06-3496 (CONR) Title 24TITLE 24 REPORT
Title 24 Report for:
Additions & Renovations -to the Citrus Clubhouse
Jefferson and 52nd
La Quinta, CA .
Project Designer:
Pearson Architects, Inc.
74-260 Highway 111, Suite 8
Palm Desert, CA 92260
(760) 779-1937
Report Prepared By:'
Steve Balderrama, CEPE
Stueven Engineering Consultants
326 Kalmia Street
Escondido, CA 92025
CITY OF LA QUINTA
(760) 735-8577
BUILDING & SAFETY DEPT.
FOR R CONSTRUCTION
DATE 13 07 gY
Job Number:
JAN 1 9 2001 i
Date:
1/18/2007
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2005 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC - www.energysoft.com.
EnergyPro 4.3 by EnergySoft Job Number: User Number: 3429
TABLE OF CONTENTS
Cover Page - 1
Table of Contents 2
Nonresidential Performance Title 24 Forms 3
Form ENV-MM Envelope Mandatory Measures 13
Form MECH-MM Mechanical Mandatory Measures 14
i
EnergyPro 4.3 by EnergySoft Job Number: User Number: 3429
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 1 of 3 PERF -1
PROJECT NAME
Additions & Renovations to the Citrus Clubhouse
DATE
1/18/2007
PROJECT ADDRESS
Jefferson and 52nd La Quinta
The documentation preparer hereby certifies that the documentation is accu to ando te.
DOCUMENTATION AUTHOR
DATE OF PLANS
PRINCIPAL DESIGNER - ENVELOPE
Pearson Architects, Inc.
TELEPHONE
(760) 779-1937
Building Permit #
DOCUMENTATION AUTHOR
Stueven Engineering Consultants
TELEPHONE
760 735-8577
Checked by/Date
EnforcementAgenc Use
GENERAL INFORMATION
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is accu to ando te.
DOCUMENTATION AUTHOR
DATE OF PLANS
Steve Balderrama CEPE
BUILDING CONDITIONED FLOOR AREA
3,030 Sq.Ft.
The Principal Designer hereby certifys that the proposed building design represented in this set of construction documents is
CLIMATE ZONE
15
BUILDING TYPE
®
NONRESIDENTIAL HIGH RISE RESIDENTIAL
HOTEL/MOTEL GUEST ROOM
PHASE OF CONSTRUCTION
California as a civil engineer, mechanical engineer, or I am a licensed architect.
NEW CONSTRUCTION ® ADDITION
❑
EXISTING + ADDITION/ALTERATION
STATEMENT OF COMPLIANCE
This Certificate of Compliance lists the building features and performance specifications needed to comply with Title 24, Parts 1 and 6 of the
California Code of Regulations. This certificate applies only to a Building using the performance compliance approach.
The documentation preparer hereby certifies that the documentation is accu to ando te.
DOCUMENTATION AUTHOR
SIGN TUDATE
Steve Balderrama CEPE
r8 :)
The Principal Designer hereby certifys that the proposed building design represented in this set of construction documents is
consistent with the other compliance forms and worksheets, with the specifications, and with any other calculations submitted with this
permit application. The proposed building as designed meets the energy efficiency requirements contained in sections 110, 116,
through 118, and 140, 142, 143 or 149 of Title 24, Part 6.
ENV. LTG. MECH.
❑ ❑ 1. 1 hereby affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code to
sign this document as the person responsible for its preparation; and that I am licensed in the State of
California as a civil engineer, mechanical engineer, or I am a licensed architect.
❑ R 2. 1 affirm that I am eligible under the provisions of Division 3 of the Business and Professions Code Section
5537.2 or 6737.3 to sign this document as the person responsible for its preparation; and that I am a licensed
contractor performing this work.
❑ ❑ 3. 1 affirm that I am eligible under Division 3 of the Business and Professions Code to sign this document
because it pertains to a structure or type of work described as exempt pursuant to Business and Professions
Code Sections 5537, 5538, and 6737.1. (These sections of the Business and Professions Code are printed in
full in the Nonresidential Manual.)
ENVELOPE COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
ENV -1
CA -W& Required Forms
PRINCIPAL ENVELOPE DESIGNER - NAME
SIGNA RE
ILIQ-a1
NO' 2
DA :Pearson
Architects Inc.'
LIGHTING COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
Lighting Compliance Not In The Scope Of
Requir or
PRINCIEAL LIGHTING DES1G - NAME
TUR
LIC. NO. _
DATE
_.
ME HANICAL COMPLIANCE
Indicate location on plans of Note Block for Mandatory Measures
ECH-1, MECH-2 MECH-3 MECH-5
Requirg,df r
PRINCIPAL MECHANICAL DESIGNER - NAME SI T
NO.
DATE
Stueven Engineering Consultants
/ ?/S p3
/I o '►
1 EnergyPro 4.3 by EnergySoft User Number: 3429 Job Number: Paae:3 of 15 1
PERFORMANCE CERTIFICATE OF COMPLIANCE Part•2 Of 3 : PERF -
PROJECT NAME ; . • DATE I .
Additions & Renovations to the Citrus Clubhouse • = '1/18/2007'
ANNUAL TDV ENERGY USE SUMMAR
N 0 aeg
Standard
ENERGY COMPONENT
Design
Space Heating
5.84
Space Cooling
335.74
Indoor Fans
97.99
Heat Rejection
0.00
Pumps & Misc.
0.00
Domestic Hot Water
0.00
Lighting
67.76
Receptacle
43.96
Process
0.00
TOTALS:
551.28
Percent better than Standard:
Y (kBtu/sqft-yr)
N 0 aeg
Proposed
Design
sp.. Hdkv
Compliance
Margin
1.62
4.22
314.86
20.88
106.68
-8.70
0.00
0.00
0.00
0.00
0.00
0.00
67.76
0.00
43.96
0.00
0.00
0.00
0-30* TfiO?90 120150ISO 210T240T270 300P330
kBtWsgft-yr',
[[r -Standard
N 0 aeg
Conditioned Floor Area
. Unconditioned Floor Area
Conditioned Footprint Area,
Fuel Type
sp.. Hdkv
sqft.
sqft. "
sqft.
1
0
sp.;, C4*V
-
- Natural Gas
Hdfto
Ratio
< P-Wa 8 W=
y - .• j
-
DIM' ! .
. Ligh ft
568
sqft.
40.1%
Left Elevation (E)
589
0-30* TfiO?90 120150ISO 210T240T270 300P330
kBtWsgft-yr',
Building Orientation
Number of Stories
Number of Systems
Number of Zones
N 0 aeg
Conditioned Floor Area
. Unconditioned Floor Area
Conditioned Footprint Area,
Fuel Type
3,030
sqft.
sqft. "
sqft.
1
0
4
3,030
5
- Natural Gas
Glazing
Ratio
Standard Proposed LEED-NC v2.2 Energy & Atmosphere Credit
Lighting Power Density 1.021 W/sgft. 1.021 W/sgft. Savings vs. Title 24:
Prescriptive Env. Heat Loss 965 Btu/h . 722 Btu/h EAc1 Credit: 0 Points
Prescriptive Env. Heat Gain 107,931 Btu/h-F 86,974 Btu/h-F '
Remarks:
• l r
Run Initiation Time: 01/18/07 16:13:56 Run Code: 1169165636
EnergyPro 4.3 by EnergySoft User Number: 3429 . • Job Number:. • - - Page:4 of 15
Orientation
Gross Area
Glazing Area
Glazing
Ratio
Front Elevation (N)
1,416
sqft.
568
sqft.
40.1%
Left Elevation (E)
589
sqft.
123
sqft.
20.9%
Rear Elevation S
1,006
sqft.
376
sqft.
37.4%
V
Right Elevation (WA
Total
Roof
565
3,576
3,030
sqft.
sqft.
sqft.
168
1,235
sqft.
sqft.
sqft.
29.7%
34.5%
Standard Proposed LEED-NC v2.2 Energy & Atmosphere Credit
Lighting Power Density 1.021 W/sgft. 1.021 W/sgft. Savings vs. Title 24:
Prescriptive Env. Heat Loss 965 Btu/h . 722 Btu/h EAc1 Credit: 0 Points
Prescriptive Env. Heat Gain 107,931 Btu/h-F 86,974 Btu/h-F '
Remarks:
• l r
Run Initiation Time: 01/18/07 16:13:56 Run Code: 1169165636
EnergyPro 4.3 by EnergySoft User Number: 3429 . • Job Number:. • - - Page:4 of 15
PERFORMANCE CERTIFICATE OF COMPLIANCE Part 3 of 3 PERF -1
PROJECT NAME
Additions& Renovations to the Citrus Clubhouse
DATE
1/18/2007
ZONE INFORMATION
System Name Zone Name
Occupancy Type
Floor
Area
(sqft.)
Inst.
LPD
(W/sf)1
Ctrl.
Credits
(W/sf)2
Allowed LPD
Area Tailored
/s 3 (W/S4
Proc.
Loads
(W/Sq
HP -1 and HP -2 Fitness Center
Exercise, Gymnasium
1,900
'1.00
HP -3 Office Areas
. Office
528
'1.20
Indoor Restrooms
Corridor/Restroom/Support
122
'0.60
Outdoor Restrooms
Corridor/Restroom/Support
80
'0.60
HP -4 Bar
Bar, Cocktail Lounge, Casino
400
"1.10
Notes: 1. See LTG -2-C
(items marked with asterisk, see LTG -2 -C by others)
2. See LTG -4-C 3. See LTG -5-C
(by others)
4. See LTG -6-C
Items above require special documentation
EXCEPTIONAL CONDITIONS COMPLIANCE CHECKLIST
I ne local entorcement agency snould pay special attention to the items specified in this checklist. These items require special written justification
and documentation, and special verification to be used with the performance approach. The local enforcement agency determines the adequacy of
the justification, and may reject a building or design that otherwise complies based on the adequacy of the special justification and documentation
submitted.
The HVAC System "HP -3" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve.
The HVAC System "HP -4" incorporates a HERS verified Refrigerant Charge test or a HERS verified Thermostatic Expansion Valve.
The exceptional features listed in this performance approach application have specifically been reviewed. Adequate written justification and
documentation for their use have been provided by the applicant.
Signature or
MWC
EnergyPro 4.3 by EnergySoft User Number: 3429 Job Number: Page:5 of 15 1
CERTIFICATE OF COMPLIANCE ENV -1-C
PROJECT NAME DATE
Additions & Renovations to the Citrus Clubhouse 1/18/2007
OPAQUE SURFACES
# Surface
Type
Area
U -Fac.
Insulation
Cay. Cont.
Act.
Am.
Tilt
Cond'
Status
Joint Appendix
IV Reference
Location / Comments
1 Wall
39E
0.069
R-21
R-0.0
0
90
New
09-A6
Fitness Center
2 Wall
42
0.069
R-21
R-0.0
180
90
New
09-A6
Fitness Center
3 Wall
2
0.069
R-21
R-0.0
90
90
New
09-A6
Fitness Center
4 Roof
1,90q
0.025
R-38
R-0.0
0
0
New
01-A18
Fitness Center
5 lWall
1 100
0.069
R-21
R-0.0
0
90
New
09-A6
Office Areas
6 Door
24
0.500
None
R-0.0
0
90
New
28-A4
Office Areas
7 Wall
3E
0.069
R-21
R-0.0
90
90
New
09-A6
Office Areas
8 Wall
10E
0.069
R-21
R-0.0
180
90
New
09-A6
Office Areas
9 Door
24
0.500
None
R-0.0
180
90
New
28-A4
Office Areas
10 Wall
3
0.069
R-21
R-0.0
270
90
New
09-A6
Office Areas
11 Roof
524
0.025
R-38
R-0.01
0
0
1 New
01-A18
Office Areas
12 lWall
1 3
0.069
R-21
R-0.0
0
90
New
09-A6
Indoor Restrooms
13 Wall
8
0.069
R-21
R-0.0
90
90
New
09-A6
Indoor Restrooms
14 Roof
12
0.025
R-38
R-0.0
0
0
New
01-A18
Indoor Restrooms
15 Wall
8
0.069
R-21
R-0.0
0
90
New
09-A6
Outdoor Restrooms
16 Wall
8
0.069
R-21
R-0.0
180
90
New
09-A6
Outdoor Restrooms
17 Wall
11
0.069
R-21
R-0.0
270
90
1 New
09-A6
Outdoor Restrooms
18 Door
41
-8q
0.5001
None
I R-0.01
270
90
New
28-A4
Outdoor Restrooms
19 lRoof
f
0.1381
None
I R-5.0
0
0
New
01-A1
Outdoor Restrooms
20 all
21
0.069
R-21
R-0.0
0
90
New
09-A6
Bar
N, E, A, R (New, Existing, Altered, Removed)
FENESTRATION SURFACES
More than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U -factors from
Standards Table 116-A and B. Certificate shall be filed in the contractor's Droiect office during construction and in the buildina manaaer's office after construction
#
T e
Area U -Fac'
SHGC2
Act.
Am.
Cond.
Stat.
Glazing Type
Location/
Comments
1
Window
Front
N
48 0.390 NFRC
0.37 NFRC
0
New
Metal Clad / Wood Windows
Fitness Center
2
Window
Front
N
48 0.390 NFRC
0.37 NFRC
0
New
Metal Clad / Wood Windows
Fitness Center
3
Window
Front
(N)
48 0.390 NFRC
0.37 NFRC
0
New
Metal Clad /Wood Windows
Fitness Center
4
Window
Front
N
48 0.390 NFRC
0.37 NFRC
0
New
Metal Clad /Wood Windows
Fitness Center
5
Window
Front
N
48 0.390 NFRC
0.37 NFRC
0
New
Metal Clad / Wood Windows
Fitness Center
6
Window
Front
(N)
60 0.390 NFRC
0.37 NFRC
0
New
Metal Clad / Wood Windows
Fitness Center
7
lWindow
Front
N
60 0.390 NFRC
0.37 NFRC
0
New
Metal Clad / Wood Windows
Fitness Center
8
Window
Rear
S
48 0.390 NFRC
0.37 NFRC
180
New
Metal Clad / Wood Windows
Fitness Center
9
Window
Rear
S
48 0.390 NFRC
0.37 NFRC
180
New
Metal Clad / Wood Windows
Fitness Center
10 Window
Rear
(S)
48 0.390 NFRC
0.37 NFRC
180
New
Metal Clad / Wood Windows
Fitness Center
11 Window
Rear
(S)
48 0.390 NFRC
0.37 INFRC
1801
New
I Metal Clad / Wood Windows
Fitness Center
12 Window
Rear
S
48 0.390 NFRC
0.37 INFRC
1801
New
I Metal Clad / Wood Windows
Fitness Center
13 Window
Rear
(S)
48 0.390 NFRC
0.37 INFRC
1801
New
I Metal Clad / Wood Windows
Fitness Center
(1) LI -factor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value.
(2) SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
#
Exterior Shade Type
SHGC
Window
Hgt. Wd.
Overhang Left Fin Right Fin
Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
1
None
0.76
8.0 6.0
2.0
0.1
2.0
2.0
2
None
0.76
8.0 6.0
2.0
0.1
2.0
2.0
3
None
0.76
8.0 6.0
2.0
0.1
2.0
2.0
4
None
0.76
8.0 6.0
2.0
0.1
2.0
2.0
5
None
0.76
8.0 6.0
2.0
0.1
2.0
2.0
6
None
0.76
10.0 6.0
2.0
0.1
2.0
2.0
7
None
0.76
10.0 6.0
2.0
0.1
2.0
2.0
8
None
0.76
8.0 6.0
2.0
0.1
2.0
2.0
9
None
0.76
8.0 6.0
2.0
0.1
2.0
2.0
10
None
0.76
8.0 6.0
2.0
0.1
2.0
2.0
11
None
1 0.76
8.0 6.0
2.0
0.1
2.0
2.0
12
None
1 0.76
8.0 6.0
2.0
0.1
2.0
2.0
13
None
1 0.76
8.0 6.0
2.0
0.1
2.0
2.0
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
aThe proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 ft2, a ceiling height greater than 15 feet, and an LPD for general
lighting of at least 0.5 Wfft2. See Section 143(c). If this box Is checked, ENV -4-C must be filled out. when submitting under the Prescriptive Compliance Approach.
1 EnergyPro 4.3 by EnergySoft User Number: 3429 Job Number: Page:6 of 15 1
CERTIFICATE OF COMPLIANCE ENV -1-C
PROJECT NAME DATE
Additions & Renovations to the Citrus Clubhouse 1/18/2007
OPAQUE SURFACES
OEM=
Area U -Fac'
SHGC2
Act.
Am.
Cond.
Stat.
IV Reference
Location/ Comments
14 Window
Rear
S
48 0.390 NFRC
0.37 NFRC
180
New
Metal Clad / Wood Windows
Fitness Center
15 Window
Left
E
48 0.390 NFRC
0.37 NFRC
90
New
Metal Clad / Wood Windows
Fitness Center
16 Window
Left
E)
48 0.390 NFRC
0.37 NFRC
90
New
Metal Clad / Wood Windows
Fitness Center
17 Window
Front
N
17 0.390 NFRCI
0.37 NFRC
0
New
Metal Clad / Wood Windows
Office Areas
18 Window
Front
N
17 0.390 NFRC
0.37 NFRC
0
New
Metal Clad / Wood Windows
Office Areas
19 Window
Front
N)
6 0.390 NFRC
0.37 NFRC
0
New
Metal Clad / Wood Windows
Office Areas
20 lWindow
Rear
S)
17 0.390 NFRC
0.37 NFRC
180
New
Metal Clad / Wood Windows
Office Areas
21 Window
Rear
S
17 0.390 NFRC
0.37 NFRC
180
New
Metal Clad /Wood Windows
Office Areas
22 Window
Rear
S
6 0.390 NFRC
0.37 NFRC
180
New
Metal Clad / Wood Windows
Office Areas
23 Window
Front
N
84 0.390 NFRC
0.37 NFRCI
0
New
I Metal Clad / Wood Windows
Bar
24 Window
Front
N)
84 0.390 NFRC
0.37 NFRC
01
New
Metal Clad / Wood Windows
I Bar
25 Window
Left
E
27 0.390 NFRC
0.37 NFRC901
0.1
New
I Metal Clad / Wood Windows
lBar
26 Window
Right
W
84 0.390 NFRC
0.37 NFRC
2701
New
I Metal Clad / Wood Windows
jBar
N. E. A. R (New, Existing, Altered, Removed)
FENESTRATION SURFACES -71
More than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default LI -factors from
Standards Table 116-A and B. Certificate shall be filed in the contractor's Droiect office durinq construction and in the building manaoer's office after construction
# IType
Area U -Fac'
SHGC2
Act.
Am.
Cond.
Stat.
Glazing Type
Location/
Comments
14 Window
Rear
S
48 0.390 NFRC
0.37 NFRC
180
New
Metal Clad / Wood Windows
Fitness Center
15 Window
Left
E
48 0.390 NFRC
0.37 NFRC
90
New
Metal Clad / Wood Windows
Fitness Center
16 Window
Left
E)
48 0.390 NFRC
0.37 NFRC
90
New
Metal Clad / Wood Windows
Fitness Center
17 Window
Front
N
17 0.390 NFRCI
0.37 NFRC
0
New
Metal Clad / Wood Windows
Office Areas
18 Window
Front
N
17 0.390 NFRC
0.37 NFRC
0
New
Metal Clad / Wood Windows
Office Areas
19 Window
Front
N)
6 0.390 NFRC
0.37 NFRC
0
New
Metal Clad / Wood Windows
Office Areas
20 lWindow
Rear
S)
17 0.390 NFRC
0.37 NFRC
180
New
Metal Clad / Wood Windows
Office Areas
21 Window
Rear
S
17 0.390 NFRC
0.37 NFRC
180
New
Metal Clad /Wood Windows
Office Areas
22 Window
Rear
S
6 0.390 NFRC
0.37 NFRC
180
New
Metal Clad / Wood Windows
Office Areas
23 Window
Front
N
84 0.390 NFRC
0.37 NFRCI
0
New
I Metal Clad / Wood Windows
Bar
24 Window
Front
N)
84 0.390 NFRC
0.37 NFRC
01
New
Metal Clad / Wood Windows
I Bar
25 Window
Left
E
27 0.390 NFRC
0.37 NFRC901
0.1
New
I Metal Clad / Wood Windows
lBar
26 Window
Right
W
84 0.390 NFRC
0.37 NFRC
2701
New
I Metal Clad / Wood Windows
jBar
(1)LI-factor Type: 116-A Default Table from Standards, Table NI -1 Default Table from the ACM Manual Appendix, NFRC Labeled value.
(2) SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
##
Exterior Shade Type
SHGC
Window
Hgt. Wd.
Overhang Left Fin Right Fin
Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
14
None
0.76
8.0 6.0
2.0
0.1
2.0
2.0
15
None
0.76
8.0 6.0
2.0
0.1
2.0
2.0
16
None
0.76
8.0 6.0
2.0
0.1
2.0
2.0
17
None
0.76
10.0 1.7
2.0
0.1
2.0
2.0
18
None
0.76
10.0 1.7
2.0
0.1
2.0
2.0
19
None
0.76
3.0 2.0
2.0
0.1
2.0
2.0
20
None
0.76
10.0 1.7
2.0
0.1
2.0
2.0
21
None
0.76
10.0 1.7
2.0
0.1
2.0
2.0
22
None
0.76
3.0 2.0
2.0
0.1
2.0
2.0
23
None
0.76
3.0 2.0
2.0
0.1
2.0
2.0
24
None
0.76
3.0 2.0
2.0
0.1
2.0
2.0
25
None0.76
3.0 2.0
2.0
0.1
2.0
2.0
26
None
0.76
3.0 2.0
2.0
0.1
2.0
2.0
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
The proposed building Is In climate zones 2 through 15 and contains an enclosed space with floor area greater than 25,000 11:2, a ceiling height greater than 15 feet, and an LPD for general
lighting of at least 0.5 W/ft2. See Section 143(c). If this box Is checked, ENV -0-C must be filled out. when submitting under the Prescriptive Compliance Approach.
EnergyPro 4.3 by EnergySofl User Number. 3429 Job Number: Paae:7 of 15 1
CERTIFICATE OF COMPLIANCE ENVA-C
)ROJECT NAME DATE
Additions & Renovations to the Citrus Clubhouse 1/18/2007
OPAQUE SURFACES -71
# I surrace msuiation Act. Iona: joint Appenaix
Twe Area U -Fac. Cay. Cont. Azm. Tilt Status IV Reference I Location/ Comments
N, E, A, R (New, Existing, Altered, Removed)
FENESTRATION SURFACES -71
More than or equal to 10,000 sq.ft. of site -built fenestration area must include a label certificate either issued by NFRC or provide a CEC Default Label Certificate using the default U -factors from
Stnndarrls Tnhlp 116-A and R renifiratp shall hp filpd in the rnntma tnrs nmiort nfrrp durinn r netn,rtinn and in the h,,ildinn m nor, nffirp aBpr rnnctn,rtinn
(1)y -tactor type: 1lb-A Uetaull Table trom Standaros, Table NI -1 oetault Table trom the ACM Manual Appendix, NFRC Labeled value.
(2) SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
Window Overhang Left Fin Right Fin
## Exterior Shade Type SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
27 None 0.76 3.0 2.0 2.0 0.1 2.0 2.0
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
U The proposed building is In climate zones Z through 15 and contains an enclosed space with Floor area greater than 25,000 ft2, a ceiling height greater than 15 feet, and an LPD for general
lighting of at least 0.5 W111:2. See Section 143(c). H this box Is checked, ENV -0-C must be filled out. when submitting under the Prescriptive Compliance Approach.
EnergyPro 4.3 by EnergySoft User Number: 3429 Job Number: Page:8 of 15 1
..Location/.
(1)y -tactor type: 1lb-A Uetaull Table trom Standaros, Table NI -1 oetault Table trom the ACM Manual Appendix, NFRC Labeled value.
(2) SHGC Type: 116-B Default Table from Standards, COG Center of Glass, NFRC Labeled Value
EXTERIOR SHADING
Window Overhang Left Fin Right Fin
## Exterior Shade Type SHGC Hgt. Wd. Len. H t. LExt.RExt. Dist. Len. H t. Dist. Len. H t.
27 None 0.76 3.0 2.0 2.0 0.1 2.0 2.0
MINIMUM SKYLIGHT AREA FOR LARGE ENCLOSED SPACES
U The proposed building is In climate zones Z through 15 and contains an enclosed space with Floor area greater than 25,000 ft2, a ceiling height greater than 15 feet, and an LPD for general
lighting of at least 0.5 W111:2. See Section 143(c). H this box Is checked, ENV -0-C must be filled out. when submitting under the Prescriptive Compliance Approach.
EnergyPro 4.3 by EnergySoft User Number: 3429 Job Number: Page:8 of 15 1
CERTIFICATE OF COMPLIANCE MECH-1-C
PROJECT NAME t DATE
Additions & Renovations to the Citrus Clubhouse 1/18/2007
Designer:
This form is to be used by the designer and attached to the plans. Listed below are all the acceptance tests for mechanical systems. The designer is required to
check the boxes by all acceptance tests that apply and list all equipment that requires an acceptance test. If all equipment of a certain type requires a test, list the
equipment description and the number of systems to be tested in parentheses. The NJ number designates the Section in the Appendix of the Nonresidential
ACM Manual that describes the test. Also indicate the person responsible for performing the tests (i.e. the installing contractor, design professional or an agent
selected by the owner). Since this form will be part of the plans, completion of this section will allow the responsible party to budget for the scope of work
appropriately.
Building Departments:
SYSTEM ACCEPTANCE. Before an occupancy permit is granted for a newly constructed building or space, or a new space -conditioning system serving a
building or space is operated for normal use, all control devices serving the building or space shall be certified as meeting the Acceptance Requirements for
Code Compliance.
In addition a Certificate of Acceptance, MECH-I-A Form shall be submitted to the building department that certifies plans, specifications, installation
certificates. and ooeratino and maintenance information meet the requirements of Section 10-103(bl and Title 24 Part 6.
STATEMENT OF COMPLIANCE
MECH-2-A: Ventilation System Acceptance Document
-Variable Air Volume Systems Outdoor Air Acceptance
-Constant Air Volume Systems Outdoor Air Acceptance
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-3-A: Packaged HVAC Systems Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit.
❑ MECH-4-A: Air -Side Economizer Acceptance Document
Equipment requiring acceptance testing
Test required on all New systems both New Construction and Retrofit. Units with economizers that are installed at the factory and certified with the
commission do not require equipment testing but do require construction inspection.
MECH-5-A: Air Distribution Acceptance Document
Equipment requiring acceptance testing
This test required If the unit serves 5,000 ft2 of space or less and 25% or more of the ducts are in nonconditioned or semiconditioned space like an
attic. New systems that meet the above requirements. Retrofit systems that meet the above requirements and either extend ducts, replace ducts or
replace the packaged unit.
❑ MECH-6-A: Demand Control Ventilation Acceptance Document
Equipment requiring acceptance testing
All new DCV controls installed on new or existing packaged systems must be tested.
❑ MECH-7-A: Supply Fan Variable Flow Control Acceptance Document
Equipment requiring acceptance testing
All new VA fan volume controls installed on new or existing systems must be tested
❑ MECH-8-A: -Hydronic System Control Acceptance Document
-Variable Flow Controls Applies to chilled and hot water systems.
-Automatic Isolation Controls Applies to new boilers and chillers and the primary pumps are connected to a common header.
-Supply Water Temperature Reset Controls
Applies to new constant flow chilled and hot water systems that have a design capacity greater than or equal to 500,000 Btulhr.
-Water-loop Heat Pump Controls
Applies to all new watertoop heat pump systems where the combined loop pumps are greater than 5 hp.
-Variable Frequency Controls Applies to all new distribution pumps on new variable flow chilled, hydronic heat pump
or condenser water systems where the pumps motors are greater than 5 hp.
Equipment requiring acceptance testing
EnergyPro 4.3 by EnergySoft User Number: 3429 Job Number: Page:9 of 15
AIR SYSTEM REQUIREMENTS Part 1 of 2 MECH-2-C
(PROJECT NAME DATE
Additions & Renovations to the Citrus Clubhouse 1/18/2007
SYSTEM FEATURES
ITEM OR SYSTEM TAG(S)
Number of Systems
T-24
MANDATORY MEASURES Section
Heating Equipment Efficiency
Cooling Equipment Efficiency
Heat Pump Thermostat
Furnace Controls
Natural Ventilation
Minimum Ventilation
VAV Minimum Position Control
Demand Control Ventilation
Time Control
Setback and Setup Control
Outdoor Damper Control
Isolation Zones
Pipe Insulation
Duct Insulation
PRESCRIPTIVE MEASURES
Calculated Heating Capacity x 1.43 2
Proposed Heating Capacity 2
Calculated Sensible Cooling Capacity x 1.212
Proposed Sensible Cooling Capacity 2
Fan Control
DP Sensor Location
Supply Pressure Reset (DDC only)
Simultaneous Heat/Cool
Economiier
Heating Air Supply Reset
Cooling Air Supply Reset
Duct Sealing for Prescriptive Compliance
AIR SYSTEMS, Central or Single Zone
HP -1 and HP -2
HP -3
HP -4
2
1
1
Reference on Plans or Specification 1
112(a)
7.50 HSPF
8.50 HSPF
8.80 HSPF
112(a)
10.3 EER
14.5 SEER / 11.5 EER
14.0 SEER / 11.5 EER
112(b)
Yes
Yes
Yes
112(c), 115(a),
n/a
n/a
n/a
121(b)
No
No
No
121 b)
760 cfm
110 cfm
200 cfm
121 c
No
No
No
121(c)
No
No
No
121(c), 122(e)
Programmable Switch
Programmable Switch
Programmable Switch
122(e)
Heating & Cooling Required
Heating & Cooling Required
Heating & Cooling Required
122
Gravity
Gravity
Gravity
122(g)
n/a
n/a
n/a
123
124
R-8.0
R-8.0
R-8.0
144 a & b
n/a
n/a
n/a
144 a & b
59,959 btuh
13,741 btuh
17,550 btuh
144 a & b
n/a
n/a
n/a
144 a & b
101,675 btuh
26,943 btuh
40,711 btuh
144 c
Constant Volume
Constant Volume
Constant Volume
144 c
144 c
144 d
No
No
No
144 a
No Economizer
No Economizer
No Economizer
144
Constant Ternp
Constant Ternp
Constant Tem
144 (f)
Constant Temp
Constant Temp
Constant Temp
144 (k)
No
No
No
1: For each central and single zone air systems (or group of similar units) fill in the reference to sheet number and/or specification section and paragraph number where the
required features are documented. If a requirement is not applicable, put "N/A" in the column.
2: Not required for hydronic heating and cooling. Either enter a value here or put in reference of plans and specificatons per footnote 1.
3: Enter Yes if System is: Constant Volume, Single Zone; Serves < 5,000 sgft; Has > 25% duct in unconditioned space. Duct sealing is required for Prescriptive Compliance,
see PERF -1 for performance method duct sealing requirements.
EnergyPro 4.3 by EnergySoft User Number: 3429 Job Number: Page: 10 of 15 1
MECHANICAL VENTILATION MECH-3-C
PROJECT NAME DATE
Additions & Renovations to the Citrus Clubhouse 1 1/18/2007
PRESCRIPTIVE REHEAT
LIMITATION Section 144 d
MECHANICAL VENTILATION Section
121 W2)
AREA
BASIS
OCCUPANCY
BASIS
VAV MINIMUM
A
B
C
D
E
F
G
H
I
J
K
L
M
N
ZONE/SYSTEM
o
ND3
'f1 N a
v01c
Uf
C
IN
'-n
3
°0
c 3
W
X>0
0' -n
3
-p c
ID 3
0 Cr
o
M
ff1 T
3
Cr
3
m
X no
TAT
v 3
m
)p
O X
°<
' D
<
c>3 (D
-n .. N
3DB
N o
,
neo
-n fq ""
g cM
o '"
-n
00
X
'pA
x
;K n
o c
wad
O X
nyo
T?
to y
:°>
'O
2.5
d
>
D
Fitness Center
1,90
0.15
285
760
760
HP -1 and HP -2
Total
760
760
Office Areas
526
0.15
79
79
79
Indoor Restrooms
122
0.151
18
18
18
Outdoor Restrooms
8C
0.15
12
12
12
HP -3
Total
110
110
Bar
40C
0.50
200
200
200
HP -4
Total
200
200
C Minimum ventilation rate per Section 121 Table 121-A
E Based on fixed seat or the greater of the expected number of occupants and 50% of the CBC occupant load foregress purposes fors aces without fixed seating.
H Required Ventilation Air REQ'D V.A. is the larger of the ventilation rates calculated on and AREA or OCCUPANCY BASIS column D or G).
I Must be greater than orequal to H or use Transfer Air column N to make up the difference.
J Design fan supplycfm Fan CFM) x 30%; or
K Condition area ft. sq. x 04 cfm/ft. sq.: or
L Maximum of Columns H, J. K, or 300 cfm
M This must be less than orequal to Column L and greater that orequal to the sum of Columns H + N.
N Transfer air must be provided where the Required Ventilation Air (column 1) is greater than the Design Minimum Air (column M). Where required, transfer air must be greater than or equal
to the difference between the Required Ventilation Air (column 1) and the Design Minimum Air (column M), column H - M.
EnergyPro 4.3 by Energysoft User Number. 3429 Job Number: Page: 11 of 15
MECHANICAL EQUIPMENT DETAILS
Part 1 of 2 MECH-5-C
PROJECT NAME
Additions & Renovations to the Citrus Clubhouse
DATE
1/18/2007 :]
CHILLER AND TOWER SUMMARY
HP
Type
Efficiency
Tons
Buried
PUMPS
Equipment Name
Equipment Type
Qty.
Tot.
Qty
GPM
I BHP
Motor
Eff.
Drive
Eff.
Pump
Control
CENTRAL SYSTEM RATINGS
HEATING
COOLING
System Name
System Type
Qtv
Output
Aux.
kW
Eff.
Output
Efficiencv
Condition
Status
Economizer Type
Carrier 38A0007 /
40RM0008
Split DX
2
48,000
0.0
7.50 HSPF
72,90010.3
EER
New
No Economizer
BOILER SUMMARY
Split DX
Energy Standby TANK INSUL.
Rated 1 Vol. Condition Factor Loss or Ext.
System Name System Type Distribution Type Qty Input (Gals.) Status I or RE Pilot I R -Val.
MULTI -FAMILY CENTRAL WATER HEATING DETAILS
Hot Water P mp
Hot Water Piping Len th ft
Control
#
HP
Type
In Plenum
Outside
Buried
Add 1/2"
Insulation
CENTRAL SYSTEM RATINGS
HEATING
COOLING
System Name
System Type
Qtv
Output
Aux.
kW
Eff.
Output
Efficiencv
Condition
Status
Economizer Type
Carrier 38A0007 /
40RM0008
Split DX
2
48,000
0.0
7.50 HSPF
72,90010.3
EER
New
No Economizer
Carrier 25HCA436 /
FX4CNF036
Split DX
1
22,000
0.
8.50 HSPF
31,100
14.5 SEER/ 11.5 EER
New
No Economizer
Carrier 25HCA448 /
FX4CNF048
Split DX
1
28,100
0.
8.80 HSPF
45,20014.0
SEER/ 11.5 EER
New
No Economizer
ENVELOPE MANDATORY MEASURES' ENV -MM
PROJECT NAME DATE
Additions & Renovations to the Citrus Clubhouse 1/18/2007
DESCRIPTION
Desi ner
Enforcement
FX
§118(a)
Installed Insulating Material shall have been certified by the manufacturer to comply
with the California Quality Standards for insulating material, Title 20, Chapter 4, Article
3.
0
§ 118(c)
All Insulating Materials shall be Installed in compliance with the flame spread rating
and smoke density requirements of Sections 2602 and 707 of Title 24, Part 2.
X❑
§117(a)
All Exterior Joints and openings in the building that are observable sources of air
leakage shall be caulked, gasketed, weatherstripped or otherwise sealed.
X]
§116(b)
Site Constructed Doors, Windows and Skylights shall be caulked between the unit
and the building, and shall be weatherstripped (except for unframed glass doors and
fire doors).
§ 116(a)1
Manufactured Doors and Windows installed shall have air Infiltration rates not
exceeding those shown in Table Number 1-E. of the Standards. Manufactured
fenestration products must be labeled for U -value according to NFRC procedures.
• i
§118(e)
Demising Walls in Nonresidential Buildings:
The opaque portions of framed demising walls in nonresidential buildings shall have
insulation with an installed R -value of no less than R-13 between framing members.
EnergyPro
By EnergySoft User Number: User Job Number: Page: 13 of 15
MECHANICAL MANDATORY MEASURES Part 1 of 2 MECH-MM
PROJECT NAME DATE
Additions & Renovations to the Citrus Clubhouse 1/18/2007
DESCRIPTION
Desi ner
Enforcement
Equipment and Systems Efficiencies
a §111 Any appliance for which there is a California standard established in the Appliance
Efficiency Regulations will comply with the applicable standard.
❑ § 115(a) Fan type central furnaces shall not have a pilot light.
❑ § 123 Piping, except that conveying fluids at temperatures between 60 and 105 degrees
Fahrenheit, or within HVAC equipment, shall be insulated in accordance with
Standards Section 123.
X] § 124 Air handling duct systems shall be installed and insulated in compliance with
Sections 601, 602, 603, 604, and 605 of the 2001 CMC Standards.
Controls
§ 122(e) Each space conditioning system shall be installed with one of the following:
§ 122(e)1A Each space conditioning system serving building types such as offices and
manufacturing facilities (and all others not explicitly exempt from the requirements
of Section 112 (d)) shall be installed with an automatic time switch with an
accessible manual override that allows operation of the system during off -hours for
up to 4 hours. The time switch shall be capable of programming different
schedules for weekdays and weekends and have program backup capabilities that
prevent the loss of the device's program and time setting for at least 10 hours if
power is interrupted; or
❑ § 122(e)1 B An occupancy sensor to control the operating period of the system; or
§ 122(e)1C A 4 -hour timer that can be manually operated to control the operating period of the
system.
X] § 122(e)2 Each space conditioning system shall be installed with controls that temporarily
restart and temporarily operate the system as required to maintain a setback
heating and/or a setup cooling thermostat setpoint
❑ § 122(g) Each space conditioning system serving multiple zones with a combined
conditioned floor area more than 25,000 square feet shall be provided with isolation
zones. Each zone: shall not exceed 25,000 square feet; shall be provided with
isolation devices, such as valves or dampers, that allow the supply of heating or
cooling to be setback or shut off independently of other isolation areas; and shall
be controlled by a time control device as described above.
® § 122(aft) Each space conditioning system shall be controlled by an individual thermostat
that responds to temperature within the zone. Where used to control heating, the
control shall be adjustable down to 55 degrees F or lower. For cooling, the control
shall be adjustable up to 85 degrees F or higher. Where used for both heating and
cooling, the control shall be capable of providing a deadband of at least 5 degrees
F within which the supply of heating and cooling is shut off or reduced to a
minimum.
0 § 122(c) Thermostats shall have numeric setpoints in degrees Fahrenheit (F) and adjustable
setpoint stops accessible only to authorized personnel.
§ 112(b) Heat pumps shall be installed with controls to prevent electric resistance
supplementary heater operation when the heating load can be met by the heat
pump alone.
EnergyPro By EnergySok User. Number: User Job Number: Page: 14 of 15
MECHANICAL MANDATORY MEASURES Part 2 of 2' MECH-MM
PROJECT NAME DATE
Additions & Renovations to the Citrus Clubhouse 1/18/2007
t
V,
a
Description
Designer
Enforcement
Ventilation
FX§
121(e)
Controls shall be provided to allow outside air dampers or devices to be operated at
the ventilation rates as specified on these plans.
F-],
§ 122(f)
Gravity or automatic dampers interlocked and closed on fan shutdown shall be
provided on the outside air intakes and discharges of all space conditioning and
exhaust systems.
§ 122(f)
All gravity ventilating systems shall be provided with automatic or readily accessible
manually operated dampers in all openings to the outside, except for combustion air
openings.
§ 121(f)1
Air Balancing: The system shall be balanced in accordance with the National
Environmental Balancing Bureau (NEBB) Procedural Standards (1983), or
Associated Air Balance Council (AABC) National Standards (1989); or
X] § 121(f)2
Outside Air Certification: The system shall provide the minimum outside air as
shown on the mechanical drawings, and shall be measured and certified by the
installing licensed C-20 mechanical contractor and certified by (1) the design
mechanical engineer, (2) the installing licenced C-20 mechanical contractor, or (3) the
person with overall responsibility for the design of the ventilation system; or
❑
§ 121(f)3
Outside Air Measurement: The system shall be equipped with a calibrated local or
remote device capable of measuring the quantity of outside air on a continuous
basis and displaying that quantity on a readily accessible display divice; or
a§
121(f)4
Another method approved by the Commission.
Service
Water Heating Systems
§113(b)2
If a circulating hot water system is installed, it shall have a control capable of
automatically turning off the circulating pump(s) when hot water is not required.
X❑
§ 113(c)
Lavatories in restrooms of public facilities shall be equipped with controls to limit the
outlet temperature to 110 degrees F.
EnergyPro
By EnergySoft User Number: User Job Number. Page: 15 of 15
t
V,