BSOL2017-0027 - Permit ExpiredDescription: HICKS / 5.6kW PV SYSTEM - (16) 350W PANELS+MICROINV/125A SUB
Type: SOLAR Subtype: RESIDENTIAL LESS THAN Status: EXPIRED
Applied: 12/15/2017 AMA
10KW
Approved:
Parcel No: 777390002 Site Address: 80957 VIA PESSARO LA QUINTA,CA 92253
Subdivision: TR 29894-3 Block: Lot: 40
Issued:
Lot Sq Ft: 0 Building Sq Ft: 0 Zoning:
Finaled:
Valuation: $17,482.00 Occupancy Type: Construction Type:
Expired: 6/15/2018 AOR
No. Buildings: 0 No. Stories: 0 No. Unites: 0
Details: 5.6kW SOLAR ARRAY - (16) 350W LG PAN ELS+ENPHASE IQ6 PLUS MICROINVERTERS W/(1) 125 AMP SUBPANEL [288SF] TILT OF
4.8/12 (22 DEGREES) WITH AZIMUTH OF 180 DEGREES REQUIRED FOR PERFORMANCE ENERGY CALCULATION COMPLIANCE. 2016
CALIFORNIA ELECTRICAL CODE.
ADDITIONAL
CHRONOLOGY
CHRONOLOGY TYPE
STAFF NAME
ACTION DATE
COMPLETION DATE
NOTES
RESUBMITTAL
AARON HICKSON
1/9/2018
1/9/2018
STEVE PYLE DROPPED OFFF REVISIONS
PHONED APPLICANT RON RUFF (760-578-4006) THAT PLANS
TELEPHONE CALL
AJ ORTEGA
12/27/2017
12/27/2017
ARE READY FOR CORRECTIONS.
PHONED APPLICANT RON RUFF (760-578-4006) THAT PLANS
TELEPHONE CALL
AJ ORTEGA
1/22/2018
1/22/2018
ARE APPROVED.
CONDITIONS
CONTACTS
NAME TYPE
NAME
ADDRESSI
CITY STATE
ZIP PHONE FAX EMAIL
APPLICANT
RON RUFF 49950 JEFFERSON ST
INDIO CA
92201 RRFFCO@DC.RR.COM
#130-134
CONTRACTOR MONARCH HOMES DESERT DIVISION 49-950 JEFFERSON ST
INDIO CA
92201
INC DBA DA
#130-134
Printed: Thursday, July 07, 2022 10:07:29 AM 1 of 3
RWSYS7EMS
FINANCIAL INFORMATION
CLTD
DESCRIPTION ACCOUNT QTY AMOUNT PAID
PAID DATE RECEIPT # CHECK # METHOD PAID BY
BY
BSAS SB1473 FEE 101-0000-20306 0 $1.00 $0.00
Total Paid for BUILDING STANDARDS ADMINISTRATION
$1.00 $0.00
BSA:
PV SYSTEM LESS THAN
101-0000-42403
0
$26.01
$0.00
10KW
PV SYSTEM LESS THAN
101-0000-42600
0
$26.01
$0.00
10KW PC
PV SYSTEM MISC
101-0000-42403
0
$26.01
$0.00
EQUIPMENT
PV SYSTEM MISC
101-0000-42600
0
$26.01
$0.00
EQUIPMENT PC
Total Paid for ELECTRICAL: $104.04 $0.00
PERMIT ISSUANCE
101-0000-42404
1 0
$98.83
$0.00
Total Paid for PERMIT ISSUANCE: $98.83 $0.00
RECORDS
101-0000-42416
0
$10.00
$0.00
MANAGEMENT FEE
Total Paid for RECORDS MANAGEMENT FEE: $10.00 $0.00
TECHNOLOGY
502-0000-43611
0
$5.00
$0.00
ENHANCEMENT FEE
Total Paid for TECHNOLOGY ENHANCEMENT FEE: $5.00 $0.00
TOTALS:00
Printed: Thursday, July 07, 2022 10:07:29 AM 2 of 3
RWSYS7EMS
REVIEW TYPE REVIEWER SENT DATE DUE DATE RETURNED STATUS REMARKS NOTES
DATE
1ST BLDG NS (1 WK) AJ ORTEGA 12/15/2017 12/22/2017 12/27/2017 REVISIONS REQUIRED SEE 1ST REVIEW CORRECTION LIST ATTACHED
2ND BLDG NS (1 AJ ORTEGA 1/9/2018 1/16/2018 1/22/2018 APPROVED
WK)
Attachment Type
CREATED
OWNER DESCRIPTION
PATHNAME
SUBDIR
ETRAKIT ENABLED
DOC
1/9/2018
AARON HICKSON 80957 VIA PESSARO
80957 VIA PESSARO
0
RESPONSES.pdf
RESPONSES.pdf
BSOL2017-0027 - 1ST
DOC
12/27/2017
1ST REVIEW SOLAR
AJ ORTEGA
REVIEW SOLAR
1
CORRECTIONS
CORRECTIONS.pdf
Printed: Thursday, July 07, 2022 10:07:29 AM 3 of 3
RWSYS7EMS
DESIGN & DEVELOPMENT D EPARTMENT
78 -495 C ALLE T AMPICO
L A Q UINTA , C ALIFORNIA 92253
(760) 777 -7 125 FAX (760) 777 -7011
Residential Plan Check Correction List (SOLAR) Page 1 of 2
RESIDENTIAL PLAN CHECK CORRECTION LIST (SOLAR)
DATE: DECEMBER 27, 2017
STATUS: FIRST REVIEW
PLAN CHECKED BY: AJ ORTEGA
TELEPHONE NUMBER: (760) 777-7018
ADDRESS: 80-957 VIA PESSARO
DESCRIPTION: PV SOLAR SYSTEM
APPLICANT: PLANET SOLAR
PLAN CHECK #: BSOL2017-0027
This submittal has been checked for compliance with the 2016 California Building Codes
and the City of La Quinta Municipal Code.
APPLICANT: BUILDING DEPARTMENT STAFF:
The following items are being returned to you
for correction:
3- SOLAR UNMARKED PLANS
2- STRUCTURAL CALCULATIONS
1- CORRECTION LIST
DO NOT accept any resubmittal unless ALL of
the following items are included:
1- 1ST REVIEW SOLAR PLAN
1- CORRECTION LIST w/responses
2- REVISED PLAN SETS
1- ASSESSORS SITE/FLOOR PLAN
INSTRUCTIONS TO APPLICANT:
1) Provide a written response to each comment on the following pages, noting specifically where the
correction can be found. Responses such as, “Sheet A-3,” or, “Handrails shall be per CBC Section 1003,” are
not acceptable. Show or note specifically how compliance with a code requirement is achieved.
Responses such as, “Added note 16 on sheet A-3” are appropriate and will help expedite your back check.
2) Corrections may not be made by handwriting on existing drawings. Revise originals and reprint Plans and/or
Calculations as necessary.
3) Return all red-marked Plans and/or Calculations with your resubmittal.
4) Each sheet of resubmitted Plans and/or Calculations shall include the preparer’s name and telephone
number and shall be wet-signed by the preparer. If the preparer is a licensed architect or engineer, all
documents prepared by that licensed individual shall also bear his/her stamp as prescribed by California
Business and Professions Code Section 5536. Resubmittals will not be accepted with signatures missing.
5) Return this list, your written responses, and all documents listed above with your resubmittal.
Residential Plan Check Correction List (SOLAR) Page 2 of 2
SECTION A - GENERAL
1) Provide the DC kW rating of the proposed system on the first sheet of Plans.
2) Provide on each sheet of resubmitted Plans and cover sheet of bound Calculations the preparer’s name and
telephone number and wet-signature. If the preparer is a licensed architect or engineer, all documents
prepared by that licensed individual shall also bear his/her stamp as prescribed by California Business and
Professions Code '5536. Resubmittals will not be accepted with signatures missing.
SECTION B – SOLAR
1) The proposed photovoltaic system does not comply with the requirements of the system to be installed per
the dwellings energy compliance report. Adjust the arrays angle to 22° (4.8 x 12 Roof Slope), revise
structural calculations to justify the proposed installation, and diagram array spacing so that shading
will not occur from panel row to panel row.
2) Photovoltaic system circuits installed on or in buildings shall include a rapid shutdown function that
controls specific conductors in accordance with 690.12 (1) through (5). The proposed system does not
require Rapid Shutdown, remove installation signage as to not conflict with systems that do.
3) The Combined Direct-Current Grounding Electrode Conductor and Alternating-Current Equipment
Grounding Conductor shall be an unspliced, or irreversibly spliced, combined grounding conductor run from
the marked dc grounding electrode conductor connection point along with the ac circuit conductors to the
grounding busbar in the associated ac equipment. This combined grounding conductor shall be the larger of
the sizes specified by 250.122 or 250.166 and shall be installed in accordance with 250.64(E). For
ungrounded systems, this conductor shall be sized in accordance with 250.122 and shall not be required to
be larger than the largest ungrounded phase conductor. Add note for compliance with underlined items.
4) Provide schedule with the location of all required markings and labels for the proposed photovoltaic system.
(CEC §690) AC system attributes needed at AC Disconnect and Dual Power Sources signage, please
update signage sheet.
SECTION C - MISCELLANEOUS COMMENTS
1) Red marks on Plans, even if not specifically mentioned in this list, indicate items needing correction. Revise
Plans as necessary and provide written response, noting where correction can be found.
2) Provide one copy each of the Site Plan and Floor Plan for the County Assessor’s office. While not required for
resubmittal, this administrative item must be addressed prior to issuance of building permit.
END CORRECTION LIST
As further information is provided and reviewed, additional corrections may be required.
Taf
"
DESIGN & DEVELOPMENT DEPARTMENT
78-495 CALLE TAMPICO
LA QUINTA, CALIFORNIA 92253
(760) 777-7125 FAX (760) 777-7011
RESIDENTIAL PLAN CHECK CORRECTION LIST (SOLAR)
DATE: DECEMBER 27, 2017
STATUS: FIRST REVIEW
PLAN CHECKED BY: AJ ORTEGA
TELEPHONE NUMBER: (760) 777-7018
ADDRESS: 80-957 VIA PESSARO
DESCRIPTION: PV SOLAR SYSTEM
APPLICANT: PLANET SOLAR
PLAN CHECK #: BSOL2017-0027
This submittal has been checked for compliance with the 2016 California Building Codes
and the City of La Quinta Municipal Code.
APPLICANT:
The following items are being returned to you
for correction:
3- SOLAR UNMARKED PLANS
2- STRUCTURAL CALCULATIONS
1- CORRECTION LIST
BUILDING DEPARTMENT STAFF:
DO NOT accept any resubmittal unless ALL of
the following items are included:
1-1ST REVIEW SOLAR PLAN I
--1- CORRECTION LIST w/responses
2- REVISED PLAN SETS
1- ASSESSORS SITE/FLOOR PLAN
INSTRUCTIONS TO APPLICANT:
1) Provide a written response to each comment on the following pages, noting specifically where the
correction can be found. Responses such as, "Sheet A-3," or, "Handrails shall be per CBC Section 1003," are
not acceptable. Show or note specifically how compliance with a code requirement is achieved.
Responses such as, "Added note 16 on sheet A-3" are appropriate and will help expedite your back check.
2) Corrections may not be made by handwriting on existing drawings. Revise originals and reprint Plans and/or
Calculations as necessary.
3) Return all red -marked Plans and/or Calculations with your resubmittal.
4) Each sheet of resubmitted Plans and/or Calculations shall include the preparer's name and telephone
number and shall be wet -signed by the preparer. If the preparer is a licensed architect or engineer, all
documents prepared by that licensed individual shall also bear his/her stamp as prescribed by California
Business and Professions Code Section 5536. Resubmittals will not be accepted with signatures missing.
5) Return this list, your written responses, and all documents listed above with your resubmittal.
Residential Plan Check Correction List (SOLAR) Page 1 of 2
SECTION A - GENERAL
-1) Provide the DC kW rating of the proposed system on the first sheet of Plans.
2) Provide on each sheet of resubmitted Plans and cover sheet of bound Calculations the preparer's name and
telephone number and wet -signature. If the preparer is a licensed architect or engineer, all documents
prepared by that licensed individual shall also bear his/her stamp as prescribed by California Business and
Professions Code '5536. Resubmittals will not be accepted with signatures missing.
SECTION B — SOLAR
1) The proposed photovoltaic system does not comply with the requirements of the system to be installed per
the dwellings energy compliance report. Adjust the arrays angle to.2.2 (4.8 x 12 Roof Slope), revise
structural calculation to justify the proposed installation, and diagram array spacing so that shading
w not occur from panel row to panel row.
ENERGY DESIGN RATING PV SYSTEM INPUTS - DETAILED
DC System Slxe (kWdc) Medd$0 Typo
4.6
CFI I Axlmuth (dog) I TIII Utipul I Array Aagle (deg)
f
nH' Inverter EH. (% )
(x In 12)
4.9 98
2) Photovoltaic system circuits installed on or in buildings shall include a rapid shutdown function that
controls specific conductors in accordance with 690.12 (1) through (5). The pro used s stgMAaaiAot
require.Raplj,d S,hutd,Qwn, remove installation signage as to not conflii w t systems that do.
3) The Combined Direct -Current Grounding Electrode Conductor and Alternating -Current Equipment
Grounding Conductor shall be an unspliced, or irreversibly spliced, combined grounding conductor run from
the marked do grounding electrode conductor connection point along with the ac circuit conductors to the
grounding busbar in the associated ac equipment. This combined grounding conductor shall be the larger of
the sizes specified by 250.122 or 250.166 and shall be installed in accordance with 250.64(E). For
ungrounded systems. this conductor shall be sized in accordance with 250,122 and shall not be required to
be larger than the #argest ungrounded phase conductors Add note for compliance with underlined items.
4) Provide schedule with the location of all required markings and labels for the proposed photovoltaic system.
(CEC §690) AC_systern,att=ibutes_naM�d at AC Disconnect and Dual Power Sources sig_qpnagg�..please
date signage sheet. _ �� --
SECTION C - MISCELLANEOUS COMMENTS
1) Red marks on Plans, even if not specifically mentioned in this list, indicate items needing correction. Revise
Plans as necessary and provide written response, noting where correction can be found.
2) Provide one copy each of the Site Plan and Floor Plan for the County Assessor's office. While not required for
resubmittal, this administrative item must be addressed prior to issuance of building permit.
END CORRECTION LIST
As further information is provided and reviewed, additional corrections may be required.
Residential Plan Check Correction List (SOLAR) Page 2 of 2
CORRECTION LIST RESPONSES
1.8.2018
ADDRESS: 80957 VIA PESSARO, 92253
ATTENTION: BUILDING PLAN REVIEW
CORRECTION
SECTION A - GENERAL
1) See DC kw rating clouded
2) See wet signature of contractor as engineer and designer of this project
SECTION B - SOLAR
1) See title 24 requirements incorporated in plan set
A) See all panels tilted 22 degrees (4.8xl2 slope)
B) See notes added to comply with 22degree title 24 requirements
2) See rapid shutdown signage removed
3) See conductor note added
4) See AC system attributes added to signage sheet
SECTION C — MISC COMMENTS
1) See red marks incorporated into plans and resubmitted herein
2) See (1) copy of floor plan and (1) copy of floor plans resubmitted herein
END CORRECTION RESPONSE LIST
PAGE
ALL
1,2
1,2
1,2
8
ATTACHED
ATTACHED