08-1817 (RC) Title 24TITLE 24 REPORT
Title 24 Report for:
Building 1 TI
79-630 HWY 111 Suite #103
La Quinta, CA 92253
MUM
Project Designer:
Michael Hurst Architect
78120 Calle Estado #207
La Quinta, CA 92253
760-799-3729
Report Prepared By:
Gina Rose
EQS, Inc.'
42280 Beacon Hill #D-3
Palm Desert, CA 92211
(760) 674-2345
Job Number:
CITY OF LA QUINTA
auiMiNa a snFEW DEPT.
APPROVED
Date: o�►.,L:��.�"� I
9/3/2008
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.6riergysoft.com.
EnergyPro 4.4 by EnergySoft Job Number: User Number: 5862
TABLE OF CONTENTS
Cover Page
Table of Contents
Nonresidential Performance Title 24 Forms
Form ENV -MM Envelope Mandatory Measures
Form LTG -MM Lighting MandatoryMeasures
Form MECH-MM Mechanical Mandatory Measures
HVAC System Heating and'Cooling Loads Summary
Room Load Summary .
R
1
2
3
17
18
19
21
23
EnergyPro 4.4 by EnergySoft Job Number: User Number: 5862
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1
PROJECT NAME
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
DATE
Building 1 TI
DOCUMENTATION AUTHOR
9/3/2008
PROJECT ADDRESS
Gina Rose
BUILDING CONDITIONED FLOOR AREA
79-630 HWY 111 Suite #103 La Quinta
The Principal Designer hereby certifys that the proposed building design represented in this set of construction documents is
CLIMATE ZONE
15
Permit #
PRINCIPAL DESIGNER - ENVELOPE
TELEPHONE
Building
Michael Hurst Architect
760-799-3729
NEW CONSTRUCTION ADDITION
DOCUMENTATION AUTHOR
TELEPHONE
Checked by/Date
EQS, Inc.
(760) 674-2345
Enforcement Agency Use
GENERAL INFORMATION
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
DATE OF PLANS
DA
Gina Rose
BUILDING CONDITIONED FLOOR AREA
.1,725 Sq.Ft.
The Principal Designer hereby certifys that the proposed building design represented in this set of construction documents is
CLIMATE ZONE
15
BUILDING TYPE
®
NONRESIDENTIAL HIGH RISE RESIDENTIAL
HOTEUMOTEL GUEST ROOM
PHASE OF CONSTRUCTION
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
NEW CONSTRUCTION ADDITION
5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
EXISTING + ADDITION/ALTERATION
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
SIGNATU
DA
Gina Rose
�`�
The Principal Designer hereby certifys that the proposed building design represented in this set of construction documents is
consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this
permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116,
through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
ENV. LTG. MECH.
❑ ❑ ❑ 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
0 F] 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section
5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in
full in the Nonresidential Manual.)
ENVELOPE COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
ENV -1
Required Forms
PRINCIPAL ENVELOPE DESIGNER - NAME
SIGNATU J
LIC. NO.
D A
Michael Hurst Architect
1-10
LIGHTING COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
LTG -1, LTG -2, LTG -3
Required Forms
PRINCIPAL LIGHTING DESIGNER -NAME
SIGNAT E
LIC. NO.
DAT
Michael Hurst Archtitect
og
MECHANICAL COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
MECH-1 MECH-2 MECH-3 MECH-5
Required Forms
PRINCIPAL MECHANICAL DESIGNER - NAME
SIG TORE
LIC. NO.
DATE
Michael Hurst Architect
I EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:3 of 24 1
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 PERF -1
PROJECT NAME DATE
Building 1. TI 9/3/2008
ANNUAL TDV ENERGY USE SUMMARY kBtu/s ft- r
ENERGY COMPONENT
Standard
Design
Proposed
Design
Compliance
Margin
l[Mstandard. Proaosea
Space Heating
Space Cooling
Indoor Fans
Heat Rejection
Pumps & Misc.
Domestic Hot Water
Lighting
Receptacle
Process
TOTALS:
Percent better than Standard:
1.92
1.51
0.41
SJ°°
155.49
123.96
31.53
5p9CeCoAv
bd-Fara
999
0.00
0.00
0.00
0.00
0.00
0.00
H.MR-*6-n
Punpi&Mi..
0.00
0.00
0.00
18.18
18.42
-0.24
DHW
39.80
50.82
-11.01
`ghft
61.03
s1.o3
0.0oF-z
R°`°p"°
o.00
o.o0
0.0o
-
276.41
255.73
20.68
_______________
0 10 20 30 40 50 60 70 80 90 100110120130140150
ketWsgfi-yr
process)
7.5%
( 7.5% excluding
BUILDING COMPLIES
GENERAL INFORMATION
Building Orientation
Number of Stories
Number of Systems
Number of Zones
N 0 deg
Conditioned Floor Area 1,725 sqn.
Unconditioned Floor Area 0 sqft.
Conditioned Footprint Area 1,725 sqn.
Fuel Type Natural Gas
1
2
21
Orientation
Front Elevation N
Left Elevation (E)
Rear Elevation S
Right Elevation (W) 1
Total 1
Roof
Gross Area
sgft.
sqn.
sgft.
sgft.
sqn.
sgft.sgft.
Glazing Area
Glazing
sgft.
sqn.
sgft.
sgft.
sgft.
Ratio
260
123
47.5%
0
0
0.0%
260
47
18.2%
0
01
0.00/0
520
171
1,725
0.0%
Standard Proposed
Lighting Power Density 0.600 W/sgft. 0.766 W/sgft.
Prescriptive Env. Heat Loss 204 Btu/h 202 Btu/h
Prescriptive Env. Heat Gain 21,681 Btu/h-F 25,892 Btu/h-F
Remarks:
Standard Building (Compliance)
Run Initiation Time: 09/03/08 11:21:43 Run Code: 1220466103
EnergyPro 4.4 by Energysoft User Number: 5862 Job Number: Page:4 of 24
'ERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1
PROJECT NAME
Building 1 TI
DATE
9/3/2008
ZONE INFORMATION
System Name Zone Name
Occupancy Type
Floor
Area
(sqft.)
Inst.
LPD
(W/sf)l
Ctrl.
Credits
(W/sf)2
Allowed LPD
Proc.
Loads
(W/sf)
Area Tailored
/S 3 Wls 4
Existing 4 Ton Unit (Cl) Empty Space
Comp Bldg All Other
900
0.47
Existing 3 Ton Unit Empty Space
Comp Bldg All Other
825
0.662
1
Notes: 1. See LTG -2-C
(items marked with asterisk, see LTG -2 -C by others)
2. See LTG -4-C 3. See LTG -5-C
(by others)
4. See LTG -6-C
Items above require special documentation '
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
The local enforcement agency should pay special attention to the items specinea in this cnecKost. t nese items require special written lusnncation
and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
submitted.
The HVAC System "Existing 4 Ton Unit (Cl)" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the 'MECH-5-
The HVAC System "Existing 3 Ton Unit' incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A.
The exceptional features listed In this performance approach application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Authorized Signature or Stamp
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:5 of 24
CERTIFICATE OF COMPLIANCE ENVA-C
PROJECT NAME DATE
Buildina 1 TI 9/3/2008
#
Surface
Type
Area
U -Fac.
Insulation
Cay. Cont.
Act.
Am.
Tilt
Cond:
Status
Joint Appendix
IV Reference
Location / Comments
1
Roof
90
0.036
R-30
R-0.0
0
0
Existin
02-A9
Empty
Space
2
Wall
13
0.074
R-19
R-0.0
0
90
Existin
09-A5
Empty
Space
3
Roof
82
0.036
R-30
R-0.0
0
0
Existin
02-A9
Emply
Space
4
Wall
213
0.074
R-19
R-0.0
180
90
Existin
09-A5
Empty
Space
Space
5
Window
Rear
S
2 0.670 NFRC
0.52 NFRC
180
Existin
Existin
Window/Doors
Em
Space
6
Window
Rear
S
12 0.670 NFRC
0.52 NFRC
180
Existin
Existin
Window/Doors
Empty
Space
7
Window
Rear
S
14 0.670INFRCI
0.52 NFRC
180
Existing
Existin
Window/Doors
Empty
Space
R
nMore than or equal to 10,000 sq.fi. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U -factors from
._. _ ... _ -.�..��
#
Type
## Exterior Shade Type
Window Overhang Left Fin Right Fin
SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
Area U -Fac'
SHGC2
Act.
Am.
Cond.
Stat.
Glazing
lype
Location/
Comments
1
Window
Front
N
32 0.670 NFRC
0.52 NFRC
0
Existin
Existin
Window/Doors
Empty
Space
2
Window
Front
N
32 0.670 NFRC
0.52 NFRC
0
Existing
Existin
Window/Doors
Empty
Space
3
Window
Front
N
12 0.670 NFRC
0.52 NFRC
0
Existing
Existin
Window/Doors
Empty
Space
4
Window
Front
N
48 0.670 NFRC
0.52 NFRC
01
Existin
Existin
Window/Doors
Empty
Space
5
Window
Rear
S
2 0.670 NFRC
0.52 NFRC
180
Existin
Existin
Window/Doors
Em
Space
6
Window
Rear
S
12 0.670 NFRC
0.52 NFRC
180
Existin
Existin
Window/Doors
Empty
Space
7
Window
Rear
S
14 0.670INFRCI
0.52 NFRC
180
Existing
Existin
Window/Doors
Empty
Space
1 U -factor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the AUM Manual Appendix, Nh HU LaDeieo value.
2 SHGC Type: 116-8 Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
## Exterior Shade Type
Window Overhang Left Fin Right Fin
SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
1 None
0.76
2 None
0.76
3 None
0.76
4 None
0.76
5 None
0.76
6 None
0.76
7 None
0.76
EEL
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
The proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 2s,000 ft2, a calling neignt greater tnan 1s rest, and an Lru Tor general
lighting of at least 0.5 WIft2. See Section 14J(c). If this box Is checked, ENV4-C must be filled out. when submitting under the Prescriptive Compliance Approach.
EnerpyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:6 of 24 1
�ERTIFICATE OF COMPLIANCE (Part 1 of 3) LTG -1 -C
PROJECT NAME DATE
Building 1 TI 9/3/2008
INSTALLED INDOOR LIGHTING POWER FOR CONDITIONED AND UNCONDITIONED SPACES
INSTALLED
WATTS
INSTALLED LIGHTING, CONDITIONED SPACES (From LTG -2-C). 976
PORTABLE LIGHTING (From LTG -3-C) 345
LIGHTING CONTROL CREDIT, CONDITIONED SPACES (From LTG -4-C) 0
CONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 1,321
INSTALLED LIGHTING, UNCONDITIONED SPACES (From LTG -2-C) 0
LIGHTING CONTROL CREDIT, UNCONDITIONED SPACES (From LTG -4-C) 0
UNCONDITIONED SPACE ADJUSTED INSTALLED LIGHTING POWER 0
ALLOWED INDOOR LIGHTING POWER FOR CONDITIONED SPACES
❑ COMPLETE BUILDING METHOD (From LTG -5-C)
ALLOWED
❑ AREA CATEGORY METHOD (From LTG -5-C)
WATTS
NOTE TO
FIELD
❑ TAILORED METHOD (From LTG -5-C) ALLOWED LIGHTING POWER
1,321
CONTROL TYPE
(Auto Time Switch, Dimming, etc.)
ALTERNATE COMPLIANCE
Check if
Dayiighting
❑X PERFORMANCE METHOD
❑ COMMMON LIGHTING SYSTEM (From LTG -8-C)
ALLOWED INDOOR LIGHTING POWER FOR UNCONDITIONED SPACES From LTG -5-C)
o
MANDATORY INDOOR AND DAYLIGHTING AUTOMATIC CONTROLS
NOTE TO
FIELD
CONTROL LOCATION
(Room #)
CONTROL
IDENTIFICATION
CONTROL TYPE
(Auto Time Switch, Dimming, etc.)
SPACE CONTROLLED
Check if
Dayiighting
NOTES TO FIELD - For Building Department Use Only
Run Initiation Time: 09/03/08 11:21:43 Run Code: 1220466103
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:7 of 24
CERTIFICATE OF COMPLIANCE (Part 3 of 3) LTG -1-C
PROJECT NAME
Building 1 TI
DATE
9/3/2008
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance
tests for lighting systems. The designer is required to check the boxes by all acceptance tests that
apply and list all equipment that require an acceptance test. If all equipment of a certain type requires
a test, list the equipment description and the number of systems to be tested in parentheses. The NJ
number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the
test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design
professional or an agent selected by the owner). Since this form will be part of the plans, completion
of this section will allow the responsible party to budget for the scope of work appropriately.
.Building Departments:
Before an occupancy permit is granted for a newly constructed building or space, or a new lighting
system system serving a building or space is operated for normal use, all control devices serving the
building or space shall be certified as meeting the Acceptance Requirements for Code Compliance.
In addition a Certificate of Acceptance, LTG -1-A, Forms shall be submitted to the building department
that:
A. Certifies plans, specifications, installation certificates, and operating and maintenance
information meet the requirements of§ 10-103(b) and Title 24 Part 6.
Test Descri tion
Test Performed By:
O LTG -2-A: Lighting Control Acceptance Document
- Occupancy Sensor Acceptance
- Manual Daylight Controls Acceptance
- Automatic Time Switch Control Acceptance
Equipment requiring acceptance testing
O LTG -3-A: Automatic Daylighting Controls Acceptance Document
Equipment requiring acceptance testing�✓a'
I EnergvPro 4.4 by EnergvSoft User Number: 5862 Job Number: Page:8 of 24 1
CERTIFICATE OF COMPLIANCE MECH-1-C
PROJECT NAME DATE
Buildina 1 TI I
9/3/2008
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance. '
In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation
certificates. and oDeratina and maintenance information meet the requirements of Section 10-103(b) and Title 24 Part 6.
STATEMENT OF COMPLIANCE
❑ MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-3-A: Packaged HVAC Systems Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-4-A: Air -Side Economizer Acceptance Document
N
Equipment requiring acceptance testing /
Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the
commission do not require equipment testing but do require construction inspection.
❑ MECH-5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
This test required If the unit serves 5,000 R2 of space or less and 25% or more of the ducts are in nonconditioned or semiconditioned space like an
attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
❑ MECH-6-A: Demand Control Ventilation Acceptance Document
) n
Equipment requiring acceptance testing I t
All new DCV controls installed on new or existing packaged systems must be tested.
❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
All new VA fan volume controls installed on new or existing systems must be tested
❑ MECH-8-A: -Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to chilled and hot water systems.
-Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 BtWhr.
-Water-loop Heat Pump Controls
Applies to all new watedoop heat pump systems where the combined loop pumps are greater than 5 hp.
-Variable Frequency Controls Applies to all new distribution pumps on new variable now chilled, Pydronic heat pump
i
or condenser water systems where the pumps motors are greater than 5 hp. n n
j' (moi
Eq ui ment requiring acceptance testingY
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:9 of 24
W
o
J
W
Z
0)
O
W
M
z
_
U
U)
O
o
r.
o
0
w
Z
_
E-
ILLI
3:
P
a
a
M
CL
z
J
m
c!)
w
J
Oo
O
M
CL
Q
Z
I --J
LU
W
J
Fa -
Installed
r
a
z
C�0 C�0 N
C0
O
0)
0)
M
M
N
r.
o
r
CO
•
a
M
CL
0
M
CL
Installed
r
00
a
C
O`
O`
E
Watts
H
U
O
J
Z
D
W
(G x 1)
0
C7
U
Lu
JO
o
N
0
r
Z
J
�
Q
F -
Z
++
N
0
U
CL
E
Number
0
of
-a
Luminaires
�
CEC
=
Default?
X
X
C]
C]
Watts
pp
Cp
U
. per
LO
00
Luminaire
C7
Number of
LL
Ballast per
N
Luminaire
O
O
Watts
1T
N
r
W
per
N
Lamp
Number of
N
m
p.
Lamps per
N
Luminaire
E
t4
J
U
Lamp
Type
N
CS
H
O
U
0
U
c
o
U
W
n
W
U
w
N
r
c,�
•�
o
_
„
CLCD
C
C
a)
J
LL
LL
v
v
N
�
•
ID
E
m
z
C�0 C�0 N
0)
0)
M
M
N
r.
o
0
a
M
CL
0
M
CL
a
C
O`
O`
E
H
U
O
J
Z
D
W
0
C7
U
Lu
JO
o
N
0
Z
J
�
Q
F -
Z
m
0
U
CL
E
0
0
R
PORTABLE LIGHTING WORKSHEET LTG -3-C
PROJECT NAME
Buildinc�1 TI
SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE
FEET
BUILDING TOTAL
DATE 1
9/3/2008
B
C
D
E
TABLE 1 - PORTABLE LIGHTING
NOT SHOWN ON PLANS FOR OFFICE AREAS >250 S
•DARE FEET
A
B
C
D
ROOM #
OR ZONE ID
DEFAULT
W/s ft
AREA
SF
TOTAL WATTS
B X C
Empty Space
0.2
900
180
Empty Space
0.2
825
165
TOTAL 1 1,725
TABLE 2 - PORTABLE LIGHTING
SHOWN ON PLANS FOR OFFICE AREAS >250 SQUARE
FEET
BUILDING TOTAL
A
B
C
D
E
F
G
ROOM #
OR ZONE ID
PORTABLE LIGHTING
Description
# OF
FIXT.
LUMIN.
WATTS PER
FIXTURE
TASK
AREA
(SF)
# OF
TASK
AREAS
TOTAL
AREA (SF)
(D x E)
TOTAL
WATTS
(C x E)
TOTAL
0
0
ROOM # TOTAL AREA
OR ZONE ID (SF)
TOTALI 0
BUILDING SUMMARY - PORTABLE LIGHTING
Designer needs to provide detailed documentation that the lighting
level provided by the overhead lighting meets the needs of the
space. The details include luminaire types and mounting locations
relative to work areas:
BUILDING SUMMARY
TOTAL AREA (SF)
(FROM TABLES 1+2+3)
TOTAL WATTS
BUILDING TOTAL
1,725
345
I Run Initiation Co1220466103
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:I I of 24
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
PROJECT NAME DATE
Ruildina 1 TI 9/3/2008
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section Reference on Plans or Specification 1I
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
112(a)
8.00 HSPF
7.60 HSPF
112(a)
13.0 SEER / 10.6 EER
13.1 SEER / 10.8 EER
112(b)
Yes
Yes
112(c), 115(a)
n/a
n/a
121(b)
Yes
Yes
121 b
135 cfm
124 cfm
121 c
No
No
121 c
No
No
121(c), 122(e)
Programmable Switch
Programmable Switch
122(e)
Heating & Cooling Required
Heating & Cooling Required
122
Auto
Auto
122
n/a
n/a
123
124
R-4.2
R-4.2
144 a & b
n/a
n/a
144 a & b
29,979 btuh
22,485 btuh
144 a & b
n/a
n/a
144 a & b
26,976 btuh
23,404 btuh
144 c
Constant Volume
Constant Volume
144 c
144 c
Yes
Yes
144 d
No
No
144 a
No Economizer
No Economizer
144
Constant Temp
Constant Tem
144 (f)
Constant Temp
Constant Temp
144 k
No
No
Lme: UZU415blU1.3
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 12 of 24
WATER SIDE SYSTEM REQUIREMENTS Part 2 of 2 MECH-2-C
PROJECT NAME
Building 1 TI
113 (a)
DATE
9/3/2008
SYSTEM FEATURES
Service Water Heating Installation
113 (c)
2 WATER SIDE SYSTEMS: Chillers, Towers, Boilers, H dronic Loops
ITEM OR SYSTEM TAG(S)
Pool and Spa Installation
Number of Systems
Pool Heater - No Pilot Light
115 (c)
T-24
MANDATORY MEASURES
Section Reference on Plans or Specification'
Equipment Efficiency
112(a)
Pipe Insulation
123
PRESCRIPTIVE MEASURES
Calculated Capacity
144 (a & b)
Proposed Capacity
144 (a & b)
Tower Fan Controls
144 h
Tower Flow Controls
144 h
Variable Flow System Design
144 0)
Chiller and Boiler Isolation
144
CHW and HHW Reset Controls
144 0)
WLHP Isolation Valves "
144 '
VSD on CHW, CW & WLHP Pumps > 5
144 '
HP
DP Sensor Location
144 '
1: For each chiller, cooling tower, boiler, and hydronic loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph
number where the required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Water side systems include wet side system using other liquids such as glycol or brine.
Service Hot Water, Pool Heating
ITEM OR SYSTEM TAG(S)
DHW Heater
Number of Systems
2
MANDATORY MEASURES
Reference on Plans or Specification'
Water Heater Certification
113 (a)
Water Heater Efficiency
113 b
Service Water Heating Installation
113 (c)
Pool and Spa Efficiency and Control
114 a
Pool and Spa Installation
114 b
Pool Heater - No Pilot Light
115 (c)
Spa Heater - No Pilot Light
115 d
Undersmk
99%
n/a
n/a
n/a
n/a
1: For each water heater, pool heat and domestic water loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and
paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" ins the column.
Run Initiation Time: 09/03/08 11:21:43 Run Code: 1220466103
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 13 of 24
U
1
A
1
U
W
0;
■2
Z
Transfer Air
N
`o
Design Min. Ai
o•
m
d
Setpoint
°
(L
t
J o
Max of
m
❑
Columns H, J,
K or 300 CFM
z
z
MB
x 0.4
E
jPO
Q
Y
CFM/sq. ft.
a
)�
x
m
30% of Design
r
a
Zone Supply
m
CFM
Design
mi
r
LO
N
N
m
o
m
m
—
Vent. Air
o
E
3
CFM
m
3
READ V.A
M
M
N
N
,
N
x
_ Max of
G)
m
m
(D or
Min CFM
m
Z
a E
E °
E
N
(D
by Occupant°a
E $
z
a
(ExF)oo�
°
>'
CFM
o
z
rn E
z
LL
per
w
x
0 3
.r
a
Person
3
m
cr
a
a
m
s
U
W
UNumber
of
s
o
�j
E
p
W
People
m m
o
.2
c
m r
E
c
Min CFM
�
N
m
m
H m
❑
by Area
H
m
o
E°
o
00
N
(BxC)
A
o
>
'9
3
N
h
CFM
'0 z
m
sZ
m
per
o
6
0
E
°
m
`_ `
E
E
N
a
Square Foot
m
a
m s
s'
o
z
c
Q
Condition
O
N
4 'c
o a.>
m
a
j
Ct
ao'_
Area
an d
d
er
a
m a
v
(SF)
3
2
m
m
c
a D
rrm.
N'
o
'Eii E
m v
Z
`o m
._.m>
Q°
=
x m
o U
cn g
m j
my
0_
m m❑
m
LL
m
r
H
T mC7'mU
m
W
C<
LL
m
Y
.� m
`5
a
0 rw
O
(n
J.
m 5
m
xx
=
o m
rn
w
.-.
°<
0
Ot c m
"
`
E
10
m m
c
Z
H
N
U
m y
m 5
.m
- c°
H
°
a y
E
W
�
Q
r
...
�.
.c %
N e
U
n
c
.�
J
Q
W
E-
v
m
c
E
° E
m'v
O
N
c
c
E N
n`
o
E y
m
a
Z
0 20
U
2
rn
f0
N
tT
C
(O
V)
f7
CY.�.2
d
w
z
W
CL
E
w
E
w
w
w
MECHANICAL EQUIPMENT DETAILS
Part 1 of 2 MECH-5-C
PROJECT NAME
Building 1 TI
DATE 9/3/2008
CHILLER AND TOWER SUMMARY
System Name
Efficiency
Tons
PUMPS
Aux.
kW
Eff.
Equipment Name
Equipment Type
Qty.
Tot.
Qty
GPM
BHP
Motor
Eff.
Drive
Eff.
Pump
Control
8.00 HSPF
45,000
13.0 SEER / 10.6 EER
Existing
No Economizer
Carrier 50HJ0004—(5/6)1
Packaged DX
1
36,000
0.0
7.60 HSPF
36,000
13.1 SEER / 10.8 EER
Existing
No Economizer
1DHW I BOILER SUMMARY
Energy I Standby ITANK INSUL.
Rated I Vol. Condition Factor Loss or Ext.
'System Name System Type Distribution Type ' QtyInput (Gals.) ' Status' or RE Pilot R -Val.
Undersink Small Elec... Point of Use 2 5,120 6 New 0.95 n/a n/a
CENTRAL SYSTEM RATINGS
HEATING
COOLING
System Name
System Type
ty
Output
Aux.
kW
Eff.
Output
Efficiency
Condition
Status
Economizer Type
Carrier 50HJQ005--- (5/6)2
Packaged DX
1
48,000
0.0
8.00 HSPF
45,000
13.0 SEER / 10.6 EER
Existing
No Economizer
Carrier 50HJ0004—(5/6)1
Packaged DX
1
36,000
0.0
7.60 HSPF
36,000
13.1 SEER / 10.8 EER
Existing
No Economizer
MECHANICAL EQUIPMENT DETAILS Part 2 of 2 MECH-5-C
ENVELOPE MANDATORY MEASURES ENV -MM
PROJECT NAME DATE
Buildina 1 TI' 1 9/3/2008
DESCRIPTION
Designer
Enforcement
X❑ §i18(a) Installed Insulating Material shall have been certified by the manufacturer to
comply with the California Quality Standards for insulating material, Title 20,
Chapter 4, Article 3.
§ 118(c) All Insulating Materials shall be installed in compliance with the flame spread rating
and smoke density requirements of Sections 2602 and 707 of Title 24,`Part 2.
X❑ § 117(a) All Exterior Joints and openings in the building that are observable sources of air
leakage shall be caulked, gasketed, weatherstripped or otherwise sealed..
X❑ § 116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit
and the building, and shall be weatherstripped (except for unframed glass doors
and fire doors).
X] § 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not
exceeding those shown in Table Number 1-E. of the Standards. Manufactured
fenestration products must be labeled for U -value according to NFRC procedures.
X] § 118(e) Demising Walls in Nonresidential Buildings:
The opaque portions of framed demising walls in nonresidential buildings shall
have insulation with an installed R -value of no less than R-13 between framing
members.
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 17 of 24
LIGHTING MANDATORY MEASURES LTG -MM
PROJECT NAME DATE
Buildina 1 TI I
9/3/2008
DESCRIPTION
Designer
Enforcement
❑X §131(d)1 For every floor, all interior lighting systems shall be equipped with a separate automatic
control to shut off the lighting. This automatic control shall meet the requirements of
Section 119 and may be an occupancy sensor, automatic time switch, or other device
capable of automatically shutting off the lighting.
FIX 1 §131(d)2Override for Building Lighting Shut-off: The automatic building shut-off system is
provided with a manual, accessible override switch in sight of the lights. The area
of override is not to exceed 5,000 square feet.
0 §119(h) Automatic Control' Devices Certified: All automatic control devices specified are
certified, all alternate equipment shall be certified and installed as directed by the
manufacturer.
0 §111 Fluorescent Ballast and Luminaires Certified: All fluorescent fixtures specified for
the project are certified and listed in the Directory. All installed fixtures shall be
certified.
❑s
§132 Tandem Wiring for One and Three Lamp Fluorescent Fixtures: All one and three
lamp fluorescent fixtures are tandem wired with two lamp ballasts where required
by Standards Section 132; or all one and three lamp fluorescent fixtures are
specified with electronic high -frequency ballasts and are exempt from tandem
wiring requirements.
0 §131(a) Individual Room/Area Controls: Each room and area in this building is equipped
with a separate switch or occupancy sensor device for each area with floor -to -
ceiling walls.
F§131(b) Uniform Reduction for Individual Rooms: All rooms and areas greater than 100
square feet and more than 0.8 watts per square foot of lighting load shall be
controlled with bi-level switching for uniform reduction of lighting within the room.
§131(c) Daylight Area Control: All rooms with windows and skylights that are greater than
250 square feet and that allow for the effective use of daylight in the area shall
have 50% of the lamps in each daylit area controlled by a separate switch; or the
effective use of daylight cannot be accomplished because the windows are
continuously shaded by a building on the adjacent lot. Diagram of shading during
different times of the year is included on plans.
❑ §131(e) Display Lighting. Display lighting shall be separately switched on circuits that
are 20 amps or less.
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 18 of 24
MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM
PROJECT NAME
Buildina 1 TI
DATE
DESCRIPTION
Desi ner
Enforcement
Equipment and Systems Efficiencies
§11 Any appliance for which there is a California standard established in the
Appliance Efficiency Regulations will comply with the applicable standard.
§115(a) Fan type central furnaces shall not have a pilot light.
0 §123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees
Fahrenheit, or within HVAC equipment, shall be insulated in accordance with
Standards Section 123.
X] §124 Air handling duct systems shall be installed and insulated in compliance with
Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards.
Controls
§122(e) Each space conditioning system shall be installed with one of the following:
§122(e)1A Each space conditioning system serving building types such as offices and
manufacturing facilities (and all others not explicitly exempt from the
requirements of Section 112 (d)) shall be installed with an automatic time switch
with an accessible manual override that allows operation of the system during
off -hours for up to 4 hours. The time switch shall be capable of programming
different schedules for weekdays and weekends and have program backup
capabilities that prevent the loss of the device's program and time setting for at
least 10 hours if power is interrupted; or
❑ §1 22(e)1 g An occupancy sensor to control the operating period of the system; or
§122(e)1 C A 4 -hour timer that can be manually operated to control the operating period of
the system.
F§122(e)2 Each space conditioning system shall be installed with controls that temporarily
restart and temporarily operate the system as required to maintain a setback
heating and/or a setup cooling thermostat setpoint.
§122(g) Each space conditioning system serving multiple zones with a combined
conditioned floor area more than 25,000 square feet shall be provided with
isolation zones. Each zone: shall not exceed 25,000 square feet; shall be
provided with isolation devices, such as valves or dampers, that allow the supply
of heating or cooling to be setback or shut off independently of other isolation
areas; and shall be controlled by a time control device as described above.
® §122(a&b) Each space conditioning system shall be controlled by an individual thermostat
that responds to temperature within the zone. Where used to control heating, the
control shall be adjustable down to 55 degrees F or lower. For cooling, the
control shall be adjustable up to 85 degrees F or higher. Where used for both
heating and cooling, the control shall be capable of providing a deadband of at
least 5 degrees F within which the supply of heating and cooling is shut off or
reduced to a minimum.
X❑ §122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and
adjustable setpoint stops accessible only to authorized personnel.
F] §112(b) Heat pumps shall be installed with controls to prevent electric resistance
supplementary heater operation when the heating 'load can be met by the heat
pump alone.
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 19 of 24
,.t
MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM
PROJECT NAME DATE
Buildina 1 TI 1 9/3/2008
Description
Designer
Enforcement
Ventilation .
F§121(e)
Controls shall be provided to allow outside air dampers or devices to be operated
at the ventilation rates as specified on these plans.
0
§122(f)
Gravity or automatic dampers interlocked and closed on fan shutdown shall be
provided on the outside air intakes and discharges of all space conditioning and
exhaust systems.
R§122(f)
All gravity ventilating systems shall be provided with automatic or readily
accessible manually operated dampers in all openings to the outside, except for
combustion air openings.
R§121(f)1
Air Balancing: The system shall be balanced in accordance with the National.
Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or
...
Associated Air Balance Council (AABC) National Standards (1989); or
0
' §121(f)2
Outside Air Certification: The system shall provide the minimum outside air as
shown on the mechanical drawings, and shall be measured and certified by the
installing licensed C-20 mechanical contractor and certified by (1) the design
-
mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3)
the person with overall responsibility for the design of the ventilation system; or
0
§1Y1(f)3
Outside Air Measurement: The system shall be equipped with a calibrated local or
remote device capable of measuring the quantity of outside air on a continuous
basis and displaying that quantity on a readily accessible display divice; or
21(f)4
Another method approved by the Commission.
Service
Water Heating Systems
FX]
§11 3(b)2
If a circulating hot water system is installed, it shall have a control capable of
automatically turning off the circulating pump(s) when hot water is not required.
0
§113(c)
Lavatories in restrooms of public facilities shall be equipped with controls to limit
the outlet temperature to 110 degrees F.
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:20 of 24
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME
DATE
Buildin 1 TI
9/3/2008
SYSTEM NAME
FLOOR AREA
Existing 4 Ton Unit(Cl)900
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible Latent
I CFM
I Sensible
1,124
14,167
1,800
440
6,343
0
708
317
0
0
135
5,400
932
135
6,295
0
..
0
708
317
21,726 2,732
Carrier 50HJQ005--- (5/6)2 26,976 14,134
Total Adjusted System Output 26,976 14,134
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 2 pm
26.0 OF 66.1oF 83.7 OF
Outside Air
135 cfm
Heating Coil
69.8 of
n
29,979
29,979
Jan 12 am
83.7 of
O Supply Air Ducts
Supply Fan 83.5 of
1600 cfm ROOMS
70.0 of
Return Air Ducts I
(COOLING SYSTEM PSYCHROMETRICS (Airstream Temoeratures at Time of Coolina Peak) I
12.0 / 77.9 of
Outside Air
135 cfm
74.4/65.4 of
77.6/66.7OF 61.7/60.9OF
0
Cooling Coil Supply Fa
1600 cfm
61.7 / 60.9 OF
Supply Air Ducts
Fan
62.2/61.0 OF
63.5% R.H. ROOMS
74.0 / 65.3 of
h Return Air Ducts 'I
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page:21 of 24
WAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
Building 1 TI 9/3/2008
SYSTEM NAME FLOOR AREA
Existing 3 Ton Unit 825
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible Latent
CFM
I Sensible
900
12,983
1,650
307
4,163
0
649
208
0
0
124
4,803
1,303
124
5,773
0
0
649
208
19,7501 2 953 F7710 353
HVAC EQUIPMENT SELECTION
Carrier 50HJ0004 --- (5/6)1 23,404 9,281 22,485
Total Adjusted System Output 23,404 9,281 22,485
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Sep 2 pm Jan 12 am
EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26.0 of 65.3 of 82.9 of 82.9 of
O Supply Air Ducts
Outside Air
124 cfm o
Heating Coil Supply Fan 82.8 F
1200 cfm ROOMS
69.8 of 70.0 of
Return Air Ducts '
:DOLING SYSTEM PSYCHROMETRICS (Airstream Temperatures at Time of Cooling Peak)
11.0/77.6OF 78.3/66.0OF. 59.9/59.0OF 59.9/59.0OF
q.-✓ �
Outside Air
124 cfm
74.5/64.4 of
Cooling Coil
—7���
Supply Air Ducts
Supply Fan 60.5 / 59.1 of
1200 cfm 59.4% R.H. ROOMS
74.0 / 64.2 of
Return Air Ducts I
I EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Paae:22 of 24 1
ROOM LOAD SUMMARY
PROJECT NAME
Building 1 TI
DATE
9/3/2008
SYSTEM NAME
Existinq 4 Ton Unit(Cl)900
FLOOR AREA
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENTCFM
SENSIBLE
LATENT
CFM
SENSIBLE
Em Space
Empty Space
1
1,124
14,167
1,800
1 124
14,167
1,800
440
6,343
PAGE TOTAL 1 1,124 14,167 1,800 440 6,343
TOTAL 1 1,124 14,167 .1,800 440 6,343
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 23 of 24
ROOM LOAD SUMMARY
PROJECT NAME
I Building 1 TI
DATE
9/3/2008
SYSTEM NAME
Existin-.q 3 Ton Unit
FLOOR AREA
825
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
Empty Space
Empty Space
1
900
12,983
1,650
900
12,983
1,650
307
4,163
PAGE TOTAL 1 900 12,983 1,650 307 4,163
TOTAL 1 900 12,983 1,650 307 4,163
EnergyPro 4.4 by EnergySoft User Number: 5862 Job Number: Page: 24 0f 24