07-2053 (CSCS) Title 24
t TITLE 24 REPORT Title 24 Report for: Mimi's Cafe -La Quinta 79-765 Highway 111 La Quinta, CA 92253 Project Designer: Lee & Sakahara Architects AIA 16842 Von.Karman Avenue, Suite 300 Irvine, CA 92606-4927 949-261-1100 Report Prepared By: Robert H. Foster FDG Consulting Enginee 17701 Cowan, Suite 23( Irvine, CA 92614 (949) 253 9630 Job Number: 07-080 Date: 7/6/2007 I CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTION DATEt 31 Q By ESC 111 6-d �7 ZGS 2 k - - H �I JUL 13 2007 The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards. This program developed by EnergySoft, LLC - www.energysoft.com. EnergyPro 4.3 by EnergySoft Job Number: 07-080 User Number: 5670 it TABLE OF CONTENTS Cover Page 1 Table of Contents 2 Nonresidential Performance Title 24 Forms 3 Form ENV -MM Envelope Mandatory Measures 12 Form MECH-MM Mechanical Mandatory Measures 13 n EnergyPro 4.3 by EnergySoft Job Number: 07-080 User Number: 5670 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1 PROJECT NAME Mimi's Cafe -La Quinta This Certificate of Compliance lists the building -features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the DATE 7/6/2007 PROJECT ADDRESS 79-765 Highway 111 La Quinta DATE OF PLANS os -22-o7 BUILDING CONDITIONED FLOOR AREA 6,102 sq.Ft. PRINCIPAL DESIGNER - ENVELOPE Lee & Sakahara Architects AIA TELEPHONE 949-261-1100 Building Permit # DOCUMENTATION AUTHOR FDG Consulting Engineers TELEPHONE 949 253 9630 Checked by/Date Enforcement Agency Use GENERAL INFORMATION This Certificate of Compliance lists the building -features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation preparer hereby certifies that the documentation is accurate and complete. DATE OF PLANS os -22-o7 BUILDING CONDITIONED FLOOR AREA 6,102 sq.Ft. Robert H. Foster �CLIMATEZONE 15 BUILDING TYPE ® NONRESIDENTIAL ❑ HIGH RISE RESIDENTIAL HOTELIMOTEL GUEST ROOM PHASE OF CONSTRUCTION ® NEW CONSTRUCTION ❑ ADDITION ENV. LTG. MECH. EXISTING + ADDITION/ALTERATION STATEMENT OF COMPLIANCE This Certificate of Compliance lists the building -features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the California Code of Regulations. This certificate applies only to a Building using the performance compliance approach. The documentation preparer hereby certifies that the documentation is accurate and complete. DOCUMENTATION AUTHOR SIGNATURE DATE Robert H. Foster 7 - & ` 7 The Principal Designer hereby certifys that the proposed building design repr sented in this set of construction documents is consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116, through 118, and 140, 142, 143 or 149 of Title 24, Part 6. ENV. LTG. MECH. 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to sign this document as the person responsible for its preparation; and that I am licensed in the State of California as a civil engineer, mechanical engineer, electrical engineer, or I am a licensed architect. ❑ ❑ ❑ 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section 5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed contractor performing this work. ❑ F1 n 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document because it pertains to a structure or type of work described as exempt pursuant to Business and Professions Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in full in the Nonresidential Manual.) ENVELOPE COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures ENV -1 Required Forms PRINCIPAL ENVELOPE DESIGNER - NAME SIGNATURE LIC. NO. DATE Lee & Sakahara Architects AIA LIGHTING COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures Lighting Compliance Not In The Scope Of This SUUMILLCII Required Forms PRINCIPAL LIGHTING DESIGNER - NAME SIGNATURE LIC. NO. DATE MECHANICAL COMPLIANCE Indicate location on plans of Note Block for Mandatory Measures MECH-1 MECH-2 MECH-3 MECH-5 Required Forms PRINCIPAL MECHANICAL DESIGNER - NAME SIGNATURE LIC. NO. DATE Robert H. Foster -�A-34_1_ 4v -o 7 EnergyPro 4.3 by EnergySoft User Number: 5670 Job Number: 07-080 Paae:3 of 14 1 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 PERF-' PROJECT NAME DATE Mimi's Cafe -La Quinta 7/6/2007 IANN ENERGY COMPONENT Standard Design Space Heating Space Cooling Indoor Fans Heat Rejection Pumps & Misc. Domestic Hot Water Lighting Receptacle Process 0.67 287.30 92.19 0.00 0.00 0.00 85.48 53.52 0.00 TOTALS: 519.15 Percent better than Standard: Proposed Design 489.59 Compliance Margin 0.40 91.17 -62.01 0.00 0.00 0.00 0.00 0.00 0.00 5.7% ( 5.7% 29.56 Sp= Heaft N 0 deg sn— cbaft r.'T sqft. sqft. sqft. Hodl=O-Um maw D ughft R.,AW. Pl- 0 20 40 60 80 100 120140 160180 200 220 240 260 280 k8lulsgft-yr Building Orientation Number of Stories Number of Systems Number of Zones N 0 deg Conditioned Floor Area Unconditioned Floor Area Conditioned Footprint Area Fuel Type 6,102 sqft. sqft. sqft. 1 0 4 6,102 41 Natural Gas Glazing Ratio Standard Proposed Lighting Power Density 1.288 W/sqft. 1.288 W/sqft. Prescriptive Env. Heat Loss 885 Btu/h 827 Btu/h Prescriptive Env. Heat Gain 88,120 Btu/h-F 98,516 Btu/h-F Remarks: EnergyPro 4.3 by EnergySoft User Number: 5670 Job Number: 07-080 Page:4 of 14 Orientation Gross Area Glazing Area Glazing Ratio Front Elevation N 1,784 sqft. 306 sqft. 17.2% Left Elevation (E 1,075 sqft. 109 sqft. 10.1% Rear Elevation S 476 sqft. 95 sqft. 20.0% Right Elevation I (WA Total 340 sqft. 30 sqft. 8.8% Roof 3,675 6,102 sqft. sqft. 540 E::::sqft. sqft. 0.0% Standard Proposed Lighting Power Density 1.288 W/sqft. 1.288 W/sqft. Prescriptive Env. Heat Loss 885 Btu/h 827 Btu/h Prescriptive Env. Heat Gain 88,120 Btu/h-F 98,516 Btu/h-F Remarks: EnergyPro 4.3 by EnergySoft User Number: 5670 Job Number: 07-080 Page:4 of 14 PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1 PROJECT NAME Mimi's Cafe -La Quints DATE 7/6/2007 ZONE INFORMATION System Name Zone Name Occupancy Type Floor Area (sgft.) Inst. LPD (W/sf)1 Ctrl. Credits (W/sf)2 Allowed LPD Proc. Loads (W/sf) Area Tailored (W/S3 (W/S4 AC -4 Zone 4 Kitchen, Food Preparation 2,300 '1.60 AC -3 Zone 3 Dining 1,610 '1.10 AC -2 Zone 2 Dining 1,027 *1.10 AC -1 Zone 1 Dining 1,165 '1.10 Notes: 1. See LTG -2-C (items marked with asterisk, see LTG -2 -C by others) 2. See LTG -4-C 3. See LTG -5-C (by others) 4. See LTG -6-C Items above require special documentation EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST The local enforcement agency should pay special attention to the items specified in this checklist. These items require special written justification and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation submitted. The HVAC S stem 'Trane YHC120" includes Demand Control Ventilation per Standards Section 121. The HVAC S stem "Trane YHC120-2" includes Demand Control Ventilation per Standards Section 121. The HVAC S stem 'Trane YFD181" includes Demand Control Ventilation peE Standards Section 121. The HVAC System "AC -4" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A. The Room "Kitchen" has a Cooling Indoor Design Temperature of 115 degrees F. The HVAC System "AC -3" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A. The Room 'Bistro Dining" has a Cooling Indoor Design Temperature of 115 degrees F. The Room 'Private Dining" has a Cooling Indoor Design Temperature of 115 degrees F. The HVAC System "AC -2" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A. The Room "Entry Vestibule" has a Cooling Indoor Design Temperature of 115 degrees F. The Room "Bar/Lounge/Waiting" has a Cooling Indoor Design Temperature of 115 degrees F. The HVAC System "AC -1" incorporates HERS verified Duct Leakage. Target leakage is calculated and documented on the MECH-5-A. The Room "Garden Dining" has a Cooling Indoor Design Temperature of 115 degrees F. The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and documentation for their use have been provided by the applicant. nature or EnergyPro 4.3 by EnergySoft User Number: 5670 Job Number: 07-080 Page:5 of 14 1 CERTIFICATE OF COMPLIANCE ENV -1-C PROJECT NAME DATE Mimi's Cafe -La Quinta 7/6/2007 OPAQUE SURFACES # Surface Type Area U -Fac. Insulation Cay. Cont. Act. Am. Tilt Cond: Status Joint Appendix IV Reference Location I Comments 1 Roof 2.30 0.048 R-19 R-0.0 0 0 New 01-A14 Zone 4 2 Wall 65C 0.110 R-11 R-0.0 0 90 New 09-A2 Zone 4 3 Roof 1,11 0.048 R-19 R-0.0 0 0 New 01-A14 Zone 3 4 Wall 35F, 0.110 R-11 R-0.0 0 90 New 09-A2 Zone 3 5 Roof 50 0.048 R-19 R-0.0 0 0 New 01-A14 Zone 3 6 Wall 310 0.110 R-11 R-0.0 270 90 New 09-A2 Zone 3 7 Wall 19 0.110 R-11 R-0.0 0 90 New 09-A2 Zone 3 8 Roof 91 0.048 R-19 R-0.0 0 0 New 01-A14 Zone 2 9 Wall 9 0.110 R-11 R-0.0 90 90 New 09-A2 Zone 2 10 Wall 9E 0.110 R-11 R-0.0 0 90 New 09-A2 Zone 2 11 IRoof 93 0.048 R-19 R-0.0 0 0 New 01-A14 Zone 2 12 Wall 27f 0.110 R-11 R-0.0 90 90 New 09-A2 Zone 2 13 Wall 18 0.110 R-11 R-0.0 0 90 New 09-A2 Zone 2 14 Roof 1,16 0.048 R-19 R-0.0 0 0 New 01-A14 Zone 1 15 Wall 59 0.110 R-11 R-0.0 90 90 New 09-A2 Zone 1 16 Wall 381 0.110 R-11 R-0.0 180 90 New 09-A2 Zone 1 - N. t, A, R (New, Existing, Altered, Removed) FENESTRATION SURFACES FE I 1 Standards Table 116-A and B. Certificate shall be filed in the contractors omiect office dudnn cnnstn.Ninn and in tha h,fiidinn e� �ffi- ano, r t -mi„ # Type Area U -Fac' SHGC2 Act. Am. Cond. Stat. Glazin T e Location/ Comments 1 Window Front N 120 0.350 NFRC 0.62 NFRC 0 New Low -E Dual Pane Zone 3 2 Window Right 4.0 7.5 30 0.350 NFRC 0.62 NFRC 270 New Low -E Dual Pane Zone 3 3 Window Front N 62 0.350 NFRC 0.62 NFRC 0 New Low -E Dual Pane Zone 3 4 Window Left E 12 0.350 NFRC 0.62 NFRC 90 New Low -E Dual Pane Zone 2 5 Window Front N 100 0.350 NFRC 0.62 NFRC 0 New Low -E Dual Pane Zone 2 6 Window Left E 12 0.350 NFRC 0.62 NFRC 90 New Low -E Dual Pane Zone 2 7 Window Front N 24 0.350 NFRC 0.62 NFRC 0 New Low -E Dual Pane Zone 2 8 Window Left E 85 0.350 NFRC 0.62 NFRC 90 New Low -E Dual Pane Zone 1 9 Window Rear S 95 0.350 NFRC 0.62 NFRC 180 New Low -E Dual Pane Zone 1 MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES (1 u -tactor type: 116-A Detault Table from standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value. (2 SHGC Type: 1168 Default Table from Standards, COG Center of Glass, NFRC Labeled Value EXTERIOR SHADING # Exterior Shade Type SHGC Window Hgt. Wd. Overhang Left Fin Right Fin Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t. 1 None 0.76 4.0 30.0 2.5 0.1 2.0 2.0 2 None 0.76 4.0 7.5 2.5 0.1 2.0 2.0 3 None 0.76 4.0 15.5 2.5 0.1 2.0 2.0 4 None 0.76 1 4.0 3.0 2.5 0.1 2.0 2.0 5 None 0.76 8.0 12.5 6.0 0.1 6.0 6.0 6 None 0.76 4.0 3.0 2.5 0.1 2.0 2.0 7 None 0.76 4.0 6.0 2.5 0.1 2.0 2.0 8 None 0.76 4.0 21.0 2.5 0.1 2.0 2.0 9 None 0.76 4.0 24.0 2.5 0.1 2.0 2.0 MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES f I r no proposea Duttamg is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 1112, a ceiling height greater than 15 feet, and an LPD for general l_J lighting of at least 0.5 Wfk2. See Section 143(c). If this box Is checked, ENV4C must be filled out. when submitting under the Prescriptive Compliance Approach. EnergyPro 4.3 by EnergySoft User Number: 5670 Job Number. 07-080 Page:6 of 14 1 CERTIFICATE OF COMPLIANCE MECH-1-C PROJECT NAME Mimi's Cafe -La Quinta DATE 7/6/2007 Designer: This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work appropriately. Building Departments: SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for Code Compliance. In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation certificates and operatinq and maintenance information meet the re uirements of Section 10-1 03 b and Title 24 Part 6. STATEMENT OF COMPLIANCE jo MECH-2-A: Ventilation System Acceptance Document -Variable Air Volume Systems Outdoor Air Acceptance -Constant Air Volume Systems Outdoor Air Acceptance Equipment requiring acceptance testing kc - 1 4kc - H Test required on all New systems both New Construction and Retrofit. © MECH-3-A: Packaged HVAC Systems Acceptance Document Equipment requiring acceptance testing Test required on all New systems both New Construction and Retrofit. MECH-4-A: Air -Side Economizer Acceptance Document L- ' Equipment requiring acceptance testing C y Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the commission do not require equipment testing but do require construction inspection. ® MECH-5-A: Air Distribution Acceptance Document Equipment requiring acceptance testing This test required If the unit serves 5,000 tt2 of space or less and 25% or more of the duds are in nonoonditioned or semiconditioned space like an • attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend duds, replace duds or replace the packaged unit. �C MECH-6-A: Demand Control Ventilation Acceptance Document Arc Equipment requiring acceptance testing -1 `,, Ac --5 All new DCV controls installed on new or existing packaged systems must be tested. ❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document L Equipment requiring acceptance testing All new VA fan volume controls installed on new or existing systems must be tested ❑ MECH-8-A: -Hydronic System Control Acceptance Document -Variable Flow Controls Applies to chilled and hot water systems. -Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header. -Supply Water Temperature Reset Controls Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Btulhr. -Water-loop Heat Pump Controls Applies to all new waterioop heat pump systems where the combined loop pumps are greater than 5 hp. -Variable Frequency Controls Applies to all new distribution pumps on new variable flow chilled, hydronic heat pump or condenser water systems where the pumps motors are greater than 5 hp. Equipment requiring acceptance testing EnergyPro 4.3 by EnergySoft User Number. 5670 Job Number: 07-080 Page:7 of 14 AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C PROJECT NAME DATE Mimi's Cafe -La Quinta 7/6/2007 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put'N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. AIR SYSTEMS, Central or Single Zone AC -4 AC -3 AC -2 1 1 1 Reference on Plans or Specification 1 112(a) 2.20 COP 2.20 COP 2.20 COP 112(a) 11.3 EER 11.5 EER 11.2 EER 112(b) Yes Yes Yes 112(c), 115(a), n/a n/a n/a 121(b) Yes Yes Yes 121 b 345 cfm 805 cfm 514 cfm 121 c No No No 121 c No Yes Yes 121(c), 122 a Pro rammable Switch Programmable Switch Programmable Switch 122(e) Heating & Cooling Required Heating & Cooling Required Heating & Cooling Required 122 Auto Auto Auto 122(g) n/a n/a n/a 123 124 R-8.0 R-8.0 R-8.0 144 a & b n/a n/a n/a 144 a & b 76,198 btuh 126,788 btuh 75,886 btuh 144 a & b n/a n/a n/a 144 a & b 160,147 btuh 215,891 btuh 123,935 btuh 144 c Constant Volume Constant Volume Constant Volume 144 (c 144 c Yes Yes Yes 144 d No No No 144 a Diff. Tem (integrated) Diff. Tem (Integrated) Diff. Tem (Integrated) 144 Constant Temp Constant Temp Constant Tem 144 (f) Constant Temp Constant Temp Constant Temp 144 (k) No No No 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF -1 for performance method duct sealing requirements. EnergyPro 4.3 by EnergySoft User Number. 5670 Job Number: 07-080 Paoe:8 of 14 1 AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C PROJECT NAME DATE Mimi's Cafe -La Quinta 7/6/2007 SYSTEM FEATURES ITEM OR SYSTEM TAG(S) Number of Systems T-24 MANDATORY MEASURES Section Heating Equipment Efficiency Cooling Equipment Efficiency Heat Pump Thermostat Furnace Controls Natural Ventilation Minimum Ventilation VAV Minimum Position Control Demand Control Ventilation Time Control Setback and Setup Control Outdoor Damper Control Isolation Zones Pipe Insulation Duct Insulation PRESCRIPTIVE MEASURES Calculated Heating Capacity :x 1.43 2 Proposed Heating Capacity 2 Calculated Sensible Cooling Capacity x 1.212 Proposed Sensible Cooling Capacity 2 Fan Control DP Sensor Location Supply Pressure Reset (DDC only) Simultaneous Heat/Cool Economizer Heating Air Supply Reset Cooling Air Supply Reset Duct Sealing for Prescriptive Compliance 1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" in the column. 2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1. 3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance, see PERF -1 for performance method duct sealing requirements. AIR SYSTEMS, Central or Single Zone AC -1 1 Reference on Plans or Specification t 112(a) 2.20 COP 112(a) 11.2 EER 112(b) Yes 112(c), 115(a) n/a 121(b) Yes 121 b 582 cfm 121 c No 121 c Yes 121(c), 122(e) Programmable Switch 122(e) Heating & Cooling Required 122 Auto 122(g) n/a 123 124 R-8.0 144 a & b n/a 144 a & b 75,886 btuh 144 a & b n/a 144 a & b 128,162 btuh 144 c Constant Volume 144 c 144 c Yes 144 d No 144 a Diff. Tem (Integrated) 144 Constant Tem 144 (f) Constant Temp 144 k No EnergyPro 4.3 by EnergySoft User Number: 5670 Job Number: 07-080 Page:9 of 14 1 MECHANICAL VENTILATION MECH-3-C ROJECT NAME Mimi's Cafe -La Quinta DATE 7/6/2007 PRESCRIPTIVE REHEAT LIMITATION Section 144(d MECHANICAL VENTILATION Section 121(b)2) AREA BASIS OCCUPANCY BASIS VAV MINIMUM A B C D E F G H I J K L M N ZONE/SYSTEM o yDii TW:►' d I;A c mvn W Mn -n 3 °o 0 a3 ao�� x D� CiN T m 3 vc rD3 9Q 0 v x-00 , �T 3 Q 3 M0 x00 -n r- �- 3"" ,. m �o3iID OKcox O< D < 033.E 3DiC 3 No 3 C) 0 39 y %C O T 3x O x b Tn 0 c w3m 07x Oy 0 T? g M (A LA. »� 0•3 » P D 'm ti. D Zone 4 2,3oq 0.15 345 1 345 345 AC -4 Total 345 345 Zone 3 1,61C 0.50 805 805 805 AC -3 Total 805 805 Zone 2 1,027 0.50 514 514 514 AC -2 Total 514 514 Zone 1 1,16E 0.50 582 582 582 AC -1 Total 582 582 C Minimum ventilation rate per Section 121 Table 121-A E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed seating. H Required Ventilation Air READ V.A. is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G). I Must be greater than orequal to H or use Transfer Air column N to make up the difference. J Design fan supply cfm Fan CFM x 30%; or K Condition area ft. sq.) x 04 cfmtft. sq.; or L Maximum of Columns H, J, K, or 300 cfm M This must be less than orequal to Column L and greater that orequal to the sum of Columns H + N. - N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M. EnergyPro 4.3 by EnergySoft User Number. 5670 Job Number: 07-080 Page: 10 of 14 MECHANICAL EQUIPMENT DETAILS Part 1 of 2 MECH-5-C PROJECT NAME Mimi's Cafe -La Quinta COOLING DATE 7/6/2007 CHILLER AND TOWER SUMMARY S stem T e Qty Output Aux. kW Eff. Output Efficiency Efficiency Tons PUMPS Packaged DX Equipment Name Equipment Type Qty. Tot. Qty GPM BHP Motor Eff. Drive Eff. Pump Control Packaged DX 1 203,000 0.012.20 COP 188,660 11.5 EER New Diff. Temp (Integrated) Trane YHC120-2 Packaged DX 1 121,500 0.0 2.20 COP 108,410 11.2 EER New Diff. Temp (Integrated) Trane YHC120 Packa ed DX 1 121,500 0.0 2.20 COP 111,780 11.2 EER New Diff. Tem (Integrated 1DHW / BOILER SUMMARY Energy Standby ITANK INSUL. Rated Vol. Condition Factor Loss or Ext. System Name System Type Distribution Type Qty Input (Gals.) Status I or RE Pilot I R -Val. CENTRAL SYSTEM RATINGS HEATING COOLING System Name S stem T e Qty Output Aux. kW Eff. Output Efficiency Condition Status Economizer Type Trane YFD151 Packaged DX 1 122,000 0.0 2.20 COP 143,110 11.3 EER New Diff. Temp (Integrated) Trane YFD181 Packaged DX 1 203,000 0.012.20 COP 188,660 11.5 EER New Diff. Temp (Integrated) Trane YHC120-2 Packaged DX 1 121,500 0.0 2.20 COP 108,410 11.2 EER New Diff. Temp (Integrated) Trane YHC120 Packa ed DX 1 121,500 0.0 2.20 COP 111,780 11.2 EER New Diff. Tem (Integrated ENVELOPE MANDATORY MEASURES ENV -MM NAME Mimi's Cafe -La Quinta DATE 7/6/2007 DESCRIPTION Designer Enforcement §118(,) Installed Insulating Material shall have been certified by the manufacturer to comply with the California Quality Standards for insulating material, Title 20, Chapter 4, Article 3. FXJ § 118(c) All Insulating Materials shall be installed in compliance with the flame spread rating and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2. © ,§ 117(a) All Exterior Joints and openings in the building that are observable sources of air leakage shall be caulked, gasketed, weatherstripped or otherwise sealed. © §116(b) Site Constructed Doors, Windows and Skylights shall be caulked between the unit and the building, and shall be weatherstripped (except for unframed glass doors and fire doors). § 116(a)1 Manufactured Doors and Windows installed shall have air infiltration rates not exceeding those shown in Table Number 1-E. of the Standards. Manufactured fenestration products must be labeled for U -value according to NFRC procedures. ❑k '§118(e) Demising Walls in Nonresidential Buildings: The opaque portions of framed demising walls in nonresidential buildings shall have insulation with an installed R -value of no less than R-13 between framing members. EnergyPro By EnergySoft User Number. User Job Number. 07-080 Page: 12 of 14 . A. MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM NAME Mimi's Cafe -La Quinta DATE 7/6/2007 DESCRIPTION Designer Enforcement Equipment and Systems Efficiencies ,®§111 Any appliance for which there is a California standard established in the Appliance Efficiency Regulations will comply with the applicable standard. F§ 115(a) Fan type central furnaces shall not have a pilot light. § 123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees Fahrenheit, or within HVAC equipment, shall be insulated in accordance with Standards Section 123. © § 124 Air handling duct systems shall be installed and insulated in compliance with Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards. Controls § 122(e) Each space. conditioning system shall be installed with one of the following: ❑X § 122(e)1A Each space conditioning system serving building types such as offices and manufacturing facilities (and all others not explicitly exempt from the requirements of Section 112 (d)) shall be installed with an automatic time switch with an accessible manual override that allows operation of the system during off -hours for up to 4 hours. The time switch shall be capable of programming different schedules for weekdays and weekends and have program backup capabilities that prevent the loss of the device's program and time setting for at least 10 hours if power is interrupted; or F§ 122(e)1B An occupancy sensor to control the operating period of the system; or ❑ § 122(e)1C A 4 -hour timer that can be manually operated to control the operating period of the system. § 122(e)2 Each space conditioning system shall be installed with controls that temporarily restart and temporarily operate the system as required to maintain a setback heating and/or a setup cooling thermostat setpoint. § 122(g) Each space conditioning system serving multiple zones with a combined conditioned floor area more than 25,000 square feet shall be provided with isolation zones. Each zone: shall not exceed 25,000 square feet; shall be provided with isolation devices, such as valves or dampers, that allow the supply of heating or cooling to be setback or shut off independently of other isolation areas; and shall be controlled by a time control device as described above. § 122(a&b) Each space conditioning system shall be controlled by an individual thermostat that responds to temperature within the zone. Where used to control heating, the control shall be adjustable down to 55 degrees F or lower. For cooling, the control shall be adjustable up to 85 degrees F or higher. Where used for both heating and cooling, the control shall be capable of providing a deadband of at least 5 degrees F within which the supply of heating and cooling is shut off or reduced to a minimum. ❑X § 122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable . setpoint stops accessible only to authorized personnel. § 112(b) Heat pumps shall be installed with controls to prevent electric resistance supplementary heater operation when the heating load can be met by the heat pump alone. EnergyPro By EnergySoft User Number: User Job Number. 07-080 Page: 13 of 14 MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM ECT NAME Mimi's Cafe -La Quinta DATE 7/6/2007 Description Designer Enforcement Ventilation § 121(e) Controls shall be provided to allow outside air dampers or devices to be operated at the ventilation rates as specified on these plans. § 122(f) Gravity or automatic dampers interlocked and closed on fan shutdown shall be provided on the outside air intakes and discharges of all space conditioning and exhaust systems. § 122(f) All gravity ventilating systems shall be provided with automatic or readily accessible manually operated dampers in all openings to the outside, except for combustion air openings. ❑) § 121(f)1 Air Balancing: The system shall be balanced in accordance with the National Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or Associated Air Balance Council (AABC) National Standards (1989); or ❑ § 121(f)2 Outside Air Certification: The system shall provide the minimum outside air as shown on the mechanical drawings, and shall be measured and certified by the installing licensed C-20 mechanical contractor and certified by (1) the design mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) the person with overall responsibility for the design of the ventilation system; or F—] § 121(03 Outside Air Measurement: The system shall be equipped with a calibrated local or remote device capable of measuring the quantity of outside air on a continuous basis and displaying that quantity on a readily accessible display divice; or F] § 121(04 Another method approved by the Commission. Service Water Heating Systems ❑ §113(b)2 if a circulating hot water system is installed, it shall have a control capable of automatically turning off the circulating pump(s) when hot water is not required. ❑ § 113(c) Lavatories in restrooms of public facilities shall be equipped with controls to limit the outlet temperature to 110 degrees F. EnergyPro By EnergySoft User Number: User Job Number: 07-080 Page: 14 of 14