BRES2017-0218 Evaluation Report11K[A._.,tIVL:U
qUES
"
199 SEP 2 5 2[ il7
Cm` OF UINTA
Originally Issued: 10/08/2010 Revised: 09/12/2017 Valid ThWMM�
� 1ELoPMENr
VELUX AMERICA, LLC.
DECK MOUNT GLASS -GLAZED UNIT
SKYLIGHTS
CURB MOUNT GLASS -GLAZED UNIT
SKYLIGHTS
TUBULAR DAYLIGHTING DEVICES
CSI Section:
08 62 00 Unit Skylights
1.0 RECOGNITION
Verco America, LLC's Deck Mount Glass -Glazed Unit
Skylights, Curb Mount Glass -Glazed Unit Skylights and
Tubular Daylighting Devices recognized in this report have
been evaluated for use .as glazed skylights. The structural
performance, air and water tightness, operating forces,
durability and thermal and optical performance properties of
the Deck Mount Glass -Glazed Unit Skylights, Curb Mount
Glass=Glazed Unit Skylights and Tubular Daylighting
Devices were evaluated for compliance with the following
codes:
• 2015 and 2012 International Building Code! -'(IBC)
2015 and 2012 International Residential Code'
(IRC)
• 2015 and 2012 International Energy Conservation
Code' (IECC)
• 2016 California Building Code (CBC) — See
attached Supplement
2.0 LIMITATIONS
Use of the VELUX Deck Mount Glass -Glazed Unit
Skylights, Curb Mount Glass -Glazed Unit Skylights and
TubuIar Daylighting Devices recognized in this report is
subject to the following. limitations:
2.1 VELUX Deck Mount Glass -Glazed Unit Skylights, Curb
Mount Glass -Glazed Unit Skylights and Tubular Daylighting
Devices shall be installed in accordance with the applicable
code, the manufacturer's instructions, and this report. In the
event of a conflict, the more restrictive governs.
2.2 Deck and curb mount glass -glazed unit skylights shall not
be used in Type I or 11 construction, over acid fume -
containing spaces, in wind-borne debris regions or where
unusual loading is expected.
2.3 Deck and curb mount glass -glazed unit skylights that are
set at an angle of less than 45 degrees from the horizontal
shall be mounted at least 4 inches (102 mm) above the plane
of the roof except for R-3 occupancies with a minimum roof
slope of 3-units vertical in 12 units horizontal.
2.4 Light transmitting plastic of tubular daylightingdevices
shall be mounted at Ieast 4 inches (102 mm) above the plane
o.fthe roof except for R-3 occupancies with a minimum roof
slope of 3-units vertical in 12 units or for buildings with a
non -classified roof covering.
2.5 Aggregate area, separation and location of tubular
daylighting devices shall be in accordance with IBC Sections
2606.7, 2610.5, 2610.6, 2610.7, 2610.8 and 803.1.1 for those
occupancies within the scope of the IBC.
2.6 Installation of skylights and tubular daylighting devices
shall be in accordance with IRC Section R308.6 for those
occupancies within the scope of the IRC.
2.7 Edges of light transmitting plastic of tubular daylighting
devices shall be protected by metal or noncombustible edge
material except where non -classified roof coverings are
permitted.
2.8 Electric motor -driven sash operators, in VSE, VSS, VCE
and VCS skylights shall comply with the applicable electrical
code requirements and are subject to approval of the code
official.
3.0 DECK MOUNT GLASS -GLAZED UNIT
SKYLIGHTS
3.1 UESES: VELUXO FS, VS, VSE and VSS No Leak
SkylightsTM are unit skylights complying with IBC Section
2405.5 that provide natural light and views into the interior
of building spaces. The skylights are intended for use on
building roofs sloped from 3-units vertical in 12 units from
the horizontal (25-percent slope) plane to 85 degrees from the
horizontal plane. Each unit contains an integral supporting
frame with continuous mounting flange intended for direct
attachment to roofing substrate. VS, VSE and VSS skylights
provide natural ventilation via an operable top -hinged sash.
FS units arc fixed. The glass is continuously supported on all
four sides.
3.2 DESCRIPTION
3.2.1 Insulati s 't 'L g lass units (IGU)
e>7 ttt , �s 'ghts complying
1 p M^� 5A 101/I.S.2/A440-
W � . are co tructed from a
%i5ww 1 c coated tempered glass
lite out Jsh e ) mm) hick laminated
lass li less -steel spaces system for an
verall ifcss f 5/x inch .9 mm). The urinated glass
to inboar� ri crich (2.4 mm)
t ick iat are each permanently
b t d o e 30 o. 0-090 inch (0.8 or 2.3 mm) thick
p nvi butyral (PVB) clear interlayer. When increased
thermal performance is desired, an additional Low-E coating
The product desc:dbelf it tllls Uniform Evalrrafien Survive (LIES) Report has been evaluated as an affemative material, design or method of construction in order to satisfy and comply vMh the
Intent of the provisions of the code. as noted In this report and for al least aquivalence to thatprescnfled in the code in quality, strength, efrealivcness, fire resistance, durability and safely, as
epMeble, in accordance with OC Section 104,11. This documanl shall only be taprOduced n Rs erbrety
Copyright C+ 2017 by fntamational Assodalion of Plumbing and MerhaMcal Officials. All rights reserved. Printed in the United States Ph: 1-877-41ESRPT • Fax: 909.472-4171
web: www.unHorm-as.org • 4755 EastPhdadelphra Street, Ontario, calilarnia 91761-2816— USA
Page 1 of 19
199
Originally Issued: 10/08/2010 Revised: 09/12/2017 Valid Through: 09/30/2018
is applied on the interior glass surface of the IGU. The space
between glass lites is filled with 95 percent argon gas.
3.2.2 Assembly Details: Condensation control gasketing for
all skylight models directs accumulated water droplets from
the inner glass surface to the exterior without compromising
required air tightness.
VELUX FS, VS, VSE and VSS skylights consist of several
integrated components: one panel of flat IGU top -mounted
onto an aluminum -clad wood sash (VS, VSE and VSS), or
directly onto an aluminum -clad wood frame (FS). Top -
hinged sash on any VS, VSE or VSS skylight is fastened to
and supported on a similar aluminum -clad wood frame. Sash
and frames are manufactured from white -finished pine wood
having a nominal specific gravity of 0.47 and are covered on
the weather -exposed sides with roll -formed aluminum
cladding that is coated with Kynar and lacquer.
Frames have mortised corners secured with adhesive and
aligned and stabilized by a 1'/a inch (44.5 mm) long corner
nail. A continuous galvanized steel mounting flange with
mitered and welded comers is attached to the lower partof
the frame and rests upon a foam isolation pad to interface with
the mounting surface. Galvanized nails secure the flange to
the frame every 9 inches (229 mm) or less. Only the VS, VSE
and VSS frames have a support ledge all around the interior
face, to which a gasket is stapled for a tight seal with the sash
frame. The frames also support the fixed half of the extruded
aluminum sash hinge on the top of the frame head, fastened
with 1 inch (25.4 mm) long No. 8 screws spaced at 10 inches
(254 mm) on center.
VELUX VS, VSE and VSS skylight sashes also use a mortise
joint corner construction with one 5/16 inch (7.9 mm) long
staple at each corner. The rotating half of the extruded
aluminum hinge is fastened with 1 inch (25.4 mm) long No.
8 screws spaced at 10 inches (254 mm) on center. The IGU is
secured with hot -applied primary sealant bonded to roll
formed aluminum glazing retaining profiles that are secured
to the sash or frame using No. 8 stainless steel screws of
various lengths (1 and 2-1/2 inches (25.4 and 63.5 mm) for
VS, VSE and VSS and 1-1/4 inch (31.8 mm) for FS spaced
every 9 inches (229 mm). All VS, VSE and VSS skylights are
equipped with insect screens.
VSE and VSS skylights employ an electric motor -driven sash
operator with radio frequency remote control and have
exterior sensors to automatically trigger the operator to close
an open sash when rain droplets are present. VSS skylights
use solar powered batteries to operate the sash. VS skylights
utilize a manually -driven rotary operator.
Sizes, general dimensions and fastener requirements for deck
mount units are described in Tahics I (FS) and 2
(VSNSENSS) and Figures 1 (FS), 2 (FS), 3 (VSNSENSS)
and 4 (VSNSENSS) of this report. Certified energy, light
and comfort factors (U, SHGC, VT and CR) shall conform to
2015 IRC Section N1101.10.3, 2012 IRC Section
N1101.12.3 and 2015 and 2012 IECC Sections C303.1.3 and
R303.1.3 (NFRC 100 and 200) and NFRC 500 for all sizes
and are shown in Table 3 of this report.
3.3 DESIGN AND INSTALLATION
Based on the positive and negative performance grade
ratings listed in Tables I_ and of this report, the product
size(s) shall be selected that have performance grades in
excess of the design pressures that are applicable to the
unit's final location. Uplift wind ratings recognized in this
report are based on attachment to a lumber substrate
exhibiting a minimum specific gravity of 0.43 as defined
in Table 11.3.2A of the ANSI/AF&PA NDS with full nail
engagement. Installation on wood substrates with a
specific gravity less than 0.43 may result in a lower wind
uplift rating.
4.0 CURB MOUNT GLASS -GLAZED UNIT
SKYLIGHTS
4.1 USES: VELUX' FCM, VCE, VCM, and VCS No Leak
SkylightsTm are unit skylights complying with IBC Section
2405.5 that provide natural light and views into the interior
of building spaces. The skylights are intended for use on
building roofs sloped from 0° (0:12 slope) from the
horizontal plane to 60' from the horizontal plane. Each unit
is designed to attach to a site -built curb that is constructed
from nominal 2-inch (50.8 mm) by 4-inch (102 mm) wood
members of sufficient strength to transfer the skylight loads
to the framing members. Skylights may be attached to other
curb materials of equal or greater size and strength. VCE,
VCM and VCS skylights provide natural ventilation via an
operable top -hinged sash supported by an integral frame
assembly. FCM units are fixed. Glass is continuously
supported on all four sides using a roll -formed aluminum
frame (assembled with ASA corner keys) to resist uplift wind
loads. Curb mount products are particularly well -suited for
replacement of existing curb -mounted skylights.
4.2 DESCRIPTION
4.2.1 Insulating Glass Units: Insulating glass units (IGU)
used in curb mount glass -glazed unit skylights complying
with Section 10.2 of AAMAIWDMA/CSA 101/I.S.2/A440-
11 comply with ASTM E2190 and are constructed from
either a 1/8 inch (3.18 mm) or 5/32 inch (3.97 mm) thick clear
Low-E3-coated tempered glass lite outboard, a sheet of 7/32
inch (5.56 mm) thick laminated glass lite inboard and a
stainless -steel spacer system for an overall thickness of 5/8
inch (15.9 mm). The Laminated glass lite inboard is
comprised of two sheets of 3/32 inch (2.4 mm) thick heat
strengthened glass that are each permanently bonded to either
a 0.030 or 0.090 inch (0.8 or 2.3 mm) thick polyvinyl butyral
(PVB) clear interlaycr. When increased thermal performance
is desired, an additional Low-E .coating is applied on the
interior glass surface of the IGU. The space between glass
lites is filled with 95 percent argon gas.
Page 2 of 19
Originally Issued: 10/08/2010
Revised: 09/12/2017
4.2.2 Assembly Details: Condensation and air leakage
control is accomplished through the use of baffled weep holes
in the pane support gasketing.
VELUX FCM, VCE, VCM and VCS skylights consist of
several integrated components. One panel of aluminum -
framed flat IGU is bottom -mounted onto a rigid polyvinyl
chloride (PVC) sash for the VCE, VCM and VCS skylights
and is directly mounted in the field onto the site -built curb for
the FCM skylight. Hot -applied primary sealant is bonded to
the aluminum frame prior to IGU placement, for all three
models. Top -hinged sashes on the VCE, VCM and VCS
Skylights are fastened to and supported on a similar rigid
PVC frame with extruded aluminum counter flashing. This
frame is supported in the field by the site -built curb. VELUX
FCM skylight utilizes a dual-durometer thermoplastic
elastomer (TPE) inner frame gasket that is T-nailed to the
glazing frame to lock the IGU in place for sealant curing and
handling stability. VCE, VCM and VCS counter flashing is
a mitered and welded frame that is used to fasten the entire
unit to the site -built curb. All VELUX VCE, VCM and VCS
skylights are equipped with insect screens.
VCE and VCS skylights employ an electric motor -driven
sash operator with radio frequency remote control and have
exterior sensors to automatically trigger the operator to
close an open sash when rain droplets are present. VCS
skylights use solar powered batteries to operate the sash.
VCM skylights utilize a manually -driven rotary operator.
Sizes, general dimensions and fastener requirements for
curb mount units are described in Tables 4 (FCM) and 5
(VCENCMNCS) and Figures 5 (FCM), 6
(VCENCMNCS) and 7 (VCENCMNCS) of this report.
Certified energy, light and comfort factors (U, SHGC, VT
and CR) for all sizes shall conform to 2015 IRC Section
N1101.10.3, 2012 IRC Section N1101.12.3 and 2015 and
2012 IECC Sections C303.1.3 and R303.1.3 (NFRC 100
and 200) and NFRC 500. The ratings are shown in Table 6
of this report.
4.3 DESIGN AND INSTALLATION
Based on the positive and negative performance grade
ratings listed in -rgh1e,: 4 and 5 of this report, the product
size(s) shall be selected that have performance grades in
excess of the design pressures that are applicable to the
unit's final location. Uplift wind ratings recognized in this
report are based on attachment of the curb to a lumber
substrate exhibiting a minimum specific gravity of 0.43 as
defined in Table 11.3.2A of the ANSI/AF&PA NDS with
full nail engagement. Installation on lumber substrates with
a specific gravity less than 0.43 may result in a lower wind
uplift rating.
5.0 TUBULAR DAYLIGHTING DEVICES
5.1 USES: VELUX SUN TUNNELT°^ TCR, TGR, TGF,
TMR, and TMF Residential Skylights, and TCC, TGC and
TMC Commercial Skylights are tubular daylighting
Valid Through: 09/30/2018
devices (TDD) complying with 2015 IBC Sections 1709.6
and 2405 and 2012 IBC Section 1710.6 and 2405 that
collect and conduct natural light from above into building
spaces. All series listed are intended for use on building
roofs sloped up to 60 degrees from the horizontal plane.
The TGF, TGR, TMF and TMR series are designed for
slopes of 3 unit's vertical in 12 units from the horizontal
plane (25-percent) and above.
5.2 DESCRIPTION
5.2.1 VELUX SUN TUNNELTM TCC, TCR, TGC, TGF,
TGR, TMC, TMF and TMR Skylights are series of tubular
daylighting devices, each consisting of an exterior steel
roof flashing capped with a clear molded acrylic copolymer
(Plexiglas"' HFI-7) exterior dome unit, and an interior
diffuser assembly consists of extruded aluminum and a
single acrylic diffuser joined by a rigid metallic telescopic
or flexible tunnel tube with a reflective interior surface.
The Dome materials comply as Class CC2 light -
transmitting plastics in accordance with criteria prescribed
in IBC Section 2606.4 and the standard referenced in IBC
Section 2405.5.
5.2.2 ASSEMBLY DETAILS
TGC, TGF and TGR standard series consist of a low profile
flashing that mounts to the roof deck, projects 4 inches
(102 mm) upward and aligns the dome base to be parallel
to the roof deck. TMC, TMF and TMR standard series
consist of a pitched flashing that mounts to the roof deck
and projects 9 inches (229 mm) upward on the downward
roof slope and allows the dome base to be inclined relative
to the adjacent roof. TCC and TCR standard series consist
of a square flashing designed for mounting on a site -built
curb of any material or height. Optional tile roof flashing
kits are available for all the series.
Each SUN TUNNEL series is available in up to three
model sizes — 10, 14 and 22 inches (254, 355 and 559 mm)
defined by the tunnel diameter - depending on the series
selected. Domes for all available in 10 and 14 inches (254
and 355 mm) models and the 22-inch (559 mm) TGF are
the traditional "shallow dish" shape proven on residential
buildings. Domes for all other 22-inch (559 mm) models
use a new light -directing assembly that is significantly
taller and houses the SunCurve Daylight Directing device
more appropriate for larger, nonresidential spaces. An
optional 12 or 36-inch (305 or 914 mm) long steel turret
extender is available for all 14 and 22 inch (355 and 559
mm) flashings if the dome elevation needs to be higher than
standard. An optional galvanized steel fire band is
available to protect the dome edge where Class A, B or C
roof coverings are required.
Flexible tunnels are used on the TGF and TMF series, in
14 and 22-inch (355 and 559 mm) sizes. Rigid tunnels with
elbow fittings are used for all other standard series. Rigid
tunnel joints are easily fastened in the field with Flexi
Page 3 of 19
7ES
199
Originally Issued: 10/08/2010 Revised: 09/12/2017 Valid Through: 09/30/2018
LocTM spring clips and sealed with metalized tape, included
in standard kits. Where building insulation is installed at
the roof level, an optional thermal break section may be
inserted into 14 and 22 inch (355 and 559 mm) rigid
tunnels in line with that insulation for enhanced energy
performance. Assemblies with this option carry numbers
ending in EO and have certified thermal ratings. Where
needed, a power -operated daylight controller wafer is
available as an additional rigid tunnel option.
Diffuser Assemblies: Three bottom designs are available:
• Type THC, for use where a rigid ceiling will support the
diffusers and lower tunnel. This assembly holds up to
four light diffusing acrylic glazing layers, with two being
standard. Two additional layers are recommended when
the attic insulation is at the ceiling, and are available as
part of the `residential" Energy Kit. That kit also
includes a heat gain shield that is attached to the
underside of the shallow dome. [10, 14 and 22 (254, 355
and 559 mm)].
• Type TOC, used where no ceiling exists. This assembly
caps the tunnel end using one diffusing acrylic layer. [14
and 22 inch (355 and 559 mm) only].
• Type TTC, used where there is a non -rigid ceiling and a
square diffuser is required. This assembly includes a
transition section to fit the round tunnel bottom and
support a 24 in square panel of diffusing acrylic_ [14 and
22 inch {355 and 559 nun) only]. Each diffuser type
utilizes one of three available lower glazing finishes —
frosted, prismatic, or Fresnel-patterned. The THC
diffuser option with a frosted finish is the standard for
TCR, TGF, TGR, TMF and TMR series assemblies. The
base kits for these series are shipped complete, with all
parts used in the tested specimens.
There is no complete "Base Kit" available for the TCC, TGC
and TMC series. These products are packaged in
subassembly cartons that shall be ordered together and field
assembled to create assemblies qualified by the tested ones.
The following are the assembly model numbers covered
herein:
Page 4 of 19
VES EVALUATION REPORT Numbe 19
Originally Issued: 10/08/2010 Revised: 09/12/2017 Valid Through: 09/30/2018
Residential Models Shipped as Complete Kits
TGF 014 0000 TGR O10 0000 TMR 010 0000
TCR 014 OOOOUS TGF 014 OOOOEO TGR 010 OOOOEO TMF 014 0000 TMR 010 OOOOEO
TCR 014 OOOOUSEO TGF 022 0000 TGR 014 0000 TMF 014 OOOOEO TMR 014 0000
TGF 022 OOOOEO TGR 014 OOOOEO TMR 014 OOOOEO
�TCC
Commercial Models Shipped as Separate Subassemblies
_
014 --- TGC 014 .. TMC 014— TCC 022
...
TGC 022 ... �!
OOOOTH
... OOOOTH
... OOOOTH
... 3000TH
... 3000TH
... OOOOTHEO
OOOOTHEO
— OOOOTHEO .,.
3000THEO
... 3000THEO
... OOOOTO
... OOOOTO
... OOOOTO
... 3000TO
... 3000TO
OOOOTOEO
OOOOTOEO
OOOOTOEO
3000TOEO
3000TOEO
... OOOOTT
... OOOOTT
... OOOOTT
... 3000TT
... 3000TT
...000OTTEO
...000OTTEO
OOOOTTEO ...3000TTEO
3000TTEO
... 0002TH
... 0002TH
... 0002TH
... 3002TH
... 3002TH
0002THEO
... 0002THEO
0002THEO ...
3002THEO
... 3002THEO
... 0002TO
... 0002TO
... 0002TO
... 3002TO
... 3002TO
... 0002TO EO
... 0002TO EO
... 0002TO EO ...
3002TO EO
... 3002TO EO
... 0002TT
... 0002TT
... 0002TT
... 3002TT
... 3002TT
0002TTE0
.0002TTEO
0002TTE0 ...3002TTEO
3002TTEO
... 0003TH
... 0003TH
... 0003TH
... 3003TH
... 3003TH
0003THEO
... 0003THEO
... 0003THEO
3003THEO
. , . 3003THEO
... 0003TO
... 0003TO
... 0003TO
... 3003TO
... 3003TO
0003TOEO
0003TOEO
0003TOEO
3003TOEO
3003TOEO
... 0003TT
... 0003TT
... 0003TT
3003TT
... 3003TT
0003TTEO
... 0003TTEO
... 0003TTEO
3003TTE0
... 3003TTEO
Sizes, general dimensions and fastener requirements for tubular daylighting devices are described in Tables 7 and 8
and Figures 8 (TGF/TMF),
(TGR/TMR), and
(TCR/TCC/TGC/TMC) of this report. Certified energy and comfort
factors (U and SHGC) applicable to many listed models for all sizes shall conform to Sections N1101.10.3 and
N1101.12.3 of the 2015 and 2012 IRC, respectively, and 2015 and 2012 IECC Sections C303.1.3
and R303.1.3 are
shown in Table 9 of this report
Page 5 of 19
Originally Issued: 10/08/2010 Revised: 09/1212017
5.3 DESIGN AND INSTALLATION
Based on the positive and negative performance grade
ratings listed in Tables 7 and 8 of this report, identify the
product size(s) that have performance grades in excess of
the design pressures that are applicable to the unit's final
location.
Uplift wind ratings recognized in this report are based on
attachment to a wood substrate exhibiting a minimum
specific gravity of 0.43 as defined in Table 11.3.2A of the
ANSI/AF&PA NDS full nail engagement. Installation on
wood substrate with a specific gravity less than 0.43 result
in a lower wind uplift rating.
Suspension wires maybe required in some projects such as
where there is no rigid ceiling to offer support at the
diffuser level. A kit is available for this purpose.
6.0 IDENTIFICATION
6.1 VELUX FS, VS, VSE, VSS FCM, VCE, VCM and VCS
skylights covered by this report shall be identified with
permanent labeling that includes the following
information:
• Manufacturer's name, address, full model number
and traceability code number.
6.2 VELUX FS, VS, VSE, VSS, FCM, VCE, VCM and VCS
skylights covered by this report shall be identified with
temporary pane labeling that includes the following
information:
• Manufacturer's name and address, tested model size
and designation, glass type and thickness, NFRC-
certified ratings and WDMA or other approved
labeling agency.
• Primary and secondary designators as required by
the AAMA/WDMA/CSA 101/I.S.2/A440
specification including but not limited to the positive
and negative performance grade ratings.
• IAPMO ES or UES Marks of Conformity and
evaluation report number (ER-199)
6.3 VELUX SUN TUNNELTM TCC, TCR, TGC, TGF,
TGR, TMC, TMF, and TMR skylights covered by this
report shall be identified with permanent labeling that
includes the following information:
• Risk of Fall and ID label with the manufacturer's
name, address and a traceability code number placed
at the bottom center of the flashing during factory
subassembly.
• The full assembly model number and any applicable
NFRC ID number is printed on an adhesive label
that will need to be applied to a specified interior
surface at installation
.199
Valid Through: 09/30/2018
6.4 VELUX SUN TUNNELTM TCC, TCR, TGC, TGF,
TGR, TMC, TMF, and TMR skylights covered by this
report shall be identified with temporary labeling that
includes the following information:
• Manufacturer's name and address, tested model size
and designation, dome type, NFRC-certified ratings
and WDMA or other approved labeling agencies.
• Primary and secondary designators as required by
the AAMA/WDMA/CSA 101/I.S.2/A440
specification including but not limited to the positive
and negative performance grade ratings.
• LkPMO ES or UES Marks of Conformity and
evaluation report number (ER-199).
IAPMO UJs
ES
or
IAPMO ER-199
8.0 SUBSTANTIATING DATA
Reports of component and assembly testing and evaluation in
accordance with AAMA/WDMA/CSA 101/I.S.2/A440-11,
NFRC 100, 200 and 500.
8.0 CONTACT INFORMATION
VELUX AMERICA, LLC.
P.O. Box 5001
Greenwood, South Carolina 29648-5001
(864)941-4828
www.veluxusa.com
Page 6 of 19
UEs
Originally Issued: 10/08/2010
9.0 STATEMENT OF RECOGNITION
Revised: 09/12/2017
This evaluation report describes the results of research
carried out by IAPMO Uniform Evaluation Service on Verco
America, LLC's Deck Mount Glass -Glazed Unit Skylights,
Curb Mount Glass -Glazed Unit Skylights and Tubular
Daylighting Devices to assess conformance to the codes
shown in Section 1.0 of this report, and serves as
documentation of the product certification.
Brian Gerber, P.E., S.E.
Vice President, Technical Operations
Uniform Evaluation Service
1'1e'�Aoz
Richard Beck, PE, CBO, MCP
Vice President, Uniform Evaluation Service
GP Russ Chan y
CEO, The IAPMO Group
For additional information about this evaluation report please visit
ss a-w.unifnrm-es.or L or email us at i is fi ifa uniform-cs.ar=
199
Valid Through: 09/30/2018
Page 7 of 19
uES
Originally Issued: 10/08/2010 Revised: 09/12/2017
199
Valid Through: 09/30/2018
Table 1 - VELUX FS Skylights - Glass Weight = 5 psf
Skylight Description
NAFS Performance Grades
Other NAFS Designators
Size
Code
Unit size0)
(inches)
inches
Download
PGpos
( )
Uplift
PGNe
( s)
Primary
Maximum Air
Z
Leakage(2)
Max. Pressure with No
Water Penetration(Z)
A06
14-% x 45-3/4
+16,758 Pa
(+350 psf)
-5,040 Pa
(-105 psf)
SKG-PG105
775x1397'
(31 x55')
0.1 L/s/m2
(<0.01 cfm/ft2)
720 Pa (psf)
sfl
C01
21 x 26-7/8
C04
21 x 37-7/8
C06
21 x 45-3/4
C08
21 x 54-7/16
D26
22 '/z x 22-15/16
D06
22 1/ x 45-3/4
M02
30-1/16 x 30
M04
30-1/16 x 37-7/8
M06
30-1 /16 x 45-3/4
M08
30-1/16 x 54-7/16
S01
44-'/a x 26-7/8
+7,670 Pa
(+160 psf)
-3,360 Pa
(-70 psf)
SKG-PG70 1137x1175
45x46
0.1 L/s/M2
(0.01 cfm/ftZ)
720 Pa (15 psf)
S06
44-1/4 x 45-3/4
01 Hough opening dimensions M Based on tested size indicated in Primary Designator
Table 2 - VELUX VS, VSE and VSS Skylights - Glass Weight = 5 psf
Skylight Description
NAFS Performance Grades
Other NAFS Designators
Size
Code
Unit size0)
inches
Downward
PGpos
( )
Uplift
PGNeg
Primary
Maximum Air
Leakage (2)
Max. Pressure with No
Water Penetration (2)
C01
21 x 26-7/8
+19,152 Pa
(+440 psf)
-5,040 Pa
(-105 psf)
SKG-PG105
775x1390"
(30x55*)
0.1 L/s/m2
(<0.01 cfm/ft2)
720 Pa (15 psf)
C04
21 x 37=7/8
C06
21 x 45-3/4
C08
21 x 54-7/16
M04
30-1 /16 x 37-7/8
M06
30-1 /16 x 45-3/4
M08 1
30-1/16 x 54-7/16
S01
44-1/4 x 26-7/8
+17,715 Pa
( +370 psf)
-3,120 Pa
(-65 psf)
SKG-PG65
1197x1238
(47x49)
0.1 L/s/m2
(0.02 cfm/ft2 )
720 Pa (15 psf)
tSO6
44-1 /4 x 45-3/4
� Rough opening dimensions "z Based on tested size indicated in Primary Designator
Table 3: Deck Mount Skylights - Energy, Light and Comfort
Model/Glazing
U-Factor
Btulftz/"F/hr
Solar Heat Gain
Coefficient SHGC
Visible Transmittance (VT)
Condensation
Resistance CR
FS ...04
0.44
0.26
0.60
0.60
50
52
FS ...06
0.42
0.26
FS ...08
0.44 J0.25
0.44
50
FS ...99 94
0.38
0.26
0.60
42
Vs ... 04
0.42
1 0.23
0.53
53
VS ... 06
0.40
0.23
0.52
55
VS ... 08
0.42
0.22
0.39
r 0.52
53
44
VS ... 99 94
0.37
0.23
1. U-factors and Solar Heat Gain Coefficient, Visible Transmittance have been determined in accordance with NFRC 100 and NFRC
200, respectively by an accredited, independent laboratory, and labeled and certified by the manufacturer.
2. Condensation Resistance have been determined in accordance with NFRC 500 by an accredited, independent laboratory, and
labeled and certified by the manufacturer.
Page 8 of 19
UES
Originally Issued: 10/08/2010 Revised: 09/12/2017 Valid Through: 09/30/2018
Figure 1 — VELUX FS Skylight
(Horizontal Section View)
,:1 C.
Figure 2 — VELUX FS Skylight
(Vertical Section View)
Page 9 of 19
qT
' ' .- 199
Originally Issued: 10/08/2010 Revised: 09/12/2017 Valid Through: 09/30/2018
Figure 3 — VELUX VS/VSE/VSS Skylight
(Horizontal Section View)
I'
i
f Ii K� '.. _(� 1 . 41 �•
r_...I-
i+
Figure 4 — VELUX VS/VSE/VSS
Skylight
Page 10 of 19
UE �?�t y y ! REPORT
Originally Issued: 10/08/2010 Revised: 09/12/2017
199
Valid Through: 09/30/2018
Table 4 — VELUX FCM Skylights — Glass Weight = 5 psf
Skylight Description
NAFS Performance Grades
Other NAFS Designators
Size
Code
Unit size0)
(inches)
Download
(PGPOS)
Uplift PGNe
p ( e)
Primary
Prima
Maximum Air
Leakage(2)
Max. Pressure with No Water
Penetration(2)
1430
17-1/2 x 33-1/2
+11,990 Pa
(+250 psf)
-5,760 Pa
(-120 psf)
SKG-PG120
1308 x 1308
(51x51*)
0.1 L/s/m2
(0.02 cfm/ftz)
720 Pa (15 psf)
720 Pa (15 psf)
1446
17-1/2 x 49-1/2
2222
25-1 /2 x 25-1 /2
2230
25-1 /2 x 33-1 /2
2234
25-1/2 x 37-1/2
2246
25-1/2 x 49-1/2
3030
33-1 /2 x 33-1 /2
3046
33-1/2 x 49-1/2
3434
37-1/2 x 37-1/2
4646
49-1/2 x 49-1/2
2270
25-1 /2 x 73-1 /2
+ 9,590 Pa
(+200 psf)
-4,800 Pa
(-100 psf)
9KG-PG100
660 x1854*
(26 x 73*)
0.1 L/s/mz
(0.01 cfm/ftz)
Table 5 — VELUX VCE, VCM and VCS Skylights — Glass Weight = 5 psf
Skylight Description FNAFS Performance Other NAFS Designators
Grades
Size Unit size0) Downward Uplift Primary Maximum Air Leakage(2) Max. Pressure with No Water
Code _(inches PGPos PGNeq Penetration 2
2222 25-1/2 x 25- r11
1/2
25-1 /2 x 37-
F
1/2
25-1/2 x 49-
2246
1/2
33-1/2 x 33-
3030
1/2 +11,052 Pa
(+230 psf)
33-1/2 x 49-
3046
1/2
3434 37-1/2 x 37-
1/2
4646 49-1 /2 x 49-
1/2
(1) Outside Curb dimensions
-2,560 Pa
(-45 psf)
SKG-
PG45 0.1 L/s/mz
1305 x
1305 (0.02 cfm/ftz)
(51 x51 *)
(2) Based on tested size indicated in Primary Designator
Page 11 of 19
720 Pa (15 psf)
UEs , ►
'�`� 199
TM Originally Issued: 10/08/2010 Revised: 09/12/2017 Valid Through: 09/30/2018
Table 6: Curb Mount Skylights - Energy, Light and Comfort
Model/Glazing U-Factor
(Btu/ft2rF/hr)-_
FCM ...04 0.48
Solar Heat Gain
Coefficient (SHGC)_
0.27
0.27
Visible Condensation
Transmittance VT Resistance CR
0.63
50
_
FCM ...06 0.46
0.62
51
FCM ...08 0.48
0.26
0.46
50
FCM ...99 94 0.43
0.25
0.57
42
VC ... 04 0.53
0.24
0.55
E 58
VC ... 06 0.50
0.24
0.54
59
VC ... 08 0.53
0.23
0.40 11
58
VC ... 99 94 0.48 0.22 0.49 49
1. U-factors and Solar Heat Gain Cent, Visible Transmittance shall be determined in accordance with NFRC 100 and NFRC 200,
respectively and by an accredited, independent laboratory, and labeled and certified by the manufacturer-
2. Condensation Resistance shall be determined in accordance with NFRC 500 and by an accredited, independent laboratory, and
labeled and certified by the manufacturer
I i ,
♦ —dW
A
7,1" Prcd-1 dim--.J n :
Pnnn dii— -.inn-
Thrnn- slim cn �ior �.
<73
�NI
G'y
1,76
34
99G
9�3.8
y.I
46-
•13C,7
I2_'ri.5
r 01
�C
1010,5
1348
1�95 5
07
F �, urr dime -Finn
Fein? dinlenSir,n
I
I
r
I I I
II I I
I I
I I I
I -
I II ,
I I I +
I •+ I i
I + I I II
I I r r II
I I �Thl�oal olm?I��ion I II
r I II I l II I
Figure 5 — VELUX FCM Skylight
Horizontal Section View
(Typical for Vertical Section View)
Page 12 of 19
(oUIFO;,IEIII 50IFFUI_1-
TD1 F'APT/i_UPOPICG.
A Cu rcr Frame
F or-s rr'.rt•
inner `raTle cja l<e
Caner Bey +I
_
Pane
se-7ani
SCHEDULE.
FASTFNEF
1_M
PAR-r':"MPOP
--
IN��nd `�rrF`VJ
11II..
UEs EVALUATION REPORT 199
Originally Issued: 10/08/2010 Revised: 09/12/2017 Valid Through: 09/30/2018
Figure 6 — VELUX VCM/VCEIVCS Skylight Horizontal Section View
Sizc
22
I'S'dc framr.
532.5
Throat
FILM
Pcnc
675.5
504.5
629
30
Y
735.5
378.5
980
708
832
933 5
837
809.5
4 G
1.1
1 286
1 t j 4,5
1238 5
FLIv1
I
nsidc Fr_
i i
I �
ll l Threal
1'
�I
Page 13 of 19
-- •�
`
lj — _
L
—" �I 1
PART
✓'TEM
A
SCHEDULE
PAPT/COMPONENT
Pan,
B
Oular Framc
-
Pnng SPgcar
,D
(Nrl own)
D
Inner frame
Corgc:r hey
Coun ler flashing
�a_h Frame
G
i
Cgeh sled mg bloc!
U!lG gr.d,cl
F::a„
j
r
'u,,.n
p�,seglgnl
E-1111,11,
7UEs EVALUATION REPORT
Originally Issued: 10/08/2010 Revised: 09/12/2017
199
Valid Through: 09/30/2018
Figure 7 — VELUX VCMNCENCS Skylight Vertical Section View
Site + In,ide frame Thront FLM Fare
22 5-2.5 6755 504_5 629
30 735.5 878.5 708 832
34 8�•� 98G 809.5 933.5
46 1142 1286 1114-5 12--8 5
- � I l f •' "J ili lill ' � i
inll�l I �,
r e
A
v
0
a
V•
r
Page 14 of 19
PART SCHEDULE
1111i PART/CMPONENT
N Counl al Ilashinn
0 Lwlatiw :1 -
Incolakn (Eldcrn• dghl)
Screen relainer P
(D.U.rn only)
0 •none r-kel
f, ur,
nr,iY;rinr
j u ::..—
II H=!= Threaded In!&
r�yimf ren heed Rf
� r H.�•lur. 3�evr
Inwr:
L ::�•:w
�� 'r Hcad Scrw
# Note decigrmlc,• the Ilem 3N[ Shown
R-s % (m,,-Nnr S rexl &Rem Y
Bro_; In srl) rre -d In R m'S (lecntcr)
Originally Issued: 10/08/2010
Revised: 09/12/2017
PE
Valid Through: 09/30/2018
Table 7 — VELUX SUN TUNNELT" Skylights (Residential)
Skylight Description
NAFS Performance Grades
Other NAFS Designators
Model
Code
Unit sized)
(inches)
Download
(PGpos)
Uplift
(PGNeg)
Primary
Maximum Air
Leakage(2)
Max. Pressure with No
Water Penetration(2)
TGF 014
14
+14,364 Pa
(+300 psf)
-6 064 Pa
(-125 psf)
TDDCC-PG125
Size Tested
559 min (22")
0.2 L/s/mz
(0.04 cfm/ftz)
720 Pa (15 psf)
TGF 022
22
TMF 014
14
TGR 010
10
TGR 014
14
TMR 010
10
TMR 014
14
TCR 014
14
+14,364 Pa
+300
( psf)
-7,980 Pa
165
( psf)
TDDCC-PG 1650.5
Size Tested
356 m)
in14"
L/s/mz
(0.09 cfm/ftz)
720 Pa (15 psf)
Table 8 — VELUX SUN TUNNELTI Skylights (Commercial)
Skylight Description
NAFS Performance Grades
Other NAFS Designators
Model
Unit size0)
Download
Uplift
Primary
Maximum Air
Max. Pressure with No
(inches)
(� )
, ( PGPos )
( PGNe e)
Leakage(z)
Water Penetration(z)
TCC 014
14
+14,364 Pa
(+300 psf)
-7,023 Pa
(-145 psf)
TDDOClTDDCC-
PG145
Size Tested
1.4 L/s/mz
(0.28 cfm/ftz)
720 Pa (15 psf)
TGC 014
TMC 014
356 mm (14")
TCC 022
TDDOClTDDCC-
22
+14,364 Pa
(+300 psf)
-6,224 Pa
(-130 psf)
PG130
Size Tested
1.5 L/s/mz
(0.30 cfm/ftz)
720 Pa (15 psf)
TGC 022
559 mm (22")
(i) Nominal tunnel size (z) Based on tested size indicated in Primary Designator
Page 15 of 19
UEs '199
Originally Issued: 10/08/2010 Revised: 09/12/2017 Valid Through: 09/30/2018
Table 9: SUN TUNNELT"9 Skylights - Energy and Comfort
Assembly Names
U-Factor
Solar Heat Gain Coefficient
Btu/ft2/°F/hr
SHGC
0.21
0.25
TGF/TMF all
0.50
TGR/TMR ...EO w/ Energy Kit
0.38
TCR ...EO w/ Energy Kit
0.38
0.25
TCC/TGC/TMC 014 ...TOEO (w/
0.55
0.28
Energy Kit) Insulation at Roof
TCC 014 ...THEO (w/ Energy Kit)
0.38
0.25
Insulation at Ceilin4
TCC 022 ...TTEO (w/ Energy Kit)
0.43
0,22
Insulation at Roof
TGC 022 ...TTEO (w/ Energy Kit)
0.41
0.26
Insulation at Roof
1. U-factors and Solar Heat Gain Coefficient shall be determined in accordance with NFRC 100 and NFRC 200, respectively and by an
accredited, independent laboratory, and labeled and certified by the manufacturer-
T1-J F
C
E.1 v
1: 4, "tim
s10e ��,
i _.
)i�aw
H i PI to
(part of Energy Kit) -
-11, F-'ti
(Optional)
Resfoontlal £nkr• . I
Port Schedule
e
Done
Pivot/Inter-ncdlota Ring Conplote
C
Pitch Flashing (TIC/TMP)
n
Top Collar
C
Lo. profile Floshing tTGr; TGP)
F-1
Scre.
r
Fle- Tubing (TGF%TMF)
a
DCP- Klt,'Celling Ring Complete
N
Diffuser Gosl•.et
[
Clear Diffusor
Heot Gain Shield Plate
Figure 8 — VELUX SUN TUNNELT" (TGF/TMF) Skylight
Page 16 of 19
CUE
EVALUATION REPORT Nut
TFA Originally Issued: 10/08/2010 Revised: 09/12/2017
T/1 n
(Optional)
—it ''hiPl d
part of Energv Kit
199
Valid Through: 09/30/2018
Port Schedule
A
Done
a
Pivot/Intermediate Ring Complete
c
Pitched Floshng (TW/TMR)
a
LoA ProfAe Flashing (TGF/TGP)
E
Top Cdlor
EA
Scree.
F
Elbor (TGR/TMR)
G
Rigid Tube (TGR/TMR)
u
Pull Clip (TGR/TMR)
DCP. Klt/Celgng Ring Conplete
Clear Dirfuser
k
MIFFuser Gasket
L
Meat Gain Sheld Plate
Figure 9 — VELUX SUN TUNNELTM (TGR/TMR) Skylight
Page 17 of 19
qIr
+F 199
Originally Issued: 10/08/2010 Revised: 09/12/2017 Valid Through: 09/30/2018
H
i0
TCC 021
Tcc 014 in
�j,an Ceiling pilfu5er
Q3
1 �I
f J '\
n K
L
Tu6it� k Ci6aus
TMC 014
TCt /TGC.`]NC_ CcmmerSiol Fieehno
TTC 1)14.'022
Trnrs�itlgr issaxi Launmercial C1lifusef<
I
0
,t
Port Schedule
i
Mgld Tu6,g
t
Open Celing Uf Fuser
INF(us
Tr.n yTipn �.
Cars W D;Ffu r Fro
.4' to 22' Pound to Pound ocbptoi
c
[."",g Ping Conplete
frin Ring
❑ho.
I
E
TG' 022
Hph P,00, D—
1 Llpnt Nrr<IL+R �.k.
Dw
.} C C✓b GI.tHrp [fCC�
PltdKd Flo t*V ,TNC�
Tw cal.-
. Pt.at/IRltr.ed.it RFq Copltlt
i Rdd Tout
Clba.
FYo. rnh SHdd Rol.
f 1�TGC C114
THC C,14 /02-
Hard Ceiling Ditfu2jLr
H - D)
Figure 10 — VELUX SUN TUNNELTM (TCC/TCR/TGC/TMC) Skylight
(Note — TCR is similar to TCC 014 with THC Diffuser)
Page 18 of 19
Originally Issued: 10/08/2010 Revised: 09/12/2017
CALIFORNIA SUPPLEMENT
VELUX AMERICA, LLC
• VELUX FS, VS, VSE and VSS Deck Mount Glass -
Glazed Unit Skylight
• VELUX FCM, VCE, VCS and VCM Curb Mount
Glass -Glazed Unit Skylights
VELUX SUN TUNNEL TM Skylights (TCC, TCR,
TGC, TGF, TGR, TMC, TMF and TMR) (plastic -
glazed tubular daylighting devices)
CSI Section:
08 62 00 Unit Skylights
1.0 Compliance with the following codes
• 2016 California Building Code (CBC)
2.0 Requirements:
All information in ER-199, dated 09/12/2017
corresponding to compliance under the International
Building Code (IBC) also apply to compliance under the
CBC. Additional requirements for compliance with the
CBC are provided in Section 3.0 of this supplement
3.0 Additional Requirements:
3.1 Compliance for Materials Used
Reports of material testing and evaluation in accordance with
Clauses 10 and 11 of AAMA/WDMA/CSA 101/LS.2/A440-
11 and -08 comply with the applicable requirements of CBC
Chapter 7A and Section 1505.1 for fire resistance and Section
2405 and Chapter 26 for light transmitting plastic
components. Acrylic Domes are in compliance with CBC
Sections 2606 and 2610.
Table 1 —Glass Area, Nominal Frame Lap and
199
Valid Through: 09/30/2018
3.2 Glazing Requirements
For those applications subject to the requirements of the
Division of the State Architect -Structural Safety/Community
Colleges (DSA-SS/CC) or the Office of Statewide Planning
and Development (OSHPD 1 & 4), Table 1 of this
supplement provides information to verify compliance with
the additional provisions of Section 2403.2.1 and Table
2403.2.1 of the 2016 California Building Code.
4.0 Contact Information
VELUX America, LLC.
P.O. Box 5001
Greenwood, South Carolina 29648-5001
(864)941-4828
www.veluxusa.com
Glass Edge Clearance
Largest Size Nominal Design Values - mm (in.)
Skylight Model Glass Area Frame Lap Glass Edge Clearance
(ftz) Sides Bottom Top Sides Bottom Top
FS 13.29 23 (7/8) 23 (7/8) 22 (7/8) 3 (1/8) 7 4 (1/8)
VS / VSE / VSS 12.02 12 (1/2) 14 (1/2) 14 (1/2) 4.5 (3/16) 3 (1/8)
FCM 16.51 18 (3/4) 18 (3/4) 18 (3/4) 31 (1-1/4) 31 (1-1/4) 31 (1-1/4)
VCE / _VC M / VCS 16.51 18 (3/4) 18 (3/4) F18 (3/4) 31 (1-1/4) 31 (1-1/4)
Page 19 of 19