07-2956 (RC) Title 24TITLE 24 REPORT
Title 24 Report for:
TEA HOUSE
TENANT 6 TH 79-630 / 79-710 HIGHWAY III
LA QU I NTA, CA 92253
CITY OF LA QUINTq
Project Designer: BUILDING & SAFETY DEPT.
Fo PaROYVED
Repo--- pared By:
RAYMON: 0NG, P. E.
PERFECT DESIGN'& E`NGINEERING, INC.
2416 W Valley
AIN rr, A CA'91'903
x('626)289-8808
I
Job Number:
R072266R
BY
By Date: J'l,9 �FCHAN�GP� \�v
6/5/2008
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoff, LLC - www.energysoft.com.
EnergyPro 4.3 by EnergySoft Jobl i=6t r: R072286M .f;-- User Number: 1919
TABLE OF CONTENTS
Cover Page
Table of Contents
Nonresidential Performance Title 24 Forms
Form ENV -MM. Envelope Mandatory Measures
Form MECH-MM Mechanical Mandatory Measures
HVAC System Heating and Cooling Loads Summary
Room Load Summary
Room Heating Peak Loads
Room Cooling Peak Loads
Room Cooling Coil Loads
1
2
3
12
13
15
17
19
21
23
EnergyPro 4.3 by EnergySoft Job Number: R072266R User Number: 1919
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1
PROJECT NAME
TEA HOUSE
This Certificate of Compliance lists the building features and performance specif' eeded to c Title 24, Parts 1 and 6 of the
DATE
6/5/2008
PROJECT ADDRESS
DOCUMENTATION AUTHOR SIGNATURE DATE
1 15
TENANT 6 TH 79-630/79-710 HIGHWAY III
LA QUINTA
HIGH RISE RESIDENTIAL
PRINCIPAL DESIGNER - ENVELOPE
TELEPHONE
Building Permit #
DOCUMENTATION AUTHOR
PERFECT DESIGN & ENGINEERING, INC.
TELEPHONE
(626) 289-8808
Checked by/Date
Enforcement Agency Use
L
02-22-2008
This Certificate of Compliance lists the building features and performance specif' eeded to c Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using t `e m c co Ii e` roach.
2,643 Sq.Ft.
DOCUMENTATION AUTHOR SIGNATURE DATE
1 15
BUILDING TYPE ® NONRESIDENTIAL
consistent with the other compliance forms and worksheets, with the specifica 0 i, other calculations submitted with thi
HIGH RISE RESIDENTIAL
HOTEUMOTEL GUEST ROOM
PHASE OF CONSTRUCTION NEW CONSTRUCTION
-�iT1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
ADDITION
EXISTING + ADDITIOWALTERATION
STATEMENT OF COMPLIANCE MEN F
This Certificate of Compliance lists the building features and performance specif' eeded to c Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using t `e m c co Ii e` roach.
The documentation preparer hereby certifies that the documentation is accurate a 63 7o
DOCUMENTATION AUTHOR SIGNATURE DATE
RAYMOND M. ZHONG P.E. "Y I
The Principal Designer hereby certifys that the proposed building design re onstruction documents is
consistent with the other compliance forms and worksheets, with the specifica 0 i, other calculations submitted with thi
permit application. The proposed building as designed meets the energy effici ents contained in sections 110, 116,
through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
ENV. LTG. MECH.
-�iT1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, or I am a licensed architect.
R ❑ F—] 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section
5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
❑ F-1 ❑ 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in
full in the Nonresidential Manual.)
ENVELOPE COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
ENV -1
Required Forms
PRINCIPAL ENVELOPE DESIGNER - NAME
SIGNATURE
LIC. NO.
DATE
LIGHTING COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
Lighting Compliance Not In The Scope Of
Required Forms
1 1 ds Submittal
PRINCIPAL LIGHTING DESIGNER - NAME
SIGNATURE
LIC. NO.
DATE
MECHANICAL COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures tipFESSION
Required Forms ME H-3 MECH-5
PRINCIPAL MECHANICAL DESIGNER - NAME SIGNATUREc.� LryDATE
PERFECT DESIGN & ENGINEERING �? o. 76
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 2 of 3 PERF-'
PROJECT NAME DATE
TEA HOUSE 6/5/2008
ANNUAL TDV ENE§
ENERGY COMPONENT
Space Heating
Space Cooling
Indoor Fans
Heat Rejection
Pumps & Misc.
Domestic Hot Water
Lighting
Receptacle
Process
Standard
Design
Proposed
Design
0.50
425.78
107.83
0.00
0.00
69.80
72.98
30.51
91.54
Compliance
Margin
TOTALS: 929.65 798.95 130.70 L — - - u°nusa -yr i
Percent better than Standard: 14.1% ( 15.6% excluding process)
BUILDING COMPLIES
Building Orientation
Number of Stories
Number of Systems
Number of Zones
(W)270deg (W)270d
Conditioned Floor Area
Unconditioned Floor Area
Conditioned Footprint Area
Fuel Type
2,643
sqn.
sgft.
sgft.
1
0
3
2,643
2
I Natural Gas
Glazing
Ratio
Standard Proposed
Lighting Power Density 1.100 wisgft. 1.196 wisgft.
Prescriptive Env. Heat Loss 470 Btum 662 Btum
Prescriptive Env. Heat Gain 49,790 Btu/h-F 84,921 Btuth-F
Remarks:
Standard Building (Compliance)
EnergyPro 4.3 by EnergySoft User Number: 1919 Job Number: R072266R Page:4 of 24
Orientation
Gross Area
Glazing Area
Glazing
Ratio
Front Elevation (W)
441
sgft.
216
sgft.
48.9%
Left Elevation (N)
600
sgft.
0
sgft.
0.0%
Rear Elevation (E)
441
sqn.
0
sgft.
0.0%
Right Elevation (S)i
Total
Roof
600
2,082
2,643
sqtt.
sqn.
sqn.sgft.
158
374
sgft.
sgft.
26.3%
Standard Proposed
Lighting Power Density 1.100 wisgft. 1.196 wisgft.
Prescriptive Env. Heat Loss 470 Btum 662 Btum
Prescriptive Env. Heat Gain 49,790 Btu/h-F 84,921 Btuth-F
Remarks:
Standard Building (Compliance)
EnergyPro 4.3 by EnergySoft User Number: 1919 Job Number: R072266R Page:4 of 24
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1
PROJECT NAME
TEA HOUSE
DATE
6/5/2008
ZONE INFORMATION
System Name Zone Name Occupancy Type
Floor
Area
(sqft.)
Inst.
LPDCredits
(W/sf)1
Ctrl.
(W/sf?
Allowed LPD
Proc.
Loads
(W/sf)
Area Tailored
/s 3 (W/S4
AC -1 & 3 AREA (E) FLOOR PLAN
Dining
2,043
0.773
1.500
AC -2 AREA (E) FLOOR PLAN
Dining
600
2.633
1.500
Notes: 1. See LTG -2-C 2. See LTG -4-C
(items marked with asterisk, see LTG -2 -C by others)
3. See LTG -5-C
(by others)
4. See LTG -6-C
Items above require special documentation
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
The local enforcement agency should pay special attention to the items specified In this checklist. These items require special written justification
and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
submitted.
The DHW System "RHEEM HE80-130" is a Large Gas water heater with Pilot Loss = 0 btuh.
r ne excepiionai reatures ustea in ims performance approach application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Authorized
EnergyPro 4.3 by EnergySoft User Number: 1919 Job Number: R072266R Pape:5 of 24
CERTIFICATE OF COMPLIANCE ENV -1-C
(PROJECT NAME DATE
TEA HOUSE 6/5/2008
OPAQUE SURFACES
#
Surface
Type
Area
U -Fac.
Insulation
Cay. Cont.
Act.
Am.
Tilt
Cond:
Status
Joint Appendix
IV Reference
Location / Comments
1
Wall
22E
0.069
R-21
R-0.0
270
90
Existing
09-A6
E FLOOR PLAN
2
Roof
2,04
0.025
R-38
R-0.0
0
0
Existing
01-A18
E FLOOR PLAN
3
Wall
44'0.069
(N)
R-21
R-0.0
90
90
Existing
09-A6
E FLOOR PLAN
4
Wall
50C
0.069
R-21
R-0.0
0
90
Existing
09-A6
(E) FLOOR PLAN
5
Wall
441
0.069
R-21
R-0.0
180
90
Existing
09-A6
E FLOOR PLAN
6
Roof
60
0.025
R-38
R-0.0
0
0
Existing
01-A18
E FLOOR PLAN
7
Wall
Left
0.069
R-21
R-0.0
270
90
Existing
09-A6
(E) FLOOR PLAN
8
Wall
Right
0.069
R-21
R-0.0
90
90
Existing
09-A6
E FLOOR PLAN
9
Wall
10
0.069
R-21
R-0.0
0
90
Existing
09-A6
(E) FLOOR PLAN
10 lWall
0.069
R-21
R-0.0
180
90
Existing
09-A6
E FLOOR PLAN
J, E, A. R (New, Existit
More than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default Ll -factors from
Standards Table 116-A and B. Certificate shall be filed in the contractor's oroiect office during construction and In the buildinn manannrc nffice after cnnstmctinn
#
T e
Area U -Fac'
SHGC2
Act.
Azm.
Cond.
Stat.
Glazing Type
Location/
Comments
1
Window
Front
W
216 1.2801116-A
0.80
116-B
270
Existing
Sin le Metal Clear
E FLOOR PLAN
2
Window
Rear
(E)
0 1.2801116-A
0.80
116-B
90
Existing
Single Metal Clear
(E) FLOOR PLAN
3
Window
Left
(N)
0 1.280 116-A
0.80
116-B
0
Existing
Single Metal Clear
(E) FLOOR PLAN
4
Window
Right
S
158 1.280 116-A
0.80
116-B
180
Existing
Single Metal Clear
E FLOOR PLAN
5
Window
Front
W
0 1.280 116-A
0.80
116-B
270
Existing
Single Metal Clear
E FLOOR PLAN
6
Window
Rear
(E)
0 1.280 116-A
0.80
116-B
90
Existing
Single Metal Clear
(E) FLOOR PLAN
7
Window
Left
(N)
0 1.280 116-A
0.80
116-B
0
Existing
Single Metal Clear
(E) FLOOR PLAN
8
Window
Right
S
0 1.280 116-A
0.80
116-B
180
Existin
Single Metal Clear
E FLOOR PLAN
1 U -factor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value.
2 SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
#): Exterior Shade Type
SHGC
Window
Hgt. Wd.
Overhang Left Fin Right Fin
Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
1 None
0.76
2 None
0.76
3 None
0.76
0.0 0.0
0.0 0.0 0.0 0.0
4 None
0.76
5 None
0.76
6 None
0.76
7 None
0.76
0.0 0.0
0.0 0.0 0.0 0.0
8 None
0.76
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
The proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a ceiling height greater then 15 feet, and an LPD for general
lighting of at least 0.5 Wfl12. See Section 143(c). If this box Is checked, ENV4-C must be filled out. when submitting under the Prescriptive Compliance Approach.
EnergyPro 4.3 by EnergySoft User Number: 1919 Job Number: R072266R Page:6 of 24
CERTIFICATE OF COMPLIANCE MECH-I-C
PROJECT NAME DATE
TEA HOUSE 6/5/2008
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation
certificates, and operating and maintenance information meet the reauirements of Section 10-1031b1 and Title 94 Part R
STATEMENT OF COMPLIANCE
❑ MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-3-A: Packaged HVAC Systems Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the
commission do not require equipment testing but do require construction inspection.
❑ MECH-5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
This test required It the unit serves 5,000 R2 of space or less and 25% or more of the ducts are in nonconditioned or semiconditioned space like an
attic. New systems that most the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
❑ MECH-6-A: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls installed on new or existing packaged systems must be tested.
❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
All new VA fan volume controls installed on new or existing systems must be tested
❑ MECH-8-A: -Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to chilled and hot water systems.
-Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Btu/hr.
-Water-loop Heat Pump Controls
Applies to all new waterioop heat pump systems where the combined loop pumps are greater than 5 hp.
-Variable Frequency Controls Applies to all new distribution pumps on new variable flow chilled, hydronic heat pump
or condenser water systems where the pumps motors are greater than 5 hp.
Equipment requirin acceptance testing
EnergyPro 4.3 by EnergySoft User Number: 1919 Job Number: R072266R Page:7 of 24
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
PROJECT NAME DATE
TEA HOUSE 6/5/2008
SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economizer
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
AIR SYSTEMS Central or Single Zone
AC -1 & 3 AREA AC -2 AREA
2 1
Reference on Plans or Specification t
112(a)
79% AFUE
79% AFUE
112(a)
13.0 SEER / 13.0 EER
10.0 SEER / 10.0 EER
112 b
n/a
n/a
112(c), 115(a)
n/a
n/a
121(b)
Yes
Yes
121 b
1022 cfm
300 cfm
121 c
No
No
121 c
No
No
121(c), 122(e)
Programmable Switch
Programmable Switch
122(e)
Heating & Cooling Required
Heating & Cooling Required
122
Auto
Auto
122
n/a
n/a
123
124
R-8.0
R-8.0
144 a & b
n/a
n/a
144 a & b
141,480 btuh
70,740 btuh
144 a & b
n/a
n/a
144 a & b
83,471 btuh
39,425 btuh
144 c
Constant Volume
Constant Volume
144 c
144 c
Yes
Yes
144 d
No
No
144 a
No Economizer
No Economizer
144
Constant Temp
Constant Tem
144(f)
Constant Temp
Constant Temp
144 k
No
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put °N/A° in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sqft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
EnergyPro 4.3 by EnergySoft User Number: 1919 Job Number: R072266R Page:8 of 24 1
WATER SIDE SYSTEM REQUIREMENTS Part 2 of 2 MECH-2-C
(PROJECT NAME DATE
TEA HOUSE 6/5/2008
SYSTEM FEATURES
2 WATER SIDE SYSTEMS: Chillers, Towers, Boilers, Hvdronic LooDS
ITEM OR SYSTEM TAG(S)
Number of Systems
MANDATORY MEASURES
Equipment Efficiency
Pipe Insulation
PRESCRIPTIVE MEASURES
Calculated Capacity
Proposed Capacity
Tower Fan Controls
Tower Flow Controls
Variable Flow System Design
Chiller and Boiler Isolation
CHW and HHW Reset Controls
WLHP Isolation Valves
VSD on CHW, CW & WLHP Pumps > 5
HP
DP Sensor Location
T-24
Section Reference on Plans or Specification'
112(a)
123
1: For each chiller, cooling tower, boiler, and hydronic loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and paragraph
number where the required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Water side systems include wet side system using other liquids such as glycol or brine.
ITEM OR SYSTEM TAG(S)
Number of Systems
MANDATORY MEASURES
Water Heater Certification
Water Heater Efficiency
Service Water Heating Installation
Pool and Spa Efficiency and Control
Pool and Spa Installation
Pool Heater - No Pilot Light
Spa Heater - No Pilot Light
113 (a)
113 (b)
113 (c)
114 (a)
114 (b)
115 (c)
115 d
Service Hot Water, Pool Heating
DHW Heater
1
RHEEM HE80-130
95%
n/a
n/a
n/a
n/a
Reference on Plans or Specification'
1: For each water heater, pool heat and domestic water loop (or groups of similar equipment) fill in the reference to sheet number and/or specification section and
paragraph number where the required features are documented. If a requirement is not applicable, put "N/A" ins the column.
Run Initiation Time: 06/05/08 16:06:52 Run Code: 1212710812
EnergyPro 4.3 by EnergySoft User Number: 1919 Job Number: R072266R Page•9 of 24
MECHANICAL VENTILATION MECH-3-C
PROJECT NAME
TEA HOUSE
DATE
6/5/2008
PRESCRIPTIVE REHEAT
LIMITATION Section 144 d )
MECHANICAL VENTILATION Section 121(b)2)
AREA
BASIS
OCCUPANCY
BASIS
VAV MINIMUM
A
B
C
I D
E
F
G
H
1
J
K
L
M
N
ZONE/SYSTEM
0
M
1n
C.0 A�'
c
X D
;vn
'
Q
Jn
m
o
0
0
X
M G
n
-n
Np
nM°
Msnn°v
X
;:v
A0
03
a
'Ca
(mnd
m
(E) FLOOR PLAN
2,043
0.50
1,022
68.1
15.0
1,022
1,022
1,022
AC -1 & 3 AREA
Total
1,022
1,022
(E) FLOOR PLAN
60C
0.50
300
20.0
15.0
300
300
300
AC -2 AREA
Total
300
300
C Minimum ventilation rate per Section 121, Table 121-A
E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes for spaces without fixed seating.
H Required Ventilation Air (REO'D V.A.) is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS (column D or G).
1 Must be greater than orequal to H, or use Transfer Air column N to make up the difference.
J Design fan supply cfm (Fan CFM) x 30%; or
K Condition area (ft. sq.) x 04 cfm/ft. sq.; or
L Maximum of Columns H, J, K, or 300 cfm
M This must be less than orequal to Column L and greater that orequal to the sum of Columns H + N.
N Transfer air must be provided where the Required Ventilation Air (column I) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal
to the difference between the Required Ventilation Air (column I) and the Design Minimum Air (column M), column H - M.
EnergyPro 4.3 by EnergySoft User Number: 1919 Job Number: R072266R Page: 10 of 24
MECHANICAL EQUIPMENT DETAILS
Part 1 of 2 MECH-5-C
PROJECT NAME
TEA HOUSE
DATE 6/5/2008
CHILLER AND TOWER SUMMARY
HP
Type
In Plenum
Outside
Buried
Add 1/2"
Insulation
Eff iclency
Tons
PUMPS
Equipment Name
Equipment Type
Qty.
Tot.
City
GPM
BHP
Motor
Eff.
Drive
Eff.
Pump
Control
CENTRAL SYSTEM RATINGS
HEATING
COOLING
System Name
System Type
Qtv1
Outout
Aux.
kW
Eff.
Outout
Eff Iclency
Condition
Status
Economizer Type
CARRIER 48SD-060090
Packaged DX
2
70,740
0.
79%AFUE
60,00013.0
SEER/ 13.0 EER
New
No Economizer
EXISTING A/C UNIT (5
TON).
Packaged DX
1
DHW BOILER SUMMARY
0.
Energy Standby TANK INSUL.
Rated Vol. Condition Factor Loss or Ext.
System Name System Type Distribution Type Ory Input I (Gals.) Status or RE Pilot R -Val.
RHEEM HE80 130 Large Gas No Pipe Insulation 1 130,000 80 New 0.95 3.80% 12.0
Hot Water P mp
Hot Water Piping Len h(ft)
Control
#
HP
Type
In Plenum
Outside
Buried
Add 1/2"
Insulation
CENTRAL SYSTEM RATINGS
HEATING
COOLING
System Name
System Type
Qtv1
Outout
Aux.
kW
Eff.
Outout
Eff Iclency
Condition
Status
Economizer Type
CARRIER 48SD-060090
Packaged DX
2
70,740
0.
79%AFUE
60,00013.0
SEER/ 13.0 EER
New
No Economizer
EXISTING A/C UNIT (5
TON).
Packaged DX
1
70,740
0.
79%AFUE
60,00010.0
SEER/ 10.0 EER
Existing
No Economizer
ENVELOPE MANDATORY MEASURES ENV-MM
NAME
TEA HOUSE
DATE
6/5/2008
DESCRIPTION
Designer
Enforcement
❑X
§118(a)
Installed Insulating Material shall have been certified by the manufacturer to comply
with the California Quality Standards for insulating material, Title 20, Chapter 4, Article
3.
RX
§118(c)
All Insulating Materials shall be Installed in compliance with the flame spread rating
and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2.
X❑
§ 117(a)
All Exterior Joints and openings In the building that are observable sources of air
leakage shall be caulked, gasketed, weatherstripped or otherwise sealed.
FX]
§.116(b)
Site Constructed Doors, Windows and Skylights shall be caulked between the unit
and the building, and shall be weatherstripped (except for unframed glass doors and
fire doors).
X❑
§ 116(a)1
Manufactured Doors and Windows installed shall have air infiltration rates not
exceeding those shown In Table Number 1-E. of the Standards. Manufactured
fenestration products must be labeled for U -value according to NFRC procedures.
a
§118(e)
Demising Walls In Nonresidential Buildings:
The opaque portions of framed demising walls in nonresidential buildings shall have
insulation with an installed R -value of no less than R-13 between framing members.
EnergyPro
By EnergySoft User Number: User Job Number: R072266R Page:12 of 24
FMECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM
NAME
TEA HOUSE
DATE
6/5/2008
DESCRIPTION
Desi ner
Enforcement
Equipment and Systems Efficiencies
❑X §111 Any appliance for which there is a California standard established in the Appliance
Efficiency Regulations will comply with the applicable standard.
§ 115(a) Fan type central furnaces shall not have a pilot light.
RI § 123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees
Fahrenheit, or within HVAC equipment, shall be insulated in accordance with
Standards Section 123.
X❑ § 124 Air handling duct systems shall be Installed and insulated in compliance with
Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards.
Controls
§ 122(e) Each space conditioning system shall be installed with one of the following:
❑X § 122(e)1A Each space conditioning system serving building types such as offices and
manufacturing facilities (and all others not explicitly exempt from the requirements
of Section 112 (d)) shall be installed with an automatic time switch with an
accessible manual override that allows operation of the system during off -hours for
up to 4 hours. The time switch shall be capable of programming different
schedules for weekdays and weekends and have program backup capabilities that
prevent the loss of the device's program and time setting for at least 10 hours if
power is Interrupted; or
§ 122(e)1 B An occupancy sensor to control the operating period of the system; or
§ 122(e)1 C A 4 -hour timer that can be manually operated to control the operating period of the
system.
X❑ § 122(e)2 Each space conditioning system shall be Installed with controls that temporarily
restart and temporarily operate the system as required to maintain a setback
heating and/or a setup cooling thermostat setpoint.
§ 122(g) Each space conditioning system serving multiple zones with a combined
conditioned floor area more than 25,000 square feet shall be provided with Isolation
zones. Each zone: shall not exceed 25,000 square feet; shall be provided with
isolation devices, such as valves or dampers, that allow the supply of heating or
cooling to be setback or shut off Independently of other isolation areas; and shall
be controlled by a time control device as described above.
® § 122(a&b) Each space conditioning system shall be controlled by an individual thermostat
that responds to temperature within the zone. Where used to control heating, the
control shall be adjustable down to 55 degrees F or lower. For cooling, the control
shall be adjustable up to 85 degrees F or higher. Where used for both heating and
cooling, the control shall be capable of providing a deadband of at least 5 degrees
F within which the supply of heating and cooling is shut off or reduced to a
minimum.
R§ 122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable
setpoint stops accessible only to authorized personnel.
§ 112(b) Heat pumps shall be installed with controls to prevent electric resistance
supplementary heater operation when the heating load can be met by the heat
pump alone.
EnergyPro By EnergySoft User Number: User Job Number: R072266R Page: 13 of 24
MECHANICAL MANDATORY MEASURES Part 2 of 2 MECH-MM
NAME
TEA HOUSE
DATE
6/5/2008
Description
Designer
Enforcement
Ventilation
"
0
§ 121(e)
Controls shall be provided to allow outside air dampers or devices to be operated at
the ventilation rates as specified on these plans.
FX] § 122(f)
Gravity or automatic dampers interlocked and closed on fan shutdown shall be
provided on the outside air Intakes and discharges of all space conditioning and
exhaust systems.
X❑ § 122(f)
All gravity ventilating systems shall be provided with automatic or readily accessible
manually operated dampers In all openings to the outside, except for combustion air
openings.
X❑ § 121(f)1
Air Balancing: The system shall be balanced in accordance with the National
Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or
Associated Air Balance Council (AABC) National Standards (1989); or
X ` § 121(f)2
Outside Air Certification: The system shall provide the minimum outside air as
shown on the mechanical drawings, and shall be measured and certified by the
Installing licensed C-20 mechanical contractor and certified by (1) the design
mechanical engineer, (2) the Installing licenced C-20 mechanical contractor, or (3) the
person with overall responsibility for the design of the ventilation system; or
§ 121(f)3
Outside Air Measurement: The system shall be equipped with a calibrated local or
remote device capable of measuring the quantity of outside air on a continuous
basis and displaying that quantity on a readily accessible display divice; or
X❑
§ 121(64
Another method approved by the Commission.
Service
Water Heating Systems
X❑
§ 113(b)2
if'a circulating hot water system is installed, it shall have a control capable of
automatically turning off the circulating pump(s) when hot water is not required.
X❑
§ 113(c)
Lavatories In restrooms of public facilities shall be equipped with controls to limit the
outlet temperature to 110 degrees F.
EnergyPro
By EnergySoft User Number: User Job Number: R072266R Page: 14 of 24
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
TEA HOUSE 6/5/2008
SYSTEM NAME FLOOR AREA
AC -1 & 3 AREA 2.043
Number of Systems
2
Heating System
Output per System
70,740
Total Output (Btuh)
141,480
Output (Btuh/sgft)
69.3
Cooling System
Output per System
60,000
Total Output (Btuh)
120,000
Total Output (Tons)
10.0
Total Output (Btuh/sgft)
58.7
Total Output (sgft/Ton)
204.3
Air System
CFM per System
2,000
Airflow (cfm)
4,000
Airflow (cfm/sqft)
1.96
Airflow (cfmlron)
400.0
Outside Air (%)
25.5
Outside Air (cfm/sqft)
0.50
Note: values above given at ARI conditions
W.
:ATING SYSTEM PSYCHROME
26.0 OF 58.5 OF
Outside Air
1022 cfm
Supply Fan
4000 cfm
69.6 of
)OLING SYSTEM PSYCHROME
111.0 / 77.6 of
Outside Air
1022 cfm
75.1/68.2 0 F
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
ISensiblel Latent
I CFM
FSensible
137,205 16 717
85,374
CARRIER 48SD-060090 83,471 34,502 141,480
Total Adjusted System Output 83,471 34,502 141,480
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Aug 4 pm Jan 12 am
58.5 OF 91.7 OF
Heating Coil
�% Return Air Ducts 4
at Time
84.2/70.7 OF 84.2/70.80F 0 64.6/63.50F
�v
Supply Fan
4000 cfm
Cooling Coil
h Return Air Ducts `{
Supply Air Ducts
91.3 of
ROOMS
70.0 of
Supply Air Ducts
65.7/63.9OF
73.5% R.H. ROOMS
74.0 / 67.9 of
EnergyPro 4.3 by EnergySoft User Number: 1919 Job Number: R072266R Page: 15 of 24
HVAC SYSTEM HEATING AND COOLING LOADS SUMMARY
PROJECT NAME DATE
TEA HOUSE 6/5/2008
SYSTEM NAME FLOOR AREA
AC -2 AREA 600
SYSTEM LOAD
Total Room Loads
Return Vented Lighting
Return Air Ducts
Return Fan
Ventilation
Supply Fan
Supply Air Ducts
TOTAL SYSTEM LOAD
COIL COOLING PEAK
COIL HTG. PEAK
CFM
I Sensible
'Latent
CFM
I Sensible
1,262
16,269
5,500
45
1,285
61.5/60.5 OF
0
O
813
64
0
0
300
12,010
1,826
300
14,038
0
0
813
64
29,9091 7,326 15 451
HVAC EQUIPMENT SELECTION
EXISTING A/C UNIT (5 TON). 39,425 16,360 70,740
Total Adjusted System Output �9 425 16,360 7o,7ao
(Adjusted for Peak Design Conditions)
TIME OF SYSTEM PEAK Jul 3 pm Jan 12 am
EATING SYSTEM PSYCHROMETRICS Airstream Temperatures at Time of Heating Peak
26.0 OF 63.4 OF 63.4 OF 96.60F
Outside Air Q Supply Air Ducts
300 cfm 96.6 of
Supply Fan Heating Coil
2000 cfm ROOMS
70.0 of 70.0 of
h Return Air Ducts `i
DOLING SYSTEM PSYCHROMETRICS Airstream Temperatures
at Time of Cooling
Peak
112.0/77.9 OF
80.0/67.7 OF 80.0/67.8 OF
61.5/60.5 OF
O
Supply Air Ducts
Outside Air
300 cfm
Supply Fan Cooling Coil
61.9 / 60.7 of
2000 cfm
ROOMS
64.4% R.H.
74.4/65.7°F
74.0/65.6OF
Return Air Ducts
I
EnergyPro 4.3 by EnergySoft
User Number: 1919
Job Number: R072266R
Page:16 of 24
ROOM LOAD SUMMARY
PROJECT NAME
TEA HOUSE
DATE
6/5/2008
SYSTEM NAME
AC -1 & 3 AREA
FLOOR AREA
2,043
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
E FLOOR PLAN
FLOOR PLAN
1
10,176
90,088
18,728
10,070
89,145
18,728
1,524
34,529
PAGE TOTAL 1 10,070 89,145 19,728 1,524 34,526
TOTAL 1 10,070 89,145 18,728 1,524 34,529
EnergyPro By EnergySoft User Number: User Job Number: R072266R Page: 17 of 24
ROOM LOAD SUMMARY 771
PROJECT NAME
TEA HOUSE
DATE
6/5/2008
SYSTEM NAME
AC -2 AREA
FLOOR AREA
600
ROOM LOAD SUMMARY
ROOM COOLING PEAK
COIL COOLING PEAK
COIL HTG. PEAK
ZONE NAME
ROOM NAME
Mult.
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
LATENT
CFM
SENSIBLE
E FLOOR PLAN
FLOOR PLAN
1
1,265
16,309
5,500
1,262
16,269
5,500
45
1,285
PAGE TOTAL
TOTAL
1 1,262
16,266
5,500
45
1,285
1 1,262
16,269
5,500
45
1,285
EnergyPro By EnergySoft User Number: User . Job Number: R072266R Page: 18 of 24
ROOM HEATING PEAK LOADS
Project Title Date
TEA HOUSE 6/5/2008
Room Information Design Conditions
Room Name FLOOR PLAN Time of Peak Jan 12 am
Floor Area 2,043 Outdoor Dry Bulb Temperature 26°F
Indoor Dry Bulb Temperature 70°F
Conduction Area U -Value AT of Btu/hr
R-21 Wall
225.2
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
0.0690
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
684
215.8
1.2800
44
12,154
2,043.0
0.0250
44
2,247
441.0
0.0690
44
1,339
500.0
0.0690
44
1,518
442.3
0.0690
44
1,343
157.7
1.2800
44
8,882
perimeter = 198.1
0.7300
44
6,363
nems snown wim an astenSK l•1 aenote conouction through an interior surtace to another room. Page Total: 34 529
Infiltration: r 1.001 X 1.064 X 2 043 X 10.00 X 0.000 / 6] X �
schedule Air Sensible Area Ceiling Height ACH pT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 34,529
EnergyPro 4.3 by EnergySoft User Number: 1919 Job Number: R072266R Page: 19 of 24
I
ROOM HEATING PEAK LOADS 71
Project Title Date
TEA HOUSE 6/5/2008
Room Information Desi n Conditions
Room Name FLOOR PLAN Time of Peak Jan 12 am
Floor Area 600 Outdoor Dry Bulb Temperature 26OF
Indoor Dry Bulb Temperature 70 OF
Conduction Area U -Value AT OF Btu/hr
Roof
600.0
X
X
X
X
X
X
X
x
X
x
x
X
X
x
x
X
X
x
X
x
x
X
X
x
x
X
x
X
X
x
x
X
X
x
X
x
X
X
X
0.0250
X
X
X
X
X
X
X
x
X
x
x
X
X
x
x
X
X
x
X
x
x
X
X
x
x
X
x
X
X
x
x
X
X
x
X
x
X
X
X
44
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
660
100.0
0.0690
44
304
perimeter= 10.0
0.7300
44
321
nems snown wim an astensK t-) aenote conauction tnrougn an interior sunace to another room. Page Total: 1 285
Infiltration: 1 1'.00 x i.osa x soo x 10go x o.000 /6] x 0 = 0
chedule Air Sensible Area Ceiling Height ACH pT
Fraction
TOTAL HOURLY HEAT LOSS FOR ROOM 1,285
EnergyPro 4.3 by EnergySoft User Number: 1919 Job Number: R072266R Page: 20 of 24
ROOM COOLING PEAK LOADS
Project Title
TEA HOUSE
53.6
Date
6/5/2008
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
FLOOR PLAN
Time of Peak Sep 4 pm
Floor Area
2,043
Outdoor Dry Bulb Temperature 106 OF
Indoor Dry Bulb Temperature
74`F
Outdoor Wet Bulb Temperature 73 OF
Conduction
Wall
Metal Clear
Area
225.2 X
215.8 X
2,043.0 X
441.0 X
500.0 X
442.3 X
157.7 X
X
X
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
INDOWS
U -Value
1 0.06901
DETD 1
X
X
X
X
X
X
X
X
X
53.6
=
=
=
=
=
=
=
=
=
20.7
43.4
32.1
30.1
40.1
20.7
(W)
215.8
Page Total
Orientation
Area
X
X
X
X
X
x
x
X
X
X
SGF
X
x
X
X
X
X
X
X
X
X
SC
Weighting
X
X
x
X
x
X
X
X
X
X
Factor
=
=
=
=
=
=
=
=
=
(W)
215.8
235
0.856
0.496
(E)
0.0
19
0.856
0.000
(N)
0.0
19
0.856
0.000
(S)
157.7
55
0.856
1.922
Page Total
Btu/hr
833
5,726
2,215
976
1,040
1,225
4,184
is tss
Btu/hr
21,550
0
0
14,273
35 823
Sched. Weighting Btu/hr
Internal Gain Frac. Area Heat Gain Factor
i hts 1.0c X 2,043 X 0.773 Watts/sgft X 3.41 Btuh/Watt X 1.000 = 5,392
ccu ants 1.0c X 2,043 X 275 Btuh/occ. / 3 sgft/occ. X 1.00 = 18,728
Receptacle 1.0c X 2,043 X 0.500 Watts/sgft x 3.41 Btuh/Watt X 1.00 = 3,486
rocess 1.0c x 2,043 X 1.500 Watts/sgft X 3.41 Btuh/Watt X 1.00 = 10,459
Infiltration: 1.00 X 1.064 X 2 043 X 10.00 X 0.00 /601 X 38
chedule Air Sensible Area Ceiling Height ACH AT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 90,088
Sched. Btu/hr
Latent Gain Frac. Area Heat Gain
Occupants 1.00 x 2 043 x 275 Btuh/occ. / 30 sgft/occ. = 18 728
Receptacle 1.00 x x Watts/sgft x Btuh/Watt =
Process 1.00 x 2,043 x 0.000 Watts/sgft x 3.413 Btuh/Watt = o
Infiltration: x anx I z'0 J x x / 6] x _
chedule Air Latent Area Ceiling Height ACH pyy
ROOM COOLING PEAK LOADS
Project Title
TEA HOUSE
Area
Date
6/5/2008
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
FLOOR PLAN
Time of Peak Jul 2 pm
Floor Area
600
Outdoor Dry Bulb Temperature 111 `F
Indoor Dry Bulb Temperature
74`F
Outdoor Wet Bulb Temperature 78 cl�
Conduction
B Roof Attic
1 Wall
Area
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
S
S
U -Value
0.0250
0.0690
Orientation
Area
X
X
X
X
X
X
X
X
X
X
SGF
X
X
X
X
X
X
X
X
X
X
SC
(W)
0.0
190
0.856
(E)
0.0
46
0.856
(N)
0.0
46
0.856
(S)
0.0
68
0.856
DETD 1
71.1 =
36.9 =
Page Total
Weighting
Factor
x 0.000 =
X 0.000 =
X 0.000 =
X 0.000 =
X =
X =
X =
X =
X =
X =
Page Total
Btu/hr
1,067
255
1 322
Btu/hr
0
0
0
0
Sched. Weighting Btu/hr
Internal Gain Frac. Area Heat Gain Factor
i hts 1.0c X 600 X 2.633 Watts/sgft X 3.41 Btuh/Watt X 1.000 = 5,392
ccu ants 1.0c X 600 X 275 Btuh/occ. / 3 sqft/occ. X 1.00 = 5,500
ece tacle 1.0 x 600 X 0.50o Watts/sgft x 3.41 Btuh/Watt x 1.00 = 1,024
rocess 1.0 x 600 X 1.500 Watts/sgft x 3.41 Btuh/Watt x 1.00 = 3,072
Infiltration: x i.o64 x soo x Height
x o.00 /6] x
chedule Air Sensible Area Ceiling Height ACH DT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 16,306
Sched.
Latent Gain Frac. Area Heat Gain Btu/hr
ccu ants 1.00 X 600 X 2751 Btuh/occ. / 30 sgft/occ. = 5 500
Receptacle 1.00 x x 0.000 Watts/sqft x Btuh/Watt =
Process 1.00 X 600 x 0.000 Watts/sgft x 3.413 Btuh/Watt = 0
Infiltration: x x 771 x x x � / 6] x � _
chedule Air Latent Area Ceiling Height ACH pyy
ROOM COOLING COIL LOADS
Project Title
TEA HOUSE
Area
Date
6/5/2008
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
FLOOR PLAN
Time of Peak Aug 4 pm
Floor Area
2,043
Outdoor Dry Bulb Temperature 1119F
Indoor Dry Bulb Temperature
74OFOutdoor
Wet Bulb Temperature 78 9F
Conduction
1 Wall
Metal Clear
Area
225.2 X
215.8 X
2,043.0 X
441.0 X
500.0 X
442.3 X
157.7 X
X
X
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
U -Value
0.0690
1.2800
Orientation
Area
X
X
X
X
X
X
X
X
X
X
SGF
X
X
X
X
X
X
X
X
X
X
SC
(W)
215.8
260
0.856
(E)
0.0
28
0.856
(N)
0.0
28
0.856
(S)
157.7
34
0.856
DETD 1
60.7 =
23.9 =
56.1 =
39.0 =
36.8 =
41.5
23.9 =
Page Total
Weighting
Factor
X 0.474 =
X 0.000 =
X 0.000 =
X 2.043 =
X =
X =
X =
X =
X =
X =
Page Total
Btu/hr
944
6,592
2,866
1,185
1.270
1,268
4,817
18 941
Btu/hr
22,763
0
0
9,376
32 139
Sched. Weighting
Internal Gain Frac. Area Heat Gain Factor Btu/hr
fights 1.0c x 2,043 X 0.773 Watts/sgft x 3.411, Btuh/Watt x 1.000 = 5,392
ccu ants 1.0c x 2,043 X 275 Btuh/occ. / 3 Sgft/OCC. x 1.00 = 18,728
Receptacle 11.0c x 2,043 X 0.500 Watts/sgft x 3.41 Btuh/Watt x 1.00 = 3,486
rocess 1.0c X 2,043 X 1.500 Watts/sgft X 3.41 Btuh/Watt X 1.00 = 10,459
Infiltration: 1.00 X 1.064 X 2 043 X 10.00 X 0.00 / 60] X 38 =
-Schedule Air Sensible Area Ceiling Height ACH AT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 89,145
Sched. Btu/hr
Latent Gain Frac. Area Heat Gain
Occupants 1.00 x 2,0431 X 275 Btuh/occ. / 30 sgft/occ. = 18 728
Receptacle 1.00 x x Watts/sgft x Btuh/Watt
Process 1.00 x 2,043 x 0.000 Watts/sgft x 3.413 Btuh/Watt = o
Infiltration: x x x x /6] x Z_
chedule Air Latent Area Ceiling Height ACH pyy
ROOM COOLING COIL LOADS
Project Title
TEA HOUSE
Area
Date
6/5/2008
ROOM INFORMATION
DESIGN CONDITIONS
Room Name
FLOOR PLAN
Time of Peak Jul 3 pm
Floor Area
600
Outdoor Dry Bulb Temperature 112 OF
Indoor Dry Bulb Temperature
74`F
Outdoor Wet Bulb Temperature 78 OF
Conduction
Roof Attic
Area
1. Design Equivalent Temperature Difference (DETD)
Items shown with an asterisk (') denote conduction through an interior surface to another room.
Solar Gain
TT
U -Value
0.0250
0.0690
Orientation
Area
x
X
X
X
X
X
X
X
X
X
SGF
X
X
X
X
x
X
X
X
X
X
SC
(W)
0.0
242
0.856
(E)
0.0
41
0.856
(N)
0.0
41
0.856
(S)
0.0
45
0.856
DETD 1
67.8 =
38.4 =
Page Total
Weighting
Factor
X 0.000 =
X 0.000 =
X 0.000 =
X 0.000 =
X =
X =
x =
X =
X =
X =
Page Total
Btu/hr
1,016
265
1281
Btu/hr
0
0
0
0
Sched. Weighting Btu/hr
Internal Gain Frac. Area Heat Gain Factor
fights 1.0c X 600 X 2.633 Watts/sgft X 3.41 Btuh/Watt X 1.000 = 5,392
ccu ants 1.0c X 600 X 275 Btuh/occ. / 3 sgft/occ. X 1.00 = 5,500
eceptacle 1.0c X 600 x 0.500 Watts/sqft x 3.41 Btuh/Watt X 1.00 = 1,024
rocess r1.0c X 600 X 1.500 Watts/sqft X 3.41 Btuh/Watt X 1.00 = 3,072
Infiltration: I 1.00 x 1.064 X 600 X 10.00 x 0.00 /6] X 38 =
chedule Air Sensible Area Ceiling Height ACH LT
Fraction
TOTAL HOURLY SENSIBLE HEAT GAIN FOR ROOM 16,269
Sched. Btu/hr
Latent Gain Frac. Area Heat Gain
Occupants 1.00 x soo x 2751 Btuh/occ. / 3o sgft/occ. = 5 500
Receptacle 1.00 x x Watts/sqft x Btuh/Watt
Process 1.00 X 600 x 0.000 Watts/sgft x 3.413 Btuh/Watt = 0
Infiltration: �� x Air 4,771 x x Ceiling xACH / 60] x I _