06-3801 (CSCS) Revision 1 Title 24EM
TITLE 24 REPORT
Title 24 Report for:
The Dunes Retail Center - Retail 1
79-630 Highway 111
La Quinta, CA 92253
11
Project Designer:
KKE Architects
525 East Colorado Boulevard
• Pasadena, CA 91101
(626) 796-8230
Report Prepared By:
y C+J Technical Solutions
C+J Technical Solutions and Services, Inc.
1320 Valley Vista Dr. Suite 206
Diamond Bar, CA 91765
(909) 896-3631
AUG 3 1 2007
Job Number: CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
C07079 APPROVED
F"OCONSFO CONSTRUCTION
Date: oar BY
8/14/2007
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.2 by EnergySoft Job Number: C07079 User Number: 5950
TABLE OF CONTENTS
Cover Page 1
Table of Contents 2
Nonresidential Performance Title 24 Forms 3
Form ENV-MM Envelope Mandatory Measures 13
Form MECH-MM Mechanical Mandatory Measures 14
HVAC System Heating and Cooling Loads Summary 16
EnergyPro 4.2 by EnergySoft Job Number: C07079 User Number: 5950
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1
PROJECT NAME
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
DATE
The Dunes Retail Center - Retail 1
DOCUMENTATION AUTHOR
8/14/2007
PROJECT ADDRESS
CLIMATE ZONE
15
,
79-630 Highway 111 La Quinta
HOTELIMOTEL GUEST ROOM
I
PRINCIPAL DESIGNER - ENVELOPE
TELEPHONE
Building Permit #
KKE Architects
(626) 796-8230
California as a civil engineer, mechanical engineer, or I am a licensed architect.
DOCUMENTATION AUTHOR
C+J Technical Solutions and Services, Inc.
TELEPHONE
909 896-3631
Checked by/Date
R F-] 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Enforcement Agency USe
GENERAL INFORMATION
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
DATE OF PLANS
DOCUMENTATION AUTHOR
BUILDING CONDITIONED FLOOR AREA
8,109 sq.Ft.
CLIMATE ZONE
15
BUILDING TYPE ®
NONRESIDENTIAL HIGH RISE RESIDENTIAL
HOTELIMOTEL GUEST ROOM
PHASE OF CONSTRUCTION ®
NEW CONSTRUCTION ADDITION
EXISTING + ADDITION/ALTERATION
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation Is accur to and comp) e.
DOCUMENTATION AUTHOR
SIGNATURE
J/A
C+J Technical Solutions
The Principal Designer hereby certifys that the proposed building d ign repent this set of construction do m is i;.M/-,
consistent with the other compliance forms and worksheets, with spedtions&d d with any other calculations s mitteih this
permit application. The proposed building as designed meets th energyncy requirements contained in sections 110, 1,
through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
ENV. LTG. MECH.
❑ F-] R 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, or I am a licensed architect.
❑ ❑ 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section
5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
R F-] 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in
full in the Nonresidential Manual.)
ENVELOPE COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
ENV -1
Required Forms
PRINCIPAL ENVELOPE DESIGNER - NAME
SIGNATURE
LIC. NO.
DATE
KKE Architects
LIGHTING COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
Lighting Compliance Not In The Scope Of
Required Forms
PRINCIPAL LIGHTING DESIGNER - NAME
SIGNATURE
LIC. NO.
DATE
MECHANICAL COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
Require orms ECH-1 MECH-2 MECH-3 MECH-5
E
PRINCIPAL MECHANICAL DESIGNER - NAME S AT LIC. NO. IM'3666j-�
Polar Barr Air Conditioning,InC. ��
I EnergyPro 4.2 by EnergySoft User Number: 5950 Job Number: C07079 Pape:3 of 20
PERFORMANCE CERTIFICATE OF -COMPLIANCE Part 2 of 3 PERF -1
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 8/14/2007
ANNUAL TDV ENERGY USE SUMMARY
kBtu/s ft -
Conditioned Floor Area
Unconditioned Floor_Area
Conditioned Footprint Area
fuel TypeI
Standard
sqft.
sqft.
sqft.
Proposed ,
Compliance
;ENERGY COMPONENT Design
8,104
Design
Margin
Space Heating 1.81
Left Elevation " ,
1.54
0.27
Space Cooling 289.56
666
260.89
28.67
_Indoor Fans 74.33.
19.1%
94.11
-19.78
Heat Rejection 0.00
S
0.00
0.00
Pumps,& Misc. 0.00
253
0.00
0.00
Domestic Hot Water o.00
Right Elevation
Total
Roof
0.00
0.00
Lighting 127:55
254
1,489
127.55
0.00
Receptacle '; 65.67
65.67 ,.
0.00
Process, o.o0
0.00
TOTALS: 558.92
549.76
9.16
Percent better than Standard:
1.6%
1.6% exdi
BUILDING COMPL
GENERAL INFORMATION
Building Orientation
Number of, Stories '.
Number of Systems.
Number of Zones
N 0 deg
Conditioned Floor Area
Unconditioned Floor_Area
Conditioned Footprint Area
fuel TypeI
8,109
sqft.
sqft.
sqft.
1
0
8
8,104
51
Natural Gas
Left Elevation " ,
Orientation Gross Area Glazing Area Glazing Ratio
Front Elevation
N
1 1,594
sqft.
855
sqft.
53.6%
Left Elevation " ,
E
666
sqft.
127
sqft.
19.1%
Rear Elevation
S
967
sqft.
253
sqft.
26.2%
Right Elevation
Total
Roof
(w)
1. 6661
3,894
8,104
sqft.
sqft.
sqft.
254
1,489
sqft.
sqft.
sqft.
38.10/,
Standard Proposed
Lighting Power Density 1.423 W/sqft. 1.423 w/sqft.
Prescriptive Env. Heat Loss 1,358 Btu/h 1,304 Btu/h
Prescriptive Env. Heat Gain 149,020 Bcuth-F 155,339 Btu/h-F
Remarks:
Run Initiation Time: 08/14/07 09:30:09 Run Code: 1187109009
EnergyPro 4.2 by Energysoft User Number: 5950 Job Number: C07079 Page:4 of 20
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1
PROJECT NAME
The Dunes. Retail Center - Retail 1
DATE
8/14/2007
ZONE INFORMATION
`
System Name Zone Name Occupancy T
Type
Floor Inst
Area LPD
ft
(s . (W/sQ1
RCt-`�I�AllowedLPD*s�P,
Cr ies
'Area 'Tailoreds
/sR
oc
Load`s
Tenant A Zone 1 Comp Bldg Restaurant
2,256 '1.20
m %V
Tenant B Zone 1 Retail Sales, Wholesale
1,960 '1.70
�b
i� . "
Tenant C Zone 1 Retail Sales, Wholesale
1,650 '1.70
Tenant D -North Half 'Zone 1 Com• Bldg Restaurant
1,119 `1.20
Tenant D -South Half Zone I Comp Bldg Restaurant
1,124 -1.204, '; p, w `
,4 Y
.��
Yip fi3:.tS?.}C
"5Y'z' a
.?
~ i
W
'
I . C
y es 3
iei ��
KM
i
i
{, k9ke''
YIN
10-1 U11.
U� H
r T"
NVEW11
Notes: 1: See LTG -2 2. See LTG -4-C 3. See LTG -5-C
. (items marked with asterisk, see LTG -2 -C by others) (by others)1r�ti�axL3:�#
EXCEPTIONAL. CONDITIONS COMPLIANCE CHECKLIST
TI... 1.. ..1 .._t_
4. See LTG -6-C
aaaxra� atm € eta�ca
Items above Mr Ug special documentation
m
, ... ,- V-' �r—,aKV 1110 nuillb sprclneu In Ims cnecKnsti. t nese nems require special written justification
and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
submitted.
The HVAC System "York BHP048" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement.
The HVAC System "York BHP036" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement.
The HVAC System "York BP090" is designated as 3 Phase or is Exempted from the NAECA 13 SEER requirement.
The HVAC System "York BP120" is designated as 3 Phase; or is Exempted from the NAECA 13 SEER requirement.
- - -- - - -- - - - - -- ••••, rte• •�• •••a••�o app•Vacn appncallon nave specmcany peen reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Authorized Signature or Stam
Run Initiation i08/14107 00:30:09 Run Code: 1187109009
EnergyPro 4.2 by EnergySoft User Number: 5950 • Job Number: C07079, Page:5 of 20
CERTIFICATE OF COMPLIANCE ENV -1-C,
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 8/14/2007
OPAQUE SURFACES
# Surface
Type
Area
U -Fac.
Insulation
Cay. Cont.
Act.
Azm.
Tilt
Cond:
Status
Joint Appendix
I IV Reference
Location / Comments
1 Wall
. 52
0.074
R-19
-0.0
0
90
New
09-A5
Zone
2 Wall
246
0.074
R-19
R-0.0
180
90
New
09-A5
Zone 1
3 Wall
412
0.074
R-19
-0.0
270
90
New
09-A5
Zone 1
4 Roof
2.256,
0.036
R-30
R-0.0
0
0
New
02-A9
Zone 1
5 Wall
109
0.074
R-19
R-0.0
0
90
New
09-A5
Zone 1
6 lWall
139
0.074
R-19
R-0.0
180
90
New
09-A5
Zone 1
7 Roof
1,960
0.036
R-30
R-0.0
0
0
New
02-A9
Zone 1
8 Wall
83
0.074
R-19
R-0.0
0
90
New
09-A5
Zone 1
9 Wall
165
0.074
R-19
R-0.0
180
90
New
09-A5
Zone 1
10 Roof
1,650
0.036
R-30
R-0.0
0
0
New
02-A9
Zone 1
11 Wall
4961
0.074
R-19
R-0.0
0
90
New
09-A5
Zone 1
12 Wall
2431
0.074
R-19
R-0.0
90
90
New
09-A5
Zone 1
13 Roof
1,1191
0.036
R-30
R-0.0
0
0
New
02-A9
Zone 1
14 lWall
1641
0.074
R-19
R-0.0
180
90
New
09-A5
Zone 1
15 Wall
296
0.074
R-19
R-0.0
90
90
New
09-A5
Zone 1
16 Roof
1 119
0.036
R-30
R-0.0
0
0
New
02-A9
Zone 1
FI-
A, R (Now, Existing, Altered, lien
❑More than or equal to 10,000 sq.tL of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default label Certificate using the default U -tactors from
Standards Table 116-A and B. Certificate shall be filed in the mntr tnes nrnian nffim A,rh,,, rnecm,.af..n -A In .hn m.,-.,..,,...
#
T e
- -
Area U -Fac'
- -- - -- --
SHGC2
Act.
Azm.
Cond.-
I Stat.
w a
Glazing Type
Location/
Comments
1
lWindow
Front
N
48 0.560 NFRC
0.41 NFRC
01
New
SOLARBAN 60 LOW -E
Zone 1
2
Window
Front
N
124 0.560 NFRC
0.41 NFRC
01
New
SOLARBAN 60 LOW -E
Zone 1
3
Window
Front
N
137 0.560 NFRC
0.41 NFRC
01
New
SOLARBAN 60 LOW -E
Zone 1
4
Window
Rear
S
24 0.560 NFRC
0.41 NFRC
1801
New
SOLARBAN 60 LOW -E
Zone 1
5
Window
Ri ht
W
64 0.560 NFRC
0.41 NFRC
2701
New
SOLARBAN 60 LOW -E
Zone 1
6
Window
Right
W
96 0.560 NFRC
0.41 NFRC
2701
New
SOLARBAN 60 LOW -E
Zone 1
7
Window
Right
W
94 0.560 NFRC
0.41 INFRC
2701
New
SOLARBAN 60 LOW -E
Zone 1
8
Window
Front
N
48 0.560 NFRC
0.41 INFRC
01
New
SOLARBAN 60 LOW -E
Zone 1
9
Window
Front
N
124 0.560 NFRC
0.41 INFRIC
0
New
SOLARBAN 60 LOW -E
Zone 1
10 Window
Rear
S
24 0.560 NFRC
0.41 NFRC
180
New
SOLARBAN 60 LOW -E
Zone 1
11 Window
Rear
S
76 0.560 NFRC
0.41 NFRC
180
New
I SOLARBAN 60 LOW -E
lZone 1
12 Window
Rear
S
4 0.560 NFRC
0.41 NFRC
180
New
ISOLARBAN 60 LOW -E
lZone 1
13 Window
Front
N
48 0.560 NFRC
0.41 NFRC
0
New
SOLARBAN 60 LOW -E
lZone 1
rrNa. , ro-.. utnaml rause from Standards, ladle Ni Default Iable from the ACM Manual Appendix, NFRC Labeled value.
2 SHGC Type: 11&B Default Table from Standards, CDG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
#
1
Exterior Shade Type
None
SHGC
0.76
Window
Hgt. Wd.
8.0 3.0
Overhang Left Fin Right Fin
Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t-
4.0 0.1 4.0 4.0
2
None
0.76
8.0 15.0
4.0 0.1
4.0
4.0
3
None
0.76
8.0 10.8
4.0 0.1
4.0
4.0
4
None
0.76
8.0 3.0
4.0 0.1
4.0
4.0
5
None
0.76
6
None
0.76
7
None
0.76
8
None
0.76
3.0 16.0
4.0 0.1
4.0
4.0
9
None
0.76
8.0 9.0
4.0 0.1
4.0
4.0
10
None
0.76
8.0 3.0
4.0 0.1
4.0
4.0
11
None
0.76
12
None
0.76
8.0 2.0
4.0 0.1
4.0
4.0
13
None
10.76 1
8.0 6.0
4.0 0.1
4.0
4.0
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
1:1The
proposed building contains an enclosed space with floor area greater than 25,000 sq.ft, a ceiling height greater than 15 feet and a LPD for general lighting of at least o.5 Wlsq.ft. If this
box Is checked. ENV.d-C ..Int tw ntlon nut -he.. �.,w..,nn......... ..- ------ 1-1- ..___.,_
a ..f+V...ar.
EnergyPro 4.2 by EnergySoft User Number: 5950 Job Number: C07079 Page:6 of 20
CERTIFICATE OF COMPLIANCE ENV -1-C
(PROJECT NAME DATE
The Dunes Retail Center - Retail 1 8/14/2007
OPAQUE SURFACES
MOM
Ins-Ala-rion
Cay. Cont.
ME
EMM
Area U -Fac'
IV Reference
Act.Cond.
Azrn
Stat.
Glazing Type
Location/
Comments
14 Window
Front
N
100 0.560 NFRC
0.41 JNFRC
01
New
SOLARBAN 60 LOW -E
Zone 1
15 Window
Rear
S
24 0.560 NFRC
0.41 INFRIC
1801
New
SOLARBAN 60 LOW -E
Zone 1
16 Window
Rear
S
42 0.560 NFRC
0.41 NFRC
1801
New
SOLARBAN 60 LOW -E
Zone 1
17 Window
Front
N
48 0.560 NFRC
0.41 NFRC
0
New
SOLARBAN 60 LOW -E
Zone 1
18 Window
Front
N
90 0.560 NFRC
0.41 NFRC
0
New
SOLARBAN 60 LOW -E
Zone 1
19 Window
Front
N
88 0.560 NFRC
0.41 NFRC
0
New
SOLARBAN 60 LOW -E
Zone 1
20 lWindow
Left
E
90 0.560 NFRCI
0.41 NFRC
90
New
SOLARBAN 60 LOW -E
Zone 1
21 Window
Rear
S
21 0.560 NFRC
0.41 NFRC
180
New
SOLARBAN 60 LOW -E
Zone 1
22 Window
Left
E
.37 0.560 NFRC
0.41 NFRC
90
New
SOLARBAN 60 LOW -E
Zone 1
More than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default label Certificate using the default 1.1 -factors from
Standards Table 116-A and B. Certificate shall be filed in the contractor's nmiect office durinn mnsmtrtinn and In the huildinn man On nxi-exp, enn<vurti..n
# T e
Area U -Fac'
SHGC2
Act.Cond.
Azrn
Stat.
Glazing Type
Location/
Comments
14 Window
Front
N
100 0.560 NFRC
0.41 JNFRC
01
New
SOLARBAN 60 LOW -E
Zone 1
15 Window
Rear
S
24 0.560 NFRC
0.41 INFRIC
1801
New
SOLARBAN 60 LOW -E
Zone 1
16 Window
Rear
S
42 0.560 NFRC
0.41 NFRC
1801
New
SOLARBAN 60 LOW -E
Zone 1
17 Window
Front
N
48 0.560 NFRC
0.41 NFRC
0
New
SOLARBAN 60 LOW -E
Zone 1
18 Window
Front
N
90 0.560 NFRC
0.41 NFRC
0
New
SOLARBAN 60 LOW -E
Zone 1
19 Window
Front
N
88 0.560 NFRC
0.41 NFRC
0
New
SOLARBAN 60 LOW -E
Zone 1
20 lWindow
Left
E
90 0.560 NFRCI
0.41 NFRC
90
New
SOLARBAN 60 LOW -E
Zone 1
21 Window
Rear
S
21 0.560 NFRC
0.41 NFRC
180
New
SOLARBAN 60 LOW -E
Zone 1
22 Window
Left
E
.37 0.560 NFRC
0.41 NFRC
90
New
SOLARBAN 60 LOW -E
Zone 1
1 U -factor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value.
2 SHGC Type: 116-B Default Table from Standards, CCG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
##
Exterior Shade Type
SHGC
Window Overhang Left Fin Right Fin
Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. Hot. Dist. Len. H t.
14
None
0.76
8.0 6.5 4.0 0.1 4.0 4.0
15
None
0.76
8.0 3.0 4.0 0.1 4.0 4.0
16
None
0.76
8.0 2.0 4.0 0.1 4.0 4.0
17
None
0.76
18
None
0.76
19
None
0.76
8.0 11.0 4.0 0.1 4.0 4.0
20
None
0.76
21
None
0.76
22
None
0.76
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
The proposed building contains an enclosed space with floor area greater than 25,000 sq.ft, a ceiling height greater than 15 feet and a LPD /or general lighting of at least 0.5 W/sq.ft. If this
box Is checked. ENV -4-C must be flned nut whpn cuhmunn� nndp. tt.p n.p�...i..u..e r•.......n......., w-
EnergyPro 4.2 by EnergySoft User Number: 5950 Job Number: C07079 Paoe:7 of 20
CERTIFICATE OF COMPLIANCE MECH-I-C
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 8/14/2007
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation
certificates, and operatinq and maintenance information meet the requirements of Section 10-103(b) and Title 24 Part 6.
STATEMENT OF COMPLIANCE
❑ MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-3-A: Packaged HVAC Systems Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the lactoty and certified with the
commission do not require equipment testing but do require construction inspection.
❑ MECH-5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
This test required If the unit serves 5,000 V of space or less and 25% or more of the ducts are in nonconditioned or semicondidoned space like an
attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
❑ MECH-6-A: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls installed on new or existing packaged systems must be tested.
❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
All new VA fan volume controls installed on new or existing systems must be tested
❑ MECH-8-A: -Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to chilled and hot water systems.
-Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Stufhr.
-Water-loop Heat Pump Controls
Applies to all new waterfoop heat pump systems where the combined loop pumps are greater clan 5 hp.
-Variable Frequency Controls Applies to all new distribution pumps on new variable flow chilled, hydronic heat pump
or condenser water systems where the pumps motors are greater than 5 hp.
Equipment re uirin acceptance testing
EnergyPro 4.2 by EnergySoft User Number: 5950 Job Number: C07079 Page:8 of 20
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 8/14/2007
SYSTEM FEATURES
I I tM UH 5Y51 tM IAG(5)
Number of Systems
MANDATORY MEASURES
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES '
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor. Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
T-24
Section
AIR SYSTEMS Central or Single Zone
Tenant A
Tenant B
Tenant C
2
2
2
Reference on Pians or Specification 1
112(a)
2.20 COP
7.70 HSPF
7.70 HSPF
112(a)
10.6 EER
13.0 SEER / 11.3 EER
13.0 SEER / 11.3 EER
112(b)
Yes
Yes
Yes
112(c), 115(a),
n/a
n/a
n/a
121(b)
No
No
No
121 b
1128 cfm
490 cfm
412 cfm
121 c
No
No
No
121 c
No
No
No
121 c 122(e)
Programmable Switch
Programmable Switch
Pro rammable Switch
122(e)
Heating & Cooling Required
Heating & Cooling Required
Heating & Cooling Required
122(f)
Gravity
Gravity
Gravity
122
n/a
n/a
n/a
123
124
R-4.2
R-4.2
R-4.2
144 a & b
n/a
n/a
n/a
144 a & b
106,177 btuh
56,212 btuh
56,212 btuh
144 a & b
n/a
n/a
n/a
144 a & b
140,200 btuh
72,172 btuh
53,564 btuh
144 c
Constant Volume
Constant Volume
Constant Volume
144 c
144 c
No
No
No
144 d
No
No
No
144 a
No Economizer
No Economizer
No Economizer
144 f
Constant Temp
Constant Temp
Constant Tem
144 (f)
Constant Temp
Constant Temp
Constant Temp
144 k
No
No
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 251% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
EnergyPro 4.2 by EnergySoft User Number: 5950 Job Number: C07079 Page:9 of 20
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
]PROJECTNAME DATE
The Dunes Retail Center - Retail 1 8/14/2007
SYSTEM FEATURES
. AIR SYSTEMS Central or Single Zone
ITEM OR SYSTEM TAG(S) .. Tenant D -North Half Tenant D -South Half
Number of Systems
T-24
MANDATORY MEASURES Section Reference on Plans or Specification t
Heating Equipment Efficiency y
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation .
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones,
t
Pipe Insulation
Duct Insulation
.PRESCRIPTIVE MEASURES
Calculated Heating Capacity z 1.43'2-
Proposed
.432Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212'
` Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer,
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
112(a)
2.20 COP
2.20 COP
112(a)
10.3 EER
10.6 EER
112(b)
Yes
Yes
112(c), 115(a)
n/a
n/a
121(b)
No
No
121 b
763 cfm
766 cfm
121 c
No
No
121 c
No
No
121 c 122(e)
Programmable Switch
Programmable Switch
122(e)
Heating & Cooling Required
Heating & Cooling Require
122(f)
Gravity
Gravity
122
n/a
n/a
123
124
R-4.2
R-4.2
144 a & b
n/a
n/a
144 a & b
53,'089 btuh
53,089 btuh
144 a & b
n/a
n/a
144 a & b
87,918 btuh
68,784 btuh
144 c
Constant Volume
Constant Volume
144 c
144 c
No
No
144 d
No
No
144 a
No Economizer
No Economizer
144 If
Constant Temp
Constant Tem
144 (f)
Constant Temp
C--ronstant Temp
144 k
No
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "NW in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgff; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
�. EnergyPro 4.2 by EnergySoft User Number: 5950 Job Number: C07079 Page: 10 of 20
MECHANICAL VENTILATION MECH-3-C
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 1
8/14/2007
PRESCRIPTIVE REHEAT
LIMITATION Section 144(d))
MECHANICAL VENTILATION Section 121(b)2)
AREA
BASIS
OCCUPANCY
BASIS
VAV MINIMUM
A
B
C
D
E
F
G
H
I
J
K
L
M
N
ZONE/SYSTEM
ti
Nn�
pa
.T.. Of .:
a
fat)
�n,T
� " E
°o
cM
�'��
xD
0
`� °'
Z
c
m3
pQ
� �
m °.
M•,0
tnm
O � �
p
Cr
`G
mfg
xp
�� �
...pp.
o00
�xv
� O �
" D
n»M
T•
'S Dtp
p
N o
p\
0M0
TN
� C �
v H
A
'�Xo
It
a
2Z n
O 0
3
an
-w
r=
Mf-.
coo
to
m
ap
.p+ P
D
rn
D
Zone 1
2,25q
0.38
857
857
1,128
Tenant A
I
Total
857
1,128
Zone 1
1196
0.25
490
490
490
Tenant B
Total
490
490
Zone1
1,650
0.25
412
412
412
Tenant C
Total
412
412
one 1
1,119
0.38
425
425
763
Tenant D -North Half
Total
425
763
one 1
1,124
0.38
427
427
766
Tenant D -South Half
Total
427
766
E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed seating.
H Required Ventilation Air REO'D V.A.1 Is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G).
i Must be greater than or equal to H or use Transfer Air column N to make up the difference.
J Design fan supply cfm Fan CFM x 30%; or
K Condition area ft. s x 04 cfm/ft. s .• or
L Maximum of Columns H J, K or 300 cfm
M This must be less than or equal to Column L and greater that or equal to the sum of Columns H + N.
N Transfer air must be provided where the Required Ventilation Air (column H) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or
equal to the difference between the Required Ventilation Air (column H) and the Design Minimum Air (column M), column H - M.
Ener Pro 4.2 by Ener Soft User Number: 5950 Job Number: C07079 Page: 11 of 20
MECHANICAL EQUIPMENT DETAILS
Part 1 of 2 MECH-5-C
PROJECT NAME
The Dunes Retail Center - Retail 1
Control
DATE
8/14/2007
CHILLER AND TOWER MARY
Type
In Plenum
EfficiencyTons
Buried
PUMPS
Equipment Name
Equipment T e
Q�-[
Tot.
GPM
BHP
Motor
Eff.
Drive
Eff.
Pump
Control
CENTRAL SYSTEM RATINGS
HEATING
•
COOLING
System Name
System Type
Output
Aux.
kW
Eff.
Output
Efficiency
Condition
Status
Economizer Type
York BPO90
Packaged DX
3
85,000
0.0
2.20 COP
89,000
10.6 EER
New
BOILER
York BHP048
Energy I Standby ANK INSUL.
Rated Condition Factor Loss or Ext.
Svstem Name Svstem TVDe Distribution Tvpe QtV Inout ,Vol.Gals.) Status or RE Pilot I R -Val.
Hot Water P mp
Hot Water Pipinq Len th ft
Control
#
HP
Type
In Plenum
Outside
Buried
Add 1/2"
Insulation
CENTRAL SYSTEM RATINGS
HEATING
•
COOLING
System Name
System Type
Output
Aux.
kW
Eff.
Output
Efficiency
Condition
Status
Economizer Type
York BPO90
Packaged DX
3
85,000
0.0
2.20 COP
89,000
10.6 EER
New
No Economizer
York BHP048
Packaged DX
2
45,000
0.0
7.70 HSP
47,000
13.0 SEER/ 11.3 EER
New
No Economizer
York BHP036
Packaged DX
2
45,000
0.0
7.70 HSPF
35,000
13.0 SEER/ 11.3 EER
New
No Economizer
York BP120
Packaged DX
1
85,00
0.0
2.20 COP
120,000
10.3 EER
New
No Economizer
ENVELOPE MANDATORY MEASURES ENV -MM
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 1 8/14/2007
DESCRIPTION
Designer
Enforcement
0 1118(a) Installed Insulating Material shall have been certified by the manufacturer to comply
with the California Quality Standards for insulating material, Title 20, Chapter 4, Article
3.
0 § 118(c) All Insulating Materials shall be Installed In compliance with the flame spread rating
and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2.
0 § 117(a) All Exterior Joints and openings in the building that are observable sources of air
leakage shall be caulked, gasketed, weatherstripped or otherwise sealed.
0 § 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit
and the building, and shall be weatherstripped (except for unframed glass doors and
fire doors).
§ 116(a)1 Manufactured Doors and Windows installed shall have air Infiltration rates not
exceeding those shown in Table Number 1-E. of the Standards. Manufactured
fenestration products must be labeled for U -value according to NFRC procedures.
0 §118(e) Demising Walls in Nonresidential Buildings:
The opaque portions of framed demising walls In nonresidential buildings shall have
Insulation with an Installed R -value of no less than R-13 between framing members.
EnergyPro By EnergySoft User Number: User Job Number: C07079 Page: 13 of 20
MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 1 8/14/2007
DESCRIPTION
Designer
Enforcement
Equipment and Systems Efficiencies
RX §111 Any appliance for which there is a California standard established In the Appliance
Efficiency Regulations will comply with the applicable standard.
R§ 115(a) Fan type central furnaces shall not have a pilot light.
§ 123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees
Fahrenheit, or within HVAC equipment, shall be insulated in accordance with
Standards Section 123.
FV -1 § 124 Air handling duct systems shall be installed and insulated in compliance with
Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards.
Controls
§ 122(e) Each space conditioning system shall be Installed with one of the following:
§ 122(e)1 A Each space conditioning system serving building types such as offices and
manufacturing facilities (and all others not explicitly exempt from the requirements
of Section 112 (d)) shall be installed with an automatic time switch with an
accessible manual override that allows operation of the system during off -hours for
up to 4 hours. The time switch shall be capable of programming different
schedules for weekdays and weekends and have program backup capabilities that
prevent the loss of the device's program and time setting for at least 10 hours if
power is Interrupted; or
F] § 122(e)1 B An occupancy sensor to control the operating period of the system; or
❑ § 122(e)1 C A 4 -hour timer that can be manually operated to control the operating period of the
system.
0 § 122(e)2 Each space conditioning system shall be installed with controls that temporarily
restart and temporarily operate the system as required to maintain a setback
heating and/or a setup cooling thermostat setpoint.
§ 122(8) Each space conditioning system serving multiple zones with a combined
conditioned floor area more than 25,000 square feet shall be provided with Isolation
zones. Each zone: shall not exceed 25,000 square feet; shall be provided with
Isolation devices, such as valves or dampers, that allow the supply of heating or
cooling to be setback or shut off independently of other isolation areas; and shall
be controlled by a time control device as described above.
§ 122(a&b) Each space conditioning system shall be controlled by an individual thermostat
that responds to temperature within the zone. Where used to control heating, the
control shall be adjustable down to 55 degrees F or lower. For cooling, the control
shall be adjustable up to 85 degrees F or higher. Where used for both heating and
cooling, the control shall be capable of providing a deadband of at least 5 degrees
F within which the supply of heating and cooling is shut off or reduced to a
minimum.
X❑ § 122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable
setpoint stops accessible only to authorized personnel.
❑ § 112(b) Heat pumps shall be installed with controls to prevent electric resistance
supplementary heater operation when the heating load can be met by the heat
pump alone.
EnergyPro By EnergySoft User Number: User Job Number: C07079 Page: 14 of 20
MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM
PROJECT NAME DATE
'The Dunes Retail Center - Retail 1 8/14/2007
Description
Designer
Enforcement
Ventilation
[X§
121(e)
Controls shall be provided to allow outside air dampers or devices to be operated at
the ventilation rates as specified on these plans.
§ 122(f)
Gravity or automatic dampers interlocked and closed on fan shutdown shall be
provided on the outside air Intakes and discharges of all space conditioning and
exhaust systems.
§ 122(f)
All gravity ventilating systems shall be provided with automatic or readily accessible
manually operated dampers in all openings to the outside, except for combustion air
openings.
X]
§ 121(f)1
Air Balancing: The system shall be balanced in accordance with the National
Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or
Associated Air Balance Council (AABC) National Standards (1989); or
❑ § 121(02
Outside Air Certification: The system shall provide the minimum outside air as
shown on the mechanical drawings, and shall be measured and certified by the
Installing licensed C-20 mechanical contractor and certified by (1) the design
mechanical engineer, (2) the Installing licenced C-20 mechanical contractor, or (3) the
person with overall responsibility for the design of the ventilation system; or
§ 121(f)3
Outside Air Measurement: The system shall be equipped with a calibrated local or
remote device capable of measuring the quantity of outside air on a continuous
basis and displaying that quantity on a readily accessible display divice; or
§ 121 (f)4
Another method approved by the Commission.
Service
Water Heating Systems
§113(b)2
if a circulating hot water system is Installed, it shall have a control capable of
automatically turning off the circulating pump(s) when hot water Is not required.
§ 113(c)
Lavatories in restrooms of public facilities shall be equipped with controls to limit the
outlet temperature to 110 degrees F.
EnergyPro
By EnergySoft User Number: User Job Number: C07079 Page: 15 of 20
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 8/14/2007
SYSTEM NAME FLOOR AREA
Tenant A 2,256
[ENGINEERING CHECKS ISYSTEM LOAD
Number of Systems
2
Heating System
Output per System
85,000
Total Output (Btuh)
170,000
Output (Btuh/sqft)
75.4
Cooling System
Output per System
89,000
Total Output (Btuh)
178,000
Total Output (Tons)
14.8
Total Output (Btuh/sqft)
78.9
Total Output (sgft/Ton)
152,1
Air System
CFM per System
3,000
Airflow (cfm)
6,000
Airflow (cfm/sqft)
2.66
Airflow (cfm/Ton)
404.5
Outside Air (%)
18.8
Outside Air (cfm/sqft)
0.50
Note: values above given at ARI conditions
:ATING SYSTEM
26.0 OF
Outside Air
1128 cfm
69.8 of
111.0 / 77.6 of
Out—�;1
—
siae Air
1128 cfm
75.6/62.4 of
4.2
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
Heating Coil
COIL COOLING PEAK
COIL HTG. PEAK
CFM
Sensible Latent
CFM
Sensible
3,313
70,522
18,800
546
20,349
0
3,526
1,017
0
0
1,128
42,529
20,484
1,128
52,628
0
0
3,526
1,017
120,1031 39 284 75 012
BPO90 140,200 20,513 106,177
Total Adjusted System Outputiao,2oo 20,513 106,177
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK I Jul 4 m Jan 12 am
105.0 of
Supply Air Ducts
Supply Fan 104.8 of
6000 cfm ROOMS
70.0 of
Return Air Ducts
82.2/65.7OF 55.0/53.7OF 55.0/53.7OF
.' T_� Supply Air Ducts
Cooling Coil Supply Fan 55.6 / 53.9 of
6000 cfm 49.1% R.H. ROOMS
75.0/62.2 of
Return Air Ducts '
User Number: 5950 Job Number: C07079 Pane:16 of 20
1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 8/14/2007
SYSTEM NAME FLOOR AREA
Tenant B 1,960
Number of Systems
1 2
Heating System
Output per System
45,000
Total Output (Btuh)
90,000
Output (Btuh/sgft)
45.9
Cooling System
Output per System
47,000
Total Output (Btuh)
94,000
Total Output (Tons)
7.8
Total Output (Btuh/sgft)
48.0
Total Output (sgftlron)
250.2
Air System
CFM per System
1,600
Airtlow (cfm)
3,200
Airflow (cfm/sqft)
1.63
Airflow (cfm/ron)
408.5
Outside Air (%)
15.3
Outside Air (cfm/sqft)
0.25
Note: values above given at ARI conditions
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
ISensiblel Latent
CFM
I Sensible
2,368
42,835
8,167
313
11,649
0
2,142
582
0
0
490
20,528
8,911
490
22,855
0
0
2,142
582
67,6771 17,0781 F 35,6691
York BHP048 72,172 10,442 56,212
Total Adjusted System Output 72172 1o,aa2 56,212
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug3 m Jan 12 am
EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26.0°F 63.1°F 105.0°F 105.0 OF
77 Supply Air
Ducts
Outside Air YJ
490 cfm �104.8 OF
Heating Coil Supply Fan
3200 cfm ROOMS
69.8 OF 70.0 °F
12.0 / 77.9 OF
) ---V
Outside Air
490 cfm
72.6/61.4 °F '
k Return Air Ducts 4
78.7 / 64.3 OF M 55.0 / 53.9 OF
Cooling Coil
Supply Fan
3200 cfm
55.0 / 53.9 of
Supply Air Ducts
55.6/54.1OF
54.2% R.H. ROOMS
72.0 / 61.2 OF
h Return Air Ducts 11
EnergyPro 4.2 by EnergySoft User Number: 5950 Job Number: C07079 Page:17 of 20 1
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 8/14/2007
SYSTEM NAME FLOOR AREA
Tenant C 1,650
Number of Systems
2
Heating System
Output per System
45,000
Total Output (Btuh)
90,000
Output (Btuh/sqft)
54.5
Cooling System
Output per System
35,000
Total Output (Btuh)
70,000
Total Output (Tons)
5.8
Total Output (Btuh/sgft)
42.4
Total Output (sgftlron)
282.9
Air System
CFM per System
1,200
Airflow (cfm)
2,400
Airflow (cfm/sqft)
1.45
Airflow (cfmrron)
411.4
Outside Air (%)
17.2
Outside Air (cfm/sqft)
0.25
Note: values above given at ARI conditions
26.0 of
0
Outs
412 cfm
73.8 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
ICOILHTG.PEAK
CFM
Sensible Latent
1CFM1
Sensible
1,665
33,671
6,875
287
9,484
0
1,684
474
0
0
412
16,391
7,527
412
20,990
0
0
1,684
474
53,4401 14 402 31 423
BHP036 53,564 8,823 56,212
Total Adjusted System Output 53,564 8,823 56,212
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK I Jul 3pml 1 Jan 12 am
65.60F N 105.00F
Heating Coil
105.0 OF
Supply Air Ducts
Supply Fan 104.8 of
2400 cfm ROOMS
74.0 OF
Return Air Ducts
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Coolin Peak
112.0/77.9 OF 81.1 /65.2 OF 55.0/53.8 OF 55.0/53.8 OF
Supply Air Ducts
Outside Air
412 cfm Cooling Coil Supply Fan 55.7 / 54.0 of
2400 cfm 50.6% R.H. ROOMS
74.7/62.10F 74.0/61.8 OF
Return Air Ducts '
EnergyPro 4.2 by EnergySoft User Number: 5950 Job Number: C07079 Paae:18 of 20
r
1HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 8/14/2007
SYSTEM NAME FLOOR AREA
Tenant D -North Half 1,119
26.0 OF
1�
Outside Air
763 cfm
69.9 OF
12.0 / 77.9 OF
Outer v
side Air
763 cfm
72.4/61.5 OF
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
.Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEA
I COIL HTG. PEAK
CFM
I Sensiblel Latent
I CFM
I Sensible
2,114
38,239
12,716
321
11,963
0
1,912
598
0
0
763
32,113
13,460
763
35,612
0
0
1,912
598
74 18 26 176 F7748 771
York BP 120 87,918 18,864 53,089
Total Adjusted System Output87,918 18,864 53,089
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 3 prn Jan 12 am
RIGS (Airstream Tei
61.50F fi5.7 105.00F
Heating Coil
Supply Fan
4000 cfm
105.0 OF
-� Supply Air Ducts
104.9 OF
ROOMS
70.0 OF
h Return Air Ducts `i
r%,nrsvMr-i r 11Ub (Airstream f emperatures at
• 80.0/65.1OF. 55.0/53.9 OF
Cooling Coil
Supply Fan
4000 cfm
55.0 / 53.9 OF
-4 Supply Air Ducts
55.4 / 54.0 of
54.9% R.H. ROOMS
72.0 / 61.3 OF
h Return Air Ducts 'I
I ' EnergyPro 4.2 by EnergySoft User Number: 5950 Job Number: C07079 Paae:19 of 20 1
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
The Dunes Retail Center - Retail 1 8/14/2007
SYSTEM NAME FLOOR AREA
Tenant D -South. Half 1,124
Number of Systems
1
Heating System
Output per System
85,000
Total Output (Btuh)
85,000
Output (Btuh/sqft)
75.6
Cooling System
Output per System
89,000
Total Output (Btuh)
89,000
Total Output (Tons)
7.4
Total Output (Btuh/sqft)
79.2
Total Output (sgft/Ton)
151.6
Air System
CFM per System
3,000
Airflow (cfm)
3,000
Airflow (cfm/sqft)
2.67
Airflow (cfm/Ton)
404.5
Outside Air (%)
25.5
Outside Air (cfm/sqft)
0.68
Note: values above given at ARI conditions
26.0 OF
?�
Outside Air
766 cfm
69.9 of
58.7 of
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
IICOILHTG. PEAK
CFM
Sensiblel Latent
11CFM1
Sensible
1,567
28,342
12,773
126
4,699
0
1,417
235
0
0
766
32,257
12,842
766
35,825
0
0
1,417
1 235
63,465 25 615 F77470:9915
York BP090 68,784 12,153 53,089
Total Adjusted System Output x8,784 12,153 53,os9
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug3 m Jan 12 am
,earn Temperatures at Time of Heating Peak)
105.0 of 105.0 of
Heating Coil
Supply Fan
3000 cfm
in Return Air Ducts `S
Supply Air Ducts
104.9 of
ROOMS
70.0 of
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Coolin Peak
112.0/77.9OF 82.6/66.4OF 55.0/53.8OF 55.0/53.8OF
Q _ Supply Air Ducts
Outside Air
766 cfm }
Cooling Coil Supply Fan 55.4 / 54.0 of
3000 cfm 55.9% R.H. ROOMS
72.4/61.8 of 72.0/61.6OF
Return Air Ducts
I EnergyPro 4.2 by EnergySoft User Number: 5950 Job Number: C07079 Page:20 of 20 1
r
'
LEGACY REPORT
NER-574
Reissued November 1, 2005
ICC Evaluation Service, Inc. lUmble-Regional
Office ■ 5360 Worimm W Road, Whiter. Caf forma 90601 ■ (562) 6990543
www.ICC�S.Org Regional Office ■ 900 Montclair Road, Suite A, Birmingham, Alabama'35213 ■ (205) 599.9800
Regional Office ■ 4051 West Flossmoor Road, Country Club Hills, Illinois 60478 ■ (708) 799-2305
t
s
.
Legacy report on the 2000 International Building Code®, the BOLA® National Building Code/1999, the 1999 Standard
Building Code®, the 1997 Uniform Building Code'*', and the 2000 International Residential Code®
DIVISION 09—FINISHES
Dens -Glass Gold sheathing is manufactured to conform tothe
<
Section 09250—Gypsum Board
applicable physical requirements of ASTM C 79 for gypsum
sheathing board and has the following characteristics:
'
G -P GYPSUM CORPORATION
r
2861 MILLER ROAD
5/8 inch (15.9 mm)
F
DECATUR, GEORGIA 300364036/2
inch (12.7 mm) thick Dens -Glass
WEBSITE: www.cip.com/gypsum
thick Dens -Glass Gold Fireguard
Gold Gypsum Type X Gypsum
1.0 SUBJECT
Sheathing Sheathing
Dens=Glass®Gold Sheathing: '/2 inch (12.7 mm) thick Dens- .
Thickness '/2" t %2" 5/e^ t '/32"
Glass® Gold Sheathing and 51, inch (15.9 mm) thick Dens -
Glass® Gold Fireguard® Type X Sheathing
Weight,
lbs/m sq. ft.,
a
2.0 PROPERTY FOR WHICH EVALUATION IS SOUGHT
nom. 1900 2500
2.1 Equivalent performance to ASTM C 79 (gypsum
Width, nom, 4 ft. t'/8" 4 ft. t'/8"
sheathing)
Length, std. 8 ft.;10 ft. t'/4" 8 ft.;10 ft. t'/,"
2.2 Noncombustibility
Color Yellow Yellow
2.3 Fire resistance
Edges Square Square
5'
2.4 Structural (racking strength)
Core Water Resistant Water Resistant
3.0 DESCRIPTION
Surfacing,
Dens -Glass Gold sheathing is a noncombustible, resinous
Face Resinous Coated Resinous Coated
coated, glass fiber mat faced, water-resistantgypsum
Glass Fiber Mat Glass Fiber Mat
sheathing. Dens -Glass Gold is mechanically attached to
Surfacing,
structural. framing as a single ply backing for exterior
surfacing or wall covering materials on buildings of all
Back Glass Fiber Mat Glass Fiber Mat
construction types.
"R" Value
Dens -Glass Gold sheathing is available in two varieties; ".
(hr ft2.°F/Btu)'
2
inch (12.7 mm) thick Dens -Glass Gold Gypsum Sheathing
(ASTM C 518) 0.56 not provided
and 518 inch (15.9 mm) thick bens -Glass Gold Fireguard Type
Permeance
X Gypsum She
CIT74�
.(ASTM E 96) 23.1 Perms 12.4 Perms
units:
BUILsl
1 inch = 25.4 mm.
1 foot = 304.8 mm
1 hr-ftz-°F/Btu = 0.176 m2.M
1 Perm = 57 ng/(Pa-s•m2)
DATE
ICC -ES legacy repos are not to be construed as representing aesthetics or any'other•attributes not specifically addressed, nor are they to be construed 41
an endorsement ofthe subject of the report ora recommendation
for its use. There is no warranty by ICC Evaluation Service, Inc., express or implied, as to
any finding or other matter in this report, or as to any product.covered by the report.
V,
Copyright ° 2005
Page 1 of 3
7q -w 1070 -/zo /ll
Page 2 of 3
NER-574
When tested in accordance with ASTM E 84,.the'Dens-Glass
4.3 Application to Metal Stud Curtain Walls (for
Gold sheathing demonstrated a flamespread index of 25 or
Transverse Wind Load Resistance)
less and a smoke=developed index of 450 or less.
For an allowable transverse wind load pressure of 21.7 psf
When tested in accordance with ASTM E 136, the Dens-
(1.04 kN/mZ), Dens -Glass Gold shall be installed with the long
Glass Gold sheathing was determined to be noncombustible.
dimension in the vertical or horizontal direction, mechanically
`
When tested in accordance with an ASTM E 119, '/Z inch
fastened to minimum 20 gauge steel framing. The stud
spacing shall not exceed 16 inches (406 mm) o.c. for'/2 inch
(1.2.7 mm) thick Dens -Glass Gold sheathing demonstrated
thick Dens -Glass and 24. inches (609 mm) o.c. for 5/e inch
that It met the code requirements for use as a 15 -minute
thick Dens -Glass. Fasteners shall be 1 inch to 11/4 inch (25.4
thermal barrier for protecting foam plastics which might be
to 31.8 mm) long No. 6 Type S-12 bugle -head, self -tapping,
installed as a part of an exterior wall covering assembly.
rust resistant screws spaced 8 inches (203 mm) o.c. along
When tested in accordance with ASTM E 119, 5/6 inch (15.9
the edges and 8 inches (203 mm) o.c..at the intermediate
mm) thick Dens -Glass Fireguard Type X sheathing applied to
supports. Screws shall be a minimum edge distance of 3/e
a partition in a single -layer nail application on each face of
inches (9.5 mm).
load-bearing wood framing members provided a one hour fire
s
resistance, thus qualifying it for the "Type X' designation of
5.0 IDENTIFICATION
ASTM C 79.
j
4.0 INSTALLATION
Each bundle or package of Dens -Glass Gold sheathing shall
bear the manufacturer's name and/or trademark, the NES
4.1 General - Application to Wood Stud Walls and
logo. and evaluation report number, NER-574 for field
identification.
is
Metal Stud Curtain Walls
6.0 EVIDENCE SUBMITTED
Installation of Dens -Glass Gold sheathing shall be in
accordance with ASTM C 1280, Application of Gypsum
6.1 Manufacturer's descriptive literature and installation
Sheathing, the manufacturer's installation instructions, and
instructions.
this report. Exterior surfacings or wall coverings shall be
provided over the Dens -Glass Gold sheathing as weather
6.2 Report of physical and racking load tests conducted
protection. Weather -resistant membranes .(No.15 asphalt-
on '/y inch (12.7 mm) thick Dens -Glass Gold
saturated felt or other approved material) shall be provided
sheathing, prepared byTimberProducts Inspection,
over the Dens -Glass Gold sheathing before attaching such
Project No. 85-03, Report No. 1, dated February 4,
surfacings or wall coverings, when required bythe.applicable
1985, signed by Walter W. Boyles.
building code. Such coverings or surfacings are beyond the
scope of this report.
6.3 Report on various physical tests conducted on'/2
.The installation instructions within this report will govern, if
inch (12.7 mm) thick Dens -Glass Gold sheathing,
prepared by Timber Products Inspection, Project
there are any conflicts with the manufacturer's instructions.
No. 89-018, Report No. 1, dated June 21, 1989,
The manufacturer's published installation instructions and this
signed by Walter W. Boyles and Franklin Holmes.
report shall be strictly adhered to and a copy of these
instructions shall be available at all times on the jobsite during
6.4 Test report in accordance with ASTM C . 79,
installation:
prepared by Timber Products Inspection, Project
4.2 Application to Wood Stud Walls (for Racking
No. 86-08, Report No. 1, dated August 22, 1986,
signed by Walter W. Boyles.
Resistance)
For resisting wind and seismic loads, the V, inch (12.7 mm)
6.5 Test report in accordance with ASTM C 79,
prepared by Timber Products Inspection, Project
thick Dens -Glass Gold sheathing is assigned an allowable
No. 89-018, Report No. 2, dated June 21, 1989,
racking value of 99 plf (1.44 kN/m) when applied to wood stud
signed by Walter W. Boyles.
walls as noted in the following paragraph. The. maximum
height -length ratio shall not exceed 1.5:1 to be considered as
6.6 Test report in accordance with ASTM E 84,
a shear wall segment. Marginal. studs and plates shall be
anchored to resist design forces. Shear walls using Dens-
prepared by Commercial Testing Company, Report
Glass Gold sheathing shall not be used to resist forces
No. 32983, dated February 6, 1985, signed by
Jonathan Jackson.
imposed by masonry and concrete walls. See Section 7.5 of
this report for allowable load adjustments or restrictions
6.7 Test report in accordance with ASTM E 84,
applicable to certain seismic regions.
prepared by Commercial Testing Company, Report
The Dens -Glass Gold sheathing shall be applied solidly to the
No. 67324, Test No. 2024-7678, dated May 5,1989,
wall with the long dimension in the vertical direction with all
signed by Jonathan Jackson.
edges backed by framing members. Application shall be by
the use of nails: 11 gauge, /18 inch (11.1 mm) head, "/Z inch
6.8 Test report in _ accordance with ASTM E 136,
long (38.1 mm) for /inch. (12.7 mm) thickness; and 1% inch
prepared by Commercial Testing Company, Report
(44.5 mm) long for /B inch (15.9 mm) thickness, spaced 4
No. 67576, Test No. 2075-9961, dated October 18,
inches (101 mm) o.c. on the edges and 8 inches (203 mm)
1989, signed by Jonathan Jackson.
o.c. at the intermediate supports. Nails shall have a minimum
edge distance of /e inch (9.5 mm). The stud spacing shall not
6.9 Test report in accordance with ASTM E 119, .
exceed 16 inches (406 mm) o.c. for V, inch (12.7 mm) thick
prepared by Commercial Testing Company, Report
Dens -Glass Gold sheathing and 24 inches (609 mm) o.c. for
No. 32984, dated February 6, 1985, signed by
% inch (15.9 mm) thick Dens -Glass Gold Fireguard Type X
Grady Gilbert, P.E.
sheathing.
Page 3'of 3
6.10 Test report in accordance with ASTM E 119,
prepared by Wamock Hersey Intemational Inc:, File
No. WHI-495-0702 and WHI-495-0703, Job No.
495-0589, dated August 711985, signed by George
E. Meyer, P.E.
6.11 Test report in accordance with ASTM C 518,
prepared by Commercial Testing Company, Report
No. 32982, dated February 7, 1985; signed by
Jonathan Jackson.
6.12 Report of wet racking tests conducted on '/2 inch
(12.7 mm) thick Dens -Glass Gold sheathing in
accordance with ASTM E. 72, prepared by Timber
Products Inspection, Project No. 85-03, Report No.
3; dated June 24, 1985, signed by Walter W..
Boyles.
6.13 Report of racking tests conducted on conditioned
samples (95 •F and 50% RH) of/2 inch (12.7 mm)
thick Dens -Glass Gold sheathing. in accordance in
accordance with ASTM E 72, prepared by Timber
Products Inspection, Project No. -89-034, ReportNo.
1, dated September 22, 1989, signed by Walter W.
Boyles.
NER-574
submitted to the building official documenting that
the Dens -Glass® Gold sheathing and its fastening
methods are adequate under wind loads of the
applicable building code.
Exception: When installed to steel framing
as noted in Section 4.3 of this report, Dens -
Glass Gold is permitted in applications
where design wind pressures do not exceed
21.7 psf (1.04 kN/m2).
7.5 Exterior stud walls shall be braced as required by
the applicable code.
6.14 Report of tests conducted in accordance with ASTM
E 96, prepared by Timber Products Inspection: 7.6
• Report No. 93-017, dated October 25,1993,
signed by Steve Standell and Diane Michael.
Report_ No. 94-017, dated July 14, 1994,
signed by. Steve Standell.
6.15 Report on testing conducted in accordance with
ASTM E 330, prepared by Timber Products 7.7
Inspection, Project No. 89-047, dated January 12,
1990, signed by Walter W. Boyles.
1.0 CONDITIONS OF USE
The ICC -ES Subcommittee for the National Evaluation
Service, Inc. finds that Dens -Glass Gold sheathing is an
acceptable alternative material, product or method of
construction to those specified in the 2000 International
Building Code®, the BOCA® National Building Code/1999, the
1999 Standard Building Code®, the.1997 Uniform Building
Coder"', and the 2000 International Residential Code®subject .
'to the following conditions:
7.1 The installation instructions given in this report and
those published by G -P Gypsum shall be strictly
adhered to.
7.2 The Dens -Glass Gold sheathing shall be protected
from weather by an exterior surfacing or covering
material approved by the local.building official. No
exterior surfacing or covering listing is granted or
implied by this report.
7.3' Dens -Glass Gold sheathing shall not be used as a
nailing base and any mechanical attachments of.
exterior coverings shall be made directly to the
studs.
7.4 Exterior surfacings may be adhered to Dens -Glass
Gold sheathing when approved by the local building .
official. When the Dens -Glass Gold is not covered
by wall covering mechanically attached directly to
the studs, structural calculations, signed and sealed
by a registered design professional, shall be
Exception: In seismic regions where the
applicable building code permits the use of
shear. walls constructed using gypsum
sheathing, wood stud walls employing '/2
inch (12.7 mm) thick Dens -Glass Gold
sheathing are permitted to be designed as
engineered shear walls in accordance with
the provisions of this report. Any reductions
in the allowable loads for gypsum sheathing
employed in certain seismic regions which
are noted in the applicable building code
shall be applied to the allowable load noted
in this report.
Dens -Glass Gold sheathing shall be kept dry prior
to installation; stored off the ground and under
protective covering. Should the boards become
wet, they shall be allowed. to dry prior to installation.
Once installed, the Dens -Glass Gold sheathing shall
be covered with an exterior surfacing or covering.
This report is subject to periodic re=examination. For
information on the current status of this report,
contact the ICC -ES.