07-0825 (CSCS) Title 24I TITLE 24 REPORT
Title 24 Report for:
Komar Desert Center - Bldg H
Hway 111 and Jefferson
La Quinta, CA, 92253
Project Designer:
SGPA Architecture Planning
1545 Hotel Circle South, Studio 20.0
San Diego, CA, 92108
619.297.0131
Report Prepared By:
Chris French
LSW Engineers California, Inc.
5560 Ruffin Rd., #1 CITY OF LA QUINTA
San Diego, CA 92123 BUILDING & SAFETY DEPT.
.(858) 268-3224 APPROVED
FOR CONSTRUCTION
DATE 1) D BYJVu-
Job Number:
2006796.000
Date:
5/23/2007
H� C � U T , H
MAY $1 2007
The EnergyPro computer program has been used to.perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.3 by EnergySoft Job Number. 2006796.000 User Number. 3137
I/ fiN'�/�- -&-- 10
77- 775 #wy l!t
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -11
PROJECT NAME
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
DATE
Komar Desert Center - Bldg H
DATE OF PLANS
5/23/2007
PROJECT ADDRESS
BUILDING CONDITIONED FLOOR AREA
10,141 sq.Ft.
--
Hway 111 and Jefferson La Quinta, CA
BUILDING TYPE
®
PRINCIPAL DESIGNER - ENVELOPE
TELEPHONE
Building Peimit ft
SGPA Architecture Planning
619.297.0131
EXISTING + ADDITION/ALTERATION
DOCUMENTATION AUTHOR
TELEPHONE
Checked by/Date
LSW Engineers California, Inc.
858 268-3224
Enforcement Agency Use
GENERAL INFORMATION
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DATE OF PLANS
SIGN R
DATE
BUILDING CONDITIONED FLOOR AREA
10,141 sq.Ft.
'�r�-
CLIMATE ZONE
15
BUILDING TYPE
®
NONRESIDENTIAL HIGH RISE RESIDENTIAL
HOTEL/MOTEL GUEST ROOM
PHASE OF CONSTRUCTION
®
NEW CONSTRUCTION ❑ ADDITION
EXISTING + ADDITION/ALTERATION
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is accurate and complete.
DOCUMENTATION AUTHOR
SIGN R
DATE
Chris French
'�r�-
-23-a7
The Principal Designer hereby certifys that the proposed Ing design represented in this set of construction documents is
consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this
permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116,
through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
ENV. LTG. MECH.
❑ F] F� 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
sign this document as the person responsible for its preparation; and that 1 am licensed in the State of
California as a civil engineer, mechanical engineer, or I am a licensed architect.
F] ❑ F 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section
5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
1-1 ❑ r-1 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant -to Business and Professions
Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in
full in the Nonresidential Manual.)
ENVELOPE COMPLIANCE
Indicate location on plans of Note Block for Mandatory Meas r
-1
Required
PRINCIPAL ENVELOPE DESIGNER - NAME
SIGN
LIC. NQ.
D�
SGPA Architecture Planning
LIGHTING COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
Light' g Compliance Not In The Scope Of
Required Forms
PRINCIPAL LIGHTING DESIGNER - NAME SIGNATURE
LIC. NO.
DATE
MECHANICAL COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
CH -1 MECH-2 MECH-3 MECH-5
Required orms
PRINCIPAL MECHANICAL DESIGNER - NAME SI E
LIC. NO.
DATE
Devin A. Abellon P.E.- LSW Engineers,
523-x:.
Faun initiation l I e: 07 07:47:35 Run Code: 1179931655
EnergyPro 4.3 by EnergySoft User Number, 3137 Job Number: 2006796.000 Paoe:2 of 12
I PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 PERF -11
PROJECT NAME DATE
Komar Desert Center - Bldq H I
5/23/2007
ENERGY COMPONENT
Standard
Design
Marginl�_
Proposed
Design
Space Heating
Space Cooling
Indoor Fans
Heat Rejection
Pumps & Misc.
Domestic Hot Water
Lighting
Receptacle
Process
1.68
0.38
437.67
341.00
92.69
128.36
0.00
0.00
0.00
0.00
16.08
16.08
184.45
184.45
85.98
85.98
0.00
0.00
TOTALS: 818.55 756.25
Percent better than Standard:
Compliance
E 90 deg
Marginl�_
10,14
1.29
1
a
se-.t1rq
5
10,141
8
96 67
0
sgft.
-35.67
Rear Elevation W 1,144 sgft.
0.00,
sgft.
..
s
0.00
Right Elevation (N 1,961 sgft.
Total 6,490 sgft.
Roof 10,141 sgft.
1,223
1,658
�p
0.00
62.4%
0.0%
1 ;,
0.00
(r
0.00
u,
0.00
..6..30 60 80 12015018087021027030013W38g316A20 %.
62.30
... ��
7.6% ( 7.6% excluding process)
Building Orientation
Number of Stories
Number of Systems
Number of Zones
E 90 deg
Conditioned Floor Area
Unconditioned Floor Area
Conditioned Footprint Area
Fuel Type
10,14
sgft.
sgft.
sqft.
1
0
5
10,141
8
Natural Gas
0
sgft.
Orientation Gross Area
Glazing Area
Glazing
Ratio
Front Elevation E 1,116 sgft.
435
sgft.
39.0%
Left Elevation (S) 2,269 sgft.
0
sgft.
0.0%
Rear Elevation W 1,144 sgft.
0
sgft.
0.0%
Right Elevation (N 1,961 sgft.
Total 6,490 sgft.
Roof 10,141 sgft.
1,223
1,658
�p
sgft.
sgft.
sgft.
62.4%
0.0%
Standard Proposed
Lighting Power Density 1.679 w/sgft. 1.679 W/sgft.
Prescriptive Env. Heat Loss 1,78 Btulh 2,690 Btu/h
Prescriptive Env. Heat Gain 18s,o13 Btum-F 2so,7sa Btum-F
Remarks:
EnergyPro 4.3 by EnergySoft User Number. 3137 Job Number: 2006796.000 Page:3 of 12
1PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1
PROJECT NAME
Komar Desert Center -
Bldg H
DATE
5/23/2007
ZONE INFORMATION
System Name Zone Name
Occupancy Type
Floor
Area
(sgft.)
Inst. Ctrl.
LPD 'CreditsArea
(W/sf)t (W/sf)2
Ajjowed.LPD Proc.
Tailored 'Loads
W /S 3 WIS 4 (W/sf)
RTU 1-11-1, 1-11-2 Lease Space
Retail Sales, Wholesale
3,676
'1.70
Restmt
Corridor/Restroom/Support
49
'0.60
RTU 2-1 Lease Space
Retail Sales, Wholesale
2,337
*1304.
Resirm
Corddor/Restroom/Support
49
'0.60
RTU 3-1 Lease Space
Retail Sales, Wholesale
2,046
"1.70
Restrm
Corridor/Restroom/Support
49
'0.60
RTU 1-14-1 Lease Space
Retail Sales, wholesale
1,886
'1.70
Restrm
Corridor/Restroom/Support
49
`0.60
Notes: 1. See LTG -2-C
(items marked with asterisk, see LTG -2 -C by others)
Z See LTG -4 -C 3. See LTG -5-C
(by others)
4. See LTG -6-C Items above require special documentation
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
amvraemem agency anoura pay special attention to me items specmeo in tnis cnecKust. These items require special written justification
and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
suhmittPd_
The Roof Roof R-30 is a CRRC Certified Roof with Reflectance = 0.30, Emittance = 0.75.
The HVAC System "Carrier 50HJ0006-5 w/ DCV" includes an Economizer. This system has a cooli ng output < 75,000 Btuh or a supply cfm < 2500.
The HVAC System "Carrier 50HJ0006-5 w/ DCV" is designated as 3 Phase, or is Exempted from the NAECA 13 SEER requirement.
The HVAC System "Carrier 50HJ0006-5 w/ DCV" includes Demand Control Ventilation per Standards Section 121.
The Zone "Lease Space" has a North/East/South Display Perimeter Credit of 87 ft.
The Zone "Lease Space' has a West Display Perimeter Credit of 14 ft.
The Zone "Lease Space' has a North/East/South Displav Perimeter Credit of 87 ft.
The Zone "Lease Space" has a West Display Perimeter Credit of 14 ft.
The Zone "Lease Space' has a North/East/South Display Perimeter Credit of 87 ft.
The Zone "Lease Space' has a West. Display Perimeter Credit of 14 ft.
The Zone "Lease Space" has a North/East/South Display Perimeter Credit of 87 ft.
The Zone "Lease Space' has a West Display Perimeter Credit of 14 ft.
IIV V—VJJUvnaI ieawres nsrea In tnis penormance approacn appucation nave speciticauy been reviewed. Adequate written justification and .
documentation for their use have been provided by the applicant.
Authorized Sianature or Stamo
EnergyPro 4.3 by EnergySoft User Number. 3137 Job Number: 2006796.000 Page:4 of 12
ICERTIFICATE OF COMPLIANCE ENV -1-C1
PROJECT NAME DATE
Komar Desert Center - Bldg H 5/23/2007
OPAQUE SURFACES
# Surface
Type
Area
U -Fac.
Insulation
Cay. Cont.
Act.
Am.
Tilt
Cond:
Status
I Joint Appendix
IV Reference
Location / Comments
1 Roof
3.67
0.036
R-30
R-0.0
0
0
New
102-A9
Lease Space
2 Wall
29
0.074
R-19
R-0.0
0
90
New
09-A5
Lease Space
3 Wall
67
0.074
R-19
R-0.0
90
90
New
09-A5
Lease Space
4 Wall
75
0.074
R-19
R-0.0
180
90
New
09-A5
Lease Space
5 Door
1 22
0.700
None
R-0.01
180
90
1 New
28-A2
Lease Space
6 Wall
11C
0.074
R-19
R-0.0
180
90
New
09-A5
Restrm
7 Roof
4S
0.036
R-30
R-0.0
0
0
New
02-A9
Restart
8 Roof
2,33
0.036
R-30
R-0.0
0
0
New
02-A9
Lease Space
9 Wall
137,
0.074
R-19
R-0.0
0
90
New
09-A5
Lease Space
10 Wall
0.074
R-19
R-0.0
90
90
New
09-A5
Lease Space
11 Wall
38
0.074
R-19
R-0.0
180
90
New
09-A5
Lease Space
12 Door
2
0.700
None
R-0.01
180
90
1 New
28-A2
Lease Space
13 Wall
11
0.074
R-19
R-0.01
180
90
New
09-A5
Restrm
14 Roof
4
0.036
R-30
R-0.01
0
0
New
02-A9
Restrm
15 Roof
2,04
0.036
R-30
R-0.0
0
0
New
02-A9
Lease Space
16 Wall
17
0.074
R-19
R-0.0
0
90
New
09-A5
Lease Space
17 Wall
31
0.074
R-19
R-0.0
180
90
New
09-A5
Lease Space
18 Door
21
0.7001
None
R-0.0
180
90
New
28-A2
Lease Space
19 Wall
11q
0.074
R-19
R-0.0
180 1
90
1 New
09-A5
Restrm
20 Roof
4q
0.036
R-30
R-0.0
0 1
0
1 New
02-A9
Restrm
❑More than or equal to 10,000 sq.ft. of site -built fenestration area must Include a label certificate either Issued by NFRC or provide a CEC Default Label Certificate using the default U -factors from
Standards Table 116A and B. Certificate shall be filed In the, contractor's orolect office dudno construction and In the bulldina manaoer's office after construction
# Type
Area U -Fac'
SHGC2
Act.
Am.
Cond.
Stat.
Glazing Type
Location/
Comments
1 Window
Right
N
253 1.190 116-A
0.83 116-B
0
New
Storefront
Lease Space
2 Window
Right
N
177 1.190 116-A
0.83 116-B
0
New
Storefront
Lease Space
3 Window
Front
E
135 1.190 116-A
0.83 116-B
90
New
Storefront
Lease Space
4 Window
Front
E
253 1.190 116-A
0.83 116-B
90
New
Storefront
Lease Space
5 Window
Ri ht
N
127 1.190 116-A
0.83 116 -BI
0
New
I Storefront
Lease Space
6 lWindow
Ri ht
N
177 1.190 116-A
0.83 116-B
0
New
Storefront
Lease Space
7 lWindow
Front
E
47 1.190 116-A
0.83 116-B
90
New
Storefront
Lease Space
8 Window
Right
N
223 1.190 116-A
0.83 116-B
0
New
Storefront
Lease Space
9 Window
Right
N
177 1.190 116-A
0.83 116-B
0
New
Storefront
Lease Space
10 Window
Right
N
89 1.190 116-A
0.83 116-B
0
New
Storefront
Lease Space
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
i v -,cum , yyv. , Iva. v m , nun mI acus, I auitl rvr I uertlull I9ule Imm me AUM M3aaal AppenaIX. Nr HG LaMea Va us.
2) SHGC Type: 1166 Default Table from Standards. COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
##
Exterior Shade Type
SHGC
Window
Hgt. Wd.
Overhang Left Fin Riqht Fin
Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
1
None
0.76
10.0 25.3
11.0 0.1
32.0
32.0 1.2 3.8 0 1.2 5.0 0
2
None
0.76
10.0 12.7
9.4 0.1
7.3
30.0
3
None
0.76
10.0 9.7
6.8 0.1
20.0
10.0
4
None
0.76
10.0 25.3
6.8 0.1
0.1
20.0
5
None
0.76
10.0 12.7
7.0 0.1
10.8
15.0
6
None
0.76
10.0 12.7
6.0 0.1
20.0
20.0
7
None
0.76
10.0 3.3
28.0 0.1
0.0
6.7
8
None
0.76
10.0 22.3
7.0 0.1
10.0
10.0
9
None
0.76
10.0 12.7
6.0 0.1
11.0
7.0
10
None
0.76
10.0 6.3
8.0 0.1
3.3
21.0
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
UI no proposea culling Is in climate zones z mrougn it) and contains an enclosed space with floor area greater than 25,000 112, a ceiling height greater then 15 feet, and an LPD for general
lighting of at least 0.5 W/112. See Section 143(c). It this box is checked, ENVa1-C must be filled out. when submitting under the Prescriptive Compliance Approach.
I EnergyPro 4.3 by EnergySoft User Number. 3137 Job Number: 2006796.000 Paae:5 of 12 1
CERTIFICATE OF COMPLIANCE ENV -1 -Cl
PROJECT NAME DATE
Komar Desert Center - Bldg H 5/23/2007
# Surface
Tvpe
Area
U -Fac.
Insulation
Cay. Cont.
Act.
Am.
Tilt
Cond.
Status
Joint Appendix
IV Reference
Location / Comments
21 Roof
1.88
0.036
R-30
R-0.0
0
0
New
02-A9
Lease Space
22 Wall
1,1
0.074
R-19
R-0.0
270
90
New
09-A5
Lease Space
23 Wall
132
0.074
R-19
R-0.0
. 0
90
New
09-A5
Lease Space
24 Wall
290
0.074
R-19
R-0.0
180
90
New
09-A5
Lease Space
25 Door
24
0.700 1
None
R-0.01
180
90
New
28-A2
Lease Space
26 Wall
11
0.074
R-19
R-0.0
180
90
New
09-A5
Restrm
27 Roof
4
0.036
R-30
R-0.0
0
0
New
02-A9
Restrm
more manor equal to t u,ouu sq.n. of site -bunt fenestration area must include a label certificate either Issued by NFRC or provide a CEC Default Label Certificate using the default U -factors from
Standards Table 116-A and S. Certificate shall be filed in the contractor's project office during construction and In the building managers office after construction
Act. I Cond. Location/
$ Tvnn Arnim I 11_C -n t I CLJl2/12 A-- 04-6
2 SHG rY�tl' "o•r. unrnun i sole from atanoaros, i sore IVI.1 usmuft I aote from me AGM Manual Appendix, NFRC Labeled value.
C Type: 1166 Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
Window Overhang Left Fin Right Fin
# Exterior Shade Type SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
❑The proposed building Is in climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a ceiling height greater than 15 feet, and an LPD for general
lighting of at bast 0.5 W1ft2. See Section 143(c). If this box is checked, ENV -4-C must be filled out. when submitting under the Prescriptive Compliance Approach.
Run Initiation Time: 05/23107 07.47.35 Run Code: 1179931655
EnergyPro 4.3 by EnergySoft User Number: 3137 Job Number: 2006796.000 Paae:6 of 12
CERTIFICATE OF COMPLIANCE MECH-I-C I
PROJECT NAME DATE
Komar Desert Center - Bldg H 5/23/2007
---]
u.esigner:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation
certificates. and ODeratlna and maintenance information meet the reouirements of Section 10-103th1 and T1tla Pd Part R
STATEMENT OF COMPLIANCE
❑ MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-3-A: Packaged HVAC Systems Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit. Units with economizers that are Installed at the factory and certified with the
commission do not require equipment testing but do require construction inspection.
❑ MECH-5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
This test required If the unit serves 5,000 h2 of space or less and 25% or more of the ducts are in noncondifioned cr semicondidoned space like an
attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
A
❑ MECH-6-A: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls Installed on new or existing packaged systems must be tested.
❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
Ali new VA fan volume controls installed on new or existing systems must be tested
❑ MECH-8-A: -Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to Milled and hot water systems.
-Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Btu/hr.
-Water-loop Heat Pump Controls
Applies to all new watedoop heat pump systems where the combined loop pumps are greater than 5 hp.
-Variable Frequency Controls Applies to all new distribution pumps on new vadableflow chilled. hydronicheat pump
or condenser water systems where the pumps motors are greater than 5 hp.
Equipment re uiring acceptance testing
EnergyPro 4.3 by EnergySott User Number. 3137 Job Number: 2006796.000 Page:7 of 12
FAIR SYSTEM REQUIREMENTS .. I Part 1 of 2 MECH-2-Cl
(PROJECT NAME DATE
Komar. Desert Center - Bldg H 5/23/2007
SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
MANDATORY MEASURES
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
T-24
Section
AIR SYSTEMS, Central or Single Zone
RTU H1-1, 1-111-2 RTU 2-1
RTU 3-1
2 1
1
Reference on Plans or Specification t
112(a)
7.70 HSPF
7.70 HSPF
7.70 HSPF
112(a)
13.0 SEER / 11.0 EER
13.0 SEER / 11.0 EER
13.0 SEER / 11.0 EER
112(b)
Yes
Yes
Yes
112(c), 115(a)
n/a
n/a
n/a
121(b)
Yes
Yes
Yes
121 b
378 cfm
277 cfm
255 cfm
121 c
No
No
No
121 c
Yes
Yes
Yes
121 c 122(el
Programmable Switch
Programmable Switch
Pro rammable Switch
122(e)
Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required
122(f)
Auto
Auto
Auto
122
n/a
n/a
n/a
123
No
124
R-8.0
I R-8.0
R-8.0
144 a & b
n/a
n/a
n/a
144 a & b
70,202 btuh
35,101 btuh
35,101 btuh
144 a & b
n/a
n/a
n/a
144 a & b
92,576 btuh
45,918 btuh
45,961 btuh
144 c
Constant Volume
Constant Volume
Constant Volume
144 (c
144 c
Yes
Yes
Yes
144 d
No
No
No
144 a
Diff. Enth (Integrated)
Diff. Enth Inte rated
Diff. Enth (integrated)
144 f
Constant Temp
Constant Temp
Constant Tem
144 (f)
Constant Temp
Constant Temp
Constant Temp
144 k
No
I No
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put 'N/A' in the column.
2: Not required for hydronic heating and cooling. Elther enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqf ; Has > 25% duct in unconditioned space. Duct sealing Is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
mun irnnanon lime: u5/-L'3/u/ ul:4/:3ib rtun Gocfe: 1179931655
EnergyPro 4.3 by EnergySoft. User Number. 3137 Job Number: 2006796.000 Page:8 of 12
JAIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-CI
PROJECT NAME DATE
Komar Desert Center - Bldg H 5/23/2007
SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
MANDATORY MEASURES
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
T-24
Section
AIR SYSTEMS Central or Single Zone
RTU H4-1
1
Reference on Plans or Specification 1
112(a) 7.70 HSPF
n/a
112(a) 13.0 SEER / 11.0 EER
35,101 btuh
112(b) Yes
I n/a
112(c), 115(a) n/a
46,166 btuh
121(b) Yes
Constant Volume
121 b) 243 cfm
121 c No
Yes
121 c Yes
No
121(c), 122(e) Programmable Switch
Diff. Enth (Integrated)
122(e) Heating & Cooling Required
Constant Tem
122(f) Auto
Constant Temp
122 n/a
No
123
124 1 R-8.0
144 a & b
n/a
144 a & b
35,101 btuh
144 a & b
I n/a
144 a & b
46,166 btuh
144 c
Constant Volume
144 c
144 c
Yes
144 d
No
144 a
Diff. Enth (Integrated)
144 f
Constant Tem
144 (f)
Constant Temp
144 k
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put °N/A° in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% dud in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
EnergyPro 4.3 by EnergySoft User Number. 3137 Job Number: 2006796.000 Paae:9 of 12
[MECHANICAL VENTILATION MECH-3-CI
NAME
Komar Desert Center - BI
DATE
5/23/2007
PRESCRIPTIVE REHEAT
LIMITATION (Section 144 d )
MECHANICAL VENTILATION Section
121(b)2)
AREA
BASIS
OCCUPANCY
BASIS
VAV MINIMUM
A
B
C
D
E
F
G
H
I
J
K
L
M
N
ZONE/SYSTEM
n
�D7
TNa
v
a
d -an
fDaT
o
rr
���
X Dn
lv 3
Z
m3
DQ
fD o
.,
M9n
N03 0 W
rr
m� B.
Xan
m
_ X1
�d 0
0X
D
n� �0
T�.N
D
o c
neo
-n(0�'
�v a
t7
�z�
y X
CD
a s
x
0 0
w3y
O3X
0 =°
n
-n-
c_
9
�'
D
'1
N
D
-
Lease Space
3,67E
0.25
919
36.8
7.6
278
919
278
640
Restrm
49
0.15
7
7
100
RTU 1-11-1, 1-11-2
Total
926
378
Lease Space
2,337
0.251
564
23.4
7.6
177
584
1771
407
Restrm
4S
0.15
7
7
100
RTU 2-1
Total
592
277
Lease Space
2,04E
0.25
512
20.5
7.6
155
512
155
357
Restrm
49
0.15
7
7
100
RTU 3-1
I
Total
519
255
Lease Space
1,88E
0.25
472
18.9
7.6
143
472
143
329
Restrm
4S
0.15
7
7
100
RTU 1-14-1
Total
479
243
C Minimum ventilation rate per Section 127 Table 121-A
E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes for spaces without fixed sealing.
H Required Ventilation Air REO'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G).
1 Must be areater than orequal to H, or use Transfer Air column N' to make up the difference.
J Design fan supply dm Fan CFM x 30116; or
K condition area h. sq.) x 04 cfmttt. sq.; or
L Maximum of Columns H. J. K, or 300 cfm
M This must be less than or equal to Column L and greater that orequal to the sum of Columns H + N.
N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal
to the difference between the Required Ventilation Air (column Q and the Design Minimum Air (column M), column H • M.
EnergyPro 4.3 by EnergySoft User Numbe- 3137 Job Number: 2006796.000 Page: 10 of 12
MECHANICAL EQUIPMENT DETAILS,
Part 1 of 2 MECH-S-C
PROJECT NAME
Komar Desert Center - BldgH
DATE
5/23/2007
CHILLER AND TOWER SUMMARY
Efficiency
Tons
PUMPS
Equipment Name
Equipment Type
Oty.
Tot.
Oty
GPM
BHP
Motor
Eff.
Drive
Eff.
Pump
Control
DHW BOILER
EnergyI Standby NK AINSUL.
Rated Vol. Condition Factor Loss or Ext.
System Name System Type Distribution Type Oty Input (Gals.) Status or RE Pilot R -Val.
CENTRAL SYSTEM RATINGS
HEATING COOLING
Aux. Condition
System Name System Type Ply Output kW I Eff. Outout Efficiencv Status Economizer Type
Carrier 50HJ0006-5 w/
DCV Packaged DX 5 56,200 0.0 7.70 HSPF 61,000 13.0 SEER / 11.0 EER New Diff. Enth (Integrated)
MECHANICAL EQUIPMENT DETAILS. Part 2 of 2 MECH-5-CI