08-0640 (RC) Title 24
TITLE 24 REPORT Title 24 Report for: Cafe Posada Restaurant TI 79-630 HWY 111 Suite #103 La Quinta, CA 92253 Project Designer: Michael Hurst Architect 78120 Calle Estado #207 La Quinta, CA 92253 760-799-3729 Report Prepared By: Gina Rose EQS, Inc. 42-280 Beacon Hill #D-3 Palm Desert, CA 92211 (760) 674-2345 Job Number: Date: 7/3/2008 CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTION DATE ger I Il JUL 0 7 2008 The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC www.energysoft.com. EnergyPro 4.4 by EnergySoft Job Number: User Number: 5862 A •t Orr lGF-1 TABLE.OF CONTENTS Cover Page 1 Table of Contents 2 Nonresidential Performance Title 24 Forms 3 Form ENV-MM Envelope Mandatory Measures 17 Form LTG-MM Lighting Mandatory Measures 18 Form MECH-MM Mechanical Mandatory Measures 19 HVAC System Heating and Cooling Loads Summary 21 Room Load Summary 22 EnergyPro 4.4 by EnergySoft Job Number: User Number: 5862 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1 PROJECT NAME Cafe Posada Restaurant TI This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the DATE 7/3/2008 PROJECT ADDRESS 79-630 HWY 111 Suite #103 La Quinta DOCUMENTATION AUTHOR DATE OF PLANS DT3Z6 PRINCIPAL DESIGNER - ENVELOPE Michael Hurst Architect TELEPHONE 760-799-3729 Building Permit # - DOCUMENTATION AUTHOR EQS, Inc. TELEPHONE (760) 674-2345 Checked by/Date Enforcement Agency Use GENERAL INFORMATION This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation preparer hereby certifies that the documentation is accurate and complete. DOCUMENTATION AUTHOR DATE OF PLANS DT3Z6 Gina Rose BUILDING CONDITIONED FLOOR AREA 2,340 Sq.Ft. CLIMATE ZONE 15 BUILDING TYPE ® NONRESIDENTIAL HIGH RISE RESIDENTIAL HOTEL/MOTEL GUEST ROOM PHASE OF CONSTRUCTION ❑ NEW CONSTRUCTION F-] ADDITION ❑ EXISTING + ADDITION/ALTERATION STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation preparer hereby certifies that the documentation is accurate and complete. DOCUMENTATION AUTHOR SIGNAT RE DT3Z6 Gina Rose The Principal Designer hereby certifys that the proposed bui ding design represented in this set of construction docume is i consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116, through 118, and 140, 142, 143 or 149 of Title 24, Part 6. ENV. LTG. MECH. 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or Lar alicensed architect M F1 F-1 2. 1 affirm that.I am eligible under the provisions of Division 3 of the Business and Professions Code Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. M F] 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.) ENVELOPE COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures ENV -1 Requir d Forms PRINCIPAL ENVELOPE DESIGNER - NAMES IG U LIC. NO. DAT Michael Hurst Architect LIGHTING COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures T -1, LTG -2, LTG -3 Required Form PRINCIPAL LIGHTING DESIGNER - NAME LIC. NO. DAT Michael Hurst Archtitect jS32NA=TRE U C ft MECHANICAL COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures CH -1 MECH-2 MECH-3 MECH-5 Required F ms PRINCIPAL MECHANICAL DESIGNER - NAME GNAT E LIC. NO. DATE Michael Hurst Architect G%Oct 6 `" EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: - Paae:3 of 22 1 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 PERF -1 PROJECT NAME Cafe Posada Restaurant TI DATE 7/3/2008 ANNUAL TDV ENERGY USE SUMMARY kBtu/s ft- r Standard ENERGY COMPONENT Design Space Heating 2.49 Space Cooling 292.77 Indoor Fans 0.00 Heat Rejection 0.00 Pumps & Misc. 0.00 Domestic Hot Water 50.21 Lighting 79.61 Receptacle 48.21 Process 0.00 TOTALS: 473.28 Percent better than Standard: Proposed Design Compliance Margin IQ standard_ �.Pr°posad 2.11 0.38 Sp-H.ft 229.01 63.75 '5pae0aokv '"'°° -- _ 0 20 40 60.80 100120 140 160 180 200 220 240 260 280 ketulsgft-yr 0.00 0.00 0.00 0.00 H�tR°'°""' 0.00 0.00 P -k - &Mies 43.79 6.42 DHW 89.69 -10.08 , 09hU'a ReCepCade 48.21 0.00 0.00 0.00 P`- 412.82 60.47 process) 12.8% ( 12.8% excluding BUILDING COMPLIES GENERAL INFORMATION Building Orientation Number of Stories Number of Systems Number of Zones (N)Odeg Conditioned Floor Area Unconditioned Floor Area Conditioned Footprint Area Fuel Type 2,340 sqft, sqft. sqft. 1 0 2 2,340 11 Natural Gas Orientation Front Elevation N Left Elevation (E) Rear Elevation S Right Elevation I (W)i Total Roof Gross Area sqft. sqft. sqft. sqft. sqft. 1 sgft.sgft. Glazing Area Glazing sqft. sqft. sqft. sqft. sqft. Ratio 400 0 0.0% 0 0 0.0% 400 0 0.0% 670 0 1 0.00/6 1,470 0 0.0% 2,340 E0.0% Standard Proposed Lighting Power Density 1.200 w/sgft. 1.352 w/sgft. Prescriptive Env. Heat Loss 269 Btu/h 193 Btu/h Prescriptive Env. Heat Gain 20,887 Btu/h-F 18,909 Btu/h-F Remarks: Standard Building (Compliance) Run Initiation Time: 07/03/08 10:14:18 Run Code: 1215105258 EnergyPro 4.4 by Energysoft User Number: 5862 Job Number: Page:4 of 22 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 Of 3 PERF -1 PROJECT NAME Cafe Posada Restaurant TI DATE 7/3/2008 ZONE INFORMATION System Name Zone Name Occupancy Type Floor Area (sqft.) Inst. LPD (W/sf)1 Ctrl. Credits (W/sf)2 Allowed LPD Proc. Loads (W/sf) Area Tailored (W/S3 (W/S4 Existing 7-1/2 Ton Unit Restaurant Comp Bldg Restaurant 2,340 1.15 Notes: 1. See LTG -2-C 2. See LTG -4-C 3. See LTG -5-C (items marked with asterisk, see LTG -2 -C by others) (by others) 4. See LTG -6-C Items above require special documentation EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. The DHW System "A O Smith Water Products BTH 120" is a Large Gas water heater with Pilot Loss = 0 btuh. The HVAC System "Existing 7-1/2 Ton Unit" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A. The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant. or EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:5 of 22 1 CERTIFICATE OF COMPLIANCE ENV -1 -C PROJECT NAME DATE Cafe Posada Restaurant TI 7/3/2008 OPAQUE SURFACES # Surface Type Area U -Fac. Insulation Cay. Cont. Act. Am. Tilt Cond' Status Joint Appendix IV Reference Location / Comments 1 Wall 67 0.074 R-19 R-0.0 270 90 Existing 09-A5 Restaurant 2 Roof 2,34 0.036 R-30 R-0.0 0 0 Existin 02-A9 Restaurant 3 Wall 40C 0.074 R-19 R-0.0 0 90 Existing 09-A5 Restaurant 4 Wall 40C 0.074 R-19 R-0.0 180 90 Existing 09-A5 Restaurant Restaurant 5 Window Right 0 0.670 NFRC 0.52 NFRC 270 Existing Existing Window/Doors Restaurant 6 Window Right 0 0.670 NFRC 0.52 NFRC 270 Existing Existing Window/Doors Restaurant 7 lWindow Front N 0 0.670 NFRC 0.52 NFRC 0 Existing Existing Window/Doors Restaurant 8 Window Front N 0 0.670 NFRCI 0.52 NFRC 0 Existing Existing Window/Doors Restaurant 9 Window Front N 0 0.670 NFRC 0.52 NFRC 0 Existing Existing Window/Doors Restaurant 10 Window Front N 0 0.670 NFRC 0.52 NFRC 0 Existing Existing Window/Doors Restaurant 11 Window Front N 0 0.670 NFRC 0.52 NFRC 0 Existing Existing Window/Doors Restaurant N, E, A, R (New, Existing, Altered, Removed) FENESTRATION SURFACES More than or equal to 10,000 sq.ft.of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U -tactors from Standards Table 116-A and B. Certificate shall be filed in the contractors oroiect office dudno construction and in the buildinc manacefs office after construction # lTvoe # Exterior Shade Type Window Overhang Left Fin Right Fin SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t. Area U -Fac' SHGC2 Act. Am. Cond. Stat. Glazing Ty e Location/ Comments 1 Window Right 6 None 0 0.670 NFRC 0.52 NFRC 270 Existing Existing Window/Doors Restaurant 2 Window Right 0.76 0 0.670 NFRC 0.52 NFRC 270 Existing Existing Window/Doors Restaurant 3 Window Right W 0 0.670 NFRC 0.52 NFRC 270 Existinq Existing Window/Doors Restaurant 4 Window Right 0 0.670 NFRC 0.52 NFRC 270 Existinq Existin Window/Doors Restaurant 5 Window Right 0 0.670 NFRC 0.52 NFRC 270 Existing Existing Window/Doors Restaurant 6 Window Right 0 0.670 NFRC 0.52 NFRC 270 Existing Existing Window/Doors Restaurant 7 lWindow Front N 0 0.670 NFRC 0.52 NFRC 0 Existing Existing Window/Doors Restaurant 8 Window Front N 0 0.670 NFRCI 0.52 NFRC 0 Existing Existing Window/Doors Restaurant 9 Window Front N 0 0.670 NFRC 0.52 NFRC 0 Existing Existing Window/Doors Restaurant 10 Window Front N 0 0.670 NFRC 0.52 NFRC 0 Existing Existing Window/Doors Restaurant 11 Window Front N 0 0.670 NFRC 0.52 NFRC 0 Existing Existing Window/Doors Restaurant (1 LI -factor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value. (2 SHGC Type: 116-8 Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING # Exterior Shade Type Window Overhang Left Fin Right Fin SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t. 1 None 0.76 2 None 0.76 3 None 0.76 4 None 0.76 5 None 0.76 6 None 0.76 7 None 0.76 8 None 0.76 9 None 0.76 10 None 0.76 11 None 0.76 MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES 1:1The proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 142, a ceiling height greater than 15 feet, and an LPD for general lighting of at least 0.5 W/R2. See Section 143(c). If this box Is checked, ENV -4-C must be filled out. when submitting under the Prescriptive Compliance Approach. EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Paoe:6 of 22 1 CERTIFICATE OF COMPLIANCE (Part 1 of 3) LTG -1 -C (PROJECT NAME DATE Cafe Posada Restaurant TI 7/3/2008 INSTALLED INDOOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0 LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) _ 0 UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0 ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES ❑ COMPLETE BUILDING METHOD (From LTG -5-C) ALLOWED ❑ AREA CATEGORY METHOD (From LTG -5-C) WATTS ❑ TAILORED METHOD (From LTG -5-C) ALLOWED LIGHTING POWER 3,164 ALTERNATE COMPLIANCE ❑X PERFORMANCE METHOD ❑ COMMMON LIGHTING SYSTEM (From LTG -8-C) ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C o MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS CONTROL LOCATION (Room #) CONTROL IDENTIFICATION CONTROL TYPE Time Switch, Dimming, etc.) Check if SPACE CONTROLLED IDaylightingl NOTE TO FIELD EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Paae:7 of 22 1 INSTALLED WATTS INSTALLED LIGHTING, CONDITIONED SPACES (From LTG -2-C) 2,696 PORTABLE LIGHTING (From LTG -3-C) 468 LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG -4-C) 0 CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 3,164 INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0 LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) _ 0 UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0 ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES ❑ COMPLETE BUILDING METHOD (From LTG -5-C) ALLOWED ❑ AREA CATEGORY METHOD (From LTG -5-C) WATTS ❑ TAILORED METHOD (From LTG -5-C) ALLOWED LIGHTING POWER 3,164 ALTERNATE COMPLIANCE ❑X PERFORMANCE METHOD ❑ COMMMON LIGHTING SYSTEM (From LTG -8-C) ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C o MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS CONTROL LOCATION (Room #) CONTROL IDENTIFICATION CONTROL TYPE Time Switch, Dimming, etc.) Check if SPACE CONTROLLED IDaylightingl NOTE TO FIELD EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Paae:7 of 22 1 CERTIFICATE OF COMPLIANCE (Part 3 of 3) LTG-1-C PROJECT NAME Cafe Posada Restaurant TI DATE 7/3/2008 Designer: This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for lighting systems. The designer is required to check the boxes by all acceptance tests that apply and list all equipment that require an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Building Departments: Before an occupancy. permit is granted for a newly constructed building or space, or a new lighting system system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate of Acceptance, LTG-1-A, Forms shall be submitted to the building department that: A. Certifies plans, specifications, installation certificates, and operating and maintenance information meet the requirements of§ 10-103(b) and Title 24 Part 6. Test Descri tion Test Performed By: ❑ LTG-2-A: Lighting Control Acceptance Document - Occupancy Sensor Acceptance - Manual Daylight Controls Acceptance - Automatic Time Switch Control Acceptance Equipment requiring acceptance testing ❑ LTG-3-A: Automatic Daylighting Controls Acceptance Document Equipment requiring acceptance testing I EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Pape:8 of 22 1 CERTIFICATE OF COMPLIANCE MECH-1-C PROJECT NAME Posada Restaurant TI DATE F Designer: This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. ,Building Departments: SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate 'of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation certificates, and operatinq and maintenance information meet the reauirements of Section 10-103(b) and Title 24 Part 6. STATEMENT OF COMPLIANCE ❑ MECH-2-A: Ventilation System Acceptance Document -Variable Air Volume Systems Outdoor Air Acceptance -Constant Air Volume Systems Outdoor Air Acceptance Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. ❑ MECH-3-A: Packaged HVAC Systems Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. ❑ MECH-4-A: Air -Side Economizer Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the commission do not require equipment testing but do require construction inspection. ❑ MECH-5-A: Air Distribution Acceptance Document Equipment requiring acceptance testing This test required If the unit serves 5,000 R2 of space or less and 25% or more of the ducts are in nonconditioned or semiconditioned space like an attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or replace the packaged unit. ❑ MECH-6-A: Demand Control Ventilation Acceptance Document Equipment requiring acceptance testing All new DCV controls installed on new or existing packaged systems must be tested. ❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document Equipment requiring acceptance testing All new VA fan volume controls installed on new or existing systems must be tested ❑ MECH-8-A: -Hydronic System Control Acceptance Document -Variable Flow Controls Applies to chilled and hot water systems. -Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header. -Supply Water Temperature Reset Controls Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Btulhr. -Water-loop Heat Pump Controls Applies to all new waterfoop heat pump systems where the combined loop pumps are greater than 5 hp. -Variable Frequency Controls Applies to all new distribution pumps on new variable flow chilled, hydronic heat pump or condenser water systems where the pumps motors are greater than 5 hp. Equipment re uirin acceptance testing EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:9 of 22 INDOOR LIGHTING SCHEDULE (Part 1 of 2) LTG -2-C PROJECT NAME Cafe Posada Restaurant TI INSTALLED LIGHTING POWER FOR CONDITIONED SPACES I11L•�i=1 7/3/2008 Luminaire Lamps/Ballasts Installed Watts C D E F G H I J Name Type Description �w -03 �� �3c 3 3 3 �ycr _..0 m cm ° w� 3mw -� N cdc 3.tv 3 :3 0' m _.� m `, c 3v �(D x _ N m O m n dm cn - ' Yes No r Z 3• � 0 =1 y�Q D- - (D y G)�� dm x cx— 41 CD n (1) 6" Circline 1 32 32.0 X 2 64 (2) 4 ft Fluorescent T12 ES EIecAO 2 27 2.0 56.0-&— 4 224 (4) 4 ft Fluorescent T12 ES + MagEE 40T 2/ES Plus 4 21 2.0 86.0 X 281 2,408 PAGE TOTAL 2 696 BUILDING TOTAL (sum of all pages) 2,696 PORTABLE LIGHTING (From LTG -3-C) 468 CONTROL CREDIT (From LTG -4-C) D ADJUSTED ACTUAL WATTS 3 164 EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Pape: 10 of 22 1 PORTABLE LIGHTING WORKSHEET LTG -3-C PROJECT NAME Cafe Posada Restaurant TI DATE 7/3/2008 FEET BUILDING TOTAL TABLE 1 - PORTABLE LIGHTING NOT SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE FEET A B C D ROOM # OR ZONE ID DEFAULT W/s ft AREA SF TOTAL WATTS B X C Restaurant 0.2 2,340 468 # OF FIXT. LUMIN. WATTS PER FIXTURE TASK AREA (SF) # OF TASK AREAS TOTAL AREA (SF) (D x E) TOTAL WATTS (C x E) TOTAL 2,340 468 TABLE 2 - PORTABLE LIGHTING SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE FEET BUILDING TOTAL 2.340 468 A B C D E F G ROOM # OR ZONE ID PORTABLE LIGHTING Description # OF FIXT. LUMIN. WATTS PER FIXTURE TASK AREA (SF) # OF TASK AREAS TOTAL AREA (SF) (D x E) TOTAL WATTS (C x E) TOTAL 0 0 TABLE 3 - PLANS SHOW PORTABLE LIGHTING IS NOT REQUIRED FOR OFFICE AREAS > 250 SQUARE FEET ROOM # TOTAL AREA OR ZONE ID (SF) TOTALI 0 BUILDING SUMMARY - PORTABLE LIGHTING Designer needs to provide detailed documentation that the lighting level provided by the overhead lighting meets the needs of the space. The details include luminaire types and mounting locations relative to work areas. BUILDING SUMMARY TOTAL AREA (SF) (FROM TABLES 1+2+3) TOTAL WATTS BUILDING TOTAL 2.340 468 I Run Initiation 7 4.1 Code: 12151052 EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 11 of 22 AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C PROJECT NAME DATE Cafe Posada Restaurant TI 7/3/2008 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer. Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF -1 for performance method duct sealing requirements. AIR SYSTEMS, Central or Single Zone Existing 7-1/2 Ton Unit 2 Reference on Plans or Specification 1 112(a) 3.30 COP 112(a) 10.3 EER 112(b) Yes 112(c), 115(a) n/a 121(b) Yes 121 b 351 cfm 121 c No 121 c No 121 c 122(e) Programmable Switch 122(e) Heating & Cooling Required 122 Auto 122 n/a 123 124 R-4.2 144 a & b n/a 144 a & b 106,177 btuh 144 a & b n/a 144 a & b 110,608 btuh 144 c Constant Volume 144 c 144 c Yes 144 d No 144 a No Economizer 144 Constant Tem 144 (f) Constant Temp 144 k No MWIo EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 12 of 22 1 WATER SIDE SYSTEM REQUIREMENTS Pali 2 of 2 MECH-2-C PROJECT NAME DATE Cafe Posada Restaurant TI 7/3/2008 SYSTEM FEATURES 2 WATER SIDE SYSTEMS: Chillers, Towers, Boilers, H dronic Loops ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Reference on Plans or Specification Equipment Efficiency 112(a) Pipe Insulation 123 PRESCRIPTIVE MEASURES Calculated Capacity Proposed Capacity Tower Fan Controls Tower Flow Controls Variable Flow System Design Chiller and Boiler Isolation CHW and HHW Reset Controls WLHP Isolation Valves VSD on CHW, CW & WLHP Pumps > 5 HP DP Sensor Location 1: For each chiller, cooling tower, boiler, and hydronic loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. 2: Water side systems include wet side system using other liquids such as glycol or brine. Service Hot Water, Pool Heating ITEM OR SYSTEM TAG(S) DHW Heater Number of Systems 1 MANDATORY MEASURES Reference on Plans or Specification Water Heater Certification 113 (a) Water Heater Efficiency 113 b Service Water Heating Installation 113 (c) Pool and Spa Efficiency and Control 114 a Pool and Spa Installation 114 b Pool Heater - No Pilot Light 115 (c) Spa Heater - No Pilot Light 115 d A O Smith Water Products n/a n/a n/a n/a 1: For each water heater, pool heat and domestic water loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" ins the column. Run Initiation Time: 07/03/08 10:14:18 Run Code: 1215105258 EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 13 of 22 L) M � �I = 00 O C=) ! 1714 C ` | � | � 2 � � 3 U) @ � � � @ m 0 IL � @ A z Transfer &rLO04 Design Min. Air s mom -,r k § LJ s Max « =:)u Columns mJ, U § Ke 300 CFM L § B.o4 E §0 } "f CFM/sq. ■ - L§ #s r Design \ / Zone Supply ). CFM - osp k k M® — Vent. &r E | CFM $ REQ'D 2 c - I �.a © m ®C r. prm -§ `z i! &n CF 2 #{ ) c 2 0 Occupant o / » |� § �� m k0 ## z R� )� }Mm '\ CL Pers_ L) ®fk o:§ |_E J Numarof . !§£ !f{ 0 mo e - !± ! k[{ Min CFM m e by k© 00 !)$ z=!CV mx@ t ��� 00 m T� cF m §#z |7- _� mo per 6 -6 E E 04 4 Square Foot �2§ 7/\ z CK Condition ik�k kR# ) = m_ & . \ $m - �2 f U)®!%|0 E0> 2 §{}&§&2]�! �LU { \ hz t 7 / L k � \z k� § 2®�`2E r= 3 >>- § - ] $ \ 0 a k z / }/(a42CEV{ ° E.,. Q o . ;«� 2 ® §lM20L)2 k{ z ' 2 ƒ o / / ] z ) W MECHANICAL EQUIPMENT DETAILS Part 1 of 2 MECH-5-C PROJECT NAME Cafe Posada Restaurant TI DATE 7/3/200$ CHILLER AND TOWER SUMMARY Efficiency Tons PUMPS Equipment Name Equipment Type Qty. Tot. Qty GPM I BHP Motor I Eff. Drive Eff. Pump Control 1QHW BOILER SUMMARY Energy Standby TANK INSUL. Rated Vol. Condition Factor Loss or Ext. System Name System Type Distribution Type Qty Input (Gals.) Status or RE Pilot R -Val. R O Smith Water Products Large Gas All Pipes Ins 1 125,000 120 New 0.92 2.12% 15.0 CENTRAL SYSTEM RATINGS HEATING COOLING Aux. Condition System Name System Type Qty. Output kW Eff. Output Efficiencv Status Economizer Type Carrier 50HJQ008--- (5/6)2 Packaged DX 2 85,000 0.0 3.30 COP 88,000 10.3 EER Existing No Economizer MECHANICAL EQUIPMENT DETAILS Part 2 of 2 MECH-S-C ENVELOPE MANDATORY MEASURES ENV -MM PROJECT NAME Cafe Posada Restaurant TI DATE 7/3/2008 DESCRIPTION Designer Enforcement §118(a) Installed Insulating Material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20, Chapter 4, Article 3. X] § 118(c) All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. 0 §117(a) All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. X❑ § 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors). JAI § 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not exceeding those shown in Table Number 1-E. of the Standards. Manufactured fenestration products must be labeled for U -value according to NFRC procedures. X❑ §118(e) Demising Walls in Nonresidential Buildings: The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value of no less than R-13 between framing members. EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 17 of 22 LIGHTING MANDATORY MEASURES LTG -MM PROJECT NAME Cafe Posada Restaurant TI DATE 7/3/2008 DESCRIPTION Designer Enforcement ❑X §131(d)1 For every floor, all interior lighting systems shall be equipped with a separate automatic control to shut off the lighting. This automatic control shall meet the requirements of 'Section 119 and may be an occupancy sensor, automatic time switch, or other device capable of automatically shutting off the lighting. 0 §131(d)2Override for Building Lighting Shut-off: The automatic building shut-off system is provided with a manual, accessible override switch in sight of the lights. The area of override is not to exceed 5,000 square feet. X] §119(h) Automatic Control Devices Certified: All automatic control devices specified are certified, all alternate equipment shall be certified and installed as directed by the manufacturer. X❑ §111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for the project are certified and listed in the Directory. All installed fixtures shall be certified. §132 Tandem Wiring for One and Three Lamp Fluorescent Fixtures: All one and three lamp fluorescent fixtures are tandem wired with two lamp ballasts where required by Standards Section 132; or all one and three lamp fluorescent fixtures are specified with electronic high -frequency ballasts and are exempt from tandem wiring requirements. FIX I §131(a) Individual Room/Area Controls: Each room and area in this building is equipped with a separate switch or occupancy sensor device for each area with floor -to - ceiling walls. JAI §131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100 square feet and more than 0.8 watts per square foot of lighting load shall be ' controlled with bi-level switching for uniform reduction of lighting within the room. X] §131(c) Daylight Area Control: All rooms with windows and skylights that are greater than 250 square feet and that allow for the effective use of daylight in the area shall have 50% of the lamps in each daylit area controlled by a separate switch; or the effective use of daylight cannot be accomplished because the windows are continuously shaded by a building on the adjacent lot. Diagram of shading during different times of the year is included on plans. §131(e) Display Lighting. Display lighting shall be separately switched on circuits that are 20 amps or less. EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:18 of 22 MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM PROJECT Cafe Posada Restaurant TI DATE 7/3/2008 DESCRIPTION Designer Enforcement Equipment and Systems Efficiencies FX §11 Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply with the applicable standard. FX] §115(a) Fan type central furnaces shall not have a pilot light. §123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC equipment, shall be insulated in accordance with Standards Section 123. 0 §124 Air handling duct systems shall be installed and insulated in compliance with Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards. Controls §122(e) , Each space conditioning system shall be installed with one of the following: 0 §122(e)1A Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not explicitly exempt from the requirements of Section 112 (d)) shall be installed with an automatic time switch with an accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch shall be capable of programming different schedules for weekdays and weekends and have program backup capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power is interrupted; or ❑ §122(e)1 B An occupancy sensor to control the operating period of the system; or ❑ §122(e)1 C A 4 -hour timer that can be manually operated to control the operating period of the system. §122(e)2 Each space conditioning system shall be installed with controls that temporarily restart and temporarily operate the system as required to maintain a setback heating and/or a setup cooling thermostat setpoint. §122(g) Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000 square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided with isolation devices, such as valves or dampers, that allow the supply of heating or cooling to be setback or shut off independently of other isolation areas; and shall be controlled by a time control device as described above. ® §I22(a&b) Each space conditioning'system shall be controlled by an individual thermostat that responds to temperature within the zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or reduced to a minimum. §122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable setpoint stops accessible only to authorized personnel. ❑ §112(b) Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the heating load can be met by the heat pump alone. EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 19 of 22 MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM PROJECT NAME Cafe Posada Restaurant TI DATE 7/3/2008 Description Designer Enforcement Ventilation §121(e) Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified on these plans. §122(f) Gravity or automatic dampers interlocked and closed on fan shutdown shall be provided on the outside air intakes and discharges of all space conditioning and exhaust systems. §q 22(f) All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers in all openings to the outside, except for combustion air openings. §'21(f)1 Air Balancing: The system shall be balanced in accordance with the National Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or Associated Air Balance Council (AABC) National Standards (1989); or §121(f)2 Outside Air Certification: The system shall provide the minimum outside air as shown on the mechanical drawings, and shall be measured and certified by the installing licensed C-20 mechanical contractor and certified by (1) the design mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) "the person with overall responsibility for the design of the ventilation system; or ❑ §121(f)3 Outside Air Measurement: The system shall be equipped with a calibrated local or remote device capable of measuring the quantity of outside air on a continuous basis and displaying that quantity on a readily accessible display divice; or ❑ §121(f)4 Another method approved by the Commission. Service Water Heating Systems IAI §413(b)2 If a circulating hot water system is installed, it shall have a control capable of automatically turning off the circulating pump(s) when hot water is not required. §113(c) Lavatories in restrooms of public facilities shall be equipped with controls to limit the outlet temperature to 110 degrees F. EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:20 of 22 WAC SYSTEM HEATING AND COOLING LOADS SUMMARY PROJECT NAME DATE Cafe Posada Restaurant TI 7/3/2008 SYSTEM NAME FLOOR AREA Existing 7-1/2 Ton Unit 2,340 Total Room Loads Return Vented Lighting Return Air Ducts Return Fan Ventilation Supply Fan Supply Air Ducts TOTAL SYSTEM LOAD COIL COOLING PEAK COIL HTG. PEAK CFM ISensiblel Latent CFM I Sensible 2,216 34,371 4,680 896 13,215 0 1,719 661 0 0 35 14,094 4,363 351 16,397 0 0 1,719 661 53 F 30,933 HVAC EQUIPMENT SELECTION Carrier 50HJQ008 --- (5/6)2 110,608 45,160 106,177 Total Adjusted System Output 110,608 45,160 106,177 (Adjusted for Peak Design Conditions) TIME OF SYSTEM PEAK Jul 2 pm Jan 12 am EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak 26.0°F 67.3°F 84.0°F 84.0°F O Supply Air Ducts Outside Air 351 cfm 83 9 °F Heating Coil Supply Fan 6000 cfm ROOMS 69.9 OF 70.0 °F h Return Air Ducts 11 (COOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Coolina Peak) 12.0 / 77.9 OF Outside Air 351 cfm 74.3/63.7 °F 76.5 / 64.8 OF 59.2 / 58.2 OF 59.2/58.20 --& , � Supply Air Ducts Supply Fan 59.4 / 58.3 OF 6000 cfm 57.2% R.H. ROOMS 74.0 163.7 OF Return Air Ducts I Cooling Coil EnergyPro 4.4 by Energysoft User Number: 5862 Job Number: Page: 21 of 22 ROOM LOAD SUMMARY PROJECT NAME Cafe Posada Restaurant TI DATE 7/3/2008 SYSTEM NAME Existing 7-1/2 Ton Unit FLOOR AREA 2,340 ROOM LOAD SUMMARY ROOM COOLING PEAK COIL COOLING PEAK COIL HTG. PEAK ZONE NAME ROOM NAME Mult. CFM SENSIBLE LATENT CFM SENSIBLE LATENT CFM SENSIBLE Restaurant Restaurant 1 2,216 34,371 4,680 2,216 34,371 4,680 896 13,215 PAGE TOTAL 1 2,216 34,371 4,680 896 13,215 TOTAL 1 2,216 34,371 4,680 896 13,215 EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 22 of 22