Loading...
0211-108 (CSCS) Smoke Control TestingMHUGHES ASSOCIATES, INC. L U FIRE SCIENCE & ENGINEERING 2102 Business Center Dr., Ste.130, Irvine, CA 92612 USA Phone 949-253A606 a FAX 949-253-4607 a www.haifire.com REPORT OF ATRIUM SMOKE EXHAUST SYSTEM TESTING 5e �77 OCT 2 3 2006 CITY OF LA EMBASSY SUITES, LA QUINTA, CALIFORNIA SA41-A 1Z&SA 'jA.azo. October 20, 2006 Prepared By: Michael J. Madden, P.E. Hughes Associates, Inc. 2102 Business Center Drive, Suite 130 Irvine, CA 92612 CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED ❑ATE BY —'L Offices located throughout the continental U.S., Europe, Korea, Singapore, and Taiwan REPORT OF ATRIUM SMOKE EXHAUST SYSTEM TESTING EMBASSY SUITES, LA QUINTA, CALIFORNIA I have reviewed this report and by personal knowledge and on -site observation certify that the smoke control system is in substantial compliance with the design intent, and to the best of my understanding complies with the requirements of the Code. Christopher Lever, P.E. Gage -Babcock & Associates 7-26-- &(P Date CITY OF LA QUlNtA_ BUILDING & SAFETY DEPT. APPROVED n,•.T?[C�44_ . _. HUGHES ASSOCIATES, INC. FIRE SCIENCE & ENGINEERING 2102 Business Center Dr., Ste.130, Irvine, CA 92612 USA Phone 949-253-4606 1 FAX 949-253-4607 a www.haifire.com REPORT OF ATRIUM SMOKE EXHAUST SYSTEM TESTING EMBASSY SUITES, LA QUINTA, CALIFORNIA October 20, 2006 Prepared By: Michael J. Madden, P.E. Hughes Associates, Inc. 2102 Business Center Drive, Suite 130 Irvine, CA 92612 J Michael J. Madden, PE Senior Engineer CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED DA TE — R), — f F P Offices located throughout the continental U.S., Europe, Korea, Singapore, and Taiwan ■ J Atrium Smoke Exhaust System Testing October 20, 2006 Fmhassv Suites Santa Rosa Plaza , .-,\ I" _ A Page 1 1.0 INTRODUCTION �.- AFET BY This report is intended to document the atrium smoke exhaust system testing performed at the new Santa Rosa Plaza Embassy Suites Hotel located in the City of La Quinta, California. This document also provides the necessary documentation required by Section 905 of the California Building Code. The Santa Rosa Plaza Embassy Suites Hotel retained Michael J. Madden, P.E., of Hughes Associates, Incorporated, to provide the Special Inspection Services described in Section 905.15 of the California Building Code. These services included observations of the construction of smoke barrier walls, observation of the installation of the fire alarm and detection system serving the atrium, preliminary testing of the smoke exhaust system components, preliminary testing of smoke exhaust system operation, and final testing of the smoke exhaust system and individual system components. Associated Air Balance, Incorporated, provided air balancing services and provided documentation of air flow velocities and air flow volumes as required by Section 905.15 of the California Building Code. The complete Air Balance Report for all HVAC systems in the building is not included in this report, however the measurement of all air handling equipment and components involved in the Atrium Smoke Exhaust System is provided in Appendices D through F of this Document. The originally proposed testing protocol is provided in Appendix A of this report. 2.0 FACILITY DESCRIPTION The Embassy Suites is a new four-story building classified by the California Building Code (CBC) as a Group R, Division 1 (R-1) Occupancy. The building has been constructed with a 6,900 ft2 atrium extending from the ground floor through the fourth - level (4-stories). The atrium is separated from adjacent guest room spaces by one -hour fire resistive construction with protected openings. Exit access balconies around the atrium are open to the atrium space at all levels. In addition, the exit access corridor to the first floor conference/meeting rooms is also open to the atrium space. Per CBC Section 402.2, the atrium and areas open to the atrium must be provided with a smoke control system complying with the requirements of CBC Section 905. CBC Section 905 provides requirements for the design of smoke control systems intended to provide a tenable environment for the evacuation or relocation of occupants. The exhaust method was chosen for the Embassy Suites project, which is typically the method applied to atria or large space applications. The goal of a smoke control system designed using the Exhaust Method is to maintain the smoke layer interface of the HUGHES ASSOCIATES, INC. Atrium Smoke Exhaust System Testing October 20, 2006 Embassy Suites Santa Rosa Plaza Page 2 accumulating smoke layer at least 10 feet above any walking surface in the smoke zone. In order to accomplish this goal on this project, a mechanical smoke exhaust system has been provided to maintain the smoke layer at a height of 43'-2" above the finished floor, which is 10 feet above the highest walking surface within the atrium (0 floor balcony). The mechanical smoke exhaust system provided for the project includes the following features: 1. The system provides 180,000 cfm of total exhaust for the removal of smoke and other products of combustion. The exhaust system consists of sixteen (16) exhaust inlets (four in each skylight). 2. Outside air is supplied to the atrium to make up approximately an equal volume of air exhausted. Make-up air will be a combination of forced air, and natural/free openings. 3. The fire alarm and detection systems for the building are zoned to facilitate the correct sequencing and activation of the smoke control system. The smoke exhaust system has been arranged for automatic activation, and by manual activation at the Firefighters Control Panel. 4. An Underwriter's Laboratories (UL) UUKL Listed smoke control panel is provided in the Fire Control Room. The panel has been arranged to provide manual override, and manual control of smoke control system components, as required by the California Building Code. 5. The system is supervised for positive confirmation of activation (i.e. fans, dampers, automatic doors, etc.), testing of devices, manual override mechanisms, and the presence of power downstream of all disconnects. Conductors and connections which interconnect equipment, devices, and appliances are monitored for integrity in accordance with NFPA 72, as adopted by the State of California. 6. All exhaust fans are rated and certified by the manufacturer for temperatures up to 1440F or higher. In addition, all belt -driven fans have 1.5 times the number of belts required for duty, or a minimum of two. 7. All electrical components of the smoke control system are provided with a standby power source in accordance with CBC Section 905.8. 8. All of the smoke exhaust system equipment meets the applicable provisions of Section 905 of the CBC. The Atrium Smoke Control System Design Report, prepared by Gage -Babcock & Associates, has been provided in Appendix B of this report. CITY OF LA QU BUILDING & "'I"A ETY CREPT. APPROVED HUGHES ASSOCIATES, INC. IRATE ���_... fl BY Atrium Smoke Exhaust System Testing October 20, 2006 Embassy Suites Santa Rosa Plaza Page 3 The building is divided into two smoke zones, for the purpose of operating the smoke control system. These zones are referred to elsewhere in this report and the Rational Analysis Report as Zones 1 and 2. These smoke zones are defined as follows: Zone 1 - The atrium space and all areas open to the atrium. Zone 2 - The remainder of the building not open to the atrium. The automatic activation of the smoke control system is accomplished through actuation of smoke detection in the atrium smoke zone (Zone 1). The system does not actuate upon actuation of a manual pull station. Once activated the system remains running until manually overridden at the fire department control panel. A smoke detection system is provided throughout the atrium space. This is has been accomplished by providing system smoke detectors in all corridors, lobbies, and balcony areas open to the atrium, and providing a projected -beam smoke detection system installed at the 4th floor level at approximately 33 feet above the atrium floor. The beam detectors are installed so that they project a beam horizontally across the atrium floor opening and with maximum beam spacing (between parallel beams) of approximately 8.25 feet. All devices are UL listed and installed per the listing, NFPA 72, and manufacturer's recommendations. The building is provided with a fire alarm notification system to initiate evacuation of the building in a fire emergency. The fire alarm notification system, when initiated, is audible throughout the building. The alarm system includes both audible and visual alarms located in accordance with the Fire Code, NFPA 72 and ADA requirements. The fire alarm and detection system is zoned to facilitate the activation of the smoke control system, as described above. The atrium zone (Zone 1) will include the atrium space and all areas open to the atrium which includes the main entrance lobby, the balconies/walkways around the perimeter of the atrium, and corridors to the meeting/conference rooms on the 1 st floor. A smoke barrier, consisting of one hour fire rated construction with protected openings, is provided to separate all adjacent areas from the atrium. 3.0 SMOKE ZONES AND SMOKE BARRIERS As indicated above, the building is divided into two smoke zones to accommodate the j atrium smoke exhaust system. Zone 1 includes the atrium, and all areas open to the J atrium atmosphere. The remainder of the building, beyond the atrium smoke barrier walls, is considered Zone 2. " L_.i":'r°';' 8: Srtr E�4Y [KEPT. HUGHES ASSOCIATES, INC. Jtk Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza October 20, 2006 Page 4 A smoke barrier provides the separation between Smoke Zone 1 and Smoke Zone 2. This smoke barrier is required to comply with the requirements of Section 905.2 of the California Building Code. The inspection of the construction of the smoke barrier wall was included under the Special Inspection requirements for the project. Several site inspections were made 1 during the course of the construction to verify that the construction of the smoke barrier walls was proceeding in accordance with the requirements of the Code. Physical inspections of the smoke barrier wall construction were made on the following dates: September 9, 2004 October 1, 2004 October 5, 2004 October 26, 2004 October 28, 2004 November 9, 2004 December 10, 2004 January 13, 2005 January 19, 2005 February 9, 2005 GATY OF LA QUN'Ti-A, BUILDING &SAFET`( D L-PT. Ate" P ROV IE D [•�i1i��Ti� These inspections involved reviewing wall framing installations, drywall installation, taping, and sealing, penetration and joint sealing, and the installation of the fire rated glazing assemblies and 20 minute fire -rated smoke and draft control door assemblies. During the construction, a significant portion of the guest room smoke barrier wall installation had to be redone due to drywall getting wet prior to the atrium roof being finished. The re -installation of the drywall in these areas was also reviewed for J compliance with the applicable requirements of the Building Code. The smoke barrier walls separating the atrium guest rooms from the atrium are in compliance with the requirements of Section 905.2 of the California Building Code. The construction of the walls consists of a one -hour steel framed, gypsum board fire -rated wall assembly. Drywall joints are staggered, and all joints are taped and sealed. Joints floor and ceiling have been protected with an approved fire rated sealing material. The Firelite fire rated glazing assemblies have been installed in accordance with the listing requirements, and the manufacturer's instructions. The doors self -closing, 20 minute fire -rated smoke and draft control door assemblies. All penetrations of these smoke barrier walls have been protected using approved penetration protection methods. On the first floor of the atrium, the smoke barrier wall separates the atrium from the meeting rooms, the Administrative Office areas, the Health Club, and the main kitchen HUGHES ASSOCIATES, INC. Atrium Smoke Exhaust System Testing October 20, 2006 Embassy Suites Santa Rosa Plaza Page 5 area. The smoke barrier wall typically involves a one -hour steel framed, fire -rated gypsum board wall assembly, with 20 minute fire -rated smoke and draft control door assemblies. All doors in these smoke barrier walls are either self -closing, or automatic closing door assemblies. In the kitchen area, the smoke barrier wall runs between the front cooking line and the back kitchen area. This wall has been constructed as a one -hour assembly, and has been installed with a tile facing to accommodate the cooking operations on both sides of the wall. In this wall, however, two bi-directional, metal swinging doors (non -fire rated) have been installed to facilitate movement between the kitchen and dining room area. These doors do not comply with the original design intent of the smoke barrier wall assembly. In reviewing the impact of these doors on the performance of the smoke exhaust system, calculations have been performed to identify the leakage areas involved with these non -protected door openings. In addition to the calculations performed, airflows and airflow velocities through these door openings were measured during smoke exhaust system operation. These air flow measurement results, and the leakage calculations performed for this portion of the first floor smoke barrier wall, are provided in Appendix C. The calculations in Appendix C calculate the leakage area to wall area ratio as stipulated in Building Code Section 905.2.3. Estimates were provided for the leakage around all doors in the smoke barrier, and actual leakage measurements were used to reflect leakage around the two bi-swing kitchen doors. The calculations performed show that the leakage around the kitchen doors, plus the leakage area estimated for all other doors in the smoke barrier wall on the first floor, do not exceed the allowable leakage area to wall area ratio specified in Building Code Section 905.2.3. As seen from the air flow measurements at these doors under both open and closed conditions, the airflow through these doors is not really significant given the amount of make-up air flow provided into the atrium. It should also be noted that the doors are not pulled open by the smoke exhaust system when the system is operated. 4.0 COMPONENT TESTING Testing of the smoke control system components, including fans, dampers, controls, and fire alarm systems, began in July of 2006. At that time, the mechanical equipment installation had been completed, and the fire alarm system work was nearing completion. Operational testing of the system components were performed by Hughes Associates personnel, with the assistance of the Fire Alarm and Mechanical System contractors and Embas v uites ersonnel. Actual measurements of component NITA PT. ]iF HUGHES ASSOCIATES, INC. TF I BY - - Atrium Smoke Exhaust System Testing October 20, 2006 Embassy Suites Santa Rosa Plaza Page 6 performance were made by Associated Air Balance personnel prior to the functional testing performed. Performance testing of the atrium exhaust fans, and supply and make-up air fans were performed by Associated Air Balance on August 1, 2006. These tests were run when 1 the system was in full smoke exhaust operation. f Weather conditions for August 1, 2006, were as follows: August 1, 2006 Maximum Temperature: 100 degrees F Average Wind Speed: 10.1 mph Wind Direction: 320 degrees (NW) A copy of the weather data from the National Weather Service is included in Appendix D of this report. A performance demonstration of the system was done on August 15, 2006, in the presence of Building Department and Fire Department personnel. Weather Conditions during the performance demonstration were as follows: -' August 15, 2006 1 Maximum Temperature: 104 degrees F Average Wind Speed: 7.0 mph Wind Direction: 330 degrees (NW) Additional testing of the make-up air gravity openings and RTU-25 fan unit air registers were performed on August 23, 2006. Weather conditions during these tests were as follows: August 23, 2006 Maximum Temperature: Average Wind Speed: 106 degrees F 4.7 mph CITY OF LA QUINTA EDLUNG & SAFETY DEPT. APPROVE vf: rE 0 E'.Y HUGHES ASSOCIATES, INC. I Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza Wind Direction: 330 degrees (SE) October 20, 2006 Page 7 All of the exhaust and make-up air supply fans were tested for proper operation, and control from the fire alarm system. The following fans make up the mechanical exhaust and make-up air systems for the atrium smoke exhaust system: Table 4.1.A Make-up Air Fans, Design and Specification Information Equipment SF-1 SF-2 RTU-25a RTU-25b Location Roof Roof Roof Roof Make Cook Cook AAON AAON Model 330 CPS 330 CPS RK-25-3 RK-25-3 Airflow, (cfm) 22,000 22,000 4500 4500 Static Pressure (in. wc) 0.5 0.5 1 1 Horsepower 101 10 31 3 Elec. Volts/ph/Hz 460/3/60 460/3/60 460/3/60 460/3/60 Table 4.13 Exhaust Air Fans, Design and Specification Information Equipment EF-9a EF-9b EF-9c EF-9d Location Roof Roof Roof Roof Make Cook Cook Cook Cook Model CA-SWSI CA-SWSI CA-SWSI CA - SWSI Airflow (cfm) 22500 22500 22500 22500 Static Pressure (in. we) 0.5 0.5 0.5 0.5 Horsepower 15 15 1 15 15 Elec. Volts/ph/Hz 460/3/60 460/3/60 1 460/3/60 460/3/60 m W a HUGHES ASSOCIATES, INC. Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza October 20, 2006 Page 8 Table 4.1.6 (cont.) Exhaust Air Fans, Design and Specification Information Equipment EF-9e EF-9f EF-9g EF-9h Location Roof Roof Roof Roof Make Cook Cook Cook Cook Model CA-SWSI CA-SWSI CA-SWSI CA - SWSI Airflow (cfm) 22500 22500 22500 22500 Static Pressure (in. wc) 0.5 0.5 0.5 0.5 Horsepower 15 15 15 15 Elec. Volts/ph/Hz 460/3/60 1 460/3/60 1 460/3/60 460/3/60 Those portions of the Air Balance Report pertaining to the supply and exhaust fan installations are provided in Appendix E of this report. The results of the airflow and velocity measurements made by Associated Air Balance, under full atrium exhaust system operation, for Supply Air Fans 1 and 2, and Supply Air Fans RTU-25a and RTU-25b, are summarized in the following performance tables: Criteria Airflow (cfm) Static Pres. (in. wc) Belts RPMs Voltage Amperage Table 4.2.A Supply Fan Performance Measurements ign Values 22000 0.5 3 SF-1 SF-2 Measured Measured 22940 22705 .63 .59 3 3 744 753 490 490 8.7/8.6/8.9 1 8.6/8.8/9 m HUGHES ASSOCIATES, INC. Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza Criteria Airflow (cfm) Static Pres. (in. wc) Belts RPMs Voltage Amperage Design Values 4500 1 1 October 20, 2006 Page 9 RTU-25a RTU-25b Measured Measured 4620 4655 .77 .78 1 1 1725 1725 490 470 3.6/3.7/3.7 3.6/3.8/3.9 Gi >-LU u- 0ELI d c� The results of the airflow and velocity measurements made by Associated Air Balance, under full atrium exhaust system operation, for the Atrium Exhaust Fans, are summarized in the following performance tables: Criteria Airflow (cfm) Static Pres. (in. wc) Belts RPMs Voltage Amperage Criteria Airflow (cfm) Static Pres. (in. wc) Belts RPMs Voltage Amperage Table 4.2.13 Exhaust Performance Measurements Design Values 22500 0.3 3 ign Values 22500 0.3 3 EF-9a EF-9b EF-9c EF-9d Measured Measured Measured Measured 23225 23400 23280 23135 .47 .53 .50 A8 3 3 3 3 1760 1760 1760 1760 490 490 490 490 15.4/16.3/15.7 15.7/16.3/15.9 16.1 /16.9/16.3 1 15.6/16.2/15.2 EF-9e EF-9f EF-9 EF-9h Measured Measured Measured Measured 23570 22865 23375 23175 .53 A9 .57 .46 3 3 3 3 1760 1760 1760 1760 490 490 490 490 16.1 /16.2/16.1 15.5/15.1 /15.6 1 15.7/14.7/16.2 1 15.5/16.7/16.1 HUGHES ASSOCIATES, INC. 11 Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza October 20, 2006 Page 10 The RTU-25a and RTU-25b air handlers supply conditioned air to the atrium space under normal conditions. These fans are normally controlled by the building energy management system, however under fire conditions, the unit controls are overridden by the fire alarm system. These air handlers and their supply registers in the atrium are balanced for the normal air conditioning operation. Under atrium fire conditions, these fans will continue to run or they will be started up, to provide make-up air at the first level of the atrium. To reduce velocities from the slot registers at the side of the atrium, normally closed fire dampers will open up, diverting some of the air flows to three more ceiling registers. The results of the airflow and velocity measurements made by Associated Air Balance, under full atrium exhaust system operation, for the RTU-25a Supply air Registers, are summarized in the following performance tables: Table 4.2.0 RTU-25a Supply Air Register Air Flow Measurements a b c d LSD LSD CD CD 48x6 48x6 24x24 24x24 CFM Flow Rate Design 400 400 300 200 Observed 565 500 230 170 Velocity (fpm) Design 200 200 200 200 Observed 158 43 e f g h I CD CD LSD LSD CD 14x14 14x14 48x6 48x6 14x14 CFM Flow Rate 200 200 4001 400 200 -Design Observed 335 290 485 535 275 Velocity (fpm) Design 200 200 200 200 200 Observed 1 1 1243 261 HUGHES ASSOCIATES, INC. Atrium Smoke Exhaust System Testing October 20, 2006 Embassy Suites Santa Rosa Plaza Page 11 k I CD CD LSD 24x24 2424 24x24 CFM Flow Rate Design 600 600 600 Observed 320 500 415 Velocity (fpm) Design 150 150 150 Observed 80 1125 104 a n { 9 AFT� The results of the airflow and velocity measurements made by Associated Air Balance, under full atrium exhaust system operation, for the RTU-25b Supply air Registers, are summarized in the following performance tables: Table 4.2.D RTU-25b Supply Air Register Air Flow Measurements a b c d LSD LSD LSD CD 48x6 48x6 48x6 2424 CFM Flow Rate 400 400 400 150 -Design Observed 525 555 570 125 Velocity (fpm) Design 200 200 200 200 Observed 1263 1278 1285 132 e f G h I LSD CD LSD LSD CD 48x6 24x24 48x6 48x6 24x24 CFM Flow Rate 400 1501 400 400 600 -Design Observed 515 120 509 475 385 Velocity (fpm) Design 200 200 200 200 200 Observed 1256 130 255 1 1 193 HUGHES ASSOCIATES, INC. Atrium Smoke Exhaust System Testing October 20, 2006 Embassy Suites Santa Rosa Plaza Page 12 J K CD CD 2424 2424 CFM Flow Rate Design 600 600 Observed 420 465 Velocity (fpm) Design 150 150 Observed 1 105 _ , r LA O Uyes` JFA SAFETY DEPT. APPROVED CNIEV7a�C•T• Based on the test results indicated above, several of the slot registers and ceiling registers have outlet velocities that exceed the design value of 200 feet per minute (values indicated in red). The 200 foot per minute design parameter is based on Section 4.6.4 of NFPA 92B, Smoke Management Systems in Malls, Atria, and Large Spaces. Section 4.6.4 states that "the make-up air velocity shall not exceed 200 ft/min where the make-up air could come into contact with the plume unless a higher make-up air velocity is supported by engineering analysis". The 200 ft/min limitation is intended to prevent significant plume deflection and disruption of the smoke interface. The location of the ceiling dampers in the atrium with face flow velocities greater than 200 ft/min are not in locations where the plume or smoke layer would be disrupted. With these ceiling dampers, the velocity would decrease rapidly as the air flow moves beyond the register. Similarly, the velocities from the slot registers will rapidly decrease as the airflow moves out from the register. In this situation, it does not appear that these velocities would significantly deflect the plume and disrupt the smoke layer interface. The flow measurements performed for the RTU-25a and RTU-25b make-up air systems are documented in Appendix F of this report. As indicated above, normally closed dampers in the RTU-25a and RTU-25b distribution duct work open up under atrium smoke exhaust conditions to divert airflow to additional registers, to reduce air flow velocities at the slot registers. These dampers were tested for proper operation and proper closure times during the component testing performed. The results of these tests are presented in the following tables: HUGHES ASSOCIATES, INC. Atrium Smoke Exhaust System Testing October 20, 2006 Embassy Suites Santa Rosa Plaza Page 13 Table 4.2.E RTU-26 First Floor Damper Performance Testing RTU-25a Damper RTU-25b Damper Correct Installation Yes Yes Time to Open (sec) Design 15 15 Observed Time 5 5 Additional make-up air is provided through natural airflows through operable doors and windows on the first floor level, and by make-up air louvers on the second, third, and fourth floors. Upon activation of the smoke exhaust system in the atrium, the operable doors and windows on the first floor open up to allow for natural make-up air flow into the atrium. At the same time, the outside air louvers at the end of the atrium corridors on floors 2, 3, and 4 open up, allowing make-up air to flow down the corridor. Make-up air supplied to the second, third, and fourth floors is by way of these outside air damper and louver assemblies. The control dampers are provided at the exterior wall, and additional louvered panels are provided inside of the damper location. The effective area of the outside air dampers were confirmed to be approximately 30 square feet in area, while the inside air louvers were confirmed to have an effective area of approximately 17 square feet. These opening areas are consistent with the design intent. The operational testing of the system verified proper operation of the make-up air openings. Associated Air Balance personnel performed air flow and velocity measurements at these make-up air openings. Their measurements are summarized in the following tables: C TA _U!NG 3: SAFETY DEPT. PAPPROVED DhTF Q(P-- BY HUGHES ASSOCIATES, INC. Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza October 20, 2006 Page 14 Table 4.2.F First Floor Make-up Air Openings, Performance Testing Opening Effective Area Flow Rate _(CFM) Velocity (fpm) Outside Door at Fire Control Room 23 sq. ft. 6026 262 Window at Lobby 30.1 sq. ft. 9692 322 Side Door at Main Entry 23 s . ft. 8349 363 Double Sliding Entry Door 38.2 sq. ft. 11536 302 Side Door at Main Entry 23 sq. ft. 8763 381 Pool Lobby Double Doors 159.25 20974 354 For the make-up air openings indicated above, the face velocities exceed the 200 ft/min guideline provided in NFPA 92B. These openings, however, are remote from the main atrium space, and the velocity of air flow from the lobby area into the atrium will be substantially less than the 200 fpm requirement. Air Flow and velocity measurements were also taken at the outside make-up air louvers at the end of the guest room corridors on floors 2 through four. Measurements were taken at the outside air damper, at the inside louver, and additionally, velocity calculations of air flowing down the corridor into the atrium space were performed to identify air flow velocities at the atrium. The results of the Associated Air Balance measurements at these make-up air openings are summarized in the following table: CITY OF LA QUINTH, E,U11 DIN a & SAFETY DEPT. APPROVEED C]fTE 1 O BY HUGHES ASSOCIATES, INC. Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza October 20, 2006 Page 15 Table 4.2.G Floors 2 through 4 Make-up Air Openings, Performance Testing Opening Effective Area Flow Rate (CFM) Velocity (fpm) 4�Floor E, Outside Louver 30 sq. ft. 10500 350 e Floor E, Inside Louver 17 sq. ft 6127 360 4 Floor E Corridor 49 sq. ft. 6127 125 4 Floor W, Outside Louver 30 sq. ft. 11520 384 -`ID 4 Floor W, Inside Louver 17 sq. ft 5936 349 4 Floor W, Corridor 49 sq. ft. 5936 121 i 3r Floor E, Outside Louver 30 sq. ft. 9180 306 3Fd Floor E, Inside Louver 17 sq. ft 4635 272 3rd Floor E Corridor 49 sq. ft. 4635 95 3 Floor W, Outside Louver 30 sq. ft. 9810 327 3"Floor W, Inside Louver 17 sq. ft. 4835 284 3 Floor W, Corridor 49 sq. ft. 4835 99 2" Floor E, Outside Louver 30 sq. ft. 6430 215 2" Floor E, Inside Louver ILN ft. 3742 220 2" Floor E Corridor 49 sq. ft. 3742 77 2" Floor W, Outside Louver 30 sq. ft. 4430 272 2" Floor W, Inside Louver 17 sq. ft 2534 149 2" Floor W, Corridor 49 2534 52 a_ W n - >LU U_. =C 0 a �4, y a LN The total make-up air flows from the corridor outside air louvers is 27,809 cfm. As you can see from the above table, even though the face velocity at the inner louver exceeds 200 ft/min, the velocity of the airflow as it flows into the atrium from the corridor is less than the 200 ft/min limitation in the Code. The flow measurements taken by Associated Air Balance during Smoke Exhaust system operation are documented in Appendix G of this report. 5.0 SYSTEM FUNCTIONAL TESTING In addition to the component testing discussed above, the smoke exhaust system was functionally tested to verify system operation and control functions were in accordance with the design intent, and in accordance with the requirements of the Building Code. A The functional testing included inspecting the operation of all fans, dampers, make-up air doors and louvers, and reviewing system supervisory features, Smoke Exhaust JSystem Control Board functions, and status indications. Hughes Associates personnel, along with representatives of the Building Safety Department and Fire Department participated in functional testing of the system on August 15, 2006. J HUGHES ASSOCIATES, INC. Atrium Smoke Exhaust System Testing October 20, 2006 Embassy Suites Santa Rosa Plaza Page 16 During the testing, the smoke exhaust system was activated using fire detection devices provided in the atrium, specifically the spot -type smoke detectors located in the lobby and the perimeter of the atrium, and the projected -beam smoke detectors located at the fourth floor level in the atrium. The response of the system controls to these detector activations was in accordance with design requirements. Upon smoke exhaust system activation, the roof -top exhaust fans were confirmed to start and continue to operate until the system was reset. The fans started immediately, well within the 15 second start-up time dictated by Section 905.14 of the Building Code. Full fan output was witnessed to be achieved after about 15 to 20 seconds of fan operation, which is within the time limits specified in the Code. In addition, power supplies to the fans were disconnected to verify fan power supervision features. Upon smoke exhaust system operation, it was verified that the make-up air louvers provided at the ends of the open corridors at the second, third, and fourth floor levels opened as intended, and remained open until the system was reset. When the system was reset, the louvers closed and assumed their normal status position. The make-up air doors and windows on the first floor were verified to open and remain open during system operation, and to assume their closed, normal operating condition, upon system reset. Doors and windows began to open immediately upon system activation, well within the 15 second time limit specified in the Building Code. Doors and window openings achieved their full open position within approximately 15 seconds of operation. The Smoke Exhaust system was also tested under emergency power conditions, in two ways. First off, the smoke exhaust system was activated through the activation of a lobby level spot -type smoke detector (using the magnet test procedure). When all of the fans and other components were in full operation, the main power was disconnected. The emergency generator started up, and picked up the smoke exhaust system power loads, to include all exhaust fans and make-up air fans. With the main power disconnected, and the smoke exhaust system reset to its normal standby mode, the system was activated automatically. The system went to full operational status on emergency power, to include the operation of all exhaust and make-up air fans, control dampers, make-up air door, window, and louver operators, and functions at the Firefighters Smoke Exhaust System Control Board. The operation of the Smoke Exhaust System Control Board was also reviewed, and the functions provided with the required On -Off -auto switches were tested for proper functioning. -- C IC G BUILDING $ ED 5f=1; = i c =Di=R pp�IL. ; HUGHES ASSOCIATES, INC. J � BY Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza October 20, 2006 Page 17 The RTU-25 air handlers that provide make-up air to the first floor level upon smoke exhaust system operation are also arranged to provide continuous ventilation for the atrium area. These units are set up to run continuously to provide ventilation, and they are provided with cooling and heating coils for temperature control. These units are supervised by the smoke exhaust system panel. If these units are programmed "off', a supervisory "fault' condition is indicated at the smoke exhaust system control panel. RTU-25 supervisory conditions were verified during the smoke control system testing. fir,", 1 F'- iU,LDINIG & SAFETY Dt ' T. VED IDATE FY HUGHES ASSOCIATES, INC. Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza APPENDIX A October 20, 2006 Page 18 CITY OF LA QUANTA BUILDING & SAFETY DEPT. APPROVED DATE JCy" BY ! ATRIUM SMOKE EXHAUST SYSTEM TESTING PROCEDURES HUGHES ASSOCIATES, INC. C iTY OF LA QU I N TA �, •� BUILDING & SAFETY DEPT. O -d cd a H APP E 4 - � Gi y •� � � �a&� aUwO a)Cd U � y cod U O A O 7 U Q -0 6 U vUi •� Z cd '� y U � � l 0 Z W a�pd,'�� ( o O C CA y Ll 5 — 0 Z 0 .0 N Q W UO ° QR cd•- a Q 1 X 0 2.4 ch c as .�.�-p- on �- o'•� v J W a .5 cd 40 C Y 0 o to . y a-� Cd a m � W U m oo�on� ' W ed 00 o y 0 a M -0 � o °) m 4: (2 a�i fib+ y 1� 0 9 y C� Cd Cd � y 0 O a Cd OQ" 0 {�• •-- ¢¢,N'v 1 O � 0. J EH°'`�Q o U Q. ¢, O� to E O rn cd N O N 0 cn D 7U 0, �t4 o C 3 5: L)•�(L)�� `� A U 0 a 00 �' 0 :� Cd � O a" r}n • � C�. d ., � Cd o Cd e ° ... C] + r_i � Orn U o rn ` 3 r, Cd a � o ) U y Cd d) O C 3 cn Cd U U a �O U � ..W, 'C U 0�E.1 4, Cd Cd >1 CdCd o« rn N ,� a o O O Cd °n G r a O - ;. a. � Cd Id Cd o a d) ++ 0.0 () cd 0— 0 bq i -O ti cn xYd o o O 'aW U r'n . - N av � aU tea�-• +4 Cd (D Cd�U � ° E►? 9aE� --Ei E "0 N m 0a� `' 'd � 0 cd N " o� °' �US � w ° u; o �� v 4 0o o ° � w � � ° 0' � ° a U U U A .. Ca U a 4" > ILI f/3 iy 'b H a ° p v rn N �"� 'G .�, 4� a-ry O L, QUINTA BUILD & SAFETY 0 U O Vl O 1 ATE " ` 4r Y Q v v O C v R m vi C) rA m 0 CO) c ca 0 i Cd O 0 Cd 4. - ~ Cd � U O U N _O O � O Cd �3 � � c w Cd I qq O oM N � O IL O r. O U .r., 4-4 rn y a i O U 4. .b a� U U 0. 0 Cd 1= Gn d N N ❑ ccU W 0 Y O , >, E a� Q N m a. N � � w +N+ m 4. CD y yo o M E o N rn � o c (D N W H �✓ ► i k! (�.,) F LA- lam' S..r 9 l "I -FA GL .4j_.^EMIC & SAFETY DEFT. A;.G L E i0V' x O e 0 U t� cn cn Cd O. W 0 O w Cd N rn O N � � o O rn 'b U �, N t02 'd O Cd -0 Yr O rn Cd cd Cd am "0 U 44 N N 3 Cd A Cd Cd 0 3 rn >, O O -0 El '0 3 U Cd 6 - H �¢ A C7 U N L: O .0 N 0 4. O U U r .5 U U 0. .r: O .0 D 0 U 'C .b U U CA o C o V ~ Cd 4.1 w CA r coEn ' a .� o.M p El El U U CFr ' o o V a zs .0 0 a ++ ate.+ > •� 0 cd U iy N U p 0 0 ICZ a °' 0 ❑ U O .O O id a� '[] rn U p Cd ti N D CJ +�+ C4 U rn O ed 0 4-4 N cad Cd In cd �y N w �_ 0. O CP ci - '0 v O0 a to Ld prl 1.K O O 'O GL N O O 'O t ++ 0 O 'V +� O to a7 o .0 G cd � ,C o ° U N GO] • 0 0 Cd Cd 0 o, V.0 ° El ,� ❑ +' U • 0 O N U cd ¢] _+ '� �'� 0 Eled d d El H m u -c� a� cti a� .,c cd O O X- a -- O O o U O U N � d m _. Q+ p N `� o w U O O cd a O O N O 0. cd U2 cd cd `n cd O N CIS 0 O O O rcd '+• "+ 3 C'sU W � cd d CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED 0 ]ATE l0"BYQ X 0 O c� c� m d a1 O Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza APPENDIX B October 20, 2006 Page 19 CITY OF IA QUINTA BUILDING & SAFETY DEPT. APPROVED DATE 1 BY ATRIUM SMOKE CONTROL SYSTEM DESIGN REPORT HUGHES ASSOCIATES, INC. - ATRIUM SMOKE CONTROL SYSTEM DESIGN REPORT EMBASSYSUITES LA QUINTA, CAUFORNIA 4frlzn� off" car( GAGE-BABCOCK & ASSOCIATES Integrating Fire Protedon, Life Safety, and Security ATRIUM SMOKE CONTROL SYSTEM DESIGN REPORT EMBASSY SUITES LA QUANTA, CAUFORNw 6 0 -''Ml SkaTA go5A f.a-JA August 30, 2004 (Revised February 17, 2005) Prepared fbr. BHG Santa Rosa Plaza P.O. Box 1503 La Quinta, CA 92253 CITY OF LA QUANTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTION DATE= vS Y _ d Ate2 Prepared by. Gagne -Babcock & Associates, Inc. 6 Centerpointe Dr, Suite 760 La Palma, CA 90623 GAGE-BABCOCK & ASSOCIATES Fire Protection Life Safety Security I i I CIT`l ®F LA QUNNT"�' BUILDisd 5�,r-�i'' ` Er L_. J DATF 9W — FY - �- Table of Contents i 4age Babcock & Associates, Inc. 1.0 PROJECT SCOPE..............................................................................................................1 2.0 APPLICABLE CODES AND STANDARDS.......................................................................2 3.0 DESIGN METHOD............................................................................ .......................2 3.1 AXISYMMETRIC PLUME.......................................................................................................3 3.2 BALCONY SPILL PLUME......................................................................................................4 3.3 WINDOW PLUME................................................................................................................5 4.0 ANALYSIS ................ .......... ........ .......................................... .................................... ........ 6 4.1 EXHAUST CALCULATIONS...................................................................................................6 42 NUMBER OF EXHAUST INLETS......._.....................................................................................8 4.3 STACK EFFECT ........................... ................................................ ..................... .9 4A TEMPERATURE EFFECT OF FRE.. ::.......................... ... ...........12 4.5 WIND EFFECT.................................................................................................................12 4.6 HVAC SYSTEMS.............................................................................................................13 4.7 CLIMATE....................................................................................................................13 . 4.8 STRATIFICATION AND DETECTION.....................................................................................14 5.0 DESIGN CRITERIA .................... 5.1 MECHANICAL SMOKE EXHAUSTSYSTEM..................................................:.:.........:..:.........15 5.2 FIRE SPRINKLER SYSTEM .......... _....... _............................................................. 17 5.3 FIRE ALARM AND DETECTION SYSTEM..............................................................................18 ...... . 5A CONSTRUCTION .............. ............:::::......................... .................................................:..... 18 5.5 ATRIUM FUEL LOADING...................................................................................................19 6.0 SYSTEM INSPECTION & TESTING ... ........... ....................... ........................... „.....:....... 19 6.1 COMPONENT SYSTEM TESTING ...........................................................""'..............•...........19 6.1.1 Defection Devices .....................................................................................................19 6.1.2 Ducts ................................. ............................................................................19 61.3 Dampers, Louvers, and Automatic Doors.................................................................19 61.4 Inlets and Outlets......................................................................................................20 6.1.5 Fans........................................................................................................................20 61.6 Smoke Barriers.........................................................................................................20 62 ACCEPTANCE TESTING ....................................................................................................20 APPENDDC A — ATRIUM SECTION APPENDDI B — MAKE-UP AIR LAYOUT APPENDIX C — FIRE MODELING CALCULATIONS Embassy Suites (La Quinta, CA) Atrium Smoke Control System Conceptual Design Report GBA P.N. LF040026 August 30, 2004 (2-17-05 Revisions) Page i CITY OF LA QUINTA ll BUILDINGS�',.F� fy JEPT. FCC ;; C(NASTR_ C. Gage -Babcock & Associates, Inc. DATE,*_Q5_RY Ij 1.0 PROJECT SCOPE I f Gage -Babcock & Associates was contracted to provide fire protection engineering and code consulting support for the design of the atrium smoke control system proposed at the Embassy Suites located In La Quinta, California. The Embassy Suites is a new four-story building classified by the Califomia Building Code (CBC) as a Group R, Division 1 (R-1) Occupancy. The building is being proposed with a 6,900 ftz atrium extending from the ground floor through the fourth -level (4-stories). The atrium is proposed to be separated from adjacent spaces by one -hour fire resistive construction with protected openings at all levels as required by CBC Section 402.3. Exit access balconies around the atrium are not separated from the atrium space at all levels. Per CBC Section 402.2, the atrium and areas open to the atrium must be provided with a smoke control system complying with the requirements of CBC Section 905. Per CBC J Section 905, smoke control systems shall be based on a rational analysis in -accordance with well -established principals of engineering. This Design Report is intended to serve as the "Rational Analysis" for the proposed system and provide relevant design criteria for design and installation of all systems and construction features integral to the performance of the smoke control system:_ This report is intended 'tor review and approval by the City of La Quinta Building Department and Riverside County Fire Department. All designs should be reviewed for compliance.,with applicable code requirements and the specific requirementstrestrictions outlined in this report. Any deviations from the recommendations in this report will require review and approval by Gage -Babcock or similarly qualified person/firm approved by the City of La Quinta and Riverside County. Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Mum Smoke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page 1 C!?i( OF LA QUINTA BUILDING ca Sf FE—li .' DEPT. FOR G—ONISTIRUOTIONGagc�a bcQck sassodates, inc. SY Jk 2.0 APPLICABLE CODES AND STANDARDS The following codes, standards, design guides, and reference materials were employed in the engineering analysis and for developing the recommendations contained in this report 1) 2001 Edition, Cal'ifomia Code of Regulations (CCR), Title 24 • Part 1 — California Administrative Code (CAC) ■ Part 2 — California Building Code (CBC) A Part 3 — California Electric Code (CEC) Part 4 — California Mechanical Code (CMC) • Part 9 — California Fire Code (CFC) - 2) NFPA 92B - Smoke Management Systems in Malls, Able, and Large Spaces, 2000 Edition 3) ASHRAE (American Society of Heating, Refrigeration,_ and Air Conditioning Engineers) - Principals of Smoke Management, 2002 4) Society of Fire Protection Engineers/National Fire -Protection_Association, :The - - SFPE Handbook of Fire Protection Engineering, 3ro Edition 3.0 DESIGN METHOD CBC Section 402.2 requires that the atrium and arras open to the atrium be provided with a smoke control system complying with the requirements of CBC Section 905.. CBC Section 905 provides requirements for the design of smoke control systems Intended to provide a tenable environment for the evacuation or relocation of occupants. CBC Section 905 allows systems to be designed using one of the following methods: • Pressurization Method • Airflow Method • Exhaust Method The exhaust method was chosen for this project, which is typically the method applied to atria or large space applications. The goal of a smoke control system designed using the Exhaust Method is to maintain the smoke layer interface of the accumulating smoke layer Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page 2 CITY OF LA QUINTA BUILDING & SAFEETY DEPT. APPROVED FOR CCIvSTr-iUCTION �Ga o-l3atacack 8. Associates, Inc. at least 10 feet above any walking surface in the smoke zone. In order to accomplish this goal on this project, a mechanical smoke exhaust system Is being provided to maintain the smoke layer at a height of 43'-2" above the finished floor, which is 10 feet above the highest walling surface within the atrium (4t' floor balcony). To determine the required exhaust capacity of .the mechanical exhaust system, the plume mass flow rates (smoke generation) for the plume configurations applicable to this specific project must be calculated. There are three typical plume configurations that must be considered when using the Exhaust Method, which are outlined in CBC Section 905.5, and they are: • Axisymmetric • Balcony Spill • Window Not all of these configurations are applicable for all projects. Each has very specific applications and restrictions and each must be evaluated as to their suitability for the specific project. In the sections to follow, each configuration is, discussed, and evaluated. 3.1 Axisymmetric Plume An axisymmetric plume is expected for a fire originating on the atrium floor, removed -from any walls. In this case, air is entrained from all sides and along the entire height of the plume until the plume becomes submerged in the smoke layer. The mass rate of smoke production is calculated, based on the rate of entrained air, using the equations shown below from CBC Section 905.5.2.2. For z > zl mp = 0.022Q,"3z513 +0 0042Q� (1) For z < z, mp = 0.0208Q,311z where: Q = total heat output (fire size), BTU/s QC = convective heat output, BTU/s (taken as 0.70Q) z = height of smoke layer interface above fire, feet z! = limiting flame height, feet = 0.533QQ2, s These equations for the mass flow of axisymmetric plumes do not apply if obstructions Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Con6nl System August 30, 2004 (2-15-05 Revisions) Design Report Page 3 [3l]i? Q6 G S.4\r-ETY DEPT. �I a FOR CONSTRUC i-IO'N DAT BYX0 Ga e-B hcock & Associates, Inc. break up the plume flow. Given that we have a clear opening from floor to ceiling in the -' proposed atrium, the plume will not be obstructed unless it becomes wide enough to contact the edge of the balconies. Calculating the plume diameter using the equation below from CBC Seaton 905.5.2.5 can check this. d = 0.48[(T,; +460)/(Ta +460)1" z (2) where: d = plume diameter, feet TQ =ambient air temperature, 'F T, = plume center line temperature, °F = (318Qe2/3H-513 )+ T. z = height at which T. is determined, feet Based on the specifics of this project a design fire of 5,000 BTU/s (Q=3,500 BTU/s) and an ambient temperature of 68°F (inside temperature) will be used (See Appendix D for calculations relating to the desic,�n fine for the axisymmetric plume scenario). The plume diameter is calculated at the 4 floor balcony level (337) _to see if the plume will be obstructed, using Equation 2. _. ( — T 318Qc 2"H-Sf31+T - c—J a w-- = (318(3500Y13 (33.167) 513 )+ 68 = 282° F d = 0.48[(282 + 460)/(68 + 460)1'2 (33.167) =18.9 feet At the highest balcony level the plume is calculated to be 18.9 feet in diameter and the opening at that level is approximately 59' X 57'. Therefore, an axisymmetric plume is valid for this project and it can be assumed that the plume will not contact the walls.to confine the flow. 3.2 Balcony Spill Plume A balcony spill plume is one that flows under and around a balcony before rising, giving the impression of spilling from the balcony, from an inverted perspective. The equation for the mass rate of smoke production from a balcony spill plume is found in CBC Section 905.5.2.3. The mass flow rate is determined using the geometrically probable width based on architectural elements and projections using the following equation: Embassy Suites (La Quinte, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (215-05 Revisions) Design Report Page 4 CITY OF LACCU DEPT. TA BUILDING & S APPROVED FC2 CONSTRUC-riON •-1 i3A�E=-�� mP = 0.124(QW2 Y'1(zb +0.3HX1+0.063(zb +0.6H)I WF13 (3) where: m'P = plume mass flow rate, lb/s H = height above fire to underside of balcony, feet W = plume width at point of spill, feet zb = height from balcony to smoke layer, feet 8. Associates, Inc. The atrium contains geometry that may produce balcony spill plumes. Therefore, this plume equation will be used in evaluating the design. 3.3 Wil dow Plume A window plume is one that flows through an opening, such as a door or window, from a room into a large -volume open space. For this project, there are rooms adjacent to the atrium with doors and windows that open into the atrium space. However, the wall separating these spaces from atrium will be fire resistive construction with self -closing rated doors and fire rated windows. A window plume will only be valid if: the glass window is expected to break -due to a fire in these separated spaces. The building will be protected throughout with sprinklers; therefore it can be evaluated -using modeling whether a sprinkler -controlled fire would produce enough heat to break a fire rated window. i A compartment fire model was run using CFAST to determine if the glass: window may break for this project. The model was run using a- moderate t squared fire with a maximum fire size determined based on sprinkler activation. The upper layer temperature was recorded and compared to the exposure temperature curve used to test fine rated windows. The results below show that the temperatures the glass window is exposed to in a sprinkler controlled fire on this project are well below the exposure temperatures for testing and it can be expected that the glass will not break during the typical time frame a smoke control system is expected to perform. (See Appendix D for additional modeling input/output) Therefore, consideration was not given to window plumes for this project. Embassy Suites -(Le 4uinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (215-05 Revisions) Design Report Page 5 rF l-A U�I��'i �' BUILDING & SF`,FETY >,Li?T. FOR CONSTRUCTION Gag Babcock & Associates, Inc. DAl'E�—BY [.�� 4.0 ANALYSIS As identified above, the approach selected for the smoke control system design is the ! _ exhaust method. To design this type of system, several calculations and possible effects must be completed to ensure proper performance of the system. In the sections to follow, appropriate calculations and results are outlined, and relevant design factors are -_� considered. The final design criteria based on this analysis is summarized below in Section 11 5.0. 4.1 Exhaust Calculations Based on the design approach selected, the goal of our system is to provide mechanical _ smoke exhaust with the capacity to remove smoke from the atrium to maintain the smoke _l layer interface at a predefined height in the space for an indefinite .period of time. To 1 accomplish this goal, the system must exhaust the same quantity as the smoke produced by a .fire with the smoke layer interface at that predefined height. 1 In Section 3.0, the different plume configurations and their applicability to this project were discussed. For this project, the axisymmetric iplume and balcony spill configurations were 1 proven to be applicable. Therefore, the system as a minimum must have a total .exhaust J capability equal to the mass rate of smoke production calculated for -these plume configurations. Using Equation 1 found in Section 3.1 above, the smoke mass production rate is calculated for the axisymmetric plume scenario. The same design fire used in Section 3.1 above will be used, 5,000 BTU/s (Q,=3,500 BTU/s), and the smoke layer interface height (z) will be 43'2" (10 feet above the highest walking surface) as required by Code. a zl = 0.533(3500y" =13.9 fed :.z>zl MP = 0.022(3500Y"(43.167)5/3 +0.0042(3500) =1921b/s Based on the results, the system must provide at least 192 Ib/s of exhaust to maintain the smoke layer at the design height for an axisymmetdc plume scenario. This quantity can be converted to a volumetric rate using the equations below from CBC Sections 905.5.2.2 and 905.7.2. Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2-15-05 Revisions) JDesign Report Page 6 CITY OF #A QUINTAL BUILDV IC & SP IFEW GE -PT. APPROVED FOR 00� ISTRUCTIL N DATE-3(4'�--13Y V = 60mo / p (4) where: v =volumetric flow rate, cubic feet per minute (cfin) p = density of air at the temperature of the smoke layer, lb/ft3 Ts — Q. +Ta (5) me where: c = specific heat of smoke, (0.24 BTU/lb•° F) m = exhaust rate, lb/s Ta = ambient air temperature, °F TS = smoke temperature, OF & Associates, Inc. The smoke temperature using the same assumptions as before is calculated to be 144°F. At this temperature, the density of air is 0.066 Ib/ft3 and the volumetric exhaust rate is determined to be 174,545 cfm. v = 60(192)/ 0.066 =174,545 cfin Using Equation 3 found in Section 3.2 above, the smoke mass production rate is calculated for the balcony spill plume scenario. The fire scenario representing the worst case smoke production is on the first floor. Based on the Irchitectural design of the first floor ceiling the spill width (W) is assumed to be 10 feet (see Architectural RCP fro detail). The fire size used for this calculation is 625 BTU/s, which was determined based on sprinkler activation using ...(See Appendix D). The height of the balcony (H) used in the calculation was 9'-10" and the distance from the balcony to the smoke layer interface (zb) was 33'-4°. mp = 0.124(625 x 102 Y" (33.33 + 0.3 x 9.83X1 + 0.063(33.33 + 0.6 x 9.83)/ 10f 13 = 2081b/s The mass flow rate is then converted to a volumetric rate similar to the axisymmetric plume using a smoke temperature of 79°F and density of 0.074 IWO. Embassy Suites (La Quints, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page 7 CITY OF L.A QUINTA BUILDING & SA.FE -P( DE --PT. FOR CotN2 i R i GT10'iL Ga e4labcock & Associates, Inc. DATE_—EY V = 60(210)/0.074 =168,745 cfm Based on the results of each plume configuration the system must be capable of a minimum exhaust rate of 174,545 cfm. 4.2 Number of Exhaust Inlets The exhaust fan inlets should be sized and distributed in the space to be exhausted to minimize the likelihood of air beneath the smoke layer from being drawn through the layer, a phenomenon sometimes referred to as `plugholing". To accomplish this, the velocity of the exhaust inlet should not exceed a value to cause fresh air to be drawn into the smoke layer. The CBC does not provide equations or other guidance on this design aspect. Therefore, equations from NFPA 92BYwere used. The maximum volumetric flow rate that can be exhausted by a single exhaust inlet without "plugholing" is: V. = 0.537,6d 112 [TQ (T, —Ta )T iz (6) where: 7 V� =maximum volumetric flow rate without plugholing at Ts, cfm T. = abosulte ambient temperature, `R T,= absolute smoke temperature, °R d = depth of smoke layer below: the lowest point of the exhaust inlet, feet P = exhaust location factor (dimensionless) Using the smoke temperature calculated earlier of 1440F (6040R), an ambient temperature of 68°F (5280R), smoke layer depth of 5 feet (see Atrium section in Appendix A), and an exhaust location factor of 2.0, the maximum flow without plugholing can be calculated. The exhaust location factor was selected based on the suggested value for wall exhaust inlets near a ceiling. V. = 0.537(2.OX5)"' [528(604 — 528)1" =12,026 efm The maximum volumetric flow rate for an exhaust inlet is 12,026 cfi n, based on the required total exhaust of 174,545 cfm a minimum of 15 inlets are required. For purposes of symmetry, 16 inlets will be provided on this project each exhausting 11,250 cfm for a total of 180,000 dm. Embassy Suites (Le Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page 8 CITY OF LA QUINTA BUILDING & SAFETf DEP,r. FOR GONSTPUCTION DAT 4 By 4��ge & Associates, lnc. When the exhaust at an inlet is near this maximum flow rate, adequate separation between exhaust Inlets needs to be maintained to minimize Interaction between the flows near the inlets. The separation distance recommended is based on the distance from a single inlet that would result in arbitrarily small velocity (40 ftfmin) based on sink flow and Is calculated using the following equation from NFPA 92B. S.i. =0.023,6V,1/2 (7) where: Sffi = minimum edge - to - edge separation between inlets, ft v = volumetric flow rate of one exhaust inlet, cf n .8 = exhaust location factor (dimensionless) Using 11,250 cfm for the exhaust of an inlet and .the same exhaust- location#actor as before the minimum required distance between inlets is found to be 4'-11" for this project. SMk = 0.023(2.OX11,250y" 4.88 feet j A final requirement for exhaust Inlets is their size. It is recommended b Y_... NFPA 926, that the ratio d/D shall be greater than 2, where. D is the "effective -diameter'-of -the- inlet:: For. rectangular exhaust inlets, D = 2ab/(a + b), where a and b are the length and width of -the inlet. Based on the specifics in this project the effective diameter of the inlets must be less than 2.5 feet to comply with this recommendation. 4.3 Stack Effect The code requires that smoke management systems be designed such that the maximum probable normal or reverse stack effect will not adversely interfere with the system's ability to function as designed. The proposed system is based on an exhaust method of smoke control and does not use pressure differences to control smoke. Therefore, once the J system has been operated the smoke movement driven back either normal or reverse stack effect will be eliminated. To ensure that the system will perform as designed the exhaust and supply fans will need to be selected to compensate for the pressure difference caused by stack effect. During winter conditions, the atrium will be warmer than the outside air causing a normal stack effect where the airflow in the building will be in an upward direction with air flowing into the building below the neutral plane and out of the building above the neutral plane. This will not have a negative effect on the systemtfan performance except for supply fans J Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrlum Smoke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page 9 r ! z OF LA QUINTiUILDING & S�'t=ETY DEPT. FOR COVSTrUGT10N r age-Sabcoc &Associates, Inc. pp BY located above the neutral plane, which will need to counteract the positive pressure � difference trying to force air out of the building.. To determine the magnitude of the pressure difference caused by normal stack effect, the location of the neutral plane must be determined and then based on the distance and direction from neutral plane the pressure differenoe can be estimated. Based on a winter temperature of 26OF (4860R) and an inside temperature of 68OF (5280R) - the neutral plane location is calculated as follows: 1 H. =H 1+(TalTouis Where: H„ = height of neutral plane, ft H = height of shaft, ft TS = absolute temp of air in shaft, ' R T. = absolute temperature of outside air, *, R H = 54 1 1 + (528/486Y13 = 26.6 ft (8) Knowing the location of the neutral plane we can now estimate the pressure difference and direction based on the distance above or below the neutral plane. Since we are only concerned with the effect on supply points above the neutral plan for normal stack effect the pressure at the 4th floor calling elevation ' will be used, since all make-up air will be supplied below this point. Using an elevation above the floor of 40'6" the pressure difference is calculated below: Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2 15-05 Revisions) Design Report Page 10 CITY OF LA QUANTA BUILDING& BAFETY DEPT. FOR CONSTRUGTION DATE 65 6YA�:&Gago4 AP,. = 7. 1 1 h 4f. T, where: AIL = pressure difference from. shaft to outside, in. H2O (9) h = height above neutral plane, ft (negative numbers indicate below neutral plane) T, = absolute temperature of air in shaft, °R T = absolute temperature of outside air, "R AP,,, = 7. 4 1 — ' 13.9 486 528 = 0.0174 in. H2O & Associates, Inc. During summer conditions, the atrium will be cooler than the outside air causing a reverse stack effect where the airflow in the building will be in a downward direction with air flowing into the building above the neutral plane and out of the building below the neutral plane. This will have a negative effect on the system/fan performance in two areas, the.exhaust fans at the roof and the supply fans located below the neutraLplane.: These. fans will need to compensate for the pressure differences working against each of.these-fans. Similar :to before the neutral plane and pressure differences are determined. Fora reverse stack effect condition the calculations will be based on a summer temperature of 1170F (5770R) and the pressure differences will be evaluated- at the --floor (elevation 0'0") and exhaust inlets (elevation 50'01. - _ 1 H. _ 5 1 + (528/577r = 27.4 ft At the floor* AP = 7.64(1-1 — 27.4 577 528 = 0.0337 in. H2O At the exhaust inlets: Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (21"5 Revisions) Design Report Page 11 C1W OF. LA QU NTA BUILDING 8, SAFE;_W ❑EPT. APPROVED Fbk CONSTRUCTION Gage -Be cock & Associates, Inc. LATE o 13Y 1 _ 1 AP,.7.4577 528 2.b = —0.0278 in. H2O Based on the results of the normal and reverse stack effect above, the fans for this design must be selected using a higher static pressure as follows: 1. Exhaust fans - increase static pressure used in selection by 0.0278 in. H2O 2. Supply fans providing at the 4th floor level - increase static pressure used in selection by 0.0174 in. H2O 3. Supply fans providing at the 3'd, floor level and below - increase static pressure used in selection by 0.0337 in. H2O - 4.4 Temperature Effect of Fire CBC Section 905.2.2.3 requires that the buoyancy and expansion relating to gases produced by the design fire be addressed. The impact of the buoyancy and expansion of hot combustion gases was analyzed for this design -as follows: 1. As a result of using an exhaust system, gas expansion is not -a concern because the exhaust system will not allow any pressure to build-up in the space. 2. The system has been designed accounting for the worst -case change in density as a result of temperature increase from the design fire. 3. Buoyancy is addressed by evaluating smoke stratification issues for this design. Once the smoke evacuation system' has started in for the atrium, the stratification condition (if present) will be eliminated by removal of the hot layer. The problem facing is to ensure that the presence of smoke is promptly detected. To account for ensure appropriate detection and activation of the system a specifically designed detection system is being proposed. (See Section 4.8 for details) 4.5 Wind Effect CBC Section 905.2.2.4 requires that the adverse effects of wind be considered in the design of a smoke control system. In many instances, wind can have a pronounced effect on smoke movement within a building. The effect of wind on air movement within tightly constructed buildings with all doors and windows closed is slight. However, the effects of wind can become important for loosely constructed buildings or for buildings with open Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2 15-05 Revisions) Design Report Page 12 CITY OF IA QUINTA BUILDING & SAFETY DEPT_ APPROVED FOR CONSTRUCT ION Gage- hcock & /associates, Inc. DATE- 6 -,Y.XZ doors or windows, The building will be tightly constructed and all spaces are separated from the atrium so wind effects will be minimal. When the system is activated, because the exhaust method is being employed on this project, the driving force for smoke movement in the building will be the ventilation (exhaust) system. Given the size of the exhaust system, any wind driven smoke flow will be over powered by the forced exhaust. A final consideration is the location of the exhaust outlets and supply air intakes. Inlets and outlets must be configured so that smoke is not reintroduced into the building by the smoke control system. Therefore, all inlets will be upwind of outlets under prevailing wind conditions, which is Northwest, or otherwise located to reduce the possibility of drawing smoke back into the building. 4,6 HVAC SYStems CBC Section 905,22.5-- requires that consideration be given to the effects caused by heating, ventilation and air-conditioning (HVAC) systems on the smoke production and transport. The design for this project requires that the building HVAC systems (excluding guest room stand alone units) shut down upon the detection of a fire to eliminate any effects caused by its operation, In addition, all smoke barriers must be provided with smoke dampers in accordance with CBC Section 713.10. The kitchen exhaust fans located within the: atrium enclosure will not be controlled by the smoke exhaust system. If these fans are running during an atrium system activation, they will continue to run. In our opinion, the impact of these fans on the performance of the atrium exhaust system is negligible. In addition, to effects cased by the HVAC system the effects of the fire on equipment used for smoke exhaust must be addressed. The exhaust fans must be rated and certified for the probable temperature rise that they May be exposed. Previously, the smoke temperature was calculated to be 144OF in accordance with the calculation found in CBG Section 905.7.2. Therefore, to account for the effects of a fire and ensure continued operation of the smoke control system the exhaust fans must be rated for operating temperature greater than 144°F. 4.7 Climate CBC Section 905.2.2.6 states that the effects of low temperatures on systems, property and occupants shall be considered. In addition, the code states that air inlets and outlets associated with the smoke control system, where applicable, shall be located to prevent snow or ice blockage. Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium SmQke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page 13 TA OF LA QUINI BUILDING- SAFETY DEPT. FQR G—ONSTRUCTION Gage-Ba cock & Associates, Inc. DATC 'I. D 8Y The proposed location of the project is not subject to extreme cold temperatures that will require special measures to protect the system, property, or occupants from low temperatures. Also, the proposed location does not require special attention to prevent snow or ice blockage. Other climate considerations have been addressed elsewhere in this report. 4.8 Stratification and Detection When the temperature of the air in the upper portion of the atrium space is greater than that at lower levels, smoke can stratify under the hot layer of air and not reach ceiling. Stratification is only a concern with the exhaust method prior to activation of the system, since the exhaust system will remove any heated air from the top of the atrium upon activation. Therefore, smoke stratification must be accounted for the early stages of the fire this will be done by ensuring that proper detection and activation of the system will occur. Due to the high ceiling in the atrium, sprinkler activation is not an effective method for activating the system. As a result, smoke detection is proposed as the means for activating the smoke control system. To help ensure, that a fire is detected early and that the detection is not significantly affected by stratification horizontal beam detection is being added to the atrium to detect the smoke plume. The purpose of this approach is to detect the rising plume rather than the smoke layer. For this approach,, an arrangement of beams ' close enough to each other to assure intersection of the plume is installed. The spacing between beams shall be based on the narrowest potential width of the plume at the level of detection. The spacing of these beams, as suggested by NFPA 92B, shall be calculated using the following equation: d = 025z where: (10) d = minimum plume diameter/beam spacing, ft z = height above fire, ft a J The proposed height of the beam detectors is at the 0 floor level (33' AFF), solving the above equation the maximum beam spacing (between parallel beams) shall be 8.25 feet. Based on this proposed height of the beams, we must ensure that the plume will rise (overcome stratification) to reach the detection with a small enough fire size (i.e. early stages of the fire), Using the formula below we can solve for the maximum temperature change above ambient conditions that would prevent smoke from reaching our detection system for a given fire size. Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System .August 30, 2004 (2-15-05 Revisions) Design Report Page 14 cay of o, QUINTA BUiLDIN &. Sp,FETY KEPT, AP P RO\, = FOR CONSTRUCTICIN Gage- abcock&Associates, Inc. C) a 314 013Y AT. =1300Q,,i'H"' where: AT. =ambient temperture increase, 'F Q, = convective heat release rate of fire, BTU/s H = height above the floor, ft Solving using a height of 33 feet, and a convective heat release rate of 350 BTU/s (10% of the design fire size). AT. =1300(350y"(33y" =180°F 1 The atrium up through the 0 level Is condition spaces and a significant temperature change is not expected. It can be assumed 'that the temperature difference will be less than the 180OF required per the above calculation. Therefore, the detection system should effectively detect a fire within the atrium without being hindered by smoke stratification. 5.0 DESIGN CRITERIA Based on the above analysis and additional code requirements, design criteria applicable the smoke control system for this project is identified in the sections below_ 51 !Mechanical Smoke Exhaust Sysfiem Design Specifications 1. 180,000 cfm of total exhaust for the removal of smoke and other products of combustion. The exhaust system shall consist of sixteen (16) exhaust inlets (four in each skylight) mounted vertically with the bottom of the exhaust inlets at 487 or higher. Each inlet must be separated from each other (edge -to -edge) by at least 4'110. The maximum diameter of each inlet must not exceed 2.5 feet (for rectangular inlets see Section 4.2 of this report). 2. Outside air will be supplied to the atrium to make up approximately an equal volume of air exhausted. Make-up air will be a combination of forced air, and natural/free openings. The -proposed make-up air design Is illustrated in Appendix B. Nate that make-up air system has been design to keep the velocity towards the fire below 2.00 fpm. I Embassy Suites (La Quints, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 f2-15-05 Revisions) Design Report Page 15 J c1Ty 6F LA QUINTA LIJILD€NG &. SAFETY DEPT. FOR CONSTRUCTION GageE abcock & Associates, Inc. DATI=_3124CW BY -- 3. Mechanically supplied make-up air will be provided around the atrium perimeter at the ceiling of the first floor, supplied from air -handling units installed on the roof. Additional make-up air will be provided from air registers located within the make-up air _shafts located on each side of the atrium elevators. All make-up air fans, ducting, equipment, and controls will comply with the requirements of Section 905 of the Building Code. 4. Natural make-up air openings into the atrium will be provided through the use of automatic opening doors and windows located on the first floor (Main Entry, and Pool Entry), and through the use of automatic opening make-up air dampers located at the end of the atrium guest room corridors at the southwest and northeast comers of the atrium. Dampers and controls will be provided in accordance with the requirements of Section 905 of the Building Code. Door and window operators and controls will be UL listed systems meeting the performance requirements for smoke control system components required by Section. 905 of the Building Code. 5. The suppression and detection systems for the building must be zoned to facilitate the sequencing described below (See also Sections 5.2 & 5.3 for additional information). Automatic smoke control system activation will be accomplished in accordance with the sequencing described below, and by manual activation at the Firefighters Control Panel. 6. An Underwriter's Laboratories (UL): UUKI� Listed smoke control panel shall be provided in . a location accessible to the -fire department. The panel. shall- have a means. for manually starting and stopping the smoke control system and should indicate the status: of system graphically. The Fire Department must approve design of this panel. 7. All dedicated smoke control system components shall be required to undergo a weekly self -test, as required by the UUKL Listing. 8. The system shall be supervised for positive confirmation of activation (i.e. fans, dampers, automatic doors, etc.), testing of devices, manual override mechanisms, and the presence of power downstream of all disconnects. Conductors and connections which interconnect equipment, devices, and appliances shall be monitored for integrity in accordance with NFPA 72, as adopted by the State of California. 9. All exhaust fans shall be rated and certified by the manufacturer for temperatures up to 144OF or higher. In addition, all belt -driven fan shall have 1.5 times the number of belts required for duty or a minimum of two. 10.All wiring associated with the smoke control system, regardless of voltage, shall be fully enclosed within continuous raceways. 11.All electrical components of the smoke control system are required to be provided with a standby power source In accordance with CBC Section 905.8. 12.All of the proposed equipment shall meet the applicable provisions of Section 905 of the CBC. Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page 16 C,Ty oF; LA IN TA. QUILE)itMG & Sr - APPR(DVPD FOR CONSTRUCTION G -8abcack&Associates,Inc. 1 3Y Sequencing A very important piece of any smoke control system is proper activation sequencing. tf the sequencing is not con-ed, the system may not function properly and may not achieve the intended objectives. The following describes the recommended activation sequencing for the smoke control system in order to facilitate the goals of this project. The building should be divided into a minimum of two smoke zones, for the purpose of operating the smoke control system. These zones will be referred to as Zones 1 and 2. These smoke zones are defined as follows: Zone 1 - The atrium space and all areas open to the atrium. Zone 2 - The remainder -of the building not open to the atrium. The automatic activation of the smoke control system ' will be accomplished through actuation of smoke detection in the atrium smoke zone (Zone 1). The system shall not activate upon actuation of a manual pull station. Once activated the system will remain running until manually overridden at the fire dcparbnent control panel. In addition, .an alarm in any zone will shut down all normal HVAC operations for the building. f 5.2 Fine Sprinkler Systwn The Building Code requires that any building with an atrium be protected -throughout: by an automatic sprinkler system. The sprinkler system must be designed and installed in accordance with NFPA 13. The building will have a sprinkler system installed throughout - with quick response sprinklers installed in the atrium and areas open to the atrium as required for Light Hazard Occupancies by'NFPA 13 (other areas may require quick i response sprinklers based on code requirements). There is no special design J requirements or restrictions for the sprinkler system as a result of the smoke control system analysis. All valves controlling the water supply and water flow switches should be electrically monitored. Monitoring should consist of distinctively different alarm and trouble signals being automatically transmitted to an approved central station, remote station, or proprietary monitoring station. No special zoning of the sprinkler system is required for activation of the smoke control system. J Embassy Suites (La Quinta, CA) GBA P.N. LF040026 J Atrium Smoke Control System August 30, 2004 (2-J&05 R Page 17 Design Report 1 CITY OF LA CUINTA BUILDING & SAFETY DEPT. APPROVED FOR G0jNSTBUGTiGN GagL-E abcock & Associates, Inc. D""Tc--4-sa Lv�—i3y 5.3 Fire Alarm and Detection System The Building Code does not specffically require a detection system due to the presence of the atrium. However, Gage -Babcock has recommended that the automatic activation of the smoke control system be controlled using smoke detection in the atrium. Therefore, as a minimum, a smoke detection system covering the atrium space (excluding the skylights) and all areas open to the atrium shall be provided. Any detection devices meeting the requirements of the Building and Fire Codes may be used for this system. In addition to this protection, a specialized beam detection system must be install at the 41i floor level at approximately 33 feet above the atrium floor. The beam detectors shall be installed so that they project a beam horizontally across the atrium floor opening and with a maximum beam spacing (between parallel beams) of 8.25 feet. All devices shall be UL listed and installed per the listing, NFPA 72, and manufacturers recommendations. The building shall be provided with a fire alarm notification system to -initiate _evacuation of the building in a fire emergency. The fire alarm'notification system, when initiated, shall be audible throughout the building. The alarm system should include both audible and visual alarms located In accordance with the Fire Code, NFPA 72 and ADA requirements.. The fire alarm and detection system must be zoned to facilitate the activation of the smoke control system, as described above. The atrium zone (Zone, 1,) :will ;include the -atrium space and all areas open to the atrium, which includes balconiestwaikways,around-the perimeter of the atrium. The central monitoring station shall supervise the fire alarm system including the smoke control system. 5.4 Construction The intent of this analysis is not to prescribe any alternate to the building construction required by the Code. However, there are somb assumptions relating to the location of fire resistive construction and smoke barriers that need to be addressed (See Architectural Dwgs). The analysis assumes that one -hour fire rated construction separates all adjacent areas from the atrium. The three stair towers are enclosed to the exterior by two-hour fire rated construction. It is also assumed that the atrium separation will also act as smoke barriers and comply with CBC Section 905.2.3. Embassy Suites (La Quints, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page 18 CITY OF LA QUINTA BUILDING & S€.FUY DEFT. AP PROVED FOR CONSTRUCTION OAT> 3aZf)j�' BY 5.5 Atrfum Fuel Loading & Associates, Inc. It was the intent of this analysis to not limit the atrium fuel loading beyond its typical use or the restrictions present in the fire code. Therefore, in the open area of the atrium (i.e. high ceiling areas not adequately protected by sprinklers) furnishings and decorative materials must not exceed a potential heat of combustion of 9,000 BTUAb in compliance with CFC Section 1103.3.4.1. Decorative materials within the atrium shall be noncombustible, flame resistant or treated with flame retardant. 6.0 SYSTEM INSPECTION & TESTING Devices, equipment, components and sequences associated with the smoke control system shall be individually tested as required by CBC Section 9,05.15. The purpose of the inspections and testing. is to verify the functionality, sequence -and capacity of the installed - components and equipment -perform as required by this design analysis. All inspections and testing fro the smoke control system shall be witnessed and/or performed by a qualified special inspector or special inspection agency approved by the City of La Quinta. The special Inspector shall prepare a report documenting the inspections and testing performed in compliance with the requirements of CBC Section 90515.9. The report shall. be reviewed and signed by the responsible designer, and a copy of the final report shall be - filed with the building official and an identical copy maintained in an approved location.at ., the building. s 1 Component System Testing The intent of component system testing is to establish that the final installation complies with the specified design, is functioning properly, and is ready for acceptance testing. 6.1.1 Detection Devices _ Smoke detection associated with the smoke control system shall be tested in accordance with the Fire Code. Testing shall confirm that the system is completely installed and functional, and that the zoning of the system is compliant with the design. 6.1.2 Ducts Ducts that are part of the smoke control system shall be traversed using generally accepted practices to determine actual air quantities. 6.1.3 Darriggrs, Louvers, and Automatic Doors All dampers, lowers, and automatic doors associated with the smoke control system shall J Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2-15-05 Revisions) - Design Report Page 19 CITY OF LA QUINTA BUILDING & SAFFfy DEPT. APPROVED FDR CC)NSTRuCTION ❑R`l:_L BY Gag Ba cock & Associates, Inc. _AA_g5 be inspected to ensure proper installation per the manufacturer's instructions and to verify -- that equipment required to provide positive confirmation of actuation is installed. All dampers, louvers, and automatic doors shall be tested to confirm that they open and/or close fully in their Installed condition within the required response times stated In CBC Section 905.14. 6.1.4 Inlets and Outlets All inlets and outlets shall be read using generally accepted practices to determine air quantities and confirm that capacities are meeting the design requirements. 6.1.5 Fans Fans associated with the smoke control system shall be examined for correct rotation and number of belts. Measurements of voltage, amperage, rpm's and belt tension shall be taken and recorded. -- 6.1.6 Smoke Barriers All smoke barriers required by_ the smoke control system shall be inspected -for completeness of the construction by verifying: 1. The assembly is installed such that it completely separates the intended areas -to,:;; resist the passage of smoke: 2. All penetration are sealed with appropriate fire stopping. 3. Doors and closer are provided and listed for the intended purpose. 4. Glazing/windows are installed, sealed and listed for the intended purpose. Smoke barriers shall be 100% inspected during construction by the special inspector or inspection agency. 6.2 Acceptance Testing The intent of acceptance testing is to demonstrate that the final integrated system installation complies with the specific design and is functioning properly. Prior to beginning acceptance testing, all building equipment shall be placed in the normal operating mode, including equipment that is not used to implement smoke management, such as toilet exhaust, elevator shaft vents, elevator machine room fans, and similar systems. Wind speed, direction, and outside temperature shall be recorded for each test day. If conditions change greatly during the testing, new conditions shall be recorded. Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Actium Smoke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page 20 E F iA QUINTA & SAFETY DEPT. NS���TiDage-8abco k & Associates, Inc. .5 BY The acceptance testing shall be conducted while on both normal and standby power. - Disconnect the normal building power at the main service disconnect to simulate true operating conditions in standby power mode. Initiate the system via automatic means by initiating an alarm in a smoke zone. Confirm and document the sequence of operations for all equipment related to the smoke control system and response times of all individual components. While the system is running t measurements shall be taken to record volumetric flow rates for exhaust and supply air, and airflow velocities at the atrium openings. Each smoke zone shall be put into alarm to confirm the proper sequence of operations, fan motors may be bypassed during subsequent testing to avoid damage if approved by the AHJ and/or special inspector. Manual override of the system in normal or automatic modes shall be confirmed. Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page 21 -CITY OF LA QUINTA BUILDING & ,,;AFETY DEPT. APPROVED FOR CONSTRUCTION ❑A 5 BY U- I APPENDIX A - ATRIUM SECTION Z 0 C) W Iz J!A L4 C7 a g Cc� �� -A In CITY 4F LA QUINTA BUILDING & SAFMY D,PT. FOR GG;qSTRUGTIGN DATE 7+ � aY 0� J 0. IL N � 0. N 7 5 ag 9 � N a N N �L4 mo N eLL � g O u ul u Mm s L 0 5O G EM w M. rV O O J LL FL I § | § [ | § | r § | �i <8> < Old � § � f § � ■ � b � 2 b 0 � -I to OF ILA QU - A=� cam �V� o� �c APPENDIX C - FIRE MODELING CALdULATIONS C LA QU INTO► BUILDING e SAFE KEPT. FOR CONSTRUCTION DATF*ID!L—BY Axis nie#rr`c Plume: The design fire for the axisymmetric plume was arrived at using , the Sprinkler effective assumption allowed by CBC 905.6.2.4. Using the computer model CFAST Version 3.1.7 predictions for sprinkler activation were developed. The model was run as a one - compartment model representing the area of the open atrium space. A fire was placed in the center of room at the floor level. The fire was assumed to be a growing fire based on t- squared assumption. For this project the fire was assumed to grow at a moderate rate, which Gage -Babcock feels is appropriate given the occupancy, fuel loading, typical fuel spacing, and natural time delays that occur when a initial burning item spreads to adjacent items with any separation distance. Sprinklers were assumed at the atrium ceiling with spacing representative of the furthest away a sprinkler could be based on the proposed atrium ceiling design. The sprinklers were assumed to- be quick response; intermediate temperature sprinklers. The input file for the model follows with a printout of the spreadsheet output from the model. The model shows predicts that the sprinkler will activate at 508 seconds after ignition, which corresponded to a fire size of 2,870 BTU/s. The design fire used for this analysis is a steady state fire of 5,000 BTU/% which provides a very conservative design basis based on the results of the model. Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page C-1 EMBASSYI.DAT LABEL 1 970. 960. 0.1231. 1005. 10.15 00.00:00 0.00 0.00 GRAPH 1 100. 50. 0. 600. 475. 10.3 TIME HEIGHT GRAPH 2 100. 550. 0. 600. 940. 10.3 TIME CELSIUS GRAPH 3 720. 50. 0. 1250. 475. 10. 3 TIME FIRF—SIZE(kW) GRAPH 4 720., 550. 0.1250. 940. 10. 3 TIME OID2100 HEAT 00003 1 U TEMPE 00002 1 U INTER 00001 1 U 02 00004 1 U Page 2 CITY OF I.A. QUINITA BUILDING & SAFETY DEPT. APPROV�� FOR CONSTRUCTION DATE '3 BY J&-b a l ? 1 ! rsy i }I)IN f �Utlaa"1� _ •i^ Ruc G - K14--i TIME Main Fire Size Sensor Temperature( 1) Sensor fffJet Tom ng 1) s W K � K y 0.00 0.00 293.15 -93w- 10.00 11720.00 293.31 20.00 23440.00 293.59 295.41 30.00 35160.00 293.88 295.53 40.00 46880.00 294.17 295.60 50.00 68600.00 294.44 295.65 - 60.00 70320.00 294.68 295.68 70.00 82040.00 294.90 295.86 80.00 93760.00 295.15 296.19 90.00 106480.00 295.43 296.53 ` } 100.00 117200.00 295.73 296.89 !I 110.00 152360.00 296.12 297.65 120.00 187520.00 296.62 298.43 130.00 222679.00 297.21 299.23 1 140.00 257839.00 297.88 300.06 150.00 292999.00 298.61 300.92 160.00 328159.00 299.39 301.80 - -170.00 363318:00 = 300.21 302.70 180.00 398478.00 301.07 303.64 1 1 190.00 433637.00 301.97 304.59 200.00 468797.00 302.89 305.57 210.00 527396.00 303.90 306.87 220.00 585994.00 305.01I 308.21 230.00 644593.00 = 30622' 309.58 240.00 703191.00 307.5Q 311.00 '250.00 761789.00 :.. 306.84 312.47 260.00 820386.00 = - 310.25 -313.98 , i 270.00 878983.00 - 311.71 315.54 280.00 937579.00 313.20 317.14 290.00 996175.00 314.77' 318.77 ` 300.00 1054770.00 316.36 320.45 310.00 1136800.00 = 318.07 322-42 320.00 1218830.00 319.89 324.44 f 330.00 1300870.00 321.81 326.54 340.00 1382900.00 = _ - 323.81 ! 328.69 f 350.00 1464920.00 325.90 330.92, 360.00 1546950.00 328.06 333.21 l 370.00 1628970.00 330.30 335.56 380.00 1710990.00 =60 337.99 390.00 1793010.00 334.98 340.48 400.00 1875030.00 337.41 342.93 410.00 1980480.00 339.87 345,50 420.00 2085920.00 342.42 348.50 430.00 2191360.00 345.04 350.87 J 440.00 2296800.00 347.74 353.67 450.00 2402230.00 350.51 356.55 466.00 2507650.00 353.35 359.50 470.00 2613070.00 356.25 362.53 480.00 2718470.00 359.27 365.65 490.00 2823870.00 362.34 368.86 500.00 2929250.00 365.53 372.15 510.00 3016030.00 368.79 375.39 520.00 2933250.00 371.74 377.47 _# MODERATE paged LA �PT APPROVED UCTIG I ja�s TIME Main Fire Size Sensor Temperature( 1) re( 1) a W K 530.00 2852740.00 374.32 540.00 2774430.00 376.61 381.14 550.00 2698260.00 378.68 382.80 580.00 2824190.00 380.56 384.35 570.00 2552140.00 382.28 385.78 580.00 2482060.00 383.87 387.11 590.00 2413910.00 385.34 388.34 600.00 2347630.00 386.69 389.47 610.00 2283160.00 387.94 390.50 620.00 2220460.00 389.08 391.43 630.00 2159480.00 390.12 392.28 640.00 2100180.00 391.07 393.04 650.00 2042500.00 391.93 393.72 660.00 1966410.00 392.71 394.32 670.00 1931860.00 393.40 394.85 680.00 1878810.00 394,02 395.30 690.00 1827210.00 394.56 395.68_, 700.00 1777040.00 395.02 395.98 710.00 1728240.00 '` 395.42 396.23 720.00 1680790.00 395.76 396.43 730.00 1634640.00 396.03 396.56 740.00 1589770.00 396.24 396.65 750.00 1546120.00 396.40 396.69 760.00 1503680.00 396.50 396.67 770.00 1462410.00 396.55 ' 396.60 780.00 1422270.00 396.55 396.49 790.00 1383240.00 396.50 396,34 800.00 1345280.00 396.41 396.14 810.00 1308370.00 396.27 395.91 820.00 1272470.00 396.10 395.64 830.00 1237570.00 395.89 395.34 840.00 1203620.00 395.64 395.01 850.00 1170610.00 395.37 394.66 860.00 1138500.00 395.06 394.27 870.00 1107280.00 394.72 1 393_86 880.00 1076910.00 394.35 393.43, 890.00 1047380.00 393.96 392.974' 900.00 1018660.00 393.55 392.50 910.00 990733.00 393.11 392.00 920.00 963569.00 392.66 391.49 930.00 937151.00 392.18 390.97 940.00 911458.00 391.69 390.43 960•00 886469.00 391.18 389.87 960.00 862166.00 390.66 389.31 970.00 838530.00 390.12 388.73 980.00 816542.00 389:67 388.15 990.00 793184.00 389.02 387.55 1000.00 771438.00 388.45 366.95 1010.00 750289.00 387.87 386.34 1020.00 729719.00 387.28 385.73 1030.00 709715.00 386.69 385.11 1040.00 690258.00 386.09 384.49 1050.00 671336.00 385.48 383.86 MODERATE page 2 TIME s 1060.00 1070.00 1080.00 1090.00 1100.00 1110.00 1120.00 1130.00 1140.00 1150.00 1160.00 1170.00 1180.00 1190.00 Main Fire Size W 652932.00 635033.00 817624.00 BOW94.00 584227.00 568911.00 552635.00 537486.00 522752.00 508422.00 494485.00 480930.00 467747.00 454925.00 SensorTempwMre( 1) K 384.87 384.26 383.64 383.02 382.39 381.77 381.14 380.51 379.88 379.25 378.83 378.00 377.37 376.75 MODERATE Sensor Gas Jet Temperature( 1) K 38323 382.59 381.96 381.32 380.68 380.04 379.40 378.76 378.13 377.49 376.85 376.22 375.59 374.96 r,r.: LA 0;NTA BUILDING & SAFF' D,EPT. APPROVED F:)2 CONS T RUCT;oN Page 3 CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED FOR CONSTRUCTION Salconu SRni11 Plume: The design fire for the balcony spill plume was arrived at using the Sprinkler effective assumption allowed by CBC 905.6.2.4. Using a subroutine of the computer model FPETooI predictions for sprinkler activation were developed. The model was run using quick response, ordinary temperature sprinklers with a 10 ft. ceiling and spacing from the fire to the sprinkler of 10 ft. The fire was assumed to be a growing fire based on t-squared assumption. For this project the fire was assumed to grow at a moderate rate. The model shows predicts that the sprinkler will activate at 237 seconds after ignition, which corresponded to a fire. size of approximately 618 BTU/s. Based on this result the design fire for balcony spill plume used for this analysis is a steady state fire of 625 BTU/s. jSprinkler/detector activation calculation PRINTOUT/SCREEN DISPLAY INTERVAL (sec.) 1 HEIGHT OF CEILING ABOVE FUEL ft 10 �} DISTANCE OF DETECTOR FROM AXIS OF FIRE ft 10 INITIAL ROOM TEMPERATURE OF 70 DETECTOR ACTUATION TEMPERATURE OF 155 DETECTOR RESPONSE TIME INDEX (RTI) (ft/s)^.5 90 !� PRINTER DISABLED (Press ENTER to enable) FINISHED WITH INPUT (Press ENTER) FINISHED WITH ROUTINE (Press ENTER)I �I e Time(Sec) RHR(BTU/s) Jet (F) Head/det (F) 236 618 183 154 ---- Detector actuation at 237 seconds------- RTI —. 90.0 Height (ft) = 10.0 Dist. = fire axis (ft) _ Embassy Suites (La Quinta, CA) Atrium Smoke Control System Design Report 10.0 GBA P.N. LF040026 August 30, 2004 (2-15-05 Revisions) Page C-7 rlITY OF 1A QUINTA BUILDING & SAFETY DEPT- APpkOVED FOR CONSTRUCTION i Embassy Suites (La Quinta, CA) GBA P.N. LP040026 Atrium Smoke Control System August 30, 2004 (21"5 Revisions) Design Report Page G8 BUik DING & SAFETY D4' T. APPROVED FOR COWSTRUCTICI� DA7E1`��8Y d Wlndow lame: To determine if a window plume is an applicable scenario far this project fire modeling was done to determine If a window would break when exposed to a fire in a guest room_ Using the computer model CFAST Version 3.1.7, a one -compartment model representing the front room of a typical gust suite.was entered. A fine was placed in comer of the 13 ft. by 15 ft. room and a quick response, ordinary temperature sprinkler was placed at the midpoint of the wall away from the fire (sidewali sprinklers are proposed in guest rooms). The fine was assumed to be a moderate t-squared fire that stops growing and remains steady at sprinkler activation, which the model predicted at approximately 105 seconds or a fire size of 134 BTU/s. The ceiling height used was 8 ft. 6 inches. The input file for the model follows with a printout of the spreadsheet output from the, model. The upper layer temperature form the fire was recorded and compared to the standard time -temperature curve used for testing of windows. The model predicts that the temperature the window would be exposed to Is well below the exposure required to pass the testing required to obtain a fire rating. Therefore, it is assumed that the window will not break and a window plume does not need to be used in the smoke control design on this project. Embassy Suites (La Quinta, CA) GBA P.N. LF040026 Atrium Smoke Control System August 30, 2004 (2-15-05 Revisions) Design Report Page C-9 40 r� m 0 =� U. a l ~ f 3 0 _c ( o c w z a I 0 a m N S 8 m � N O T T T T ftp) WnPUBMJL 1 l l l S IOf) O � oO p O O O O C9 O N N OLo (emus) ems a!d 0 v T 0 co 0 co c� EiYOFLAQUIN'� FUII_'JA€ G & SA:-IEW DEPT. via ROVED ' f- UN EMB-WIN.DAT F R CNZDTR.J�-jT[ VERSN 3EMBASSY WINDOW PLUME MODEL #VERSN 3 EMBASSY WINDOW PLUME MODEL I z o BY TIMES 1200 0 10 20 0 OHTC ADUMP EMB-WIN.CSV N TAMB 293.150 101300.0.000000 EAMB 293.150 101300.0.000000 HVF 0.000000 WIDTH 3.9W40 DEPTH 4.57200 HEIGH 2.59080 CEILI GYPSUM WALLS GYPSUM FLOOR PLYWOOD #CEILI GYPSUM #WALLS GYPSUM #FLOOR PLYWOOD HVENT 1 2 1 3.66000 0.0108540 0.0100000 0.000000 0.000000 0.000000 CVENT 1 2 1 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00M 1.00000 1.00000 - HVENT 1 2 2 3.66000 2.43000 2.42915 0.000000 0.000000 0.000000 CVENT 1 2 2 1.00000 1.00000- 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 1.00000 HVENT 1 2 3 0.910000 2.13000 0.000000 0.000000 0.0000o0 0.000000 CVENT 1 23 1.00000 1.00000 1.00000 1.00000 1.00000 - 1.00000 1.00000 1.00000, 1.00000 1.00000 1.00000 1.00000 11.00000 1.00000 1.00000 1..00000 1.00000 1.00000 1.00000 1.00000 - CHEMI 16.0000 50.0000 10.00001.95000E+007, 293.150 493.150 0.300000 LFBO 1 _ LFBT 2 CJET ALL EPOS 0.304800 3.65760 0.000000 FTIME 12.0000 24.0000 36.0000 48.0000 60.0000 72.0000 84.0000 96.0000 110.000 1200.00 1212.00 1224.00 1236.00 1248.00 1260.00 1279.00 1284.00 1296.00 1310.00 FMASS 0.000000 8.65476E-005 0.000346191 0.000778929 0.00138476 0.00216369 0.003,1572 0.00424083 0.00553906 0.00727239 0.00727239 0.00577224 0.00444518 0.00329122 0.00231035 0.00150256 0.000867884 0.000406293 0.000117801 0.000000 FODOT 0.000000 1687.68 6750.73 15189.1 27002.9 42192.0 60756.5 � 82696.2 108012. 141812. 141812. 112559. 86681.1 64178.7 45051.7 29300.0 16923.7 792-2.72 2297.12 0.000000 HCR 0.0800000 0.0800000 0.0800000 0.0800000 0.0800000 0.0800000 0.0800000 0.0800000 0.0800000 0.0800000 0.0800000 0.0800000 0.0800000 0.0800000 0,0800000 0.0800000 0.0800000 0.0800000 0.0800000 0.0800000 ❑D 0.0300000 0.0300000 0.0300000 0.0300000 - 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0-0300000 0.0300000 0.0300000 0.0300000 0.0300000 CO 0.0300000 0-0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 0.0300000 ]DETECT 5 1 330.370 2.28600 0.152400 2.51460 50.0000 0 7.00001E-005 SELECT 1 2 3 *GRAPHICS ON DEVICE 1 WINDOW 0. 0.-100.1280.1024.1100. Page 1 LABEL 1 970. 960. GRAPH 1 100. 50. GRAPH 2 100. 550. GRAPH 3 720. 50. GRAPH 4 720. 550. HEAT 00003 1 U TEMPE 00002 1 U INTER 00001 1 U 02 00004 1 U 0 EMB-WIN.DAT 0. 1231. 1005. 10.15 00:00:00 0.00 0.00 0. 600. 475. 10.3 TIME HEIGHT 0. 600. 940. 10.3 TIME CELSIUS 0.1250. 475. 10. 3 TIME FIRE SVE(kW) 0.1250. 940. 10.3 TIME OID210() Page 2 IA CITY OF LA QUIN j B'ILOINIG & S�� DEPT. APp FOR CONSTRUCTION I ART BY Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza APPENDIX C October 20, 2006 Page 20 CITY OF LA QUANTA BUILDING & SAFETY DEPT. APPROVED AIR FLOW AND LEAKAGE TESTING AT KITCHEN SMOKE BARRIER HUGHES ASSOCIATES, INC. V--j HUGHES ASSOCIATES, INC. ENGINEERING CALCULATIONS TITLE DATE SHEET NO. ayv, Z -*c S s a.-,jTia% dit Z-7 a r DESCRIPTION _ CALL, BY J _ 9 K} LLD w +� QLI'E S r►�D tick tS,�� � � L..�f �s_� ��. & `A ETY DEPT. ❑I;TI _ FY -----�►.25� �l��o.v2 S mOlr�y�, - 13 ��,e. t dye - �;.�1�4-C.L, +Pr►2K. p� ti3AV-a-Vt- l Ve- -- 1 ❑ , L 4i l 41 t ri 6WVf- Vg AWE re ► lCr2 4F Z�l o-��cY4.� loo-- P<T ►aol-TvrA . (\\ 2-)C-71 o) ► IN 1q, Z +�/ ,_ S [�3 Pw-r- ooave. cz) (I?:,. 2,cj -- (�r�.w�Ic►��. r4� � � v4 `1U S r���� 13 rt✓LvL � 1�02 w� W2;�K� Aug 24 06 09:03a Srp ConstrucLn 760 777-9538 p.2 Associated. Air Balane, 4:57 E. Arrow HWY, Ste F, Azusa, CA Air Sound HydrGnic Professionals Tel: 626-915-8117 Fax. 626-915-8112 AIR DISTRIBUTION Inc. 91702 CITY OF LA BUILDING & SAFETY DE.--. A P P R 0 WEI'. [ATE BY C. t-,:. cn4 NOTES: Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza APPENDIX D October 20, 2006 Page 21 CITYOF LA QUIN A BUILDING & SAFETY DEPT. APPROVED NATIONAL WEATHER SERVICE WEATHER DATA AUGUST, 2006 HUGHES ASSOCIATES, INC. T fD Form Page 1 or 1 QUALITY CONTROLLED LOCAL CLIMATOLOGICAL DATA krinal) NOAA, National Climatic Data Center &nth: 08/2006 Pemperature 'FahrenheitBase DegDays 65 egred v 'Weieating vgtifax -Min vg.m rF,-P Pt ling nal t 100 76 88 -4 59 69 0 23 101 75 88 -3 59 70 0 23 101 74 88 -3 61 71 0 23 102 75 89 -2 56 68 0 24 103 66 85 -6 50 65 0 20 107 74 91 0 54 68 0 26 109 73 91 0 43 65 0 26 105 67 86 -5 59 70 0 21 107 74 91 0 63 73 0 26 105 81 93 2 66 75 0 28 107 83 95• 4 55 71 0 30 106 71 89 -2 50 67 0 24 104 70 87 -4 55 68 0 22 107 74 91 1 51 67 0 26 104 71 88 -2 56 68 0 23 104 71 88 -2 47 65 0 23 103 63 83 -7 44 63 0 18 108 71 90 0 44 65 0 25 110 78 94 4 46 66 0 29 109 77 93 3 48 66 0 28 110 69 90 0 54 68 0 25 104 79 92 2 71 77 0 27 106 80 93 4 67 76 0 28 1 108 77 93 4 52 69 0 28 106 71 89 0 54 68 0 24 106 60* 83' -6 35 60 0 18 111 69 90 1 44 64 0 25 113• 66 90 1 43 64 0 25 103 65 84 -5 66 73 0 19 104 75 90 2 69 75 0 25 104 76 90 2 65 73 0 25 24-4 �- -cc Days Monthly Season to Date Total Departure Total Departure Heating: 0 0 M M Cooling: 757 -20 Significant Weather 3Z liz Greatest 24-hr Precipitation: M Date: M Greatest 24-hr Snowfall: M Date: M Greatest Snow Depth: M Date: M EXTREME FOR THE MONTH - LAST OCCURRENCE IF MORE THAN ONE. Station Location: DESERT RESORTS RGNL ARPT (03104) PALM SPRINGS, CA Lat. 33.628 Lon.-116.160 Elevation(Ground): -122 ft. below sea level S--W'ICe on Groum 1 "ecipitation In Pressure(inches of H Nmd Speed�ph � ofdegrees D 1200 1200 2400 2400 max max a UTC LST LST LST Avg. Station Avg. Sea Level Resultant Speedd Res Avg. 5-second I 2-rairiine t e De th Water Snow Water Speed Dir Speed Dir F 'v Fall iv M M M 0.00 29.85 29.74 6.6 32 10.1 28 320 21 320 1 M M M 0.00 29.91 29.79 3.0 34 9.9 25 340 21 330 2 M M M 0.00 29.85 29.74 1.0 06 6.8 18 320 15 330 3 M M M 0.00 29.89 29.78 4.0 33 9.6 23 330 18 330 4 M M M 0.00 29.91 29.80 1.2 36 6.2 17 120 15 310 5 M M M 0.00 29.85 29.74 3.8 33 9.1 23 330 18 320 6 M M M 0.00 29.88 29.77 3.0 33 7.3 18 330 15 340 7 M M M 0.00 29.93 29.82 0.4 17 4.7 17 140 14 150 8 M M M 0.00 29.91 29.78 4.2 12 6.6 21 140 15 130 9 M M M 0.00 29.88 29.76 1.8 14 6.7 17 320 14 310 10 M M M 0.00 29.82 29.71 3.4 33 8.5 26 330 21 340 11 M M M 0.00 29.78 29.67 3.7 32 6.7 22 310 18 310 12 M M M 0.00 29.82 29.71 L4 02 6.6 22 320 18 340 13 M M M 0.00 29.88 29.76 3.1 34 6.7 20 330 15 330 14 M M M 0.00 29-88 29.76 4-6 33 7.0 24 340 21 320 15 M M M 0.00 29.90 29.78 5.1 32 7.3 24 320 18 330 16 M M M 0.00 29.95 29.83 2.1 35 5.9 16 320 15 330 17 M M M 0.00 29.91 29.80 6.0 32 8.1 20 320 17 320 18 M M M 0.00 29.85 29.74 6-6 33 10.5 25 320 20 310 19 M M M 0.00 29.85 29.74 2.0 33 7.8 18 320 15 320 20 M' M M 0.00 29.86 29.75 1.7 08 6.1 16 140 14 130 21 M M M 0.00 29.96 29.84 3.2 15 6.8 23 110 17 120 22 M M M 0.00 29-92 29.81 1.2 14 4.7 15 330 13 340 23 M M M 0.00 29.80 29.69 0.9 07 7.0 22 340 18 340 24 M M M 0.00 29.80 29.68 2.6 31 6.9 28 280 22 290 25 M M M 0.00 29.82 29.71 2-9 32 6.3 26 340 22 330 26 M M M 0.00 29.85 29.73 1.3 33 5.7 16 320 13 320 27 M M M 0.00 29.81 29.69 0-7 06 6.3 17 120 13 130 28 M M M 0.00 29.82 29.71 1.9 18 4.9 17 150 14 160 29 M M M 0.00 29.80 29.69 2.4 16 •4.6 17 130 15 140 30 M M M 0.00 29-82 29.71 0-5 12 5-0 16 130 13 l20 31 ntal. M M M 1 1-6 1331 7,0 onthiyAvrrage Number of Days with 1 Sea Level Pressure Date Time Maximum M M M Minimum M M M Temp>=90: M r4eavy Temp -32: M Temp <=32: Tempr-0 :M iderstorms :0 Fog :0 8(QAFETY DEFT. FROVE L) pitation >=.01 M pitation -.10 M fall>=1.0 :M 1fi1e:HC:\Documents and SetdngsMke Madden\Desktop\Aug LCD Form.htm 9/27/2006 Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza APPENDIX E October 20, 2006 Page 22 CITY OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED DATE ! D BY --j PORTIONS OF AIR BALANCE REPORT PERTAINING TO SMOKE EXHAUST SYSTEM COMPONENTS HUGHES ASSOCIATES, INC. Associated Asir ]balance Inc. J 457 E. Arrow 13wy, Ste F, Await, CA 91702 AIR SOUND HYDRONIC 1 ROF MIONAT.3......` TES,: 626-915-8117 '5 OF LA Q U I NTA FAX: 626-9154112 ',., .__ � ,,A2 Yt SAFETY DEPT. FAN SHEET F-7 y PROJECT: Embtmy Suites -La Qu iuta PAGE: 1 1 FAN NAME RTU - 25A� RTU' - 25H SF -1 1 5ER1iICE SF - 2 Atriiun Atxi�um S�mvke Evac Atrnrm Smoke Ewc Atrium: - LOC�,TION Awn Roof Raaf MANUFAG'TURER Traft 1Loof Aron Cock Coa1� MODEL RNi025 kCM-U25 365 - CPS SF,RIAL #' Ta 365 - CPS 2004ft-AMG M93 30040&- GR- Ck�V1 DESIGN. .CT-tTA}. DESIGN DESIGN ACTkJA11 DE51GN .ACTUAL TaTAL FAN TOTAL o4503 NT-VL 4500 WVL- 228 .22,940 : .Z004 4620 4�55 22,705- -- RE -AIR . ;'2270 0 0 a _ 0 4U7SII]E 0 450o 46.,0- - (• - 0c: _- _ - 0 - a - 0 �" DISCHARGE wx. 0.38" f136" SUCTION' n gg /�■+i}.63" -: //77 rr 1.0" - - 0.77" 4.0" 0 7S " FILTERIC=UIL 0.50 0.�53 { 0:50- MOTOR- M�[UFACTCTI�R HORSEPOWER A. Q. Srrti 3 A. O.StniTla Reliae Eloc#c Rc1i .,.- :.-- VOLTAGE 3 ance:ElecWc, 'W 490 460 47o z° 10 POSE 3 � �490 460 - 490 AMPERAGE 3 3 3 3 4-7 3.G%3.713-7 4.7 3.6l3.SJ3.9 3 3 3 RPM/SPF.Ep 1725 1725 13 8.718.68.9 13 SERVICE FAGTOR 1725 1725 1755 1755 8.618.8/9 1.15 1755 1755 MTR REAVE S12T- % CLOSE VP62 I� 71$ VP62 X 718" 3AK60 X 1 5I8" FAN SIIEAVE S 300/9 306/ 3AK60 X 1518 FAN RPM 13KI O X 13116" DK1 O X 13/16" Firm F1xed DNL 3' 3 X 3.6 X 2 3I16" . 3TS I 3.6 X 2 3I16" ���.T SI2E 1 # pF 945 DNS. 9S3 �� 7Q� NaT�S; DX70 - 2 HX74 - 2 7S3 g�93 i PROJECT: FAN NAME SERVICE LOCATION MANUFACTURER MODEL # CFI!',# TOT FAN TOTAL OUFT-ETS STAT PRES DI5CHAROE SUCTION TOTAL S.P. - Associated Air Balance Inc. 457 E. Arrow Hwy, Ste F, Azmx, CA 91702 AIR SOUND HYDRONIC PROFESSIONALS T)EL: 626-915-8117 FAX: 626-915-8112 5 yr��4 1' 3. I3 ,d c p1 �_ � L • A_..�Y' . ..`Zq�...Y i`1_ e � .. APPR VI -D EXHAUST FAN SHEET Embassy Suites - La Quints f1 �t DESIGN ACTUAL UMSIGN A:: Y p 22,5765 1+FVI. ��_St7f1 z r� . f NVJ- 0.47" 3" 0 47' 0.53" EF-9C Atriums Roof Cook 300CAS 22 5�t0 I I� 2?,5 J3 . 23,281 MANi3FACTURER Reliance Electric fiance Ei+�ctiic Reliance H01tS94�R EP0 15 VOLTAGE 460 ¢93 4 U 4 1S 460 PHASE 3 3 3 3 AMPERAGE RP MJSPEED 18.5 I$.4I163n5_ 18.5 t5.7/iS3/1S 1$.5 x� SERVICE FACTOR 1760 1764 1750 1760 1 1760 1.15 1.15 _�.i DRI VIE MIME r MZR SHEAVE SIZE 2TB66 X 1 51&,, 2 TB66 X 1 818" % CLOSED FAN SHEAVE SIZE Fixed FAN RPM 2TS94 X 2- 2TS94 X 22 5116" BELT SIZE 1 # OF ]DNL i212 DNL 1203 Vn't-ca. BX62 - 2 BX62 - 7. NNE (�. J()1x f1.50" 15 ass 3 F116.9/I I760 1.15 2TB66 X 1518" Fixed 2TB94 X 2 5I16" bR- 1220 BX62 - 2 BY PAGE: 2 EF - 9D Atrium Roof Cook 300CAS DE SIGN ACTUAL 22,50U' NVL 22,5 r_ 23,135-- N��VQQL 0.48" -. 0-3" Reliance Electric 1$ 460 490 3 3 I 8.5 1760 - - - 1760 1.15 TIB66 X 1 519" Fixed 2T,B94 X 2 5115" gam- 1215 BX62 - 2 7 PROJECT: Associated Air Balance., Inc 457 F_ Airrow Hwy, Ste F. Azusa, CA 91702 AIR SOUND HYDRONIC PROFESSIONALS TE , 626-915- 117 FAX: 626-915-8112 N F. L EXHAUST FAN SHEET Embassy Suite* -La Oukta Y '5 BULLMN.��GA 67- PAGR: 3 FAN NAME EF - 9E EF-9F EF-9G EF - 9H SERVICE Atrium Atrium Atdum Alrium LOCAT70N Roof Roof Roof Roof MANUFACTURER Cook Cook i Cook Cook MODEL# 300CAS 300CAS 300CAS 300CAS Cm DESIGN ACTUAL ]DESIGN C D=-, 107Nl AC 7-LIALT SZGIq, jjc-,ujj,. TOTAL FAN 22,SUfl NVL 22,500 NNIL 22,500 NAIL_ TOTAL OUTLETS 22,500 23,570 22,500. 2: 23,375 21,5ry 23,17.5 STAY PRES DISCHARGE SUCTION TOTAL S.P. 0�53" 03" 0-49" 03" 0.46" 2 1 "En L MOTOR FAN . . . . . MANUR&CTWER_ HORSEF()WER Reliance FleaWc Reliance Eli;�m�c Reliance EleeWc-1 —Reliance-Electric VOL 15 460 490 —3 15 15 490 15 460 PHASE 3 —3 3 490 AMPERAFJE— M5 3 3 pIpm/sp 1760 1760 17i 60 1760 1 IS * 6 SERVICE-FAr-Tok 1.15 1760 56-0 1760 1760 1-15 1.15 1.15 JD ME �ATR VE Sim 46 CLOSED .1 '1[1;111�1111116 X 519,1111111 ............... ZTFB66 1518- 2TB66 X 1 5/8to - AN SMAVf _S_1rZE Fixed 2TB94 X 2 5/16" Fixed Fixed Fixed 'AN RFM DNL I i'2'33 — 27B94 X 2 5/1 K_ 2TB 91-4X23/16" 1ELT # OF BX62 - 2 DNL 1221 I'll ] 2=2 3 Z07ES: _­ DX62 - Z— BX62 - 2 I Associated Air Balance Inc. 457 E. Arrow Hwy, Ste F, Azusa, CA 91TTTF� ,gg �/�, //-��,<<I jk�Air Sound Hydronic Professionals 0 Y- LA �Q U y � !% ; TEL:626-915-8117 1 BUILDING & SAFE i Y DEPT. FAX: 626-915-81.12 AIR DISTRIBUTION PROJECT: Embassy Suites - LR Quint& APPROVED I OM rt+F-_W*.m PAGE: 4 jtv p me— Mwjmm�� Associated Air Balance, Inc. 457 E. Arrow Hwy, Ste F, Azusa, CA 917.02 l Air Sound Hydronic PnDfesskpWa N. Uo LM TA TEL: 626-915-8117 Bijki- S'IVEEIFY DEPT. FAX: 626-9154112 V ED AIR DISTRMUTION UfJEz 1017-41do BY PROJECT: Embassy suifts Lm Quinta PAGE: 5 ZONE NAI\,E TERMNAL EFFECT DESIGN ACTUAL NUMBER TYPE - SIZE AREA FPM CFM FPM CFM Nons EF-9A Attium 1 SWE 42X24 6.3 1785 1 11,250 1968 11,769 Atrium 2 SWE 42X24 --6-3 1795— 11,250 1868 11,456 JL2,50JO 3,225 EF-9B Atrium 1 SWE-742 X-24 —6.3 1785 11,250 1883 11,865 Atrium 6-3 1785— —2 2— X24 1830 11,535 (23,400) E-F-qC Atrium 1 SWE--iYX 2-4 63 1785 11,250 —1881 11915 AUiUM 2 SWE —4 2--X- 2-4 6-3 11,250 1-804 11,365 2 L5-0-0-)- 2 �80) Atrium 1EF-9D .. ...... . . . SWE 42X24 6-3 --- Atri 11785 Lii,25o 1789 11,275. SWE 42 X 24 —6-3 1 178.5 11,250 _1882 1 I,g&o 22,500 23,135 EF-9E Atrium 1SWE 42X24 6.3 1785 Atrium L,250 1851 — —SWE L 42X24 6.3 1785 1 _��50 1989 11,11,665 __905 J22, 5 �OO 223,570 NOTES: ---------- Associated Air Balance, Inc, 457 E. Arrow Hwy, Ste F, Azusa, CA 917 E 1 1 r � Air Sound "tunic Professionals T• Y OF i.._ A Q U I N A TEL:626-9154117 BUILDING' &_SAFElYDEPT. FAX:62"1.54112 i APPROVED PROJECT: Embassy Suites - La Quiatx PAGE: 6 Atrium Smoke Exhaust System Testing October 20, 2006 Embassy Suites Santa Rosa Plaza Page 23 CITY OF LA QUANTA BUILDING & SAFETY DEPT. APPROVED APPENDIX F RTU-25A AND RTU-25B AIRFLOW MEASUREMENTS IN SMOKE EXHAUST MODE BY HUGHES ASSOCIATES, INC. Aug 01 06 08:03a Srp Constructn 760 777-9538 p.2 Associated Air Balance Inc. 457 [ . Arrow Hwy, Ste F AYu5n,CA 917 rB � LA Air acund Hydronic Proressionak L OF QNpATcl: 626-915-8117 1SAFETY I�;ix: 626-915-8112 P P R VED -i t ! AIR DISTRU .IJ110N4;7 � BY PROJECT: PAC..l:: 4 7.ON I 1 NAMF, T1-RMINAL -- NUMlilDl FY-vi � LSD tfF k� tS Ltyk � � y 3p 1! i f'rs Atrium Smoke Exhaust System Testing Embassy Suites Santa Rosa Plaza October 20, 2006 Page 24 CITE'( OF LA QUINTA BUILDING & SAFETY DEPT. APPROVED APPENDIX G JDATF ° MAKE-UP AIR SYSTEM AIR FLOW MEASUREMENTS IN SMOKE EXHAUST MODE BY HUGHES ASSOCIATES, INC. Aug 24 06 09:04a Srp Constructn 760 777-9538 p.4 Associated Aix' Balance Inc. 457 E. Arrow Hwy, Ste F, Azusa, CA 91.701 �—._.�------ - Air Sound Hydronic Professionals --'V QUNTA <= r Tel: 626-915-8117 i E3U«_DI,�IG & SAFETY DEPT. ' 3 Fax: 626-915-8112 APPROVED •' n AIR DISTRIBUTION DATE-7 R1� J-69�:j PAGE: PROJECT: • ZONE TERMINAL EFFECT DESIGN AC AL NAME NUMBER TYPE SIZE AREA FPM CFM FP%-i CFM NOTES .w t i'l r • r-1 • ]C 3 (6 2 �S. gum rqu i tlx: � Si 340 ' _ ^ '- C. Aug 24 06 09:04a Srp Consbuctn 760 777-9538 P.3 Associated Air Balance Inc. h.4:V •, 457 E. Arirow Hwy, Ste F, Azusa, CA 9170 Ci� OF -� QU4�A Air Sound Hydronic Professionals Tel: 626-915-8117 BUILDING & SAFETY DEPT. Fax: 626-915-8112 APPROVED j�juVCp? 5�i{� ?av1r . AIR DISTRIBUTION DATE 1 BY PROJECI_ ZONE TERMINAL EFFECT D£S1GN ACTUAL NAME NUMBER TYPE SIZE AREA FPM CFM FPM CFM NOTES ; o . c: y`r -, j D IV L 3 5G to c7 i : vI •c s h rill Law(. !a 1 ' • - 2 ss l 7� 1-1( 9 NOTES: