BSOL2020-0003 Solar PlansJURISDICTIONAL NOTES:
Fj
UTY OF LA QUINTA
BUILDING DIVISION
REVIEWED FOR
CODE
COMPLIANCE
DATE 2-BY
GOVERNING CODES
ALL WORK SHALL CONFORM TO THE FOLLOWING
1. 2019 CA BUILDING CODE
2. 2019 CA ELECTRICAL CODE
3. 2019 CA FIRE CODE
4. 2019 CA RESIDENTIAL CODE
5. ANY OTHER LOCAL AMENDMENTS
SHEET INDEX:
PV 0.0 - COVER SHEET
PV 1.0 - SITE PLAN
S 1.0 - MOUNT DETAILS
E 1 - ELECTRICAL DIAGRAM
E 2 - ELECTRICAL NOTES
E 3 - WARNING LABELS
E 4 - WARNING LABEL LOCATIONS
E 5.0 - ELEC PANEL PHOTOS
E 5.1 - ELEC MSP/STICKER PHOTOS
GENERAL ELECTRICAL NOTES: GENERAL STRUCTURAL NOTES: ••'`` vt C''••,,
���� �L�
ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL a. THE SOLAR PANELS ARE TO BE MOUNTED TO THE ROOF FRAMING USING ��` y� �� & Cy
MEANS DESIGNED AND LISTED FOR SUCH USE. FOR ROOFSMOUNTED THE ROCK -IT SYSTEM BY ECOFASTEN. THE MOUNTING FEET ARE TO BE
•` SYSTEMS, WIRING MUST BE PERMANENTLY AND COMPLETELY HELD OFF OF SPACED AS SHOWN IN THE DETAILS, AND SHOULD BE STAGGERED, WHERE
THE ROOF SURFACE. POSSIBLE, TO ADJACENT FRAMING MEMBERS TO SPREAD OUT THE
ANY CODE VIOLATIONS EVIDENT IN THE INTERCONNECTION PANEL WILL BE ADDITIONAL LOAD. %ramp 9Tgf�
CORRECTED ON INSTALLATION. s rrr
b. UNLESS NOTED OTHERWISE, MOUNTING ANCHORS SHALL BE /6 LAG rri Od
SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH ALL RELEVANT CODE SCREWS WITH A MINIMUM OF 2Y" PENETRATION INTO ROOF FRAMING.►�e���i �t�ti�N'� 1
RAPID SHUTDOWN INITIATION TAKES PLACE WITHIN THE FIRMWARE OF THE G. THE PROPOSED PV SYSTEM ADDS 3.0 psf TO THE ROOF FRAMING SYSTEM. a
INVERTER. RAPID SHUTDOWN COMMENCES;UPON LOSS OF UTILITY SOURCE d. ROOF LIVE LOAD = 20 psf TYPICAL, 0 psf UNDER NEW PV SYSTEM.
VOLTAGE. e. GROUND SNOW LOAD = 0 psf
- f SEE *E 1.0 AND `E 2.0 FOR DIAGRAMS, CALCULATIONS, SCHEDULE AND f. WIND SPEED = 130 mph
SPECIFICATIONS. 9. EXPOSURE CATEGORY = C
•.r
vivint.Solar
f PHOTOVOLTAIC SYSTEM SPECIFICATIONS. 1800ASHTON BLVD, LEHI, UT84043
1.877.404.4129
SYSTEM SIZE - 8.000kW DC 17.227kW CEC AC CA LICENSE: B/C46/C10/C39-973756
MODULE TYPE & AMOUNT - (25) Hanwha Solar Q.PEAK DUO BLK-G5 320w WITH 25 SolarEdge P340
OPTIMIZERS JACOBS RESIDENCE
MODULE DIMENSIONS - L/W/H 66.34"/ 39.37"/ 1.26" 50INT , CA, 92 DR
■ ( ) LA QUINTA, CA, 92253-9011
INVERTER - (1) SolarEdge Technologies SE760OH-USOOOBNC4 * UTILITY ACCOUNT #: 50688654
"INVERTER USED IN THIS DESIGN IS COMPLIANT WITH CEC 69012 (RAPID SHUTDOWN). SEE MANUFACTURER DATA SHEET.
INTERCONNECTION METHOD (GRID -TIED) - LOAD BREAKER iSERVICE #:S-6279294 f REGIONAL P V\/
0.0 MT
R
/
OPEATING CENTER: CA-21 - - COVER SHEET 40
� 7- f� 00 I Z BY: BDATE: 20 ul
� �! � DRAWN BY: RENT PERSCHON
PV STRING-(S): OOF SECTIC
1 SLOPE-23
®
#1)13 MODULES AZIMUTH - 211.4
®
MATERIAL - TILE -
#2)12 MODULES CURVE
2 SLOPE-23
AZIMUTH - 211.4
MATERIAL - TILE -
S-CURVE
SITE PLAN
SCALE: 1/8" =1'-0"
w
co
Z3
O
2
u-
O
H
Z
O
of
u-
ROOF FIRE SUPPRESSION SPRINKLER
SYSTEM: NO
TOTAL ROOF AREA: 4282ft
TOTAL MODULE AREA: 453ft2
TOTAL AREA COVERED: 11 %
SYSTEM LEGEND
PV SYSTEM SIZE:
NEW 8.000kW DC I 7.227kW CEC AC
EXISTING EXTERIOR MAIN SERVICE PANEL
&
POINT OF INTERCONNECTION. TIED TO ATTACHE[
UTILITY METER 1 B4SORD-114726.
NEW PV SYSTEM AC DISCONNECT (RSD). LOCATE[
Q WITHIN 10' OF MSP.
1 NEW PV SYSTEM INVERTER: SolarEdge
Technologies SE760OH-USOOOBNC4 (RSD EQUIPPED)
25 NEW HANWHA SOLAR Q.PEAK DUO BLK-G5
320W MODULES.
NEW SOLAREDGE P340 OPTIMIZERS, MOUNTED
ON THE BACK OF EACH MODULE.
NEW PV CONDUIT RUN.'SEE E1-0 CONDUIT SCHEDULE
—_—_— EXTERIOR RUN — — — — — = ATTIC RUN
NEW JUNCTION BOX. (MOUNTED TO PV MODULE)
��
.►����rO't�Callf��i�
Sell
sad Co(%-0%%
y�1111111111 %
FIRE CODE OFFSET
RIDGE: 36"1 PATHWAY: 36"
vivint.Solar
1.877.404.4129
CA LICENSE: B/C46/C10/C39-973756
JACOBS RESIDENCE
50485 VERANO DR
LA QUINTA, CA, 92253-9011
UTILITY ACCOUNT #: 50688654
SERVICE #: S-6279294
REGIONAL Pv 1.0
OPERATING CENTER: GA-21
DATE: 2.3.2020
DRAWN BY: BRENT PERSCHON
MOUNTING LEGEND
S-CURVE TILE
-ROCK-IT SLIDE
EPUM BONDED WASHER
FORMS WATERTIGHT SEAL
TILE BASE
2' EMBEDMENT RAIN BUSTER IS APPLIED TO THE
UP -SLOPE EDGE OF THE TILE BASE AS
WELL AS TO THE LOCATIONS
OF THE LAG SCREW.
(2) MIN J" DIAM SS LAG SCREW
TORQUE=13t2 FT-LBS.
PILOT HOLE BACKFILLED WITH
SEALANT PRIOR TO LAG INSTALLATION
1 ROCK -IT MOUNT DETAIL
ry 1.i1 NOT TO SCALE
ROCK -IT COUPLING
MID CLAMP
ROCK-IT--�
COUPLING SHELF
ISOMETRIC VIEW
U L LISTING FOR ECOFASTEN: 2703
WEIGHT: 2.3 lb
.ANDSCAPE=MAX 48" (4'-0")
PORTRAIT=MAX 48" (4'-0")
COUPLING—, CLAMP
MODULE
3"
RAFTER
3 ILSCO SGB-4 GROUNDING LUGS 1772F
NOT TO SCALE TRUSS
2"x4" AT 24" O.C.
e1.04PV SYSTEM MOUNTING DETAIL
NOT TO SCALE
3" MIN AND 6" MAX BETWEEN TOP OF ROOF AND BOTTOM OF MODULE
PV MODULE, TYP. MOUNT
TO FRAMING OF EXISTING
ROOF TYPE, PARALLEL S 1.0
WITH PLANE OF ROOF
6'- MAXIMUMS
6 PV ARRAY TYP, ELEVATION
S 1.0 NOT TO SCALE
FLASHING/TILE STRAP
11*1WIilI.
�QCK-IT COUPLING ASSEMBLY
NOT TO SCALE
• CLAMP + ATTACHMENT
COUPLINGn Fes`
ROCK -IT 3.0 COUPLING
MID CLAMP
COUPLING SHELF
� 5/16"x1 1 /2"
HEX FLANGE BOLT
SIDE VIEW 300 SERIES SS
PERMITTED
CLAMP SPACING
RAFTER MODULE
MODULE
s MODULES IN PORTRAIT/LANDSCAPE
NOT TO SCALE
ONE HOLE STEEL STRAP CONDUIT
CONDUIT MOUNT BRACKET
CONDUIT MOUNTING DETAIL
S 1.0 NOT TO SCALE
CLAMP + ATTACHMENT
r COUPLING
1 1 2- r-TILE ROOF TOP
RAFTER
18s r:4101.111
`tt`�� CI�Callfo ,,,
� '° � X
�0.973r.+�,-
�� MrrMN e� t►
"'*Nd cap'
MOUNT DETAILS
SCALE: NOT TO SCALE
1.877.404.4129
L CA LICENSE: B/C46/C10/C39-973756 J
JACOBS RESIDENCE
50485 VERANO DR
LA QUINTA, CA, 92253-9011
UTILITY ACCOUNT #: 50688654
SERVICE #: S-6279294
REGl01 k r
OPERATING CENTER: CA 2S. O1
DATE: 2.3.2020
DRAWN BY: BRENT PERSCHON
SolarEdge
SE760OH-US
STRING 2: 12 PV
MODULES
W/OPTIMIZERS
STRING 1: 13 PV
MODULES
W/OPTIMIZERS
25 PV M
Photovoltaic System
Conduit Conductor Schedule (Unless Otherwise Specified Conductors Shall be Copper)
DC System Size (Watts)
8000
Tag
Description
Wire Gauge
# of Conductors/Color
Conduit Type
Conduit Size
AC System Size (Watts)
7351
1
DC -to -DC Converter Output (PV Wire)
12 AWG
2(V+, V-) B/R
Free Air
N/A
Total Module Count
25
1
EGC (Bare)
6 AWG
1 BARE
Free Air
N/A
2
DC -to -DC Converter Output (THWN-2)
12 AWG
4(2V+, 2V-) B/R
EMT
1/2"
2
1 EGC (THWN-2)
12 AWG
I 1(GRN)
EMT
11121,
3
Inverter Output (THWN-2)
8 AWG
3(1-1, L2, N) B/R/W
EMT
3/4"
3
1 EGC(THWN-2)
10AWG
1(GRN)
EMT
3/4"
Rapid Shutdown
nl�— —'t n
Disconnect
�tt,�•� Ct ca/it" 1
2"0"
975
ed C00010�*11ti
4,041181111111010
It
m 'n
of V) W
U 0 N 00
W
y O o
v Z Q Ln
Ln < U c
w Q :3
> H o
^ Z U
0 u1
Q
u o
,n Q
-J
0)
N
ai
It
�
O
O
�
U
U
W
r;
r`
Cq
ci!
ko
J
A
u
v7
z
w
Point of Interconnection, Load
Z
>
c0
n
rn
Side 705.12(B)(2)(3)(b)
>
Z
W
w
w
J
w
J
W
Ln
Z
N
Z
Q
N
U
�D
Existing Cutler Hammer
SHEET
240V/200AService Panel,
Single Phase, with 200A
NAME:
Main Disconnect- NOT
CENTER FED -
tw
C
c
3
J
M
M
C
SHEET
NUMBER:
rq
IW
Optimizer
SolarEdge P340
DC Input Power
340
Watts
DC Max. Input Voltage
48
Volts
DC Max. Input Current
13.75
Amps
DC Max. Output Current
15
Amps
Max. string rating inverter dependent. See SE documents.
Inverter Make/Model
SolarEdge SE760OH-US
CEC Efficiency
99
AC Operating Voltage
240
Volts
Cont. Max Output Current
32
Amps
DC Max Input Current
20
Amps
Input Short Circuit Current
45
Amps
Max Output Fault Current
40 A/20 ms
Other Notes
PV Module Rating @ STC
Module Make/Model
Hanwha Q.PEAK DUO BLK-G5 320
Max. Power -Point Current (Imp)
9.47
Amps
Max. Power -Point Voltage (Vmp)
33.8
Volts
Open -Circuit Voltage (Voc)
40.56
Volts
Short -Circuit Current (Isc)
9.94
Amps
Max. Series Fuse (OCPD)
20
Amps
Nom. Max. Power at STC (Pmax)
320
Watts
Max. System Voltage
1000 V (IEC) (UL)
Voc Temperature Coefficient
-0.28
%/C
AC Output Current According to art. 690.8(B)(1)
32 Amps
Nominal AC Voltage
240 Volts
THIS PANEL IS FED BY MULTIPLE SOURCES (UTILITY AND SOLAR)
Rooftop conductor ampacities designed in compliance with art.
690.8, Tables 310.15(B)(2)(a), 310.15(B)(3)(a), 310.15(B)(3)(c),
310.15(B)(16), Chapter 9 Table 4, 5, & 9. Location specific
temperature obtained from ASHRAE 2017 data tables.
AHJ Provided Data -
Max Temp: 47 °C
Min Temp: -7.4 °C
Power Production Calculation
Main Bus Rating: 200 Amps
Main Service Breaker Rating: 200 Amps
PV Breaker Rating: 40 Amps
200A + 40A <= 200 x 1.2; 240 <= 240A, OK
• Designed according to and all code citations are relevant to the 2019 California Electrical Code.
• Inverter(s) used in this design is/are compliant with 690.12 (Rapid Shutdown). See manufacturer data sheet.
• All inverters installed in California are Rule 21 Utility interactive compliant.
• Array grounding and bonding designed in compliance with 690.47(A).
• All terminations and conductors listed for use at 75°C
Conductor Calculations
Wire gauge calculated from 310.15(B)(16) & (17) with ambient temperature calculations from wrn
u
310.15(B)(2)(a) & 310.15(B)(3)(c) and raceway fill adjustments from 310.15(B)(3)(a). Conduit on o Cn
the roof shall be installed no less than 1" above the roof deck, -0 z <
"Under Array" conductors use the 90°C ampacity in 310.15(B)(17) with relevant ambient a, W
p[ W <
temperature adjustments. 0 >Ln
z
PV Circuit conductors use the larger ampacity in 310.15(B)(16) or (17) using the 75°C column with o 0
the continuous duty uprating or the 90°C column with the relevant ambient temperature and 0
raceway fill adjustments and without the continuous duty uprating per 690.8(B).
Non-PV Circuit conductors use the ampacity in 310.15(B)(16) in the 75°C column or the 90'C
column with the relevant ambient temperature and raceway fill adjustments, whichever is less
(110.14(C) & 310.15(A)(2)). The rating of the conductor after adjustments shall be greater than,
or equal to, the continuous duty uprated current.
More information about conductor calculations can be provided upon request.
Calc. Ex: Wire Ampacity x Ambient Temp. Corr. Factor x Conduit Fill Adj. Factor >= Output Current
(Tag 1 Under Array):
DC -to -DC Converter Output: 12 AWG rated 40 A, 40 A x 0.82 x 1 = 32.8 A >= 15 A o
(Tag 2 On Roof): U)
DC -to -DC Converter output: 12 AWG rated 30 A, 30 A x 0.82 x 0.8 = 19.68 A 7= 15 A 0
(Tag 3 Exterior);
Inverter Output: 8 AWG rated 50 A, 50 A >= 40 A ■
■
OCPD Calculations
Breakers sized according to continuous duty output current. PV circuit nominal current based off
inverter continuous output current X (1.25[art. 690.8(A)]).
Inverter 1: SE760OH-US Max Output = 32 A x 1.25 [art. 690.8(A))
= 40 A <= 40 A (OCPD)
system output current w/ continuous duty = 40 <= 40A (System OCPD)
••,4Oct COO
rn
N
0
0
v
09
r-i
LU
w
m
z
w
J
J
H
ut
Z
SHEET
NAME:
66
Ln
to
00
00
LO
0
u,
C
7
0
u
v
U
Ln
rn
r`
m
r`
m
ui
V)
Z 0)
W 0)
U N
J �
r\
Uw
+a a°Jo
Z a
(SHEET
1 NUMBER:
N
W
Conduit, Raceways, and J-Boxes (Labeled Every 10') per
690.31(G)(3) & (4)
Interactive System Point of Interconnection per 690.54
Plaques and Directories at the Service Equipment (MSP) and the
Location of All System Disconnects per 690.56(B) & 705.10
SE760OH-US String 2 DC Disco
PV System Disconnects per 690.13(B)
PV SYSTEM DISCONNECT
• •^ •1 •I�
WARNING
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
Power Source Output Connection, Adjacent to Back -
fed Breaker per705.12
Mk . S1111411TWO. •�
RAPID SHUTDOWN SWITCH FOR
SOLAR PV SYSTEM
PV With Rapid Shutdown, Installed Within 3 ft of the Service
Disconnecting Means per 690.56(C)(1)(a)
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN 1
SWITCH TO THE SOLAR EIVTXX
"OFF" POSITION TO FAgELS
SHUTDOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN ARRAY
ALL STICKERS DESCRIBED HEREIN SHALL BE MADE OF WEATHERPROOF ADHESIVE, THEY SHALL BE REFLECTIVE, THEY SHALL CONTAIN NO
SMALLER THAN 3/8" WHITE ARIAL FONT TEXT, AND HAVE A RED BACKGROUND, UNLESS OTHERWISE DEPICTED OR DESCRIBED.
ALL PLACARDS SHALL BE WEATHER -RESISTANT, PERMANENTLY ETCHED PLACARDS. HANDWRITTEN SIGNS WILL. NOT BE ACCEPTABLE.
690.53
will
.�'`%0+ot'CalliS
. GjD
i iui�'■•-
v
m Ln
Ln l0
00
u N W
N O
z Q Ln
v <LU
U
GJ
> Q O
Ln z U
U
,J o Ef Y
Ln
J y�
I_
v
U
rn
N
-i
� o
o
lz� U
n o�
� n
DO
JO U
N f �O
w
z CO n
M
> rn
z
s W w
w w
J J W
J J U N
L.n N J
z z u "0
SHEET
NAME:
SHEET
NUMBER:
MAIN BREAKER DE -RATED TO*** DUE TO SOLAR PHOTOVOLTAIC AC POWER SOURCE PHOTOVOLTAIC DC POWER SOURCE DISCONNECT
1 CIRCUITS 4 RATED AC OUTPUT CURRENT: *** A MAXIMUM VOLTAGE: ***A value calculated for each m Ln
EVERY MAX OF ***AMPS PV SOURCE ALLOWED NOM. OPERATING AC VOLTAGE: *** V MAXIMUM CURRENT: ***V account, for specific value see the a( 0 N 00
DO NOT INCREASE MAIN BREAKER RATING Property of Vivint Solar DC -TO -DC CONVERTER MAXIMUM RATED OUTPUT CURRENT: ***A previous warning label page v 0 m 1Oo
Property of Vivint Solar Property of Vivint Solar a a u Y
5 WARNING: PHOTOVOLTAIC POWER SOURCE w Q �
2 WARNING Property of Vivint Solar SITE PLAN PLACARD SHOWING ADDITIONAL POWER SOURCE -0 L z o
ELECTRICAL SHOCK HAZARD o 0 Q
TERMINALS ON THE LINE AND LOAD SIDES MAY BE G AND DISCONNECT LOCATIONS. PLACARD SHALL BE O
ENERGIZED IN THE OPEN POSITION V POWER SOUR E OUT UT CONNECTION MOUNTED ON EXTERIOR OF ELECTRICAL PANEL `" g +,
Property of Vivint Solar Property of Vivint Solar
P Y DO NOT RELOCATE THIS OVERCURRENT DEVICE
PV SYSTEM DISCONNECT Property of Vivint Solar
3 Property of Vivint Solar 10 PV rapid shutdown label required by
7 RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM 690.56(C)(1) indicated on E.3
Property of Vivint Solar
L
rQ
�sµ1f111rrr��
Callf &*
N
m
r 0
_CU
fu
(10) U
N
�''�•ad Cfln�•`''•ru
IF APPLICABLE
ROOFTOP ARRAY 7 7 INSIDE PANEL 6 INSIDE PANEL 6 9
$ 2 3 2 3 4 4 1 IF APPLICABLE
5 � GsF���a
Q0 "t IF APPLICABLE
DC
M M
5 DISCONNECT
INSIDE
--- —7r--
JUNCTION
BOX
0
SOLAR INVERTERS COMBINER PANEL VISIBLE/LOCKABLE VIVINTSOLAR METER
(MAY BE ON ROOFTOP (WHEN USED) A/C DISCONNECT (WHERE REQUIRED)
INTEGRATED WITH (WHERE REQUIRED)
ARRAY) TYPICAL SOLAR GENERATION INSTALLATION
(NOT ALL DEVICES ARE REQUIRED IN EVERY JURISDICTION)
VISIBLE/LOCKABLE
A/C DISCONNECT
SUB PANEL
(WHEN REQUIRED)
MAIN SERVICE
DISCONNECT PANEL
ALL STICKERS DESCRIBED HEREIN SHALL BE MADE OF WEATHERPROOF ADHESIVE, THEY SHALL THESE PLACARDS SHALL BE PLACED ON ALL INTERIOR AND EXTERIOR DIRECT -CURRENT (DC) CONDUIT, ENCLOSURES,
BE REFLECTIVE_, THEY SHALL. CONTAIN NO SMALLER THAN 3/8" WHITE ARIAL FONT TEXT, AND RACE -WAYS, CABLE ASSEMBLIES, JUNCTION BOXES COMBINER BOXES, AND DISCONNECTS TO ALERT THE FIRE
HAVE A RED BACKGROUND, UNLESS OTHERWISE DEPICTED OR DESCRIBED. ALL PLACARDS SERVICE TO AVOID CUTTING THEM. MARKINGS SHALL BE PLACED ON ALL DC CONDUIT EVERY 10 FT {3048 MM), ABOVE
SHALL BE WEATHER -RESISTANT, PERMANENTLY ETCHED PLACARDS. HANDWRITTEN SIGNS WILL AND BELOW PENETRATIONS OF ROOF/CEILING ASSEMBLIES, WALLS OR BARRIERS.
NOT BE ACCEPTABLE.
m
N
r1
�rI
U
n oZ
J=
JJ _ U
LA O 6� W
w Ln
Z m r,
rn
M
z w
�c N
LU Uj
J J LJJ
J J U
LA L J
Z Z U ko
SHEET
NAME:
SHEET
NUMBER:
R*
Ld
NOTES
v'lv'lnt.Sola-,-----'
1.877.404.4129
CA LICENSE: B/C46/C10/C39-973756
JACOBS RESIDENCE
50485 VERANO DR
LA QUINTA, CA, 92253-9011
UTILITY ACCOUNT #: 50688654
SERVICE #: S-6279294
REGNAL
OPERATING CENTER: CA•21 E 5.0
DATE: 2.3.2020
QRAWN BY: BRENT PERSCMON
NOTES
';►1►1i1iI111jjl
vt.cam'��..
g�� a & C &
Nfivin#.Solar
1.877.404.4129
CA LICENSE: B/C46/C10/C39-973756
L
BS RESIDENCE
485 VERANO DR
INTA, CA, 92253-9011
ACCOUNT M 50688654
SERVICE M S-6279294
REGIONAL
OPERATING CENTER: CA-21 5.1
I
DATE: 2.3.2020
DRAWN BY: BRENT PERSCHON