07-0821 (CSCS) Title 24TITLE 24 REPORT
Title 24 Report for:
Komar Desert Center - Bldg B&C
Hway 111 and Jefferson
La Quinta, CA, 92253
7 =45 7
Project Designer:
SGPA Architecture -Planning
1545 Hotel Circle South, Studio 200
San Diego, CA, 92108
619.297.0131
Report Prepared .By:
Chris French
LSW Engineers California, Inc.
5560 Ruffin Rd., #1
San Diego, CA 92123
(858) 268-3224
Job Number:
2006796.000
Date:
11/2/2007
CITY OF LA QUINTA
BUILDING & SAFETY DEPT.
APPROVED
FOR CONSTRUCTION
DATE IZ !'00 BY�A
- �7- 92-)
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and Is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.4 by EnergySoft Job Number: 2006796.000 of User Number: 3137
/ALZ&,/",- Y
-Jr/ ,—w�
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1
PROJECT NAME ''
'''"" ''
DATE
Komar Desert Center - Bldg B&C
DOCUMENTATION AUTHOR
11/2/2007
PROJECT ADDRESS
BUILDING CONDITIONED FLOOR AREA
11,568 Sq.Ft.
Hway 111 and Jefferson La Quinta,
CA
,.
PRINCIPAL DESIGNER -ENVELOPE
HOTEL/MOTEL GUEST ROOM
TELEPHONE
Building Permit #
SGPA Architecture Planning
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
619.297.0131
5537.2 or'6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
DOCUMENTATION AUTHOR
F1 7 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
TELEPHONE
Checked by/Date
LSW Engineers California, Inc.
ENVELOPE COMPLIANCE
858 268-3224
Enforcement Agency. Use
GENERAL INFORMATION
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is rate an tete.
DOCUMENTATION AUTHOR
DATE OF PLANS
DATE
BUILDING CONDITIONED FLOOR AREA
11,568 Sq.Ft.
CLIMATE ZONE
1 15
BUILDING TYPE
®
NONRESIDENTIAL HIGH RISE RESIDENTIAL
HOTEL/MOTEL GUEST ROOM
PHASE OF CONSTRUCTION
F ❑ 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
NEW CONSTRUCTION ADDITION
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
EXISTING + ADDITION/ALTERATION
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is rate an tete.
DOCUMENTATION AUTHOR
SIG E
DATE
Chris French
Chris
1a —7
The Principal Designer hereby certifys that the proposed b ' design represented in this set of construction documents is
consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this
permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116,
through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
ENV. LTG. MECH.
F ❑ 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect.
❑ ❑ F1 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section
5537.2 or'6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
F1 7 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in.
full in the Nonresidential Manual.)
ENVELOPE COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
Required For IBJ
PRINCIPAL ENVELOPE DESIGNER - NAME
SIGNATOR
ILIC NOO
D/
SGPA Architecture Planning1
/ / J Q
LIGHTING COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
Lighting Compliance Not In The Scope Of
is Submittal
Required Forms
PRINCIPAL LIGHTING DESIGNER - NAME
SIGNATURE LIC. NO.
DATE
MECHANICAL COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
MKHO, MECH-2 MECH-3 MECH-5
Required Fo s
PRINCIPAL MECHANICAL DESIGNER -NAME
SIGNAT!j����
LIC. NO.
DATE
Devin A. Abellon P.E.- LSW Engineers, I
7/1 -/ k-0
j.A2 -
i EnergyPro 4.4 by EnergySoft User Number. 3137 Job Number: 2006796.000 Paae:2 of 16 1
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 PERF -1
PROJECT NAME 711/2/2007
Komar Desert Center - Bld B&C
ANNUAL TDV ENERGY USE SUMMARY
kBtu/s ft- r
Standard
Proposed Compliance
ENERGY COMPONENT Design
Design Margin'snndad_
Space Heating 3.44
1.02 2.42
Space Cooling 463.83
400.76 63.07
s -
Indoor Fans 119.87
161.10 -41.23
i
Heat Rejection 0.00
0.00 0.00
Pumps & Misc. 0.00
0.00 0.00
Domestic Hot Water 22.36
22.36 0.00
Lighting 160.71
160.71 0.00
Receptacle 79.06
79.06 0.00.
Process 153.89
153.89 0.00
0 30,60 90.420160160210240270300930880380420450
TOTALS: 1,003.16
978.90 24.26
;-- --- - ---wr>r=- -
Percent better than Standard:
2.4% ( 2.9% excluding
process)
BUILDING COMPLIES
GENERAL INFORMATION
Building Orientation
E 90 deg
Conditioned Floor Area
11,568
sqft.
1
201
Number of Stories
Unconditioned Floor Area
sqft.
10
11,568
Number of Systems
Conditioned Footprint Area
sqft.
171
Natural Gas
Number of Zones
Fuel Type
Orientation
Gross Area
Glazing Area
Glazing
Ratio
2,396
130
5.4%
Front Elevation
E
sqft.
sqft.
1,626
0
0.0%
Left Elevation
(s)
sqft.
sqft.
2,242
1,026
45.8%
Rear Elevation
W
sqft.
sqft.
1,672
818
48.9%
Right Elevation
Total
Roof
(N)l
sqft.
sqft.
ft.
sqft'
sgft.
sqft.
7,936
1,974
24.9%
=11,56L
[:::::�
0.0%
Standard Proposed
Lighting Power Density
1.564 w/sgft. 1.564 w/sgft.
Prescriptive Env. Heat Loss
2,067 Btu/h 3,199 Btu/h
Prescriptive Env. Heat Gain
220,444 Btu/h-F 326,537 Btu/h-F
Remarks:
Run Initiation Time: 10/09/07 12:01:03 Run Code: 1191956463
EnergyPro 4.4 by EnergySoft User Number. 3137 Job Number: 2006796.000 Page:3 of 16
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1
PROJECT NAME
Komar Desert Center - Bldg
B&C
DATE
11/2/2007
ZONE INFORMATION
System Name
Zone Name
Occupancy Type
Floor
Area
(sqft.)
Inst.
LPD
(W/sf)l
Ctrl.
Credits
. (W/sf)2
Allowed LPD
Proc.
Loads
.(VU/sf)
Asea. Tailored
1N/s 3 _ W/s 4
RTU C5-1
Lease Space
Office
532
*1.20
Restrm
Corridor/Restroom/Support
72
*0.60
RTU 81-1
Lease Space
Retail Sales, Wholesale
1,719
*1.70
Restrm
Corridor/Restroom/Support
49
*0.60
RTU B2-1
Restrm
Corridor/Restroom/Support
49
*0.60
Lease Space
Retail Sales, Wholesale
1,771
*1.70
RTU 131-1
Lease Space
Retail Sales, Wholesale
1,705
-1.7001
Restrm
Corridor/Restroom/Support
49
*0.60
RTU C1-1 & RTU C1-2
Lease Space
Comp Bldq Restaurant
1,151
-1.20C
16.000
RTU C1-3
Lease Space
Comp Bldq Restaurant
672
*1.20C
16.000
RTU C2-1
Restrm
Corridor/Restroom/Support
49
*0.60
Lease Space
Retail Sales, Wholesale
1,117
*1.70
Corridor (Uncond.)
Corridor/Restroom/Support
201
*0.60
RTU C3-1
Restrm
Corridor/Restroom/Support
49
*0.60
Lease Space
Retail Sales, Wholesale
1,137
*1.70
RTU C4-1
Restrm
Corridor/Restroom/Support
49
*0.60
Lease Space
Retail Sales, Wholesale
1,398
*1.70
Notes: 1. See LTG -2-C 2. See LTG -4-C 3. See LTG -5-C
(items marked with asterisk, see LTG -2 -C by others) (by others)
4. See LTG -6-C
Items above require special documentation
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
I
ne iocai enforcement agency snouia pay special attention to the items specified in this checklist. These items require special written justification
and documentation, and special verification to be used with the performance approach. The local enforcement agency- determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
submitted.
The Roof Roof R-30 is a CRRC Certified Roof with Reflectance = 0.30, Emittance = 0.75.
The HVAC System "Carrier 50HJ0004-3/5/6" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500.
The HVAC System "Carrier 50HJ0006-5 w/ DCV" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500.
The HVAC System "Carrier 50HJ0006-5 w/ DCV" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement.
The HVAC System "Carrier 50HJ0006-5 w/ DCV" includes Demand Control Ventilation per Standards Section 121.
The HVAC System "Carrier 50HJ0007-5 w/ DCV" includes an Economizer. This system has a cooling output < 75,000 Btuh or a supply cfm < 2500.
The HVAC System "Carrier 50HJ0007-5 w/ DCV" includes Demand Control Ventilation per Standards Section 121.
The HVAC System "Carrier 50HJ0008-5 w/ DCV" includes Demand Control Ventilation per Standards Section 121.
The Zone "Lease Space" has a North/EasVSouth Display Perimeter Credit of 87 ft.
The Zone "Lease Space" has a West Display Perimeter Credit of 14 ft.
The Zone "Lease Space" has a North/East/South Display Perimeter Credit of 87 ft.
The Zone "Lease Space" has a West Display Perimeter Credit of 14 ft.
The Zone "Lease Space" has a North/East/South Display Perimeter Credit of 87 ft.
The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Authorized Signature or
L EnergyPro 4.4 by EnergySoft User Number. 3137 Job Number: 2006796.000 Page:4 of 16 1
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PER
PROJECT NAMEDATE
. Komar Desert Center - Bldq B&C
Zone "Lease Space"
has a West Display Perimeter Credit of 14 ft.
11/2/2007
ZONE INFORMATION
has a North/East/South Display Perimeter Credit of 87 ft.
The
System Name Zone Name Occupancy Type
Floor
Area
(sgft.)
Inst.
LPD
(W/sf)l
. Ctrl. Allowed LPD
Credits . Aeea Tailored
(W/sf)2VV/s 3 W/s 4
. Proc.
Loads
(W/sf)
Zone "Lease Space" has a West Display Perimeter Credit of 14 ft.
The
Zone "Lease Space"
has a North/EasVSouth Display Perimeter Credit of 87 ft.
The
Zone "Lease Space"
has a West Display Perimeter Credit of 14 ft.
The
Zone "Lease Space"
has a North/EasVSouth Display Perimeter Credit of 87 ft.
The
Zone "Lease Space"
has a West Display Perimeter Credit of 14 ft.
The
Zone "Lease Space"
has a North/EasVSouth Display Perimeter Credit of 87 ft.
The
Zone "Lease Space"
has a West Display Perimeter Credit of 14 ft.
The
Zone "Lease Space'
has a North/East/South Display Perimeter Credit of 87 ft.
The
Zone "Lease Space"
has a West Display Perimeter Credit of 14 ft.
Notes: 1. See LTG -2-C 2. See LTG -4-C 3. See LTG -5-C
(items marked with asterisk, see LTG -2 -C by others) (by others)
4. See LTG -6-C
Items above require special documentation
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
I
he local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification
and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
submitted.
The
Zone "Lease Space"
has a West Display Perimeter Credit of 14 ft.
The
Zone "Lease Space"
has a North/East/South Display Perimeter Credit of 87 ft.
The
Zone "Lease Space"
has a West Display Perimeter Credit of 14 ft.
The
Zone "Lease Space" has a North/EasVSouth Display Perimeter Credit of 87 ft.
The
Zone "Lease Space" has a West Display Perimeter Credit of 14 ft.
The
Zone "Lease Space"
has a North/EasVSouth Display Perimeter Credit of 87 ft.
The
Zone "Lease Space"
has a West Display Perimeter Credit of 14 ft.
The
Zone "Lease Space"
has a North/EasVSouth Display Perimeter Credit of 87 ft.
The
Zone "Lease Space"
has a West Display Perimeter Credit of 14 ft.
The
Zone "Lease Space"
has a North/EasVSouth Display Perimeter Credit of 87 ft.
The
Zone "Lease Space"
has a West Display Perimeter Credit of 14 ft.
The
Zone "Lease Space'
has a North/East/South Display Perimeter Credit of 87 ft.
The
Zone "Lease Space"
has a West Display Perimeter Credit of 14 ft.
The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Authorized Signature or Stam
v.b=
I EnergyPro 4.4 by EnergySoft User Number: 3137 Job Number: 2006796.000 Paae:5 of 16
CERTIFICATE OF COMPLIANCE ENV -1 -C
(PROJECT NAME DATE
Komar Desert Center - Bldg B&C 11/2/2007
OPAQUE SURFACES
# Surface
Type
Area
U -Fac.
Insulation
Cay. Cont.
Act.
Am.
Tilt
Cond:
Status
Joint Appendix
IV Reference
I Location / Comments
1 Roof
532
0.036
R-30
R-0.0
0
0
New
02-A9
Lease Space
2 Wall
14
0.074
R-19
R-0.0
-0
90
New
09-A5
Lease Space
3 Roof
7
0.036
R-30
R-0.0
0
0
New
02-A9
Restrm
4 Roof
1,71
0.036
R-30
R-0.0
0
0
New
02-A9
Lease Space
5 lWall
35d
0.074
R-19
R-0.0
90
90
New
09-A5
Lease Space
6 IDoor
2A
0.700
None
R-0.0
90
90
New
28-A2
Lease Space
7 Wall
94
0.074
R-19
R-0.0
180
90
New
09-A5
Lease Space
8 Wall
224
0.074
R-19
R-0.0
270
90
New
09-A5
Lease Space
9 Roof
4
0.036
R-30
R-0.0
0
0
New
02-A9
Restrm
10 Wall
ill
0.074
R-19
R-0.01
90
90
New
09-A5
Restrm
11 Roof
4
0.036
R-30
R-0.0
0
0
New
02-A9
Restrm
12 Wall
ill
0.074
R-19
R-0.0
90
90
New
09-A5
Restrm
13 lRoof
1,77
0.036
R-30
R-0.0
0
0
New
02-A9
Lease Space
14 Wall
37
0.074
R-19
R-0.0
90
90
New
09-A5
Lease Space
15 Door
22
0.700
None
R-0.0
90
90
New
28-A2
Lease Space
16 Wall
231
0.074
R-19
R-0.0
270
90
New
09-A5
Lease Space
17 Roof
1,70
0.036
R-30
R-0.01
0
0
New
02-A9
Lease Space
18 Wall
36
0.074
R-19
R-0.01
90
90
1 New
09-A5
Lease Space
19 Door
2
0.7001
None
R-0.0
90
90
New
28-A2
Lease Space
20 lWall
23
0.074
R-19
R-0.01 270
90
New
09-A5
Lease Space
- N, t_, A. H (New, ExiSting, Altered, Removed)
FENESTRATION SURFACES
More than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either Issued by NFRC or provide a CEC Default Label Certificate using the default Ll -factors from
Standards Table 116-A and B. Certificate shall be filed in the contractors Drolect office durinn construction and in ma hnudlnn mann eft office after construcuo„
#
1TvDe
Area U -Fac'
SHGC2
Act.
Am.
Cond.
Stat.
Glazinq Type
Location/
Comments
1
Window
Right
N
82 1.190 116-A
0.83
116-B
0
New
Storefront
Lease Space
2
lWindow
Rear
W
223 1.1901116-A
0.83
116-B
270
New
Storefront
Lease Space
3
lWindow
Rear
W
227 1.1901116-A
0.83
116-B
270
New
Storefront
Lease Space
4
lWindow
Rear
W
223 1.190 116 -Al
0.83
116-B
270
New
Storefront
Lease Space
5
lWindow
Right
N
63 1.190 116-A
0.83
116 -BI
0
New
I Storefront
Lease Space
6
Window
Right
N
127 1.190 116-A
0.83
116-B
0
New
Storefront
Lease Space
7
Window
Rear
W
130 1.190 116-A
0.83
116-B
270
New
Storefront
Lease Space
8
Window
Rear
W
223 1.190 116-A
0.83
116-B
270
New
I Storefront
Lease Space
9
Window
Right
N
190 1.190 116-A
0.83
116-B
0
New
IStorefront
Lease Space
10 Window
Right
N
167 1.190 116 -Al
0.83
116-B
0
New
I Storefront
I Lease Space
11 Window
Front
E
130 1.190 116-A
0.83
116-B
90
New
IStorefront
IlLease Space
12 lWindow
Right
N
190 1.1901116 -Al
0.83
116 -BI
0
New
I Storefront
Lease Space
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
(1) Ll -factor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value.
(2) SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
#
Exterior Shade Type
�SHGC�
Window
Hgt. Wd.
Overhang
Len. H t. LExt.RExt.
Left Fin
Dist. Len. H t.
Right Fin
Dist. Len. H t.
1
None
0.76
10.0 25.3
7.0
0.1
15.0
0.0
2
None
0.76
10.0 22.3
14.5
0.1
15.0
4.1
0.0 0.0 0
5.0 11.1 0
3
None
0.76
10.0 22.7
14.5
0.1
15.0
15.0
4
None
0.76
10.0 22.3
14.5
0.1
15.0
15.0
5
None
0.76
10.0 6.3
28.0
0.1
0.0
32.0
6
None
0.76
10.0 12.7
6.0
0.1
20.0
0.1
7
None
0.76
10.0 13.0
12.8
0.1
10.0
10.0
8
None
0.76
10.0 22.3
14.5
0.1
10.0
10.0
9
None
0.76
10.0 19.0
6.0
0.1
0.0
14.0
10
None
0.76
10.0 25.3
7.0
0.1
15.0
0.0
11
None
0.76
10.0 13.0
7.0
0.1
0.1
10.1
12
None
1 0.76
10.0 19.0
7.0
0.1
10.8
15.0
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
The proposed building Is in climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a ceiling height greater than 15 feet, and an LPD for general
lighting of at least 0.5 W/142. See Section 143(c). If this box Is checked, ENV -4-C must be filled out. when submitting under the Prescriptive Compliance Approach.
EnergyPro 4.4 by EnergySoft User Number. 3137 Job Number: 2006796.000 Pape:6 of 16
CERTIFICATE OF COMPLIANCE ENV -1-C
(PROJECT NAME DATE
Komar Desert Center - Bldg B&C 11/2/2007
OPAQUE SURFACES
# Surface
Type I
Area
U -Fac.
Insulation
Cay. Cont.
Act.
Am.
Tilt
Cond:
Status
Joint Appendix
IV Reference
Location / Comments
21 Roof 1
49
0.036
R-30
R-0.0
0
0
New
02-A9
Restrm
22 Wall 1
113
0.074
R-19
R-0.0
90
90
New
09-A5
Restrm
23 Roof 1
1,15-
0.036
R-301
R-0.0
0
0
New
02-A9
Lease Space
24 Wall
304
0.074
R-19
R-0.0
0
90
New
09-A5
Lease Space
25 lWall
52
0.074
R-19
R-0.0
270
90
New
09-A5
Lease Space
26 Roof
672
0.036
R-30
R-0.0
0
0
New
02-A9
Lease Space
27 Demising
390,
0.110
R-11
R-0.0
0
90
New
09-A2
Restrm faces Uncond. Corridor
28 Roof
4
0.036
R-30
R-0.0
0
0
New
02-A9
Restrm
29 Roof
1,11 1
0.036
R-30
R-0.01
0
0
New
02-A9
Lease Space
30 Wall
10
0.074
R-191.
R-0.0
0
90
New
09-A5
Lease Space
31 Demising
10
0.110
R-11
R-0.0
0 1
90
New
09-A2
Restrm faces Uncond. Corridor
32 lRoof
45,
0.0361
R-30
R-0.0
0
0
New
02-A9
Restrm
misin
20
0.110
R-11
R-0.0
0
90
New09
A2
LeaseS ace faces Uncond. Corridorl
24
0.074
R-19
R-0.0
180
90
New
09-A5
LeaseS ace
r
2
0.700
None
R-0.0
180
90
New
28-A2
LeaseS ace
f
E
1,13
0.0361
R-30
R-0.0
0
0
New
02-A9
LeaseS ace
ll
126
0.074
R-19
R-0.0
0
90
New
09-A5
LeaseS ace
l
11
0.074
R-19
R-0.0
180
90
New
09-A5
Restrm
ll
11
0.074
R-19
R-0.0
90
90
New
09-A5
Restrm
f 1
4
0.036
R-30
R-0.0
0
0
1 New
02-A9
Restrm
v, c, n. , t'—, caisnng, Nrtereu, nemoveu)
FENESTRATION SURFACES
u e r-1-1ior equar - LV,Vua 5WL or bile-ouin renesirauon area must incivae a 1aoel cenlllcale enner Issueo Oy NYMU or provide a ctt: Uetault Label Gertitiople using the default U -factors from
Standards Table 116-A and B. Certificate shall be filed in the contractor's project office dudn constructlon and in the building manager's office after construction
Act. Cond. Location/
# Tvpe Area I -Fac? I SHGC' Am. Stat. Glazing Tvne CnmmPnts
1 u -rector type: 11U -A uetawt table from standards, i able NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value.
2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
Window Overhang Left Fin Right Fin
# Exterior Shade Type SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
I
I
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
Urnu proposed ouuamg is in cnmate zones z mrougn 10 and contains an enclosed space with floor area greater than 25,000 ft2, a ceiling height greater than 15 feet, and an LPD for general
lighting of at least 0.5 W/ft2. See Section 143(c). If this box is checked, ENVA-C must be filled out. when submitting under the Prescriptive Compliance Approach.
I EnergyPro 4.4 by EnergySoft User Number: 3137 Job Number: 2006796.000 Page:7 of 16 1
CERTIFICATE OF COMPLIANCE ENV -1-C'
PROJECT NAME DATE
Komar Desert Center - Bldg B&C 11/2/2007
OPAQUE SURFACES
# Surface
Type
Area
6Fac.
Insulation
Cay. Cont.
Act.
Am.
Tilt
Cond:
Status
Joint Appendix
IV Reference
Location / Comments
41 Wall
65&
0.074
R-19
R-0.0
90
90
New
09-A5
Lease Space
42 Wall
284
0.074
R-19
R-0.0
180
90
New
09-A5
Lease Space
43 Door
2A
0.700
None
R-0.0
180
90
New
28-A2
Lease Space
44 Roof
1,398
0.036
R-30
R-0.0
0
0
New
02-A9
Lease Space
45 Wall
17C
0.074
R-19
R-0.0
0
90
New
09-A5
Lease Space
I
I
' N. E, A, R (New, Existing, P
FENESTRATION
More than or equal to 10,000 sq.h. of site -built fenestration area must Include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default Ll -factors from
Standards Table 116-A and B. Certificate shall be filed In the contractor's project office during construction and In the building manager's office after construction
Act. Cond. Location/
# Tvpe Area U -Fac' SHGC2 Am. Stat. Glazi'n_q Type Comments
I
i I
I u-iaclor i ype: 11 b -A ueraun I able from tiumoaras, cable NH uelault Iable from the AGM Manual Appendix, NFRC Labeled value.
2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
Window Overhang Left Fin Right Fin
# Exterior Shade Type SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
The proposed building is in climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a calling height greater than 15 feet, and an LPD for general
lighting of at least 0.5 Wtft2. See Section 143(c). If this box is checked, ENV -4-C must be filled out. when submitting under the Prescriptive Compliance Approach.
EnergyPro 4.4 by EnergySoft User Number. 3137 Job Number: 2006796.000 Paae:8 of 16 1
CERTIFICATE OF COMPLIANCE MECH-I-C
ECT NAME
Komar Desert Center - Blda B
DATE
11/2/2007
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation
certificates, and operating and maintenance information meet the requirements of Section 10-103(b) and Title 24 Part 6.
STATEMENT OF COMPLIANCE
❑ MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-3-A: Packaged HVAC Systems Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the
commission do not require equipment testing but do requ!re construction inspection.
❑ MECH-5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
This test required If the unit serves 5.000 V of space or less and 25% or more of the ducts are in nonconditioned or semiconditioned space like an
attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
❑ MECH-6-A: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls installed on new or existing packaged systems must be tested.
❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
All new VA fan volume controls installed on new or existing systems must be tested
❑ MECH-8-A: -Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to chilled and hot water systems.
-Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Bfu/hr.
-Water-loop Heat Pump Controls
Applies to all new watedoop heat pump systems where the combined loop pumps are greater than 5 hp.
-Variable Frequency Controls Applies to all new distribution pumps on new variable flow chilled, hydronic heat pump
or condenser water systems where the pumps motors are greater than 5 hp.
Equipment requirin acceptance testing
EnergyPro 4.4 by EnergySoft User Number. 3137 Job Number: 2006796.000 Page:9 of 16
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
PROJECT NAME DATE
Komar Desert Center - Bldg B&C 11/2/2007
SYSTEM FEATURES .
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
AIR SYSTEMS Central or Single Zone
RTU C5-1.
RTU B1-1
RTU 132-1
1
1
1
Reference on Plans or Specification 1
112(a)
7.70 HSPF
7.70 HSPF
7.70 HSPF
112(a)
13.1 SEER / 11.0 EER
13.0 SEER / 11.0 EER
13.0 SEER / 11.0 EER
112(b)
Yes
Yes
Yes
112(c), 115(a)
n/a
n/a
n/a
121(b)
Yes
Yes
Yes
121 b
230 cfm
358 cfm
366 cfm
121 c
No
No
No
121 c
No
Yes
Yes
121 c 122(e)
Programmable Switch
Programmable Switch
Programmable Switch
122(e)
Heating & Cooling Required
Heating & Cooling Required
Heating & Cooling Required
122(f)
Auto
Auto
Auto
122
n/a
n/a
n/a
123
124
R-8.0
R-8.0
R-8.0
144 a & b
n/a
n/a
n/a
144 a & b
21,610 btuh
35,101 btuh
35,101 btuh
144 a & b
n/a
n/a
n/a
144 a & b
26,921 btuh
46,981 btuh
47,102 btuh
144 c
Constant Volume
Constant Volume
Constant Volume
144 (c
144 c
Yes
Yes
Yes
144 d
No
No
No
144 a
Diff. Enth Non-Inte
Diff. Enth Non-Inte
Diff. Enth Non-Inte
144 f
Constant Temp
Constant Temp
Constant Tem
144 (f)
Constant Temp
Constant Temp
Constant Temp
144 k
No
No
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
stun Inniatlon Ilme: iumumt iz:ui:u3 Faun code: 1191956463
EnergyPro 4.4 by EnergySoft User Number. 3137 Job Number: 2006796.000 Page:10 of 16
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
(PROJECT NAME DATE
Komar Desert Center - Bldg B&C 11/2/2007
SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
AIR SYSTEMS Central or Single Zone
RTU 61-1
RTU C1-1 &RTU C1-2
RTU C1-3
1
1 2
1
Reference on Plans or Specification 1
112(a)
7.70 HSPF
2.20 COP
2.20 COP
112(a)
13.0 SEER / 11.0 EER
11.0 EER
10.5 EER
112 b
Yes
Yes
Yes
112(c), 115(a).n/a
46,667 btuh
n/a
n/a
121(b)
Yes
Yes
Yes
121 b
229 cfm
97 cfm
57 cfm
121 c
No
No
No
121 c
Yes
Yes
Yes
121 c 122(e)
Pro rammable Switch
Programmable Switch
Programmable Switch
122(e)
Heating & Cooling Required
Heating & Cooling Required
Heating & Cooling Required
122(f)
Auto
Auto
Auto
122
n/a
n/a
n/a
123
124
R-8.0
R-8.0
R-8.0
144 a & b
n/a
n/a
n/a
144 a & b
35,101 btuh
86,191 btuh
54,650 btuh
144 a & b
n/a
n/a
n/a
144 a & b
46,667 btuh
121,929 btuh
67,959 btuh
144 c
Constant Volume
Constant Volume
Constant Volume
144 (c)
144 c
Yes
Yes
Yes
144 d
No
No
No
144 a
Diff. Enth Non-Inte
Diff. Enth Non-Inte)
Diff. Enth Non-Inte
144 f
Constant Temp
Constant Temp
Constant Tem
144 (f)
Constant Temp
Constant Temp
Constant Temp
144 k
No
No
No
EnergyPro 4.4 by EnergySoft User Number: 3137 Job Number: 2006796.000 Page: 11 of 16
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
(PROJECT NAME DATE
Komar Desert Center - Bldg B&C 11/2/2007
SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
AIR SYSTEMS, Central or Sin le Zone
RTU C2-1
RTU C3-1
RTU C4-1
1
1
1
Reference on Plans or Specification 1
112(a)
7.70 HSPF
7.70 HSPF
7.70 HSPF
112(a)
13.0 SEER / 11.0 EER
13.0 SEER / 11.0 EER
13.0 SEER / 11.0 EER
112 b
Yes
Yes
Yes
112(c), 115 a
n/a
n/a
n/a
121(b)
Yes
Yes
Yes
121 b
185 cfm
186 cfm
206 cfm
121 c
No
No
No
121 c
Yes
Yes
Yes
121 c 122(e)
Programmable Switch
I Programmable Switch
Programmable Switch
122(e)
Heating & Cooling Re uired
Heating & Cooling Required
Heatinq & Cooling Required
122(f)
Auto
I Auto
Auto
122
n/a
n/a
n/a
123
124
R-8.0
R-8.0
R-8.0
144 a & b
n/a
n/a
n/a
144 a & b
35,101 btuh
35,101 btuh
35,101 btuh
144 a & b
n/a
n/a
n/a
144 a & b
46,703 btuh
46,681 btuh
46,600 btuh
144 c
Constant Volume
Constant Volume
Constant Volume
144 c
144 c
Yes
Yes
Yes
144 d
No
No
No'
144 a
Diff. Enth Non-Inte
Diff. Enth Non-Inte )
Diff. Enth Non-Inte
144 f
Constant Temp
Constant Temp
Constant Tem
144 (f)
Constant Temp
Constant Temp
Constant Temp
144 k
No
No
No
Run Initiation Time: 10/09/07 12:01:03 Run Code: 1191956463
EnergyPro 4.4 by EnergySoft User Number: 3137 Job Number: 2006796.000 Page: 12 of 16
MECHANICAL VENTILATION MECH-3-C
(PROJECT NAME DATE
Komar Desert Center - Bldg B&C 11/2/2007
PRESCRIPTIVE REHEAT
LIMITATION (Section 144(d))
MECHANICAL VENTILATION Section 121(b)2)
AREA
BASIS
OCCUPANCY
BASIS
VAV MINIMUM
A
B
C
D
E
F
G
H
I
J
K
L
M
N
ZONE/SYSTEM
o
DO
�1 fD n'
C
U)Q
c
dvn
W tD -h
'111 E
o
a�
��O'
K >0
0; -A
`� d
vr-
mB
L Q'
��
°
v n
N <D -n
�' �
mph
O
x n
-n T
EM
D
0 X
� O 0
`- D
p
n ro
'n ,fin N
� D10
IV p
A O
-n N
�a9 a
o w
T�
9
y K
A O
a
A 0
W3fv
0 7 x
O N O
T=
0
mcc
>
09
^ P
>
T
T.
D
Lease Space
532
0.15
80
5.3
15.0
80
80
80
Restrm
72
0.15
11
11
150
RTU C5-1
Total
91
230
Lease Space
1,719
0.25
430
17.2
15.0
258
430
258
172
Restrm
49
0.15
7
7
100
RTU 61-1
Total
437
358
Restrm
49
7
100
Lease Space
1,77
0.25
443
17.7
15.0
266
443
266
177
RTU B2-1
Total
450
366
Lease Space
1,705
0.25
426
17.1
7.6
129
426
129
297
Restrm
4S
0.151
7
7
100
RTU 131-1
Total
434
229
Lease Space
1,15
0.38
437
11.5
8.4
97
437
97
340
RTU C1-1 & RTU C1-2
Total
437
97
II
I
Lease Space
672
0.381
255
6.7
8.4
57
255
57
199
RTU C1-3
Total
255
57
Restrm
49
0.15
7
7
100
Lease Space
1,117
0.25
279
11.2
7.6
85
279
85
195
RTU C2-1
Total
287
185
Restrm
49
0.15
7
7
100
Lease Space
1,137
0.25
284
11.4
7.6
86
284
86
198
RTU C3-1
Total
292
186
Restrm
49
0.15
7
7
100
Lease Space
11398
0.25
350
14.0
7.6
106
350
106
244
RTU C4-1
r Total
357
206
C Minimum ventilation rate per Section 121 Table 121-A
E Based on fixed seat or the greater of the expacted number of occupants and 50% of the CBC occupant load foregress purposes fors aces Without fixed seating.
H Required Ventilation Air REO'D V.A. is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G).
I Must be greater than orequal to H or use Transfer Air column N to make up the difference.
J Design tan supply cfm Fan CFM x 30%; or
K Condition area ft. s x 04 cfm/(t. sq.; or
L Maximum of Columns H, J. K, or 300 cfm
M This must be less than orequal to Column L and greater that orequal to the sum of Columns H + N.
N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal
to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M.
EnergyPro 4.4 by EnergySoft User Number: 3137 Job Number: 2006796.000 Page: 13 of 16
a>w
MECHANICAL EQUIPMENT DETAILS
Part 1 of 2 MECH-5-C
PROJECT NAME
Komar Desert Center - Bld-q B&C
DATE 11/2/2007
CHILLER AND TOWER SUMMARY
System Name
System Type
Efficiency
Tons
PUMPS
Eff.
Equipment Name
Equipment TypeQty.
Condition
Status
Tot.
Qty
GPM
BHP
Motor
Eff.
Drive
Eff.
Pump
Control
7.70 HSPF
36,700
13.1 SEER/ 11.0 EER
New
Diff. Enth (Non-Integ)
Carrier 50HJQ006-5 w/
DCV
Packaged DX
6
56,200
0.0
7.70 HSPF
61,000
13.0 SEER / 11.0 EER
New
Diff. Enth (Non-Integ)
Carrier 50HJ0007-5 w/
DCV
Packaged DX
2
69,000
0.
2.20 COP
76,000
11.0 EER
New
Diff. Enth (Non-Integ)
Carrier 50HJ0008-5 w/
DCV
Packaged DX
1
87,500
0.0
2.20 COP
91,300
10.5 EER
New
Diff. Enth Non-Inte
DH BOILER SUMMARY
Energy I Standby rrANK INSUL.
Rated Vol. I Condition Factor Loss or Ext.
System Name System Type Distribution Type QtyInput I (Gals.) ' Status or RE Pilot I R -Val.
CENTRAL SYSTEM RATINGS
HEATING
COOLING
System Name
System Type
PW
Output
Aux.
kW
Eff.
Out ut
Efficiency
Condition
Status
Economizer Type
Carrier 50HJ0004-3/5/6
Packaged DX
1
34,600
0.0
7.70 HSPF
36,700
13.1 SEER/ 11.0 EER
New
Diff. Enth (Non-Integ)
Carrier 50HJQ006-5 w/
DCV
Packaged DX
6
56,200
0.0
7.70 HSPF
61,000
13.0 SEER / 11.0 EER
New
Diff. Enth (Non-Integ)
Carrier 50HJ0007-5 w/
DCV
Packaged DX
2
69,000
0.
2.20 COP
76,000
11.0 EER
New
Diff. Enth (Non-Integ)
Carrier 50HJ0008-5 w/
DCV
Packaged DX
1
87,500
0.0
2.20 COP
91,300
10.5 EER
New
Diff. Enth Non-Inte
MECHANICAL EQUIPMENT DETAILS Part 2 of 2 MECH-5-C
PROJECT NAME
Komar Desert Center - Bldg B&C
DATE 11/2/2007
ZONE TERMINAL SUMMARY
TERMINAL
UNIT
VAV
RMI
4AL EA N
Zone Name
System Name
System Type
Heating
Cooling
oty.
Min CFM
Ratio I
Reheat
Coil
CFM
BHP
Motor
Eff.
Drive
Eff.
EXHAUST FAN SUMMARY
EXHAUSTFAN
EXHAUST
AN
Room Name
aty.
CFM
BHP
Motor
Eff.
Drive
Eff.
Room Name
CFM
BHP
Motor
Eff.
Drive
Eff.
C3 Restrm
1.0
15
0.12
49.0°/
97.0%
B-3 Restrm
t
10
0.10
49.0°/
97.0%
B-1 Restrm
1.0
10
0.10
49.0°/
97.0%
C2 Restrm
100
0.10
49.0°/
97.0%
B-2 Restrm
1.0
100
0.10
49.0%
97.0%
Uncond. Corridor.
1.0
10
0.10
49.00/
97.0%
Run Initiation Time: 10/09/07 12:01:03 Run Code: 1191956463
EnergyPro 4.4 by EnergySoft User Number. 3137 Job Number: 2006796.000 Page: 15 of 16
MECHANICAL EQUIPMENT DETAILS Part 2 of 2 MECH-S-C