- trical ground when installed in accordance with NEC (National Electrical Code) ANSI/NFPA (National Fire Protection Association), latest edition, and local elec- trical codes. Do not use gas piping as an electrical ground Failure to follow this warning could result in the in- staller being liable for personal injury of others. FIELD POWER SUPPLY—All units except 208230-v units are factory wired for the voltage shown on the nameplate. If the 208230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v orange wire on the transformer and con- necting it to the 200-v red wire from the transformer. The end of the orange wire must then be insulated. Refer to unit label diagram for additional information. Pig- tails are provided for field service. Use UL (Underwriters' Laboratories) approved copper/aluminum connector. When installing units, provide a disconnect per NEC. Table 1 - Physical Data BASE UNIT 48 HJE/HJF004 HJD/HJEI JFOOS KJDAUE/HJF006 HJDIHJEJHJF007 NOMINAL CAPACITY 3 4 5 6 OPERATING WEIGHT (lb) Unit 530 540 560 615 With Durablade Economizer 564 574 594 649 With Parablade Economizer 572 582 602 657 With MoistureMiser Dehumidification Package 548 558 578 633 Roof Curb 115 115 115 115 COMPRESSOR Scroll Quantity 1 1 1 1 Oil (oz) 42 53 50 60 REFRIGERANT TYPE R-22 Operating Charge (lb -oz) Standard Unit 5- 8 8-0 10- 0 9-10 Unit With MoistureMiser Dehumidification 8.13 11-2 12-13 13 6 Package CONDENSER FAN Propeller Quantity... Diameter (in.) Nominal Cfm 1...22 1.. 1.. 2 1...22 5 Motor Hp Rpm +� Ir -72-5 +� ... Watts Input (Total) 14--TT-00 180 180 320 320 CONDENSER COIL Enhanced Copper Tubes. Aluminum Lanced Fins Standard Unit Rows ... Finslin. 1..17 2...17 2...17 2...17 Total Face Area (sq ft) 14.6 16.5 16.5 16.5 Unit With MoistureMiser Dehumidification Package Rows ... Finslin. 1...17 1..17 1...17 1...17 Total Face Area (sq ft) 3.9 3.9 3.9 3,9 EVAPORATOR FAN Centrifugal Size (in.) 10 x 10 10 x 10 10 x 10 10 x 10 Type Drive Belt Bell Belt Belt Nominal Cfm 1200 1800 2000 2400 Maximum Continuous Bhp 1.20 1.20 1.80 2.40 Motor Frame Size 48 48 56 56 Fan Rpm Range 760-1090 840-1185 1020-1460 1120-1585 Motor Bearing Type Ball Ball Ball Ball Maximum Fan Rpm 2100 2100 2100 2100 Motor Pulley Pitch Diameter AIB (in.) 1.9/2.9 1.92.9 2.4f3.4 24/3.4 Nominal Motor Shaft Diameter (In.) +h +h +h s Fan Pulley Pitch Diameter (in.) 4.5 4.0 4.0 3.7 Belt - Type... Length (in.) A...33 A...36 A...40 A...38 Pulley Center Line Distance (in.) 10.0-12.4 10.0.12.4 14.7-15.5 14.7-15.5 Speed Change Per Full Tum of Movable Pulley Flange (rpm) 65 70 75 g5 Movable Pulley Maximum Full Tums from Closed Position 5 5 B 5 Factory Setting - Full Turns Open 3 3 3 3 Factory Speed Setting (rpm) 890 980 1240 1305 Fan Shaft Diameter at Pulley (in.) ey 51A sh e, EVAPORATOR COIL Enhanced Copper Tubes, Aluminum Double Wavy Fins, Acutmll' Feed Dewce Rows...Fins/in. 2...15 2...15 4...15 4...15 Total Face Area (sq ft) 5.5 5.5 5.5 5.5 FURNACE SECTION Rollout Switch Cutout Temp (F)• 195 195 195 195 Sumer Orifice Diameter (in. ...drill size)t Natural Gas - Std .113...33 .113...33/.113...33/.129...30 .113...331.113...331.129...30 .113...33/.113...33/.129...30 Liquid Propane - Alt" .089...43 .089...43/.089...431.102...38 .089...43/.089...43/.102...38 .089...43/.089...43/.102...38 Thermostat Heat Anticipator Setting (amps) 208/2301460 v First Stage .14 .14 .14 Second Stage .14 .14 .14 .14 Gas Input (Stuh) .14 First Stage 50.000/ 82.000 50,000/ 82,000/120.000 50,000/ 82,000/120.000 50.000/ 82.000/120.000 Second Stage 72.000/115.000 72,000/115.000/150,000 72,000/115.000/150,000. 72.000/115.000/150.000 Efficiency (Steady State) (%) Temperature Rise Range (OnO`> t896T18M> 82/81/80 82/81/80 15--21=545 15.45735.85/50-80 15-45/35.65/50-80 1545/35.65/50-80 Manifold Pressure (in. wg) Natural Gas - Std 3.5 3.5 3.5 3.5 Liquid Propane - Alt" 3.5 3.5 3.5 3.5 Maximum Static Pressure (in. wg) 1.0 1.0 1.0 1.0 Field Gas Connection Size (in.) +h +h 'h l HIGH-PRESSURE SWITCH (psig) Standard Compressor Internal Relief 450 t 50 Cutout 448 Reset (Auto.) 320 LOSS-OF-CHARGE/LOW-PRESSURE SWITCH (Liquid Line) (psig) Cutout 7 t 3 Reset lAut0.) 22 t 5 FREEZE -PROTECTION THERMOSTAT Opens (F) 30:t 5 Closes (F) 45:k 5 OUTDOOR -AIR INLET SCREENS Cleanable Quantity... Size (in.) 1...20 x 24 x 1 RETURN -AIR FILTERS Throwaway Quantity ... Size (in.) 2...16 x 25 x 2 LEGEND 'Indicates automatic reset. ' Bhp - Brake Horsepower t48HJD00S-007 and 48HJE004 (72,000 Stuh heat input) units have 2 bumers. 48HJE00S-007 and 48HJF004 (115,000 Stuh heat input) units and 48HJF005- 007 (150,000 Stuh heat input) units have 7 burners. "An LP Conversion Kit is available as an accessory. 5 STD DURABLADE PARABLADECORNER CORNER CORNER CORNER UNIT ECONOMIZER ECONOMIZER WEIGHT WEIGHT WEIGHT WEIGHT NOTES' 1 Dimensions in ( ) r• in m4lmeten UNIT WEIGHT WEIGHT WEIGHT (A) (B) (C) (D) 2. Comer of gravity Lb Kg Lb I Kg LA Kg Lb Kg Lbj Kg LbKg Lb Kg REAR 48MJFIHJED04 530 240 34 154 42 191 127 576 122 55.3 138 62.6 t 64 9 3. oTAi. Dncmn of arfbw. 48HJFIHJEIMJDOOS 540 245 34 154 42 191 129 585 124 56.2 141 64.0 1 66.2 4 On vencol Cuular9e units. ductwork to be attached to accessory roof curb 48HJFIHJE/HJD008 560 254 34 154 42 191 134 608 1291585 146 66.2 151 68.5 only. For nonzomal discharge units. field-supoiied flanges snows be at- tached to hdr¢Orttal tlischarge openings. and all ductwork snouto be at- ,548HJF/HJE/HJD007 615 279 34 4 42 19 1 147 66.7 142 64 a 160 72.6 1 75 3 tamed to the flanges (45)4• ' S. Mnmun Ctaarsive (loch miles or jurisdiction may prevail) - <`- •Select either s." or ih .' for power. de• a. Between unit. flu sae and Combustible surfaces. 48 inches (18 in when -(6523 r 0'-7 1/4' (184 uWV accessory flue discharge de11aU0r.) I "-10 130F1 b. Bottom of unit to cdmoustrole surfaces (when not using nabl. 1 inch I Bottom d base rail t0 COmbwttble surfaces (when not using taut) 0 ernes 3' -9' I I c. Condenser coil. for proper arflow. 36 n. one side. 12 in the other The (1144I 1 sae goading the greater clearance is optional i d.OvenhaW. 60 in. to assuns Proper Condenser fan operation I e. Betwsan units. Oonuol box sae. 42 n. per NEC (National Electrical Code) 1 '-7 3/1 6' (487.4)/1 0'-3 13/16" I f. Sol~ unit and ungrounded surfaces. control box sae. 36 n. Per NEC 1977 I0'"3• I'M. 23 1h iii g. 8elwom unit and block or Concrete walls and other grounded surfaces. - - � [533]F141911 -i 1/2 ContrW box sae. 42 in. Per NEC. FACTORY SUPPLIED (108.8) (512.4] h. Hortzaeal uand urn ernes 6. Wfph pie e:oadienPty dathe geretarrheeend. for0 the condenser ODiI dna Combustion B FLUE HOW SEE BOTTOM FOYER SEE NOTE .B CuIART tF1Ec. ONLY)CORNER "D" stile as stated n rides 5a. D and e. a removable farm or bemicaoe repures no cerrhea. 7. Units may be installed an Combustible floors made from wg0tl or Class A I B. or C roof covering material R set an base rad. 2'-9 5/16" CONDENSER COIL B. Tths vertical earner d gravity is 1'-6-1457) up nom the bottom of pie base [846.5) 1'-4 S/16' rail. (414.5) BOTTOM Connection Sixes OF IAi1TI D I ,r.� A 13&' Dia 135) Field Power Suppry Holo { - J �b 8 2' Du (511 Power Supply Knockoul 0 -6 5/B 1 (fJ (168.2) / ' 0"-4 9/16" TrP 5 3'-5 3/16 [11.8) 0'-2 9/16" (1046) ELECTRICAL 1651 LEFT SIDE OLOCCAOT OIICT 0'-4 1/2' C1 141 1'-4 3M, 14167 F b'-14 N G 2'b- Dia FILTER ACCESS PANEL (DISPOSABLE FILTERS) P EL OYER '8' IalRIGHT SIDE 0 -10 15/16' 4M RE -RIM AIR 127!7 1 r-0'-5 3/8' 2 11 (906i/16 0'-3 1/) "E - 3063 1817 ' 3'-0 [911) (1672) 0'-0 3/6' -� (l0I CONTROL BOX/COMPRESSOR/ OUTSIDE AIR ' PANEL Sr THESE HOLES REO'D FOR USE REAR 2-ols' !S INDOOR FAN MOTOR 9 FILTER/ECODMIZER ACCESS PA/EL (MM ' NSER COIL 7 4 OPTIONAL ECONOMIZER MOOD \ 0'-3 S/16' CORNER -A" 2* -7112" 0'-5 7/16' 0 Q (NO (45)4• ' /�-------�2-111/16" 'LEFT C - <`- •Select either s." or ih .' for power. de• l f -(6523 r 0'-7 1/4' (184 SIDE ; ; EVAPORATOR I "-10 130F1 RETURNNAIROPENING I 11 +- I I L---- r --- - - - -- 3' -9' I I I (1144I 1 - - - -- - -- -- i I ALT. CpO DENSATE ' I DRAIN OPENING IN SAMPAN ISUPPLY AIRI I0'"3• I'M. 23 1h iii "ING VERTICAL I "49) - - � [533]F141911 -i 1/2 1 15/16' ( l - - -3 5/16' (108.8) (512.4] (99.4 SEE BOTTOM FOYER SEE NOTE .B CuIART tF1Ec. ONLY)CORNER "D" ' F R 0 N T 0'-4 1/2' C1 141 1'-4 3M, 14167 F b'-14 N G 2'b- Dia FILTER ACCESS PANEL (DISPOSABLE FILTERS) P EL OYER '8' IalRIGHT SIDE 0 -10 15/16' 4M RE -RIM AIR 127!7 1 r-0'-5 3/8' 2 11 (906i/16 0'-3 1/) "E - 3063 1817 ' 3'-0 [911) (1672) 0'-0 3/6' -� (l0I CONTROL BOX/COMPRESSOR/ BURNER ACCESS (103.27 FILTER ACCESS PANEL WISPOSABLE FILTERS) PANEL THESE HOLES REO'D FOR USE -2 8/16• INDOOR FAN MOTOR 9 SLOWER ACCESS PANEL F Ct, 1'-5 3V4' SUPPLY 1451] THREADED REG'D HOLE 0'-3 S/16' WIRE CONDUIT SIZES SIZE USE (un-) 0'-5 7/16' 0 Q o• .0 Hale VIEW 5-5 439.71--11274.6] BOTTOM POWER CHART, (103.27 FILTER ACCESS PANEL WISPOSABLE FILTERS) THESE HOLES REO'D FOR USE -2 8/16• WITH ACCESSORY PACKAGES - am CRSTMPWRO01A00 (i 2", 547 1'-5 3V4' SUPPLY 1451] THREADED REG'D HOLE 20RAL WIRE CONDUIT SIZES SIZE USE (un-) 0'-5 7/16' by 24 V 's"(22.21 11381 sen' Power 1 (28.4) 077.01 NR 1 h4' I Power* 1 1 s .' (44.41 3/16 C. •Select either s." or ih .' for power. de• pedin9 on wire size. 0'-7 1/4' (184 "-10 130F1 ' 01-4 1/16' 439.71--11274.6] (103.27 FILTER ACCESS PANEL WISPOSABLE FILTERS) 1( Ni ACCESSORY 2'-1 11/16' I RETURN MOM FILTER (652.9 I� AIR ( OPENING Nall- I I 1 20RAL 1 i� i 4' �f Lr120AIR SII I( T t � 077.01 NR Al l •' OUTSIDE AIR •(7i6.21 0'-B 7116 E1463 TRUCK SLOTS / 0'-5 3/1'1 1 15/16;) to S 05 I'l (146] Cm.Ell1144.3] [214) 0'-2 1/4'DIA FRONT (TV 1571 PLACES) OF PAOUTtNEL SIPPLr AIR ItETI/el A III RIGHT SIDE E 5T0. CONDENSATE MAIN ' Fig. 6 - Base Unit Dimensions 6 INTAKE LOUVERS FLUE OPENING Fig. 7 — Flue Hood Details x - ' 9- MINIMUM CLEARANCE FOR PANEL REMOVAL MANUAL GAS GAS 7.BASEE SHUTOFF VALVE' REGULATOR' 48- MINIMUM —� T I I DRIP LEG PER BASE RAIL ROOF CURB FIELD -FABRICATED FROM GAS METER SUPPORT' LEGEND SPACING OF SUPPORTS NFGC — National Fuel Gas Code STEEL PIPE 'Field Supplied. NOMINAL x NOTE: Follow all local codes. DIAMETER DIMENSION (in.) tRl 1y 6 swor1 6 1l4 or larger 10 Fig. 8 — Gas Piping Guide (With Accessory Thru-the-Curb Service Connections) All field wiring must comply with NEC and local requirements. Install conduit through side panel openings indicated in Fig. 6. Route power lines through connector to terminal con- nections as shown in Fig. 9. Voltage to compressor terminals during operation must be within volta_e range indicated on unit nameplate (also see Tables 2A and 26). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Tables 2A and 2B. Note 2 to de- termine the percent voltage imbalance. Operation on im- proper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty. NOTE: If accessory thru-the-bottom connections and roof curb are used. refer to the Thru-the-Bottom Accessory In- stallation Instructions for information on power wiring. The power wiring will be routed through a field -drilled hole in the basepan. The basepan is specially designed and dimpled for drilling the power access connection holes. FIELD CONTROL WIRING — Install a Carrier -approved accessory thermostat assembly according to installation in- structions included with the accessory. Locate thermostat as- sembly on a solid wall in the conditioned space to sense av- erage temperature in accordance with thermostat installation instructions. Route thermostat cable or equivalent single leads of col- ored wire from subbase terminals through connector on unit to low -voltage connections (shown in Fig. 10). Connect thermostat wires to matching screw terminals of low -voltage connection board. See Fig. 10. NOTE: For wire runs up 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 feet, use no. 14 AWG insulated wire (35 C mini- mum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junc- tion box and splice at the thermostat. Pass the control wires through the hole provided in the corner post; then feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 11. The raceway provides the UL required clearance between high- and low -voltage wiring. HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for the first stage and .14 for second stage heating, when available. Step 8 — Adjust Factory -Installed Options MOISTUREMISER DEHUMIDIFICATION PACKAGE — MoistureMiser package operation can be controlled by field installation of a Carrier -approved humidistat (Fig. 12). To install the humidistat: 1. Route humidistat cable through hole provided in unit cor- ner post. 2. Feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 11. The raceway provides the UL -required clearance between high- and low -voltage wiring. 3. Use a wire nut to connect humidistat cable into low - voltage wiring as shown in Fig. 13. APOLLO CONTROL—The optional Apollo Control is used to actively monitor all modes of operation as well as indoor fan status, filter status, and indoor -air quality. The Apollo Control is designed to work with Carrier TEMP and VVTI; systems. The thermostat must be wired to the Apollo Control be- fore starting the unit. Refer to the Apollo Control installa- tion instructions for information on installing the thermostat. DISCONNECT SWITCH — The optional disconnect switch is non-fused. The switch has the capability of being locked in place for safety purposes. BLK eLK I I II 27 YEL II 13 C — Compressor I I I I I I , 1 1 I I 21 2! SLu 1 1 I II I 1 1 , I i 1 � II 1 , I 1 1 I 1 I I EQ 1 1 , I I 1 I GNO 1 I 1 , I I I I 1 1 1 I , 1 O O I 1 1 I 1 CC - pT�C2 -� 11 EAAJTO -0 O ?' ~� FIELD POWER SUPPLY FIELD POWER SUPPLY 208/230-1.60 1, asC1 ONL NLEtT (SIZES 48HJ004-006) L PEN MEC J eLK I I TO I� i3 II 13 I ; I� YEL—Q — Compressor 21 23 I I I I , 1 1 I I GND SLu 111 I 1 1 , I i 1 � II 1 , I 1 I � I 1 1 , I I (SEMS 48HJ004, 005) 1 I 1 , I I I IFc 1 1 1 I 1 , O O I 1 CC - pT�C2 -� 11 EAAJTO -0 O ?' ~� FIELD POWER SUPPLY 1 1 1 r - J_1 1 - 1 460.3.60 1 1 1 (SIZES 48HJ004. 005) 206/230.3.60 FIELD POWER SUPPLY i.Lr__ LOW -VOLTAGE SECTION 460.3.60 �OISCONNECT1 10 3 - (SIZES 48HJ006. 007) ` ?ER NEC L., OLK TO COMP 1 I I _ I� i3 I rEL�I �Bw ON — Compressor 21 23 I I I I , 1 1 I I GND FAN 111 I 1 1 , I i 1 � II 1 , I 1 I 10 CC 1 1 , I I (SEMS 48HJ004, 005) , 1 1 , 1 1 1 g I - 1 1 1 1 I 1 CC - pT�C2 -� 11 EAAJTO -0 O ?' ~� FIELD POWER SUPPLY 208/230.3.60 r - J_1 1 - 1 460.3.60 , OISCONNEL'T , VER NEC (SIZES 48HJ004. 005) L- _ J COMP eLK I I I 1Q 11 IS YEL�i?LOLu C III , ( 1 111 I I ,II FIELD POMIER SUPPLY it L_ 575.3-60 rDISCONNECT? (SIZES 48WOO6, 007) L PtR NEC -J Fig. 9 — Power Wiring Connections r---- JUMPER _ C TO COMP I I ON — Compressor II 13 I YEL-1pI4`fiLu GND FAN C 21 2S I 1 1 , I i 1 � II 1 , III I 1 1 ( I FIELD POIYER SUPPLY 10 CC /N: (SEMS 48HJ004, 005) L -PER NEC _ J g TCt - g I - CC - pT�C2 -� 11 EAAJTO -0 O ?' ~� ® WIRE CONNECTIONS HEAT LOW -VOLTAGE SECTION 10 3 - OFF F -RAI►1 ( OpL .0-THt ANA I a, AUTO - TH2 AHA ' HEAT O�0-11►-0�� . O OFF TYPICAL THERMOSTAT CONNECTION BOARD LEGEND AHA - Adjustable Heat Anticipator TH - Thermostat -Heating CC - Cooling Compensator _ _ _ _ Field Wiring TC - Thermostat -Cooling Factory Wiring NOTE: Connect Y2 when unit is equipped with an integrated economizer. Fig. 10 — Low -Voltage Connections With or Without Economizer 8 RACEWAY LOW VOLT4GE INTEGRATED GAS UNIT HOLE IN END PANEL (HIDDEN) Fig. 11 — Field Control Wiring Raceway BLK C TO COMP I I COMP — Compressor II 13 I YEL-1pI4`fiLu GND — Ground C 21 2S I 1 1 , I i 1 � II 1 , III I 1 1 ( I FIELD POIYER SUPPLY 575.3-60 rDISCONNECT (SEMS 48HJ004, 005) L -PER NEC _ J RACEWAY LOW VOLT4GE INTEGRATED GAS UNIT HOLE IN END PANEL (HIDDEN) Fig. 11 — Field Control Wiring Raceway LEGEND C — Contactor COMP — Compressor EQUIP — Equipment GND — Ground IFC — Indoor (Evaporator) Fan Contactor NEC - National Electrical Code TB - Terminal Block RACEWAY LOW VOLT4GE INTEGRATED GAS UNIT HOLE IN END PANEL (HIDDEN) Fig. 11 — Field Control Wiring Raceway Table 2A - Electrical Data (Units Without Electrical Convenience Outlet) UNIT NOMINAL VOLTAGE (V -Ph -Hz) VOLTAGE RANGE Min Max COMPRESSOR RLA LRA OFM FLA IFM FLA COMBUSTION FAN MOTOR FLA POWER SUPPLY MCA MOCP MINIMUM UNIT DISCONNECT SIZE FLA LRA 48HJE/HJF004 (3 Tons) 208/230-1.60 187 254 16.0 88.0 0.7 4.9 .57 25.6/25.6 35/35 25/25 101/101 208/230-3-60 187 254 10.3 77.0 0.7 4.9 .57 18.5/18.5 25/25 18/18 90/90 460-3-60 414 508 5.1 39.0 0.4 2.2 .30 9.0 15 9 46 575-3-60 518 632 4.2 31.0 0.4 2.2 .30 7.3 15 7 36 48HJD/HJE/HJF005 (4 Tons) 208/230-1-60 187 254 23.7 129.0 0.7 4.9 .57 35.2/35.2 45/45 34/34 142/142 208/230-3-60 187 254 13.5 99.0 0.7 4.9 .57 22.5/22.5 30/30 22/22 112/112 460-3-60 414 508 7.4 49.5 0.4 2.2 .30 11.9 15 12 56 575-3-60 518 632 5.8 40.0 0.4 2.2 .30 9.3 15 9 45 48HJD/HJE/HJF006 (5 Tons) 208/230-1-60 187 254 28.8 169.0 1.5 8.8 .57 46.3/46.3 60/60 45/45 216216 208/230-3-60 187 254 17.3 123.0 1.5 5.8 .57 28.928.9 35/35 2828 168/168 460-3-60 414 508 9.0 62.0 0.8 2.6 .30 14.7 20 14 84 575-3-60 518 632 7.1 50.0 0.8 2.6 .30 11.6 15 11 67 48HJD/HJE/HJF007 (6 Tons) 208/230-3-60 187 254 20.5 156.0 1.4 5.8 .57 32.8/32.8 40/40 32/32 200/200 460-3-60 414 508 9.6 70.0 0.6 2.6 .30 15.2 20 15 92 575-3-60 1 518 1 632 7.7 56.0 0.6 2.6 .30 12.2 15 13 78 Table 2B - Electrical Data (Units With Electrical Convenience Outlet) UNIT NOMINAL VOLTAGE (V -Ph -Hz) VOLTAGE RANGE -- Min Max COMPRESSOR RLA LRA OFM FLA IFM FLA COMBUSTION FAN MOTOR FLA POWER SUPPLY WITH OUTLET MCA MOCP MINIMUM UNIT DISCONNECT SIZE FLA LRA 48HJE/HJF004 (3 Tons) 208/230-1-60 187 254 16.0 88.0 0.7 4.9 .57 31.6/31.6 40/40 30/30 106/106 208230-3-60 187 254 10.3 77.0 0.7 1 4.9 .57 24.524.5 30/30 24/24 , 95/95 460-3-60 414 508 5.1 39.0 0.4 2.2 .30 11.7 15 11 48 575-3.60 518 632 4.2 31.0 0.4 2.2 .30 9.5 15 9 38 48HJD/HJE/HJF005 14 Tons) 208/230-1-60 187 254 23.7 129.0 0.7 4.9 .57 41.2/41.2 50/50 39/39 147/147 208230-3-60 187 254 13.5 99.0 0.7 4.9 .57 28.528.5 35/35 2727 117/117 460-3-60 414 508 7.4 49.5 0.4 2.2 .30 14.6 20 14 58 575-3-60 518 632 5.8 40.0 0.4 1 2.2 .30 11.5 15 1 11 47 48HJD/HJE/HJF006 (5 Tons) 208/230-1-60 187 254 28.8 169.0 1.5 8.8 .57 52.3/52.3 60/60 50/50 221/221 208/230-3-60 187 254 17.3 123.0 1.5 5.8 .57 34.9/34.9 40/40 34/34 173/173 460-3-60 414 508 1 9.0 62.0 0.8 2.6 .30 17.4 20 17 86 575-3-60 518 632 7.1 50.0 0.8 2.6 .30 13.8 20 13 69 48HJD/HJE/HJF007 (6 Tons) 208230-3-60 187 254 20.5 156.0 1.4 5.8 .57 38.8/38.8 45/45 37/37 205/205 460-3-60 414 508 9.6 70.0 1 0.6 2.6 .30 17.9 1 20 17 94 575-3-60 518 632 7.7 56.0 1 0.6 2.6 .30 1 14.3 1 20 15 79 LEGEND FLA - Full Load Amps HACR - Heating, Air ' Conditioning and Refrigeration IFM - Indoor (Evaporator) Fan and LRA - Locked Rotor Amps MOCP - Maximum Overcurrent Protection MCA - Minimum Circuit Amps ' NEC - National Electrical Code OFM - Outdoor (Condenser) Fan Motor RLA - Rated Load Amps UL Underwriters' Laboratories 'Fuse or HACR circuit breaker. ' NOTES: 1. In compliance with NEC requirements for multimotor and combi- nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR ' breaker. UL Canada units may be fuse or circuit breaker. 2. Unbalanced 3 -Phase Supply Voltage Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine ' the percent voltage imbalance. = 100 x max voltage deviation from average voltage average voltage ' u a C e 9 Example: Supply voltage is 460-3-60. AB = 452 v A 8 C BC = 464 v AC = 455 v Average Voltage 452 + 464 + 455 = MOMR 3 1371 3 457 Determine maximum deviation from average voltage. (AB) 457 452 = 5 v (BC) 464 457 = 7 v (AC) 457 455 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance. % Vottage Imbalance = 100 x 457 = 1.53% This amount of phase imbalance is satisfactory as 4 is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. OPTIONAL DURABLADE ECONOMIZER — The op- tional economizer hood assembly is packaged and shipped in the filter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position. NOTE: Horizontal discharge block -off plate is shipped with the air hood package. If unit is to be used for vertical dis- charge application. discard this plate. Assemblv 1. Determine if ventilation air is required in building. if so, determine minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 7. 2. Remove filter access panel by raising panel and swing- ing panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter access panel. Remove outdoor -air opening panel. Save panels and screws. See Fig. 14. Remove econo- mizer: and remove optional outdoor -air damper hood pack- age from filter section (located behind economizer). 3. Assemble outdoor -air hood top and side plates as shown in Fig. 15. Install seal strips on hood top and sides. Put aside screen retainer and retainer screw for later assem- bly. Do not attach hood to unit at this time. 4. Slide economizer into unit and secure with screws. See Fig. 16. NOTE: Be sure to engaee rear economizer flange under tabs in vertical return -air opening. 5. To convert to horizontal discharge application: a. Rotate economizer 90 degrees until the economizer motor faces the condenser section (see Fig. 17). b. Rotate the barometric relief damper cover 90 decrees. c. Install horizontal discharge block -off plate over the opening on the access panel. (Block -off plate MUST be .installed before installing hood assembly.) See Fig. 18. ' FIELD WIRE 51DE CONTROL BOX AREA LEGEND C — Contactor (Compressor) CCH — Crankcase Heater COMP — Compressor FU — Fuse HU — Humidstat IFM — Indoor (Evaporator) Fan Motor LLSV — Liquid Line Solenoid Valve S-LPS — Low Pressure Switch (Subcooler Only) TRAN — Transformer Factory Wiring - Accessory or Optional Wiring �--- YEL FROM C CONTROL Sc BLK CCH1 COMP1 CCH2 6. Insert economizer plug into economizer harness. Re- move tape from barometric relief damper. See Fig. 19. 7. If ventilation air is not required, proceed to Step 8. If ventilation air is required, determine minimum position setting for required airflow. See Fig. 20. Adjust mini- mum position setting by adjusting the screws on the po- sition setting bracket. Slide bracket until the top screw is in the position determined by Fig. 20. Tighten screws. 8. Remove tape from outdoor -air thermostat (OAT). Fas- ten OAT to inside of hood using screws and speed clips provided. See Fig. 21. Make sure OAT terminals are po- sitioned up. 9. Replace outdoor -air opening panel using screws from Step 2. Replace filter access panel. Ensure the filter ac- cess panel slides along the tracks and is securely engaged. 10. Fasten hood top and side plate assembly (Fig. 15) to outdoor -air opening panel with screws provided. 11. Place knob supplied with economizer on OAT. See Fig. 21. Set for 3° F below indoor room thermostat set- ting. If accessory enthalpy control (EC) is used in place of OAT, see instructions shipped with EC for installa- tion and adjustment. See Fig. 21. Currier �1 ri Fig. 12 —Accessory Field -Installed Humidistat L.7U LVO L k- 4,5,6 TON ONLY 4 C TRAN RED BRN FU RED G TN/ BRNYEL� BLU BLK I— — S-LPS1- LLSV1 BLU (—BLUE-BLK I HU YEL--� BLK TO IFM Fig. 13 — Typical MoistureMiser Dehumidification Package Humidistat Wiring (2081230-V Unit Shown) 10 12. Connect OAT per Fig. 22. 13. Slide outdoor -air inlet screen into screen track on hood side plate. While holding screen in place, fasten screen retainer to hood using screws provided. NOTE: Refer to Fig. 23 for economizer barometric relief damper characteristics. OPTIONAL PARABLADE ECONOMIZER — The op- tional Parablade economizer hood assembly is packaged and shipped in the filter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position. NOTE: Horizontal discharge block -off plate is shipped with the air hood package. The Parablade economizer can only be used for vertical discharge applications. Discard this plate. Assembly I. Determine if ventilation air is required in building. If so, determine minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 6. VyG PANEL OPENING nR4NELJJ Fig. 14 — Typical Access Panel Locations SEAL STRIP SCREEN RETAINER HOOD TOP - HOOD SEAL' SIDE STRIP -� i - PLATE SEAL STRIP SCREEN HOOD TRACKS � SIDE PLATEww� OUTDOOR -AIR INLET SCREEN HOOD SIDE PLATE OUTDOOR -AIR HOOD -UNASSEMBLED HOOD SIDES AND TOP -ASSEMBLED DR AIR EEN Fig. 15 — Outdoor -Air Hood Details 2. Remove filter access panel by raising panel and swing- ing panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter access panel. Remove outdoor -air opening panel. Save panels and screws. Remove optional economizer so the outdoor -air damper hood package can be re- moved from filter section. See Fig. 14, ECONOMIZER ECONOMIZER ECONOMIZER TOP CONTROLSOARD PLUG MOTOR SCREW �NGSCR SETTING EWS BRACKET Fig. 16 — Durablade Economizer Installed in Unit ECONOMIZER CONTROL BOARD BAROMETRIC RELIEF DAMPER ECONOMIZER PLUG ECONOMIZER MOTOR Fig. 17 — Horizontal Durablade Economizer Installation BLOCK -OFF PLATE Fig. 18 — Horizontal Discharge Block -Off Plate 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 U -SNAP HOLE (NOT SI- ECONOI PLUG WIRING HARNE; a Z D _z W Q 7 y N M CL W Q LU LU Z Fig. 19 — Typical Durablade Economizer and Wiring Harness OUTDOOR AIRFLOW (cfm in iws) - — -- EXAMPLE: Given —Negative Pressure ................... 0.2 in. wg Outdoor Air ......................... 900 ctrn Determine — Setting = 5 in. Fig. 20 — Durablade Economizer Minimum Position Setting 3. Assemble outdoor -air hood top and side plates as shown in Fig. 15. Install seal strips on hood top and sides. Put aside screen retainer and retainer screw for later assem- bly. Do not attach hood to unit at this time. 4. Slide economizer into unit and secure with screws. See Fie. 24. NOTE Be sure to engage rear economizer flange under tabs in vertical return -air opening. �. Insert economizer plug into economizer harness. Re- move tape from barometric relief damper. See Fig. 24. 6. If ventilation air is not required, proceed to Step 7. If ventilation air is required, perform the following: a. Make sure the factory -installed jumper is in place across terminals P and PI on the economizer logic module. T and TI should be disconnected during adjustment. b. The 2 potentiometers with slots for adjustment are located on the face of the economizer logic module. Tum the lower potentiometer fully clockwise. The dampers should be fully closed. Turn the potentiom- eter gradually counterclockwise until the desired po- sition is reached. c. Connect T and TI to the 24-v power supply. 12 E c H OUTDOOR -AIR THERMOSTAT (TERMINALS ARE UP) 'Outdoor -Air Thermostat or Enthalpy Control can be attached to either side inside hood. Fig. 21 — Outdoor -Air Thermostat/Enthalpy Control Installation 11 1 OAT 1 ---GRAY ' 3 RED LEGEND OAT — Outdoor -Air Thermostat NOTE. See unit wiring diagram for details. Fig. 22 — Wiring Connections for Outdoor -Air Thermostat 0.e0 0.60 0.70 0.60 0 0.50 0 M 0.40 D Lu W cc Q. 030 Y 020 0.10 0.00 160 200 WO 400 SW 600 700 600 CFM Fig. 23 — Durablade Economizer Barometric Relief Damper Characteristics ' RIN HARNESS SS wnaMAETAIC CONTROL ., SENSOR T RELIEF DAMPER MODULEMAMPER ACTUATOR Fig. 24 — Parablade Economizer Installed in Unit ' d. After installation is complete, calculate the mini- mum airflow across the economizer. To calculate the minimum airflow, the following data is needed: total cfm (cfm3), temperature of the total cfm (T3), tem- perature of the return air (T,), and temperature of the entering outdoor air (T,). Cfrl, is the outdoor air (mini- mum) cfm., 13 Insert the data into the following equations: T, (cfm') + T, (cfm_) = T3 cfm3 cfm: = (cf n3 cfm,) Therefore: T, (cfm,) + TZ (cfm3 cfm,) = T3 3 Further derivation reveals the following formula for airflow: cfin, (T3 Tz) cftn, _ (Tl T2) Use this equation to determine cft-q, which is the mini- mum airflow across the economizer. If cfm, does not match the desired minimum airflow from Step 1, re -adjust the minimum position setting screw. 7. Determine the enthalpy changeover set point from Fig. 25. The enthalpy changeover set point should be set to return the outdoor -air damper to the minimum po- sition when enthalpy rises above the set point. The set- tings are A, B, C, and D. Set the enthalpy changeover per the setting in Fig. 25. 8. Replace outdoor -air opening panel using screws from Step 2. Replace filter access panel. Ensure the filter ac- cess panel slides along the tracks and is securely engaged. See Fig. 26. 9. Fasten hood top and side plate assembly (Fig. 27) to outdoor -air opening panel with screws provided. 10. Slide outdoor -air inlet screen into screen track on hood side plate. While holding screen in place, fasten screen retainer to hood using screws provided. See Fig. 28. Refer to Fig. 29 for economizer barometric relief damper characteristics. CONTROL CONTROL POINT" e w /m s 110 a�s� am as an �0111106 CURVE :r% ll % RRH A 73 (23) �► 0 70(21) p p C 67 (19) �A 0 63 (17) as a+ A n s o w 100 wf FIW 01 a!1i "93,11011 011 WI 0/1.10.51 on W 0.1 wa CMwroreunwa PM0Mrm~f#*jMFeriMM LEGEND RM — Relative Humidity Fig. 25 — Enthalpy Settings for Parablade Economizer ' Step 9 — Adjust Evaporator -Fan Speed — Adjust evaporator -fan speed to meet jobsite conditions. Table 3 shows fan rpm at motor pulley settings. Table 4 shows maximum amp draw of belt -drive motor. Table 5 shows ' motor nominal horsepower for evaporator -fan motors. Refer to Tables 6-13 to determine fan speed settings. and see Tables 14 and 15 for accessory and option static pressure drops. BELT DRIVE MOTORS — Fan motor pulleys are factory ' set for speed shown in Table 1. Check pulley alignment and belt tension prior to start-up. NOTE: Before adjusting fan speed, make sure the new fan speed will provide an air temperature rise range as shown in ' able 1. change fan speed: I. Shut off unit power supply. ' ?. Loosen belt by loosening fan motor mounting nuts. See Fit. 30. 3. Loosen movable pulley flange setscrew (see Fig. 31). ' 4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not ex- ceed maximum speed specified in Table 1. ' FILTER ACCES, PANEL OUTDO ' OPENIN 1 Fig. 26 — Panels Reinstalled on Unit Fig. 27 — Outdoor -Air Hood Installed on Unit 14 Fig. 28 — Filter Installed on Outdoor -Air Hood O.w 100 200 300 goo Soo 600 700 r�0 CFM Fig. 29 — Parablade Economizer Barometric Relief Damper Characteristics MOTOR MOUNTING PLATE NUTS Fig. 30 — Belt Drive Motor Mounting f1• Fig. 28 — Filter Installed on Outdoor -Air Hood O.w 100 200 300 goo Soo 600 700 r�0 CFM Fig. 29 — Parablade Economizer Barometric Relief Damper Characteristics MOTOR MOUNTING PLATE NUTS Fig. 30 — Belt Drive Motor Mounting 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table I for speed change for each full turn of pulley flange.) To align fan and motor pulleys, loosen fan pulley set- screws and slide fan pulley along fan shaft. Make angular alignment by loosening motor from mounting. To adjust belt tension: 1. Loosen fan motor mounting nuts. 2. Slide motor mounting plate away from fan scroll for proper belt tension (lb -in. deflection with one finger) and tighten mounting nuts. 3. Adjust lock bolt and nut on mounting plate to secure mo- tor in fixed position. STRAIGHTEDGE MUST MOVABLE BE PARALLEL FLANGE WITH BELT 1 MOTOR AND FAN SHAFTS MUST BE PARALLEL SETSCREWS i FIXED FLANGE SINGLE -GROOVE Fig. 31 - Evaporator -Fan Pulley Adjustment Table 3 - Fan Rpm at Motor Pulley Settings Table 4 - Maximum Amp Draw of Belt Drive Motor MOTOR MAXIMUM UNIT All PULLEY TURNS OPEN PHASE CONTINUOUS UNITMOTOR AMPS Single Phase 1.50 SHP Single 1.20 208/230 5.4 2.00 0 1k 1 112 2 212 3 312 4 4'2 S 512 6 48HJE,HJF004 1090 1055 1025 990 960 925 890 860 825 795 760 - - 48HJD.HJE,HJF005 1185 1150 1115 1080 1045 1015 980 945 910 875 840 - - 48HJD,HJE.HJF006 1460 1425 1385 1350 1315 1275 1240 1205 1165 1130 1095 1055 1020 48HJD,HJE,HJF007 1585 1540 1490 1445 1400 1350 1305 1260 1210 1165 1120 - - Table 4 - Maximum Amp Draw of Belt Drive Motor BHP - Brake Horsepower 15 Table 5 - Motor Nominal Horsepower UNIT 48 MOTOR MAXIMUM UNIT All UNIT 48 PHASE CONTINUOUS VOLTAGE AMPS Single Phase 1.50 SHP Single 1.20 208/230 5.4 2.00 208/230 5.4 HJE/HJF004 Three 1.20 460 2.4 575 2.4 Single 1.20 208/230 5.4 208/230 5.4 HJD/HJE/HJF005 Three 1.20 460 2.4 575 2.4 Single 1.80 208/230 9.71 HJD/HJE/HJF006 208/230 6.4 Three 1.80 460 2.9 575 2.9 208/230 6.4 HJD/HJE/HJF007 Three 2.40 460 2.9 575 2.9 BHP - Brake Horsepower 15 Table 5 - Motor Nominal Horsepower UNIT 48 MOTOR NOMINAL HORSEPOWER NJEIHJF004 All 1.00 HJD/HJE/HJFOOS All 1.00 Single Phase 1.50 HJDIHJEIHJF006 Three Phase 2.00 HJDIHJEIHJF007 All 2.00 Table 6 - Fan Performance, 48HJ0O4 - Vertical Discharge Units AIRFLOW EXTERNAL STATIC PRESSURE (in. wg) 0.1 0.2 0.3 0.4 0.5 0.6 (Ctm) Rpm Bhp Rpm 7 Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 581 0.12 673 0.18 736 0.22 805 0.25 865 0.29 911 0,34 1000 644 0.19 709 0.22 782 0.28 835 0.30 900 0.35 937 0.38 1100 687 0.22 746 0.26 806 0.30 867 0.35 929 0.40 964 0.40 1200 733 0.26 785 0.32 843 0.35 903 0.41 960 0.47 994 0.50 1300 1400 754 810 0.29 0.35 826 868 0.38 0.45 891 937 0.43 0.51 942 984 0.48 991 0.53 1047 0.60 1500 1 841 1 0.42 1 911 1 0.53 985 0.61 1029 0.57 0.66 1032 1073 0.62 0.72 1067 1109 0.67 11 0.77 1700 AIRFLOW 0.49 873 EXTERNAL STATIC PRESSURE (in. wg) 0.7 0.6 0.9 1.0 1.1 1.2 (Cfm) 1800 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 1000 957 992 0.39 0.44 988 1039 0.43 0.49 1039 0.45 1061 0.47 1083 0.53 1105 0.57 1100 1013 0.49 1068 0.55 1061 1090 0.51 0.58 1086 1109 0.55 0.61 1111 1127 0.59 0.64 1136 1145 0.63 1200 1300 1045 1075 0.56 0.64 1090 1122 0.64 1109 0.64 1156 0.68 1203 0.71 1250 0.67 0.74 1400 1110 0.73 1160 0.70 0.84 1152 1181 0.72 0.81 1190 1237 0.76 0.85 1228 1293 0.80 0.89 1266 1349 0.84 1500 1150 0.82 1190 1.00 1225 0.90 1271 0.95 1371 1.00 1363 1 0.93 1.05 LEGEND Bhp - Brake Horsepower NOTES: 1. Boldface indicates field -supplied motor and drive required. (See Note 5.) 2. Maximum continuous bhp is 1.20. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 3. Values include losses for filters, unit casing, and wet coils. 4. Use of a field -supplied motor may affect wire sizing. Contact Carrier representative to verify. 5. Motor drive range: 760 to 1090 rpm. All other rpms require field -supplied drive. 6. Interpolation is permissible. Do not extrapolate. ITable 7 - Fan Performance, 48HJOO5 - Vertical Discharge Units AIRFLOW EXTERNAL STATIC PRESSURE (in. ) 0.1 0.2 0.3 0.4 0.6 0.7 0.8 (C�) Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm' I Bhp 1200 596 0.20 665 0.25 722 0.31 779 0.36 872 0.48 915 0.54 957 0.63- 1300 633 0.24 699 0.30 754 0.36 809 0.42 902 0.55 943 0.61 984 0.67 1400 672 0.30 735 0.36 788 0.42 840 0.48 933 0.62 972 0.69 1011 0.75 1500 711 0.35 770 0.42 822 0.49 873 0.55 963 0.69 1002 0.77 1041 0.84 1600 751 0.42 835 0.49 871 0.56 907 0.63 993 0.77 1033 0.85 1072 0.93 1700 791 0.49 873 0.57 907 0.65 941 0.72 1024 0.87 1064 0.96 1103 1.04 1800 831 0.58 881 0.66 929 0.74 976 0.81 1057 0.97 1095 1.06 1132 1.14 1900 872 0.67 919 0.75 965 0.84 1011 0.92 1091 1.08 1127 1.17 ='1182- _ 1:25 2000 913 0.77 958 0.86 1002 0.95 1046 1.03 t :.:30 :=1185 1.38 AIRFLOW EXTERNAL STATIC PRESSURE (in. wg) 0.9 1.0 1.1 1.2 1.4 1.6 1.8 (Cfm) Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm7 Bhp 1200 993 0.65 1028 0.69 1056 0.72 1083 0.74 1134 0.80 1185 0.88 1331 0.99 1300 1021 0.74 1058 0.80 1090 0.85 1121 0.89 1171 0.94 1219 1.00 1268 1.10 1400 1049 0.82 1086 0.89 1120 0.96 1153 1.00 1210 1.12 1257 1.17 '1307" '..125 1500 1077 0.92 1113 0.99 1147 1.06 1180 1.13 3 - ar ; 1339, ' •,;1.43 1600 1107 1.00 1141 1.09 1174 1.17 `.1 = ..� .T -_1376: ;; .37,'- 1.65 ; 1700 1137 1.12 1171 1.20 1203 1.29 1235.' .1:3T<: `1 �0: :�Q7:^ ;-.1.84 ; 1800 1167 1.23 1202 1.32 1233 1.41 °.T283 .% .$T': 1:.85r :.•1436;• 2.02 ' 1900 1197 1.35 1232 1.45 1263 1.54 1294: .:��3 a .ias' i, ,T$1 :' 108 • am00 2000 1229 1 1.48 1 1262 J1.58 1.1294 1.68 1325 LEGEND Bhp - Brake Horsepower Input to Fan NOTES: 1. Boldface indicates field -supplied drive is required. (See Note 3.) 2. = indicates field -supplied motor and drive required. 3. Motor drive range is 840 to 1185 rpm. All other rpms require a field -supplied drive. 4. Values include losses for filters, unit casing, and wet coils. 5. Maximum continuous bhp is 1.20. Extensive motor and electrical testing on these units ensure that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 6. Use of a field -supplied motor may affect wire sizing. Contact your Carrier representative to verify. 7. Interpolation is permissible. Do not extrapolate. 16 Table 8 - Fan Performance, 48HJ006 - Vertical Discharge Units AIRFLOW EXTERNAL STATIC PRESSURE (in. wg) (Cfm) 0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp I Rpm I Bhp Rpm I Bhp 1500 771 0.37 828 0.44 935 0.58 1027 0.73 1107 0.88 1185 1.04 1257 1.20 1330 1.38 1411 1.59 1600 816 0.45 869 0.51 968 '0.66 1056 0.81 1137 0.97 1215 1.14 1286 1.31 1353 1.49 1421 1.68 1700 902 0.61 940 0.60 1007 0.75 1094 0.91 1175 1.09 1245 1.26 1315 1.44 1381 1.52 1443 1.69 1800 942 0.70 978 0.66 1063 0.82 1147 0.97 1248 1.20 1322 1.33 1395 1.46 1475 1.56 1542 1.71 1900 982 0.80 1023 0.78 1097 0.91 1175 1.11 1266 1.29 1356 1.47 1430 1.58 1504 1.69 1556 " 182 2000 1022 0.91 1068 0.90 1132 1.01 1218 1.23 1303 1.41 1397 1.52 1459 1.67 `1532 -1.82 1.97 2100 1063 0.99 1115 1.00 1180 1.17 1261 1.35 1340 1.53 1428 1.66 1489 1.80 1567 1.99 .1588 1626 216 2200 1104 1.13 1159 1.15 1214 1.28 1310 1.52 1375 1.63 1459 1.80 .. 528' ° 1:.'W 1603 217 1666 237 2300 1130 1.26 1202 1.29 1248 1.38 1358 1.69 141.0 1.72 - 11581:.'ZIT..1637 T, . _ 2.35 -1710 2.54 2400 1174 1.37 1237 1.41 1292 1.55 1397.: 2.19 - z ;2`14'; ;:1584• :228 1671 55 2_TO 2500 1201 1.48 1272 1.53 1335 1.71 1427 '=1'.94; .. 518' =9' X35? 1`1633' 253 1698 .2 '272 ..1756 - . - 2900 LEGEND Bhp .- Brake Horsepower Input to Fan NOTES: 1. Boldface indicates field -supplied drive is required. (See Note 3.) 2. 0. indicates field -supplied motor and drive required. 3. Motor drive range is 1020 to 1460 rpm. All other rpms require a field -supplied drive. 4. Values include losses for filters, units casing, and wet coils. 5. Maximum continuous bhp is 1.80. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 6. Use of afield -supplied motor may affect wire sizing. Contact your Carrier representative to verify. 7. Interpolation is permissible. Do not extrapolate. Table 9 - Fan Performance, 48HJ007 - Vertical Discharge Units AIRFLOW EXTERNAL STATIC PRESSURE (in. ) (Cfm) 0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1 1.6 Rpm Bhp Rpm Bhp Rpm Shp Rpm Bhp Rpm Bhp Rpm I Bhp Rpm Bhp_ Rpm I Bhp Rpm Bhp 1800 942 0.70 978 0.66 1063 0.82 1147 0.97 1248 1.20 1322 1.33 1395 1.46 1475 1.56 1542 1.71 1900 982 0.80 1023 0.78 1097 0.91 1175 1.11 1266 1.29 1356 1.47 1430 1.58 1504 1.69 1556 1.82 2000 1022 0.91 1068 0.90 1132 1.01 1218 1.23 1303 1.41 1397 1.52 1459 1.67 1532 1.82 1588 1.97 2100 1063 0.99 1115 1.00 1180 1.17 1261 1.35 1340 1.53 1428 1.66 1489 1.80 1567 1.99 1626 2.16 2200 1104 1.13 1159 1.15 1214 1.28 1310 1.52 1375 1.63 1459 1.80 1528 1.95 1603 2.17 1666 2.37 2300 1130 1.26 1202 1.29 1248 1.38 1358 1.69 1410 1.72 1488 1.93 1561 2.13 1637 2.351710 2-54- 2400 1174 1.37 1237 1.41 1292 1.55 1392 1.81 1460 1.90 1532 2.14 1584_ 2.28 "1671" 255 :1756 270 2500 1201 1.48 1272 1.53 1335 1.71 1427 1.94 1518 2.16 1575 2.35 ;; ' :;2.53' ..1698. , 2600 1246 1.62 1320 1.68 1368 1.81 1458 2.06 . � - T, . _ :272, _ 2700 1285 1.75 1361 1.82 1400 1.91 1490 2.19 - • -' - - - 2800 1304 1.87 1402 1.95 1439 2.08 1543 , 2900 1345 2.07 1446 2.16 1477 2.16 1585' ZW-' 3000 1 1378 1 2.26 1 1489 1 2.36 1 1529 2.52 1 1598 LEGEND Bhp - Brake Horsepower Input to Fan NOTES: 1. Boldface indicates field -supplied drive is required. (See Note 3.) 2. = indicates field -supplied motor and drive required. 3. Motor drive range is 1120 to 1585 rpm. All other rpms require a field -supplied drive. 4. Values include losses for filters, units casing, and wet coils. 5. Maximum continuous bhp is 2.40. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 6. Use of a field -supplied motor may affect wire sizing. Contact your Carrier representative to verify. 7. Interpolation is permissible. Do not extrapolate. 17 Table 10 - Fan Performance, 48HJ004 - Horizontal Discharge Units AIRFLOW EXTERNAL STATIC PRESSURE (in. wg) 0.1 0.2 0.3 O.t 0.5 0.6 (Ctm) Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm I Bhp 900 1000 900 526 0.06 584 0.08 656 0.12 734 0.22 818 0.25 875 0.27 1000 570 0.09 627 0.13 738 0.19 800 0.26 848 0.29 895 0.31 1100 614 0.13 670 0.16 758 0.23 812 0.29 863 0.32 914 0.35 1200 658 0.16 710 0.23 780 0.28 840 0.32 889 0.36 938 0.40 1300 703 0.20 752 0.27 808 0.32 868 0.37 916 0.41 963 0.45 1400 725 0.29 776 0.31 845 0.38 891 0.42 937 0.47 983 0.51 1500 755 0.33 816 0.38 870 0.43 924 0.48 969 0.53 1 1014 1 0.58 AIRFLOW (Cfm) EXTERNAL STATIC PRESSURE (in. wg) 0.7 0.8 0.9 1.0 1 1.1 1.2 0.4 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 1000 924 936 0.32 0.35 953 977 0.35 0.39 989 1020 0.38 0.44 1028 1064 0.42 0.48 1074 1124 0.49 0.54 1120 0.54 1100 960 0.39 1005 0.43 1052 0.49 1100 0.52 1163 0.59 1185 1225 0.60 0.65 1200 960 0.45 1038 0.50 1076 0.53 1136 0.59 1201 0.65 1266 0.72 1300 1012 0.51 1061 0.56 1090 0.61 1172 0.65 1239 0.72 1306 0.79 1400 1027 0.56 1071 0.60 1108 0.67 1208 0.70 1278 0.79 1347 0.87 1500 1056 1 0.63 1 1097 1 0.68 1 1117 0.70 1245 0.74 1315 0.87 1385 0.96 LEGEND Bhp - Brake Horsepower Input to Fan ' NOTES: 1. Boldface indicates afield -supplied drive is required. (See Note 4.) 2. Maximum continuous bhp is 1.20. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. ' 3. Values include losses for filters, unit casing, and wet coils. 4. Motor drive range: 760 to 1090 rpm. All other rpms require field -supplied drive. 5. Interpolation is permissible. Do not extrapolate. 6. Use of a field -supplied motor may affect wire sizing. Contact your Carrier representative to verify. ITable 11 - Fan Performance, 48HJOOS - Horizontal Discharge Units AIRFLOW (Cfm) EXTERNAL STATIC PRESSURE (in. wg) 0.9 EXTERNAL STATIC PRESSURE (In. wp) 0.1 0.2 0.3 0.4 0.6 0.7 0. 8Bhp Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm 1 1200 569 0.18 641 0.23 701 0.29 761 0.34 859 0.46 901 0.52 943 0.58 1300 604 0.22 673 0.28 731 0.34 788 0.39 887 0.52 928 0.59 968 0.65 1400 640 0.27 705 0.33 761 0.39 817 0.45 914 0.59 955 0.66 996 0.72 1500 676 0.32 738 0.38 793 0.45 847 0.51 940 0.65 982 0.73 1024 0.81 1600 713 0.38 772 0.44 825 0.51 877 0.58 967 0.73 1009 0.81 1051 0.89 1700 750 0.45 806 0.51 857 0.59 908 0.66 997 0.81 1037 0.90 1077 1.01 1800 788 0.52 841 0.59 890 0.67 939 0.75 1026 0.91 1065 1.01 1104 1.07 1900 826 0.60 876 0.68 924 0.76 971 0.84 1056 1.01 L 1094 1 1.10 1132 1.18 2000 1 864 1 0.70 1 912 1 0.77 1 958 1 0.86 1 1004 1 0.94 1 1087 1.12 2:' X1182 '=-1:30 AIRFLOW (Cfm) EXTERNAL STATIC PRESSURE (in. wg) 0.9 1.0 1.1 1.2 1.4 1.6 1.8 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1200 987 0.64 1030 0.70 1068 0.79 1106 0.87 1134 0.98 1189 1.12 :AM: 121 1300 1006 0.71 1044 0.77 1086 0.84 1128 0.91 1183 1.10 '- `' ••..1297 Y1.35 1400 1033 0.79 1069 0.86 1104 0.93 1139 1.01 1218 1.14 j . ` 1320: 1500 1060 0.88 1095 0.95 1129 1.02 1162 1.09 303: X34.'.:. '",j +Ip'" ; ,:1343'' .:.1.48 %� 1600 1087 1.01 1123 1.05 1156 1.13 118.5 1.20 9�: 1 ':1382 :'1.88 •< 1700 1114 1.07 1151 1.15 1183 ' 123 1800 1900 1141 1168 1.17 128 1178 1.26 1211 1.35 1204 1.37 1238 1.47%: 1 ' ; . �..t31Ci.:::. ,1439'; Z11• :; 2000 1197 1.39 1231 1.48 ' 1265 1.59 ' '^1288' .~ �:. "., : d99;<...;: 7 :_:. O8 - y ''2 ! LEGEND Bhp - Brake Horsepower Input to Fan NOTES: 1. Boldface indicates field -supplied drive required. (See Note 3.) 2. = indicates field -supplied motor and drive required. 3. Motor drive range: 840 to 1185 rpm. All other rpms require a field -supplied drive. 4. Values include losses for filters, unit casing, and wet coils. 5. Maximum continuous bhp is 1.20. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 6. Use of a field -supplied motor may affect wire sizing. Contact your Carrier representative to verify. 7. Interpolation is permissible. Do not extrapolate. 18 Table 12 - Fan Performance, 48HJ006 - Horizontal Discharge Units AIRFLOW EXTERNAL STATIC PRESSURE (in. wg) (Cfm) 0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm I Bhp Rpm I Bhp Rpm Bhp Rpm Bhp Rpm I Bhp 1500 741 0.38 798 0.43 895 0.54 990 0.67 1073 0.80 1154 0.95 1218 1.12 1295 1.36 1360 1.40 1600 783 0.45 838 0.51 933 0.63 1016 0.75 1102 0.90 1182 1.04 1251 1.20 1310 1.40 1385 1.49 1700 825 0.53 878 0.60 969 0.72 1049 0.84 1134 1.00 1206 1.14 1281 1.31 1342 1.48 1398 1.53 1800 885 0.63 942 0.73 1047 0.90 1139 1.05 1193 1.14 1276 1.30 1341 1.40 1413 1.55 1474 1.58 1900 928 0.73 982 0.83 1084 1.02 1160 1.11 1223 1.24 1301 1.38 1374 1.53 1437 1.62 1490 1.67 2000 971 0.84 1022 0.94 1121 1.12 1188 1.22 1254 1.36 1329 1.44 1396 1.66 1460 1.68 1509 1.77 2100 1015 0.97 1063 1.10 1140 1.18 1196 1.27 1272 1.45 1354 1.58 1413 1.75- 1475 1.73 1529 1.92 2200 1060 1.10 1104 1.20 1159 1.23 1229 1.41 1306 1.53 1363 1.70 ;f434' 1181 1487 1.85 1554 2.07 2300 1104 1.25 1130 1.27 1196 1.37 1264 1.56 1340_ 1661459 1494 2.19 L: > `.1:88 1520 2.07 1576 2.24 2400 1138 1.30 1174 1.37 1245 1.57 1305 1.63 1474 :8i; '140' .f.9;t5M : 206 1552 224 1604 2-42 2500 1183 1.43 1201 1.50 1284 1.65 1338 1.75 X1402: 1339 1468% '1524 .2.24 1585 2.42 1638 2.60 LEGEND Bhp - Brake Horsepower Input to Fan NOTES: 1. Boldface indicates field -supplied drive required. (See Note 3.) 2. 0 indicates field -supplied motor and drive required. 3. Motor drive range: 1020 to 1460 rpm. All other rpms require a field -supplied drive. 4. Values include losses for filters, unit casing, and wet coils. 5. Maximum continuous bhp is 1.8. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 6. Use of a field -supplied motor may affect wire sizing. Contact your Cartier representative to verify. 7. Interpolation is permissible. Do not extrapolate. ITable 13 - Fan Performance, 48HJ007 - Horizontal Discharge Units AIRFLOW EXTERNAL STATIC PRESSURE (in. wg) (Cfm) 0.1 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm. Bhp Rpm.. Bhp Rpm Bhp Rpm Bhp 1800 885 0.63 942 0.73 1047 0.90 1139 1.05 1193 1.14 1276 1.30 1341 1.40 1413 1.55 1474 ` 1.58 1900 928 0.73 982 0.83 1084 1.02 1160 1.11 1223 1.24 1301 1.38 1374 1.53 1437 1.62 1490 1.67 2000 971 0.84 1022 0.94 1121 1.12 1188 1.22 1254 1.36 1329 1.44 1396 1.66 1468 1.68 1509 1.77 2100 1015 0.97 1063 1.10 1140 1.18 1196 1.27 1272 1.45 1354 1.58 1413 1.75 1465 1.73 1529 1.92 2200 1060 1.10 1104 1.20 1159 1.23 1229 1.41 1306 1.53 1363 1.70 1434 1.81 1487 1.85 1554 2.07 2300 1104 1.25 1130 1.27 1196 1.37 1264 1.56 1340 1.66 1397 1.86 1465 1.88 1520 2.07 1576 2.24 2400 1138 1.30 1174 1.37 1245 1.57 1305 1.63 1373 1.84 1440 1.95 1502 2.06 1552 2.24 1604 2.42 2500 1183 1.43 1201 1.50 1284 -1.65 1338 1.75 1402 1.99 1469 2.04 1524 2.24 -ISM '2.42 1638 2.60 2600 1210 1.58 1243 1.67 1312 1.76 1366 1.96 1435 2.10 1494 2.19 L: > '141'; '1611& 2.63 1671. 2.80 2700 1254 1.76 1285 1.80 1354 1.95 1403 2.14 1474 2.21 1i384c 1-61 '1646 2.83 - 2800 1274 1.82 1304 1.85 1374 2.12 1459 2.25 =4_2-85 - - - - 2900 1318 1.95 1345 2.05 1412 2.32 1496 2481 `t1329i, 2:61;1 1W - - - - - - 3000 1 1362 1 2.20 1 1378 1 2.30 1 1451 1 2.40 1 1534 2M, :1560'.2 LEGEND ' Bhp - Brake Horsepower Input to Fan NOTES: 1. Boldface indicates field -supplied motor and drive required. (See Note 6.) 2. = indicates field -supplied motor and drive required. 3. Maximum usable bhp is 2.4. Extensive motor and electrical testing on these units ensures that the full horsepower range of the motor can be utilized with confidence. Using your fan motors up to the horsepower ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. ' 4. Values include losses for filters, unit casing, and wet coils. 5. Use of a field -supplied motor may affect wire sizing. Contact Carrier representative to verify. 6. Motor drive range: 1120 to 1585 rpm. All other rpms require field -supplied drive. 19 Table 14 - Economizer Static Pressure Drop (in. wg) CFM UNIT 900 1200 1400 1600 1800 2000 2200 2400 2600 Durablade .05 .05 1 .05 1 .05 1 .05 1 .OS .OS 05 .05 Parabiade .08 .10 1 .17 1 .26 1 .33 1 .34 1 .36 1 .40 1 .44 PRE -START-UP Failure to observe the following warnings could result in serious personal injury: 1. Follow recognized safety practices and wear protec- tive goggles when checking or servicing refrigerant system. 2. Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured. 3. Do not remove compressor terminal cover until all electrical sources are disconnected. 4. Relieve all pressure from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals. 5. Never attempt to repair soldered connection while re- frigerant system is under pressure. 6. Do not use torch to remove any component. System contains oil and refrigerant under pressure. To re- move a component, wear protective goggles and pro- ceed as follows: a. Shut off electrical power and then gas to unit. b. Reclaim refrigerant to relieve all pressure from system using both high- and low-pressure ports. C. Cut component connection tubing -with tubing cut- ter and remove component from unit. d. Carefully unsweat remaining tubing stubs when necessary. Oil can ignite when exposed to torch flame. Proceed as follows to inspect and prepare the unit for ini- tial start-up: I. Remove all access panels. 2. Read and follow instructions on all WARNING, CAU- TION, and INFORMATION labels attached to, or shipped with, unit. 3. Make the following inspections: a. Inspect for shipping and handling damages such as bro- ken lines, loose parts, disconnected wires, etc. b. Inspect for oil at all refrigerant tubing connections and on unit base. Detecting oil generally indicates a re- frigerant leak. Leak -test all refrigerant tubing connec- tions using electronic leak detector, halide torch, or liquid -soap solution. c. Inspect all field- and factory -wiring connections. Be sure that connections are completed and tight. Table 15 - FIOP MoistureMiser Dehumidification Package Static Pressure Drop (in. wg) UNIT SIZE UNIT CFM PER TON 48HJ NOMINAL TONS 300 1 400 1 Soo E/F004 3 .04 1 .07 1 .09 DIE/F005 1 4 1 .07 1 .12 1 .15 D/E/F006 5 ( .09 1 .15 1 .21 D/EIF007 1 6 1 .12 1 .20 LEGEND FIOP - Factory -Installed Option b. Make sure that air filters are in place. c. Make sure that condensate drain trap is filled with wa- ter to ensure proper drainage. d. Make sure that all tools and miscellaneous loose pacts have been removed. START-UP Unit Preparation - Make sure that unit has been installed in accordance with installation instructions and applicable codes. Return -Air Filters - Make sure correct filters are installed in unit (see Table 1). Do not operate unit without return -air filters. Outdoor -Air Inlet Screen - Outdoor -air inlet screen must be in place before operating unit. Compressor Mounting - Compressors are inter- nally spring mounted. Do not loosen or remove compressor holddown bolts. Internal Wiring - Check all electrical connections in unit control boxes. Tighten as required. Refrigerant Service Ports - Each unit system has 3 Schrader type service ports: one on the suction line, one on the liquid line, and one on the compressor discharge line. Be sure that caps on the ports are tight. Two additional Schrader valves are located under the high-pressure and low-pressure switches, respectively. Compressor Rotation - On 3-phase units with scroll compressors, it is important to be certain compressor is rotating in the proper direction.. To determine whether or not compressor is rotating in the proper direction: 1. Connect service gages to suction and discharge pressure fittings. Energize the compressor. 3. The suction pressure should drop and the discharge pres- sure should rise, as is normal on any start-up. If the suction pressure does not drop and the discharge pressure does not rise to normal levels: 1. Note that the evaporator fan (006 and 007 only) is prob- ably also rotating in the wrong direction. 2. Tum off power to the unit. 3. Reverse any two of the unit power leads. d. Inspect coil fins. If damaged during shipping and han- 4. Reapply power to the compressor. dling, carefully straighten fins with a fin comb. The suction and discharge pressure levels should now move 4. Verify the following conditions: to their normal start-up levels. a. Make sure that condenser -fan blade is correctly NOTE: When the compressor is rotating in the wrong positioned in fan orifice. Refer to Condenser -Fan Ad- direction, the unit will make an elevated level of noise and justment section on page 25 for more details. will not provide cooling. 20